®
CoRayVac
Custom Engineered,
Gas-Fired, Low-Intensity
Infrared Heating System
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
Design Manual
®
All designs must be installed in strict accordance with the CORAYVAC
Installation, Operation and Service Manual (P/N 127102NA).
Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
© 2009 Roberts-Gordon LLC
P/N 127500NA Rev D 05/09
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
SECTION 1: Concept ..............................................................1
SECTION 2: The CRV-Series System.....................................2
2.1 Safety...........................................................................2
2.2 Zero Regulator.............................................................2
2.3 Fuel Savings and Comfort ...........................................4
SECTION 3: Clearances to Combustibles.............................5
3.1 Required Clearances to Combustibles.........................5
SECTION 4: Sizing and Design Considerations...................9
4.1 Radiant Adjustment to Heat Loss ................................9
4.2 Radiant Height Adjustment Factor...............................9
4.3 Selecting the Burners ................................................ 10
4.4 Radiant Distribution ................................................... 10
SECTION 5: Flow Loading.................................................... 12
5.1 Radiant Branch Flow ................................................. 12
5.2 Pump Capacity .......................................................... 14
5.3 Tailpipe Flow.............................................................. 14
SECTION 6: Radiant Tube and Tailpipe............................... 15
6.1 Radiant Tube Length.................................................. 15
6.2 Tailpipe....................................................................... 15
6.3 Design Parameters .................................................... 16
6.4 CRV-Series Design Methods..................................... 16
6.5 Tailpipe Design Method ............................................. 18
SECTION 7: Example CRV-Series System Layouts............21
7.1 Example System Layout (Option 1)............................21
7.2 Example System Layout (Option 2)............................22
7.3 Example System Layout (Option 3)............................22
7.4 Example System Layout (Option 4)............................23
7.5 Example System Layout (Option 5)............................23
7.6 Example System Layout (Option 6)............................24
7.7 Example System Layout (Option 7, 8 and 9)...............25
SECTION 8: Control Methods ..............................................26
8.1 ROBERTS GORDON® System Control
(P/N 02770002) .........................................................26
8.2 ROBERTS GORDON® ULTRAVAC™..........................26
8.3 SPST Transformer Relay (P/N 90417600K)...............27
8.4 DPST Transformer Relay (P/N 90436300).................27
8.5 Pressure Switch .........................................................27
SECTION 9: Air Supply System ...........................................28
9.1 Pressurized................................................................28
9.2 Non-Pressurized ........................................................28
9.3 Outside Air System Design Requirements.................28
SECTION 10: ROBERTS GORDON® ULTRAVAC™ Design
Requirements.................................................31
SECTION 11: CRV-Series Equipment Specifications.........32
11.1 Burner and Burner Controls......................................32
11.2 Equipment ................................................................32
Roberts-Gordon LLC
© 2009
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon LLC.
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF FIGURES
Figure 1: Assembly Overview (Two Branch System Shown).....3
Figure 2: Standard Reflector .....................................................6
Figure 3: One Side Reflector.....................................................6
Figure 4: Two Side Reflectors ...................................................6
Figure 5: Universal Shield, Position 1 .......................................7
Figure 6: Universal Shield, Position 2 .......................................7
Figure 7: Universal Shield, Position 3 .......................................7
Figure 8: 2-Foot Deco Grille......................................................8
Figure 9: Barrier Shield.............................................................8
Figure 10: Protective Grille........................................................8
Figure 11: Radiant Distribution (Average Coverage)............... 11
Figure 12: Radiant Distribution (Increased Coverage) ............ 11
Figure 13: Radiant Distribution (Heavy Coverage).................. 11
Figure 14: Burner Flow Units .................................................. 13
Figure 15: Vacuum Loss Curve for 4" Shared Tailpipe...........14
Figure 16: Tube Length vs. Efficiency...................................... 16
Figure 17: Possible Damper Coupling Locations ....................20
Figure 18: Example System Layout (Option 1).......................21
Figure 19: Example System Layout (Option 2).......................22
Figure 20: Example System Layout (Option 3).......................22
Figure 21: Example System Layout (Option 4).......................23
Figure 22: Example System Layout (Option 5).......................23
Figure 23: Example System Layout (Option 6).......................24
Figure 24: Example System Layout (Option 7).......................24
Figure 25: Example System Layout (Option 8).......................24
Figure 26: Example System Layout (Option 9).......................25
Figure 27: Air Supply System Capacity by Duct Length and
Diameter................................................................28
Figure 28: Outside Air Blower.................................................29
Figure 29: Sample Layout for Pressurized Outside Air
Systems..................................................................30
LIST OF TABLES
Table 1: CORAYVAC® Design Parameters ............................12
Table 2: Pump Capacity..........................................................14
Table 3: Pump Exhaust Requirements...................................14
Table 4: Allowable Tailpipe Lengths.......................................17
Table 5: Operating Characteristics; Condensing or
Non-Condensing ......................................................18
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION1:CONCEPT
SECTION 1: CONCEPT
The concept of CRV-Series is easy to understand.
However, it means discarding old ideas because CRV-
Series is a different kind of heating system.
CRV-Series is a gas-fired, vacuum-operated, low-
intensity infrared heating system incorporating a pat-
ented incremental burner system.
Gas-Fired means it uses clean-burning Natural or
Propane gas.
Vacuum-Operated means that the pump draws all
the products of combustion through the system and
expels them outdoors.
Low-Intensity means the radiant surfaces of the
tubes do not glow red; instead they operate at a lower
temperature (less than 900° F or 482.2° C) and radiate
heat at lower intensity per square foot of radiating sur-
face. Area coverage is provided by long runs of 4" (10
cm) O.D. tubing which hang from the ceiling or roof
supports. Reflectors direct the radiant heat downward
to occupied areas.
Radiant refers to the heat radiated by the CRV-Series
system. Because this heat is in the form of infrared
rays, it does not directly heat the air. Instead, the rays
heat objects such as floors, people, walls, cars,
machines, tools, etc. The warm objects, in turn, heat
the air through convection.
Incremental Burner System means that several
burners can operate in-series and fire into the same
run of steel tube that carries the combustion gases
from upstream burners. Each of these burners in a
radiant branch may have different firing rates; also, the
space between burners may vary. This allows the
designer to match heat gain to heat loss for each area
of the building. Firing burners in-series provides higher
thermal and radiant efficiency.
In a properly designed low-intensity radiant system,
the occupants should be barely aware of the radiant
heat when the system is firing. They will feel little or no
change when the thermostat is satisfied and the sys-
tem is not firing. This combines with warm floors,
warm walls and draft-free operation to improve the
mean radiant temperature of the space. This is the key
to the exceptional comfort and fuel efficiency provided
by the CRV-Series system.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
SECTION 2: THE CRV-SERIES SYSTEM
A CRV-Series system consists of one pump, a control With CRV-Series, all equipment and controls are
system, and a number of burners, see Page 3, Figure C.S.A. design certified, both as individual parts and
1. It also includes an extended tube surface (4" (10
also as a complete heating system. Also, individual
cm) steel tubing) covered by highly efficient reflectors electrical component parts are listed as applicable.
to direct the radiant heat downward to the floor. The
tubing nearest the burners radiates with the most
intensity and is called radiant tube. This should be
located over areas with the greatest heat loss. The
rest of the tubing surface (located between the radiant
tube and the pump) radiates with less intensity and is
called tailpipe. This can be located in areas with
lower heat loss.
2.2 Zero Regulator
CRV-Series uses a 100% pre-mix burner with the input
dependent on system vacuum. With no vacuum, the
zero regulator prevents gas flow. When vacuum is
present, the burner fires and input increases as vac-
uum increases. As the input increases, the amount of
air also increases. Over the normal range of operating
vacuum, the gas/air ratio is essentially linear.
