Toshiba Air Conditioner HFC R 410A User Manual



4-way ceiling cassette  
MMU-AP0091H, AP0121H, AP0151H,  
MMU-AP0181H, AP0241H, AP0271H,  
MMU-AP0301H, AP0361H, AP0481H  
MMU-AP0561H  
Ref.-No. SMMS01-AE-01-05  
2-way ceiling cassette  
MMU-AP0071WH, AP0091WH, AP0121WH,  
MMU-AP0151WH, AP0181WH, AP0241WH,  
MMU-AP0271WH, AP0301WH  


1-way ceiling cassette  
MMU-AP0071YH, AP0091YH, AP0121YH,  
MMU-AP0151SH, AP0181SH, AP0241SH  
Standard ducted unit  
MMD-AP0071BH, AP0091BH, AP0121BH,  
MMD-AP0151BH, AP0181BH, AP0241BH,  
MMD-AP0271BH, AP0301BH, AP0361BH,  
MMD-AP0481BH, AP0561BH  


High-pressure ducted unit  
MMD-AP0181H, AP0241H, AP0271H,  
MMD-AP0361H, AP0481H, AP0721H,  
MMD-AP0961H  
Slim duct unit  
MMD-AP0071SPH, AP0091SPH,  
MMD-AP0121SPH, AP0151SPH,  
MMD-AP0181SPH  


Ceiling-suspended unit  
MMC-AP0151H, AP0181H, AP0241H,  
MMC-AP0271H, AP0361H, AP0481H  
High-wall unit  
MMK-AP0071H, AP0091H, AP0121H,  
MMK-AP0151H, AP0181H, AP0241H  
MMK-AP0072H, AP0092H, AP0122H  



Floor-mounted console unit  
MML-AP0071H, AP0091H, AP0121H,  
MML-AP0151H, AP0181H, AP0241H  
Super Modular Multi  
Design Manual  
Concealed chassis unit  
MML-AP0071BH, AP0091BH, AP0121BH,  
MML-AP0151BH, AP0181BH, AP0241BH  
Floor-mounted cabinet unit  
MMF-AP0151H, AP0181H, AP0241H  
MMF-AP0271H, AP0361H, AP0481H  
MMF-AP0561H  
HFC R-410A  
COOLING ONLY MODEL  


Inverter unit  
MMY-MAP0501T8, MAP0601T8  
MMY-MAP0801T8, MAP1001T8  
MMY-MAP1201T8  
HEAT PUMP MODEL  
Inverter unit  
MMY-MAP0501HT8, MAP0601HT8  
MMY-MAP0801HT8, MAP1001HT8  
MMY-MAP1201HT8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Super Modular Multi System  
Contents  
1. Outline of Toshiba Super Modular Multi System (S-MMS) ..................................................................................  
2. Summary of system equipment ...........................................................................................................................  
4
7
3. Basic system configuration.................................................................................................................................. 13  
4. Equipment selection procedure ........................................................................................................................... 19  
5. Refrigerant piping design..................................................................................................................................... 29  
6. Wiring design ....................................................................................................................................................... 34  
7. Controls................................................................................................................................................................ 39  
8. Accessories.......................................................................................................................................................... 45  
9. Technical specifications ....................................................................................................................................... 46  
10. Fan characteristics............................................................................................................................................... 69  
11. Dimensional drawings.......................................................................................................................................... 75  
This manual is used for both cooling only and heat pump models.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Outline of Toshiba Super Modular Multi System (S-MMS)  
Branching  
Combination of line and header branching is highly flexible. This  
allows for the shortest design route possible, thereby saving on  
installation time and cost. Line/header branching after header  
branching is only available with Toshiba Super MMS.  
Line branching  
Outdoor unit  
Branching joint  
8F  
Indoor unit  
Header branching  
Outdoor unit  
Branching  
header  
7F  
2F  
Indoor unit  
Line and header branching  
Header  
Outdoor unit  
Indoor  
unit  
Branching joint  
Line branching after header branching  
1F  
Outdoor unit  
Branching joint  
Header  
Super MMS  
only  
Indoor unit  
Header branching after header branching  
Outdoor unit  
Header  
Super MMS  
only  
Header  
Indoor unit  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
•
Non-polarized control wiring between  
outdoor and indoor units  
Outdoor unit  
Indoor unit  
•
Wiring diagnosis system  
Use the switches on the micro  
processor PCB of the outdoor unit.  
•
Detects wiring to the indoor unit a4  
which should not be in system A.  
b4 is missing in system B.  
8F  
7F  
2F  
•
Piping  
Outdoor unit  
A
system  
Wiring  
Indoor unit  
B
system  
Outdoor unit  
Allowable pipe length:  
175 m equivalent length  
Outdoor unit  
1st branching  
section  
From 1st branching to the  
farthest indoor unit: 65 m  
1F  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compact  
The design of the modular Toshiba Super MMS outdoor unit allows for easy unit manoeuvring into  
any standard lift. Its compactness also allows it to be easily installed in limited spaces.  
Largest system capacity  
Toshiba Super MMS can be combined up to 48 hp (135 kW) as one refrigerant system.  
Energy saving design  
The units have the best energy efficiency ratio of any VRF unit. Compared with a conventional chiller  
fan coil system, a large energy saving can be realized.  
Advanced bus communication system  
Wiring between indoor and outdoor units is a simple 2-wire system.  
The communication address is also automatically configured.  
A default test mode operation is available.  
Self-diagnostic system  
Comprehensive troubleshooting code enables quick identification of problems arising.  
High lift design  
An equivalent pipe length of 175 m and vertical lift of 50 m are possible with the Toshiba Super  
MMS.  
The vertical lift between indoor units of 30 m is the highest in the industry.  
This allows for greater flexibility in the location of the system.  
Multiple indoor units  
Indoor units with different capacities and configurations can be combined up to 135% of the  
outdoor unit capacity.  
A maximum of 48 indoor units can be combined with the 30-48 hp outdoor units.  
Intelligent control  
Toshiba Super MMS intelligent controls and modulating valves deliver the required capacity, in  
accordance with the load variation from 50% to 100%.  
The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so  
humidity and temperature are kept in the comfort zone.  
Wide control applications  
Artificial Intelligence Network system  
•
•
Central control and monitoring system available  
Weekly schedule operation through weekly timer  
Integration with a Building Management System (BMS) is available.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Summary of system equipment  
Technical specifications - outdoor units  
Rating  
hp  
5
6
8
10  
12  
Cooling only model MMY-MAP  
Heat pump model MMY-MAP  
Cooling capacity  
0501T8  
0501HT8  
14.0  
0601T8  
0601HT8  
16.0  
0801T8  
0801HT8  
22.4  
1001T8  
1001HT8  
28.0  
1201T8  
1201HT8  
33.5  
kW  
kW  
Heating capacity  
16.0  
18.0  
25.0  
31.5  
37.5  
Technical specifications - combination of outdoor units  
Rating  
hp  
5
6
8
10  
12  
14  
16  
Cooling only model MMY-MAP  
Heat pump model MMY-MAP  
Cooling capacity  
Heating capacity  
Combined outdoor units  
0501T8  
0501HT8  
14.0  
16.0  
5
-
0601T8  
0601HT8  
16.0  
18.0  
6
0801T8  
0801HT8  
22.4  
25.0  
8
1001T8  
1001HT8  
28.0  
31.5  
10  
1201T8  
1201HT8  
33.5  
37.5  
12  
1401T8  
1401HT8  
38.4  
43.0  
8
1601T8  
1601HT8  
45.0  
50.0  
8
kW  
kW  
hp  
-
-
-
-
6
8
No. of connectable indoor units  
8
10  
13  
16  
20  
23  
27  
Rating  
hp  
18  
20  
22  
22  
24  
24  
26  
Cooling only model MMY-MAP  
Heat pump model MMY-MAP  
Cooling capacity  
Heating capacity  
Combined outdoor units  
1801T8  
1801HT8  
50.4  
56.5  
10  
8
2001T8  
2001HT8  
56.0  
63.0  
10  
2201T8  
2201HT8  
61.5  
69.0  
8
2211T8  
2211HT8  
61.5  
69.0  
12  
2401T8  
2401HT8  
68.0  
76.5  
8
2411T8  
2411HT8  
68.0  
76.5  
12  
2601T8  
2601HT8  
73.0  
81.5  
10  
8
kW  
kW  
hp  
10  
8
10  
8
12  
-
-
6
-
8
-
8
No. of connectable indoor units  
30  
33  
37  
37  
40  
40  
43  
Rating  
hp  
28  
30  
32  
32  
34  
34  
36  
Cooling only model MMY-MAP  
Heat pump model MMY-MAP  
Cooling capacity  
Heating capacity  
Combined outdoor units  
2801T8  
2801HT8  
78.5  
88.0  
10  
10  
8
3001T8  
3001HT8  
84.0  
95.0  
10  
3201T8  
3201HT8  
90.0  
100.0  
8
8
8
3211T8  
3211HT8  
90.0  
100.0  
12  
3401T8  
3401HT8  
96.0  
108.0  
10  
8
3411T8  
3411HT8  
96.0  
108.0  
12  
3601T8  
3601HT8  
101.0  
113.0  
10  
kW  
kW  
hp  
10  
10  
10  
10  
12  
10  
10  
8
8
-
-
8
-
8
-
8
No. of connectable indoor units  
47  
48  
48  
48  
48  
48  
48  
Rating  
hp  
36  
38  
40  
42  
44  
46  
48  
Cooling only model MMY-MAP  
Heat pump model MMY-MAP  
Cooling capacity  
Heating capacity  
Combined outdoor units  
3611T8  
3611HT8  
101.0  
113.0  
12  
3801T8  
3801HT8  
106.5  
119.5  
10  
4001T8  
4001HT8  
112.0  
126.5  
10  
4201T8  
4201HT8  
118.0  
132.0  
12  
4401T8  
4401HT8  
123.5  
138.0  
12  
4601T8  
4601HT8  
130.0  
145.0  
12  
4801T8  
4801HT8  
135.0  
150.0  
12  
kW  
kW  
hp  
12  
10  
10  
10  
12  
12  
12  
12  
10  
10  
10  
10  
12  
12  
-
8
10  
10  
10  
10  
12  
No. of connectable indoor units  
48  
48  
48  
48  
48  
48  
48  
Branching joints and headers  
Model  
Usage  
Indoor unit capacity code (*1) : Total below 6.4  
Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2  
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2  
Indoor unit capacity code (*1) : Total 25.2 or more  
Appearance  
Y-shape branching joint (*3)  
RBM-BY53E  
RBM-BY103E  
RBM-BY203E  
RBM-BY303E  
(*2)  
(*2)  
(*2)  
4-branching header (*4)  
RBM-HY1043E Indoor unit capacity code (*1) : Total below 14.2  
Max.4  
RBM-HY2043E Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2  
RBM-HY1083E Indoor unit capacity code (*1) : Total below 14.2  
branches  
Max.8  
8-branching header (*4) (*5)  
RBM-HY2083E Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2  
branches  
T-shape branching joint  
(For connection of  
outdoor units)  
RBM-BT13E  
1 set of 3 types of T-shape joint pipes as described below:  
The required quantity is arranged and they are combined at the site.  
Connection piping  
Balance pipe  
Liquid side piping  
Gas side piping  
Corresponding dia. (mm)  
Ƙ3/8ā€  
Ƙ3/8ā€ to Ƙ7/8ā€  
Ƙ5/8ā€ to Ƙ1-5/8ā€  
Q’ty  
1
1
1
*1  
*2  
*3  
*4  
*5  
*6  
The capacity code can be obtained from page 10 (capacity code is not actual capacity).  
If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.  
When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.  
Max. 6.0 capacity code in total can be connected.  
If capacity code of outdoor unit is 26 and more, it is not used for 1st branching.  
Model names for outdoor and indoor units described in this guide are shortened because of the space constraints.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor unit model line-up - cooling only units  
hp  
(capacity  
code)  
Model  
MMY-  
No. of  
combined  
units  
1
Inverter  
5 hp  
MMY-  
Q’ty  
used  
Inverter  
6 hp  
MMY-  
Q’ty  
used  
Inverter  
8 hp  
MMY-  
Qty  
used 10 hp  
MMY-  
Inverter  
Q’ty  
used  
Inverter  
12 hp  
MMY-  
Q’ty  
used  
5 hp (5)  
MAP0501T8  
MAP0601T8  
MAP0801T8  
MAP1001T8  
MAP1201T8  
AP1401T8  
AP1601T8  
AP1801T8  
AP2001T8  
AP2201T8  
AP2211T8  
AP2401T8  
AP2411T8  
AP2601T8  
AP2801T8  
AP3001T8  
AP3201T8  
AP3211T8  
AP3401T8  
AP3411T8  
AP3601T8  
AP3611T8  
AP3801T8  
AP4001T8  
AP4201T8  
AP4401T8  
AP4601T8  
AP4801T8  
MAP0501T8  
1
6 hp (6)  
8 hp (8)  
1
1
1
1
2
2
2
2
3
2
3
2
3
3
3
4
3
4
3
4
3
4
4
4
MAP0601T8  
MAP0601T8  
MAP0601T8  
1
1
1
MAP0801T8  
10 hp (10)  
12 hp (12)  
14 hp (14)  
16 hp (16)  
18 hp (18)  
20 hp (20)  
22 hp (22)  
22 hp (22)  
24 hp (24)  
24 hp (24)  
26 hp (26)  
28 hp (28)  
30 hp (30)  
32 hp (32)  
32 hp (32)  
34 hp (34)  
34 hp (34)  
36 hp (36)  
36 hp (36)  
38 hp (38)  
40 hp (40)  
42 hp (42)  
44 hp (44)  
46 hp (46)  
48 hp (48)  
MAP1001T8  
1
MAP1201T8  
1
MAP0801T8  
MAP0801T8  
MAP0801T8  
2
1
MAP1001T8  
MAP1001T8  
1
2
MAP0801T8  
MAP0801T8  
2
3
MAP1001T8  
1
MAP1201T8  
MAP1201T8  
1
2
MAP0801T8  
MAP0801T8  
2
1
MAP1001T8  
MAP1001T8  
MAP1001T8  
1
2
3
MAP0801T8  
MAP0801T8  
MAP0801T8  
MAP0801T8  
4
3
2
1
MAP1001T8  
MAP1001T8  
MAP1001T8  
MAP1001T8  
2
1
1
2
MAP1201T8  
MAP1201T8  
MAP1201T8  
1
2
3
MAP1001T8  
MAP1001T8  
MAP1001T8  
MAP1001T8  
MAP1001T8  
3
4
3
2
1
MAP1201T8  
MAP1201T8  
MAP1201T8  
MAP1201T8  
1
2
3
4
4
4
4
1. Product designation  
MMY-  
M
AP  
000  
0
T
8
8: Power supply, 3 ph, 380-415 V, 50 Hz  
T: Inverter unit  
Development series number  
Model size hp x 10  
New refrigerant R-410A  
M: Single module unit. No mark: Combined model name  
Super Modular Multi  
2. Combined capacity range  
No. of combined units:  
Capacity of combined units:  
1 to 4 units  
14 hp (140 type) to 48 hp (480 type)  
3. Rated conditions  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor unit model line-up - heat pump units  
hp  
(capacity  
code)  
Model  
MMY-  
No. of  
combined  
units  
1
Inverter  
5 hp  
MMY-  
Q’ty  
used  
Inverter  
6 hp  
MMY-  
Q’ty  
used  
Inverter  
8 hp  
MMY-  
Qty  
used 10 hp  
MMY-  
Inverter  
Q’ty  
used  
Inverter  
12 hp  
MMY-  
Q’ty  
used  
5 hp ( 5)  
MAP0501HT8  
MAP0601HT8  
MAP0801HT8  
MAP1001HT8  
MAP1201HT8  
AP1401HT8  
AP1601HT8  
AP1801HT8  
AP2001HT8  
AP2201HT8  
AP2211HT8  
AP2401HT8  
AP2411HT8  
AP2601HT8  
AP2801HT8  
AP3001HT8  
AP3201HT8  
AP3211HT8  
AP3401HT8  
AP3411HT8  
AP3601HT8  
AP3611HT8  
AP3801HT8  
AP4001HT8  
AP4201HT8  
AP4401HT8  
AP4601HT8  
AP4801HT8  
MAP0501HT8  
1
6 hp ( 6)  
8 hp ( 8)  
1
1
1
1
2
2
2
2
3
2
3
2
3
3
3
4
3
4
3
4
3
4
4
4
MAP0601HT8 1  
MAP0601HT8 1  
MAP0601HT8 1  
MAP0801HT8 1  
10 hp (10)  
12 hp (12)  
14 hp (14)  
16 hp (16)  
18 hp (18)  
20 hp (20)  
22 hp (22)  
22 hp (22)  
24 hp (24)  
24 hp (24)  
26 hp (26)  
28 hp (28)  
30 hp (30)  
32 hp (32)  
32 hp (32)  
34 hp (34)  
34 hp (34)  
36 hp (36)  
36 hp (36)  
38 hp (38)  
40 hp (40)  
42 hp (42)  
44 hp (44)  
46 hp (46)  
48 hp (48)  
MAP1001HT8 1  
MAP1201HT8 1  
MAP0801HT8 1  
MAP0801HT8 2  
MAP0801HT8 1  
MAP1001HT8 1  
MAP1001HT8 2  
MAP0801HT8 2  
MAP0801HT8 3  
MAP1001HT8 1  
MAP1201HT8 1  
MAP1201HT8 2  
MAP0801HT8 2  
MAP0801HT8 1  
MAP1001HT8 1  
MAP1001HT8 2  
MAP1001HT8 3  
MAP0801HT8 4  
MAP0801HT8 3  
MAP0801HT8 2  
MAP0801HT8 1  
MAP1001HT8 2  
MAP1001HT8 1  
MAP1001HT8 1  
MAP1001HT8 2  
MAP1201HT8 1  
MAP1201HT8 2  
MAP1201HT8 3  
MAP1001HT8 3  
MAP1001HT8 4  
MAP1001HT8 3  
MAP1001HT8 2  
MAP1001HT8 1  
MAP1201HT8 1  
MAP1201HT8 2  
MAP1201HT8 3  
MAP1201HT8 4  
4
4
4
1. Product designation  
MMY-  
M
AP  
000  
0
H
T
8
8: Power supply, 3 ph, 380-415 V, 50 Hz  
T: Inverter unit  
H: Heat pump  
Development series number  
Model size hp x 10  
New refrigerant R-410A  
M: Single module unit. No mark: Combined model name  
Super Modular Multi  
2. Combined capacity range  
No. of combined units:  
Capacity of combined units:  
1 to 4 units  
14 hp (140 type) to 48 hp (480 type)  
3. Rated conditions  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db.  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Technical specifications - indoor units  
Model type  
Model  
name  
Capacity  
code  
Cooling  
capacity  
kW  
2.8  
3.6  
4.5  
5.6  
7.1  
8.0  
9.0  
11.2  
14.0  
16.0  
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
8.0  
9.0  
14.0  
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
8.0  
9.0  
11.2  
14.0  
16.0  
5.6  
7.1  
8.0  
11.2  
14.0  
22.4  
28.0  
2.2  
2.8  
3.6  
4.5  
5.6  
4.5  
5.6  
7.1  
8.0  
11.2  
14.0  
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
2.2  
Heating  
capacity  
kW  
3.2  
4.0  
5.0  
6.3  
8.0  
9.0  
10.0  
12.5  
16.0  
18.0  
2.5  
3.2  
4.0  
5.0  
6.3  
8.0  
9.0  
10.0  
16.0  
2.5  
3.2  
4.0  
5.0  
6.3  
8.0  
2.5  
3.2  
4.0  
5.0  
6.3  
8.0  
9.0  
Height  
mm  
Width  
mm  
Depth  
mm  
Weight  
kg  
4-way ceiling cassette  
MMU-AP0091H  
MMU-AP0121H  
MMU-AP0151H  
MMU-AP0181H  
MMU-AP0241H  
MMU-AP0271H  
MMU-AP0301H  
MMU-AP0361H  
MMU-AP0481H  
MMU-AP0561H  
MMU-AP0071WH  
MMU-AP0091WH  
MMU-AP0121WH  
MMU-AP0151WH  
MMU-AP0181WH  
MMU-AP0241WH  
MMU-AP0271WH  
MMU-AP0301WH  
MMU-AP0481WH  
MMU-AP0071YH  
MMU-AP0091YH  
MMU-AP0121YH  
MMU-AP0151SH  
MMU-AP0181SH  
MMU-AP0241SH  
MMD-AP0071BH  
MMD-AP0091BH  
MMD-AP0121BH  
MMD-AP0151BH  
MMD-AP0181BH  
MMD-AP0241BH  
MMD-AP0271BH  
MMD-AP0301BH  
MMD-AP0361BH  
MMD-AP0481BH  
MMD-AP0561BH  
MMD-AP0181H  
MMD-AP0241H  
MMD-AP0271H  
MMD-AP0361H  
MMD-AP0481H  
MMD-AP0721H  
MMD-AP0961H  
MMD-AP0071SPH  
MMD-AP0091SPH  
MMD-AP0121SPH  
MMD-AP0151SPH  
MMD-AP0181SPH  
MMC-AP0151H  
MMC-AP0181H  
MMC-AP0241H  
MMC-AP0271H  
MMC-AP0361H  
MMC-AP0481H  
MMK-AP0071H  
MMK-AP0091H  
MMK-AP0121H  
MMK-AP0151H  
MMK-AP0181H  
MMK-AP0241H  
MMK-AP0072H  
MMK-AP0092H  
MMK-AP0122H  
1
256  
256  
256  
840  
840  
840  
840  
840  
840  
20  
22  
23  
1.25  
1.7  
2
2.5  
3
3.2  
4
5
6
0.8  
1
1.25  
1.7  
2
2.5  
3
3.2  
5
0.8  
1
1.25  
1.7  
2
2.5  
0.8  
1
1.25  
1.7  
2
2.5  
3
3.2  
4
5
319  
398  
840  
830  
840  
550  
28  
33  
2-way ceiling cassette  
398  
398  
1350  
1350  
550  
550  
44  
48  
406  
235  
1650  
850  
620  
400  
52  
22  
1-way ceiling cassette  
Standard ducted unit  
198  
1100  
655  
27  
198  
320  
1200  
550  
655  
800  
31  
27  
320  
320  
700  
800  
800  
30  
39  
1000  
10.0  
12.5  
16.0  
18.0  
6.3  
320  
1350  
800  
51  
6
2
2.5  
3
4
High-pressure ducted unit  
380  
380  
850  
850  
660  
660  
50  
52  
8.0  
9.0  
12.5  
16.0  
25.0  
31.5  
2.5  
3.2  
4.0  
5.0  
6.3  
5.0  
6.3  
8.0  
9.0  
12.5  
16.0  
2.5  
3.2  
4.0  
380  
380  
470  
850  
1200  
1380  
660  
660  
1250  
56  
67  
155  
5
8
10  
0.8  
1
1.25  
1.7  
2
1.7  
2
2.5  
3
Slim duct unit  
210  
845  
645  
22  
22  
22  
23  
23  
21  
Ceiling-suspended unit  
210  
210  
210  
368  
910  
680  
680  
680  
210  
1180  
1595  
895  
25  
33  
18  
4
5
High-wall unit  
0.8  
1
1.25  
1.7  
2
2.5  
0.8  
1.0  
1.25  
5.0  
6.3  
8.0  
2.5  
3.2  
4.0  
368  
1055  
210  
19  
368  
275  
1430  
790  
210  
208  
25  
11  
2.8  
3.6  
Floor-mounted console unit  
Concealed chassis unit  
MML-AP0071H  
MML-AP0091H  
MML-AP0121H  
MML-AP0151H  
MML-AP0181H  
MML-AP0241H  
MML-AP0071BH  
MML-AP0091BH  
MML-AP0121BH  
MML-AP0151BH  
MML-AP0181BH  
MML-AP0241BH  
MMF-AP0151H  
MMF-AP0181H  
MMF-AP0241H  
MMF-AP0271H  
MMF-AP0361H  
MMF-AP0481H  
MMF-AP0561H  
0.8  
1
1.25  
1.7  
2
2.5  
0.8  
1
1.25  
1.7  
2
2.5  
1.7  
2
2.5  
3
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
2.2  
2.8  
3.6  
4.5  
5.6  
7.1  
4.5  
5.6  
7.1  
8.0  
11.2  
14.0  
16.0  
2.5  
3.2  
4.0  
5.0  
6.3  
8.0  
2.5  
3.2  
4.0  
5.0  
6.3  
8.0  
5.0  
6.3  
8.0  
9.0  
12.5  
16.0  
18.0  
630  
950  
230  
37  
630  
600  
950  
745  
230  
220  
40  
21  
600  
1045  
220  
29  
Floor-mounted cabinet unit  
1750  
1750  
1750  
600  
600  
600  
210  
210  
390  
48  
49  
65  
4
5
6
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Remote controller  
Appearance  
Wired remote controller  
RBC-AMT31E  
Application  
Function  
Connected to indoor unit  
•
•
•
•
•
Start/stop  
Mode change  
Temperature adjustment  
Air flow adjustment  
Timer function  
Three options are available:  
 On after selected time (one cycle)  
 Off after selected time (one cycle)  
 Off after selected time (re-occurring)  
To use, choose one of these options and  
the time delay before it occurs (minimum  
period is 0.5 hours).  
ļ‚‚Combined with the weekly timer a  
weekly operating schedule can be set.  
Filter maintenance time  
•
Wired remote  
controller  
Wired remote controller  
(for control with two  
controlling positions)  
Automatically displays the maintenance  
time of the indoor filter.  
Filter LED flashes.  
•
•
Self-diagnosis function  
Pressing the ā€˜CHECK’ button displays the  
problem cause using a check code.  
Two controlling positions are available.  
Two remote controllers can be connected  
to one indoor unit. The indoor unit can then  
be operated from two separate locations.  
Simplified remote controller  
RBC-AS21E  
Connected to indoor unit  
•
•
•
•
Start/stop  
Temperature adjustment  
Air flow adjustment  
Check code display  
Simplified remote controller  
Wireless remote controller kit  
Connected to indoor unit  
•
•
•
•
•
Start/stop  
Mode change  
Temperature adjustment  
Air flow adjustment  
TCB-AX21U (W)-E  
RCB-AX22CE  
TCB-AX21E  
Timer function  
Three options are available:  
On after selected time (one cycle)  
Off after selected time (one cycle)  
Off after selected time (re-occurring)  
To use, choose one of these options and  
the time delay before it occurs (minimum  
period is 0.5 hours).  
•
•
Two controlling positions are available.  
Two wireless remote controllers can be  
connected to one indoor unit. The indoor  
unit can then be operated from two  
separate locations.  
Check code display.  
TCB-AX21U (W)-E  
(For 4-way ceiling cassette)  
RBC-AX22CE  
(For ceiling-suspended unit)  
TCB-AX21E  
(For all units except high-pressure ducted units)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appearance  
Infrared remote controller  
Application  
Function  
Connected to indoor unit  
•
•
•
•
•
•
Start/stop  
Mode change  
Temperature adjustment  
Air flow adjustment (5 steps)  
Clock  
WH-H2UE  
Timer function  
- ON/OFF timer (10 min. steps)  
- Daily timer  
•
•
•
High power mode  
ECO mode (sleep timer with ECO-logic)  
One-touch pre-set memory  
Weekly timer  
RBC-EXW21E  
Connected to central remote  
controller, wired remote controller  
•
Weekly schedule operation  

