SSI America Work Light 7SL User Manual

Instruction Manual  
PN 31302  
MODEL 7SL  
HIGH/LOW LIMITROL®  
7sl-0-00.p65  
1
9/17/02, 2:35 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Congratulations  
Unpack the  
Instrument  
Congratulationsonyourpurchaseofoneoftheeasiestto  
configure high/low Limitrols on the market. After a 3 step  
configuration procedure, your process will be up and  
running.  
Wiring  
Guide to simple set-up  
Configuration  
To set-up the Limitrol only 3 steps are required:  
1. Wire the instrument (page 7).  
2. Configure the instrument (page 14).  
3. Check the operating parameters (page 22).  
Operating  
Parameters  
SV  
3
7sl-0-00.p65  
3
9/17/02, 2:35 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
CAUTION:  
1/16 DIN, FOUR DIGIT HIGH/LOW LIMITROL.......... 2  
Guide to simple set-up ...................................... 3  
MOUNTING REQUIREMENTS.................................. 5  
DIMENSIONS AND PANEL CUTOUT ....................... 6  
WIRING GUIDELINES ............................................... 7  
PRELIMINARY HARDWARE SETTINGS ............... 12  
CONFIGURATION KEY FUNCTIONS ..................... 14  
CONFIGURATION PROCEDURE ........................... 14  
OPERATING MODE ................................................ 20  
Normal Display Mode ..................................... 20  
Indicators ........................................................ 20  
Key Functions in Normal Display Mode .......... 21  
Parameter Display Mode................................. 21  
Key Functions in Parameter Display Mode ..... 21  
OPERATING PARAMETERS................................... 22  
ERROR MESSAGES ............................................... 23  
DEFAULT PARAMETERS ........................................ 24  
SPECIFICATIONS ................................................... 26  
CALIBRATION PROCEDURE .................................. 30  
General Guidelines ......................................... 30  
Calibration Parameters ................................... 30  
Procedure ....................................................... 31  
Entering Calibration Values ............................. 31  
MAINTENANCE ....................................................... 35  
USE WIRE SUITABLE  
FOR 75°C MINIMUM.  
NOTES  
For supply connections use No 16 AWG or larger  
wires rated for at least 75 °C.  
Use copper conductors only.  
Class 2 wiring must be a minimum of 1/4 inch from  
any Class 1 conductors.  
4
7sl-0-00.p65  
4
9/17/02, 2:35 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING REQUIREMENTS  
Panel surface texture must be better than 6.3 µmm.  
Select a mounting location with the following  
characteristics:  
1) Minimal vibration.  
2) An ambient temperature range between 0 and  
50°C (32 and 122 °F).  
The instrument is shipped with a rubber panel gasket (50  
to 60 Sh). To assure the IP65 and NEMA 4 protection,  
insert the panel gasket between the instrument and the  
panel as shown below.  
3) Easy access to the rear of the instrument.  
4) No corrosive gases (sulfuric gas, ammonia, etc.).  
5) No water or other fluid (i.e. condensation).  
6) Relative humidity of 20% to 80% non condensing.  
Install the instrument as follows:  
1) Insert the instrument in the gasket.  
2) Insert the instrument in the panel cutout.  
3) Pushing the instrument against the panel, insert the  
mounting bracket.  
4) Torque the mounting bracket screws between 0.3  
and 0.4 Nm (2.66 and 3.54 lbf-in).  
The instrument can be mounted on a panel up to 15 mm  
(0.591 in) thick with a square cutout of 45 x 45 mm (1.772  
x 1.772 in). For outline refer to Dimensions and Panel  
Cutout.  
5) To insure NEMA 4X/IP65 protection, make sure the  
instrument does not move within the cutout .  
Bracket  
Panel  
Gasket  
5
7sl-1-00.p65  
5
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS AND PANEL CUTOUT  
48 mm  
(1.890 in)  
48 mm  
(1.890 in)  
10 mm  
(0.394 in)  
122 mm (4.803 in) w/ RS-485  
105 mm (4.134 in) w/o RS-485  
75 mm  
(2.953 in)  
60 mm  
(2.362 in)  
45 mm, -0, +0.6 mm  
(1.772 in, -0, +0.024 in)  
45 mm, -0, +0.6 mm  
(1.772 in, -0, +0.024 in)  
6
7sl-1-00.p65  
6
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING GUIDELINES  
Terminal Layout  
A) Measuring Inputs  
NOTE: Any external components (like Zener diodes,  
etc.)connectedbetweensensorandinputterminalsmay  
cause errors in measurement due to excessive and/or  
not balanced line resistance or possible leakage cur-  
rents.  
+
NO  
A/A'  
C
6
11  
1
2
TC Input  
OUT 1  
OUT 2  
+
C
NO  
10  
12B/B'  
7
_
RS485  
_
9
C
NC  
8
13  
14  
3
4
5
Shield  
9
_
+
10  
TC  
DIG 1  
10 +  
15  
_
9
Shield  
NOTE:  
NOTE: When a relay output is used to drive an inductive  
load, connect an external snubber network (RC) across  
the terminals:  
1) Do not run input wires with power cables.  
2) For TC wiring use proper compensating cable,  
preferably shielded (see Thermocouple Compen-  
sating Cable Color Codes).  
R
C
3) Shielded cable should be grounded at one end  
only.  
in accordance with the following table:  
Load  
C
R
P
Resistor and  
Current  
(µF)  
()  
(W) Capacitor Voltage  
< 40 mA  
< 150 mA  
< 0.5 Amp  
0.047  
0.1  
100  
22  
1/2  
2
260 Vac  
260 Vac  
260 Vac  
0.33  
47  
2
7
7sl-1-00.p65  
7
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Linear Input  
RTD Input  
RTD  
RTD  
+
10  
+
_
mA,  
mV  
or  
_
9
V
Shield  
+
+
10  
8
8
9
10  
9
10  
mA  
mV  
or  
V
NOTE:  
_
_
9
1) Do not run RTD wires with power cables.  
2) Ground shielded cable at one end only.  
3) Use the correct size copper wires.  
G
4) The resistance of the 3 wires must be the same.  
NOTE:  
1) Do not run input wires with power cables.  
2) High line resistance can cause measurement  
errors.  
3) When shielded cable is used, ground it at one end  
only to avoid ground loop currents.  
4) The input impedance is equal to:  
B) Logic Input  
Less than 5 for 20 mAdc input  
Greater than 1 Mfor 60 mVdc input  
Greater than 400 Kfor 5 Vdc and 10 Vdc input  
This input is used as a remote reset.  
Safety note:  
-
-
Do not run logic input wiring with AC power cables.  
Use an external contact with a contact rating  
greater than 0.5 mA, 5 Vdc.  
-
The instrument needs 100 ms to recognize a  
contact status variation.  
Logic input  
14  
15  
8
7sl-1-00.p65  
8
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Thermocouple Compensating Cable Color Codes.  
