Spectra Watermakers Water System MPC 5000 User Manual

Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section 1  
Page Number  
Installation  
Introduction ......................................................................................................................... 5  
Getting Started..................................................................................................................... 6  
Installation Basics ............................................................................................................... 7  
Ventura Plumbing Schematic.............................................................................................. 8  
Feed Pump Relocation ........................................................................................................ 9  
Product Water plumbing ................................................................................................... 10  
Tube Fitting Assembly Procedures ................................................................................... 11  
Wiring................................................................................................................................ 14  
MPC Tank Switch Wiring and operation……………………………………………….. 16  
Z Brane Installation........................................................................................................... 43  
Operation  
New Systems Start Up and Testing................................................................................... 17  
Dry Testing........................................................................................................................ 21  
Normal Start Up Using the Auto Run............................................................................... 22  
Flushing............................................................................................................................. 23  
Manual Operation.............................................................................................................. 24  
Maintenance ...................................................................................................................... 28  
Service & Maintenance  
Long Term Storage Procedures......................................................................................... 25  
Winterizing........................................................................................................................ 27  
Maintenance ...................................................................................................................... 28  
Membrane Cleaning .......................................................................................................... 29  
Suggested Spares............................................................................................................... 31  
Troubleshooting Procedures, Service Bulletins ................................................................ 33  
Part Numbers .................................................................................................................... 46  
Section 2: Programming & Controls  
A-31 MK1 CONTROLS Operation Guide (Single Run Speed mode) ……... …………...5  
Programming from the display…………………………………………….……………..13  
Tank Switch Operation and Installation …………………………………………………16  
Programming from a Computer…………………………………………………………..16  
Software Installation……………………………………………………………………...17  
Software Port Settings …………………………………………………………………...18  
Software Features ………………………………………………………………………..22  
Computer Settings ………………………………………………………………….……25  
Salinity Probe Calibration ……………………………………………………….………26  
Detailed Controls Data……………………………………………….……….…...……..28  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction to the Ventura 150 MPC  
The Ventura represents the finest watermaker for small and midsized yachts available today. The Spectra  
Clark Pump is matched to a 21” high rejection membrane. Properly installed and maintained it will supply  
years of reliable service. The MPC-5000 control provides the ultimate in operational convenience and reli-  
ability. Note that prudent operation is required with any marine equipment. Always maintain enough reserve  
water to get safely into your next port.  
The Spectra High Pressure Intensifier, known as the Clark  
Pump, was introduced in 1997 and has continually im-  
proved since. It holds a lifetime warranty for the original  
purchaser! It is built of modern non-corroding composites.  
Front View  
Pressure relief valve  
Quick disconnect fitting to  
facilitate maintenance.  
Double rubber mounts to  
absorb vibration  
Rear view  
The Clark Pump membrane module.  
Pre-mounted and plumbed together as a single unit.  
Saves time and adds reliability.  
Ventura feed pump inlet module.  
Includes the feed pump, cooling fan, charcoal filter for the flushing  
system, manual flush valve, service valve and service port . Compact  
and streamlined plumbing. Feed pump may be removed and relocated  
if necessary. Cooling fan is included for long life.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
Unpack the system and inspect it to make sure that it has not been damaged in shipment.  
Refer to the shipping list for your system to make sure you have received all of the compo-  
nents listed. Do not discard any packaging until you have found and identified all of the  
parts. The small installation parts are listed on the kit list.  
Warning! We will not be held responsible for shortages and/or freight damage that are  
not reported within thirty days of the ship date.  
Study the system plumbing and wiring diagrams before beginning your installation. This  
will assist you in understanding the function of each component.  
Layout the system. Before starting the installation, identify the location where each module  
and component will be placed. Insure that there is proper clearance around the components  
for removal of filters and system service. Also check to make sure you have adequate tub-  
ing and hose before starting so additional parts may be ordered.  
Ventura MPC Shipping List  
High Pressure Clark Pump and reverse osmosis membrane module.  
Feed pump inlet module with automatic fresh water flush system.  
Accumulator tank  
Seawater strainer  
MPC 3000 control with harnesses  
MPC 3000 display panel.  
Dual filter assembly with pressure sensors  
Installation Fittings Kit  
Service Hose kit  
5/8” Hose (25’) 2 ea  
1/4 product tubing (25’)  
Filter wrench  
Teflon pipe tape  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Basics  
Thruhull  
Not Supplied.  
Read the directions!  
Avoid tight hose bends and excessive runs  
Use heavy gauge wire  
Install feed pump as low as possible  
Use a dedicated thruhull with scoop type strainer  
Flow  
Thru-hulls  
It is mandatory that a dedicated 1/2” to 3/4” forward facing scoop type intake thru-hull and  
seacock be installed. Install the intake for the system close to the middle and as far below the  
water line as possible. Thru-hulls in the bow area are susceptible to air intake in rough condi-  
tions. Sharing a thru-hull with another system is not acceptable and will void the warranty.  
Sharing a thru-hull can introduce unforeseen problems such as intermittent flow restriction,  
air bubbles, and contaminates. For racing boats and high speed power boats above 15 knots a  
retractable snorkel-type thru-hull fitting is preferred to be able to pick up water away from  
the hull.  
Do not install the intake close to or downstream of a head discharge. Install as far below the  
waterline and as close to center line as possible to avoid contamination and air induction.  
The brine discharge thru-hull should be mounted above the waterline, in or just above the  
boot stripe to minimize water lift.  
Double clamp all hose connections below the waterline.  
Pipe Fitting Instruction  
Plastic to plastic fittings should have 3 to 4 wraps of Teflon tape and will thread almost all  
the way in.  
Avoid getting dirt or debris into the piping or hoses during assembly. A small bit of de-  
bris can stop the system! Avoid getting tape over the end of fittings that might get into the  
system. To insure this does not happen, leave the very first thread uncoated.  
Avoid restrictions or long runs on the entire inlet side of the plumbing from the thru hull to  
the main feed pump module.  
Prevent tight bends and excessive elbows. Any restrictions will hamper system performance.  
Secure the piping away from moving objects such as engine belts and hatches. Prevent chafe  
on the tubing as required. Test and inspect all piping and hose clamps after several hours of  
operation.  
Wiring  
Pay attention to wire size or system performance will be impaired  
Perform wiring to UL, ABYC, CE or applicable standards  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura 150 MPC Plumbing  
Brine Discharge thru hull place  
above waterline or tee brine into  
another visible drain.  
Spectra Clark Pump. Mount in a cool location. May  
be oriented in any position and can be well above  
waterline. Leave access to the pressure relief valve.  
Do not mount over electrical equipment. Use supplied  
spacers and washers for the vibration mounts.  
Plastic fittings should have 3-4 wraps of Teflon  
tape and will thread almost all the way in. Leave  
the first pipe thread uncoated. Avoid getting dirt  
or debris in the system during assembly. Avoid  
tight bends and elbows. Secure piping away from  
moving objects and protect from chafe.  
20 and 5 micron filters. Do not mount  
over electrical equipment. Leave clear-  
ance underneath for filter change  
Accumulator, Factory  
pre-charged. Install so  
that gauge is visible.  
Red In  
Green Out  
Fresh water flush inlet to charcoal  
filter. Plumb to pressure side of  
fresh water system.  
Sea Strainer, Mount with  
Quick Block  
Inlet pump module. Mount vertically as low as prac-  
tical, no more than 4’ (1.1 M) above waterline and do  
not mount over electrical equipment.  
Leave clearance below for filter change.  
1/2” or 3/4” scoop strainer thru-hull and seacock for  
watermaker only. Mount low, in a clear flow and away  
from head discharge. Thru-hull is owner supplied.  
Water Flow  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Feed Pump Relocation  
If you do not have adequate space to install the feed pump inlet module it is possible to re-  
move and relocate the feed pump. Before you install the module, disconnect the hose that  
connects the feed pump to the module plumbing. Remove the cooling fan and the heat sink  
from the pump. Both are friction fits with no fasteners. Remove the 4 machine screws hold-  
ing the pump to the module.  
Cooling fan  
Machine Screws  
Heat sink  
With the pump on a flat surface. Remove the three  
screws that hold the pump head on. See Fig1  
Re-orient the pump head 120 degrees. See Fig2  
Reinstall the screws and tighten firmly. See Fig3  
Now the feed pump may be installed where you wish.  
Do not install with the pump head over the motor in-  
case of leaks. Wire size may have to be increased if  
wire runs are longer.  
Fig 1  
Fig 2  
Fig 3  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Water Plumbing  
Product water tubing is 1/4”(6mm) on the Ventura 150 models. See the Parker tube fitting as-  
sembly diagram next page. Product water is pre-plumbed from the membrane into the electric  
diversion valve. The diversion valve will reject product water into the overboard brine stream  
until good quality is measured by the MPC-5000 control. Product water is then diverted into the  
fresh water tank.  