Setting start/stop times for each day  
of the week  
ļ‚‚
ON/OFF can be set 3 times a day.  
ļ‚ƒ
ļ‚„
ļ‚…

Press ā€˜CHECK’ ā€˜PROGRAM’ ā€˜DAY’  
button for easy program copying.  
Two schedules a week can be  
specified (summer/winter schedule).  
Press ā€˜CANCEL’ ā€˜DAY’ button for easy  
holiday override setting.  
Weekly  
timer  
Wired remote  
controller  
If power supply fails, the settings are  
stored in the memory for 100 hours.  
Outdoor unit  
Weekly  
timer  
Central remote  
controller  
Central remote controller  
TCB-SC642TLE  
Connected to outdoor unit,  
indoor unit  
•
•
Individual control of up to 64 indoor units  
Individual control of max. 64 indoor units  
divided into 1 to 4 zones.  
Slave  
Master  
Up to 16 indoor units for each  
zone.  
)
(
•
•
Up to 16 outdoor master units are  
connectable.  
4 central control setting types to inhibit  
individual operation by remote controller  
can be selected.  
•
•
Setting for one of 1 to 4 zones is available.  
Usable with other central control devices  
(up to 10 central control devices in one  
control circuit).  
Outdoor unit  
•
•
Two control mode choices  
Centrol controller mode  
Central remote  
controller  
(
)
Remote controller mode  
Settings of simultaneous ON/OFF 3 times  
for each day of the week combined with  
weekly timer.  
Central  
remote  
controller  
Indoor remote controller  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Basic system configuration  
System legend (example)  
8 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
13 units  
Min. 4  
Max. 10.8  
Capacity code - total 10.4  
Total number of units - 13  
Outdoor unit  
8HP  
Capacity code  
over the branch  
(0.8 + 0.8 = 1.6)  
Indoor unit  
designation  
Capacity  
code  
Indoor unit  
Remote  
controller  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
16 units  
Min. 5  
Max. 13.5  
Capacity code - total 12.8  
Total number of units - 16  
Outdoor unit  
10HP  
Indoor unit  
Remote  
controller  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
33 units  
Min. 10  
Max. 27  
Capacity code - total 26.75  
Total number of units - 19  
Outdoor unit  
10HP 10HP  
Indoor unit  
Remote  
controller  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
48 units  
Min. 15  
Max. 40.5  
Capacity code - total 40  
Total number of units - 28  
Outdoor unit  
10HP  
10HP 10HP  
Indoor unit  
Remote  
controller  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
48 units  
Min. 20  
Max. 54  
Capacity code - total 53.75  
Total number of units - 32  
Outdoor unit  
10HP  
10HP  
10HP 10HP  
Indoor unit  
Remote  
controller  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48 hp system  
•
•
Max. number of indoor units:  
Indoor unit capacity code:  
48 units  
Min. 24  
Max. 64.8  
Capacity code - total 61.9  
Total number of units - 40  
Outdoor unit  
Indoor unit  
Remote  
controller  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Equipment selection procedure  
1. Selection ļ¬‚ow chart  
1. Determination of indoor air conditioning load  

2. Preliminary selection of indoor units  


3. Preliminary selection of outdoor unit with indoor units  

4. Capacity correction for piping length/height between indoor and outdoor units  

5. Capacity correction based on indoor and outdoor temperature  

No  
6. Validate preliminary selection of indoor units  

7. Confirmation of selection for indoor unit and outdoor units  

End  
2. Indoor unit and outdoor unit combination  
For indoor unit, the capacity code is decided for each model size.  
Model size  
Cooling capacity, kW  
Capacity code  
007  
2.2  
0.8  
009  
2.8  
1
012  
3.6  
1.25  
015  
4.5  
1.7  
018  
5.6  
2
024  
7.1  
2.5  
027  
8.0  
3
030  
9.0  
3.2  
036  
11.2  
4
048  
14.0  
5
056  
16.0  
6
072  
22.4  
8
096  
28.0  
10  
Note: Model size: corresponding to Btu/h. Capacity code: corresponding to horsepower.  
For outdoor unit, maximum number of connectable indoor units and total capacity code of indoor units are decided.  
Outdoor unit  
(cooling only)  
Outdoor unit  
(heat pump)  
Capacity code  
of outdoor unit  
5
6
Max. No. of  
indoor units  
8
Total indoor unit  
capacity code  
2.5 to 6.75  
3 to 8.1  
4 to 10.8  
5 to 13.5  
6 to 16.2  
7 to 18.9  
8 to 21.6  
9 to 24.3  
10 to 27.0  
11 to 29.7  
11 to 29.7  
12 to 32.4  
12 to 32.4  
13 to 35.1  
14 to 37.8  
15 to 40.5  
16 to 43.2  
16 to 43.2  
17 to 45.9  
17 to 45.9  
18 to 48.6  
18 to 48.6  
19 to 51.3  
20 to 54.0  
21 to 56.7  
22 to 59.4  
23 to 62.1  
24 to 64.8  
MMY-MAP0501T8  
MMY-MAP0601T8  
MMY-MAP0801T8  
MMY-MAP1001T8  
MMY-MAP1201T8  
MMY-AP1401T8  
MMY-AP1601T8  
MMY-AP1801T8  
MMY-AP2001T8  
MMY-AP2201T8  
MMY-AP2211T8  
MMY-AP2401T8  
MMY-AP2411T8  
MMY-AP2601T8  
MMY-AP2801T8  
MMY-AP3001T8  
MMY-AP3201T8  
MMY-AP3211T8  
MMY-AP3401T8  
MMY-AP3411T8  
MMY-AP3601T8  
MMY-AP3611T8  
MMY-AP3801T8  
MMY-AP4001T8  
MMY-AP4201T8  
MMY-AP4401T8  
MMY-AP4601T8  
MMY-AP4801T8  
MMY-MAP0501HT8  
MMY-MAP0601HT8  
MMY-MAP0801HT8  
MMY-MAP1001HT8  
MMY-MAP1201HT8  
MMY-AP1401HT8  
MMY-AP1601HT8  
MMY-AP1801HT8  
MMY-AP2001HT8  
MMY-AP2201HT8  
MMY-AP2211HT8  
MMY-AP2401HT8  
MMY-AP2411HT8  
MMY-AP2601HT8  
MMY-AP2801HT8  
MMY-AP3001HT8  
MMY-AP3201HT8  
MMY-AP3211HT8  
MMY-AP3401HT8  
MMY-AP3411HT8  
MMY-AP3601HT8  
MMY-AP3611HT8  
MMY-AP3801HT8  
MMY-AP4001HT8  
MMY-AP4201HT8  
MMY-AP4401HT8  
MMY-AP4601HT8  
MMY-AP4801HT8  
10  
13  
16  
20  
23  
27  
30  
33  
37  
37  
40  
40  
43  
47  
48  
48  
48  
48  
48  
48  
48  
48  
48  
48  
48  
48  
48  
8
10  
12  
14  
16  
18  
20  
22  
22  
24  
24  
26  
28  
30  
32  
32  
34  
34  
36  
36  
38  
40  
42  
44  
46  
48  
50 to 135% of outdoor unit capacity  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Cooling/heating capacity characteristics  
Cooling capacity calculation method:  
Required cooling capacity = cooling capacity x factor (, ļ‚‚, ļ‚ƒ, ļ‚„, ļ‚…*1) kW  

Indoor air wet bulb temperature vs. capacity correction value  
Indoor air wet bulb temperature (°C)  
ļ‚‚
Outdoor air dry bulb temperature vs. capacity correction value  
Outdoor air dry bulb temperature (°C)  
ļ‚ƒ
Air flow variation ratio of indoor unit vs. capacity correction (for ducted units only)  
Air flow variation ratio (%)  
*1  
Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ļ‚„
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value  
Outdoor unit (5 to 44 hp)  
Pipe length (equivalent length) L (m)  
Outdoor unit  
Outdoor unit (46 to 48 hp)  
L’ is the longest dimension of  
(l’o + l’a, l’o + l’b, l’o + l’c)  
ho  
hc  
l’o  
ha  
H = ho + (longest dimension of  
ha, hb and hc)  
l’a  
hb  
l’b  
Indoor unit  
l’c  
Pipe length (equivalent length) L (m)  
ļ‚…
Correction of outdoor unit diversity  
Standard capacity ratio  
Indoor unit total capacity ratio (%)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Heating capacity calculation method:  
Required heating capacity = heating capacity x factor (, ļ‚‚, ļ‚ƒ, ļ‚„, ļ‚…*1, *2) kW  

Indoor air dry bulb temperature vs. capacity correction value  
Indoor air dry bulb temperature (°C)  
ļ‚‚
Outdoor air wet bulb temperature vs. capacity correction value  
Outdoor air wet bulb temperature (°C)  
ļ‚ƒ
Air flow variation ratio of indoor unit vs. capacity correction (for ducted units only)  
Air flow variation ratio (%)  
*1  
*2  
Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.  
Refer to the capacity correction for frosting on the outdoor heat exchanger section on page 24.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ļ‚„
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value  
Outdoor unit (5 to 48 hp)  
Pipe length (equivalent length) L (m)  
Outdoor unit  
L’ is the longest dimension of  
(l’o + l’a, l’o + l’b, l’o + l’c)  
ho  
l’o  
ha  
H = ho + (longest dimension of  
ha, hb and hc)  
hb  
l’a  
l’b  
hc  
Indoor unit  
l’c  
ļ‚…
Correction of outdoor unit diversity  
Standard capacity ratio  
Indoor unit total capacity ratio (%)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Capacity correction for frosting on the outdoor heat exchanger (heating mode)  
Correct the heating capacity when frost was found on the outdoor heat exchanger.  
Heating capacity =  
Capacity after correction of outdoor unit Ɨ correction value of capacity resulting from frost  
(Capacity after correction of outdoor unit: Heating capacity calculated in the previous  
section.)  

Capacity correction for frosting on the outdoor heat exchanger  
Outdoor air wet bulb temperature (°C)  
Capacity calculation for each indoor unit  
Capacity for each indoor unit =  
Required standard capacity of indoor unit  
Total value of standard indoor unit capacity  
Capacity after correction of outdoor unit Ɨ  
Operating temperature range  
In cooling mode  
In heating mode  
Continuous  
operating  
range  
Continuous  
operating  
range  
Indoor air wet bulb temperature (°C)  
Indoor air dry bulb temperature (°C)  
The unit can be operated even if outdoor  
Rated conditions  
temperature falls to -20°C. However, the warranty  
only covers operation down to -15°C, as lower  
temperatures are outside the operating range.  
Cooling: Indoor air temperature 27°C db/19°C wb.  
Outdoor air temperature 35°C db.  
Heating: Indoor air temperature 20°C db.  
Outdoor air temperature 7°C db/6°C wb.  
When the outdoor air temperature falls to below  
-15°C, unit operation may reduce the product life.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example of equipment selection  
The following shows an example of equipment selection based upon a building model.  
Fig. 1 - Overview of building model  
Outside view  
Floor configuration  
Small meeting room  
Executive rooms  
Office rooms  
(Entire floor)  
Office rooms  
Stores  
Non-air conditioning zone  
•
Steel frame, reinforced concrete building, four floors  
above ground. Total floor area : 415 m²  
Outdoor unit is installed on the roof.  
Indoor design conditions:  
Cooling: 27.0/19.0°C db/wb. Heating: 20°C db  
Outdoor design conditions:  
•
•
Cooling: 35°C db (standard condition). Heating: 3°C wb (standard condition: 6°C wb)  
Selection criteria for each floor  
1F: Outdoor unit capacity exactly matches the total indoor unit capacity.  
Total indoor unit hp = Outdoor unit hp  
Indoor: 2.5 hp x 2 units + 3.2 hp + 2 hp = 10.2 hp  
Outdoor: 10 hp Same capacity  
2F: Outdoor unit capacity matches the potential total indoor unit capacity with the possibility of future  
extension.  
Office rooms 2 and 3 are to be used as warehouses at first, so air conditioning is not necessary at present.  
However, there is a plan to convert them into offices, so an outdoor module with extra capacity is required.  
Piping/wiring are carried out. Indoor unit is not yet installed.  
When the rooms are used as an office later, the indoor unit is installed.  
3F: One indoor unit is connected to one outdoor unit.  
The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit connected.  
4F: Consider the diversity factor and have the outdoor module match 135% of indoor unit capacity.  
This is a typical matching of indoor/outdoor units for a Super MMS system.  
•
•
Total indoor unit hp > Outdoor unit hp  
Select each indoor unit based on individual peak room load.  
Indoor: 2.5 hp + 2.5 hp + 2 hp + 2 hp (capacity difference in each room) + 1.3 hp =  
10.3 hp (different capacity)  
Outdoor: 8 hp (different capacity)  
•
The cooling load profile needs to be taken into consideration.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Procedure and result of equipment selection  
1. Procedure of equipment selection  
a. Calculate cooling for every room.  
b. Select an indoor unit to match the cooling load for every room from the table on page 10.  
c. Select the outdoor module to match the indoor units selected in point b. Select the outdoor modules  
based on the critical factors and the combination rule. Choose a tentative outdoor module that will match  
the indoor units, and check whether the selection agrees with the combination rule. Perform the capacity  
correction based on the pipe length, system lift, indoor set temperature, outdoor temperature.  
Then, make sure the corrected system cooling capacity satisfies the cooling load.  
2. Equipment selection and capacity check  
Air conditioning load  
Equipment selection  
Indoor unit  
Floor  
Room No.  
Indoor air conditioning load (kW)  
Outdoor unit  
Model  
Model  
Capacity (kW)  
Capacity (kW)  
Cooling  
6.0 (16 o’clock)  
5.2 (14 o’clock)  
5.0 (14 o’clock)  
3.2 (12 o’clock)  
6.4 (10 o’clock)  
12.7  
4.8  
4.6  
—
Heating  
5.4  
4.2  
4.2  
2.7  
5.4  
12.0  
4.5  
4.8  
—
MMU-  
Cooling  
7.1  
5.6  
5.6  
3.6  
7.1  
14.0  
5.6  
5.6  
—
Heating  
8.0  
6.3  
6.3  
4.0  
8.0  
16.0  
6.3  
6.3  
—
MMY  
AP2801HT8  
Cooling  
78.5  
Heating  
88.0  
4F  
4-1  
4-2  
4-3  
4-4  
4-5  
3-1  
2-1  
2-2  
2-3  
1-1  
1-2  
1-3  
1-4  
AP0241H  
AP0181H  
AP0181H  
AP0121H  
AP0241H  
AP0481H  
AP0181H  
AP0181H  
—
3F  
2F  
1F  
6.5  
6.5  
7.2  
5.1  
6.0  
6.3  
7.0  
4.5  
AP0241H  
AP0241H  
AP0301H  
AP0181H  
7.1  
7.1  
9.0  
5.6  
8.0  
8.0  
10.0  
6.3  
Note: ( ): Peak occurrence time  
Piping distance  
Capacity correction  
Pipe correction x  
temp. correction  
Capacity check after correction  
Capacity (kW)  
Floor  
Room No.  
Equivalent  
length (m)  
Height  
difference (m)  
Result  
Cooling  
0.920  
Heating  
0.957  
Cooling  
6.5  
Heating  
6.9  
4F  
4-1  
4-2  
4-3  
4-4  
4-5  
3-1  
2-1  
2-2  
2-3  
1-1  
1-2  
1-3  
1-4  
43  
12  
Good  
x
1.0  
x
1.0  
=
0.920  
x
1.0  
x
0.95  
x
0.95  
=
5.2  
5.2  
3.3  
6.5  
12.9  
5.2  
5.2  
—
6.5  
5.4  
5.4  
3.5  
6.9  
13.8  
5.4  
5.4  
—
6.9  
3F  
2F  
0.864  
1F  
6.5  
8.3  
5.2  
6.9  
8.6  
5.4  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example: Equipment selection based on system load profile  
Since the five rooms on the 4th floor face different directions, their hourly cooling load profile will also be different.  
We select each indoor unit based on the individual room peak load. However, we need to use the total load profile  
on the 4th floor as a base to choose the outdoor module.  
Load in each room  
Total load in all rooms of 4th floor  
4-1  
Time  
4-2  
Time  
4-3  
4-4  
Time  
1. The total load on the 4th floor is calculated by  
adding up the hourly cooling loads of the five  
rooms.  
2. The maximum value of the total load is used to  
select the outdoor module.  
Time  
Time  
Time  
4-5  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Schematic diagram  
MMY-AP2801T8  
MMY-AP2801HT8  
Outdoor unit  
3rd branching  
joint  
4th branching  
joint  
5th branching  
joint  
1st branching  
joint  
2nd branching  
joint  
Indoor unit  
MMU-AP0121H  
Indoor unit  
MMU-AP0241H  
Indoor unit  
MMU-AP0181H  
Indoor unit  
MMU-AP0181H  
Indoor unit  
MMU-AP0241H  
2nd branching  
joint  
4-1  
4-2  
4-5  
4-3  
4-4  
3-5  
Indoor unit  
MMD-AP0481H  
3rd branching  
joint  
4th branching  
joint  
Indoor unit  
MMU-AP0181H  
Indoor unit  
MMU-AP0181H  
No air conditioner  
2-1  
2-2  
2-3  
Branching header  
Indoor unit  
MMU-AP0181H  
Indoor unit  
MMU-AP0301H  
Indoor unit  
MMU-AP0241H  
Indoor unit  
MMU-AP0241H  
1-1  
1-2  
1-3  
1-4  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Refrigerant piping design  
1. Warnings on refrigerant leakage  
Check of concentration limit  
The room in which the air conditioner is to be installed requires a design that ensures that the concentration of  
refrigerant gas will not exceed a set limit if there is a leak.  
Refrigerant R-410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia,  
and is not restricted by laws that protect the ozone layer. However, since it contains more than air, it poses the  
risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R-410A is almost non-  
existent. With the recent increase in the number of high concentration buildings, however, the installation of multi  
air conditioner systems is on the increase because of the need for effective use of floor space, individual control,  
energy conservation by curtailing heat and carrying power, etc.  
Most importantly, the multi air conditioner system is able to contain a large amount of refrigerant compared with  
conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room,  
select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration  
does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).  
In a room where the concentration may exceed the limit, create an opening to adjacent rooms, or install mechanical  
ventilation combined with a gas leak detection device. The concentration is as given below.  
Total amount of refrigerant (kg)  
Min. volume of the indoor unit installed room (m³)  
≤ Concentration limit (kg/m³)  
The concentration limit of R-410A which is used in multi air conditioners is 0.3 kg/m³.  
Note 1: If there are 2 or more refrigeration systems in  
a single refrigeration device, the amounts of refrigerant  
should be as charged in each independent device.  
Outdoor unit  
e.g. charged  
amount (10 kg)  
e.g. charged amount (15 kg)  
For the amount of charge in this example:  
•
•
The possible amount of leaked refrigerant gas in  
rooms A, B and C is 10 kg.  
The possible amount of leaked refrigerant gas in  
rooms D, E and F is 15 kg.  
Room A  
Room C Room D  
Room E  
Room F  
Room B  
Indoor unit  
Note 2: The standards for minimum room volume are as  
follows:  
(1) No partition (shaded portion)  
Outdoor unit  
(2) When there is an effective opening with the adjacent  
room for ventilation of leaking refrigerant gas (opening  
without a door, or an opening 0.15% or larger than the  
respective floor spaces at the top or bottom of the door).  
Refrigerant piping  
Indoor unit  
Refrigerant piping  
(3) If an indoor unit is installed in each partitioned room and  
the refrigerant piping is interconnected, the smallest  
room is the critical room. But when a mechanical  
ventilation device is installed in combination with a gas  
leak detector in the smallest room where the density  
limit is exceeded, the volume of the next smallest  
room is used.  
Outdoor unit  
Very  
small  
room  
Indoor unit  
Small  
room  
Large room  
Medium room  
Mechanical ventilation device - gas leak detector  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note 3: The minimum indoor floor area compared with  
the amount of refrigerant is roughly as follows (when the  
ceiling is 2.7 m high):  
Range below the  
density limit of  
0.3 kg/m3  
m2  
(countermeasures  
not needed)  
Range above the  
density limit of  
0.3 kg/m3  
(countermeasures  
needed  
kg  
Total refrigerant amount  
2. Free branching system  