While it is important to locate radiant tubes over areas
with high heat loss, such as the perimeter of the build-
ing, it is not essential to cover all areas directly with
radiant heat. Center areas (away from external walls)
This unique and patented feature provides optimum
combustion conditions at all times. Combustion condi-
tions are unaffected by fluctuations in fuel pressure,
vacuum, dirty air filters, changes in atmospheric pres-
and other areas of low heat loss can be adequately
sure, wind velocity or other climate conditions.
heated without direct coverage as long as the input of
the system is adequate for the total building heat loss.
However, to achieve the highest degree of comfort and
fuel savings, it is recommended that the CRV-Series
system be located to provide as complete and even a
distribution as is practical. In addition, several different
reflector and shield configurations are available to
direct the radiant heat to or away from desired areas.
Page 3, Figure 1 illustrates the components of a typi-
cal CRV-Series system. The system shown is a four
burner system composed of two branches. A branch
consists of a single run of tubing, including an end
burner, followed by any burners downstream. A
branch ends at a tee or a cross (where other branches
connect). For a single branch system, the branch ends
at the pump.
2.1 Safety
Safety is a prime consideration of CRV-Series. First,
there is a pre-purge of the complete tube network prior
to flame ignition. Then, to ensure that there will be no
gas flow unless the pump is operating, a pressure
switch located at the pump must activate prior to igni-
tion. After the pressure switch has closed, there are
two valves in-series in each burner that must be ener-
gized, as well as a zero regulator. Additionally, slow
opening gas valves provide smooth ignition and
enhance reliability. Once the thermostat has been sat-
isfied, the burners turn off and the pump continues to
run for two minutes to purge the entire system of flue
gases.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 2: THE CRV-SERIES SYSTEM
FIGURE 1: Assembly Overview (Two Branch System Shown)
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
2.3 Fuel Savings and Comfort
Space heating can be accomplished with less input
capacity when a radiant heating system is utilized,
rather than with a conventional convective heating
system. Why is this so?
A conventional, convective heating system, such as a
unit heater or central furnace works by heating the air,
which then indirectly heats the area and
occupants. CRV-Series utilizes infrared energy to heat
objects, people and surfaces directly, not the air. The
warm objects and floor create a heat reservoir, which
then re-radiates to the surroundings and also heats
the air by convection.
The radiant energy received by the occupants, directly
from the heater or indirectly from the
surroundings via re-radiation, serves to increase the
mean radiant temperature (MRT) of the space. In a
manner similar to direct sunlight, the increased MRT
allows the occupant to perceive a comfort condition at
a reduced air temperature. The resulting reduced air
temperature within the space provides the
following fuel-saving advantages:
• Reduced stratification of air in the space.
• Reduced transmission heat loss due to lower tem-
perature inside than assumed design
condition.
• Reduced air change heat loss, to the extent that
exfiltration through cracks or openings near the
roof will be decreased because of decreased
stack effect.
• Decreases the actual degree days experienced.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3: CLEARANCES TO COMBUSTIBLES
SECTION 3: CLEARANCES TO COMBUSTIBLES
3.1 Required Clearances to Combustibles
• Hang heater in accordance to the minimum sus-
pension requirements.
Clearances are the required distances that combusti-
ble objects must be away from the heater to prevent
serious fire hazards. Combustibles are materials,
which may catch on fire and include common items
such as wood, paper, rubber, fabric, etc. Maintain
clearances to combustibles at all times for safety.
• If the radiant tubes must pass through the building
structure, be sure that adequate sleeving and fire
stop is installed to prevent scorching and/or fire
hazard.
Clearances for all heater models are located on the
burner assembly and on Page 6, Figure 3 through
Page 8, Figure 10 in this manual. Check the clear-
ances on each burner for the model heater being
installed to make sure the product is suitable for your
application and the clearances are maintained. Read
and follow the safety guidelines below:
WARNING
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this heater or any other appli-
ance.
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from heater.
•
The stated clearances to combustibles represents
a surface temperature of 90° F (32° C) above
room temperature. Building materials with a low
heat tolerance (such as plastics, vinyl siding, can-
vas, tri-ply, etc) may be subject to degradation at
lower temperatures. It is the installer’s responsibil-
ity to assure that adjacent materials are protected
from degradation.
Some objects will catch fire or explode when
placed close to heater.
Failure to follow these instructions can result
in death, injury or property damage.
• Maintain clearances from heat sensitive
equipment and workstations.
• Maintain clearances from vehicles parked below
the heater.
• Maintain clearances from swinging and overhead
doors, overhead cranes, vehicle lifts, partitions,
storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible
materials, signs must be posted to specify the
maximum permissible stacking height to maintain
required clearances from the heater to the com-
bustibles. Signs must be posted adjacent to the
heater thermostat. In the absence of a thermo-
stat, signs must be posted in a conspicuous loca-
tion.
• Consult local Fire Marshal, Fire Insurance Carrier
or other authorities for approval of proposed
installation when there is a possibility of exposure
to combustible airborne materials or vapors.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
FIGURE 2: STANDARD REFLECTOR
(inches)
(centimeters)
Model
A
4
4
4
4
4
4
4
4
B
20
20
20
20
36
36
36
36
C
D
A
B
C
D
CRV-B-2
48
48
48
48
60
60
60
60
20
20
20
20
36
36
36
36
11
11
11
11
11
11
11
11
51
51
51
51
92
92
92
92
122
122
122
122
153
153
153
153
51
51
51
51
92
92
92
92
A
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
B
D
C
.
FIGURE 3: ONE SIDE REFLECTOR
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
C
D
A
B
31
31
31
31
31
31
31
31
C
D
51
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
12
12
12
12
12
12
12
12
56
56
56
56
60
60
60
60
20
20
20
20
42
42
42
42
11
11
11
11
11
11
11
11
143
143
143
143
153
153
153
153
A
51
51
51
107
107
107
107
B
D
C
FIGURE 4: TWO SIDE REFLECTORS
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
C
D
A
B
31
31
31
31
31
31
31
31
C
D
A
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
12
12
12
12
12
12
12
12
56
56
56
56
60
60
60
60
12
12
12
12
12
12
12
12
11
11
11
11
11
11
11
11
143
143
143
143
153
153
153
153
31
31
31
31
31
31
31
31
B
D
C
6
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3: CLEARANCES TO COMBUSTIBLES
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
FIGURE 5: UNIVERSAL SHIELD, POSITION 1
(inches)
(centimeters)
Model
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
A
4
4
4
4
8
8
8
8
B
C
D
A
B
31
31
31
31
46
46
46
46
C
D
12
12
12
12
18
18
18
18
12
12
12
12
24
24
24
24
12
12
12
12
18
18
18
18
11
11
11
11
21
21
21
21
31
31
31
31
61
61
61
61
31
31
31
31
46
46
46
46
A
C
B
D
FIGURE 6: UNIVERSAL SHIELD, POSITION 2
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
C
D
A
B
61
61
61
61
92
92
92
92
C
D
CRV-B-2
24
24
24
24
36
36
36
36
48
48
48
48
48
48
48
48
24
24
24
24
36
36
36
36
11
11
11
11
11
11
11
11
122
122
122
122
122
122
122
122
61
61
61
61
92
92
92
92
A
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
B
D
C
FIGURE 7: UNIVERSAL SHIELD, POSITION 3
Model
(inches)
(centimeters)
A
4
4
4
4
8
8
8
8
B
C
D
A
B
31
31
31
31
31
31
31
31
C
D
77
CRV-B-2
12
12
12
12
12
12
12
12
56
56
56
56
60
60
60
60
30
30
30
30
42
42
42
42
11
11
11
11
21
21
21
21
143
143
143
143
153
153
153
153
A
CRV-B-4
CRV-B-6
CRV-B-8
77
77
77
B
D
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
107
107
107
107
C
7
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
FIGURE 8: 2-FOOT DECO GRILLE
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
C
D
A
B
31
31
31
31
46
46
46
46
C
D
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
12
12
12
12
18
18
18
18
48
48
48
48
56
56
56
56
12
12
12
12
18
18
18
18
11
11
11
11
11
11
11
11
122
122
122
122
143
143
143
143
31
31
31
31
46
46
46
46
A
C
B
D
FIGURE 9: BARRIER SHIELD
(inches)
(centimeters)
Model
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
A
4
B
12
12
12
12
C
12
12
12
12
D
A
11
11
11
11
B
31
31
31
31
C
31
31
31
31
D
31
31
31
31
12
12
12
12
A
4
4
4
B
D
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
C
FIGURE 10: PROTECTIVE GRILLE
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
C
D
A
B
51
51
51
51
92
92
92
92
C
D
A
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
20
20
20
20
36
36
36
36
48
48
48
48
60
60
60
60
20
20
20
20
36
36
36
36
11
11
11
11
11
11
11
11
122
122
122
122
153
153
153
153
51
51
51
51
92
92
92
92
C
B
D
8
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 4: SIZING AND DESIGN CONSIDERATIONS
SECTION 4: SIZING AND DESIGN CONSIDERATIONS
The building heat loss must be calculated in accor-
dance to accepted energy load calculation methods.
