IL•1F CANopen DS301
Fieldbus interface
Fieldbus manual
V2.01, 11.2008
www.schneider-electric.com
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
Table of Contents
Table of Contents
3 Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fieldbus interface
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
IL•1F CANopen DS301
6.4.1
Operating mode Profile Position:
Operating mode Profile Position:
6.4.2
4
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
Table of Contents
10 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Fieldbus interface
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
IL•1F CANopen DS301
6
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
Writing conventions and symbols
Writing conventions and symbols
Work steps If work steps must be performed consecutively, this sequence of steps
is represented as follows:
Special prerequisites for the following work steps ̈ Step 1
୵ Specific response to this work step
̈ Step 2
If a response to a work step is indicated, this allows you to verify that the
work step has been performed correctly.
Unless otherwise stated, the individual steps must be performed in the
specified sequence.
Bulleted lists The items in bulleted lists are sorted alphanumerically or by priority. Bul-
leted lists are structured as follows:
•
•
Item 1 of bulleted list
Item 2 of bulleted list
– Subitem for 2
– Subitem for 2
•
Item 3 of bulleted list
Making work easier Information on making work easier is highlighted by this symbol:
Sections highlighted this way provide supplementary
information on making work easier.
SI units SI units are the original values. Converted units are shown in brackets
behind the original value; they may be rounded.
Example:
2
Minimum conductor cross section: 1.5 mm (AWG 14)
Fieldbus interface
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Writing conventions and symbols
IL•1F CANopen DS301
8
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
1 Introduction
1
Introduction
1.1
About this manual
This manual describes the fieldbus specifics for products in a fieldbus
network addressed via CANopen DS301.
1.2
CAN-Bus
The CAN bus (Controller Area Network) was originally developed for
fast, economical data transmission in the automotive industry. Today, the
CAN bus is also used in industrial automation technology and has been
further developed for communication at fieldbus level.
Features of the CAN bus The CAN bus is a standardized, open bus enabling communication be-
tween devices, sensors and actuators from different manufacturers. The
features of the CAN bus comprise
•
Multimaster capability
Each device in the fieldbus can transmit and receive data independ-
ently without depending on an "ordering" master functionality.
•
Message-oriented communication
Devices can be integrated into a running network without reconfigu-
ration of the entire system. The address of a new device does not
need to be specified on the network.
•
•
Prioritization of messages
Messages with higher priority are sent first for time-critical applica-
tions.
Residual error probability
Various security features in the network reduce the probability of
-11
undetected incorrect data transmission to less than 10
.
Transmission technology In the CAN bus, multiple devices are connected via a bus cable. Each
network device can transmit and receive messages. Data between net-
work devices are transmitted serially.
Network devices Examples of CAN bus devices are
•
•
•
•
•
•
Automation devices, e.g. PLCs
PCs
Input/output modules
Drives
Analysis devices
Sensors and actuators
Fieldbus interface
9
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Introduction
IL•1F CANopen DS301
1.3
Fieldbus devices networked via CAN bus
Different fieldbus devices can be operated in the same fieldbus seg-
ment. The CANopen bus provides a common basis for interchanging
commands and data between the product described and other network
devices.
L
N
Figure 1.1
Fieldbus devices in the network
1.4
Operating modes and functions in fieldbus mode
This manual only describes the protocol for the slave. See the chapters
"Operation" and "Parameters" for descriptions of the operating modes,
functions and all parameters of the slave:
Operating modes
Functions
•
•
•
•
•
•
•
•
Profile Velocity
Profile position
Homing
Jog
Definition of direction of rotation
Motion profile generation
Quick Stop
Fast position capture
Settings The following settings can be made via the fieldbus:
•
•
•
Reading and writing parameters
Monitoring the inputs and outputs of the 24 V signal interface
Activating diagnostics and fault monitoring functions
Fieldbus mode
10
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
1 Introduction
1.5
Documentation and literature references
Manuals In addition to this fieldbus manual, the following manuals also belongs to
the product:
•
Product manual, describes the technical data, installation, com-
missioning and all operating modes and functions.
CAN users and manufacturers CiA - CAN in Automation
organization
Am Weichselgarten 26
D-91058 Erlangen
http://www.can-cia.org/
CANopen standards
•
CiA Standard 301 (DS301)
CANopen application layer and communication profile
V4.02, February 2002
•
CiA Standard 402 (DSP402)
Device profile for drives and motion control
V2.0, July 2002
•
•
ISO/DIS 11898: Controller Area Network (CAN) for high speed
communication;1993
EN 50325-4: Industrial communications subsystem based on
ISO 11898 for controller device interfaces (CANopen); 2002
Literature Controller Area Network
Konrad Etschberger, Carl Hanser Verlag
ISBN 3-446-19431-2
Fieldbus interface
11
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Introduction
IL•1F CANopen DS301
12
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
2 Before you begin - safety information
2
Before you begin - safety information
The information provided in this manual supplements the product man-
ual. Carefully read the product manual before you begin.
Fieldbus interface
13
Download from Www.Somanuals.com. All Manuals Search And Download.
2 Before you begin - safety information
IL•1F CANopen DS301
14
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3
Basics
3.1
CANopen technology
3.1.1 CANopen description language
CANopen is a device- and manufacturer-independent description lan-
guage for communication via the CAN bus. CANopen provides a com-
mon basis for interchanging commands and data between CAN bus
devices.
3.1.2 Communication layers
CANopen uses the CAN bus technology for data communication.
CANopen is based on the basic network services for data communica-
tion as per the ISO-OSI model model. 3 layers enable data communica-
tion via the CAN bus.
•
Physical Layer
Data Link Layer
Application Layer
•
•
device communication
application Layer
data Link Layer
physical Layer
fielb bus communication
CAN-Bus
Figure 3.1
CANopen layer model
Physical Layer The physical layer defines the electrical properties of the CAN bus such
as connectors, cable length and cable properties such as bit-coding and
bit-timing.
Data Link Layer The data link layer connects the network devices. It assigns priorities to
individual data packets and monitors and corrects errors.
Application Layer The application layer uses communication objects (COB) to exchange
data between the various devices. Communication objects are elemen-
tary components for creating a CANopen application.
Fieldbus interface
15
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.1.3 Objects
All processes under CANopen are executed via objects. Objects carry
out different tasks; they act as communication objects for data transport
to the fieldbus, control the process of establishing a connection or mon-
itor the network devices. If objects are directly linked to the device (de-
vice-specific objects), the device functions can be used and changed via
these objects.
Object dictionary The object dictionary of each network device allows for communication
between the devices. Other devices find all objects with which they can
communicate in this dictionary.
CANopen
Communication
Object
directory
Device
functions
Process data
objects (PDO)
1000h
3000h
6000h
FFFFh
Application
Service data
objects (SDO)
Power
amplifier
Device profile
Motor
SYNC, EMCY
Specific functions
Network
management NMT
Figure 3.2
Device model with object dictionary
Objects for describing the data types and executing the communication
tasks and device functions under CANopen are included in the object
dictionary.
Object index Every object is addressed by means of a 16 bit index, which is repre-
sented as a four-digit hexadecimal number. The objects are arranged in
groups in the object dictionary.
Index (hex) Object groups
Supported
by the drive
0000
Reserved
No
No
No
h
0001 -009F Static and complex data types
h
h
00A0 -0FFF Reserved
h
h
1000 -1FFF Communication profile, standardized in DS 301 Yes
h
h
2000 -5FFF Manufacturer-specific device profiles
Yes
No
No
h
h
6000 -9FFF Standardized device profiles, e.g. in DSP 402
h
h
A000 -FFFF Reserved
h
h
Table 3.1 Object index
jects.
Object group data types Data types are used so that the messages that are transmitted via the
network as bit streams have the same meaning for the transmitting and
16
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
receiving devices. Data types are declared by means of the objects of
the data types.
Object groups of the profiles CANopen objects carry out various tasks in fieldbus mode. Profiles
group the objects by tasks.
Fieldbus interface
17
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.1.4 CANopen profiles
Standardized profiles Standardized profiles describe objects that are used with different de-
vices without additional configuration. The users and manufacturers or-
ganization CAN in Automation has standardized various profiles. These
include:
•
•
DS301 communication profile
DSP402 device profile
Application Layer
Application
Device Profile for Drives and Motion Control (CiA DSP 402)
CANopen Communication Profile (CiA DS 301)
Data Link Layer
Physical Layer
CAN-Bus
Figure 3.3
CANopen reference model
DS301 communication profile The DS301 communication profile is the interface between device pro-
files and CAN bus. It was specified in 1995 under the name DS301 and
defines uniform standards for common data exchange between different
device types under CANopen.
The objects of the communication profile in the device carry out the
tasks of data exchange and parameter exchange with other network de-
vices and initialize, control and monitor the device in the network.
Objects of the communication profile are:
•
•
•
Process Data Objects = PDO
Service Data Objects = SDO
Objects with special functions for synchronization SYNCand for
error messages and error response EMCY
•
Network management NMT objects for initialization, error monitor-
ing and device status monitoring.
DSP402 device profile The DSP402 device profile describes standardized objects for position-
ing, monitoring and settings of drives. The tasks of the objects include:
•
•
•
Device monitoring and status monitoring (Device Control)
Standardized parameterization
Changing, monitoring and execution of operating modes
IMPORTANT: The product does not support the CiA 402 device profile.
Vendor-specific profiles The basic functions of a device can be used with objects of standardized
device profiles standardized. Only vendor-specific device profiles offer
the complete range of functions. The objects with which the special func-
tions of a device can be used under CANopen are defined in these ven-
dor-specific device profiles.
18
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3.2
Communication profile
CANopen manages communication between the network devices with
object dictionaries and objects. A network device can use process data
objects (PDO) and service data objects (SDO) to request the object data
from the object dictionary of another device and, if permissible, write
back modified values.
The following can be done by accessing the objects of the network de-
vices
•
•
•
Exchange parameter values
Start motion functions of individual CAN bus devices
Request status information
3.2.1 Object dictionary
Each CANopen device manages an object dictionary which contains all
objects for communication.
Index, subindex The objects are addressed in the object dictionary via a 16 bit index.
One or more 8 bit subindex entries for each object specify individual data
fields in the object. Index and subindex are shown in hexadecimal nota-
tion with a subscript " ".
h
The following example shows the index entries and subindex entries for
the object receive PDO4 mapping, 1603 for mapping in R_PDO4.
h
Index Subindex Object
Meaning
1603
00
Number of elements
Number of subindexes
h
h
h
h
1603
01
1st mapped object
R_PDO4
First object for mapping in
R_PDO4
1603
1603
02
03
2nd mapped object
R_PDO4
Second object for mapping
in R_PDO4
h
h
h
h
3rd mapped object
R_PDO4
Third object for mapping in
R_PDO4
Table 3.2 Examples of index and subindex entries
Fieldbus interface
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Structure of object dictionary The objects in the object dictionary are sorted by index values. Table 3.3
shows the index ranges of the object dictionary according to the CAN-
open specifications.
Index range Object groups
(hex)
Supported
by the drive
0000
Reserved
No
No
No
No
No
No
No
Yes
Yes
No
No
h
0001 -001F
Static data types
h
h
h
h
h
h
0020 -003F
Complex data types
h
0040 -005F
Manufacturer-specific data types
Static data types for the device profiles
Complex data types for the device profiles
Reserved
h
0060 -007F
h
0080 -009F
h
00A0 -0FFF
h
h
h
h
h
1000 -1FFF
Communication profile
Manufacturer-specific profiles
Standardized device profiles
Reserved
h
2000 -5FFF
h
6000 -9FFF
h
A000 -FFFF
h
h
Table 3.3 Index ranges of the object dictionary
Object descriptions inthe manual For CANopen programming of a product, the following object groups are
described in detail:
•
•
1xxx objects: Communication objects in this chapter
h
3xxx objects: Manufacturer-specific objects to the extent they are
h
required for controlling the product
All operating modes and functions of the product are controlled by
means of manufacturer-specific objects. These functions and objects
are described in the device documentation.
The manufacturer-specific objects are stored in the index range starting
at 3000 . To derive the CAN index from the indexes given in the device
h
documentation, it is sufficient to add 3000 .
h
Example: The control word for a state transition has the index 28 and the subindex
1. In the CAN protocol, this results in the index 301C (3000 + 1C [=
h
h
h
28 ]) and the subindex 1.
d
20
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3.2.2 Communication objects
Overview The communication objects are standardized with the DS301 CANopen
communication profile. The objects can be classified into 4 groups ac-
cording to their tasks.
Special objects
PDO
T_PDO1 R_PDO1
SYNC
EMCY
T_PDO2 R_PDO2
T_PDO3 R_PDO3
T_PDO4 R_PDO4
Communication
objects
Network
management
SDO
NMT Services
NMT Node guarding
T_SDO
R_SDO
NMT Heartbeat
Figure 3.4
Communication objects; the following applies to the perspective
of the network device: T_..: "Transmit", R_..: "Receive"
•
•
•
PDOs (process data objects) for real-time transmission of process
data
SDOs (service data object) for read and write access to the object
dictionary
Objects for controlling CAN messages:
– SYNC object (synchronization object) for synchronization of net-
work devices
– EMCY object (emergency object), for signaling errors of a device
or its peripherals.
•
Network management services:
– NMT services for initialization and network control (NMT: net-
work management)
– NMT Node Guarding for monitoring the network devices
– NMT Heartbeat for monitoring the network devices
Fieldbus interface
21
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
CAN message Data is exchanged via the CAN bus in the form of CAN messages. A
CAN message transmits the communication object and a variety of ad-
ministration and control information.
CAN message
1
11
1
6
0..8 Byte
16
1
1
1
7
>=3
End-Bits
CRC
Data
Acknowledge
Control
RTR-Bit
Identifier
COB-ID
Start-Bit
data carrier
11 Bit
0..8 Byte
4 Bit 7 Bit
0
1
2
3
4
5
6
7
CANopen message (simplified)
Figure 3.5
CAN message and simplified representation of CANopen mes-
sage
CANopen message For work with CANopen objects and for data exchange, the CAN mes-
sage can be represented in simplified form because most of the bits are
used for error correction. These bits are automatically removed from the
receive message by the data link layer of the OSI model, and added to
a message before it is transmitted.
