63230-319-211A1
2/2006
Instruction Bulletin
ConneXium Ethernet Gateway TSXETG100
User’s Guide
Instrucciones en Español: página 19
Instructions en Français: page 39
Anweisungen auf Deutsch: Seite 59
Retain for future use.
TABLE OF CONTENTS
Additional Resources.................................................................................. 3
Logging into the ETG.................................................................................. 3
SETUP........................................................................................................ 5
SNMP Parameters.................................................................................... 13
DIAGNOSTICS......................................................................................... 14
Updating the Firmware File....................................................................... 18
1
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Accessing the ETG Over a Network
Additional Resources
Documentation and Firmware: Go to www.telemecanique.com, select
Products > Products index > Systems and architectures > Connexium.
ACCESSING THE ETG OVER A
NETWORK
After you set up the Ethernet parameters (see the installation guide), you
can access the ETG over an Ethernet LAN using Internet Explorer 6.0 or
higher.
Logging into the ETG
Action
Result
1. Launch Internet Explorer 6.0 or higher.
Opens Internet Explorer.
2. In the Address text box, type the address Opens the Login dialog box.
of your ETG (169.254.0.10 is the default),
then press Enter.
3. Type your user name (Administrator is the Enters the user name and password, then
default) and password (Gateway is the
opens the ETG home page.
default) into the text boxes, then click OK.
4. Click Setup to access the ETG setup page, Opens the Setup or Diagnostics pages.
or click Diagnostics to access the ETG
diagnostics page.
Figure 1:
The ETG Home Page
Menu bar
Logging Out
We recommend logging out whenever you do not need access to the ETG.
To log out of the ETG configuration session, click Log Out to end your
session.
© 2006 Schneider Electric. All Rights Reserved.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
ETG User Interface OVERVIEW
63230-319-211A1
2/2006
ETG USER INTERFACE
OVERVIEW
The ETG ships with seven pre-installed web pages used for ETG setup and
Table 1: ETG static web pages
See
Page
ETG Web Page
Description
Setup
Ethernet & TCP/IP
Serial Port
Configure Ethernet and TCP/IP communication settings.
Set up or change serial communication parameters.
Identify serial devices on the daisy chain.
Device List
➀
User Accounts
Create and edit groups and users.
➀
Web Page Access
Select web page access rights for each user group.
➀
Modbus TCP/IP Filtering
Set up which IP addresses can access the ETG through
Modbus TCP/IP.
➀
SNMP Parameters
Enable and configure the Simple Network Management
Protocol (SNMP), which allows the ETG to identify itself
to network devices requesting SNMP data.
Diagnostics
Statistics
Displays diagnostic data used to troubleshoot network
problems. This page also contains information about
your specific ETG, including the serial number,
manufacturing date, and Media Access Control (MAC)
address.
Read Device Registers
Allows ETG administrators to read register data from a
serial device connected to the ETG.
➀
Accessible by administrator only
4
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Setup
SETUP
To access the Setup web page links, click Setup on the ETG menu bar.
Ethernet and TCP/IP Settings
Action
Result
1. From the Setup page, click Ethernet &
Opens the Ethernet & TCP/IP page.
TCP/IP.
2. Select your frame format and media type.
Contact your network administrator if you
do not know.
Selects the frame format and media type.
3. Enter your IP address, subnet mask, and
default gateway address assigned to your
ETG by your network administrator.
Enters the Ethernet parameters for the ETG.
NOTE: If you enter an IP address that is used
by another device, you will be prompted to
select a new IP address. See “Duplicate IP
4. Click Apply.
Updates the ETG Ethernet and TCP/IP
settings.
NOTE: After making changes to the Ethernet parameters and clicking
Apply, the ETG will reboot.
Figure 2:
Ethernet & TCP/IP Page
Table 2: ETG Ethernet and TCP/IP Settings
Option
Description
Setting
Frame Format
Used to select the format for data sent over Ethernet II, 802.3 SNAP
an Ethernet connection.
Default: Ethernet II
Media Type
Used to define the physical Ethernet
connection or media type.
•
•
•
•
•
10T/100Tx Auto
10BaseT-HD
10BaseT-FD
100BaseTX-HD
100BaseTX-FD
Default: 10T/100Tx Auto
0.0.0.0 to 255.255.255.255
Default: 169.254.0.10
IP Address
Used to enter the static IP address of the
ETG.
Subnet Mask
Used to enter the Ethernet IP subnet mask 0.0.0.0 to 255.255.255.255
address of your network.
Default: 255.255.0.0
Default Gateway Used to enter the gateway (router) IP
address used for wide area network (WAN)
communications.
