State Industries Water Heater SBD30 150 User Manual

SERVICE HANDBOOK  
®
SandBlaster  
Self-Cleaning Induced Draft Multi Flue  
Commercial Gas Water Heaters  
M O D E L S C O V E R E D  
SBN71 120 Through SBN85 390 (A)  
Series 108 Models and  
SBD30 150, SBD30 199  
Booster Heaters  
SBN Meets Low NOx Requirements of SCAQMD  
Rules 1121 & 1146.2  
Part Number 317927-000  
Printed in the U.S.A. - 0D8o1w0nload from Www.Somanuals.com. All Manuals Search And Download.  
COMMERCIAL  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED  
INTERPRETATION.............................................................................................................................33  
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED  
INTERPRETATION.............................................................................................................................34  
TEST 2 – POLARITY CHECK.............................................................................................................35  
TEST 3 - CONTINUITY CHECK OF HIGH LIMIT (ECO)....................................................................36  
TEST 4 - UPPER TEMPERATURE PROBE CONTINUITY CHECK..................................................37  
TEST 5 - CALLING FOR HEAT – NO INDUCER OPERATION.........................................................38  
TEST 6 - INDUCER ON.............NO IGNITION..................................................................................39  
TEST 7 – INDUCER ON, PROVER SWITCH AND LOW GAS PRESSURE SWITCH CLOSED  
....................NO IGNITER OPERATION.............................................................................................40  
TEST 8 – IGNITER HEATS .............. NO MAIN BURNER.................................................................41  
TEST 9 – IGNITER HEATS .......NO MAIN BURNER.........................................................................42  
TEST 10 - MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS.............................................43  
TEST 11 - WATER HEATER SHUTTING OFF BELOW SETTING....................................................44  
DISPLAY LIGHTS ON INTEGRATED WATER HEATER CONTROL................................................45  
PARTS SBN71-120 thru 85-390 series 100.......................................................................................46  
PARTS SBN71-120 thru 85-390 series 100.......................................................................................47  
PARTS SBN71-120 thru 85-390 series 100.......................................................................................48  
PARTS SBN71-120 thru 85-390 series 108.......................................................................................49  
PARTS SBN71-120 thru 85-390 series 108.......................................................................................50  
PARTS SBN71-120 thru 85-390 series 108.......................................................................................51  
PARTS SBD30-150/199NE.................................................................................................................52  
PARTS SBD30-150/199NE.................................................................................................................53  
SBN 71-120 thru 85-390, SBD30-150/199 SERVICE HANDBOOK INTRODUCTION  
This service handbook is a supplement to the SBN and SBD151/201 Installation and  
Operation Manual. The handbook provides information on servicing and troubleshooting State  
SBN/SBD30-150/199/ water heaters in the field. While this handbook is not intended to be all  
inclusive, it contains:  
• step-by-step procedures with illustrations to verify proper installation, operation,  
and troubleshooting  
• quick reference data to assist in servicing the product line  
• answers to common questions encountered in the operation of the product line.  
The handbook is intended to be used by licensed plumbing professionals. Reference should  
be made to the installation manual accompanying the product. If you are experiencing a  
problem not covered in this handbook, please contact the State Technical Information  
Department at 1-800-365-0024 or your local State Water Heater representative for further  
assistance. No duplication or reproduction of this book may be made without the expressed  
written authorization of the State Water Heaters.  
State Water Heaters  
2
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
QUALIFICATIONS  
Installation or service of this water heater requires ability equivalent to that of a licensed  
tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical testing  
skills are required.  
TOOLS REQUIRED  
Phillips head screwdriver  
standard screwdrivers  
3/8 and 7/16 inch open end wrench  
• set of marked drill bits  
electrical multimeter tester capable of measuring continuity, AC voltage and DC  
voltage  
• gas pressure gauge or manometer  
• water pressure gauge  
• thermometer (range 0 - 220 degrees F)  
• 1/2 inch socket with extension for removal of the clean out cover  
• 1-1/16 inch socket with extension for anode removal  
COMMERCIAL TANK TYPE GAS MODEL NUMBER BREAK DOWN  
Rev. 1 Adds SBD30-150 and 30-199 models with parts lists. Adds SBN series 108 parts list.  
State Water Heaters  
3
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
INSTALLATION CONSIDERATIONS - CLEARANCES  
This portion of the handbook reviews some often overlooked installation considerations  
clearances, air supply, gas pressure requirements, and venting—taking note of necessary  
installation requirements for SBN and SBD30-150/199 . The installation manual covers most  
of these items in detail.  
A 24-inch clearance for all serviceable parts is recommended. Clearances may vary between  
models. See instruction manual or the label on the heater for clearances applicable to your  
specific model.  