ļ‚‚
ļ‚ƒ
ļ‚„
ļ‚…
Line branching system  
Header branching system  
Header branching after line branching  
Line branching after header branching  
Header branching after header branching  
The above five branching systems are available to increase significantly the flexibility of refrigerant piping design.  
Outdoor unit  
Branching joint  
Line  
branching  
system  
Indoor unit  
Remote  
controller  
Outdoor unit  
Branching header  
Header  
branching  
system  
Indoor unit  
Remote controller  
Outdoor unit  
Branching joint  
Branching header  
Header  
branching  
after line  
branching  
Indoor unit  
Remote  
controller  
Outdoor unit  
Line  
branching  
after header  
branching  
Branching header  
Branching  
joint  
Header  
branching  
after header  
Indoor unit  
Remote  
controller  
branching  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Allowable length/height difference of refrigerant piping  
D slave  
Example 1  
unit 3  
Example 2  
Slave  
unit 2  
Slave  
unit 1  
Slave  
unit 2  
Master  
unit  
Slave  
unit 1  
Master  
unit  
C slave  
unit 2  
A master B slave  
unit unit 1  
Height difference  
between outdoor  
units H3 ≤ 5 m  
Connecting  
piping of  
outdoor unit  
Outdoor unit  
Lb  
Lc  
La  
T-shape branching  
joint  
Ld  
LA  
LB  
Main connecting piping between outdoor units  
Length corresponding to farthest piping  
between outdoor units LO ≤ 25 m  
Note: In case of connecting method in Example 2, a large amount of  
refrigerant and refrigerant oil may return to the master unit. Therefore,  
set the T-shape joint so that oil does not enter directly.  
Main  
piping  
Branching  
header  
L1  
Branching piping L2  
Connecting piping of indoor unit  
1st branching  
section  
Height difference  
betweeen outdoor  
units H1 ≤ 50 m  
L3  
Indoor unit  
Equivalent length corresponding to farthest piping L ≤ 175 m  
Equivalent length corresponding to farthest piping after 1st branching Li ≤ 65 m  
Height difference  
between indoor  
units H2 ≤ 30 m  
L6  
L5  
L4  
Y-joint  
Indoor unit  
Note 1:  
Note 2:  
Combination of outdoor units: Master unit (1 unit) + slave units (0 to 3 units).  
Master unit is the outdoor unit nearest to the connected indoor units.  
Install the outdoor units in order of capacity.  
System restrictions  
(Master unit ≄ slave unit 1 ≄ slave unit 2 ≄ slave unit 3)  
Refer to outdoor unit combination table on page 7.  
Piping to indoor units shall be perpendicular to piping to the master outdoor unit as in  
Example 1. Do not connect piping to indoor uints in the same direction as the master  
outdoor unit in Example 2.  
Max. No. of combined outdoor units  
Max. capacity of combined outdoor units  
Max. No. of connected indoor units  
4 units  
48 hp  
48 units  
135%  
105%  
Note 3:  
Note 4:  
Max. capacity of combined  
indoor units  
H2 ≤ 15  
H2 > 15  
Allowable length and height difference of refrigerant piping  
Allowable value Piping section  
Piping length  
Total extension of pipe (liquid pipe, actual length)  
300 m  
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+  
L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j  
LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j  
Farthest piping length L (*)  
Actual length  
Equivalent length  
150 m  
175 m  
65 m  
25 m  
85 m  
10 m  
30 m  
50 m  
40 m (**)  
30 m  
5 m  
Equivalent length of farthest piping from 1st branching Li (*)  
Equivalent length of farthest piping between outdoor units LO (*)  
Max. equivalent length of main piping (***)  
Max. equivalent length of outdoor unit connection piping  
Max. actual length of indoor unit connection piping  
L3 + L4 + L5 + L6 + j  
LA + LB + Ld, (LA + Lb, LA + LB + Lc)  
L1  
Ld, (La, Lb, Lc)  
a, b, c, d, e, f, g, h, i, j  
——  
——  
——  
——  
Height difference Height between indoor  
and outdoor units H1  
Upper outdoor unit  
Lower outdoor unit  
Height between indoor units H2  
Height between outdoor units H3  
*
**  
***  
(D) is outdoor unit farthest from 1st branching, and ( j ) is indoor unit farthest from 1st branching.  
If the height difference (H2) between indoor units exceeds 3 m, set below 30 m.  
If the maximum combination capacity of the outdoor units is 46 hp or more, the maximum equivalent length is restricted up to 70 m.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Selection of refrigerant piping  
Header branching pipe  
Branching pipe  
Slave  
unit 2  
Slave  
unit 1  
Master  
unit  
Slave  
unit 3  
Indoor unit connection piping  
Outdoor unit  
Balance pipe  
T-shape  
branching joint  
Indoor unit  
Y-shape  
branching  
joint  
Outdoor unit  
connection  
piping  
Main piping  
Main connection  
piping between  
outdoor units  
Indoor unit  
connection piping  
1st branching  
section  
Indoor unit  

Pipe size of outdoor unit (Table 1)  
ļ‚…
Piping of indoor unit (Table 5)  
Model name  
MAP0501T8  
MAP0601T8  
MAP0801T8  
MAP1001T8  
MAP1201T8  
MMY-  
Gas side  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
Ƙ7/8ā€  
Liquid side  
Ƙ3/8ā€  
Ƙ3/8ā€  
Ƙ1/2ā€  
Ƙ1/2ā€  
Indoor unit size  
Gas side  
Liquid side  
Ƙ1/4ā€  
Ƙ1/4ā€  
Ƙ1/4ā€  
Ƙ3/8ā€  
MAP0501HT8  
MAP0601HT8  
MAP0801HT8  
MAP1001HT8  
MAP1201HT8  
007 to 012  
Actual length 15 m or less Ć˜3/8ā€  
Actual length exceeds 15 m Ć˜1/2ā€  
015 to 018  
024 to 056  
072 to 096  
Ƙ1/2ā€  
Ƙ5/8ā€  
Ƙ7/8ā€  
Ƙ1-1/8ā€  
Ƙ1/2ā€  
Ƙ1/2ā€  
ļ‚‚
Connecting pipe size between outdoor units (Table 2)  

