FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
®
5. Leave the building.
CoRayVac
6. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier’s
instructions.
7. If you cannot reach your gas
supplier, call the Fire Department.
Custom-Engineered,
Low-Intensity Infrared
Heating Systems
WARNING
Installation, Operation &
Fire Hazard
Service Manual
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
CRV-B-2
CRV-B-4
Some objects will catch fire or explode
when placed close to heater.
CRV-B-6
CRV-B-8
Failure to follow these instructions can
result in death, injury or property
damage.
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
Installer
WARNING
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the Installation, Operation and Service
Manual thoroughly before installing or servicing
this equipment.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
Roberts-Gordon, LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
Quality in Any Language™
P/N 127102NA Rev. F 05/06
© Copyright 2006 Roberts-Gordon
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
SECTION 1: Heater Safety......................................................1 SECTION 12: Control Methods............................................ 42
1.1 Manpower Requirements .............................................1
SECTION 2: Installer Responsibility .....................................2
2.1 Wall Tag.......................................................................2
2.2 Corrosive Chemicals....................................................2
12.1 ROBERTS GORDON® System Control................... 42
12.2 ROBERTS GORDON® ULTRAVACTM ..................... 42
12.3 SPST Transformer Relay (P/N 90417600)............... 42
12.4 DPST Transformer Relay (P/N 90436300)............... 42
2.3 National Standards and Applicable Codes ..................2 SECTION 13: Starting The System...................................... 49
SECTION 3: Critical Considerations......................................3
3.1 Required Clearances to Combustibles.........................3
SECTION 4: National Standards and Applicable Codes .....7
4.1 Gas Codes...................................................................7
13.1 Checking the Gas Line ............................................ 49
13.2 Checking the Electrical System ............................... 49
13.3 Starting the System ................................................. 49
13.4 Setting the Vacuum.................................................. 49
4.2 Aircraft Hangars ...........................................................7 SECTION 14: Operation and Maintenance.......................... 51
4.3 Public Garages ............................................................7
4.4 Electrical ......................................................................7
4.5 Venting.........................................................................7
4.6 High Altitude ................................................................7
SECTION 5: Major Components ............................................8
14.1 Sequence of Operation............................................ 51
14.2 To Shut Off Heater................................................... 51
14.3 To Start Heater ........................................................ 51
14.4 Pre-Season Maintenance and Annual Inspection.... 51
14.5 Maintenance Checklist............................................. 52
5.1 Standard Parts List .................................................... 11 SECTION 15: Troubleshooting............................................. 55
SECTION 6: Design Requirements...................................... 13 15.1 Troubleshooting Flow Chart..................................... 55
SECTION 7: Heater Installation............................................ 15 SECTION 16: Replacement Parts ........................................ 57
7.1 Tube Installation ........................................................16 SECTION 17: General Specifications.................................. 58
7.2 Coupling and Tube Assembly....................................16
7.3 Elbow Package Configuration..................................... 17
7.4 Reflector Installation ..................................................18
7.5 Burner Installation......................................................20
17.1 Material Specification ............................................... 58
17.2 Heater Specifications ............................................... 58
17.3 Suspension Specifications ....................................... 58
17.4 Controls Specifications............................................. 58
SECTION 8: Optional Heater Accessories..........................21 SECTION 18: The ROBERTS GORDON® CORAYVAC®
8.1 Tee Installation ..........................................................21
8.2 Reflector Joint............................................................21
8.3 Reflector Side Extension............................................23
8.4 Universal Shield.........................................................24
8.5 Barrier Shield.............................................................24
8.6 Two-Foot Decorative Grille Installation.......................25
8.7 One-Foot Decorative Grille Installation......................26
8.8 Protective Grille Installation........................................29
8.9 Classic Cast-Iron Components.................................30
SECTION 9: Pump Installation and Venting .......................31
9.1 Pump Installation .......................................................31
9.2 General Venting Requirements Model EP-100,
Limited Warranty............................................ 61
EP-200 and EP-300 Series Pumps............................32
9.3 Horizontal Venting 4" (10 cm) Pipe ............................34
SECTION 10: Outside Air Supply.........................................37
10.1 Pressurized ..............................................................37
10.2 Non-Pressurized ......................................................37
10.3 Outside Air Blower Internal Wiring ...........................38
SECTION 11: Gas Piping ......................................................41
© 2006 ROBERTS GORDON, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon, LLC.
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF FIGURES
Figure 1: Standard Reflector .....................................................4
Figure 2: One Side Reflector.....................................................4
Figure 3: Two Side Reflectors ...................................................4
Figure 4: Universal Shield, Position 1 .......................................5
Figure 5: Universal Shield, Position 2 .......................................5
Figure 6: Universal Shield, Position 3 .......................................5
Figure 7: 2-Foot Deco Grille......................................................6
Figure 8: Barrier Shield .............................................................6
Figure 9: 1-Foot Deco Grille ......................................................6
Figure 10: Major Component Descriptions................................8
Figure 11: Heater Assembly Overview ................................... 14
Figure 12: Critical Hanger Placement ..................................... 15
Figure 13: Reflector Joint Detail..............................................22
Figure 14: EP-200 Condensate Valve Assembly.....................31
Figure 15: Vertical Venting Configuration................................33
Figure 16: EP-100 Horizontal Venting Configurations .............34
Figure 17: EP-200 Series Horizontal
Venting Configurations...........................................35
Figure 18: EP-300 Series Horizontal
Venting Configurations...........................................36
Figure 19: Duct Sizing ............................................................37
Figure 20: Outside Air Blower Internal Wiring Diagram...........38
Figure 21: Filter Housing Assembly ........................................38
Figure 22: Air Supply Blower Support.....................................39
Figure 23: Pressurized Outside Air Supply..............................39
Figure 24: Non-Pressurized Outside Air Supply......................40
Figure 25: Gas Connection with Flexible Gas Hose................41
Figure 26: One Zone Operation without Control Panel ...........43
Figure 27: One Zone Operation (with Outside Air Blower)
without Control Panel.............................................44
Figure 28: Two Zone Operation without Control Panel............45
Figure 29: General System Wiring ..........................................46
Figure 30: External Wiring Diagram EP-100 and EP-201
120 V 1 Ø Pump ....................................................46
Figure 31: External Wiring Diagram EP-301
120 V 1 Ø Pump ....................................................47
Figure 32: External Wiring Diagram EP-203 or
EP-303 208 V - 230 V (or 460 V) 3 Ø Pump..........47
Figure 33: Burner Internal Wiring............................................48
Figure 34: Burner Internal Ladder Diagram ............................48
Figure 35: Vacuum Reading....................................................50
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 1: HEATER SAFETY
SECTION 1: HEATER SAFETY
Your Safety is Important to Us!
This symbol is used throughout
the manual to notify you of
possible fire, electrical or burn
hazards. Please pay special
attention when reading and
following the warnings in these
sections.
Installation, service and annual inspection of heater
must be done by a contractor qualified in the
installation and service of gas-fired heating
equipment.
Read this manual carefully before installation,
operation or service of this equipment.
This heater is designed for heating nonresidential
indoor spaces. Do not install in residential spaces.
These instructions, the layout drawing, local codes
and ordinances, and applicable standards that apply
to gas piping, electrical wiring, venting, etc. must be
thoroughly understood before proceeding with the
installation.
Thin sheet metal parts, the aluminum reflector
portion of the heater and the various venting
components, have sharp edges. To prevent injury,
the use of work gloves is recommended. The use of
gloves will also prevent the transfer of body oils from
the hands to the surface of the reflector.
Before installation, check that the local distribution
conditions, nature of gas and pressure, and
adjustment of the appliance are compatible.
1.1 Manpower Requirements
To prevent personal injury and damage to the heater,
two persons will be required for installation.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
Service Manual. See Page 4, Figure 1 through Page
6, Figure 9. Write the proper clearance dimensions in
permanent ink according to your model number and
configuration in the open spaces on the tag.
• To ensure the system is designed in accordance
with the parameters of the CRV-Series Design
Manual (P/N 127500NA).
2.2 Corrosive Chemicals
• To install the heater, as well as the gas and
electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon
recommends the installer contact a local Building
Inspector or Fire Marshal for guidance.
CAUTION
Do not use heater in an area containing corrosive
chemicals.
• To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
Avoid the use of corrosive chemicals to ensure a
longer life of the burner, tubing and other parts.
Failure to follow these instructions can result in
property damage.
• To install the heater in accordance with the
clearances to combustibles requirements.
Roberts-Gordon cannot be responsible for ensuring
that all appropriate safety measures are undertaken
prior to installation; this is entirely the responsibility of
the installer. It is essential that the contractor, the
sub-contractor, or the owner identifies the presence
of combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
premises.
• To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access to burners on all sides for
servicing or burner removal.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as a support for ladder or
other access equipment and to never hang or
suspend anything from heater.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements
(fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life span
of the heater components will be greatly reduced. An outside air
supply must be provided to the burners whenever the presence
of these compounds is suspected. Warranty will be invalid if the
heater is exposed to halogenated hydrocarbons.
• To ensure there is adequate air circulation around
the heater and to supply air for combustion,
ventilation and distribution in accordance with
local codes.
2.3 National Standards and Applicable Codes
• To safely and adequately install heater using
materials with a minimal working load of 75 lb
(33 kg).
All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.
2.1 Wall Tag
A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Roberts-Gordon or
your ROBERTS GORDON® independent distributor
to obtain the wall tag. Affix the tag by peeling off the
backing of the adhesive strips on the rear surface
and position the tag on a wall near the CRV-Series
heater (e.g. thermostat or controller).
A copy of the wall tag (P/N 91037912) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the burner and in the Installation, Operation and
2
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3: CRITICAL CONSIDERATIONS
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Required Clearances to Combustibles
WARNING
Clearances are the required distances that
combustible objects must be away from the heater to
prevent serious fire hazards. Combustibles are
materials that may catch fire and include common
items such as wood, paper, rubber, fabric, etc.
Maintain clearances to combustibles at all times
for safety.
Clearances for all heater models are located on the
burner of the heater and on Page 4, Figure 1 through
Page 6, Figure 9 in this manual. Check the
clearances on each burner for the model heater
being installed to make sure the product is suitable
for your application and the clearances are
maintained. Read and follow the safety guidelines
below:
Fire Hazard
Some objects will catch fire or explode when placed
close to heater.
Keep all flammable objects, liquids and vapors the
required clearances to combustibles away from heater.
Failure to follow these instructions can result in death,
injury or property damage.
• Keep gasoline or other combustible materials
including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.
• Maintain clearances from heat sensitive material,
equipment and workstations.
• Maintain clearances from vehicles parked below
the heater.
• Maintain clearances from swinging and overhead
doors, overhead cranes, vehicle lifts, partitions,
storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible
materials, signs must be posted to specify the
maximum permissible stacking height to maintain
required clearances from the heater to the
combustibles. Signs must be posted adjacent to
the heater thermostat. In the absence of a
thermostat, signs must be posted in a
conspicuous location.
• Consult local Fire Marshal, Fire Insurance Carrier
or other authorities for approval of proposed
installation when there is a possibility of exposure
to combustible airborne materials or vapors.
• Hang heater in accordance to the minimum
suspension requirements on Page 15, Figure 12.
• If the radiant tubes must pass through the building
structure, be sure that adequate sleeving and fire
stop is installed to prevent scorching and/or fire
hazard.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
*
Protective Grille clearances are the same as Standard Reflector.
FIGURE 1: STANDARD REFLECTOR
(inches)
(centimeters)
Model
A
4
4
4
4
4
4
4
4
B
20
20
20
20
36
36
36
36
C
48
48
48
48
60
60
60
60
D
20
20
20
20
36
36
36
36
A
11
11
11
11
11
11
11
11
B
51
51
51
51
92
92
92
92
C
D
51
51
51
51
92
92
92
92
CRV-B-2
122
122
122
122
153
153
153
153
A
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
B
D
C
.