Thermocouple  
Material  
T Copper Constantan  
British  
BS 1843  
White  
Blue  
Blue  
Yellow  
Blue  
Black  
Brown  
Blue  
Red  
White  
Blue  
Green  
White  
Blue  
Green  
Brown  
Blue  
American  
ANSI MC 96.1  
German  
DIN 43710  
Red  
French  
NFE 18-001  
Yellow  
Blue  
Blue  
+
-
+
-
Blue  
Red  
Blue  
White  
Red  
Black  
Yellow  
Red  
Yellow  
Black  
Red  
Green  
Black  
Red  
Green  
Violet  
Red  
+
-
+
-
Brown  
Brown  
Red  
Blue  
Blue  
Red  
Green  
Green  
Red  
White  
White  
Red  
J/L Iron Constantan  
+
-
+
-
+
-
+
-
Yellow  
Black  
Black  
Yellow  
Purple  
Yellow  
White  
Green  
Green  
White  
Green  
Green  
K Nickel Chromium  
Nickel Aluminum  
+
-
+
-
+
-
+
-
R Platinum/Platinum  
13% Rhodium  
+
-
+
-
+
-
+
-
S Platinum/Platinum  
10% Rhodium  
+
-
+
-
+
-
+
-
White  
White  
E Chromel  
Constantan  
+
-
+
-
Brown  
Violet  
Grey  
Red  
Grey  
B Platinum 30% Rh  
Platinum 6% Rh  
+
-
N Nicrosil / Nisil  
9
7sl-1-00.p65  
9
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C.1) Relay Outputs  
OUT 1  
C.2) Inductive Loads  
Highvoltagetransientsmayoccurwhenswitchinginduc-  
tive loads. Through internal contacts these transients  
may introduce disturbances which can affect the perfor-  
mance of the instrument. The same problem may occur  
when a switch is used in series with the internal contacts  
as shown below.  
NO - OUT 1  
C - OUT 1  
1
2
3
Class 1  
NC - OUT 1  
C
C
R
OUT 2  
Class 1  
(Alarm)  
6
7
POWER  
LINE  
NO  
LOAD  
For all the outputs, the internal protection (varistor)  
assures protection up to 0.5 Amp on inductive loads.  
The cable used for relay output wiring must be as far  
away as possible from input or communication cables.  
Relay output: Protected by varistor.  
OUT 1: Form C contact rating of 3 Amps/250 Vac  
resistive load.  
ItisgoodelectricalpracticetoinstallanadditionalRCnet-  
work across and as close to the external contacts as  
possible.  
OUT 2: Form A Contact rating of 2 Amps/250 Vac  
resistive load.  
Number of operations: 2 x 105 at the specified rating.  
The value of capacitor (C) and resistor (R) are shown in  
the following table.  
NOTES:  
Load  
Current  
C
(µF)  
R
()  
P
Resistor and  
1) To avoid shock and possible instrument damage,  
connect power last.  
(W) Capacitor Voltage  
2) For power connections use 16 AWG or larger wires  
rated for 75 °C.  
3) Use copper conductors only.  
4) Do not run input wires with power cables.  
< 40 mA  
< 150 mA  
< 0.5 Amp  
0.047  
0.1  
100  
22  
1/2  
2
260 Vac  
260 Vac  
260 Vac  
0.33  
47  
2
1 0  
7sl-1-00.p65  
10  
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D) Serial Interface  
The RS-485 interface can connect up to 31 instruments  
with the remote master unit (see below).  
For units built with optional RS-485 communication  
I
I
A'/A  
B'/B  
A/A'  
B/B'  
N
S
T
R
U
M
E
N
T
A'/A  
B'/B  
A/A'  
B/B'  
11  
12  
13  
N
S
T
R
U
M
E
N
T
11  
12  
13  
M
A
S
T
E
R
M
A
S
T
E
R
COMMON  
COMMON  
I
11  
12  
13  
N
S
T
R
U
M
E
N
T
Maximum cable length: 1.5 km (9/10 mile) at 9600 baud.  
NOTE: According to EIA specification for RS-485:  
a) The “A” terminal of the generator shall be negative  
with respect to the “B” terminal for a binary 1  
(MARK or OFF) state.  
b) The “A” terminal of the generator shall be positive  
with respect to the “B” terminal for a binary 0  
(SPACE or ON) state.  
1 1  
7sl-1-00.p65  
11  
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E) Power Line and grounding  
PRELIMINARY HARDWARE SETTINGS  
N, L2  
1) Remove the instrument from its case.  
2) Set J106 according to the following table:  
4
POWER SUPPLY  
100 to 240 Vac  
24 Vac/Vdc  
5
N, L2  
R (S,T), L1  
R (S,T), L1  
J106  
Input Type  
1-2  
3-4  
5-6  
7-8  
NOTE:  
T/C, RTD,  
0-60 mV, 12-60 mV  
(standard configuration)  
1) Before connecting the power line, check that the  
voltage is correct (see Model Number).  
2) For supply connections use 16 AWG or larger wires  
rated for at least 75 °C.  
open  
close  
open open  
0-5 V, 1-5V  
open close open open  
open open close open  
open open open close  
3) Use copper conductors only.  
0-10V, 2-10 V  
4) Do not run input wires with power cables.  
5) Polarity does not matter for 24 Vdc wiring.  
6) The power supply input is not fuse protected.  
Please provide it externally.  
0-20 mA, 4-20 mA  
Input CTTC R192=180K  
SH120=Closed CH101=Open  
Power Supply  
24 Vac/Vdc  
Type  
Current  
500 mA  
125 mA  
Voltage  
250 V  
T
T
100/240 Vac  
250 V  
When the fuse is damaged the instrument should be  
returned to your supplier to check the power supply.  
7) Safety requirements for permanently connected  
equipment:  
-
Include a switch or circuit-breaker in the  
installation.  
-
Place the switch in close proximity to the  
equipment and within easy reach of the  
operator.  
-
Mark the switch as the disconnecting device for  
the equipment. NOTE: A single switch or  
circuit-breaker can drive more than one  
instrument.  
8) When the NEUTRAL line is present, connect it to  
terminal 4.  
9) To avoid shock and possible instrument damage,  
connect power last.  
1 2  
7sl-1-00.p65  
12  
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limitrol with RS-485  
2
1
4
3
6
5
8
7
J106  
V101  
Limitrol without RS-485  
1 3  
7sl-1-00.p65  
13  
9/17/02, 2:39 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONFIGURATION KEY FUNCTIONS  
RESET In Configuration Mode, used only to scroll  
back parameters  
The following is a complete list of parameters. The lower  
display will show the parameter code (L1 to d1) and the  
upper display will show the selection code or numerical  
value. No timeout is applied in the configuration mode.  
Used in Configuration Mode to decrease the  
parameter value.  
L1  
=
Serial Interface Protocol  
(Skipped if option is not available.)  
OFF = No serial interface  
nbUS= Modbus  
Used in Configuration Mode to increase the  
parameter value.  
jbUS = Jbus  
FUNC Monitors/Modifies parameters.  
L2  
=
Serial Link Device Address  
+
Loads the default parameters.  
(Skipped if option is not available or L1 = OFF)  
From 1 to 255  
+ FUNC or + FUNC  
Increases/decreases values at a higher rate  
when modifying parameters.  
NOTE: The device can connect up to 31 instruments.  
L3  
=
Baud Rate for Serial Link  
(Skipped if option is not available or L1 = OFF)  
Set value from 600 to 19200 baud.  
+ RESET or + RESET  
Jumps to the Maximum or Minimum parameter  
value when modifying parameters.  
(19200 baud is shown on display as 1920)  
L4  
=
Byte Format for Serial Link  
CONFIGURATION PROCEDURE  
(Skipped if option is not available or L1 = OFF)  
8E = 8 bits + even parity  
8O = 8 bits + odd parity  
1) Remove the instrument from its case.  
2) Open switch V101 (See illustrations under “Prelimi-  
nary Hardware Settings.”)  
8
= 8 bits without parity  
3) Re-insert the instrument in its case.  
4) Switch on power to the instrument.  
The upper display will show COnF.  
