Roberts Gorden Patio Heater POP ECA PGP ECA 015 to 0100 User Guide

FOR YOUR SAFETY  
If you smell gas:  
1. Open windows.  
®
2. DO NOT try to light any appliance.  
3. DO NOT use electrical switches.  
4. DO NOT use any telephone in  
your building.  
5. Leave the building.  
Combat  
Cabinet Heaters  
6. Immediately call your local gas  
supplier after leaving the building.  
Follow the gas supplier’s  
instructions.  
7. If you cannot reach your gas  
supplier, call the Fire Department.  
Installation, Commissioning,  
Operation & Service Manual  
WARNING  
OIL-FIRED:  
Model POP-ECA  
015 to 0100  
Fire Hazard  
GAS-FIRED:  
Model PGP-ECA  
015 to 0100  
Do not store or use petrol or other  
flammable vapours and liquids in the  
vicinity of this or any other appliance.  
Some objects will catch fire or explode  
when placed close to heater.  
Failure to follow these instructions can  
result in death, injury or property  
damage.  
Installer  
WARNING  
Please take the time to read and understand  
these instructions prior to any installation.  
Installer must give a copy of this manual to the owner.  
Improper installation, adjustment, alteration, service  
or maintenance can result in death, injury or property  
damage. Read the installation, operation and service  
manual thoroughly before installing or servicing  
this equipment.  
Owner  
Keep this manual in a safe place in order to provide  
your serviceman with necessary information.  
Installation must be done by a registered installer/  
contractor qualified in the installation and service of  
gas/oil-fired heating equipment or your fuel supplier.  
Roberts-Gordon Europe Limited  
Unit A, Kings Hill Business Park  
Darlaston Road, Wednesbury  
West Midlands,WS10 7SH UK  
Telephone: +44 (0)121 506 7700  
Fax: +44 (0)121 506 7701  
Service Telephone: +44 (0)121 506 7709  
Service Fax: +44 (0)121 506 7702  
Quality in Any Language™  
© Copyright 2008 Roberts-Gordon LLC  
P/N X523 Rev G 10/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
SECTION 1: Heater Safety......................................................2  
SECTION 2: Installer Responsibility .....................................2  
2.1 Clearances to Combustibles........................................2  
2.2 Corrosive Chemicals....................................................2  
2.3 National Standards and Applicable Codes ..................2  
SECTION 3: Critical Considerations .....................................3  
3.1 Basic Information.........................................................3  
3.2 Location and Suspension ............................................3  
3.3 Minimum Required Installation Clearances .................3  
3.4 Clearances to Combustibles........................................3  
9.11 CCH Wiring Diagram Gas Models 60-100  
(floor standing) .........................................................28  
9.12 CCH Wiring Diagram Oil Models 60-100  
(floor standing) .........................................................29  
9.13 CCH Wiring Diagram Gas Models 60-100  
(horizontal mounting) ...............................................30  
9.14 CCH Wiring Diagram Oil Models 60-100  
(horizontal mounting) ...............................................31  
9.15 Final Connections to Ecoflam HIGH/LOW or  
Modulating Burners (all models) ..............................32  
3.5 Ventilation ....................................................................3 SECTION 10: Commissioning ..............................................33  
3.6 Fuel Supply..................................................................3  
3.7 Electrical Supply..........................................................3  
3.8 Flue..............................................................................3  
SECTION 4: Specifications ....................................................5  
4.1 PGP & POP Internal Heaters.......................................5  
4.2 PGP & POP External Heaters .....................................6  
4.3 Air Outlet and Flue Arrangements ...............................7  
4.4 General Technical Data Table (all models)  
10.1 Pre-Commission Checks..........................................33  
10.2 Commissioning the Burner (gas heaters).................34  
10.3 Control - Gas-Fired Heaters .....................................35  
10.4 Gas Valves ...............................................................37  
10.5 Combustion Testing (all models) ..............................37  
10.6 Commissioning the Burner (Oil Heaters)..................38  
10.7 Control - Oil-Fired Heaters .......................................38  
10.8 Turning Off the Heater (all models) ..........................39  
10.9 External Controls......................................................39  
10.10 Instruction to the User ............................................39  
Appliance Category II 2H/L 3B/P .......................................8  
4.5 Technical Data - Ecoflam ON/OFF Burners  
(all models - burner reference "C")..............................8 SECTION 11: User Instructions............................................40  
4.6 Technical Data - Ecoflam Modulating Burners  
(all models - burner reference "H")..............................9  
4.7 Technical Data - Ecoflam Oil-Fired Burners  
11.1 User Instructions.......................................................40  
11.2 Common User Controls (all models).........................40  
11.3 Lighting Instructions (all models) ..............................41  
11.4 Simple Fault Finding (all models)..............................41  
(burner reference "G") ............................................... 10  
SECTION 5: Heater Installation............................................ 11 SECTION 12: Servicing.........................................................43  
5.1 General...................................................................... 11  
5.2 Handling .................................................................... 11  
SECTION 6: Flue Installation ............................................... 13  
6.1 Flue Installation.......................................................... 13  
SECTION 7: Air Supply......................................................... 15  
12.1 Servicing Instructions...............................................43  
12.2 Burner Maintenance.................................................43  
12.3 Fan/Motor Assembly Maintenance (all models) .......43  
12.4 Heat Exchanger Maintenance..................................43  
12.5 Thermal Insulation ...................................................43  
7.1 Air Supply................................................................... 15 SECTION 13: Conversion Between FUELS.........................44  
7.2 Isolated Equipment Rooms ........................................ 15  
13.1 General ....................................................................44  
7.3 Building Ventilation..................................................... 15  
13.2 Burner Conversion ...................................................44  
7.4 Distribution Ducting .................................................... 15 SECTION 14: Troubleshooting .............................................45  
7.5 Return Air Ducting...................................................... 15  
SECTION 8: Fuel Piping........................................................ 16  
8.1 Connections............................................................... 16  
8.2 Fuel Oil Supply .......................................................... 17  
SECTION 9: Wiring and Electrical Information................... 19  
9.1 Electrical Supply........................................................ 19  
9.2 Remote Controls........................................................ 19  
9.3 CCH Wiring Diagram Gas Models 15-30  
14.1 General ....................................................................45  
14.2 Troubleshooting for Oil Burners  
(see manufacture’s instructions) ..............................46  
14.3 Troubleshooting for Gas Burners  
(see manufacturer’s instructions).............................47  
14.4 Troubleshooting for Flame Supervision System .......48  
14.5 Troubleshooting for Solenoid Valves Circuit .............49  
14.6 Troubleshooting for Main Fan Circuit (1 Ø)...............49  
14.7 Troubleshooting for Main Fan (3 Ø)..........................50  
SECTION 15: Removal and Replacement Parts..................51  
15.1 Burner Components ..............................................51  
15.2 Direct On-Line Main Fan Starter and  
(floor standing)...........................................................20  
9.4 CCH Wiring Diagram Oil Models 15-30  
(floor standing)...........................................................21  
9.5 CCH Wiring Diagram Gas Models 15-30  
(horizontal mounting).................................................22  
9.6 CCH Wiring Diagram Oil Models 15-30  
Thermal Overload Unit (3 Ø) ...................................51  
15.3 Control Circuit Fuse  
(horizontal mounting).................................................23  
9.7 CCH Wiring Diagram Gas Models 40-50  
(floor standing)...........................................................24  
9.8 CCH Wiring Diagram Oil Models 40-50  
(10 or 5 A, 1-1/4" long sand filled)............................51  
15.4 Combination Fan/Limit Thermostat..........................51  
15.5 Main Fan Motor (3 Ø Belt Drive) ..............................51  
15.6 Main Fan Units.........................................................51  
(floor standing)...........................................................25 SECTION 16: Parts List.........................................................53  
9.9 CCH Wiring Diagram Gas Models 40-50  
16.1 Spare Parts List........................................................53  
(horizontal mounting).................................................26  
9.10 CCH Wiring Diagram Oil Models 40-50  
(horizontal mounting) ...............................................27  
Roberts-Gordon LLC  
© 2008  
All rights reserved. No part of this work covered by the copyrights herein may be reproduced  
or copied in any form or by any means - graphic, electronic, or mechanical, including  
photocopying, recording, taping or information storage and retrieval systems - without the  
written permission of Roberts-Gordon LLC.  
Printed in U.K.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF FIGURES  
Figure 1: Installation Clearances and Clearances to  
Combustibles.............................................................4  
Figure 2: Typical Installation of a Gas Fired Cabinet Heater... 11  
Figure 3: Typical Installation of a Oil-Fired Cabinet Heater..... 12  
Figure 4: Flue Termination ...................................................... 13  
Figure 5: Offset Flues with 135° bends ................................... 13  
Figure 6: Guy Wire.................................................................. 14  
Figure 7: Socket Direction....................................................... 14  
Figure 8: Flue and Roof Detail ................................................ 14  
Figure 9: Flue and Heater Spigot Joint Detail ......................... 14  
Figure 10: Gas Connection ..................................................... 16  
Figure 11: B. M. Oil Lifter......................................................... 17  
Figure 12: Pressurised System Installation - Duplex System .. 18  
Figure 13: Combination Thermostat (all models)....................34  
Figure 14: Gas-Fired Heater Control Box Sequence...............35  
Figure 15: Motor Starter (models 040 -100 and Thermal  
Overload (models 060 - 100) .................................36  
Figure 16: Gas Train Circuit for Dungs Gas Valves  
(all models) ............................................................36  
Figure 17: Dungs Gas Valve ...................................................37  
Figure 18: Oil-Fired Heaters Control Box Sequence ...............38  
Figure 19: Heater Operating Sequence ..................................40  
Figure 20: Fan/Limit Thermostat.............................................40  
Figure 21: Belt Tension ...........................................................43  
Figure 22: Combination Fan/Limit Thermostat........................52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Product Approval  
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential  
requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic  
Compatibility Directive and the Machinery Directive for use with natural gas and LPG when installed,  
commissioned and maintained in accordance with these instructions.  
These instructions refer to gas appliances designed to operate in the European Union.  
Appliances designed for other countries (Non-European Union) are available on request.  
Oil-fired versions are constructed to the same basic design criteria to burn fuel oil as specified below,  
but no similar testing is available for these products at the time of writing. Oil-fired appliances should be  
operated in accordance with local rules and laws.  
Oil heaters are supplied as standard for use with Gas Oil, also known as 35-second Oil, Red Diesel,  
Class D or Class A2. They are also available to order for Kerosine, also known as 28-second Oil or  
Class C2.  
These appliances must be installed in accordance with the local and national codes in force and used  
only in a sufficiently ventilated space, as specified in these instructions.  
Before installation, check that the local gas distribution systems, nature of gas and pressure, and  
adjustment of the appliance are compatible.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
SECTION 1: HEATER SAFETY  
Your Safety Is Important to Us!  
This symbol is used throughout the  
clearances to combustibles. Affix the tag on a wall  
near the heater.  
manual to notify you of possible fire,  
electrical or burn hazards. Please pay  
special attention when reading and  
2.2 Corrosive Chemicals  
following the warnings in these sections.  
Installation, Service and Annual Inspection of heater  
must be done by a registered installer/contractor  
qualified in the installation and service of gas/oil-  
fired heating equipment.  
CAUTION  
Do not use heater in an area containing corrosive  
chemicals.  
Corrosive chemicals will damage the burner and  
heat exchanger parts.  
Read this manual carefully before installation,  
operation, or service of this equipment.  
Burner manufacturers manual is also provided to  
give detailed instructions on the operation of the  
burner. The settings for use of the burner with the  
heater are shown in these instructions.  
Failure to follow these instructions can result in  
property damage.  
Roberts-Gordon cannot be responsible for ensuring  
that all appropriate safety measures are undertaken  
prior to installation; this is entirely the responsibility  
of the installer. It is essential that the contractor, the  
sub-contractor or the owner identifies the presence  
This heater is designed for heating non-residential  
indoor spaces. Do not install in residential spaces.  
These instructions, the layout drawing, local codes  
and ordinances, and applicable standards that apply of combustible materials, corrosive chemicals or  
to gas piping, electrical wiring, venting, etc., must be halogenated hydrocarbons* anywhere on the  
thoroughly understood before proceeding with the  
installation.  
premises.  
* Halogenated Hydrocarbons are a family of chemical  
compounds characterized by the presence of halogen  
elements (fluorine, chlorine, bromine, etc.). These com-  
pounds are frequently used in refrigerants, cleaning  
agents, solvents, etc. If these compounds enter the air  
supply of the burner, the lifespan of the heater compo-  
nents will be greatly reduced. Warranty will be invalid if  
the heater is exposed to halogenated hydrocarbons.  
SECTION 2: INSTALLER RESPONSIBILITY  
To install the heater, as well as the fuel and  
electrical supplies, in accordance with applicable  
specifications and codes. Roberts-Gordon  
recommends the installer contact a local  
building inspector, Fire Officer or insurance  
company for guidance.  
To use the information given in this manual  
together with the local and national codes to  
perform the installation.  
To install the heater in accordance with the  
Clearances to Combustibles of this heater.  
To furnish all needed materials not furnished  
as standard equipment.  
To plan location of supports, flues and air  
intakes.  
To provide access to burners for servicing.  
To provide the owner with a copy of this  
installation, commissioning, operation and  
service manual.  
To never use heater as support for ladder or  
other access equipment and never hang or  
suspend anything from heater.  
2.3 National Standards and Applicable Codes  
All appliances must be installed in accordance with  
the latest revision of applicable standards and local  
and national codes. This refers also to the electric,  
gas and venting installation. NOTE: Additional  
standards for installations in Public Garages, Aircraft  
Hangars, etc. may be applicable.  
The main relevant regulations for installation within  
the UK are:  
• Gas safety (installation and use) regulations,  
1984 and amendments - 1996.  
• BS6230 - Specification for the installation of gas  
fired forced convection air heaters for commer-  
cial and industrial space heating of rated input  
exceeding 60kW. (This standard also applies to  
oil-fired heaters, except for the fuel supply).  
• BS6230 - Parts 2 & 3, fire precautions in the  
design and construction of buildings.  
• BS6891 - Low pressure installation pipes.  
• BS5410 - Codes of practice for oil firing. Part 2  
installation of 44 kW and above output capacity  
for space heaters, hot water and steam supply  
purposes.  
To ensure that there is sufficient ventilation in the  
area to comply with the requirements of  
all relevant local and national codes.  
• Institute of Gas Engineers document IGE/UP/2.  
• Building regulations.  
• IEE regulations.  
• Health and safety at work acts.  
• Requirements of local authority, fire officer and  
insurance company.  