heating system. The ability of a radiant system to pro-
vide the advantages of these radiant effects rests
ASHRAE (American Society of Heating, Refrigeration largely with the ability of this system to establish a
and Air-Conditioning Engineers) offers in-depth infor-
reserve heat capacity in the floor. Without this reserve
mation that is useful in calculating energy loads. The
capacity, radiant comfort cannot be achieved. (The
CRV-Series system input is determined in concert with exception is station heating/spot heating applications
the required radiant adjustment to heat loss and height where sufficiently high levels of direct radiation are
adjustment factors.
received from the heater.) The height adjustment fac-
tor is a means to insure adequate floor level radiant
intensity to “charge” the floor heat reservoir.
4.1 Radiant Adjustment to Heat Loss
The practice of applying an adjustment factor to heat
loss calculations for radiant heating systems is well
known within the radiant heating industry, having been
used by manufacturers for over 25 years. A number of
studies have been conducted to identify the values of
the adjustment factor in the range of 0.8 to 0.85
depending on efficiency (higher efficiency uses lower
factor). This adjustment can be more thoroughly
understood when considering the following radiant
effect issues:
Proportionately larger wall surfaces also remove
energy from the floor to a larger degree, decreasing
the heat reservoir.
The increased input capacity recommended by a
height adjustment factor is not extraneous as com-
pared to the heat loss calculation. Rather, it is a real-
ization that in order to maintain radiant comfort
conditions (and the economic benefits), a minimum
radiant level must be maintained at the floor.
• Infrared energy heats objects, not the air.
It is recommended that an adjustment to the heat loss
of 1% per foot (3% per meter) for mounting heights
above 20' (6 m), be added up to 60' (18 m). Above this
height, additional correction overstates the BTU
requirement as determined by the heat loss.
• Lower ambient temperatures reduce the amount
of air infiltration.
• Less air stratification with radiant heat.
• Lower ambient air temperatures reduce the trans-
mission heat loss through walls and roof.
EXAMPLE 1:
• Elevated floor temperature provides a thermal
reserve capacity.
Given a building with a calculated heat loss of
350,000 (Btu/h), what is the installed capacity
required of a CORAYVAC system mounted at
• Increased mean radiant temperature allows occu-
pants to perceive thermal comfort at the reduced
air temperature.
®
30' (9 m)?
®
CORAYVAC Installed Capacity = Heat Loss x
Each of these issues impacts favorably on the reduc-
tion of the installed capacity of the radiant heating sys-
tem. This fact, together with the realization that the
standard ASHRAE heat loss calculation methods
(particularly the transmission heat loss coefficients)
have been developed specifically for conventional hot
air systems, demonstrates the need for the heat loss
adjustment factor.
Radiant Adjustment x Height Adjustment
®
For CORAYVAC systems, a .80 radiant adjust-
ment factor is used.
The height adjustment is 1% per foot over 20'
(3% per meter over 6 meters), or 1.10.
®
∴CORAYVAC Installed Capacity = 350,000
(Btu/h) x .80 x 1.10 = 308,000 (Btu/h)
• In general, a .80 adjustment factor should be
used for CRV-Series systems.
A 12% reduction in installed capacity vs. a
conventional heating system.
4.2 Radiant Height Adjustment Factor
As discussed above, the installed input capacity of
radiant heating systems is typically reduced as com-
pared to the calculated heat loss due to the radiant
effects associated with a properly designed radiant
9
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
EXAMPLE 2:
calculated CRV-Series system required installed
capacity.
Given a building with a calculated heat loss
of 500,000 Btu/h, what is the installed capac-
ity required of a CRV-Series system mounted
at 50' (15 m)?
4.4 Radiant Distribution
Radiant heat distribution at occupant level must be
considered in the burner and design selection
process.
®
CORAYVAC Installed Capacity = Heat Loss x
Distribution of heat between radiant branches at floor
level is more critical at the perimeter of buildings. This
is where the heat loss is highest. Therefore, it may be
possible to combine different applications of distribu-
tion within the same building. The following figures
show three different applications of rules to determine
distribution.
Radiant Adjustment x Height Adjustment.
®
For CORAYVAC systems, a .80 radiant adjust-
ment factor is used.
The height adjustment is 1% per foot over 20'
(3% per meter over 6 meters), or 1.30.
®
∴ CORAYVAC Installed Capacity = 500,000
(Btu/h) x .80 x 1.30 = 520,000 (Btu/h).
4.4.1 Radiant Distribution (Average Coverage)
The aim of this distribution is to provide average or
lighter than average radiant intensity and works well
for general building heating. See Page 11, Figure 11.
The distance between radiant branches can vary
between 2.5 to 4 (or more) times the mounting height.
Note in Example 2, if equipment had been convention-
ally sized based on thermal output only, a nearly iden-
tical input requirement would result. For mounting
heights above 60' (18 m), no further correction is gen-
erally necessary if the floor level radiant intensity is
sufficient to establish a reserve capacity (hence, radi-
ant comfort), and the heat loss
This distribution is commonly used in applications
such as warehouses and lower heat loss areas of a
building.
Lighter coverage can be used in areas where occu-
pant traffic is low.
requirement is satisfied based on thermal output.
Due to the complexity of installations with mounting
heights over 60' (18 m), it is advisable to contact Rob-
erts-Gordon for further information regarding the spe-
cific application.
4.4.2 Radiant Distribution (Increased Coverage)
The aim of this distribution is to provide continuous
radiant intensity. See Page 11, Figure 12. The
distance between radiant branches is about 2 times
the mounting height.
4.3 Selecting the Burners
The number of burners and input for each must be
specified in the design layout. The following
factors should be considered when selecting burner
input:
This distribution is commonly used in areas bordering
high heat loss areas or areas requiring increased radi-
ant intensity to achieve occupant comfort.
4.4.3 Radiant Distribution (Heavy Coverage)
• Heat gain and distribution required.
• Mounting height.
The aim of this distribution is to provide increased radi-
ant intensity in areas that range from sedentary work
to spot heating for loading docks. See Page 11, Figure
13. The y dimensions in the diagram is the height
above floor level where overlap of the radiant output
will occur.
• Flow loading restrictions.
• Length of radiant branches.
• Distance required between burners.
• Desired radiation intensity.
In practice, y = 6' (1.83 m) is commonly used in areas
where occupant comfort doing sedentary work is an
important factor. In loading bays, spot heating and
areas of high heat loss, the horizontal distance (x)
between branches can be as little as 0.5 times the
mounting height.
In general, lower burner inputs can be used for lower
mounting heights and where lower heat gains are
required. Higher burner inputs are used primarily with
higher mounting heights and where high heat gain is
required.