Product to tank.  
Route the product water into the top of the tank, or a tee in the  
water tank fill hose.  
DO NOT! feed into a vent line, a manifold or the bottom of the  
tank. Make sure that there is no restriction in this piping.  
Accepted Product  
Water Outlet  
Automatic Valve  
Check Valve  
Rejected product outlet  
Product from membrane  
RotoFlow Meter  
Salinity Probe  
Product Diversion Valve Manifold  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Tube Fitting Assembly  
Spacer  
O-ring  
Grab Ring  
Body  
Nut  
Tubing  
Step 1: Dissemble fitting components  
1/2" max  
Step 2: Install the Nut first then use the bevelled side of the Spacer to push the  
Grab Ring onto the tube no more than 1/2". Slip the O-ring over the tube  
to hold the Spacer in place. If the Grab Ring is pushed too far, trim back  
the tube so about 1/4" of tube extends past the O-ring.  
Step 3: Gently fit the tube into the body and loosely thread on the nut.  
Step 4:  
Push the tube into the body until it bottoms out then hand tighten the nut.  
DO NOT OVER TIGHTEN!  
1/4" Tube Fitting Assembly  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Membrane Pressure Vessel Relocation  
Use ONLY Dayco Imperial Nylo-Seal 88-NSR-1/2 tubing for high pressure connections.  
Pay attention to the direction and flow path of the tubing before disassembly. Make sure  
that you reinstall the tubing in the same manner. Rotate the 90 degree high pressure tube  
fittings on the Clark Pump for ideal tube runs. The high pressure fittings are typically pre-  
installed at the factory. These fittings seal with an O-ring and require no Teflon tape or pipe  
dope. Loosen the backing nut, rotate the fitting, and reseat the backing nut.  
Follow the high pressure tube connection instructions on the next page. Connect the  
tubes to one of the components, secure the tube runs, and then trim and connect to the other  
component. A 90 degree bend in a tube is better than a 90 degree fitting. A tube, when  
mounted, should have at least one gentle bend to allow for expansion. Do not connect a  
tube straight between hard mounted fittings.  
When connecting the tubes to their components, be sure to hold the fitting body with a  
wrench during the final tightening. Of special note are the stainless steel tube fittings on the  
membrane housing which seal with an O-ring and should be seated all the way in, but need  
only to be snug, not tight as with tapered threads. Hold the fitting with a wrench while in-  
stalling the tube.  
The fittings on the Clark pump have an O-ring seal and can be re-oriented by backing out  
the O-ring stop nut. Rotate the fitting to align with the tube and tighten the nut just past  
hand tight. Do not over tighten!  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Spectra High Pressure Tube Fitting Assembly  
Use ONLY Dayco Imperial Nylo-Seal 88-NSR-1/2 tubing for high pressure connections.  
Carefully fit and measure the tubing before cutting with a sharp razor knife or hose cutter and remove  
any burrs. Minimum tubing bend radius is 6”. Route tubing away from excessive heat sources and  
secure from vibration and chafe. Have at least one shallow bend in the tube assembly after it is installed.  
Refer to figure 1. If a fitting has been dissembled, reassemble as illustrated. The notch on the ferrule  
must engage the inside of the nut properly for the nut to seat down fully. Once the tube is inserted the  
ferrule and nut will naturally align.  
Refer to figure 2. Insert tube fully into the fitting, it should go in 0.9”. Tighten the nut finger tight while  
moving the tube around to prevent binding. One thread should be showing under the nut. Secure the tube  
so it won’t back out when tightening.  
Refer to figure 3. Use 13/16” wrench to hold a straight body fitting or a 3/4” wrench for a 90º body, and  
a 7/8” wrench for the nut. Hold the body, recheck the tube insertion, then tighten the nut 1-1/4 turns. Use  
the index mark on the nut as a guide. The threads should be completely covered by the nut.  
Make sure these fittings are tight on initial assembly or they will fail!  
The correct torque is specification is 85 foot pounds  
Index mark  
Straight or 90 deg.  
3/8" pipe thread  
Straight thread  
Figure 1.  
Figure 2.  
Nut  
Body  
Ferrule  
Nut finger tight with  
1 thread showing  
Cut tube square  
Black high pressure tubing  
Tighten 1-2/3 turns (10 flats of the  
nut) with a7/8" wrench after finger tight.  
Use index mark as guide  
No threads showing  
Figure 3.  
Insert tube 0.9" until it stops  
IMPORTANT!  
Hold fitting body with
a
wrench when tightening  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MPC-5000 Wiring  
Mount the control box on a vertical surface with the wire grommets down, central to the  
other system components. Make sure the cables will reach all of the modules to avoid  
splices.  
Filter Sensor harness  
6’ (2M)  
Control cable 50’ (15.2M)  
Protect connector while routing through  
MPC-5000 display. Mount in  
dry central location. Only con-  
nect the MPC “plug in” cable.  
the vessel.  
Control Box  
Fresh water flush  
feed 15’ (4.5M)  
Splice to flush valve.  
Heat connectors to  
shrink.  
Pump feed 4’(1.2M) may be  
extended as required. Count  
additional length in wire siz-  
ing. Wire fan in parallel.  
Main power feed. Install cover  
after terminating wires.  
Use a 15 amp breaker or fuse  
Clark Pump harness, RotoFlow meter,  
salinity probe, and diversion valve feed  
15’ (4.5M). See next page.  
Wire Size Guide for Ventura 150 12V  
Protect with 15 Amp Fuse or Circuit Breaker  
# 10 Gauge (6mm) to 15 feet (4.5M)  
# 8 Gauge (10 mm) to 25 feet (7.5M)  
#6 Gauge (16mm) to 35 feet (10.6M)  
Total length for a pair of wires!  
Wire Size Guide for the Ventura 150 24V  
Protect with 7 Amp Fuse or Circuit Breaker  
#12 Gauge(4mm) to 10 feet (3M)  
#10 Gauge (6mm) to 25 feet (7.6M)  
#8 Gauge (10mm) to 35 feet (10.6M)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Clark Pump Harness  
Salinity Probe  
Roto Flow meter.  
Diversion  
Valve.  
To Roto Flow Meter  
To Diversion Valve  
To Salinity Probe  
The RotoFlow meter measures product flow. It is supplied with a three pin plug-in connector.  
Plug it in to the RotoFlow cable and seal the connection with the supplied heat shrink tubing.  
The salinity probe uses a telephone style jack and plug. Plug it in and slide the black plastic  
boot over the sensor to waterproof the connection.  
The diversion valve cable has two conductors. There is no polarity. Crimp the supplied heat  
shrink butt connectors to the diversion valve leads and heat them to seal.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Tank Switch Installation and Operation:  
There are two sets of terminals on the MPC-5000 PCB that can be used in four different con-  
figurations to automatically start and stop the watermaker, or to automatically stop the water-  
maker when the tank(s) are full without the auto start feature. These terminals are on the  
green ten pin connector and are labeled “Float Switch 1” and “Float Switch 2.” Float Switch  
1 is the tank full switch and Float Switch 2 is the tank empty switch.  
If the unit is wired for both Autostart and Autostop, it can be put into AutoFill Mode by push-  
ing and holding the Auto Run switch on the MPC-5000 display. In this mode the watermaker  
will start whenever the water level drops below the tank empty switch, so that it is open (not  
conducting electricity). When the tank fills up and both the tank full switch and the tank  
empty switch have remained closed for two minutes, the watermaker will shut down and flush  
itself. The watermaker will start back up when the water level drops below the tank empty  
switch and it remains open for 2 minutes. This configuration allows for completely automatic  
operation. If the watermaker does not need to start up within five days it will automatically do  
a fresh water flush. AutoFill mode can be ended by pushing the stop button or the Autoflush  
button. If the watermaker is in Autorun mode it can be put into Autofill mode without stop-  
ping it by holding down the Autorun button.  
If the owner prefers to install the automatic shutoff feature without the automatic start up op-  
tion, only the tank full switch is used. A jumper must be placed between the tank empty ter-  
minals (Float Switch 2) in place of the tank empty switch, because the watermaker will only  
shut down if both sets of terminals are closed. To use this mode the watermaker must be  
started up with the Stop/Start button or the Autorun button. After the unit starts up, then press  
and hold the Autorun button until the display reads “Auto Fill Mode”. The watermaker will  
fill the tank and automatically enter Autoflush mode.  
It is possible to use the autofill feature with 2 tanks. A double throw electrical switch must be  
installed in a convenient location. If only the single tank full switch is installed in each tank,  
connect the wire from Float Switch 1 terminal “1” to the common on the switch and run sepa-  
rate wires from the switch to each tank switch. The second wires can both be run to the Float  
Switch 1 terminal 2. If you are using two switches in each tank, you will need a double pole  
double throw switch.  
