Quadra Fire Indoor Fireplace QV PIER User Guide

Owner’s Manual  
Installation and Operation  
Models:  
QV-Pier  
QV-ST  
Series: HV-IPI  
CAUTION  
DO NOT DISCARD THIS MANUAL  
Important operating  
and maintenance  
instructions included.  
Read, understand and follow  
these instructions for safe  
installation and operation.  
Leave this manual with  
party responsible for  
use and operation.  
WARNING: IMPROPER INSTALLATION,  
ADJUSTMENT, ALTERATION, SERVICE OR  
MAINTENANCE CAN CAUSE INJURY OR  
PROPERTY DAMAGE. REFER TO THIS  
MANUAL. FORASSISTANCE ORADDITION-  
AL INFORMATION CONSULT A QUALIFIED  
INSTALLER, SERVICE AGENCY, OR THE  
GAS SUPPLIER.  
WARNING: If the information in these  
instructions is not followed exactly, a fire  
or explosion may result causing prop-  
erty damage, personal injury, or death.  
• Do not store or use gasoline or other flam-  
mable vapors and liquids in the vicinity of this  
or any other appliance.  
• What to do if you smell gas  
- Do not try to light any appliance  
This appliance may be installed in an aftermarket,  
permanently located, manufactured (mobile) home,  
where not prohibited by local codes.  
- Do not touch any electrical switch. Do not  
use any phone in your building.  
This appliance is only for use with the type of gas  
indicated on the rating plate. This appliance is not  
convertible for use with other gases, unless a certi-  
fied kit is used.  
- Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas suppli-  
er’s instructions.  
- If you cannot reach your gas supplier, call  
the fire department.  
Î
In the Commonwealth of Massachusetts:  
• installation must be performed by a licensed plumber  
or gas fitter;  
• a CO detector shall be installed in the room where the  
appliance is installed.  
• Installation and service must be performed by  
a qualified installer, service agency, or the gas  
supplier.  
Printed in U.S.A.  
Copyright 2006  
Please contact your Quadra-Fire dealer with any questions  
or concerns. For the number of your nearest Quadra-Fire dealer,  
please call 1-800-926-4356.  
Quadra-Fire, a brand of Hearth & Home Technologies Inc.  
1445 North Highway, Colville, WA 99114  
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356,  
5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481,  
6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802, 6796302, 6840261, 6848441,  
6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or other U.S. and foreign  
patents pending.  
1
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Safety and Warning Information.................................................. 2  
Î
Service Parts List ......................................................................... 4  
Approvals and Codes .................................................................. 9  
Appliance Certification ................................................................................... 9  
Installation Codes .......................................................................................... 9  
Getting Started............................................................................ 10  
Introducing the Quadra-Fire Gas Fireplaces ................................................. 10  
Pre-install Preparation ................................................................................. 10  
Installing the Fireplace ............................................................... 13  
Î
Step 1. Locating the Fireplace .................................................................... 13  
Step 2. Framing the Fireplace ..................................................................... 14  
Step 3. Installing the Vent System .............................................................. 17  
A. Vent System Approvals ......................................................... 17  
B. Installing Vent Components ................................................... 24  
C. Vent Termination.................................................................... 26  
Step 4. Positioning, Leveling, and Securing the Fireplace ........................... 29  
Step 5. The Gas Control System ................................................................ 29  
Step 6. The Gas Supply Line ...................................................................... 30  
Step 7. Gas Pressure Requirements........................................................... 30  
Step 8. Wiring the Fireplace........................................................................ 31  
Step 9. Finishing......................................................................................... 33  
Step 10. Installing Trim, Logs & Ember Material........................................... 34  
Installing the Trim........................................................................ 34  
Positioning the Logs ................................................................... 34  
Shutter Settings .......................................................................... 34  
Glass Specifications ................................................................... 34  
Preparing Electric Ember Bed and Lava Rock ............................. 34  
Placing the Ember Material ......................................................... 36  
Ember Light Replacement ........................................................... 37  
Step 11. Before Lighting the Fireplace........................................................ 37  
Step 12. Lighting the Fireplace ................................................................... 37  
After the Installation ..................................................................................... 37  
Maintaining and Servicing Your Fireplace................................ 38  
Troubleshooting ......................................................................... 39  
Warranty ...................................................................................... 41  
Î
Î = Contains updated information.  
3
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Parts List  
QV-Pier-HV-IPI  
Beginning Manufacturing Date: 6-03  
Ending Manufacturing Date: ______  
(NG, LP) Exploded Parts Diagram  
3
1
5
4
2
6 Log Assembly  
7
13  
11  
12  
9
8
7
10  
Part number list on following page.  
4
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE PARTS LIST  
QV-PIER-HV-IPI  
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,  
supply serial and model numbers to ensure correct service parts.  
ITEM  
COMMON PART  
SERIAL #  
PART NUMBER  
582-833  
Burner Orifice NG (#33DMS)  
Burner Orifice LP (#50DMS)  
End Glass Assembly  
582-850  
1
2
3
GLA-MS  
Glass Door Assembly  
Burner Assembly  
GLA-6TROC  
2005-006  
4
5
6
7
Log Grate  
2005-012  
Side Refractory  
Log Set Assembly  
Log 1  
SRV2005-730  
LOGS-MSR  
SRV2005-701  
8
9
Log 2  
Log 3  
Log 4  
SRV2005-700  
SRV2005-702  
SRV2005-703  
10  
11  
12  
13  
Log 5  
SRV2005-704  
SRV2005-705  
SRV703-703  
80784  
Log 6  
Log 7  
Andirons  
Lava Rock Bag  
2005-790  
Flue Restrictor  
Teco-Sil, 5 lb. bag  
Mineral Wool  
385-128  
700-790  
050-721  
Í
Í
Fiberglass Rope  
060-455  
Í
Í
Bracket, Andiron  
2005-149  
2005-165  
386-122A  
Kapton, Lens  
Glass Latch Support Assembly  
Í
Í
Insullation Board (side)  
Insullation Board (end)  
Ember Mesh Assembly  
2006-136  
2006-137  
2006-008  
Í
Junction Box  
4021-013  
593-593A  
NGK-MS  
3V Plug  
Conversion Kit NG  
Conversion Kit LP  
Pilot Tube  
LPK-MS  
SRV485-301  
593-594A  
Battery Pack  
ACCESSORIES  
Fan Kit  
GFK-160A  
Remote Control Kit  
Remote Control Kit  
Remote Control - Multi-functional  
Wall Switch, Multi-functional  
Plug Adapator Kit (for WSK-MLT  
RC-SMART-HNG  
SMART-STAT-HNG  
RCT-MLT-HNG  
WSK-MLT  
PLUG-ADP  
5
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
QV-ST-HV-IPI  
Beginning Manufacturing Date: 6-03  
Ending Manufacturing Date: ______  
Service Parts  
(NG, LP) Exploded Parts Diagram  
4
2
3
1
5 Log Assembly  
7
12  
7
11  
10  
8
6
9
Part number list on following page.  
6
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE PARTS LIST  
QV-ST-HV-IPI  
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,  
supply serial and model numbers to ensure correct service parts.  
ITEM  
COMMON PART  
SERIAL #  
PART NUMBER  
Burner Orifice NG (#32DMS)  
Burner Orifice LP (#50DMS)  
Glass Door Assembly  
Burner Assembly  
582-832  
582-850  
1
2
GLA-6TROC  
2005-006  
3
4
5
6
Log Grate  
2005-012  
Side Refractory  
Log Set Assembly  
Log 1  
SRV2005-730  
LOGS-MSR  
SRV2005-701  
7
8
9
Log 2  
Log 3  
Log 4  
SRV2005-700  
SRV2005-702  
SRV2005-703  
10  
11  
12  
Log 5  
SRV2005-704  
SRV2005-705  
SRV703-703  
80784  
Log 6  
Log 7  
Andirons  
Lava Rock Bag  
2005-790  
Flue Restrictor  
Teco-Sil, 5 lb. bag  
Hood, Black  
385-128  
700-790  
SRV60-143-BK  
386-122A  
Í
Í
Glass Latch Support Assembly  
Mineral Wool  
050-721  
Í
Í
Í
Í
Í
Í
Fiberglass Rope  
Bracket, Andiron  
Kapton, Lens  
060-455  
2005-149  
2005-165  
Non-Combustible board  
2005-172  
2005-008  
4021-013  
593-593A  
NGK-MS  
Ember Mesh Assembly  
Junction Box  
3V Plug  
Conversion Kit NG  
Conversion Kit LP  
Pilot Tube  
LPK-MS  
SRV485-301  
593-594A  
Battery Pack  
ACCESSORIES  
Fan Kit  
GFK-160A  
Remote Control Kit  
Remote Control Kit  
Remote Control - Multi-functional  
Wall Switch, Multi-functional  
Plug Adapator Kit (for WSK-ML  
RC-SMART-HNG  
SMART-STAT-HNG  
RCT-MLT-HNG  
WSK-MLT  
PLUG-ADP  
7
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
QV-PIER-HV-IPI  
QV-ST-HV-IPI  
Service Parts  
(NG, LP) Exploded Parts Diagram  
Beginning Manufacturing Date: 6-03  
Ending Manufacturing Date: ______  
Î
13  
9
14  
8
7
10  
11  
12  
6
1
2
5
4
3
Î
ITEM  
DESCRIPTION  
SERIAL #  
PART NUMBER  
060-511  
1
2
ON/OFF Rocker Switch  
ON/OFF Wire Assembly  
060-521A  
3
3
4
5
6
7
Valve NG  
750-500  
750-501  
2005-009  
593-592  
593-590A  
2005-114  
Valve LP  
Flexible Gas Connector  
Module  
Wire Assembly  
Ember Box Assembly  
8
8
9
Pilot Assembly NG  
Pilot Assembly LP  
Pilot Bracket  
385-510A  
385-511A  
2005-118  
10  
11  
12  
13  
14  
Gasket Orifice  
Valve Bracket  
Flex Ball Valve Assembly  
Pilot Assembly Support  
Ground Strap  
2005-166  
2005-120  
302-320A  
385-120  
385-512  
NGK-DXV  
LPK-DXV  
446-301  
446-505  
446-517  
Í
Í
Regulator, NG  
Regulator, LP  
Pilot Tube  
Orifice Spud NG  
Orifice Spud LP  
NOTE: Replacement bulbs to be supplied by homeowner. Recommended replacements: Sylvania Mini Candelabra 75 watts.  