TOP AND FRONT VIEWS OF MINIMUM CLEARANCES TO COMBUSTIBLES  
State Water Heaters  
4
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
MINIMUM CLEARANCE TO COMBUSTIBLES  
Model Number  
"A" Right Side  
"B" Left Side  
"C" Back "D"  
Ceiling  
SBN-120 thru  
200A  
2"  
2"  
2"  
12"  
SBN-250/A thru  
310/A  
3"  
3"  
3"  
12"  
SBN-366  
6"  
4"  
2”  
6"  
4"  
2”  
6"  
4"  
2”  
6"  
4"  
SBN-390  
SBD30-150/199  
12”  
A, B, and C clearances to non-combustibles is “0” inches - a 12 inch clearance to cover remains  
unchanged.  
State Water Heaters  
5
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
REQUIRED EXTERIOR CLEARANCES  
The illustration below shows the required clearances for venting units using natural draft  
venting.  
The vent must extend at least 3 feet above the highest point where it passes through a roof of  
a building and at least 2 feet higher than any portion of a building within a horizontal distance  
of 10 feet (for vents of 12 inches in diameter or less).  
References: NFPA 54 2006; ANSI Z 223.1 SEC 12.6.2 and Sec12.7.2 may allow reduction to  
8 feet with a “listed vent cap.”  
Copyright by the American Gas Association. Used by permission of the copyright holder”.  
State Water Heaters  
6
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
REQUIRED EXTERIOR CLEARANCES  
Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1,000  
BTUH of gas supplied. The National Fuel Gas code also recommends an additional 2.5 cubic  
feet of “excess” air. For information on minimum make-up air opening sizes for various  
building installations, refer to the National Fuel Gas Code NFPA 54, ANSI Z223.1, Sec. 5.3  
INSUFFICIENT MAKEUP AIR ........ NEGATIVE AIR PRESSURE .....DOWNDRAFTS  
One common example is in a  
restaurant  
installation  
where  
exhaust vent equipment was not  
considered in sizing make-up  
requirements. This condition may  
result in air being back drafted by  
the restaurant exhaust equipment  
through the heater causing the draft  
proving switch to open and/or  
erratic heater shutdown.  
State Water Heaters  
7
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
MAKE-UP AIR – DIRECT COMMUNICATION WITH OUTDOORS  
A fresh supply of make-up air for combustion can be supplied to the heater through  
make-up air ducts, which directly communicate with the outdoors.(Not Direct Vent)  
Two openings are required: one within 12 inches of the top of the enclosure and one within 12  
inches of the bottom of the enclosure. Each opening must have a free area of not less than 1 square  
inch per 4,000 BTUH of the total input of all appliances within the enclosure. The lower opening  
primarily provides combustion air. The upper opening provides vent dilution air and acts as a relief  
opening for flue gases should the vent become obstructed or a downdraft condition occur.  
Additionally, when the heater is installed in a confined space and communicating with the outdoor air,  
one permanent opening, beginning within 12 inches (30 cm) of the top of the enclosure, must be  
permitted where the equipment has clearances of at least 1 inch (2.5 cm) from the sides and back,  
and 6 inches (16 cm) from the front of the appliance. The opening must directly communicate with the  
outdoors and must communicate through a vertical or horizontal duct to the outdoors or spaces (crawl  
or attic) that freely communicate with the outdoors, and must have a minimum free area of a) 1 square  
inch per 3,000 BTUH (7cm2 per kW) of the total input of all equipment located in the enclosure and b)  
not less than the sum of the areas of all vent connectors in the confined space.  
State Water Heaters  
8
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
CONTAMINATED AIR  
Along with adequate make-up air, the quality of the air is important. Contaminants in  
combustion air can lead to premature heater failure. Vapors from bleaches, soaps, waxes,  
salts, etc. are drawn into the combustion chamber with the make-up air and, once fired, mix  
with water vapor in the gases to form extremely corrosive hydrochloric or hydrofluoric acid  
and other corrosive by-products.  
AIR FOR COMBUSTION – FLAMMABLE ITEMS  
State Water Heaters  
9
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
GAS VALVE  
The supply gas pressure is normally measured at the gas valve inlet gas pressure tap, if  
available, when the gas is flowing. The manifold gas pressure is measured at the manifold  
pressure tap of the gas valve when the gas is flowing. Gas valves used are 24 volt AC  
combination-step opening gas valves. They incorporate the main valve and gas pressure  
regulator into one body. The Low Gas Pressure Switch, the Supply Gas Inlet, and the Supply  
Gas Pressure Tap are shown in the Inlet View to the right.  