5) Press the “ ” key and the lower display will show the  
firmware version.  
Press the "FUNC" key to start the configuration proce-  
dure with the first parameter (L1). Press the "RESET"  
key to start the configuration procedure with the last  
parameter (d1).  
1 4  
7sl-2-00.p65  
14  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
r1 =  
Input Type and Range Value  
r2 = Decimal Point Position  
0
1
2
3
4
5
6
7
8
9
=
=
=
=
=
=
=
=
=
=
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
J
From -100  
From -100  
From -200  
From -100  
From -100  
to 1000 °C  
to 1370 °C  
(Available only for linear range r1 = 15 to 22)  
K
T
E
N
S
R
B
L
U
G
D
C
_ _ _ _ .  
_ _ _ . _  
_ _ . _ _  
_ . _ _ _  
= No decimal  
to  
to  
400 °C  
800 °C  
= One decimal place  
= Two decimal places  
= Three decimal places  
to 1400 °C  
to 1760 °C  
to 1760 °C  
to 1820 °C  
From  
From  
From  
-50  
-50  
0
r3 = Low Scale Range Value  
(Available only for linear range r1 = 15 to 22)  
Range: From -1999 to 9999  
From -100  
From -200  
to  
to  
900 °C  
600 °C  
10 =  
11 =  
12 =  
13 =  
14 =  
15 =  
16 =  
17 =  
18 =  
19 =  
20 =  
21 =  
22 =  
23 =  
24 =  
25 =  
26 =  
27 =  
28 =  
29 =  
30 =  
31 =  
32 =  
33 =  
34 =  
35 =  
36 =  
37 =  
From  
From  
From  
0
0
0
to 2300 °C  
to 2300 °C  
to 2300 °C  
to 1400 °C  
r4 = High Scale Range Value  
(Available only for linear range r1 = 15 to 22)  
Range: From -1999 to 9999  
TC Plat. II  
RTD Pt 100 From -200  
From -100  
to  
to  
to  
to  
to  
to  
to  
to  
to  
850 °C  
60 mV  
60 mV  
20 mA  
20 mA  
r5 = Offset Adjustment  
Range: From -500 to 500  
Offset value algebraically added to the measured value.  
Linear  
Linear  
Linear  
Linear  
Linear  
Linear  
Linear  
Linear  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
TC  
From  
From  
From  
From  
From  
From  
From  
From  
0
12  
0
4
0
1
0
2
r6 = Time Constant for Filter on Displayed Value  
Range: From 0 (filter OFF) to 8 seconds.  
(First order filter with selected time constant.)  
5
5
V
V
V
V
10  
10  
r7 = Alarm Action on Fault  
uP = The alarm assumes an upscale reading.  
doun = The alarm assumes a downscale reading.  
J
K
T
From -150  
From -150  
From -330  
From -150  
From -150  
to 1830 °F  
to 2500 °F  
to  
750 °F  
E
N
S
R
B
L
U
G
D
C
to 1470 °F  
to 2550 °F  
to 3200 °F  
to 3200 °F  
to 3300 °F  
to 1650 °F  
to 1110 °F  
to 4170 °F  
to 4170 °F  
to 4170 °F  
to 2550 °F  
to 1560 °F  
C1 = Type of Limit Action  
Hi. = High limit (for heating process)  
Lo. = Low limit (for cooling process)  
Hi.Lo = Band limit (for special process)  
From  
From  
From  
-60  
-60  
32  
From -150  
From -330  
C2 = Acknowledgment Mode  
O = The acknowledgment action is ignored if performed  
when setpoint is exceeded.  
I = The acknowledgment action is recognized also  
when the setpoint is exceeded. (In this case, the  
control output is instantaneously restored when  
process variable is within setpoint).  
From  
From  
From  
0
0
0
TC Plat. II  
RTD Pt100 From -330  
From -150  
1 5  
7sl-2-00.p65  
15  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Output Function  
Example of limit function when C1 = Hi and C2 = O  
The relay output operates in fail-safe mode (relay de-  
energized during reset condition) and latching mode.  
HS  
(Setpoint  
threshold  
Su  
(Setpoint  
threshold)  
The control output turns OFF when the setpoint is ex-  
ceeded when C1 = Hi, or C1 = Lo. (When C1 = Hi.Lo  
control output turns off when the process is greater than  
“Su” or less than “S1”).  
hysteresis)  
ON  
Relay OUT 1  
OFF  
ON  
"Reset" LED  
OFF  
The control output remains OFF until the process is  
within setpoint and the acknowledge action has been  
performed (the sequence of action may or may not be  
important depending on parameter C2).  
Flash  
Upper display  
Steady  
FLASH  
B
FLASH  
A
C
The upper display flashes when the setpoint is exceeded  
andreturnstoasteadydisplaywhentheprocessiswithin  
setpoint.  
A, B, C = Acknowledgment action by RESET button,  
digitalinputorseriallink. NOTE:AcknowledgmentBhas  
no effect.  
When the control output is OFF the RESET LED is ON  
(if C2 = 0) or flashes (if C2 = 1).  
Example of limit function when C1 = Hi and C2 = 1  
When C2 = 1 the RESET LED is steady ON when control  
output is OFF and acknowledged.  
Su  
(Hysteresis)  
(Setpoint  
The reset condition can be stored in permanent memory  
(see C4).  
threshold)  
ON  
Relay OUT 1  
OFF  
Acknowledgment can be performed by pressing the  
RESET key, by momentarily closing the external dry  
contact or by a command from the serial link.  
ON  
"Reset" LED  
OFF  
FLASH  
FLASH  
FLASH  
FLASH  
The length of the reset condition and max/min values  
detected are stored in memory and available for viewing  
until the next reset condition occurs. The information is  
lost at power down.  
Flash  
Upper display  
Steady  
A
B
During a reset condition the values are continuously  
updated and can be monitored.  
A, B = Acknowledgment action by RESET button, digital  
input or serial link.  
1 6  
7sl-2-00.p65  
16  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C3  
=
Reset at Power-up  
LED lit steady  
Relay in alarm status  
P2 = H.A.  
Ack.  
Auto = Automatic reset  
Alarm  
still  
exists  
=
Manual reset  
nAn  
No  
Ack.  
LED flashing  
Relay in alarm status  
C4  
0
=
=
Reset Memory  
Alarm  
clears  
LED off  
Relay not in alarm status  
The reset condition will be saved (at next  
power up it will be reactivated)  
The reset condition will be lost in case of  
power down  
P2 = L.A.  
LED lit steady  
Ack.  
P2 = H.A.Ac  
1
=
Alarm  
still  
exists  
Relay not in alarm status  
No  
Ack.  
LED flashing  
Relay in alarm status  
C5 = Time Constant for Filter on Measured Value  
for Reset Action  
Range: From 0 (filter OFF) to 8 seconds  
Note: First order filter with selected time Constant.  
Alarm  
clears  
LED off  
Relay not in alarm status  
P2 = L.A.Ac  
P2 = H.L.  
LED lit steady  
Ack.  
Alarm  
still  
exists  
Relay in alarm status  
P1 = Alarm Function  
(Skipped if option not available)  
nonE = Not provided  
AL.P = Process alarm  
AL.b = Band alarm  
No  
Ack.  
LED flashing  
Relay in alarm status  
LED OFF  
Relay not in alarm status  
Ack.  
Alarm  
clears  
P2 = L.L.  
No  
Ack.  
LED flashing  
Relay in alarm status  
AL.d = Deviation alarm  
When C1 = Hi.Lo, “AL.b” and “AL.d” are not available.  
