Therma Stor Products Group Dehumidifier XT150H User Manual

INSTALLER’S & OWNER’S MANUAL  
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER  
P/N 4026480 • Serial No.___________________________  
Fresh Air Ventilation  
Dehumidification  
The highly efficient Ultra-Aire XT150H dehumidifier utilizes  
refrigeration to cool the incoming air stream below its dew point.  
This cooled and drier air is used to pre-cool the incoming air stream  
resulting in a significant increase in overall efficiency. After the pre-  
cooling stage, the processed air is reheated by passing through the  
condenser coil. The heat removed by the evaporator coil is returned  
to the air stream, resulting in an overall temperature increase of the  
air leaving the unit.  
Optional fresh outdoor air may be ducted to the unit via a six inch  
round duct. This provides fresh air to dilute pollutants and maintain  
high oxygen content in the air. The amount of fresh air ventilation  
can be regulated by a variety of dampers and controls.  
Air Filtration  
The Ultra-Aire XT150H includes air filtration to improve indoor air  
quality. A MERV-11 media filter is standard. An optional external  
MERV-14 deep pleated 95% media filter is available for optimum air  
filtration and to reduce potentially harmful airborne particles. If the  
optional filter is chosen, a standard filter operates as a prefilter.  
The Ultra-Aire XT150H is controlled by 24 volt remote wired controls.  
A variety of controls are available suitable to various applications.  
P.O. Box 8680 Madison, WI 53708 TOLL-FREE 1-800-533-7533 www.thermastor.com [email protected]  
© 2007 Therma-Stor LLC • Manual P/N TS-372, 8/07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY PRECAUTIONS  
1. Safety Precautions  
Read the installation, operation and maintenance instructions  
carefully before installing and operating this device. Proper  
adherence to these instructions is essential to obtain maximum  
benefit from your Ultra-Aire XT150H indoor air quality system.  
READ AND SAVE THESE INSTRUCTIONS  
• The device is designed to be installed INDOORS IN A SPACE THAT  
IS PROTECTED FROM RAIN AND FLOODING.  
• Install the unit with space to access the back or side panels  
for maintenance and service. DO NOT INSTALL UNIT WITH THE  
SERVICE PANELS INACCESSIBLE.  
• Avoid directing the discharge air at people, or over the water in  
pool areas.  
• If used near a pool or spa; be certain there is NO chance the unit  
could fall into the water, be splashed and that it is plugged into a  
GFI GROUND FAULT INTERRUPT OUTLET.  
• DO NOT use the device as a bench or table.  
• DO NOT place the device directly on structural members. Provide  
vibration isolation in order to minimize operational vibration  
and/or noise.  
• A drain pan MUST be placed under the unit if installed above a  
living area or above an area where water leakage could cause  
damage  
3
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Place the Ultra-Aire XT150H on supports that raise the base of  
the unit above the top of the flanges on the drain pan beneath it.  
Raising the Ultra-Aire XT150H will help the unit drain with gravity  
flow. Do not place the Ultra-Aire XT150H directly on structural  
building members without vibration absorbers or unwanted noise  
may result.  
1. Intended Application for Ultra-Aire XT150H  
For the ideal installation, draw air from the central part of the home  
and return it to isolated areas of the home like the bedrooms, den,  
utility room, or family room. The ductwork of the existing heating  
system can be used to supply air to the home.  
2. Specifications  
The Ultra-Aire XT150H may be suspended with steel hanger straps  
(plumbers tape) or a suitable alternative from structural members,  
unit must be supported from underneath. Don't hang from sides  
or ends. Remember to place a drain pan under the unit if it is  
suspended above a finished area or above an area where water  
leakage could cause damage.  
Model:  
Ultra-Aire XT150H  
Indoor Air Quality System  
Electrical:  
110-120 VAC, 6.9 Amps, 60 Hz,  
grounded  
Water Removal Capacity: 150 pints/day @ 80°F, 60% RH  
Operating Temp. Range:  
Air Flow:  
56°F min., 100°F max.  
415 CFM @ 0.0" WG  
365 @ 0.4" WG  
The Ultra-Aire XT150H should be located near the existing air  
handling system to minimize the required ductwork for connecting  
the Ultra-Aire XT150H to the existing air handling system. The  
controls for the Ultra-Aire XT150H are remote from the unit and  
must be located in the space that is to be conditioned. The controls  
are low voltage (24 volt) and should be connected to the Ultra-Aire  
XT150H with low voltage thermostat cable.  
Refrigerant Charge:  
2 lb., R-410.A  
Duct connections:  
(ovaled)  
Round 10" & 6" inlets, 10" outlet  
Filter Size:  
2" X 16" X 16"  
If fresh air ventilation is desired, thought should be given to the  
location for the fresh air ducting. A 6" round insulated duct will  
have to be installed on the Ultra-Aire XT150H and run to the outside  
of the structure to bring in fresh air. Use an 8" insulated round duct  
for lengths of more than 50 feet or if more than 100 CFM is needed.  
Consult local codes for necessary distances from exhaust ports  
when installing fresh air return.  
Size (w/o duct collars):  
Unit Weight:  
37" wide X 22" high X 20 5/8" deep  
134 lbs.  
3. Installation  
3.1 Location  
The Ultra-Aire XT150H can be installed in a variety of locations  
to meet the owner's needs as listed below. In all cases keep the  
following cautions in mind:  
3.2 Electrical Requirements  
WARNING: DO NOT ALLOW THE YELLOW LEAD FROM THE  
ULTRA-AIRE TO CONTACT THE RED LEAD OR WHITE LEAD FROM  
THE ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER WILL  
RESULT.  
• It is designed to be installed INDOORS IN A SPACE THAT IS  
PROTECTED FROM RAIN AND FLOODING.  
• Install the unit with space to access the back and side panels for  
maintenance and service and also to allow easy access to the filter  
cover panel. DO NOT INSTALL UNIT WITH THE FRONT PANEL OR  
FILTER COVER PANEL INACCESSIBLE.  
The Ultra-Aire XT150H plugs into a common grounded outlet. It  
draws around 6.9 Amps under normal operating conditions. If used  
in a wet area (pool, spa room, or basement prone to flooding), a  
ground fault interrupter protected circuit is required.  
• Avoid discharging the air directly at people, or over the water in  
pool areas.  
Install the remote control panel in a central area of the structure  
where it will sense the relative humidity of the structure accurately.  
Do not install the control panel where it may not accurately sense  
the relative humidity such as near HVAC supply registers, near  
exterior doors, or near a pool or spa. The installer must supply the  
wiring between the Ultra-Aire XT150H and the control panel. Be  
sure to safely route the control wiring to prevent damage during  
installation. Be careful not to cross the wires when connecting the  
Ultra-Aire XT150H and the remote control panel or damage to the  
transformer may result.  
• If used near a pool or spa, be certain there is NO chance the unit  
could fall into the water or be splashed and that it is plugged into a  
GROUND FAULT INTERRUPTER.  
• DO NOT use the Ultra-Aire XT150H as a bench or table.  
• DO NOT place the Ultra-Aire XT150H directly on structural  
members. Provide vibration isolation in order to minimize  
operational vibration and/or noise.  
• A drain pan MUST be placed under the unit if installed above a  
living area or above an area where water leakage could cause  
damage.  
4
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
The remote controls of the Ultra-Aire XT150H are powered by a low  
voltage circuit (24 Vac) and must NEVER contact or be connected  
to a high voltage circuit. The control wires leaving the Ultra-Aire  
XT150H and the remote control panels are numbered and color-  
coded to prevent confusion. Some of the control wires leaving the  
Ultra-Aire XT150H may not be used with certain control panels and  
should be left safely disconnected with wire nuts taped onto the  
stripped ends. Be sure to consult the electrical schematic in this  
manual or inside the access panel of the Ultra-Aire XT150H before  
making the control connections.  
may draw air from a basement that is open to the home. All flexible  
ducting connected to the Ultra-Aire XT150H should be UL listed.  
The inlet of the Ultra-Aire XT150H is the 10" diameter hole in the  
filter enclosure of the unit. A 10" round collar is supplied with the  
unit to attach to round duct. The duct may be permanently attached  
to the collar. A 6" round collar is provided with the unit to attach to  
the 6" hole in the filter enclosure. The 6" collar should be capped  
if fresh make-up air is not desired. If fresh make-up air is desired,  
see Section 3.4C.  
A 10" round (ovaled) collar is supplied with the unit for the outlet of  
the Ultra-Aire XT150H.  
3.3 Condensate Water Removal  
Condensate drains by gravity via the drain port. Use 3/4" male NPT  
PVC pipe. Route drain pipe to drain. Install a trap if possible. Take  
care when installing drain pipe to drain port. Use an adjustable  
wrench to secure the drain port. An optional condensate pump kit  
may be installed if a lift is required to dispose of the condensate.  
The condensate pump kit can be ordered directly from the factory.  
See the optional parts list for information on the kit.  