FIGURE 2: ONE SIDE REFLECTOR
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
12
12
12
12
12
12
12
12
C
56
56
56
56
60
60
60
60
D
20
20
20
20
42
42
42
42
A
11
11
11
11
11
11
11
11
B
31
31
31
31
31
31
31
31
C
D
51
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
143
143
143
143
153
153
153
153
A
51
51
51
107
107
107
107
B
D
C
FIGURE 3: TWO SIDE REFLECTORS
(inches)
(centimeters)
Model
A
4
4
4
4
4
4
4
4
B
12
12
12
12
12
12
12
12
C
56
56
56
56
60
60
60
60
D
12
12
12
12
12
12
12
12
A
11
11
11
11
11
11
11
11
B
31
31
31
31
31
31
31
31
C
D
31
31
31
31
31
31
31
31
A
C
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
143
143
143
143
153
153
153
153
B
D
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 3: CRITICAL CONSIDERATIONS
NOTE:
1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
FIGURE 4: UNIVERSAL SHIELD, POSITION 1
Model
(inches)
(centimeters)
A
4
4
4
4
8
8
8
8
B
12
12
12
12
18
18
18
18
C
12
12
12
12
24
24
24
24
D
12
12
12
12
18
18
18
18
A
11
11
11
11
21
21
21
21
B
31
31
31
31
46
46
46
46
C
31
31
31
31
61
61
61
61
D
31
31
31
31
46
46
46
46
CRV-B-2
A
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
B
D
C
FIGURE 5: UNIVERSAL SHIELD, POSITION 2
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
24
24
24
24
36
36
36
36
C
48
48
48
48
48
48
48
48
D
24
24
24
24
36
36
36
36
A
11
11
11
11
11
11
11
11
B
61
61
61
61
92
92
92
92
C
D
61
61
61
61
92
92
92
92
CRV-B-2
122
122
122
122
122
122
122
122
A
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
B
D
C
CRV-B-10
CRV-B-12
CRV-B-12A
FIGURE 6: UNIVERSAL SHIELD, POSITION 3
Model
(inches)
(centimeters)
A
4
4
4
4
8
8
8
8
B
12
12
12
12
12
12
12
12
C
56
56
56
56
60
60
60
60
D
30
30
30
30
42
42
42
42
A
11
11
11
11
21
21
21
21
B
31
31
31
31
31
31
31
31
C
D
77
CRV-B-2
143
143
143
143
153
153
153
153
A
CRV-B-4
CRV-B-6
CRV-B-8
77
77
77
B
D
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
107
107
107
107
C
5
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
NOTE:
1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.
FIGURE 7: 2-FOOT DECO GRILLE
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
12
12
12
12
18
18
18
18
C
48
48
48
48
56
56
56
56
D
12
12
12
12
18
18
18
18
A
11
11
11
11
11
11
11
11
B
31
31
31
31
46
46
46
46
C
D
31
31
31
31
46
46
46
46
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
122
122
122
122
143
143
143
143
A
C
B
D
FIGURE 8: BARRIER SHIELD
(inches)
(centimeters)
Model
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
A
4
B
12
12
12
12
C
12
12
12
12
D
12
12
12
12
A
11
11
11
11
B
31
31
31
31
C
31
31
31
31
D
31
31
31
31
A
4
4
4
B
D
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
- UNAPPROVED -
C
FIGURE 9: 1-FOOT DECO GRILLE
Model
(inches)
(centimeters)
A
4
4
4
4
4
4
4
4
B
12
12
12
12
18
18
18
18
C
48
48
48
48
56
56
56
56
D
12
12
12
12
18
18
18
18
A
11
11
11
11
11
11
11
11
B
51
51
51
51
92
92
92
92
C
D
51
51
51
51
92
92
92
92
A
CRV-B-2
CRV-B-4
CRV-B-6
CRV-B-8
CRV-B-9
CRV-B-10
CRV-B-12
CRV-B-12A
122
122
122
122
153
153
153
153
C
B
D
6
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES
4.1 Gas Codes
4.3 Public Garages
The type of gas appearing on the nameplate
must be the type of gas used. Installation must
comply with national and local codes and
requirements of the local gas company.
Installation in garages must be in accordance
with the following codes:
United States: Standard for Parking Structures
NFPA-88A - latest revision or the Code for Motor
Fuel Dispensing Facilities and Repair Garages,
NFPA 30A - latest revision. Canada: Refer to
CAN/CGA B149.1 and B149.2: Installation
Codes for Gas Burning Appliances.
United States: Refer to National Fuel Gas Code,
ANSI Z223.1 - latest revision (same as NFPA
54).
Canada: Refer to CAN/CGA B149.1 and B149.2:
Installation Codes for Gas Burning Appliances.
• Heaters must not be installed less than 8'
(2.4 m) above the floor. Minimum clearances to
combustibles must be maintained from vehicles
parked below the heater.
4.2 Aircraft Hangars
• When installed over hoists, minimum
clearances to combustibles must be maintained
from the uppermost point of objects on the hoist.
Installation in aircraft hangars must be in
accordance with the following codes:
United States: Refer to Standard for Aircraft
Hangars, ANSI/NFPA-409 - latest revision.
4.4 Electrical
Canada: Refer to Standard CAN/CGA B149.1
and B149.2: Installation Codes for Gas Burning
Appliances.
The heater must be electrically grounded in
accordance with the following codes:
• In aircraft storage and servicing areas, heaters
shall be installed at least 10' (3 m) above the
upper surface of wings or of engine enclosures
of the highest aircraft which may be housed in
the hangar. The measurement shall be made
from the wing or engine enclosure (whichever is
higher from the floor) to the bottom of the heater.
United States: Refer to National Electrical
Code®, ANSI/NFPA-70 - latest revision. Wiring
must conform to the most current National
Electrical Code®, local ordinances and any
special diagrams furnished.
Canada: Refer to Canadian Electrical Code,
CSA C22.1 Part 1 - latest revision.
• In shops, offices and other sections of aircraft
hangars communicating with aircraft storage or
servicing areas, heaters shall be installed not
less than 8' (2.4 m) above the floor.
4.5 Venting
The venting must be installed in accordance with
the requirements within this manual and the
following codes:
• Suspended or elevated heaters shall be so
located in all spaces of aircraft hangars that they
shall not be subject to injury by aircraft, cranes,
movable scaffolding or other objects. Provisions
shall be made to assure accessibility to
suspended heaters for recurrent maintenance
purposes.
United States: Refer to NFPA-54/ANSI Z223.1 -
latest revision, National Fuel Gas Code.
Canada: Refer to CAN/CGA B149.1 and B149.2:
Installation Codes for Gas Burning Appliances.
4.6 High Altitude
These heaters are approved for installations up
to 2000' (610 m) (US), 4500' (1370 m) (Canada)
without modification. Consult factory if US
installation is above 2000' (610 m) or Canadian
installation is above 4500' (1370 m).
7
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 5: MAJOR COMPONENTS
The figures in this section provide a general overview Optional reflector configurations are shown on Page
of component placement in a CRV-Series system.
The location of some components such as supports appropriate suspension hardware, beam clamps,
and couplings is crucial for proper installation. chain or rod at predetermined locations. Adjustments
4, Figure 1 through Page 6, Figure 9. Install
Assemble the heater components as shown on Page of chain length will provide uniform pitch.
14, Figure 11.
FIGURE 10: Major Component Descriptions
Tube
Burner
Hot rolled, heat treated or
coated aluminized tube
supplied in 10' (3 m) lengths.
Reflector
Reflector with Hole
(Aluminum or
Stainless Steel)
Alternate overlap as
shown on overview.
Minimum overlap is 6"
(16 cm).
(Aluminum or
Stainless Steel)
Alternate overlap as
shown on overview.
Minimum overlap is 6"
(16 cm).
Flex Gas Line
with shut-off cock
90° Elbow
Cross
45° Elbow
Tee
Combustion Chamber
End Vent
Tube Adapter
Coupling Assembly
with Lock
8
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 5: MAJOR COMPONENTS
FIGURE 10: Major Component Descriptions (Continued)
Reflector Joint
Reflector End Cap
(Aluminum or Stainless
Steel)
Barrier Shield
Punch out center section to
accommodate heat
exchanger tube when
necessary.
Tube and Reflector Hanger
with Clamp Package
Position this hanger no more
than 4" (10 cm) away from the
burner.
Reflector Side Extension
Tube and Reflector Hanger
Suspend system from these
hangers.
Deco Grille
Reflector Support Strap &
Wire Form
S-Hook
Turnbuckle
Protective Grille
Condensate
Valve
Assembly
Reflector Side
Extension Bracket
Universal Shield
Universal Shield with Holes
Bracket Assembly
9
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 10: Major Component Descriptions (Continued)
ROBERTS GORDON®
ULTRAVAC™
Variable Frequency Drive
ANGER
D
Électrique
Choc
de
er
ANGER
D
Dang
d
Hazar
le courant
nt
ava
her
k
branc
Shoc
Dé
électrique
vision.
toute
Electrical
electrical
ré
Cet
Disconnect
vicing.
ser
ore
être
bef
wer
doit
une
po
appareil
e
de
terre
c
sour
t
be
y
operl
sour
à
mus
.
connecter
á
appliance
c
mise
This
ave
a
pr
courant
to
.
ce
connected
electrical
ces
grounded
de suivre
la
îner
ute
Fa
entra
peut
these
w
instructions
follo
é
lectriques.
to
ilure
c
hoc
Fa
les
ou
mor
result
t
can
080
910
01
k
.
P/N
instructions
shoc
electrical
e
U.
in th
s-U
Etat
S.A
or
ted
death
Prin
in
nis
aux
rimé
Imp
.com
-inc
w.rg
ww
©
®
™
GORDON
ROUBElRTtSraVac
Controller
Part Number:
uméro de la Pièce:
N
(8 total)
,
3A
ber:
EP-100 Pump Package - 4" dia
For more information, refer to the EP-100
Installation, Operation and Service
Manual (P/N 127201NA).
Serial Num
No. de Série:
n
do
or
-Gutputs
ts
er
ob
put 120V AC, 25A
O
e
s
t
120V AC
et
tre
W
R
Ratings: In
S
Y
RG
ain
M
6
1R
NE
T
76
D
E
E
EN
PM
on
E
ord
0
3
M
L
OS
NC
ME
A
GE
AN
Q
UI
-G
it
1
L
r
io
nta
E
N
T
erts
Un
ob
O
R
4
y
,
SB
4
4
2.4
58
4
00
s
b
M
ox
0-
rim
24
G
C
4
03
.5
.
B
P.O
14
00
Y
4
da
na
45
11
B
,
N
5.9
ev
lo
5
a
Te
0
R
ffa
6.8
:
4
5.0
5.9
9
005
08
Bu
Te
Fa
1
ne
e:
7
pho
910
on
4
8.7
le
5
ph
85
P
/N
le
.0
52
0
is
-Un
.8
45
:
90
16
re
ats
Et
F
ax
x:
7
.82
x
au
00
8
é
e:
rim
p
ll
F
om
A/Im
To
c.c
.S.
U
-in
in
.rg
ted
w
n
Pri
w
w
©
ROBERTS GORDON®
ULTRAVAC™ Controller
EP-201 Pump Package - 4" dia
EP-203 Pump Package - 4" dia
For more information, refer to the EP-200
Series Installation, Operation and Service
Manual (P/N 127200NA).
System Control
ROBERTS GORDON®
ULTRAVAC™
Adjustable Indoor Sensor
EP-301 Pump Package - 4" dia
EP-301 Pump Package - 6" dia
EP-303 Pump Package - 4" dia
EP-303 Pump Package - 6" dia
For more information, refer to the
EP-300 Series Installation, Operation
and Service Manual (P/N 127202NA).
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 5: MAJOR COMPONENTS
5.1 Standard Parts List
02722100 Adapter, 4" (10 cm) Cast Iron
91240010 Tube Hanger, 6" (15 cm)
Table 1: Contents of CRV-Series Burner Carton
91308001 High Temperature Pipe Compound, 1lb. can
Part No.