0.0.0.0 to 255.255.255.255
Default: 0.0.0.0
© 2006 Schneider Electric. All Rights Reserved.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Setup
63230-319-211A1
2/2006
Duplicate IP Address Detection
While connected to your network, the ETG publishes its IP address. To
avoid any duplicate IP address conflicts, the ETG uses the Address
Resolution Protocol (ARP) to see if any other device on your network is
duplicate IP address when it is detected.
Table 3: Duplicate IP Detection Scenarios
Scenario
Duplicate IP Detected
Power/Status LED
Boot Process /
Power Restore
Reverts to the default ETG IP
address, subnet mask, and gateway
address. ARP requests are sent every
15 seconds until the IP address is
available. When the IP address
becomes available, the ETG will use
it.
Four blinks, pause pattern
Ethernet Link Detected
Manual Address Change ETG keeps it’s previous IP address
and displays a message indicating
that the IP address is already in use
by another device.
Receives an ARP request Reverts to the default ETG IP
address, subnet mask, and gateway
address if a connected device sends
four ARP requests for the ETG’s IP
address. The ETG will send ARP
requests every 15 seconds until the
IP address is available again. When
the IP address becomes available,
the ETG will use it.
Four blinks, pause pattern
6
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Setup
Serial Port
Action
Result
1. From the Setup page, click Serial Port.
Opens the Serial Port page.
2. Select your mode, physical interface,
transmission mode, baud rate, parity, and
Selects the serial port options.
3. If you select Slave mode, enter the IP
addresses for the remotely connected
Enters the IP addresses of the remote devices.
Updates the ETG Serial Port settings.
4. Click Apply.
Figure 3:
Serial Port Page
Table 4: Serial Port Settings
Option
Description
Setting
Mode
Used to select how the COM port on the
ETG is utilized (master or slave).
Master, Slave
Default: Master
NOTE: When the Mode is changed, the
ETG reboots.
Physical Interface Used to select how the ETG serial port is
physically wired.
RS485 4-wire, RS485 2-wire,
or RS232
Default: RS485 2-wire
Transmission
Mode
Used to select how data is transmitted over Modbus RTU, Modbus ASCII
a serial connection.
Default: Modbus RTU
Baud Rate
Used to select the data transmission speed 2400, 4800, 9600, 19200,
over a serial connection.
38400, 56000*, 57600*
Default: 19200
Even, None
Parity
Used to select if data is checked for
accuracy using a parity bit.
Default: Even
Response Timeout Used to select how long the ETG will wait 0.1 to 10 seconds
to receive a response from a serial device.
Default: 3 seconds
Remote Modbus
TCP/IP
Connections
(Slave mode only)
Used to define a list of Modbus TCP/IP
addresses for the ETG to use during slave
mode communications.
—
* Available only if the physical interface and transmission mode is RS232/Modbus ASCII.
© 2006 Schneider Electric. All Rights Reserved.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Setup
63230-319-211A1
2/2006
Device List
Before you begin, keep in mind the following:
For master mode usage of the COM port:
•
Modbus devices do not have to be defined in the Device List, but it helps
you manage your system.
Master Mode Device List Setup
Figure 4:
Master Mode Topology
Ethernet
Connection
ETG in
master
mode
RS485 connection
Up to 128 serial
slave devices
using repeaters
Serial Slave Devices
If you selected Master mode on the Serial Port page, follow the steps below
to set up the device list:
Action
Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to Selects the number of viewable locations that
128), then click Apply.
can be used to define serial slave devices
connected to the ETG.
3. In the Local ID text box, type the local ID
Enters the local address of the device.
Enters all of the connected devices.
Updates the Device List settings.
(address) of the serial slave device.
4. Repeat step 3 until all of the devices are
entered.
5. Click Apply.
Figure 5:
Device List Page in Master Mode
8
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Setup
Slave Mode Device List Setup
Serial port slave mode allows serial Modbus master devices to access
information from serial slave devices across a TCP/IP network. Figure 6
below illustrates how the devices are connected using the device list
settings in Figure 7.
Figure 6:
Slave Mode Topology
Ethernet
Connection
Up to 16 remote IP connections
with up to 128 serial slave devices
are possible
ETG in
slave mode
ETG in master
mode
ETG in
master mode
IP address:
169.254.0.28
IP address:
169.254.0.75
RS232 or RS485
connection
RS485
connection
RS485
connection
2
5
2
3
4
5
6
7
Serial Slave Devices
Serial Slave Devices
If you selected Slave mode on the Serial Port page, follow the steps below
to set up the device list:
Action
Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to Selects the number of viewable locations that
128), then click Apply.
can be used to define remote Modbus TCP/IP
devices.