2.1 Clearances to Combustibles  
In all situations, clearances to combustibles must be  
maintained. Caution must be used when running the  
heater near combustible materials such as wood,  
paper, rubber, etc. A wall tag is on the back cover of  
this manual as a permanent reminder of the safety  
instructions and the importance of the required  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 3: CRITICAL CONSIDERATIONS  
SECTION 3: CRITICAL CONSIDERATIONS  
3.1 Basic Information  
3.7 Electrical Supply  
Cabinet heaters are supplied with burners suitable  
for on/off operation as standard. As an option, oil-  
A permanent 230 V, 50 Hz, 1 Ø is required on  
models 15 to 30 and 400 V, 50 Hz, 3 Ø and neutral  
fired burners are available with two-stage operation required on models 40 to 100 (special version PGP  
and gas-fired burners are available with full  
modulation.  
and POP 040 and 050 models are available as belt  
drive). The heater also requires suitable energy  
controls in accordance with Section 9.  
ON/OFF control, temperature control, time control,  
and frost protection are available as a remote  
control, which needs to be site wired for proper  
operation of the heater. Alternatively, any remote  
energy controls may be used which must be wired in  
accordance with Section 9.3 through Section 9.10.  
3.2 Location and Suspension  
All models:  
• Are designed to be installed indoors within the  
heated space. Special versions are available for  
installation outdoors.  
• Are designed for floor standing vertical installa-  
tion.  
• Must be installed in a manner which allows all  
the upper panels and either of the lower side  
panels to be removed to provide access to all  
serviceable components.  
• Must be placed on a firm, level, non-combustible  
surface that can support its weight. See Page 5,  
Section 4.1 for weight details.  
3.8 Flue  
Choose heater siting to allow for the proper location  
of the flue. Each heater must be fitted with an  
individual and correctly sized sealed flue system  
(See Page 13, Section 6).  
Horizontal models:  
• Special versions supplied with steel channels to  
support the heater are available and may be  
mounted horizontally. When installed horizon-  
tally, the heater will normally lie on its left side  
when viewed from the burner. The same clear-  
ances and comments on panels must be used,  
except for the side the heater lies on.  
3.3 Minimum Required Installation Clearances  
Clearances around the heater and flue must be as  
indicated on Page 4, Figure 1 and Page 13, Figure 4  
through Figure 5 to ensure access for servicing, and  
correct operation.  
3.4 Clearances to Combustibles  
Clearances must be as indicated on Page 4, Figure  
1. If no clearances to combustibles are indicated,  
then installation clearances apply.  
3.5 Ventilation  
It is important to ensure adequate air circulation  
around the heater to supply air for combustion,  
ventilation and distribution in accordance with local  
and national codes.  
3.6 Fuel Supply  
It is important that the fuel supply pipe is sized  
correctly to provide the inlet pressure as stated on  
the heater data plate. The fuel supply pipe and  
electrical connections must not support any of the  
heater's weight.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
WARNING  
Fire Hazard  
Some objects will catch fire or explode when  
placed close to heater.  
Keep all flammable objects, liquids and  
vapours the required distance away from the  
heater.  
Failure to follow these instructions can result  
in death, injury or property damage.  
Figure 1: Installation Clearances and Clearances to Combustibles  
.6 m  
.6 m  
4 m  
.6 m  
*.6 m  
*.6 m  
The flue pipe must have clearance from combustibles by 5 cm.  
If installed where individuals can come in contact with the pressure relief door or other hot components,  
adequate guarding must be provided.  
All distances are minimum clearance requirements for service access, air flow and safety.  
*A service clearance of 1m is required on one side to allow for fan replacement.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4: SPECIFICATIONS  
SECTION 4: SPECIFICATIONS  
4.1 PGP & POP Internal Heaters  
Front View  
(all models)  
Rear View  
(all models)  
Side View  
Side View  
(Models 060 - 0100)  
(Models 015 - 050)  
D
D
E
C
G
G
G
108  
70  
38  
A
70  
38  
38  
F
B
H
38  
38  
F
B
38  
Dimension Data - PGP & POP Internal Heaters  
Model 015/020  
030  
040  
050  
060/070/080  
0100  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
724  
29  
857  
34  
1740  
69  
1267  
50  
1988  
78  
781  
31  
457  
18  
648  
26  
724  
29  
857  
34  
1740  
69  
1267  
50  
2058  
81  
781  
31  
457  
18  
648  
26  
857  
34  
857  
34  
1930  
76  
1337  
53  
2235  
88  
781  
31  
560  
22  
781  
31  
1016  
40  
1016  
40  
1930  
76  
1496  
59  
2235  
88  
940  
37  
560  
22  
781  
31  
1016  
40  
1676  
66  
1930  
76  
2156  
85  
2235  
88  
1600  
63  
560  
22  
1016  
40  
1994  
79  
1930  
76  
2496  
98  
2235  
88  
1918  
76  
559  
22  
A
B
C
D
E
Width  
Depth, Cabinet Only  
Height, Cabinet Only  
Depth, Overall  
Height, Including Heads  
Left/Right Air Inlet Spigot - Depth  
Left/Right Air Inlet Spigot - Height  
Rear Air Inlet Spigot - Depth  
Rear Air Inlet Spigot - Height  
Flue Diameter*  
F
G
H
J
NA  
NA  
NA  
NA  
mm  
(in)  
mm  
(in)  
361  
14  
178  
7
361  
14  
178  
7
446  
18  
178  
7
446  
18  
178  
7
229  
9
229  
9
Weight  
kg  
200  
200  
245  
270  
440  
530  
NOTES: Horizontal cabinet heaters are designed to lie on their left side as standard.  
For vertical models, add 54 mm (2 in) to the right side of the cabinet for the fan/limit thermostat.  
For horizontal models, add 54 mm (2 in) to the top of the cabinet for the fan/limit thermostat.  
*All heaters must be connected to a suitable flue constructed of single wall stainless steel.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
4.2 PGP & POP External Heaters  
Front View  
Side View  
Rear View  
F
D
H
275  
G
P
J
50  
C
C
L
M
70  
38  
108  
38  
A
N
B
38  
E
38  
K
A
Dimension Data - PGP & POP External Heaters  
Model  
015/020/030  
040  
050  
060/070/080  
0100  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
724  
29  
857  
34  
1740  
69  
1396  
55  
373  
15  
840  
33  
857  
34  
857  
34  
1930  
76  
1498  
59  
474  
19  
973  
38  
857  
34  
1016  
40  
1930  
76  
1657  
65  
474  
19  
973  
38  
1016  
40  
1676  
66  
1930  
76  
2483  
98  
639  
25  
1132  
45  
1016  
40  
1994  
79  
1930  
76  
2800  
110  
639  
25  
1132  
45  
A
B
C
D
E
Width  
Depth, Cabinet Only  
Height, Cabinet Only  
Depth Overall  
External Heater Housing  
Width Overall  
F
mm  
(in)  
mm  
(in)  
mm  
(in)  
476  
19  
648  
26  
178  
7
476  
19  
781  
31  
178  
7
610  
24  
781  
31  
178  
7
1238  
49  
940  
37  
229  
9
1524  
60  
940  
37  
229  
9
G
H
J
Air Outlet Spigot - Depth  
Air Outlet Spigot - Width  
Flue Diameter  
mm  
(in)  
mm  
(in)  
mm  
(in)  
mm  
(in)  
648  
26  
178  
7
457  
18  
781  
31  
781  
31  
178  
7
560  
22  
781  
31  
781  
31  
178  
7
560  
22  
940  
37  
K
L
Rear Return/Fresh Air Inlet - Width  
Rear Return/Fresh Air Inlet - Height  
Left/Right Return Fresh Air Inlet - Height  
Left/Right Return Fresh Air Inlet - Width  
Rear of Heater to Air Outlet Spigot*  
NA  
NA  
229  
9
560  
22  
1600  
63  
96  
4
229  
9
560  
22  
1918  
76  
96  
4
M
N
P
mm  
(in)  
401  
16  
401  
16  
426  
17  
NOTE: *For Models 060-0100, the circular flue spigot is at the front of the heater, with the rectangular air outlet spigot at the rear.  
COMBAT® external cabinet heaters are designed to be sited externally, with heat ducted into the building. These models  
are fitted with a special metal rain drip cover, and all cabinet joints are silicone sealed to ensure that the heaters are  
weatherproof.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4: SPECIFICATIONS  
4.3 Air Outlet and Flue Arrangements  
4.3.1 Vertical and Horizontal Heaters - Free Blowing (top view)  
0100  
060/070/080  
015/020  
030  
040  
050  
229  
165  
165  
203  
184  
284  
NOTE: Models 015-020 are fitted with 229 mm (9") diameter discharge heads as standard.  
Models 030-0100 are fitted with 356 mm (14") diameter discharge heads as standard.  
4.3.2 Vertical and Horizontal Heaters - Air Outlet Spigots (top view)  
050  
015/020/030  
040  
060/070/080  
K
0100  
38  
K
38  
38  
38  
38  
38  
100  
368  
100  
100  
343  
100  
100  
L
L
L
L
L
38  
38  
38  
38  
38  
38  
400  
38  
K
38  
K
38  
K
432  
Outlet Spigot Dimensions  
Model  
015/020/030  
040  
050  
060/070/080  
0100  
mm  
(in)  
mm  
(in)  
648  
26  
476  
19  
781  
31  
476  
19  
781  
31  
610  
24  
940  
37  
1238  
49  
940  
37  
1524  
60  
K
L
Spigot width  
Spigot Depth  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
4.4 General Technical Data Table (all models)  
Appliance Category II 2H/L 3B/P  
Model  
015  
020  
030  
040  
050  
060  
070  
080  
0100  
Electrical Supply*  
Main Fan Motor Type  
Motor Size  
230 V / 50 Hz / 1 Ø  
Direct Drive  
400 V / 50 Hz / 3 Ø  
Belt Drive  
2.2  
(kW)  
0.75  
2.2  
1.5  
4.0  
2 A x  
2 A x  
Motor Pulley  
Fan Pulley  
(PCD)  
NA  
2 A x 95 mm  
80 mm  
106 mm  
2 A x  
180 mm  
10.2  
3.5  
11044  
6500  
2 A x  
180 mm  
2 A x  
2 A x  
180 mm 180 mm  
(PCD)  
NA  
28  
6.3  
5097  
3000  
Start Current  
Run Current  
Airflow  
(Amps)  
(Amps)  
24  
5.3  
3398  
2000  
24  
5.3  
3398  
2000  
21  
6.2  
6796  
4000  
21  
6.2  
8495  
5000  
30  
5.1  
30  
5.1  
35  
9.6  
17330  
10200  
3
12443  
7500  
12443  
7500  
(m /h)  
3
Free Blowing  
(ft /min)  
NOTE: *Models 40 & 50 are available with 230 V 1 Ø electrical supply as an extra cost option.  
A permanent uninterrupted electrical supply is required for all models.  
When reading the following data tables, ensure that you are using the correct table for the burner and gas valve  
installed. The data tables include a burner reference letter that can be found on the heater data plate. Refer to the  
burner manufacturer’s instructions and the specific instructions supplement where applicable. The burner settings  
shown in the instructions must be used for burner settings.  
