INSTALLATION AND
OPERATING INSTRUCTIONS
STANDARD SERIES
Unvented Decorative Gas Fireplaces
P/N 903302 REV. M 12/2007
MODELS
VF5000-CMN-2
VF5000-CMP-2
VF6000-CMN-2
VF6000-CMP-2
FOR USE ONLY WITH DECORATIVE TYPE UNVENTED ROOM
HEATERS.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
DO NOT BUILD A WOOD FIRE.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, AL-
TERATION, SERVICE OR MAINTENANCE CAN CAUSE IN-
JURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL.
FOR ASSISTANCE OR ADDITIONAL INFORMATION CON-
SULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE
GAS SUPPLIER.
US
WARNING: DO NOT BURN WOOD OR OTHER MATERIAL IN
THESE APPLIANCES.
WARNING:IFTHEINFORMATIONINTHISMANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-
SIONMAYRESULTCAUSINGPROPERTYDAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
CAREFULLY REVIEW THE INSTRUCTIONS SUPPLIED WITH
THE DECORATIVE TYPE UNVENTED ROOM HEATER FOR
THE MINIMUM FIREPLACE SIZE REQUIREMENT.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicinity
of this or any other appliance.
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX, UN-
LESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS
REQUIRED FOR THE INSTALLATIONS.
FOR YOUR SAFETY: What to do if you smell gas:
This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and ventila-
tion air must be provided. Refer to Combustion
and Ventilation Air Section, Page 3.
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.
Due to high temperatures, the appliance should be located out
of traffic and away from furniture or draperies.
Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the
fire department.
Do not place clothing or other materials on or near this appli-
ance.
Installation and service must be performed by a
qualified installer, service agency or the gas sup-
plier.
IMPORTANT: READ AND UNDERSTAND THESE INSTRUCTIONS
COMPLETELY BEFORE INSTALLING YOUR UNVENTED ROOM
HEATERS.
Download from Www.Somanuals.com. All Manuals Search And Download.
• The installation must conform with local
codesor, intheabsenceoflocalcodeswiththe
National Fuel Gas Code, ANSI Z223.1.
Massachusetts:
WARNING: ANY CHANGE TO THIS UN-
VENTED ROOM HEATER OR ITS CON-
TROLSCANBEDANGEROUS.IMPROPER
INSTALLATIONORUSEOFTHISHEATER
CANCAUSESERIOUSINJURYORDEATH
FROM FIRE, BURNS, EXPLOSION OR
CARBON MONOXIDE POISONING.
These fireplaces are approved for installation
in the US state of Massachusetts if the follow-
ing additional requirements are met-
• The heater and its individual shut-off valve
must be disconnected from the gas supply
piping system while performing any tests of
the gas supply piping system at pressures in
excess of 1/2 psig.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Common-
wealth of Massachusetts.
• The flexible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The heater must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig.
WARNING: THESE APPLIANCES ARE
DESIGNED TO OPERATE ON NATURAL
OR PROPANE GAS ONLY. THE USE OF
OTHER FUELS OR COMBINATION OF
FUELS WILL DEGRADE THE PERFOR-
MANCE OF THIS SYSTEM AND MAY
BE DANGEROUS.
• The individual manual shut-off must be a T-
handle type valve.
• Vent-Free appliances may NOT be installed in
bedrooms or bathrooms.
• Any safety screen or guard removed for
servicing the heater must be replaced prior to
operating the heater.
• A working smoke detector must be installed
in the area where vent-free appliances are
installed.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
thefluwithheadaches, dizzinessand/ornau-
sea. If you have these signs, obtain fresh air
immediately. Turn off the gas supply to the
heater and have the Unvented Gas Heater
servicedasitmaynotbeoperatingcorrectly.
• Keep heater area clear and free from com-
bustible materials, gasoline and other flam-
mable vapors and liquids.
Seller of unvented propane or natural gas-
fired supplemental room heaters shall pro-
vide to each purchaser a copy of 527 CMR 30
upon sale of the unit.
• Do not use these appliances if any part has
been under water. Immediately call a qualified
professional service technician to inspect the
appliance and to replace any parts of the
control system and any gas control which
have been under water.
New York:
• Duetohightemperatures, theheatershould
be located out of traffic and away from furni-
ture and draperies.
These appliances are approved for installa-
tion in the US state of New York, but not in
New York City.
• Test gage connections are provided on the
front of the gas control valve (identified A for
the manifold side and E for inlet pressure).
• Children and adults should be alerted to the
hazardofhighsurfacetemperaturesandshould
stay away to avoid burns or clothing ignition.
