Raypak Water Heater HD101 User Guide

Catalog No.: 3500.961A  
Hi Delta SS™, TYPE WH - MODELS HD101 – HD401  
SUGGESTED SPECIFICATIONS  
Effective:  
Replaces:  
12-29-09  
6-25-09  
DIVISION 23 52 33.13  
FINNED WATER-TUBE WATER HEATERS  
PART 1 - GENERAL  
1.1 SUMMARY  
A. Section includes gas-fired, copper finned-tube water heaters for use with a storage tank.  
B. Related Sections  
Specifier Note: Use as needed  
1. Building Services Piping – Division 23 21 00  
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00  
3. HVAC Instrumentation and Controls – Division 23 09 00  
4. Electrical – Division 23 09 33  
1.2  
REFERENCES  
A. ANSI Z21.10.3/CSA 4.3  
B. ASME, Section IV  
C. 2006 UMC, Section 1107.6  
D. ANSI/ASHRAE 15-1994, Section 8.13.6  
E. National Fuel Gas Code, ANSI Z223.1/NFPA 54  
F. NEC  
1.3  
1.4  
SUBMITTALS  
A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)  
B. Wiring diagram  
C. Warranty information  
D. Installation and operating instructions  
QUALITY ASSURANCE  
A. Regulatory Requirements  
1. ANSI Z21.10.3/CSA 4.3  
2. Local and national air quality regulations for low NOx (<20 PPM NOx emissions) water heaters  
B. Certifications  
1. CSA  
2. ASME HLW Stamp and National Board Listed  
1.5  
WARRANTY  
A. Limited five-year warranty from date of installation  
B. Limited twenty-year thermal shock warranty from date of installation  
C. Limited ten-year warranty for cupro-nickel heat exchangers only  
PART 2 - PRODUCTS  
2.1  
MANUFACTURER  
A. Raypak, Inc.  
1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;  
2. Product: HD™ copper finned-tube water heater(s)  
2.2  
WATER HEATERS  
Project Name / Date  
Division 23 52 33.13 - 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
H. Water Heater Diagnostics  
1. Provide internal LED displaying the following water heater status/faults:  
a. Steady on – Internal control failure  
b. One flash – Air flow fault  
c. Two flashes – Erroneous flame signal  
d. Three flashes – Ignition lockout  
I. Combustion Chamber: The lightweight, high temperature, multi-piece, interlocking ceramic fiber  
combustion chamber liner shall be sealed to reduce standby radiation losses, reducing jacket  
losses and increasing unit efficiency.  
J. Venting  
1. When routed vertically, the water heater’s flue material and size shall be in accordance with  
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 latest edition (Category I).  
2. When routed horizontally, the water heater(s) flue material and size shall meet or exceed the  
requirements as specified for Category III in the National Fuel Gas Code, ANSI Z223.1/NFPA  
54 latest edition.  
3. The water heater(s) shall be TruSeal™ direct vent ready. The water heater(s) shall meet  
safety standards for direct vent equipment as noted by: the 2006 UMC Section 1107.6;  
ASHRAE 15-1994, Section 8.13.6; and ANSI Z21.10.3/CSA 4.3.  
K. Cabinet  
1. The corrosion-resistant galvanized steel jackets shall be finished with a baked-on epoxy  
powder coat which is suitable for outdoor installation, applied prior to assembly for complete  
coverage, and shall incorporate louvers in the outer panels to divert air past heated surfaces.  
2. The water heater(s), if located on a combustible floor, shall not require a separate combustible  
floor base.  
3. Combustion air intake shall be on left side of the cabinet.  
Specifier Note: The remaining items in this section are options. Delete those that are not being  
specified.  
L. Water Heater Operating Controls  
1. The water heaters(s) shall feature an optional controller.  
M. Water Heater Pump - Refer to Equipment Schedule  
N. Cold Water Run System  
1. The water heater(s) shall be configured with a cold water run automatic proportional bypass  
system that ensures the water heater will experience inlet temperatures in excess of 105ºF to  
avoid damaging condensation.  
2. The cold water run system shall be configured with a variable speed pump that is controlled by  
a system-matched PID control that injects the correct amount of cold water directly into the  
water heater loop to maintain a minimum inlet temperature. The PID controller temperature  
sensor shall be located in the inlet header of the water heater.  
3. The control shall have a temperature setting DIP switches located on the face of the board.  
The PID Logic shall be capable of limiting system overshoot on initial start-up or call-for-heat.  
4. The cold water run system shall be shipped loose for field installation.  
2.3  
SOURCE QUALITY CONTROL  
A. The water heater(s) shall be completely assembled, wired, and fire-tested prior to shipment from  
the factory.  
B. The water heater(s) shall be furnished with the sales order, ASME Manufacturer’s Data Report,  
inspection sheet, wiring diagram, rating plate and Installation and Operating Manual.  
PART 3 - EXECUTION  
3.1  
INSTALLATION  
A. Must comply with:  
1. Local, state, provincial, and national codes, laws, regulations and ordinances  
2. National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition  
Project Name / Date  
Division 23 52 33.13 - 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. National Electrical Code, ANSI/NFPA 70 – latest edition  
4. Canada only: CAN/CSA B149 Installation Code and CSA C22.1 CEC Part I  
5. Manufacturer’s installation instructions, including required service clearances and venting  
guidelines  
B. Manufacturer’s representative to verify proper and complete installation.  
3.2  
START-UP  
A. Shall be performed by Raypak factory-trained personnel.  
B. Test during operation and adjust if necessary:  
1. Safeties (2.2 - F)  
2. Operating Controls (2.3)  
3. Static and full load gas supply pressures  
4. Gas manifold and blower air pressures  
C. Submit copy of start-up report to Architect and Engineer.  
TRAINING  
3.3  
A. Provide factory-authorized service representative to train maintenance personnel on procedures  
and schedules related to start-up, shut-down, trouble shooting, servicing, and preventive  
maintenance.  
B. Schedule training at least seven days in advance.  
END OF SECTION  
Project Name / Date  
Division 23 52 33.13 - 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Radio Shack Motorized Toy Car 60 8512 User Guide
Regency Indoor Fireplace E21 LP3 User Guide
Samsung Cell Phone DM S105 User Guide
Samsung Computer Monitor 193S User Guide
Samsung DVD Player DVD S428K User Guide
Sanus Systems Indoor Furnishings CFAV34 User Guide
Sanyo DVR DSR 300 User Guide
Schumacher Battery Charger 20071230 User Guide
Scientific Atlanta DVR 8640HDC User Guide
Sennheiser Headphones HD 448 User Guide