Ack. = Alarm Acknowledgment  
(For relay status see configuration parameter P3.)  
P2  
=
Alarm configuration  
(Skipped if option is not available or P1 = none)  
H.A. = High alarm with automatic reset  
Example for P2 = H.A.  
L.A.  
=
Low alarm with automatic reset  
(Alarm  
threshold)  
(Hysteresis)  
H.A.Ac = High alarm with automatic reset and  
acknowledge  
Alarm status*  
Relay  
No alarm status  
L.A.Ac =Low alarm with automatic reset and  
acknowledge  
H.L.  
L.L.  
=
=
High alarm with manual reset  
Low alarm with manual reset  
ON  
ALM LED  
OFF  
FLASH  
FLASH  
NOTE: For band alarm, H.A./H.A.Ac/H.L. signifies  
outside band alarm, while L.A./ L.A.Ac/L.L. signifies  
inside band alarm.  
ACK  
ACK = Alarm acknowledgment from "AK" parameter  
or serial link.  
For every alarm configuration:  
LED flashes, relay placed in alarm status  
* Alarm Status:Relay energized (P3 = dir)  
Relay de-energized (P3 =rEV)  
1 7  
7sl-2-00.p65  
17  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Example for P2 = H.A.A.c  
(Hysteresis)  
P3 = Alarm Action  
(Skipped if option not is available or P1 = none)  
(Alarm  
threshold)  
dir  
=
Direct action  
(Relay energized in alarm condition)  
Reverse action  
(Relay energized in non-alarm condition)  
Alarm status*  
Relay  
No alarm status  
rEV  
=
ON  
ALM LED  
OFF  
P4  
=
Alarm Standby Function  
FLASH  
FLASH  
(Skipped if option is not available or P1= none)  
OFF =  
On  
Standby function disabled  
Standby function enabled  
ACK  
=
ACK = Alarm acknowledgment from "AK" parameter  
or serial link.  
If the alarm is programmed as band or deviation, this  
function masks the alarm condition at start up and at a  
“Su” setpoint change until the process variable reaches  
thealarmthreshold,plusorminushysteresis.Thisstandby  
functionmasksaProcessAlarmconditionatstartupuntil  
the process variable reaches the alarm threshold plus or  
minus hysteresis.  
* Alarm Status:Relay energized (P3 = dir)  
Relay de-energized (P3 =rEV)  
Example for P2 = H.L.  
PF = Time Constant for Filter on Measured Value for  
Alarm Action  
(Skipped if option is not available or P1 = none)  
Range: From 0 (filter OFF) to 8 seconds  
(First order filter with selected time constant.)  
(Alarm  
threshold)  
(Hysteresis)  
Alarm status*  
Relay  
No alarm status  
n 1 = Safety Lock  
ON  
ALM LED  
OFF  
0
=
UNLOCKed.ThedeviceisalwaysUNLOCKed  
and all parameters can be modified.  
LOCKed. The device is always LOCKed and  
no parameters can be modified  
FLASH  
FLASH  
l
=
ACK  
ACK  
ACK = Alarm acknowledgment from "AK" parameter  
or serial link.  
From 2 to 9999 = This number is a password, to be used  
in run time (see “nn”), to LOCK/UNLOCK the  
device.  
* Alarm Status:Relay energized (P3 = dir)  
Relay de-energized (P3 =rEV)  
1 8  
7sl-2-00.p65  
18  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
t1 = Timeout Selection  
tn10 =  
tn30 =  
10 second timeout  
30 second timeout  
d1 = Digital Input (contact closure)  
(This is a read only parameter)  
Enb =  
dlS  
Digital input enabled  
Digital input disabled  
=
(The digital input is used as a remote process restart.)  
The configuration procedure is now complete. The  
display should show "COnF".  
1 9  
7sl-2-00.p65  
19  
9/17/02, 2:40 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING MODE  
6) The upper display shows the minimum value of the  
process variable detected during the last "reset" con-  
dition while the lower display shows "PL.” (if no data  
is available, the upper display will show “- - - -”) This  
information is not available if C1 = Hi. The information  
is lost at power down and at powerup the device will  
display the process variable .  
1) Remove the instrument from its case.  
2) Set switch V101 to the closed position.  
3) Re-insert the instrument in its case.  
4) Switch on the instrument.  
Normal Display Mode  
On powerup the device starts in the "Normal Display  
Mode."  
NOTE: in case the “reset condition” was generated by  
a fault condition in the measure variable, the upper  
By pressing the  
displayed information; therefore, one of the following  
display modes can be selected:  
or key, it is possible to change the  
"m.Err"  
display will indicate  
At powerup the display will show the process variable  
unless otherwise stated in one of the above display  
options  
1) The upper display shows the measured value while  
the lower display shows the "Pu" (Process variable)  
2) The upper display shows the setpoint threshold while  
thelowerdisplayshows"Su." Ifthisdisplaywasactive  
at power down, it will be active at powerup.  
3) The upper display shows the setpoint1 threshold  
while the lower display shows "S1." This information  
is available only if C1 = Hi.Lo If this display was active  
at power down, it will be active at powerup  
4) The upper display shows the total time (hh.mm) of the  
last reset condition while the lower displays shows “t.”  
(if no data is available, the upper display will show  
"- - - -" ). The information is lost at power down and at  
powerup the device will display the process variable.  
5) The upper display shows the maximum value of  
process variable detected during the last "reset" con-  
dition while the lower display shows "Ph." (if no data  
is available, the upper display will show “- - - -” ). This  
informationisnotavailableifC1=Lo. Theinformation  
is lost at power down and at powerup the device will  
display the process variable.  
If, at power off, the device was in reset condition and  
configured to save it (C4 = 0), and/or it was programmed  
for manual reset at startup (C3 = 1), then at the next  
power up the lower display will be flashing.  
Indicators  
“RESET“  
=
Indicates control output status  
as follows:  
a) With configuration parameter  
C2 = 0  
LED ON when Output is OFF  
LED OFF when Output is ON  
b) With configuration parameter  
C2 = 1  
LEDflasheswhenOutputisOFF  
LED ON when Output is OFF  
and acknowledged  
LED OFF when Output is ON  
Indicatesalarmstatusasfollows:  
Flashes when alarm is ON  
ON when alarm has been  
acknowledged  
“ALM”  
=
NOTE: In case the reset condition was generated by a  
fault condition in the measure variable, the upper display  
"m.Err"  
will indicate  
OFF when alarm is OFF  
2 0  
7sl-3-00.p65  
20  
9/17/02, 2:41 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Allparameters(except )canbemodifiedonlywhenthe  
device is UNLOCKed.  
Key Functions in Normal Display Mode  
“FUNC”  
=
By pressing it, the display changes from  
“Normal Display Mode” to “Parameter  
Display Mode.”  
TheLOCK/UNLOCKstatuscanbeselectedinconfigura-  
tion using parameter n1 or during the operating mode  
with the parameter password.  
=
Pressing it for more than ten seconds  
initiates the Lamp Test. During the  
LampTestthedevicefunctionsnormally  
while all display segments and LED's  
are lit with a 50% duty cycle. No timeout  
is applied to a lamp test.  
To switch from LOCKED to UNLOCKED, enter the n1  
parameter setting. To switch from UNLOCKED to  
LOCKED, enteranynumberotherthanthen1parameter  
setting.  
When the device is in remote (the serial link controls the  
device) no parameters can be modified.  
Press the "FUNC" key again to end the  
Lamp Test.  