COMBUSTION AND VENTILATION AIR
These heaters shall not be installed in a con-
fined space. The heater may be located in
unusually tight construction provided the
space is unconfined, or if confined, is pro-
vided with two permanent openings commu-
nicating directly with an additional room(s)
of sufficient volume so that the combined
volume of all connected spaces meets the
criteria for an unconfined space, (National
Fuel Gas Code ANSI Z223.1 (latest edition),
Section 5.3). Generally 50 ft 3 per 1,000 BTU
input of all operating appliances in the space.
• Input ratings are shown in BTU per hour and
are for elevations up to 7,000 feet. Operating
heater above elevations of 7,000 feet may
cause ODS pilot outage.
• Young children should be carefully super-
vised when they are in the same room with the
heater.
• Do not place clothing or other flammable
material on or near the heater for the purpose
of drying.
• Ensure that the heater is clean when operat-
ing.Excessivedustaccumulationontheburner
and logs will increase the amount of carbon
monoxide formation and could lead to carbon
monoxide poisoning and death.
• Installation and repair should be done by a
qualified service person. The heater should be
inspected before use and at least annually by
a professional service person. More frequent
cleaning may be required due to excessive lint
from carpeting, bedding material, etc. It is
important that control compartments, burn-
ers and circulating air passageways of the
heater be kept clean.
CODES
The National Fuel Gas Code defines a con-
fined space as a space whose volume is less
than 50 ft 3 per 1,000 BTU/Hr (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space and an unconfined
space as a space whose volume is not less
than 50 ft 3 per 1,000 BTU/Hr (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space.
Adhere to all local codes or in their absence the
latest edition of The National Fuel Gas Code
ANSI Z223.1 or NFPA54 which can be obtained
from The American National Standards Insti-
tute, Inc. (1430 Broadway, New York, NY,
10018) or National Fire Protection Association,
Inc. (Batterymarch Park, Quincy, MA, 02269).
• Allow the heater to cool before servicing.
Always shut off any electricity or gas to the
heater while performing service work.
Massachusetts And New York Require-
ments
• DonotinstalltheVF5000andVF6000series
heaters in a bedroom or bathroom.
Roomscommunicatingdirectlywiththespace
in which the appliances are installed, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.
These appliances are approved for installation
in the following USA locations listed in the
following:
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Unusuallytightconstructionisdefinedascon-
struction where:
4. Compare the maximum BTU/Hr the space
can support with the actual amount of BTU/
Hr used.
LOCATION OF FIREPLACE
Carefullyselectthebestlocationforinstallation
of your VF5000 and VF6000 series Unvented
Room Heater. The following factors should be
taken into consideration:
a. wall and ceilings exposed to the outside
atmosphere have a continuous water vapor
retarder with a rating or one perm or less with
openings gasketed or sealed, and
_________ BTU/Hr
(max. the space can support)
_________ BTU/Hr
(actualamountofBTU/Hrused)
• Clearance to side wall, ceiling, woodwork
and windows.
b. weather stripping has been added on oper-
able windows and doors, and
Example:
61,440 BTU/Hr
(max. the space can support)
66,000 BTU/Hr
• Location must not be affected by drafts
caused by kitchen exhaust fans, return air reg-
isters for forced air furnaces/air conditioners,
windows or doors.
c. caulking or sealants are applied to areas
suchasjointsaroundwindowanddoorframes,
between sole plates and floors, between wall-
ceiling joints, between wall panels, at penetra-
tions for plumbing, electrical, and gas lines,
and at other openings.
(actualamountofBTU/Hrused)
The space in the above example is a confined
space because the actual BTU/Hr used is more
than the maximum BTU/Hr the space can sup-
port. You must provide additional fresh air.
• Installation must provide adequate ventila-
tion and combustion air.
Use the following equations to determine if
you have a confined or unconfined space.
• DonotinstalltheVF5000andVF6000series
heaters in a sleeping room or bathroom.
WARNING: IF THE AREA IN WHICH THE
HEATERMAYBEOPERATEDISSMALLER
THAN THAT DEFINED AS AN UNCON-
FINED SPACE, PROVIDE ADEQUATE
COMBUSTIONANDVENTILATIONAIRBY
ONE OF THE METHODS DESCRIBED IN
THE NATIONAL FUEL GAS CODE, ANSI
Z223.1 1992, SECTION 5.3 OR APPLI-
CABLE LOCAL CODES.
1. Determine the volume of space — ft 3.
• Never obstruct the front opening of the
heater or restrict the flow of combustion and
ventilation air.
Length x Width x Height = _____ ft 3
(Includeadjoiningroomswithdoorlesspas-
sageways or ventilation grills between
rooms.)
• This appliance may be installed in an after-
market manufactured (Mobile) Home, where
not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for pur-
pose of resale, from the manufacturer.
Example: 24' (L) x 16' (W) x 8' (H) = 3072
ft 3
2. Divide the volume of space by 50 ft 3 to
determine the maximum BTU/Hr the space
can support.