4.5 Technical Data - Ecoflam ON/OFF Burners (all models - burner reference "C")  
Model  
Gross Heat Input  
Net Heat Input  
015  
55.5  
189.4  
50.0  
170.6  
020  
73.3  
250.1  
66.0  
225.2  
030  
93.2  
318.0  
84.0  
286.6  
040  
129.9  
443.2  
117.0  
399.2  
050  
162.0  
552.7  
146.0  
498.2  
060  
208.0  
709.7  
187.4  
639.4  
070  
242.0  
825.7  
218.0  
743.8  
080  
275.2  
939.0  
248.0  
846.2  
0100  
348.5  
1189.1  
314.0  
1071.4  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
47.4  
161.7  
61.2  
208.8  
78.4  
267.5  
110.2  
376.0  
134.5  
458.9  
177.7  
606.3  
205.3  
700.5  
230.4  
786.1  
293.4  
1001.1  
Heat Output  
Pressure Switch Setting  
Flue Static Pressure  
Gas Connection  
(mbar)  
(mbar)  
(in)  
1.5  
4.5  
-0.09  
4.0  
-0.30  
6.5  
-0.05  
5.0  
-0.25  
6.5  
-0.17  
1 1/4"  
7.5  
0.10  
7.0  
0.45  
-0.05  
-0.05  
3/4"  
Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min 17 mbar (6.8 in WG) Max 25 mbar (10 in WG)  
Main Burner Gas Pressure  
Start Gas Pressure  
mbar  
mbar  
4.0  
NA  
5.3  
187  
2.7  
NA  
7.0  
247  
4.2  
NA  
8.9  
314  
4.8  
1.8  
12.4  
438  
7.7  
2.8  
15.4  
546  
5.2  
0.9  
19.8  
701  
7.1  
1.1  
23.1  
816  
9.5  
1.7  
26.2  
928  
10.0  
3.4  
33.2  
1175  
3
(m /h)  
Gas Rate  
3
(ft /h)  
Start Gas Orifice  
Burner Type  
(mm dia)  
5.0  
6.0  
7.0  
7.0  
7.0  
AZUR 60 BLU 120 BLU 120 BLU 170 BLU 250R BLU 250  
BLU 250 BLU 250S BLU 350  
Burner Head  
Burner Head Setting  
Air Setting  
S
0
2.6  
S
10  
4.2  
S
11  
6
S
15  
2.2  
S
14  
3.5  
S
24  
2.9  
S
24  
3.6  
S
24  
1.4  
S
21  
1.6  
(mm)  
MBDLE  
405  
NA  
MBDLE  
407  
MBDLE  
410  
S.I.T. 0 832 051  
MBDLE  
412  
Valve Type Main Gas  
Valve Type Start Gas  
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 in WG) Min 25 mbar (10 in WG) Max 45 mbar (18 in WG)  
Main Burner Gas Pressure  
Start Gas Pressure  
mbar  
mbar  
(m /h)  
(kg/h)  
4.2  
NA  
2.1  
3.9  
3.3  
NA  
2.8  
5.1  
4.6  
NA  
3.5  
6.5  
4.8  
1.6  
4.9  
9.1  
7.5  
2.5  
6.1  
11.3  
5.8  
0.8  
7.8  
14.5  
7.8  
1.0  
9.1  
16.9  
12.0  
1.5  
10.4  
19.2  
7.6  
3.1  
13.1  
24.3  
3
Gas Rate  
Start Gas Orifice  
Main Gas Orifice  
(mm dia)  
(mm dia)  
5.0  
14.5  
6.0  
14.5  
7.0  
14.5  
7.0  
14.5  
7.0  
14.5  
8.5  
10.0  
10.0  
AZUR  
60 AH  
BLU  
120 AH  
BLU  
120 AH  
BLU  
170 AH  
BLU  
250R AH  
BLU  
250 AH  
BLU  
250 AH  
BLU  
250S AH  
BLU  
350 AH  
Burner Type  
Burner Head  
Burner Head Setting  
Air Setting  
S
0
3.0  
S
10  
4.8  
S
13  
6.6  
S
15  
2.6  
S
14  
4.5  
S
24  
3.1  
S
24  
4.2  
S
24  
1.6  
LPG  
20  
1.8  
(mm)  
MBDLE  
405  
NA  
MBDLE  
407  
MBDLE  
MBDLE  
412  
Valve Type Main Gas  
Valve Type Start Gas  
410  
S.I.T. 0 832 051  
NOTE: For adjustment of head setting, see Ecoflam Instructions  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 4: SPECIFICATIONS  
4.6 Technical Data - Ecoflam Modulating Burners (all models - burner reference "H")  
Model  
015  
020  
030  
040  
050  
060  
070  
080  
0100  
(kW)  
55.5  
73.3  
93.2  
129.9  
443.2  
117.0  
399.2  
90.9  
310.2  
81.9  
279.5  
110.2  
376.0  
162.0  
552.7  
146.0  
498.2  
113.4  
386.9  
102.2  
348.7  
134.5  
458.9  
94  
321  
208.0  
709.7  
187.4  
639.4  
145.6  
496.8  
131.2  
447.7  
177.7  
606.3  
124  
423  
242.0  
825.7  
218.0  
743.8  
169.4  
578.0  
152.6  
520.7  
205.3  
700.5  
144  
491  
275.2  
939.0  
248.0  
846.2  
192.6  
657.2  
173.6  
592.3  
230.4  
694.0  
161  
549  
348.5  
Maximum Gross Heat Input  
Maximum Net Heat Input  
Minimum Gross Heat Input  
Minimum Net Heat Input  
Maximum Heat Output  
Minimum Heat Output  
(Btu/h) x (1000)  
189.4  
250.1  
318.0  
1189.1  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
50.0  
170.6  
38.9  
132.7  
35.0  
119.4  
47.4  
161.7  
66.0  
225.2  
51.3  
175.0  
46.2  
157.6  
61.2  
208.8  
84.0  
286.6  
65.2  
222.5  
58.8  
200.6  
78.4  
267.5  
314.0  
1071.4  
244.0  
832.5  
219.8  
750.0  
293.4  
1001.1  
205  
699  
(kW)  
(Btu/h) x (1000)  
33  
113  
43  
147  
55  
188  
77  
263  
Pressure Switch Setting  
Flue Static Pressure  
Gas Connection  
(mbar)  
(mbar)  
(in)  
1.5  
-0.05  
1.0  
-0.30  
1.5  
-0.25  
2.0  
0.10  
2.5  
0.45  
-0.05  
-0.09  
-0.05  
-0.17  
1 1/4"  
3/4"  
Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min 17 mbar (6.8 in WG) Max 25 mbar (10 in WG)  
Main Burner Gas Pressure  
Min. Burner Gas Pressure  
Start Gas Pressure  
(mbar)  
(mbar)  
(mbar)  
4.9  
3.2  
NA  
5.3  
187  
2.4  
2.8  
NA  
7.0  
247  
3.3  
2.4  
NA  
8.9  
314  
4.1  
2.3  
1.1  
12.4  
438  
6.7  
3.7  
1.8  
15.4  
544  
5.2  
2.5  
0.6  
19.8  
699  
6.7  
3.4  
0.7  
23.1  
816  
8.0  
4.3  
0.9  
26.2  
925  
8.6  
5.4  
1.0  
33.2  
1172  
3
(m /h)  
Maximum Gas Rate  
Minimum Gas Rate  
3
(ft /h)  
3
(m /h)  
3.8  
134  
5.0  
177  
6.3  
222  
8.8  
311  
11.0  
388  
14.2  
501  
16.5  
583  
18.7  
660  
23.7  
837  
3
(ft /h)  
Start Gas Orifice  
(mm dia)  
NA  
NA  
NA  
7.0  
Burner Type  
Burner Head  
AZUR 60 BLU 120 BLU 120 BLU 170 BLU 250R BLU 250  
BLU 250  
S
BLU 250 BLU 350  
S
0.0  
20°  
33°  
0-1, 5  
S
S
S
15.0  
S
14  
18°  
32°  
S
S
S
Burner Head Setting  
Low Flame Air Orange Cam  
High Flame Air Red Cam  
Gas Valve Setting  
Valve Type Main Gas  
Valve Type Start Gas  
(mm)  
**  
**  
8.0  
13°  
40°  
0-1  
10.0  
22°  
80°  
T.O.  
22°  
35°  
25°  
30°  
30°  
0-1, 4  
55°  
60°  
MBDLE 407  
NA  
MBDLE 412  
S.I.T. 0 832 051  
LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 in WG) Min 25 mbar (10 in WG) Max 45 mbar (18 in WG)  
Main Burner Gas Pressure  
Min. Burner Gas Pressure  
Start Gas Pressure  
(mbar)  
(mbar)  
(mbar)  
4.3  
2.3  
NA  
2.09  
3.87  
5.7  
2.9  
NA  
2.76  
5.11  
4.7  
1.4  
NA  
3.51  
6.49  
3.1  
1.6  
1.1  
4.89  
9.05  
5.9  
2.0  
1.7  
6.10  
11.29  
5.3  
2.3  
0.6  
7.83  
14.49  
7.2  
2.5  
0.7  
9.11  
16.86  
9.0  
3.2  
0.7  
10.36  
19.18  
6.4  
2.0  
1.5  
13.12  
24.29  
3
(m /h)  
Maximum Gas Rate  
Minimum Gas Rate  
(kg/h)  
3
1.46  
2.71  
1.93  
3.58  
2.46  
4.55  
3.42  
6.34  
4.27  
7.90  
5.48  
10.15  
6.38  
11.80  
7.25  
13.42  
9.18  
17.00  
(m /h)  
(kg/h)  
Start Gas Orifice  
Main Gas Orifice  
(mm dia)  
(mm dia)  
NA  
8.5  
NA  
NA  
7.0  
10.0  
14.5  
NA  
Burner Type  
Burner Head  
AZUR 60 BLU 120 BLU 120 BLU 170 BLU 250R BLU 250  
BLU 250  
S
BLU 250 BLU 350  
S
0.0  
20°  
S
8.0  
13°  
S
S
15.0  
S
14  
18°  
32°  
S
S
S
Burner Head Setting  
Low Flame Air Orange Cam  
High Flame Air Red Cam  
Gas Valve Setting  
Valve Type Main Gas  
Valve Type Start Gas  
(mm)  
**  
**  
10.0  
22°  
80°  
T.O.  
22°  
35°  
25°  
33°  
40°  
30°  
30°  
55°  
60°  
0-1, 4  
0, 3-0, 9  
0-1, 1  
0-1, 4  
0-1, 5  
0-0, 85  
MBDLE 407  
NA  
MBDLE 412  
S.I.T. 0 832 051  
NOTE: The air setting is a guide only. The final setting is subject to combustion testing.  
When setting the minimum firing rate, a check must be made following the setting of the burner combustion. The  
check is made by running the heater on low fire for a minimum of 15 minutes at the full transport air rate and at typical  
ambient conditions. During the test, check that the flue gas temperature does not fall below 125° C. Should the flue  
gas temperature fall below 100° C, then the low fire gas setting must be increased to a value that will achieve 125° C  
flue gas temperature; otherwise condensation may form in the heat exchanger and flue, causing rapid corrosion and  
short operational life.  
NOTE: For adjustment of head setting, see Ecoflam Instructions.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
4.7 Technical Data - Ecoflam Oil-Fired Burners (burner reference "G")  
Model  
Gross Heat Input  
Heat Output  
015  
55.5  
189.4  
47.4  
161.8  
020  
73.3  
250.1  
61.2  
208.9  
030  
93.2  
318.0  
78.4  
267.4  
040  
129.9  
443.2  
110.2  
375.9  
050  
162.0  
552.7  
134.5  
458.8  
060  
208.0  
709.7  
177.7  
606.5  
070  
242.0  
825.7  
205.3  
700.3  
080  
275.2  
939.0  
230.4  
786.2  
0100  
348.5  
1189.1  
293.4  
1001.0  
(kW)  
(Btu/h) x (1000)  
(kW)  
(Btu/h) x (1000)  
Burner Type  
Minor 8  
Minor 12  
Minor 20  
Minor 30  
Major 30  
Oil Pump Connections  
(in)  
3/8  
Light Fuel Oil (Gas Oil) Data  
Nozzle Size  
Angle & Type  
Make  
Head Setting  
Air Setting  
*US (gal/h)  
1.00  
1.50  
1.75  
60S  
Danfoss  
14  
5.5  
12.4  
180  
2.50  
3
11.7  
170  
12.09  
2.66  
3.50  
4.00  
5.00  
5.00  
6.2  
13.0  
188  
25.62  
5.63  
7.00  
60A  
Delavan  
(mm)  
(number)  
(Bar)  
8
4.2  
12.1  
175  
5.17  
1.14  
0
8.5  
10.3  
150  
6.82  
1.50  
(full back)  
3.7  
11.0  
160  
19.36  
4.26  
(fixed)  
1.8  
11.0  
160  
32.44  
7.14  
4
10.0  
145  
15.08  
3.32  
4
10.0  
145  
22.53  
4.96  
Burner Fuel Pressure  
Fuel Consumption  
2
(lbf/in )  
(L/h)  
*UK (gal/h)  
8.68  
1.91  
Maximum Oil Pressure to  
Pump Inlet  
(Bar)  
.21  
3
2
(lbf/in )  
Kerosene Data  
Nozzle Size  
Angle & Type  
Make  
Head Setting  
Air Setting  
*US (gal/h)  
1.25  
1.75  
2.50  
3.00  
3
9.7  
140  
12.81  
2.82  
4.00  
5.00  
6.00  
4.5  
8.3  
120  
23.87  
5.25  
6.50  
6
9.3  
135  
27.14  
5.97  
8.50  
60B  
60S  
Danfoss  
(mm)  
(number)  
(Bar)  
8
4
8.6  
125  
5.47  
1.20  
0
6.6  
9.7  
140  
7.23  
1.59  
14  
6
8.3  
120  
9.19  
2.02  
(full back)  
3.7  
9.0  
130  
20.52  
4.51  
(fixed)  
1.4  
8.3  
120  
34.37  
7.56  
4
8.3  
120  
15.98  
3.51  
Burner Fuel Pressure  
Fuel Consumption  
2
(lbf/in )  
(L/h)  
*UK (gal/h)  
NOTE: For adjustment of head setting, see Ecoflam Instructions.  
* Nozzle sizes are quoted in US gal/h. Fuel consumption is quoted in imperial gal/h.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 5: HEATER INSTALLATION  
SECTION 5: HEATER INSTALLATION  
5.1 General  
should be placed on a firm, level, non-combustible  
surface that can support its weight. See Page 5,  
Section 4.1 for weight details.  
Heaters are designed for floor standing vertical  
installation. Special versions supplied with steel  
channels to support the heater are available and  
may be mounted horizontally. When installed  
horizontally, the heater will normally lie on its left  
side when viewed from the burner. The heater  
5.2 Handling  
All cabinet heaters are supplied secured to a  
wooden pallet and shrink wrapped. Use the pallet to  
support the heater during handling and installation.  
Figure 2: Typical Installation of a Gas Fired Cabinet Heater  
Flues up to 200 mm dia. are  
fitted with Bird Screens, over  
200 mm with a Rain Cap.  
1 m  
Minimum  
Lead Roof Plate  
Flue  
Air  
Distribution  
Heads  
Roof  
Building Ventilation  
Electric Supply  
Gas Isolating Valve  
Union  
Connection  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
Figure 3: Typical Installation of a Oil-Fired Cabinet Heater  
Flues up to 200 mm dia. are  
fitted with Bird Screens, over  
200 mm with a Rain Cap.  
1 m  
Minimum  
Lead Roof Plate  
Flue  
Air  
Distribution  
Heads  
Roof  
Fusible  
Link  
Gauge  
Vent Filler  
Building Ventilation  
Electric Supply  
Fuel  
Tank  
Fire Valve  
Gate Valve  
Plugged Drain Valve  
Manual Isolating Fuel Filter  
Valve  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 6: FLUE INSTALLATION  
SECTION 6: FLUE INSTALLATION  
6.1 Flue Installation  
Figure 6 through Page 14, Figure 9. The joints  
between the flue and the roof or wall must be  
properly sealed. If the flue passes through a wall or  
ceiling of combustible material it must be enclosed  
by a sleeve of non-combustible material and be  
separated from the sleeve by at least a 25 mm air  
gap.  
WARNING  
Fire Hazard  
Some objects will catch fire or explode when  
placed close to heater.  
Flues must be adequately supported so that the  
heater does not bear the weight of the flue.  
For straight and offset flue termination See Page 13,  
Figure 4 and Figure 5.  
Keep all flammable objects, liquids and  
vapours the required distance away from the  
heater.  
90° bends and horizontal pipe must not be used  
in flues except for the immediate connection to  
horizontally mounted heaters (1 m max). 135°  
bends are used to offset the flue as in Figure 5.  
If condensation is likely to occur in the flue, then  
provision should be made for drainage.  
Failure to follow these instructions can result  
in death, injury or property damage.  
Flues must be correctly sized for the model. See  
Page 5, Section 4.1. Flues should be assembled as  
on Page 13, Figure 4 and Figure 5 and Page 14,  
Figure 4: Flue Termination  
Figure 5: Offset Flues with 135° bends  
Flues up to 200 mm dia. are fitted  
with Bird Screens, over 200 mm  
with a Rain Cap.  
Minimum Total  
1m +  
(0.5m for each 135° bend) +  
(1m for each 0.33m of flue  
running in the 135° direction)  
1 m  
Minimum  
above roof  
*1 m  
Minimum  
1 m  
Minimum  
Nearby  
Structure  
Roof  
Use adequate  
*Less than  
2.5 m  
support to  
prevent heater  
from carrying  
the weight of  
the flue.  
Roof  
135°  
Use adequate  
support to  
prevent heater  
from carrying  
the weight of  
the flue.  
*If the point  
of roof  
intersection  
is within 2.5 m  
of a nearby  
structure, the  
flue must  
terminate  
at least  
1 m above  
that structure.  
Wall  
Wall  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
Figure 6: Guy Wire  
Figure 8: Flue and Roof Detail  
Screws,  
four typical.  
Over 2 m  
use Guy Wires  
Roof  
Clamp ring  
Rain Collar  
Roof Plate  
Heat Sealed  
Flash Band  
Wall  
Use adequate  
support to  
Secure Bolts  
prevent heater  
from carrying  
the weight of  
the flue.  
Stainless Steel  
Roof Tidy Plate  
Figure 7: Socket Direction  
Figure 9: Flue and Heater Spigot Joint Detail  
If it is necessary to cut any section of flue, the  
cut is made at the bottom of the lowest section  
where it connects to the heater.  
Masterflash  
Soaker Flashing  
or Rain Collar.  
Male spigot  
facing up.  