The two bit fields "Identifier" and "Data" form the simplified CANopen
message. The "Identifier" corresponds to the "COB ID" and the "Data"
field to the data frame (maximum length 8 bytes) of a CANopen mes-
sage.
COB ID The COB ID (Communication OBject Identifier) has 2 tasks as far as
controlling communication objects is concerned:
•
•
Bus arbitration: Specification of transmission priorities
Identification of communication objects
An 11 bit COB identifier as per the CAN 3.0A specification is defined for
CAN communication; it comprises 2 parts
•
•
Function code, 4 bits
Node address (node ID), 7 bits.
Bit:10
0
1
2
3
4
1
2
3
4
5
6
7
COB-ID
Function code
0...15
Node-ID
0...127
Figure 3.6
COB ID with function code and node address
22
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
COB IDs of the communication The following table shows the COB IDs of all communication objects
objects
with the factory settings. The column "Index of object parameters"
shows the index of special objects with which the settings of the com-
munication objects can be read or modified via an SDO.
Communication object Function Node address,
COB ID decimal (hexadecimal)
Index of object
parameters
code
node ID [1...127]
NMT Start/Stop Service 0 0 0 0
0 0 0 0 0 0 0 0 (0 )
-
h
SYNC object
EMCY object
0 0 0 1
0 0 0 1
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 1 0
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
0 0 0 0 0 0 0 128 (80 )
1005 ....1007
h
h
h
x x x x x x x 128 (80 ) + node ID
1014 , 1015
h
h
h
T_PDO1
x x x x x x x 384 (180 ) + node ID
1800
1400
1801
1401
1802
1402
1803
1403
-
h
h
h
h
h
h
h
h
h
R_PDO1
x x x x x x x 512 (200 ) + node ID
h
T_PDO2
x x x x x x x 640 (280 ) + node ID
h
R_PDO2
x x x x x x x 768 (300 ) + node ID
h
T_PDO3
x x x x x x x 896 (380 ) + node ID
h
R_PDO3
x x x x x x x 1024 (400 ) + node ID
h
T_PDO4
x x x x x x x 1152 (480 ) + node ID
h
R_PDO4
x x x x x x x 1280 (500 ) + node ID
h
T_SDO
x x x x x x x 1408 (580 ) + node ID
h
R_SDO
x x x x x x x 1536 (600 ) + node ID
-
h
NMT error control
x x x x x x x 1792 (700 ) + node ID
h
1)
LMT Services
1 1 0 0 1 0 x 2020 (7E4 ), 2021 (7E5 )
h
h
NMT Identify Service
1 1 0 0 1 1 0 2022 (7E6 )
h
DBT Services
1 1 0 0 x x x 2023 (7E7 ), 2024 (7F8 )
h
h
NMT Services
1 1 0 1 0 0 x 2025 (7E9 ), 2026 (7EA )
h
h
1) Not supported by the device
Table 3.4 COB IDs of all communication objects
COB IDs of PDOs can be changed as required. The
assignment pattern for COB IDs only specifies a basic
setting.
Function code The function code classifies the communication objects. Since the bits
of the function code in the COB ID are more significant, the function
code simultaneously controls the transmission priorities: Objects with a
lower function code are transmitted with higher priority. For example, an
object with function code "1" is transmitted prior to an object with func-
tion code "3" in the case of simultaneous bus access.
Node address Every network device is configured before it is operated on the network.
The device is assigned a 7 bit node address (node ID) between 1 (01 )
h
and 127 (7F ). The device address "0" is reserved for "broadcast" trans-
h
missions which are used to send messages to all devices simultane-
ously.
Fieldbus interface
23
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Example Selection of a COB ID
For a device with the node address 5, the COB ID of the communication
object T_PDO1 is:
384+node ID = 384 (180 ) + 5 = 389 (185 ).
h
h
Data frame The data frame of the CANopen message can hold up to 8 bytes of data.
In addition to the data frame for SDOs and PDOs, special frame types
are specified in the CANopen profile:
•
•
Error data frame
Remote data frame for requesting a message
The data frames contain the respective communication objects.
3.2.3 Communication relationships
CANopen uses 3 relationships for communication between network de-
vices:
•
•
•
Master-slave relationship
Client-server relationship
Producer-consumer relationship
Master-slave relationship A network master controls the message traffic. A slave only responds
when it is addressed by the master.
The master-slave relationship is used with network management ob-
jects for a controlled network start and to monitor the connection of de-
vices.
Slave
Slave
Slave
Master
Master
data
request
data
Slave
Figure 3.7
Master - slave relationships
Messages can be interchanged with and without confirmation. If the
master sends an unconfirmed CAN message, it can be received by a
single or by several slaves or by no slave.
To confirm the message, the master requests a message from a specific
slave, which then responds with the desired data.
24
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Client-server relationship A client-server relationship is established between 2 devices. The
"server" is the device whose object dictionary is used during data ex-
change. The "client" addresses and starts the exchange of messages
and waits for a confirmation from the server.
A client-server relationship with SDOs is used to send configuration data
and long messages.
data
Client
Server
data
Client-server relationship
Figure 3.8
The client addresses and sends a CAN message to a server. The server
evaluates the message and sends the response data as an acknowl-
edgement.
Producer-consumer relationship The producer-consumer relationship is used for exchanging messages
with process data, because this relationship enables fast data exchange
without administration data.
A "Producer" sends data, a "Consumer" receives data.
Consumer
Producer
Producer
Consumer
Consumer
data
request
data
Consumer
Consumer
Figure 3.9
Producer-consumer relationships
The producer sends a message that can be received by one or more
network devices. The producer does not receive an acknowledgement
to the effect that the message was received. The message transmission
can be triggered
•
•
•
by an internal event, e.g. "target position reached"
by the synchronization object SYNC
a request of a consumer
For details on the function of the producer-consumer relationship and on
requesting messages see chapter 3.4 "Process data communication".
Fieldbus interface
25
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.3
Service data communication
3.3.1 Overview
Service Data Object(SDO: Service Data Object) can be used to access
the entries of an object dictionary via index and subindex. The values of
the objects can be read and, if permissible, also be changed.
Every network device has at least one server SDO to be able to respond
to read and write requests from a different device. A client SDO is only
required to request SDO messages from the object dictionary of a dif-
ferent device or to change them there.
The T_SDO of an SDO client is used to send the request for data ex-
change; the R_SDO is used to receive. The data frame of an SDO con-
sist of 8 bytes.
SDOs have a higher COB ID than PDOs and therefore are sent over the
CAN bus at a lower priority.
3.3.2 SDO data exchange
A service data object (SDO) sends parameter data between two de-
vices. The data exchange conforms to the client-server relationship. The
server is the device to whose object dictionary an SDO message refers.
Client
R_SDO T_SDO
(request)
COB-ID
data
CAN
data
COB-ID
(response)
T_SDO R_SDO
Server
Figure 3.10 SDO message exchange with request and response
Message types Client-server communication is triggered by the client to send parameter
values to the server or to get them from the server. In both cases, the cli-
ent starts the communication with a request and receives a response
from the server.
26
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3.3.3 SDO message
3 Basics
Put simply, an SDO message consists of the COB ID and the SDO data
frame, in which up to 4 bytes of data can be sent. Longer data se-
quences are distributed over multiple SDO messages with a special pro-
tocol.
The device sends SDOs of up to 4 bytes data length (data). Greater
amounts of data such as 8 byte values of the data type "Visible String 8"
can be distributed over multiple SDOs and are transmitted successively
in 7 byte blocks.
Example The following illustration shows an example of an SDO message.
SDO
0
1
2
3
4
5
6
7
581
43 00 10 00 92 01 02 00
Data
Subindex
COB-ID
(581 )
Index
h
Command Code
Figure 3.11 SDO message, example
COB ID and data frame R_SDO and T_SDO have different COB IDs.
The data frame of an SDO messages consists of:
•
•
•
Command code (ccd) in which the SDO message type and the data
length of the transmitted value are encrypted
Index and subindex which point to the object whose data is trans-
ported with the SDO message
Data of up to 4 bytes
Evaluation of numeric values Index and data are transmitted left-aligned in Intel format. If the SDO
contains numerical values of more than 1 byte in length, the data must
be rearranged byte-by-byte before and after a transmission.
Index:
Data:
0
1
2
3
4
5
6
7
581
43 00 10 00 92 01 02 00
Hex:
Figure 3.12 Rearranging numeric values greater than 1 byte
00 02 01 92
10 00
h
h
Fieldbus interface
27
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.3.4 Reading and writing data
Writing data The client starts a write request by sending index, subindex, data length
and value.
The server sends a confirmation indicating whether the data was cor-
rectly processed. The confirmation contains the same index and
subindex, but no data.
Client
write request
Server
0
2
3
4
5
6
7
1
ccd
Idx
Idx
Sidx
COB-ID
ccd=
data
2
1
data
23h
27h
2Bh
2Fh
data
data
data
ccd=
ccd=
ccd=
write response
0
2
3
4
5
6
7
1
Idx
Idx
Sidx
ccd
COB-ID
data
1
2
ccd= 60h
Figure 3.13 Writing parameter values
Unused bytes in the data field are shown with a slash in the graphic. The
content of these data fields is not defined.
ccd coding The table below shows the command code for writing parameter values.
It depends on the message type and the transmitted data length.
Message type
Data length used
4 bytes 3 bytes 2 bytes 1 byte
Write request
23
27
2B
2F
Transmitting param-
eters
h
h
h
h
Write response
Error response
60
80
60
80
60
80
60
80
Confirmation
Error
h
h
h
h
h
h
h
h
Table 3.5 Command code for writing parameter values
28
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Reading data The client starts a read request by sending the index and subindex that
point to the object or the object value whose value it wants to read.
The server confirms the request by sending the desired data. The SDO
response contains the same index and subindex. The length of the re-
sponse data is specified in the command code "ccd".
Client
read request
Server
0
2
3
4
5
6
7
1
ccd
Idx
Idx
Sidx
COB-ID
ccd=
data
2
1
40h
read response
0
2
3
4
5
6
7
1
Idx
Idx
Sidx
ccd
COB-ID
data
1
2
data
ccd= 43h
data
data
data
ccd= 47h
ccd= 4Bh
ccd= 4Fh
Figure 3.14 Reading a parameter value
Unused bytes in the data field are shown with a slash in the graphic. The
content of these data fields is not defined.
ccd coding The table below shows the command code for transmitting a read value.
It depends on the message type and the transmitted data length.
Message type Data length used
4
3
2
1 byte
bytes bytes bytes
read request
40
40
47
80
40
40
h
Request read value
Return read value
Error
h
h
h
h
h
h
h
Read response 43
Error response 80
4B
4F
h
h
h
80
80
h
Table 3.6 Command code for transmitting a read value
Fieldbus interface
29
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Error response If a message could not be evaluated without errors, the server sends an
error message. For details on the evaluation of the error message see
Client
Server
error response
0
2
3
4
5
6
7
1
Idx
Idx
Sidx
ccd
COB-ID
ccd:
data
1
2
Byte 4-7
error code
80
Figure 3.15 Response with error message (error response)
30
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3.4
Process data communication
3.4.1 Overview
This chapter describes the flow of information from the
perspective of your product in compliance with CiA
standard DS301. The designation "receive" relates to a
flow of data from the master to the product, while "transmit"
represents a flow of data from the product to the master.
Process data objects (PDO: Process Data Object) are used for real-time
data exchange of process data such as actual and reference or operat-
ing state of the device. Transmission is very fast because the data is sent
without additional administration data and a response from the recipient
is not required.
The flexible data length of a PDO message also increases the data
throughput. A PDO message can transmit up to 8 bytes of data. If only
2 bytes are assigned, only 2 data bytes are sent.
The length of a PDO message and the assignment of the data fields are
specified by PDO mapping. For more information see chapter 3.4.2.1
PDO messages can be exchanged between devices that generate or
process process data.
One PDO each is available for sending and receiving a PDO message:
•
•
T_PDO to transmit the PDO message (T: "Transmit"),
R_PDO to receive data (R: "Receive").
Fieldbus interface
31
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.4.2 PDO data exchange
PDO Consumer
R_PDO
PDO Consumer
R_PDO
COB-ID
Data
CAN
T_PDO
PDO Producer
R_PDO
PDO Consumer
Figure 3.16 PDO data exchange
Data exchange with PDOs follows to the producer-consumer relation-
ship and can be triggered in 3 ways
•
•
•
Synchronized
Event-driven, asynchronous
On request of a consumer, asynchronous
The SYNC object controls synchronized data processing. Synchronous
PDO messages are transmitted immediately like the standard PDO
messages, but are only evaluated on the next SYNC. For example, sev-
eral drives can be started simultaneously via synchronized data ex-
change.
The device immediately evaluates PDO messages that are called on re-
quest or in an event-driven way.
The transmission type can be specified separately for each PDO with
subindex 02 (transmission type) of the PDO communication parameter.
h
The objects are listed in 8 "Object directory".
Event-driven The "event" is a change of the PDO data. In this mode, the data is im-
mediately transmitted after a change. Please note that in the case of, for
example, a positioning movement, the actual position changes con-
stantly so that a large number of PDOs is transmitted. There are two
ways to avoid such a large number of PDOs:
•
A) You can set an "Inhibit Timer" (object 1803 subindex 3). The
PDO is not sent until after this inhibit time has passed.
h
•
B) By using a bit mask, you can limit the check for changes
(=event). See section "Bit mask for T_PDO4" for a description.
A further possibility of "creating" an event consists of activating an
"Event Timer" (object 1803 subindex 5). You activate this counter by en-
h
tering a value not equal to zero. When this counter is reached, this rep-
resents an additional event. This means that the PDO is transmitted
when a value changes or when the counter event occurs.
Synchronized In the case of this transmission mode, a PDO is transmitted in relation
32
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Remotely requested Transmission of an asynchronous PDO is triggered when an external re-
quest is received. Such a "Remote Request" is represented by a special
bit in the CAN transmission frame; it has the same COB ID (communi-
cation object identifier) as the requested communication object.