• Minimizemodificationstoexistingconstruc-
tion. RefertoFigure1 forlocationsuggestions.
Your options are:
a. Rework equations adding the space of ad-
joiningroom(s). Iftheextravolumeprovides
an unconfined space, then remove door or
add ventilation grills between rooms. Refer
to National Fuel Gas Code, ANSI Z223.1
1992, Section 5.3.
______ (volume of space – ft 3)/ 50 ft 3
=
(Maximum BTU/Hr the space can support)
Example: 3072 ft 3 / 50 ft 3 = 61.44
or 61,440 BTU/Hr the space can support.
b. Vent room directly to the outdoors. Refer to
National Fuel Gas Code, ANSI Z223.1 1992,
Section 5.3.
3. Add the BTU/Hr of all the fuel burning appli-
ances in the space.
Vent-Free heater
Gas appliance #1*
Gas appliance #2
_______ BTU/Hr
_______ BTU/Hr
+ _______ BTU/Hr
c. Install a lower BTU/Hr heater, such as the
25,000 BTU/Hr, to make the area an uncon-
fined space.
Figure 1
Total = _______ BTU/Hr
If the actual BTU/Hr used is less than the
maximum BTU/Hr the space can support, then
thespaceisanunconfinedspace. Youwillneed
no additional fresh air ventilation for an uncon-
fined space.
To ensure even heat distribution, it is best to
position the heater centrally against the long-
est wall of the room. Make sure there is ad-
equateventilationwheretheheaterisinstalled.
The gas appliance will shut off if the oxygen
level falls below 18.0%.
Example:
VF6000 Vent-free heater 32,000 BTU/Hr
Gas appliance #1
(water heater)
34,000 BTU/Hr
Total = 66,000 BTU/Hr
These appliances are uniquely suited for in-
stallations requiring a utility shelf positioned
directly above the fireplace. Utility shelves like
these are commonly used for locating televi-
sion sets and decorative plants.
* Do not include direct-vent gas appliances.
Direct-vent is sealed combustion and draws
combustion air from the outdoors.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
To provide for the lowest possible shelf sur-
face, combustible materials used to support a
utility shelf directly above these appliances
should be positioned just above the appliance
top spacers. The minimum height from the
base of the VF5000 to the underside of com-
bustible materials used to construct a utility
shelf is 34-1/2” (876 mm). The minimum
height from the base of the VF6000 to the
underside of combustible materials used to
construct a utility shelf is 39-1/2” (1003 mm).
Combustible
Finished Wall
Materials
Remove wood slats and remove and discard
the wood slat mount brackets. Loosen and
remove the three (3) 1/4"-20 x 1" Phillips pan
head screws at the three (3) tabs located along
the door frame top edge. Tilt the glass door
frame assembly outward and disengage the
three(3)tabsalongthebottomofthedoorfrom
the three (3) brackets at the bottom of the
firebox opening. Remove the door and set the
panel aside protecting it from inadvertent dam-
age. Retain the three (3) screws for use on
reassembly. Remove the logs, packaged inside
the firebox, and also set aside.
12"
( mm)
10''
Header
Spacer
26"
8''
6''
( mm)
22-1/2"
( mm)
18-5/8"
( mm)
2-1/2"
( mm)
14-1/2"
( mm)
Top of Appliance
8"
( mm)
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materi-
als. However, if installed on combustible mate-
rials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.
Top of Door Frame
Check Gas Type
VF Series
Thisappliancecanonlybeconnectedtothegas
type specified on the appliance data plate. This
appliance can not be modified in the field for a
different gas type. If the gas type to be used is
not the one specified contact the dealer to
obtain the correct gas appliance.
Figure 2
A hearth extension is not required with this
appliance. If a hearth extension is used, do not
blockthelowercontrolcompartmentdoor. Any
hearth extensions used is for appearance only
and does not have to conform to standard
hearth extension installation requirements.
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.
Note: Illustrations shown in this manual reflect
“typical”installationswithnominaldimensions
and are for design and framing reference only.
Actual installations may vary due to individual
design preferences. However, always maintain
minimum clearances to combustible materials
and do not violate any specific installation re-
quirements.
WARNING: MAINTAIN MINIMUM
CLEARANCES.
Note: Combustible wall finish materials and/or
surround materials must not be allowed to
encroach the area defined by the appliance
front face (black sheet metal). Never allow
combustible materials to be positioned in front
of or overlapping the appliance front face.
Do not install in the vicinity of gasoline or other
flammableliquids. Theheatermustbekeptclear
and free from these combustible materials and
may not be located near where they are stored.
6" Clearance
to Combustible
Side Wall
Note: The following steps represent the normal
sequence of installation. Each installation is
unique, however, and might require a different
sequence.
Clearances
WARNING: DO NOT INSTALL VF SE-
RIES UNVENTED ROOM HEATERS IN
SLEEPING QUARTERS, OR IN RECRE-
ATIONAL VEHICLES.