The number of burners required can be calculated by
dividing the input rating of the selected sizes into the
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 4: SIZING AND DESIGN CONSIDERATIONS
FIGURE 11: Radiant Distribution (Average Coverage)
H= mounting height
3 H
90°
H
FIGURE 12: Radiant Distribution (Increased Coverage)
H= mounting height
2 H
90°
H
FIGURE 13: Radiant Distribution (Heavy Coverage)
H= mounting height
y= height above the
floor level where
overlap of radiant
output will occur
x=2H-2y
x
H
90°
y
11
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
SECTION 5: FLOW LOADING
The patented CRV-Series burner system allows a
burners, the burner inlet flow consists the of the total of
number of burners to be installed in-series, in the
the end vent air plus the combustion gases from all
same radiant tube, resulting in a long, continuous radi- upstream burners.
ant emitting surface to give even heat distribution
The requirement for minimum burner inlet flow is met if
the total flow units entering the combustion chamber
To enable the burners to be correctly located within the meets or exceeds the minimum as shown on Page 12,
within the building.
system, to maintain system operating vacuum and
obtain design flue gas temperatures at the pump, the
design layout is based on a simplified flow principle
using a “flow unit.”
Table 1.
5.1 Radiant Branch Flow
The flow in a radiant branch consists of the end vent
flow units plus the flow units of combustion air from all
burners. Page 13, Figure 14 shows a representation
of flow units for various types of branches.
The flow unit is defined as the amount of fuel/air mix-
ture for a heat input of 10,000 (Btu/h). This corre-
sponds to a flow rate of 1.83 cfm at 65-70°F.
The limiting factor for maximum flow in the radiant sec-
tion has been determined experimentally in terms of
the maximum burner inlet flow units that can be toler-
ated without degradation of combustion characteris-
tics at the last downstream burner. If more than the
maximum number of burners are installed per radiant
branch, the vacuum loss across the additional burners
will increase appreciably.
For the purpose of design, flow units enter the CRV-
Series system in one of two ways:
• Through the burner.
• Through the end vent plate.
Flow units exit the system as spent products of com-
bustion via the pump.
The purpose of the end vent air is to dilute the hot
combustion gases at the burner, thereby promoting
uniform heating of the tube while avoiding excessive
heating of the combustion chamber.
This maximum flow in the radiant branch can be
expressed for each burner firing rate by either a maxi-
mum number of burners per branch or the maximum
number of flow units. See Page 12, Table 1.
For the end burner, the burner inlet flow consists of the
end vent air and combustion air. For all other
®
Table 1: CORAYVAC Design Parameters
Burner Model
B-2
B-4
40
4
B-6
60
6
B-8
80
8
B-9*
90
B-10 B-12A B-12
Input (Btu/h) x (1000)
Flow Units per Burner
20
2
100
10
110
12
120
12
9
Flow Units per End Vent
(minimum flow units entering combustion chamber)
6
10
15
20
15
20
20
20
Maximum Number of Burners per Branch
Maximum Number of Flow Units per Branch
Radiant Tube Length (average distance between burners)
Minimum (ft)
6
4
4
4
2
4
3
3
18
26
39
52
33
60
56
56
10
15
20
5
12.5
20
25
5
20
25
35
10
8
20
30
45
10
10
20
30
50
10
10
30
40
60
15
15
35
50
70
15
15
35
50
70
15
15
Recommended (ft)
Maximum (ft)
Minimum Distance from Burner to Downstream Elbow (ft)
Suggested Minimum mounting Height (ft)
8
8
* CRV B-9 requires first downstream tube from burner to be aluminized heat-treated.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 5: FLOW LOADING
FIGURE 14: Burner Flow Units
B-10 Burner #1
Total Flow
End Burner
Units
B-10 Burner #2
B-10 Burner #3
20 + 10 + 10 + 10
= 50 Flow Units
Downstream Burner
Downstream Burner
End Vent Air
+ 20 Flow Units
Combustion Gas
Combustion Gas
+ 10 Flow Units
+ 10 Flow Units
Combustion Gas
+ 10 Flow Units
Coupling
Burner 1
Burner 2
Burner 3
Burner #2
Flow Units
Burner Firing Rate
Burner #3 Total Flow
End Vent
Burner #1
Burner #
Btu/h
Flow Units
Units
Flow Units Flow Units
1
2
3
20,000
20,000
20,000
2
2
4
6
2
6
12
1
2
3
40,000
40,000
40,000
4
4
6
8
22
33
10
1
2
3
60,000
60,000
60,000
6
15
1
2
3
80,000
80,000
80,000
8
9
8
9
44
33
50
20
15
1
2
90,000
90,000
1
2
3
100,000
100,000
100,000
10
10
10
12
20
20
1
2
3
120,000 (or 110,000)
120,000 (or 110,000)
120,000 (or 110,000)
12
12
12
10
56
50
1
2
3
120,000
100,000
80,000
20
8
13
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
5.2 Pump Capacity
number of flow units carried in the tube.
The flow unit capacity of the pump is indicated on
Page 14, Table 2, as a function of installed altitude.
When the CRV-Series system is designed in accor-
dance with this set of instructions and is in proper
operating condition, a vacuum from 2-3" w.c. will be
obtainable at each end vent (i.e. at all burners).
See Figure 15. Readings for length and flow when
plotted on the graph must fall on OK side to avoid
excessive vacuum losses.
FIGURE 15: Vacuum Loss Curve for 4" Shared
Tailpipe
130
120
100
Table 2: Pump Capacity
Installed Altitude
Maximum Flow Units
EP-200 EP-300
Feet Above
Sea Level
Meters Above
Sea Level
EP-100
Series
112
105
100
95
Series
224
215
206
197
188
180
170
161
NOT OK
90
0 m - 609 m
66
63
60
57
54
51
48
45
0' - 2000'
610 m - 914 m
2001' - 3000'
3001' - 4000'
4001' - 5000'
5001' - 6000'
6001' - 7000'
7001' - 8000'
8001' - 9000'
80
915 m - 1219 m
1220 m - 1524 m
1525 m - 1828 m
1829 m - 2134 m
2135 m - 2438 m
2439 m - 2743 m
70
OK
SIDE
60
90
84
50
40
30
20
10
80
75
There are a number of design requirements which, if
not met, will reduce the vacuum obtainable and
thereby the effective flow capacity of the pump. These
include:
30 40 50 60 70
90 100 110 120
80
Maximum Flow Units per Single Tailpipe Section
NOTE: For 6" (15 m) tailpipe, length is limited to a
maximum of 100’ (30 m). See Page 16, Section 6.3
for more details.
Lengths shown include allowance for 1 elbow every
50' (15 m); deduct 15% of length for each additional
elbow used per 50' (15 m) length.
• Minimum Length of Tailpipe - If less than the
minimum length of tailpipe is provided per radiant
branch, there will be insufficient cooling of the com-
bustion gases and improper operation of the pump.
• Line Loss Check for Tailpipe is applicable to
sections of tailpipe which are common to two or
more radiant branches (i.e. shared lengths). See
Page 14, Figure 15.
5.3.1 Pump Exhaust Length Requirements
The tube length on the exhaust side of the pump is
considered excessive if not within the following condi-
tions:
Table 3: Pump Exhaust Requirements
Pump Series Exhaust Tube Length Exhaust Tube Diameter
• Excessive back pressure on discharge line of
pump can be caused by partial blockage or too
much flow for length. See Section 5.3.1
EP-100
EP-100
EP-200
EP-200
EP-200
EP-300
EP-300
EP-300
Up to 25' (7.6 m)
Up to 50' (15 m)
Up to 10' (3 m)
Up to 25' (7.6 m)
Up to 50' (15 m)
Up to 10' (3 m)
Up to 25' (7.6 m)
Up to 50' (15 m)
4" 3 Elbows
5" 3 Elbows
4" 0 Elbows
5" 3 Elbows
6" 3 Elbows
6" 1 Elbows
7" 3 Elbows
8" 3 Elbows
• More than maximum number of burners or flow
units per radiant branch. See Page 14, Table 2.
• Excessive number of elbow or tee fittings
which increases vacuum loss.