3. In the Local ID text box, type the local ID
Enters the address of the device that the local
Modbus master device will use to access the
remote device.
(address) of the serial slave device.
4. In the Remote ID text box, type the remote Enters the serial slave address of the remotely
ID (address) of the serial slave device.
connected device.
5. Select the Connection.
Selects the Modbus TCP/IP address to
associate with the remote ID.
6. Repeat steps 3 through 5 until all of the
devices are entered.
Enters all of the mapping information for the
ETG to communicate to the remote devices.
7. Click Apply.
Updates the Device List settings.
Figure 7:
Device List Page in Slave Mode
© 2006 Schneider Electric. All Rights Reserved.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Setup
63230-319-211A1
2/2006
User Accounts
ETG users are assigned user names and passwords. Each user belongs to
a group, and each group has access rights to the ETG Web pages assigned
by the ETG administrator.
NOTE: There are two default user accounts: Administrator (password is
Gateway) and Guest (password is Guest).
Action
Result
1. From the Setup page, click User
Opens the User Accounts page.
Accounts.
2. If you want to change a group name, type a Enters a new group name.
new name in one of the Groups text boxes
(the Administrator group name cannot be
changed).
3. In the Users section, enter a Name (1 to 24 Enters the name and password for a user.
characters) and Password (0 to 12
characters) for a new user.
NOTE: User names and passwords are
case-sensitive and can contain only
alphanumeric characters.
4. Select a group and the default language for Selects the group and language for a user.
the new user.
5. Repeat steps 3 and 4 for each additional
user you want to add.
Continues adding users.
6. Click Apply.
Saves all of the user account settings.
Table 5: ETG accounts and passwords
Account
Default Password
Administrator
Gateway
Guest
Guest
User-defined accounts (up to 11 accounts possible)
No default –Password is user-defined
Figure 8:
User Accounts Page
10
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Setup
Web Page Access
Action
Result
1. From the Setup page, click Web Page
Opens the Web Page Access page.
Access.
2. In the Ethernet & TCP/IP row, select the
access level (None, Read-only, or Full) that levels for each group.
each user group will have for the Ethernet &
TCP/IP web page.
3. To allow Guest access to the web page,
Allows the default Guest group to access the
select Read-only under the Guest column. web page.
NOTE: If the Guest group is Read-only,
other groups may only be set to Read-only
or Full.
4. Repeat steps 2 and 3 for the Serial Port,
Device List, Statistics, and Read Device
Registers rows.
Selects the access level for each web page.
5. Click Apply.
Saves the password settings.
Table 6: Group Access
Group
Access
Administrator
Full access to all web pages
NOTE: We recommend that you change the default administrator
password for system security the first time you log in.
Guest
Read-only access to selected web pages.
Three user-defined
groups
Choosing from the following options, the administrator assigns web
page access for each group. Access levels are as follows:
•
•
None: a group has no access to selected web page
Read-only: password grants a group read-only access to the
selected web page
•
Full: a group has the same access as the Administrator group to the
selected web page
Figure 9:
Web Page Access Page
© 2006 Schneider Electric. All Rights Reserved.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Setup
63230-319-211A1
2/2006
Modbus TCP/IP Filtering
This function allows the administrator to specify Modbus TCP/IP client
devices that have or do not have access to serial slave devices connected
to the ETG.
NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that
can be set to Read-only or None. Setting it to Read-only allows any
Modbus TCP/IP client not in the filtered list to access serial slave devices
with read-only access. Setting it to None blocks all Modbus TCP/IP clients
not in the filtered list.
Action
Result
1. From the Setup page, click Modbus
Opens the Modbus TCP/IP Filtering page.
TCP/IP Filtering.
2. Check Enable Filtering.
Activates filtering.
3. In the IP address column, enter the
Enters an IP address for a Modbus TCP/IP
client that will have access to the serial devices
connected to the ETG.
Modbus TCP/IP client address
4. In the Access Level column, select Read- Selects the access level for the corresponding
only or Full.
IP address. When set to Read-only, only the
following Modbus TCP/IP function codes are
allowed:
Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,
43, 100
Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,
11, 14, 18, 2B, 64
5. Repeat steps 3 and 4 to add more IP
addresses.
Continues adding IP addresses for filtering.
Saves the Modbus TCP/IP address filtering list.
6. Click Apply.
Figure 10: Modbus TCP/IP Filtering Page
12
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Setup
SNMP Parameters
The ETG supports SNMP, allowing a network administrator to remotely
access an ETG with an SNMP manager and view the networking status and
diagnostics in the MIB2 format.