Description
0270XXXX Burner (Rate and Fuel Varies)
Venting Accessories
01324401 Outside Air Supply Takeoff, 4" (10 cm)
01326801 Outside Air Filter Housing
*91412200 Flexible Stainless Steel Gas Hose, 1/2" NPT
(US models only)
013676XX End Vent Plate
01397300 Accessory Package
90707501 Air Supply Blower/Power Venter
01361200
01367800
02724901
91115100
91119500
91905500
92123900
92511601
96411600
01312401
Filter Support Disk
Combustion Chamber Gasket
Door Assembly w/ Hole
Screw #10 - 24 x 5/8
U-Clip
Filter Support
Nut 5/16 - 18
Wing Nut #10 - 24
Lock Washer 5/16"
Filter and Gasket
91409601 Outside Air Flex Duct, 4" (10 cm)
(Box of 8 - 8' [2.4 m] sections)
Reflectors and Related Accessories
01329910 Reflector Side Extension Support
03050010 Reflector Support Package (Tubing)
02712700 Reflector Side Extension, 2 Clips, 2 Screws
02716400 Reflector Support Package (Schedule 40 Pipe)
02750303 Reflector, Aluminum
027503SS Reflector, Stainless Steel
02750304 Reflector, Aluminum with Hole
027503SH Reflector, Stainless Steel with Hole
02750800 Reflector End Cap, Aluminum
027508SS Reflector End Cap, Stainless Steel
027508SH Reflector End Cap, Stainless Steel with Hole
02750900 Reflector Joint
* Canadian Models: Rubber (Type 1) Gas Hoses
available as an accessory, see Page 41.
Table 2: Common CRV-Series Components
Part No.
Description
Combustion Chamber:
027509SS Reflector Joint, Stainless Steel
027127SS Reflector Side Extension, Stainless Steel
03090100 Tube and Reflector Hanger
02790300 Tube and Reflector Hanger, Cast Iron
91907302 S-Hook
02722300-1P Hot Rolled Steel Combustion Chamber
02722301-1P Heat-Treated Aluminized Steel Combustion Chamber
0272230D-1P Porcelain Coated Steel Combustion Chamber
02721200-1P Cast Iron Combustion Chamber
91903201 Turnbuckle
91903300 Spring Hook
91903202 Turnbuckle with Eyebolt
02712100 Universal Shield Support
Tubing and Related Accessories
01312700 Coupling, 4" (10 cm) Plain
01312706 Coupling, 6" (15 cm) Plain
0131270I
Coupling, 4" (10 cm) Lined
02751800 Universal Shield with Holes
02751801 Universal Shield
027518SS Universal Shield, Stainless Steel
01331900 Coupling, 4" (10 cm) Damper
E0009356 Coupling, 6" (15 cm) Damper
0133022D Tee, 4" (10 cm) Coated
01330203 Tee, 4" (10 cm) Aluminized
01330204 Tee, 6" (15 cm) Aluminized
0133092D Cross, 4" (10 cm) Coated
01330903 Cross, 4" (10 cm) Aluminized
01330904 Cross, 6" (15 cm) Aluminized
01335801 Elbow, 4" (10 cm) Aluminized 90°
T0100320 Elbow, 6" (15 cm) Aluminized 90°
0133580D Elbow, 4" (10 cm) Coated 90°
01336101 Elbow, 4" (10 cm) Aluminized 45°
0133610D Elbow, 4" (10 cm) Coated 45°
91409300 Tube, Hot Rolled Steel 4" (10 cm) dia 10' (3 m)
91409403 Tube, Non-Heat Treated Aluminized 4" (10 cm)
dia 10' (3 m)
91409408 Tube, Heat Treated Aluminized 4" (10 cm) dia 10' (3 m)
91409420 Tube, Non-Heat Treated Aluminized 6" (15 cm)
dia 10' (3 m)
9141030D Tube, Coated 4" (10 cm) dia 10' (3 m)
E0009105 Tube, Heat Treated Aluminized 6" (15 cm) dia 10' (3 m)
91418200 Tube Adapter, Aluminized
6" (15 cm) dia x 4" (10 cm) dia
11
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Control Packages and Accessories
10001501 Water Resistant Sensor
02770002 System Control
Protective Grille
08050001 Protective Grille, 40" (1 m)
08050002 Protective Grille End Cap
ROBERTS GORDON® ULTRAVAC™ Central Controller
(with Modem Chip & Software) Includes:
URVCCM
Shields
02750303 Barrier Shield
02751801 Universal Shield
027518SS Universal Shield, Stainless Steel
02751800 Universal Shield with Holes
ROBERTS GORDON® ULTRAVAC™ Controller
Modem Chip
Outdoor Sensor
URVSC
10080142
10081501
10080410
URVCCR
PC Connection Cable Package
ROBERTS GORDON® ULTRAVAC™ Central Controller
(with RS-485 Converter & Software) Includes:
Pump Packages and Accessories
02719105 EP-100 Pump Package
02719100
02724700
ROBERTS GORDON® ULTRAVAC™ Controller
RS-485 Converter with 9 V Power Supply
Outdoor Sensor
URVSC
10080430
10081501
10080410
URVCCL
EP-100 Pump
Accessory Package
PC Connection Cable Package
02716305 EP-201 Pump Package
ROBERTS GORDON® ULTRAVAC™ Central Controller
(with TCP/IP Communication Module & Software)
Includes:
01312001
01317805
EP-201 Pump
Accessory Package
02712034 EP-203 Pump Package
ROBERTS GORDON® ULTRAVAC™ Controller
TCP/IP Communication Module
Outdoor Sensor
URVSC
10080440
10081501
10080410
URVSC
01312002
01317805
EP-203 Pump
Accessory Package
02723014 EP-301 Pump Package 4"
PC Connection Cable Package
02730101
02730104
EP-301 Pump Assembly
Accessory Package
Controller, ROBERTS GORDON® ULTRAVAC™ , 1
Pump 3 Zones (Satellite Control)
02723016 EP-301 Pump Package 6"
VFD75115 Variable Frequency Drive Assembly, 75 HP, 115 V Input
VFD75230 Variable Frequency Drive Assembly, 75 HP, 230 V Input
VFD20230 Variable Frequency Drive Assembly, 2 HP, 230 V Input
10080142 Modem, Plug-In Chip
10080410 Cable Package, PC Connection
10080430 RS-485 Converter with 9V Power Supply
10080440 TCP/IP Communication Module
02730101
02730106
EP-301 Pump Assembly
Accessory Package
02723034 EP-303 Pump Package 4"
02730103
02730104
EP-303 Pump Assembly
Accessory Package
02723036 EP-303 Pump Package 6"
02730103
02730106
EP-303 Pump Assembly
Accessory Package
Sensor, Adjustable Indoor, Deg F, ROBERTS GORDON®
ULTRAVAC™ Controller
10081500
10081501 Sensor, Outdoor, ULTRAVAC™
10081502 Sensor, Adjustable Indoor, Deg C, ULTRAVAC™
Pump Accessories
90430600K Pressure Switch
01327001 Condensate Check Valve Assembly
02718851 Drain Cap, 4" (10 cm)
02718852 Drain Cap, 6" (15 cm)
Thermostats
05023000 Load Relay Package
90417600 Transformer Relay - SPST (12 A)
90436300 Transformer Relay - DPST (12 A)
90423000 24 V Low Voltage Thermostat (Marked 1-5)
90424300 Thermostat Guard
Starters
10050001 Starter, 120 Vac for EP-203, 3 Ø
10050002 Starter, 12 Vdc for EP-201, 1Ø
10050003 Starter, 120 Vac for EP-201, 1 Ø
10050008 Starter, 120 Vac for EP-301, 1 Ø
10050009 Contactor Package-230 Vac Coil for EP-301, 2 HP
10050010 Starter, 120 Vac for EP-303, 3 Ø
Deco Grille (1' x 8' [.3 m x 2.4 m])
01363003 Bracket
01365901 End Piece
01326801 Reinforcement
01365903 Joint Piece
91406700 1' (.3 m) x 8' (2.4 m) Protective Grille
Deco Grille (2' x 4' [.6 m x 1.2 m])
01365900 Shield Frame
01370408 Reflector Side Extension 8" x 48" (20.3 cm x 122 cm)
01370412 Reflector Side Extension 12" x 48" (30.5 cm x 122 cm)
01370416 Reflector Side Extension 16" x 48" (40.6 cm 122 cm)
91407000 Grille, Aluminum 2' x 4' (.6 m x 1.2 m)
12
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 6: DESIGN REQUIREMENTS
SECTION 6: DESIGN REQUIREMENTS
The CRV-Series system’s design is related to the
system operation and performance required by the
building being heated. Every effort should be made
to follow the dimensions on the layout drawing. If
deviations are necessary, either contact the
company responsible for the layout design, your
ROBERTS GORDON® independent distributor,
or consult the CRV-Series Design Manual
(P/N 127500NA).
13
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 11: Heater Assembly Overview
14
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: HEATER INSTALLATION
SECTION 7: HEATER INSTALLATION
Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heaters must be installed in accordance with
clearances to combustibles as indicated on the rating
plate and in this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating plate.
Typical installation configurations are shown in
Figure 12.
Expansion and contraction of the tube dictates that
the minimum suspension lengths in the table on
Figure 12 be maintained.
WARNING
Suspension Hazard
Hang heater with materials with a
minimum working load of 75 lbs
(33 kg).
Failure of the supports can result
in death, injury or property damage.
To ensure your safety and comply with the terms of
the warranty, all units must be installed in
accordance with these instructions.
The gas or the electrical supply lines must not be
used to support the heater.
FIGURE 12: Critical Hanger Placement
Typical Suspension Details
Concrete Beam
Wood Beam
Beam Clamp
Anchor
Locknut
Screw Hook
3/8"
Chain size
3/16" minimum
Washers
Rod 3/8"
"X" (See Table)
24" min.
(61 cm)
Turnbuckle
S-Hook
Locknut
(Typical)
7'6" (2.3 m)
Turnbuckle
Hanger
Reflector
Side View
Towards Pump
Front View
Run Length Typical Expansion Minimum “X” Length
50' (15 m)
100' (31 m)
150' (46 m)
200' (61 m)
250' (76 m)
1" (3 cm)
2" (5 cm)
3" (8 cm)
4" (10 cm)
5" (13 cm)
12" (30 cm)
24" (61 cm)
36" (91 cm)
46" (122 cm)
57" (145 cm)
Description
Turnbuckle
S-Hook
Part Number
91903201
91907302
03090100
Tube/Reflector Hanger
15
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.1 Tube Installation
NOTE: Tubing requires a downward slope of
1/2" (13 mm) per 20' (6 m) away from
burner. Tailpipe tubing requires a
downward slope of 1" (26 mm) per
20' (6 m) away from burner.
End View
Combustion
Chamber
Weld
Seam
Bottom
of Tube
Tube
7' 6"
(229 cm)
Hanger
Turnbuckles
10'
maximum
(3 m)
Combustion
Chamber
Description
Tube
Turnbuckle
Part Number
91409XXX
91903201
Tube/Reflector Hanger
03090100
Step 7.2 Coupling and Tube Assembly
Close coupling with tab.
Start slide bar/coupling lock
B onto coupling.
A
Tab
Slide Bar/Coupling Lock
Wide End
Coupling
Open
3" (8 cm) to
4" (10 cm)
Closed
Insert tubes into coupling.
Tighten coupling to join tubes.
C
D
Slide Bar/Coupling Lock
Coupling
Orient coupling so that
the impact block is in the
2:00 or 10:00 o’clock
positions.
Tube
Tube
Description
Coupling
Part Number
01329600
Tube
Slide Bar/Coupling Lock
Tube
01329700
91409XXX
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: HEATER INSTALLATION
Step 7.2.1 Coupling and Tube Assembly (Continued)
Tighten slide bar as shown below.
Drive slide bar until tight.
End of slide bar should be
within tolerance listed below.
± 2" (5 cm)
Correct Slide Bar
Dimensions
Incorrect Slide Bar
Position
Repeat Step 7.2, A - D until all tubes are assembled.