8
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Approvals and  
Codes  
1
Appliance Certification  
High Altitude Installations  
U.L. Listed gas appliances are tested and approved with-  
out requiring changes for elevations from 0 to 2,000 feet in  
the U. S. A. and in Canada.  
The Quadra-Fire fireplace models discussed in this Installers  
Guide have been tested to certification standards and listed  
by the applicable laboratories.  
When installing this appliance at an elevation above 2,000  
feet, it may be necessary to decrease the input rating by  
changing the existing burner orifice to a smaller size. Input  
rate should be reduced by 4% for each 1000 feet above a  
2000 foot elevation in the U.S.A. or 10% for elevations  
between 2000 and 4500 feet in Canada. If the heating value  
of the gas has been reduced, these rules do not apply. To  
identify the proper orifice size, check with the local gas  
utility.  
Certification  
MODELS: QV-PIER-HV-IPI, QV-ST-HV-IPI  
LABORATORY: Underwriters Laboratories  
TYPE: Vented Gas Fireplace Heater  
STANDARD: ANSI Z21.88•CGA2.22•UL307B  
Installation Codes  
If installing this appliance at an elevation above 4,500 feet  
(in Canada), check with local authorities.  
The fireplace installation must conform to local codes. Before  
installing the fireplace, consult the local building code  
agency to ensure that you are in compliance with all  
applicable codes, including permits and inspections.  
In the absence of local codes, the fireplace installation must  
conform to the National Fuel Gas CodeANSI Z223.1 (in the  
United States) or the CAN/CGA-B149 Installation Codes  
(in Canada). The appliance must be electrically grounded  
in accordance with local codes or, in the absence of local  
codes with the National Electric Code ANSI/NFPA No. 70  
(in the United States), or to the CSAC22.1 Canadian Electric  
Code (in Canada).  
These models may be installed in a bedroom or bed-sitting  
room in the U.S.A. and Canada.  
9
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
2
Introducing the Quadra-Fire Gas Fireplaces  
The Quadra-Fire Warranty will be voided by, and Quadra-  
Fire disclaims any responsibility for, the following actions:  
Quadra-Fire direct vent gas fireplaces are designed to op-  
erate with all combustion air siphoned from outside of the  
building and all exhaust gases expelled to the outside.  
Installation of any damaged fireplace or vent system  
component.  
Modification of the fireplace or direct vent system.  
Installation other than as instructed by Quadra-Fire.  
Improper positioning of the gas logs or the glass door.  
The information contained in this Installers Guide, unless  
noted otherwise, applies to all models and gas control  
systems. Gas fireplace diagrams, including the dimensions,  
are shown in this section.  
Installation and/or use of any component part not manu-  
factured and approved by Quadra-Fire, not withstanding  
any independent testing laboratory or other party approval  
of such component part or accessory.  
Pre-install Preparation  
This gas fireplace and its components are tested and safe  
when installed in accordance with this Installers Guide.  
Report to your dealer any parts damaged in shipment,  
particularly the condition of the glass. Do not install any  
unit with damaged, incomplete, or substitute parts.  
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE  
HAZARD.  
When planning a fireplace installation, it’s necessary  
to determine:  
The vent system components are shipped in separate pack-  
ages. The gas logs are packaged separately and must be  
field installed.  
Where the unit is to be installed.  
The vent system configuration to be used.  
Gas supply piping.  
Read all of the instructions before starting the instal-  
lation. Follow these instructions carefully during the  
installation to ensure maximum safety and benefit.  
Failure to follow these instructions will void the own-  
er’s warranty and may present a fire hazard.  
Electrical wiring.  
Framing and finishing details.  
Whether optional accessories—devices such as a fan,  
wall switch, or remote control—are desired.  
If the fireplace is to be installed on carpeting or tile,  
or on any combustible material other than wood  
flooring, the fireplace should be installed on a metal  
or wood panel that extends the full width and depth  
of the fireplace.  
10  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5-1/4  
(133mm)  
1/2  
(13mm)  
12  
(306mm)  
Ø8  
(205mm)  
12  
(305mm)  
42-5/8  
(1082mm)  
Ø8  
(205mm)  
ELECTRICAL  
ACCESS  
32-5/16  
(820mm)  
42  
21-9/16  
(547mm)  
(1067mm)  
GAS LINE  
ACCESS  
21-9/16  
34-3/4  
(883mm)  
(547mm)  
2-5/16  
(58mm)  
4-1/16  
(102mm)  
17-15/16  
(455mm)  
37-7/16  
(950mm)  
24  
(610mm)  
4-1/2  
(114mm)  
4-3/4  
(121mm)  
TOP VENT  
COLLARS  
TOP STANDOFFS  
REAR VENT  
COLLARS  
SIDE GLASS  
DOOR  
GAS CONTROLS  
& LABELS  
GAS LINE  
ACCESS  
ELECTRICAL  
ACCESS  
Figure 1. Diagram of the QV-PIER-HV-IPI  
11  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5-14  
(133mm)  
1/2  
(13mm)  
(4)  
12  
(306mm)  
Ø8  
(205mm)  
12  
(305mm)  
Ø8  
46-5/8  
(205mm)  
(1183mm)  
ELECTRICAL  
ACCESS  
32-5/16  
(821mm)  
4-1/2  
34-3/4  
(882mm)  
42  
(114mm)  
(1067mm)  
21-9/16  
(548mm)  
GAS LINE  
ACCESS  
8-1/2  
(216mm)  
36-3/16  
(919mm)  
2-5/16  
(58mm)  
24  
(610mm)  
4-1/16  
(102mm)  
2-9/16  
(64mm)  
4-3/4  
(121mm)  
4-1/2  
(114mm)  
Figure 2. Dimensions of the QV-ST-HV-IPI  
TOP VENT  
COLLARS  
TOP STANDOFFS  
REAR VENT  
COLLARS  
GAS CONTROLS  
& LABELS  
SIDE GLASS  
DOOR  
GAS LINE  
ACCESS  
ELECTRICAL  
ACCESS  
Figure 3. Diagram of the QV-ST-HV-IPI  
12  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Fireplace  
3
Step 1. Locating the Fireplace  
Note: This location diagram MUST be followed when in-  
stalling a QV-Pier-HV with a Catalina shelf/marble package  
since the fireplace is installed further from finished wall.  
The diagram below shows space and clearance require-  
ments for locating a fireplace within a room.  
FINISHED  
WALL  
Note: Refer to Figure 4B for dimensions and appliance  
locations if installing a QV-PIER-HV unit with a Catalina  
shelf and/or marble package.  
Î
GLASS  
GLASS  
36"  
QV-PIER-HV-IPI  
TOP VIEW  
GLASS  
36"  
45 -1/4 in.  
(1149mm)  
36"  
34-1/2 in.  
50-1/2 in.  
7 in.  
36"  
GLASS  
47-1/2 in.  
QV-ST-HV-IPI  
TOP VIEW  
13/16 in.  
GLASS  
36"  
45-1/4 in.  
Marble sizes (inches):  
Header .................................. 26 x 8  
Side headers .................. 45-1/2 x 8  
Legs................................ 33-1/2 x 7  
Figure 4A. Fireplace Dimensions and Locations  
Î
Note: Refer to the Catalina installation instruction  
included with kit for assembly and installation.  
Fireplace Locations/Dimensions with  
Catalina Shelf/Marble Package ONLY  
Figure 4B.  
Í
Clearance Requirements  
The top, back, and sides of the fireplace are defined by  
stand-offs. The minimum clearance to a perpendicular wall  
extending past the face of the fireplace is one inch (25 mm).  
The metal ends of the fireplace may NOT be recessed into  
combustible construction.  
13  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2. Framing the Fireplace  
Minimum Clearances  
from the Fireplace to Combustible Materials  
Fireplace framing can be built before or after the fireplace is  
set in place. Framing should be positioned to accommo-  
date wall coverings and fireplace facing material. The dia-  
gram below shows framing reference dimensions.  
Inches  
mm  
Glass Sides or Ends .......... 36 .................... 914  
CAUTION: MEASURE FIREPLACE DIMENSIONS AND  
VERIFY FRAMING METHODS AND WALL COVERING  
DETAILS BEFORE FRAMING.  