An overview of the individual transmission types can be found in the ob-
ject dictionary, PDO parameters.
Bit mask for T_PDO4 A bit mask can be defined for the objects CAN.pdo4msk1(30:9) and
CAN.pdo4msk2(30:10) in T_PDO4. All bit positions containing a "zero"
are then no longer considered in the checks for changes (=event). This
allows you, for example, to limit checks to changes of the driveStat in-
formation.
NameIdx:Sub MeaningBit assignment
dec. (hex.)
Data type UnitDe-
R/W/
fault (dez.) rem. Info
30:9 (1E:09h) The default value 4294967295 corresponds to 0xFFFFFFFF.
UINT32
UINT32
-
R/W/-
R/W/-
429496729
5
30:10
See object pdo4msk1 for a description.
-0
(1E:0Ah)
Table 3.7 Parameters for the CAN bus
Example In this example, setting the object CAN.pdo4msk2 to zero keeps modi-
fications to the current position from triggering an event.
00h 00h 00h 00h
pdo4msk2
FFh FFh FFh FFh
pdo4msk1
T_PDO4
1
2
3
4
5
6
7
8
Byte
actual Position
reserved
modeStat
driveStat
Figure 3.17 Setting the object CAN.pdo4msk2to zero
Fieldbus interface
33
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Requesting process data One or more network devices with consumer function can request PDO
messages from a producer. The producer is identified by the COB ID of
the request and responds with the requested PDO.
RTR
COB-Id
COB-Id
1
0
Producer
Consumer
Daten
Figure 3.18 Requesting a message with RTR = 1
The RTR bit (RTR: Remote Transmission Request) of a CAN message
is used to detect a request. The COB ID remains the same for both mes-
sages:RTR = 0: transmission of dataRTR = 1: request for data.
Setting RTR request You can set for each PDO separately whether it responds to RTR re-
quests. This is switched on or off via subindex 01, bit 30 of each PDO.
h
Subindex 02 (transmission type) of the objects defines the transmis-
h
sion type. The PDO only responds to a request via bit RTRif RTR trans-
mission is enabled for a PDO. The subindex values for the RTRbit are:
Objects 1403 , 1803 subindex 02 , Meaning
h
h
h
"transmission type"
252
253
RTR active, synchronous
RTR active, asynchronous
Table 3.8 Subindexes for using the bit
An overview of all values for the subindex 02 can be found in the object
h
dictionary for the corresponding object.
The product cannot request PDOs, but it can respond to the request of
PDOs.
3.4.2.1 Dynamic and static PDO mapping
Dynamic PDO mapping The settings for PDO mapping are defined in an assigned communica-
tion object for each PDO. If the PDO mapping settings for a PDO can be
changed, this is referred to as dynamic PDO mapping for the PDO. Dy-
namic PDO mapping enables flexible combination of different process
data during operation.
Static PDO mapping Static PDO mapping means that all objects are mapped in accordance
with a fixed setting in the corresponding PDO.
Properties of the integrated drive. The integrated drive supports 2 PDOs, the communication objects
T_PDO4and R_PDO4. These two PDO4 are enabled by default.
These PDOs are mapped statically, i.e. they cannot be configured but
only read. The indexes for the permanently entered objects can be read
from the PDO mapping object range:
•
•
•
•
Object 1403 : receive PDO4 communication parameter
h
Object 1603 : receive PDO4 mapping
h
Object 1803 : transmit PDO4 communication parameter
h
Object 1A03 : transmit PDO4 mapping
h
34
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3.4.2.2 Receive PDO R_PDO4 (master -> slave)
The master device can execute the following actions via the PDO4 chan-
nel to the slave:
•
Control the state machine of the slave
– Enable/disable the power stage of the product
– Trigger and reset a "Quick Stop"
– Resetting faults
•
Toggle the operating modes
– Profile Position operating mode, absolute and relative
– Profile Velocity operating mode
– Reference movement
– Position setting
•
Set reference values
– Reference position
– Reference speed
– Type of reference movement
Structure of R_PDO4:
1
2
3
4
5
6
7
8
Byte
Ref32 -> reference 32 bits - e.g. position
Ref16 -> reference 16 bits - e.g. velocity
modeCtrl
driveCtrl
driveCtrl - 8 Bits
Bit
7
0
6
0
5
0
4
3
2
1
0
QR FR QS EN DI
Disable
Enable
Quickstop
Fault Reset
Quickstop Release
modeCtrl - 8 Bits
Bit
7
MT
6
5
4
3
0
2
1
0
ACTION
MODE
Requested Mode
Action within Mode
Mode Toggle
Figure 3.19 Structure of R_PDO4
Fieldbus interface
35
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
State machine – drivectrl
The state machine is controlled via PDO4 or the SDO object
drivectrl, 28:1, in both cases via bits Bits 0 ... 4.
In PDO mode, a change form 0 to 1 triggers the corresponding function.
In the case of access via SDO, a write access with a set bit value is suf-
ficient, i.e. a change of edge is not required.
Controlling the state machine
Bit 0: Power stage Disable
Bit 1: Power stage Enable
Bit 2: Quickstop
PDO4Bits 0 ... 4
SDO object drivectrl, 28:1Bits 0 ... 4
Triggered when 0 changes to 1
Triggered at write access if bit value = 1
Bit 3: Fault Reset
Bit 4: Quickstop Release
The value "0" is a special case: If during transmission all bits 0 ... 7 are
"zero", the product interprets this as "Disable" command and disables
the power stage. This applies to both PDO and SDO access.
Handling of errors If requests for controlling the state machine cannot be executed by the
product, the product ignores such request. There is no error response.
36
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Operating modes – modeCtrl
In PDO mode, the operating modes are controlled via object modeCtrl.
The master must enter the following values to activate an operating
mode or to change reference values:
•
•
•
Reference values in fields "Ref16" and "Ref32"
Select operating mode with modeCtrl, Bits 0 ... 2 (MODE)
Select action for this operating mode with modeCtrl, bits 4 ... 6
(ACTION)
•
Toggle modeCtrl, bit 7 (MT)
The following table shows the possible operating modes and the corre-
sponding reference values:
Mode bits Action
modeCtrl Description
Corre-
Reference value Ref16 Reference
value Ref32
1)
0... 2
bits 4 ...
6
. Bits 0
sponds to
2)
... 6
01h
02h
object
1 (JOG)
2 (REF)
0
0
Jog
41:3
40:3
Start (as object 41:1)
-
-
Position setting
Position for posi-
tion setting
1
0
12h
03h
Reference movement
Absolute positioning
40:1
35:1
Type (as object 40:1)
Reference speed
-
3 (PTP)
Reference posi-
tion
1
13h
Relative positioning
35:3
Reference speed
Reference posi-
tion
2
0
23h
04h
Continue positioning
Profile Velocity
35:4
36:1
Reference speed
Reference speed
-
-
4 (VEL)
1) Column corresponds to the value to be entered in byte modeCtrl, but without ModeToggle (bit 7)
2) Column shows Index:Subindex (decimal) of the corressponding operating mode objects modes which are described in more
detail in the device documentation.
Fieldbus interface
37
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Reference positions are entered in increments, reference speeds in
-1
[min ].
@ WARNING
UNINTENDED OPERATION
•
Note that any changes to the values of these parameters are exe-
cuted by the drive controller immediately on receipt of the data
set.
•
Verify that the system is free and ready for movement before
changing these parameters.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
If operating mode, reference position and reference speed are transmit-
ted simultaneously in one PDO, data consistency is required. For this
reason, the product evaluates the operating mode data only if bit 7 was
toggled. Toggling means that a "0 -> 1" or a "1 -> 0" change of edge was
detected.
Bit 7 is mirrored in the response PDO4 from the product so that synchro-
nized operation is possible via PDO4.
Handling of errors Requests for operating mode are triggered by toggling the bit 7 . If these
requests cannot be executed, the product provides an error response as
described in section Transmit PDO4 - Handling of errors.
3.4.2.3 Transmit PDO T_PDO4 (product to master)
With the default product settings, the transmit PDO is sent asynchro-
nously and in an "event-driven" way; an "Inhibit Time" can be set.
The product provides the master with the following information via
PDO4:
•
•
•
•
State of state machine
Errors and warnings
Active operating mode
Status of active operating mode
– Operating mode terminated
– Error occurred
– Reference speed or reference position reached
– Actual position
•
•
•
Slave referenced
Acknowledgement of operating mode requests
Status of the 24 V inputs and outputs
38
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Structure of T_PDO4:
1
2
3
4
5
6
7
8
Byte
actual position (pact), 32 bits
IO_act, 8 bits
modeStat, 8 bits
driveStat, 16 bits
driveStat
15
14
13
12 --- 8
7
6
5
4 3 --- 0
Bit
Bit
x err x_end x_info 0 0 0 0 0
warn Sig_SR FltSig 0 cos
modeStat
7
6
5
4
0
3
0
2
1
0
MT ME ref_ok
mode
actual operation mode
drive referenced
Mode Error
Mode Toggle
IO_act
Bit
7
0
6
0
5
4
3
2
1
0
STO_B STO_A
IO3 IO2 IO1 IO0
STO_A / STO_B
(PWRR_A / PWRR_B)
Figure 3.20 Structure of T_PDO4
Status word driveStat The information in the status word driveStatcorresponds to bits 0
...15 of object Status.driveStat, 28:2.
Contents of information:
•
•
•
State of state machine
Warning and error bits
Status of the current operating mode
Fieldbus interface
39
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Operating mode modeStat This field corresponds to bits 0 ... 2 of the object Status.xMode_act.
Bits 6 and 7 provide additional information that can be used for synchro-
nized operating mode control via the PDOs.
The field contains the following information:
Bit
0...2
5
Name
mode
ref_ok
Description
currently set operating mode as in R_PDO4
Is set if homing of the product by means of a reference movement or position setting was
successful.
6
7
ME, ModeError
Set if a request of the master via R_PDO4 data was rejected by the product.
MT, ModeToggle Mirrors bit 7 (Mode Toggle) of R_PDO4
3.4.2.4 Handshake with Mode Toggle Bit
Mode Toggle Synchronized processing is possible with the transmit data modeCtrl,
bit 7 (MT) and the receive data modeStat, bits 6 (ME) and 7 (MT). Syn-
chronized processing means that the master waits for feedback mes-
sages from the slave so it can respond appropriately.
Example of positioning The master starts a positioning movement at point in time t . At points in
0
time t , t ..., the master checks the responses from the slave. It waits
1
2
for the end of the positioning movement by checking the Input Assembly
for bit x_end = 1(end of positioning).
t0
t1
t2
t3
Master
Slave
Mode Toggle
1
Mode Toggle
x_end
2
3
Figure 3.21 Mode Toggle Handshake
(1)
(2)
Master starts positioning with MT = 1 in byte modeCtrl
Slave signals that positioning is active with MT = 1 in
modeStatand simultaneously with x_end= 0 in driveStat
Slave signals end of positioning with x_end= 1 in
driveStat
(4)
40
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Example of short positioning The master starts a positioning movement that will only take a very short
time. The duration is shorter than the polling cycle of the master. At point
in time t the movement is already complete. Using bit x_end, the mas-
1
ter does not know whether the movement is already complete or has not
yet been started. However, it detects this with the MT bit from the slave:
Master
MT
Slave
MT
Slave
x_end
1
1
0
1
1
0
Slave has not yet detected command
Slave has detected command, positioning
running
1
1
1
Slave signals that positioning is complete
The master may only evaluate data in which the received MT bit is iden-
tical to the last bit transmitted by the master.
t0
t1
t2
Master
Slave
Mode Toggle
1
Mode Toggle
x_end
2
3
Figure 3.22 Mode Toggle Handshake, short movement
(1)
(2+3)
Master starts positioning with MT = 1 in byte modeCtrl
Slave signals that positioning is active with MT = 1 in
modeStatand simultaneously with x_end= 0 in driveStat
Slave signals end of positioning with x_end= 1 in
driveStat
(4)
Fieldbus interface
41
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Handling of errors If the master toggles bit 7 (MT), this is interpreted by the slave as a re-
quest to start an operating mode or to change data of the current oper-
ating mode. If the request cannot be processed, the active operating
mode is not changed and the slave sets bit 6 in modeStat(ME =
ModeError).
The active operating mode is not changed and there is no state transi-
tion.
Bit 6 (ME) remains set until the master toggles bit 7 (MT) in modeCtrl
again, thus triggering a new command.
The master can read the corresponding error code by a read access to
parameter ModeError.
Possible reasons for a failure of the operating mode request:
•
•
•
•
Reference values outside the value range
Change of the operating mode during processing (impossible)
Invalid operating mode requested
The device is not in state 6 (Operation Enable) of the state
machine.
For more information see the product manual.
42
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
3.4.2.5 Emergency service
The Emergency Service signals internal device errors via the CAN bus.
The error is sent to all network devices with an EMCYobject according to
the "Consumer-Producer" relationship.
EMCY-Consumer
EMCY-Consumer
CAN
COB-ID
data
EMCY-Consumer
EMCY-Producer
Figure 3.23 Error message with the EMCYobject
EMCY message Causes of an EMCYcomprise:
•
asynchronous errors, error code = 1000 In the case of an internal
h
device error, the product switches to fault state in accordance with
the device's state machine. At the same time, the product transmits
an EMCYmessage with error register and error code.
•
•
PDO4 error during operating mode control, error code = 8200 If
the request for an operating mode via PDO4 fails, the product also
sends an EMCY message.
h
CAN communication error, error code = 8100
h
0
1
2
3
4
5
6
7
81
12 22 00 00 00 00 00 00
Manufacturer specific error field
Error code
Error register
Error code
COB-ID (80 + Node-ID)
0
1
12 22
h
22 12
h
Figure 3.24 EMCYmessage
•
•
•
Bytes 0, 1 (error code): CANopen error codeThis value is 1000,
8200 or 8100 , depending on the cause of the error.
h
h
Byte 2: Error registerThe value is also stored in the object Error reg-
ister, 1001 .
h
Byte 3 (Manufacturer-Specific Error Field):Manufacturer-specific
error, error class
Bytes 6 and 7 are 0. Bytes 4,5 contain a manufacturer-specific error
number.See the product manual for a list of the error numbers.