Selection of branching section (Table 6)  
Total capacity code of indoor unit (*1)  
Total capacity code of  
outdoor units downstream  
14 to below 22  
22 to below 26  
26 to below 36  
Gas side  
Liquid side  
Balance pipe  
Model  
Y-shape  
branching joint  
(*2)  
Below 6.4  
RBM-BY53E  
RBM-BY103E  
RBM-BY203E  
RBM-BY303E  
RBM-HY1043E  
RBM-HY2043E  
RBM-HY1083E  
RBM-HY2083E  
RBM-BT13E  
Ƙ1-1/8ā€  
Ƙ1-3/8ā€  
Ƙ1-3/8ā€  
Ƙ1-5/8ā€  
Ƙ5/8ā€  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
Ƙ3/8ā€  
Ƙ3/8ā€  
Ƙ3/8ā€  
Ƙ3/8ā€  
6.4 to below 14.2  
14.2 to below 25.2  
25.2 or more  
Below 14.2  
36 or more  
Branching  
header  
(*3)  
For 4  
branching 14.2 to below 25.2  
For 8 Below 14.2  
ļ‚ƒ
Size of main pipe (Table 3)  
branching 14.2 to below 25.2  
1 set of 3 types of T-shape joint pipes as  
branching joint described below:  
(For connecting The required quantity is arranged and  
Total capacity code of  
all outdoor units (*1)  
Below 6  
Gas side  
Liquid side  
T-shape  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
Ƙ1-1/8ā€  
Ƙ1-1/8ā€  
Ƙ1-3/8ā€  
Ƙ1-3/8ā€  
Ƙ1-5/8ā€  
Ƙ3/8ā€  
Ƙ3/8ā€  
Ƙ1/2ā€  
Ƙ1/2ā€  
Ƙ5/8ā€  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
Ƙ7/8ā€  
6 to below 8  
outdoor unit)  
combined at the site.  
8 to below 12  
12 to below 14  
14 to below 22  
22 to below 26  
26 to below 36  
36 to below 46  
46 or more  
•
•
•
Balance pipe (Corresponding difference  
Ƙ3/8ā€) Ɨ 1  
Piping at liquid side (Corresponding  
difference Ƙ3/8ā€ to Ƙ7/8ā€) Ɨ 1  
Piping at gas side (Corresponding  
difference Ƙ5/8ā€ to Ƙ1-5/8ā€) Ɨ 1  
Ƙ1-5/8ā€ (*5)  
Determine thickness of the main pipe according to capacity of the outdoor units. ļ‚‡  
Minimum wall thickness for R-410A application (Table 7)  
ļ‚„
Pipe size between branching sections (Table 4)  
Soft  
OK  
OK  
OK  
OK  
NG  
NG  
NG  
NG  
NG  
Half hard or hard  
OK  
OK  
OK  
OK  
OK (*4)  
OK (*4)  
OK (*4)  
OK (*4)  
OK (*4)  
OD (Inch)  
1/4ā€  
3/8ā€  
1/2ā€  
5/8ā€  
3/4ā€  
7/8ā€  
1-1/8ā€  
1-3/8ā€  
1-5/8ā€  
Minimum wall thickness (mm)  
0.80  
0.80  
0.80  
1.00  
1.00  
1.00  
1.00  
1.10  
1.25  
Total capacity code of  
indoor units downstream (*1)  
2.8 or less  
Gas side  
Liquid side  
Ƙ1/2ā€  
Ƙ5/8ā€  
Ƙ7/8ā€  
Ƙ1-1/8ā€  
Ƙ1-3/8ā€  
Ƙ1-3/8ā€  
Ƙ1-5/8ā€  
Ƙ3/8ā€  
Ƙ3/8ā€  
Ƙ1/2ā€  
Ƙ5/8ā€  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
2.8 to below 6.4  
6.4 to below 12.2  
12.2 to below 20.2  
20.2 to below 25.2  
25.2 to below 35.2  
35.2 or more  
If the total capacity code value of indoor units exceeds that of the outdoor units,  
apply the capacity code of the outdoor units.  
*1  
*2  
*3  
*4  
*5  
Code is determined according to the unit size. For details, refer to pages 7-9.  
When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.  
For one line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected.  
If the pipe size is Ƙ3/4ā€ or more, use a hard type or half hard type for material of the pipe.  
The maximum equivalent length of the main pipe should be 70 m or shorter.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Charging requirement with additional refrigerant  
After the system has been evacuated, replace the vacuum pump with a refrigerant cylinder and charge the system  
with additional refrigerant.  
Calculating the amount of additional refrigerant required  
Refrigerant in the system when shipped from the factory  
5 hp  
6 hp  
8 hp  
10 hp  
12 hp  
Factory refrigerant  
charge  
Heat pump  
Cooling only  
8.5 kg  
8.0 kg  
8.5 kg  
8.0 kg  
12.5 kg  
11.0 kg  
12.5 kg  
11.0 kg  
12.5 kg  
11.0 kg  
When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the site  
is not included. Calculate the additional amount needed, and add that amount to the system.  
Calculation  
Additional refrigerant charge amount is calculated from the size of the liquid pipe at the site and its actual length.  
Additional refrigerant charge amount at the site =  
Actual length of liquid pipe Ɨ  
Additional refrigerant charge amount + Compensation by system hp (Table 2)  
per 1 m liquid pipe (Table 1)  
Example: Additional charge amount R (kg) =  
(L1 x 0.025 kg/m) + (L2 x 0.055 kg/m) + (L3 x 0.105 kg/m) + (3.0 kg)  
L1: Actual total length of liquid pipe Ƙ1/4ā€ (m)  
L2: Actual total length of liquid pipe Ƙ3/8ā€ (m)  
L3: Actual total length of liquid pipe Ƙ1/2ā€ (m)  
Table 7-1  
Liquid side pipe diameter  
Ƙ1/4ā€  
Ƙ3/8ā€  
Ƙ1/2ā€  
Ƙ5/8ā€  
Ƙ3/4ā€  
Ƙ7/8ā€  
Additional refrigerant amount/1 m  
0.025 kg  
0.055 kg  
0.105 kg  
0.160 kg  
0.250 kg  
0.350 kg  
Table 7-2  
Combined  
horse power  
(hp)  
5
6
Outdoor unit combination  
(hp)  
Compensation  
by system hp  
Combined  
horse power  
(hp)  
28  
30  
Outdoor unit combination  
(hp)  
Compensation  
by system hp  
(kg)  
-2.0  
0.0  
1.0  
-6.0  
3.0  
(kg)  
0.0  
0.0  
1.5  
2.5  
3.5  
0.0  
0.0  
0.0  
3.0  
5.0  
0.0  
7.0  
-4.0  
-4.0  
5
6
8
10  
10  
12  
8
10  
10  
10  
8
12  
8
8
10  
10  
8
10  
8
8
32  
10  
12  
14  
16  
18  
20  
22  
10  
12  
8
8
8
34  
36  
12  
10  
12  
10  
10  
10  
12  
12  
12  
12  
6
-6.0  
4.0  
8
8
12  
10  
10  
10  
10  
12  
12  
12  
12  
8
10  
10  
12  
8
8
8
8
-6.0  
-6.0  
-5.0  
-4.0  
-2.0  
0.0  
10  
10  
8
38  
40  
42  
44  
46  
48  
10  
10  
10  
10  
12  
12  
10  
10  
10  
10  
12  
6
24  
26  
12  
8
10  
12  
8
8
8
8
2.0  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Wiring design  
1. General  
(1) Perform wiring of the power supply in conformance with the regulations of the local electric company.  
(2) For the control wires connecting indoor units, outdoor units, and between indoor and outdoor units, use of  
double-core shielded wires is recommended to prevent noise disturbance.  
(3) Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit.  
(4) Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit.  
(5) Never connect the 220–240 V power to the terminal block (U1, U2, U3, U4, U5, U6) for control cables, as this  
will cause problems.  
(6) The control wiring system and refrigerant piping system should be in the same line.  
(7) Arrange the cables so that the power cables do not come into contact with the high-temperature part of the  
pipe; otherwise the coating may melt and cause an accident.  
(8) Do not turn on the power to the indoor unit until the refrigerant pipes have been completely evacuated.  
2. Outdoor unit power supply  
•
Select the power supply cabling and fuse of each outdoor unit from the following specifications:  
5-core cable, in accordance with 60245 IEC 66.  
•
Connect the outdoor units via the incorporated terminal block (L1, L2, L3, N).  
Outdoor unit power supply  
3-phase, 380-415 V, 50 Hz  
3. Electrical wiring design  
3-phase  
Earth  
50 Hz, 380-415 V  
Earth leakage breaker  
manual switch  
Outdoor unit  
power source  
Junction box  
Indoor unit  
power source  
Single-phase  
50 Hz, 220-240 V  
Earth leakage breaker  
power switch  
Model  
Outdoor unit power supply  
MMY-AP***T8, HT8  
3-phase, 380-415 V, 50 Hz  
Unit capacities and power supply wire sizes (reference)  
Model  
MMY-  
Power supply wiring  
Wire size  
Field-supplied fuse  
MAP0501T8  
MAP0601T8  
MAP0801T8  
MAP1001T8  
MAP1201T8  
MAP0501HT8  
MAP0601HT8  
MAP0801HT8  
MAP1001HT8  
MAP1201HT8  
3.5 mm² (AWG #12) Max. 26 m  
3.5 mm² (AWG #12) Max. 26 m  
3.5 mm² (AWG #10) Max. 20 m  
5.5 mm² (AWG #10) Max. 28 m  
5.5 mm² (AWG #10) Max. 27 m  
20 A  
20 A  
30 A  
30 A  
30 A  
•
•
Determine the wire size for the indoor unit according to the number of connected indoor units downstream.  
Observe local regulations regarding wire size selection and installation.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Indoor unit power supply (must be independent from outdoor unit power)  
Model  
Power supply wiring  
Wire size  
Field-supplied fuse  
All models of indoor units  
2.0 mm² (AWG #14) Max. 20 m  
3.5 mm² (AWG #12) Max. 50 m  
15 A  
Note: The connecting length indicated in the table represents the length from the junction box to the outdoor unit when the indoor units are connected in parallel for  
power, as shown in the illustration on the previous page. A voltage drop of no more than 2% is assumed. If the connecting length exceeds the length indicated  
in the table, select the wire thickness in accordance with local wiring standards.  
CAUTIONS  
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems  
together.  
(2) When running power wires and control wires parallel to each other, either run them through separate  
conduits, or maintain a suitable distance between them.  
(Current capacity of power wires: 10 A or less for 300 m, 50 A or less for 500 m)  
5. Control wiring design  
Power supply  
Single-phase  
220-240 V, 50 Hz  
(Open)  
Earth  
[Central remote controller] (option)  
TCB-SC642TLE (for line 64)  
Interconnecting wire for control  
between outdoor units  
Shielded wire must be connected  
to each outdoor unit  
Interconnecting wire for control  
between outdoor unit and indoor  
unit  
Shielded wire must be connected  
to each indoor unit  
Standard  
remote controller  
Wire specification, quantity, size of interconnecting wiring and remote controller wiring  
Name  
Quantity  
Size  
Specification  
Up to 500 m  
1.25 mm²  
Up to 1000 m  
1000 to 2000 m  
2.0 mm²  
Interconnecting wiring  
2 cores  
Shielded wire  
(indoor-indoor/indoor-outdoor/outdoor-outdoor  
control wiring, central control wiring)  
Remote controller wiring  
2 cores  
0.5 to 2.0 mm²  
-
-
-
(1)  
The interconnecting wiring and central control wiring use 2-core non-polarity interconnecting wires. Use 2-core shielded wires to prevent noise disturbance. In  
this case, close (connect) the end of shielded wires, and perform the functional grounding for the end of the shielded wires which are connected to both indoor  
and outdoor units. For the shielded wires which are connected between the central remote controller and the outdoor unit, perform the functional grounding at  
only one end of the central control wiring.  
(2)  
Use 2-core non-polarity wire for remote controller (A, B terminals).  
Use 2-core non-polarity wire for wiring of group control (A, B terminals).  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Control wiring diagram  
1. All control wiring is 2-core non-polarity wire.  
2. Be sure to use shielded wire for the following wiring to prevent noise disturbance.  
•
Outdoor-outdoor/indoor-indoor/outdoor-indoor control wiring, central control wiring.  
Central control  
device  
Super Modular Multi System  
Table 1  
Master  
unit  
Slave  
unit  
Slave  
unit  
Slave  
unit  
Slave  
unit  
Master  
unit  
Master  
unit  
Outdoor unit  
Table 1  
Table 2  
Indoor unit  
Table 3  
Remote  
controller  
Remote controller  
Remote controller  
Table 1  
Control wiring between indoor and outdoor units (L1, L2, L3)  
Central control wiring (L4)  
Wiring  
Type  
2-core, non-polarity  
Shielded wire  
Size  
Length  
1.25 mm²: Up to 1000 m  
2.0 mm²: Up to 2000 m (*1)  
(*1): Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )  
Table 2  
Control wiring between outdoor units (L5)  
Wiring  
Type  
2-core, non-polarity  
Shielded wire  
Size  
Length  
1.25 mm² to 2.0 mm²  
Up to 100 m (L5)  
Table 3  
Remote controller wiring (L6, L7)  
Wire  
2-core  
Size  
0.5 mm² to 2.0 mm²  
Length  
•
•
•
Up to 500 m ( L6 + L7 ).  
Up 400 m in case of wireless remote controller in group control.  
Up to 200 m total length of control wiring between indoor units ( L6 ).  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Design  
Type  
Model  
Nominal voltage  
(V-ph-Hz)  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
230-1-50  
Voltage range  
Max.  
Fan motor  
kW  
Power supply  
MOCP  
Min.  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
198  
FLA  
0.20  
0.20  
0.22  
0.24  
0.28  
0.28  
0.40  
0.68  
0.93  
0.95  
0.36  
0.36  
0.36  
0.37  
0.37  
0.53  
0.53  
0.54  
1.33  
0.28  
0.28  
0.28  
0.55  
0.55  
0.63  
0.33  
0.33  
0.39  
0.39  
0.50  
0.60  
0.60  
0.70  
0.96  
1.13  
1.13  
0.93  
1.55  
1.55  
1.87  
2.12  
6.04  
6.35  
0.35  
0.35  
0.37  
0.38  
0.47  
0.33  
0.37  
0.48  
0.48  
0.90  
0.96  
0.35  
0.35  
0.35  
0.37  
0.37  
0.40  
0,20  
0,21  
0,22  
0.30  
0.30  
0.49  
0.49  
0.54  
0.54  
0.29  
0.29  
0.29  
0.52  
0.52  
0.53  
0.77  
0.77  
1.01  
1.01  
1.48  
1.84  
1.84  
MCA  
0.25  
0.25  
0.28  
0.30  
0.35  
0.35  
0.50  
0.85  
1.16  
1.19  
0.45  
0.45  
0.45  
0.46  
0.46  
0.66  
0.66  
0.68  
1.67  
0.35  
0.35  
0.35  
0.69  
0.69  
0.79  
0.41  
0.41  
0.49  
0.49  
0.62  
0.75  
0.75  
0.88  
1.20  
1.41  
1.41  
1.16  
1.94  
1.94  
2.34  
2.65  
7.55  
7.94  
0.44  
0.44  
0.47  
0.48  
0.59  
0.41  
0.46  
0.60  
0.60  
1.13  
1.20  
0.44  
0.44  
0.44  
0.46  
0.46  
0.50  
0,24  
0,26  
0,27  
0.37  
0.37  
0.62  
0.62  
0.68  
0.68  
0.36  
0.36  
0.36  
0.65  
0.65  
0.66  
0.96  
0.96  
1.27  
1.27  
1.85  
2.30  
2.30  
4-way ceiling cassette  
MMU-AP0091H  
MMU-AP0121H  
MMU-AP0151H  
MMU-AP0181H  
MMU-AP0241H  
MMU-AP0271H  
MMU-AP0301H  
MMU-AP0361H  
MMU-AP0481H  
MMU-AP0561H  
MMU-AP0071WH  
MMU-AP0091WH  
MMU-AP0121WH  
MMU-AP0151WH  
MMU-AP0181WH  
MMU-AP0241WH  
MMU-AP0271WH  
MMU-AP0301WH  
MMU-AP0481WH  
MMU-AP0071YH  
MMU-AP0091YH  
MMU-AP0121YH  
MMU-AP0151SH  
MMU-AP0181SH  
MMU-AP0241SH  
MMD-AP0071BH  
MMD-AP0091BH  
MMD-AP0121BH  
MMD-AP0151BH  
MMD-AP0181BH  
MMD-AP0241BH  
MMD-AP0271BH  
MMD-AP0301BH  
MMD-AP0361BH  
MMD-AP0481BH  
MMD-AP0561BH  
MMD-AP0181H  
MMD-AP0241H  
MMD-AP0271H  
MMD-AP0361H  
MMD-AP0481H  
MMD-AP0721H  
MMD-AP0961H  
MMD-AP0071SPH  
MMD-AP0091SPH  
MMD-AP0121SPH  
MMD-AP0151SPH  
MMD-AP0181SPH  
MMC-AP0151H  
MMC-AP0181H  
MMC-AP0241H  
MMC-AP0271H  
MMC-AP0361H  
MMC-AP0481H  
MMK-AP0071H  
MMK-AP0091H  
MMK-AP0121H  
MMK-AP0151H  
MMK-AP0181H  
MMK-AP0241H  
MMK-AP0072H  
MMK-AP0092H  
MMK-AP0122H  
MML-AP0071H  
MML-AP0091H  
MML-AP0121H  
MML-AP0151H  
MML-AP0181H  
MML-AP0241H  
MML-AP0071BH  
MML-AP0091BH  
MML-AP0121BH  
MML-AP0151BH  
MML-AP0181BH  
MML-AP0241BH  
MMF-AP0151H  
MMF-AP0181H  
MMF-AP0241H  
MMF-AP0271H  
MMF-AP0361H  
MMF-AP0481H  
MMF-AP0561H  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
264  
0.060  
0.060  
0.060  
0.060  
0.060  
0.060  
0.060  
0.090  
0.090  
0.090  
0.053  
0.053  
0.053  
0.039  
0.039  
0.053  
0.053  
0.053  
0.092  
0.022  
0.022  
0.022  
0.034  
0.034  
0.034  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.120  
0.160  
0.160  
0.160  
0.260  
0.260  
0.370 Ɨ 3  
0.370 Ɨ 3  
0.060  
0.060  
0.060  
0.060  
0.060  
0.030  
0.030  
0.040  
0.040  
0.080  
0.080  
0.030  
0.030  
0.030  
0.030  
0.030  
0.030  
0,030  
0,030  
0,030  
0.045  
0.045  
0.045  
0.045  
0.070  
0.070  
0.019  
0.019  
0.019  
0.070  
0.070  
0.070  
0.037  
0.037  
0.063  
0.063  
0.110  
0.160  
0.160  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
2-way ceiling cassette  
1-way ceiling cassette  
Standard ducted unit  
High-pressure ducted unit  
Slim duct unit  
Ceiling-suspended unit  
High-wall unit  
Floor-mounted console unit  
Concealed chassis unit  
Floor-mounted cabinet unit  
Legend  
MCA  
FLA  
Minimum circuit current, A  
Full load current, A  
MOCP Maximum overcurrent protection current, A  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single outdoor unit  
Heat pump Cooling only Nominal  
Voltage  
range  
Min.  
342  
342  
342  
Compressor  
Max. RLA  
Fan motor  
Power supply  
MMY-  
MMY-  
voltage  
(V-ph-Hz)  
kW  
FLA  
MCA  
16.5  
16.5  
20.0  
22.5  
24.5  
MOCP  
20  
20  
30  
30  
MAP0501HT8 MAP0501T8 400-3-50  
MAP0601HT8 MAP0601T8 400-3-50  
MAP0801HT8 MAP0801T8 400-3-50  
MAP1001HT8 MAP1001T8 400-3-50  
MAP1201HT8 MAP1201T8 400-3-50  
457  
457  
457  
457  
457  
4.0 + 4.0  
4.6 + 4.6  
5.2 + 5.2  
6.5 + 6.5  
9.5 + 9.5  
0.60  
0.60  
0.60  
0.60  
0.60  
0.8  
0.8  
1.0  
1.1  
1.1  
342  
342  
30  
Combination of outdoor units  
Heat pump Cooling only Nominal  
Voltage  
range  
Min.  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
342  
Compressor  
Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4  
Max. RLA  
5.2 + 5.2  
Fan motor  
Power supply  
MMY-  
MMY-  
voltage  
(V-ph-Hz  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
400-3-50  
RLA  
RLA  
—
—
—
—
4.6 + 4.6  
—
5.2 + 5.2  
—
5.2 + 5.2  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
9.5 + 9.5  
6.5 + 6.5  
6.5 + 6.5  
6.5 + 6.5  
6.5 + 6.5  
9.5 + 9.5  
9.5 + 9.5  
RLA  
—
—
—
—
—
—
—
—
—
—
—
5.2 + 5.2  
—
5.2 + 5.2  
—
5.2 + 5.2  
—
kW  
FLA  
MCA  
36.5  
40.0  
42.5  
45.0  
56.5  
47.0  
60.0  
49.0  
62.5  
65.0  
67.5  
80.0  
69.5  
82.5  
71.5  
85.0  
73.5  
87.5  
90.0  
92.0  
94.0  
96.0  
98.0  
MOCP  
40  
50  
50  
60  
70  
60  
70  
60  
70  
80  
80  
90  
80  
100  
80  
100  
90  
AP1401HT8 AP1401T8  
AP1601HT8 AP1601T8  
AP1801HT8 AP1801T8  
AP2001HT8 AP2001T8  
AP2201HT8 AP2201T8  
AP2211HT8 AP2211T8  
AP2401HT8 AP2401T8  
AP2411HT8 AP2411T8  
AP2601HT8 AP2601T8  
AP2801HT8 AP2801T8  
AP3001HT8 AP3001T8  
AP3201HT8 AP3201T8  
AP3211HT8 AP3211T8  
AP3401HT8 AP3401T8  
AP3411HT8 AP3411T8  
AP3601HT8 AP3601T8  
AP3611HT8 AP3611T8  
AP3801HT8 AP3801T8  
AP4001HT8 AP4001T8  
AP4201HT8 AP4201T8  
AP4401HT8 AP4401T8  
AP4601HT8 AP4601T8  
AP4801HT8 AP4801T8  
Legend  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
457  
4.6 + 4.6  
5.2 + 5.2  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
9.5 + 9.5  
5.2 + 5.2  
6.5 + 6.5  
6.5 + 6.5  
5.2 + 5.2  
6.5 + 6.5  
5.2 + 5.2  
9.5 + 9.5  
6.5 + 6.5  
9.5 + 9.5  
6.5 + 9.5  
6.5 + 6.5  
6.5 + 6.5  
9.5 + 9.5  
9.5 + 9.5  
9.5 + 9.5  
0.6 Ɨ 2 1.0 + 0.8  
0.6 Ɨ 2 1.0 + 1.0  
0.6 Ɨ 2 1.0 + 1.1  
0.6 Ɨ 2 1.1 + 1.1  
0.6 Ɨ 3 1.0 + 1.0 + 0.8  
0.6 Ɨ 2 1.1 + 1.1  
0.6 Ɨ 3 1.0 + 1.0 + 1.0  
0.6 Ɨ 2 1.1 + 1.1  
0.6 Ɨ 3 1.1 + 1.1 + 1.0  
0.6 Ɨ 3 1.1 + 1.1 + 1.0  
0.6 Ɨ 3 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.0 + 1.0 + 1.0 + 1.0  
0.6 Ɨ 3 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.0 + 1.0 + 1.0  
0.6 Ɨ 3 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.0 + 1.0  
0.6 Ɨ 3 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.0  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.1  
0.6 Ɨ 4 1.1 + 1.1 + 1.1 + 1.1  
5.2 + 5.2  
6.5 + 6.5  
6.5 + 6.5  
5.2 + 5.2  
9.5 + 9.5  
5.2 + 5.2  
9.5 + 9.5  
6.5 + 6.5  
6.5 + 6.5  
6.5 + 6.5  
5.2 + 5.2  
9.5 + 9.5  
6.5 + 6.5  
9.5 + 9.5  
6.5 + 6.5  
9.5 + 9.5  
6.5 + 6.5  
6.5 + 6.5  
9.5 + 9.5  
9.5 + 9.5  
9.5 + 9.5  
9.5 + 9.5  
5.2 + 5.2  
6.5 + 6.5  
6.5 + 6.5  
6.5 + 6.5  
6.5 + 6.5  
9.5 + 9.5  
100  
100  
110  
110  
110  
110  
MCA  
Minimum circuit current, A  
FLA  
Full load current, A  
MOCP Maximum overcurrent protection current, A  
kW  
RLA  
Rated fan motor output, kW  
Rated load current, A  
Note: RLA is based on the following conditions:  
Indoor temperature: 27°C db/19°C wb  
Outdoor temperature: 35°C db  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Controls  
A range of controls to meet various system needs  
As the size of the building increases so does the number of air conditioning units required. The multiple air  
conditioning system Super MMS ensures energy savings and comfort by allowing control of multiple units requiring  
different loads.  
The Super MMS provides a range of functions to enable integrated, centralized control of multiple units. Design an  
optimal system that best suits the application and scale of your project.  
1. Control via indoor remote controller  
1-1. Remote contoller  
Individual air conditioning units can be controlled remotely.  
1-2. Group control  
One remote controller can control a maximum of 8 indoor units in a group.  
1-3. Two controlling positions  
The units can be controlled from two locations using two remote controllers.  
1-4. Weekly timer  
The units can be run on a weekly schedule using a ā€œremote controller with weekly timerā€.  
2. Control via the central remote controller  
2-1. Central control + individual control  
Up to 64 units can be controlled using the central remote controller and/or indoor remote controllers.  
2-2. Weekly timer controller  
The central remote controller can be connected to a weekly timer to set a weekly running schedule.  
2-3. Control without indoor remote controller  
The units can be operated from the central remote controller only, without the use of indoor remote controllers.  
2-4. Central control with 1 to 1 models  
Additionally, 1 to 1 models like the Digital Inverter or Super Digital Inverter can be joined into the Super MMS  
central control scheme.  
3. Network control  
The Super MMS control system can offer flexible centralized network control according to various customer  
requirements, for both open network building control in combination with other building apparatus such as  
elevator, fire alarm, lighting, etc., and also for stand-alone central air conditioning control.  
These central control systems are mainly established by advanced local server platforms.  
3-1. Open network control  
Super MMS open network control is applicable for major global building management standards.  
3-1-1. LONWORKS  
The LONWORKS interface manages the Super MMS air conditioning system as a LON device to  
command a building computer message and to monitor the operating status.  
3-1-2. BACnet  
The local server serves air conditioning sub-system in a building control BACnet system.  
3-2. Stand-alone central control  
Simple exclusive air conditioning central control with less system integration work.  
3-2-1. Touch-screen controller  
A combination of touch-screen and local server enables easy operation and user-friendly display.  
3-2-2. Windows-based plug-in central controller  
The local server provides the central control function only by plug-in into a customer’s computer.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Applications for indoor remote controller  
Basic function  
System diagram  
Model  
1-1  
Individual control  
Air conditioner is individually  
operated at a distance.  
•
•
•
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
RBC-AS21E  