NOTE: If coupling is not tight, loss of vacuum can occur.
7.3 Elbow Package Configuration
Step 7.3.1 Elbow Installation
Tube
Coupling
Minimum Distance Required Between
Burner and Elbow
90° Elbow
Model
MinimumDistance
5' (1.5 m)
CRVB-2
CRVB-4
CRVB-6
CRVB-8
CRVB-9
CRVB-10
CRVB-12A
CRVB-12
Description
Elbow Package
90° Elbow
Part Number
02718702
01335801
01312700
02750800
02750900
91107720
5' (1.5 m)
10' (3 m)
10' (3 m)
10' (3 m)
15' (4.5 m)
15' (4.5 m)
15' (4.5 m)
Coupling
Reflector End Cap
Reflector Joint Piece
U-Clip Package
Step 7.3.2 Elbow Installation
Tube
Coupling
17
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.4 Reflector Installation
Step 7.4.1 Reflector Installation with Hole
Reflector
with Hole
Slide Reflector
with hole
through hanger.
Unhook combustion
chamber from chain
and insert through hole.
Reconnect chain.
Hanger
Tube
Description
Tube/Reflector Hanger
Tube
Part Number
03090100
91409XXX
02750304
Combustion
Chamber
Reflector with Hole
Step 7.4.2 Reflector Installation
Wire Form
Sheet Metal
Reflector
Screw
Tube
Reflector Support
Strap
U-Clip
(2 Clips per
Alternate Overlaps
per Side)
Description
Reflector Support Package
U-Clip Package
Part Number
03050010
91107720
Reflector End Cap
027508XX
18
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 7: HEATER INSTALLATION
Step 7.4.3 Reflector, U-Clip and Reflector Support Installation
The pictorial drawings of the heater construction in
Section 7 are schematic only and provide a general
guideline of where hangers, reflector supports and
U-clips are to be installed.
To ensure proper expansion and contraction
movement of the reflectors, a combination of U-clips
and reflector supports are used. The positioning of
reflector supports and U-clips depend on the
individual installation. Use either pop rivets or sheet
metal screws instead of u-clips when installing end
caps and joint pieces in areas where impact and high
wind may be a factor. The following rules must be
observed.
1. The first reflector after the burner must be affixed in
the middle of the reflector with a reflector support and
tight screws.
Tight
Sheet Metal
Screw
Wire Form
Reflector
End Cap
First Reflector
Reflector Support
Strap
U-Clips
2 B
Slip Overlap
Overlap must be a
minimum of " (16 cm)
6
"
Reflector
Reflector
Support
(16 cm)
6
2. The overlap at the first and second reflector is a slip overlap.
Thereafter, every third reflector joint is a slip overlap. A slip
overlap is achieved by either:
Loose screws
loosened 1/16"
(1.6 mm)
a.) both reflectors lay inside a hanger.
(No reflector support needed).
to allow slippage.
b.) using a reflector support with
loose screws at the reflector
2 A
Slip Overlap
overlap.
3. The remaining reflector overlaps require a non-slip
overlap connection. To affix the reflectors together in
a non-slip overlap either:
a.) use reflector support and tight screws.
b.) if both reflectors lay inside a hanger, u-clips or
sheet metal screws may be used.
3 A
Non-Slip Overlap
Reflector
This section of three reflectors joined together must
be affixed to the tube with at least one reflector support
with tight screws.
Tight
Screws
3 B
Non-Slip Overlap
Description
Reflector Support Package
Wire Form
Reflector Support Strap
Screw #8 x 3/4
U-Clip Package
Part Number
03050010
91908004
03050000
94320812
91107720
027508XX
U-Clip
(2 Clips per
Non-slip Overlap
inside a Hanger)
Reflector End Cap
19
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 7.5 Burner Installation
Burner
Burner
Combustion
Chamber
Gasket
End
Vent
Combustion
Chamber
NOTE:
End
Vent
Clips
Install end vent
at end combustion
chamber position only.
Description
Bolt
Burner
Lock Washer
Gasket
End Vent
Part Number
94273914
0270XXXX
96411600
01367800
013676XX
End Vent
Rating
Number
20
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: OPTIONAL HEATER ACCESSORIES
SECTION 8: OPTIONAL HEATER ACCESSORIES
Step 8.1 Tee Installation
Tube
Coupling
Tee
Description
Tee
Tube/Reflector Hanger
Tube
Part Number
01330XXX
03090100
91409XXX
01312700
Coupling
Step 8.2 Reflector Joint
Step 8.2.1 Reflector Joint Installation
Reflector
Reflector
Joint
Flatten Edge
Scribe
Contour
1" (2.5 cm)
Maximum
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.2.2 Reflector Joint Installation
Cut away contour
with tin snips.
Punch/drill six 3/32" (2 mm) holes.
Step 8.2.3 Reflector Joint Detail
Install reflector
end cap.
Attach reflector joint
with six #8 sheet
metal screws.
FIGURE 13: Reflector Joint Detail
Reflector
Reflector
Joint
22
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: OPTIONAL HEATER ACCESSORIES
8.3 Reflector Side Extension
Step 8.3.1 Bracket Installation
Tube
Reflector
Tube and Reflector Hanger
Reflector Support
Reflector Side
Extension Bracket
(2 per reflector)
Use additional supports
in high air movement
applications.
Description
Part Number
Reflector Side Extension Package
Reflector Side Extension
Retainer Clips
02712700
01368000
02751200
94118106
Sheet Metal Screws
Order Separately
Reflector Side Extension Bracket
01329910
Step 8.3.2 Side Reflector Installation
#8 x 3/8 (3.9 x 9.5 mm) Sheet Metal Screw
Cut relief notches for
supports and hangers.
Retainer Clip
(2 per Side)
Reflector Side Extension
23
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
8.4 Universal Shield
Universal shields are adjustable
aluminum reflectors whose
angle and height can be
Standard Reflector
adjusted to direct heat to or
away from a desired area.
See Page 5, Figure 4 through
Page 5, Figure 6 for positions.
Tube
Flattened
Section
Tube and Reflector Support Assembly*
Stud*
Universal Shield
Shield Support Bracket*
Hex Nut*
Description
Universal Shield
Part Number
02751801
02751800
02712100
01329802
02751700
02721400
02790900
92114800
Bracket Assembly*
Universal Shield with Holes
Universal Shield Support Package
Tube and Reflector Support Assembly
Universal Shield Support
Shield Bracket Assembly
Stud
* Included in universal shield
support package.
Hex Nut
8.5 Barrier Shield
Do not install barrier shield less than 20' (6 m) downstream of any burner.
Do not attach end caps to the ends of the barrier shields. For lengths
greater than 8' (2.6 m), use universal shields.
Do not use barrier shields for burner sizes larger than 80,000 Btu/h.
Tube and Reflector Hanger
Standard Reflector
Flatten Reflector Edges
Attach U-Clips
Reflector Support Strap
Cut Relief Notch
Barrier Shield
Description
Part Number
Barrier Shield
U-Clip Package
02750303
91107720
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: OPTIONAL HEATER ACCESSORIES
8.6 Two-Foot Decorative Grille Installation
Step 8.6.1 Grille Installation
Tube and Reflector
Hanger
Reflector
Heat Exchanger
Tube
2' x 4' (60 cm x 120 cm)
Aluminum Grille
Suspended Ceiling Frame
Description
Part Number
Aluminum Grille 2' x 4' (60 cm x 120 cm)
91407000
Step 8.6.2 Frame Shield Installation
Shield
Description
Deco Grille Shield
Part Number
01365900
25
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.6.3 Reflector Side Extension Installation for Decorative Grilles
NOTE: If the decorative grille system is to be installed in an area with
considerable air movement, it is recommended that one
#8 x 3/8" sheet metal screw be installed per reflector extension to
6" (15 cm) Minimum
prevent it from blowing over.
Cut relief notches for tube
and reflector hangers.
Allow 6" (15 cm)
minimum clearance
between burner box
and overhead
obstructions for
service.
Insert screw
here (see note).
A
Reflector Side Extension
Distance "A"
Extension
Part No.
Minimum
2" (4 cm)
Maximum
6" (15 cm)
10" (26 cm)
14" (37 cm)
Width
01370408
01370412
01370416
8" (20 cm)
12" (30 cm)
16" (40 cm)
Description
Reflector Side Extension
Part Number
01370412
6" (15 cm)
10" (26 cm)
8.7 One-Foot Decorative Grille Installation
Step 8.7.1 One-Foot Decorative Grille Bracket
In order to maintain reflector shape,
do not fasten brackets together.
Do not fasten bracket to adjoining
reflectors. Maintain same slipjoint
position as reflectors.
#8 Sheet Metal Screws
Decorative Grille Bracket
2" (5 cm)
Minimum
Bracket
Cut relief notches for
supports and hangers.
Overlap
Description
Part Number
Bracket
01363003
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: OPTIONAL HEATER ACCESSORIES
Step 8.7.2 Decorative Grille
Spread apart brackets
and install
decorative grille.
Description
Part Number
Decorative Grille 8' x 1' (2.4 m x .3 m)
91406700
Step 8.7.3 Joint Piece and Reinforcement
Joint Piece
Slip joint piece into
support bracket
and fasten to
bracket on one side
of the joint only.
Reinforcement
#8 Sheet Metal Screws
Joint Piece
Description
Joint Piece
Part Number
01365903
Reinforcement
01365902
27
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.7.4 End Piece and Reflector End Cap
Reflector
End Cap
End Piece
Insert end piece
between grille and
brackets.
Fasten end piece
to brackets using two
#8 sheet metal screws
and replace reflector end cap.
Description
Part Number
End Piece
01365901
Step 8.7.5 90° Elbow
Inside
Corner
Grille Brackets
Joint Piece
Insert
end piece
between
grille and
brackets.
Joint Piece
Decorative Grille
Brackets
Cut grille bracket at
reflector joint piece.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 8: OPTIONAL HEATER ACCESSORIES
8.8 Protective Grille Installation
Step 8.8.1 Silicone Cap Installation
Silicone Cap
Description
Grille Section
Grille End Cap
Silicone Cap
Part Number
08050001
08050002
Grille
Finger
91915951-6P
Step 8.8.2 Grille End Cap Installation
B
D
A
Grille
Grille End Cap
C
Bend up 90°
Pull outward
Step 8.8.3 Grille Installation
Reflector
40"
(101 cm)
Final Grille
Section
Grille
Grille
End Cap
29
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Step 8.9 Classic Cast-Iron Components
WARNING
Suspension Hazard
Hang heater with materials
with a minimum working load
of 750 lbs. (340 kg).
Use special tube and reflector
hangers when suspending
the schedule 40 steel pipe
system.
Schedule 40 steel pipe is
heavy and will fall
if not supported properly.
Distance between supports
must be 7' (2.13 m) or less.
Failure to follow these
instructions can result in
death, injury or property
damage.
Turnbuckle
Hang cast-iron combustion chamber with a turnbuckle
(spring clips will not fit around cast-iron hanging loop).
Special Tube and Reflector Hanger
7' (2.13 m) Maximum
End Vent
Clips
ROBERTS-GORDON®
Schedule 40 Steel Pipe
End Vent Plate for
End Burner Only
Cast-Iron Adapter
Cast-Iron Combustion Chamber
CORAYVAC® Classic
Cast-Iron Combustion
Chamber
with Schedule 40 Steel Pipe
The total weight of each burner and
combustion chamber is 40.25 lbs (18 kg).
4" Schedule 40 pipe weighs 10.9 lbs.
(5 kg) per foot.
Coupling
End Vent
Clips
ROBERTS-GORDON®
4" Tube
End Vent Plate for
End Burner Only
Cast-Iron Combustion Chamber with
Standard 4" O.D. Infrared Tubing
The total weight of each burner and
combustion chamber is 40.25 lbs (18 kg).
4" O.D. 16 Ga. tubing weighs 2.8 lbs.
(1.3 kg) per foot.