Key Functions in Parameter Display Mode  
"
" or “ " = By pressing these keys it is possible to  
change the displayed information. See  
FUNC  
=
Press the “FUNC” key again and the  
instrument stores the new setting  
(if changed) and goes to the next  
parameter.  
“NormalDisplayModeonpreviouspage.  
“RESET”  
=
Press and hold for 1 second to initiate  
“reset.”  
or  
=
=
Changes the setting of the selected  
parameter.  
Parameter Display Mode  
The "FUNC" key initiates the Parameter Display Mode  
when pressed for less than 10 seconds in the "Normal  
Display Mode."  
RESET  
Pressandholdformorethan1secondto  
initiate reset.  
The lower display shows the parameter identification  
codewhiletheupperdisplayshowstheparametervalue.  
The value of these parameters can be modified with the  
and keys.  
Press the "FUNC" key again to store the new value and  
advance to the next parameter.  
If no keys are pressed within the timeout period (see t1),  
the display will automatically return to the "Normal Dis-  
play Mode" in the previous display and any modifications  
of the last displayed parameter will be lost.  
2 1  
7sl-3-00.p65  
21  
9/17/02, 2:41 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING PARAMETERS  
Alarm Threshold (optional)  
(Available only if P1=AL.P, AL.b or AL.d.)  
Lower display: AL  
Upper display: Alarm threshold value  
Range:  
Some of the following parameters may not appear,  
depending on the configuration.  
Alarm Acknowledge  
(Available only if P1 = AL.p, AL.b or AL.d)  
Lower display:  
Span limits  
From 0 to 500  
From -500 to 500 (if deviation alarm P1 = AL.d)  
(if process alarm  
(if band alarm  
P1 = AL.P)  
P1 = AL.b)  
Upper display: OFF/ON  
Select ON and press the FUNC key  
in order to acknowledge the alarm.  
ON = Alarm Acknowledged  
OFF = Alarm Not Acknowledged  
Alarm Hysteresis (optional)  
(Available only if P1 = AL.P, AL.b or AL.d)  
Lower display: HA  
Upper display: Hysteresis value  
Range:  
From 0.1% to 10.0% of span value  
or 1 LSD  
Software Key  
(Skipped if n1 = 0 or 1)  
Lower display: nn  
Serial LInk (optional)  
Upper display: Numeric password to  
LOCK/UNLOCK the device  
NOTE: The upper display will  
initially show the "LOCK" status.  
ON = the device is LOCKED.  
OFF = the device is UNLOCKED.  
The device can be connected to a host computer via  
serial link.  
The host can put the device in LOCAL (parameters are  
controlled via keyboard) or in REMOTE (functions and  
parameters are controlled via serial link).  
Setpoint Threshold  
Lower display: Su  
REMOTE is signified by the decimal point to the left of  
"RMT" which is on the right side of the numeric display.  
Upper display: Setpoint threshold value  
Range:  
Span limits (From "S1" to high span  
limit when C1 = Hi.Lo)  
Via serial link it is possible to read and/or to modify all the  
operative and configuration parameters.  
The following conditions must apply to implement this  
function:  
Setpoint1 Threshold  
(Available when C1 = Hi.Lo)  
Lower display: S1  
1) Configure parameters L1 through L4 with the front  
keyboard  
Upper display: Setpoint threshold value  
2) The device must be in the Operating mode.  
Range:  
From low span limit to "Su"  
Control output is OFF during the download procedure.  
Setpoint Threshold Hysteresis  
Lower display: HS  
Upper display: Hysteresis value  
At the end of configuration downloading procedure the  
devicepreformsanautomaticresetandreturnstonormal  
condition.  
Range:  
From 0.1% to 10.0% of span value  
or 1 LSD  
2 2  
7sl-3-00.p65  
22  
9/17/02, 2:41 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ERROR MESSAGES  
Error List  
100  
Error in EEPROM writing  
Overrange, Underrange and  
Sensor Break Indications  
150  
200  
XXX  
301  
307  
400  
500  
502  
510  
Short circuit on CPU's outputs  
Error on "protect register" in EEPROM  
Configuration parameter error.  
Error on calibration of selected input.  
rj input calibration error.  
Error on operative parameter.  
Error on autozero measurement.  
Error on reference junction measurement.  
Error during calibration procedure.  
This device detects process variable faults  
(OVERRANGE,UNDERRANGEORSENSORBREAK).  
When the process variable exceeds the span limits  
established by configuration parameter r1 an  
OVERRANGE condition will appear as:  
Dealing with Error Messages  
1) When a configuration parameter error is detected,  
repeat the configuration procedure of that specific  
parameter.  
An UNDERRANGE condition will appear as:  
2) If an error 400 is detected, simultaneously press  
the  
and keys to load the default parameters  
and then repeat the control parameter setup.  
3) For all other errors, contact your  
Service Representative.  
A sensor break is signaled as "OPEN”. On the mA/V  
input, a sensor break can be detected only when the  
range selected has a zero elevation (4/20 mA, 12/60 mV,  
1/5 V or 2/10 V.)  
On the RTD input "shrt" is signalled when input resis-  
tance is less than 15 (short circuit sensor detection).  
This device detects reference junction errors or errors on  
the internal autozero measurement. When a fault is  
detectedtheoutputgoesOFFandthealarmassumesan  
upscale/downscale reading in accordance with r7.  
Error Messages  
On powerup, the instrument performs a self-diagnostic  
test. When an error is detected, the lower display shows  
an"Er" indicationwhiletheupperdisplay showsthecode  
of the detected error.  
2 3  
7sl-4-00.p65  
23  
9/17/02, 2:42 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEFAULT PARAMETERS  
Default Operating Parameters List  
Parameter Default Value  
Alarm Acknowledge OFF  
Loading Default Operating Parameters  
The control parameters can be loaded with predeter-  
mined default values. These are the settings loaded into  
the instrument prior to shipment from the factory. To load  
the default values proceed as follows:  
Software Key  
Setpoint Threshold  
Unlock  
Low range value (if low limit)  
High range value (if high or high/  
low limit)  
Setpoint1 Threshold Low range value  
Setpoint Threshold  
a) Press and hold the key and press the  
displays will show:  
key; the  
Hysteresis  
0.1%  
Alarm Threshold  
Low range (if process alarm)  
100 (if deviation or band alarm)  
0.1%  
Alarm Hysteresis  
Loading Default Configuration Parameters  
The configuration parameters can be loaded with prede-  
termined default values. These are the settings loaded  
into the instrument prior to shipment from the factory. To  
load the default values proceed as follows:  
b) Press either the or  
key; the display will show:  
a) Internal switch V101 must be open.  
b) The upper display will show:  
c) Press the "FUNC" key; the display will show:  
c) Press the key; the lower display will show the  
firmware version.  
This indicates that the loading procedure has been  
initiated. After about 3 seconds the loading procedure is  
complete and the instrument reverts to the “Normal  
Display Mode.” The following is a list of the default  
operating parameters loaded during the procedure:  
2 4  
7sl-4-00.p65  
24  
9/17/02, 2:42 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
d) Still holding the key, press the key; the display  
will show:  
Default Configuration Parameter List  
PARA.  
Table 1  
Table 2  
European  
American  
L1  
L2  
L3  
L4  
r1  
nbUS  
nbus  
1
1
19200  
19200  
e) Press the  
key to select Table 1 (European) or  
8E  
8E  
Table 2 (American) default parameters; the display  
will show:  
Type J  
Type J  
(-100 to 1000 °C)  
(-150 to 1830 °F)  
r2  
——.  