5.3 Tailpipe Flow
Excessive flow loading in a single section of tailpipe
can cause low vacuum and lower effective pump
capacity. For the pump to develop the proper vacuum,
the length of tailpipe must not be excessive for the
14
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 6: RADIANT TUBE AND TAILPIPE
SECTION 6: RADIANT TUBE AND TAILPIPE
The main purpose of the tailpipe and the radiant tube Page 16, Figure 16 relates the effect on system ther-
is to provide sufficient tube surface to transfer the heat mal efficiency of variations in radiant and tailpipe
from the flue gases to the tube wall where it radiates
from the tube. Radiant tube is defined as the tubing
between burners firing in a radiant branch, plus the
radiant tubing immediately following the last down-
stream burner. Tailpipe is defined as all tubing
between the radiant tube and the pump.
lengths. The chart was created based on test data
obtained in accordance with methodology developed
by the National Bureau of Standards (NBSIR 80-2110)
and recommendations on flue loss calculation con-
tained in ANSI Z83.20/CSA 2.34 (latest edition).
Actual installation variables (gas BTU content, air tem-
perature and operation cycle, etc.) may effect efficien-
cies (positively or negatively). Page 16, Figure 16 is
presented as a guide to the designer for information
only.
Most of the radiant heat supplied by each burner is
released from the radiant tube; the balance is released
by the tailpipe. The placement of radiant tube to corre-
spond to areas of major heat loss is the key to provid-
ing uniform comfort levels. The use of adequate
tailpipe is the key to high combustion efficiency and
proper operation of the pump.
NOTE: When accounting for the required tailpipe
lengths during the design process, it is important to
verify that the tailpipe for each branch is at least equal
to the specified minimum.
6.1 Radiant Tube Length
The considerations in the selection of the length of
radiant tube include the following:
6.1.1 Minimum Radiant Tube Length
Provides for the highest level of intensity per length of
radiant tube and good radiant heat uniformity between
burners. More tailpipe length is required to maintain
operating efficiency and pump capacity.
6.1.2 Maximum Radiant Tube Length
Provides the lowest level of intensity per length of radi-
ant tube, and consequently the largest span between
burners. The radiant intensity will be reduced slightly
for the last 5'-10' (2-3 m) of radiant tube before the
next burner.
The length of radiant tube required varies according to
the burner input. Consideration has been given to the
use of a standard 10' (3 m) length of tube or lengths
that can be cut from same without waste. See Page
12, Table 1.
When positioning radiant tube to give the required
radiant distribution, it is important to consider:
• Clearances to combustible materials.
• Lighting equipment and other suspended objects.
6.2 Tailpipe
Tailpipe provides a low level of radiant intensity per
length. The length of tailpipe for systems can be varied
according to the flow units in the system and the
designed radiant length. Longer lengths of tailpipe will
attain higher operating efficiencies and therefore con-
densation will occur.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
FIGURE 16: Tube Length vs. Efficiency
3.0
2.5
2.0
1.5
1.0
83%
84%
85%
86%
87%
88%
89%
90%
Steady State Thermal Efficiency (%)
NOTE: Thermal efficiency values shown do not include the contribution due to condensing conditions when
operating in cyclic fashion. To estimate cyclic efficiencies, add 2-3% to the values obtained from the graph.
6.3 Design Parameters
in insufficient vacuum to burners.
When designing branches of 4 B-8 or larger burners
in-series, the following limitation to the pump capacity
applies:
6.4 CRV-Series Design Methods
1. Layout the system to suit the BTU input
required.
Pump Model Series Maximum Loading
2. Calculate the system design for each branch
EP-100:Not Allowed
individually.
EP-200:1 Branch of 4 burners
EP-300:2 Branches of 4 burners
3. Calculate the number of flow units per branch of
burners. Add the flow units for each branch
together to get the total system flow units. See
Page 12, Table 1 for the rules for each burner
model. See Page 13, Figure 14 for example flow
unit calculations.
For systems that are designed above 90% pump
capacity, the following limitations of shared tailpipe
apply:
• 4" (10 cm) tailpipe: limited to maximum of 2 com-
bined branches and length limited to maximum of
20' (6 m). See Page 14, Figure 15 for all other
tailpipe considerations.
Flow Units Per Branch
Branch 1
Branch 2
Branch 3
Branch 4
Branch 5
Branch 6
+
+
+
+
+
+
• 6" (15 cm) tailpipe limited to maximum of 4 com-
bined branches and length limited to maximum of
100' (30 m).
• When calculating required tailpipe length 1' (.3 m)
of 6" manifold tube is equivalent to 1.3' (.4 m) of 4"
tailpipe.
Total System
Flow Units =
Failure to comply with the above parameters will result
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 6: RADIANT TUBE AND TAILPIPE
4. Select pump model series for total system flow
units:
EP-100: up to 66 flow units
EP-200: up to 110 flow units
EP-300: up to 224 flow units
5. See Page 14, Table 2 for altitudes greater than
2000'.
6. For each branch, add the length of radiant tube
after each heater:
Radiant Tube Length
After Each Burner
Burner
1
2
3
4
5
6
+
+
+
+
+
+
Total Radiant Tube
Length in Branch =
Repeat this calculation for each branch in the
system.
7. Divide the total radiant tube length in the branch
by the number of burners in the branch to get
the average radiant length per burner.
Average Radiant
Length Per Burner =
Repeat this calculation for each branch in the
system.
8. Using the average radiant length per burner
(Calculated in Step 7) See Page 17, Table 4 to
select the allowable tailpipe lengths per flow
unit.
Table 4: Allowable Tailpipe Lengths
Burner Model
B-2
B-4
B-6
B-8
B-9
B-10
B-12/B-12A
Radiant Tube Length (average distance between burners)
Minimum (ft)
10
15
20
12.5
20
20
25
35
20
30
45
20
30
50
30
40
60
35
50
70
Recommended (ft)
Maximum (ft)
25
Tailpipe length per flow unit
Minimum (ft)*
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
1.2
1.5
2.5
1.7
Recommended (ft)
Maximum (ft)
Maximum (ft) for EP-100 only
*Minimum tailpipe lengths can only be used if radiant tube length is recommended or greater.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
EXAMPLE 3: B-10 Radiant Tube vs. Tailpipe Length
For a B-10 burner system of 200 flow units and an average of 40' radiant tube length per burner, See
Page 17, Table 4 for the tailpipe lengths per flow unit that can be used and the corresponding
operating characteristic.
From Table 4, we can use between 1.2' per flow unit and 2.5' per flow unit when the average radiant length
per B-10 burner is 40'. By multiplying the number of flow units in the system (200 flow units) by the mini-
mum tailpipe length from the chart (1.2' per flow unit), we see that we will need a minimum of 240' of tailpipe
for this system. Likewise, by multiplying the number of flow units in the system (200 flow units) by the maxi-
mum tailpipe length from the chart (2.5' per flow unit), we see that maximum system, tailpipe length is 500'.
Tailpipe length range for a B-10 burner system with 200 flow units and an average radiant tube length of 40’
is 240'-500'. The length of the tailpipe will determine whether the system is condensing or non-condensing.
Given a certain radiant tube length and tailpipe length, the operating characteristic can be determined
using Table 5.
Table 5: Operating Characteristics; Condensing or Non-Condensing
Tailpipe Length per Flow Unit
Minimum
Recommended 1.7 ft/flow unit
Maximum
Radiant Tube Length (average distance between burners)
Minimum
N/A
NC
NC
Borderline
C
Borderline
C
C
C
Recommended
C
C
Maximum
Borderline
N/A=Not Allowed NC=Non Condensing C=Condensing
6.5 Tailpipe Design Method
the section of tailpipe.
Given the overall length of tailpipe for the system, the
following section provides the method for ensuring the
design will function correctly.
If flow units entering a shared tailpipe system exceed
90% of pump capacity, the length of 4" diameter
tailpipe must not exceed 20'.
System with EP-300 Series Pump
Total tailpipe
' (includes 1 elbow / 50').