Floor ................................... 0 ....................... 0  
Rear Vent...........................1/2 ..................... 13  
Metal Sides or Ends ..........1/2 ..................... 13  
Top ................................... 2 1/2 ................... 64  
WARNING: FRAMING DIMENSIONS ASSUME  
!
Ceiling* .............................. 31 .................... 787  
USE OF 1/2 INCH THICK WALL COVERING  
MATERIALS ON EXTERIOR OF FRAMING ONLYAND  
NO SHEETROCK ON INTERIOR OF FRAMING.  
* The clearance to the ceiling is measured from the top of  
the unit, excluding the standoffs (see Figures 35 & 36).  
The distance from the unit to combustible construction is to  
be measured from the unit outer wrap surface to the com-  
bustible construction, NOT from the screw heads that se-  
cure the unit together.  
Minimum Clearances  
from the Vent Pipe to Combustible Materials  
Inches  
mm  
Vertical Sections. ............. 1 ................ 25  
Horizontal Sections  
Top ..................................... 3 ................ 75  
Bottom ............................... 1 ................ 25  
Sides ................................. 1 ................ 25  
At Wall Firestops  
Top .................................. 2 1/2 ............63.7  
Bottom .............................. 1/2 ............... 13  
Sides ................................. 1 ................ 25  
For minimum clearances, see the direct vent termination  
clearance diagrams on pages 25 and 26 in this manual.  
14  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shows center of 10” x 12” vent framing holes for top and rear venting. The center  
of the hole is one inch (25.4mm) above the center of the horizontal vent pipe.  
E
D
Framing should be  
constructed of 2 X 4  
lumber or heavier.  
QV-PIER-HV-IPI  
QV-ST-HV-IPI  
B
B
C
A
A
C
Model  
A
B
C
D
E
QV-PIER-HV-IPI  
QV-ST-HV-IPI  
42-1/8  
47-5/8  
42-1/2  
42-1/2  
23  
23  
35-3/4  
35-3/4  
48  
48  
NOTE: DIMENSIONS SHOWN IN INCHES  
Figure 5. Framing Dimensions  
15  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
6
12  
DVP4  
DVP6  
DVP12  
14-1/4  
12-3/16  
MAX.  
2
MIN.  
24  
36  
DVP12A  
48  
9-7/8  
DVP24  
45.0O  
10-1/4  
DVP45  
DVP36  
11-1/4  
7-1/4  
1-1/4 TYP  
DVP48  
1/2 TYP  
8-9/16  
12-9/16  
NOTE: PIPES OVERLAP 1-1/4 INCHES  
AT EACH JOINT.  
DVP90ST  
Figure 6. DVP-Series Direct Vent Component Specifications (5-inch inner pipe / 8-inch outer pipe)  
16  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Identifying Vent Components  
Step 3. Installing the Vent System  
The vent systems installed on this gas fireplace may in-  
clude one, two, or three 90° elbow assemblies. The rela-  
tionships of vertical rise to horizontal run in vent configura-  
tions using 90° elbows MUST BE strictly adhered to. The  
rise to run relationships are shown in the venting drawings  
and tables. Refer to the diagrams on the next several pages.  
A. Vent System Approvals  
These models are approved to use DVP series direct vent  
pipe components and terminations (see Figures 6 and 7).  
Approved vent system components are labeled for identifi-  
cation. This pipe is tested and listed as an approved com-  
ponent of the fireplace. The pipe is tested to be run inside  
an enclosed wall. There is no requirement for inspection  
openings at each joint within the wall. There is no required  
pitch for horizontal vent runs. NO OTHER VENTING SYS-  
TEMS OR COMPONENTS MAY BE USED.  
NOTE: Two 45° elbows may be used in place of one  
90° elbow. Rise to run ratios in the vent system must  
be followed if 45° elbows are used.  
This model has 450 elbow built into this unit. It may be  
positioned to vent either horizontal or vertical. Depending  
on the installation, decide which direction the elbow should  
be facing. Remove the 8 screws from the corner cover plate.  
Position the 450 elbow as desired and replace the corner  
cover plate with the 8 screws.  
Detailed installation instructions are included with each vent  
termination kit and should be used in conjunction with this  
Installers Guide.  
The flame and ember appearance may vary based on the  
type of fuel burned and the venting configuration used.  
STORM COLLAR  
ROOF FLASHING  
VERTICAL  
TERMINATION  
HORIZONTAL  
TERMINATION  
WALL FIRESTOP  
PIPE LENGTH  
Termination kits  
90 DEGREE  
ELBOW  
CEILING  
FIRESTOP  
DVP-TVHW  
DVP-TB1  
PVK-80  
DVP-TRAP  
(IPI models only)  
Figure 7. Vent System Components and Termination Kits  
17  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STRAIGHT UP  
VERTICAL VENTING  
V (FT.)  
BREAK  
HERE  
CAP  
50' MAX. (15.2 M)  
NOTE: On vertical venting  
configurations you may  
want to install the flue re-  
strictor (385-128). See flue  
restrictor installation in-  
structions.  
Figure 10. Flue Restrictor  
- CHART -  
3. Match the amount of  
vertical you have in the  
system with the chart to  
find the appropriate po-  
sition to set the Flue Re-  
strictor.  
Vertical  
Settings  
1-1  
4'  
8'  
1-2  
2-2  
2-3  
3-3  
4-3  
4-4  
4-4  
4-5  
15'  
20'  
25'  
30'  
35'  
40'  
50'  
Figure 8  
4. Center the Flue Restrictor on vent and secure in  
place using two self-tapping screws (see Figure 11).  
Flue Restrictor Instructions  
1. Locate the flue restrictor which is in the manual  
1
2
3
4
5
bag.  
SETTINGS  
FLUE  
RESTRICTOR  
1
2
3
4
5
Figure 11  
STRAIGHT OUT  
HORIZONTAL VENTING  
H
Max. Run  
24" (610 mm)  
Figure 9  
H
2. Break the Flue Restrictor into two pieces. Do this  
by bending the part back and forth until it breaks  
(see Figure 10).  
Figure 12.  
18  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NATURAL GAS - VENTING WITH ONE 90° ELBOW  
V (FT.)  
H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
6’ MIN. (1.83m)  
V + H = 50’ MAX. (15.2m)(11.3m)  
PROPANE - VENTING WITH ONE 90° ELBOW  
V (FT.)  
H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
6’ MIN. (1.83m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
V
V + H = 50’ MAX. (15.2m)  
H
Figure 13. Venting with One 90° Elbow  
H
V
NATURAL GAS  
PROPANE  
VENTING WITH ONE 90° ELBOW  
VENTING WITH ONE 90° ELBOW  
V (FT.)  
H (FT.)  
V (FT.)  
H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2.5’ MAX. (64mm)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2’ MAX. (610mm)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
6’ MIN. (1.83m)  
V + H = 50’ MAX. (15.2m)  
V + H = 50’ MAX. (15.2m)  
Figure 14. Venting with One 90° Elbow  
19  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NATURAL GAS  
VENTING WITH TWO 90° ELBOWS  
H
V
1
1
V (FT.)  
H + H (FT.)  
H
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2.5’ MAX. (64mm)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
6’ MIN. (1.83m)  
V + H + H1 = 50’ MAX. (15.2m)  
H + H1 = 18’ MAX. (5.5m)  
PROPANE  
VENTING WITH TWO 90° ELBOWS  
1
V (FT.)  
H + H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2’ MAX. (610mm)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
V + H + H1 = 50’ MAX. (15.2m)  
H + H1 = 12’ MAX. (3.6m)  
NATURAL GAS  
VENTING WITH TWO 90° ELBOWS  
V + V1 (FT.)  
H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2.5’ MAX. (64mm)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
V
1
V
6’ MIN. (1.83m)  
H
V + V1 + H = 50’ MAX. (15.2m)  
PROPANE  
VENTING WITH TWO 90° ELBOWS  
V + V1 (FT.)  
H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
6’ MIN. (1.83m)  
1
2’ MAX. (610mm)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
V + V + H = 50’ MAX. (15.2m)  
Figure 15. Venting with Two 90° Elbows  
20  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NATURAL GAS  
PROPANE  
VENTING WITH TWO 90° ELBOWS  
VENTING WITH TWO 90° ELBOWS  
1
V (FT.)  
H + H (FT.)  
1
V (FT.)  
H + H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
6’ MIN. (1.83m)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
V + H + H1 = 50’ MAX. (15.2m)  
1
V + H + H = 50’ MAX. (15.2m)  
1
H + H = 18’ MAX. (5.5m)  
1
H + H = 12’ MAX. (3.6m)  
H
1
V
H
Figure 16.  
Venting with Two 90° Elbows  
NATURAL GAS  
PROPANE  
VENTING WITH TWO 90° ELBOWS  
VENTING WITH TWO 90° ELBOWS  
1
V (FT.)  
H + H (FT.)  
1
V (FT.)  
H + H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
6’ MIN. (1.83m)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
V
V + H + H1 = 50’ MAX. (15.2m)  
1
V + H + H = 50’ MAX. (15.2m)  
H + H1 = 12’ MAX. (3.6m)  
H + H1 = 18’ MAX. (5.5m)  
H
1
H
Figure 17. Venting with Two 90° Elbows  
21  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NATURAL GAS  
PROPANE  
VENTING WITH THREE 90° ELBOWS  
VENTING WITH THREE 90° ELBOWS  
1
1
V + V (FT.)  