A length of flexible ducting on all Ultra-Aire XT150H duct  
connections is recommended to reduce noise and vibration  
transmitted to rigid ductwork in the structure.  
Ducting the Ultra-Aire XT150H as mentioned in Sections 3.4A-3.4G  
requires consideration of the following points:  
Duct Sizing: For total duct lengths up to 25', use a minimum 10"  
diameter round or equivalent rectangular. For longer lengths, use a  
minimum 12" diameter or equivalent. Grills or diffusers on the duct  
ends must not excessively restrict airflow.  
External drain trap on unit  
is recommended  
Isolated Areas: Effective dehumidification may require that ducting  
be branched to isolated, stagnant areas. Use 8" or larger diameter  
branch ducting to each of two or three areas, use 6" or larger to  
each of four or more areas.  
1.00"  
Connecting to existing HVAC systems: An optional 10" check  
damper is available from the factory to prevent reverse flow  
through the Ultra-Aire XT150H. If the Ultra-Aire XT150H is ducted  
to the supply ducting air handler, it is recommended that the check  
damper be placed in the Ultra-Aire XT150H supply duct. Contact  
the factory when connecting to a static pressure of greater than or  
equal to +.5" WG.  
3.4 Ducting  
3.4A Installing Duct Collars  
The Ultra-Aire XT150H is equipped with 10" and 6" round inlet  
collars and a 10" round (ovaled) exhaust collar. Follow instructions  
included with collars.  
3.4B Ducting for Dehumidification  
For the ideal installation, draw air from the central part of the  
home and return it to the isolated areas of the home like the  
bedrooms, den, utility room, or family room. The ductwork of the  
existing heating system can be used to supply air to the home. If  
the existing supply goes to isolated areas of the home, discharge  
the supply of the Ultra-Aire XT150H into the supply of the existing  
heating system. If the existing heating system incorporates a  
central supply, installation of a separate supply duct from the Ultra-  
Aire XT150H to each isolated area is recommended. DO NOT draw  
air directly from the kitchen, laundry, or isolated basement. You  
5
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
3.4C Ducting for Fresh Air  
3.4D Installation in a Basement or Crawlspace  
with an Existing Forced Air HVAC System  
Fresh air can be brought into the structure by connecting an  
insulated duct from outside to the 6" Ultra-Aire XT150H inlet and  
by turning on the fan switch or activating the humidity control (on  
units with the humidity control panel). Activate the ventilation timer  
on units with the ventilating and humidity control panel to bring in  
fresh air. Refer to Section 4.5 for programming instructions for the  
ventilation timer. Advantages of this form of ventilation include:  
It is recommended that a new, separate return duct be installed for  
the Ultra-Aire XT150H from a central area of the house. If this is not  
possible, and if the existing system has multiple returns, select one  
to disconnect from the existing forced air system and use it for the  
dedicated Ultra-Aire XT150H return. Always select a return from a  
central location in the structure in an area that is always open to  
the rest of the structure. Do not use a return from a room that may  
have its door closed much of the time.  
1. Outside air is filtered before entering the building.  
2. Outside air will be dehumidified before entering if the Ultra-  
Aire XT150H is running in dehumidification mode.  
3. Drawing air from outside and blowing inside aids in slightly  
pressurizing the structure. This helps prevent dirty and humid  
air from entering elsewhere. It also reduces the potential for  
carcinogenic radon gas to enter and provides make-up air for  
open combustion and exhaust devices like the clothes drier,  
fireplace, and water heater.  
4. Adequate exhaust fans are recommended in the bath rooms  
and kitchen.  
In cold climates or areas where the outdoor dew point is low  
at times, ventilation can be used to dehumidify the structure.  
This is accomplished by bringing the dry, low dew point air into  
the structure during these times. This approach is often more  
economical than running the dehumidifier to remove excess  
moisture from the structure. In cold climates, it is critical to  
adequately ventilate to reduce the inside moisture content to  
avoid moisture accumulating in the wall cavities. For example; in a  
house that experiences condensation on the interior surface of the  
windows during the winter, increasing the amount of ventilation will  
often cure the problem.  
If the structure in which the Ultra-Aire XT150H is to be installed has  
an existing forced air HVAC system, utilize the HVAC system to make  
the Ultra-Aire XT150H installation easier.  
Basement Installation: Install a separate 10" return for the Ultra-  
Aire XT150H in a central area of the structure. Duct the supply of the  
Ultra-Aire XT150H to an optional 10" x 10" x 10" tee/damper that  
is 20% open to the basement. This allows the ability to discharge a  
variable amount of dehumidified air into a basement that may not  
be well served by the existing duct system. Duct the other side of  
the tee to the air supply of the existing HVAC system. A backdraft  
damper is required in the duct between the 10" tee and the central  
supply duct to prevent air from being discharged into the basement  
during central fan operation. Connect a duct from outside to the  
6" collar of the Ultra-Aire XT150H if you wish to provide fresh air  
ventilation.  
An insulated 6" diameter duct is generally sufficient to provide up  
to 125 CFM of outside air. Large quantities of outside air will either  
positively or negatively impact the performance of the Ultra-Aire  
XT150H, depending upon inside and outside air conditions. Consult  
the factory by calling 1-800-533-7533 for recommendations  
regarding the use of higher flows with your specific application.  
The outside air duct should be connected to the 6" round collar  
on the filter enclosure of the unit. The 6" round collar includes a  
manual damper. Adjust the manual damper to provide the desired  
amount of fresh air for ventilation. The amount of fresh air should  
be based on the size and occupancy of the residence. If you are  
unsure of your ventilation air requirements, consult the factory by  
calling 1-800-533-7533 for assistance.  
Crawl Space Installation: Install a separate return for the Ultra-  
Aire XT150H in a central area of the structure. Duct the supply of  
the Ultra-Aire XT150H to a 10" x 10" x 10" tee/damper that is 20%  
open to the crawl space if desired. Duct the other side of the tee  
to the air supply of the existing HVAC system ventilation. Connect  
an insulated duct from outside to the 6" collar of the Ultra-Aire  
XT150H if you wish to provide optional fresh air.  
6
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
from outside to the 6" collar of the Ultra-Aire XT150H if you wish to  
provide fresh air ventilation.  
3.4E Installation in an Attic with an  
Existing Forced Air HVAC System  
ALWAYS install a catch pan with a drain and/or float interrupt  
switch for condensate under the Ultra-Aire XT150H in an attic to  
reduce liklihood of water damage.  
3.5 Quiet Installation  
Consider compression vibration and airflow noise during  
installation. Use of flex duct and/or vibration isolation materials  
during mounting and ducting will result in quieter operation.  
Locate a separate return for the Ultra-Aire XT150H in a central  
area of the structure. Duct the supply of the Ultra-Aire XT150H to  
the air supply of the existing HVAC system. Connect an insulated  
duct from outside to the 6" collar of the Ultra-Aire XT150H if you  
wish to provide fresh air ventilation. Adjust damper in the collar  
to provide the desired amount of fresh air. Using a remote control,  
program the unit to bring in the desired amount of fresh air.  
3.6 Noise Abatement  
A length of flexible ducting on all Ultra-Aire XT150H duct  
connections is recommended to reduce noise and vibration  
transmitted to rigid ductwork in the structure.  
4. Controls  
All control panels should be mounted in a central area of the  
structure where it can accurately sense the humidity of the air in  
the living space and be accessed. All controls require field wiring  
from the unit location to the panel mount location.  
Figure 1:  
Humidity/Fan Control Panel  
Part No. 4024155  
Figure 2: Ventilation Timer  
and Humidity Control Panel  
Part No. 4024125  
To determine how each control operates the Ultra-Aire XT150H,  
it must first be determined which control is being used and  
whether or not the Ultra-Aire XT150H is ducted for fresh air  
ventilation. Refer to appropriate section.  
3.4F Installation in a Structure with  
Two Forced Air HVAC Systems  
The Ultra-Aire XT150H can be installed into two typical HVAC  
ducting systems. Install a separate return for the Ultra-Aire XT150H  
as directed above. Discharge air from the dehumidifier should be  
split and routed to each supply ducting system. A balancing damper  
and a backdraft damper is required in each duct between the Ultra-  
Aire XT150H and the HVAC ducting system. This allows airflow to  
be adjusted and prevents flow of air between the ducting systems.  
Contact the factory for assistance, if necessary.  
Humidity/Fan Control Panel (P/N 4024155) (Figure 1, p.7)  
4.1A  
4.1B  
4.1C  
Humidity/Fan Control Panel WITHOUT Fresh Air  
Ventilation or Damper  
Humidity/Fan Control Panel WITH Fresh Air  
Ventilation and WITHOUT Damper  
Humidity/Fan Control Panel WITH Fresh Air  
Ventilation AND Damper  
3.4G Installation in a Structure with No Existing  
Forced Air HVAC System  
When installing the Ultra-Aire XT150H in a structure that does not  
have a forced air HVAC system, a single return for the Ultra-Aire  
XT150H should be installed in central open area of the structure.  