Action
Result
1. From the Setup page, click SNMP
Opens the SNMP Parameters page.
Parameters.
2. Check Enable SNMP to turn ON the simple Activates SNMP.
network management protocol.
NOTE: If you uncheck Enable SNMP and
click Apply, the ETG will reboot and SNMP
functionality will be turned OFF.
3. Enter the system contact, system name,
system location, read-only community
Enters the SNMP system information and
community access names.
name, and the read-write community name.
4. Click Apply.
Saves the SNMP settings.
Figure 11: SNMP Parameters Page
© 2006 Schneider Electric. All Rights Reserved.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Diagnostics
63230-319-211A1
2/2006
DIAGNOSTICS
Statistics
To access the Diagnostics web page links, click Diagnostics on the ETG
menu bar.
Action
Result
1. From the Diagnostics page, click
Opens the Statistics page (see Figure 12).
Statistics.
NOTE: The Statistics page displays data based
on the mode selected in “Serial Port” on
2. View the data.
3. Click Reset.
Resets the ETG cumulative diagnostic data to
0.
NOTE: This page will show accumulated readings since the ETG was last
activated. If power to the ETG is lost, all cumulative values reset to zero.
Figure 12: Statistics Page
Reading with Serial Port in MASTER MODE
Reading with Serial Port in SLAVE MODE
14
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Diagnostics
Interpreting Statistics
Statistic
Description
Ethernet
Link Status
A status string that represents the speed and
duplex setting being used to communicate with
the linking partner.
Frames Transmitted OK
Collisions
A counter that increments each time a frame is
successfully transmitted.
A counter that increments each time a frame is
retransmitted due to collision detection.
Excessive Collisions
A counter that increments each time a frame is
not able to be sent due to reaching the
maximum collision status based on the
Truncated Binary Exponential Backoff
algorithm.
Frames Received OK
CRC Errors
A counter that increments each time a frame is
successfully received.
A counter that increments each time a frame is
received that has a checksum/CRC that does
not match what is calculated.
Alignment Errors
Frames Too Long
A counter that increments each time a frame is
received that has a checksum/CRC error and
does not end on an 8-bit frame boundary.
A counter that increments each time a frame is
received that is larger than the allowed
maximum size defined in the standards (frames
larger than 1518 bytes).
Frames Too Short
A counter that increments each time a frame is
received that is smaller than the allowed
minimum size defined in the standards (frames
smaller than 64 bytes).
Modbus TCP/IP
Frames Sent
A counter that increments each time a frame is
sent.
Frames Received
Protocol Errors
A counter that increments each time a frame is
received.
A counter that increments each time an
ill-formed message is received.
c
Active Connections
A status value that represents the number of
connections that are active at the moment the
diagnostics page is refreshed. A maximum of
32 connections are supported. Clicking Active
Connections opens a new window with a list of
all of the active client connections.
c
Accumulative Connections
A counter that increments each time a
connection is made to the ETG.
c
Maximum Connections
A status value that represents the maximum
number of connections that were active at any
given moment.
c
Inbound Read Messages
A counter that increments each time a read
request message is received.
d
Outbound Read Messages
A counter that increments each time a read
request message is sent.
c
Inbound Write Messages
A counter that increments each time a write
request message is received.
d
Outbound Write Messages
A counter that increments each time a write
request message is sent.
d
Inbound Reply Messages
A counter that increments each time a reply
message is received.
c
Outbound Reply Messages
A counter that increments each time a reply
message is sent.
c
Available when the serial port is in Master mode.
Available when the serial port is in Slave mode
d
© 2006 Schneider Electric. All Rights Reserved.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Diagnostics
63230-319-211A1
2/2006
Statistic
Description
Serial Port
Frames Sent
A counter that increments each time a frame is
sent.
Frames Received
CRC Errors
A counter that increments each time a frame is
received.
A counter that increments each time a
message is received that has a CRC that does
not match what is calculated. Typically the
result of wiring issues.
Protocol Errors
Timeouts
A counter that increments each time an ill-
formed message is received.
A counter that increments each time a request
message is sent without receiving a
corresponding response message within the
allowed time. Timeouts are typically the result
of configuration errors or a non-responsive
device.
d
Inbound Read Messages
A counter that increments each time a read
request message is received.
c
Outbound Read Messages
A counter that increments each time a read
request message is sent.
d
Inbound Write Messages
A counter that increments each time a write
request message is received.
c
Outbound Write Messages
A counter that increments each time a write
request message is sent.
Gateway Information
Firmware Version
The firmware version that is installed on the
ETG.