H + H (FT.)  
1
1
V + V (FT.)  
H + H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
6’ MIN. (1.83m)  
V+ V1 + H + H1 = 50’ MAX. (15.2m)  
1
+ H + H = 50’ MAX. (15.2m)  
V+ V1  
1
H + H = 18’ MAX. (5.5m)  
1
H + H = 12’ MAX. (3.6m)  
V
1
V
H
1
H
V
H
2
H
1
H
NATURAL GAS  
VENTING WITH THREE 90° ELBOWS  
PROPANE  
VENTING WITH THREE 90° ELBOWS  
1
1
2
V + V (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
H + H + H (FT.)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
1
1
2
V + V (FT.)  
H + H + H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
6’ MIN. (1.83m)  
V+ V1 + H + H1 + H2 = 50’ MAX. (15.2m)  
V+ V1 + H + H1 + H2 = 50’ MAX. (15.2m)  
1
H + H  
= 18’ MAX. (5.5m)  
+ H2  
1
H + H  
= 12’ MAX. (3.6m)  
+ H2  
Figure 18. Venting with three 90° elbows  
22  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
H
1
V
1
V
H
NATURAL GAS  
VENTING WITH THREE 90° ELBOWS  
1
1
V + V (FT.)  
H + H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2.5’ MAX. (64mm)  
3' MAX. (914mm)  
6' MAX. (1.83m)  
9' MAX. (2.7m)  
12' MAX. (3.6m)  
15’ MAX. (4.5m)  
18’ MAX. (5.5m)  
6’ MIN. (1.83m)  
V+ V1 + H + H1 = 50’ MAX. (15.2m)  
1
H + H = 18’ MAX. (5.5m)  
PROPANE  
VENTING WITH THREE 90° ELBOWS  
1
1
V + V (FT.)  
H + H (FT.)  
900 Elbow on top  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5’ MIN. (1.5m)  
2’ MAX. (610mm)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6’ MAX. (1.83m)  
8' MAX. (2.4m)  
10' MAX. (3.0m)  
12' MAX. (3.6m)  
6’ MIN. (1.83m)  
1
+ H + H = 50’ MAX. (15.2m)  
V+ V1  
1
H + H = 12’ MAX. (3.6m)  
V
1
H
1
V
H
Figure 19. Venting with three 90° elbows  
23  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting Out Vertically  
B. Installing Vent Components  
After determining which direction the 45O elbow will be used  
follow venting instructions accordingly.  
If your vertical vent component is over 4 feet, you may want  
to install the flue restrictor (located in the bag containing  
the install manual) to improve flame appearance. Center  
the flue restrictor on the 5” flue being used, and with self  
tapping screws secure the restrictor to the inside of the  
firebox as shown in Figure 22.  
This fireplace comes ready to vent horizontally.  
To vent off the unit vertically, the elbow cover plate must  
first be removed from the unit (see Figure 20).  
The elbow can be removed from the unit by aligning the  
seams of the elbow to the arrows on the surrounding  
heat shield (see Figure 21).  
Position the elbow in the vertical position. Snap in place  
with the starting collar.  
FLUE  
RESTRICTOR  
Replace the elbow cover plate aligning it with the elbow  
and secure in place with the 8 screws.  
Place rope ring around the first section of pipe and slide  
it up against the cover plate.  
NOTE: The rope ring is required for the heat manage-  
ment and to prevent cold air infiltration.  
ELBOW COVER PLATE  
Figure 22  
1. Attach the First Vent Component to the  
Starting Collars  
To attach the first vent component to the starting collars  
of the fireplace:  
• Slide the first vent section onto the unit and push in until  
they snap lock in position.  
Figure 20  
HEAT  
• Rotate this section to the desired position.  
• Using the two tabs provided on the elbow cover plate,  
secure the first section of venting to the fireplace with  
two screws.  
ARROWS  
SHIELD  
Refer to Cinch Pipe and Termination Cap installation  
instructions.  
If the installation is for a termination cap attached directly  
to the fireplace, skip to the sections, Install Firestops and  
Vent Termination.  
ELBOW  
SEAM  
ELBOW  
FRONT VIEW  
Figure 21  
TOP VIEW  
24  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Continue Adding Vent Components  
Refer to Cinch Pipe and Termination Cap installation in-  
structions.  
10"  
INTERIOR  
WALL SHIELD  
• Continue adding vent components, locking each succeed-  
ing component into place.  
• Ensure that each succeeding vent component is secure-  
ly fitted and locked into the preceding component in the  
vent system. Securing pipe sections with a maximum of  
two screws is recommended.  
12"  
• 90° elbows may be installed and rotated to any point  
around the preceding component’s vertical axis. If an el-  
bow does not end up in a locked position with the pre-  
ceding component, attach with a minimum of two (2)  
sheet metal screws.  
Figure 23. 10" x 12" Hole and Vent Pipe  
3. Install Support Brackets  
Refer to Cinch Pipe and Termination Cap installation  
instructions.  
HEAT SHIELD  
TRIM HEAT  
SHIELD IF TOO  
4. Install Firestops  
LONG, ADD TO  
SHIELD IF TOO  
SHORT  
For Horizontal Runs - Firestops are REQUIRED on both  
sides of a combustible wall through which the vent passes.  
NOTE: Model DVP-TRAP does not need an exterior  
firestop on an exterior combustible wall. The firestop is  
built into the cap.  
EXTERIOR  
FIRESTOP  
INTERIOR  
FIRESTOP  
To install firestops for horizontal runs that pass through either  
interior or exterior walls:  
• Cut a 10” x 12” (254mm X 305mm) hole through the wall.  
NOTE: The center of the hole is one (1) inch (25.4mm)  
above the center of the horizontal vent pipe.  
• Position the firestops on both sides of the hole previ-  
ously cut and secure the firestops with nails or screws.  
Figure 24 Heat Shield, Interior & Exterior Firestops  
• The heat shields of the firestops MUST BE placed to-  
wards the top of the hole.  
• Continue the vent run through the firestops.  
For Vertical Runs - One ceiling firestop is REQUIRED at  
the hole in each ceiling through which the vent passes.  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
To install firestops for vertical runs that pass through ceilings:  
• Position a plumb bob directly over the center of the verti-  
cal vent component.  
• Mark the ceiling to establish the centerpoint of the vent.  
• Drill a hole or drive a nail through this centerpoint.  
• Check the floor above for any obstructions, such as wir-  
ing or plumbing runs.  
• Reposition the fireplace and vent system, if necessary,  
to accommodate the ceiling joists and/or obstructions.  
• Cut an 10-inch X 10-inch (254mm x 254mm) hole through  
the ceiling, using the centerpoint previously marked.  
• Frame the hole with framing lumber the same size as the  
ceiling joists.  
25  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
10" (254mm)  
10" (254mm)  
C. Vent Termination  
CHIMNEY  
HOLE  
For Horizontal Terminations - To attach and secure the  
termination to the last section of horizontal vent refer to the  
Cinch Pipe and Termination Cap installation instructions.  
EXISTING CEILING  
JOISTS  
NEW  
FRAMING  
MEMBERS  
• Push on and snap lock as described at the beginning of  
the Installing Vent Components section.  
CEILING  
• The termination kit should pass through the wall firestops  
from the exterior of the building.  
Figure 25 Hole & New Framing Members  
• Adjust the termination cap to its final exterior position on  
the building and interlock the flue sections.  
If the area above the ceiling is NOT an attic, position and  
secure the ceiling firestop on the ceiling side of the previously  
cut and framed hole.  
WARNING: THE TERMINATION CAP MUST BE  
POSITIONED SO THAT THE ARROW IS  
POINTING UP.  
!
For trapezoidal cap termination kits:  
• Using screws secure the cap to the exterior wall through  
the flanges in the cap.  
JOIST  
WARNING: VENTING TERMINALS SHALL  
NOT BE RECESSED INTO A WALL OR SID-  
!
ING. VENT TERMINATION CLEARANCES MUST  
BE FOLLOWED TO AVOID FIRE DANGER. SEE  
VENT TERMINATION MINIMUM CLEARANCES DI-  
AGRAM ON FOLLOWING PAGE.  
CEILING  
NAILS (4 REQUIRED)  
CEILING FIRESTOP  
Figure 26. Ceiling Firestop (Ceiling Side)  
If the area above the ceiling IS an attic, position and secure  
the firestop on top of the previously framed hole.  
NOTE: Keep insulation away from the vent pipe at least 1  
inch (25mm).  
NAILS (4 REQUIRED)  
7 1/4"  
(184mm)  
Figure 28. Trapezoid Termination Cap  
RAFTER  
CEILING  
CEILING FIRESTOP  
Figure 27. Attic Firestop  
26  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
O
N
P
G
R
v
A
H
D
Q
(See Note 2)  
v
V
B
L
U.S.  
(3 FT)  
B
T
v
v
v
B
v
S
S
Electrical  
Service  
V
V
F
v
M
I
D*  
V
v
X
A
J or K  
X
= VENT TERMINAL  
=AIR SUPPLY INLET  
= AREA WHERE TERMINAL IS NOT PERMITTED  
V
A
B
= 12" ....................... clearances above grade, veran-  
K
= 3 ft. (U.S.A.)  
