Owners &
P42 Gas Fireplace
Installation Manual
MODELS: P42-NG4 Natural Gas P42-LP4 Propane
WARNING:
FOR YOUR SAFETY
Iftheinformationintheseinstructionsarenotfollowedexactly, What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fire department.
a fire or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-523a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
03/06/08
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
SAFETY LABEL
OPERATING INSTRUCTIONS
Copy of Safety Decal.....................................................4
Optional Remote Control.............................................34
Optional Wall Switch....................................................34
Optional Wall Thermostat ...........................................34
Operating Instructions .................................................34
Lighting Procedure ......................................................34
Copy Of The Lighting Plate Instructions.....................35
REQUIREMENTS
MA Code - CO Detector ................................................5
INSTALLATION
MAINTENANCE
Important Message ......................................................6
Before You Start ............................................................6
General Safety Information ...........................................6
Installation Checklist......................................................6
Manufactured Mobile Home Additional Requirements ..7
Locating Your Gas Fireplace .........................................7
Unit Specifications.........................................................7
Heatwave Optional Duct System Kit#946-556 .............7
Optional Hearth .............................................................7
Clearances ....................................................................8
Mantels..........................................................................8
Mantel Leg Clearances .................................................8
Framing And Finishing...................................................9
Top Assembly & Nailing Strips.......................................9
Venting Introduction.......................................................9
Vent Restrictor...............................................................9
Exterior Vent Termination Requirements.....................10
Venting ........................................................................11
4” x 6-5/8” Rigid Pipe Cross Reference Chart.............12
Rigid Pipe Venting.......................................................14
Horizontal Terminations..............................................15
Vertical Terminations ...................................................17
Installation Procedures................................................23
High Elevation .............................................................24
Gas Line Installation....................................................24
Gas Pipe Pressure Testing..........................................24
Aeration Adjustment ....................................................25
Brick Panels ................................................................25
Log Set Installation......................................................26
Standard Flush Door ...................................................27
Flush Louvers..............................................................27
Double Screen Doors .................................................27
Optional Bay Door.......................................................28
Bay Louvers ................................................................28
Full Screen doors ........................................................29
Wiring Diagrams .........................................................32
Normal Operating Sounds Of Gas Appliances............36
Shutdown Procedure...................................................36
First Fire ......................................................................36
Maintenance Instructions ............................................36
Gold-Plated Louvers....................................................37
Log Replacement ........................................................37
Thermopile / Thermocouple.........................................37
Glass Replacement.....................................................37
Door Glass ..................................................................37
Removing The Fan......................................................38
Replacing The Fan ......................................................38
Removing Valve...........................................................38
Installing Valve.............................................................39
PARTS LIST
Main Assembly ............................................................40
Burner & Log Assembly...............................................41
Flush Door & Louvers..................................................42
Bay Front & Louvers....................................................43
WARRANTY
Warranty......................................................................47
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY LABEL
This is a copy of the label that accompanies each P42 Zero Clearance
Direct Vent Gas Fireplace. We have printed a copy of the contents here
for your review. The safety label is located on the front inside base of
the unit, visible when the bottom louver is open.
NOTE: Regency® units are constantly being improved. Check the label
on the unit and if there is a difference, the label on the unit is the correct
one.
COPY OF SAFETY DECAL FOR P42
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm
with battery back up in the same room where the gas appliance is installed.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
4
Download from Www.Somanuals.com. All Manuals Search And Download.
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
IMPORTANT MESSAGE
SAVE THESE
CLOTHINGOROTHERFLAMMABLE
MATERIALSHOULDNOTBEPLACED
ON OR NEAR THE APPLIANCE.
INSTRUCTIONS
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
TheP42-NG/P42-LPDirectVentFireplacemust
beinstalledinaccordancewiththeseinstructions.
Carefully read all the instructions in this manual
first.Consultthe"authorityhavingjurisdiction"to
determine the need for a permit prior to starting
the installation. It is the responsibility of the
installer to ensure this fireplace is installed in
compliancewithmanufacturersinstructionsand
all applicable codes.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform
with local codes or, in the absence of local
codes,withthecurrentCanadianorNational
Gas Codes, CAN1-B149 or ANSI Z223.1
Installation Codes.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
INSTALLATION
CHECKLIST
2) The appliance when installed, must be
electrically grounded in accordance with
localcodes, orintheabsenceoflocalcodes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
BEFORE YOU START
1) Locate appliance, refer to the following
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
sections:
a) Locating Your Gas Fireplace
b) Clearances
c) Mantels
d) Mantels Legs Clearance
e) Framing and Finishing
3) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
INSTALLATION AND REPAIR
SHOULD BE DONE BY AN
AUTHORIZED SERVICE PERSON.
THE APPLIANCE SHOULD BE
INSPECTED BEFORE USE AND
AT LEAST ANNUALLY BY A
PROFESSIONALSERVICEPERSON.
MORE FREQUENT CLEANING MAY
BEREQUIREDDUETOEXCESSIVE
LINTFROMCARPETING,BEDDING
MATERIAL, ETC. IT IS IMPERATIVE
THATCONTROLCOMPARTMENTS,
BURNERS AND CIRCULATING
AIR PASSAGEWAYS OF THE
APPLIANCE BE KEPT CLEAN.
4) This appliance must be connected to the
specified vent and termination cap to the
outsideofthebuildingenvelope.Nevervent
to another room or inside a building. Make
sure that the vent is fitted as per Venting
instructions.
2) Assemble Top Facing Support and Side
Nailing Strips, see the "Top Assembly
& Nailing Strips" section. NOTE: must
be done before installing unit into
fireplace.
3) Install venting, refer to the "Venting"
5) Inspect the venting system annually for
section.
blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into 4) Make gas and electrical connections. Test
a wall or siding.
the pilot. Must be as per diagram. See the
"Pilot Adjustment" section.
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
5) Test Gas Pressure. Refer to the "Gas Pipe
Pressure Testing" section.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
6) Install standard and optional features.
Refer to the following sections where
applicable:
DUETOHIGHTEMPERATURES,THE
APPLIANCESHOULDBELOCATED
OUTOFTRAFFICANDAWAYFROM
FURNITURE AND DRAPERIES.
9) Wearglovesandsafetyglassesforprotection
a. Brick Panels
b. Log Set
while doing required maintenance.
WARNING: FAILURE TO INSTALL
THISAPPLIANCECORRECTLYWILL
VOID YOUR WARRANTY AND MAY
CAUSE A SERIOUS HOUSE FIRE.
c. Standard Flush Door
d. Flush Louvers
e. Double Screen Door
f. Bay Door
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
g. Bay Louvers
11) Under no circumstances should this
appliancebemodified. Partsthathavetobe
removed for servicing should be replaced
prior to operating this appliance.
h. Full Screen Front
i. Remote Control
j. Wall Switch
CHILDREN AND ADULTS SHOULD
BEALERTEDTOTHEHAZARDSOF
HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE
GLASS, AND SHOULD STAY AWAY
TO AVOID BURNS OR CLOTHING
IGNITION.
k. Wall Thermostat
12) Installationandanyrepairstothisappliance
should be done by an authorized service
person.Aprofessionalservicepersonshould
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
11) Final check.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
firing correctly and operation fully explained
to customer.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
13) Do not slam shut or strike the glass door.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
6
INSTALLATION
This includes:
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
1) Clockingtheappliancetoensurethecorrect
firingrate(ratenotedonlabel35,000Btu/h)
after burning appliance for 15 minutes.
HEATWAVE
OPTIONAL DUCT
SYSTEM KIT
#946-556
2) If required, adjusting the primary air to
ensure that the flame does not carbon.
First allow the unit to burn for 15-20 min.
to stabilize.
2) Provide adequate clearances for
servicing.
CAUTION:Anyalterationtotheproductthat
causes sooting or carboning that results
in damage is not the responsibility of the
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, metal,
concrete).Thismaybethefloor,orraisedup
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
flooring,theappliancemustbeinstalledona
metal or wood panel extending the full width
and depth of the appliance.
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warmairfromthefireplacetoremotelocationsin
the same room or other rooms in your home.
manufacturer.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
MANUFACTURED
MOBILE HOME
ADDITIONAL
OPTIONAL
HEAT RELEASE KIT
#946-570
4) The P42 Direct Vent Gas Fireplace can be
installedinarecessedpositionorframedout
into the room as in A, B, C, D. See Diagram
1.
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
The Heat Release Kit expels warm air from
the fireplace to the outside of the building,
allowing the fireplace to be operated with less
heat entering the room. The kit may be used on
either the left or right side.
2) Ensure proper grounding using the #8
ground lug provided. See the "Wiring
Diagram" section.
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into
Wall/Alcove
UNIT SPECIFICATIONS
HEARTH
Ahearth is not mandatory, but is recommended
for aesthetics and for added safety.
D) Corner
5) This appliance is Listed for bedroom
installationswhenusedwithaListedMillivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P42 Direct Vent Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) Werecommendthatyouplanyourinstallation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For vent terminations see the
"ExteriorVentTerminationLocations"
section.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
7
INSTALLATION
MANTELS
CLEARANCES
Because of the extreme heat this fireplace emits, the mantel clearances are critical.
Combustible mantel clearances from louver are shown in the diagram below.
The clearances listed below are Minimum
distances unless otherwise stated:
Note: A non-combustible mantel may be installed at a lower height if the framing is made
of metal studs covered with a non-combustible board.
A major cause of chimney related fires is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fireplace and
vent system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back
Side
Floor
0"
0"
0"
(0mm)
(0mm)
(0mm)
Minimum Clearance from Louver to:
Mantel
Ceiling
min. 7" (177mm)
36"
(914mm) from top
of louvers
Side Wall
Vent
6"
1-1/2"
1-1/4"
(152mm)
(38mm) Flex
(32mm) Rigid Pipe
Alcove Clearances:
Max. Depth 36"
(914mm)
(1321mm)
(2286mm)
Min. Width
52"
Min. Height 90"
This drawing is to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area using the above scale for units with the Flush
Front and with the optional Bay Front.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the
paint may discolour.