Max. Projection (See Fig. 2)
CAUTION:HEATERSCREATEWARMAIRCUR-
RENTS. THESE CURRENTS MOVE HEAT TO
WALLSURFACESNEXTTOHEATER.INSTALL-
INGHEATERNEXTTOVINYLORCLOTHWALL
COVERINGS OR OPERATING HEATER WHERE
IMPURITIES IN THE AIR (SUCH AS TOBACCO
SMOKE) EXISTS, MAY DISCOLOR WALLS.
37-1/2" Min.
to Ceiling
(953 mm)
Combustible
Mantel
WARNING: DO NOT INSTALL THE VF
UNVENTED ROOM HEATER:
• WHERE CURTAINS, FURNITURE,
CLOTHING OR OTHER FLAMMABLE
OBJECTS ARE LESS THAN 42" FROM
THEFRONTOFTHEUNVENTEDROOM
HEATER.
(See Fig. 2)
Step 1. Position heater in desired location
(freestanding, onto surround base or into pre-
pared framing) and secure.
Figure 3
• IN HIGH TRAFFIC AREAS.
• IN WINDY OR DRAFTY AREAS.
PREINSTALLATION
Step2.Plumbgasline.(Gasconnectionsshould
onlybeperformedbyanexperienced, licensed/
certified tradesman.)
Check that all listed parts have been received.
Ensure the minimum clearances shown in Fig-
ures 2 and 3 are maintained.
Carefully inspect the heater case and contents
for shipping damage and immediately inform
the dealer from whom you purchased the gas
fireplace if any damage is found.
Step 3. Assemble logs and test flame appear-
ance.
Minimum clearance to combustibles are:
Appliance:
side and back - 0"
floor - 0"
adjacent wall - 6"
ceiling - 37-1/2” (953 mm)
Step4. Completefinishwallmaterial, surround
andoptionalhearthextensiontoyourindividual
taste.
The appliance is shipped with all gas controls
and components installed and pre-wired. Re-
move the shipping carton, exposing the op-
tional (if installed) front glass door frame.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: Framing dimensions in Figures 4 - 9 are calculated for a nailing flange depth of ¹⁄₂" (13 mm).
INSTALLATION STEPS
Built-In Systems
Back Wall of
Back Wall of
WARNING: DO NOT ALLOW FANS TO
BLOW DIRECTLY INTO THE FIREPLACE.
AVOID ANY DRAFTS THAT ALTER
BURNER FLAME PATTERNS.
Chase/Enclosure
Including Finishing
Materials If Any.
Chase/Enclosure
Including Finishing
Materials If Any.
Outside Wall
Outside Wall
15 1/2"
(394mm)
19 1/2"
(495mm)
WARNING: DO NOT USE A BLOWER IN-
SERT, HEAT EXCHANGER INSERT OR
OTHER ACCESSORY NOT APPROVED
FOR USE WITH THIS HEATER.
37" (940mm)
41" (1041mm)
VF5000
VF6000
Do not burn solid fuels in this listed unvented
gas room heater.
Figure 4
Figure 7
Step 1. Frame VF5000 appliance enclosures
as illustrated in Figures 4, 5 and 6. Frame
VF6000 appliance enclousures as illustrated
in Figures 7, 8 and 9 for surround installations
proceed to Step 8.
Back Wall of
Back Wall of
Chase/Enclosure
Including Finishing
Materials If Any.
Chase/Enclosure
Including Finishing
Materials If Any.
41"
(1041mm)
47 7/8"
(1216mm)
13 1/2"
(343mm)
14 1/4"
(362mm)
Note: The framed depth (15-1/2" for a flat wall,
29-1/4" for a corner VF5000 and 22-5/8" and
36-3/8" for a VF6000 ) must always be mea-
sured from a finished surface. If a wall covering
suchasdrywallistobeattachedtotherearwall,
thenthedimensionmustbemeasuredfromthe
drywall surface.
29"
(737mm)
33 7/8"
(860mm)
37" (940mm)
58" (1473mm)
41" (1041mm)
67 3/4" (1721mm)
VF5000
VF6000
Step 2. Route a 1/2" (13 mm) gas line along the
left or right side framing (Figure 10 ).
Figure 8
Figure 5
42 3/8"
(1076 mm)
37 1/4"
(946 mm)
19 1/2"
15 1/2"
(495 mm)
(394 mm)
37"
(940 mm)
3"
VF6000 - 11"
(279 mm)
41"
(76 mm)
(1041 mm)
VF5000 - 7 1/2"
(191 mm)
Figure 10
VF6000
VF5000
Figure 6
Figure 9
All appliances have a 3" long 3/8" NPT nipple
installed at the valve. To quickly and easily
complete the gas line routing, use the gas flex
line kit, Model GFLV.