(See Note 1)  
da, porch, deck or balcony  
6 ft. (Canada) ......... clearance to a mechanical  
air supply inlet  
= 12" ....................... clearances to window or door  
that may be opened, or to per-  
L** = 7 ft. ......................... clearance above paved  
(See Note 1)  
sidewalk or a paved driveway  
located on public property  
manently closed window.  
D*  
= 18" ....................... vertical clearance to unventilat-  
ed soffit or to ventilated soffit lo-  
M*** = 18" ......................... clearance under veranda,  
porch, deck or balcony  
cated above the terminal  
N
O
P
= 6” ........................... non-vinyl sidewalls  
12” ......................... vinyl sidewalls  
*30” min. .............. for vinyl clad soffits and below  
electrical service  
= 18” ......................... non-vinyl soffit and overhang  
42” ......................... vinyl soffit and overhang  
F
=
9" ........................ clearance to outside corner  
G
H
= 6" ......................... clearance to inside corner  
= 8 ft.  
= 3 ft. (Canada) ...... not to be installed above a gas  
meter/regulator assembly within  
______________________________Q___M_I_N___________________________________  
______1__c__a_p__________________3___f_e_e__t_________________2__x___Q___A_C_T_U_A_L____  
______2__c__a_p__s________________6___f_e_e__t_________________1__x___Q___A_C_T_U_A_L____  
______3__c__a_p__s_________________9__f_e_e__t_______________2_/_3__x___Q___A_C_T_U_A__L___  
4 caps 12 feet 1/2 x Q ACTUAL  
RMAX  
3 feet (90cm) horizontally from the  
center-line of the regulator  
I
= 3 ft. (U.S.A.)  
6 ft. (Canada) ...... clearance to gas service regu-  
lator vent outlet  
= 9" (U.S.A.)  
QMIN = # termination caps x 3  
RMAX = (2 / # termination caps) x QACTUAL  
J
12" (Canada) ........ clearance to non-mechanical air  
supply inlet to building or the  
combustion air inlet to any other  
appliance  
S = 6" MIN................... clearance from sides of elec-  
(See Note 5)  
trical service  
T
= 12" MIN. ................ clearance above electrical  
(See Note 5)  
service  
NOTE 3: Local codes or regulations may require different  
clearances.  
** a vent shall not terminate directly above a sidewalk or paved  
driveway which is located between two single family dwellings  
and serves both dwellings.  
NOTE 4: Termination caps may be hot. Consider their proximity to  
doors or other traffic areas.  
*** only permitted if veranda, porch, deck or balcony is fully open on  
a minimum of 2 sides beneath the floor.  
NOTE 5: Location of the vent termination must not interfere with  
access to the electrical service.  
NOTE 1: On private property where termination is less than 7 feet  
above a sidewalk, driveway, deck, porch, veranda or balcony, use of  
a listed cap shield is suggested.  
WARNING: In the U.S: Vent system termination is NOT permitted  
in screened porches. You must follow side wall, overhang and  
ground clearances as stated in the instructions.  
NOTE 2: Termination in an alcove space (spaces open only on one side  
and with an overhang) are permitted with the dimensions specified for  
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum  
between termination caps. 2. All mechanical air intakes within 10 feet  
of a termination cap must be a minimum of 3 feet below the termination  
cap. 3. All gravity air intakes within 3 feet of a termination cap must be  
a minimum of 1 foot below the termination cap.  
In Canada: Vent system termination is NOT permitted in screened  
porches. Vent system termination is permitted in porch areas  
with two or more sides open. You must follow all side walls,  
overhang and ground clearances as stated in the instructions.  
Quadra-Fire assumes no responsibility for the improper perfor-  
mance of the fireplace when the venting system does not meet  
these requirements.  
Figure 29. Vent Termination Minimum Clearances  
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE  
INSTALLED.  
27  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To seal the roof hole, and to divert rain and snow from the  
vent system:  
For Vertical Terminations - To locate the vent and install  
the vent sections:  
• Locate and mark the vent centerpoint on the underside  
of the roof, and drive a nail through the centerpoint.  
• Attach a flashing to the roof using nails, and use a non-  
hardening mastic around the edges of the flashing base  
where it meets the roof.  
• Make the outline of the roof hole around the centerpoint  
nail.  
• Attach a storm collar over the flashing joint to form a  
water-tight seal. Place non-hardening mastic around the  
joint, between the storm collar and the vertical pipe.  
• The size of the roof hole framing dimensions depend on the  
pitch of the roof. There MUST BE a 1-inch (25.4mm) clear-  
ance from the vertical vent pipe to combustible materials.  
• Slide the termination cap over the end of the vent pipe  
and snap into place.  
• Mark the roof hole accordingly.  
HORIZONTAL  
OVERHANG  
• Cover the opening of the installed vent pipes.  
• Cut and frame the roof hole.  
2 FT.  
MIN.  
20 INCH MIN.  
VERTICAL  
WALL  
• Use framing lumber the same size as the roof rafters  
and install the frame securely. Flashing anchored to the  
frame must withstand heavy winds.  
LOWEST  
DISCHARGE  
OPENING  
TERMINATION  
CAP  
• Continue to install concentric vent sections up through  
the roof hole (for inside vent installations) or up past the  
roof line until you reach the appropriate distance above  
the roof (for outside terminations).  
X
12  
ROOF PITCH  
IS X/ 12  
H (MIN.) - MINIMUM HEIGHT FROM ROOF  
TO LOWEST DISCHARGE OPENING  
WARNING: MAJOR U.S. BUILDING CODES  
SPECIFY MINIMUM CHIMNEY AND/OR  
!
VENT HEIGHTABOVE THE ROOF TOP. THESE MIN-  
IMUM HEIGHTS ARE NECESSARY IN THE INTER-  
EST OF SAFETY. SEE THE FOLLOWING DIAGRAM  
FOR MINIMUM HEIGHTS, PROVIDED THE TERMI-  
NATION CAPISAT LEAST 20 INCHES FROMAVER-  
TICAL WALLAND 2-FEET BELOWAHORIZONTAL  
OVERHANG.  
Roof Pitch  
H (min.) ft.  
flat to 6/12  
1.0  
1.25  
1.5  
2.0  
2.5  
over 6/12 to 7/12  
over 7/12 to 8/12  
over 8/12 to 9/12  
over 9/12 to 10/12  
NOTE: This also pertains to vertical vent systems in-  
stalled on the outside of the building.  
over 10/12 to 11/12  
over 11/12 to 12/12  
over 12/12 to 14/12  
over 14/12 to 16/12  
over 16/12 to 18/12  
over 18/12 to 20/12  
over 20/12 to 21/12  
3.25  
4.0  
5.0  
6.0  
7.0  
7.5  
8.0  
Figure 30. Minimum Height from Roof to  
Lowest Discharge Opening  
28  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4. Positioning, Leveling, and Securing  
the Fireplace  
Step 5. The Gas Control System  
WARNING: THIS UNIT IS NOT FOR USE WITH  
!
The diagram below shows how to properly position, level,  
and secure the fireplace.  
SOLID FUEL.  
FLAME  
SENSOR  
IPI PILOT  
ROD  
NAILING  
TABS  
(BOTH SIDES)  
Figure 32. Gas Control System  
Intermittent Pilot Ignition (IPI) System  
This system includes a 3V control valve, electronic module  
and intermittent pilot.  
WARNING: CONTINUOUS 110-120 VAC  
SERVICE MUST BE WIRED DIRECTLY TO  
!
THE FIREPLACE JUNCTION BOX IN A IPI SYSTEM.  
Figure 31. Proper Positioning, Leveling, and  
Securing of a Fireplace  
• Place the fireplace into position.  
• Level the fireplace from side to side and from front to  
back.  
• Shim the fireplace with non-combustible material, such  
as sheet metal, as necessary.  
• Secure the fireplace to the framing by nailing or screwing.  
• Holes are provided in the base pan for securing the unit  
to the floor.  
29  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 6. The Gas Supply Line  
NOTE: Have the gas supply line installed in accordance  
with local building codes by a qualified installer  
approved and/or licensed as required by the locality.  
(In the Commonwealth of Massachusetts installation  
must be performed by a licensed plumber or gas  
fitter).  
USE A WRENCH ON  
SHUT-OFF VALVE  
WHEN TIGHTENING  
GAS LINE.  
NOTE: Before the first firing of the fireplace, the gas  
supply line should be purged of any trapped air.  
MANUAL  
SHUT-OFF  
VALVE  
NOTE: Consult local building codes to properly size  
the gas supply line leading to the 1/2 inch  
(13 mm) hook-up at the unit.  
FLEX CONNECTOR  
GAS VALVE  
GAS LINE  
ACCESS  
This gas fireplace is designed to accept a 1/2 inch  
(13 mm) gas supply line.  
CONTROL VALVE  
Figure 33. Gas Supply Line  
To install the gas supply line:  
• A listed (and Commonwealth of Massachusetts approved)  
1/2 inch (13mm) tee-handle manual shut-off valve and a  
listed flexible gas connector are connected to the 1/2  
inch (13mm) inlet of the control valve. NOTE: If substi-  
tuting for these components, please consult local codes  
for compliance.  
Step 7. Gas Pressure Requirements  
Pressure requirements for Quadra-Fire gas fireplaces  
are shown in the table below.  