TOP VIEW  
INLET VIEW  
The top view of the gas valve, shown on the right, shows the Main Gas Regulator, Manifold  
Pressure Tap, Top Knob, and the Limited Bleed Vent Port. The main gas regulator is found  
under the silver cap (silver cap for Natural Gas or black cap for Propane) screw. It is factory  
preset to 3.5 inches W.C. and  
adjusts gas pressure output from 3.0 to 5 inches water column. Caution: Always test the  
manifold pressure at the outlet when the gas is flowing.  
State Water Heaters  
10  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
GAS VALVE  
The outlet view of the Gas Valve, shown on the right, shows the Manifold Gas Outlet  
Connection, the two 24 volt Main Valve (MV) Solenoid connections, and the Manifold  
Pressure Tap. The two yellow wires from the 12-pin plug on the Ignition Board attach to the  
MV terminals.  
OUTLET VIEW  
State Water Heaters  
11  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENTING  
All SBN and SBD water heaters are classified by ANSI as Category I (non-condensing,  
negative pressure venting) appliances. They are approved for type B vent. The draft inducer  
does not pressurize the exhaust.  
VENTING – MULTIPLE CATEGORY I GAS WATER HEATERS  
State Water Heaters  
12  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT  
Multiple Gas Fired Tank-Type Heaters  
When venting multiple Category I tank type heaters using Type B vent pipe, follow the  
installation tables below which give sizing and data based upon NFPA 54/ANSI Z223.1-2006.  
Model: SBN 71-120  
Input:120,000 Btu/hr.  
Total Vent Height (feet)  
Vent Connector Size: 5”  
6
8 10 15 20 30 50 100  
Input Btu/hr  
Rise  
1'  
Vent Connector Diameter (inches)  
120,000  
120,000  
120,000  
6
5
5
6
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2'  
3'  
No. of Units  
Combined Input (Btu/hr x 1,000)  
Combined Vent/Manifold Diameter  
2
3
4
240,000  
360,000  
480,000  
7
8
9
7
8
9
6
7
9
6
7
8
6
7
8
6
6
7
6
6
7
6
6
6
Model: SBN 154; SBD30-150  
Input:150,000/154,000 Btu/hr.  
Vent Connector Size: 6”  
Input Btu/hr  
Total Vent Height (feet)  
8 10 15 20 30 50 100  
6
Rise  
1'  
Vent Connector Diameter (inches)  
150,000/154,000  
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
150,000/154,000  
2'  
150,000/154,000  
3'  
No. of Units  
Combined Input (Btu/hr x 1,000)  
300,000/ 308,000  
Combined Vent/Manifold Diameter  
2
3
4
7
8
9
7
8
9
6
7
9
6
7
8
6
7
8
6
6
7
6
6
7
6
6
6
450,000/ 462,000  
600,000/ 616,000  
State Water Heaters  
13  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT  
Model: SBN80-180; SBN100-199; SBN100-200; SBD30-199  
Input:180,000, 190,000 and 199,000 Btu/hr.  
Vent Connector Size: 6”  
Total Vent Height (feet)  
6
8 10 15 20 30 50 100  
Input Btu/hr  
180,000  
Rise  
Vent Connector Diameter (inches)  
1'  
1'  
2'  
2'  
3'  
3'  
7
7
6
7
6
6
7
7
6
7
6
6
6
7
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
199,000/200,000  
180,000  
199,000/200,000  
180,000  
199,000/200,000  
No. of Units  
2
Combined Input (Btu/hr x 1,000)  
360,000  
Combined Vent/Manifold Diameter  
7
7
7
6
6
6
7
7
6
6
6
6
6
7
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
398,000/400,000  
540,000  
3
4
597,000/600,000  
720,000  
796,000/800,000  
State Water Heaters  
14  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT  
Model: SBN100-250  
Input:250,000 Btu/hr.  
Total Vent Height (feet)  
Vent Connector Size: 6”  
6
8 10 15 20 30 50 100  
Input Btu/hr  
Rise  
1'  
Vent Connector Diameter (inches)  
250,000  
250,000  
250,000  
8
7
7
8
7
7
7
7
7
7
7
7
7
6
6
6
6
6
6
6
6
6
6
6
2'  
3'  
No. of Units  
Combined Input (Btu/hr x 1,000)  
Combined Vent/Manifold Diameter  
2
3
4
500,000  
750,000  
1,000,000  
9
9
9
8
8
7
9
7
8
9
7
8
9
12 12 10 10 10  
14 14 12 12 10 10  
Model: SBN100-275  
Input:275,000 Btu/hr.  