The header may be in direct contact with the top
metal spacers, but must not rest on them or be
notched to fit around them.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
B. Brush all joints and connections with the
gas leak test solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” posi-
tion. Either tighten or refasten the leaking
connection and retest as described above.
Gas Flex Line Kit, Model GFLV
3/8" NPT x 3/8"
1/2" x 3/8" Flare
Shut-Off Valve
Flare Fitting
Gas Valve
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
3/8" Flex Tubing
D. When the gas lines are tested and leak free,
observe the individual tongues of flame on the
burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.
3/8" Nipple, Standard
with all Units
3/8" Union
3/8" Close Nipple
An external regulator must be used on all pro-
pane (L.P.G.) heaters, in addition to the regula-
torfittedtotheheater,toreducethesupplytank
pressure to 13" w.c. (maximum).
Gas Stub
3/8" Shut-Off Valve
1/2" x 3/8" Reducer
WARNING: CONNECTING DIRECTLY TO
AN UNREGULATED PROPANE TANK CAN
CAUSE AN EXPLOSION.
Figure 11
Step 3. Ensure the hood is properly positioned
in the open area above the appliance door. If
required insert the tabs, on each end of the
hood, into the bracket at each end. Bend the
two tabs over to secure.
Step 6. Installing the Optional Remote Wall
Switch – The standard millivolt system comes
from the factory wired as shown in Figure 13.
Select a convenient location for the remote wall
switch and connect the wiring to the appliance
(Figure 14 ).
Step 4. Position appliance into prepared
framing, secure with 6d nails or equivalent at
the nailing flange along each side.
Control
Valve
CAUTION: DO NOT CONNECT THE OPTIONAL
REMOTE SWITCH TO A 120V POWER SUP-
PLY.
Lower Control
Compartment Door
Step 5. Connecting Gas Line – Make gas line
connections. All codes require a shut-off valve
mounted in the supply line. Figure 11 illus-
trates two methods for connecting the gas
supply. Installation methods and materials
must be in compliance with local codes.
Note: The optional rocker switch is mounted to
the appliance and wired in the same way as the
remote wall switch.
Figure 12
Secure all joints tightly using appropriate
tools and sealing compounds (ensure pro-
pane resistant compounds are used in pro-
pane applications).
Step 7. Installing the Optional Forced Air
Blower Kit Wiring – A receptacle plate is pro-
videdfortheinstallationoftheFAB-1100forced
air blower kit (optional). Electrical power must
be provided to this plate to operate the blower.
The gas control valve is located in the lower
control compartment. To access the valve
open the lower control compartment door
(Figure 12 ). The control valve has a 3/8" NPT
thread inlet port and is fitted with a 3" (76 mm)
long nipple, 3/8" NPT on both ends.
Turn on gas supply and test for gas leaks,
using a gas leak test solution (also referred to
as bubble leak solution).
Route a 3-wire, 120Vac power line with control
switch to the lower left front corner of the
appliance. Supply wires are to be connected to
the outlet as shown in Figure 15, ensuring that
the polarity (as determined by the colors of the
wires) is exactly as shown. The black and red
wire loop must be left intact, with the mating
connectors connected.
Plan the connections accordingly. We recom-
mend that the gas line be routed for the left
side of the appliance to ensure adequate ac-
cess to the rear lower compartment for instal-
lation and servicing of the optional FAB-1100
blower.
Note: Using a soapy water solution (50% dish
soap, 50% water) is an effective leak test
solution but it is not recommended, because
the soap residue that is left on the pipes/
fittingscanresultincorrosionovertime. Never
use an open flame to check for leaks.
A. Light the appliance (refer to safety and
lighting instructions on pages 18 and 19) (See
*Note).
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT: Ground lead must be connected
tothegreenscrewlocatedonthejunctionbox
cover plate. Failure to do so will prevent the
appliancefromoperating.Theappliancemust
be electrically grounded in accordance with
localcodesor,intheabsenceoflocalcodes,the
National Electrical Code, ANSI/NFPA 70-(latest
edition). (In Canada, the current CSA C22-1
Canadian Electrical Code.)
VF5000/VF6000 Series
VF5000/VF6000 Series
Optional Wiring Diagram
Standard Wiring Diagram
If any of the original wire as supplied must be replaced, it
must be replaced with Type AWM 105°C – 18 GA. wire.
If any of the original wire as supplied must be replaced, it
must be replaced with Type AWM 105°C – 18 GA. wire.
From Thermocouple
From Thermocouple
Optional ON/OFF
Wall Switch/Rocker Switch
*
*
*
*
Thermopile
Thermopile
The forced air blower kit may be mounted at
initialapplianceinstallationoratanytimethere-
after. Follow the instructions provided with the
blower kit.