Screws  
Tidy  
Plate  
Fire  
Cement  
Heat  
Resistant  
Rope  
Heater  
Spigot  
Metal Sleeve  
Conversion Collar -  
last joint below  
the roof line.  
Clamp Ring  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 7: AIR SUPPLY  
SECTION 7: AIR SUPPLY  
7.1 Air Supply  
It is important to ensure adequate air supply at all  
times for both combustion and heating requirements  
in accordance with BS 6230 for UK installations and  
the latest revisions of applicable standards and local  
and national codes.  
The main fan requires a minimum free air return  
path of 1 m2 per 197 kW of heater output or 0.33 m2,  
whichever is greater.  
NOTE: When heaters are installed in the horizontal  
mode and connected to distribution ducting and/or  
inlet ducting, then the natural convected air flow  
through the heater, before the main fan turns on may  
be disrupted.  
7.2 Isolated Equipment Rooms  
Ventilation must prevent the temperature of isolated  
equipment room from exceeding 32°C as well as  
prevent any negative air pressure within the room.  
Any isolated equipment room containing air heaters  
will require permanent air vents direct to outside air  
in compliance with local codes.  
Where natural ventilation is used, suitable  
permanent openings at low and high levels,  
communicating directly with the outside air, must be  
provided.  
To ensure correct operation of the fan under these  
circumstances, in all COMBAT® cabinet heaters  
designed for horizontal mounting, the main fan will  
operate in conjunction with the burner sequence by  
the use of a time delay or direct acting relay.  
It is strongly recommended that when any heater is  
connected to installation ducting, a similar approach  
to the fan control is used. Any such control must be  
in parallel with the fan thermostat so that the fan  
"run on" feature is still able to operate (See Page 22,  
Section 9.5).  
Where mechanical ventilation is used, extract rate  
must be 5% - 10% less than the inlet rate. The  
mechanical ventilation must be interlocked with the  
burner on the heater.  
7.2.1 Heaters Installed Within the Heated Space  
Where the volume of the heated space is greater  
than 4.7 m3 per kilowatt of total rated heat input and  
the air change rate is at least 0.5/h, additional high  
and low level ventilation will not be required.  
For a building having an air change rate less than  
0.5/h, ventilation will be necessary in accordance  
with local and national codes.  
7.3 Building Ventilation  
Where ventilation is required, air must be taken from  
an outside point where it is not likely to be  
contaminated or obstructed.  
7.4 Distribution Ducting  
Duct should be full size for at least twice the minor  
dimension before change of direction or reduction of  
area.  
7.5 Return Air Ducting  
In installations employing recirculation or fresh air  
ducting, this ducting shall comply with the following:  
1. There shall be an unobstructed air path con-  
nected directly to the heater.  
2. The return air or fresh air shall be connected by  
ducting directly to the air inlet on the heater.  
3. Where automatic or manual dampers are pro-  
vided for operational adjustment in these ducts,  
they shall be proved in the correct position dur-  
ing the operation of the burner.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
SECTION 8: FUEL PIPING  
8.1 Connections  
Connect the heater to the gas supply, ensuring that  
WARNING  
the final connections are as follows:  
• Gas supply pipe is run in medium or heavy  
gauge tubing in compliance with local and  
national codes.  
• The gas supply pipe is adequately sized to carry  
the total volume of gas for the complete  
installation.  
Fire Hazard  
Connect gas supply according to Figure 10.  
Gas can leak if not installed properly.  
• An isolating valve and union connection should  
be used and fitted into the supply adjacent to the  
heater.  
Failure to follow these instructions can result in  
death, injury or property damage.  
IMPORTANT - The complete installation must be  
purged and tested for gas soundness in accordance  
with local and national codes.  
It is important that the gas supply pipe and the  
electrical connections do not support any of the  
heater’s weight.  
A gas meter is connected to the service pipe by the  
Gas Supply Company. Any existing meter should be  
checked, preferably by the company, to ensure that  
the meter is adequate for the rate of gas supply  
required.  
Installation pipes must be fitted in accordance with  
local and national codes. Pipe work from the meter  
to the heater(s) must be of adequate size. Pipes of  
smaller size than the heater inlet gas connection  
should not be used.  
Figure 10: Gas Connection  
Medium or Heavy  
Gauge Tubing  
Gas Connector  
Gas Isolating Valve  
Union  
Connection  
Drip Leg  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 8: FUEL PIPING  
8.2 Fuel Oil Supply  
8.2.4 B. M. Oil Lifter  
8.2.1 Fuel Storage Tank  
Where a gravity feed system cannot be used, a B.  
M. oil lifter may be used for small installations up to  
the equivalent of a single model 050 on minimum lift  
or a single model 020 on maximum lift.  
The fuel output from the oil lifter is gravity fed.  
The B. M. oil lifter requires a constant 230 V 50 Hz  
1 Ø electrical supply. The maximum pipe size to be  
used on the suction side is 1/4" ID, 5/16" OD (8  
mm). For maximum loading of oil lifters See Page 17,  
Figure 11. Consult the manufacturer’s information  
regarding the need to prime these devices.  
The fuel storage tank should be located outside the  
building as close as possible to the heater. The tank  
must be installed per local and national codes.  
8.2.2 Fuel Pipes  
The fuel pipes must be sized to ensure an adequate  
supply of oil to the entire installation. Galvanised  
pipe must not be used for oil installations. The fuel  
pipe must terminate at each heater with an isolating  
manual valve, a fire valve and a fuel filter. See Page  
12, Figure 3. The fusible link of the fire valve should  
be installed 100 mm (4 in) above the burner.  
The heater’s oil burner pump inlet is provided with a  
flexible oil line which should be used for the final  
connection. When making the final connection to the  
heater, do not block any of the removable panels of  
the heater. All COMBAT® oil-fired cabinet heaters are  
supplied with burner pumps fitted for one pipe  
systems.  
8.2.5 Pressurised Systems  
See Page 18, Figure 12. For larger installations, a  
pressurised system may be used. In this type of  
system the pump draws fuel from the tank, then  
pushes it through the installation under pressure.  
The pressure is controlled at the pump by a  
pressure relief valve at approximately 0.8 BAR (12  
psi). When a presurised system is used, a pressure  
reducing valve set at approximately 0.3 BAR (5 psi)  
should be installed on the fuel inlet to each heater  
after the manual isolating valve. This protects the oil  
pump from the danger of possible over pressure  
under fault conditions.  
8.2.3 Gravity Feed Systems  
The simplest installation is a gravity feed system.  
This system relies on the head of the fuel to push  
the fuel through the system. See Page 12, Figure 3.  
The electrical supply for the pump installation will  
depend upon the type of pumps chosen, but will  
normally be set to run continuously.  
Figure 11: B. M. Oil Lifter  
Total Suction Length in Feet  
8mm (5/16”) O.D. Copper Tube  
6
25  
5
4
3
2
1
0
20  
15  
10  
5
33’  
65’  
99’  
132’  
165’  
240 V  
0
Oil Lifter  
0
5
10 15 20 25  
Lift in Feet  
0 1 2 3 4 5 6 7  
Lift in Metres  
8
Oil  
Heater  
Air Vent  
Technical Data  
Filler Pipe  
Maximum Lift.............  
Maximum Capacity....  
Actual Capacity..........  
8 m  
20 L/h  
10 - 20 L/h  
Dependant upon vertical lift and suction  
line length.  
Storage Tank  
50 mm  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
Figure 12: Pressurised System Installation - Duplex System  
Pressure Gauge  
Relief Valve  
Check  
Check  
Valve  
Valve  
Stop  
Stop  
Valve  
Pressure  
Reducing  
Valve  
Valve  
No. 1  
Pump  
No. 2  
Pump  
For  
Fuel Tanks  
above  
Pump Set  
Stop  
Valve  
Stop  
Valve  
Burner  
Pressure  
Reducing  
Valve  
Duplex Pump Set  
Check  
Valve  
Burner  
Storage Tank  
Below Ground  
(The system shown has one pump for run and the  
other for standby. The valves allow the standby pump  
to be removed for maintenance while the system is still running).  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.1 Electrical Supply  
9.2.2 Positioning Room Thermostats or  
Roberts-Gordon Control  
A 230 V 50 Hz 1 Ø supply is required for all heater  
Models 015 to 030 connected to the heater terminals  
L1, N and Earth.  
A room thermostat or Roberts-Gordon control  
should be mounted on a wall or column at a height  
of approximately 1.5-1.8 metres from the floor to  
measure the ambient temperature. It should be clear  
of both cold draughts and the direct path of warm air  
from the heater.  
Standard models 040 to 0100 and all High Flow  
models require a 400 V 50 Hz 3 Ø and neutral  
supply connected to the heater terminals L1, L2, L3,  
N and Earth.  
9.2.3 Remote Frost Thermostat  
When required, connect to terminals 2 and 3 in the  
main terminal block.  
Locate the thermostat within the heated space  
adjacent to the most vulnerable equipment that  
requires protection.  
See Page 20, Section 9.3 through Page 27, Section  
9.10.  
All heaters and controls must be correctly earthed.  
All external wiring must comply with the relevant IEE  
and local regulations and be carried out by a  
qualified electrician.  
It is important that "L and N" polarity is correct for  
these heaters, as incorrect polarity may prevent the  
burner control box from operating properly. It is also  
important that the voltage between N and earth is at  
0 V and can never exceed 15 V.  
9.2.4 Controls for High/Low Burner Operation  
For heaters with a high/low burner, the controls will  
need to provide two stage signal to operate these  
burners. This is best provided by a two stage  
thermostat.  
The thermostat may control the heater outlet  
temperature if the heater is designed for a duct  
distribution system or the room temperature.  
The site wiring will be across terminals 2 and 3 for  
any time control and the on/off function of the burner  
(stage two), and across terminals 7 and 8 for the  
high fire (first stage) setting.  
An isolator with a contact separation of at least 3  
mm on all poles should be installed adjacent to the  
heater, but not attached to it, to disconnect all  
supplies to the heater and where necessary to  
isolate the remote control panel.  
The final connection to the heater should be made in  
metal sleeved flexible cable or flexible conduit to the  
main terminal block under the front lower panel of  
the heater using 1 sq. mm cable. Model 0100 and  
High Flow models with 5.5kW or 7.5kW motors use  
1.5 sq. mm cable. Cable entry is provided into the  
rear horizontal frame of the cabinet.  
The burner will then operate as follows:  
Temp. from cold up to  
the 1st set point..................... Full fire at max. rate  
Temp. above 1st set point  
WARNING  
up to 2nd set point.................Low fire at min. rate  
Temp. above 2nd set point ...............................Off.  
9.2.5 Controls for Fully Modulating Burners  
For heaters that incorporate a fully modulating  
burner, a special temperature control is provided  
with the heater. On-site wiring of the temperature  
sensor is required with any time control.  
The heater will normally be controlled by the  
temperature of the air in the outlet duct, but it is  
possible to control on room temperature.  
The position of the sensor in the outlet duct is  
determined on site. Using a themometer, select a  
position in the outlet duct approximately 1 m from  
the heater, across the cross section of the duct that  
provides a reasonable average of the temperatures  
found. Mount the sensor at this position for best  
results.  
Electrical Shock Hazard  
Disconnect electrical power before servicing.  
Failure to follow these instructions can result in  
death or electrical shock.  
9.2 Remote Controls  
The heater is designed to be operated by controls  
installed remotely from the heater. See Page 20,  
Section 9.3. through Page 27, Section 9.10.  
When operating at reduced heat input, the leaving  
air temperature may be low when controlled on room  
temperature.  
The time control and any other on/off controls will be  
across terminals 2 and 3. The sensor will be  
connected to terminals 8 and 9.  
9.2.1 Burner Controls (Thermostat)  
Controls to operate the burner must be voltage free  
contacts connected between terminals 2 & 3 of the  
main terminal block.  
The operation will occur in the following sequence:  
1. The burner will fire. When the burner sequence  
reaches the release to modulation stage, the  
control will begin to monitor the outlet  
temperature.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
2. The control will then adjust the burner input  
If a switch is required to turn on the main fan for  
continuously to attempt to maintain the  
temperature set on the control.  
ventilation, this must be voltage free, from external  
sources, and may be connected between terminals  
L1 & 1 for models 015 to 030 and terminals 2 & 1 for  
all other models.  
3. If the temperature continues to rise with the  
burner operating at minimum fire, the control  
will turn off the burner until the temperature falls  
again, and the burner will restart.  