For shared tailpipe up to 115 flow units, 4" diameter
tailpipe can be used. See Page 14, Figure 15 for max-
imum permissible length of tailpipe for the number of
flow units entering the section of tailpipe.
6.5.1 Rule of Thumb Unshared Calculations
Total tailpipe - 10'
= Optimum unshared
Number of branches
tailpipe per branch
Select a pump discharge location and plan the route of
the tailpipe. For example system layouts See Page 21,
Figure 18 through Page 25, Figure 26 for different
pump and system efficiency requirements. If these lay-
outs are not suitable, it is necessary to customize the
layout for the CRV-Series system to the individual
building requirements.
Shared tailpipe greater than 115 flow units use 6"
diameter tube. Note that all tailpipe lengths for the pur-
poses of calculation are expressed in terms of 4"
diameter tube.
Effective length: 10' (3 m) of 6" (15 cm) diameter
tube = 13' (4 m) of 4" diameter tube.
6.5.3 To Calculate the Total System Tailpipe
For multiple branch systems, always plan to connect
the unshared tailpipe together as close to the pump as
possible for better system efficiency.
Total unshared tailpipe + shared 4" branch tailpipe +
effective length of shared 6".
6.5.4 To Check Performance Criteria
6.5.2 Shared Tailpipe Calculation
Total system tailpipe
= Tailpipe ft/flow unit
Total flow units
System with EP-100 or EP-200 Series Pump
See Page 14, Figure 15 for maximum permissible
Compare the results to Page 17, Table 4 and Page 18,
length of tailpipe for the number of flow units entering
18
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 6: RADIANT TUBE AND TAILPIPE
Table 5 for the burner model to ensure that the result-
ing tailpipe lengths maintain intended operating char-
acteristic.
6.5.5 Damper Couplings
Damper couplings are needed:
• In any tailpipe branch that carries less flow units
than other tailpipe branches connected to the
same pump
• In unsymmetrical layouts with branches having
the same number of flow units, the damper cou-
pling is placed in every branch except for the
longest branch.
The purpose of the damper coupling is to adjust the
end vent vacuum down to the desired level. These are
to be placed in the tailpipe section and not the radiant
branch. The recommended location is before the first
tee fitting or 10'-40' from the end of the radiant pipe.
See Page 20, Figure 17; Page 23, Figure 21, Page
24, Figure 25, and Page 25, Figure 26 for placement
examples.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
FIGURE 17: Possible Damper Coupling Locations
20
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: EXAMPLE CRV-SERIES SYSTEM LAYOUTS
SECTION 7: EXAMPLE CRV-SERIES SYSTEM LAYOUTS
Systems that are symmetrical are preferred because
the vacuum available in the system branches are bal-
anced as a function of design (damper couplings are
not needed).
FIGURE 18: Example System Layout (Option 1)
Where radiant tube lengths are variable in a single
branch, the average length shall be used to determine
the total radiant tube length. Tailpipe will begin after
the last radiant tube following the last burner in the
branch.
20'
(6 m)
20'
(6 m)
20'
(6 m)
CRV-Series is most effective when there are at least 3
burners in the radiant branch.
30'
(9 m)
To assist with the selection of burners and system
designs, the following figures show system layouts that
have been used extensively with CRV-Series since
1962. Designing systems using these layouts will
mean altering the dimensions to suit the individual
building.
30'
(9 m)
30'
(9 m)
Generally, shared tailpipe reduces the available sys-
tem vacuum. See Page 14, Section 5.3 for shared
tailpipe design rules.
10' (3 m)
LEGEND
7.1 Example System Layout (Option 1)
®
CORAYVAC
Burner
Six B10 burners at minimum radiant tube length and
2.5 ft/flow unit tailpipe, the recommended pump for
this system is an EP-200 Series pump.
Pump
This system provides maximum radiant intensity on
the left and right and adds supplemental radiant
effects through the center creating very even radiant
effects over the coverage area.
Damper
Radiant Tube
Layout to provide high system efficiency, condensed
radiant output and good uniformity of distribution.
Adjust the lengths as necessary for different input sys-
tems and to change the efficiency levels.
Tailpipe
6" Tailpipe
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
FIGURE 19: Example System Layout (Option 2)
FIGURE 20: Example System Layout (Option 3)
40'
(12 m)
40'
(12 m)
30'
(9 m)
10' (3 m)
40'
20' (6 m)
30'
(9 m)
(12 m)
30'
(9 m)
40'
(12 m)
40'
(12 m)
6" Tailpipe
50'
(15 m)
40'
(12 m)
40'
(12 m)
7.2 Example System Layout (Option 2)
Six B10 burners at recommended radiant tube length
and 1.2'/flow unit tailpipe, the recommended pump for
this system is an EP-200 Series pump.
Layout will minimize up front equipment cost of tubing
by implementing minimum tailpipe length.
Layout will exhibit minimum system efficiency. Adjust
the lengths as necessary for different input systems
and to increase the efficiency levels.
7.3 Example System Layout (Option 3)
Twelve B10 burners at minimum radiant tube length
and 1.56'/flow unit tailpipe, the pump for this system is
an EP-300 Series Pump.
All shared tailpipe is 6" diameter.
Layout will provide maximum radiant intensity
between burners.
Layout will exhibit minimum system efficiency. Adjust
the lengths as necessary for different input systems
and to increase the efficiency levels.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: EXAMPLE CRV-SERIES SYSTEM LAYOUTS
FIGURE 21: Example System Layout (Option 4)
FIGURE 22: Example System Layout (Option 5)
30'
(9 m)
40'
(12 m)
30'
(9 m)
40'
(12 m)
30'
(9 m)
40'
(12 m)
70'
(21 m)
30'
(9 m)
30'
(9 m)
40'
(12 m)
6" Tailpipe
30'
(9 m)
10'
(3 m)
7.4 Example System Layout (Option 4)
Nine B10 burners at recommended radiant tube length
and 1.58'/flow unit tailpipe, the pump for this system is
an EP-300 Series Pump.
All shared tailpipe is 6" diameter.
Layout will exhibit nominal system efficiency. Adjust
the lengths as necessary for different input systems
and to increase the efficiency levels.
7.5 Example System Layout (Option 5)
Six B10 burners at minimum radiant tube length and
1.5'/flow unit tailpipe, the pump for this system is an
EP-200 Series pump.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
Layout to provide minimum system efficiency. Adjust
the lengths as necessary for different input systems
and to increase the efficiency levels.
This layout method is often used effectively in heatloss
and perimeter heating applications.
FIGURE 24: Example System Layout (Option 7)
This system is generally accompanied by an addi-
tional system, as shown, so that the radiant output of
the additional system supplements the lack of radiant
intensity from the tailpipe of the first system. This lay-
out method is used in high heatloss and perimeter
heating applications.
30'
(9 m)
180'
(55 m)
30'
(9 m)
FIGURE 23: Example System Layout (Option 6)
10' (3 m)
negligible
30'
(9 m)
30'
(9 m)
30'
100'
(9 m)
(30 m)
30'
(9 m)
30'
(9 m)
10' (3 m)
FIGURE 25: Example System Layout (Option 8)
30'
(9 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
10' (3 m)
7.6 Example System Layout (Option 6)
10' (3 m)
Six B10 burners at minimum radiant tube length and
2.3'/flow unit tailpipe, the pump for this system is an
EP-200 Series pump.
30'
(9 m)
Layout to provide high system efficiency, condensed
radiant output and good uniformity of distribution.
Adjust the lengths as necessary for different input sys-
tems and to change the efficiency levels.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: EXAMPLE CRV-SERIES SYSTEM LAYOUTS
FIGURE 26: Example System Layout (Option 9)
Layout to provide condensed radiant output and good
uniformity of distribution. Layout will exhibit minimum
system efficiency.