Cast-Iron Adapter
Description
Part Number
Special Tube & Reflector Hanger
Turnbuckle
02790300
91903201
Cast-Iron Combustion Chamber
Cast-Iron Adapter
02721200-1P
02722100
Coupling
01312700
30
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 9: PUMP INSTALLATION AND VENTING
SECTION 9: PUMP INSTALLATION AND VENTING
9.1 Pump Installation
For complete pump installation, please refer to the EP-100, EP-200 or EP-300 Series Installation,
Operation and Service Manuals.
FIGURE 14: EP-200 Condensate Valve Assembly
Description
Condensate Valve Assembly
Part Number
01327001
Wall
1" NPT threaded hole.
Use 1" x ¾" reducer.
(not supplied)
Copper or
galvanized pipe
between pump
and condensate
valve.
36" (.9 m)
Minimum
3/4" female
vertical drop
between pump
and condensate
valve assembly.
Condensate
flow
Valve
Assembly
Must be connected
to a drain system
in accordance with
local codes.
3/4" female
31
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
9.2 General Venting Requirements Model EP-100, EP-200 and EP-300 Series Pumps
WARNING
Carbon Monoxide Hazard
Heaters installed unvented must
be interlocked with sufficient
building exhaust.
Heaters must be installed
according to the installation
manual.
Failure to follow these
instructions can result in death
or injury.
This heater must be vented in accordance with the
rules contained in this manual and with the following
national codes and any state, provincial or local
codes which may apply: United States: Refer to
ANSI Z223.1 (NFPA 54) - latest revision; Canada:
Refer to CAN/CGA-B149.1 and B149.2 - latest
revision.
9.2.2 Horizontal Venting
See Page 34, Figure 16 through Page 36, Figure 18
for recommended horizontal venting options.
9.2.3 United States Requirements
Vent must terminate at least 3' (.9 m) above any
forced air inlet located within 10' (3.1 m).
Any portion of vent pipe passing through a
combustible wall must have an approved thimble
to conform with the above listed codes.
Vent must terminate at least 4' (1.2 m) below,
4' (1.2 m) horizontally from, or 1' (.3 m) above any
door, operable window, or gravity air inlet into any
building.
Vent pipe must be sloped downward away from the
pump ¼'' every 10' (3 m).
9.2.4 Canadian Requirements
The bottom of the vent or air intake terminal shall not
be located less than 1' (.3 m) above grade level.
The vent shall not terminate within 6' (1.8 m) of a
mechanical air supply inlet to any building.
The vent shall not terminate less than 7' (2.1 m)
above grade where located adjacent to public
walkways.
The vent shall not terminate within 3' (.9 m) of a
window or door that can be opened in any building,
any non-mechanical air supply inlet to any building,
or of the combustion air inlet of any other appliance.
Vent terminal must be installed at a height sufficient
to prevent blockage by snow, and building materials
protected from degradation by flue gases.
Length Requirements
See Page 33, Figure 15 through Page 36, Figure 18
for recommended vent lengths and sizes.
Secure all joints with #8 x 3/8 sheet metal screws.
Seal all joints with high temperature silicone sealant.
Seal all pipe joints with high temperature silicone
sealant in the vent pipe. Insulation and additional
sealing measures will be required.
Vent terminal must be beyond any combustible
overhang.
Optional heat exchanger lengths are considered as
vent length for length determination.
9.2.1 Vertical Venting
See Page 33, Figure 15 for recommended vertical
venting options.
Subtract 15' (4 m) of maximum allowed vent or
outside air duct length per vent elbow if more than
three are used.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 9: PUMP INSTALLATION AND VENTING
FIGURE 15: Vertical Venting Configuration
Approved
Vent Cap
2' (.6 m)
Minimum
Approved
Thimble
Flexible Boot
Clamps
1" (2.5 cm)
P.V.C to drain
system in
accordance
with local
Aluminized Tee
Drain Cap
codes.
6"(1.5 cm)
20"(5.1 cm) for EP-300
Part Number
01330203
01330204
01331900
01335801
02718851
02718852
90502300
90502302
90505600
Description
Tee, 4" (10 cm) Aluminized
Part Number
Description
Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
Flexible Boot, 4" (10 cm)
91409403
91409420
91412800
91412801
91412802
91901300
91913703
E0009356
T0100320
Tee, 6" (15 cm) Aluminized
Damper Coupling, 4" (10 cm)
Elbow, 4" (10 cm) Aluminized 90°
Drain Cap, 4" (10 cm)
4 - Flexible Boot, 1/2" (1.3 cm)
Flexible Boot, 6" (15 cm)
Drain Cap Assembly, 6" (15 cm)
Vent Cap, 4" (10 cm) Metalbestos
Vent Cap, 6" (15 cm) Metalbestos
Wall Thimble, 4" (10 cm)
Boot Clamp, 4" (10 cm)
Boot Clamp, 6" (15 cm)
Damper Coupling, 6" (15 cm)
Elbow, 6" (15 cm) Aluminized 90°
33
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
9.3 Horizontal Venting 4" (10 cm) Pipe
FIGURE 16: EP-100 Horizontal Venting Configurations
18" (46 cm) Minimum -
40" (102 cm) Maximum
Bird
Screen
4" (10 cm) Single Wall Pipe
4" (10 cm)
25' (8 m) and 3 Elbows Maximum
Approved Thimbles
Band Clamp
18" (46 cm) Minimum -
40" (102 cm) Maximum
Pitch single wall pipe
downward away from pump
1/4" (6 mm) for every 10' (3 m).
Vent Terminal
Tjernlund VH1-4
6" to 5" Reducer
(15 cm to 12.5 cm)
5" to 4" Reducer
(12.5 cm to 10 cm)
Vent Terminal
Tjernlund VH1-6
5" (12.5 cm) Single Wall Pipe
50' (15 m) and 3 Elbows Maximum
Part Number
01330203
01331900
01335801
01365400
Description
Tee, 4" (10 cm) Aluminized
Part Number
Description
90505600
91409403
91412800
91901300
Wall Thimble, 4" (10 cm)
Damper Coupling, 4" (10 cm)
Elbow, 4" (10 cm) Aluminized 90°
Bird Screen, 4" (10 cm)
Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
Flexible Boot, 4" (10 cm)
Boot Clamp, 4" (10 cm)
02537801-1P Vent Terminal (Non-Combustible Wall)
Not Supplied Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)
Not Supplied Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.
Not Supplied Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.
02718851
90502100
90502101
Drain Cap, 4" (10 cm)
Vent Terminal, 4" (10 cm) (Combustible Wall)
Vent Terminal, 6" (15 cm) (Combustible Wall)
34
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 9: PUMP INSTALLATION AND VENTING
FIGURE 17: EP-200 Series Horizontal Venting Configurations
18" (46 cm) Minimum -
40" (102 cm) Maximum
Bird
Screen
4" (10 cm) Single Wall Pipe
Approved Thimbles
4" (10 cm)
Band Clam
10' (3 m) Maximum and No Elbows
18" (46 cm) Minimum -
40" (102 cm) Maximum
4" (10 cm) Vent Terminal
Pitch single wall pipe
downward away from pump
1/4" (6 mm) for every 10' (3 m).
Vent Terminal
Tjernlund VH1-4
6" to 5" Reducer
(15 cm to 12.5 cm)
5" to 4" Reducer
(12.5 cm to 10 cm)
5" (12.5 cm) Single Wall Pipe
Vent Terminal
Tjernlund VH1-6
25' (8 m) and 3 Elbows Maximum
6" to 4" Reducer
(15 cm to 10 cm)
6" (15 cm) Single Wall Pipe
Vent Terminal
Tjernlund VH1-6
50' (15 m) and 3 Elbows Maximum
Part Number
01330203
01331900
01335801
01365400
Description
Part Number
91409403
91409420
91412801
91418200
91901300
91906900
Description
Tee, 4" (10 cm) Aluminized
Damper Coupling, 4" (10 cm)
Elbow, 4" (10 cm) Aluminized 90°
Bird Screen, 4" (10 cm)
Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
4 - Flexible Boot, 1/2" (1.3 cm)
Tube Adapter, 6" (15.2 cm) dia. x 4" (10 cm) dia.
Boot Clamp, 4" (10 cm)
02537801-1P Vent Terminal (Non-Combustible Wall)
02718851
90502100
90502101
90505600
4" Drain Cap
Silicone Ring
Vent Terminal, 4" (10 cm) (Combustible Wall)
Vent Terminal, 6" (15 cm) (Combustible Wall)
Wall Thimble, 4" (10 cm)
Not Supplied Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)
Not Supplied Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.
Not Supplied Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 18: EP-300 Series Horizontal Venting Configurations
18" (46 cm) Minimum -
40" (102 cm) Maximum
10' (3 m) Maximum and 1 Elbow
6" (15 cm)
Bird Screen
(Included)
Single Wall Pipe/Tube 6" (15 cm)
6" (15 cm)
Band Clamp
Pitch single wall pipe
Approved
downward away from
pump 1/4" ( 6 mm) for
Thimble
every 10' (3 m).
Vent Terminal
Tjernlund VH1-
6" (15 cm)
or Equivalent
(Not Included)
Part Number
01330203
01330204
01331900
01335801
01397400
Description
Tee, 4" (10 cm) Aluminized
Part Number
91409403
91409420
91412800
91412802
91418200
91901300
91913703
E0009356
T0100320
Description
Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
Flexible Boot, 4" (10 cm)
Tee, 6" (15 cm) Aluminized
Damper Coupling, 4" (10 cm)
Elbow, 4" (10 cm) Aluminized 90°
Bird Screen, 6" (15 cm)
Flexible Boot, 6" (15 cm)
Tube Adapter, 6" (15.2 cm) dia. x 4" (10 cm) dia.
Boot Clamp, 4" (10 cm)
02537801-1P Vent Terminal (Non-Combustible Wall)
02718851
02718852
90502100
90502101
90502302
90505600
Drain Cap, 4" (10 cm)
Boot Clamp, 6" (15 cm)
Drain Cap, 6" (15 cm)
Damper Coupling, 6" (15 cm)
Vent Terminal, 4" (10 cm) (Combustible Wall)
Vent Terminal, 6" (15 cm) (Combustible Wall)
Vent Cap, 6" (15 cm) Metalbestos
Wall Thimble, 4" (10 cm)
Elbow, 6" (15 cm) Aluminized 90°
36
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 10: OUTSIDE AIR SUPPLY
SECTION 10: OUTSIDE AIR SUPPLY
The CRV-Series system is approved for use with an
outside air system. Halogenated hydrocarbons or
blower motor has a pressure switch interlock that
must be used. Wire this switch in series with the
other corrosive chemicals in the air can be drawn into pump pressure switch. When using an outside air
blower with a ROBERTS GORDON® System Control
or ROBERTS GORDON® ULTRAVAC™ control or
relay transformer, a separate load relay package is
required. Wire the control for the relay in parallel with
the pump. The outside air blower must have a
separate 20A, 120V power supply. See Page 38,
Figure 21 for outside air blower internal wiring
requirements.
the equipment and seriously damage the system
components. Avoid the use of such chemical
compounds near the air inlet to the heaters.
IMPORTANT: If the building has a slight negative
pressure or contaminants are present in the air, an
outside combustion air supply to the heaters is
strongly recommended.
All joints and seams in the air supply system must be
airtight. Attach the filter housing to the burner
assembly using the wing nut provided.
10.2 Non-Pressurized
For a non-pressurized outside air supply, a 4" (O.D.)
single wall pipe duct may be attached to the burner
and end vent. For length and duct sizing
requirements, see duct design rules in Figure 19. To
prevent condensation, insulate the outside air duct.
10.1 Pressurized
See Page 39, Figure 23 for a typical layout of a
pressurized air supply system.
For pressurized outside air supplies, the outside air
FIGURE 19: Duct Sizing
Outside Air System Design Requirements:
Blower Performance (90707501):
112 Flow Units
One outside air blower is required per each EP-100 or
EP-200 series pump and two outside air blowers may
be required for each EP-300 series pump. Outside air
blowers cannot be shared between two separate CRV-
Series systems.