Vent Connector Size: 6”  
Total Vent Height (feet)  
8 10 15 20 30 50 100  
Vent Connector Diameter (inches)  
6
Input Btu/hr  
Rise  
1'  
275,000  
275,000  
275,000  
8
8
7
8
8
7
7
7
7
7
7
7
6
6
6
6
6
6
6
6
6
6
6
6
2'  
3'  
No. of Units  
Combined Input (Btu/hr x 1,000)  
Combined Vent/Manifold Diameter  
2
3
4
550,000  
825,000  
1,100,000  
10 9  
9
8
8
9
8
9
7
8
9
7
8
9
12 12 12 10  
14 14 14 12 12 10  
State Water Heaters  
15  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT  
Model: SBN 85-310  
Input:310,000 Btu/hr.  
Total Vent Height (feet)  
Vent Connector Size: 6”  
6
8 10 15 20 30 50 100  
Input Btu/hr  
Rise  
1'  
Vent Connector Diameter (inches)  
310,000  
310,000  
310,000  
9
8
8
8
8
8
8
8
8
8
7
7
7
7
7
7
7
7
6
6
6
6
6
6
2'  
3'  
No. of Units  
Combined Input (Btu/hr x 1,000)  
Combined Vent/Manifold Diameter  
2
3
4
620,000  
930,000  
1,240,000  
10 10 9  
9
8
8
9
7
9
7
8
9
14 12 12 12 10  
14 14 14 12 12 12 10  
State Water Heaters  
16  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
VENT TABLES FOR CATEGORY I - TYPE B GAS VENT  
Model: SBN 85-366NE, SBN 85-390NE  
Input:366,000/399,000 Btu/hr.  
Vent Connector Size: 6”  
Input Btu/hr  
366,000  
Total Vent Height (feet)  
6
8 10 15 20 30 50 100  
Rise  
1'  
Vent Connector Diameter (inches)  
9
9
9
9
8
9
8
8
8
9
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
399,000  
10 9  
366,000  
9
9
9
9
9
9
8
9
2'  
3'  
399,000  
366,000  
399,000  
No. of Units  
2
Combined Input (Btu/hr x 1,000)  
732,000  
Combined Vent/Manifold Diameter  
12 10 10  
9
9
9
9
9
8
8
9
8
8
9
9
798,000  
12 12 10 10  
1,098,000  
14 14 14 12 12 10  
3
4
1,197,000  
14 14 14 12 12 10 10  
1,464,000  
16 16 14 14 14 12 12 10  
16 16 16 14 14 12 12 10  
1,596,000  
State Water Heaters  
17  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
SBN /SBD30-150/199 SEQUENCE OF OPERATION  
Sequence  
2
1. Thermistors (probes) call for heat.  
2. Inducer fan starts and provides draft.  
3. Hot surface igniter = 20 sec. warm-up.  
1
4. Main gas valve opens 4 sec. trial for  
ignition. (Maximum 5 trials.)  
5. Main burner ignites and proves.  
6. Thermostat reaches the temperature  
6
setting.  
7. Main burners “OFF” - Auto restart after  
60 min. - 20 sec blower  
1
4
5 & 7  
3
State Water Heaters  
18  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
COMBINED VENTING  
COMBINING VENTS (MANIFOLDING  
Vent Size  
Area in  
Square  
Inches  
Vent Size  
Area in  
Square  
Inches  
When vents are combined, the area of the  
combined vent should be equal to area of  
the largest single vent, plus 50% of area of  
all others joining.  
5"  
6"  
7"  
8"  
9"  
20  
28  
38  
50  
64  
10"  
12"  
14"  
16"  
18"  
79  
113  
154  
201  
254  
EXAMPLE: To combine two 6” vents with  
an 8” vent, the area of a combined vent  
should be one half area of two 6 inch vents  
(14 + 14) plus area of 8 inch vent (50)  
or 78 sq. inches.  
Referring to chart: 78 sq. inches requires  
a 10” diameter vent.  
Maximize height from water heater vent connection to first elbow or tee.  
State Water Heaters  
19  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
9 RULES FOR GOOD VENTING  
VENT PIPE  
VENT  
CONNECTOR  
1.The vent pipe should ALWAYS be the  
2.  
The diameter of a vent pipe should  
same size as the outlet of the draft hood or  
factory supplied vent reducer.  
Model SBN71-120 is supplied with a  
6” to 5” reducer.  
NEVER be reduced, no matter what the  
circumstances.  
3. In some cases it may be necessary to  
run a vent larger than the vent connector.  
4.  
Take the maximum vertical rise (x)  
possible immediately above the draft hood.  
State Water Heaters  
20 Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
9 RULES FOR GOOD VENTING  
5.Use a 45° elbow in place of a 90° elbow where possible. Avoid the use of a 90° elbow  
immediately above the draft hood. Allow the maximum vertical rise before any elbow.  
VERTICAL RISE  
EQUAL TO  
1/4” PER FOOT OF  
HOROZONTAL  
RUN  
HORIZONTAL RUN  
6.Horizontal pipe should be sloped  
upward at a minimum of ¼” per foot.  