9.3 CCH Wiring Diagram Gas Models 15-30 (floor standing)  
GAS BURNER 7 WAY PLUG  
PACKAGED  
BURNER  
Blue  
FAN / LIMIT STAT  
Red / White  
FAN  
LIMIT  
Note: Remote fan control  
carries full load of fan motor  
7 amp inductive  
TIME/TEMPERATURE  
CONTROLS  
4
3
2
Red / White  
10 A  
Red / White  
FAN CONTROL  
1
Brown  
Red  
L
1
L
2
MAIN  
FAN  
L
230 V 50 Hz  
1 PH SUPPLY  
3
MOTOR  
Blue  
N
Blue  
1 mm2 Ø Red Tri Rated Flex Cable  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with  
wiring material having a temperature  
rating of at least 105°C and 600 V.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.4 CCH Wiring Diagram Oil Models 15-30 (floor standing)  
OIL BURNER 6 WAY PLUG  
PACKAGED  
BURNER  
Blue  
FAN / LIMIT STAT  
Red / White  
FAN  
LIMIT  
Note: Remote fan control  
carries full load of fan motor  
7 amp inductive  
TIME/TEMPERATURE  
CONTROLS  
4
3
2
Red / White  
10 A  
Red / White  
FAN CONTROL  
1
Brown  
Red  
L
1
L
2
MAIN  
FAN  
L
230 V 50 Hz  
1 PH SUPPLY  
3
MOTOR  
Blue  
N
Blue  
1 mm2 Ø Red Tri Rated Flex Cable  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with  
wiring material having a temperature  
rating of at least 105°C and 600 V.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.5 CCH Wiring Diagram Gas Models 15-30 (horizontal mounting)  
GAS BURNER 7-WAY PLUG  
FOR GAS BURNER  
T1 IS NOT USED  
B4 = BURNER RUN TO R1 COIL  
ALL OTHER WIRES SAME AS OIL  
BURNER  
PACKAGED  
BURNER  
Blue  
LOCKOUT SIGNAL  
R1 COIL 240v  
LOCKOUT RESET SIGNAL  
OUTPUTS  
FROM  
BURNER  
7
2
BURNER RUN SIGNAL  
1
3
Red / White  
8
7
6
REMOTE LOCKOUT  
RESET  
N
5
FOR BURNERS WITH  
LANDIS & STEFA  
CONTROL BOX  
(GAS-FIRED)  
REMOTE LOCKOUT  
LAMP 230V  
FAN / LIMIT STAT  
Red / White  
LIMIT  
FAN  
4
3
2
Red / White  
10 A  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
1
FAN CONTROL  
(OPTIONAL)  
Brown  
L
1
Red  
1 mm2 Ø RED TRI RATED FLEX CABLE  
L
2
3
MAIN FAN  
MOTOR  
230 V 50 Hz  
1 PH SUPPLY  
L
Blue  
N
Blue  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with  
wiring material having a temperature  
rating of at least 105°C and 600 V.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.6 CCH Wiring Diagram Oil Models 15-30 (horizontal mounting)  
OIL BURNER 6-WAY PLUG  
PACKAGED  
BURNER  
Red / White  
Blue  
BURNER RUN SIGNAL  
R1 COIL 240v  
LOCKOUT RESET SIGNAL  
OUTPUTS  
FROM  
BURNER  
7
2
LOCKOUT SIGNAL  
1
3
8
7
6
REMOTE LOCKOUT  
RESET  
N
5
REMOTE LOCKOUT  
LAMP 230V  
FOR BURNERS WITH  
SATRONIC CONTROL BOX  
(OIL-FIRED)  
FAN / LIMIT STAT  
Red / White  
LIMIT  
FAN  
4
3
Red / White  
10 A  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
2
1
FAN CONTROL  
Brown  
(OPTIONAL)  
L
Red  
1
1 mm2 Ø RED TRI RATED FLEX CABLE  
L
2
MAIN FAN  
MOTOR  
230 V 50 Hz  
1 PH SUPPLY  
L
3
Blue  
N
Blue  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with wiring  
material having a temperature rating of  
at least 105°C and 600 V.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.7 CCH Wiring Diagram Gas Models 40-50 (floor standing)  
GAS BURNER 7-WAY PLUG  
FAN / LIMIT STAT  
PACKAGED  
BURNER  
LIMIT  
FAN  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
4
3
Red / White  
10 A  
Red / White  
2
1
FAN CONTROL  
Red  
L
CONTACTOR  
1
Red / White  
Red  
Red  
L
2
MAIN  
Black  
400 V 50 Hz  
FAN  
3 PH SUPPLY  
L
Brown  
Red  
3
MOTOR  
Grey  
C1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with wiring  
material having a temperature rating of  
at least 105°C and 600 V.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.8 CCH Wiring Diagram Oil Models 40-50 (floor standing)  
OIL BURNER 6-WAY PLUG  
FAN / LIMIT STAT  
PACKAGED  
BURNER  
LIMIT  
FAN  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
4
Red / White  
3
10 A  
Red / White  
2
1
FAN CONTROL  
Red  
L
CONTACTOR  
1
Red / White  
Red  
Red  
L
2
MAIN  
FAN  
Black  
400 V 50 Hz  
3 PH SUPPLY  
L
Brown  
Red  
3
MOTOR  
Grey  
C1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with  
the heater must be replaced with wiring  
material having a temperature rating of  
at least 105°C and 600 V.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.9 CCH Wiring Diagram Gas Models 40-50 (horizontal mounting)  
FOR GAS BURNER  
T1 IS NOT USED  
B4 = BURNER RUN TO R1 COIL  
ALL OTHER WIRES SAME AS OIL  
BURNER  
GAS BURNER 7-WAY PLUG  
PACKAGED  
BURNER  
LOCKOUT SIGNAL  
Red / White  
LOCKOUT RESET SIGNAL  
BURNER RUN SIGNAL  
OUTPUTS  
FROM  
BURNER  
R1 COIL 240v  
2
7
3
1
8
7
6
REMOTE LOCKOUT  
RESET  
N
5
FOR BURNERS WITH  
LANDIS & STEFA  
CONTROL BOX  
(GAS FIRED)  
REMOTE LOCKOUT  
LAMP 230V  
FAN / LIMIT STAT  
Red / White  
LIMIT  
FAN  
4
3
2
Red / White  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
FAN CONTROL  
(OPTIONAL)  
10 A  
1
Red  
L
1
CONTACTOR  
Red / White  
Red  
Red  
Red  
L
2
MAIN  
FAN  
400 V 50 Hz  
Black  
3 PH SUPPLY  
L
Brown  
Grey  
3
MOTOR  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.10 CCH Wiring Diagram Oil Models 40-50 (horizontal mounting)  
OIL BURNER 6-WAY PLUG  
PACKAGED  
Red / White  
BURNER  
BURNER RUN SIGNAL  
LOCKOUT RESET SIGNAL  
OUTPUTS  
FROM  
BURNER  
LOCKOUT SIGNAL  
R1 COIL 240v  
2
7
3
1
8
7
6
REMOTE LOCKOUT  
RESET  
FOR BURNERS WITH  
SATRONIC CONTROL BOX  
(OIL FIRED)  
REMOTE LOCKOUT  
LAMP 230V  
N
5
FAN / LIMIT STAT  
Red / White  
LIMIT  
FAN  
4
3
2
Red / White  
TIME/TEMPERATURE  
CONTROLS  
Red / White  
FAN CONTROL  
(OPTIONAL)  
10 A  
1
L
Red  
CONTACTOR  
1
Red / White  
Red  
Red  
Red  
L
2
MAIN  
FAN  
400 V 50 Hz  
3 PH SUPPLY  
Black  
L
Brown  
Grey  
3
MOTOR  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.11 CCH Wiring Diagram Gas Models 60-100 (floor standing)  
GAS BURNER 7-WAY PLUG  
FAN / LIMIT STAT  
PACKAGED  
BURNER  
LIMIT  
FAN  
TIME/TEMPERATURE  
Red / White  
4
3
CONTROLS  
Red / White  
10 A  
Red / White  
2
1
Red  
FAN CONTROL  
L
1
CONTACTOR  
Red / White  
Red  
Red  
L
2
MAIN  
400 V 50 Hz  
Black  
Brown  
Grey  
FAN  
3 PH SUPPLY  
L
Red  
3
MOTOR  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.12 CCH Wiring Diagram Oil Models 60-100 (floor standing)  
OIL BURNER 6-WAY PLUG  
FAN / LIMIT STAT  
PACKAGED  
BURNER  
LIMIT  
FAN  
TIME/TEMPERATURE  
4
CONTROLS  
Red / White  
Red / White  
3
10 A  
Red / White  
2
1
Red  
FAN CONTROL  
L
1
CONTACTOR  
Red / White  
Red  
Red  
L
2
MAIN  
400 V 50 Hz  
Black  
FAN  
3 PH SUPPLY  
L
Brown  
Red  
3
MOTOR  
Grey  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.13 CCH Wiring Diagram Gas Models 60-100 (horizontal mounting)  
FOR GAS BURNER  
T1 IS NOT USED  
B4 = BURNER RUN TO R1 COIL  
ALL OTHER WIRES SAME AS OIL  
BURNER  
GAS BURNER 7-WAY PLUG  
Red / White  
PACKAGED  
BURNER  
Blue  
LOCKOUT SIGNAL  
Blue  
LOCKOUT RESET SIGNAL  
OUTPUTS  
FROM  
BURNER  
Red / White  
R1 COIL 240v  
BURNER RUN SIGNAL  
7
2
Red / White  
3
1
8
7
REMOTE LOCKOUT  
RESET  
6
N
5
FOR BURNERS WITH  
REMOTE LOCKOUT  
LAMP 230 V  
LANDIS & STEFA  
CONTROL BOX  
(GAS-FIRED)  
FAN / LIMIT STAT  
Red / White  
FAN  
LIMIT  
4
3
2
Red / White  
TIME/TEMPERATURE  
CONTROLS  
10 A  
Red / White  
FAN CONTROL  
(OPTIONAL)  
1
Red  
L
1
CONTACTOR  
Red / White  
Red  
Red  
Red  
L
2
MAIN  
400 V 50 Hz  
3 PH SUPPLY  
Black  
FAN  
L
Brown  
3
MOTOR  
Grey  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 9: WIRING AND ELECTRICAL INFORMATION  
9.14 CCH Wiring Diagram Oil Models 60-100 (horizontal mounting)  
OIL BURNER 6-WAY PLUG  
Red / White  
PACKAGED  
BURNER  
Blue  
BURNER RUN SIGNAL  
Red / White  
LOCKOUT RESET SIGNAL  
OUTPUTS  
FROM  
BURNER  
R1 COIL 240v  
Red / White  
LOCKOUT SIGNAL  
7
2
Red / White  
3
1
8
7
6
REMOTE LOCKOUT  
RESET  
FOR BURNERS WITH  
SATRONIC CONTROL BOX  
(OIL-FIRED)  
REMOTE LOCKOUT  
LAMP 230V  
N
5
FAN / LIMIT STAT  
Red / White  
FAN  
LIMIT  
4
3
2
Red / White  
TIME/TEMPERATURE  
CONTROLS  
10 A  
Red / White  
FAN CONTROL  
(OPTIONAL)  
1
Red  
L
1
CONTACTOR  
Red / White  
Red  
Red  
Red  
L
2
MAIN  
400 V 50 Hz  
3 PH SUPPLY  
Black  
FAN  
L
Brown  
3
MOTOR  
Grey  
R1  
Blue  
N
Blue  
1 mm2 Ø RED TRI RATED FLEX CABLE  
MAIN TERMINALS  
IN CONTROL PANEL  
NOTE:  
Any of the original wire supplied with the  
heater must be replaced with wiring material  
having a temperature rating of at least 105°C  
and 600 V.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
9.15 Final Connections to Ecoflam HIGH/LOW or Modulating Burners (all models)  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 10: COMMISSIONING  
SECTION 10: COMMISSIONING  
Installation, service, commissioning and annual  
inspection of the heater must be done by a  
contractor qualified in the installation and service of  
gas or oil-fired heating equipment. Read this manual  
carefully before installation, commissioning,  
operation or service of this equipment.  
2. Check the correct fuse size is fitted in the local  
supply isolator. See Page 8, Section 4.4.  
10.1.3 Polarity Test - 1 Ø  
L
230v 50Hz AC  
V
WARNING  
0v  
N
V
(must be less than 15v)  
Supply  
Earth  
Terminal  
Electrical Shock Hazard  
Less Than  
0.1 ohm  
Use extreme caution while commissioning.  
Failure to follow these instructions can result in  
death or electrical shock.  
ohm  
10.1.4 Polarity Test - 3 Ø  
10.1 Pre-Commission Checks  
Voltage between each phase L1, L2 and L3 and  
Earth or Neutral should be approximately 230 V.  
Voltage between any 2 phases should be  
approximately 400 V. Test Neutral to Earth as single  
phase.  
All pre-commission checks must be carried out  
before lighting the heater.  
Ensure that the heater and all controls are suitable  
for the fuel, pressure and electrical supply to which  
they are to be connected.  
10.1.5 Fan Rotation Check  
10.1.1 Louvers  
Switch on the electricity supply at the isolator and  
the manual switch to "fan on" (if no remote fan switch  
is installed, press the white button on the fan/limit  
thermostat). On 3 Ø heaters, check the rotation of  
the main fan. Rotation should be clockwise looking  
at the drive end. If rotation is not correct, turn off the  
isolator and change over any two of the incoming  
supply phases and recheck. It will be necessary to  
remove the lower front or right side panel to see fan  
rotation.  
Where fitted, the air delivery louvers need to be set  
during commissioning to give the required air  
distribution.  
WARNING  
10.1.6 Fan Motor Overload Check  
On 3 Ø belt drive heaters, check the correct settings  
of the fan motor overload. This should be 0.2 A  
above the rated current on the heater data plate.  
See Page 8, Section 4.4.  
Cut Hazard  
Turn off fuel and electrical supply before maintenance.  
Fan can start automatically at any time.  
10.1.7 Mechanical Checks  
1. Check that the flue is installed in accordance  
with these instructions and local regulations.  
Failure to follow these instructions can result in severe  
injury or product damage.  
2. Check that the settings of the Combination Fan/  
Limit thermostat are correct - See Page 34,  
Figure 13.  
10.1.2 Electrical Checks  
All pre-commission checks must be carried out  
before commissioning the heater.  
1. Check that all site wiring is connected in  
accordance with the appropriate wiring dia-  
grams on Page 20, Section 9.3 through Page  
32, Section 9.15.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
Figure 13: Combination Thermostat (all models)  
See Page 34, Section 10.2.5 and repeat until  
the burner fires.  
Set Point 3  
10.2.4 Initial Setting  
Limit  
1 2 0  
Set to 110°C  
NOTE: Skip this step for models 015 to 030.  
Once firing, the start gas pressure should be set to  
the value given in the Data Tables for the burner  
type and the model concerned (see the burner  
reference letter on data plate). This is carried out by  
turning the governor adjusting screw (accessed  
under the black push-on cover) clockwise to  
increase pressure, or counter clockwise to decrease  
pressure.  
80  
60  
40  
C°  
20  
Set Point 1  
Fan Off  
Set to 38°C  
Set Point 2  
Fan On  
Set to 60-65°C  
10.2.5 Set Gas Rate  
10.2 Commissioning the Burner (gas heaters)  
1. Switch off and refit the main gas valve plug  
(removed earlier to allow the main gas valve to  
operate).  
High/Low and modulating burners have additional  
specific requirements. Follow the manufacturer’s  
instructions using the data provided on Page 8,  
Section 4.4 through Page 10, Section 4.7.  
2. Switch on again and allow the burner to fire and  
to settle for a few minutes.  
10.2.1 Gas Supply  
3. Adjust the main gas burner pressure to the  
value given in the relevant Data Table for the  
model concerned using the Main Gas Regula-  
tor (accessed under the swivel cover). See  
Page 37, Figure 17.  
All aspects of the gas installation, including the gas  
meter, must be inspected, tested for soundness and  
purged in accordance with local and national codes.  
Ensure that the air is fully purged from the heater  
inlet pipe up to the main gas valve inlet test nipple.  
10.2.2 Before Operating the Heater  
The results of setting the gas flow rate by using  
burner pressure only can lead to quite wide  
variations in heat input due to the nature of the  
burners used.  
Ensure the burner head, air damper and pressure  
switch settings are adjusted for the correct burner in  
accordance with the Data Tables on Page 8, Section  
4.4 through Page 10, Section 4.7 (see the burner  
reference letter on data plate).  
To ensure that all the controls are in safe working  
order, operate the heater for the first time with the  
isolating gas valve turned off.  
NOTE: If the correct burner pressure cannot be  
reached, then check the inlet pressure to the valve,  
with the burner firing. See Technical Data Tables on  
Page 8, Section 4.5 for inlet pressure requirements.  
1. Turn off the gas isolating valve  
Do not continue to adjust the regulator if the  
pressure is not changing.  
2. Using the installed external control, turn on the  
burner. The automatic sequence will now begin  
as described on Page 35, Figure 14.  
There will be no ignition of the burner and lockout  
will occur, which proves the controls are operating  
correctly.  
If the inlet pressure is too low to allow the correct  
burner pressure setting, then the gas inlet pressure  
must be corrected before completing the  
commissioning.  