Note: If the Automatic startup is enabled the watermaker may start at any time. Because no  
one may be available to check for oil in the water around the boat, it is recommended that an  
oil-water separator, part number FT-FTC-OW be installed in place of the 20 micron filter.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC New System Start-Up and Testing  
Avoid running the Ventura system if the vessel is in contaminated water, such as in a harbor  
or canal. The system should be fully tested before leaving port. If the location or weather  
prevents proper testing refer to the section “Dry Testing.”  
Warning! Damage may occur if the purge sequence is bypassed and the membrane is  
pressurized with storage chemical in it.  
First check that:  
Thru-hull inlet valve is open and the brine discharge valve is open.  
All of your hose connections are tight.  
The green tag with the spacer under the pressre relief valve has been removed.  
The pressure relief valve is open 1/2 turn.  
The switch on the MPC control box is set to the“Auto” position.  
Remove Tag and Washer!  
Open 1/2 Turn when Purging Chemicals!  
Power up the system by turning on the cir-  
cuit breaker. A message on the display will  
read Open Pressure Relief Valve Now  
Push the “Auto Run” Button. The feed  
pump will start and the message  
Purging Storage Solution” will appear.  
Note: See Part 2 for instructions on dimming the display and programming from the display  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The system will go into a start mode and the feed pump will start shortly after. The system  
should prime within 60-90 seconds. Check the strainer and the brine discharge for water  
flow. There should be few bubbles anywhere in the intake hoses and the feed pump should  
sound smooth after priming. After confirming that the system is primed, inspect for leaks.  
Note: The reject light will be on whenever the  
product water is being rejected or not being made.  
When the product water is below 750 PPM the  
green (Good) light will show that water is going  
to the tank.  
Note: You can bypass the purge sequence and initiate a normal start at any time by  
Pressing both “Auto Run” and “Stop” simultaneously. This will bypass the  
purge sequence and enable a normal start.  
If you must stop the purge sequence for any reason, the control will default  
back to the beginning of the purging mode to protect your system.  
Do not bypass the purge mode unless you are sure that the chemicals are  
purged from the system or you will permanently damage the membrane.  
1. After the purge sequence, the control will alarm with the message “Close pressure relief  
valve”. Close the valve and proceed by pressing “Auto Run.”  
2. The system is now running under pressure and making water. The display will read  
“purging product water.” This mode dumps the product water overboard for ten min-  
utes in case there is any residual chemicals in the membrane. Carefully inspect for leaks  
over the entire system! Shut down the system and repair any leaks you find.  
3. The system is now in the operational mode. You may start and run your system as you  
desire. You will not have to go through the purging mode unless you “de-power” the sys-  
tem. If you do, you can bypass the purging mode by pushing Stopand Auto Run”  
buttons at the same time. It is best to use the “Auto Run” button which defaults to the  
automatic fresh water rinse. If you shut down the system from the “Stop” button then use  
the “Auto Store” button to effect a fresh water flush cycle.  
4. Check that the system is operating within its normal parameters. Compare with the chart  
on the next page.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MPC Display Modes  
Scroll through the modes with the alarm display key.  
Product  
The Ventura will produce 6- 6.5 GPH (26-27 LPH)  
Salinity  
This may not show any lit bars on a new system. Each square represents 100 ppm. System re-  
jects water higher than 750 PPM. LED lights (Reject, Good) indicate product mode.  
Feed  
Water Pressure range 60-70 PSI (4.2-5 BAR)  
Filter Condition  
When filters become partially clogged the MPC-5000 will alarm “Service Prefilters”. If  
the filters become fully clogged (all squares highlighted) the unit will shut off automati-  
cally.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC Dry Testing With Artificial Ocean  
If it is not possible to test run the system with the boat in the water, testing may be accom-  
plished with an artificial ocean. Purchase enough aquarium salt to make 5 gallons (20 liters)  
of salt water.  
Make sure that the domestic water system is powered up and that there is water in the tank.  
Confirm that the charcoal filter is installed in the fresh water flush module and that the domestic  
water line had been installed and all valves are open.  
1. Open Pressure Relief Valve on the Clark Pump. Remove the green tag and spacer!  
2. Close the yellow service valve on the inlet module. This will be the center location.  
3. Power up the control. Bypass the purge mode by pushing “Auto Run” and “Stop” simulta-  
neously.  
4. Push the “Auto Store” button and allow it to run a flush cycle. Do this five times to purge  
the storage chemicals.  
5. Hook up your inlet and brine discharge service hoses per the photo and route them into the 5  
gallon (20 liter) container. Turn your product sample valve, if installed, to the sample posi-  
tion. If no sampling valve is installed, temporarily route the product to tank tube into the  
bucket.  
6. Push the “Auto Store” button and fill the bucket with fresh water from the brine discharge.  
Stop the system when it is full.  
7. Rotate the yellow service valve to the service position.  
8. Mix the salt to the proper proportion or use an aquarium hydrometer to adjust the salinity  
level.  
9. Push the “Auto Run” button, allow the system to prime and then close the pressure relief  
valve. The system should build pressure and after several minutes start making water.  
10. Run the system under pressure and check for proper operation and leaks.  
After testing the system, stop and replace the brine discharge hose. Restart and drain the bucket.  
You can now store the system by using the above procedure for adding fresh water to the  
bucket and pickling the system, or using the “Auto Store” system.  
Valve in closed position  
Valve in service position  
Inlet service hose connected  
Connecting the brine  
discharge service hose  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC Operation  
Normal operation  
If the system has been pickled or stored, use the “New System Startup” procedure.  
1. Check to see that the inlet seacock is open.  
2. Push the “Auto Run” one or more times. The machine will run for one hour for each  
time the button is pushed, then shut off and automatically do a fresh water flush. If you  
receive a “System Stalled” error code, there is no flow in the system. Open the pressure  
relief valve on the Clark Pump and bleed the air out of the feed pump.  
3. Run the system until you have filled your tank or have made enough to meet your re-  
quirements for several days.  
4. When the unit shuts down it will enter the “Auto Store” mode, which will flush the unit  
every five days unless you run it to make water, the unit is de-powered, or the “Stop”  
button is pressed.  
5. You may stop the system at any time with the “Stop” button, but if you do it will not  
flush itself or go into “Auto Flush” mode.  
You may now leave the system unattended for up to five days without further attention  
We recommend operating the system for longer periods and effecting a fresh water flush  
rather than running the machine every day and not flushing the system. Remember that you  
need to run the system almost a half hour to make the flushing water. You may notice that  
the system output is higher while charging your batteries as the machine is voltage sensitive.  
Storage mode. The timer counts down in hours until the next flush cycle.  
Warning! Understanding automatic fresh water flush system is essential for it to be effec-  
tive.  
1. Make sure that the system has continuous power. Shutting down power will reset control.  
2. Make sure that the potable water system is “on” and that there is adequate water in the  
tank for the extended period.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flush Cycle Adjustment  
Before shipping from the factory the Ventura watermaker flush cycle is set to factory default  
settings. After initial start up, and annually thereafter, the flush cycle parameters must be ad-  
justed to ensure that the salt water is thoroughly flushed out of the machine while at the same  
time using the least amount of fresh water possible. Check the flush by closing the sea cock.  
If the system alarms “Check sea strainer” insufficient water is being supplied from the vessels  
fresh water system. If the fresh water supply is insufficient sea water will be drawn in to make  
up the difference and the system will not be properly flushed. After checking the flush water  
flow adjust the “Flush Duration” from the Programming Function on the display. Set the Flush  
duration so that the Flush comes to an end just as the salinity of the water going overboard  
drops below 1000 ppm or no longer tastes brackish.  
Automatic Store Cycle  
Warning! Proper understanding of the Spectra flush system and the vessel’s fresh water sys-  
tem configuration is mandatory for extended Auto Store cycles. The flush cycles must not be  
allowed to drain all the fresh water from the vessel or damage to the vessel’s systems may oc-  
cur.  
Make sure there is enough water in the fresh water supply system to supply the water-  
maker for more than the expected time of operation in the “re-flush every 5 days” mode.  
The Ventura 150 requires about 2.5 gallons (10 liters) every 5 days.  
Make sure that the pressure water supply is on and will stay on during the flush mode (If  
this is not possible contact your certified dealer.).  
Make sure that the pressure relief valve is closed. It should be closed if the system was  
just used to make water. The auto flush may not operate if the valve is open.  
The power for the system must remain on during the auto flush mode. Turning off the  
power will disable the auto store function and damage may occur.  