DO NOT locate the return in a bathroom or a kitchen. The supply of  
the Ultra-Aire XT150H should be located in the remote areas of the  
structure (such as bedrooms, den, etc.). By ducting this way, the air  
inside the structure will circulate through the Ultra-Aire XT150H to  
be filtered and dehumidified. Avoid discharging all the air from the  
dehumidifier in one location to prevent heat build up in that area. 4"  
diameter duct is recommended for branches to the bedrooms, 6"  
diameter duct is recommended for branches to larger areas. Refer  
to section 3.4B for branch duct sizing. Connect an insulated duct  
7
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Ventilation Timer/Humidity Control Panel (P/N 4024125)  
(Figure 2, p.7)  
4.2 Humidity Control Adjustment  
Set the humidity control to the desired humidity level for the home.  
Turning the knob clockwise results in a drier setting. See the back  
of the control panel cover for set points.  
4.6D  
Ventilation Timer and Humidity Control WITH Fresh Air  
AND Motorized Damper  
The dehumidifier will run continuously until  
the relative humidity (RH) is reduced to the  
humidity control dial setting. Setting the  
humidity control to lower RH levels will NOT  
DEH 3000 Digital Control (P/N 4024539) (Figure 1, p.10)  
4.6E  
4.6F  
Digital Controller WITH Fresh Air AND Damper  
Digital Controller WITHOUT Fresh Air  
Figure 3:  
Humidity Control  
Adjustment Knob  
increase the dehumidification rate; the unit  
will simply run longer to reduce the RH to  
the setting. The Ultra-Aire XT150H unit (and  
4.1A Humidity/Fan Control Panel WITHOUT Fresh Air  
Ventilation or Damper  
The humidity/fan control panel automatically controls the humidity  
of the living space. The humidity/fan control panel contains an  
adjustable humidity control and a fan switch. The panel has a  
cover that must remain open to the air within the living space for  
accurate humidity sensing. When the fan switch is in the “ON”  
position, air will be continually filtered and circulated throughout  
the home. For humidity control operation refer to section 4.2.  
refrigerant-based dehumidifiers in general) will reduce a warm  
space’s RH to a lower level than that of a cool space. Therefore  
there is no benefit to set the humidity control to excessively  
low levels in cool rooms; doing so will result in long periods of  
ineffective dehumidifier run time. Settings below 45% are not  
recommended.  
4.3 Fan/Filter Switch  
4.1B Humidity/Fan Control Panel WITH Fresh Air  
Ventilation and WITHOUT Damper  
Turning ON the fan/filter switch will  
cause the Ultra-Aire XT150H fan to run  
continuously, whether the Ultra-Aire XT150H  
is dehumidifying or not. This function is  
desirable if the unit is used for air circulation  
The humidity/fan control panel automatically controls the humidity  
of the living space. The humidity/fan control panel contains an  
adjustable humidity control and a fan switch. The panel has a  
cover that must remain open to the air within the living space for  
accurate humidity sensing. Outside air is continually introduced  
whenever fan is “ON.” Manual operation of fan filter switch controls  
outside air ventilation. Since the fan operates whenever the Ultra-  
Aire XT150H is dehumidifying outside air will also be introduced.  
For humidity control operation refer to section 4.2.  
Figure 4  
Fan/Filter Switch  
and filtration to achieve maximum indoor air  
quality. When the switch is ON; air will be  
constantly filtered through the Ultra-Aire XT150H and circulated  
throughout the house. When the switch is OFF the fan will operate  
only when the humidity control calls for dehumidification or when  
the ventilation timer calls for ventilation.  
4.1C Humidity/Fan Control Panel WITH Fresh Air  
Ventilation AND Damper  
In this configuration, a motorized damper has been installed in the  
fresh air duct. When the fan/filter switch is in the “OFF” position,  
the damper is closed. The Ultra-Aire XT150H will then circulate and  
dehumidify air to provide humidity control.  
4.4 Ventilation Timer  
The ventilation timer controls the fan and the motorized fresh  
air damper. When the ventilation timer is activated, the Ultra-  
Aire XT150H will circulate the indoor air, and bring in fresh air  
from outside. The ventilation timer should be set for the required  
ventilation of the residence. The home should be ventilated with  
fresh air as suggested by applicable codes and standards or as  
required by the homeowner. The ventilation timer is an electronic  
timer that displays the current time. This timer has battery backup,  
so it will not require resetting after a power outage. Following  
a prolonged power outage the display of the timer will flash on  
and off indicating a power outage has occurred. The one-minute  
time increments of the ventilation timer allow you to program the  
ventilation of your home to fit your schedule.  
When the fan/filter switch is in the “ON” position, the motorized  
damper will open and the fan will run, introducing outside air. The  
unit may or may not be dehumidifying in the ventilation mode,  
depending on the humidity control setting. See Section 4.2 for  
humidity control operation.  
4.1D Ventilation Timer and Humidity Control WITH  
Fresh Air AND Motorized Damper  
Refer to sections 4.7 through 4.9C.  
4.1E DEH 3000 Digital Control WITH Fresh Air AND  
Damper  
Refer to Section 5.  
Humidity/Fan Control Panel  
P/N 4024155  
Ventilation Timer & Humidity  
Control Panel • P/N 4024125  
4.1F DEH 3000 Digital Control WITHOUT Fresh Air  
Refer to Section 5.  
8
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
The ventilation timer allows six programs with each program  
having one “ON” and one “OFF” event. A program allows the  
user to turn the ventilation on at a certain day and time, then it  
allows them to turn the ventilation off at a certain day and time.  
Each of these programs can be repeated daily or weekly or  
during a specified block of days. All six of the programs operate  
independently of each other. If the timer fails to operate or operates  
erratically, check that the control panel receives 24Vac from the  
Ultra-Aire XT150H. If 24Vac is present at the control panel, reset  
the timer by pressing the reset button at the bottom center of the  
timer face. The reset button is the small recessed button with an R  
beneath it located below the 1-7 and h buttons. Depress the reset  
button until the display clears. Release the reset button. The display  
will reappear as 00:00. Resetting the timer will clear the time and  
all program settings. After resetting the timer follow the instructions  
below to set the correct time and ventilation programs.  
4.4C Automatic or Manual Mode  
The slide switch in the upper left of the timer is used to choose  
between automatic and manual operation. When the slide switch  
is set to AUTO mode, the Ultra-Aire XT150H will ventilate when  
the scheduled programs call for ventilation. When the slide switch  
is set to manual (set to hand symbol on the right), the operation  
of the timer is controlled by the I/O button only. Pressing the I/O  
button will switch the ventilation timer between ON (detent) and  
OFF (detent). As you press the I/O button, “ON” or “OFF” will be  
displayed to the right of the time. The “ON” or “OFF” indicates if the  
ventilation timer is on or off. The I/O button will manually override  
scheduled programs if the timer is in AUTO mode.  
4.4A Setting the Time  
Set the correct time on the timer by sliding the switch in the upper  
right hand corner of the timer to the clock symbol. and pressing the  
1-7 (DAY), h (HOUR), and m (MINUTE) buttons. Remember this timer  
operates on a 24-hour (military time) clock.  
4.4B Ventilation Schedule  
Slide the switch in the upper right hand corner to the program  
symbol P. ON” will appear to the right of the time and the number  
“1” will appear in the lower right hand corner of the display. The  
“1” and “ON” signify the turn on time for the first program. Press  
the 1-7, h and m button to choose the days of the week for this  
program. You can choose Mon.-Sun., Mon.-Fri., Sat.-Sun., or any  
single day of the week. The days chosen are shown along the top  
of the display on the ventilation timer. Next press the h button to  
set the hour for the start of the ventilation period. Remember this  
timer operates on a 24-hour clock (military time). Then press the m  
button to set the minutes past the hour to start the ventilation.  
Now, with the ventilation start time set; press the I/O button. The  
word “OFF” should appear to the right of the time and the number  
“1” should remain in the lower right hand corner of the display. The  
“1” and “OFF” signify the turn off time for the first program. Set  
the turn off time using the 1-7, h and m buttons in the same way  
as described above and continue on to the second through sixth  
programs. When setting the ventilation programs, you can return  
to the current time display by sliding the switch in the upper right  
corner of the timer to RUN. The slide switch must be set to RUN for  
the timer to operate its scheduled programs.  
9
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ATTENTION INSTALLER  
WIRE THE UNIT AND CONTROL PACKAGE AS SHOWN IN THE DIAGRAM BELOW  
Humidity/Fan Control Panel  
Ventilation Timer/  
Humidity Control Panel  
DEH 3000 Digital Control  
UA Base Unit  
White  
DMP COMP FAN  
Control Part No. 4026570  
WARNING: DO NOT allow the yellow lead from the unit to contact the red lead or the white lead from the  
unit or damage to the transformers will result. Do not direct connect the white lead on the unit to the violet  
lead on the ventilation control or damage to the transformer will result.  