WARNING
Fire hazard is an extreme risk
if these clearances are
not adhered to.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram below:
The HeatWave Duct Kit
and the Heat Release
Kit have different
clearance and framing
requirements, check
Heat Release Kit
theHeatWaveandHeat
Release manual for
details.
Maximum
1-1/2" projection at 2"
minimum clearance.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Position of Top Facing Support
for material depth of 3/4” to 1-1/2"
5) The unit does not have to be completely
enclosed in a chase. The clearance on top
of the unit from the top standoffs is 0" so
combustible building materials can be laid
directly on top of the standoffs. You must
maintain these clearances from the vent
to combustible materials: Flex Termination
clearance1-1/2"(38mm),SimpsonDura-Vent
clearance or (1-1/4" (32mm). Combustible
materials can be laid against the side and
back standoffs and the fireplace base.
FRAMING AND
FINISHING
1) Determine the total thickness of facing
material (ie. drywall plus ceramic tiles) to
allow the finished surface to be flush with
the front of the unit. Total facing thickness
canvaryfrom1/2"(13mm)to1-1/4"(32mm)
thick.
Top Facing
Support
Diagram 3
2) Frame in the enclosure for the unit with
framing material. The framed opening for
the assembled kit is 36-5/8" high x 40-1/4"
wide x 19" deep (930mm H x 1022mm W
x 483mm D). See Diagram 1.
Diagram 4
The HeatWave Duct Kit has different
clearance and framing requirements,
check the HeatWave manual for details.
b) Mount the Side Nailing Strip using the 3
supplied screws into the 3 screw holes
or slots (diagram 4) on the side of the
unit and repeat for the other side. Use
the hole for a 1/2" (13mm) thick facing
material and the slot for a range of
thickness from 3/4" to 1-1/2" (25mm to
38mm).
TOP ASSEMBLY &
NAILING STRIPS
The Top Facing Support and Side Nailing Strips
mustbecorrectlypositionedandattachedbefore
the unit is slipped into position.
Diagram 1
VENTING
INTRODUCTION
1) The top standoffs are shipped installed.
The P42 uses the "balanced flue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer
liner draws outside combustion air into the
combustion chamber thereby eliminating the
needtouseheatedroomairforcombustionand
losing warm room air up the chimney.
2) The Top Facing Support and the 2 Side
Nailing Strips can be installed at different
depthsdependingonthewidthofyourfacing.
Match the depths of the top facing support
and the side nailing strips.
a) Mount Top Facing Support using the 3
supplied screws into the 3 pre-punched
screw holes on the top front of the unit.
See Diagrams 2 & 3 for the proper
position of the Top Facing Support for
the various material depths.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Eachdirectventgasappliancemustuseit'sown
separate vent system. Common vent systems
are prohibited.
VENT RESTRICTOR
A vent restrictor may be required. Check
the diagrams in the "Rigid Pipe Venting
Arrangements" section to determine if the #6
restrictor is needed for your vent configuration.
If required, attach the 2 piece #6 restrictor
using 4 screws per piece to the inside top of
the firebox.
Diagram 1
Note: 43"(1092mm)istheminimumheight
for flex termination and Rigid Pipe
terminations.
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per
local installation codes. (Do not insulate
the fireplace itself.)
4) The top louvers must not be closer than
36" (914mm) to the ceiling.
Diagram 2
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
9
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
10
INSTALLATION
VENTING
Regency® Direct Vent System (Flex) Horizontal Terminations Only
These venting systems, in combination with the P42 Direct Vent Gas
1) 6-7/8" dia. flexible liner (4 ft. length)
2) 4" dia. flexible liner (4 ft. length)
3) spring spacers (4)
Fireplace, have been tested and listed as a direct vent heater system
by Warnock Hersey. The location of the termination cap must conform to
the requirements in the Vent Terminal Locations diagram in the "Exterior
Vent Termination Locations" section.
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
Regency® Direct Vent (Flex) System Termination Kit (Part # 946-515)
includes all the parts needed to install the P42 with a maximum
run of 4 feet.
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1/2" Drill Point, stainless steel (4)
Wall Thimble (2 pc)
4" (102mm)
dia. flue pipe
AstroCap
Termination Cap
Part #946-523/P
6-7/8"
(173mm) dia.
Flue pipe
spring
spacer
Note:
If longer runs are needed, the Regency® Direct Vent system (Flex)
# 946-516 includes all the parts needed to install the P42 with a
maximum 10' run.
a) Liner sections should be continuous without any joints or seams.
b) Only Flex pipe purchased from Regency® may be used for Flex
Installations.
1) 6-7/8" dia. flexible liner (10 ft. length)
2) 4" dia. flexible liner (10 ft. length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1/2" Drill Point, stainless steel (4)
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
11
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Simpson
American Metal
Simpson
Metal-Fab®
Security
Selkirk
Direct Vent GS®
Products®
Description
Direct Vent Pro®
Sure Seal
Secure Vent®
Direct-Temp™
Amerivent Direct
Discontinued
46DVA-06
908
4DT-6
N/A
4D6
SV4L6
SV4LB6
N/A
6” Pipe Length, Galvanized
6” Pipe Length, Black
7” Pipe Length, Galvanized
7” Pipe Length, Black
9” Pipe Length, Galvanized
9” Pipe Length, Black
12” Pipe Length, Galvanized
12” Pipe Length, Black
18” Pipe Length, Galvanized
18” Pipe Length, Black
24” Pipe Length, Galvanized
24” Pipe Length, Black
36” Pipe Length, Galvanized
36” Pipe Length, Black
48” Pipe Length, Galvanized
48” Pipe Length, Black
46DVA-06B
N/A
908B
N/A
4DT-6B
N/A
N/A
4D6B
N/A
4D7
4D7B
N/A
N/A
N/A
N/A
N/A
N/A
46DVA-09
46DVA-09B
46DVA-12
46DVA-12B
46DVA-18
46DVA-18B
46DVA-24
46DVA-24B
46DVA-36
46DVA-36B
46DVA-48
46DVA-48B
46DVA-60
46DVA-60B
907
4DT-9
N/A
N/A
907B
906
4DT-9B
4DT-12
4DT-12B
4DT-18
4DT-18B
4DT-24
4DT-24B
4DT-36
4DT-36B
4DT-48
4DT-48B
N/A
N/A
N/A
N/A
4D12
4D12B
N/A
4D12
4D12B
4D18
4D18B
4D24
4D24B
4D36
4D36B
4D48
4D48B
N/A
SV4L12
SV4LB12
SV4LA
SV4LA
SV4L24
SV4LB24
SV4L36
SV4LB36
SV4L48
SV4LB48
N/A
906B
N/A
N/A
N/A
904
4D2
4D2B
4D3
4D3B
4D4
4D4B
N/A
904B
903
903B
902
902B
N/A
60” Pipe Length, Galvanized
60” Pipe Length, Black
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
911B
N/A
N/A
4DAL
4DALB
N/A
N/A
Adjustable Length 3”-10”, Galvanized
Adjustable Length 3”-10”, Black
Adjustable Length 11”-14”, Galvanized
Adjustable Length 11”-14”, Black
Adjustable Length 17”-24”, Galvanized
Adjustable Length 17”-24”, Black
Adjustable Length 7”, Galvanized
Adjustable Length 7”, Black
Extension Pipe 8-1/2”, Galvanized
Extension Pipe 8-1/2”, Black
Adjustable Length 12”, Galvanized
Adjustable Length 12”, Black
N/A
N/A
N/A
N/A
Disc - See 46DV-08A
Disc - See 46DV-08AB
Disc - See 46DV-16A
Disc - See 46DV-16AB
N/A
4DT-AJ
4DT-AJB
N/A
N/A
N/A
N/A
N/A
917 - N/A from FPI N/A
N/A
N/A
N/A
917B
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SV4LBA24
N/A
4D7A
4D7AB
N/A
N/A
N/A
N/A
N/A
46DVA-08A
46DVA-08AB
N/A
N/A
N/A
N/A
N/A
N/A
4D12A
4D12AB
N/A
N/A
SV4LA12
SV4LBA12
N/A
N/A
N/A
46DVA-16A
46DVA-16AB
N/A
Extension Pipe 16”, Galvanized
Extension Pipe 16”, Black
N/A
N/A
N/A
46DVA-E45
945
4DT-EL45
4DT-EL45B
N/A
4D45L
4D45LB
N/A
N/A
N/A
45º Elbow, Galvanized
45º Elbow, Black
45º Elbow, Swivel, Galvanized
46DVA-E45B
945B
945G
N/A
N/A
Disc - See 46DVA-E45
4D45L
SV4E45
Disc - See 46DVA-
E45B
945BG
N/A
N/A
4D45LB
SV4EB45
45º Elbow, Swivel, Black
46DVA-E90
990
4DT-EL90S
4DT-EL90SB
N/A
4D90LS
4D90LBS
N/A
N/A
N/A
90º Elbow, Galvanized
90º Elbow, Black
90º Elbow, Swivel, Galvanized
46DVA-E90B
990B
990G
N/A
SV4EBR90-1
SV4E90-1
Disc - See 46DVA-E90
4D90L
Disc - See 46DVA-
E90B
990BG
N/A
N/A
4D90LB
SV4EB90-1
90º Elbow, Swivel, Black
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
4D90A
4DDA
N/A
N/A
90º Starter Elbow, Swivel, Galvanized*
Adaptor*
N/A
949 - N/A from FPI 4DT-CS
4DFSP
4DRSB
4DWS
N/A
4DSP
4DRS
4DWS
N/A
SV4SD
SV4CSB
SV4BM
SV4SU
SV4RSM
SV4PF
SV4BF
SV4LA
N/A
Ceiling Support
Cathedral Support Box
Wall Support/Band
Offset Support
Wall Thimble, Black
Wall Thimble Support Box/Ceiling Support
Firestop Spacer
Trim Plate, Black
Masonry Chimney Flashing
Brass Trim for Wall Thimble/Ceiling Support
46DVA-CS
46DVA-WS
46DVA-ES - N/A from FPI
46DVA-WT
46DVA-DC
46DVA-FS
N/A
941
988
4DT-CSS
4DT-WS/B
989 - N/A from FPI 4DT-OS
942
N/A
963
N/A
N/A
3951
4DT-WT
N/A
4DWT
N/A
4DWT
N/A
4DT-FS
4DT-TP
N/A
4DFSP
4DFPB
N/A
4DFS
4DCP
N/A
N/A
DISC.