COB ID The COB ID for every device on the network supporting an EMCYobject
is determined on the basis of the node address:
COB ID = Function code of EMCY object, 80 + Node-Id
h
Fieldbus interface
43
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.5
Synchronization
The synchronization object SYNC controls the synchronous exchange
of messages between network devices for purposes such as the simul-
taneous start of multiple drives.
The data exchange conforms to the producer-consumer relationship.
The SYNC object is transmitted to all devices by a network device and
can be evaluated by all devices that support synchronous PDOs.
SYNC-Consumer
SYNC-Consumer
CAN
COB-ID
SYNC-Consumer
SYNC- Producer
Figure 3.25 SYNC message
Time values for synchronization Two time values define the behavior of synchronous data transmission:
•
The cycle time specifies the time intervals between 2 SYNC mes-
sages. It is set with the object Communication cycle
period(1006 ).
h
•
The synchronous time window specifies the time span during which
the synchronous PDO messages must be received and trnasmitted.
The time window is defined with the object Synchronous window
length (1007 ).
h
SYNC
T_PDO (status)
R_PDO (controller)
CAN-Bus
SYNC
synchronous
time window
process
R_PDO data
cycle time
Figure 3.26 Synchronization times
Synchronous data transmission From the perspective of a SYNC recipient, in one time window the status
data is transmitted first in a T_PDO, then new control data is received via
an R_PDO. However, the control data is only processed when the next
SYNC message is received. The SYNC object itself does not transmit
data.
44
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Cyclic ad acyclic data transmission Synchronous exchange of messages can be cyclic or acyclic.
T_PDO1: acyclical
T_PDO2: cyclical
SYNC
Figure 3.27 Cyclic and acyclic transmission
In the case of cyclic transmission, PDO messages are exchanged con-
tinuously in a specified cycle, e.g. with every SYNC message.
If a synchronous PDO message is transmitted acyclically, it can be
transmitted or received at any time; however, it will not be valid until the
next SYNC message.
Cyclic or acyclic behavior of a PDO is specified in the subindex
transmission type (02 )of the corresponding PDO parameter,
h
e.g. in the object 1st receive PDO parameter (1400 :02 )for
h
h
R_PDO1.
COB ID, SYNC object For fast transmission, the SYNC object is transmitted unconfirmed and
with high priority.
The COB ID of the SYNC object is set to the value 128 (80 ) by default.
h
The value can be changed after initialization of the network with the ob-
ject COB-ID SYNC Message (1005 ) .
h
Fieldbus interface
45
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
3.6
Network management services
Network management (NMT) is part of the CANopen communication
profile; it is used to initialize the network and the network devices and to
start, stop and monitor the network devices in network mode.
NMT services are executed in a master-slave relationship. The NMT
master addresses individual NMT slaves via their node address. A mes-
sage with node address "0" is directed to all NMT slaves simultaneously.
NMT-
Slave
NMT-
Slave
NMT-
Slave
NMT-
Master
COB-ID
data
CAN
NMT-
Slave
NMT-
Slave
Figure 3.28 NMT services via the master-slave relationship
The device can only take on the function of an NMT slave.
NMT services NMT services can be divided into two groups:
•
Services for device control, to initialize devices for CANopen com-
munication and to control the behavior of devices in network mode
•
Services:for connection monitoring
3.6.1 NMT services for device control
NMT state machine The NMT state machine describes the initialization and states of an
NMT slave in mains operation.
Power on
Reset
Application
Reset
Communication
Initialization
SDO, EMCY
NMT
E
Pre-Operational
B
D
NMT
C
Stopped
A
PDO, SDO, SYNC
EMCY, NMT
Operational
Figure 3.29 NMT state machine and available communication objects
To the right, the graphic shows all communication objects that can be
used in the specific network state.
46
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Initialization An NMT slave automatically runs through an initialization phase after
the supply voltage is switched on (power on) to prepare it for CAN bus
operation. On completion of the initialization, the slave switches to the
state "Pre-operational" and sends a boot-up message. From now on, an
NMT master can control the operational behavior of an NMT slave in the
network via 5 NMT services, represented in the above illustration by the
letters A to E.
NMT service
Transition
Meaning
Start remote node
(Start network node)
A
Transition to state "Operational"
Start normal network mode with all network devices
Stop remote node
(Stop network node)
B
C
Transition to state "Stopped"
Stops communication of the network device in the network. If connection mon-
itoring is active, it remains on. If the power stage is active (state "Operation
Enabled" or "QuickStop"), an error of error class 2 is triggered. The drive is
stopped and switched off.
Enter Pre-Operational
(Transition to "Pre-Opera-
tional")
Transition to "Pre-Operational"
All communication objects except for PDOs can be used.
The state "Pre-Operational" can be used for configuration by SDOs:
- PDO mapping
- Start of synchronization
- Start of connection monitoring
Reset node
(Reset node)
D
E
Transition to state "Reset application"
Load stored data of the device profiles and automatically transition to "Pre-
operational" via "Reset communication".
Reset communication
(Reset communication
data)
Transition to state "Reset communication"
Load stored data of the communication profile and automatically switch to the
state "Pre-Operational.". If the power stage is active (state "Operation Ena-
bled" or "QuickStop"), an error of error class 2 is triggered. The drive is
stopped and switched off.
Persistent data memory When the supply voltage is switched on (power on), the device loads the
saved object data from the non-volatile EEPROM for persistent data to
the RAM.
Fieldbus interface
47
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
NMT message The NMT services for device control are transmitted as unconfirmed
messages with the COB ID = 0 . By default, they have the highest priority
on the CAN bus.
The data frame of the NMT device service consists of 2 bytes.
NMT-
Slave
Byte 0
1
NMT-
Master
0
01 00
NMT-
Slave
Node-ID
Command specifier
COB-ID
NMT-
Slave
Figure 3.30 NMT message
The first byte, the "Command specifier", indicates the NMT service
used.
Command Specifier
1 (01 )
NMT service
Transition
Start remote node
Stop remote node
Enter Pre-Operational
Reset node
A
B
C
D
E
h
2 (02 )
h
128 (80 )
h
129 (81 )
h
130 (82 )
Reset communication
h
The second byte addresses the recipient of an NMT message with a
node address between 1 and 127 (7F ). A message with the node ad-
h
dress "0" is directed to all NMT slaves.
3.6.2 NMT services for connection monitoring
Connection monitoring monitors the communication status of network
devices, so a response to the failure of a device or an interruption in the
network is possible.
Three NMT services for connection monitoring are available:
•
•
"Node guarding" for monitoring the connection of an NMT slave
"Life guarding" for monitoring the connection of an NMT master
3.6.2.1 Node/Life guarding
COB ID Communication object NMT error control (700 +node-Id)is
h
used for connection monitoring. The COB ID for every NMT slave is de-
termined on the basis of the node address:
COB ID = function code NMTerror control (700 ) + node-Id..
h
48
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
3 Basics
Structure of the NMT message After a request from the NMT master, the NMT slave responds with one
data byte.
Node-ID=04h
Slave
COB-ID
704h
Master
704h
05h
85h
05h
guard
time
704h
704h
704h
704h
...
Bit 7 6
0
Bit 7 6
0
05h
=
85h
=
0 0 0 0 0 1 0 1
1 0 0 0 0 1 0 1
Figure 3.31 Acknowledgement of the NMT slave
Bits 0 to 6 identify the NMT state of the slave:
•
•
•
4 (04 ): "Stopped"
h
5 (05 ): "Operational"
h
127 (7F ): "Pre-Operational"
h
After each "guard time" interval, bit 7 switches toggles between "0" and
"1", so the NMT master can detect and ignore a second response within
the "guard time" interval. The first request when connection monitoring
is started begins with bit 7 = 0.
Connection monitoring must not be active during the initialization phase
of a device. The status of bit 7 is reset as soon as the device runs though
the NMT state "Reset communication".
Connection monitoring remains active in the NMT state "Stopped".
Configuration Node/Life Guarding is configured via:
Guard time (100C )
•
h
•
Life time factor (100D )
h
Fieldbus interface
49
Download from Www.Somanuals.com. All Manuals Search And Download.
3 Basics
IL•1F CANopen DS301
Connection error The NMT master signals a connection error to the master program if:
•
•
the slave does not respond within the "guard time" period
the NMT state of the slave has changed without a request by the
NMT master.
Figure 3.32 shows an error message after the end of the third cycle be-
cause of a missing response from an NMT slave.
request
Slave
Master
response
guard
time
life
time
request
request
response
no
response
message
Figure 3.32 "Node Guarding" and "Life Guarding" with time intervals
Boot-up message The communication profile DS 301, version 4.0, defines an additional
task for the NMT services: sending a boot-up message.
A network device informs all other network devices that it is ready for op-
eration using a boot-up message.
A boot-up message consists of the COB ID of the NMT object NMT Er-
ror Controland is transmitted without data. The default setting of the
COB ID is 1792 (700h) + node-Id
50
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
4 Installation
4
Installation
@ WARNING
LOSS OF CONTROL
•
The designer of any control scheme must consider the potential
failure modes of control paths and, for certain critical functions,
provide a means to achieve a safe state during and after a path
failure. Examples of critical control functions are EMERGENCY
STOP, overtravel stop, power outage and restart.
•
•
Separate or redundant control paths must be provided for critical
functions.
System control paths may include communication links. Consid-
eration must be given to the implication of unanticipated transmis-
sion delays or failures of the link.
•
•
Observe the accident prevention regulations and local safety
guidelines.
1)
Each implementation of the product must be individually and thor-
oughly tested for proper operation before being placed into serv-
ice.
Failure to follow these instructions can result in death or serious
injury.
1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control
and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and
Guide for Selection, Installation for Construction and Operation of Adjustable-
Speed Drive Systems.
@ WARNING
SIGNAL AND DEVICE INTERFERENCE
Signal interference can cause unexpected responses of device.
•
•
Install the wiring in accordance with the EMC requirements.
Verify compliance with the EMC requirements.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
For information on installation of the device and connecting the device to
the fieldbus see the product manual.
Slave withDIP switches Before installing the slave in the system, you must set the network ad-
dress and the baud rate via the DIP switches in the connector housing.
See the chapter "Installation" in the product manual for information on
the DIP switch settings.
Fieldbus interface
51
Download from Www.Somanuals.com. All Manuals Search And Download.
4 Installation
IL•1F CANopen DS301
52
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
5 Commissioning
5
Commissioning
@ DANGER
UNINTENDED CONSEQUENCES OF EQUIPMENT OPERATION
When the system is started, the drives are usually out of the opera-
tor's view and cannot be visually monitored.
•
Only start the system if there are no persons in the hazardous
area.
Failure to follow these instructions will result in death or serious
injury.
@ WARNING
UNINTENDED OPERATION
•
•
Do not write values to reserved parameters.
Do not write values to parameters unless you fully understand the
function. For more information see the product manual.
•
•
Run initial tests without coupled loads.
Verify that the system is free and ready for the movement before
changing parameters.
•
Verify the use of the bits with fieldbus communication: bit 0 is far
right (least significant). Bit 15 is far left (most significant).
•
•
Verify the use of the word sequence with fieldbus communication.
Do not establish a fieldbus connection unless you have fully
understood all communications principles.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
5.1
Commissioning the device
For installation in the network, the device must first be properly installed
(mechanically and electrically) and commissioned.
Commission the device as per product manual. This prepares the device
for operation in the network.
Fieldbus interface
53
Download from Www.Somanuals.com. All Manuals Search And Download.
5 Commissioning
IL•1F CANopen DS301
5.2
Address and baud rate
Up to 32 devices can be addressed in one CAN bus network branch and
up to 127 devices in the extended network. Each device is identified by
a unique address. The default node address for a device is 127.
The default baud rate is 125 kbaud.
Each device must be assigned its own node address, i.e.
any given node address may be assigned only once in the
network.
Setting address and baud rate The address is set directly at the device via parameter canAddrand the
baud rate via parameter canBaud.
The baud rate must be the same for all devices in the fieldbus.
5.3
Commissioning the fieldbus network
5.3.1 Starting fieldbus mode
Configuration with SyCon Note on using the Hilscher configuration software SyCon:
Do not change the setting Geräteprofil(value = 0) in the
Knotenkonfigurationdialog box!
If this value is changed, communication with the drive will no longer
work. However, the setting cannot be reset to the initial value.
To restore communication with the product:
̈ Click the Knoten BootUp button in the Knotenkonfiguration
dialog box.
̈ Click Prüfe Knoten Type and Profilein the Knoten Auf-
schaltreihenfolgedialog to skip this step.
Testing fieldbus operation After correct configuration of the transmission data, test fieldbus opera-
tion.
This requires installation of a CAN configuration tool that displays CAN
messages. The acknowledgement from the product is indicated by a
boot-up message:
̈ Switch the power supply of the product off and on again.
̈ Observe the network messages shortly after switching on the
device. The positioning controller sends a 1 byte boot-up message
after initialization of the bus: 128 (80 )+node-Id.
h
With the node address factory-set to 127 (7F ), boot-up message 255
h
(FF ) is transmitted via the bus. The drive can then be put into operation
h
via NMT services.
54
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
5.3.2 Troubleshooting
5 Commissioning
Check the following settings if the slave does not respond:
̈ Did you start the slave and switch on the master?
̈ Are all cable connections ok (electrically and mechanically)?
̈ Did you set the correct address at the slave? Check the DIP switch
and HEX switch settings. The settings are described in the product
manual. Products without DIP switches have the following default
settings: CAN address 127 (7F ) and baud rate 125 [kBit/s]. You
h
can change these settings via CAN itself or by means of the PC
commissioning tool via the RS 485 interface.
̈ Did you set the same baud rate and the same interface parameters
for the master and the slave?
If the slave still does not respond:
̈ Open the cover of the connector housing.