30'
(9 m)
30'
(9 m)
10'
(3 m)
30'
(9 m)
10'
(3 m)
6"
Tailpipe
30'
(9 m)
30'
(9 m)
7.7 Example System Layout (Option 7, 8 and 9)
These systems are for B9 burners only, this burner is
specially rated for 2 burners in-series applications in
the systems shown.
Option 7 is a 180' (55 m) straight system connected to
an EP-100 pump.
Option 8 is a system connected to an EP-200 Series
pump.
Option 9 is a system connected to an EP-300 Series
pump.
These layouts show minimum allowed lengths. Addi-
tional tubing may be added. The distance between the
burners can be varied from 30' (9 m) to 20’ (6 m), but
the overall system lengths must remain the same.
Layout will minimize upfront equipment cost of tubing
by implementing special shortened minimum tailpipe
lengths.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
SECTION 8: CONTROL METHODS
Electronic 24 Vac thermostats and mechanical ther-
mostats with heat anticipator can be used. The sys-
tem control offers a 24 Vac power supply to power
electronic thermostats.
DANGER
Roberts-Gordon offers a selection of low voltage
thermostats approved for use with the system
control.
A System Control operated system has two minutes
post purge pump operation to completely exhaust
products of combustion from the system. A system
control provides indication of power to the pump and
zones and indicates the status of the pressure switch
with lights.
Electrical Shock Hazard
Disconnect electric before service or
maintenance.
More than one disconnect switch may be
required to disconnect electric to the unit.
The System Control is ETL listed in accordance with
UL873 – Standard for Temperature Indicating and
Regulating Equipment.
Control must be properly grounded to an
electrical source.
Failure to follow these instructions can
result in death or electrical shock.
®
™
8.2 ROBERTS GORDON ULTRAVAC
®
™
The ROBERTS GORDON ULTRAVAC is a micro
processor based control package designed for modu-
lating control of CRV-Series heaters based on outdoor
temperatures. The controls offer full modulation
between 60% and 100% of system maximum rated
input.
WARNING
This controller is capable of giving control outputs to
one pump and three heating zones. The controller
also features inputs which are used for indoor and out-
door signal condition monitoring.
Explosion Hazard
System status and settings are viewed and altered
Turn off gas supply to heater before service.
from a PC (not supplied) running ROBERTS GOR-
DON ULTRAVAC Software.
Failure to follow these instructions can result
®
™
in death, injury or property damage.
®
™
ROBERTS GORDON ULTRAVAC Software requires
®
a PC (not supplied) running Windows 95 or higher,
There are several methods of controlling CRV-Series
systems. The options are as follows:
®
with a Pentium class processor and at least 64k of
RAM.
®
8.1 ROBERTS GORDON System Control (P/N
Special design requirements apply for CRV-Series
02770002)
®
systems using the ROBERTS GORDON ULTRA-
®
The ROBERTS GORDON System Control is an
™
VAC Controller, See Page 31, Section 10.
electronic controller designed for the control of
®
®
CORAYVAC and VANTAGE NP (multiburner only)
systems.
The System Control is capable of giving four zones of
burners' temperature control and power. The control
will also give power output to as many as two pumps,
provided that the load is not greater than 20 A and 1
Ø. For additional electrical specifications see the
System Control Installation, Operation and Service
manual (P/N 10091601NA).
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: CONTROL METHODS
Buildings today demand all sorts of control options
based on the user’s preference. ULTRAVAC™
controls offer a host of communication options for
integration with controls’ networks to best serve
individual needs:
indication of operating conditions. The transformer
relay wiring diagram is shown in the CORAYVAC
Installation, Operation and Service Manual (P/N
127102NA).
®
8.5 Pressure Switch
®
BACnet : Interface ULTRAVAC™ with other building
management control platforms with our BACnet
A pressure switch is required to confirm pump opera-
tion on all systems.
option.
TCP/IP (LAN): Connect to ULTRAVAC™ via your
local area network of computers. Load ULTRAVAC™
software onto any computer on the network and
control and view your heating system from your
computer.
A pressure switch is also required on the inlet duct of a
non-pressurized air supply.
MODEM: Dial into ULTRAVAC™ from anywhere in
the world via modem. Supplied as standard on all
central controllers!
RS-485: Hard wire ULTRAVAC™ directly to your
computer.
There are references in this manual to various trademarks. All
trademarks mentioned herein, whether registered or not, are the
property of their respective owners. Roberts-Gordon is not
sponsored by or affiliated with any of the trademark or registered
trademark owners, and make no representations about them,
their owners, their products or services.
Roberts-Gordon LLC is not sponsored by or affiliated with
BACnet®.
8.3 SPST Transformer Relay (P/N 90417600K)
The transformer relay can be used to control an EP-
®
100 or EP-201 pump CORAYVAC system. The single
pole relay can only be used to control one zone of
burners. The electrical circuit is a 120 V AC (20 A)
supply. The transformer 24 V AC output for the ther-
mostat is rated at 40 V A. Thermostats used with the
transformer must not exceed this power requirement.
A transformer relay operated system will not give any
post purge pump operation to completely exhaust
products of combustion from the system or provide
indication of operating conditions. The transformer
®
relay wiring diagram is shown in the CORAYVAC
Installation, Operation and Service Manual (P/N
127102NA).
8.4 DPST Transformer Relay (P/N 90436300)
The transformer relay can be used to control an EP-
®
100 or EP-201 pump CORAYVAC system. The double
pole relay can only be used to control two zones of
burners. The electrical circuit is a 120 V AC (20A) sup-
ply. The transformer 24 V AC output for the thermostat
is rated at 40 VA. Thermostats used with the trans-
former must not exceed this power requirement. A
transformer relay operated system will not give any
post purge pump operation to completely exhaust
products of combustion from the system or provide
27
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
SECTION 9: AIR SUPPLY SYSTEM
®
™
An air supply free of dust and corrosive contaminants DON ULTRAVAC or relay transformer, a separate
is essential for proper operation and best life expect- load relay package is required. Wire the control for the
ancy with any heating system. With CRV-Series, there relay in parallel with the pump. The outside air blower
are two alternatives available to the designer for pro-
must have a separate 20 A, 120 V power supply.
viding the air supply. These are:
9.2 Non-Pressurized
• Room air, a filter is standard for each burner.
For a non-pressurized outside air supply, a 4" O.D. sin-
gle wall pipe duct may be attached to the burner and
end vent. For length and duct sizing requirements See
Section 9.3. To prevent condensation, insulate the
outside air duct.
• Outside air system to duct air from an uncontami-
nated source. The outside air system can be
designed as a pressurized or non-pressurized
system.
9.3 Outside Air System Design Requirements
9.3.1 Non Pressurized
The first alternative above is usable when the dust
load is not excessive and there is no usage of corro-
sive contaminants such as solvents or vapors inside
the building.
• 6" diameter duct must not exceed 90' (27 m)
• 4" diameter duct must not exceed 90' (27 m)
The outside air system must be used in all applica-
tions where corrosive contaminants may be present in
the air even in trace amounts (few parts per million).
• Elbows are equivalent to 10' (3 m) of duct length.
• See the CRV-Series Installation, Operation, and
Service Manual (P/N 127102NA) for ducting
installation details.
It is important for designers and owners of heating
systems to note that the presence of contaminants in
the combustion air supply will greatly accelerate the
rate of corrosion on tube surfaces and will shorten the
useful life of the heating system. This is true regard-
less of whether the heating system is CRV-Series,
other infrared systems or conventional gas or oil-fired
equipment such as unit heaters, central boiler plant,
etc.
9.3.2 Pressurized Systems
• 6" diameter duct must not exceed 120' (36 m) total
per system.
• 4" diameter duct must not exceed 120' (36 m) per
radiant branch.
• See the CRV-Series Installation, Operation, and
Service Manual (P/N 127102NA) for ducting
installation details.
With the unique vacuum powered burners, the fuel/air
mix remains constant, even if combustion air filters are
dirty. It can be expected that the use of an outside air
system will reduce but not eliminate the potential for
corrosion due to contamination.