10  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
5. DEH 3000 Digital Control  
Installation Instructions  
Control Part No. 4026570  
5.1 Specifications  
Part # (P/N)  
Model:  
4026570  
DEH 3000 Digital Control  
24 VAC  
Electrical:  
Humidity Range:  
Humidity Accuracy:  
Output:  
Relay Capacity  
Temp Range/Accuracy  
Size  
10 – 95% RH  
+/- 5%  
3 Amps 24 VAC  
5 Amps  
2%  
4.95" wide x 4.19" high  
5.2B Wiring  
FOR HVAC INSTALLER ONLY:  
WARNING:  
DO NOT ALLOW THE YELLOW LEAD  
FROM THE ULTRA-AIRE TO CONTACT THE RED OR WHITE LEADS  
FROM THE ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER  
WILL RESULT  
5.2 Installation  
This control panel must be installed in the conditioned space  
and in accordance with all applicable codes and standards.  
Follow the instructions below when installing and setting this  
control.  
WARNING:  
UNPLUG ULTRA-AIRE BASE UNIT  
BEFORE WIRING CONTROL.  
5.2A Install Instructions  
The installer must supply the wiring between the Ultra-Aire  
and the control panel. Be sure to safely route the control wires  
to prevent damage during installation. Be careful not to cross  
the wires when connecting the Ultra-Aire and the remote  
control panel or damage to the transformer may result.  
1. Separate the front panel from the back panel by  
depressing the middle sections of the top and bottom of  
the front panel.  
2. Line the back panel up against the wall or flat surface  
onto which it is to be mounted and drill in the appropriate  
mounting holes.  
The remote control of the Ultra-Aire is powered by a low  
voltage circuit (24 VAC) and must NEVER contact or be  
connected to a high voltage circuit. Some of the control wires  
leaving the Ultra-Aire may not be used with certain control  
panels and should be left safely disconnected with wire nuts  
taped onto the stripped ends. Be sure to consult the electrical  
schematic in this manual or on the front panel of the Ultra-  
Aire before making the control connections.  
3. Insert the screws and tighten down so they extend  
approximately 1/8” from the back plate.  
4. Align the back panel so that the control is level.  
5. Tighten the screws to lock into position.  
6. Make the electrical connections to the terminals on the  
back panel as shown in the wiring diagram.  
7. Reassemble the front to the back panel. Connect at the top  
first, then at the bottom.  
8. Test connections (see Section 2.6)  
11  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER AND HOMEOWNER  
Engage the A/C central fan during dehumidification  
1. Disconnect the green wire that runs to the fan relay from the  
screw on the thermostat.  
2. Connect the green wire that runs to the fan relay to the COM  
screw on the DEH3000 board.  
3. Run a wire from the red wire screw on the thermostat to the NO  
(Normally Open) screw on the DEH3000 board.  
4. Run a wire from the green wire screw on the thermostat to the  
NC (Normally Closed) screw on the DEH3000 board.  
The central fan should run when the Thermostat fan switch  
is turned to ON and when the dehumidifier is operating.  
WARNING:  
TO AVOID TRANSFORMER DAMAGE ONLY  
CONNECT THE WHITE WIRE TO THE CONTROL IF A DAMPER IS  
USED.  
The white wire controls the optional motorized damper that  
can be installed into a fresh air duct. This provides the ability  
to control when fresh air is introduced into the building by  
using the ventilation timer function labeled “DMP” on the  
control (See Section 3.7). IF THE MOTORIZED DAMPER IS  
NOT USED, DO NOT CONNECT THE WHITE WIRE TO THE  
CONTROL OR DAMAGE TO THE TRANSFORMER MAY  
RESULT. Simply leave the (DMP) terminal unused if the  
damper is not used, and cap off the white lead from the Ultra-  
Aire dehumidifier.  
2.4 Dehumidifier lockout/activation:  
AC sensor feature  
The control has the ability to activate the dehumidifier or  
deactivate the dehumidifier when the air conditioner is running.  
2.3 Auxiliary relay operation  
At times it may be desirable to coordinate fan operation  
of the central heating/cooling system with dehumidifier  
operation. The DEH 3000 features a relay that provides  
this ability. The relay terminals labeled NC, COM and NO  
operate according to the following chart:  
Dehumidification  
Operation  
COM/NO  
CLOSED  
OPEN  
COM/NC  
OPEN  
Standard wire colors for thermostats are as follows:  
ON  
Description  
24VAC Return  
Call for Heat  
Force Fan On  
Color  
Red  
Terminal code  
OFF  
CLOSED  
R
White  
Green  
W or W1  
G
Common uses (assuming standard thermostat wiring color  
schemes as noted):  
Compressor  
Call for Cooling  
Disengage A/C during dehumidification  
Redirect the yellow thermostat wire to the NC terminal. Wire  
Yellow  
Y or Y1  
the yellow wire from the A/C to the COM terminal.  
12  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
After connections have been verified, this short test will  
confirm proper wiring.  
1. Install front cover of control; insert at top first, then bottom.  
DEHUMIDIFIER DEACTIVATES WHEN THE  
AIR-CONDITIONER IS RUNNING  
• The common wire on the thermostat transformer  
(black) needs to be wired with the yellow wire from the  
dehumidifier.  
2. Plug in Ultra-Aire base unit. The control should power up.  
3. Turn control on by pressing the ON/OFF button.  
• The Yellow wire from the thermostat must be wired to the  
AC off sensor terminal.  
4. Engage dehumidification operation by adjusting RH  
setpoint below ambient conditions.  
a. Press RH until RH setpoint is 20%.  
b. Verify Ultra-Aire fan and compressor operation.  
c. Verify ventilation damper (if used) is closed.  
5. Verify fan only operation by disengaging dehumidification and  
operating fan:  
a. Adjust RH setpoint above ambient conditions by pressing and  
holding RH until set point is 80%.  
b. Press fan button, then press again to toggle fan to “ON”  
setting.  
DEHUMIDIFIER ACTIVATES WHEN THE  
AIR-CONDITIONER IS RUNNING  
c. Release fan button, then press again to toggle fan to “ON”  
setting until “FAN” flashes on display.  
• The common wire on the thermostat transformer  
(black) needs to be wired with the yellow wire from the  
dehumidifier.  
d. Verify fan operation of Ultra-Aire. No compressor operation  
should be noted, and ventilation damper (if used) should be  
closed.  
• The Yellow wire from the thermostat must be wired to the  
AC on sensor terminal.  
6. Verify ventilation damper operation (if installed) by disengaging  
from operation and engaging ventilating operation.  
a. Press and hold fan button until “FAN” flashes on display.  
b. Release “FAN” button, then press again to toggle fan  
operation off.  
c.Press and hold “VENT” button until“VENT” flasheson display.  
d. Release “VENT” button, then press again until “OPEN” is  
displayed.  
e. Verify Ultra-Aire fan operation and ventilation damper is open,  
with no compressor operation.  
7. If any functions are not working properly, verify wiring and  
connections. Meters may be used across terminals to verify voltage.  
If there is a concern about the base unit not operating properly, the  
leads exiting the base unit may be connected and operation verified  
according to the following matrix:  
5.2E Location  
Install the remote control panel in a central area of the  
structure where it will sense the relative humidity of the  
structure accurately. Do not install the control panel where it  
may not accurately sense the relative humidity such as near  
HVAC supply registers, near exterior doors and windows, or  
near a pool or spa.  
Wire connections  
Yellow & Blue  
Operation  
Fan & Compressor  
Fan Only  
Yellow & Green  
5.2F Testing  
Do not test any other connections or transformer damage  
may result. Refer to the appropriate Ultra-Aire base unit  
manual for additional information.  
After wiring connections have been made, verify connections.  
First, make sure the white wire from the base unit is not  
wired directly to the DEH 3000 control. There must be a  
motorized damper in series with these connections, or the  
white wire must not be connected to the control. Mis-wiring  
may result in transformer damage.  
13  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
8. Verify additional optional control operations such as fan interlock  
or lockout.  
9. Proceed to operation/setting section.  
FOR INSTALLER & HOMEOWNER:  
5.3 Operation  
5.3A Display  
• When there is power to the control, the control display will  
show the time, day, humidity, and temperature.  
• When the control is turned on, the setpoint, fan status,  
auto/hold mode, and fresh air vent status is displayed.  
• When a key is pressed the display will light.  
• The “TIME” and “DAY” is displayed at the top of  
the screen.  
• RH and Temperature are displayed in real time.  
• An “  
is operating the device.  
• A flashing “ ” before the set point, vent, or fan indicates  
O” before the set point, vent, or fan indicates the unit  
O
5.3D Setting Clock Time  
the unit is in a delay prior to operating the device.  
1. Press and hold the “CLOCK” button. The hour display  
will flash. Release the button.  