Duct Design Rules:
- System should be designed so that the blower is
positioned closest to the highest flow
requirements (end vents).
- When a duct is carrying more than 40 flow units, it
must be at least 6" (15 cm) diameter.
Pressurized Systems
- 6" (15 cm) diameter duct must not exceed 120'
(36 m) total per system.
- 4" (10 cm) diameter duct must not exceed 120'
(36 m) per radiant branch.
Non Pressurized
- 6" (15 cm) diameter duct must not exceed 90'
(27 m) maximum 100 flow units
- 4" (10 cm) diameter duct must not exceed 90'
(27 m)
- Elbows are equivalent to 10' (3 m) of duct length.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
10.3 Outside Air Blower Internal Wiring
FIGURE 20: Outside Air Blower Internal Wiring Diagram
Outside air blower is shipped with the blower
manufacturer’s standard internal wiring.
For use with Roberts-Gordon heaters, the
outside air blower must be rewired with existing
wires by the electrical contractor. See diagram.
BLOWER
PRESSURE
SWITCH
C
NO
Internal 24 V transformer provided will not be
used and can be discarded.
MOTOR
BLK
BLU
BLU
WHT
N
L
M
T1 T2 T3
FIGURE 21: Filter Housing Assembly
Door-Control
Housing
Filter
Filter
Support
Bottom Gasket
Filter Housing
Top Gasket
and Disk
Wing Nut
4" (10 cm)
Air Flex Duct
Description
Part Number
01326801
01312401
91905500
92511601
91409601
Filter Housing
Filter and Gaskets
Filter Support
Wing Nut
Clamp
4" (10 cm) Air Flex Duct (box of eight 8' (2.4 m) sections)
38
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 10: OUTSIDE AIR SUPPLY
FIGURE 22: Air Supply Blower Support
5" (12.5 cm)
Inlet Pipe
Outside
Air Supply
Blower
Vent
Cap
or
Bird
Screen
Outside
Wall
5" (12.5 cm)
Outlet Pipe
Wall
Description
Blower
5" (12.7 cm) Vent Cap
6" (15 cm) Bird Screen
6" (15 cm) Band Clamp
Part Number
90707501
90502302
01397400
91913703
FIGURE 23: Pressurized Outside Air Supply
Description
Filter Housing
Part Number
01326801
01324401
90707501
90502301
01365400
91913703
Vent Cap or
Bird Screen
4" (10 cm) Take Off
Blower
5" (12.7 cm) Vent Cap
6" (15 cm) Bird Screen
6" (15 cm) Band Clamp
Burner
Outside
Outside
Air Supply
Wall
Blower
Filter
Housing
4" (10 cm)
Air Flex Duct
Clamp
4" (10 cm)
Take Off
Sheet Metal
or PVC
39
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 24: Non-Pressurized Outside Air Supply
Description
Part Number
90434501
01365400
90502300
90502302
Pressure Switch Kit
4" (10 cm) Bird Screen
4" (10 cm) Vent Cap
6" (15 cm) Vent Cap
Vent Cap
or
Pressure Switch
Bird Screen
Lock Nuts
7/16" (11.1 mm)
Diameter Hole
6' (1.8 m)
Maximum
Outside Wall
40
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 11:GAS PIPING
SECTION 11: GAS PIPING
There is an expansion of the tube with each firing
cycle. This will cause the burner to move with respect
to the gas hose. This can cause a gas leak resulting
in an unsafe condition if the gas connection is not
made in strict accordance with Figure 25.
WARNING
Meter and service must be large enough to handle all
the burners being installed plus any other connected
load. The gas hose which feeds the system must be
large enough to supply the required gas with a
maximum pressure drop of 1/2" w.c. When gas piping
is not included in the layout drawing, the local gas
supplier will usually help in planning the gas piping.
Fire Hazard
Fre Hazard
Tighten gas hose fittings to connect gas supply
according to Figure 25.
Gas hose can crack when twisted.
Gas hose moves during normal operation.
Failure to follow these instructions can result in death,
• Do not high pressure test the gas piping with
the burner connected. Failure to follow these
instructions can result in property damage.
injury or property damage.
• Check the pipe and tubing ends for leaks
before placing heating equipment into
service. When checking for gas leaks, use a
soap and water solution; never use an open
flame.
Install the gas hose as shown in Figure 25. The gas
hose accommodates expansion of the heating system
and allows for easy installation and service of the
burner. Before connecting the burners to the supply
system, verify that all high pressure testing of the gas
piping has been completed.
FIGURE 25: Gas Connection with Flexible Gas Hose
Hold gas nipple securely with pipe
wrench when attaching the gas hose.
Failure to follow these instructions can
result in product damage.
Shut-Off Valve must be
parallel to burner gas
inlet. The 2" (50 mm)
displacement shown is for
the cold condition. This
displacement may reduce
when the system is fired.
3/4" NPT Pipe
Shut-Off Valve
(Included
With Gas Hose)
45°
2" (5 cm)
12"
(30 cm)
Flexible
Gas
Hose
Horizontal
Burner
Rear View
Description
Part Number
91412200
91412203
91412206
91412207
1/2" Flexible Stainless Steel Gas Hose (US Models)
3/4" Flexible Stainless Steel Gas Hose (US Models)
1/2" Rubber (Type 1) Gas Hose (Canadian Models)
3/4" Rubber (Type 1) Gas Hose (Canadian Models)
41
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
12.2 ROBERTS GORDON® ULTRAVACTM
SECTION 12: CONTROL METHODS
The ROBERTS GORDON® ULTRAVACTM is a micro
processor based control package designed for
modulating control of CRV-Series heaters based on
outdoor temperatures. The controls offer full
modulation between 60% and 100% of system
maximum rated input.
WARNING
This controller is capable of giving control outputs to
one pump and three heating zones. The controller
also features inputs which are used for indoor and
outdoor signal condition monitoring.
System status and settings are viewed and altered
from a PC (not supplied) running ROBERTS
GORDON® ULTRAVACTM Software.
Electrical Shock Hazard
Disconnect electrical power and gas supply before
servicing.
This appliance must be connected
to a properly grounded electrical source.
ROBERTS GORDON® ULTRAVACTM Software
requires a PC (not supplied) running Windows® 95 or
higher, with a Pentium® class processor and at least
64k of RAM.
Special design requirements apply for CRV-
Series systems using the ROBERTS GORDON®
ULTRAVACTM Controller.
Failure to follow these instructions can result in
death or electrical shock.
There are several methods of controlling CRV-Series
systems. The options are as follows:
12.1 ROBERTS GORDON® System Control
The System Control is an electronic control panel
designed to control CRV-Series heating systems.
The System Control wiring is shown on Page 46,
Figure 29 through Page 47, Figure 32 and in the
System Control Installation Manual
(P/N 10091601NA). The System Control can be used
to control an EP-100 or EP-201 pump from the control
panel. Other pumps such as the EP-301 and 3 phase
models may be controlled by a relay or motor starter.
The System Control can control up to four zones of
burners.
The electrical circuit is a 120V AC (20A) supply.
The output for the thermostat is 12V DC. Do not use
thermostats that draw power from the low voltage
supply.
A System Control operated system has two minutes
post purge pump operation to completely exhaust
products of combustion from the system. A system
control provides indication of power to the pump and
the zones as well as indicating the status of the
pressure switch with lights.
12.3 SPST Transformer Relay (P/N 90417600)
The transformer relay wiring diagram is shown on
Page 43, Figure 26. The transformer relay can be
used to control an EP-100 or EP-201 pump
CORAYVAC® system. The single pole relay can only
be used to control one zone of burners.
The electrical circuit is a 120V AC (20 A) supply.
The transformer 24V AC output for the thermostat is
rated at 40 V A. Thermostats used with the
transformer must not exceed this power requirement.
A transformer relay operated system will not give any
post purge pump operation to completely exhaust
products of combustion from the system or provide
indication of operating conditions.
12.4 DPST Transformer Relay (P/N 90436300)
The transformer relay wiring diagram is shown on
Page 45, Figure 28. The transformer relay can be
used to control an EP-100 or EP-201 pump
CORAYVAC® system. The double pole relay can only
be used to control two zones of burners.
The electrical circuit is a 120V AC (20A) supply.
The transformer 24V AC output for the thermostat is
rated at 40VA. Thermostats used with the
The System Control is UL listed in accordance with
UL873 – Temperature Indicating and Regulating
Equipment.
transformer must not exceed this power requirement.
A transformer relay operated system will not give any
post purge pump operation to completely exhaust
products of combustion from the system or provide
indication of operating conditions.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 12:CONTROL METHODS
FIGURE 26: One Zone Operation without Control Panel
SPST (12A)
Transformer
Relay
R
C
W
G
Y
Thermostat
Black
1
3
120 V
1 Ø
2
5
4
6
COIL
COIL
60 Hz
L
Black
White
N
Ground
Red
Pump
Motor
L
N
L
N
Zone 1
Burners
Pressure
Switch
(Pump)
Nine Burners Maximum
Description
Part Number
SPST Transformer Relay
90417600
43
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 27: One Zone Operation (with Outside Air Blower) without Control Panel
SPST (12 A)
Transformer
Relay
R
C
W
G
Y
Thermostat
Black
1
3
6
COIL
2
5
4
120 V
1 Ø
COIL
60 Hz
L
Black
White
N
Outside Air
Blower
Ground
N
L
Pressure Switch
(Outside Air Blower)
Red
L
N
L
N
Zone 1
Burners
Pressure
Switch
(Pump)
Pump
Motor
Nine Burners Maximum
44
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 12:CONTROL METHODS
FIGURE 28: Two Zone Operation without Control Panel
DPST (12 A)
DPST (12 A)
Transformer
Relay
Transformer
Relay
R
C
R
C
G
G
W
Y
W
Y
Zone 1
Thermostat
Zone 2
Thermostat
Purple
Red
Red
1
1
3
3
2
2
Purple
4
6
6
4
COIL
COIL
COIL
COIL
5
5
Black
Black
Black
120 V
1 Ø
60 Hz
Red/Yellow
White
White
Red/Yellow
L
Black
N
L
N
L
N
L
N
Zone 1
Burners
Zone 2
Burners
Pump
Motor
Nine Burners Total
Maximum Between Zones
Pressure
Switch
(Pump)
Description
Part Number
DPST Transformer Relay
90436300
45
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 29: General System Wiring
Burner Receptacles
4 Zone Max
Pressure
Switch
Pump Motor
115 Vac Operation
(230 Vac Operation-
separate power circuit
required for EP-203 or
EP-300 series pumps)
Thermostats
Motor Starter
(Needed for EP-203 and EP-300 Series Pump)
Outside
Air Supply
Blower Motor
and Pressure
Switch
120 V
1 Ø
60 Hz
L
N
120 Vac
Maximum 20 Amps Total
FIGURE 30: External Wiring Diagram EP-100 and EP-201 120 V 1 Ø Pump
Pump
All burners must be
connected to Ground
(Not shown)
Zone 1 Zone 2 Zone 3 Zone 4
Low voltage thermostats
located in heated zone
Zone
4
Zone Zone Zone
1
2
3
120 V
1 Ø
Pressure switch
located at pump
60 Hz
L
12 Vdc
N
120 V
1 Ø
60 Hz
Ground
N L
Z1
N L
N L
Z4
N L
Ground
N L
Z3
Z2
PUMP
System Control
46
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 12:CONTROL METHODS
FIGURE 31: External Wiring Diagram EP-301 120 V 1 Ø Pump
EP 301
Pump
Do not directly connect the controller relay
terminals to the pump motor. Product
damage will result.
IEC contactor (P/N
10050009) rated for
the EP 301 pump
motor
All burners must be connected
to Ground. (Not shown.)
Zone 1 Zone 2 Zone 3Zone 4
The power supply for the
6
5
4
3
2
pump must be separate
M
from the controller supply.
1
Individual supply for
pump rated for total
full load current.
230 V
1 Ø
N
L
60 Hz
120 V
1 Ø
60 Hz
120 V
1 Ø
60 Hz
Low voltage thermostats
located in heated zone.