Pressing the Auto Store button momentarily will start a flush and then activate  
the 5 day flush cycle. The feed pump will start, the flush water solenoid will open and  
the display will read “FRESH WATER FLUSH” with a countdown timer. After 5-7 min-  
utes the pump will stop, the display will read “FLUSH TIMER INTERVAL,” and the  
countdown timer will reflect the number of hours until the next flush.  
Pressing and holding the Auto Store button for 3 seconds will engage a 1  
time flush. The system flushes as described above but will not re-flush every 5 days. Dis-  
play will read “FRESH WATER FLUSH” with a countdown timer, then the default dis-  
play when finished.  
Pressing the Stop button will cancel the auto store mode.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manual Operation  
In the event of a component failure resulting in a shut down due to a false alarm, the failed  
component can be overridden using the Programming Function on the display. High Pressure,  
Service Prefilter, System Stalled (airlock), and Salinity Probe Failed can be defeated. The other  
safety shutdown will still be activated. The pressure sensors and salinity probe can also be cali-  
brated from the display. Complete instructions are found in Part 2 of this manual under  
“Programming from the Display”. Be absolutely certain that the alarm is in error before defeat-  
ing the automatic controls.  
In the event of complete MPC control failure, the system may be operated manually using  
the switch on the feed pump module.  
For manual start up, set the switch to “Manual”. Shut the unit down if the Clark Pump does  
not cycle. In manual operation, the salinity control is inoperative and the diversion valve  
will not operate. Instead, product water must be taken directly from the membrane product  
water outlet. The automatic safety controls are disabled in manual mode.  
Bypass the diversion valve as follows:  
Disconnect the 1/4 inch tube “A” that runs between the membrane product outlet and  
the RotoFlow meter at the membrane outlet fitting. Product water will run out of the  
fitting.  
Taste the product water before sending it to a tank. Always discard the product water  
for the first few minutes of operation. The initial product water from the system may not  
be potable.  
Disconnect the product-to-tank tube from the diversion valve manifold outlet and con-  
nect it to the membrane product outlet fitting.  
To shut down manually, set the switch “Auto” .  
If the system is to be left idle for more than a day it should be given a fresh water flush. To  
manually flush, collect 3 gallons of product water in a bucket. Connect the service hose to  
the service connection on the pump module. Place the service valve in “SERVICE” posi-  
tion and start the feed pump with the manual switch. Run the feed pump until the bucket is  
empty and turn the service valve back to “RUN”.  
Diversion valve  
manifold outlet  
Tube “A”  
Tube to tank  
Membrane  
Tube “A”  
product outlet  
Automatic  
Operation  
Tube to tank  
Manual  
Operation  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Long Term Storage Procedures  
Watermakers are best run continuously. When not in use, biological growth in the mem-  
brane is the leading cause of membrane fouling. A warm environment will cause more  
growth than a cold environment. The fresh water flush system will greatly reduce biologi-  
cal growth but may not stop it completely in certain conditions. If an optional “Zeta Guard”  
or Z-Brane water treatment system is installed in the system, then three to five day flushing  
intervals will maintain the system as long as fresh water is provided and the charcoal filter  
maintained.  
System Storage or “Pickling”  
If the system is to be left unused for more than five days, perform the following storage pro-  
cedure. The procedure introduces a chemical compound into the system that prevents bio-  
logical growth. This procedure requires de-chlorinated water which can be made with the  
charcoal filter. Charcoal filters last a maximum of 6 months once wetted.  
Spectra SC-1 a special storage compound used by the US Navy. It is formulated to be  
compatible with the modern engineering plastics and composites in the Spectra pumps.  
Do not use any substitute except propylene Glycol, If you chose to use glycol follow the  
winterizing instructions. SC-1 Storage Compound has to be mixed at a ratio of 1 Spectra  
container to 3 gallons (12L) of fresh water to have the proper solution for short term stor-  
age (under two months use 1/2 of a container)  
Caution! Avoid contact with skin, eyes, or lungs with the storage chemical.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC Storage Procedure  
1. Shut the service valve by moving it to the middle position.  
2. Perform two fresh water flushes by pushing the “Auto Store” button .  
3. Remove the cap on the service port on the feed pump module and install the service hose  
from your kit. Remove the quick disconnect fitting from the brine discharge outlet of the  
Clark Pump, and replace with a quick disconnect service hose from your service kit.  
Lead the hoses to a 5 gallon bucket or container.  
4. Push the “Auto Store” button and run the feed pump until you have one gallon of fresh  
water in the bucket. Stop the system.  
5. Mix 1 container of SC-1 storage compound with the water in the bucket.  
6. Make sure the pressure relief valve on the Clark pump is OPEN (un-pressurized)  
by turning 1/2 turn counterclockwise  
7. Place the service valve in “Service” position  
8. Turn on the feed pump. You can use the man-  
ual switch on the MPC-5000 control box. Circu-  
late the storage chemical in the system for ap-  
proximately 10 minutes. Turn off the feed pump  
when finished.  
Clean Up  
Remove the quick disconnect from the Clark Pump brine discharge, and replace the original  
hose that leads to the thru-hull. You may at this point, if you choose, pump the bucket dry by  
using the feed pump switch. Stop when the bucket is empty.  
Turn the service valve 180° back to its original position, and remove the service hose.  
Close the seacock and drain and clean the strainer and any filters in the system. Reassemble  
dry.  
Service valve Off  
Service hose connected  
Brine disconnect fitting  
Service valve in service position  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Winterizing  
1. Close yellow service valve, push “Auto Store” to flush the system.  
2. Connect the inlet service hose and the brine discharge service hose. Place them in the  
service container or bucket.  
3. Push “Auto Store” and run until there is 1 gallon (4L) of fresh water in the bucket, then  
stop the system.  
4. Reconnect the brine overboard hose to the Clark Pump  
5. Turn the service valve to the “Service” position.  
6. Pour 2 gallons (8L) of Propylene Glycol in the bucket.  
7. Make sure that the pressure relief valve is OPEN (un-pressurized).  
8. Turn on the feed pump with the manual switch on the MPC control box until antifreeze  
appears in the brine overboard hose.  
9. Stop the pump. Reconnect the brine service hose. Start the pump and re-circulate the re-  
maining antifreeze for a few minutes.  
10. Close the seawater intake and the service valve. Drain the strainer and the hose leading to  
the inlet module.  
11. Disconnect the product to tank tube and blow the water out of it with compressed air.  
Open the pressure relief valve  
Valve in off position  
27  
Valve in service position  
Connecting brine discharge hose  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
General  
Periodically inspect the entire system for leakage and chafe on the tubing and hoses. Repair  
any leaks you find as soon as practical. Some crystal formation around the Clark Pump  
blocks is normal. Wipe down any salt encrusted areas with a damp cloth.  
The Seawater Strainer  
The sea water strainer’s stainless steel element should be inspected, removed, and cleaned as  
needed. Be careful to ensure that the thru-hull is closed before disassembly and the gasket is  
in place before reassembly. When the system is put into storage, remove, rinse, and reassem-  
ble dry to impede corrosion. Check frequently during operation.  
The Prefilters  
Service the pre-filters on a regular basis. The MPC will alarm when the filters reach a 5  
PSI (.35 BAR) pressure drop. You may clean and reuse the filters at this level. If you con-  
tinue to use the system until it stops at 10 PSI (.75 BAR) then the filters will have to be  
discarded.  
To service the filters, shut off the service valve, open the housing, and discard the old fil-  
ters. Clean out the housing bowl and reassemble the housings with new 5 and 20 micron  
filter elements. Leave dry until next startup.  
Use only Spectra approved filters or you may void your warranty. The filters may be  
cleaned several times with a soft brush and water in a bucket. Occasionally, lightly lube  
the filter housing O-ring with silicone grease.  
Oil Water Separator (Optional)  
To install oil water separator capability remove the 20 micron filter from the dual filter hous-  
ing and replace with the oil water separator element.  
The Charcoal Fresh Water Flush Filter  
Replace the charcoal filter element at least every 6 months! This filter protects the  
membrane by removing chlorine from the fresh flush water. Use only a Spectra replace-  
ment!  
The Feed Pump and Clark Pump  
The feed pump and the Clark Pump require no routine maintenance except inspection for  
leaks. Tighten any hose clamps or fittings the show signs of leakage. The high pressure  
stainless steel fittings threaded into the Clark Pump have o-ring seals with a straight thread.  
These should never leak and should never be over tightened. If one of the tube nuts starts to  
leak it can be un-threaded, sealed with a bit of silicone grease or silicone seal, and, using two  
wrenches, tightened very tight.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Membranes  
The membranes need to be cleaned only when operating pressures have risen 10% due to fouling, or  
when the product quality degrades. The leading cause of fouling is from biological growth that occurs  
when the system is left unused without flushing or pickling. Fouling from mineral scaling can happen  
during operation under certain sea water conditions, and from rust. Monitor the product salinity and  
feed pressure for higher than normal readings for the existing conditions. Other conditions can cause  
high pressure such as cold feed water or clogged filters. Low product flow is usually due to low volt-  
age, damaged feed pump or Clark Pump. Look for all other causes before cleaning the membrane.  