Wireless remote controller kit  
TCB-AX21U(W)-E  
RBC-AX22CE  
Wireless remote controller  
Main remote controller  
Indoor  
unit  
Indoor  
unit  
TCB-AX21E  
Possible up to max.  
total length 500 m  
Receiver unit  
Wireless  
remote  
controller  
Remote  
controller  
1-2  
GROUP control  
•
•
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
Max. 8 indoor units  
One remote controller can  
control a group of max. 8  
indoor units. Operating on  
the same setting.  
RBC-AS21E  
Indoor  
unit  
Indoor  
unit  
Indoor  
unit  
Indoor  
unit  
Remote  
controller  
Possible up to max. total length 500 m  
1-3  
Two remote controllers  
Air conditioner is controlled by  
two remote controller in two  
places.  
•
•
•
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
Wired system  
Wireless system  
RBC-AS21E  
Wireless remote controller kit  
TCB-AX21U(W)-E  
RBC-AX22CE  
Indoor  
unit  
Indoor  
unit  
TCB-AX21E  
Wireless  
remote  
controller 1  
Wireless  
remote  
controller 2  
Remote  
controller  
Remote  
controller  
Master  
Sub-controller  
Master  
Sub-controller  
Possible up to max.  
total length 500 m  
Indoor  
unit  
Wired and wireless  
combination control  
(either controller  
should be set as  
sub-controller)  
Wireless  
remote  
controller  
Remote  
controller  
1-4  
Control by weekly timer  
Weekly schedule operation.  
•
•
Wired remote controller  
RBC-AMT31E  
+
Weekly timer  
RBC-EXW21E  
Weekly timer function  
Settings of ON/OFF  
3 times per day  
Timer time is displayed  
Designation of holiday  
Indoor  
unit  
Weekly  
timer  
Remote  
controller  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Application controls for central remote controller  
Basic function  
Central management  
controller for 64 units  
System diagram  
Master  
unit  
Model  
Central remote controller  
TCB-SC642TLE  
2-1  
•
Outdoor unit  
Line 3  
U3, U4  
Indoor remote controller  
•
Wired remote controller  
U5, U6  
Indoor unit  
RBC-AMT31E  
•
Simplified remote controller  
RBC-AS21E  
U1, U2  
Zone 4  
Master  
unit  
Indoor remote controller  
U3, U4  
Outdoor unit  
Line 2  
Indoor unit  
U5, U6  
U1, U2  
Zone 3  
Zone 2  
Master  
unit  
Indoor remote controller  
U3, U4  
Outdoor unit  
Line 1  
Indoor unit  
U1, U2  
Zone 1  
Power  
supply  
Indoor remote controller  
Central  
remote controller  
Single-phase  
220/240 V  
Function of central remote controller  
•
•
Individual control of up to 64 indoor units.  
Individual control for max. 64 indoor units divided into 1 to 4 zones (up to  
16 indoor units for each zone).  
•
•
Up to 16 outdoor master units are connectable.  
4 central control settings to inhibit individual operation by remote controller  
can be selected.  
•
•
Setting for one of 1 to 4 zones is available.  
Usable with other central control devices (up to 10 central control devices  
in one control circuit).  
•
•
Choice of two control modes: central controller mode/remote controller  
mode.  
Setting of simultaneous ON/OFF 3 times for each day of the week  
combined with weekly timer.  
2-2  
Central remote controller  
+
weekly timer  
•
•
Central remote controller  
TCB-SC642TLE  
+
Weekly timer  
RBC-EXW21E  
U3, U4  
Outdoor unit  
Indoor unit  
U1, U2  
Weekly operation schedule can  
be set by connecting a weekly  
timer to the contral remoter  
controller.  
Indoor remote controller  
•
Wired remote controller  
RBC-AMT31E  
or  
•
Simplified remote controller  
RBC-AS21E  
Indoor remote controller  
Weekly timer  
Single-phase  
220/240 V  
Power  
supply  
Central  
remote controller  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic function  
System diagram  
U3, U4  
Model  
Central remote controller  
TCB-SC642TLE  
2-3  
Remote central control  
without indoor remote  
controller  
•
Outdoor unit  
U1, U2  
Indoor remote controller  
Power  
supply  
•
Wired remote controller  
RBC-AMT31E  
Indoor unit  
Central remote controller  
Single-phase,  
220-240 V  
Even when grouping operation is performed  
by connecting multiple indoor units to 1 line,  
the indoor remote controller is required.  
Example of grouping operation  
U3, U4  
Outdoor unit  
U1, U2  
Power  
supply  
(Group)  
Indoor remote controller is required  
Single-phase,  
220-240 V  
Available  
Central remote controller  
U3, U4  
Outdoor unit  
U1, U2  
Power  
supply  
(Group)  
Available  
Single-phase,  
220-240 V  
Central remote controller  
2-4  
Central management control  
with ā€œ1:1 modelā€  
•
•
Central remote controller  
TCB-SC642TLE  
ā€œ1:1 modelā€ connection interface  
Power  
supply  
Central remote controller  
interface  
TCB-PCNT30TLE  
U3, U4  
RAV-SM560KRT-E,  
SM800KRT-E, are not available  
Master  
unit  
Indoor remote controller  
U1, U2  
ā€œ1:1 modelā€  
connection  
interface  
•
Wired remote controller  
Indoor unit  
RBC-AMT31E  
•
Simplified remote controller  
RBC-AS21E  
Indoor remote controller  
*1  
Toshiba Digital Inverter System and Super Digital Inverter System  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Application control for network  
Basic function  
System diagram  
Model  
3-1-1  
LONWORKS  
•
LON Gateway  
TCB-1FLN****  
LON Centre  
•
ā€œ1:1 modelā€ connection interface  
TCB-PCNT30TLE  
LON Talk  
(RAV-SM560KRT-E,  
SM800KRT-E are not available)  
LON  
interfaces  
Indoor remote controller  
•
Wired remote controller  
RBC-AMT31E  
or  
•
Simplified remote controller  
RBC-AS21E  
ā€œ1:1 modelā€  
connection interface  
Remote controller  
*1  
Toshiba Digital Inverter System and Super Digital Inverter System  
The LONWORKS interface shall be connected between a building management  
computer and the Super MMS air conditioning system.  
3-1-2  
BACnet  
•
•
•
BACnet local server  
BMS-LSV******  
BACnet Centre  
Local server  
TCS-Net relay interface  
BMS-1FLSV1E  
ā€œ1:1 modelā€ connection interface  
TCB-PCNT30TLE  
(RAV-SM560KRT-E,  
SM800KRT-E are not available)  
TCS-Net  
relay interface  
Indoor remote controller  
•
Wired remote controller  
RBC-AMT31E  
•
Simplified remote controller  
RBC-AS21E  
ā€œ1:1 modelā€  
connection interface  
Remote controller  
*1  
Toshiba Digital Inverter System and Super Digital Inverter System  
The local server can be connected within the BACnet network, and can be  
connected to the Super MMS air conditioning system through the interface.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic function  
System diagram  
Model  
3-2-1  
Touch screen controller  
•
Touch screen controller  
BMS-TP5120ACE  
Intelligent server  
Touch screen controller  
•
BMS-LSV2E  
BMS-STC01E  
•
•
•
•
TCS-Net relay interface  
BMS-1FLSV1E  
Energy monitoring relay interface  
BMS-1FWH3E  
Digital I/O relay interface  
BMS-1FDD01E  
ā€œ1:1 modelā€ connection interface  
TCB-PCNT30TLE  
Local server  
Relay interface  
(RAV-SM560KRT-E,  
SM800KRT-E are not available)  
Indoor remote controller  
•
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
RBC-AS21E  
ā€œ1:1 modelā€  
connection interface  
Remote controller  
•
Energy monitoring relay interface  
Digital I/O relay interface  
*1  
Toshiba Digital Inverter System and Super Digital Inverter System  
Combination of touch screen and local server.  
Personal computer on site  
3-2-2  
Windows-based central  
controller  
•
•
•
Windows-based central controller  
BMS-LSV**  
TCS-Net relay interface  
BMS-1FLSV1E  
Intelligent server  
BMS-LSV2E  
BMS-STC01E  
Energy monitoring relay interface  
BMS-1FWH3E  
Digital I/O relay interface  
BMS-1FDD01E  
Local server  
•
•
•
Relay interface  
ā€œ1:1 modelā€ connection interface  
TCB-PCNT30TLE  
(RAV-SM560KRT-E,  
SM800KRT-E are not available)  
Indoor remote controller  
•
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
RBC-AS21E  
ā€œ1:1 modelā€  
connection interface  
Remote controller  
•
Energy monitoring relay interface  
Digital I/O relay interface  
*1  
Toshiba Digital Inverter System and Super Digital Inverter System  
The local server shall be a plug-in into a customer’s personal computer.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Accessories  
Indoor unit accessories  
Remote controller  
Indoor unit type  
Accessory name  
Model  
Applicable model  
Common parts for  
all model types  
4-way ceiling cassette  
2-way ceiling cassette  
1-way ceiling cassette  
Standard ducted unit  
High-pressure ducted unit  
Slim duct unit  
Ceiling-suspended unit  
High-wall unit (1 Series)  
High-wall unit (2 Series)  
Floor-mounted console unit  
Concealed chassis unit  
Floor-mounted cabinet unit  
Wired remote controller  
Central remote controller  
Weekly timer  
Simplified remote controller  
Wireless remote controller kit*1  
RBC-AMT31E  
TCB-SC642TLE  
RBC-EXW21E  
RBC-AS21E  
TCB-AX21U(W)-E  
4-way ceiling cassette  
Ceiling-suspended unit  
RBC-AX22CE  
TCB-AX21E  
Universal type  
(except high-pressure ducted units)  
*1  
For availability of the wireless remote controller kit, consult your dealer.  
Panels  
Indoor unit type  
Accessory name  
Model  
Application model  
Remarks  
4-way ceiling cassette  
Required accessory Ceiling panel  
RBC-U21PG(W)-E  
TCB-UF1601UE  
TCB-UFM1601UE  
TCB-UFH1601UE  
TCB-DF21UKE  
Optional  
Super long life filter  
High efficiency filter 65  
High efficiency filter 90  
Filter frame  
Needed for initial installation  
Used with TCB-GFC1601UE  
Fresh air and filter chamber TCB-GFC1601UE  
Fresh air inlet box  
TCB-GB1601UE  
TCB-FF101URE  
Auxiliary fresh air flange  
Spacer for height adjustment TCB-SP1601UE  
TCB-SP1601U-KW50E  
TCB-BC1601UE  
Air discharge direction kit  
Three-piece kit  
2-way ceiling cassette  
1-way ceiling cassette  
Standard ducted unit  
Required accessory Ceiling panel  
RBC-UW136PG  
RBC-UW266PG  
RBC-UW466PG  
RBC-US165PG  
RBC-US265PG  
RBC-UY135PG  
TCB-UFM11BFCE  
TCB-UFM21BFCE  
TCB-UFM11BE  
TCB-UFM21BE  
TCB-UFM31BE  
TCB-UFM41BE  
TCB-UFH51BFCE  
TCB-UFH61BFCE  
TCB-UFH51BE  
TCB-UFH61BE  
TCB-UFH71BE  
TCB-UFH81BE  
RBC-UD281PE(W)  
RBC-UD501PE(W)  
RBC-UD801PE(W)  
RBC-UD1401PE(W)  
TCB-CA281BE  
TCB-CA501BE  
TCB-CA801BE  
TCB-CA1401BE  
TCB-FC281BPE  
TCB-FC501BPE  
TCB-FC801BPE  
TCB-FC1401BPE  
TCB-FK281BE  
TCB-FK501BE  
TCB-FK801BE  
TCB-FK1401BE  
TCB-UFM1D-1E  
TCB-UFM2D-1E  
TCB-UFM3DE  
TCB-UFH5D-1E  
TCB-UFH6D-1E  
TCB-UFH7DE  
AP0071-0121  
AP0151-0301  
AP0361-0561  
AP0151-0181  
AP0241  
Required accessory Ceiling panel  
AP0071-0121  
Optional  
High efficiency filter 65  
AP0071-0121/AP0241-0301 AP0241-AP0301 two-piece kit  
AP0151-0181/AP0361-0561 AP0361-AP0581 two-piece kit  
AP0071-0121  
AP0151-0181  
AP0241-0301  
AP0361-0561  
AP0071-0121/AP0241-0301 AP0241-AP0301 two-piece kit  
AP0151-0181/AP0361-0561 AP0361-AP0581 two-piece kit  
AP0071-0121  
AP0151-0181  
AP0241-0301  
AP0361-0561  
AP0071-0121  
AP0151-0181  
AP0241-0301  
AP0361-0561  
AP0071-0121  
AP0151-0181  
AP0241-0301  
AP0361-0561  
AP0071-0121  
AP0151-0181  
AP0241-0301  
AP0361-0561  
AP0071-0121  
AP0151-0181  
AP0241-0301  
High efficiency filter 90  
Ceiling panel  
Suction canvas  
Filter chamber  
Bottom filter kit  
AP0361-0561  
High-pressure ducted unit Optional  
High efficiency filter 65  
High efficiency filter 90  
Long life pre filter  
AP0181-0481  
AP0241-0361  
AP0721-0961  
AP0181-0481  
AP0241-0361  
AP0721-0961  
AP0181-0481  
AP0241-0361  
AP0721-0961  
AP0181  
AP0481 two-piece kit  
Two-piece kit  
AP0481 two-piece kit  
Two-piece kit  
TCB-PF1D-1E  
TCB-PF2D-1E  
TCB-PF3DE  
TCB-FCY21DE  
TCB-FCY31DE  
TCB-FCY51DE  
TCB-FCY100DE  
TCB-DP21DE  
TCB-DP22DE  
TCB-DP22CE  
TCB-KP12CE  
TCB-KP22CE  
AP0481 two-piece kit  
Two-piece kit  
Filter chamber  
AP0241-0361  
AP0481  
AP0721-0961  
AP0181-0481  
AP0721-0961  
AP0151-0481  
AP0151-0181  
AP0241-0481  
Drain pump kit  
Drain pump kit  
Ceiling-suspended unit  
Optional  
*
Required accessory when  
using drain pump kit  
Note: For availability of the wireless remote controller kit and other optional equipment not in this table, consult your dealer.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Technical specifications  
Indoor units  
4-way ceiling cassettes  
Model MMU-AP  
Cooling capacity*  
Heating capacity  
0091H  
2.8  
3.2  
0121H  
3.6  
4.0  
0151H  
4.5  
5.0  
0181H  
5.6  
6.3  
0241H  
7.1  
8.0  
0271H  
8.0  
9.0  
0301H  
9.0  
10.0  
0361H  
11.2  
12.5  
0481H  
14.0  
16.0  
0561H  
16.0  
18.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Starting current  
A
kW  
A
0.17  
0.020  
0.30  
0.17  
0.020  
0.30  
0.19  
0.022  
0.33  
0.21  
0.026  
0.36  
0.24  
0.032  
0.42  
0.24  
0.032  
0.42  
0.35  
0.048  
0.59  
0.59  
0.070  
0.87  
0.81  
0.110  
1.23  
0.83  
0.112  
1.26  
Unit appearance  
Zinc hot dipping steel plate - heat insulating material attached  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
256  
840  
840  
20  
256  
840  
840  
20  
256  
840  
840  
22  
256  
840  
840  
22  
256  
840  
840  
23  
256  
840  
840  
23  
256  
840  
840  
23  
319  
840  
840  
28  
319  
840  
840  
28  
319  
840  
840  
28  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Turbo fan  
Fan motor power input  
W
60  
60  
60  
60  
60  
60  
60  
90  
90  
90  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
222  
203  
189  
222  
203  
189  
258  
231  
219  
292  
256  
222  
333  
256  
228  
333  
256  
228  
367  
308  
236  
467  
361  
297  
567  
397  
314  
581  
422  
342  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
800  
730  
680  
800  
730  
680  
930  
830  
790  
1050  
920  
800  
1200  
920  
820  
1200  
920  
820  
1320  
1110  
850  
1680  
1300  
1070  
2040  
1430  
1130  
2090  
1520  
1230  
Sound power level (high/medium/low)  
43/42/40 43/42/40 44/42/40 45/42/41 47/44/41 47/44/41 50/46/43 53/49/46 57/51/47 58/53/47  
30/29/27 30/29/27 31/29/27 32/29/28 34/31/28 34/31/28 37/33/30 40/36/33 44/38/34 45/40/34  
Standard long-life filter supplied  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
Ceiling panel model number  
Panel colour  
in  
in  
in  
3/8  
1/4  
1
3/8  
1/4  
1
1/2  
1/4  
1
1/2  
1/4  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
RBC-U21PG (W)-E  
Moon white (Munsell/2.5GY 9.0/0.5)  
Panel dimensions  
Height  
Width  
Depth  
Panel weight  
mm  
mm  
mm  
kg  
35  
35  
35  
35  
35  
35  
35  
35  
35  
35  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
950  
950  
4.5  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
2-way ceiling cassettes  
Model MMU-AP  
Cooling capacity*  
Heating capacity  
0071WH  
2.2  
2.5  
0091WH  
2.8  
3.2  
0121WH  
3.6  
4.0  
0151WH  
4.5  
5.0  
0181WH  
5.6  
6.3  
0241WH  
7.1  
8.0  
0271WH  
8.0  
9.0  
0301WH  
9.0  
10.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.31  
0.070  
97  
0.31  
0.070  
97  
0.31  
0.070  
97  
0.32  
0.072  
97  
0.32  
0.072  
97  
0.46  
0.105  
99  
0.46  
0.105  
99  
0.47  
0.106  
98  
kW  
%
A
0.47  
0.47  
0.47  
0.60  
0.60  
0.89  
0.89  
0.98  
Unit appearance  
Zinc hot dipping steel plate - heat insulating material attached  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
398  
830  
550  
33  
398  
830  
550  
33  
398  
830  
550  
33  
398  
1350  
550  
44  
398  
1350  
550  
44  
398  
1350  
550  
48  
398  
1350  
550  
48  
398  
1350  
550  
48  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
53  
53  
53  
39  
39  
53  
53  
53  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
158  
142  
125  
158  
142  
125  
158  
142  
125  
217  
195  
167  
217  
195  
167  
317  
267  
200  
317  
267  
200  
350  
317  
267  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
570  
570  
570  
780  
780  
1140  
1140  
1260  
510  
510  
510  
700  
700  
960  
960  
1140  
450  
450  
450  
600  
600  
720  
720  
960  
Sound power level (high/medium/low)  
47/45/43  
34/32/30  
47/45/43  
34/32/30  
47/45/43  
34/32/30  
48/46/43  
35/33/30  
48/46/43  
35/33/30  
51/48/46  
38/35/33  
51/48/46  
38/35/33  
53/50/47  
40/37/34  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Standard long-life filter supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
Ceiling panel model number  
Panel colour  
in  
in  
in  
3/8  
1/4  
1
3/8  
1/4  
1
3/8  
1/4  
1
1/2  
1/4  
1
1/2  
1/4  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
RBC-UW136PG  
Light ivory (Munsell 10Y 9/0.5)  
RBC-UW266PG  
Panel dimensions  
Height  
Width  
Depth  
Panel weight  
mm  
mm  
mm  
kg  
8
8
8
8
8
8
8
8
1000  
650  
8
1000  
650  
8
1000  
650  
8
1520  
650  
11  
1520  
650  
11  
1520  
650  
11  
1520  
650  
11  
1520  
650  
11  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
1-way ceiling cassettes  
Model MMU-AP  
Cooling capacity*  
Heating capacity  
0071YH  
2.2  
2.5  
0091YH  
2.8  
3.2  
0121YH  
3.6  
4.0  
0151SH  
4.5  
5.0  
0181SH  
5.6  
6.3  
0241SH  
7.1  
8.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.24  
0.053  
95  
0.24  
0.053  
95  
0.24  
0.053  
95  
0.48  
0.103  
93  
0.48  
0.103  
93  
0.55  
0.115  
91  
kW  
%
A
0.60  
0.60  
0.60  
0.80  
0.80  
1.10  
Unit appearance  
Zinc hot dipping steel plate - heat insulating material attached  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
235  
850  
400  
22  
235  
850  
400  
22  
235  
850  
400  
22  
198  
1000  
655  
27  
198  
1000  
655  
27  
198  
1200  
655  
31  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
22  
22  
22  
34  
34  
34  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
150  
133  
117  
150  
133  
117  
150  
133  
117  
217  
200  
183  
217  
200  
183  
333  
317  
283  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
540  
540  
540  
780  
780  
1200  
480  
480  
480  
720  
720  
1140  
420  
420  
420  
660  
660  
1020  
Sound power level (high/medium/low)  
55/52/47  
42/39/34  
55/52/47  
42/39/34  
55/52/47  
42/39/34  
55/52/48  
42/39/35  
55/52/48  
42/39/35  
56/54/50  
43/41/37  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Room thermostat  
Connection pipes  
Standard long-life filter supplied  
Remote controller  
Supplied  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
Ceiling panel model number  
Panel colour  
in  
in  
in  
3/8  
1/4  
1
3/8  
1/4  
1
3/8  
1/4  
1
1/2  
1/4  
1
1/2  
1/4  
1
5/8  
3/8  
1
RBC-UY135PG  
W: Silky shade (1Y8.5/0.5)  
RBC-US165PG  
RBC-US265PG  
Panel dimensions  
Height  
Width  
Depth  
Panel weight  
mm  
mm  
mm  
kg  
18  
18  
18  
10  
10  
10  
1050  
470  
3.5  
1050  
470  
3.5  
1050  
470  
3.5  
1220  
755  
8.0  
1220  
755  
8.0  
1420  
755  
9.0  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Standard ducted units  
Model MMD-AP  
0071BH 0091BH 0121BH 0151BH 0181BH 0241BH 0271BH 0301BH 0361BH 0481BH 0561BH  
Cooling capacity*  
Heating capacity  
kW  
kW  
2.2  
2.5  
2.8  
3.2  
3.6  
4.0  
4.5  
5.0  
5.6  
6.3  
7.1  
8.0  
8.0  
9.0  
9.0  
10.0  
11.2  
12.5  
14.0  
16.0  
16.0  
18.0  
Electrical data  
Power supply  
V-ph-Hz 230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Starting current  
A
kW  
A
0.29  
0.033  
0.50  
0.29  
0.033  
0.50  
0.34  
0.039  
0.59  
0.34  
0.039  
0.59  
0.43  
0.050  
0.75  
0.52  
0.060  
0.90  
0.52  
0.060  
0.90  
0.61  
0.071  
1.05  
0.83  
0.107  
1.44  
0.98  
0.128  
1.70  
0.98  
0.128  
1.70  
Unit appearance  
Zinc hot dipping steel plate  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
320  
550  
800  
28  
320  
550  
800  
28  
320  
550  
800  
28  
320  
700  
800  
32  
320  
700  
800  
32  
320  
1000  
800  
43  
320  
1000  
800  
43  
320  
1000  
800  
43  
320  
1350  
800  
55  
320  
1350  
800  
55  
320  
1350  
800  
55  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
120  
120  
120  
120  
120  
120  
120  
120  
120  
120  
120  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
133  
117  
95  
133  
117  
95  
158  
136  
111  
181  
150  
133  
217  
183  
150  
317  
275  
242  
317  
275  
242  
350  
300  
242  
450  
392  
333  
550  
475  
414  
550  
475  
414  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
Pa  
Pa  
dB(A)  
480  
420  
340  
40  
480  
420  
340  
40  
570  
490  
400  
40  
650  
540  
480  
40  
780  
660  
540  
40  
1140  
990  
870  
40  
1140  
990  
870  
40  
1260  
1080  
870  
40  
1620  
1410  
1200  
40  
1980  
1710  
1490  
40  
1980  
1710  
1490  
40  
Static pressure (factory setting)  
Static pressure (max.)  
Sound power level (high/medium/low)  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
43/41/39 43/41/39 44/42/40 44/42/40 45/43/41 46/44/42 46/44/42 47/45/42 49/47/45 51/49/45 51/49/45  
30/28/26 30/28/26 31/29/27 31/29/27 32/30/28 33/31/29 33/31/29 34/32/29 36/34/32 38/36/32 38/36/32  
Standard long-life filter supplied  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
in  
3/8  
1/4  
1
3/8  
1/4  
1
3/8  
1/4  
1
1/2  
1/4  
1
1/2  
1/4  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
Panel dimensions  
Height  
Width  
Depth  
Panel weight  
mm  
mm  
mm  
kg  
9
9
9
9
9
9
9
9
9
9
9
630  
500  
3.5  
630  
500  
3.5  
630  
500  
3.5  
780  
500  
4.0  
780  
500  
4.0  
1080  
500  
6.0  
1080  
500  
6.0  
1080  
500  
6.0  
1430  
500  
7.0  
1430  
500  
7.0  
1430  
500  
7.0  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
High-pressure ducted units  
Model MMD-AP  
Cooling capacity*  
0181H  
5.6  
0241H  
7.1  
0271H  
8.0  
0361H  
11.2  
0481H  
14.0  
0721H  
22.4  
0961H  
28.0  
kW  
Heating capacity  
kW  
6.3  
8.0  
9.0  
12.5  
16.0  
25.0  
31.5  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.81  
0.184  
99  
1.35  
0.299  
96  
1.35  
0.299  
96  
1.63  
0.368  
98  
1.84  
0.414  
98  
5.25  
1.200  
99  
5.52  
1.260  
99  
kW  
%
A
1.3  
3.5  
3.5  
4.1  
4.8  
13.6  
14.8  
Unit appearance  
Zinc hot dipping steel plate  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
380  
850  
660  
50  
380  
850  
660  
52  
380  
850  
660  
52  
380  
850  
660  
56  
380  
1200  
660  
67  
470  
470  
1380  
1250  
150  
1380  
1250  
150  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
160  
160  
160  
260  