N/A
N/A
N/A
N/A
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
12
INSTALLATION
4” x 6-5/8” Rigid Pipe Cross Reference Chart (Cont.)
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Simpson
American Metal
Simpson
Metal-Fab®
Security
Selkirk
Direct Vent GS®
Products®
Description
Direct Vent Pro®
Sure Seal
Secure Vent®
Direct-Temp™
Amerivent Direct
Discontinued
46DVA-IS - N/A from FPI
N/A
N/A
N/A
4DAIS12
4DAIS36
N/A
N/A
SV4RSA
N/A
Attic Insulation Shield 12”
Attic Insulation Shield - Cold Climates 36”
N/A
N/A
DISC.
46DVA-KHA
(Changed Components)
DISC.
970
971
978
4DT-HKA
4DT-HKB
4DT-VKC
4DHTK2
4DHTK1
4DVTK
4DHTKA
4DHTKB
4DVTK
SV - SHK
SV - HK
SV - FK
Basic Horizontal Termination Kit (A)
Horizontal Termination Kit (B)
Vertical Termination Kit
46DVA-VCH
46DVA-HC
991
985
984
980
953
N/A
N/A
N/A
N/A
High Wind Vertical Cap
High Wind Horizontal Cap
Horizontal Square Termination Cap
Vertical Termination Cap
Storm Collar
N/A
N/A
N/A
N/A
Disc - See 46DVA-HC
46DVA-VC
4DT-HHC
4DT-HVC
4DT-SC
4DHC
4DVC
4DSC
4DHT
4DVT
4DSC
SV4CHC-1
SV4CGV-1
SV4FC
46DVA-SC
46DVA-F6
943
4DT-AF6
4DF
4DF
SV4FA
SV4FB
Adjustable Flashing, 0/12-6/12
Adjustable Flashing, 6/12-12/12
46DVA-F12
943S
4DT-AF12
4DF12
4DF-12
46DVA-VSS
N/A
950
N/A
4DT-VS
N/A
N/A
4DVS
N/A
SV4VS
SV4VS
Vinyl Siding Standoff
Vinyl Siding Shield Plate
4DT-VSP
46DVA-SNK14
N/A
982
981
4DT-ST14
4DT-ST36
4D12S
4D36S
4DST14
4DST36
SV4STC14
SV4STC36
Snorkel Termination 14”
Snorkel Termination 36”
46DVA-RD
929
930
931
932
933
934
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Restrictor Disk
46DVA-VCE
46DVA-KCA
46DVA-KCB
46DVA-KCC
46DVA-KMC
Extended Vertical Termination Cap
Chimney Conversion Kit A
Chimney Conversion Kit B
Chimney Conversion Kit C
Chimney Conversion Kit Masonry
Mansonry Chimney Conversion Kit
(includes: Cap Adapter 18”x18” Flashing)
46DVA-KCT
935
N/A
N/A
N/A
N/A
46DVA-WFS
46DVA-ADF
947
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Wall Firestop
Colinear Flex Connectors
923F
FPI
946-506/P
510-994
Vent Guard (Optional) for AstropCap
Rigid Pipe Adapter (Must use with all Rigid Piping)
Riser Vent Terminal
946-205
Vinyl Siding Shield for Riser Vent Terminal
Vent Guard (Optional) for Riser Vent Terminal
AstroCap Horizontal Cap
946-208/P
946-523/P
946-206
640-530/P
Vinyl Siding Standoff for AstroCap
*NOTE: When using Metal-Fab Sure Seal Rigid Piping please note that either the Adaptor (4DDA) or 90º Starter Elbow (4D90A)
must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection:
Use this table to determine offset pipe lengths.
For specific instructions or details on particular
4” x 6-5/8” Venting
venting components please visit the following
websites:
Pipe Length
Run (X)
Rise (Y)
Simpson Direct Vent Pro: www.duravent.com
0”(0mm)
4-7/8”(124mm)
8”(203mm)
13-3/8”(340mm)
16-1/2”(419mm)
18-5/8”(473mm)
6”(152mm)
9”(229mm)
L
American Metal Products Amerivent Direct:
10-1/8”(257mm)
Y
12”(305mm)
24”(610mm)
36”(914mm)
48”(1219mm)
12-1/4”(311mm)
20-5/8”(524mm)
29”(737mm)
20-3/4”(527mm)
29-1/8”(740mm)
37-1/2”(953mm)
45-15/16”(1167mm)
37-7/16”(951mm)
X
NOTE: Horizontal runs of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards
the termination. Never allow the vent to run downward. This could cause high temperatures and
may present a possible fire hazard.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
RIGID PIPE VENTING
Horizontal or Vertical Terminations
The Rigid Pipe Venting System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are
offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the P42.
Wall thickness is measured from the back
Alternate
Horizontal
Termination Caps
The minimum components required for a basic
horizontal termination are:
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mount the vent terminal. The Terminal must
not be recessed into siding. Measure the wall
thickness including furring strips.
1
1
1
1
1
Horizontal Termination Cap
90o Elbow
Flue Adaptor
Wall Thimble
Length of pipe to suit wall thickness
(see chart)
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
Vertical
Terminal
Storm Collar
Part # 953
Vinyl Siding
Standoff (Optional)
Part #950
Flashing
943 or 943S
WARNING:
Do not combine venting components from
different venting systems.
Ceiling Firestop
(Part # 963)
Horizontal
Termination
Cap
TM
However use of the the AstroCap and FPI
Riser is acceptable with all systems.
Wall Thimble
Part # 942
ThisproducthasbeenevaluatedbyIntertekfor
using a Rigid Pipe Adaptor in conjunction with
DuraventDirect-VentGS,SelkirkDirect-Temp,
Ameri Vent Direct venting and Security Secure
Vent systems. Use of these systems with the
Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
Pipe Length
Adj.Pipe Length
11" - 14-5/8"
90o Elbow
24" Pipe
Length
Flat Wall Installation
Wall Thickness
Vent Length
(inches)
Required (inches)
Rigid Pipe Adaptor
(Part# 510-994)
4" - 5-1/2"
7" - 8-1/2"
10" - 11-1/2"
9" - 14-1/2"
15" - 23-1/2"
6"
9"
12"
11" - 14-5/8" Adj. Pipe
17" - 24" Adj. Pipe
Corner Installation
Wall Thickness
(inches)
Vent Length
Required (inches)
3-1/4" - 6-3/4"11" - 14-5/8" Adj. Pipe
7-3/4" - 16-1/4"
7-1/4" - 8-3/4"
17" - 24" Adj. Pipe
6" + 12"
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
9" + 9"
6" + 9"
4-1/4" - 5-3/4"
The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS,
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
14
INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
REGENCY® DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas)
The shaded areas in the diagram show all allowable combinations of vertical runs with horizontal terminations. The chart below shows the
distances with one 90o bend (two 45o elbows equal one 90o elbow). For a second 90o bend, see the "Rigid Pipe Venting Arrangements - Horizontal
Terminations" section.
A vent guard may be required, check local codes.
Note: Must use optional rigid pipe adaptor (Part # 510-994)
Minimum height
requirement
when using rigid pipe venting systems.
Rigid Pipe Systems:
4"(100mm) inner diameter
6-5/8"(168mm) outer diameter
Regency® Flex:
4"(100mm) inner diameter
6-7/8"(175mm) outer diameter
• Rigid Pipe Systems: Maintain a 1-1/4"(32mm) clearance to combustibles
• Regency® Flex: Maintain a 1-1/2"(38mm) clearance to combustibles
• Horizontal vent must be supported every 3 feet (0.9 meter)
• Firestops are required at each floor level and whenever passing through a wall
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
15
INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
REGENCY® DIRECT VENT SYSTEM (FLEX) - Propane & Natural Gas
The diagram below shows examples of horizontal termination arrangements using two 90o elbows.
Note:
1) A maximum of two 90o elbows are permitted (two 45o elbows equal one 90o elbow).
2) A minimum of 6 ft.(1.8m) vertical from base of unit is required if two 90o elbows are used.
3) Minimum distance between elbows is 2 ft. (0.6m).
If length "B" is increased, length "A" must be decreased by a corresponding amount.
For All Horizontal Terminations
All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter
Regency® Flex Vent
4" inner diameter
6-7/8" outer diameter
A vent guard may be required, check local codes.
•
Maintain a 1-1/4" clearance to
combustibles for rigid pipe systems
and 1-1/2" for Regency® Flex Vent.
Horizontal vent must be supported
every 3 feet
Firestops are required at each floor
level and whenever passing through
a wall.
•
•
Note: Regency®DirectVentSystem(Flex)isonly
approved for horizontal terminations.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
16
INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
(Propane & Natural Gas)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset
TheP42isapprovedfora 37ft. (11.3m)straight
vertical, including a 20" (0.5m) horizontal offset
using two 90o elbow (two 45o elbows equal one
90o elbow) with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram
to the right.
to vertical terminations with rigid pipe vent systems for Propane and Natural Gas.
Maximum two 45o elbows allowed.
•
•
Vent restrictor #6 must be used in shaded area in diagram below.