Pressure switch
located at pump.
Zone
4
Zone Zone Zone
1
2
3
L
N
12 Vdc
Ground
Ground
N L N L
Z1
Z2
N L
Z4
N L
Z3
N L
PUMP
System Control
FIGURE 32: External Wiring Diagram EP-203 or EP-303 208 V - 230 V (or 460 V) 3 Ø Pump
EP-203 or
Do not directly connect the
controller relay terminals to the
pump motor. Product damage will
result.
Motor starter (P/N 10050001)
rated for EP-203 pump motor;
motor starter (P/N 10050010)
rated for EP-303 pump motor.
EP- 303 3 Ø Pump
The power supply for the
pump must be separate
from the controller supply.
All burners must be
connected to Ground.
(Not shown.)
OL
208 - 230 V
Zone 1Zone 2 Zone 3 Zone 4
(or 460 V)
3 Ø
M
60 Hz
Individual supply
for pump rated for
L3
L2
L1
total full load current.
120 V
1 Ø
60 Hz
120 V
1 Ø
60 Hz
Low voltage thermostats
located in heated zone.
Zone Zone Zone Zone
1
2
3
4
Pressure switch
located at pump.
L
N
12 Vdc
Ground
Ground
N L N L
Z1
Z2
N L N L
N L
Z3
Z4
PUMP
System Control
47
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 33: Burner Internal Wiring
TRANSFORMER
5
1
Yellow
White
Black
120 V
Power Supply
4
3
Green
Blue
Yellow
Green
TH
GAS
VALVE
Brown
V1
S1
Yellow
V2/GND
Black
IGNITION
MODULE
BURNER
If any of the original wire as supplied with the heater must be replaced, it must be replaced with
wiring material having a temperature rating of at least 105°C and 600 volts.
FIGURE 34: Burner Internal Ladder Diagram
L1
L2
TRANSFORMER
Black
White
Yellow
Blue
Yellow
ELECTRODE
Brown
Black
GAS VALVE
Gap
V2 S1 V1
Gnd
TH
IGNITION
MODULE
48
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 13: STARTING THE SYSTEM
SECTION 13: STARTING THE SYSTEM
Start with the main gas valve closed and the electric
power off.
2. Allow at least ½ hour operation for temperature
to normalize, then check system vacuum bal-
ance. Vacuum can be measured by inserting a
manometer hose into the end vent as shown on
Page 50, Figure 35. Normal end vent vacuum
should be set at approximately 2.5'' w.c. to 3.0''
w.c. (hot).
13.1 Checking the Gas Line
1. Open the main valve and verify that no gas is
flowing through the meter.
2. Purge the line if this was not done following
pressure testing with air.
Vacuum adjustments are made by means of the
damper in the pump inlet and the adjustable
damper coupling(s) in the system. Check the
vacuum at all end vents and then adjust the
damper coupling to obtain equal vacuum
readings of 2.5'' w.c. to 3.0'' w.c. If end vent
vacuum exceeds 3.0" w.c., adjust the pump inlet
damper until vacuum readings are 2.5'' w.c. to
3.0'' w.c.
3. Verify that the gas pressure is not above
14'' w.c. (1/2 PSIG).
4. Close the main gas valve.
13.2 Checking the Electrical System
1. See that all temperature setpoints are set below
room temperature.
2. Turn on power supply to system controls.
With systems designed to operate at maximum
vacuum, it may not be possible to obtain
vacuum differential readings at or slightly above
2.5'' w.c. If so, adjust the damper couplings to
maximum but equal vacuum reading. Be sure to
lock all dampers securely after adjustment.
3. Check to see that no part of the system (i.e.
burners, pump or air supply blower) is powered.
4. Individually check each zone by raising the zone
temperature set points separately. Raising each
zone temperature set point above room
temperature should start the pump immediately.
After a 45 second delay, the burners will begin
their ignition sequence by sparking at the
3. Reset temperature setpoints to desired room
temperature.
electrode (visible through the burner window).
4. If heat is not required, turn off main switch and
close the main gas valve.
5. Make a preliminary vacuum check at burners in
branches that have an adjustable damper
coupling. See Page 50, Figure 35 for manome-
ter hookup to check vacuum. This check is to
insure that all dampers are open before the
system is fired. Vacuum, as measured at the
end vents, should be approximately 3.5'' w.c. or
slightly above (cold).
13.3 Starting the System
NOTE: During the initial firing, the protective oil on
the tubing may smoke for 30 to 60 minutes and
adequate ventilation should be provided.
1. Start with all temperature setpoints below room
temperature.
2. Open main gas valve.
3. Turn up temperature setpoints one zone at a
time, waiting to see that all burners in a zone
start. When the burner ignites, a blue flame will
be observed through the viewer window.
4. If any abnormal operation occurs, see the trou-
bleshooting section of the service instructions.
13.4 Setting the Vacuum
1. Set temperature setpoints above room tempera-
ture. See that all burners are operating properly.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
FIGURE 35: Vacuum Reading
Combustion Chamber
at end position
End Vent
Insert tubing
about 6" (15 cm).
6
5
4
3
2
1
0
1
2
3
4
5
6
Manometer
Approximate reading after
adjusting damper couplings and
~
pump inlet. ( 2.5"- 3.0" w.c.)
~
50
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 14: OPERATION AND MAINTENANCE
SECTION 14: OPERATION AND MAINTENANCE
The heater is equipped with a direct-spark ignition
system.
14.4 Pre-Season Maintenance and Annual
Inspection
14.1 Sequence of Operation
WARNING
1. Turn the thermostat up. When the thermostat
calls for heat, the pump will start immediately.
After a short period, the burners will begin their
ignition sequence. Sparking will begin at the
electrodes and the gas valve will be energized
45 seconds later.
2. The flame will be sensed by the flame sensing
rod and the electrode is de-energized.
Explosion Hazard
Service and annual inspection must be done by a
contractor qualified in the installation and service of
gas-fired heating equipment or your gas supplier.
3. If a flame is detected, the gas valve
remains open. When the call for heat is
satisfied, the burner shuts off. On CRV-Series
systems equipped with the optional ROBERTS
GORDON® System Control, or ROBERTS
GORDON® ULTRAVACTM, the pump will
continue operation for a post-purge period of
two minutes.
Turn off gas and electrical supplies before performing
service or maintenance.
Failure to follow these instructions can result in death,
injury or property damage.
To ensure your safety and years of trouble-free
operation of the heating system, service and annual
inspections must be done by a contractor qualified in
the installation and service of gas-fired heating
equipment.
Turn off gas and electric supplies before performing
service or maintenance. Allow heater to cool before
servicing.
4. If no flame is detected, the module will close and
a purge period begins. If a flame is not
established, a second purge and warm-up will
take place and then a third trial cycle will begin.
After three trials, the module will lockout for one
hour or until reset.
5. A reset is accomplished by removing power
from the module for at least 5 seconds (thermo-
stat cycle is required) or automatically after 1
hour.
Before every heating season, a contractor qualified in
the installation and service of gas-fired heating
equipment must perform a thorough safety
inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, tubing, venting, suspensions and
overall heater condition should be thoroughly
inspected.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please see Page 52, Section 14.5 for suggested
items to inspect.
14.2 To Shut Off Heater
Set thermostat to lowest setting.
Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.
14.3 To Start Heater
Turn gas valve and electric power OFF and wait five
minutes for unburned gases to vent from heater.
Turn ON main gas valve.
Turn ON electric power.
Set thermostat to desired temperature.
Burner should light automatically.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
14.5 Maintenance Checklist
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON®
products must be performed by a contractor qualified
in the installation and service of products sold and
supplied by Roberts-Gordon and conform to all
requirements set forth in the ROBERTS GORDON®
manuals and all applicable governmental authorities
pertaining to the installation, service and operation of
the equipment. To help facilitate optimum
WARNING
Explosion Hazard
performance and safety, Roberts-Gordon
Service and annual inspection must be done by a
contractor qualified in the installation and service of
gas-fired heating equipment or your gas supplier.
recommends that a qualified contractor annually
inspect your ROBERTS GORDON® products and
perform service where necessary, using only
ROBERTS GORDON® replacement parts.
Turn off gas and electrical supplies before performing
service or maintenance.
Failure to follow these instructions can result in death,
injury or property damage.
The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heating sys-
tem. Immediately remove these items if they are present.
See Page 3, Section 3.
Vehicles and Other
Objects
Maintain the clearances to combustibles.
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).
Immediately remove objects in violation of the clearances to combustibles.
See Page 3, Section 3.
Reflector
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. See Page 19, Figure 7.4.3.
Clean outside surface with a damp cloth.
Vent Pipe
Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe or gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
Outside Air Inlet
Inlet must be intact. Look for obstructions, cracks on the pipe or gaps in the
sealed areas or corrosion.
The area must be free of dirt and dust. Clean and reinstall as required.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 14: OPERATION AND MAINTENANCE
Tubes
Make sure there are no cracks.
Make sure tubes are connected and suspended securely.
See Page 15, Figure 12 through Page 17, Section 7.2.1.
Make sure there is no dirt, sagging, bending or distortion.
Clean or replace as required.
Gas Line
Check for gas leaks. See Page 41, Figure 25.
Combustion Chamber
Window
Make sure it is clean and free of cracks or holes.
Clean or replace as required.
Blower Scroll, Wheel and Compressed air or a vacuum cleaner may be used to clean dust and dirt.
Motor
Burner Head and Orifice
Electrode
Make sure it is clear of obstructions. (Even spider webs will cause problems).
Carefully remove any dust and debris from the burner.
Replace if there are cracked ceramics, excessive carbon residue, or erosion
of the electrode.
The electrode gap should be 1/8" (3 mm).
Thermostat or Sensor
Suspension Points
There should be no exposed wire or damage to the thermostat or sensor.
Make sure the heater is hanging securely. Look for signs of wear on the chain
or ceiling.
See Page 15, Figure 12.
Decorative and Protective The grille must be securely attached.
Grille (optional)
Check that side reflector extensions are installed correctly and secured in
place if necessary. (Decorative grille only.)
See Page 25, Section 8.6.1 through Page 28, Section 8.7.5
Make sure shield is installed correctly and secured in place if necessary.
(Decorative grille only.) See Page 25, Section 8.6.2.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Pump
With pump operating, check for excessive vibration or noise. Vibration is usu-
ally a sign that the impeller is out of balance. Turn off the system, insure
power is shut off and remove the inlet plate. Check the shaft seal and replace
it if worn or missing.
With the Power off:
Check the inlet and outlet of the pump for blockage or excessive soot and
clean as necessary.
Check boots for cracking or deterioration and replace if necessary.
If a condensate trap is installed, check the condition of the trap and the drain
line attached. Note: the condensate trap should be filled with water at the
beginning of each heating season.
Check the condition of the motor mounts. Lift the motor from the rear; look for
breaks in the rubber and replace if necessary.
Check the condition and operation of the pressure switch.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION15:TROUBLESHOOTING
SECTION 15: TROUBLESHOOTING
15.1 Troubleshooting Flow Chart
55
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
Troubleshooting Flow Chart
56
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 16: REPLACEMENT PARTS
SECTION 16: REPLACEMENT PARTS
Use only genuine ROBERTS GORDON® replacement parts.
Use of parts not specified by Roberts-Gordon voids warranty.
Failure to follow these instructions can result in property damage.
Gasket (Burner to Mixing Chamber)
F
O F
Transformer
O N
Burner Head
Mixing Chamber
Ignition Module
Ignition Cable
Regulator
Electrode
Electrode Gasket
Combustion
Chamber
Gasket
Gas Valve
Description
Part Number
Gas Valve (All Burners)
Gasket (Burner to Mixing Chamber)
Burner Head Assembly Replacement Package
Mixing Chamber
Transformer
Regulator
Gasket (Combustion Chamber)
Electrode Replacement Kit (includes electrode, electrode gasket and mounting screws)
Ignition Module
90032502
01351100
02713000
02790400
90436900K
90207100
01367800
02713200
90439500
90427706
01312401
Ignition Cable
Filter Cartridge with Gasket (not shown)
57
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
SECTION 17: GENERAL SPECIFICATIONS
17.1 Material Specification
17.3 Suspension Specifications
17.1.1 Reflectors
Hang heater with materials with a minimum working
load of 75 lbs (33 kg). See Page 15, Figure 12.