Note: Delay is an intentional factory installed time delay  
cycle that is meant to prevent short cycles, extending the  
life of the Ultra-Aire. If a delay is encountered, WAIT 10  
MINUTES BEFORE EXPECTING NORMAL OPERATION.  
2. Use the “UP/DOWN RH” buttons to change the value.  
3. Press the “CLOCK” button again and the minute display  
will flash. Use the RH buttons to change the value.  
4. Press the “CLOCK” button again and the AM/PM” display  
will flash. Use the RH buttons to toggle the value.  
5. Press the “CLOCK” button again and the day display will  
flash. Use the “RH” buttons to change the value.  
5.3B Setting  
During the set-up process, if you make a mistake, simply  
continue. You can always go back to adjust the settings. If  
you leave the control alone and don’t touch any buttons for  
10 seconds, the control will remember any changes made  
and return to “home.”  
If the “CLOCK” button is pressed again or no button is  
pressed for 5 seconds, the display will automatically return to  
“home.”  
5.3C On/Off Setting  
Press the “ON/OFF” button to turn the system on or off.  
When the system is on, the setpoint, fan status, auto/hold  
mode, and fresh air vent status is displayed. In the off  
mode, the control will show the time, day, humidity, and  
temperature. When the unit is shipped, it is in manual mode.  
5.3E Setting Relative Humidity Setpoint  
The relative humidity setpoint (the average RH that is  
maintained) operates the dehumidifier function of the Ultra-  
Aire. It has no effect on any other function of the unit. The  
control senses the ambient relative humidity of the space in  
which it is located.  
14  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
Operation  
continuously are filtration and air recirculation.  
The initial dead band setting (the range that the dehumidifier  
cycles on and off) is 3%. With a setpoint of 50%, the dumidifier  
turns on when the reading reaches 53%. The dehumidifier  
continues to remove water from the air until the reading is  
47%. The dehumidifier remains off until the reading is 53%.  
“AUTO” – indicates the fan will run when the control calls for  
dehumidification or ventilation. If the control has not called for  
dehumidification for 3 hours, the control will automatically run  
the fan for 10 minutes. The fan must run a specific amount of  
time per day. This helps to keep the dehumidifier dry.  
After dehumidification cycle, fan automatically shuts off for 10  
minutes.`  
To set the operation:  
1. Press and hold the “FAN” button. The current fan setting  
will begin to flash. Release the button.  
2. Press the “FAN” button to toggle between the “ON” and  
“AUTO” modes.  
If the setpoint is equal to or greater than the current ambient  
condition, the space does not need to be dried so the  
dehumidifier function will be off.  
Example: Setpoint: 50% RH  
Current condition: 45% RH = Dehumidifier off, the “  
O”  
indicator will not be shown.  
If the setpoint is less than the ambient condition, the  
dehumidifier will be on and the red “DEHU” indicator will be  
lit. Since the space is more humid than the set point, the  
controller operates the dehumidifier to dry the space.  
An “  
indicator indicates the fan is in a wait mode and will  
operate shortly. No “ ” indicates the fan is off.  
Oindicator indicates the fan is operating. A flashing  
O  
O
Example: Setpoint: 50% RH  
Current condition: 55% RH = Dehumidifier on, the “  
indicator will be shown.  
With the fan in the “AUTO” mode, the fan will operate only  
when needed by other functions of the system. The fan  
will remain off unless the system is dehumidifying and/or  
ventilating. The fan always runs during dehumidification and  
ventilation and the fan Oicon will be lit. To completely turn  
the system off, use the “ON/OFF” button as described earlier.  
O”  
To set the relative humidity setpoint, press up or down “RH”  
buttons to adjust the relative humidity setpoint as desired.  
Therma-Stor recommends relative humidity levels not exceed  
50% in the summer, and 25-35% in the winter if you live  
in a cold climate. It is not recommended that the humidity  
setpoint be set below 35%. In order to dry the home in the  
winter in a cold climate, use the ventilation function of the  
system rather than the dehumidifier function. Call the factory  
or refer to the owner’s manual for more information.  
To adjust the ventilation mode see Section 3.7.  
5.3G Damper Operation and Setting (Ventilation)  
Manual/Hold Mode  
Ultra-Aire units can be installed to incorporate optional ventilation.  
The damper setting controls the ventilation function of the system.  
It has no control over the dehumidification function, although  
the ventilation function can and should be used to dry the space  
depending on the climate and the outside air conditions. Refer to  
the appropriate Ultra-Aire manual for more information.  
5.3F Fan Setting and Operation  
Use the “FAN” button to adjust the fan operation. There are  
2 choices for fan operation: “ON” or “AUTO.”  
“ON” – indicates the fan of the Ultra-Aire will run  
In order to provide ventilation, the damper must be open (“ON”)  
and the fan must be running.The controller takes care of these  
two functions automatically, so that whenever the damper is open  
(“ON”), the fan is running.  
continuously. This does not affect either the dehumidification  
or ventilation functions of the system. In other words, the  
system may or may not be ventilating or dehumidifying while  
the fan is running. Common reasons for operating the fan  
15  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
There are two programs available for ventilation Monday  
through Friday. There are also two programs for Saturday and  
Sunday. No other choice of days is available.  
The ventilation indicator Owill be displayed whenever  
the unit is ventilating.The fan operation indicator Owill also be  
lit.  
Each program has:  
• A “START” time of day when the ventilation schedule  
begins.  
• An “OPEN FOR” duration for the amount of time the  
damper stays open in 5 minute intervals, from 0 to 60.  
• A “CLOSED FOR” duration which closes the vent for a  
specified time in 5 minute intervals from 0 to 60.  
There are three damper operation modes, “OPEN HOLD,”  
“CLOSED – HOLD” and “PROGRAM” (denoted by “ON TIME”  
“OFF TIME.” Refer to section 3.8).With the damper in the  
“OPEN HOLD” mode, the damper will be open and the fan of  
the system will be operating in order to introduce fresh air into  
the space. Use this mode for continuous fresh air ventilation.The  
fan is always on when the damper is open.When in “CLOSED  
– HOLD” mode, the damper will not open and the system will not  
ventilate.  
Example:  
1. Press “PROGRAM ENTER” button. The following menu  
appears:  
When in theprogrammode, the control will operate the damper  
and fan (ventilate) according to the programmed ventilation  
schedule (See Section 3.8).  
To set the damper operation:  
1. Press the “VENT” button.The current setting will begin to  
flash on the display. Release the button.  
2. Press the “VENT” button again to toggle between “OPEN,”  
“CLOSED” and “PROGRAM.”  
3. Leave the control alone for 10 seconds to select the indicated  
2. Using the up/down RH buttons, select “PROGRAM.” The  
damper mode and return to “HOME.”  
following menu appears:  
5.3H Intermittent or Programmed Ventilation  
You can select from:  
“MON-FRI”or “SAT-SUN” for separate weekday/weekend  
schedules or “MON-SUN”which gives you equal weekday/  
weekend schedules.  
Menu when you select “MON-FRI” or SAT-SUN”:  
The system will operate the ventilation function according to the  
current ventilation program.The control needs to be programmed  
to turn the ventilation function on and off at the desired intervals.  
This is done by programming the ventilation timer.  
1. Enter the starting time for weekdays using the up/down  
RH keys to change the time.  
16  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY AND HOMEOWNER  
2. Press the program enter key to toggle to the “open for”  
setting. Using the up/down “RH” keys, change the  
duration that the damper will ventilate fresh air.  
feature will not need to be used. If temperature cutout is desired,  
program the setpoint by pressing the “PROGRAM ENTER”  
button. Press RH until “TEMP CUTOUT” is flashing. Use “RH”  
up or “RH” down to adjust setpoints.  
3. Press the program enter key to toggle to the “closed  
for” setting. Using the up/down “RH” keys, change the  
duration that the damper will remain closed between  
ventilation.  
5.3J Default Settings  
Upon initial power-up or after prolonged power outages (more  
than 30 minutes), the DEH 3000 is programmed with the  
following defaults.A space is provided to make note of user  
inputs.  
For the example given, starting at 8:00AM in the morning,  
the control will ventilate fresh air for 15 minutes then stop for  
15 minutes. This schedule of 15 minutes open; 15 minutes  
closed will continue until the start time of the night schedule.  
Setting  
Default  
My Setting  
Press “PROGRAM ENTER” again to go to the “MON-FRI”  
night schedule. Repeat the steps listed above for this and the  
“SAT-SUN” day and night schedules.  
RH setpoint  
50%  
__________  
__________  
__________  
__________  
Ventilation Operation  
Fan Setting  
Closed  
Auto  
80%  
When you return to the main program menu, use the  
up/down “RH” buttons to select “RUN PROGRAM.”  
Temp Cutout  
If you have questions about the  
DEH 3000, please call Therma-Stor LLC  
at 1-800-533-7533 or email us at  
Press “PROGRAM ENTER” to run the program. The  
display will appear as follows:  
5.3I Temperature Cutout Programming  
Ultra-Aire units produce heat when dehumidifying. Depending  
on outside conditions, the ventilation function may introduce  
warm air into the space. Occasionally, the operation of the  
Ultra-Aire may produce enough heat to drive temperatures up.  