Vent must be supported at offsets
•
•
Vent restrictor #6 is required for
terminations in shaded area.
Vent must be supported at offsets.
Note: Must use optional rigid pipe adaptor
when using rigid vent systems (Part
# 510-994).
Note: Regency® Direct Vent System (Flex)
is only approved for horizontal
terminations.
Diagram 1
Diagram 2
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
17
INSTALLATION
The P42 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset
using two 90o elbows (two 45o elbows equal one 90o elbow) with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram below.
TheP42isapprovedfora 37ft. (11.3m)straight
vertical,withrigidpipeventsystemsforPropane
and Natural Gas, as per the diagram below.
•
•
No Vent restrictor is required.
Vent must be supported at offsets
•
Vent restrictor #6 must be used
Diagram 3
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
Diagram 4
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
18
INSTALLATION
VERTICAL TERMINATION
WITH CO-LINEAR FLEX SYSTEM
Masonry chimneys may take various contours which the flexible liner will accommodate. However,
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.
keep the flexible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium flex running
the full length of the chimney. See the Venting
Arrangements on next page for minimum and
maximum heights.
Co-linear DV
Vertical Termination
Cap # 946-529
A maximum
of two certified
joiner kits
may be used
per length.
#948-305 (35 ft)
Required Parts:
Part #
Description
946-529
Co-linear DV Vertical
Termination Cap
Flex Liner
948-305
946-563
3" Flex - 35 ft.
Co-Axial to Co-Linear Adapter Kit
which contains the following:
Co-linear Flex Adapter
Outer Pipe
Inner Pipe Adapter
Rigid Pipe Adaptor
510-994
Alternate Approved Caps
Exhaust
Flue
980
991
Vertical Termination Cap
High Wind Cap
923GK 3" Co-linear Adapter with flashing
Outer
Pipe
FPI Cabinet and/or Flat Wall Mantles may
be used in these applications ensuring
that clearances to combustibles are
maintained.
with Kit#
946-563
Air Intake
Pipe Length
Co-Linear
Flex
Adapter
with Kit#
Rigid Pipe Adapter
946-563
# 510-994
90 Degree
Elbow
Inner Pipe
Adapter
with Kit#
946-563
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
19
INSTALLATION
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
with Co-linear Flex System for both
Residential & Manufactured Homes
into Masonry Fireplaces
The shaded area in the diagrams show the allowable vertical terminations.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
20
INSTALLATION
b) Horizontal runs of vent must be
supported every 3 feet (0.9meter). Wall
straps are available for this purpose.
*Diagrams 3, 3a & 4: As
HORIZONTAL
specified in CGA B149
Installation Code. Local
codes or regulations
TERMINATIONS
5) Mark the wall for a 10" x 10" (254mm x may require different
254mm) square hole. The center of the clearances.
square hole should line up with the center-
1) Set the unit in its desired location. Check
to determine if wall studs or roof rafters
are in the way when the venting system is
attached. If this is the case, you may want
to adjust the location of the unit. Rough in
the gas preferably on the right side of the
unit and the electrical (junction block is on
the left side) on the left.
lineofthehorizontalpipe.Cutandframethe
10inch (254mm)squareholeintheexterior
wall where the vent will be terminated.
If the wall being penetrated is constructed
of non-combustible material, i.e. masonry
blockorconcrete,a7"(178mm)diameter(7-
1/2" (190mm) for flex) hole is acceptable.
2) DirectVentpipeandfittingsaredesignedwith
specialtwist-lockconnectionstoconnectthe
ventingsystemtotheapplianceflueoutlet.A
twist-lock appliance adaptor is an available
option that must be used in conjunction with
the Simpson Dura-Vent Direct Vent GS
system. Install the adaptor after the unit is
set in its desired location otherwise the unit
will not fit through the 36-5/8" (930mm) high
frame opening.
Diagram 3
Note: Riser Vent
is only for use
in above grade
terminations.
3) Put a bead of silicone inside the outer
section of the adapter and a bead of Stove
Mate on the inner collar. Slip the adapter
over the existing inner and outer flue collar
and fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will
make this easier). Level the fireplace and
fasten it to the framing using nails or screws
through the nailing strips.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Diagram 2
Note:
Note:
a) Thehorizontalrunofventmustbelevel,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the vent to run downward. This
couldcausehightemperaturesandmay
a) Twist-lockprocedure:Fourindentations,
locatedon thefemaleendsofpipesand
fittings, are designed to slide straight
onto the male ends of adjacent pipes
and fittings, by orienting the four pipe
indentations so they match and slide in
to the four entry slots on the male ends.
(Diagram 1) Push the pipe sections
completely together, then twist-lock
one section clockwise approximately
one-quarter turn, until the two sections
arefullylocked.Thefemalelockinglugs
will not be visible from the outside, on
the Black Pipe or fittings. They may be
located by examining the inside of the
female ends.
Diagram 3a
Below Grade Installation
present the possibility of a fire.
If the Snorkel Termination must be installed
below grade, i.e. basement application,
proper drainage must be provided to prevent
water from entering the Snorkel Termination.
Refer to Diagram 4.
b) The location of the horizontal vent
termination on an exterior wall must
meet all local and national building
codes, and must not be blocked or
obstructed. For External Vent Terminal
Locations, see diagram in the "Exterior
Vent Termination Locations" section.
Do not attempt to
enclose the Snorkel
within the wall, or
anyothertypeof
enclosure.
c) Snorkel Terminations:
For installations requiring a vertical rise
on the exterior of the building, 14-inch
and 36-inch tall Snorkel Terminations
(diagram 3 & 4) are available, as well
as the standard Riser Vent, diagram 3a.
Followthesameinstallationprocedures
as used for standard Horizontal
Termination. NEVER install the snorkel
upside down.
Diagram 1
NOTE: For best results and optimum
performance with each approved venting
system, it is highly recommended to apply
“Mill-Pac” sealant (supplied) to every in-
ner pipe connection. Failure to do so may
result in drafting or performance issues not
covered under warranty. Silicone (red RTV)
is optional.
NOTE: For Snorkel terminations in ABOVE
gradeinstallations,follownationalor
local code requirements.
Diagram 4
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
21
INSTALLATION
6) The arrow on the vent cap should be 9) Install wall thimble in the center of the 10"
pointing up. Insure that the 1-1/4"(32mm)
clearances to combustible materials
are maintained (Diagram 5). Install the
termination cap.
(254mm) square and attach with wood
screws (Diagram 6).
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or furring strips must be used to
ensure that the termination is not
recessed into the siding.
Diagram 3
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
Diagram 7
VERTICAL
TERMINATIONS
1) M a i n t a i n t h e 1-
1/4"(32mm) clearances
( a i r
s p a c e s )
t o
combustibles when
passing through ceilings,
walls, roofs, enclosures,
atticrafter,orothernearby
combustible surfaces.
Do not pack air spaces
with insulation. Check
the "Rigid Pipe Venting
Arrangements"sectionfor
themaximumverticalrise
oftheventingsystemand
the maximum horizontal
offset limitations.
NOTE: For best results and optimum
performance with each approved venting
system, it is highly recommended to apply
“Mill-Pac” sealant (supplied) to every in-
ner pipe connection. Failure to do so may
result in drafting or performance issues not
covered under warranty. Silicone (red RTV)
is optional.
Diagram 5
The four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet
the minimum requirements for clearance
to combustibles of 1-1/4"(32mm). Slip the
flashing under the shingles (shingles should
overlap half the flashing) as per Diagram 4.
7) Before connecting the horizontal run of vent
pipe to the vent termination, slide the Wall
Thimble (Part # 942) over the vent pipe.
2) S e t t h e g a s
appliance in its
desired location.
Drop a plumb bob
down from the
8) Slide the appliance and vent assembly
towards the wall carefully inserting the
vent pipe into the vent cap assembly. It is
important that the vent pipe extends into the
vent cap sufficient distance so as to result
in a minimum pipe overlap of 1-1/4 inches
(32mm).Securetheconnectionbetweenthe
vent pipe and the vent cap by attaching the
two sheet metal strips extending from the
vent cap assembly into the outer wall of the
vent pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 6.
Diagram 1
ceiling to the position of the appliance flue
exit,andmarkthelocationwheretheventwill
penetrate the ceiling. Drill a small hole at his
point.Next,dropaplumbbobfromtheroofto
the hole previously drilled in the ceiling, and
mark the spot
where the vent
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
willpenetratethe
roof. Determine
if ceiling joists,
roof rafters or
other framing
6) Continue to assemble pipe lengths.
will obstruct the
venting system.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the vent pipe every 3
feet (0.9 meter), to avoid excessive
stress on the elbows, and possible
separation. Wall straps are available
for this purpose
You may wish
to relocate the
appliance or to
offset, as shown
i n
t o
D i a g r a m
2
avoid cutting
Diagram 2
load bearing members.
(Diagram 2).
3) A Firestop spacer must be installed in the
floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling or wall, cut
a 10 inch (254mm) square hole. Frame the
hole as shown in Diagram 3 and install the
firestop.
Galvanizedpipeisdesirableabovetheroofline
duetoitshighercorrosionresistance.Continue
to add pipe sections through the flashing until
the height of the vent cap meets the minimum
heightrequirementsspecifiedinDiagram5or
local codes. Note that for steep roof pitches,
the vertical height must be increased.
Diagram 6
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
22
INSTALLATION
3) Assemble the vent assembly by applying
Mill Pac to the 4"(100mm) inner collar of the
terminationand slippingthe4"(100mm)liner
over it at least 1-3/8" (35mm). Fasten with
the3screws(drillingpilotholeswillmakethis
easier). Apply Mill Pac or high temperature
silicone to the 6-7/8"(175mm) flex pipe and
slip it over the 6-7/8" outer collar of the vent
terminal at least 1-3/8"(35mm) and fasten
with the 3 screws.