State Water Heaters  
21  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
9 RULES FOR GOOD VENTING  
VENT RUNS  
BEYOND EXTERIOR  
WALLS OR INTO  
UNHEATED AREAS  
SHOULD BE  
DOUBLE WALL.  
HORIZONTAL  
ELEMENTS  
LIMITED TO  
75% OF  
TOTAL  
VERTICAL  
HEIGHT  
7.Horizontal elements should be limited  
8.Flue gases must be kept hot for proper  
to 75% of the vertical rise of the vent above  
the connection.  
venting. Single wall vent exposed to cold air  
may not vent properly.  
9.Obstructions can cause down drafts. The vent pipe should be extended to meet local  
codes.  
State Water Heaters  
22  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
DRAFT PROVING PRESSURE SWITCH - SETTINGS  
Draft Proving Pressure Switch Table  
Pressure Setting  
To Close Switch  
(Inches W.C.)  
SBN  
Models  
SBD  
Models  
366  
275  
(-) 1.60 ± .10"  
(-) 2.00" ± .10"  
(-) 1,75" ± .10"  
(-) 2.40" ± .10"  
(-) 2.60" ± .10"  
(-) 2.50" ± .10"  
310  
120/200  
154/180  
30-150/199  
NOTE: Pressure Switch Contacts are Normally Open “N.O.” and close on a fall in pressure.  
State Water Heaters  
23  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
THERMOSTAT AND IGNITION CONTROL BOARD VIEW  
State Water Heaters  
24  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WHITE RODGERS INTEGRATED CONTROL - THERMOSTAT  
State Water Heaters  
25  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WHITE RODGERS IGNITION CONTROL BOARD  
State Water Heaters  
26  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
GAS CONTROL VALVE / BURNER AREA VIEW  
SBN's  
HSI  
Part Number  
194405  
80 VAC  
Volts AC Nominal  
Ohms Resistance  
11.0 - 20.0 @ 77° F (25°  
C)  
NOTICE FLAME ROD CROSSES PATH OF  
FLAME .1 - .25”  
State Water Heaters  
Ashland City, Tennessee © 2007  
27  
Technical Training Department  
317927-000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WIRING DIAGRAM  
State Water Heaters  
28  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
ELECTRICAL SEQUENCE – SBN, SBD30-150/199  
1. Switch Power on to unit.  
2. Thermostat calls for heat.  
3. Ignition Control Board performs diagnostic check on system components.  
4. On completion of diagnostics check, the Ignition Control Board sends signal to  
Exhaust Inducer.  
5. Exhaust Inducer begins drawing air through appliance closing the Prover Switch.  
6. On completion of Prover Switch engagement, the Ignition Control Board begins  
the ignition cycle.  
7. The Ignition Control Board provides power to the Silicon Nitride Ignitor.  
8. The Silicon Nitride Ignitor heats up for approximately 17 to 20 seconds.  
9. At the end of Silicon Nitride Ignitor’s warm-up, the Ignition Control Board opens  
the Gas Valve.  
10. From the time the Gas Valve opens, the Ignition Control Board waits 3 seconds  
and then shuts off power to the Silicon Nitride Ignitor.  
11. From the time the Silicon Nitride Ignitor’s power is shut off, the Ignition Control  
Board waits 3 more seconds to monitor the Flame Sensor.  
12. If the Flame Sensor does not detect a strong enough flame, the Ignition Control  
Board shuts off the Gas Valve and allows the Exhaust Inducer to purge the  
unit for 20 seconds. At that time, the Ignition Control Board restarts with step  
7. It will try and ignite the main burners 2 more times. If the unit does not light,  
the Ignition Control Board will wait one hour and then re-start at step 3. This  
cycle will continue until the unit lights or the power is shutoff to the unit.  
13. If the Flame Sensor detects a strong flame, the Ignition ControlBoard will allow  
the unit to operate until the thermostat is satisfied.  
14. Once the unit is satisfied, the Ignition Control Board will shut off the Gas Valve  
and the unit will be in standby mode until another call for heat is initiated by  
the thermostat.  
.
State Water Heaters  
29  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
OPERATING SEQUENCE – FLOW CHART  
State Water Heaters  
30  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
DIAGNOSTIC SEQUENCE OF OPERATION – FLOW CHART  
State Water Heaters  
31  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PRE-SERVICE CHECK LIST  
Use the following checklist BEFORE you begin servicing the water heater.  
1. Have you removed the cover from the controls?  
____________________________________________________  
Did you take notice of the status lights on the upper water  
heater control?  
____________________________________________________  
Did you take notice of the red LED in the upper left corner of  
the lower ignition control?  