The temperature cutout feature disables all Ultra-Aire operations  
if temperatures reach cutout setpoint. In most installations this  
17  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
7.2 Technical Description  
6. Maintenance  
The Ultra-Aire XT150H uses a refrigeration system similar to an air  
conditioner's to remove heat and moisture from incoming air, and  
add heat to the air that is discharged (See Figure 15).  
6.1 Standard Air Filter  
The Ultra-Aire XT150H is equipped with a pleated cloth air filter.  
This filter should be checked every six months. Operating the unit  
with a dirty filter will reduce dehumidifier capacity and efficiency  
and may cause the compressor to cycle off and on unnecessarily  
on the defrost control.  
Hot, high-pressure refrigerant gas is routed from the compressor  
to the condenser coil (See Figure 3). The refrigerant is cooled  
and condensed by giving up its heat to the air that is about to be  
discharged from the unit. The refrigerant liquid then passes through  
a filter/drier and capillary tubing which causes the refrigerant  
pressure and temperature to drop. It next enters the evaporator  
coil where it absorbs heat from the incoming air and evaporates.  
The evaporator operates in a flooded condition, which means that  
all the evaporator tubes contain liquid refrigerant during normal  
operation. A flooded evaporator should maintain nearly constant  
pressure and temperature across the entire coil, from inlet to outlet.  
To access the air filter, remove the filter access panel from the end  
of the Ultra-Aire XT150H. The filter should be readily visible and can  
be removed by pulling them straight out of the Ultra-Aire XT150H.  
The pleated cloth filter can generally be vacuumed clean several  
times before needing replacement. Replacement filters can be  
ordered from the factory or purchased locally if available. DO NOT  
operate the unit without the standard filter or with a less effective  
filter than the standard filter. The heat exchange coils inside the  
unit could become clogged and require disassembly to clean. Filter  
non-compliance invalidates the product warranty.  
The mixture of gas and liquid refrigerant enter the accumulator  
after leaving the evaporator coil. The accumulator prevents any  
liquid refrigerant from reaching the compressor. The compressor  
evacuates the cool refrigerant gas from the accumulator and  
compresses it to a high pressure and temperature to repeat the  
process.  
6.2 High Efficiency Air Filter  
An optional high efficiency pleated microglass paper filter is  
available for the Ultra-Aire . This filter is rated as 90%-95% efficient  
by the ASHRAE Dust Spot test method 52-76. The high efficiency  
pleated microglass paper filter should be used in conjunction with  
the standard filter, and placed directly beneath the standard filter.  
This filter is able to remove allergy causing particles from the  
airstream. The high efficiency filter has a much larger surface area  
than the standard filter, thus the standard filter may need to be  
cleaned or replaced several times before the high efficiency filter  
requires replacement. Be careful not to damage the fabric media  
when handling the high efficiency pleated paper filter. Do not  
attempt to clean the high efficiency pleated paper filter. It should be  
replaced when it becomes restrictive (See Figure 7).  
6.3 Impeller Fan Oiling  
The impeller fan motor is factory lubricated for many years of  
normal operation, and no further oiling is required.  
Figure 15: Refrigeration System of Ultra-Aire XT150H  
6.4 Optional Fresh Air Return  
Check and clean the screen on the outdoor fresh air return  
seasonally. The screen may become plugged during the seasons  
when there are many particles in the outdoor air.  
7.3 Troubleshooting  
No dehumidification, neither impeller fan nor compressor run  
with fan switch and ventilation timer OFF.  
1. Unit unplugged or no power to outlet.  
2. Humidity control set too high or defective  
(Sec. 3.3 & 5.7A)  
7. Service  
7.1 Warranty  
A warranty certificate has been enclosed with this unit; read  
it before any repair is initiated. If a warranty repair is required,  
call the factory first at 1-800-533-7533 for warranty claim  
authorization and technical assistance.  
3. Loose connection in internal or control wiring.  
4. Defective Compressor relay.  
5. Defective control transformer.  
6. Low pressure Control open (Sec 3.7 & 5.10).  
7. Optional Condensate Pump Safety Switch open (Sec 5.11).  
18  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
No dehumidification, compressor does not run but impeller fan  
runs with fan switch and ventilation timer OFF and humidity  
control turned to ON.  
Unit removes some water, but not as much as expected.  
1. Air temperature and/or humidity have dropped.  
2. Humidity meter and or thermometer used are out of  
calibration.  
1. Defective compressor run capacitor (Sec. 5.6).  
2. Bad connection in compressor circuit  
(See Fig. 4).  
3. Unit has entered defrost cycle (Sec. 5.8).  
4. Air filter dirty (Sec. 4.1 & 4.2).  
3. Defective compressor overload (Sec. 5.6A).  
4. Defective compressor (Sec. 5.6).  
5. Defective defrost thermostat (Sec 5.8).  
6. Low refrigerant charge (Sec. 5.4).  
5. Defrost thermostat open (Sec. 5.8).  
7. Air leak such as loose cover or ducting leaks.  
8. Defective compressor (Sec. 5.6).  
9. Restrictive ducting (Sec. 2.4).  
Impeller fan runs with fan switch and ventilation timer OFF, but  
compressor cycles on & off.  
10.Optional Condensate Pump Safety Switch open (Sec 5.11).  
1. Low ambient temperature and/or humidity causing unit to  
cycle through defrost mode.  
Unit Test to determine problem:  
2. Defective compressor overload (Sec. 5.6A).  
3. Defective compressor (Sec. 5.6).  
4. Defrost thermostat defective (Sec. 5.8).  
5. Dirty air filter(s) or airflow restricted.  
1. Detach field control wiring connections from main unit.  
2. Connect the yellow and green pigtails from the main unit  
together; only the impeller fan should run. Disconnect the  
wires.  
6. Low refrigerant charge, causing defrost control to cycle.  
7. Bad connection in compressor circuit.  
3. Connect the yellow and blue pigtails from the main unit  
together; the compressor and impeller fan should run.  
4. If these tests work, the main unit is working properly. You  
should check the control panel and field control wiring for  
problems next.  
5. Remove the control panel from the mounting box and detach  
it from the field installed control wiring. Connect the blue,  
yellow, and green wires from the control panel directly to the  
corresponding colored pigtails on the main unit. Leave the  
violet, white and red wires disconnected!  
Impeller fan does not run with fan switch in either position.  
Impeller fan does not run with ventilation timer activated.  
Compressor runs briefly but cycles on & off with humidity  
control turned to ON.  
1. Loose connection in impeller fan circuit (See Fig. 4).  
2. Obstruction prevents impeller fan rotation.  
3. Defective impeller fan.  
4. Defective impeller fan relay.  
5. Defective impeller fan capacitor.  
6. Turn on the fan switch; the impeller fan should run. Turn off  
the fan switch.  
Impeller fan runs with fan switch ON. Impeller fan does not run  
with ventilation timer activated.  
7. Turn on the humidity control; the compressor and impeller fan  
should run.  
1. Defective ventilation timer.  
8. If these tests work, the problem is most likely in the field  
control wiring.  
2. Time not correct on ventilation timer.  
3. Ventilation timer set to manual & switched OFF.  
4. Defective fan switch.  
7.4 Refrigerant Charging  
If the refrigerant charge is lost due to service or a leak, a new  
charge must be accurately weighed in. If any of the old charge is  
left in the system, it must be recovered before weighing in the new  
charge. Refer to the unit nameplate for the correct charge weight  
and refrigerant type.  
Evaporator coil frosted continuously, low dehumidifying  
capacity.  
1. Defrost thermostat loose or defective (Sec. 5.8).  
2. Low refrigerant charge  
3. Dirty air filter(s) or airflow restricted.  
4. Excessively restrictive ducting connected to unit.  
7.5 Impeller Fan Replacement  
The motorized impeller fan is a unitary assembly consisting of the  
motor and impeller fan. If defective, the complete assembly must  
be replaced.  
Unit not providing ventilation. Ventilation timer not operating  
correctly.  
1. If timer is not functioning correctly reset timer and reprogram  
(Sec. 3.5).  
2. Check control wire connections (check  
connections at fresh air damper also).  
3. Defective fresh air damper (Sec. 5.9).  
4. Defective fan switch.  
1. Unplug the power cord.  
2. Remove the cabinet access panel.  
3. Remove the screw attaching the impeller fan support bracket  
to the base.  
4. Disconnect the impeller fan leads inside the electric box.  
19  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
5. Remove fan/bracket assembly by removing 3 screws from  
the bracket and inlet ring assembly.  
6. Remove the defective impeller fan from the bracket and  
replace with it with the new impeller fan.  
7. Reassemble the new impeller fan by reversing the above  
procedure. Note: There are two pins on the backside of the  
cabinet that must align with the two holes in the impeller fan  
support bracket.  
replace the run capacitor.  