INSTALLATION
PROCEDURES
for Regency® Direct Vent
System (Flex)
Diagram 5
1) Locate the unit in the framing, rough in the
gas (preferably on the right side of the unit)
and the electrical (Junction block is on the
left side) on the left. Locate the centerline of
the termination and mark wall accordingly.
Cut a 10"(254mm) hole in the wall (inside
dimension).
Roof Pitch
flat to 7/12
Minimum Vent Height
Feet
2
2
Meters
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
NOTE: Horizontal sections must be
supportedatintervalsnotexceeding
3 feet (0.9 meter). (Flame picture and
performance will be affected by sags
in the liner).
over 7/12 to 8/12
over 8/12 to 9/12
2
Note: To make
the installation
more aesthetically
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
2.5
3.25
4
5
6
7
7.5
8
4) Separatethe2halvesofthewallthimbleand
securely fasten the one with the tabs to the
outside wall making sure that the tabs are
on top and bottom. Fasten the other thimble
half to the inside wall. The thimble halves
slip inside each other and can be adjusted
for 2 x 4 or 2 x 6 walls. The liners must slip
over the collars a minimum of 1-3/8".
p l e a s i n g ,
w e
recommendframing
out
a
square to
mount the terminal
to.
5) Slip the assembled liner and termination
assembly through the thimble making sure
the termination cap faces up (there are
markings on the cap that show which way
is up). This will position the termination cap
with proper down slope for draining water.
Fasten the cap to the outer wall with the 4
supplied screws.
A poor draft, or down drafting can result
from high wind conditions near big trees
or adjoining roof lines, in these cases,
increasing the vent height may solve the
problem.
Note: A 1-1/2"(38mm) clearance around
the liner must be maintained except
that only a 1" (25mm) clearance is
needed at the termination end. We
recommend framing a 10"(254mm) x
10"(254mm)(insidedimensions)hole
togivestructuralrigidityformounting
the termination.
7) Ensure vent is vertical and secure the base
of the flashing to the roof with roofing rails,
slide storm collar over the pipe section and
seal with a mastic.
6) Pull the centre 4"(100mm) liner and outer
6-7/8"(175mm) liner out enough to slip over
the flue collars of the fireplace. (You may
wish to cut the liner shorter to make it more
workable.) Do not bend liner more than
90o.
Note: If installing termination on a siding
covered wall, furring strips must be
used to ensure that the termination
is not recessed into the siding.
8) Install the vertical termination cap by twist-
locking it.
Note: Anyclosetsorstoragespaces,which
the vent passes through must be
enclosed.
2) Levelthefireplaceandfastenittotheframing
using nails or screws through the nailing
strips.
7) Apply Mill Pac over the fireplace inner collar
and slip the 4"(100mm) liner down over it
and attach with 3 supplied screws.
Offset Chart
8) Do the same with the 6-7/8"(175mm) liner.
9) Applyabeadofsiliconebetweenthethimble
and termination and around the outer edge
of the terminal at the wall in order to keep
the water out.
IMPORTANT:
Do not locate termination hood where
excessive snow or ice buildup may
occur.Besuretocheckventtermination
area after snow falls, and clear to
prevent accidental blockage of venting
system. When using snow blowers,
makesuresnowisnotdirectedtowards
vent termination area.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
23
INSTALLATION
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID
hose.
GAS LINE
System Data
INSTALLATION
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas Propane
4) Light the pilot and turn the valve to "ON"
The gas line can be brought through either the
right or the left side of the appliance. The gas
valve is situated on the right hand side of the
unit and the gas inlet is on the right hand side
of the valve.
position.
Burner
#33
#50
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
Max. Input Rating
- Natural Gas
- Propane
35,000 Btu/h
35,000 Btu/h
Note: If the gas line is being installed from
the left side, be sure to leave room to
accommodate servicing of the fan.
6) When finished reading manometer, turn
off the gas valve, disconnect the hose
and tighten the screw (clockwise) with a
1/8"(3mm) flat screwdriver. Note: Screw
should be snug, but do not over
tighten.
Min. Input Rating
-Natural Gas
-Propane
17500 Btu/h
17500 Btu/h
The gas line connection may be made of rigid
pipe,copperpipeoranapprovedflexconnector.
(If you are using rigid pipe, ensure that the valve
can be removed for servicing.) Since some
municipalities have additional local codes it is
alwaysbesttoconsultwithyourlocalauthorities
and the CAN/CGA B149 installation code.
Output Capacity with blower Off
Natural Gas
Propane
25,725 Btu/h
26,740 Btu/h
S.I.T. Valve Description
Output Capacity with blower On
Natural Gas
Propane
26,250 Btu/h
27,300 Btu/h
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
Supply Pressure
Natural Gas
Propane
min. 5.0" w.c.
min. 11.0" w.c.
When using copper or flex connectors use only
approvedfittings.Alwaysprovideaunionsothat
gas lines can be easily disconnected for burner
or fan servicing. Flare nuts for copper lines and
flex connectors are usually considered to meet
this requirement.
7) Pilot Outlet
8) Main Gas Outlet
Manifold Pressure (High)
9) Alternative TC Connection Point
Natural Gas
Propane
3.8" +/- 0.2" w.c.
10" +/- 0.2" w.c.
Electrical: 120 V A.C. System.
Circulation Fan: variable speed
130 CFM.
Important:Alwayscheckforgasleakswitha
soapandwatersolutionorgasleakdetector.
Do not use open flame for leak testing.
Log Set: Ceramic fibre, 3 per set.
Vent System: Simpson Dura-Vent
Direct Vent System or Regency®
Direct Vent System (Flex)
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig (3.45 kPa).
Note: Output capacity. The efficiency rating
of the appliance is a product thermal efficiency
rating determined under continuous operating
conditions and was determined independently
of any installed system. Vent height may or may
not change your efficiency ratings.
Themanifoldpressureiscontrolledbyaregulator
builtintothegascontrol,andshouldbechecked
at the pressure test point.
HIGH ELEVATION
Note: Toproperlycheckgaspressure,both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
This unit is approved in Canada for altitude 0
to 4500 ft. (CAN1 2.17-M90) with the orifice
supplied.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a 1/8"
(3mm) wide flat screwdriver.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
24
INSTALLATION
AERATION
BRICK PANELS
ADJUSTMENT
6) Rest the narrow end of the top brick panel
on top of the back wall brick panel. Then,
with both hands, lift the top panel up.
1) Unhook the 2 spring loaded hooks from the
bottom of the flush door and lift the Flush
Front off the unit.
The aeration adjustment gears are located on
the valve mounting plate and are accessed
from underneath through the bottom louver
opening.
7) Slotthetopmetalchannel1/2wayintoplace
2) Unwrap the brick pattern panels from the
protectivewrapping.Handlethepanelswith
care as they can break easily.
onto the top of the panel.
Toaccesstheairshutterloosenthelocknutand
then use the allen key to turn the turning gear
which will adjust the air shutter. Open the air
shutter for a blue flame or close it for a yellower
flame. Tighten the lock nut when adjustment is
complete. The burner aeration is factory set but
may need adjusting due to either the local gas
supply or altitude.
8) Carefully position and push the top panel
intoposition.Makesurethetabsofthemetal
channel fit into the baffle openings (refer to
Diagram 2). Push downwards to secure the
channel and top panel.
Note: The logs must not be in the unit.
3) Remove the metal channel from the firebox
top, and use it later for installing the top
brick panel (refer to Diagram 1).
Tab
Tab
CAUTION: Carbon will be produced if air
shutter is closed too much. (Should be
3/16"(4mm) open for natural gas and 1/2"
(13mm) for propane.)
Metal
Channel
Note: Aeration Adjustment should only be
performedbyanauthorizedRegency®
Installer at the time of installation or
service.
Diagram 1
Diagram 2
4) Insert the back brick panel first by carefully
slipping it between the back wall of the
firebox and the rear log bracket.
9) Ensureallpanelsaresecurelyinplace(refer
to Diagram 3).
5) Insert the side panels. Tilt them in towards
the middle of the firebox and put the bottom
front corner in first. Be very careful not to
scratchthemonthefireboxhardware.Place
them flat up against the wall, they should fit
snugly against the top of the firebox.
Diagram 3
(front)
(back)
IMPORTANT: Dangerousoperating
conditions may occur if the panels
are broken.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
25
INSTALLATION
LOG SET INSTALLATION
WARNING: Dangerous operating conditions may occur if these logs are not positioned in their correct certified locations. Read the
following instructions carefully and refer to the attached diagram.
The log kit contains the following:
5) Place the front logs in the unit, aligning the holes on the underside
of the logs with the log support pins in the front of the unit. Carefully
push the logs down onto the pins. (Hint: Install the front right side
first.)
a)
b)
c)
d)
e)
f)
Front Right Log
Front Left Log
Rear log
Embers
6) Place a few embers under the front logs and a few under the front
Rockwool
part of the burner assembly to make it look like fallen embers.
Vermiculite
g)
Platinum Embers (supplied with packaged manual)
7) Test for pilot ignition.
1) Remove the logs from the box and carefully unwrap them. The logs
8) Install the door and louvers.
are fragile, handle with care. Do not force into position.
2) Place the rear log on the rear log support in the back of the unit with
the flat side of the log facing the back of the unit. Carefully push the
log down onto the pins.
NATURAL GAS
3) Sprinkle the vermiculite on the sides and front of the fireplace bot-
tom being careful not to get any into the air shutter or the burner
ports (burner ports are the little holes in the top of the burner). The
vermiculite is used to cover the sheet metal and hardware on the
firebox floor and burner assembly.
4) Pull off ember size pieces of rockwool and separate platinum em-
bers and gently place them around the burner. Do not compress the
rockwool or platinum embers, leave it loose for the most realistic
looking embers. Refer to the diagrams below for correct placement
of rockwool and platinum embers on the Natural Gas and Propane
units.