̈ When a slave works properly with the power stage disabled, the
LED in the connector housing flashes constantly at 0.5 Hz (1 sec-
ond on, 1 second off). If this is not the case, the product is inopera-
tive. See the product manual for information on errors and
troubleshooting.
̈ Compare the behavior of LED with the information in the table
below.
Error
Error class
Cause of error
Troubleshooting
LED off
–
No supply voltage.
Check supply voltage and fuses.
LED flashes at 0.5 Hz(1 s .–
on, 1 s off)
Firmware works without errors,
power stage disabled.
Check cable connections. Check
DIP switch settings.
LED flashes at 6 Hz.
4
4
Incorrect flash checksum.
Hardware error
Reinstall firmware. Replace slave.
LED flashes at 10 Hz.
Watchdog
Switch slave off and on again.
Replace slave.
See the product manual for additional information on the cause of errors
and on troubleshooting.
Fieldbus interface
55
Download from Www.Somanuals.com. All Manuals Search And Download.
5 Commissioning
IL•1F CANopen DS301
5.4
SyCon CANopen configuration software
The CANopen network can be configured with the "SyCon" configura-
tion software. An additional EDS file is included in the SYCON subdirec-
tory on the product CD.
̈ Procedure:
5.4.1 Creating a new network
Create a new network via the menu item "File - New".
̈ Select CANopen as the fieldbus network.
̈ Confirm your selection with "OK".
5.4.2 Selecting the CANopen master
Use the menu item "Insert - Master" to select the network master. The
screenshot shows the example of a TSX CCP 110 board of a Premium
PLC.
The node ID and a brief description can be entered in the appropriate
fields.
̈ Confirm your selection with "OK".
56
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
5 Commissioning
5.4.3 Setting the bus parameters
The menu item "Settings - Bus Parameter..." allows you to set the CAN-
open communication parameters. Please also consult the operating in-
structions of the SyCon configuration software.
̈ Confirm your selection with "OK".
Fieldbus interface
57
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6
Operation
@ WARNING
UNINTENDED OPERATION
•
•
Do not write values to reserved parameters.
Do not write values to parameters unless you fully understand the
function. For more information see the product manual.
•
•
Run initial tests without coupled loads.
Verify that the system is free and ready for the movement before
changing parameters.
•
Verify the use of the bits with fieldbus communication: bit 0 is far
right (least significant). Bit 15 is far left (most significant).
•
•
Verify the use of the word sequence with fieldbus communication.
Do not establish a fieldbus connection unless you have fully
understood all communications principles.
Failure to follow these instructions can result in death, serious
injury or equipment damage.
6.1
Overview
The programming examples show hands-on applications for network
operation. There are 2 access methods via the CANopen fieldbus: SDO
"Service Data Objects" and PDO "Process Data Objects".
Using SDOs An SDO access is a write or a read access to an individual object. The
available objects are described in the product manual and also summa-
rized in a table in the chapter "Parameters". This chapter describes the
use of SDOs on the basis of just a small number of objects since this
type of communication can be used with all available objects and the
structure is very similar in all cases.
Using PDOs PDOs are recommended for positioning mode because the information
is transmitted much more efficiently. The chapter provides various
hands-on examples of the application of PDO4 supported by the product
and describes the general procedure.
•
•
The PDO from the master to the product is referred to as "R_PDO".
The PDO from the product to the master is referred to as "T_PDO".
Fieldbus interface
59
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
Structure of the examples The PDOs are described from the perspective of the slave:
The examples describe:
•
•
•
•
•
Task
Initial conditions
Required commands in the transmit data frame
Response of the product in the receive data frame
Possible restrictions for command execution.
You should be familiar with the following to be able to understand the ex-
amples:
•
Operating concept and functionality of the product. For more infor-
mation see the product manual.
•
•
Fieldbus protocol and connection to the master controller
Functionality of the fieldbus profile.
Product manual The examples are intended to supplement the function descriptions in
the product manuals. The basic function principles of the operating
modes and functions are described in the product manual.
All parameters for the operating modes and functions are also listed in
the product manual.
See table 9.2, page 9-1 in the device manual for a description of the
number format of the parameter values in a fieldbus command.
60
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6.2
Using SDO commands
6.2.1 Writing parameters
Task The parameter Motion.acc, 29:26 (acceleration) is to be set to a value
of 10,000.
Index and subindex must be converted to hexadecimal notation and the
constant 3000 added to the index for the SDO access:
h
•
•
•
Index:29 = 1D + 3000 = 301D
h
h
h
Subindex: 26 = 1A
h
Value:10000 = 00002710
h
The value 23 is to be entered as a CCD (Client Command Specifier)
h
since the parameter has a 32 bit data type.
Transmit data
COB ID CCD Idx
Object
Sdx
1A
Data
10 27 00 00
Description
Tx 301D :1A Motion.acc 600 +ID 23
1D 30
Sets the acceleration to
h
h
h
h
h
h
h
h
h
-1
10000 min *s = 2710 as a 32 bit
h
value
Refer to the column "Data type" in the parameter description for the data
type of the value to be written. The CAN protocol used transmits 16 bit
values and 32 bit values in the format "lowest value byte first – highest
value byte last". When an INT16 or a UINT16 value is transmitted, the
CCD corresponding to the data type must be included. The value must
be stored in the first two data bytes, the last two data bytes must be "0".
Receive data
Object
COB ID CCD Idx
1D 30
Sdx
1A
Data
Description
Rx 301D :1A Motion.acc 580 +ID 60
XX XX XX XX
The response data does not have
a meaning.
h
h
h
h
h
h
h
Fieldbus interface
61
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
6.2.2 Reading a parameter
Task The parameter Status.n_act, 31:9(actual speed) is to be read.
Index and subindex must be converted to hexadecimal notation and the
constant 3000 added to the index for the SDO access:
h
•
•
Index:31 = 1F + 3000 = 301F
h
h
h
Subindex 9 = 09
h
The value "40 " must be entered as the CCD. This value identifies a
h
"Read Request".
Transmit data
COB ID CCD Idx
Object
Sdx
09
Data
Description
Tx 301F :09 Sta-
tus.n_actT
600 +ID 40
1F 30
XX XX XX XX
Reads the actual speed. The data
has no significance.
h
h
h
h
h
h
h
The 4 data bytes have no significance for a read request.
Receive data
Object
COB ID CCD Idx
1F 30
Sdx
09
Data
Description
Rx 301D :09 Status.n_act 580 +ID 43
E8 03 00 00
The data 000003E8 corresponds
h
h
h
h
h
h
h
-1
to 1000 min .
The product transmits the data as 32 bit values back to the master (CCD
is "43 "). It also sends back data as a 32 bit value which are described
h
as INT16 or UINT16 data types in the product manual. When an INT16
or a UINT16 value is read, it is therefore possible to evaluate all 4 data
bytes. However, for 16 bit data it is also correct to evaluate only the first
two data bytes and to ignore the last two data bytes.
6.2.3 Synchronous errors
Receive data with error frame "Error If an SDO write or read command fails, the product responds with an er-
Response"
ror frame "Error Response". This may happen if, for example, you try to
read or write a non-existent object. The transmitted error number pro-
vides information on the exact cause.
Object
COB ID CCD Index
580 +ID 80 28 30
Sub
20
Data
Description
Rx 3028 :20
00 00 02 06
Error value 06020000h means
"object does not exist in object dic-
tionary"
h
h
h
h
h
h
h
The example shows the response to a write or read request for a non-
existent object 40:32.
The error number of a synchronous error message is stored as a
UINT16 value and the corresponding CCD (Error Response) is as-
h
error numbers.
62
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6.3
Changing operating states with PDO4
The product operates in different operating states. The individual oper-
ating states are numbered from 1 to 9 . The operating states and the
transition conditions are described in more detail in the product manual,
chapters "Basics" and "Operation".
Operating Name
state
Power
stage
Description
4
6
7
9
Ready To Switch On off
Passive operating state,
motor without current
Operation Enable
Quick Stop active
Fault
on
on
off
Active operating state, current
available to motor
Fault state, power stage
remains enabled
Fault state, power stage is
disabled
Table 6.1 Important operating states
Requests for switching operating states are transmitted to the product in
R_PDO4in the field drivectrl. The product signals the current oper-
ating state back to the master in T_PDO4, field driveStat.
R_PDO4:
Bit no.
Value
Meaning
0
1
2
3
4
01
02
04
08
10
Disable
h
h
h
h
h
Enable
Quick Stop
Fault Reset
Quick Stop release
Table 6.2 R_PDO4, drivectrl, bit assignment
Fieldbus interface
63
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
6.3.1 Switching the power stage on and off
The power stage is enabled by the transition from operating state 4 to 6
. For this purpose, the two bits Enableand Disableare available in the
R_PDO4. One of them must be "1", the other "0".
Enabling the power stage Prerequisite: the product in in operating state 4.
To enable the power stage, a "0 -> 1" edge must be generated in
drivectrl, bit 1 (Enable). This can be done by deleting bit 0 (Disable)
and setting bit 1 . The master then waits until the product signals oper-
ating state 6 . This may take a while (approx. 1 second) since various
tests are run when the power stage is enabled.
Example
Master <---> Slave
Disable is requested
--->
<---
drivectrl01
h
Slave signals operating
state 4
driveStat XXX4
h
Request Enable
--->
<---
drivectrl02
h
Slave signals operating
state 5
driveStat XXX5
h
h
Slave signals operating
state 6
<---
driveStat XXX6
Disabling the power stage Prerequisite: Product is in operating state 6 or 7.
To disable the power stage, a "0 -> 1" edge must be generated in drivec-
trl, bit 0 (Disable). This can be done by setting Bit 0(Disable) and de-
leting bit 1 (Enable). The product switches to operating state 4.
Example
Master <---> Slave
Enable is requested
--->
<---
drivectrl 02
h
Slave signals operating
state 6
driveStat XXX6
h
h
Request disable
--->
<---
drivectrl 01
h
Slave signals operating
state 4
driveStat XXX4
6.3.2 Triggering a "Quick Stop"
A running motion command can be interrupted via the fieldbus at any
time with the Quick Stop command. The stop is triggered by a "0 -> 1"
edge in drivectrl, bit 2. After the state transition to operating state 7
(Quick Stop), the product decelerates with the set EMERGENCY STOP
ramp and comes to a standstill.
In order to start a new motion command, you must first set the product
to operating state 6 . To achieve this, do one of the following:
•
•
Fault Reset"0 -> 1" edge in drivectrl, bit 3
Quick Stop release"0 -> 1" edge in drivectrl, bit 4
64
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
Example
Master <---> Slave
"Enable" is requested
--->
<---
drivectrl 02
h
Slave signals operating
state 6
driveStat XXX6
h
request "Quick Stop" and --->
"Enable"
drivectrl 06
h
Slave signals operating
state 7
<---
driveStat XXX7
h
Wait until the product has --->
come to a standstill and the
system is to resume opera-
tion
Request "Quick Stop
Release" and "Enable"
<---
--->
<---
drivectrl 12
h
Slave signals operating
state 6
driveStat XXX6
h
Cancel "Quick Stop
Release"
drivectrl 02
h
Fieldbus interface
65
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
6.3.3 Resetting faults
If an error occurs during operation, the product switches to operating
state 7 "Quick Stop" or operating state 9 "Fault", depending on the type
of error.
After having remedied the cause of the fault, you can reset the error
state with a Fault Reset ("0 -> 1" edge in drivectrl, bit 3).
If the product was originally in operating state 7, it will switch to operating
state 6 after the "Fault Reset".
If the product was originally in operating state 9, it will switch to operating
state 4 after the "Fault Reset". You then have to transmit a "0 -> 1" edge
in drivectrl, bit 1 "Enable", in order to enable the power stage.
Example
Master <---> Slave
Request Enable
--->
<---
drivectrl 02
h
Slave signals operating
state 9 (Fault)
driveStat XXX9
h
Remedy cause of error
Request "Fault Reset"
--->
<---
drivectrl 08
h
Slave signals operating
state 4
driveStat XXX4
h
h
Request "Enable"
--->
<---
drivectrl 02
h
Slave signals operating
state 5
driveStat XXX5
Slave signals operating
state 6
<---
driveStatXXXX6
h
Table 6.3 Disabling the power stage
Note: In this example, the master deletes the Bit 1"Enable" during the
"Fault Reset" in order to implicitly effect a "0 -> 1" edge in Bit 1. This
switches the product back to operating state 6.
66
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6.4
Examples for the operating modes with PDO4
R_PDO4 With the R_PDO4you can start motion commands and change them
while they are being processed.
R_PDO4provides three fields for these purposes:
• modeCtrlStarting and changing operating modes
•
"Ref16" and "Ref32" Operating mode-dependent reference values
The specified values for these three fields are not taken over by the prod-
uct until modeCtrl, bit 7 (ModeToggle) changes.
Proceed as follows to assign values to the product:
̈ Enter the desired operating mode and the corresponding values in
the fields modeCtrl, "Ref16" or "Ref32".
̈ Change modeCtrl, bit 7 (ModeToggle)
This avoids consistency problems within the R_PDO4.
T_PDO4 T_PDO4allows you to monitor motion commands.
T_PDO4 provides three fields for this purpose:
• modeStatFor Handshake purposes
• driveStatSignals motion status and errors
• p_actActual position of the product
ModeToggle The bit ModeToggleis available in the R_PDO4and in the T_PDO4. The
master provides this bit in the and the product mirrors is in the . This pro-
cedure allows the master to detect whether the data transmitted by the
slave is current.
Example The master starts a positioning movement that will only take a very short
time. The master waits for the end of the positioning movement by
checking T_PDO4for bit x_end = 1(positioning end).
The master may receive data from the slave that still originate from a
point in time before the positioning movement was started. This data
also contains x_end = 1. The master detects that the data is obsolete
because the included bit ModeToggledoes not match that of its motion
command.
The master may only evaluate data in which the received ModeToggle
bit is identical to the last bit transmitted by the master.