____________________________________________________  
2.Did you note conditions of the room?  
____________________________________________________  
Where does the supply air come from?  
____________________________________________________  
Is the room clean?  
____________________________________________________  
What is stored with the heater?  
____________________________________________________  
How is the heater vented?  
____________________________________________________  
Are all water and gas shut-off valves open?  
____________________________________________________  
Are there room exhaust or air intake fans?  
____________________________________________________  
3. Did you note the condition of the heater?  
____________________________________________________  
Is the ON/OFF switch “On”?  
____________________________________________________  
What is the temperature of the stored water? (Test at T&P valve or nearby faucet.)  
____________________________________________________  
Is the thermal expansion tank installed?  
____________________________________________________  
4. Did you write down the complete model and serial number of the water heater? If so,  
what are they? ____________________________________________________  
5. Does the heater have a good ground wire connection? If not, the inducer will typically  
come on for a short time (3-5 seconds), then go off, and the red LED will flash 8  
times.  
State Water Heaters  
32  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED  
INTERPRETATION  
TEST 1 – 120VAC POWER CHECK  
No Green display “Power” LED on.  
Plugs are in receptacles.  
Supply power breaker is not “open”  
On/Off heater switch is “On”.  
White Rodgers  
Integrated Control  
120 V. AC check to water heater ON/OFF switch  
TEST 1  
Check for 115-125 V. AC black wire to ground\  
115 V. AC check to E13 Terminal and 2B receptacle.  
IF.........  
Then............  
voltage is not present from on/off switch center  
Check conditions above  
black wire to ground  
Check wiring from switch to break box  
Power is present from center on/off terminal  
Voltage is not present at E13 to ground  
Power is present at E13  
Check power from on/off switch to ignition board terminal  
E13  
check wiring from on/off. Left-outside terminal to E13.  
Replace on/off switch.  
Check power from E14 to water heater control E2 receptacle  
Voltage is not present from water heater control receptacle  
E2 black to ground  
Check wiring from ignition control board E14 to water heater  
control receptacle E2.  
Replace ignition control board.  
Power is present at E2.  
Green LED should be on.  
State Water Heaters  
33  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
WATER HEATER CONTROL BOARD TROUBLESHOOTING AND DIAGNOSTIC LED  
INTERPRETATION  
Conditions:  
Power On  
Red, heater control “Call for Heat” LED – on  
Red, ignition control board diagnostic LED – Flashing  
Note LED Flash Code before resetting heater.  
LED Status  
1 Flash  
Indication  
System is in lock out.  
2 Flashes  
Draft proving (pressure) switch failed to open within 5 seconds at the end of the last  
cycle.  
3 Flashes  
Draft proving (pressure) switch failed to close ( -2.1 inches of water column pressure)  
within 5 seconds after the inducer was started. The low gas pressure switch )closes  
at 5.2" ± .04" w. c.) may have remained open (Nat Gas only.)  
4 Flashes  
Open on high temperature limit switch (ECO).  
Not Used  
5 Flashes  
6 Flashes  
115-volt supply power connection is indicating reversed polarity.  
Flame sensor reads a low flame signal for more than 4.25 sec.  
No ignition sensed.  
7 Flashes  
8 Flashes  
Continuous Flash  
Continuous ON  
Continuous flame sensed for more than 5 seconds without gas valve being energized.  
Internal control board failure.  
*Control system self adjusts to use a minimum voltage for ignition. Lower voltage results in lower IGNITOR  
temperature which results in longer IGNITOR life. IGNITOR voltage may vary from Nominal 80 VAC.  
State Water Heaters  
34  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 2 – POLARITY CHECK  
Conditions:  
No hot water  
Green “Power” LED is on.  
Tank is more than 5° F below  
temperature dial setting.  
Red ignition control board diagnostic  
LED is flashing 6 times between  
pauses.  
Red, diagnostic “Call for Heat” LED-  
OFF.  
Polarity Check  
TEST 2  
Check from on/off switch center and white wire terminals to ground  
115-125 VAC is not present  
see Test 1.  
Voltage is present white (right terminal) to ground but not  
black (center terminal) to ground  
reverse supply wire connections - polarity is  
reversed.  
State Water Heaters  
35  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 3 - CONTINUITY CHECK OF HIGH LIMIT (ECO)  
Conditions:  
0.0  
Ohms  
Power On – No Hot Water  
Red, heater control “Call for Heat”  
LED – on  
Red ignition control board  
diagnostic LED – 4 Flashing  
Note LED Flash Code before  
resetting water heater control.  
See Description of diagnostic LED  
Flashes.  
Turn Power “Off”  
Continuity check of ECO (energy cut-off, high limit)  
TEST 3  
Black to Black wires of upper probe. Power is off.  
then.....  