10.2.6 Check Gas Rate  
10.2.3 Fire the Burner for Dungs Combination  
Gas Valves  
1. Open the gas isolating valve.  
It is important to check that the gas rate set during  
the commissioning is within 5% of the required  
flow rate.  
This may be achieved by checking the gas flow to  
the heater wherever possible by using the gas meter  
and timing the flow through the meter. The results  
should be compared with the required flow rate for  
the model given in the Data Tables, adjusting the  
burner pressure to correct for any error.  
Checking the gas rate must be carried out with all  
other appliances including any pilots, turned off.  
1. After burner pressure adjustment, allow the  
heater to operate for at least 15 minutes and  
then re-check settings.  
2. Connect a suitable pressure gauge to the  
burner pressure test point.  
3. On models 040 or larger, to ensure that start  
gas only may pass to the burner, remove the  
gas valve electrical plug for the main gas valve.  
4. Reset the lockout button of the control box and  
the burner should now fire. If lockout should  
occur when the start gas valve energises (or  
the main gas valve for models up to 030),  
repeat 3 or 4 times. If after several attempts the  
burner does not fire, then turn the start gas  
governor adjusting screw (or main gas gover-  
nor for models 015 to 030) 3 turns clockwise.  
2. Remove the manometer and refit all covers to  
the valve and tighten the screw of the outlet  
pressure tap.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 10: COMMISSIONING  
3. Check gas flow rate at gas meter.  
NOTE: If the pressure switch contacts (normally  
closed) are open, the heater will not start.  
10.3 Control - Gas-Fired Heaters  
For High/Low and modulating burners, follow the  
general sequence as described below and also  
have extra functional stages related to air damper  
positions. Refer to the burner manufacturers  
instructions for further detail. Gas burners have only  
one pressure switch, which is configured to cover  
combustion air and reaction to increases in  
combustion chamber pressure.  
2. The combustion air fan turns on and the pres-  
sure switch contacts close within the next 5  
seconds to indicate sufficient combustion air or  
lockout will occur.  
3. The sequence continues with a purge period  
with the burner fan running.  
4. The electrical ignition switches ON at the end  
of the purge period.  
10.3.1 Description of Gas-Fired Heater Control  
The gas fired burner fitted to all COMBAT® cabinet  
heaters is controlled by a full sequence plug-in  
control. This control ensures the safe start and stop  
sequence and also monitors the safe presence of a  
flame and burner air pressure.  
5. The start gas valve opens (main gas valve for  
015 - 030) and once a flame has been estab-  
lished, this remains open until close down. The  
flame probe is now continuously monitoring for  
the safe presence of flame.  
Models 015 - 030 are wired for direct ignition of the  
main flame. All other models are wired for ignition of  
a start gas flame as the first stage and then the main  
gas flame as the second stage.  
6. Five seconds later, the electric ignition turns off,  
leaving the start gas flame to be proved as sta-  
ble.  
10.3.2 Sequence of Operation  
1. With the external controls on calling for heat,  
and the pressure switch at rest, the burner fan  
will switch on after the control does a "self  
check".  
7. The start gas runs for ten seconds, then the  
main gas valve opens. The control is now in its  
normal run position  
Figure 14: Gas-Fired Heater Control Box Sequence  
Thermostat  
Motor  
Pressure Switch  
Transformer  
Gas Valve  
Ionization Probe  
+
30 s  
3 s  
+
2 s  
Necessary Input Signal  
Output Signal of the Device  
10.3.3 Motor Starter and Thermal Overload  
10.3.4 Burners  
On belt-driven models, the motor is controlled by a  
direct on-line contactor starter fitted with thermal  
overload protection. If the thermal overload  
operates, the main fan will not run. To reset, press  
the reset button on the overload unit.  
For details of the packaged burners, see the  
manufacturer’s instructions and Page 8, Section 4.5  
through Page 9, Section 4.6. When reading the data  
tables, ensure that the correct table for the burner  
and gas valve installed is being used. The data  
NOTE: For models with a 5.5 kW motor or larger, the tables are listed under a burner reference letter  
direct on-line starter will be replaced by a automatic which can be found on the heater data plate.  
starter.  
The overload should be set to indicate  
approximately 0.2 A above the normal running  
current of the heater. See Page 8, Section 4.4.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
Figure 15: Motor Starter (models 040 -100 and Thermal Overload (models 060 - 100)  
Wire Connecting  
Overload Switch to Coil  
Line Connections  
Contactor  
Load Connections  
Thermal  
Overload  
Overload  
Reset Button  
Overload  
Overload Scale  
Overload  
Connection (motor current amps) Adjusting Level  
Figure 16: Gas Train Circuit for Dungs Gas Valves (all models)  
Models 15 to 30 - All types of valve  
To Burner  
Models 40 to 100 - All types of valve  
Automatic  
To Burner  
Burner  
Flange  
Regulator  
Gas Valves  
1
1
Union  
Automatic  
Gas Valve &  
Regulator  
Automatic  
Gas Valve  
2
2
TP3  
TP3  
TP1  
TP2  
TP1  
TP2  
Gas  
Inlet  
Gas  
Inlet  
T
T
T
NOTE: Orifice plate  
fitted into union  
between valve and  
burner where required.  
1
Automatic  
Gas Valve &  
Regulator  
Automatic  
Gas Valve  
NOTE: Orifice plate  
fitted into union  
between valve and  
burner for models  
1
TP1 = Inlet Pressure  
TP2 = Pressure between Main Gas Valves  
TP3 = Valve Outlet Pressure  
40/50, and burner flange  
for models 60 and over.  
1 = Start Gas  
2 = Main Gas  
Burner Pressure TP on Burner  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 10: COMMISSIONING  
Figure 17: Dungs Gas Valve  
10.4 Gas Valves  
Dungs Combination Gas Valve  
All model 015 - 030 gas-fired burners operate as  
direct main flame ignition and have no separate start  
gas train. All other models operate with a first stage  
start gas flame supplied from a start gas train  
containing a start gas pressure regulator and two  
safety shut-off valves, for all gas types.  
appliances and need no further adjustment. When  
replacing a gas valve, ensure that this device is set  
in the fully open position by releasing the locking  
screw and turning the "V MAX" fully counter-  
clockwise towards the "+" and then retightening the  
locking screw.  
10.4.4 Rate of Opening  
The main gas is released at the second stage, and  
the combination main gas valve block contains a  
main burner pressure regulator and two safety shut-  
off valves, for all gas types. See Page 37, Figure 17.  
For high/low or modulating burners, the Dungs gas  
valve has extra features because it is an air/gas ratio  
control valve. Please refer to the manufacturer’s  
instructions for setting the controls.  
The slow opening adjustment can be seen on Page  
37, Figure 17. This device is a hydraulic damper  
which slows down the rate of opening of the second  
main gas valve to give a smooth main gas ignition.  
This is preset at the factory at the slowest setting  
and will need no further adjustment. If a new valve is  
fitted, then remove the plastic screw on top and with  
a small screwdriver turn the "V Start" screw fully  
clockwise towards the "-" and refit the plastic cover.  
10.4.1 Start Gas Valves  
10.5 Combustion Testing (all models)  
Where fitted, the start gas valve train is fitted with a  
pressure regulator and two start gas safety shut off  
valves. The start gas regulator is used to adjust the  
burner firing rate during the start gas phase of these  
models.  
Combustion quality must be tested to prove correct  
heater operation. Incorrect results will indicate faults  
with the installation or appliance.  
Combustion testing must be carried out with all  
covers in place. The flue gas is sampled in the flue,  
within 1 meter of the heater. The values of CO2  
should be between 9.5% and 10.0% for natural gas  
and 11% for LPG, depending upon the model.  
The CO will be up to 80 ppm (0.008%) dry, air free,  
depending upon the model. Temperature rise of the  
flue gases above ambient should be approximately  
160°C to 180°C. Seal the test hole in the flue after  
testing.  
To alter combustion performance, open/close the  
combustion air damper to reduce or increase these  
values. Once adjusted to the optimum combustion  
setting, lock the air damper into position. Repeat the  
steps in Section 10.2.6.  
10.4.2 Main Gas Valves  
See Page 37, Figure 17 for the position of the burner  
pressure regulator. This must be used to set the  
burner pressure indicated in the data tables in  
Section 4.  
For high/low or modulating burners, the Dungs gas  
valve has extra features because it is an air/gas ratio  
control valve. Please refer to the manufacturer’s  
instructions for setting the controls.  
10.4.3 Throughput Adjuster  
These valves have a throughput adjuster fitted to the  
second main gas valve. See Page 37, Figure 17.  
This will be factory set at fully open on new  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
10.5.1 Pressure Switch  
10.6 Commissioning the Burner (Oil Heaters)  
Check all valves between the fuel tank and the  
heater are open, including the fire valve.  
WARNING  
Ensure that oil is available at the heater inlet and  
that the air has been vented from the fuel pipe  
installation. Vent the air by opening the bleed screw  
on top of the fuel filter. On pressurised systems,  
check that the installation is running at the correct  
pressure. B.M. oil lifters will need priming.  
10.6.1  
Electrical Shock Hazard  
Ensure that the burner head and air damper settings  
are adjusted for the correct burner and that the  
correct atomising nozzle is fitted. See Page 10,  
Section 4.7 and the burner reference number on the  
data plate.  
Use extreme caution while commissioning.  
Failure to follow these instructions can result in  
death or electrical shock.  
Setting of the pressure switch must only be  
carried out as part of a complete commission  
which includes combustion testing.  
10.6.2 Preparation for Burner Pressure Test  
Attach a pressure gauge 0-15 BAR (0 - 200 psi) to  
the burner pump pressure test port. (See  
manufacturer’s information). A test manifold gives  
you the facility for the connection of the pressure  
gauge and the venting of the pump.  
Remove the cover of the pressure switch. With the  
burner firing, turn the pressure switch dial to the  
setting indicated for that model and burner. See  
Page 8, Section 4.5 through Page 9, Section 4.6.  
10.7 Control - Oil-Fired Heaters  
For High/Low oil burners, follow the general  
sequence as described below and also have extra  
functional stages related to air damper positions.  
Refer to the burner manufacturer’s instructions for  
further detail.  
10.5.2 Complete the Commissioning  
Ensure that all covers are fitted correctly and all test  
points are properly sealed.  
10.7.1 Description of Oil Fired Heater Control  
10.5.3 High/Low and Modulating Burners  
The oil fired burners fitted to the heater are  
controlled by a fully automatic control and  
photoelectric flame monitor unit. This control  
ensures the safe start,  
ignition and stop sequence and also monitors the  
flame. If the flame should fail the control will go into  
"lockout". The button on ther front of the control will  
illuminate to indicate lockout. Press the button to  
reset the control to restart the burner firing cycle.  
After setting the minimum burner input and  
combustion, the following check must be made:  
Run the heater on low fire for a minimum of 15  
minutes. Check the flue gas temperature. If the flue  
gas temperature falls below 125° C, increase the low  
fire gas setting until the temperature reaches 125° C,  
otherwise condensation may form.  
Figure 18: Oil-Fired Heaters Control Box Sequence  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 10: COMMISSIONING  
10.7.2 Sequence of Operation  
The operating sequence is as follows:  
pump at the same time by loosening the pump vent  
port (pump must be running). If the burner goes into  
"lockout" before the pump has vented, wait one  
minute, then reset the control box and repeat 10.7.5  
until all the air has been vented from the pump and  
the burner fires.  
With the external controls on and calling for heat,  
the burner fan and electric ignition will switch on.  
After a combustion air purge of approximately twelve  
seconds, the oil solenoid valve will open and the  
burner will fire. After another five seconds, the  
electric ignition is turned off and the burner will go  
into its normal run position. The photo cell  
continuously monitors the safe presence of the  
flame. When the temperature control is satisfied, the  
control box will turn off all its outputs simultaneously  
and return to the rest position for the beginning of  
the next sequence.  
NOTE: The burner plug and socket may be used to  
turn off the burner during commissioning.  
10.7.6 Adjust Burner Oil Pressure  
Adjust the burner oil pressure to the value in the  
data table for the burner reference letter and burner  
manufacturer’s information for details of the burner  
oil pump. When completed, turn off burner and  
remove test gauge and refit plug.  
10.7.3 Fault Display Messages  
10.7.7 Set Combustion Air  
On burner failure, the red LED is permanently  
illuminated for a period of approximately 10  
seconds, followed by a brief “dark phase, then one  
of the following flash-codes will indicate the cause of  
the fault. See Table 1 and Table 2. This indication  
will repeat as long as the lockout reset button is not  
reset.  
The combustion air must be set. Measure the  
emissions in the flue at a point within one metre from  
the outlet of the heater and adjust for the highest  
carbon dioxide (CO2) levels obtainable, usually 10.5  
- 11.0%, while making little or no smoke (smoke  
number 0-1). The test must be carried out with all  
covers fitted and after the heater has been running  
for 15 minutes.  
Table 1: Fault Display  
Flash-Code Key Message  
10.7.8 Complete the Commissioning  
Flash-Code  
Pre-ignition  
tv1  
Safety Time  
tv2  
l l l l .  
Test the burner for correct start and stop operation  
several times. Check that all safety devices operate  
correctly. Inspect the heater for any oil leaks and  
repair where necessary.  
Short Pulse l  
l l .  
Long Pulse l  
Delay Time to Valve V2  
tv2  
Running  
Low Mains Voltage  
l l l .  
Short Pause .  
Long Pause _  
10.8 Turning Off the Heater (all models)  
l _  
l l l _  
Set the external controls to the “off” position and the  
main burner will stop. The fans will run until they are  
stopped automatically by the fan thermostat.  
Table 2: Error Diagnosis  
Do not use Electrical Isolator for control of  
heater. The Electrical Isolator will switch off the  
fan. The heat exchanger could be damaged. The  
Warranty will not cover damage to the heat  
exchanger if operated improperly.  
Error Message  
Flash-Code  
Possible Fault  
Within lockout safety time,  
no flame established.  
Stray light during monitor  
phase, detector may be  
faulty.  
Lockout  
l l l l l  
Stray Light  
l l l l l  
Flash-Code for Manual Lockout  
10.9 External Controls  
Manual/External  
Lockout  
l l l l l _ l l l l l  
External controls may include a time switch, room  
thermostat and frost thermostat. Operate each  
control to ensure that they function correctly. Set the  
time switch (if fitted) and room thermostat to the  
user’s requirements.  
10.7.4 Fault Conditions  
If at any stage during normal running the photo  
electric cell fails to detect the flame, the control will  
switch off and make an instant restart attempt. If the 10.10 Instruction to the User  
flame signal is still missing, “lockout” will occur.  
Explain the controls of the heater to the user,  
including how to turn it on and off, using the controls  
fitted on site.  