Acceleration Prior to positioning, you can first set the desired acceleration with an
SDO access (object Motion.acc, 29:26). Note that the acceleration
can only be changed when the product is at a standstill.
Assumptions The examples in this chapter are based on the following assumptions:
•
•
Operating state 6 "Operation Enable"
Homing has not yet been performed (bit ref_ok = 0)
• p_act = 0(actual position)
• R_PDO4: modeCtrl, Bit 7 = 0(ModeToggle)
Fieldbus interface
67
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
6.4.1 Operating mode Profile Position: absolute positioning
To start an absolute positioning movement, the following settings must
be made in the R_PDO4:
̈ Enter the reference speed in "Ref16" and the target position in
"Ref32".
̈ Enter operating mode 03 (Profile Position operating mode, abso-
h
lute positioning) in the field modeCtrl.
̈ Change modeCtrl, bit 7, so the data is taken over by the product.
Example Absolute positioniing to position 100,000 (000186A0 )
h
-1
at a reference speed of 1000 min (03E8 )
h
Master <---> Slave
Triggering positioning
R_PDO4 --->
drivectrl
02
modeCtrl Ref16
83 03E8
Ref32
000186A0
h
h
h
h
Positioning runningx_err = 0,
x_end = 0
T_PDO4 <---
T_PDO4 <---
driveStat
0006
modeStat
83
p_act
XXXXXXXX
h
h
h
Positioning completex_err = 0,
x_end = 1, x_info = 1
driveStat
6006
modeStat
83
p_act
000186A0
h
h
h
Table 6.4 Operating mode Profile Position, absolute positioning at constant ref-
erence speed
Note: The data frame "positioning running" can be sent several times;
the current actual position is contained in the field p_act.
-
Example As the above example, but the reference speed is changed to 2000 min
1
(07D0 ) during the movement.
h
Master <---> Slave
Triggering positioning
R_PDO4 --->
drivectrl
02
modeCtrl Ref16
83 03E8
Ref32
000186A0
h
h
h
h
Positioning runningx_err = 0,
x_end = 0
T_PDO4 <---
R_PDO4 --->
T_PDO4 <---
T_PDO4 <---
driveStat
0006
modeStat
83
p_act
XXXXXXXX
h
h
h
h
Change reference speed
drivectrl
02
modeCtrl Ref16
03 07D0
Ref32
000186A0
p_act
h
h
h
h
Positioning runningx_err = 0,
x_end = 0
driveStat
0006
modeStat
03
XXXXXXXX
h
h
Positioning complete x_err=0,
x_end = 1, x_info = 1
driveStat
6006
modeStat
03
p_act
000186A0
h
h
h
Table 6.5 Operating mode Profile Position, absolute positioning with change of
reference speed
Note: The data frame "positioning running" can be sent several times.
The current actual position is contained in the field p_act. When the ref-
erence speed is changed, the same target position is sent because it
does not change in this example.
68
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6.4.2 Operating mode Profile Position: relative positioning
Relative positioning is similar to absolute positioning. You only need to
enter the value 13 (operating mode Profile Positioning, relative posi-
h
tioning) in field modeCtrl. Also note that several target positions trans-
mitted in succession are added up.
Example: Relative positioning by 100,000 (000186A0 ) increments at a speed of
h
-1
1000 min (03E8 )
h
-1
During the movement, the speed is to be changed to 2000 min
(07D0 ).
h
Master <---> Slave
Triggering positioning
R_PDO4 --->
drivectrl
02
modeCtrl Ref16
93 03E8
Ref32
000186A0
h
h
h
h
Positioning runningx_err = 0,
x_end = 0
T_PDO4 <---
driveStat
0006
modeStat
83
p_act
XXXXXXXX
Ref32
h
h
h
h
Change reference speed Trans- R_PDO4 --->
mit relative postion "0"
drivectrl
02
modeCtrl Ref16
13 07D0
00000000
h
h
h
h
Positioning runningx_err = 0,
x_end = 0
T_PDO4 <---
driveStat
0006
modeStat
03
p_act
XXXXXXXX
p_act
h
h
Positioning completex_err = 0,
x_end = 1, x_info = 1
T_PDO4 <---
driveStat
6006
modeStat
03
000186A0
h
h
h
Table 6.6 Profile Position operating mode, relative positioning with change of
reference speed
Note: The data frame "positioning" running can be sent several times;
the current actual position is contained in the field p_act. When the ref-
erence speed is changed, the value "0" must be sent as the new target
position because the new value is added to the previously calculated tar-
get position.
6.4.3 Operating mode Profile Velocity
In Profile Velocity operating mode, a reference speed for the motor is set
and a movement without a target position is started.
To start the Profile Velocity operating mode or to change the reference
speed in Profile Velocity operating mode, you must make the following
settings in R_PDO4:
̈ Enter the reference speed in Ref16t. (Ref32has no significance
here)
̈ Enter the operating mode 04 (operating mode Profile Velocity) in
h
modeCtrl.
̈ Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Fieldbus interface
69
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
Example The Profile Velocity operating mode is started with a reference speed of
-1
1000 min (03E8 ).
h
-1
The reference speed is changed to 2000 min (07D0 ) during the
h
movement.
Master <---> Slave
Start Profile Velocity operating
mode with 1000 min
R_PDO4 --->
T_PDO4 <---
T_PDO4 <---
R_PDO4 --->
T_PDO4 <---
T_PDO4 <---
R_PDO4 --->
T_PDO4 <---
T_PDO4 <---
drivectrl
02
modeCtrl Ref16
84 03E8
Ref32
XXXXXXXX
-1
h
h
h
h
h
h
h
h
h
h
h
h
Product accelerates xerr=0,
xend=0, xinfo=0
driveStat
0006
modeStat
84
p_act
XXXXXXXX
h
h
Reference speed reached
xerr=0, xend=0, xinfo=1
driveStat
2006
modeStat
84
p_act
XXXXXXXX
h
h
-1
Change speed to 2000 min
drivectrl
02
modeCtrl Ref16
04 07D0
Ref32
XXXXXXXX
h
h
h
Product accelerates xerr=0,
xend=0, xinfo=0
driveStat
0006
modeStat
04
p_act
XXXXXXXX
h
h
Reference speed reached
xerr=0, xend=0, xinfo=1
driveStat
2006
modeStat
04
p_act
XXXXXXXX
h
h
-1
Change speed to 0 min
drivectrl
02
modeCtrl Ref16
84 0000
Ref32
XXXXXXXX
h
h
h
Product decelerates xerr=0,
xend=0, xinfo=0
driveStat
0006
modeStat
84
p_act
XXXXXXXX
h
h
Profile Vel. mode terminated
xerr=0, xend=1, xinfo=1
driveStat
6006
modeStat
84
p_act
XXXXXXXX
h
h
The Profile Velocity operating mode is terminated when the reference
speed "0" is transmitted; standstill is waited for.
Note: The field p_actof the T_PDO4contains the current position of the
drive in increments.
6.4.4 Position setting
During position setting, a new position is assigned to the current motor
position. This only shifts the coordinate system, the motor itself does not
move.
You must make the following settings for position setting in the R_PDO4:
•
•
Enter the new position in Ref32. (Ref16has no significance here)
Enter operating mode 02 in modeCtrl("Homing", "Position Set-
h
ting").
•
Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Example: The motor is at position -100,000 (FFFE7960 ).
h
Position 200,000 is assigned to the motor (00030D40 ).
h
Master <---> Slave
Product signals position-100,000 T_PDO4 <---
driveStat
XXXX
modeStat
XX
p_act
FFFE7960
h
h
h
Position setting to 200,000
R_PDO4 --->
T_PDO4 <---
drivectrl
02
modeCtrl Ref16
82 XXXX
Ref32
00030D40
h
h
h
h
Position taken over x_err = 0,
x_end = 1, x_info = 0
driveStat
4006
modeStat
A2
p_act
00030D40
h
h
h
70
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
6.4.5 Operating mode Homing
During the reference movement a limit switch or reference switch is ap-
proached and then a new value is assigned to this position.
Before a reference movement is started, the parameters must be set by
means of SDO write access to satisfy the requirements. See the product
manual for detailed information on parameterization and on performing
a reference movement.
To start a reference movement the following settings must be made in
the R_PDO4:
•
Enter the type of reference movement in Ref16(Ref32has no sig-
nificance here).
The available types of reference movement are described in the
device manual.
•
•
In modeCtrl, enter operating mode 12 "Homing".
h
Toggle modeCtrl, bit 7, so the data is taken over by the slave.
Example A reference movement to the negative limit switch (LIMN) is to be per-
formed; this is reference movement type 2.
Master <---> Slave
Trigger reference movement
R_PDO4 --->
drivectrl
02
modeCtrl Ref16
92 0002
Ref32
XXXXXXXX
h
h
h
h
h
Reference movement runningx- T_PDO4 <---
err=0, xend=0
driveStat
0006
modeStat8
p_act
XXXXXXXX
2
h
h
Reference movement complete T_PDO4 <---
xerr=0, xend=1
driveStat
4006
modeStat
A2
p_act
00000000
h
h
h
Table 6.7 Reference movement
Fieldbus interface
71
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
6.5
Error signaling via PDO4
6.5.1 Synchronous errors
If a request for an operating mode sent via R_PDO4 cannot be proc-
essed by the product, the product rejects processing and sets
modeStat, bit 6 ("ModeError") in the T_PDO4. This does not interrupt
the current process. To determine the cause of the error, the master can
read the error number from the object CAN.modeError, 30:11 with an
SDO access.
Example The product rotates in Profile Velocity operating mode.
Master <---> Slave
Profile Velocity operating
modex_end = 0
T_PDO4 <---
driveStat
0006
modeStat
04
p_act
XXXXXXXX
h
h
h
Request: Dimension setting to 0 R_PDO4 --->
drivectrl
02
modeCtrl Ref16
82 XXXX
Ref32
00000000
h
h
h
h
Request rejected "ModeError" = T_PDO4 <---
1
driveStat
0006
modeStat
C4
p_act
XXXXXXXXh
h
h
Table 6.8 Synchronous error, invalid operating mode request
NOTE: When the request for position setting is rejected, the product
continues to run in Profile Velocity operating mode; there is no change.
However, the product sends an EMCY message with the corresponding
error number to the master .
6.5.2 Asynchronous errors
Asynchronous errors are triggered by internal monitoring (e.g. temper-
ature) or by external monitoring (e.g. limit switch). If an asynchronous er-
ror occurs, the product responds by braking or by disabling the power
stage.
Asynchronous errors are indicated in the following way:
•
Change to operating state 7 "Quick Stop" or to operating state 9
"Fault".
The change is represented in T_PDO4, driveStat, bits 0 ... 3.
•
•
Setting of driveStat, bit 5 (fault detected by internal monitoring)
or driveStat, bit 6 (fault detected by internal monitoring)
In the event of an error message by internal monitoring:
Setting of the bit corresponding to the fault in object
Status.FltSig_SR, 28:18.
In the event of an error message by external monitoring:Setting of
the bit corresponding to the fault in object Status.Sign_SR, 28:15
•
In addition, an error number is assigned to each error. In the event
of an asynchronous error, the corresponding error number can be
read from the object Status.StopFault(32:7).
72
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
6 Operation
Example: External monitoring triggers a fault message; positive limit switch "LIMP"
was hit.
Master <---> Slave
Positioning running xerr=0,
xend=0
T_PDO4 <---
T_PDO4 <---
T_PDO4 <---
driveStat
0006
modeStat
03
p_act
XXXXXXXX
h
h
h
h
h
Limit switch detected xerr=1,
xend=0
driveStat
8047
modeStat
03
p_act
XXXXXXXX
h
h
Motor stopped xerr=1, xend=1
driveStat
C047
modeStat
03
p_act
XXXXXXXX
h
h
Table 6.9 Asynchronous error, triggering of an external
Note: When the limit switch is detected, the motor is decelerated with the
EMERGENCY STOP ramp until it comes to a standstill and the bit
x_erris set. After the motor has come to a standstill, bit x_endis set.
Fieldbus interface
73
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Operation
IL•1F CANopen DS301
74
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
7 Diagnostics and troubleshooting
7
Diagnostics and troubleshooting
7.1
Fieldbus communication error diagnostics
A properly operating fieldbus is essential for evaluating operating and er-
ror messages.
Connections for fieldbus mode If the product cannot be addressed via the fieldbus, first check the con-
nections. The product manual contains the technical data of the device
and information on network and device installation. Check the following:
•
•
•
•
24V power supply
dc
Power connections to the device
Fieldbus cable and fieldbus wiring
Network connection to the device
You can also use the commissioning software for troubleshooting.
Baud rate and address If it is impossible to connect to a device, check the baud rate and node
address.
•
•
The baud rate must be the same for all devices in the network.
The node address of each device must be between 1 and 127 and
unique for each device.
Fieldbus function test After correct configuration of the transmission data, test fieldbus mode.
This requires installation of a CAN configuration tool that displays CAN
messages. Feedback from the product is indicated by a boot-up mes-
sage:
•
•
Switch the power supply off and on again.
Observe the network messages after switching on. After initializa-
tion of the bus, the device sends a boot-up message (COB ID 700
h
+ node ID and 1 data byte with the content 00 ).
h
•
With the factory setting 127 (7F ) for the node address, the boot-up
message is sent via the bus . The device can then be put into oper-
ation via NMT services.
h
If network operation cannot be started, the network
function of the device must be checked by your local
representative. Contact your local sales representative.
Fieldbus interface
75
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Diagnostics and troubleshooting
IL•1F CANopen DS301
7.2
Error diagnostics via fieldbus
7.2.1 Message objects
A number of objects provide information on the operating and error
state:
•
Object Statusword (6041 )
Operating states, see product manual
h
•
Object EMCY (80 + Node-ID)
Error message from a device with fault state and error code, see
chapter 3.4.2.5 "Emergency service"
h
•
•
•
Object Error register (1001 )
Fault state
h
Object Error code (603F )
h
Error code of the most recent error
Devices use the special SDO error message ABORT to signal
errors in exchanging messages by SDO.
7.2.2 Messages on the device status
Synchronous and asynchronous errors are distinguished in the evalua-
tion and handling of errors.