-100  
——.  
-150  
r3  
r4  
1000  
0
1830  
0
r5  
r6  
1 second  
uP  
1 second  
uP  
f) Press the FUNC key; the display will show:  
r7  
c1  
c2  
c3  
c4  
c5  
P1  
P2  
P3  
P4  
PF  
n1  
t1  
Hi  
Hi  
1
0
Auto  
0
Auto  
0
This indicates that the loading procedure has been  
initiated. After about 3 seconds the procedure is com-  
plete and the instrument reverts to the “COnF” display.  
The following is a list of the default configuration param-  
eters loaded during the procedure:  
1 second  
nonE  
H.A.  
1 second  
nonE  
H.A.Ac  
rEV  
rEV  
OFF  
OFF  
1 second  
0
1 second  
0
10 seconds  
30 seconds  
2 5  
7sl-4-00.p65  
25  
9/17/02, 2:42 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Case RABS Grey dark color (RAL 7043).  
“ALM” indicates alarm status as follows:  
Flashes when alarm is ON.  
ON when alarm has been  
acknowledged  
Self-extinguishing degree V0  
according to UL 94  
OFF when alarm is OFF  
Front panel Designed and tested for IP65 and NEMA  
4Xforindoorlocation (whenpanelgasket  
is installed). Tests were performed in  
accordance with IEC 529, CEI 70-1 and  
NEMA 250-1991 STD.  
RMT  
A decimal point on the right side  
of the upper display flashes to  
indicate the device is controlled  
by serial link  
Keyboard  
Four keys (covered by polyester mem-  
brane) labelled RESET, & FUNC.  
Installation Panel mounting  
,
Rear Terminal Block  
Power Supply 100 to 240 Vac 50/60 Hz switching or  
24 Vac/Vdc with interruptions less than  
100 ms  
15 screw terminals with safety rear cover  
Dimensions Unit with RS-485 communications  
DIN 43700 48 x 48 mm x 122 mm  
(1.890 x 1.890 in. x 4.803 in).  
Dimensions Unit without RS-485 communications  
DIN 43700 48 x 48 mm x 105 mm  
(1.890 x 1.890 in. x 4.134 in).  
Power Supply Variation  
-15% to 10% (for 100 to 240 Vac)  
-10% to 10% (for 24 Vac/Vdc)  
Power Consumption 8 VA max  
Insulation Resistance Greater than 100 MΩ  
Insulation Strength1500 V rms for 1 minute  
EC Compatibility  
Cutout  
Weight  
45 x 45 mm (1.772 x 1.772 in).  
250 g (8.75 oz).  
Upper Display 4 digits, 7 segment red LED’s with  
decimal point, 7.62 mm high (0.3 in).  
Lower Display 2 digits, 7 segment red LED’s with  
decimal point, 7.62 mm high (0.3 in).  
Conforms with 89/336/EEC directives re-  
garding electro-magnetic compatibility  
Emission Complies with:  
Generic emission standard EN50081-2  
Immunity Complies with the generic im-  
munity standard EN50082-2. Conforms  
with72/23/EECand93/68/EECdirectives  
regardinglowvoltage. Itcomplieswiththe  
safety requirements for electrical equip-  
ment for measurement, control and  
laboratory use, Generic Standard  
EN61010-1, Installation Category II.  
Sampling  
Indicator  
2 red LED annunciators for:  
“RESET” Indicates control output status  
as follows:  
a)  
b)  
With configuration parameter  
C2 = 0  
LED ON when Output is OFF  
LED OFF when Output is ON  
With configuration parameter  
C2 = 1  
LED flashes when Output is OFF  
LED ON when Output is OFF  
and acknowledged  
Time  
250 ms for linear input  
500 ms for TC/RTD input  
LED OFF when Output is ON  
2 6  
7sl-5-00.p65  
26  
9/17/02, 2:43 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Display Update Time  
Range  
1) TC type J  
2) TC type K,  
3) TC type T  
4) TC type E  
5) TC type N  
6) TC type S  
7) TC type R  
8) TC type B  
-100 to 1000 °C  
-150 to 1830 °F  
-100 to 1370 °C  
-150 to 2500 °F  
-200 to 400 °C  
-330 to 750 °F  
-100 to 800 °C  
-150 to 1470 °F  
-100 to 1400 °C  
-150 to 2550 °F  
-50 to 1760 °C  
-60 to 3200 °F  
-50 to 1760 °C  
-60 to 3200 °F  
500 ms  
The display value can be filtered  
Reference Accuracy  
± 0.2% fsv ±1 digit @ 25 °C and nominal  
power supply voltage.  
Temperature Drift  
Less than 200 ppm/°C of full span for mV  
and TC ranges 1, 2, 4, 5, 9, 14 (CJ  
excluded).  
Less than 300 ppm/°C of full span for mA/  
V and TC ranges 11, 12, 13 (CJ excluded)  
Lessthan400ppm/°CoffullspanforRTD  
range 15 and TC range 10 (CJ excluded).  
Less than 500 ppm/°C of full span for TC  
ranges 3, 6, 7 (CJ excluded).  
Less than 600 ppm/°C of full span for TC  
range 8.  
NOTE: Precision and drift guaranteed  
(for T>300°C/570°F).  
0
to 1820 °C  
32 to 3300 °F  
9) TC type L [DIN43710-1977]  
-100 to 900 °C  
-150 to 1650 °F  
10) TC type U [DIN43710-1977]  
Reference Junction Drift  
-200 to 600 °C  
-330 to 1110 °F  
0.1 °C/°C  
Common Mode Rejection Ratio  
120 dB @ 50/60 Hz  
Normal Mode Rejection Ratio  
60 dB @ 50/60 Hz  
11) TC type G [W - W, 26% Re]  
to 2300 °C  
to 4170 °F  
12) TC type D [W, 3% Re - W, 25% Re]  
0
0
Ambient Temperature  
0 to 50 °C  
Storage Temperature  
-20 to 70 °C  
0
0
0
0
to 2300 °C  
to 4170 °F  
to 2300 °C  
to 4170 °F  
13) TC type C  
Humidity  
Input  
Maximum of 85% RH non condensing  
14) TC type Platinel II  
Thermocouple (J, K, T, E, N, S, R, B, L, U,  
G, D, C, Platinel II), RTD Pt100, mVdc,  
Vdc, mAdc. The type of inputs are key-  
board and jumper selectable.  