System Idle Time
MAC Address
A percentage from 0% to 100% indicating the
average processor time that is not being used.
The unique Ethernet hardware address of an
ETG.
Serial Number
Model Number
Hardware Version
The serial number of the ETG.
The ETG model number (100).
ETG hardware version.
Manufacture Date
Date the ETG was manufactured.
c
Available when the serial port is in Master mode.
Available when the serial port is in Slave mode
d
16
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
63230-319-211A1
2/2006
ConneXium™ Ethernet Gateway
Diagnostics
Read Device Registers
Action
Result
1. From the Diagnostics page, click Read
Opens the Read Device Registers page.
Device Registers.
2. Enter the device ID, starting register
number, and the number of registers to
read.
Enters the values to begin reading registers for
the specified device.
3. Click Read Holding Registers or Read
Displays the values for the listed registers.
Input Registers.
4. To change how the data is displayed in the Selects how the data values are displayed.
Value column, select Decimal,
Hexadecimal, Binary, or ASCII.
Table 7: ETG Read Device Register Settings
Option
Description
Default
Device ID
The address of the device that registers are read.
The first register to read.
1
1000
10
Starting Register
Number of Registers
Register column
Value column
The number of registers to read (1 to 10).
Lists the register numbers
—
Lists the data stored in a register.
—
Decimal, Hexadecimal, Select an option to specify how the Value column
Binary, or ASCII options data is displayed.
Decimal
Figure 13: Read Device Registers Page
© 2006 Schneider Electric. All Rights Reserved.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Instruction Bulletin
63230-319-211A1
2/2006
FIRMWARE
Firmware on the ETG can be updated using File Transfer Protocol (FTP).
the latest firmware update.
Finding the Firmware Version
Action
Result
1. Log into the ETG.
Opens the ETG home page.
2. Locate the firmware version on the
bottom-left corner of the page.
Determines the firmware version of the ETG.
NOTE: If you recently updated your
firmware, press F5 to refresh the web page
and update the displayed firmware number.
3. Alternatively, you can select Diagnostics > Also determines the firmware version of the
Statistics to find the firmware version in the ETG.
Gateway Information section.
Getting New Firmware
Action
Result
1. Launch Internet Explorer, type
text box, then press Enter.
Opens the Telemecanique web site.
2. Select Products, then click Product Index. Opens the Products page.
3. Select Systems and architectures.
Displays the Systems and architectures card.
4. Click ConneXium.
Opens the ConneXium systems and
architectures page.
5. Click Software/firm.
Opens the software/firmware page.
6. Click the firmware file link (eg#####.bin,
Opens the File Download dialog box, then
where ##### is the firmware number), then saves the firmware file.
click Save.
Updating the Firmware File
Action
Result
1. Launch Internet Explorer, type ftp:// and the Opens the Log On As dialog box.
IP address of the ETG in the Address text
press Enter.
2. Type the user name Administrator and the Opens an FTP session with the ETG.
administrator password in the text boxes,
then click Log On.
3. Locate the saved firmware file on your
computer, select it, then press CTRL+C.
Copies the firmware file to the clipboard.
4. Right-click in the Internet Explorer window, Copies the firmware to the ETG, and the ETG
then click Paste.
reboots.
NOTE: Instead of copying and pasting the
firmware file, you can drag-and-drop the
firmware file into Internet Explorer.
5. Click the Close button on the Internet
Closes Internet Explorer and ends the FTP
connection to the ETG.
Explorer window.
6. To verify that the firmware version was
updated successfully, follow the steps in
Verifies the updated firmware version.
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified electrical personnel. No responsibility is assumed by Schneider Electric for
any consequences arising out of the use of this material.
© 2006 Schneider Electric. All Rights Reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
ConneXium™ Ethernet Gateway
Handbuch
63230-319-211A1
2/2006
Maßnahme
Ergebnis
5. Schließen Sie das Internet Explorer-
Fenster.
Schließen von Internet Explorer und Beenden
der FTP-Verbindung zum ETG
6. Um zu kontrollieren, ob die Firmware-
Version erfolgreich aktualisiert wurde,
befolgen Sie die Schritte unter „Firmware-
Überprüfung der aktualisierten Firmware-
version
Elektrisches Gerät sollte stets von qualifizierten Elektrikern installiert, betrieben und
gewartet werden. Schneider Electric übernimmt keine Verantwortung für jegliche
Konsequenzen, die sich aus der Verwendung dieses Gerãts ergeben könnten.
eine Marke von
© 2006 Schneider Electric.
Alle Rechte vorbehalten.
Download from Www.Somanuals.com. All Manuals Search And Download.
|