Synchronous errors The device signals a synchronous error directly as a response to a mes-
sage that cannot be evaluated. Possible causes comprise transmission
errors or invalid data. For a list of synchronous errors see chapter 7.3.1
Asynchronous errors Asynchronous errors are signaled by the monitoring units in the device
as soon as a device fault occurs. An asynchronous error is signal via bit
3, "Fault", of the object statusword (6041 ). In the case of errors
h
that cause a an interruption of the movement, the device transmits an
EMCY message.
Asynchronous errors are also reported via bits 5..7 of the object
driveStat (2041 ).
h
76
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
7 Diagnostics and troubleshooting
7.3
CANopen error messages
CANopen error messages are signaled in the form of EMCY messages.
They are evaluated via the objects Error register (1001 )and
h
Error code (603F ). For information on the object EMCYsee chapter
h
CANopen signals errors that occur during data exchange via SDO with
the special SDO error message ABORT.
7.3.1 Error register
The object Error register(1001 )indicates the error state of a de-
h
vice in bit-coded form. The exact cause of error must be determined with
the error code table. Bit 0 is set as soon as an error occurs.
Bit Message
Meaning
0
1
2
3
4
5
6
7
Generic error
An error has occurred
reserved
-
-
reserved
-
reserved
Communication
Device profile-specific
-
Network communication error
Error in execution as per device profile
reserved
Manufacturer-specific
Vendor-specific error message
7.3.2 Error code table
The error code is evaluated with the object error code (603F ), an
h
object of the DSP402 device profile, and output as a four-digit hexadec-
imal value. The error code indicates the cause of the last interruption of
movement. See the Troubleshooting chapter of the product manual for
the meaning of the error code.
Fieldbus interface
77
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Diagnostics and troubleshooting
7.3.3 SDO error message ABORT
IL•1F CANopen DS301
An SDO error message is generated as a response to an SDO trans-
mission error. The cause of error is contained in error code, byte 4 to
byte 7.
Client
Server
error response
0
2
3
4
5
6
7
1
Idx
Idx
Sidx
ccd
COB-ID
ccd:
data
1
2
Byte 4-7
error code
80
Figure 7.1
SDO error message as a response to an SDO message
The table below shows all error messages that may occur during data
exchange with the product.
Error code
Meaning
0504 0000
0504 0001
0601 0000
0601 0001
0601 0002
0602 0000
0604 0041
0604 0042
Time-out during SDO transfer
h
h
h
h
h
h
h
h
Command specifier CS incorrect or unknown
Access to object impossible
No read access, because write-only object (wo)
No write access, because read object (ro)
Object does not exist in object dictionary
Object does not support PDO mapping
PDO mapping: number or length of objects exceed the byte
length of the PDO
0607 0010
0607 0012
0607 0013
0609 0011
0609 0030
Data type and parameter length do not match
Data type does not match, parameter too long
Data type does not match, parameter too short
Subindex not supported
h
h
h
h
h
Value range of parameter too large (relevant only for write
access)
0609 0031
0609 0032
0800 0000
0800 0022
Parameter values too great
h
h
h
h
Parameter values too small
General error
Device status keeps data from being transmitted and saved.
78
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
8
Object directory
8.1
Overview
This object dictionary only describes the protocol for the product as per
CANopen DS 301. The objects for controlling operating modes, func-
tions and all parameters can be found in the product manual for the prod-
uct.
8.1.1 Specifications for the objects
Index The index specifies the position of the object in the object dictionary. The
index value is specified as a hexadecimal value.
Object code The object code specifies the data structure of the object.
Object code
Meaning
Coding
VAR
A single value, for example of the type
Integer8, Unsigned32 or Visible String8.
7
ARR (ARRAY)
A data field in which every entry is of the
same data type.
8
9
REC (RECORD)
A data field that contains entries that are
a combination of single data types.
Data type
Boolean
INT8
Value range
Data length
1 byte
0 = false, 1 = true
-128 ..+127
1 byte
INT16
-32768 ..+32767
-2147483648 ..+2147483647
0 ..255
2 byte
INT32
4 byte
UINT8
1 byte
UINT16
0 ..65535
2 byte
UINT32
0 ..4294967295
ASCII characters
ASCII characters
4 byte
Visible String8
Visible String16
8 byte
16 byte
Access ro: "Read Only"value can be read only
rw: "Read Write"value can be read and written
wo: "Write Only"value can be written only
PDO R_PDO: mapping for R_PDO possible
T_PDO: mapping for T_PDO possible
No specification: PDP mapping not possible with the object
Value range Specifies the permissible range in which the object value is defined and
valid.
Default value Load the saved factory settings to reset the product to the default values.
Fieldbus interface
79
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Can be saved yes: values can be saved to the memory of the product and are available
when the product is switched on again.
–: values are lost when the product is switched off.
8.1.2 Objects, overview
Index
Subindex
Designation
Obj. code Data type
Access
ro
1000
1001
1008
device type
VAR
VAR
VAR
VAR
VAR
VAR
UINT32
UINT8
String
h
h
h
error register
ro
manufacturer device name
guard time
ro
100C
100D
UINT16
UINT8
UINT16
rw
rw
rw
ro
h
h
life time factor
1015
1018
1018
1018
1018
1403
1403
1403
1403
1403
1403
1403
1603
1603
1603
1603
1603
1603
1803
1803
1803
1803
1803
1803
1803
inhibit time EMCY
h
identity object
RECORD Identity
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
h
0
1
2
number of elements
VAR
VAR
VAR
UINT8
UINT32
UINT8
ro
Vendor id
ro
product code
ro
receive PDO4 communication parameter
number of elements
RECORD PDO_Com
ro
0
1
2
3
4
5
VAR
VAR
VAR
VAR
VAR
VAR
UINT8
UINT32
UINT8
UINT16
UINT8
UINT16
ro
COB ID used by R_PDO4
transmission type R_PDO4
inhibit time R_PDO4
compatibility entry R_PDO4
event timer R_PDO4
receive PDO4 mapping
number of elements
ro
rw
rw
rw
rw
ro
RECORD PDO_Map
0
1
2
3
4
VAR
VAR
VAR
VAR
VAR
UINT8
ro
1st mapped object R_PDO4
2nd mapped object R_PDO4
3rd mapped object R_PDO4
4th mapped object R_PDO4
transmit PDO4 communication parameter
number of elements
UINT32
UINT32
UINT32
UINT32
ro
ro
ro
ro
RECORD PDO_Com
ro
0
1
2
3
4
5
VAR
VAR
VAR
VAR
VAR
VAR
UINT8
UINT32
UINT8
UINT16
UINT8
UINT16
ro
COB ID used by T_PDO4
transmission type T_PDO4
inhibit time T_PDO4
ro
rw
rw
rw
rw
ro
reserved T_PDO4
event timer T_PDO4
transmit PDO4 mapping
number of elements
1A03
1A03
1A03
1A03
1A03
1A03
RECORD PDO_Map
h
h
h
h
h
h
0
1
2
3
4
VAR
VAR
VAR
VAR
VAR
UINT8
ro
1st mapped object T_PDO4
2nd mapped object T_PDO4
3rd mapped object T_PDO4
4th mapped object T_PDO4
UINT32
UINT32
UINT32
UINT32
ro
ro
ro
ro
80
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
8.2
Objects of the product
1000h Device type
The object specifies the device profile used as well as the device type.
Object description
Index
1000
h
Object name
Object code
Data type
device type
VAR
Unsigned32
Value description
Subindex
00 , device type
h
Meaning
Device type and profile
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0
–
1001h Error register
The object specifies the error state of the product. The manufacturer-
specific object Status.StopFault 32:7 provides detailed informa-
tion on the cause of the error.
Errors are signaled by an EMCY message as soon as they occur.
Object description
Value description
Index
1001h
Object name
Object code
Data type
error register
VAR
Unsigned8
Subindex
00 , error register
h
Meaning
error register
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
–
–
Fieldbus interface
81
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Bit coding, subindex 00h
Bit
0
Access Value
Meaning
ro
ro
ro
ro
ro
ro
ro
ro
–
–
–
–
–
–
–
–
Error! (generic error)
Current
1
2
Voltage
3
Temperature
4
Communication profile (communication error)
Device profile (device profile error)
Reserved
5
6
7
Manufacturer-specific
1008h Manufacturer device name
The object specifies the device name (e.g. “IFS ”)
Object description
Index
1008
h
Object name
Object code
Data type
manufacturer device name
VAR
String
Value description
Subindex
00 , manufacturer device name
h
Meaning
Manufacturer name
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
–
–
100Ch Guard time
The object specifies the time span for node guarding of an NMT slave.
Object description
Index
100C
h
Object name
Object code
Data type
guard time
VAR
Unsigned16
Value description
Subindex
00 , guard time
h
Meaning
Time span for node guarding [ms]
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
0...65535
0
–
82
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
The time span for connection monitoring of an NMT master results from
the time span "guard time" multiplied by the factor "life time", object
Life time factor(100D ).
h
The time span can be changed in the NMT state "Pre-Operational".
100Dh Life time factor
The object specifies the factor that, together with the time span "guard
time", results in the time interval for connection monitoring of an NMT
master. Within this period, the NMT slave device expects a monitoring
request via node guarding from the NMT master.
life time = guard time * life time factor
The value "0" deactivates monitoring of the NMT master.
Object description
Value description
Index
100D
h
Object name
Object code
Data type
life time factor
VAR
Unsigned8
Subindex
00 , life time factor
h
Meaning
Time factor for the node guarding protocol
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
0...255
0
–
If there is no connection monitoring through the NMT master during the
time interval "life time", #Variable:device-name# signals an error and
switches to error state.
The time factor can be changed in the NMT state "Pre-Operational".
The time span "guard time" is set with the object Guard time(100C ).
h
1015h Inhibit time emergency message
The object specifies the waiting time for the repeated transmission of
EMCY messages as a multiple of 100μs.
Object description
Index
1015
h
Object name
Object code
Data type
inhibit time EMCY
VAR
Unsigned16
Fieldbus interface
83
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Value description
Subindex
00h, inhibit time EMCY
Meaning
Waiting time for repeated transmission of an EMCY
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
0...65535
0
–
1018h Identity Object
The object provides information on the product. Subindex 01 (vendor
h
Id) contains the vendor identification, subindex 02 (product Id) contains
h
the vendor-specific product code.
Value description
Index
1018
h
Object name
Object code
Data type
Identity Object
RECORD
Identity
Subindex
00h, number of elements
Meaning
Number of subindexes
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
1...4
2
–
Subindex
01 , vendor id
h
Meaning
Vendor ID
read-only
–
Access
PDO mapping
Value range
Default value
Can be saved
0...4294967295
0x0100002E
–
Subindex
02 , product code
h
Meaning
Product identification
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
0...4294967295
0x01
–
84
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
1403h Receive PDO4 communication parameter
The object stores settings for the fourth receive PDO R_PDO4.
Object description
Value description
Index
1403
h
Object name
Object code
Data type
receive PDO4 communication parameter
RECORD
PDO Communication parameter
Subindex
00 , number of elements
h
Meaning
Number of subindexes
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
5
–
Meaning
Identifier of the R_PDO4
Subindex
01 , COB-ID R_PDO4
h
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x40000500+nodeID
–
Subindex
02 , transmission type R_PDO4
h
Meaning
Transmission type
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
254
–
Subindex
03 , inhibit time R_PDO4
h
Meaning
Delay time for repeated transmissions (1=100 μsec)
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
0...65535
0
–
Fieldbus interface
85
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Subindex
04 , compatibility entry R_PDO4
h
Meaning
For compatibility purposes only
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
–
–
Subindex
05 , event timer R_PDO4
h
Meaning
Time setting for event triggering
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
0
–
Bit assignment subindex 01h
Bit
Acces Value Meaning
s
31
30
rw
ro
0
0
0: PDO is active 1: PDO is inactive
b
b
0: RTR (see below) is possible 1: RTR is not per-
mitted
29
ro
0
0: 11 bit identifier (CAN 2.0A) 1: 29 bit identifier
(CAN 2.0B)
b
28-11 ro
0000
0100
–
Only relevant if bit 29=1 is not used by the product.
Function code, bit 10-7 of the COB ID
h
10-7
6-0
rw
ro
h
Node address, bit 6-0 of the COB ID
Bit 31 A R_PDO can only be used if bit 31="0".
Bit 30 RTR bit If a device supports R_PDOs with RTR (remote transmission request),
it can request a PDO from a PDO producer with RTR = "0" in accordance
with the producer-consumer relationship.
The product cannot request PDOs, but it can respond to the request for
a PDO, see RTR bit for T_PDO1 settings (1800h).
Bit coding, subindex 02h The control for evaluating R_PDO data is specified via subindex 02h.
The values 241..251 are reserved.
Transmission type cyclic
acyclic
synchronous
asynchronous
RTR-controlled
0
–
X
–
–
–
–
X
–
–
–
–
–
X
X
X
–
–
–
–
–
–
X
X
X
–
–
1-240
252
253
254
255
X
X
–
–
86
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
If an R_PDO is transmitted synchronously (transmission type=0..252),
the product evaluates the received data depending on the SYNC object.
•
In the case of acyclic transmission (transmission type=0), the evalu-
ation depends on the SYNC object, but not the transmission of the
PDO. A received PDO message is evaluated with the following
SYNC.
A value between 1 and 240 specifies the number of SYNC cycles
after which a received PDO is evaluated.
The values 252 to 254 are relevant for updating T_PDOs, but not for
sending them.
•
•
252: Updating of transmit data with receipt of the next SYNC
253: Updating of transmit data with receipt of a request from a PDO
consumer
•
254: Updating of data in an event-controlled way, the triggering
event is specified in a manufacturer-specific way
R_PDOs with the value 255 are updated immediately upon receipt of the
PDOs. The triggering event is the data that is transmitted corresponding
to the definition of the device profile in the PDO.
Subindex 03h The "Inhibit time" interval is only relevant for T_PDOs.