-100 to 1400 °C  
-150 to 2550 °F  
-200 to 850 °C  
-330 to 1560 °F  
15) RTD PT100  
16) Linear  
17) Linear  
18) Linear  
19) Linear  
0
0
0
0
to  
to  
to  
to  
20 mA  
60 mV  
5
V
V
10  
2 7  
7sl-5-00.p65  
27  
9/17/02, 2:43 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Source Impedance  
100 maximum for TC/mV input  
Less than 20 per wire for RTD input  
Input Impedance  
Alarm Function  
Process alarm  
Deviation alarm  
Band alarm  
Greater than 1 Mfor TC/mV input  
Greater than 400 Kfor 5V to 10V input  
range  
Type of Alarm  
High/Low (Outside/Inside if band alarm)  
Direct/Reverse  
Less than 5 for mA input  
Cold Junction  
Automatic/Manual reset  
Standbysequence/Nostandbysequence  
Automatic compensation from 0 to 50 °C  
Digital Input Input from dry contact (voltage free) to  
restart process (optional)  
Alarm Threshold  
Span limits for process alarm  
From 0 to 500 digits for band alarm  
Control OUT 1  
From-500to500digitsfordeviationalarm  
Relay(formC)3Amp@250Vacresistive  
load (with varistor on contacts)  
(Relay operates in failsafe mode)  
Limit Type High limit (for heating process)  
Low limit (for cooling process)  
High/Low limit (for special process)  
Acknowledgment Mode  
Alarm Hysteresis  
From 0.1 to 10.0% of span value or 1 LSD  
(whichever is greater)  
Serial Interface  
RS-485 Opto-isolated (optional)  
Protocol Type  
Modbus/Jbus (RTU mode)  
To restart the process, two conditions  
must apply  
Device Address  
From 1 to 255. NOTE: The interface can  
a) The process returns within setpoint  
b) The operator has acknowledged the  
process (from keyboard, digital input or  
serial link)  
support up to 31 devices  
Baud Rate 600 up to 19200 baud  
Format  
1 start bit  
8 bit with/without parity  
1 stop bit  
The “a” and “b” sequence may or may not  
matter depending on C2 (see C2)  
Power-Up Mode  
Parity  
Even/Odd  
Watch dog Hw/Sw is provided for automatic restart  
Protection Internal dip switch for calibration and con-  
figuration parameter protection.  
Automatic or Manual restart. When in  
automaticrestartthecontroloutputisguar-  
anteed OFF for 1 second.  
Setpoint Threshold  
Span limits  
Threshold hysteresis  
From 0.1 to 10.0% of span value or 1 LSD  
(whichever is greater)  
OUT 2  
Relay(formA)2Amp@250Vacresistive  
load. OUT 2 is used as alarm output  
(optional)  
2 8  
7sl-5-00.p65  
28  
9/17/02, 2:43 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
References  
UL 94  
ENV50141  
Electromagnetic compatibility - Basic im-  
munitystandard-Conducteddisturbances  
induced by radio-frequency fields - Immu-  
nity test.  
Tests for flammability of plastic materials  
for pans in devices and appliances  
CEI 70-1 (IEC 529)  
Degrees of protection provided by enclo-  
sures (IP Code)  
NEMA 250-1991  
DIN 43710-1977  
Thermocouples - Reference table.  
IEC 584-1  
DIN 43760  
Thermocouples-Part1-Referencetable.  
Thermometer Reference table.  
Enclosures for equipment (1000 Volts  
maximum)  
DIN 43700  
Measurements and control instruments  
for panel mounting. Nominal front and  
cut-out dimensions.  
EN 50081-2 Electromagnetic compatibility - Generic  
emission standard - Part 2. Industrial  
environment.  
EN 55011  
Limits and methods of measurement of  
radio disturbance characteristics of in-  
dustrial,scientificandmedical(ISM)radio  
frequency equipment.  
EN 50082-2 Electromagnetic compatibility - Part 2 -  
Industrial environment  
ENV50140  
Electromagnetic compatibility - Basic im-  
munity standard -  
Radiated radio - frequency electro-mag-  
netic field- Immunity test.  
IEC 1000-4-2 Electromagnetic compatibility (EMC)  
Part 4: Testing and measurement tech-  
nique. Section 2: Electrostatic discharge  
immunity test.  
EN-61000-4-8Electromagnetic compatibility (EMC)  
Part 4: Testing and measurement tech-  
niques  
Section8:Powerfrequencymagneticfield  
immunity test.  
IEC 1000-4-4 Electromagnetic compatibility. Part 4:  
Testing and measurement techniques -  
Section 4: Electrical fast transient/burst  
immunity test.  
2 9  
7sl-5-00.p65  
29  
9/17/02, 2:43 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CALIBRATION PROCEDURE  
f) during calibration, connect one input at a time to the  
rear terminal block.  
Calibration parameters are logically divided into groups  
of two parameters each – initial scale value and final  
scalevalue. Acalibrationcheckisprovidedafterentering  
the values of each group. It is also possible to perform a  
calibration check without making an entry: press the  
FUNC button twice when “OFF” is displayed. The instru-  
ment goes directly to the group check.  
g) Use calibrators with the following:  
Accuracy  
TC Input:  
+0.005% output  
+0.001% range  
+5 mV  
RTD Input:  
+0.02%  
+0.0025 decade  
better than 0.1°C  
CJ Compensation:  
Before beginning calibration, be sure the internal DIP  
switch V101 is open.  
Current Transformer: 0.1 mA AC rms  
Resolution  
TC Input:  
1 mV  
WARNING:Performthecalibrationprocedureaccording  
to J106 jumper positions as shown in Figure 1. Other-  
wise, the stored calibration values may be lost.  
RTD Input:  
CJ Compensation:  
Current Transformer: 0.1 mA AC rms  
10 mΩ  
better than 0.1°C  
Calibration Parameters  
Following is a complete list of calibration symbols:  
Code Parameter  
J106  
Input Type  
1-2  
3-4  
5-6  
7-8  
T/C, RTD,  
0-60 mV, 12-60 mV  
(standard configuration)  
tL  
tH  
t.  
TC Input Initial Scale Value  
TC Input Final Scale Value  
TC Input Check  
open  
close  
open open  
0-5 V, 1-5V  
open close open open  
open open close open  
open open open close  
rJ  
Cold Junction Compensation  
0-10V, 2-10 V  
rJ. Cold Junction Compensation Check  
PL RTD Input Initial Scale Value  
PH RTD Input Final Scale Value  
0-20 mA, 4-20 mA  
Input CTTC R192=180K  
SH120=Closed CH101=Open  
P.  
RTD Input Check  
AL Current Input Initial Scale Value  
AH Current Input Final Scale Value  
Figure 1. J106 Settings  
A.  
Current Input Check  
nL 5 Volt Input Initial Scale Value  
nH 5 Volt Input Final Scale Value  
General Guidelines  
a) The instrument should be mounted in its case in order  
to keep the internal temperature constant.  
b) Ambienttemperatureshouldbestable. Avoiddriftdue  
to air conditioning or other mechanical devices.  
c) Relative humidity should not exceed 70%.  
d) Minimum warm up time of at least 20 minutes.  
e) Operate as much as possible in a noise free  
environment.  
n.  
5 Volt Input Check  
UL 10 Volt Input Initial Scale Value  
UH 10 Volt Input Final Scale Value  
U.  
10 Volt Input Check  
3 0  
7sl-6-00.p65  
30  
9/17/02, 2:44 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Procedure  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
Switch on the instrument; the upper display will show  
“COnf”. Press the button; the upper display will show  
“CAL”.  
tH  
TC Input Final Scale Value  
a) Set the calibrator to 60.000 mV.  
Using the  
and pushbuttons (buttons), it is possible  
b) Push the button; the displays will show “ON”  
and “tH”.  
c) After a few seconds, start calibration by pressing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
to select between ON and OFF. To go to the next  
parameter without modifying the calibration, press the  
FUNC button when the display shows “OFF”. To enter a  
calibration value, press the FUNC button when the dis-  
play shows “ON”.  
t.  
TC Input Check  
Press the FUNC button to show the first calibration code  
on the lower display. Repeatedly press the FUNC button  
until the desired calibration (parameter) code appears.  
The display (Figure 3) shows “t.” followed by a number  
showing the measured value in counts:  
t.300  
00  
NOTE: by pushing the SMRT button it is possible to go  
back to a previous parameter without memorizing the  
new calibration.  