• Locate the gas line access hole in the outer casing of  
the fireplace.  
Pressure  
Natural Gas  
Propane  
• The gas line may be run from either side of the fireplace  
provided the hole in the outer wrap does not exceed 2” in  
diameter and it does not penetrate the actual firebox.  
Minimum  
Inlet Pressure  
5.0 inches  
w.c.  
11.0 inches  
w.c.  
Maximum Inlet  
Gas Pressure  
14.0 inches  
w.c.  
14.0 inches  
w.c.  
• Open the fireplace lower grille, insert the gas supply line  
through the gas line hole, and connect it to the shut-off  
valve.  
Manifold  
Pressure  
3.5 inches  
w.c.  
10.0 inches  
w.c.  
• When attaching the pipe, support the control so that the  
lines are not bent or torn.  
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is  
provided on the inlet and outlet side of the gas control for a  
test gauge connection to measure the manifold pressure.  
• After the gas line installation is complete, all connec-  
tions must be tightened and checked for leaks with a  
commercially-available, non-corrosive leak check solu-  
tion. Be sure to rinse off all leak check solution following  
testing.  
The fireplace and its individual shut-off valve must be  
disconnected from the gas supply piping system during  
any pressure testing of the system at test pressures in  
excess of one-half (1/2) psig (3.5 kPa).  
WARNING: DO NOT USE AN OPEN FLAME  
TO CHECK FOR GAS LEAKS.  
!
The fireplace must be isolated from the gas supply piping  
system by closing its individual shut-off valve during any  
pressure testing of the gas supply piping system at test  
pressures equal to or less than one-half (1/2) psig (3.5 kPa).  
• Insert insulation from the outside of the fireplace and  
pack the insulation tightly to totally seal between the  
pipe and the outer casing.  
• At the gas line access hole the gap between the supply  
piping and gas access hole can be plugged with non-  
combustible insulation to prevent cold air infiltration.  
30  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
I
BULB SOCKET  
ASSEMBLY (3)  
IGNITION MODULE 3 VAC  
INTERMITTENT  
PILOT IGNITOR  
S
PLUG-IN  
3V TRANSFORMER  
ON/OFF  
WALL SWITCH  
FLAME SPARKER/  
SENSOR  
IGNITION  
MODULE  
(3V)  
WHT  
ORG  
BLK  
WHT  
GROUND TO  
FIREPLACE  
CHASSIS  
LOW VOLTAGE  
SEE NOTE 1  
VALVE  
REMOTE  
CONTROL  
GROUND  
NEUTRAL  
HOT  
SCALE 1/1  
TERMINAL BLOCK  
ELECTRONIC EMBERS  
Note: An alternate electronic ember  
switch can be installed on the wall  
by connecting a minimum 18 gage  
Romexto the leads supplied on  
the back of the electric ember  
switch.  
FLAME ON/OFF  
3 VAC  
TRANSFORMER  
WHITE WIRE  
CAN BE  
BLACK WIRE CAN BE  
VALVE  
PLUGGED INTO ANY OF  
#1 - #5 LOCATIONS  
ON THE HOT SIDE  
PLUGGED  
INTO ANY  
OF #1 - #5  
LOCATIONS  
ON THE  
NEUTRAL  
SIDE  
LCOR & RCOR JUNCTION BOX  
PLUG IN  
Figure 34. Intermittent Pilot Ignition (IPI) Wiring Diagram  
Step 8. Wiring the Fireplace  
NOTE: Electrical wiring must be installed by a licensed  
electrician.  
Operation using Battery Power  
This fireplace has an optional battery operation. The sys-  
tem is fully functional with the use of two “D” size batteries  
without ordinary 110-120 VAC power.  
CAUTION: DISCONNECT REMOTE CONTROLS IF AB-  
SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-  
VENTACCIDENTAL FIREPLACE OPERATION.  
Wiring to the battery pack should be left disconnected in  
order to conserve battery life. In the case of a loss of power,  
simply connect red and black wire leads to activate battery  
power (connect red to red, black to black). The fireplace  
can be used as necessary. Once power (110 VAC) is re-  
stored, disconnect red and black wire leads to extend bat-  
tery life.  
For Intermittent Pilot Ignition Wiring  
Appliance Requirements  
This appliance requires that 110-120 VAC be wired to the  
junction box. Maintain correct polarity when wiring the junc-  
tion box.  
31  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: If any of the original wire as supplied with  
the appliance must be replaced, it must be replaced  
with the type 105oC rated wire.  
TEMPERATURE  
SENSOR SWITCH  
FAN  
JUNCTION  
BOX  
SPEED CONTROL  
(RHEOSTAT)  
DETAIL A  
SCALE 1/1  
SEE DETAIL A  
Figure 35. Fan Wiring Diagram  
Optional Accessories  
Wall Switch  
Position the wall switch in the desired position on a wall.  
Run a maximum of 25 feet (7.8 m) or less length of 18A.W.G.  
minimum wire and connect it to the fireplace ON/OFF switch  
pigtails.  
Optional fan and remote control kits require that 110-120  
VAC be wired to the factory installed junction box before  
the fireplace is permanently installed.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-  
TION WHEN SERVICING CONTROLS. WIRING ERRORS  
CAN CAUSE IMPROPERAND DANGEROUS OPERATION.  
VERIFY PROPER OPERATION AFTER SERVICING.  
Fan Installation  
Recommended fan locations for the type of fireplace you  
have (see Figures 36 and 37).  
FAN  
FAN  
Figure 37. ST & PIER fan location  
ST & Pier fan location  
Figure 36. Corner fan location  
Corner fan location  
It is recommended to position the fan in this location as  
shown. This will provide the best air flow (see Figure 36).  
It is recommended to position the fan on the same side of  
the fireplace as the vent collars are on. This will provide the  
best air flow (see Figure 37).  
32  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: IF JOINTS BETWEEN THE FIN-  
ISHED WALLS AND THE FIREPLACE SUR-  
ROUND (TOP AND SIDES) ARE SEALED, A  
300° F. MINIMUM SEALANT MATERIAL  
MUST BE USED. THESE JOINTS ARE NOT  
REQUIRED TO BE SEALED. ONLY NON-  
COMBUSTIBLE MATERIAL (USING 300° F.  
MINIMUM ADHESIVE, IF NEEDED) CAN BE  
APPLIED AS FACING TO THE FIREPLACE  
SURROUND. SEE THE DIAGRAM BELOW.  
Step 9. Finishing  
Figure 38 shows the minimum vertical and corresponding maximum  
horizontal dimensions of fireplace mantels or other combustible  
projections above the top front edge of the fireplace. See Figures 4 and  
5 for other fireplace clearances. Only non-combustible materials  
may be used to cover the black fireplace front.  
WARNING: WHEN FINISHING THE FIREPLACE, NEVER  
OBSTRUCT OR MODIFY THE AIR INLET/OUTLET GRILLES  
!
IN ANY MANNER.  
NOTE: Sheetrock or other combustible mate-  
rial such as wood can be placed on the top  
edge and sides of the fireplace.  
12”  
MANTEL  
11”  
10”  
9”  
QV-ST-HV-IPI  
TOP EDGE  
8”  
7”  
6”  
5”  
Mantel dimensions shown are  
for standard hood on models:  
QV-PIER-HV-IPI.  
4”  
SIDE EDGE  
*
16”  
3”  
15”  
14”  
13”  
2”  
5”  
12”  
11”  
1”  
10”  
9”  
8”  
7”  
To use mantel dimensions  
shown the fireplace must have  
the standard hood replaced  
with a larger hood (060-143)  
on model: QV-ST-HV-IPI.  
6”  
*
0” GAP  
QV-PIER-HV-IPI  
HOOD  
TOP EDGE  
*
NOTE: 12” mantel  
at 16” above hood.  
SIDE EDGE  
Minimum Vertical and Maximum Horizontal  
Dimensions of Combustibles above Fireplace  
Figure 38.  
12”  
MANTEL  
11”  
0” GAP  
10”  
9”  
Figure 40. Sealant Material  
8”  
Mantel dimensions shown are  
for standard hood on model:  
QV-ST-HV-IPI  
*
7”  
6”  
5”  
Hearth Extensions  
4”  
3”  
A hearth extension may be desirable for  
aesthetic reasons. However,ANSI or CAN/CGA  
testing standards do not require hearth  
extensions for gas fireplace appliances.  
2”  
1”  
23”  
22”  
21”  
20”  
19”  
18”  
17”  
16”  
15”  
14”  
13”  
12”  
HOOD  
NOTE: 12” mantel at  
23” above hood.  
*
Minimum Vertical and Maximum Horizontal  
Dimensions of Combustibles above Fireplace  
Figure 39.  
33  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparing Electric Ember Bed and Lava Rock  
Step 10. Installing Trim, Logs & Ember Material  
Installing the Trim  
Start with fitting your grate with the andirons found in your  
manual bag assembly. You will find four andirons and four  
andiron tabs as shown (see Figure 41).  
Combustible materials may be brought up to the specified  
clearances on the side and top front edges of the fireplace,  
but MUST NEVER overlap onto the front face. The joints  
between the finished wall and the fireplace top and sides  
can only be sealed with a 300° F. (149° C) minimum sealant.  