If the flame is not detected by the photo cell during a  
normal start, there will be no restart attempt and  
“lockout” will occur in approximately 17 seconds  
after the start.  
Give this manual to the user.  
If a flame is detected during the first 12 seconds  
(purge), the solenoid valve will not open and the  
control will “lockout. For the control sequence, see  
Page 38, Figure 18.  
Ensure that the user is shown and understands the  
importance of maintaining clearances to  
combustibles; the user instructions on Page 40,  
Section 11 through Page 41, Section 11.4; and all  
warnings defined in this manual.  
10.7.5 Switching On  
Turn on the heater with the external controls. (Heat  
ON). If the "Lockout Reset" button is illuminated,  
press to reset. The combustion air fan and electric  
ignition should work immediately. Vent the burner oil  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
SECTION 11: USER INSTRUCTIONS  
11.1 User Instructions  
to low fire. If the temperature rises to the second set  
point, the burner will turn off. The burner will come  
on again at either High or Low fire, depending on the  
thermostat set point.  
The COMBAT® Cabinet heaters are fully automatic  
and operate from the external controls fitted on site.  
The only user controls at the heater are the:  
Fan Run Button - See Page 40, Figure 20.  
Burner lockout reset button - See Page 41, Section  
11.2.2.  
Set the two stage thermostat to the desired  
temperature.  
Modulating Operation  
The on-site control for modulating burners is a  
temperature controller that provides a varying output  
signal dependant upon the ambient temperature to  
the control. The burner firing rate will continuously  
vary between the maximum and minimum setting. If  
the temperature rises with the firing rate set to the  
minimum, the burner will shut down. Set the  
operating temperature according to the instructions  
provided with the control.  
Limit thermostat reset button - See Page 40, Figure  
20.  
WARNING  
11.2 Common User Controls (all models)  
11.2.1 Combination Fan/Limit Thermostat  
The Combination Fan/Limit Thermostat is located at  
the top right side of the heater.  
Electrical Shock Hazard  
This control ensures the heater does not blow cold  
air in the normal heating cycle and protects the heat  
exchanger against overheating.  
Disconnect electrical power before servicing.  
Failure to follow these instructions can result in  
death or electrical shock.  
Figure 20: Fan/Limit Thermostat  
If the air flow is reduced due to power failure, the  
limit thermostat will cause the burner to lockout.  
11.1.1 Heater Operation  
When the heater has been switched on by the  
remote controls installed on site, the main burner will  
automatically turn on. The burner control will control  
the safe ignition of the flame. When the heat  
exchanger is sufficiently heated, the fan thermostat  
turns on the main fan(s).  
Red limit reset button  
(Press to reset)  
All heaters require a constant gas and electricity  
supply, which must not be interrupted during the  
normal operation of this heater.  
NOTE: The fan will come on during burner firing for  
horizontally mounted and high-flow heaters and  
modulating burners.  
White fan button  
Pull out for normal operation.  
Press in for constant fan.  
The combination fan/limit thermostat is preset  
during commissioning.  
See Page 8, Section 4.4 and Page 34, Figure 13.  
NOTE: To reset, the heat exchanger must be cool.  
Figure 19: Heater Operating Sequence  
ON  
CLOSE  
DOWN  
Description  
Combination Fan/Limit Thermostat  
Part Number  
THERMOSTAT  
CALL FOR  
HEAT  
K017A  
ON  
BURNER  
RUN  
ON  
2-3 MINUTES  
RUN ON  
FAN  
11.1.2 Heater Operation (high/low or modulating)  
The heater will operate as described in Section  
11.1.1 with these added features:  
High/Low Operation  
A second limit thermostat or a two-stage thermostat  
will be installed on site so that as the temperature  
reaches the first set point, the firing rate will reduce  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 11: USER INSTRUCTIONS  
11.4 Simple Fault Finding (all models)  
Some possible reasons for the heater not operating  
are:  
1. Gas supply not turned ON.  
2. Electricity supply not turned ON.  
3. The time and/or temperature controls are not  
ON.  
4. The Limit Thermostat may have operated. This  
may be caused by an interruption of the electri-  
cal supply or failure of the distribution fan.  
Explosion Hazard  
If control locks out, do not make more than 3  
attempts to restart the heater.  
5. The burner supply plug has been discon-  
nected.  
Dangerous fuel mixtures can build up.  
If the Limit Thermostat persistently operates, there  
is a fault which must be investigated by a contractor  
qualified in the installation and service of gas or oil-  
fired heating equipment.  
The fault must be traced and repaired by a  
registered installer or service engineer.  
Failure to follow these instructions can result in  
death, injury or property damage.  
NOTE: If the main fan runs continuously, the white  
button (Figure 20) may have been pressed in - make  
sure it is pulled out. Alternatively, if a remote fan  
switch is fitted it may be in the ON position.  
11.2.2 Burner Lockout Reset Button  
The red warning light built into the burner control  
box will illuminate when the control has gone to  
lockout. This may be caused by flame failure. Wait  
one minute then press the reset button.  
11.4.1 Simple Fault Finding (burner faults)  
If the burner fails to ignite for any reason, it will go to  
lockout. This will be indicated by the red light on the  
heater or at the remote indicator (if fitted).  
1. Press in and release the lockout reset button on  
the burner or, if fitted, the remote reset.  
11.3 Lighting Instructions (all models)  
11.3.1 To Turn On Heater  
1. Ensure that the electrical and gas supplies to  
the heater are on. Check that the on-site con-  
trols are “ON.  
Lockout should not occur during normal operation of  
the heater and indicates there is a fault condition  
which must be corrected.  
NOTE: The thermostat setting must be above the  
ambient temperature for the heater to operate.  
2. The automatic firing sequence will begin as  
described on Page 40, Figure 19. The heater  
will now operate automatically under the control  
of the on-site controls. Following long shut  
down periods, the control may go to lockout.  
See Page 41, Section 11.2.2.  
11.4.2 Simple Fault Finding (oil fired heaters)  
Make sure the appliance fuel valve is open and  
there is oil in the tank. If the fuel tank or lines have  
run dry, the fuel system will need to be vented. For  
venting oil-fired heaters, See Page 38, Section 10.6  
through Section 10.7.5.  
11.3.2 To Turn the Heater Off  
Set the installed remote controls to the “OFF”  
position or turn down the remote thermostat below  
the ambient temperature.  
The burner will turn off immediately.  
The fan will continue to run for a few minutes.  
To restart, turn the remote control to “ON".  
If the heater will remain off for a long period of time,  
when the main fan(s) have stopped, turn off the fuel  
supply valve and main electrical isolator. To restart  
open the fuel supply valve and follow the  
instructions in Section 11.3.1.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
FOR YOUR SAFETY  
If you smell gas:  
1. Open windows.  
2. DO NOT try to light any appliance.  
3. DO NOT use electrical switches.  
4. DO NOT use any telephone in  
your building.  
5. Leave the building.  
6. Immediately call your local gas  
supplier after leaving the building.  
Follow the gas supplier’s  
instructions.  
7. If you cannot reach your gas  
supplier, call the Fire Department.  
WARNING  
Fire Hazard  
Do not store or use petrol or other  
flammable vapours and liquids in the  
vicinity of this or any other appliance.  
Some objects will catch fire or explode  
when placed close to heater.  
Failure to follow these instructions can  
result in death, injury or property  
damage.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 12: SERVICING  
SECTION 12: SERVICING  
12.1 Servicing Instructions  
After commissioning, the heater will require  
maintenance to be carried out annually. If the heater  
is used in a dirty or dusty area, more frequent  
maintenance may be necessary.  
12.3 Fan/Motor Assembly Maintenance (all  
models)  
The main fan bearings are permanently sealed and  
do not need lubrication. Before cleaning, turn off fuel  
and electrical supply. Remove the heater side  
panels and use a small brush or duster to clean the  
fan blades from each side. Replace panels when  
done.  
Installation, Service and Annual Inspection of the  
heater must be done by a contractor qualified  
in the installation and service of gas or oil-fired  
heating equipment.  
Figure 21: Belt Tension  
8 mm to 10 mm  
WARNING  
Fan  
Pulley  
Motor  
Pulley  
Check the condition and tension of the drive belts.  
The condition is best inspected with the belts  
removed. Check for chaffing or lateral cracks.  
Replace belts as a matched pair as necessary.  
Do not over-tighten belts, as this may cause bearing  
damage.  
Cut Hazard  
Turn off fuel and electrical supply before maintenance.  
Fan can start automatically at any time.  
Failure to follow these instructions can result in severe  
injury or product damage.  
12.4 Heat Exchanger Maintenance  
Ensure that the front collector box is clean and that  
the turbulators fitted to the tubes are in good  
condition.  
Also inspect the joint between the heat exchanger  
and the flue to ensure that it is still sealed.  
NOTE 1: After any maintenance or repair work,  
always test fire the heater in accordance with the  
commissioning instructions on Page 33, Section 10  
through Page 39, Section 10.10 to ensure all safety  
systems are in working order before leaving the  
heater to operate. Minor faults may be traced by  
using the troubleshooting charts on Page 45,  
Section 14 through Page 50, Section 14.7.  
1. If maintenance is needed, remove the burner.  
See Page 51, Section 15.1.  
2. Remove the upper front panel.  
3. Remove the front cover of the heat exchanger.  
4. Remove and inspect the turbulators.  
NOTE 2: Check all fuel pipes and pipe joints to  
ensure there are no cracks or gas leaks. Any cracks  
in the pipes or pipe joints must be repaired.  
5. Clean out any deposits from flue ways and the  
combustion chamber, using a vacuum cleaner  
and brush. Inspect the combustion chamber  
and heat exchanger for damage or corrosion.  
NOTE 3: Inspect all suspended components and  
hardware. Insure that they are in good condition,  
properly tightened, and corrosion free.  
6. Any damage must be referred to  
Roberts-Gordon.  
12.2 Burner Maintenance  
1. See the manufacturer’s information for specific  
instructions.  
7. Replace components in reverse order to above  
- replacing gasket material and any damaged  
turbulators.  
2. Clean the fan (and fuel filters, when fitted).  
Inspect all components, including the flame  
monitoring and ignition system, and correct  
operation of fuel control valves.  
8. Inspect and repair any damage to the seal  
between the flue and the flue spigot.  
12.5 Thermal Insulation  
While the upper panels are removed for heat  
3. For oil-fired burners it is recommended that the  
atomising oil nozzle be replaced during the  
annual service.  
exchanger servicing, the thermal insulation fitted to  
all the upper panels must be inspected. Insulation  
should be sound, with the foil face in good condition.  
If any thermal insulation is in poor condition, then it  
must be replaced with new insulation material and  
suitably sealed at the edges with adhesive foil tape.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
SECTION 13: CONVERSION BETWEEN FUELS  
13.1 General  
All COMBAT® Cabinet heaters may be operated on  
fuel oil, natural gas or propane gas, depending on  
which burner type has been fitted. Any conversion  
between fuels must be done by a contractor  
qualified in the installation and service of gas or oil-  
fired heating equipment. Conversion must be carried  
out in accordance with the information provided to  
maintain compliance with the CE product  
certification.  
13.2 Burner Conversion  
Burners designed to operate on class D (35 sec)  
fuel oil (Gas Oil) may be converted to operate on  
kerosine (28 sec). This may shorten the life  
expectancy of the fuel pump and fuel train  
components.  
Burners designed to burn natural gas may be  
converted to burn LPG propane gas or vice versa.  
For details of the changes necessary, please  
contact Roberts-Gordon with the heater serial  
number and burner type or consult the burner  
manufacturer’s information.  
Heaters designed to burn fuel oil may only be  
converted to burn gas by replacing the complete  
burner.  
Heaters designed to burn gas may only be  
converted to burn fuel oil by replacing the complete  
burner.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 14: TROUBLESHOOTING  
SECTION 14: TROUBLESHOOTING  
14.1 General  
WARNING  
Explosion Hazard  
Installation must be done by a registered installer/  
contractor qualified in the installation and service of  
gas-fired heating equipment or your gas supplier.  
Failure to follow these instructions can result in death,  
injury or property damage.  
START  
Assuming fuel & electrical  
supplies are ON  
Is the 'lockout' button on the  
Check if the control fuse in  
the heater has blown.  
Repair or Replace.  
No  
Does the burner fire?  
No  
Yes  
burner alight?  
Yes  
No  
Test burner as in  
14.2 (oil-fired),  
14.3 (gas-fired).  
Check external controls are  
ON and the fuse in the  
burner is sound.  
Yes  
Press in the white button on  
Use 14.6 or 14.7 to test fan.  
Does the main fan run?  
No  
No  
fan/limit thermostat.  
Yes  
See Figure 13 to check  
thermostat settings.  
Replace fan/limit  
thermostat.  
No  
Yes  
Check main fan for blockage  
or belt tension and correct  
rotation.  
Does the burner stop after  
running for several minutes  
with controls still ON ?  
Yes  
Did burner 'lockout' ?  
No  
No  
Yes  
Check operation and setting  
of fan/limit thermostat. Repair  
or replace as necessary.  
Test burner as in  
14.2 (oil-fired),  
14.3 (gas-fired).  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown on Page 33, Section 10.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
14.2 Troubleshooting for Oil Burners (see manufacture’s instructions)  
WARNING  
Electrical Shock Hazard  
Do not touch ignition components.  
Voltage from ignition components is high.  
Failure to follow these instructions can  
result in death or electrical shock.  
START  
Assuming fuel & electrical  
supplies are ON  
Check if the control fuse in  
the heater has blown.  
Check supply to burner  
Check control box.  
Does the burner fire?  
No  
No  
No  
motor.  
Yes  
No  
Yes  
Repair or replace.  
Yes  
Does the burner control  
box 'lockout' before 15  
seconds?  
Disconnect photo cell  
and try again.  
Control box faulty.  
Repair or replace.  
Yes  
No  
Yes  
Use Section 14.4 to  
trace fault.  
No  
Check ignition electrodes are  
set as in the manufacturer's  
instructions, the fuel supply  
and nozzle.  
Does the burner control  
box 'lockout' after 15  
seconds?  
No  
Did the burner fire?  
Yes  
Yes  
No  
Use Section 14.4 to  
Check oil solenoid valve.  
trace fault.  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
For your safety and optimum heater performance,  
use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown  
on Page 33, Section 10.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 14: TROUBLESHOOTING  
14.3 Troubleshooting for Gas Burners (see manufacturer’s instructions)  
WARNING  
Electrical Shock Hazard  
Do not touch ignition components.  
Voltage from ignition components is high.  
START  
Assuming fuel & electrical  
supplies are ON.  
Failure to follow these instructions can  
result in death or electrical shock.  
Is the pressure switch  
at rest?  
(no contact open)  
See Section 10.5.1 for  
setting.  
Does the burner fan run?  
No  
No  
Yes  
Fault lies elsewhere.  
Yes  
Use Section 14.4 to check  
the flame  
Does the burner control  
box 'lockout' before 10  
seconds?  