* For Rocker or ON/OFF Wall Switch Attachment Only.
Factory Wired
Field Wired
Finished Wall Details
* For Rocker Switch Attachment Only.
Figure 13
It is sometimes best to frame the appliance
afterithasbeenpositionedinplace. Framewith
2 x 4s or heavier lumber. Always frame in
accordance with local building codes.
Figure 14
OFF/ON Blower
Wall Switch
Note: The header may rest on the top spacers
but must not be notched to fit around them.
To Fuse or
Circuit Breaker
Black
Inordertoinstalltheappliancefacingflushwith
the finished wall, position the framework to
accommodatethethicknessofthefinishedwall
(Refer to Figures 2 and 3 ).
120V
AC
Receptacle
}
White
60Hz
Fireplace
Junction Box
Blower Wiring Diagram
If you live in a cold climate, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter the
room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level.
Ground Wire
Connection
White
(Supply)
Blower
(Lower)
Outlet
Proceed to Step 12.
120 Vac
60 Hz
Bipolar
Terminal
Screw
Surround Installations
Black
Wire
Black
(Supply)
Note: The VF5000/VF6000 series appliances
must be installed giving full consideration to
the clearance and height requirements identi-
fied in this manual.
Mating
Connectors
Red Wire
Figure 15
Note: Supply wires may be alternatively connected to the outlet using the screw terminals,
however the black supply wire must be ganged wired to the same terminal that the pre-wired black
wire is attached to and the white supply wire must be connected to the opposite side of the outlet.
Figure 16
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 8. Position Heater – Place the heater in
desired location. It may be helpful to tempo-
rarily assemble the surround around the appli-
ance to properly locate the unit. Refer to
Figure 16 for floor and platform installations.
If the heater is to be installed into a framed wall
refer to the built-in assembly steps beginning
on page 4.
WARNING: FAILURE TO POSITION THE
PARTS IN ACCORDANCE WITH THESE
DIAGRAMS OR FAILURE TO USE ONLY
PARTS SPECIFICALLY APPROVED WITH
THIS HEATER MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY.
WARNING: DO NOT PLACE ANY LAVA
ROCKONLOGSORBURNERS. THISMAY
CAUSE SOOTING.
Step 13. The heater includes a unitized set of
ceramic fiber logs. Handle these logs with
great care. The logs can be easily damaged,
but when handled properly they can provide
years of performance and enjoyment.
Flame Appearance
Note: The heater may be installed directly on a
floor made of standard combustible wood con-
struction materials. Do not install the heater
directly on carpeting or other soft floor cover-
ing such as vinyl tile or flooring materials. Use
a wood or metal panel that extends the full
width and depth of the heater between the
heater and any soft floor covering material.
RefertoFigures26and27forbasedimensions.
REFER TO THE OPERATING INSTRUCTIONS
LOCATED AT THE BACK OF THIS MANUAL
BEFORELIGHTINGTHEHEATERTOOBSERVE
THE FLAMES.
Position the unitized log set unto the burner as
shown in Figure 17.
Flames from the pilot, front and rear burner
should be visually checked as soon as the
heater is installed. In addition a periodic visual
check of the flames should be made. The pilot
flameshouldalwaysbepresentwhentheheater
is in operation and should just envelope the tip
of the thermocouple (Figure 18 ).
Step 9. Secure Heater – Bend the tabs down
(Figures 2 and 15 ). Using two (2) screws
securely tighten the appliance to the platform.
Note: Heater must be anchored to the floor or
platform.
WARNING: NO ADJUSTMENTS ARE TO
BE MADE TO THE ODS PILOT SYSTEM.
TAMPERING WITH THIS SYSTEM CAN
BE EXTREMELY HAZARDOUS.
Step 10. Install Optional 120V Wiring – Refer
to Step 5 for wiring instructions.
Connecting Gas Line
Step 11. A qualified gas appliance installer
must connect the gas room heater to the gas
supply.
Consult all local codes and refer to Step 5.
The heater gas inlet connection is 3/8" NPT,
located on the left side facing the heater. If a
right side connection is required, the connec-
tion pipe may be piped under the rear of the
appliance to end at the left hand side for con-
nection to the inlet.
Figure 18
An incorrect pilot flame is shown in Figure 19.
This pilot flame will cause the thermocouple to
cool. Whenthethermocouplecools, theheater
will shut off. If pilot flame pattern is incorrect,
or if heater shuts off, contact your service
representative.
When tightening up the joint to the valve hold
the valve securely with a wrench to prevent the
valve from moving.
Step 12. For Surround Installations Only –
Finish the assembly of the surround compo-
nentsandsecurethesurroundtotheappliance.
Assembling the Logs
Figure 17
WARNING: DO NOT ADD EXTRA LOGS
OR ORNAMENTS SUCH AS PINE CONES,
VERMICULITE OR ROCK WOOL. USING
THESE ADDED ITEMS CAN CAUSE
SOOTING.