11. If the unit still does not start, adding a hard-start kit (relay &  
capacitor) will provide greater starting torque. If this doesn't  
work, the compressor has an internal mechanical defect and  
must be replaced.  
7.6B Replacing a Burned Out Compressor  
The refrigerant and oil mixture in a compressor is chemically  
very stable under normal operating conditions. However, when an  
electrical short occurs in the compressor motor, the resulting high  
temperature arc causes a portion of the refrigerant oil mixture to  
break down into carbonaceous sludge, a very corrosive acid, and  
water. These contaminants must be carefully removed otherwise  
even small residues will attack replacement compressor motors  
and cause failures.  
7.6 Compressor/Capacitor Replacement  
This compressor is equipped with a two terminal external overload  
and a run capacitor, but no start capacitor or relay (See Figure 4).  
7.6A Checking Compressor Motor Circuits  
Perform the following tests if the impeller fan runs but the  
compressor does not with the fan switch and ventilation timer OFF  
and the humidity control ON.  
The following procedure is effective only if the system is monitored  
after replacing the compressor to insure that the clean up was  
complete.  
1. Unplug the unit; remove the cabinet side and the electrical  
connection cover on the compressor top.  
1. This procedure assumes that the previously listed compressor  
motor circuit tests revealed a shorted or open winding.  
2. Remove and properly dispose of the system charge. DO NOT  
vent the refrigerant or allow it to contact your eyes or skin.  
3. Remove the burned out compressor. Use rubber gloves if  
there is any possibility of contacting the oil or sludge.  
4. To facilitate subsequent steps, determine the type of burn  
out that occurred. If the discharge line shows no evidence  
of sludge and the suction line is also clean or perhaps has  
some light carbon deposits, the burn out occurred while the  
compressor was not rotating. Contaminants are therefore  
largely confined to the compressor housing. A single  
installation of liquid and suction line filter/driers will probably  
clean up the system.  
2. Plug in the unit and turn the humidity control to ON. Check for  
110 volts from compressor terminal R to overload terminal  
3 using an AC voltmeter. If voltage is present, go to step  
3. If no voltage, there may be a loose connection in the  
compressor circuit. Test each component for continuity. See  
the appropriate section if a defect is suspected.  
3. Unplug the unit, and then disconnect the red and yellow wires  
from compressor terminals R & S. Using an ohmmeter check  
continuity between the points listed below.  
4. Compressor terminals C and S: No continuity indicates an  
open start winding. The compressor must be replaced.  
Normal start winding resistance is 3 to 7 ohms.  
5. Compressor terminals C and R: No continuity indicates an  
open run winding. The compressor must be replaced. Normal  
run winding resistance is .5 to 2 ohms.  
If sludge is evident in the discharge line, it will likely be found in the  
suction line. This indicates the compressor burned out will running.  
Sludge and acid have been pumped throughout the system. Several  
changes of the liquid and suction filter/driers will probably be  
necessary to cleanse the system.  
6. Compressor terminal C and overload terminal 1: No continuity  
indicates a defective overload lead.  
7. Overload terminals 1 and 3: If there is no continuity, the  
overload may be tripped. Wait 10 minutes and try again.  
If there is still no continuity, it is defective and must be  
replaced.  
8. Compressor terminal C and compressor case: Continuity  
indicates a grounded motor. The compressor must be  
replaced.  
5. Correct the system fault that caused the burn out. Consult the  
factory for advice.  
6. Install the replacement compressor with a new capacitor and  
an oversized liquid line filter.  
9. Disconnect the wires from the run capacitor. Set the  
ohmmeter to the Rx1 scale. The capacitor is shorted and  
must be replaced if continuity exists across its terminals.  
If there is no needle movement with the meter set on the  
Rx100000 scale, the capacitor is open and must be replaced.  
10. Reconnect the wires to the compressor and capacitor. Plug  
in and turn on the unit. If the compressor fails to start,  
In a running burn out, install an oversized suction line filter/drier  
between the accumulator and compressor. Thoroughly flush the  
accumulator with refrigerant to remove all trapped sludge and to  
prevent the oil hole from becoming plugged. A standing burn out  
does not require a suction line filter/drier.  
20  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
7. Evacuate the system with a good vacuum pump and accurate  
vacuum gauge. Leave the pump on the system for at least an  
hour.  
8. Operate the system for a short period of time, monitoring the  
suction pressure to determine that the suction filter is not  
becoming plugged. Replace the suction filter/drier if pressure  
drop occurs. If a severe running burn out has occurred,  
several filter/driers may have to be replaced to remove all of  
the acid and moisture.  
ventilation of the residence. The home should be ventilated with  
fresh air as suggested by applicable codes and standards.  
If the Ultra-Aire XT150H fails to ventilate as expected, check that  
the time on the timer is correct. For the timer to carry out the  
program schedule, the slide switch in the upper left corner on the  
timer must be set to “AUTO”. The slide switch in the upper right  
corner of the Ultra-Aire XT150H must be set to “RUN”. Also check  
the programs on the timer to be sure that the timer is calling for  
ventilation at the correct times. If the timer fails to operate or  
operates erratically, reset the timer; see section 4.5 of this manual.  
NOTE: NEVER use the compressor to evacuate the system or  
any part of it.  
7.8 Defrost Thermostat  
The defrost thermostat is attached to the refrigerant suction tube  
between the accumulator and the compressor. It will automatically  
shut the compressor off if the low side refrigerant temperature  
drops due to excessive frost formation on the evaporator coil. The  
impeller fan will continue to run, causing air to flow through the  
evaporator coil and melt the ice. When the ice has melted, the  
evaporator temperature will rise and the thermostat will restart the  
compressor.  
7.6C Replacing a Compressor, Nonburn Out  
Remove the refrigerant from the system. Replace the compressor  
and liquid line filter/drier. Charge the system to 50 PSIG and check  
for leaks. Remove the charge and weigh in the refrigerant quantity  
listed on the nameplate. Operate the system to verify performance.  
7.7 Remote Controls  
The Ultra-Aire XT150H is controlled by devices mounted on a panel  
that is remote from the unit. You may or may not have the devices  
listed below depending on the model of the remote control panel  
you purchased. If the Ultra-Aire XT150H fails to operate as desired,  
always check the settings of the controls to insure that they are  
correct. Check that the controls are receiving 24Vac from the  
Ultra-Aire XT150H. Check the connections between the Ultra-Aire  
XT150H, the control panel, and the field control wiring.  
7.9 Electric Ventilation Damper  
The electric ventilation damper is controlled by the ventilation timer.  
The damper will open when the ventilation timer is activated to allow  
fresh air into the structure through the 6” diameter fresh air inlet duct.  
The electric ventilation damper will remain closed when the ventilation  
timer is not activated to prevent over-ventilating the structure when  
the unit is dehumidifying or recirculating the indoor air.  
7.7A Humidity Control  
The electric ventilation timer operates on 24 Vac from the control  
circuit. DO NOT connect high voltage to the damper motor or  
damage to the motor may result. DO NOT force the blade of the  
damper by hand or damage to the damper motor may result.  
The humidity control is an adjustable switch that closes when the  
relative humidity of the air in which it is located rises to the dial set  
point. It opens when the RH drops 4 to 6% below the set point. If  
the Ultra-Aire XT150H does not run, try turning the humidity control  
clockwise until it reaches the stop and the knob pointer points at  
“Max Dry” (see back of control panel cover). If it still does not run,  
remove the stop screw from the panel and turn the knob farther. If  
it then runs, the humidity control is out of calibration or the RH is  
below 40%.  
The damper opens in one direction only. The damper rotates very  
slowly, allow sufficient time for the damper to cycle. The damper  
will take approximately 1 minute to cycle from closed to open or  
from open to closed.  
If the electric ventilation damper fails to operate:  
1. Check that the wiring is correct and that voltage is present at  
the damper motor.  
The Ultra-Aire XT150H is equipped with an automatic defrost  
mechanism. If the Ultra-Aire XT150H operates in conditions that  
develop frost on the evaporator, it will sense the frost build-up and  
automatically defrost the evaporator. The Ultra-Aire XT150H may  
not appear to be operating correctly during the defrost sequence,  
but once the defrost sequence is completed, the Ultra-Aire XT150H  
will resume dehumidifying.  
2. Check for any obstruction inside the damper. If the electric  
ventilation damper fails to operate after performing these  
checks, it must be replaced.  
7.10 Condensate Pump Kit  
An optional condensate pump kit is available from the factory  
for use with the Ultra-Aire XT150H. Condensate is automatically  
pumped to a remote location when the water level in the pump's  
reservoir rises to close the float switch.  