Yes  
Yes  
monitoring system.  
No  
Check combustion air fan is  
clean. Check combustion  
chamber is clean and sound.  
Check flue is clean and  
Does the burner control  
box 'lockout' after 10  
seconds?  
Check settings  
pressure switches.  
No  
sound. Check joint between  
flue spigot and flue is sound.  
No  
Check ignition circuit, fuel  
supply and gas solenoid  
valves.  
Does the burner fire?  
No  
Yes  
No  
Yes  
Use Section 14.4 to check  
the flame  
Does 'lockout' occur?  
monitoring system.  
No  
Check main gas valves and  
Does main gas fire?  
wiring.  
Yes  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
14.4 Troubleshooting for Flame Supervision System  
The flame supervision system is different for gas-fired and oil-fired heaters but may be tested in a  
similar way.  
Gas-fired heaters use a rectification flame probe to monitor the flame.  
Oil-fired heaters use a photo sensitive cell to monitor the flame.  
To connect a suitable meter into the circuit to monitor the flame signal current, disconnect one of the  
wires to the monitor (there is only one for gas-fired).  
Connect a suitable DC ammeter between the terminal just disconnected and the wire taken from it.  
Should the meter read backwards, then reverse its connections.  
Readings should be approximately as follows(For further details see burner manufacturer’s  
instructions):  
Oil-Fired  
Gas-Fired  
Maximum flame Minimum flame Maximum flame Minimum flame  
current with no  
flame  
current with  
flame  
current with no  
flame  
current with  
flame  
12 μ Amp  
25 μ Amp  
0.5 μ Amp  
1.0 μ Amp  
START  
Connect a DC ammeter in  
series with the flame monitor.  
Turn on all controls and  
ensure supply to burner  
OIL-FIRED  
Is there a stray light entering  
the burner or is there a  
flame?  
Is there a current flowing  
in excess of the max.  
value for NO flame?  
Repair or replace.  
Yes  
Yes  
GAS-FIRED  
Inspect and test the flame  
probe and wiring for a short  
circuit to earth.  
No  
OIL-FIRED  
Clean or replace photo  
electric cell as necessary.  
GAS-FIRED  
Does 'lockout' occur when  
a flame is present?  
Replace flame probe.  
Check for it's correct position.  
Check wiring to flame probe.  
Check burner earth  
connection.  
No  
Control box faulty.  
Replace with correct type.  
'Lockout' still occurs?  
Yes  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Heater Operating  
TROUBLESHOOT ENDS.  
No  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.5 Troubleshooting for Solenoid Valves Circuit  
START  
Is there pressure on the  
outlet of the valve when the  
valve should be closed?  
Is there an electrical supply  
to the valve terminals?  
Fault lies elsewhere.  
Investigate and correct.  
Yes  
Yes  
No  
Valve faulty.  
Replace with correct type.  
No  
Is there an electrical supply  
to the valve terminals?  
Fault lies elsewhere.  
Investigate and correct.  
Does valve open at the  
Yes  
No  
correct time?  
No  
Valve faulty.  
Replace with correct type.  
Yes  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Valve Operating  
TROUBLESHOOT ENDS.  
No  
14.6 Troubleshooting for Main Fan Circuit (1 Ø)  
START  
Main fan will not operate  
following warm up  
period of heat exchanger.  
Press in white button  
of fan/limit thermostat  
Re check supply to  
terminals L1 to N.  
Fault lies elsewhere.  
No  
No  
No  
and retest.  
Check for 230 V  
at terminals 1 to N.  
Yes  
Yes  
Check the setting of the  
fan thermostat as in  
Figure 13.  
Check calibration of the  
fan thermostat.  
The dial should indicate  
the approximate  
Yes  
temperature of the  
sampled air.  
No  
Fan thermostat faulty.  
Replace and reset.  
Yes  
Check and test wiring to  
motor. Does the motor run  
now?  
Motor faulty.  
Replace complete fan unit.  
No  
Yes  
No  
Yes  
Thermal overload in motor  
is faulty.  
Replace complete fan unit.  
Motor stops after running  
some time.  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Motor running.  
TROUBLESHOOT ENDS.  
For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as shown on Page 33, Section 10.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14.7 Troubleshooting for Main Fan (3 Ø)  
START  
Main fan will not operate  
following warm up  
period of heat exchanger.  
Check for 400 V three phase  
No  
Fault lies elsewhere.  
supply at main terminals.  
Yes  
Press in white button  
of fan/limit thermostat  
and retest.  
Check for 230 V at terminals  
No  
Fault lies elsewhere.  
No  
1 to N  
Yes  
Check the setting of the  
fan thermostat as in  
Section 5.1.  
Check calibration of the  
fan thermostat.  
The dial should indicate  
the approximate  
Yes  
temperature of the  
sampled air.  
No  
Fan thermostat faulty.  
Replace and reset.  
Yes  
Reset thermal overload  
and check setting. See  
page 28, Section 10.1.6.  
Check for 230 V at coil  
No  
terminals  
of fan contactor.  
Check for 400 V three phase  
at input and output of  
contactor.  
Contactor or overload faulty.  
Replace as necessary.  
Does fan run now?  
No  
No  
Yes  
Check and test wiring to  
motor.  
Motor faulty.  
Replace complete fan unit.  
Yes  
Thermal overload in motor  
is faulty.  
Replace complete fan unit.  
(direct drive fans only)  
Motor stops after running  
Yes  
some time.  
No  
If problems persist, contact  
ROBERTS GORDON® at  
Tel: +44 (0)121 506 7709  
www.rg-inc.com  
Motor running.  
TROUBLESHOOT ENDS.  
No  
For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.  
Conduct Commissioning procedure as on Page 33, Section 10.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 15: REMOVAL AND REPLACEMENT PARTS  
SECTION 15: REMOVAL AND REPLACEMENT  
PARTS  
See warnings and notes on Page 43, Section 12  
before removing or replacing parts.  
a new fuse into the spring clips. To replace the  
holder, remove the fuse, pull off the two tag  
connectors from either end, and then unscrew the  
central screw. Reverse these instructions to refit.  
15.4 Combination Fan/Limit Thermostat  
15.1 Burner Components  
To gain access to the thermostat:  
1. Loosen the cover retaining screw (on top) and  
remove cover.  
To remove the burner from the heater:  
1. Unplug the burner electrical supply from the  
heater.  
2. Disconnect the electrical connections by push-  
ing in with a small screwdriver and pulling out  
the wiring. See Page 52, Figure 22.  
2. Isolate the fuel supply at the inlet manual valve  
and disconnect the inlet fuel pipe.  
3. Unscrew the nuts holding the burner mounting  
flange to the heater.  
3. Unscrew the conduit bush and the two screws  
and withdraw the unit from the cabinet.  
4. Remove the burner from the heater, retaining  
the gasket for reuse.  
For removal of burner components, follow the  
manufacturer’s instructions. To refit the burner,  
reverse the instructions above. Fit the gasket  
between the burner mounting flange and the heater.  
Use a new gasket if necessary.  
4. Reverse these instructions to refit. See Page  
34, Figure 13 to set the new thermostat.  
15.5 Main Fan Motor (3 Ø Belt Drive)  
1. Disconnect electrical connections at contactor  
and overloads. See Page 51, Section 15.2.  
2. For Star/Delta starters, there are six wires  
between the motor and the starter.  
15.2 Direct On-Line Main Fan Starter and  
Thermal Overload Unit (3 Ø)  
3. Remove the left lower side panel to access the  
motor.  
This assembly comprises two parts, the contactor  
and the overloads, which may be changed  
seperately.  
4. Unscrew the bolts securing the motor to the  
mounting bracket. Lift the motor out.  
15.2.1 The Contactor  
5. Reverse these instructions to refit, tensioning  
the belts as on Page 43, Figure 21 and ensur-  
ing the pulleys are aligned.  
To remove the contactor:  
1. Remove the overloads as on Page 51, Section  
15.2.2.  
6. For Star/Delta starters, pay specific attention to  
the six motor connections.  
2. Remove the line connections to the top of the  
contactor (noting the colour code) and the two  
coil connections at the top rear of the contactor.  
15.6 Main Fan Units  
3. Unscrew the fixing screws to remove the con-  
tactor from the panel.  
Depending on the model of the heater, the main fan  
unit will be direct drive (with integral motor) or belt  
drive. Models 060-100 are belt drive, double fan  
units. All the fans are secured to the base of the  
heater by four bolts per fan case, and to the fan tray  
by bolts through the outlet flange.  
4. Reverse these instructions to refit. Check rota-  
tion of the fan after working on the contactor.  
15.2.2 The Overloads (models 060 to 100)  
To remove the overloads:  
To gain access to the fans:  
1. Unscrew the motor connecting wires from their  
terminals at the bottom of the assembly. Note  
the colour code.  
1. Remove the lower side panels of the heater.  
For models 060-100 and High Flow models,  
remove the upper side panels of the same side  
and the vertical centre bar to allow the fans to  
slide out of the cabinet.  
2. Disconnect the overload circuit connections  
near the overload reset button.  
2. Disconnect the electrical connections. On  
direct drive units, these will be at the terminal  
block for single phase and at the contactor for  
three phase.  
3. Disconnect the overload fixing and connecting  
screws from the bottom of the contactor.  
4. Ensure that any replacement overload is of the  
correct rating and that it is reset correctly. See  
Page 33, Section 10.1.6.  
3. Remove the screws. The fan will pull out of the  
heater through the side.  
15.3 Control Circuit Fuse (10 or 5 A, 1-1/4" long  
sand filled)  
4. Reverse these instructions to refit, tensioning  
the belts as on Page 43, Figure 21.  
The control fuse is removed by grasping the centre  
and pulling it out of the spring clips. To replace, push  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL  
5. Check the correct rotation of the fan as on  
Page 33, Section 10.1.5.  
NOTE: The direct drive fan unit motor can only be  
replaced as a complete fan/motor assembly.  
Figure 22: Combination Fan/Limit Thermostat  
WARNING  
Fire Hazard  
Break-off link must be removed from replacement  
thermostat.  
Heat exchanger damage may result.  
Failure to follow these instructions can result in  
death, injury, property damage or product damage.  
Dial  
Set Point 3 Limit Temp.  
Set Point 2 Fan On  
Set Point 1 Fan Off  
Push Screwdriver in  
and hold to release  
Push in Lock  
Wire to Controlled Equipment  
Fan Terminals  
Limit Stat  
Manual  
Reset Button  
(Red)  
Manual Fan Switch  
(White)  
Pull out for normal operation.  
Push in for continuous fan.  
Limit Terminals  
ROBERTS GORDON®  
thermostats do not have a  
break-off link. Remove  
break-off link if thermostat  
was not provided by  
Roberts-Gordon.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION 16: PARTS LIST  
SECTION 16: PARTS LIST  
The following items are recommended as spares  
which may be required during routine service and  
replacement of the air heater. There is also a list of  
parts in the burner manufacturer’s manual which  
relates to the parts required for the packaged burner  
fitted to the heater.  
16.1 Spare Parts List  
Part No.  
A 025  
Description  
DDC 1220 Direct Drive Fan  
DDC 1500 Direct Drive Fan  
BDC 1500 Belt Drive Fan  
A49 Vee Belt  
1
-
1
-
1
-
-
1
-
-
1
-
-
-
-
-
-
-
A 029  
-
-
A 038  
-
-
-
1
2
1
1
1
-
1
2
1
1
1
-
1
2
1
1
1
-
1
2
1
1
-
A 136  
-
-
-
-
-
K 017  
Combination Fan/Limit Thermostat  
Motor Contactor  
1
-
1
-
1
-
1
-
1
-
D 004A  
D 020A  
D 024A  
Motor Overload 4.5/7.5 A  
Motor Overload 6-10 A  
-
-
-
-
-
-
-
-
-
-
1
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Attach this information to the wall near the ROBERTS GORDON®heater  
®
Read the Installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.  
OPERATING INSTRUCTIONS  
WARNING  
1. STOP! Read all safety instructions on this information sheet.  
2. Open the manual fuel valve in the heater supply line.  
3. Turn on electric power to the heater.  
4. Set the thermostat to desired setting (above ambient temperature).  
The automatic starting sequence begins.  
NOTE: Following long shutdown periods, the burner control may go  
to ‘LOCKOUT’ during the start sequence. Push the reset button to  
recommence firing. Contact service department if ‘LOCKOUT’  
continues (see manual for details).  
TO TURN OFF THE HEATER  
Fire Hazard  
1. Turn the thermostat/time switch to ‘OFF. The burner will turn off  
immediately, but fans will continue to cool theheat exchanger until  
the fan thermostat switches off.  
Some objects can catch fire or explode when placed  
close to heater.  
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,  
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER  
Keep all flammable objects, liquids and vapours the  
required clearances to combustibles away from heater.  
1. Set the thermostat to ‘OFF’ or the lowest setting.  
2. Turn off electric power to the heater.  
Failure to follow these instructions can result in death,  
injury or property damage.  
3. Turn off the manual fuel valve in the heater supply line.  
4. Call your registered installer/contractor qualified in the  
installation and service of gas or oil-fired heating equipment.  
Installation Clearances  
Clearances to Combustibles  
.6 m  
.6 m  
.6 m  
.6 m  
4 m  
.6 m  
Roberts-Gordon Europe Limited  
Unit A, Kings Hill Business Park  
Darlaston Road, Wednesbury  
West Midlands WS10 7SH UK  
Telephone: +44(0)121 506 7700  
Fax: +44(0)121 506 7701  
Telephone: 716.852.4400  
Fax: 716.852.0854  
Toll Free: 800.828.7450  
Roberts-Gordon, LLC  
1250 William Street  
P.O. Box 44  
Service Telephone: +44(0)121 506 7709  
Service Fax: +44(0)121 506 7702  
E-mail: uksales@rg-inc.com  
Buffalo, NY 14240-0044 USA  
E-mail: export@rg-inc.com  
Installation Code and Annual Inspections:  
All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and  
conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help  
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary,  
using only replacement parts sold and supplied by Roberts-Gordon.  
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.  
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives.  
Please contact us for any further information you may require, including the Installation, Commissioning, Operation and Service Manual.  
This product is not for residential use.  
© 2007 Roberts-Gordon, LLC  
www.rg-inc.com  
Printed in U.S.A.  
P/N 91040095  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Reebok Fitness Home Gym RBE09951 User Guide
Remington Electric Shaver R 510 User Guide
Roberts Radio Portable Stereo System CD9913 User Guide
Rotel Radio RT 850 User Guide
Russell Hobbs Cooktop RHGC1 User Guide
Samsung Clothes Dryer DV457 User Guide
Sanyo Computer Monitor 42LM5WPTC User Guide
Sanyo Projector PLC WL2500S User Guide
Seagate Computer Drive 100516226 User Guide
Sears Air Compressor 91915033 User Guide