Membrane life can be shortened by excessive cleaning.  
There are two types of cleaners: acid and alkaline. The acid cleaner (SC-3) will remove mineral scal-  
ing. The alkaline cleaner (SC-2) is used to remove biological by-products, oil, and dirt particles that  
get past the prefilters. If membrane performance is reduced and they have not been “pickled” recently,  
cleaning is recommended. The acid cleaner should be used first. If the problem persists after the acid  
cleaning, do the alkaline cleaning. If the membrane fails to respond to both cleanings, this is an indica-  
tion of another problem with the system, or that it is time to replace the membrane. Contact Spectra  
Watermakers before removing a membrane.  
Membrane Cleaning  
For normal cleaning, the SC-3 Acid Cleaning Compound is used first, then the SC-2 Alkaline Cleaning  
Compound. If known bio-fouling is present, the SC-2 may be used first. Using hot water if possible, up  
to 120° (45C) is recommended as it greatly enhances the ability of the cleaners to do their jobs.  
If the history of the system is unknown or it has been left “unpickled” for an extended length of time  
and biological growth is present, it is recommended that the system be cleaned with SC-2, using an  
alternate source of unchlorinated fresh water before the system is run under pressure. A simple test can  
be performed to see if biological growth has occurred. Before running the system, remove the prefil-  
ters and examine their condition. If the housings are full of smelly discolored water, the system was  
not properly stored. Install clean prefilters if they were bad. Next, check the membrane. Detach the  
brine discharge hose and lead to a bucket. Open the pressure relief valve one turn, and manually run  
the system for 30 seconds. Examine the brine water. If it is discolored and smells bad, perform an SC-2  
cleaning with an alternate source of unchlorinated water before running the system pressurized. If the  
brine is fairly clean, the system can be purged, run normally, and checked for performance. Clean the  
membranes only if performance is reduced.  
Heating the water is preferable. The cleaning solution throughout the system will heat as it circulates in  
and out of the pot. An alternative is to heat the one or two gallons of initial water to 120° on the main  
stove before mixing in the cleaner and circulating it into the system. Periodically stop and reheat the  
solution.  
Perform the cleaning procedures while the ship is in acceptable sea water for purging and test-  
ing, or follow the flushing, purging, and testing procedure given in the “Dry Testing with Artificial  
Ocean” instructions.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Spectra cleaning compound (SC-2 or SC-3) must be mixed with fresh water at a ratio of 1 con-  
tainer of compound to 3 gallons (12L) of unchlorinated water to have the proper solution. An av-  
erage of two gallons (8L) of water is already present inside a Ventura 150 system . This water has  
to be figured into the mixture. A Ventura 150 system will use one container of compound.  
Cleaning Procedure:  
1. Close the service valve and push “Auto Store” to effect a fresh water flush.  
2. Connect your inlet service hose and the brine discharge service hose. Push “Auto Store”  
again and allow to run until there is 1 gallon (4L) of water in the bucket. Stop the system.  
3. Turn the service valve to the service position.  
4. Make sure that the pressure relief valve is open (un-pressurized).  
5. Mix the cleaning chemical in the bucket.  
6. Start the system with the manual switch on the MPC control box and circulate the chemi-  
cal through the system for the required time.  
7. Stop the pump, replace the brine discharge hose and start the pump until the bucket is  
empty. Stop the pump and rotate the service valve back to the run position. Restart the  
pump and run for 20 minutes to flush the chemicals out of the system.  
(DO NOT CLOSE the pressure relief valve!)  
8. The system may now be restarted to make water, flushed or stored.  
.
Service valve in off position  
Open the pressure relief valve!  
Connecting brine discharge hose  
Service hose connected  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Suggested Spares Ventura MPC  
Short term cruising, weekends etc.  
A basic cruise kit B. This kit consists of three 5 micron filters, three 20 micron filters, and  
SC-1 storage chemicals.  
Cruising 2 to 6 months at a time.  
Two basic cruise kits, one replacement charcoal filter, and one replacement feed pump head.  
Longer than 6 months  
Additional filters, offshore cruising kit consisting of Clark Pump seals, O-rings, tools and  
membrane cleaning chemicals. One replacement strainer screen, O-ring for strainer screen,  
O-rings for filter housing,  
Spectra Watermakers recommended spare parts  
Part Number  
SC-1 STORAGE CHEMICAL  
SC-2 CLEANER  
SC-3 CLEANER  
BASIC CRUISE B  
OFFSHORE REBUILD KIT  
5 MICRON FILTER  
KIT-CHEM-SC1  
KIT-CHEM-SC2  
KIT-CHEM-SC3  
KIT-BCK-B  
KIT-OFFSH  
FT-FTC-5  
20 MICRON FILTER  
CHARCOAL FILTER  
5” STRAINER SCREEN  
OIL/WATER FILTER  
FEED PUMP HEAD  
5” STRAINER O-RING  
FILTER HOUSING O-RING  
20” MEMBRANE  
FT-FTC-20  
FT-FTC-CC  
FT-STN-5S  
FT-FTC-OW  
PL-PMP-SFPH  
SO-STN-5SS  
SO-FHS-10H  
FT-MB-20  
SALINITY PROBE  
SALINITY PROBE CABLE  
EL-MPC-SP  
EL-MPC-SC15  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC Troubleshooting Procedures  
SYMPTOMS  
PROBABLE CAUSE  
REMEDY  
Close Valve  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ventura MPC Troubleshooting Procedures  
Error Messages  
SYMPTOMS  
PROBABLE CAUSE  
REMEDY  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCUMULATOR PRESSURE  
All Spectra Watermakers, except the Newport 700 and 1000 series, are supplied with a pres-  
sure accumulator tank (part no. PL-ACC-TK) to be installed in the feed water line between the  
prefilters and the Clark Pump. In addition, the Catalina 300 and Newport 400 series also have  
an accumulator mounted inside the fresh water flush module.  
The purpose of the feed line accumulator is to reduce the spikes in the feed pressure caused by  
the cycling of the Clark pump. If the accumulator is not properly charged it can lead to prob-  
lems with the ShurFlo pump pressure cutout switches. The accumulators have an air valve on  
top similar to those found on car tires. This allows the internal air bladder of the accumulator  
to be precharged. The accumulator should be pumped up to about 65psi (4.5bar) for best re-  
sults. Add air using a tire pump or air compressor. You can experiment with the exact pres-  
sure that will give the best pulsation dampening on your installation.  
The purpose of the fresh water flush accumulator is to allow a steady flow of 1.5 gallons per  
minute of flush water through the charcoal filter. Because the feed pump on the 300 and 400  
hundred series exceeds this maximum allowed flow rate, the controller turns it on and off, to  
reduce the overall flow rate. The accumulator gives the water flowing through the charcoal  
filter somewhere to go while the feed pump is cycled off. The flush water accumulator should  
be preloaded to 5 psi (.35bar).  
9/27/04  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OP-2 BAD SMELLING PRODUCT WATER  
The reverse osmosis membrane is permeable by many gases including hydrogen sulfide, the gas  
that causes rotten eggs to smell the way they do. If there are bad odors in the feed water they  
will go through the membrane and the product water will be affected. Usually the source of the  
odor is from the decay of planktonic creatures trapped in the sea strainer and prefilters. These  
tiny oxygen loving creatures soon suffocate and die inside the prefilter housings when the unit  
is shut down. Once all the available oxygen is consumed, anaerobic bacteria begin to grow,  
causing the odor. If a unit being used frequently begins to make smelly water, it will be the pre-  
filters that are the source of the problem. This occurs in a week or two in cold climates, but in  
less than one night in very warm waters like the Sea of Cortes or the Red Sea. These bacteria  
can spread throughout the watermaker, and begin to grow on the membrane, causing poor water  
quality and high feed pressures.  
Filling the system with fresh water after every use greatly slows this process, allowing the auto-  
mated Spectra units to operate with less frequent prefilter changes. Units operated for only an  
hour or so a day will probably need to have the filters changed due to odor before they are dirty  
enough to restrict water flow. Prefilters can be cleaned. We recommend that you have three  
sets in service, one in the unit, one set soaking overnight in a bucket of clean fresh or salt water  
and one set drying for the next use. After shutting down the unit, remove the used prefilters and  
install the dry set. Leave the housings full of air until the next use. On non-automated sys-  
tems, open the pressure relief when starting if there is a lot of air in the system until the air is  
cleared out through the brine overboard. The filters will get just as clean when soaked in sea  
water, but dry much faster if soaked in fresh. Given gentle handling, prefilters can be reused  
many times.  