After setting the logs into position as shown
above, ensure they are properly and firmly
situated. The heater will not function as in-
tended if the logs are not correctly positioned.
Figure 19
Periodically check the positioning of the logs.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
The pilot flame should be steady, not lifting or
floating. Flame should be blue in color with
traces of orange at the outer edge.
In normal operation, at full rate, after 15 min-
utes the following flame appearance should be
observed:
OPTIONAL EQUIPMENT
An incomparable package of options are avail-
able for use with these appliances. These op-
tionscanbothcustomizetheoperationofthese
unique appliances and enhance their beauty
and charming appeal. All options are available
in kit form, are easy to install and are packaged
complete with all required parts and instruc-
tions. Some of the option kits need to be fitted
prior to completing the installation of the appli-
ance. The following paragraphs detail the kit
options available for use with the appliances
covered in this manual.
The top 3/8" (10 mm) at the pilot generator
(thermopile) should be engulfed in the pilot
flame (NG only).
Rear Burner Flame Characteristics – The
rear flames should be yellow. The flames
should extend about 3 – 4" above the center
log (front of the unitized log group) for natu-
ral gas and 2 – 3" above for propane (L.P.G.)
gas (Figure 20 ).
Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the optional
remote wall switch (if installed) and rotate the
gas valve control knob counterclockwise to the
“ON” position.
Step 15. Installing the Optional Screen As-
sembly – Retrieve the screen door frame. Po-
sition the door frame in front of the firebox
opening in the brackets at the base of the
fireplace front opening. Lean the door frame
back towards the fireplace ensuring that the
frame seats evenly as it draws shut.
These outstanding optional items can be added
individuallyorinsetsoftwoormoretocustom-
ize your vent-free appliance to fit your homes
unique needs. Kit part numbers are provided
on pages 16 and 17 along with descriptive
illustrations.
Figure 20
The appliances covered in this manual are
heater rated and produce a great deal of heat.
Decorative brass trim pieces and hoods may
tarnish because of their proximity to the heater
opening and front face. Tarnishing of these
pieces is normal, unavoidable and should be
expected.
Installing the Optional Glass Door
Main Burner – The flames at the front burner
holes will be blue becoming yellowish as they
hit the bark-like texture of the base and front
face of the center log (front of the unitized
group) (Figure 20 ).
Position the door frame in front of the firebox
opening, with the joint in the gasket down.
Locate the three (3) tabs at the bottom edge of
the door frame into the three (3) brackets at the
base of the fireplace front opening. Lean the
doorframebacktowardsthefireplaceensuring
that the frame seats evenly as it draws shut.
Appliance Operation
Forced Air Kit
WARNING: THE LOWER CONTROL COM-
PARTMENT AREA AND LOWER CONTROL
COMPARTMENT ACCESS DOOR ARE EX-
TREMELY HOT WHEN THE APPLIANCE IS
INOPERATION. EXERCISEEXTREMECARE
WHEN ACCESSING THIS AREA. TOUCH
ONLY THE FAR ENDS OF THE LOWER
CONTROL COMPARTMENT DOOR WHEN
OPENING WHILE THE APPLIANCE IS HOT.
Install the three (3) 1/4"-20 x 1" Phillips pan
headscrewsremovedpreviouslyandtightento
secure. Ensure that the tab on the bottom of the
door frame engages the door switch.
The FAB-1100 assembly provides a forced air
circulation feature for your appliance. This kit
mounts directly into the lower intake chamber
withanelectricalconnectionmadeattherecep-
tacle provided. The appliance must have an
independent120Vacpowerlineincorporatedat
the time of installation. Refer to Step 6 of the
installationinstructionssuppliedwiththeforced
air kit (Figures 22 and 23 ).
Make sure the screws are tightened equally to
avoid torquing the door (Figure 21 ).
Step 14. Checking the System – With gas line
installed run initial system checkout before
closing up the front of the unit. Follow the pilot
lighting instructions on page 16.
Screws
Note: Instructions are also found on the pull
out panel located on the bottom surface of the
appliance.
When first lighting the appliance, it will take a
few minutes for the line to purge itself of air.
Once purging is complete, the pilot and burner
willlightandoperateasindicatedintheinstruc-
tion manual. Subsequent lightings of the appli-
ance will not require such purging. Inspect the
pilotflame(removelogs,ifnecessary,handling
carefully).
Figure 22
Figure 21
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Decorative Volcanic Stone
Screen Panel Kit
Blower Motor
The decorative volcanic stone, Model FDVS,
can be used to enhance the look of your appli-
ance. Spread the decorative volcanic stone
evenly around the bottom of the firebox.