.024 Aluminium (Optional - 024 Stainless Steel Type 304).
17.2 Heater Specifications
17.4 Controls Specifications
Time switches, thermostats, etc. can be wired into
the electrical supply. External controls supplied as an
option.
17.2.1 Ignition
Fully Automatic, Three-Try, Direct Spark, Electronic
Ignition Control, 100% Safety Shut-Off.
General Specifications for CRV-Series heaters are as follows:
Length "A"
9 1/2"
(24 cm)
6 1/2"
(16 cm)
10 3/4"
(27 cm)
4"
(10 cm)
6 7/8"
(17 cm)
7 5/8"
(19 cm)
Reflector
3 1/2"
(9 cm)
10"
(24.4 cm)
5/32"
(.4 cm)
14 1/4"
(36 cm)
20"
(51 cm)
Recommended Minimum
Heat Input Rate
Length “A”
Mounting Height*
Spot Heating
8' (2.4 m)
Model
(Btu/h) x (1000)
Minimum
Maximum
20' (6.1 m)
25' (7.6 m)
35' (10.7 m)
45' (13.7 m)
50' (15.2 m)
60' (18.3 m)
70' (21.3 m)
70' (21.3 m)
CRV-B-2 (NG only)
CRV-B-4
20
40
10' (3 m)
12.5' (3.8 m)
20' (6.1 m)
20' (6.1 m)
25' (7.6 m)
30' (9.1 m)
35' (10.7 m)
35' (10.7 m)
8' (2.4 m)
CRV-B-6
60
8' (2.4 m)
CRV-B-8
80
10' (3 m)
CRV-B-9
90
10' (3 m)
CRV-B-10
100
110
120
15' (4.5 m)
15' (4.5 m)
15' (4.5 m)
CRV-B-12A (NG only)
CRV-B-12 (LP only)
*See Page 3, Section 3 for clearances to combustibles.
PIPE CONNECTION:
1/2" NPT
DIMENSIONS:
Vent Connection Size: 4" (10 cm) or 6" (15 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.
GAS INLET PRESSURE:
Natural Gas: 4.5" w.c. Minimum 14.0" w.c. Maximum
LP Gas: 10.5" w.c. Minimum 14.0" w.c. Maximum
ELECTRICAL RATING:
120 V - 60 Hz, 0.3 A
58
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 17: GENERAL SPECIFICATIONS
General Specifications for pumps are as follows:
Pump Dimensional Data (in.)
Model
EP-100
EP-201/203
EP-301/303
A
17
17.75
25.6
B
14.5
17
C
21
20.25
22.7
D
E
10
10
F
4
4.5
6
G
4
4.5
6
G
A
3.75
3.25
4.8
D
E
24.8
15.2
B
C
F
dia.
Pump Specifications
Model
EP-100
1/3
EP-201
3/4
EP-203
EP-301
EP-303
Horsepower (Hp)
Phase (Ø)
3/4
2*
1
2*
1
1
3
60
3
Hertz (Hz)
60
60
60
60
Voltage (V)
115/230
4.8/2.4
3450
56
115/230
6.6/3.3
3450
56
208-230/460
2.4-2.2/1.1
3500
208-230
208-230/460
Full Load Amp (Amps)
R.P.M.
12.8-11.5
3450
90
5.5-5.2/2.6
3450
90
Motor Frame
56
Motor Enclosure
Noise Level @ 5' (DBA)
Inlet/Outlet (In.)
Weight (lbs.)
TENV
-
TENV
70
TEFC
TEFC
-
TEFC
-
70
4/4
4/4
4/4
6/6
6/6
170
62
112
112
170
* For starter, see National Electric Code (NEC) requirement for motors 1 hp or higher.
Air Supply Blower Specifications
Capacity
240 CFM @ 0.75 in wc
Power (W)
167
1
Phase
Hertz (Hz)
60
Voltage (V)
Full Load Amp (Amps)
R.P.M.
120
1.5
3000
OPEN FC
5/5
Motor Enclosure
Inlet/Outlet (In.)
Weight (lbs.)
10
59
Download from Www.Somanuals.com. All Manuals Search And Download.
CRV-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
60
Download from Www.Somanuals.com. All Manuals Search And Download.
SECTION 18: THE ROBERTS GORDON® CORAYVAC® LIMITED WARRANTY
SECTION 18: THE ROBERTS GORDON® CORAYVAC® LIMITED WARRANTY
The data plate and/or serial number are removed,
ROBERTS-GORDON WILL PAY FOR:
defaced, modified or altered in any way.
Within 42 months from date of shipment from Roberts-
Gordon, replacement parts will be provided free of
charge for any part of the product which fails due to a
manufacturing or material defect.
Roberts-Gordon will require the part in question to be
returned to the factory. Roberts-Gordon will, at its sole
discretion, repair or replace after determining the nature
of the defect and disposition of part in question.
The ownership of the CORAYVAC® is moved or
transferred. This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged
controller and/or component parts.
READ YOUR INSTALLATION, OPERATION AND
SERVICE MANUAL
ROBERTS GORDON® warrants the cast iron
combustion chamber of the CORAYVAC® Classic
System will be free from defects in material and
workmanship. This warranty is limited to twenty-five
(25) years from the date of shipment by Roberts-
Gordon. All other components of the CORAYVAC®
Classic System adhere to the standard warranty listed
in the paragraph above.
ROBERTS GORDON® Replacement Parts are
warranted for a period of 18 months from date of
shipment from Roberts-Gordon or the remaining
CORAYVAC® warranty.
If you have questions about your controller, contact your
installing professional. Should you need Replacement
Parts or have additional questions, call or write Roberts-
Gordon:
U.S.A.
1250 William Street
P. O. B ox 4 4
Buffalo, New York 14240-0044
716.852.4400
On the web at: www.rg-inc.com
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Roberts-Gordon's liability, and your exclusive remedy,
under this warranty or any implied warranty (including
the implied warranties of merchantability and fitness
for a particular purpose) is limited to providing
replacement parts during the term of this warranty.
Some jurisdictions do not allow limitations on how long an
implied warranty lasts, so this limitation may not apply to
you. There are no rights, warranties or conditions,
expressed or implied, statutory or otherwise, other than
those contained in this warranty.
Claims where the total price of the goods have not
been paid.
Damage due to:
• Improper installation, operation or maintenance.
• Misuse, abuse, neglect, or modification of the
CORAYVAC® in any way.
• Use of the CORAYVAC® for other than its intended
purpose.
Roberts-Gordon shall in no event be responsible for
incidental or consequential damages or incur liability
for damages in excess of the amount paid by you for
the CORAYVAC®. Some jurisdictions do not allow the
exclusion or limitation of incidental or consequential
damages, so this limitation or exclusion may not apply to
you. This warranty gives you specific legal rights, and you
may also have other rights which vary from jurisdiction to
jurisdiction.
• Incorrect gas or electrical supply, accident, fire,
floods, acts of God, war, terrorism, or other casualty.
• Improper service, use of replacement parts or
accessories not specified by Roberts-Gordon.
• Failure to install or maintain the CORAYVAC® as
directed in the Installation, Operation and Service
Manual.
• Relocation of the CORAYVAC® after initial
installation
• The use of the CORAYVAC® in a corrosive
atmosphere containing contaminants.
• The use of the CORAYVAC® in the vicinity of a
combustible or explosive material.
Roberts-Gordon shall not be responsible for failure to
perform under the terms of this warranty if caused by
circumstances out of its control, including but not limited to
war, fire, flood, strike, government or court orders, acts of
God, terrorism, unavailability of supplies, parts or power.
No person is authorized to assume for Roberts-Gordon
any other warranty, obligation or liability.
• Any defect in the CORAYVAC® arising from a
drawing, design, or specification supplied by or on
behalf of the consumer.
LIMITATIONS ON AUTHORITY OF
REPRESENTATIVES:
• Damage incurred during shipment. Claim must be
filed with carrier.
No representative of Roberts-Gordon, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon's duly authorized
Executive Officer.
WARRANTY IS VOID IF:
The CORAYVAC® is not installed by a contractor qualified
in the installation and service of gas fired heating
equipment.
You cannot prove original purchase date and required
annual maintenance history.
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
®
OWNER WARRANTY REGISTRATION CARD
Mail or Fax to:
Roberts Gordon, LLC •1250 William Street, P.O. Box 44 • Buffalo, NY 14240-0044 • Phone: 716-852-4400 • Fax: 716-852-0854
About the Owner:
Name:
Address:
Phone:
City:
City:
City:
State:
State:
State:
Zip Code:
Zip Code:
Fax:
E-mail:
E-mail:
E-mail:
About the Installer:
Name:
Address:
Phone:
Fax:
Purchased From (if different than installer):
Name:
Address:
Phone:
Zip Code:
Fax:
About your Heater:
Model#:
Serial #:
Fuel:
Installation Date:
Type of Installation (check one):
o Automotive
o Public Building
o Manufacturing
o Office
o Warehouse
o Retail
o Recreational
o Agricultural
o Aircraft
o Other
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® products must be performed by a
contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements
set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and
operation of the equipment.
To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your
ROBERTS GORDON® products and perform service where necessary, using only ROBERTS GORDON® replacement parts.
This product is not for residential use.
This product is intended to assist licensed professionals in the exercise of their professional judgement.
© 2006 Roberts-Gordon, LLC - All rights reserved. No part of this work covered by the copyrights herein my be reproduced or copied
in any form or by any means – graphic, electronic, or mechanical, including photcopying, recording,
taping, or information storage and retrieval systems – without written permission of
Roberts Gordon, LLC. Printed in the U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Attach this information to a wall near the ROBERTS GORDON® heater.
®
I n f r a r e d H e a t i n g
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration.
Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual.
Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
WARNING
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
TO TURN OFF THE HEATER
1. Set the thermostat to off or the lowest setting.
Fire Hazard
IFTHE HEATER WILL NOT OPERATE, TO ENSUREYOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
to heater.
Some objects can catch fire or explode when placed close
Keep all flammable objects, liquids and vapors the required
1. Set the thermostat to off or the lowest setting.
clearances to combustibles away from heater.
2. Turn off electric power to the heater.
Failure to follow these instructions can result in death,
injury or property damage.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation
and service of gas-fired heating equipment.
Maintain ???? cm clearance
to the side and
???? cm clearance below
the heater from vehicles
and combustible materials.
Roberts-Gordon Europe Limited
Service Telephone: +44(0) 1902 498733
Service Fax: +44(0) 1902 401464
Roberts-Gordon, LLC
1250 William Street
Oxford Street
Bilston, West Midlands WV14 7EG UK E-mail: uksales@rg-inc.com
Telephone: +44(0) 1902 494425
Fax: +44(0) 1902 403200
P.O. Box 44
E-mail: export@rg-inc.com
Buffalo, NY 14240-0044 USA
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON® products must be performed by a contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements set forth
in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon
recommends that a qualified contractor annually inspect your ROBERTS GORDON® products and perform service where necessary, using only ROBERTS GORDON® replacement parts.
© 2006 Roberts-Gordon, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying,
recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon, LLC.
Printed in U.S.A.
P/N 91037912 Rev. C
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Radio Shack Two Way Radio 21 417 User Guide
Rival Food Saver VS110 User Guide
Ryobi Trimmer RY41002A User Guide
Samsung All in One Printer CLX 8540ND User Guide
Samsung MP3 Player YP 90S User Guide
Samsung Stereo System AH68 02272Y User Guide
Samsung Washer C1035 User Guide
Sanyo Battery Charger CR1 3N User Guide
Sanyo Computer Monitor VMC 7321P User Guide
Schlage Door 609 User Guide