Bad smelling product water is usually caused by bad smelling feed water, but can also be  
caused by a fouled membrane if the membrane has been left unpickled. If the unit makes  
smelly but not salty water after a long idle period and the prefilters are new, the smell can be  
eliminated by running the unit unpressurized for an hour or so to flush the membrane.  
Odors in the product water can also be eliminated by adding a charcoal filter in the product wa-  
ter line. Spectra offers a product water filter kit (part no. KIT-FLT-CC).  
8/17/04  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OP-3 CHEMICALS 101  
Spectra systems use four types of chemicals: SC-1, SC-2, SC-3, and propylene glycol anti-  
freeze.  
NOTE: Never use any chemicals with the system pressurized! Always open the pressure relief  
valve 1/2 turn. Always purge a system containing chemicals for at least 20 minutes unpressur-  
ized before pressurizing and making water.  
The SC-1 is for storage only. It is no longer used as a cleaning chemical. To prepare the sys-  
tem for storage, first do a fresh water flush until the brine discharge is below 1000 ppm or does  
not taste salty. Mix one jar of SC-1 with 1 to 2 gallons of product or de-chlorinated fresh water  
in a bucket and circulate UNPRESSURIZED with the fresh water in the system for 10 minutes,  
then discard. The system should be re-pickled every six months in warm conditions, and every  
eight months in cooler conditions.  
The Spectra systems should be stored with propylene glycol if freezing could occur. This is the  
food grade antifreeze used to winterize RVs, boats and cabins. This works very well for storing  
in warm climates and is good for one year. See “Wintering or Pickling With Antifreeze” for  
instructions on this procedure.  
NOTE: Do not use metasodium bisulfate, the standard chemical used to store most watermak-  
ers. This chemical will damage the Clark pump and void the warranty.  
CLEANERS: Cleaning can be detrimental to the membrane and shorten its life. Avoid unnec-  
essary cleaning. Avoid cleaning as a diagnostic tool.  
SC-2 is an alkaline cleaner used to remove light oil, grime and biological growth. It is most  
effective if heated to 120 oF On a boat this is not easy to do. If not heated, circulate for 2 hours  
and let set for several hours and re-circulate for one hour and discard. In most cases the water  
quality will increase in PPM after an SC-2 cleaning. After a few hours it should recover to near  
the PPM it produced before the cleaning.  
SC-3 is an acid cleaner used to remove mineral and scale deposits. This is used in the same way  
as the SC-2. In most cases this is used first, and if no results are achieved, proceed with the SC-  
2. SC-3 will in most cases lower the product PPM and over all pressures. Scaling is a slow  
process that may take several months or years. SC-3 is less harmful to the membrane and will  
almost always improve the performance of an older membrane.  
7/19/04  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OP-4 FRESH WATER FLUSH  
The purpose of the fresh water flush is to replace the sea water in the watermaker with fresh  
water whenever the system is not operating. The “Auto Flush Mode” on the MPC 3000  
changes the fresh water every five days if the system has been idle that long. The watermaker  
will last longer and operate better if it is always kept filled with fresh water between uses.  
Most spectra watermakers are equipped with a fresh water flush module. This module in-  
cludes a 50 micron filter to filter out abrasive particles in the feed water that might damage the  
feed pump, a charcoal filter to remove any chlorine in the fresh water that might damage the  
membrane, an electrically operated valve and a check, or “one way”, valve. The electrically  
operated solenoid valve opens during the fresh water flush allowing the boats pressurized wa-  
ter system to supply water to the system. The check valve prevents the fresh water from going  
out backwards through the sea strainer and sea cock. The charcoal filter has a maximum flow  
rate of 1.5 gallons per minute (6lpm) so the feed pump is operated at a reduced speed on some  
models, or is cycled on and off on other models, to avoid exceeding this flow rate.  
If the ship’s water system is unable to provide flush water at the required flow rate, sea water  
will be drawn in to make up the difference. This will cause the flush water to be brackish, and  
ineffective in preserving the watermaker. At initial startup the fresh water flush system should  
be tested by taking a sample of the brine discharge water just as the flush cycle is ending.  
This water should not taste salty, and should read less than 1000 ppm on a digital tds meter.  
The flush cycle can also be tested by closing the sea cock during the flush cycle. If the MPC-  
5000 display gives a CK SEA STRAINER alarm this means that the fresh water supply is in-  
sufficient.  
Because the pre-filters trap the plankton in the feed water they can be subject to “going an-  
aerobic” or starting to smell like rotten eggs, as the trapped plankton decay. For this reason it  
is advisable to always put in clean elements if the unit is going to be left on Auto Flush Mode.  
In daily or regular use the fresh water flush after each shutdown will help prevent this prob-  
lem, but in excessively warm or fertile waters the pre-filters will need regular attention.  
7/26/04  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PF-3 PREFILTERS– ShurFlo  
Up to four different filters are used on all Spectra Systems using ShurFlo feed pumps to en-  
sure that no damaging foreign materials enter the system. There are 2 or 3 filters in the system  
to clean the feed water of abrasive materials while the system is in operation, and an addi-  
tional filter to prevent the entrance of chlorine during fresh water flushing.  
During normal operation, the feed water is filtered in two stages. First it enters a fine mesh  
metal sea strainer. This protects the feed pump from damage due to foreign materials and lar-  
ger sea creatures. After passing through the pump the feed water enters the filter housings  
containing 20 and 5 micron elements. These filters remove very fine particles which could  
damage the Clark Pump and shorten membrane life. Some units have only the 5 micron filter.  
Cleaning schedules will vary widely depending on how and where the system is used. If large  
amounts of feed water are run through the system in a relatively short period in biologically  
fertile near shore waters, the prefilters will plug up, the pressure drop across the filters will  
rise, production and quality will drop, and the system will sense plugged filters and give a  
Service Prefilters” or “Check Strainer” alarm if so equipped. Plugged filters can be  
cleaned several times by soaking in a bucket, towing behind the boat at moderate speeds, or  
cleaning with a hose.  
When operated only an hour or two a day in inland or near shore waters, the trapped plankton  
will begin to decay in the filters long before the elements plug up, and the bacteria involved in  
the decay will cause a “rotten egg” smell in the product water. This decay will set in overnight  
in tropical waters, or after a week or two in high latitudes. If handled gently and changed regu-  
larly before they get too smelly, filters in this service can last through dozens of cleanings.  
In crystal clear blue water conditions the filters may need to be cleaned much less frequently.  
The charcoal filter used in the fresh water flush system will not plug up unless you have some  
incredibly dirty domestic water in your boat. About six months after installation the charcoal  
filter element will lose its effectiveness at removing any membrane-damaging chlorine which  
may be present in domestic water. Charcoal filter elements must be replaced every six months  
if there is ANY chance that chorine could be introduced into the flush water.  
To ensure that filter elements fit properly and remove chlorine effectively, they should be pur-  
chased at factory authorized dealers. Our element part number is FT-FTC-XX. The last two  
digits indicate the micron rating, e.g. FT-FTC-05 is for a 5 micron element. Charcoal ele-  
ments are FT-FTC-CC.  
06/03/04  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SF-1 SHURFLO PUMP WON’T RUN  
If the pump has power to it (the fan runs), but the pump won’t run, the first thing to check is  
the pressure switch. The pressure switch, p/n EL-FP-PS, is located on the wet end of the  
pump and has two red wires plugged into it. Jump the two red wires together and see if the  
pump runs. You can safely run the system with the pressure switch jumped, just keep an eye  
on the pressure gauge and don’t let system pressure exceed 110 psi. Replace the switch when  
a spare is available.  
If the pump will not run with the pressure switch jumped then it is most likely a problem with  
the brushes or overheat protection switch inside the motor. The motor will come completely  
apart by removing the two screws on the end of the motor. Remove the rear cover and paper  
insulator. Pull out the plastic brush holder. The thermal switch is located on one of the brush  
leads. With an ohmmeter, check for continuity through the switch. If it is open, you can  
make temporary repairs by wiring around it, being careful that your new wiring doesn’t chafe  
on the moving parts, nor resist the springs that push the brushes on to the commutator.  
If any corrosion is apparent the brushes may be sticking. Once apart clean all the carbon dust  
from all the parts. Clean the commutator with light sand paper. Make sure to clean the small  
grooves on the commutator with a small sharp tool to remove the carbon in between the seg-  
ments. Adjust the springs on the brush holders so the brushes slide smoothly in and out. If  
the bearings are rough and binding, remove the rubber dust cover and clean the best you  
can, grease them, and work it free by hand. Don't service the bearing unless absolutely neces-  
sary. Reassemble in reverse order. You can hold the carbon brushes back with papers clips  
inserted through the slots in the brush holder so they don't hang up on the bearing during as-  
sembly. Make sure the corrugated bearing shim doesn't push out, if it does, push it back into  
place.  