260  
370 x 3  
370 x 3  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
300  
250  
200  
439  
367  
295  
439  
367  
295  
533  
445  
356  
700  
583  
467  
1200  
1000  
800  
1400  
1167  
933  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
Pa  
Pa  
dB(A)  
1080  
900  
720  
137  
1580  
1320  
1060  
137  
1580  
1320  
1060  
137  
1920  
1600  
1280  
137  
2520  
2100  
1680  
137  
4320  
3600  
2880  
137  
5040  
4200  
3360  
137  
Static pressure (factory setting)  
Static pressure (low/medium/high)  
Sound power level (high)  
68.6/137/196 68.6/137/196 68.6/137/196 68.6/137/196 68.6/137/196 68.6/137/196 68.6/137/196  
50  
53  
53  
53  
53  
62  
63  
Sound pressure level (high/medium/low)** dB(A)  
37/35/33  
40/38/36  
40/38/36  
40/38/36  
40/38/36  
49/47/45  
50/48/46  
Air filter  
Controller  
Optional or field-supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia***  
in  
in  
in  
1/2  
1/4  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
5/8  
3/8  
1
7/8  
1/2  
1
7/8  
1/2  
1
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
***  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
Male screw connection one side  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Slim duct units  
Model MMD-AP  
Cooling capacity*  
Heating capacity  
0071SPH  
2.2  
2.5  
0091SPH  
2.8  
3.2  
0121SPH  
3.6  
4.0  
0151SPH  
4.5  
5.0  
0181SPH  
5.6  
6.3  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Starting current  
A
kW  
A
0.29  
0.039  
0.51  
0.29  
0.039  
0.51  
0.31  
0.043  
0.54  
0.32  
0.045  
0.56  
0.39  
0.054  
0.68  
Unit appearance  
Zinc hot dipping steel plate  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
210  
845  
645  
22  
210  
845  
645  
22  
210  
845  
645  
22  
210  
845  
645  
23  
210  
845  
645  
23  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Polyethylene foam and polyurethane foam  
Centrifugal fan  
Fan motor power input  
W
60  
60  
60  
60  
60  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
150  
131  
111  
150  
131  
111  
167  
145  
125  
192  
167  
145  
217  
189  
161  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
Pa  
Pa  
Pa  
540  
540  
600  
690  
780  
470  
470  
520  
600  
680  
400  
400  
450  
520  
580  
Static pressure (factory setting)  
Static pressure (max.)  
Air filter pressure loss  
Lower air inlet  
6
6
5
5
4
-16/-31/-46  
4
-16/-31/-46  
4
-15/-30/-45  
5
-15/-30/-45  
5
-14/-29/-44  
6
Sound power level (high/medium/low)  
Sound pressure level (high/medium/low)**  
Rear air inlet  
dB(A)  
dB(A)  
49/46/43  
36/33/30  
49/46/43  
36/33/30  
51/48/45  
38/35/32  
52/49/46  
39/36/33  
53/51/49  
40/38/36  
Sound power level (high/medium/low)  
Sound pressure level (high/medium/low)**  
Air filter  
dB(A)  
dB(A)  
41/39/37  
28/26/24  
Standard long-life filter supplied  
Remote controller  
41/39/37  
28/26/24  
42/40/38  
29/27/25  
45/43/41  
32/30/28  
46/44/42  
33/31/29  
Controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
in  
3/8  
1/4  
1
3/8  
1/4  
1
3/8  
1/4  
1
1/2  
1/4  
1
1/2  
1/4  
1
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Ceiling-suspended units  
Model MMC-AP  
Cooling capacity*  
Heating capacity  
0151H  
4.5  
5.0  
0181H  
5.6  
6.3  
0241H  
7.1  
8.0  
0271H  
8.0  
9.0  
0361H  
11.2  
12.5  
0481H  
14.0  
16.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Starting current  
A
kW  
A
0.29  
0.033  
0.43  
0.32  
0.038  
0.48  
0.42  
0.050  
0.62  
0.42  
0.050  
0.62  
0.78  
0.091  
1.17  
0.84  
0.110  
1.25  
Unit appearance  
White (Munsell 10Y 9.3/0.4)  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
210  
910  
680  
22  
210  
910  
680  
22  
210  
1180  
680  
26  
210  
1180  
680  
26  
210  
1595  
680  
34  
210  
1595  
680  
34  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
30  
30  
40  
40  
80  
80  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
200  
167  
150  
217  
183  
150  
308  
250  
233  
308  
250  
233  
458  
383  
333  
500  
433  
367  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
720  
780  
1110  
1110  
1650  
1800  
600  
660  
900  
900  
1380  
1560  
540  
540  
840  
840  
1200  
1320  
Sound power level (high/medium/low)  
48/45/43  
35/32/30  
49/46/43  
36/33/30  
51/49/46  
38/36/33  
51/49/46  
38/36/33  
54/51/48  
41/38/35  
56/53/50  
43/40/37  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Room thermostat  
Connection pipes  
Standard long-life filter supplied  
Remote controller  
Supplied  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
in  
1/2  
1/4  
3/4  
1/2  
1/4  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
High-wall units (1 Series)  
Model MMK-AP  
Cooling capacity*  
Heating capacity  
Electrical data  
Power supply  
Operating current  
Power input  
Starting current  
Unit appearance  
Suction grille and side panel  
Discharge grille  
Bottom surface  
Unit dimensions  
Height  
0071H  
2.2  
2.5  
0091H  
2.8  
3.2  
0121H  
3.6  
4.0  
0151H  
4.5  
5.0  
0181H  
5.6  
6.3  
0241H  
7.1  
8.0  
kW  
kW  
V-ph-Hz  
A
kW  
A
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
0.30  
0.035  
0.36  
0.30  
0.035  
0.36  
0.30  
0.035  
0.36  
0.32  
0.037  
0.42  
0.32  
0.037  
0.42  
0.35  
0.040  
0.47  
Silky mist (Munsell 1Y 8.9/0.5)  
City grey (Munsell N6.5)  
Silky mist (Munsell 1Y 8.9/0.5)  
mm  
mm  
mm  
kg  
368  
895  
210  
18  
368  
895  
210  
18  
368  
895  
210  
18  
368  
1055  
210  
19  
368  
1055  
210  
19  
368  
1430  
210  
25  
Width  
Depth  
Unit weight  
Heat exchanger  
Sound proofing/heat insulating material  
Fan type  
Finned tube  
Non-flammable insulation  
Tangential fan  
Fan motor power input  
Air flow  
W
30  
30  
30  
30  
30  
30  
High  
Medium  
Low  
l/s  
l/s  
l/s  
167  
150  
133  
167  
150  
133  
167  
150  
133  
217  
183  
167  
217  
183  
167  
333  
283  
250  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
600  
600  
600  
780  
780  
1200  
540  
540  
540  
660  
660  
1020  
480  
480  
480  
600  
600  
900  
Sound power level (high/medium/low)  
52/47/44  
39/34/31  
52/47/44  
39/34/31  
52/47/44  
39/34/31  
55/51/48  
42/38/35  
55/51/48  
42/38/35  
55/51/48  
42/38/35  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Standard single filter supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
in  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
1/2  
1/4  
3/4  
1/2  
1/4  
3/4  
5/8  
3/8  
3/4  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
High-wall units (2 Series)  
Model MMK-AP  
Cooling capacity*  
Heating capacity  
0072H  
2,2  
2,5  
0092H  
2,8  
3,2  
0122H  
3,6  
4,0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Starting current  
A
kW  
A
0,17  
0,017  
0,22  
0,18  
0,018  
0,23  
0,19  
0,019  
0,24  
Unit appearance  
Suction grille and side panel  
Discharge grille  
Bottom surface  
Moon white  
Moon white  
Moon white  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
275  
790  
208  
11  
275  
790  
208  
11  
275  
790  
208  
11  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Fan motor power input  
Non-flammable insulation  
Tangential fan  
30  
W
30  
30  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
133  
117  
100  
142  
125  
100  
150  
125  
100  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
dB(A)  
480  
510  
540  
420  
450  
450  
360  
360  
360  
Sound power level (high/medium/low)  
Sound pressure level (high/medium/low)**  
Air filter  
48/45/42  
35/32/29  
49/46/42  
36/33/29  
50/46/42  
37/33/29  
Standard single filter supplied  
Remote controller  
Controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
mm  
3/8  
1/4  
16  
3/8  
1/4  
16  
3/8  
1/4  
16  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Floor-mounted console units  
Model MML-AP  
Cooling capacity*  
Heating capacity  
0071H  
2.2  
2.5  
0091H  
2.8  
3.2  
0121H  
3.6  
4.0  
0151H  
4.5  
5.0  
0181H  
5.6  
6.3  
0241H  
7.1  
8.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.26  
0.056  
94  
0.26  
0.056  
94  
0.43  
0.092  
93  
0.43  
0.092  
93  
0.47  
0.102  
94  
0.47  
0.102  
94  
kW  
%
A
0.60  
0.60  
0.80  
0.80  
1.10  
1.10  
Unit appearance  
Silky shade (Munsell 1Y 8.5/0.5)  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
630  
950  
230  
37  
630  
950  
230  
37  
630  
950  
230  
37  
630  
950  
230  
37  
630  
950  
230  
40  
630  
950  
230  
40  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
45  
45  
45  
45  
70  
70  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
133  
117  
100  
133  
117  
100  
250  
217  
181  
250  
217  
181  
300  
258  
217  
300  
258  
217  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
480  
480  
900  
900  
1080  
1080  
420  
420  
780  
780  
930  
930  
360  
360  
650  
650  
780  
780  
Sound power level (high/medium/low)  
52/50/48  
39/37/35  
52/50/48  
39/37/35  
58/54/51  
45/41/38  
58/54/51  
45/41/38  
62/57/52  
49/44/39  
62/57/52  
49/44/39  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Standard single filter supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia (polyvinyl tube)  
in  
in  
in  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
1/2  
1/4  
3/4  
1/2  
1/4  
3/4  
5/8  
3/8  
3/4  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Concealed chassis units  
Model MML-AP  
Cooling capacity*  
Heating capacity  
0071BH  
2.2  
2.5  
0091BH  
2.8  
3.2  
0121BH  
3.6  
4.0  
0151BH  
4.5  
5.0  
0181BH  
5.6  
6.3  
0241BH  
7.1  
8.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.25  
0.056  
97  
0.25  
0.056  
97  
0.25  
0.056  
97  
0.45  
0.090  
87  
0.45  
0.090  
87  
0.46  
0.095  
90  
kW  
%
A
0.60  
0.60  
0.60  
0.80  
0.80  
1.00  
Unit appearance  
Zinc hot dipping steel plate  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
600  
745  
220  
21  
600  
745  
220  
21  
600  
745  
220  
21  
600  
1045  
220  
29  
600  
1045  
220  
29  
600  
1045  
220  
29  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
19  
19  
19  
70  
70  
70  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
128  
111  
83  
128  
111  
83  
128  
111  
83  
206  
167  
136  
206  
167  
136  
264  
220  
178  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
kPa  
460  
460  
460  
740  
740  
950  
400  
400  
400  
600  
600  
790  
300  
300  
300  
490  
490  
640  
Static pressure  
0
0
0
0
0
0
Sound power level (high/medium/low)  
Sound pressure level (high/medium/low)** dB(A)  
dB(A)  
49/47/45  
36/34/32  
49/47/45  
36/34/32  
49/47/45  
36/34/32  
49/47/45  
36/34/32  
49/47/45  
36/34/32  
55/50/46  
42/37/33  
Air filter  
Controller  
Standard single filter supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia.***  
in  
in  
in  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
3/8  
1/4  
3/4  
1/2  
1/4  
3/4  
1/2  
1/4  
3/4  
5/8  
3/8  
3/4  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
***  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
Male screw connection one side.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor units  
Floor-mounted cabinet units  
Model MMF-AP  
Cooling capacity*  
Heating capacity  
0151H  
4.5  
5.0  
0181H  
5.6  
6.3  
0241H  
7.1  
8.0  
0271H  
8.0  
9.0  
0361H  
11.2  
12.5  
0481H  
14.0  
16.0  
0561H  
16.0  
18.0  
kW  
kW  
Electrical data  
Power supply  
V-ph-Hz  
230-1-50 (voltage range 220-240 V) - power supply to indoor unit only  
Operating current  
Power input  
Power factor  
Starting current  
A
0.67  
0.150  
97  
0.67  
0.150  
97  
0.88  
0.190  
94  
0.88  
0.190  
94  
1.29  
0.280  
94  
1.60  
0.350  
95  
1.60  
0.350  
95  
kW  
%
A
0.90  
0.90  
1.10  
1.10  
1.70  
2.10  
2.10  
Unit appearance  
W: Silky shade (1Y 8.5/0.5)  
Unit dimensions  
Height  
Width  
Depth  
Unit weight  
mm  
mm  
mm  
kg  
1750  
600  
210  
1750  
600  
210  
48  
1750  
600  
210  
49  
1750  
600  
210  
49  
1750  
600  
390  
65  
1750  
600  
390  
65  
1750  
600  
390  
65  
48  
Heat exchanger  
Finned tube  
Sound proofing/heat insulating material  
Fan type  
Non-flammable insulation  
Centrifugal fan  
Fan motor power input  
W
37  
37  
63  
63  
110  
160  
160  
Air flow  
High  
Medium  
Low  
l/s  
l/s  
l/s  
250  
217  
183  
250  
217  
183  
333  
283  
233  
333  
283  
233  
533  
467  
383  
600  
517  
433  
600  
517  
433  
Air flow  
High  
Medium  
Low  
m3/h  
m3/h  
m3/h  
dB(A)  
900  
900  
1200  
1200  
1920  
2160  
2160  
780  
780  
1020  
1020  
1680  
1860  
1860  
660  
660  
840  
840  
1380  
1560  
1560  
Sound power level (high/medium/low)  
59/56/51  
46/43/38  
59/56/51  
46/43/38  
62/58/53  
49/45/40  
62/58/53  
49/45/40  
64/61/57  
51/48/44  
67/63/59  
54/50/46  
67/63/59  
54/50/46  
Sound pressure level (high/medium/low)** dB(A)  
Air filter  
Controller  
Standard single filter supplied  
Remote controller  
Connection pipes  
Gas connection diameter  
Liquid connection diameter  
Drain connection, nom. dia***  
in  
in  
in  
1/2  
1/4  
3/4  
1/2  
1/4  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
5/8  
3/8  
3/4  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
*
Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main  
piping and 2.5 m of branch piping connected with 0 metre height.  
**  
***  
The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating  
environment become larger than the indicated values due to the effects of external sound.  
Male screw connection one side  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units  
Rating  
hp  
5
6
8
10  
12  
Cooling only model MMY  
Heat pump model MMY  
Outdoor unit type  
Cooling capacity  
MAP0501T8  
MAP0501HT8  
Inverter  
14.0  
MAP0601T8  
MAP0601HT8  
Inverter  
16.0  
MAP0801T8  
MAP0801HT8  
Inverter  
22.4  
MAP1001T8  
MAP1001HT8  
Inverter  
28.0  
MAP1201T8  
MAP1201HT8  
Inverter  
33.5  
kW  
Heating capacity  
kW  
16.0  
18.0  
25.0  
31.5  
37.5  
Power supply  
Voltage range  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
V-ph-Hz  
V
kW  
%
400-3-50 ± 10%  
380-415  
3.65  
90  
5.85  
400-3-50 ± 10%  
380-415  
4.64  
92  
7.28  
400-3-50 ± 10% 400-3-50 ± 10% 400-3-50 ± 10%  
380-415  
5.67  
95  
380-415  
7.68  
96  
380-415  
11.92  
94  
A
8.62  
3.95  
1.0  
11.55  
3.65  
1.0  
18.30  
2.81  
1.0  
kW/kW  
A
3.84  
1.0  
3.45  
1.0  
Starting current  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
3.84  
91  
6.09  
4.17  
4.56  
93  
7.08  
3.95  
5.88  
95  
8.93  
4.25  
1.0  
7.97  
96  
11.98  
3.95  
1.0  
10.19  
94  
15.65  
3.68  
1.0  
Starting current  
1.0  
1.0  
Unit appearance  
Silky shade (Munsell 1Y8.5/0.5)  
Dimensions  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
227  
228  
Finned type  
68  
55  
Propeller  
0.6  
1800  
990  
750  
227  
228  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
Motor power input  
Air flow  
Compressor type  
Motor power input  
Refrigerant charge R-410A*  
Cooling  
kg  
dB(A)  
dB(A) at 1 m  
69  
56  
70  
57  
71  
58  
72  
59  
Propeller  
0.6  
2500 - 9000  
Hermetic  
1.4 x 2  
Propeller  
0.6  
2750 - 9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917 - 10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917 - 10500  
Hermetic  
4.2 x 2  
kW  
l/s - m3/h  
2500 - 9000  
Hermetic  
1.1 x 2  
kW  
kg  
kg  
8.0  
8.5  
8.0  
8.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Heating  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Flare - 5/8  
Flare - 3/8  
Flare - 3/8  
175  
Brazed - 3/4  
Flare - 3/8  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 1-1/8  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
40/50  
300  
40/50  
300  
40/50  
300  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
8
10  
13  
16  
20  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
14  
16  
18  
20  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply  
AP1401T8  
AP1401HT8  
Inverter  
AP1601T8  
AP1601HT8  
Inverter  
AP1801T8  
AP1801HT8  
Inverter  
AP2001T8  
AP2001HT8  
Inverter  
Inverter  
0601T8  
0601HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1001T8  
1001HT8  
0801T8  
0801T8  
1001T8  
1001T8  
0801HT8  
38.4  
43.0  
0801HT8  
45.0  
50.0  
1001HT8  
50.4  
56.5  
1001HT8  
56.0  
63.0  
kW  
kW  
V-ph-Hz  
400-3-50 ± 10%  
400-3-50 ± 10%  
400-3-50 ± 10%  
400-3-50 ± 10%  
Voltage range  
V
kW  
%
A
kW/kW  
A
380-415  
11.12  
94  
17.08  
3.45  
1.0  
380-415  
12.20  
95  
18.54  
3.69  
1.0  
380-415  
14.16  
96  
21.29  
3.56  
1.0  
380-415  
16.17  
96  
24.31  
3.46  
1.0  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
Starting current  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
10.96  
94  
16.83  
3.92  
1.0  
12.28  
95  
18.65  
4.07  
1.0  
14.37  
96  
21.61  
3.93  
1.0  
16.46  
96  
24.75  
3.83  
1.0  
Starting current  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
227  
228  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
72.5  
dB(A)  
73  
60  
73.5  
60.5  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
74  
61  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
dB(A) at 1 m 59.5  
Propeller  
0.6  
Propeller  
0.6  
2500  
9000  
Hermetic  
1.4 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2750  
9900  
Hermetic  
2.3 x 2  
m3/h  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
8.0  
8.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8 Brazed - 3/4 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8  
Flare - 1/2 Flare - 3/8  
Flare - 3/8 Flare - 3/8  
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8  
175  
175  
175  
175  
175  
175  
175  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
23  
27  
30  
33  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
22  
22  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply  
AP2201T8  
AP2201HT8  
Inverter  
AP2211T8  
AP2211HT8  
Inverter  
Inverter  
0801T8  
0801HT8  
Inverter  
0601T8  
0601HT8  
Inverter  
1001T8  
1001HT8  
0801T8  
1201T8  
0801HT8  
61.5  
69.0  
400-3-50 ± 10%  
380-415  
17.39  
95  
26.42  
3.54  
1201HT8  
61.5  
69.0  
400-3-50 ± 10%  
380-415  
20.41  
95  
31.01  
3.01  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50 ± 10%  
380-415  
400-3-50 ± 10%  
380-415  
400-3-50 ± 10%  
380-415  
Voltage range  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
17.35  
95  
26.36  
3.98  
18.68  
95  
28.38  
3.69  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
227  
228  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
74.5  
dB(A)  
74.5  
61.5  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 61.5  
Propeller  
0.6  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2500  
9000  
Hermetic  
1.4 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2750  
9900  
Hermetic  
2.3 x 2  
m3/h  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
8.0  
8.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 3/4  
Flare - 3/8  
Flare - 3/8  
175  
Brazed - 1-1/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
40/50  
300  
40/50  
300  
40/50  
300  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
37  
37  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
24  
24  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply  
AP2401T8  
AP2401HT8  
Inverter  
AP2411T8  
AP2411HT8  
Inverter  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1201T8  
1201HT8  
0801T8  
1201T8  
0801HT8  
68.0  
76.5  
400-3-50 ± 10%  
380-415  
18.44  
96  
27.73  
3.69  
1201HT8  
68.0  
76.5  
400-3-50 ± 10%  
380-415  
25.02  
95  
38.02  
2.72  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50 ± 10%  
380-415  
400-3-50 ± 10%  
380-415  
400-3-50 ± 10%  
380-415  
Voltage range  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
18.79  
97  
27.96  
4.07  
21.32  
96  
32.06  
3.59  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
75.0  
dB(A)  
75.0  
62.0  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 62.0  
Propeller  
0.6  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Motor power input  
Air flow  
kW  
l/s  
2750  
9900  
Hermetic  
2.3 x 2  
m3/h  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed - 1-1/8  
Flare - 1/2  
Flare - 3/8  
175  
Brazed -1-1/8  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
40/50  
300  
40/50  
300  
40/50  
300  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
40  
40  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
26  
28  
30  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP2601T8  
AP2601HT8  
Inverter Inverter  
AP2801T8  
AP2801HT8  
Inverter  
AP3001T8  
AP3001HT8  
Inverter  
Inverter  
Inverter  
Inverter  
Inverter  
Inverter  
1001T8 0801T8  
0801T8  
1001T8  
1001T8  
0801T8  
1001T8  
1001T8  
1001T8  
1001HT8 0801HT8 0801HT8 1001HT8 1001HT8 0801HT8 1001HT8 1001HT8 1001HT8  
73.0  
81.5  
400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50  
380-415 380-415 380-415 380-415  
20.29  
96  
30.51  
3.60  
1.0  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
78.5  
88.0  
84.0  
95.0  
380-415  
380-415  
380-415  
24.26  
96  
380-415  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
22.27  
96  
33.48  
3.52  
1.0  
36.48  
3.46  
1.0  
kW/kW  
A
Starting current  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
20.51  
95  
31.16  
3.97  
22.60  
96  
33.98  
3.89  
1.0  
24.82  
97  
36.93  
3.83  
1.0  
Starting current  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
75.0  
dB(A)  
dB(A) at 1 m 62.0  
75.5  
62.5  
76.0  
63.0  
Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller  
0.6  
2917  
10500  
Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
0.6  
2750  
9900  
0.6  
2750  
9900  
0.6  
2917  
10500  
0.6  
2917  
10500  
0.6  
2750  
9900  
0.6  
2917  
10500  
0.6  
2917  
10500  
m3/h  
Compressor type  
Motor power input  
kW  
2.3 x 2  
2.3 x 2  
3.1 x 2  
3.1 x 2  
2.3 x 2  
3.1 x 2  
3.1 x 2  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8  
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
175  
175  