A T_PDO is retransmitted after expiration of the "Inhibit time" interval at
the earliest. The value is specified as a multiple of 100 μs, however, it is
rounded down to milliseconds as an integer value.
Subindex 04h The value is reserved and not used. Write or read access triggers an
SDO error message.
Subindex 05h The time interval "event timer" is only relevant for T_PDOs. A T_PDO is
transmitted after expiry of the time interval "event timer". At the same
time, the time interval is restarted. The "transmission type" must be set
to one of the values 254 or 255 via subindex 02h.
Settings R_PDO4 is processed asynchronously and in an event-controlled way.
The byte assignment of R_PDO4 is specified via PDO mapping with the
object Receive PDO4 mapping(1603 ) and cannot be modified. The
h
assignment is described in 3.4.2.2 "Receive PDO R_PDO4 (master ->
The COB ID of the object can be changed in the NMT state "Pre-Oper-
ational".
1603h Receive PDO4 mapping
The object specifies the objects mapped in R_PDO4 and transmitted
with the PDO. When the object is read, subindex 00 , the number of
h
mapped objects is read.
Object description
Index
1603h
Object name
Object code
Data type
receive PDO4 mapping
RECORD
PDO Mapping
Fieldbus interface
87
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Value description
Subindex
00h, number of elements
Meaning
Number of subindexes
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
4
–
Subindex
01 , 1st mapped object R_PDO4
h
Meaning
First object for mapping in R_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0108
–
Subindex
02 , 2nd mapped object R_PDO4
h
Meaning
Second object for mapping in R_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0208
–
Subindex
03 , 3rd mapped object R_PDO4
h
Meaning
Third object for mapping in R_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0510
–
Subindex
04 , 4th mapped object R_PDO4
h
Meaning
Fourth object for mapping in R_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0620
–
88
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
Bit coding from subindex 01h Every subindex entry from subindex 01h on specifies the object and the
byte length of the object. The object is identified via the index and the
subindex, which refer to the object dictionary of the device.
Bit
Meaning
31..16
15..8
7..0
Index
Subindex
Object length in bytes
Settings The assignment of the R_PDO4 is preset and cannot be modified.
The assignment is described in 3.4.2.2 "Receive PDO R_PDO4 (master
1803h Transmit PDO4 communication parameter
The object stores settings for the fourth transmit PDO T_PDO4.
Object description
Index
1803
h
Object name
Object code
Data type
Transmit PDO4 communication parameter
RECORD
PDO Communication Parameter
Value description
Subindex
00 , number of elements
h
Meaning
Number of subindexes
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
5
–
Subindex
01 , COB ID used by T_PDO4
h
Meaning
Identifier of the T_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x00000480+nodeID
–
Subindex
02 , transmission type T_PDO4
h
Meaning
Transmission type
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
254
–
Fieldbus interface
89
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Subindex
Meaning
03 , inhibit time T_PDO4
h
Delay time for repeated transmission (in [100μsec]). The
value is rounded down to milliseconds as an integer
value.
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
0...65535
0
–
Subindex
04 , reserved T_PDO4
h
Meaning
Reserved (for compatibility purposes only)
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
–
–
Subindex
05h, event timer T_PDO4
Meaning
Time setting for event triggering
Access
read-write
PDO mapping
Value range
Default value
Can be saved
–
–
0
–
The meaning of the bit states and subindex values is described with the
object receive PDO4 communication parameter(1403 ).
h
Settings R_PDO4 is transmitted asynchronously and in an event-driven way.
The byte assignment of T_PDO4 is specified via PDO mapping with the
object transmit PDO4 mapping(1A03 ) and cannot be modified.
h
The COB ID of the object can be changed in the NMT state "Pre-Oper-
ational".
1A03h Transmit PDO4 mapping
The object specifies the objects mapped in T_PDO4 and transmitted
with the PDO. When the object is read, subindex 00 , the number of
h
mapped objects is read.
Object description
Index
1A03
h
Object name
Object code
Data type
transmit PDO4 mapping
RECORD
PDO Mapping
90
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
8 Object directory
Value description
Subindex
00 , number of elements
h
Meaning
Number of subindexes
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
4
–
Subindex
01 , 1st mapped object T_PDO4
h
Meaning
First object for the mapping in T_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0410
–
Subindex
02 , 2nd mapped object T_PDO4
h
Meaning
Second object for the mapping in T_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0308
–
Fieldbus interface
91
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Object directory
IL•1F CANopen DS301
Subindex
03 , 3rd mapped object T_PDO4
h
Meaning
Third object for the mapping in T_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0708
–
Subindex
04 , 4th mapped object T_PDO4
h
Meaning
Fourth object for the mapping in T_PDO4
Access
read-only
PDO mapping
Value range
Default value
Can be saved
–
–
0x301E0820
–
The meaning of the bit states is described with the object receive
PDO4 mapping(1603 ).
h
Settings The PDO assignment for T_PDO4 cannot be modified. The assigne-
92
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
9 Glossary
9
Glossary
9.1
Units and conversion tables
The value in the specified unit (left column) is calculated for the desired
unit (top row) with the formula (in the field).
Example: conversion of 5 meters [m] to yards [yd]
5 m / 0.9144 = 5.468 yd
9.1.1 Length
in
ft
yd
m
cm
mm
in
-
/ 12
/ 36
* 0.0254
* 0.30479
* 0.9144
-
* 2.54
* 30.479
* 91.44
* 100
-
* 25.4
* 304.79
* 914.4
* 1000
* 10
ft
* 12
-
/ 3
yd
m
* 36
* 3
-
/ 0.0254
/ 2.54
/ 25.4
/ 0.30479
/ 30.479
/ 304.79
/ 0.9144
/ 91.44
/ 914.4
cm
mm
/ 100
/ 1000
/ 10
-
9.1.2 Mass
lb
oz
* 16
-
slug
kg
g
lb
-
* 0.03108095
* 1.942559*10
-
* 0.4535924
* 0.02834952
* 14.5939
-
* 453.5924
* 28.34952
* 14593.9
* 1000
-3
oz
slug
kg
g
/ 16
-3
/ 0.03108095
/ 0.45359237
/ 453.59237
/ 1.942559*10
/ 0.02834952
/ 28.34952
/ 14.5939
/ 14593.9
/ 1000
-
9.1.3 Force
lb
oz
p
dyne
N
lb
-
* 16
* 453.55358
* 28.349524
-
* 444822.2
* 27801
* 980.7
-
* 4.448222
* 0.27801
oz
p
/ 16
-
-3
/ 453.55358
/ 444822.2
/ 4.448222
/ 28.349524
/ 27801
/ 0.27801
* 9.807*10
3
dyne
N
/ 980.7
/ 100*10
-3
3
/ 9.807*10
* 100*10
-
9.1.4 Power
HP
W
HP
W
-
* 746
-
/ 746
Fieldbus interface
93
Download from Www.Somanuals.com. All Manuals Search And Download.
9 Glossary
IL•1F CANopen DS301
9.1.5 Rotation
-1
min (RPM)
rad/s
* π / 30
-
deg./s
-1
min (RPM) -
* 6
rad/s
* 30 / π
/ 6
* 57.295
-
deg./s
/ 57.295
9.1.6 Torque
lb·in
lb·ft
oz·in
* 16
* 192
-
Nm
kp·m
kp·cm
dyne·cm
6
lb·in
-
/ 12
* 0.112985
* 1.355822
* 7.0616*10
-
* 0.011521
* 0.138255
* 720.07*10
* 0.101972
-
* 1.1521
* 13.8255
* 72.007*10
* 10.1972
* 100
* 1.129*10
6
lb·ft
* 12
-
* 13.558*10
* 70615.5
-3
-6
-3
oz·in
Nm
/ 16
/ 192
-3
6
/ 0.112985
/ 0.011521
/ 1.1521
/ 1.355822
/ 0.138255
/ 13.8255
/ 13.558*10
/ 7.0616*10
/ 720.07*10
/ 72.007*10
/ 70615.5
* 10*10
-6
-3
6
6
kp·m
kp·cm
dyne·cm
/ 0.101972
/ 10.1972
* 98.066*10
* 0.9806*10
-
/ 100
-
6
6
6
6
6
/ 1.129*10
/ 10*10
/ 98.066*10
/ 0.9806*10
9.1.7 Moment of inertia
2
2
2
2
2
2
lb·in
lb·ft
kg·m
kg·cm
kp·cm·s
/ 335.109
* 0.429711
* 10.1972
/ 980.665
-
oz·in
2
lb·in
-
/ 144
-
/ 3417.16
* 0.04214
-
/ 0.341716
* 16
2
lb·ft
* 144
* 421.4
* 2304
* 54674
* 5.46
* 5361.74
-
2
3
kg·m
* 3417.16
* 0.341716
* 335.109
/ 16
/ 0.04214
/ 421.4
* 10*10
2
3
kg·cm
/ 10*10
-
2
kp·cm·s
/ 0.429711
/ 2304
/ 10.1972
/ 54674
* 980.665
/ 5.46
2
oz·in
/ 5361.74
9.1.8 Temperature
°F
°C
K
°F
°C
K
-
(°F - 32) * 5/9
(°F - 32) * 5/9 + 273.15
°C * 9/5 + 32
-
°C + 273.15
-
(K - 273.15) * 9/5 + 32
K - 273.15
9.1.9 Conductor cross section
AWG
1
2
3
4
5
6
7
8
9
10
11
12
13
2
mm
42.4
33.6
26.7
21.2
16.8
13.3
10.5
8.4
6.6
5.3
4.2
3.3
2.6
AWG
14
15
16
17
18
19
20
21
22
23
24
25
26
2
mm
2.1
1.7
1.3
1.0
0.82
0.65
0.52
0.41
0.33
0.26
0.20
0.16
0.13
94
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
9 Glossary
9.2
Terms and Abbreviations
AC Alternating current
CAN (Controller Area Network), standardized open fieldbus as per ISO
11898, allows drives and other devices from different manufacturers to
communicate.
CANopen Device- and manufacturer-independent description language for com-
munication via the CAN bus
CiA CAN in Automation, CAN interest group, standardization group for CAN
and CANopen.
COB ID Communication OBject IDentifier; uniquely identifies each communica-
tion object in a CAN network
DC Direct current
Default value Factory setting.
DriveCom Specification of the DSP402 state machine was created in accordance
with the DriveCom specification.
DS301 Standardizes the CANopen communication profile
DSP402 Standardizes the CANopen device profile for drives
E
Encoder
EDS (Electronic Data Sheet); contains the specific properties of a product.
Electronic gear Calculation of a new output speed for the motor movement based on the
input speed and the values of an adjustable gear ratio; calculated by the
drive system.
EMC Electromagnetic compatibility
EMCY object Emergency Object
Encoder Sensor for detection of the angular position of a rotating component. In-
stalled in a motor, the encoder shows the angular position of the rotor.
Error Discrepancy between a computed, observed or measured value or con-
dition and the specified or theoretically correct value or condition.
Error class Classification of errors into groups. The different error classes allow for
specific responses to faults, for example by severity.
Fault Operating state of the drive caused as a result of a discrepancy between
a detected (computed, measured or signaled) value or condition and the
specified or theoretically correct value or condition.
Fault reset A function used to restore the drive to an operational state after a de-
tected error is cleared by removing the cause of the error so that the er-
ror is no longer active (transition from operating state "Fault" to state
"Operation Enable").
I/O Inputs/outputs
Input device A device that can be connected via the RS232 interface; either the hand-
held HMI device or a PC with commissioning software.
Limit switch Switches that signal overtravel of the permissible range of travel.
Fieldbus interface
95
Download from Www.Somanuals.com. All Manuals Search And Download.
9 Glossary
IL•1F CANopen DS301
Power stage The power stage controls the motor. The power stage generates current
for controlling the motor on the basis of the positioning signals from the
controller.
Heartbeat Used for unconfirmed connection acknowledgement messages from
network devices.
HMI Human Machine Interface: hand-held operating device.
Power amplifier See power stage
Life guarding For monitoring the connection of an NMT master
Mapping Assignment of object dictionary entries to PDOs
Node ID Node address assigned to a device on the network.
NMT Network Management (NMT), part of the CANopen communication pro-
file; tasks include initialization of the network and devices, starting, stop-
ping and monitoring of devices
Node guarding Monitoring of the connection to the slave at an interface for cyclic data
traffic.
Object dictionary List of all parameters, values and functions available in the device. Each
entry is uniquely referenced via index (16 bit) and subindex (8 bit).
Parameter Device data and values that can be set by the user.
PDO Process Data Object
Persistent Indicates whether the value of the parameter remains in the memory af-
ter the device is switched off.
Quick Stop Function used to enable fast deceleration of the motor via a command
or in the event of an error.
R_PDO Receive PDO
SDO Service Data Object
SYNC object Synchronization object
T_PDO Transmit PDO
Warning If the term is used outside the context of safety instructions, a warning
alerts to a potential problem that was detected by a monitoring function.
A warning is not an error and does not cause a transition of the operating
state.
96
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
10 Index
IL•1F CANopen DS301
Command-code
Communication objects
Communication profile
Communication relationship
Connection error
Connection monitoring
D
Data
Data length
Data transmission
Device profile
DS301
DS402
E
EMCY
Emergency object
Error
98
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
10 Index
Error code
Error diagnostics
Example
F
function code
Function test
G
H
I
Identification
Index
Interruption of movement
L
Layer model
M
Fieldbus interface
99
Download from Www.Somanuals.com. All Manuals Search And Download.
10 Index
IL•1F CANopen DS301
Messages
N
Network management
NMT
Services
O
Object groups
Operating mode
Overview
P
Process Data Object
process data objects
Producer-consumer
100
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
IL•1F CANopen DS301
10 Index
Profiles
R
Recipient
Response
S
Service Data Object
Services
Specification
State machine
Subindex
Synchronization object
Synchronous
T
Tasks
Fieldbus interface
101
Download from Www.Somanuals.com. All Manuals Search And Download.
10 Index
IL•1F CANopen DS301
Time values
U
V
Vendor-specific
102
Fieldbus interface
Download from Www.Somanuals.com. All Manuals Search And Download.
|