This will at least keep you going until the motor can be replaced if necessary.  
6/03/04  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SF-2 ADJUST SHURFLO PRESSURE SWITCH  
The ShurFlo feed pumps are equipped with a high pressure cut out switch (part no. EL-FP-  
PS). This is the small black unit on the end of the wetted end of the pump head (part no. PL-  
PMP-SFPH) where the two red wires connect. If the pressure switch is not properly adjusted  
the pump may cut out each time the Clark Pump cycles and the feed pressure spikes. When  
this happens, the production will drop and an unusual noise will be heard when operating with  
two pumps, but the system will function normally during one pump operation on either pump.  
The points in the switch will fail fairly quickly if set too low because of the constant arcing  
from cutting out each time the Clark pump shifts.  
For all systems except the Gulfstream, the feed pump pressure switches should be set to shut  
off at 125 psi (8.5 bar) as follows. On the very center of the switch is a small 5/64” allen  
screw. Run the system on pump one and close the brine discharge valve (1/2 way 90 deg) to  
block the flow. Watch the pressure gauge and adjust the pressure switch to shut off at 125  
psi. Repeat for pump two. Turn the allen screw clockwise to increase the cut off set point.  
Gulfstream models could experience seal failures in the manifold if pressurized too high. For  
this reason, the pump should be removed from the system and the switch adjusted using a  
separate pressure gauge. If replacing a feed pump or pump head for a Gulfstream model ar-  
range to preset the switch before installation.  
8/05/04  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HS LF-1 POOR PRODUCT QUALITY  
With any product water quality issue, you need to check the calibration of the salinity tester  
that you are using before proceeding.  
Membranes are not an exact science and two identical systems can have a different product  
quality result. World health standards deem water of up to 1000 PPM of total dissolved solids  
acceptable for drinking consumption. We consider any thing below 700 PPM acceptable but  
not ideal, and anything below 500 PPM excellent. Factors that could affect water quality are  
addressed below.  
LOW SYSTEM FLOW OR PRESSURE will equate to lower product quality (higher  
PPM). A 200-C system running at 70 psi will deliver product water in the 400- 500  
PPM range, while the 380-C systems with twice the flow and operating at 100 psi into  
the same size membrane, will produce 200-300 PPM water. Ventura 150 systems,  
which have a higher feed to output pressure ratio (See MISC-4 nominal pressures), as  
well as a higher feed flow/membrane area ratio, will produce water in the 150-200  
PPM range. These improvements in product quality come at the expense of energy  
efficiency.  
DAMAGE TO THE MEMBRANE by chlorine contamination. Flushing the system with  
chlorinated water will irreparably damage the membrane. Charcoal filters are used to  
absorb any chlorine which might be present in flush water. They must be of proper  
specification to be suitable. There is no test for chlorine damage except the process of  
elimination of other causes.  
DIRTY OR SCALED membranes. A dirty (foreign material), scaled (mineral deposits), or  
contaminated (bacterial growth) membrane can result in poor water quality and abnor-  
mal operating pressures. If operating pressures are above normal, then cleaning is indi-  
cated. If the system pressures are within operating normal range, cleaning may have  
little result. Cleaning is no better for a membrane than it is for your clothes. Avoid  
cleaning as a diagnostic tool.  
MECHANICAL LEAKAGE within the membrane pressure vessel. This is an unlikely but  
possible cause of poor water quality with old style Codeline pressure vessels (white)  
that we have used in the past. The Spectra pressure vessel has a double O-ring arrange-  
ment that includes a telltale hole between them so that any salt water leaking past an  
O-ring will drip into the boat and not go into the product water.  
If system flow (product plus brine) is 1.5 GPM or above on one pump, the membrane is clean,  
the product flows are consistent with the system flow and the water quality is still not accept-  
able, then replacement of the membrane is indicated. See “HS-LF2 Flow Check” for instruc-  
tions on checking flow rates  
7/6/14  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HS LF-2 FLOW TEST/ SHURFLO  
Before the test, change all filters and clean the strainer. Make sure that there are no leaks.  
Check for air leaks, as air in the system will cause low production and erratic salinity. Look  
for air bubbles in the product flow meter, feed pump discharge hose, and brine overboard  
hose.  
Run the system and watch the pressures very closely. Make sure that on each shift everything  
is even from side to side. If the feed pressure to the Clark pump is different (asymmetrical) on  
one stroke than on the other this could be part of the problem. A difference of a few PSI is ac-  
ceptable, but anything over that is an issue. If the pump is asymmetrical Clark pump repairs  
should be done before continuing with these tests. Ask for CP-5 Clark Pump Checkout in-  
structions. If no asymmetry is noted, please do this test.  
NOTE: On Ventura 150 and 200 models with only one feed pump, disregard the instructions  
concerning “pump two” and “both”  
Make sure the ShurFlo overpressure cutout switches (part no. PL-PMP-SFPH) are set to 125  
psi. With pump 1 running, close the brine service valve. The feed pressure should rise to 125  
psi and the pump should shut off. Repeat with pump 2. If the pumps shut off at a lower pres-  
sure see “SF-2 Adjust ShurFlo Pressure Switch” bulletin.  
1. Log the pressure on pump 1, pump 2, and both. Log the product GPH (LPH) at the same  
time.  
2. Log the voltage at the feed pumps at the same time. Confirm at least 12.5 volts at the  
pumps. You may have to run the engine or battery charger.  
3. Measure the total flow rate of the system. Run the system making water and divert BOTH  
the brine discharge AND product water into a bucket. Time how long it takes to make a  
given amount of water. Repeat with pump 2 and both pumps.  
In order to make good water, you need the proper amount of feed water flow. Each pump  
alone should produce 1.5 gallons per minute (5.7 lpm). Running on both pumps the flow  
should be 2.7 gpm (10 lpm).  
Compare the product flow to the total feed flow. Product flow should be 7% of total flow for  
a 150, and 9.5% of total flow for a 200 or 380 model. If product percentage is low, you may  
have an internal leak in the Clark pump.  
For every 1/10th of a gallon per minute of feed water flow loss, we will lose about 1/2 gallon  
per hour of product flow and the salinity will go up 100ppm. Low feed flow combined with  
low system pressures, (see “Misc-4: Nominal Pressures”), is most frequently due to worn  
ShurFlo pump heads (part no. PL-PMP-SFPH).  
9/24/04  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Z-BRANE  
OPERATION  
MANUAL  
Spectra Watermakers Inc.  
20 Mariposa Rd., San Rafael, CA 94901  
Phone 415-526-2780 Fax 415-526-2787  
Current manuals/Z-Brane 12/10/04  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Z-brane is a revolutionary product which incorporates the Z-Guard High Voltage  
Capacitive technology into the membrane pressure vessel. Always active, the Z-Brane  
creates an environment that is unfriendly to bio-film and bacteria. The Z technoalgy also  
assits in the prevention of scale formation on the membrane surfaces. The Z-Brane allows  
the system to be shut down or decommissioned for extended periods of time without  
chemicals or preservatives. The Z-Brane will not prevent freezing so that in cold climates  
Propylene Glycol is still required.  
The Z-Brane system is integral with the watermaker unit and only requires continuous  
12Vor 24V DC power to be operative. The installation of the Z-Brane only consists of  
wiring the power supply to a continuous source The Z-brane power supply can tolerate  
voltages between 10V and 28V DC.  
Note: There is no reason to open the transformer enclosure. Do not ser-  
vice this unit without disconnecting the power source! There may be  
high voltage present.  
It is recommended that the Z-Brane be connected to a discreet continuous power source.  
The power must be on during the time that the system is operation and during the time the  
Z-Brane is used for membrane storage. If the power is obtained from the MPC then the  
MPC must be powered up at all times during storage. This may not be desirable.  
Fuse the power at the source with a 5 amp fuse or circuit breaker.  
Red is Positive (+) , Black is Ground (-)  
Z-Brane Power Harness  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
During normal operation the Red LED should be on . Power needs to be supplied to the Z-  
Brane unit at all times that you wish to have the biofouling and scale protection. We recom-  
mend that your watermaker be flushed after each use not only to protect the membrane but to  
prevent corrosion in the feed water system. To achieve full effectiveness thoroughly fresh  
water flush the watermaker several times before leaving the vessel.  
The Z-Brane may be de-powered if the system is stored with chemicals or winterized with  
Glycol.  
Power on LED  
High Voltage  
connector  
DO NOT DISCONNECT  
OR SPLICE ANY OF THE  
HIGH VOLTAGE WIRING!  