175  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
43  
47  
48  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
32  
32  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP3201T8  
AP3201HT8  
Inverter  
AP3211T8  
AP3211HT8  
Inverter  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
0801T8  
1201T8  
0801HT8  
90.0  
1201HT8  
90.0  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
100.0  
400-3-50  
380-415  
24.41  
95  
100.0  
400-3-50  
380-415  
28.65  
96  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
37.09  
3.69  
43.08  
3.14  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
24.56  
95  
37.32  
4.07  
26.78  
95  
40.69  
3.73  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
258  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
76.0  
dB(A)  
76.0  
63.0  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 63.0  
Propeller  
0.6  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2750  
9900  
Hermetic  
2.3 x 2  
m3/h  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 7/8 Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
48  
48  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
34  
34  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP3401T8  
AP3401HT8  
Inverter  
AP3411T8  
AP3411HT8  
Inverter  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1001T8  
1001HT8  
1001T8  
1201T8  
1001HT8  
96.0  
1201HT8  
96.0  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
108.0  
400-3-50  
380-415  
26.53  
96  
108.0  
400-3-50  
380-415  
33.08  
95  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
39.89  
3.62  
50.26  
2.90  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
27.03  
97  
40.22  
4.00  
29.54  
96  
44.42  
3.66  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
76.5  
dB(A)  
76.5  
63.5  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 63.5  
Propeller  
0.6  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2917  
m3/h  
10500  
Hermetic  
3.1 x 2  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
48  
48  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-20 to 16 wb -20 to 16 wb  
-5 to 43 db  
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
36  
36  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP3601T8  
AP3601HT8  
Inverter  
AP3611T8  
AP3611HT8  
Inverter  
Inverter  
1001T8  
1001HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1201T8  
1201HT8  
1001T8  
1201T8  
1001HT8  
101.0  
113.0  
400-3-50  
380-415  
28.38  
96  
1201HT8  
101.0  
113.0  
400-3-50  
380-415  
37.16  
94  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
42.67  
3.56  
57.06  
2.72  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
28.74  
96  
43.21  
3.93  
31.49  
94  
48.36  
3.59  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
76.5  
dB(A)  
77.0  
64.0  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 63.5  
Propeller  
0.6  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Motor power input  
Air flow  
kW  
l/s  
2917  
m3/h  
10500  
Hermetic  
3.1 x 2  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 1-1/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
48  
48  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db  
-5 to 43 db -5 to 43 db  
-5 to 43 db  
-20 to 16 wb  
-5 to 43 db  
-20 to 16 wb  
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
38  
40  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP3801T8  
AP3801HT8  
Inverter  
AP4001T8  
AP4001HT8  
Inverter  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
0801T8  
0801HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
1001T8  
1001T8  
1001HT8  
106.5  
119.5  
400-3-50  
380-415  
30.36  
96  
1001HT8  
112.0  
126.5  
400-3-50  
380-415  
32.34  
96  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
45.65  
3.51  
48.63  
3.46  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
30.83  
96  
46.36  
3.88  
33.05  
96  
49.69  
3.83  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
77.0  
dB(A)  
77.0  
64.0  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
dB(A) at 1 m 64.0  
Propeller  
0.6  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2750  
9900  
Hermetic  
2.3 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2917  
m3/h  
10500  
Hermetic  
3.1 x 2  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
in  
in  
in  
m
m
m
m
Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2 Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8 Flare - 3/8  
Flare - 1/2  
Flare - 3/8  
175  
175  
175  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Central remote controller  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
Max. number of connectable indoor units  
48  
48  
High-pressure switch  
Protection devices  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db -5 to 43 db -5 to 43 db 5 to 43 db  
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
-5 to 43 db -5 to 43 db 5 to 43 db  
-5 to 43 db  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
42  
44  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP4201T8  
AP4201HT8  
Inverter  
AP4401T8  
AP4401HT8  
Inverter  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1001T8  
1001HT8  
1201T8  
1201T8  
1201HT8  
118.0  
132.0  
400-3-50  
380-415  
36.74  
96  
1201HT8  
123.5  
138.5  
400-3-50  
380-415  
40.99  
95  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
55.24  
3.21  
62.28  
3.01  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
35.14  
95  
53.39  
3.76  
37.36  
95  
56.76  
3.69  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
77.5  
dB(A)  
77.5  
64.5  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 64.5  
Propeller  
0.6  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Motor power input  
Air flow  
kW  
l/s  
2917  
m3/h  
10500  
Hermetic  
4.2 x 2  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Maximum lift - indoor unit above/below***  
Control wiring  
Central remote controller  
Max. number of connectable indoor units  
High-pressure switch  
Protection devices  
in  
in  
in  
m
m
m
m
Brazed - 1-1/8Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 1-1/8Brazed - 1-1/8Brazed - 7/8 Brazed - 7/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8  
175  
175  
175  
175  
175  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
300  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
48  
48  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db  
-5 to 43 db -5 to 43 db 5 to 43 db -5 to 43 db  
-5 to 43 db  
5 to 43 db -5 to 43 db  
-20 to 16 wb -20 to 16 wb-20 to 16 wb-20 to 16 wb-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor units (combination)  
Rating  
hp  
46  
48  
Cooling only system MMY  
Heat pump system MMY  
Outdoor unit type  
Outdoor unit combination  
cooling only MMY-MAP  
Outdoor unit combination  
heat pump MMY-MAP  
Cooling capacity  
Heating capacity  
Power supply ± 10%  
Voltage range  
AP4601T8  
AP4601HT8  
Inverter  
AP4801T8  
AP4801HT8  
Inverter  
Inverter  
1201T8  
1201HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1001T8  
1001HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1201T8  
1201HT8  
Inverter  
1201T8  
1201HT8  
1201T8  
1201T8  
1201HT8  
130.0  
145.0  
400-3-50  
380-415  
45.59  
95  
1201HT8  
135.0  
150.0  
400-3-50  
380-415  
49.67  
95  
kW  
kW  
V-ph-Hz  
V
kW  
%
A
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
400-3-50  
380-415  
Power input, cooling  
Power factor, cooling  
Operating current, cooling  
EER, cooling  
69.27  
2.85  
75.47  
2.72  
kW/kW  
Starting current  
A
1.0  
1.0  
Power input, heating  
Power factor, heating  
Operating current, heating  
COP, heating  
kW  
%
A
kW/kW  
A
39.85  
95  
60.55  
3.64  
41.80  
94  
64.19  
3.59  
Starting current  
1.0  
1.0  
Unit appearance  
Dimensions  
Silky shade (Munsell 1Y8.5/0.5)  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
1800  
990  
750  
256  
258  
Total weight - cooling only unit  
Total weight - heat pump unit  
Heat exchanger  
Sound power level  
Sound pressure level  
Fan type  
kg  
Finned type  
78.0  
dB(A)  
78.0  
65.0  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
dB(A) at 1 m 65.0  
Propeller  
0.6  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
3.1 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Propeller  
0.6  
2917  
10500  
Hermetic  
4.2 x 2  
Motor power input  
Air flow  
kW  
l/s  
2917  
m3/h  
10500  
Hermetic  
4.2 x 2  
Compressor type  
Motor power input  
kW  
Refrigerant charge R-410A*  
Cooling  
Heating  
kg  
kg  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
11.0  
12.5  
Pipework**  
Suction line type - diameter  
Liquid line type - diameter  
Balance pipe type - diameter  
Maximum equivalent length separation  
Maximum actual piping length  
Maximum total piping length  
Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 7/8  
Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 1-1/8 Brazed - 1-1/8  
in  
in  
m
m
m
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2 Flare - 1/2  
Flare - 3/8 Flare - 3/8  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
Flare - 1/2  
Flare - 3/8  
175  
175  
175  
150 (if equivalent bend length is longer, equivalent length is standard)  
300  
300  
300  
300  
300  
300  
300  
300  
Maximum lift - indoor unit above/below***m  
Control wiring  
Central remote controller  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
40/50  
Shielded wire 1.25 mm2 x 2 cores up to 2000 m  
Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m  
Max. number of connectable indoor units  
48  
48  
High-pressure switch  
Protection devices  
MPa  
Off: 2.90/On: 3.73  
Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,  
high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,  
overcurrent relay  
Operating range, cooling†  
Operating range, heating†  
°C  
°C  
-5 to 43 db -5 to 43 db -5 to 43 db 5 to 43 db  
-20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb -20 to 16 wb  
-5 to 43 db -5 to 43 db 5 to 43 db  
-5 to 43 db  
Rated conditions:  
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db  
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb  
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.  
*
The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.  
The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.  
If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.  
Please refer to page 24.  
**  
***  
†
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. Fan characteristics  
In case of square duct flange of discharge section  
MMD-AP0121BH  
MMD-AP0071BH, AP0091BH  
Standard air flow 133 l/s (480 m3/h)  
Standard air flow 158 l/s (570 m3/h)  
Air flow, m3/h  
Air flow, m3/h  
Air flow, l/s  
Air flow, l/s  
MMD-AP0151BH  
MMD-AP0181BH  
Standard air flow 181 l/s (650 m3/h)  
Standard air flow 217 l/s(780 m3/h)  
Air flow, m3/h  
Air flow, l/s  
Air flow, m3/h  
Air flow, l/s  
Legend  
6.  
7.  
8.  
9.  
Application limit  
Lower air flow limit  
Upper air flow limit  
Long life filter  
1.  
2.  
3.  
4.  
5.  
High static pressure 2H tap  
High static pressure 1H tap  
Standard H tap  
Low static pressure H tap  
Standard L tap  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MMD-AP0301BH  
MMD-AP0241BH, AP0271BH  
Standard air flow 317 l/s (1140 m3/h)  
Standard air flow 350 l/s (1260 m3/h)  
Air flow, m3/h  
Air flow, l/s  
Air flow, m3/h  
Air flow, l/s  
MMD-AP0361BH  
MMD-AP0481BH, AP0561BH  
Standard air flow 450 l/s (1620 m3/h)  
Standard air flow 550 l/s (1980 m3/h)  
Air flow, m3/h  
Air flow, l/s  
Air flow, m3/h  
Air flow, l/s  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
High static pressure 2H tap  
High static pressure 1H tap  
Standard H tap  
Low static pressure H tap  
Standard L tap  
Application limit  
Lower air flow limit  
Upper air flow limit  
Long life filter  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High-pressure ducted unit  
MMD-AP0241H, AP0271H  
MMD-AP0181H  
Standard air flow 250 l/s (900 m3/h)  
Standard air flow 367 l/s (1320 m3/h)  
Air flow, m3/h  
Air flow, l/s  
Air flow, m3/h  
Air flow, l/s  
MMD-AP0481H  
MMD-AP0361H  
Standard air flow 583 l/s (2100 m3/h)  
Standard air flow 444 l/s (1600 m3/h)  
Air flow, m3/h  
Air flow, l/s  
Air flow, m3/h  
Air flow, l/s  
Legend  
1.  
2.  
3.  
4.  
5.  
High static pressure tap  
Medium static pressure tap  
Low static pressure tap  
Lower air flow limit  
Upper air flow limit  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MMD-AP0961H  
MMD-AP0721H  
Standard air flow 1000 l/s (3600 m3/h)  
Standard air flow 1167 l/s (4200 m3/h)  
Air flow, m3/h  
Air flow, m3/h  
Air flow, l/s  
Upper air flow limit  
Air flow, l/s  
Lower air flow limit  
Lower air flow limit  
Upper air flow limit  
1.  
2.  
3.  
High static pressure tap  
Medium static pressure tap  
Low static pressure tap  
Add an air flow damper to the air supply duct, and adjust the air flow in the range from 80% to 120% of the  
standard air flow rate.  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Slim duct unit  
MMD-AP0121SPH  
MMD-AP0071SPH, AP0091SPH  
Standard air flow 167 l/s (600 m3/h)  
Standard air flow 150 l/s (540 m3/h)  
60  
50  
40  
30  
20  
10  
0
60  
2
2
1
1
50  
3
5
4
8
4
40  
3
7
6
9
#
6
9
7
30  
8
@
5
20  
0
!
!
0
@
#
10  
$
$
%
%
0
300  
300  
400  
500  
600  
700  
400  
111  
500  
Air flow, m3/h  
167  
600  
700  
194  
Air flow, m3/h  
111  
139  
167  
194  
83  
83  
139  
Air flow, l/s  
Air flow, l/s  
MMD-AP0181SPH  
Standard air flow 217 l/s (780 m3/h)  
Standard air flow 192 l/s (690 m3/h)  
MMD-AP0151SPH  
60  
60  
2
1
2
1
50  
50  
4
4
3
3
40  
30  
20  
10  
0
40  
7
7
6
30  
5
6
8
8
5
9
20  
9
!
!
$
0
0
@
@
#
#
10  
%
%
$
0
400  
400  
500  
139  
600  
700  
194  
800  
222  
500  
139  
600  
167  
700  
800  
900  
250  
Air flow, m3/h  
Air flow, m3/h  
194  
222  
167  
111  
111  
Air flow, l/s  
Air flow, l/s  
Legend  
8.  
9.  
High (20 Pa)  
Low (35 Pa)  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Upper limit of external static pressure (50 Pa)  
High (50 Pa)  
Upper limit of external static pressure (35 Pa)  
High (35 Pa)  
Upper limit of external static pressure (20 Pa)  
Low (50 Pa)  
10. Upper limit of external static pressure (10 Pa)  
11. Upper limit of external static pressure (35 Pa)  
12. High (10 Pa)  
13. Low (20 Pa)  
14. Lower limit of external static pressure (20 Pa)  
15. Low (10 Pa)  
Lower limit of external static pressure (50 Pa)  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Slim duct unit - with filter attached  
MMD-AP0071SPH, AP0091SPH  
MMD-AP0121SPH  
Standard air flow 167 l/s (600 m3/h)  
Standard air flow 150 l/s (540 m3/h)  
60  
60  
50  
40  
30  
20  
2
2
1
1
50  
7
7
!
$
3
4
4
40  
3
6
6
!
30  
20  
5
8
@
8
5
9
#
9
#
0
$
^
0
@
10  
0
10  
0
%
^
%
300  
400  
500  
600  
167  
700  
194  
300  
400  
111  
500  
600  
700  
194  
Air flow, m3/h  
Air flow, m3/h  
167  
Air flow, l/s  
111  
139  
83  
139  
83  
Air flow, l/s  
MMD-AP0151SPH  
MMD-AP0181SPH  
Standard air flow 192 l/s (690 m3/h)  
Standard air flow 217 l/s (780 m3/h)  
60  
60  
2
2
1
1
50  
50  
7
3
4
7
4
3
40  
40  
!
!
$
6
30  
30  
5
6
9
8
8
5
9
20  
20  
$
0
0
@
@
#
10  
10  
#
%
%
^
^
0
0
400  
500  
139  
600  
700  
194  
800  
222  
400  
500  
139  
600  
700  
800  
222  
900  
250  
Air flow, m3/h  
Air flow, m3/h  
167  
194  
111  
167  
111  
Air flow, l/s  
Air flow, l/s  
8.  
9.  
High (20 Pa)  
Low (35 Pa)  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Upper limit of external static pressure (50 Pa)  
High (50 Pa)  
Upper limit of external static pressure (35 Pa)  
High (35 Pa)  
Upper limit of external static pressure (20 Pa)  
Low (50 Pa)  
10. Upper limit of external static pressure (10 Pa)  
11. Upper limit of external static pressure (35 Pa)  
12. High (10 Pa)  
13. Low (20 Pa)  
14. Lower limit of external static pressure (20 Pa)  
15. Low (10 Pa)  
Lower limit of external static pressure (50 Pa)  
16. Standard ļ¬lter pressure loss  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Dimensional drawings  
Indoor unit - 4-way ceiling cassette  
MMU-AP0091H to P0561H  
Model  
AP0091H-AP0301H  
AP0361H-AP0561H  
A
250  
319  
B
120  
183  
Drain riser pipe size  
Z view  
Note: As ABS is used for the drain  
discharge of the main unit, the vinyl  
chloride paste cannot be used. Use  
the flexible hose included in the  
package.  
Space required for installation and servicing  
Wired remote controller (RBC-AMT31E)  
9.  
For square branch duct knockout Ƙ150 (2 positions at right side)  
Legend  
10. Drain connection  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Control box  
Hanging bolt pitch  
Overall panel dimension  
Air inlet  
Air outlet (4-way)  
Ceiling opening  
Hanging bolt M10 or W3/8 field-supplied  
Bottom ceiling surface  
11. Refrigerant pipe connection (gas)  
12. Refrigerant pipe connection (liquid)  
13. Indoor unit  
14. Riser  
15. Knockout for simple outdoor air for Ćø100  
16. Inspection hole  
All dimensions are given in mm.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - 2-way ceiling cassette  
MMU-AP0071WH, AP0091WH, AP0121WH  
Z view  
Space required for installation and servicing  
11. Obstruction  
Legend  
12. Hanging bolt 4-M10 field-supplied  
13. Ceiling panel field-supplied  
14. Branch duct knockout hole (also on the reverse side)  
15. Bottom ceiling surface  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Centre of main unit  
Centre of panel  
Control box  
Hanging bolt pitch  
Unit dimension  
Ceiling opening  
Overall panel dimension  
Air outlet (2-way)  
Air inlet (2-way)  
16. Indoor unit  
17. Refrigerant pipe connection (liquid Ƙ1/4ā€)  
18. Refrigerant pipe connection (gas Ƙ3/8ā€)  
19. Drain pipe connection (inner Ƙ32, nominal Ƙ25) for vinyl chloride pipe  
20. Drain test point  
21. Knockout hole for air intake (only on reverse side)  
22. Power supply connection  
10. Ceiling  
All dimensions are given in mm.  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - 2-way ceiling cassette  
MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH  
Z view  
ļ‚„
Space required for installation and servicing  
Model  
ƘA  
ƘB  
MMU-AP0151WH to AP0181WH  
MMU-AP0241WH to AP0301WH  
1/4ā€  
3/8ā€  
1/2ā€  
5/8ā€  
12. Hanging bolt 4-M10 field-supplied  
13. Ceiling panel field-supplied  
14. Branch duct knockout hole (also on the reverse side)  
15. Bottom ceiling surface  
16. Refrigerant pipe connection (liquid ƘA)  
17. Refrigerant pipe connection (gas ƘB)  
18. Drain pipe connection (inner Ƙ32, nominal Ƙ25) for vinyl chloride pipe  
19. Drain test point  
20. Knockout hole for air intake (only on reverse side)  
21. Power supply connection  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Centre of main unit  
Centre of panel  
Control box  
Hanging bolt pitch  
Unit dimension  
Ceiling opening  
Overall panel dimension  
Air outlet (2-way)  
Air inlet (2-way)  
10. Ceiling  
11. Obstruction  
All dimensions are given in mm.  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - 2-way ceiling cassette  
MMU-AP0481WH  
Z view  
Space required for installation and servicing  
Wired remote controller (RBC-AMT31E)  
12. Hanging bolt 4-M10 field-supplied  
13. Ceiling panel field-supplied  
14. Branch duct knockout hole (also on the reverse side)  
15. Bottom ceiling surface  
16. Refrigerant pipe connection (liquid Ƙ3/8ā€)  
17. Refrigerant pipe connection (gas Ƙ5/8ā€)  
18. Drain pipe connection (VP25)  
19. Drain test point  
20. Knockout hole for air intake (only on reverse side)  
21. Power supply connection  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Centre of main unit  
Centre of panel  
Control box  
Hanging bolt pitch  
Unit dimension  
Ceiling opening  
Overall panel dimension  
Air outlet (2-way)  
Air inlet (2-way)  
10. Ceiling  
11. Obstruction  
All dimensions are given in mm.  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - 1-way ceiling cassette  
MMU-AP0071YH, AP0091YH, AP0121YH  
Model MMU-  
A
B
C
AP0071YH, AP0091YH, AP0121YH  
235  
245  
200  
Wired remote controller (RBC-AMT31E)  
Space required for installation and servicing  
Legend  
8.  
9.  
Hanging bolt 4-M10 field-supplied  
Ceiling panel field-supplied  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Overall panel dimension  
Ceiling opening  
Centre of panel  
Power supply connection  
Drain pipe connection (VP25)  
Refrigerant pipe connection (gas Ƙ3/8ā€)  
Refrigerant pipe connection (liquid Ƙ1/4ā€)  
10. Bottom ceiling surface  
11. Support metal  
12. Panel mounting hole 5 positions  
13. Discharge louvre  
14. Air outlet  
15. Air inlet  
All dimensions are given in mm.  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - 1-way ceiling cassette  
MMU-AP0151SH, AP0181SH, AP0241SH  
Z view  
Model MMU-  
AP0151SH, AP0181SH  
AP0241SH  
A
1220  
1420  
B
1160  
1360  
C
545  
645  
D
485  
585  
E
530  
630  
F
470  
570  
G
254  
460  
H
800  
1000  
ƘI  
1/4ā€  
3/8ā€  
ƘJ  
1/2ā€  
5/8ā€  
N
4
5
Space required for installation and servicing  
Wired remote controller (RBC-AMT31E)  
Legend  
8.  
9.  
Knockout for front discharge  
Power supply connection  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Ƙ150 knockout hole (for air intake)  
Overall panel dimension  
Ceiling opening  
Centre of panel  
Air inlet  
10. Refrigerant pipe connection (gas ƘJ)  
11. Refrigerant pipe connection (liquid ƘI)  
12. Drain pipe connection (VP25)  
13. Ceiling  
Air outlet  
Pitch 200 x N  
14. Obstruction  
All dimensions are given in mm.  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - standard ducted unit  
MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH, AP0271BH,  
AP0301BH, AP0361BH, AP0481BH, AP0561BH  
Model MMD-  
A
B
C
D
E
ƘF  
ƘG  
AP0071BH, AP0091BH, AP0121BH  
AP0151BH, AP0181BH  
AP0241BH, AP0271BH, AP0301BH  
AP0361BH, AP0481BH, AP0561BH  
616  
766  
1066  
1416  
550  
700  
1000  
1350  
350  
500  
800  
1150  
600  
750  
1050  
1400  
470  
620  
920  
1270  
3/8ā€  
1/2ā€  
5/8ā€  