If…  
continuity is indicated (ZERO “0.0” Resistance)  
continuity is not present (meter reads “0.L”)  
water is less than 120° F  
opens at 203° F; closes at 193° F. If water is  
below 193° F, continuity is correct.  
replace ECO sensor, if water temperature is  
below 193° F.  
reset status LED should be on.  
•replace heater control if control will not manually  
reset.  
State Water Heaters  
36  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 4 - UPPER TEMPERATURE PROBE CONTINUITY CHECK  
Conditions:  
Power On - Water below temperature  
set point.  
Red, water heater control “Reset  
Status” LED-OFF  
Call For Heat” LED off.  
Ohms Resistance Table  
° F  
Ohms  
11,884  
3,759  
2,488  
1,169  
70°  
120°  
140°  
180°  
Upper Temperature probe continuity check  
TEST 4  
Red wire to red wire - Turn supply power "Off" for this test  
If…  
then.....  
Test indicates no continuity  
Continuity is indicated  
Replace probe.  
Probe should be okay (also verify Ohms  
resistance for water temperature). (Reading will  
be approximate.)  
State Water Heaters  
37  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 5 - CALLING FOR HEAT – NO INDUCER OPERATION  
Conditions:  
Water Heater Control - Thermostat  
Power on  
Plugs in Receptacles  
Red “ Call for Heat” LED-ON  
Inducer “Off”  
Note flash code on ignition control board  
diagnostic LED  
“call for heat”  
LED Indicator  
“diagnostic LED  
indicator”  
120  
If…  
then........  
Pin 1 to ground check has no voltage  
reset control by interrupting power - note  
possible reasons for this from flashing LED code  
replace ignition board  
Pin 1 to ground has voltage  
Proceed  
Pin 3 to ground has no voltage  
•check wiring harness and plugs  
replace inducer  
State Water Heaters  
38  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 6 - INDUCER ON.............NO IGNITION  
Conditions:  
Power on  
Plugs in receptacles  
Inducer operating  
No power to Hot Surface IGNITOR  
(HSI) Note LED flash code  
INDUCER EXHAUST/  
VENT CONNECTION  
DRAFT PROVING  
PRESSURE  
SWITCH  
LOW GAS  
PRESSURE  
SWITCH  
INDUCER  
MOTOR  
24 VAC Check of Blower Prover/Low Gas Pressure Circuit  
TEST 6  
If…  
then........  
ignition board receptacles E1, Pin 7 to ground shows no voltage replace Ignition board  
E1, Pin 7 has 24 Volt to ground  
check wire connection to and from inducer  
voltage check of each blower switch terminal to ground shows  
voltage to only 1 terminal  
Switch is open - check for proper draft (should also see LED 3 flash  
code)...Check for blocked exhaust.... Check that blower outlet exhaust  
damper is open....Replace blower (draft) proving switch  
Natural Gas ONLY!  
24V is present from each switch terminal to ground  
Check wiring from blower switch to low gas pressure switch  
Voltage check to each terminal of low gas pressure switch and  
ground shows only voltage on 1terminal  
Switch is open - test for a minimum of 5.2 ± " W.C. Natural Gas or  
10.5" Propane, flowing supply gas pressure (should also see 3 Flash  
LED code)..............Replace low gas pressure switch  
Voltage is present to each pressure switch terminal and ground  
Check wiring from low gas pressure switch to ignition board  
receptacles E1, Pin 10  
State Water Heaters  
39  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 7 – INDUCER ON, PROVER SWITCH AND LOW GAS PRESSURE SWITCH  
CLOSED ....................NO IGNITOR OPERATION  
Conditions:  
Power on  
Plugs in receptacles  
Inducer on  
24V at ignition board E1, Pin  
10  
CHECK E1PIN 10 TO  
GROUND – 24 V.  
CHECK E4 PIN 4 TO GROUND  
CONTINUITY TEST E4  
PLUG  
No Power to IGNITOR  
Note:LED Flash code  
Voltage check and continuity check of hot surface IGNITOR  
circuit  
TEST 7  
Continuity check - Power off- Plug removed from E4 receptacles.  
Nominal 80 VAC check - Plug in E4- Power "On".  
then.......  
If.......  
Continuity is not indicated between E4plug pin 2 to 4.  
Check wiring and connection from E4 plug to HSI receiving  
plug...................Replace HSI Assembly  
Continuity is present  
Resistance should be between 11 and 20 Ohms at a  
temperature of 77°F  
Voltage is not present between E4, Pin 2 to ground  
Voltage is present  
Replace ignition board  
Continue  
Voltage is not present between E4, Pin 4 to ground  
Voltage is present  
Check wiring and plug connections to HSI.........Replace HSI  
Note ignition board, Flash code LED.............HSI should work  
State Water Heaters  
40  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 8 – IGNITOR HEATS .............. NO MAIN BURNER  
24 V.  
E1 PLUG TO  
PIN 9  
E1 PLUG TO  
PIN 12  
TEST 8  
IGNITOR HEATS......NO MAIN BURNER  
If.......  
short heat up time of IGNITOR  
then........  