Contact the factory if  
modifications are required.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part Numbers  
3/8 NPT Quick Disc. Body  
PL-QDC-BD3/8  
Front View  
5/8 Quick Disc. Hose Barb  
PL-QDC-HB5/8  
1/2” High Pressure Tube  
PL-NLT-1/2HP  
Plate Bracket End Cap  
FM-PVB-PBE  
3/4”NPT X 1/2” Hose Barb Elbow  
PL-HBE-3/4X1/2  
1-Way Solenoid Valve  
12V,  
PL-SLN-1/4O12,  
Rear View  
Plate Bracket  
FM-PVB-PB  
Pressure Vessel End  
Cap  
FT-PV-EP  
Rubber Mount  
HD-RBP-RM  
Plastic Spacer  
HD-SPN-MKINS  
Pressure Vessel End Ring  
FT-PV-ER  
Clear Filter Housing (Bowl & Cap)  
FT-FTH-10L  
Clear Filter Housing O-ring  
SO-FHS-10H  
3/4”NPTX5/8” Hose Barb  
PL-HBS-3/4X5/8  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part Numbers  
Pressure Sensor  
EL-SSR-150  
3/8”NPT X 5/8” Hose Barb El.  
PL-HBE-3/8X5/8  
Filter Housing  
Bracket Duplex  
FT-FHB-10HD  
1/2” Female Tee  
PL-TEE-1/2FN  
1/2”NPT X 5/8  
Hose Barb  
PL-HBS-1/2X5/8  
3/4”NPT X 5/8 Hose Barb El.  
PL-HBE-3/4X5/8  
1/2” Nipple  
PL-NP-1/2N  
1/4” Street El.  
PL-MFF-1/4X1/4  
1/2” X 1/8” Bushing Reducer  
PL-BSH-1/2X1/8N  
Pressure Guage  
PL-PSG-LP1.5  
Accumulator Tank  
PL-ACC-TK  
1-Way Solenoid Valve 12V,  
PL-SLN-1/4O12,  
3/4” Nipple  
PL-NP-3/4N  
1/4”NPT X 5/8” Hose Barb El.  
PL-HBE-1/4X5/8  
High Pressure Filter Housing (Lid & Bowl)  
FT-FTH-10H  
Filter Housing O-ring  
SO-FHS-10  
Sea Strainer (Lid & Bowl& Screen)  
FT-STN-5  
Charcoal Filter Cartridge  
FT-FTC-CC  
Sea Strainer Screen  
FT-STN-5S  
Sea Strainer O-ring  
SO-STN-5SS  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part Numbers  
PL-SLN-1/4D12VB  
1/4" DIVERSION VALVE 12V W/O VB  
PL-CKV-1/4M-F  
1/4" PLASTIC CK VALVE (M-F)  
PL-MTS-1/4X3/8P  
1/4"MPT X 3/8" TUBE  
FITT. ST.  
SUB-NP-DVM  
DIVERSION VALVE  
MANIFOLD  
PL-FTS-3/8X1/4P  
3/8"FPT X 1/4"TUBE FITT ST.  
EL-MPC-SP  
SALINITY PROBE  
REDUCING COUPLING  
PL-UNN-3/8X1/4N  
EL-SSR-IFM  
INLINE FLOW METER  
SENSOR  
MPC CONTROL PANEL (VFD)  
EL-MPC-RMCDFD  
3/4”-16 ST X 1/2”  
Tube Fitting El.  
PL-MTE-3/4SX1/2  
3/8”NPTX3/8”Tube Fitting  
PL-MTS-3/8X3/8P  
1/8”FPT X 1/2”  
Tube Fitting El.  
PL-FTE-1/8X1/4P  
1/8” Hex Plug  
PL-HP-1/8  
3/8”NPT X 1/2” Tube Fitting SS.  
PL-MTS-3/8X1/2S  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part Numbers  
Valve End Block B  
HP-TB-VEB-B  
3/8”NPT Quick Disc. Coupling Body  
PL-QDC-BD3/8  
5/8” Quick Disc. Fitting Hose Barb  
PL-QDC-HB5/8  
1/2” High Pressure Tube  
PL-NLT-1/2HP  
3/8” Low Pressure Tube  
PL-NLT-3/8LP  
1/4” Product Tube  
PL-NLT-1/4LP  
1/2” Stainless Ferrule  
PL-HWR-1/2FR  
3/4”-16 Straight Thread O-ring  
SO-FT-STF  
Connector O-ring  
SO-HPP-CT  
Stainless Fitting Hex Nut  
PL-HWR-1/2HN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Part Numbers  
3/4” 3-Way Valve  
PL-VLV-3W3/4  
Cooling Fan 12V, 24V  
KIT-FK-12,24  
Feed Pump Heat Sink  
EL-FP-FPHS  
Ventura Feed Pump Bracket  
FM-VT-ITM  
Feed Pump 12V, 24V  
EL-FP-12V, 24V  
3/8”NPT X 5/8” Hose Barb El.  
PL-HBE-3/8X5/8  
Feed Pump Pressure Switch  
EL-FP-PS  
Pump Head Assembly W/Press. Switch  
PL-PMP-SFPH  
Fig 1  
Fig 2  
Fig 3  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts  
End block B  
HP-TB-VEB-B  
Valve block  
HP-TB-VB  
End block A  
Composite cylinder  
HP-TB-VEB-A  
and base  
Brine out  
HP-CYL-CCA  
Pressure relief valve  
HP-TB-BV  
Center block  
HP-CB-CB7,  
Feed in  
Stainless steel tube  
HP-CYL-SST  
Cylinder ring  
HP-CYL-R  
Clark Pump  
Front View  
End Cap  
HP-CYL-EC  
End block A  
Valve block  
End block B  
Not used  
Composite cylinder  
and base  
Alternate brine out  
High pressure in  
Test port  
Center block  
High pressure out  
Stainless steel tube  
Cylinder ring  
Clark Pump  
Back View  
End cap  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HD-CPS-5/16X3  
5/16"-3 1/4" SS AH Bolts  
Relief Valve  
O-Ring  
SO-HPP-RV  
Annular Rings  
HP-TB-AR  
Spool Assembly  
KIT-HP-10VSA  
Relief Valve  
HP-TB-BV  
Annular Ring O-Rings  
Mount inside Valve Block  
SO-HPP-AR  
Valve Block  
5/16"- 2 3/4" SS A.H. bolts  
Reset button and O-ring  
End block B  
HD-CPS-5/162.75  
Piston O-ring  
Spool piston  
SO-HPP-SP, PS20  
HP-TB-VSP,VSP20  
HP-TB-SR Spacer ring  
Valve block  
Valve bore O-ring  
Spacer ring  
Spool piston  
SO-HPP-VB  
Valve bore  
O-ring  
Brine port  
End block A  
O-ring  
SO-HPP-VP  
Valve spool  
Pilot port O-rings  
SO-HPP-PLP  
Piston O-ring  
Reversing Valve  
End Blocks  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts  
Valve port seals  
SO-HPP-VP  
Pilot valve port seals  
SO-HPP-PLP  
Piston rod  
HP-CYL-3/4R,  
Center block cylinder O-rings  
SO-HPP-ECCB  
Pilot spool O-rings (4)  
Mount inside block  
SO-HPP-PV  
HP-CB-PVS  
HP-CB-PPS  
SO-HPP-PS  
Pilot spool  
Pilot valve pin  
Pilot orifice  
HP-CB-PO  
Pin seal O-rings  
Pin seals  
HP-CB-PVPS  
HP-CB-PVCR  
Center block  
Clip rings  
Rod lip seals  
Mount inside block  
SO-HPP-PR7,  
PR10,PR15  
Feed in  
Check valve port O-rings  
SO-HPP-CVP  
Check valve assembly  
SO-HPP-CVS  
HP-CB-CVS  
Check valve  
O-ring  
Check valve seat  
HP-CB-CV  
Check valve poppet  
Check valve spring  
Check valve washer  
Center Block  
HP-CB-CVR  
Check valve retainer  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts  
1/2" SS tube  
S.S compression  
Piston with seal  
HP-CYL-SST  
fittings  
HP-CYL-PT  
PL-MTS-3/8X1/2S  
Composite cylinder  
and base  
HP-CYL-CCA  
End cap O-ring  
SO-HPP-ECCB  
Cylinder end cap  
HP-CYL-EC  
Cylinder Ring  
HP-CYL-R  
Cylinder Assembly  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sennheiser Headphones SI User Manual
Sennheiser Microphone MKH 816 TU 3 User Manual
Sharp Cash Register XEA407 User Manual
Shure Headphones PGA52 User Manual
Sony Headphones MDR DS3000 User Manual
Sony Camcorder Accessories SPK DVF4 User Manual
Sony Camcorder W570D User Manual
Sony Portable Multimedia Player NWZ E475BLK User Manual
Sony Projection Television KV 21FS120 User Manual
Sony Speaker CR205 User Manual