7.7B Programmable Ventilation Timer  
The ventilation timer controls the impeller fan and the motorized  
fresh air damper. When the ventilation timer is activated, the  
Ultra-Aire XT150H will circulate the indoor air, and bring in fresh air  
from outside. The ventilation timer should be set for the required  
21  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
The pump also contains a safety float switch. The white leads  
from this switch extend from beneath the pump cover. This switch  
should be installed in series with the field wire that connects the  
blue (#5) lead from the Ultra-Aire XT150H to the blue (#5) lead on  
the control panel.  
If the pump fails, this switch opens the compressor control circuit  
and stops water production before the reservoir overflows. The  
Ultra-Aire XT150H will continue to ventilate or circulate air as  
normal, but will not dehumidify until this switch closes.  
Electric Schematics of the Ultra-Aire XT150H  
22  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR HVAC INSTALLER ONLY  
Pictorial Electrical Diagrams of Ultra-Aire XT150H  
23  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE PARTS LIST: Ultra-Aire XT150H  
Item Part No  
Qty  
1
1
2
1
Description  
HEAT EXCHANGER  
EVAPORATOR  
CAPPILLARY TUBES .050" X .124" X 59.00"  
COMPRESSOR - TOSHIBA,8.1  
KBTU,115V,60HZ  
ACCUMULATOR  
FILTER/DRIER  
TUBE - COND TO FILTER  
TUBE - DISCHARGE LINE  
CONDENSOR  
Item Part No  
Qty  
1
1
1
1
1
1
1
4
Description  
45mFd CAPACITOR - COMPRESSOR  
TRANSFORMER  
RELAY/COMPRESSOR  
15mFd CAPACITOR - IMPELLER  
COLLAR 10 INCH  
COLLAR OVAL 10 INCH  
COLLAR W/ DAMPER 6 INCH (NOT SHOWN)  
LEVELING FOOT  
DEFROST THERMOSTAT (NOT SHOWN)  
DEFROST THERMOSTAT CLIP (NOT SHOWN)  
WIRING DIAGRAM  
1
2
3
4
4026477  
4026672  
4026934  
4026670  
12  
13  
14  
15  
16  
17  
18  
19  
20  
4026687  
4022487  
4022484  
4017021  
4026932  
4026947  
4026933  
4026221  
4021470  
4021648  
4026660  
5
6
7
8
9
4026655  
4025087  
4026674  
4026472  
4026673  
4026657  
4020924  
1
1
1
1
1
1
1
1
1
1
10  
11  
IMPELLER  
RELAY/BLOWER  
21  
2
The Ultra-Aire XT150H  
1
2
7
18  
not shown  
4
5
6
17  
7
19  
9
8
10  
11  
12  
13  
14 15  
24  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPTIONAL PARTS LIST: Ultra-Aire XT150H  
ITEM  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
PART NO.  
4024375  
4022220  
4024155  
4024125  
4023660  
4023672  
4024153  
4021495  
4024150  
4024122  
4025560  
4022486  
4024369  
4025287  
QTY.  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
DESCRIPTION  
Check Damper, 10" Diameter (not shown)  
Condensate Pump Kit, External  
Control Panel Assembly, Humidity/Fan  
Control Panel Assembly, Ventilation Timer & Humidity  
Controller, Humidity  
Duct Damper, 6" Diameter, Electrically Actuated (not shown)  
Cover for Items 28 & 29 (not shown)  
Knob, Black, .25" shaft  
Instructions, Humidity/Fan (not shown)  
Instructions, Ventilation Timer & Humidity (not shown)  
Switch, Black, SPDT, On/Off  
Timer, 7-Day, 24 Vac, Programmable  
Merv 11 Standard Filter 20" x 16 "x 2"  
Filter Box  
not shown  
not shown  
Accessories  
25  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOOR AND COLLAR ASSEMBLY  
Door Install  
Insert tab on the bottom of the door,  
in between the foam installation and  
the metal side.  
Push down on the plastic door latch  
and swing door shit. Once the door is  
shut release the door latch.  
Collar Install  
Remove the 2 round ducts, 3 seals and small bag  
of mounting hardware from inside the rectangle  
opening.  
Adhere seals onto the back of each duct and  
mount the ducts to the front of the dehumidifier  
using screws provided.  
Collars and hardware  
are located here.  
26  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ULTRA-AIRE XT150H Dehumidifier Limited Warranty  
from misuse, abuse, lack of normal care, corrosion,  
freezing, tampering, modification, unauthorized or  
improper repair or installation, accident, acts of  
nature or any other cause beyond Therma-Stor  
LLC's reasonable control.  
WARRANTOR:  
Therma-Stor LLC  
PO Box 8680  
Madison, WI 53708  
Telephone: 1-800-533-7533  
WHO IS COVERED: This warranty extends only to  
the original residential end-user of the Ultra-Aire  
XT150H dehumidifier, and may not be assigned or  
transferred.  
LIMITATIONS AND EXCLUSIONS: If any Ultra-  
Aire XT150H Dehumidifier part is repaired or  
replaced, the new part shall be warranted for  
only the remainder of the original warranty period  
applicable thereto (but all warranty periods will  
be extended by the period of time, if any, that the  
Ultra-Aire XT150H Dehumidifier is out of service  
while awaiting covered warranty service).  
FIRST YEAR WARRANTY: Therma-Stor LLC  
warrants that,for one (1) year the Ultra-Aire XT150H  
dehumidifier will operate free from any defects in  
materials and workmanship, or Therma-Stor LLC  
will, at its option, repair or replace the defective  
part(s), free of any charge.  
UPONTHEEXPIRATIONOFTHEWRITTENWARRANTY  
APPLICABLE TO THE ULTRA-AIRE DEHUMIDIFIER  
OR ANY PART THEREOF, ALL OTHER WARRANTIES  
IMPLIED BY LAW, INCLUDING MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE,  
SHALL ALSO EXPIRE. ALL WARRANTIES MADE  
BY THERMA-STOR LLC ARE SET FORTH HEREIN,  
AND NO CLAIM MAY BE MADE AGAINST THERMA-  
STOR LLC BASED ON ANY ORAL WARRANTY. IN NO  
EVENT SHALL THERMA-STOR LLC, IN CONNECTION  
WITH THE SALE, INSTALLATION, USE, REPAIR OR  
REPLACEMENT OF ANY ULTRA-AIRE DEHUMIDIFIER  
OR PART THEREOF BE LIABLE UNDER ANY  
LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR  
CONSEQUENTIAL DAMAGES INCLUDING WITHOUT  
LIMITATION WATER DAMAGE (THE END-USER  
SHOULDTAKEPRECAUTIONSAGAINSTSAME),LOST  
PROFITS, DELAY, OR LOSS OF USE OR DAMAGE TO  
ANY REAL OR PERSONAL PROPERTY.  
SECOND THROUGH FIFTH YEAR WARRANTY:  
Therma-Stor LLC further warrants that for a period  
of five (5) years, the condenser, evaporator, and  
compressor of the Ultra-Aire XT150H dehumidifier  
will operate free of any defects in material or  
workmanship, or Therma-Stor LLC, at its option,  
will repair or replace the defective part(s), provided  
that all labor and transportation charges for the  
part(s) shall be borne by the end-user.  
END-USER RESPONSIBILITIES: Warranty service  
must be performed by a Servicer authorized by  
Therma-Stor LLC. If the end-user is unable to locate  
or obtain warranty service from an authorized  
Servicer, he should call Therma-Stor LLC at the  
above number and ask for the Therma-Stor LLC  
Service Department, which will then arrange for  
covered warranty service. Warranty service will be  
performed during normal working hours.  
Some states do not allow limitations on how long an  
implied warranty lasts, and some do not allow the  
exclusion or limitation of incidental or consequential  
damages, so one or both of these limitation may not  
apply to you.  
The End-user must present proof of purchase  
(lease) upon request, by use of the warranty card  
or other reasonable and reliable means. The end-  
user is responsible for normal care. This warranty  
only applies to residential applications and does  
not cover any defect, malfunction, etc. resulting  
LEGAL RIGHTS: This warranty gives you specific  
legal rights, and you may also have other rights  
which vary from state to state.  
27  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Information in this document is subject to change without notice. No part of this document  
may be reproduced or transmitted in any form or by any means, electronic or mechanical, for  
any purpose, without the express written permission of Therma-Stor LLC.  
© 2007 Therma-Stor LLC. All rights reserved.  
PO Box 8680 • Madison, WI 53708  
Phone: 608-222-5301 • Fax: 608-222-1447  
Ultra-Aire XT150H Installer’s & Owner’s Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Targus Portable DVD Player DVD401 User Manual
Technicolor Thomson Stereo System CS104 User Manual
Teledex Amplified Phone BTX4510 User Manual
Toshiba Air Conditioner RAV SP404AT E User Manual
Tote Vision Computer Monitor LCD 4700HD User Manual
TP Link Modem TC 7610 User Manual
Transition Networks Switch MIL SM808GPXX User Manual
Troy Bilt Tiller 664Dpony User Manual
UTStarcom Cell Phone PPC 6700 User Manual
Weed Eater Lawn Mower WE16542D User Manual