FIGURE 27: Air Supply System Capacity by Duct
Length and Diameter
In a way similar to the CRV-Series pump system, the
design of the air supply system also involves consider-
ations of total flow units and acceptable combinations
of duct lengths (and diameters) versus flow units car-
ried. In certain circumstances, it may be desirable to
introduce an outside air blower to pressurize the sys-
tem. A small positive pressure is desirable and neces-
sary to prevent the system from drawing in
NOTE: For capacity requirements larger than shown, use 8" duct.
140
120
100
7"
80
60
40
20
0
6"
5"
4"
contaminated air.
9.1 Pressurized
For pressurized outside air supplies, the outside air
blower motor has a pressure switch that must be used.
Wire this switch in-series with the pump pressure
switch. When using an outside air blower with a ROB-
0
50
100
150
200
250
Straight Duct Length (feet)
®
ERTS GORDON System Control, ROBERTS GOR-
28
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 9: AIR SUPPLY SYSTEM
9.3.3 Pipe sizing
To size each section of pipe proceed as follows:
• Calculate the required flow units at each outlet of
the supply system.
• Measure the longest run of pipe from the blower
to the most remote outlet. Use only this distance
in Figure 27 (or the next longer distance if the
exact distance is not shown). This is to provide
assurance that the pressure drop to the most
remote outlet will not exceed 0.25" w.c. when all
outlets are supplied.
• See Figure 27, find the intersection point on the
graph for the appropriate duct length and number
of flow units. The duct size above this intersection
point indicates what size duct work should be
used. Proceed in a similar manner for each outlet
and each section of duct. For each section of
duct, determine the total flow unit capacity sup-
plied by that section.
Duct Design Rules
• System should be designed so that the blower is
positioned closest to the highest flow require-
ments (end vents).
• When a duct is carrying more than 40 flow units, it
must be at least 6" diameter.
Blower (P/N 90707501) Performance 112 Flow
Units:
One outside air blower is required per each EP-100 or
EP-200 series pump and two outside air blowers may
be required for each EP-300 series pump. Outside air
blowers cannot be shared between two separate
CRV-Series systems.
FIGURE 28: Outside Air Blower
29
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
FIGURE 29: Sample Layout for Pressurized Outside Air Systems
20
8
Branch A
6" duct
8
8
(44)
4" duct
15'
(4.5 m)
110'
(33 m)
B
4" duct
10'
P
Branch B
(33)
(22)
6
6
15
6
4
(3 m)
max.*
50'
(15 m)
Branch C
10
4
4
4" duct
100'
(30 m)
Walls
*NOTE: up to 10' (3 m) max. from blower
inlet can be neglected for pressure drop
calculations.
6" Duct
4" Duct
30
Download from Www.Somanuals.com. All Manuals Search And Download.
®
™
SECTION 10: ROBERTS GORDON ULTRAVAC DESIGN REQUIREMENTS
®
™
SECTION 10: ROBERTS GORDON ULTRAVAC DESIGN REQUIREMENTS
CRV-B-2 and CRV-B-4 are not available for use with
®
™
ROBERTS GORDON ULTRAVAC controls.
CRV-Series systems designed with minimum
radiant tube lengthshall have 1.5' - 2.0' per flow unit of
tailpipe length.
-OR-
CRV-Series systems with recommended radiant tube
length shall have 1.2' - 1.5' per flow unit of tailpipe
length.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES DESIGN MANUAL
SECTION 11: CRV-SERIES EQUIPMENT SPECIFICATIONS
The total heating system supplied shall be design cer- 11.2 Equipment
tified by the CSA International per American National
Standard ANSI Z83.20/CSA 2.34 (latest edition).
11.2.1 Burner
Each burner assembly shall consist of heavy-duty
11.1 Burner and Burner Controls
cast-iron burner heads, pre-wired gas controls with
electronic, three-try direct spark ignition and combus-
tion air filter.
11.1.1 Burners shall be designed to operate simulta-
neously in series without adverse effects from com-
bustion gases from upstream burners.
11.2.2 Pump
11.1.2 Burners shall be capable of firing on:
Natural Gas, or LP Gas.
The pump model supplied will vary with the capacity of
the system. See the pump technical specification
sheet or the installation, operation and service manual
for product description and specification.
11.1.3 Burners shall be supplied to fire at any one of
the input firing rates as specified:
CRV-B-2-20,000 (Btu/h)
CRV-B-4-40,000 (Btu/h)
CRV-B-6-60,000 (Btu/h)
CRV-B-8-80,000 (Btu/h)
CRV-B-9-90,000 (Btu/h)
CRV-B-10-100,000 (Btu/h)
CRV-B-12A-110,000 (Btu/h)
CRV-B-12-120,000 (Btu/h)
The pump shall be acoustically isolated from the sys-
tem with a flexible connector with temperature rating of
350°F minimum. The motor in the vacuum pump shall
be secured with rubber mounts for acoustical isolation.
11.2.3 Heat Exchanger
Radiant tubing (between burners and 10’ - 70’ down-
stream of last burner) shall be of 4" O.D. steel or heat
treated aluminized tubing.
As an option, the balance of the tubing shall be 4"
O.D. steel tubing with an internal and external coating
of acid-resistant porcelain.
®
™
When using ROBERTS GORDON ULTRAVAC con-
trols, burner rates will modulate between 60% and
100% rated input (CRV-B-2 and CRV-B-4 are not avail-
®
™
All heat exchanger (tubing) connections shall be made
with stainless steel coupling assemblies. Standard
couplings will be used in radiant sections. Lined cou-
plings will be used in tailpipe sections.
able for use with ROBERTS GORDON ULTRAVAC
controls).
11.1.4 The design of burners supplied shall provide
for maintaining a constant proportion of fuel gas to fil-
tered combustion air. These conditions are met for
burners in which the pressure of both the fuel gas
and the combustion air are introduced at zero (atmo-
spheric) pressure and the flow of each is established
by a vacuum on the downstream side of the flow
metering orifices.
11.2.4 Outside Air
When specified, in contaminated environments, the
system shall be capable of supplying air from the out-
side to each burner and end vent for the support of
combustion.
11.1.5 To assure a high degree of fail-safe operation,
the design shall preclude flow of gas if any or all of
the following abnormal conditions occur in the non-
firing mode:
1. Main valve fails in open position.
2. Vacuum pump motor fails to operate.
3. Power fails.
11.1.6 To further assure a high degree of safety, the
system will be under negative pressure at all times
during operation to preclude the possibility of the
escape of combustion gases inside the building.
11.1.7 The burner control assembly will include a zero
regulator.
11.1.8 All burners shall be pre-wired with a grounded
electrical cord and plug.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Attach this information to a wall near the ROBERTS GORDON® heater.
®
I n f r a r e d H e a t i n g
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration.
Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.
Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
WARNING
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
TO TURN OFF THE HEATER
1. Set the thermostat to off or the lowest setting.
Fire Hazard
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
Keep all flammable objects, liquids and vapors the minimum
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
required clearances to combustibles away from heater.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the
installation and service of gas-fired heating equipment.
Some objects will catch fire or explode when placed close to
heater.
Failure to follow these instructions can result in death, injury
or property damage.
Maintain
clearance
to the side and
clearance below
the heater from vehicles
and combustible materials.
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park
Darlaston Road, Wednesbury
West Midlands WS10 7SH UK
Telephone: +44 (0)121 506 7700
Fax: +44 (0)121 506 7701
Service Telephone: +44 (0)121 506 7709
Service Fax: +44 (0)121 506 7702
E-mail: [email protected]
Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, NY 14240-0044 USA
Telephone: 716.852.4400
Fax: 716.852.0854
E-mail: [email protected]
Toll Free: 800.828.7450
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and
conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON® equipment and
perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives.
Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
This product is not for residential use.
© 2009 Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying,
recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon LLC.
Printed in U.S.A.
P/N 91037912 Rev. H
Download from Www.Somanuals.com. All Manuals Search And Download.
|