5/8ā€  
1/4ā€  
3/8ā€  
3/8ā€  
3/8ā€  
Note: High-efficiency and deodorant filters cannot be used together.  
Note: Be sure to provide an inspection hole A in the position indicated in the following figure for maintenance of the equipment.  
Drain riser pipe  
Legend  
11. Panel CL  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Ƙ125 knockout hole (for air intake)  
10-Ƙ4 tapping screw Ƙ160  
When attaching directly  
Hanging bolt pitch  
Hanging bolt 4-M10 (field-supplied)  
Ceiling opening  
Drain pipe connection (inner Ƙ32 vinyl chloride pipe VP25 connection)  
Unit dimension  
Hanging bolt pitch  
12. Ceiling opening  
13. Ƙ26 power supply, remote controller cable conduit  
14. Refrigerant pipe connection (liquid ƘG)  
15. Air outlet  
16. Refrigerant pipe connection (gas ƘF)  
17. Inspection hole A  
18. For air filter maintenance  
19. Air ļ¬lter  
20. Inspection hole B  
10. Air inlet  
All dimensions are given in mm.  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - high-pressure ducted unit  
MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0271H, AP0961H  
MMD-AP0181H to AP0361H  
MMD-AP0481H  
Z view  
Z view  
Z view  
Space required for installation and servicing *1  
Models AP0181H-AP0271H  
Model AP0361H  
Model MMD-  
A
B
AP0181H  
1/4ā€  
1/2ā€  
AP0241H, AP0271H, AP0361H, AP0481H  
3/8ā€  
5/8ā€  
MMD-AP0271H, AP0961H  
*1  
Service spaces for MMD-AP0721H and AP0961H are different from  
those in the above figure. For enquiries please contact us separately.  
Wired remote controller (RBC-AMT31E)  
11. Air outlet  
Legend  
12. Refrigerant pipe connection (gas Ƙ5/8ā€)  
13. Refrigerant pipe connection (liquid Ƙ3/8ā€)  
14. Screw hole for duct mounting (8-M6)  
15. Inspection area  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Power supply/communication piping (Ƙ26) (under control box)  
Hanging bolt slot (4-Ƙ2 x 72)  
Hanging bolt mounting pitch  
Control box  
Refrigerant pipe connection (gas ƘB)  
Refrigerant pipe connection (liquid ƘA)  
Air inlet  
16. Service space  
17. Refrigerant pipe connection (gas Ƙ7/8ā€)  
18. Refrigerant pipe connection (liquid Ƙ1/2ā€)  
19. Screw hole for duct mounting (10-M6)  
Screw hole for duct mounting (6-M6)  
Drain pipe connection (VP25)  
10. Screw hole for duct mounting (4-M6)  
All dimensions are given in mm.  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - slim duct unit  
MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH  
Bottom view complete with filter  
845  
21  
803  
21  
1
3
103  
2
31  
805  
910  
59  
80  
33  
163  
6
4
5
Bottom view excluding filter  
845  
803  
21  
21  
1
7
3
103  
31  
805  
910  
80 59  
33  
163  
6
4
5
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Inside dimension  
Air filter  
Refrigerant pipe connection  
Drain pipe connection  
Hanging plate  
Fresh air inlet (knockout hole)  
Drain pipe  
All dimensions are given in mm.  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - ceiling-suspended unit  
MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H  
Model MMC-  
A
B
ƘC  
ƘD  
AP0151H, AP0181H 910  
AP0241H to AP0271H1180  
AP0361H, AP0481H 1595  
855  
1125  
1540  
1/2ā€  
5/8ā€  
5/8ā€  
1/4ā€  
3/8ā€  
3/8ā€  
Space required for installation and servicing  
Front side must be level.  
Wired remote controller (RBC-AMT31E)  
10. Drain pipe connection (Inner diameter Ƙ26, hose attached)  
11. Wireless sensor mounting section (option)  
12. Hanging bolt  
13. Ceiling surface  
14. Unit  
15. Remote controller cable conduit  
16. Piping hole in the wall (Ƙ100 hole)  
17. Air inlet (duct sold separately) (knockout hole Ƙ92)  
18. Left drain piping conduit (knockout hole)  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Hanging position  
Remote controller cable conduit (knockout hole)  
Power supply cable inlet (knockout hole)  
Upper cable conduit (knockout hole)  
Drain pipe connection  
Refrigerant pipe connection (gas ƘC)  
Refrigerant pipe connection (liquid ƘD)  
Left side drain  
Cable conduit (knockout hole)  
All dimensions are given in mm.  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - high-wall unit (1 Series)  
MMK-AP0071H, AP0091H, AP0121H  
Position of installation board hole  
Space required for service  
Wired remote controller (RBC-AMT31E)  
9.  
Drain pipe  
Legend  
10. Supplied with pipe outlet left  
11. Including installation board  
1.  
2.  
3.  
4.  
5.  
(Installation board)  
Top of installation board  
Wood screw slot 15-6 x 30  
Anchor bolt slot 10-10 x 20  
Air outlet  
Air flow direction adjustable (up/down/left/right)  
Air inlet  
12. Including installation board (accessory)  
13. Earth screw (M4) (inside control box)  
14. Refrigerant pipe connection (gas Ƙ3/8ā€)  
15. Refrigerant pipe connection (liquid Ƙ1/4ā€)  
16. Drain pipe connection  
6.  
7.  
8.  
17. Pipe outlet left/right side (knockout hole)  
Gas pipe  
Liquid pipe  
All dimensions are given in mm.  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - high-wall unit (1 Series)  
MMK-AP0151H, AP0181H  
Position of installation board hole  
Space required for service  
9.  
Drain pipe  
Legend  
10. Supplied with pipe outlet left  
11. Including installation board  
1.  
2.  
3.  
4.  
5.  
(Installation board)  
Top of installation board  
Wood screw slot 15-6 x 30  
Anchor bolt slot 10-10 x 20  
Air outlet  
Air flow direction adjustable (up/down/left/right)  
Air inlet  
Gas pipe  
12. Including installation board (accessory)  
13. Earth screw (M4) (inside control box)  
14. Refrigerant pipe connection (gas Ƙ1/2ā€)  
15. Refrigerant pipe connection (liquid Ƙ1/4ā€)  
16. Drain pipe connection  
6.  
7.  
8.  
17. Pipe outlet left/right side (knockout hole)  
Liquid pipe  
All dimensions are given in mm.  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - high-wall unit (1 Series)  
MMK-AP0241H  
Position of installation board hole  
Space required for service  
9.  
Drain pipe  
Legend  
10. Supplied with pipe outlet left  
11. Including installation board  
1.  
2.  
3.  
4.  
5.  
(Installation board)  
Top of installation board  
Wood screw slot 21-6 x 30  
Anchor bolt slot 16-10 x 20  
Air outlet  
Air flow direction adjustable (up/down/left/right)  
Air inlet  
12. Including installation board (accessory)  
13. Earth screw (M4) (inside control box)  
14. Refrigerant pipe connection (gas Ƙ5/8ā€)  
15. Refrigerant pipe connection (liquid Ƙ3/8ā€)  
16. Drain pipe connection  
6.  
7.  
8.  
17. Pipe outlet left/right side (knockout hole)  
Gas pipe  
Liquid pipe  
All dimensions are given in mm.  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - high-wall unit (2 Series)  
MMK-AP0072H, AP0092H, AP0122H  
Space required for service  
max. 100 mm  
max. 170 mm  
max. 170 mm  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Air inlet  
Air outlet  
Knockout hole  
Hook for insulation plate  
Refrigerant pipe connection (gas Ƙ3/8ā€)  
Drain pipe connection  
Refrigerant pipe connection (liquid Ƙ1/4ā€)  
All dimensions are given in mm.  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - floor-mounted console unit  
MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H  
(left side)  
Model MML-  
ƘA  
ƘB  
AP0071H, AP0091H, AP0121H  
AP0151H, AP0181H  
AP0241H  
3/8ā€  
1/2ā€  
5/8ā€  
1/4ā€  
1/4ā€  
3/8ā€  
Space required for service  
Figure shows left-hand piping  
Pipe position diagram  
8.  
9.  
Earth screw M6  
Hole for wall fixing (Ƙ10-Ƙ20 knockout x 2)  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Hole for floor fixing (2-Ƙ10)  
10. Hole for wall fixing (2-10 x 24 slot)  
11. Refrigerant pipe connection (Ƙ130 knockout hole)  
12. Drain pipe connection (Ƙ20)  
13. Refrigerant pipe connection (gas ƘA)  
14. Refrigerant pipe connection (liquid ƘB)  
15. Wall  
Lower refrigerant pipe connection (50 x 100 knockout hole)  
Switch section (switch sold separately)  
Air outlet  
Air inlet  
Refrigerant pipe connection (50 x 100 knockout hole) (both sides)  
Power supply cord (Ƙ26 knockout) (both sides)  
16. Front  
All dimensions are given in mm.  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - concealed chassis unit  
MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH  
No. Name  
Model MML-  
A
B
C
D
4
7
7
ƘE  
ƘF  
G
5
8
8
AP0071BH, AP0091BH, AP0121BH  
AP0151BH, AP0181H  
AP0241BH  
610  
910  
910  
580  
880  
880  
550  
850  
850  
1/4ā€  
1/4ā€  
3/8ā€  
3/8ā€  
1/2ā€  
5/8ā€  
0
!
@
#
$
Pipe connection (liquid side ƘE)  
Pipe connection (gas side ƘF  
Drain pipe connection (20A)  
Control box (earth terminal provided inside)  
Air filter  
Wired remote controller (RBC-AMT31E)  
5.  
6.  
7.  
8.  
9.  
G-Ƙ4.7 hole (front and rear each)  
4-Ƙ15 hole (for rear mounting)  
2-Ƙ4.7 hole (left/right side each)  
2-12 x 18 slot (hole for floor fixing)  
Expansion valve box  
Legend  
1.  
2.  
3.  
4.  
Hole for floor fixing  
Service space  
Air outlet  
Ceiling board  
All dimensions are given in mm.  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - floor-mounted cabinet unit  
MMF-AP0151H, AP0181H, AP0241H, AP0271H  
Space required for service  
(for right-hand piping)  
Front  
Refrigerant pipe positions  
Model  
ƘA  
ƘB  
MMF-AP0151H, AP0181H  
MMF-AP0241H, AP0271H  
1/2ā€  
5/8ā€  
1/4ā€  
3/8ā€  
Details of hole for bottom piping  
Details of hole for rear piping  
10. Earth screw M4  
Legend  
11. Refrigerant pipe connection (both sides) (Ƙ80 knockout hole)  
12. Control panel  
13. Panel cover  
14. 2-lower hole (for M8 screw or M8 anchor bolt)  
15. Ƙ130 knockout hole (for rear piping)  
16. Refrigerant pipe connection (gas ƘA)  
17. Refrigerant pipe connection (liquid ƘB)  
18. 4-lower hole (for M8 screw or M8 anchor bolt)  
19. 15 x 120 square hole (for bottom piping)  
20. Floor  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Wall  
With 50 mm wall clearance  
Lower refrigerant pipe connection (50 x 120 knockout hole)  
Installation plate  
Air outlet  
Air inlet  
Refrigerant pipe connection (rear) (Ƙ130 knockout hole)  
Drain hose  
Refrigerant pipe connection (bottom) (50 x 120 knockout hole)  
All dimensions are given in mm.  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit - floor-mounted cabinet unit  
MMF-AP0361H, AP0481H, AP0561H  
Space required for service  
(for right-hand piping)  
Front  
Refrigerant pipe positions  
Details of hole for bottom piping  
Details of hole for rear piping  
11. Refrigerant pipe connection (both sides) (Ƙ80 knockout hole)  
12. Control panel  
13. Panel cover  
14. 2-lower hole (for M8 screw or M8 anchor bolt)  
15. Ƙ130 knockout hole (for rear piping)  
16. Refrigerant pipe connection (gas Ƙ3/4ā€)  
17. Refrigerant pipe connection (liquid Ƙ3/8ā€)  
18. Liquid side  
Legend  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
Wall  
With 50 mm wall clearance  
Lower refrigerant pipe connection (50 x 120 knockout hole)  
Installation plate  
Air outlet  
Air inlet  
Refrigerant pipe connection (rear) (Ƙ130 knockout hole)  
Drain hose  
Refrigerant pipe connection (bottom) (50 x 120 knockout hole)  
19. Gas side  
20. 4-lower hole (for M8 screw or M8 anchor bolt)  
21. 50 x 120 square hole (for bottom piping)  
22. Floor  
10. Earth screw M4  
All dimensions are given in mm.  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Remote controller  
Wired remote controller  
RBC-AMT31E  
Simplified remote controller  
RBC-AS21E  
All dimensions are given in mm.  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wireless remote controller  
TCB-AX21U (W)-E  
Wireless remote controller kit  
RBC-AX22CE  
All dimensions are given in mm.  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wireless remote controller kit  
TCB-AX21E  
4.4 x 9.4 slot  
4.4 x 5.4 slot  
Weekly timer  
RBC-EXW21E  
All dimensions are given in mm.  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Central remote controller  
TCB-SC642TLE  
LON Gateway  
TCB-IFLN**  
200  
66  
64  
78  
78  
22  
22  
22  
22  
78  
78  
All dimensions are given in mm.  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TCS-Net relay interface  
BMS-IFLSV1E  
6 x 5.5 mounting hole  
Touch-screen controller  
BMS-TP5120ACE  
All dimensions are given in mm.  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Intelligent server  
BMS-LSV2E  
Energy monitoring relay interface  
BMS-IFWH3E  
6 x 5.5 mounting hole  
All dimensions are given in mm.  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Digital I/O relay interface  
BMS-IFDD01E  
6 x 5.5 mounting hole  
Windows-based central controller  
BMS-LSV**  
200  
(2.4)  
63.6  
6 – Ƙ5.5  
234  
22  
78  
78  
22  
220  
246  
All dimensions are given in mm.  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor module  
MMY-MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8,  
MMY-MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8,  
Notes:  
1.  
2.  
3.  
If there is an obstacle at the top of the outdoor unit, ensure that  
the top of the outdoor unit clears the obstacle by 2000 mm.  
Ensure that the height of obstacles around the outdoor unit  
does not exced 800 mm from the bottom of the outdoor unit.  
Draw out the field-supplied pipe to the front of the outdoor unit  
horizontally, and keep 500 mm or more between the outdoor  
unit and pipe if placing the pipe transversely.  
Model  
A
B
C
MMY-MAP0501T8, MAP0501HT8  
MMY-MAP0601T8, MAP0601HT8  
MMY-MAP0801T8, MAP0801HT8  
MMY-MAP1001T8, MAP1001HT8  
MMY-MAP1201T8, MAP1201HT8  
5/8ā€  
3/4ā€  
7/8ā€  
7/8ā€  
1-1/8ā€  
3/8ā€  
3/8ā€  
1/2ā€  
1/2ā€  
1/2ā€  
280  
280  
(205)  
(205)  
(205)  
*1  
Cutting position of L-shape pipe when pipe is connected at the gas side.  
(Recommended pipe connection position)  
Space required for service  
Front (for work and service)  
Front  
Front  
MMY-MAP0501T8  
MMY-MAP0601T8  
MMY-MAP0501HT8  
MMY-MAP0601HT8  
Front  
Details of front pipe/cabling holes  
Details of hole for bottom piping (plane view)  
Legend  
7.  
8.  
9.  
Refrigerant pipe connection (gas ƘA)  
Earthing section of bottom plate  
Base  
1.  
2.  
3.  
4.  
5.  
6.  
Anchor bolt pitch  
(including feet)  
4-15 x 20 (slot)  
2-60 x 150 square hole (for forklift truck)  
Balance pipe connection Ƙ3/8ā€  
Refrigerant pipe connection (liquid ƘB)  
10. Knockout for control wiring (Ƙ27)  
11. Knockout hole for power wiring (Ƙ48)  
12. Square hole  
All dimensions are given in mm.  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor module - Two units connected  
MMY-AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8,  
MMY-AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8,  
Notes:  
1.  
2.  
3.  
If there is an obstacle at the top of the outdoor unit, ensure that  
the top of the outdoor unit clears the obstacle by 2000 mm.  
Ensure that the height of obstacles around the outdoor unit  
does not exced 800 mm from the bottom of the outdoor unit.  
Draw out the field-supplied pipe to the front of the outdoor unit  
horizontally, and keep 500 mm or more between the outdoor  
unit and pipe if placing the pipe transversely.  
4.  
Arrange each outdoor unitin order of its capacity  
(Master unit ≄ slave unit)  
Unit combination  
Outdoor unit combination  
Master unit  
Slave unit  
MMY-AP1401T8, AP1401HT8  
MMY-AP1601T8, AP1601HT8  
MMY-AP1801T8, AP1801HT8  
MMY-AP2001T8, AP2001HT8  
MMY-AP2211T8, AP2211HT8  
MMY-AP2411T8, AP2411HT8  
MMY-MAP0801T8, MAP0801HT8  
MMY-MAP0801T8, MAP0801HT8  
MMY-MAP1001T8, MAP1001HT8  
MMY-MAP1001T8, MAP1001HT8  
MMY-MAP1201T8, MAP1201HT8  
MMY-MAP1201T8, MAP1201HT8  
MMY-MAP0601T8, MAP0601HT8  
MMY-MAP0801T8, MAP0801HT8  
MMY-MAP0801T8, MAP0801HT8  
MMY-MAP1001T8, MAP1001HT8  
MMY-MAP1001T8, MAP1001HT8  
MMY-MAP1201T8, MAP1201HT8  
Space required for service  
Front  
Front  
Front  
Front  
Front  
Front  
Front (For work and service)  
Legend  
1.  
2.  
3.  
Anchor bolt pitch  
(including feet)  
8-15 x 20 (slot)  
All dimensions are given in mm.  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor module - Three units connected  
MMY- AP2201T8, AP2401T8, AP2601T8, AP2801T8, AP3001T8, AP3211T8, AP3411T8,  
AP3611T8  
MMY- AP2201HT8, AP2401HT8, AP2601HT8, AP2801HT8, AP3001HT8,  
AP3211HT8, AP3411HT8, AP3611HT8  
Notes:  
1.  
2.  
3.  
If there is an obstacle at the top of the outdoor unit, ensure that  
the top of the outdoor unit clears the obstacle by 2000 mm.  
Ensure that the height of obstacles around the outdoor unit  
does not exced 800 mm from the bottom of the outdoor unit.  
Draw out the field-supplied pipe to the front of the outdoor unit  
horizontally, and keep 500 mm or more between the outdoor  
unit and pipe if placing the pipe transversely.  
4.  
Arrange each outdoor unitin order of its capacity  
(Master unit ≄ slave unit ≄ slave unit)  
Unit combination  
Outdoor unit combination  
Master unit  
Slave unit  
Slave unit  
MMY-AP2201T8, HT8  
MMY-AP2401T8, HT8  
MMY-AP2601T8, HT8  
MMY-AP2801T8, HT8  
MMY-AP3001T8, HT8  
MMY-AP3221T8, HT8  
MMY-AP3411T8, HT8  
MMY-AP3611T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP0601T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
Space required for service  
Front Front  
Front  
Front  
Front Front  
Front (For work and service)  
Front Front Front  
Legend  
1.  
2.  
3.  
Anchor bolt pitch  
(including feet)  
16-15 x 20 (slot)  
All dimensions are given in mm.  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor module - Four units connected  
MMY- AP3201T8, AP3401T8, AP3601T8, AP3801T8, AP4001T8, AP4201T8, AP4401T8,  
AP4601T8, AP4801T8  
MMY- AP3201HT8, AP3401HT8, AP3601HT8, AP3801HT8, AP4001HT8,  
AP4201HT8, AP4401HT8, AP4601HT8, AP4801HT8  
Unit combination  
Outdoor unit combination  
Master unit  
Slave unit  
Slave unit  
Slave unit  
MMY-AP3201T8, HT8  
MMY-AP3401T8, HT8  
MMY-AP3601T8, HT8  
MMY-AP3801T8, HT8  
MMY-AP4001T8, HT8  
MMY-AP4201T8, HT8  
MMY-AP4401T8, HT8  
MMY-AP4601T8, HT8  
MMY-AP4801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP1201T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP0801T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1001T8, HT8  
MMY-MAP1201T8, HT8  
Notes:  
Space required for service  
1.  
2.  
3.  
If there is an obstacle at the top of the  
outdoor unit, ensure that the top of  
the outdoor unit clears the obstacle by  
2000 mm.  
Ensure that the height of obstacles  
around the outdoor unit does not exced  
800 mm from the bottom of the outdoor  
unit.  
Draw out the field-supplied pipe to the  
front of the outdoor unit horizontally,  
and keep 500 mm or more between the  
outdoor unit and pipe if placing the pipe  
transversely.  
Front  
Front  
Front  
Front Front  
Front Front Front  
Front  
Front  
Front  
Front  
4.  
Arrange each outdoor unitin order of its  
capacity  
(Master unit ≄ slave unit ≄ slave unit ≄  
slave unit)  
Front (For work and service)  
Legend  
1.  
2.  
3.  
Anchor bolt pitch  
(including feet)  
16-15 x 20 (slot)  
All dimensions are given in mm.  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Branch header/branch joint  
Branch header  
RBM-HY1043E, HY1083E, HY2043E,HY2083E  
Gas side  
Insulation  
Liquid side  
Insulation  
Model  
A
B
C
ƘD  
ƘE  
n
3
3
7
7
3
3
7
7
Accessory socket x quantity  
6 x 4, 9 x 4, $ x 1, * x 1, ; x 1  
1 x 4, 6 x 1, 9 x 1  
RBM-HY1043E  
Gas side  
380  
360  
700  
680  
385,5  
360  
705,5  
680  
90  
83,6  
7/8ā€  
5/8ā€  
7/8ā€  
5/8ā€  
1-1/4ā€  
5/8ā€  
1-1/4ā€  
5/8ā€  
5/8ā€  
3/8ā€  
5/8ā€  
3/8ā€  
5/8ā€  
3/8ā€  
5/8ā€  
3/8ā€  
Liquid side  
Gas side  
60  
-
RBM-HY1083E  
RBM-HY2043E  
RBM-HY2083E  
90  
83,6  
6 x 8, 9 x 8, $ x 1, * x 1, ; x 1  
1 x 8, 6 x 1, 9 x 1  
Liquid side  
Gas side  
60  
-
95,5  
60  
89,3  
6 x 2, 9 x 2, u x 1, O x 1  
1 x 2  
Liquid side  
Gas side  
-
95,5  
60  
89,3  
-
6 x 7, 9 x 7, u x 1, O x 1  
1 x 7  
Liquid side  
T-shape branching joint  
RBM-BT13E  
Gas side  
Liquid side  
Balance pipe  
Accessory socket x quantity  
a x 1, s x 1, A x 2, D x 2, F x 1  
$ x 2, * x 1, b x 2, n x 1  
Gas side  
Liquid side  
All dimensions are given in mm, except where indicated.  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Y-shape branching joint  
RBM-BY53E, BY103E  
Gas side  
Liquid side  
Insulation  
Insulation  
RBM-BY203E, BY303E  
Gas side  
Liquid side  
Insulation  
Insulation  
Model  
A
B
ƘC  
ƘD  
Accessory socket x quantity  
RBM-BY53E  
RBM-BY103E  
RBM-BY203E  
RBM-BY303E  
Gas side  
250  
200  
350  
250  
350  
250  
400  
350  
80  
70  
80  
80  
80  
80  
110  
80  
5/8ā€  
1/2ā€  
7/8ā€  
5/8ā€  
1-1/4ā€  
5/8ā€  
1-1/2ā€  
7/8ā€  
1/2ā€  
3/8ā€  
3/4ā€  
1/2ā€  
1-1/8ā€  
5/8ā€  
1-1/2ā€  
3/4ā€  
5 x 2, R x 2, 9 x 1, Q x 1  
Liquid side  
Gas side  
1 x 2, 5 x 1  
7 x 1, 0 x 1, # x 2, * x 1, W x 2, ; x 1, . x 1  
2 x 1, 5 x 2, 6 x 1, 9 x 1, R x 1  
^ x 1, ) x 1, u x 1, e x 2, i x 1, o x 1, I x 1, O x 1  
3 x 1, 6 x 1, 9 x 2  
Liquid side  
Gas side  
Liquid side  
Gas side  
a x 3, s x 2, A x 2, D x 1, F x 1, G x 1, H x 1, J x 1  
4 x 1, 7 x 1, 0 x 1, # x 2, $ x 1, * x 1, W x 1  
Liquid side  
All dimensions are given in mm, except where indicated.  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Accessory socket  
Outside diameter  
Outside diameter  
Outside diameter  
Outside diameter  
Outside diameter  
Outside diameter  
Outside diameter  
Outside diameter  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Toshiba Air Conditioning  
United Technologies House  
Guildford Road  
Leatherhead  
Surrey  
KT22 9UT  
Customer Response Centre: 0870 843 0333  
E-mail: general.enquiries@toshiba-ac.com  
www.toshiba-aircon.co.uk  
Specifications are subject to change without notice.  
Printed in the Netherlands on chlorine-free paper  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson Stereo Receiver DPL5000 User Manual
Thecus Technology Computer Drive N299 User Manual
Tiger Games 70 153 User Manual
Toro Utility Trailer 3040 User Manual
Toshiba Copier GA 1120 User Manual
TRENDnet Network Hardware TPE113GI User Manual
Tripp Lite Network Cables N002 001 GY User Manual
Tripp Lite TV Cables EZA VGAX 2 User Manual
Verizon Cell Phone PSW2260VW2 User Manual
ViewSonic Car Video System VS15197 User Manual