Burner tray without
front logs in place
PROPANE
IMPORTANT
Completed Log Set Installation
For Propane Units - only place rockwool and platinum embers
on the rear burner tray behind the burner tube.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
26
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
STANDARD
DOUBLE SCREEN
DOORS
FLUSH LOUVERS
1) Install the top louver by sliding the two
bracket clips into the brackets located
underneath the top of the firebox. Diagram
1.
FLUSH DOOR
The standard flush door comes with a black
frame. To install the frame, simply hook the top
door flange onto the top of the unit and swing
the door towards the unit, diagram 1.
1) Pull out the top louver.
2) Center the screen door and hook over the
flush door.
2) Attach the 2 bottom louver hinges to the
bottom flange on the firebox using 2 screws
per hinge. Diagram 1.
Diagram 1
Note: Top and bottom louvers are
different.
Diagram 1
3) Open the screen door(s) and secure the
screen door to the flush door front with 2
clips on the bottom left and right side.
Be careful that the glass gasket does not roll
up;theremustbeagapbetweenthegasketand
the door lip to ensure that the door sits securely
on the unit. Diagram 2.
3) Attach the bottom louver to the 2 hinges
using 2 screws per hinge. Diagram 2.
Diagram 2
Clip locations
Use the hook to pull the spring out until you
can put the hook into the slot on the bottom
door bracket. Repeat for 2nd and 3rd spring.
See diagram 3.
Diagram 2
Clip installed on right side.
Diagram 3
NOTE: Springs must always be OVER
not under the gas line.
To remove the flush door, reverse the above
steps.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
27
INSTALLATION
4) Reconnect the 2 spring hooks securing the
flush door.
OPTIONAL BAY DOOR
BAY LOUVERS
The Bay louvers MUST be used
1) Install top louver by sliding the two bracket
clips into the brackets located on top of the
baydoor.Seebelow.Thefittedlouverleaves
a small gap between faceplate bottom and
louver top.
Note: If any maintenance etc. must be
done in the firebox, first remove the
Bay louvers and door.
with the Bay glass option.
The optional Bay door is an overlay on the
flush front. The standard flush door and glass
must remain on the unit.
Optional Bay Trim
1) Unhook the 2 spring loaded hooks from the
bottom of the flush door.
Attach 4 supplied magnets each to the back of
the top and bottom trim pieces, and attach trim
to the top and bottom of Bay door.
2) Hook the top of the bay door over the flush
door flange and swing the bottom against
the bottom flange of the flush door.
Note: Top and bottom louvers and
brackets are different.
2) Install bottom louver by sliding the two
bracket clips into the brackets located
underneath the bay door. Install bottom
louverbyslidingthetwobracketclipsintothe
brackets located underneath the bay door
and secure with 1 screw on each end.
3) Slide the valve extension knobs onto the
valve knobs.
3) Securetotheflushdoorbottombracketwith
2 screws provided.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
28
INSTALLATION
FULL SCREEN DOORS
1) Before beginning the installation, remove the Glass Door from the
b) Slide the cut-outs in the Top and Bottom Flange of the Full Screen
Door Frame under the screw heads which were loosened in step
3a. Once the Frame is in place, tighten the screws to secure. Also
re-secure the top center screw through the oblong hole.
unit. Refer to the manual for instructions.
2) Remove the Screen Doors from the Full Screen Door Frame by fully
opening the doors and lifting up off of the hinges. See important note
in step 9.
3) Full Screen Door Frame Installation
a) Before attaching the Full Screen Door Frame to the unit, loosen the
left and right side #8 Self Tapping Philips Screws located on the
inside top of the outer frame of the appliance.Also remove the center
screw.
Inside Top
of Outer
Frame
Screw
Screw
Full Screen
Door Frame
Screw
Cut-Out
Oblong Hole
Cut-Out
Top
Flange
Bottom
Flange
Backside of Full
Screen Door
Frame Shown
Cut-Outs
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
29
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
5) Place the Bottom Grill near hinge. Flip the hinge over the Bottom Grill
NOTE: Should the finished wall protrude beyond the face of the unit,
you can accommodate up to 1/2" depth.
and secure with 2x #8 Self Tapping Philips Screws per side.
Simply push in the Full Screen Door Frame until it aligns against
the finished wall. Secure Top Flange of Full Screen Door Frame as
described in step 3b.
Hinge Location
FortheBottomFlangeoftheFullScreenDoorFrame,pushthebottom
of the Frame until it aligns with the wall. Use the inner cut-outs to
secure the base of the Frame using the 2x #8 Hex Head Drill Point
Screws provided.
Bottom Grill
Bottom
Flange
6) Loosen the 2x #8 Self Tapping Phillips screws which secure the
Right Side Hinge Bracket to the Bottom Grill. Place the keyholes in
the Restrain Bracket through the screws and slide the Bracket to the
right. Tighten the screws to secure bracket in place.
Inner
Cut-Outs
Restrain
Bracket
Backside of Full Screen
Door Frame Shown
4) Install the Hinges to the Hinge Brackets on the left and right side
of the bottom of the outer frame, secure using 2x #8 Self Tapping
Philips Screws per hinge.
Hinge
Bracket
Right Side
of Bottom
Grill
7) Re-install Glass Door. Refer to the manual for instructions.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
30
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
8) Slide the Top Grill into the louver brackets located on the inside top
9) Install the Left and Right Side Screen Doors in the fully open position
of the firebox. Push in place.
by placing over top of the hinges on the Full Screen Door Frame.
NOTE: Failure to install the doors in the fully open position could
result in paint damage to the surface of the door.
Hinge
Top Grill
Screen Door
10) Close screen doors.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
31
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
WIRING DIAGRAMS
A three wire power cord can also be used and
plugged into a suitable receptacle.
No electrical power supply is required for the
gas control to operate. 120 Volt AC power is
needed for the fan switch and blower. The fan
can be hard wired if desired. A terminal block
is provided on the left hand side of the unit.
NOTE: Even if the fan is not purchased with the
unit, itisstillagoodideatohardwiretheterminal
block in case the fan is installed at a later date.
** However DO NOT leave this connection
live until the fan is installed.**
(Do not cut the ground terminal off under
any circumstances.)
For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes
Star washer
Green (Ground)
White (Neutral)
Black (Live)
120 VAC
60HZ
(*by others)
Lockwasher
Nut
Star washer
Ground for
mobile home
Nut
#8 Ground Lug
(mobile home
approved)
Fan
(*by others)
Rotary Speed
Control
Pilot
Assembly
White
ON
OFF
Black
(*Supplied
by others
- install
Power cord
ground wire
Fan
ground
according to
local code)
Thermodisc
Piezo
Ignitor
(To THTP)
Brown
White
To Burner
ON / OFF
Switch
F
Gas
In
Red
(To TH)
Black
To Thermocouple IN
"S.I.T" Valve
ON OFF
Remote Receiver
or Thermostat
(Millivolt) (Optional)
Remote Transmitter
(Optional)
Openings for
electrical connections
Caution:Ensurethatthewiresdo
not touch any hot surfaces and
are away from sharp edges.
CAUTION: Label all wires
prior to disconnection
when servicing controls.
Wiring errors can cause
improper and dangerous
operation.
Power IN
Millivolt Wires
4-7/16"
1-1/2"
5-1/2"
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
32
INSTALLATION
For PROPANE Units and Units Equipped with DC Spark Boxes
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
33
OPERATING INSTRUCTIONS
OPTIONAL
WALL THERMOSTAT
OPERATING
OPTIONAL
INSTRUCTIONS
REMOTE CONTROL
UsetheRegency® RemoteControlKit approved
for this unit. Use of other systems may void
your warranty.
A wall thermostat may be installed if desired, 1) Read and understand these instructions
connect the wires as per the wiring diagram.
Use table below to determine the maximum
wire length.
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
Note: Preferable if the thermostat is
installed on an interior wall.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed or with
broken glass.
1) Choose a convenient location on the wall
to install the receiver and the receptacle
box (protection from extreme heat is very
important). Run wires from the fireplace to
that location. Use Thermostat Wire Table.
Regency® offers an optional programmable
thermostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or
UL approved may be used.
5) Verify that the venting and cap are
unobstructed.
2) Connect the two wires to the gas valve. See
CAUTION
diagram below.
Do not wire millivolt
wall thermostat wires
to 120V wire.
6) Ensure that the brick panels are installed.
CAUTION
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
Do not wire millivolt
remote control wires
to 120V wire.
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
3) Install3AAAalkalinebatteriesintransmitter
and 4 AA alkaline batteries in the receiver.
Install the receiver and its cover in the wall.
Switch the remote receiver to "remote"
mode. The remote control is now ready for
operation.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size
Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.
Optional
WALL SWITCH
1) Runthesupplied15'ofwirethroughtheright
or left side gas inlet opening. Be careful not
to damage wire.
Note: We recommend a maximum of 15'
of wire but if you wish to go with a
longer run, use the Thermostat Wire
Table.
LIGHTING
PROCEDURE
2) Connect the wire to the supplied wall switch
IMPORTANT
and install into the receptacle box.
To ignite or reignite the pilot,
you must first release the
tension springs below the door.
CAUTION
Do not wire millivolt
wall switch wire
to 120V wire.
NOTE: For all propane units and units
equipped with electric spark boxes,
see "Copy of Lighting Plate Instruc-
tions" section for more details.
IMPORTANT: Gas on/off knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
34
OPERATING INSTRUCTIONS
COPY OF THE LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. (Australia: AS5601-2004, New Zealand: NZS 5261)
WARNING:Ifyoudonotfollowtheseinstructionsexactly,afireorexplosionmayresultcausingpropertydamage,
personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance
or additional information consult a qualified installer, service agency or gas supplier.
A) This appliance has a pilot which must be lighted by hand, following the instructions below exactly.
B) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do not use any phone in your building
- Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to
repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and
to replace any part of the control system and any gas control which has been under water.
E) This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high surface temperatures
keep children, clothing and furniture, gasoline and other liquids having fammable vapors away. Keep burner
and control compartment clean. See installation and operating instructions accompanying appliance.
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
FOR UNITS NOT EQUIPPED WITH ELECTRIC SPARK:
1) Push in gas control knob slightly and turn clockwise
“OFF”. Knob cannot be turned from “PILOT” to “OFF” unless
knob is pushed in slightly. Do not force.
FOR ALL PROPANE UNITS AND
UNITS EQUIPPED WITH ELECTRIC SPARK BOXES:
to
1) Push in gas control knob slightly and turn to “PILOT” position.
OFF
PILOT BURNER
VEILLEUSE
2) Push in control knob all the way and hold in until the pilot lights
up. Continue to hold the control knob in for about 20 seconds
after the pilot is lit. Release knob.
THERMOPILE
ELEMENT
Gas Inlet
3) Push in gas control knob slightly and turn to "ON" position.
THERMO-
ELECTRIQUE
4) Turn ON the flame switch.
2) Wait five (5) minutes to clear out any gas. If you then smell gas
STOP! follow “B” in the safety information above on this label. If
you don’t smell gas, go to the next step.
Gas Inlet
3) Turn knob on gas control counterclockwise
to “PILOT”.
4) Push in control knob all the way and hold in. Immediately push
black button on spark igniter until pilot lights. Continue to hold the
control knob in for about 1/2 minute after the pilot is lit. Release
knob and it will pop back up. Pilot should remain lit. If it goes out,
repeat steps 3) and 4).
If knob does not pop up when released, stop and immediately call
your service technician or gas supplier.
If the pilot will not stay lit after several tries, turn the gas control
knob to “OFF” and call your service technician or gas supplier.
5) Turn gas control knob counterclockwise
6) Use rocker switch to operate main burner.
to “ON”.
TO TURN OFF GAS APPLIANCE
1) Turn off the flame switch.
2) Push in the gas control knob slightly and turn clockwise
to “OFF”. Do not force.
3) Turn off all electric power to the appliance if service is to be performed.
You may shut off the pilot during prolonged non use periods to conserve fuel.
DO NOT REMOVE THIS INSTRUCTION PLATE
918-474a
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
35
MAINTENANCE
Unit Body/Firebox:
1) Push in gas control knob slightly and turn
clockwise to "OFF". Knob cannot be turned
from"PILOT"to"OFF"unlessknobispushed
in slightly. Do not force.
Note: When the glass is cold and the
appliance is lit, it may cause
condensation and fog the glass.
This condensation is normal and will
disappear in a few minutes as the
glass heats up.
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
2) Wait 5 minutes to clear out any gas.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
MAINTENANCE
INSTRUCTIONS
3) Turn knob on gas control countercloskwise
to "PILOT".
During the first few fires, a white film
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the film will bake on and
become very difficult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
1) Alwaysturnoffthegasvalvebeforecleaning.
For relighting, refer to lighting instructions.
Keep the burner and control compartment
clean by brushing and vacuuming at least
once a year. When cleaning the logs, use a
soft clean paint brush as the logs are fragile
and easily damaged.
4) Push in control knob all the way and hold
in. Immediately push black button on spark
igniter until pilot lights. Continue to hold the
control knob in for about 1/2 minute after
the pilot light is lit. Release knob and it will
pop back up. Pilot should remain lit.
5) Turn gas control knob counterclockwise to
2) Clean appliance and door with a damp
cloth (never when unit is hot). Never use
an abrasive cleaner. The glass should be
cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
"ON".
NORMAL OPERATING
SOUNDS OF
6) Use rocker switch to operate main burner.
GAS APPLIANCES
It is possible that you will hear some sounds
fromyourgasappliance.Thisisperfectlynormal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listedbelowaresomeexamples.Allarenormal
operatingsoundsandshouldnotbeconsidered
as defects in your appliance.
SHUTDOWN
PROCEDURE
3) The heater is finished in a heat resistant
paintandshouldonlyberefinishedwithheat
resistant paint. Regency® uses StoveBright
Paint - Metallic Black #6309.
1) Use the wall switch, thermostat or remote
control to turn off the main burner.
2) Turn the main gas control clockwise to the
4) Make a periodic check of burner for proper
position and condition. Visually check the
flameoftheburnerperiodically,makingsure
theflamesaresteady;notliftingorfloating.If
thereisaproblem,callanauthorizedservice
person.
Blower:
"OFF" position to turn off the pilot.
Regency® gasappliancesusehightechblowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
3) Turn off all electric power to appliance if
service is to be performed.
FIRST FIRE
5) The appliance and venting system must be
inspected before use, and at least annually,
by an authorized field service person, to
ensure that the flow of combustion and
ventilation air is not obstructed.
Burner Tray:
The first fire in your fireplace is part of the
paint curing process. To ensure that the paint
is properly cured, it is recommended that you
burn your fireplace for at least four (4) hours the
first time you use it with the fan on. When first
operated, the unit will release an odour caused
by the curing of the paint, the burning off of
any oils remaining from manufacturing. Smoke
detectors in the house may go off at this time.
Open a few windows to ventilate the room for
a couple of hours.
The burner tray is positioned directly under the
burner tube and logs and is made of a different
gauge material from the rest of the firebox and
body.Therefore,thevaryingthicknessesofsteel
will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fireboxes.
6) Verify proper operation after servicing.
Note: Neveroperatetheappliancewithout
the glass properly secured in
place.
Blower Thermodisc:
The glass panel may require cleaning after the
unit has cooled down.
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS HOT.
Pilot Flame:
While the pilot flame is on it can make a very
slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dullclickingsoundmaybeaudible,thisisnormal
operation of a gas regulator or valve.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
36
MAINTENANCE
Caution: Wear gloves when removing
damaged or broken glass.
GOLD-PLATED
LOUVERS
The 24 carat gold-plated finish on the louvers
and trim requires little maintenance, and need
only be cleaned with a damp cloth.
GLASS
REPLACEMENT
Bay Glass Replacement
Your P42 fireplace is supplied with high
temperature, 5 mm Neoceram ceramic glass
that will withstand the highest heat that your
unit will produce. In the event that you break the
glass,purchaseyourreplacementglassfroman
authorizedRegency® dealeronly,andfollowthe
step-by-stepinstructionsforglass,glassgasket
and door gasket replacement.
1) Remove the door from the unit and place
on a soft surface to prevent scratching.
DO NOT use abrasive materials or chemical
cleaners, as they may harm the finish and void
the warranty.
2) Remove the nuts holding the glass clips in
place and remove.
3) Replace the glass. The glass must have
Clean any fingerprints off before turning
the unit on.
gasketing around it.
DOOR GLASS
LOG REPLACEMENT
Your Regency® fireplace is supplied with high
temperature,5mmNeoceramceramicglassthat
will withstand the highest heat that your unit will
produce. If your glass requires cleaning, we
recommend using an approved glass cleaner
available at all authorized dealers. Do not use
abrasive materials. Do not clean the glass
when hot.
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
Intheeventthatyoubreakyourglassbyimpact,
purchase your replacement from an authorized
Regency® dealer only, and follow our step-by-
step instructions for replacement.
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's performance
which is not covered under
warranty.
WARNING
The use of substitute glass will
void all product warranties.
THERMOPILE /
Do not operate the appliance
with the glass panel(s) removed,
cracked or broken. Replacement of
the glass panel(s) should be done
by an authorized service person.
THERMOCOUPLE
1) Removethetoplouverandopenthebottom
louvers.
4) Reverse the previous steps, replace the
glassclipsandfastenwiththenutsbutdonot
over tighten, as this can break the glass.
2) Open and remove door.
3) Remove front logs.
4) Remove burner.
Flush Glass Replacement
Removetheflushdoorfront(asperinstructionsin
the"StandardFlushDoor"section).Removethe
4 glass clips from each corner. Slide in the new
replacement
5) Replace door on the fireplace and check
the seal.
5) Loosenthethermocoupleorthermopilewith
a 7/16" wrench.
glass. Push the
4 glass clips
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken.
Replacement of the glass panels
should be done by a licensed or
qualified service person.
6) Disconnect thermocouple by loosening
nut from the valve with a 9mm wrench.
Disconnect thermopile by loosening 2
screws marked TP on the valve.
back onto the
frame.
Theglassmust
havegasketing
around it.
7) Peel the silicone from the hole in the base
of the unit and drop the thermocouple or
thermopile down from the bracket and pull
it out of the unit.
8) Reinstall the new ones in reverse order
making sure to seal the hole in the firebox
with silicone in order to maintain the seal
integrity of the firebox.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
37
MAINTENANCE
REPLACING THE FAN
1) Shut the power off.
REMOVING VALVE
1) Shut off the gas supply.
REMOVING THE FAN
1) Shut the power off.
2) Remove the bottom louver. Slide the fan in
and push it towards the rear of the unit and
slip it over the two mounting studs.
2) Remove the louvers (and bay door if it is
2) Remove the bottom louver.
on).
3) Removeterminalblockcoveranddisconnect
3) Disconnect the inlet gas line.
the fan wires.
3) Remove the terminal block cover. Wire the
fan to the terminal block as shown in the
wiring diagram below.
Note: Be sure to have an 11/16" wrench on
the tee to ensure that the whole line
is not twisted
4) Disconnect white fan wire from the terminal
block.
4) Connect white wire from fan to neutral of
5) Disconnect black fan wire from the
terminal block.
4) Disconnect the 2 TP wires and the 2 TH
thermodisc.
wires from the valve.
5) Connect black wire from fan to the
6) Disconnect fan ground wire.
thermodisc.
5) Remove the Piezo igniter wire.
6) Open and remove the flush door.
7) Remove the logs.