Figure 3. TC Calibration Check Display  
Entering Calibration Values  
Followingisadetailed, sequentialprocedureforentering  
and checking values for each calibration parameter:  
a) Check the calibration (linear) by setting:  
0.000 mV – the readout must be equal to  
“t.000 00” ± 10 counts;  
60.000 mV – the readout must be equal to  
“t.300 00” ± 10 counts;  
30.000 mV – the readout must be equal to  
“t.150 00” ± 10 counts.  
tL  
TC Input Initial Scale Value  
a) Connect calibrator and instrument as shown in  
Figure 2.  
b) Push the FUNC button to go to the next parameter.  
10  
rJ  
Cold Junction Compensation  
NOTE: Make sure tL and tH are correctly calibrated  
before attempting rJ calibration.  
a) Measure the temperature close to terminals 9 and 10  
using an appropriate instrument – for example,  
MEMOCAL. See Figure 4.  
9
Figure 2. Calibrator Connection  
b) The upper display shows “OFF”, the lower displays  
shows “tL”.  
c) Set calibrator to 0.000 mV.  
d) Push the button; the display changes to “ON”.  
e) After a few seconds, start calibration by pushing the  
3 1  
7sl-6-00.p65  
31  
9/17/02, 2:44 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b) Set 0.00 on the resistor box.  
10  
9
Measuring  
Device  
c) Push the button; the displays show “ON” and “PL”.  
d) After a few seconds, start calibration by pushing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
Figure 4. Measure Temperature Near Terminals  
PH RTD Input Final Scale Value  
a) Set resistor box to 375.00 .  
b) Push the button; the displays will show “ON” and  
“PH”.  
b) Wait a few minutes to allow temperature stabilization  
of the entire system (compensation cable, sensor,  
calibrator and instrument).  
c) After a few seconds, start calibration by pressing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
c) The displays show “rJ” and “OFF”. Using the or  
button, make the readout value equal to the  
temperature measured by the measuring device in  
tenths of °C.  
d) After a few seconds, start calibration by pushing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
P.  
RTD Check  
The display (Figure 6) shows “P.” followed by a number  
showing the measured value in counts:  
P.300  
00  
rJ. Cold Junction Compensation Check  
ThedisplaysshowrJ.andthecoldjunctiontemperature  
in tenths of °C. Make sure the display readout is equal to  
the value read on the measuring device. Then, push the  
FUNC button to go to the next parameter.  
Figure 6. RTD Calibration Check Display  
a) Check the calibration (linear) by setting:  
0.00 – the readout must be equal to  
“P.000 00” ± 10 counts;  
125.000 – the readout must be equal to  
“P.101 90” ± 10 counts;  
PL RTD Input Initial Scale Value  
a) Connect a resistor box and the instrument as shown  
in Figure 5.  
375.00 – the readout must be equal to  
“P.300 00” ± 10 counts.  
b) Push the FUNC button to go to the next parameter.  
8
9
10  
Figure 5. Resistor Box Connection  
3 2  
7sl-6-00.p65  
32  
9/17/02, 2:44 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AL Current Input Initial Scale Value  
a) Connect calibrator and instrument as shown in  
Figure 7.  
nL 5 VOLT Input Initial Scale Value  
a) Connect calibrator and instrument as shown in  
Figure 8.  
10  
10  
9
9
Figure 7. Calibrator Connection  
Figure 8. Calibrator Connection  
b) The upper display shows “OFF”, the lower displays  
shows “AL”.  
b) The upper display shows “OFF”, the lower displays  
shows “nL”.  
c) Set calibrator to 0.000 mA (even if the minimum range  
value is 4mA).  
c) Set calibrator to 0.000 V (even if the minimum range  
value is 1V).  
d) Push the button; the display changes to “ON”.  
e) After a few seconds, start calibration by pushing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
d) Push the button; the display changes to “ON”.  
e) After a few seconds, start calibration by pushing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
AH Current Input Final Scale Value  
a) Set the calibrator to 20 mA  
nH 5 Volt Input Final Scale Value  
a) Set the calibrator to 5.000 V.  
b) Push the button; the displays will show “ON”  
and “AH”.  
b) Push the button; the displays will show “ON”  
and “nH”.  
c) After a few seconds, start calibration by pressing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
c) After a few seconds, start calibration by pressing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
A.  
Current Input Check  
n.  
5 Volt Input Check  
ThedisplayshowsA.followedbyanumbershowingthe  
measured value in counts.  
Thedisplayshowsn.followedbyanumbershowingthe  
measured value in counts.  
a) Check the calibration (linear) by setting:  
0.000 mA – the readout must be equal to  
“A.000 00” ± 10 counts;  
a) Check the calibration by setting:  
0.000 V – the readout must be equal to  
“n.000 00” ± 10 counts;  
20.000 mA – the readout must be equal to  
“A.300 00” ± 10 counts;  
5.000 V – the readout must be equal to  
“n.300 00” ± 10 counts;  
10.000 mA – the readout must be equal to  
“A.150 00” ± 10 counts.  
2.500 V – the readout must be equal to  
“n.150 00” ± 10 counts.  
b) Push the FUNC button to go to the next parameter.  
b) Push the FUNC button to go to the next parameter.  
3 3  
7sl-6-00.p65  
33  
9/17/02, 2:44 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UL 10 VOLT Input Initial Scale Value  
a) Connect calibrator and instrument as shown in  
Figure 9.  
U.  
10 Volt Input Check  
The display shows “10UH.” followed by a number show-  
ing the measured value in counts.  
a) Check the calibration by setting:  
0.000 V – the readout must be equal to  
“U.000 00” ± 10 counts;  
10  
10.000 V – the readout must be equal to  
“U.300 00” ± 10 counts;  
9
5.000 V – the readout must be equal to  
“U.150 00” ± 10 counts.  
Figure 9. Calibrator Connection  
b) Push the FUNC button.  
b) The upper display shows “OFF”, the lower displays  
shows “UL”.  
c) Set calibrator to 0.000 V (even if the minimum range  
value is 2 V).  
d) Push the button; the display changes to “ON”.  
e) After a few seconds, start calibration by pushing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
UH 10 Volt Input Final Scale Value  
a) Set the calibrator to 10.000 V.  
b) Push the button; the displays will show “ON”  
and “10UH”.  
c) After a few seconds, start calibration by pressing the  
FUNC button. When this calibration is complete, the  
instrument will go to the next parameter.  
3 4  
7sl-6-00.p65  
34  
9/17/02, 2:44 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
1. Remove power from the power supply terminals and  
from relay output terminals.  
2. Remove the instrument from case.  
3. Using a vacuum cleaner or a compressed air jet (max.  
3kg/cm2) remove dust and dirt which may be present  
on the louvers and on the internal circuits, being  
careful to not damage the electronic components.  
4. Clean external plastic or rubber parts only with a cloth  
moistened with ethyl alcohol (pure or denatured)  
[C2H5OH]; or isopropyl alcohol (pure or denatured)  
[(CH3)2CHOH]; or water [H2O]  
5. Verify that there are no loose terminals.  
6. Before re-inserting the instrument in its case, be sure  
it is perfectly dry.  
7. Re-insert the instrument and turn it ON.  
3 5  
7sl-z-00.p65  
35  
9/17/02, 2:46 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
170.IU0.LHL.S00  
02  
Cincinnati, OH  
800-666-4330  
Copyright © 2001 Super Systems Inc.  
Manual Part No. 31302 7SL  
7sl-z-00.p65  
36  
9/17/02, 2:46 PM  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Projector XG MB50X User Manual
SIIG Computer Drive 04 0725A User Manual
Sony Computer Drive DRX 710UL User Manual