ANDIRONS  
ANDIRON TABS  
WARNING: WHEN FINISHING THE FIREPLACE,  
NEVER OBSTRUCT OR MODIFY THE AIR INLET/  
!
OUTLET GRILLES IN ANY MANNER.  
Install optional marble and brass trim surround kits as  
desired. Marble, brass, brick, tile, or other non-combustible  
materials can be used to cover up the gap between  
combustible material (sheetrock or wood) and the fireplace.  
Do not obstruct or modify the air inlet/outlet grilles. When  
overlapping on both sides, leave enough space so that the  
bottom grille can be lowered and the trim door removed.  
Figure 41.  
Positioning the Logs  
If the gas logs have been factory installed they should not  
need to be positioned. If the logs have been packaged  
separately, refer to the instructions that accompany the  
logs. Save the log instructions with this manual.  
Slip the tabs onto the bottom of the andiron as shown.  
Bend the tab at the cut closest to the andiron. Repeat this  
step for all four andirons (see Figure 42).  
If sooting occurs, the logs might need to be repositioned  
slightly to avoid excessive flame impingement.  
Shutter Settings  
NG  
LP  
___________________________________________  
QV-PIER-HV-IPI  
3/8”  
FULL OPEN  
___________________________________________  
QV-ST-HV-IPI  
3/8”  
FULL OPEN  
Glass Specifications  
Model  
Type  
QV-PIER-HV-IPI  
TEMPERED  
QV-ST-HV-IPI  
TEMPERED  
Figure 42.  
Quadra-Fire fireplaces manufactured with tempered glass  
may be installed in hazardous locations such as bathtub  
enclosures as defined by the CPSC. The tempered glass  
has been tested and certified to the requirements of ANSI  
Z97.1-1984 and CPSC 16 CFR 1202. (Safety Glazing Certi-  
fication Council SGCC # 1595 and 1597. Architectural Test-  
ing, Inc. Reports 02-31919.01 and 02-31917.01.)  
Place the andiron on the grate as shown and bend the tab  
under the grate bar, positioning the andiron about 1/2” from  
the grate tine (see Figure 43).  
This statement is in compliance with CPSC 16 CFR Sec-  
tion 1201.5 “Certification and labeling requirements” which  
refers to 15 USC 2063 stating “…Such certificate shall ac-  
company the product or shall otherwise be furnished to any  
distributor or retailer to whom the product is delivered.”  
1/2”  
Some local building codes require the use of tempered glass  
with permanent marking in such locations. Glass meeting  
this requirement is available from the factory. Please con-  
tact your dealer or distributor to order.  
BENDTABUNDER  
GRATEBAR  
Figure 43.  
34  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Repeat for all four andirons as shown (see Figure 44).  
Pile a thin layer and follow the pattern on the base pan  
(see Figure 47).  
Figure 44.  
Figure 47.  
The electric ember bed must be prepared before the logs  
are set up (see Figure 45).  
Now the Lava rock can be applied (see Figure 48).  
Figure 45.  
Figure 48.  
Start by applying the teco-sil (granulated glass) to the base  
pan (see Figure 46).  
The lava rock should cover the remaining base pan area  
(see Figure 49). Do not put lava rock on top of the glass  
(teco-sil).  
Figure 46.  
Figure 49.  
35  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Turn on the electric ember lights and paint the glass to a  
darkness as desired (see Figure 50).  
Placing the Ember Material  
Ember material is shipped with this gas fireplace. The bag  
labeled Glowing Ember (050-721) is standard glowing em-  
ber material.  
To place the ember material:  
Remove the glass door from the unit.  
Place dime size pieces of ember material about 1/2 inch  
apart near port holes in burner top. Do NOT press em-  
bers into burner ports. Cover the top of the burner with a  
single layer of ember material.  
Save the remaining ember materials for use during fire-  
place servicing. The bag of embers provided is sufficient  
for 3 to 5 applications.  
Figure 50.  
Replace the glass door and a front trim door on the unit.  
Make sure to paint the glass from both sides (see  
Figure 51).  
Figure 53. Placement of the Ember Material  
Figure 51.  
The ember bed is now complete (see Figure 52).  
Figure 52.  
36  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ember Light Replacement Bulb  
Step 11. Before Lighting the Fireplace  
In the lower gas valve compartment you will find three ac-  
cess panels for the three light bulbs (see Figure 54).  
Before lighting the fireplace, be sure to do the following:  
Remove all paperwork from underneath the fireplace.  
Review safety warnings and cautions  
ACCESS PANEL  
• Read the Safety and Warning Information section at  
the beginning of this Installers Guide.  
Double-check for gas leaks  
Before lighting the fireplace, double-check the unit for  
possible gas leaks.  
Double-check vent terminations and front grilles for  
obstructions.  
• Before lighting the fireplace, double-check the unit for  
possible obstructions that could be blocking the vent ter-  
minations or the front grilles.  
Figure 54.  
Double-check for faulty components  
• Any component that is found to be faulty MUST BE re-  
placed with an approved component. Tampering with the  
fireplace components is DANGEROUS and voids all war-  
ranties.  
Using a 5/16” nut driver remove the two bolts (see  
Figure 55).  
A small amount of air will be in the gas supply lines. When  
first lighting the fireplace, it will take a few minutes for the  
lines to purge themselves of this air. Once the purging is  
complete, the fireplace will light and will operate normally.  
ACCESS PANEL  
Subsequent lightings of the fireplace will not require this  
purging of air from the gas supply lines, unless the gas  
valve has been turned to the OFF position, in which  
case the air would have to be purged.  
NOTE: The fireplace should be run 3 to 4 hours on the initial  
start-up. Turn it off and let it cool completely. Remove and  
clean the glass. Replace the glass and run the fireplace for  
an additional 8 hours. This will help to cure the products  
used in the paint and logs.  
Figure 55.  
During this break-in period it is recommended that some  
windows in the house be opened for air circulation. This will  
help avoid setting off smoke detectors, and help eliminate  
any odors associated with the fireplace’s initial burning.  
Pull the access panel to expose the light bulb. Wearing  
clean cotton gloves replace the bulb. Any skin oils which  
get on a new bulb will greatly shorten the life of the bulb.  
The bulb can be cleaned with isopropyl alcohol (see Figure 56).  
Step 12. Lighting the Fireplace  
You’ve reviewed all safety warnings, you’ve checked the  
fireplace for gas leaks, you know the vent system is  
unobstructed, and you’ve checked for faulty components.  
Now you’re ready to light the fireplace.  
WARNING: PLEASE REFER TO THE USER’S  
MANUALFORALL CAUTIONS, SAFETY, AND  
!
WARNING INFORMATION PERTAINING TO THE  
LIGHTING AND OPERATION OF THE FIREPLACE.  
Figure 56  
After the Installation  
LEAVE THIS INSTALLATION MANUAL WITH  
THE APPLIANCE FOR FUTURE REFERENCE.  
!
37  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintaining and Servicing Your Fireplace  
4
Fireplace Maintenance  
Although the frequency of your fireplace servicing and main-  
tenance will depend on use and the type of installation, you  
should have a qualified service technician perform an appli-  
ance check-up at the beginning of each heating season.  
See the table below for specific guidelines regarding each  
fireplace maintenance task.  
IMPORTANT: TURN OFF THE GAS BEFORE SERVICING  
YOUR FIREPLACE.  
Replacing old ember material  
Frequency: Once annually, during the checkup.  
By: Qualified service technician.  
MAKE SURE THE FLAMES  
ARE STEADY—NOT  
LIFTING OR FLOATING.  
Task: Brush away loose ember material near the burner.  
Replace old ember material with new dime-size and shape  
pieces of Golden Ember (GE-93) and Glowing Ember (050-  
721). New ember material should be placed alternately on  
top of the burner - a layer of Golden Ember, a layer of  
Glowing Ember, and so on. Save the remaining ember  
material and repeat this procedure at your next servicing.  
For more information, see Placing Ember Material.  
Figure 57. Burner Flame Patterns  
Checking Vent System  
Frequency: Before initial use and at least annually  
thereafter, more frequently if possible.  
Cleaning Burner and Controls  
Frequency: Once annually.  
By: Qualified service technician.  
Task: Brush or vacuum the control compartment, fireplace  
logs and burner areas surrounding the logs.  
By: Qualified service technician/Home owner.  
Task: Inspect the external vent cap on a regular basis to  
ensure that no debris is interfering with the flow of air. Inspect  
entire vent system for proper function.  
Cleaning Glass Door  
Frequency: After the first 3 to 4 hours of use. As neces-  
sary after initial cleaning.  
Cleaning Flame Sensor Rod (IPI Systems)  
Frequency: Periodically.  
By: Qualified service technician.  
By: Home owner.  
Task: Remove and clean glass after the first 3 to 4 hours of  
use. After the initial cleaning, clean as necessary, particu-  
larly after adding new ember (flame colorant) material. Film  
deposits on the inside of the glass door should be cleaned  
off using a household glass cleaner. NOTE: DO NOT handle  
or attempt to clean the door when it is hot and DO  
NOT use abrasive cleaners.  
Task: Make a visual check of the straight flame sensor rod  
(see Figure 32). Use emery cloth to carefully remove any  
existing white film or deposits.  
Checking Flame Patterns, Flame Height  
Frequency: Periodically.  
By: Qualified service technician/Home owner.  
Task: Make a visual check of your fireplace’s flame patterns.  