7) Lift the fan off the two mounting studs and
6) Connect fan ground wire. Refer to wiring
pull out.
diagram.
7) Attach the ground wire to the fireplace
IMPORTANT:
(ground lug provided).
8) Remove the burner tube by removing the 3
Phillips head screws and then lift the burner
out.
These fans collect a lot of dust
from within your home. Ensure
you maintain these fan motors on
a regular basis by vacuuming out
the fan squirrel cages.
8) Attach the terminal block cover.
Note: A 120 Volt AC power cord should be
installed at rough-in stage so that
the power is available. A three wire
power cord can be used.
9) Remove the burner grate assembly by
removing the 3 Phillips head screws on the
feet of the grate assembly.
10) Brush away all the vermiculite and embers
The bearings are lubricated for life.
Do not lubricate them. Make sure
youvacuumthefanareaonaregular
basis.
from the right hand half of the fireplace.
11) Remove the top and right hand side brick
panels.
12) Removethe12Phillipsheadscrewssecuring
the valve access plate in place and then lift
the entire assembly out.
13) Undo the pilot tube from the valve with a
7/16" wrench.
14) Undo the quick drop out thermocouple nut
on the valve with a 9mm wrench.
15) Undo the "gas out" flare nut with a 13/16"
wrench.
16) Undo the "gas out" 90o elbow flare fitting with
Grounding lug detail
an 11/16" wrench.
17) Remove the 4 Phillips head screws from
the sides of the valve bracket and remove
valve.
Hint: If you are using black pipe, ensure
that there is a union by the valve, otherwise
removal will be almost impossible.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
38
MAINTENANCE
INSTALLING VALVE
1) Attach the valve bracket to the valve with the 4 (m5x8 metric) screws
8) Reinstall the 12 hold down screws.
provided.
9) Hook up the 2 TP and 2 TH wires to the appropriate connections on
2) Reconnect the "gas out" 90o elbow flare fitting with an 11/16"
the valve.
wrench.
10) Reinstall the burner grate. Put a dab of high temperature silicone
3) Reconnect the "gas out" flare nut with a
over the 3 screw holes.
13/16" wrench.
11) Install Burner tube.
4) Reconnect the quick drop out thermocouple nut with a 9mm
wrench.
12) Hook up the gas line and check for gas leaks with a soap and water
solution or a gas leak detector. (Do not use open flame for leak
testing.)
5) Reconnect the pilot tube nut with a 7/16" wrench.
6) Scrape off the old gasket from the floor of the firebox.
7) Install a new gasket and reinstall the valve assembly.
13) Fire up the unit.
14) Check the manifold pressure.
Note: Failure to install a new gasket may severely affect the
appliance performance.
15) Reinstall the vermiculite, embers, rockwool and logs as needed.
16) Install and close the door and replace the louvers.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
39
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P42 MAIN ASSEMBLY
Part #
Description
Part #
Description
Part #
Description
1)
910-142 Fan - Auto ON/OFF
Thermodisc
38) 601-092 Baffle
20) 601-077 Top Nailing Strip
21) 601-078 Side Nailing Strip
23) 601-036 Standoff - Top
24) 511-044 Standoff - Side/Back
510-089 Gasket - Air Inlet
39) 601-171 Restrictor
2)
3)
4)
7)
8)
9)
820-389 Thermodisc Bracket
948-045 Chain
40) 510-994 Rigid Pipe Adapter
948-115 Extension Spring
910-184 Terminal Block
510-125 Terminal Block Housing
510-126 Terminal Block Housing Cover
58) 910-413 2-switch cover plate
59) 910-420 Double gang box
60) 910-363 Wall Switch - White
61) 904-687 3/8" Clamp Connector
97) 910-417 White Knob
99) 910-412 Fan Speed Control (wall
mounted)
836-105 Top Insulation
27)
30)
31)
*
*
*
Outer Flue Collar
Gasket for Flue Collar
Flue Mounting Plate
600-515/P Fan Assembly (120 V)
11) 910-157/P Fan / Blower (120 V)
910-882 Wire (Valve to Burner Switch)
13) 601-021 Bottom Hinge Bracket-Left
14) 601-022 Bottom Hinge Bracket-Right
15) 948-253 Relief Door Handle
17) 910-199 Wire Holder Clip
602-902 Brick Panel Std Red (Set)
33)
34)
35)
36)
*
*
*
*
Brick Panel Back
Brick Panel Left Side
Brick Panel Right Side
Brick Panel Top
946-556 Heat Wave Duct Kit (Optional)
92) 946-001 Oval Duct Adaptor
93) 946-007 Angle Bracket
94) 946-517/P Fan Assembly - Heat Wave
95) 946-006 Grill Plate - White
96) 946-005/01 Wall Adaptor Plate - White
97) 910-417 Knob - White
601-170 Top Front Brick Trim
98) 910-366 Switch Cover Plate - White
99) 910-412 Fan Speed Controller
100) 910-367 Box - Plastic Switch
Receptacle
101) 946-000 Round Duct Adaptor
102) 946-010 Flexible Air Duct
946-038 Insulation 6" Dia. x 24"
103) 946-002 Round to Oval Adaptor
104) 946-004 Junction Box
946-570 Heat Release Duct Kit
(Optional)
125) 910-165 Fan (120 V)
126) 946-000 Flexible Air Release Duct
127) 690-022 Cover Plate
918-523 Manual
*Not available as a replacement part.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
40
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P42 BURNER & LOG ASSEMBLY
Part #
Description
602-574/P
602-576/P
*
Valve Assembly - Natural Gas
Valve Assembly - Propane
Gasket - Valve Access Plate
Piezo Ignitor & Nut
52)
56) 910-190
57) 910-478
66) 910-038
910-039
Valve S.I.T. - NG/LPG
Pilot Assy - S.I.T. - 3 Flame NG
Pilot Assy - S.I.T. - 3 Flame LP
Pilot Holder
67)
*
68) W840470
69) 904-689
904-641
Pilot Assembly Gasket
#33 Orifice - N.G.
#50 Orifice - Propane
Orifice Gasket
936-170
70) 601-133
Pilot Flame Bracket
75)
*
Valve Access Plate
79) 601-535
82) 600-555
Burner Assy
Burner/Grate Assy
84)
*
Air Shutter Gear Assembly - Male
Air Shutter Gear Assembly - Female
Hex key 3/16" AF
88) 260-565
904-565
89) 600-964
90) 910-421
91) 910-422
P42 Log Set
Pilot ON/OFF Extension Knob (with Bay Front)
HI/LOW Extension Knob (with Bay Front)
*Not available as a replacement part.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
41
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P42 FLUSH DOOR & LOUVERS
Part #
Description
600-960
Flush Louvers (Set) - Gold/Black
600-958
Flush Louvers (Set) - Black
Flush Louvers (Set) - Steel/Black
Flush Louver Assy-Top
600-961
*
*
133)
134)
Flush Louver Assy-Bottom
Flush Door Assembly Complete
135) 940-086/P
137) 904-691
Glass (Flush)
U-Clip
138)
*
Flush Door Frame
Glass Gasket (Tadpole)
139) 936-155
140) 948-042
600-965
Spring Hinge
Finishing Trim - Black
Trim Side Left - Black
Trim Side Right - Black
Trim Top - Black
141)
142)
143)
*
*
*
600-943
Double Screen Door Complete (Optional)
Door Frame Assembly - Left
Door Frame Assembly - Right
Handle
171)
172)
*
*
174) 511-085
175) 602-540
178) 948-257
179) 948-258
180) 512-546
*
Door Support Frame Assembly
Lift Hinge on Door
Lift Hinge on Frame
Door Latch Assembly
Pushnut Fastener
*
*
Screw 6-32 x 5/16 Pan Head
Washer #6 External Star
U-Clip for Screen Door
187) 904-712
188) 948-216
Regency® Logo Plate
*Not available as a replacement part.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
42
PARTS LIST
P42 BAY FRONT & LOUVERS
Part #
Description
Part #
Description
600-954
Bay Louvers (Set) - Black
603-930
Bay Front Complete with Glass & Black Trim
600-956
Bay Louvers (Set) - Gold/Black
Bay Louvers (Set) - Steel/Black
Bay Louver Assy-Top
600-957
*
*
106) 940-102/P
107) 936-243
108) 940-101/P
Side Glass
Glass Gasket
Center Glass
115)
116)
Bay Louver Assy-Bottom
117) 904-196
120) 400-189
122) 948-216
Magnet (1" round)
111) 602-906
Brick Panel - Bay Std Red
Flush Glass Retainer Bracket
Regency® Logo Plate
113)
*
Bay Door Trim (Each) -Black
Bay Door Trim (Set) - Gold
602-932
* Not available as a replacement part.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
43
NOTES
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
44
NOTES
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
45
NOTES
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
46
WARRANTY
Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit
thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a
Excalibur Product. This warranty is not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime
Warranty for five (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for five (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date
of purchase and parts only thereafter.
Special Finishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant heating
and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and marks,
ie. finger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electricalandmechanicalcomponentssuchasblowers,switches,wiring,thermodiscs,FPIremotecontrols,spillswitches,thermopiles,thermocouples,pilotassemblycomponents,
and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and
continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any
item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided
that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of
installation. Reported damage after this time will be subject to rejection.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated
for manufacturer defect.
The authorized selling dealer is responsible for all in-field service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from
unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the field which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name,
purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.
ie. as products evolve, field modifications or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical
systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty
on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
47
Regency® fireplace products are designed
with reliability and simplicity in mind. In
addition, our internal Quality Assurance
Team carefully inspects each unit
thoroughly before it leaves our
door.
Fireplace Products International
Ltd.ispleasedtoextendthisLimited
Lifetime Warranty to the original
purchaser of a Regency® Product.
See the inside back cover for details.
Register your Regency® online at
Installer: Please complete the following information
Dealer Name & Address:______________________________________________
___________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.:__________________________________________________________