Anoptionalscreenpanelcanbeinstalledonthe
VF5000/VF6000SeriesUnits.Thisscreenpanel
is easy to install. This kit can be retrofitted to
previouslyinstalledVF5000/VF6000appliances.
Grounded
to Appliance
Refractory Liner Kit
One Piece Arch Kit
Motor Plug
Oneofthemostbeautifulenhancementsyoucan
make to this appliance is the addition of refrac-
tory liners. The refractory liner kit includes tan
ceramicfiberpanelsfortherearandsidewallsof
the firebox. The ceramic fiber panels have brick-
like features in relief. To install the three panels,
simply place them in position against the firebox
walls. This kit can be retrofitted into previously
installed appliances.
A one piece complete door arch kit is available
for use with VF appliances fitted with the op-
tional GDK-5/6 door. This kit is easy to install
and does not require hardware to attach it to a
previously installed optional door frame. The
kit can be retrofitted to previously installed
appliances.
Receptacle
120V
Appliance Junction Box
Figure 23
Gas Flex Line with Valve
Glass Door Kit
Remote Control Kit
A gas flex line kit is available to aid in attaching
the appliance to the gas supply. This kit can
only be used where local codes permit. The kit
includes a 1/2" NPT to 3/8" flare in line shut-off
valve, a 12" flex line 3/8" female flare through
and a 3/8" flare to 3/8" NPT fitting. The compo-
nents of this kit are rated for both natural and
propane gas. This kit is designed to be used as
an aid in installing the appliance.
Optional glass door kits are available for use
with both the VF5 and VF6 appliances. These
doors elegantly provide protection for the logs
while helping to prevent the buildup of con-
taminates such as pet hair, carpet lint and dust
on the burner ports. Use the GDK-5 with VF5
appliances and the GDK-6 with VF6 appli-
ances.
The Model RCL adds the convenience of re-
mote control for your appliance. The kit in-
cludes a wireless, hand held transmitter and a
receiver that replaces the wall switch. This
special receiver permits either manual or re-
mote control modes. Both receiver and trans-
mitter operate on standard 9 volt batteries (not
included). Refer to the RCL installation instruc-
tion for specific details.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OFHIGHSURFACETEMPERATURES.USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE SUPER-
VISED WHEN THEY ARE IN THE SAME
ROOM AS THE APPLIANCE.
Solid Brass Hood Kit
Wall Switch Kit
An attractive solid brass hood kit is available
for use with these VF appliances. The brass
hood kit is designed to be fitted to your appli-
ance above the door. In addition to providing
an aesthetically pleasing appearance to your
appliance installation, the hood reduces heat
effects to decorative mantles and finish mate-
rials located directly above the fireplace open-
ing. The hood kit includes the necessary
attaching hardware. This kit can be retrofitted
to previously installed appliances.
An optional wall switch kit can be installed
along with all vent-free appliances. The kit
consists of a standard UL wall switch with
cover plate. This kit provides for remote (wall)
operation of the appliance. Replace the wall
switch and cover plate of this kit with the
componentsoftheFWSKandyoucanhavetrue
remote control of your vent-free appliance,
turning it on and off from your favorite easy
chair. The wall switch kit should be installed
along with the appliance. Refer to Figure 14
andStep6fordetailedinstallationinstructions.
Wall Thermostat Kit
A wall thermostat kit is available for use with
these appliances. The wall thermostat is de-
signed to be wired directly to the appliance
millivolt gas control circuit and provide auto-
matic On/Off control of the appliance to main-
tain a desired temperature within the room.
Solid Brass Louver Kit
Solid brass louvers are available for use with
these appliances. These louvers are designed
to replace the standard black louvers that are
provided with the appliance. The brass louver
kit includes four (4) louvers that simply snap
into place. They provide a touch of elegance to
the VF appliance. This kit can be retrofitted to
previously installed appliances.
Rocker Switch Kit
An optional rocker switch kit can be installed
directly on all VF5000/VF6000 series appli-
ancestoprovideforOnandOffoperationinlieu
of a wall switch. This kit is designed to install in
the lower control compartment out of view and
is perfect for use in high volume areas such as
lobbiesandmodelhomeswherelimitedaccess
totheapplianceOn/Offswitchisdesirable. This
kit can be retrofitted to previously installed
appliances and may be temporarily installed in
place of other switch circuitry.
Brass Square Surround Kit
Decorativebrasssquaresurroundkitsareavail-
able for use with these appliances. The BSK-5
andBSK-6aredesignedtoattachdirectlytothe
front face of the appliance at its extreme edges.
The brass square surround kits provide a pic-
ture frame finish for the appliance 2-1/2" wide.
Use the BSK-5 with VF5 appliances and the
BSK-6 with VF6 appliances. The brass square
surround kit can be retrofitted onto previously
installed appliances.
NOTE: DIAGRAMS & ILLUSTRATION NOT TO SCALE.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
|