Check control box grounding.  
Normal (Approximate 20 seconds) warm up - no ignition  
Check for 24V from E1, Pin 12 to ground during 4 second trial.  
........Yes - Continue................No - Replace Ignition Board  
No voltage present E4, Pin 12 to ground  
Replace ignition board  
24 Volt was present from E1, Pin 12 to ground, but no  
main burner  
Check that air has been purged from gas circuit........check that  
wiring and connections to gas valve and E1, Pin 9 are correct  
.........check for 24 VAC at E1, Pin 9 to ground during 4 second  
trial for ignition.  
State Water Heaters  
41  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 9 – IGNITOR HEATS .......NO MAIN BURNER  
Conditions:  
Test 8 completed then:  
Turn off power  
Disconnect wires from gas valve  
TEST 9  
IGNITOR HEATS – NO MAIN BURNER  
If…  
then.....  
Check meter scale setting to read between 550 and 650 Ohms  
Replace Gas Valve  
Meter reads 0 or 1  
Meter indicates pilot and main coil have  
continuity  
Valve should be okay....still no gas to main burner, then coil  
may be stuck .........Replace Gas Valve  
State Water Heaters  
42  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 10 - MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS  
Conditions:  
Power On – plug connected  
Main Burner ignites for approximately 5  
seconds then goes out.  
Tests 8 and 9 completed  
Note flash code on ignition board LED.  
Hot Surface IGNITOR  
(Illustration of low NOx burner)  
E1, Pin 2 - From Flame Proving Rod  
MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS  
TEST 10  
If.......  
then.........  
No extended main burner ignition  
Check wiring and plug connections of HSI assembly plug  
and ignition board receptacles E1, Pin 2.......Check that HSI  
assembly is not cracked or dirty......Check that flame prover  
will be in main flame ......................Replace HSI assembly  
Still no extended main burner ignition  
Replace ignition control board  
State Water Heaters  
43  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
TEST 11 - WATER HEATER SHUTTING OFF BELOW SETTING  
Conditions:  
Main burner ignited  
Stored water is below temperature setting more than 5° F (Tank  
Average).  
Power off  
Plug disconnected from heater control board receptacle E3 and E4  
TEST 11  
If…  
WATER TEMPERATURE CIRCUIT CHECK - CONTINUITY  
then.....  
continuity check pin to pin of lower  
temperature probe shows 1 or 0 (E4)  
See Test 4  
Check wiring and plug connections to heater  
control board receptacle E4  
Replace lower temperature probe  
continuity check red wire pin to red wire pin  
on upper temperature sensor shows 1 or 0 (E3)  
see Test 4  
Check wiring and plug connections to heater  
control board receptacle  
Replace upper temperature probe  
All above checks are okay  
Replace the water heater control.  
State Water Heaters  
44  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
DISPLAY LIGHTS ON INTEGRATED WATER HEATER CONTROL  
State Water Heaters  
45  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 100  
State Water Heaters  
46  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 100  
State Water Heaters  
47  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 100  
State Water Heaters  
48  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 108  
State Water Heaters  
49  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 108  
State Water Heaters  
50  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBN71-120 thru 85-390 series 108  
State Water Heaters  
51  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBD30-150/199NE  
State Water Heaters  
52  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SBN71-120 thru SBN85-390, SBD30-150/199 TANK TYPE COMMERCIAL  
GAS WATER HEATER SERVICE HANDBOOK  
PARTS SBD30-150/199NE  
State Water Heaters  
53  
Technical Training Department  
Ashland City, Tennessee © 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Prepared by the State Water Heaters Training Department.  
For additional technical information call 800-365-0577.  
State Water Heaters  
500 Tennessee Waltz Parkway  
Ashland City, TN 37015  
800-365-8170  
COMMERCIAL  
©Copyright 2007 State Industries, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Shiro Telephone SC3128 User Manual
Singer Sewing Machine 99K28 User Manual
Soehnle Postal Equipment 2790 User Manual
Sony Indoor Furnishings SU P42T1 User Manual
Sony Stereo Receiver STR DB2000 User Manual
Speco Technologies Portable Speaker SP 5MA User Manual
SPX Cooling Technologies Fan Marley Reflex RTM User Manual
Sunbeam Coffeemaker SPR 062609 User Manual
SWR Sound Stereo Amplifier SM 1500 User Manual
Sylvania MP3 Player SMPK7904 User Manual