Make sure the flames are steady - not lifting or floating.  
See Figure 57. The flame sensor (IPI) should be covered  
with flame. See Figure 32.  
38  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
5
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do  
experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the  
corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician.  
Intellifire Ignition System  
Symptom  
Possible Causes  
Corrective Actions  
1. The  
a. Incorrect wiring.  
Verify "S" wire (white) for sensor and "I" wire (orange) for ignitor are  
connected to correct terminals on module and pilot assembly. Reversed wires  
at the module may cause system to make sparking noise, but spark may not  
be present at pilot hood.  
ignitor/module  
makes noise, but no  
spark.  
b. Loose  
Verify no loose connections or electrical shorts in wiring from module to pilot  
assembly. Rod closest to pilot hood should be ignitor. Verify connections  
underneath pilot assembly are tight; also verify connections are not grounding  
out to metal chassis, pilot burner, pilot enclosure, mesh screen if present, or  
any other metal object.  
connections or  
electrical shorts in  
the wiring.  
c. Ignitor gap is too Verify gap of igniter to pilot hood. The gap should be approximately .17 inch  
large.  
or 1/8 inch.  
d. Faulty module.  
Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor  
wire "I" from module. Place ON/OFF Rocker switch or wall switch in ON  
position. Hold ground wire about 3/16 inch away from "I" terminal on module.  
If there is no spark at "I" terminal module must be replaced. If there is a spark  
at "I" terminal, module is fine. Inspect pilot assembly for shorted sparker wire  
or cracked insulator around electrode.  
2. Pilot won't light,  
there is no noise or installed correctly.  
spark.  
a. Transformer  
Verify that transformer is installed and plugged into module. Check voltage of  
transformer under load at spade connection on module with ON/OFF switch in  
ON position. Acceptable readings of a good transformer are between 3.2 and  
2.8 volts AC.  
b. A shorted or  
Remove and reinstall the wiring harness that plugs into module. Verify there is  
loose connection in a tight fit. Verify pilot assembly wiring to module. Remove and verify continuity  
wiring configuration of each wire in wiring harness.  
or wiring harness.  
c. Improper wall  
switch wiring.  
d. Module not  
grounded.  
Verify black ground wire from module wire harness is grounded to metal  
chassis of appliance.  
e. Faulty module.  
Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor  
wire "I" from module. Place ON/OFF Rocker switch or wall switch in ON  
position. Hold ground wire about 3/16 inch away from "I" terminal on module.  
If there is no spark at "I" terminal module must be replaced. If there is a spark  
at "I" terminal, module is fine. Inspect pilot assembly for shorted sparker wire  
or cracked insulator around electrode.  
3. Pilot lights but  
a. A shorted or  
Verify all connections to wiring diagram in manual. Verify connections  
continues to spark, loose connection in underneath pilot assembly are tight. Verify connections are not grounding out  
and main burner will sensor rod.  
not ignite. (If the  
to metal chassis, pilot burner, pilot enclosure or screen if present, or any other  
metal object.  
pilot continues to  
b. Poor flame  
Verify that flame is engulfing sensor rod. If the pilot assembly does not have a  
ground strap, consider installing one to increase flame rectification. Verify  
correct pilot orifice is installed and inlet gas specifications. Flame carries  
rectification current, not the gas. If flame lifts from pilot hood, the circuit is  
broken. A wrong orifice or too high an inlet pressure can cause pilot flame to  
lift. The sensor rod may be contaminated. Clean sensor rod with emery cloth.  
spark after the pilot  
rectification or  
flame has been lit,  
contaminated  
flame rectification  
sensor rod.  
has not occurred.)  
Continued...  
39  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Intellifire Ignition System - (continued)  
Symptom  
Possible Causes  
Corrective Actions  
c. Module is not  
grounded.  
Verify that module is securely grounded to metal chassis of appliance. Verify  
that wire harness is firmly connected to module.  
d. Damaged pilot  
assembly or dirty  
sensor rod.  
Verify that ceramic insulator around the sensor rod is not cracked, damaged,  
or loose. Verify connection from sensor rod to white sensor wire. Clean  
sensor rod with emery cloth to remove any contaminants that may have  
accumulated on sensor rod. Verify continuity with a multimeter with ohms set  
at lowest range.  
e. Faulty module.  
Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor  
wire "I" from module. Place ON/OFF Rocker switch or wall switch in ON  
position. Hold ground wire about 3/16 inch away from "I" terminal on module.  
If there is no spark at "I" terminal module must be replaced. If there is a  
spark at "I" terminal, module is fine. Inspect pilot assembly for shorted  
sparker wire or cracked insulator around electrode.  
4. Pilot sparks, but a. Correct gas  
Verify that incoming gas line ball valve is "open". Verify that inlet pressure  
reading is within acceptable limits, inlet pressure must not exceed 14 in.  
W.C.  
Pilot will not light.  
supply.  
b. Ignitor gap is  
too large.  
Verify that spark gap from ignitor to pilot hood is .17 in. or 1/8 in.  
c. Module is not  
grounded.  
Verify module is securely grounded to metal chassis of appliance.  
40  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Î
Lifetime Warranty  
LIMITED LIFETIME WARRANTY  
The Hearth & Home Technologies limited Lifetime Warranty guarantees that the following components will work as  
designed for the lifetime of the stove or Hearth & Home Technologies will repair or replace them. These items  
include but are not limited to steel and cast iron components, all gas burners, gas logs, combustion chambers,  
heat exchanger systems, stainless steel firebox components, plating, doors, glass damaged by thermal breakage,  
steel baffle supports, steel and ceramic baffles and manifold tubes. Labor is for the first five years.  
THREEYEAR WARRANTY  
Our EZ Clean firepots are covered under Hearth & Home Technologies three-year warranty program. Labor is for  
3 years.  
TWO YEAR WARRANTY  
All electrical components such as but not limited to blowers, wiring, vacuum switches, speed controls, control  
boxes, thermodisc switches, igniters, pilot assembly, gas valves, thermostats and remotes are covered under  
Hearth & Home Technologies two-year warranty program. Effective April, 2005 igniters are also covered under the  
two year warranty. Labor is for two years.  
ONEYEAR WARRANTY  
Porcelain and powdercoat finishes are warranted against manufacturer defects for one year. Labor to repair or  
replace these parts is covered for one year, reimbursed per our warranty service fee schedule.  
CONDITIONS  
This warranty is nontransferable and is made to the original retail purchaser only provided that the purchase was  
made through an authorized dealer of Hearth & Home Technologies. It must be installed and operated at all times  
in accordance with the Installation and Operating Instructions furnished with this product, as well as any applicable  
local and national codes. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.  
Labor to repair or replace items covered under the limited Lifetime Warranty will be covered for the first five years per  
our warranty service fee reimbursement schedule. Parts covered under the limited Lifetime Warranty will be covered  
for the lifetime of the appliance up to a maximum of ten (10) years after Hearth & Home Technologies discontinues  
the model and two  
(2) years for optional accessories. Adjustments, regular maintenance, cleaning and temporary repairs do not  
qualify for a service call fee and will not be covered. The replacement of consumer replaceable items and installation  
of upgraded component parts do not quality for a service call fee, and will not be covered.  
This limited Lifetime Warranty does not extend to or include surface finish on the appliance, door gasketing, glass  
gasketing, glass, firebrick, pellet logs, kaowool or other ceramic insulating materials. It does not cover installation  
or operational-related problems such as overfiring, use of corrosive driftwood, downdrafts or spillage caused by  
environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate venting or ventilation, excessive  
offsets, or negative air pressures caused by mechanical systems such as furnaces, fans, clothes dryers, etc.  
Any installation, construction, transportation, or other related costs or expenses arising from defective part(s),  
repair, replacement, etc., will not be covered by this warranty, nor will Hearth & Home Technologies assume  
responsibility for them. Further, Hearth & Home Technologies will not be responsible for any incidental, indirect, or  
consequential damages, except as results in damage to the interior or exterior of the building in which this appliance  
is installed. This limited Lifetime Warranty does not apply to the venting components, hearth components or other  
accessories used in conjunction with the installation of this product not manufactured by Hearth & Home  
Technologies  
This warranty is void if the stove has been overfired or operated in atmospheres contaminated by chlorine, fluorine,  
or other damaging chemicals, the stove is subjected to prolonged periods of dampness or condensation, or there  
is any damage to the stove or other components due to water or weather damage which is the result of, but not  
limited to, improper chimney or venting installation. Hearth & Home Technologies may, at its discretion, fully  
discharge all obligations with respect to this warranty by either repairing or replacing the unit, or refunding the  
wholesale price of the defective part(s).  
This limited Lifetime Warranty is effective on all appliances sold after May 1, 2002 and supersedes any and all  
warranties currently in existence.  
250-8620J  
12/05  
41  
Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

RightWay GPS Receiver Mini S3 User Guide
Roberts Radio Clock Radio CR9900 User Guide
Roland Musical Instrument MC 909 User Guide
Rotel Stereo Amplifier RTC 965 User Guide
Ryobi Saw 4060310 User Guide
Samsung DVD Player DVD Playe User Guide
Samsung DVD VCR Combo DVD V8500 User Guide
Samsung Washer H1255A User Guide
Sanyo Gas Grill DTA 2680 User Guide
Sanyo Universal Remote RMT U340A User Guide