Regency L676-1 Sunrise Gas Fireplace
L676-1 Sunrise Gas Fireplace
Framing Dimensions:
Model
L676S-NG1
Natural Gas
L676S-LP1
Propane
Framing Dimensions
Description
Framing Width
Framing Height***
Framing Depth
L676S-1
43” (1092mm)
Fuel Type
J
Minimum Supply Pressure
Manifold Pressure - High
Manifold Pressure - Low
Orifice Size
5” W.C. (1.25 kPa)
3.5” W.C. (0.87 kPa)
1.6” W.C. (0.40 kPa)
#37 DMS
12” W.C. (2.98 kPa)
10” W.C . (2.49 kPa)
6.4” W.C (1.59kPa)
#53 DMS
K***
L
45-7/8” (1165mm)*** + Hearth
24-1/2” (622mm)
M
N
Minimum Height to Combustibles
Corner Wall Length
56-1/4” (1429mm)
57-3/16” (1453mm)
80-13/16” (2052mm)
49-1/4” (1251mm)
15-9/16 (395mm)
2” (51mm)
O
P
Corner Facing Wall Width
Vent Centerline Height
Minimum Input
Altitude 0-4500 ft. (0-1372m)
19,500 BTU/h
(5.71 kW)
21,000 BTU/h
(6.15kW)
Q
R
Non-combustible Facing Height
Gas Connection Opening Height
Gas Connection Height
Maximum Input
Altitude 0-4500 ft. (0-1372m)
29,000 BTU/h
(8.49 kW)
26,000 BTU/h
(7.61kW)
S
11-1/4” (286mm)
5-3/4” (146mm)
5” (127mm)
T
Gas Connection Inset
Vent Sizing
5” Inner / 8” Outer
5” Inner / 8” Outer
U
Gas Connection Opening Width
***Important: Framing height requires consideration of the hearth
Approved Venting Systems
depth. Dimension K = K + the thickness of installed hearth.
Flex Vent Systems:
FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems:
Simpson Direct Vent Pro®
Selkirk Direct-Temp™
Metal-Fab® Sure Seal
Unit Dimensions:
Unit Dimensions
Description
L676S-1
A
B
C
D
E
F
G
H
I
Firebox Width w/ Standoff
Rear Firebox Width
Firebox Height
42-1/2” (1080mm)
33-1/8” (841mm)
37-3/8” (949mm)
45-5/8” (1159mm)
24” (610mm)
Height w/ Standoff
Unit Depth
Height to Vent
40-3/8” (1026mm)
29-1/16” (738mm)
31-5/8” (803mm)
3” (76mm)
Fireplace Opening Height
Fireplace Opening Width
Height to Fireplace Opening
Non-Combustible Requirements:
Metal
44-1/2"
Stud
(1130mm)
Non-combustible
Material
31-5/8"
(803mm)
This manual is intended to be a Sales Reference Guide only.
Do NOT use for actual framing and installation of any unit.
Some specifications may change without notice.
You must use the actual manual for exact installation specifications.
WARNING
Non-combustible Material
Failure to maintain required clearances is a major cause of chimney related fires.
Finished Floor
6-7/16"
(163mm)
3"
Installation of this fireplace must comply with these clearances
(76mm)
Please note: Due to ongoing product development, product appearance and specifications
are subject to change without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
Regency L676-1 Sunrise Gas Fireplace
L676-1 Sunrise Gas Fireplace
Vertical Terminations:
Clearance Requirements:
Installed
Close to Floor
Installed Close
to Ceiling
Clearance:
Dimension
16-1/2” (419mm)
14-3/4” (375mm)
52” (1321mm)
13” (330mm)
Measured From:
A: Mantel Height
B: Sidewall
Minimum
Side of fireplace opening
Top of fireplace opening
Maximum
C: Ceiling
D: Mantel Depth
E: Alcove Width
F: Alcove Depth
84” (2134mm)
36” (914mm)
Sidewall to Sidewall (Minimum)
Front to back wall (Maximum)
Combustible Mantels
Becauseoftheextremeheatthisfireplaceemits,themantelclearances
are critical. Combustible mantel clearances from top of the front facing
are shown in the diagram below. Mantel may be installed anywhere in the
shaded area or higher.
Mantel
From Top of
Clearances Fireplace Opening
A
B
C
D
31-1/16”
26-1/2”
17-1/2”
16-1/2”
Horizontal Terminations:
Note:
A non-combustible mantel may
be installed at a lower height if
the framing is made of metal
studs covered with a non-com-
bustible board.
Ensure the paint that is used
on the mantel and the facing is
“heat resistant” or the paint may
discolour.
Mantel Leg
Clearances
Combustible mantel leg
clearances as per diagram.
Clearances are from the
finished edge of the fireplace
opening.
Download from Www.Somanuals.com. All Manuals Search And Download.
|