®
Powerware 9395 UPS
1000–1100 kVA
Installation and Operation Manual
For use with Three UPM (650–825 kVA) and Four UPM (1000–1100 kVA) UPS Models
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1−1
1.1
UPS Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1−2
1−2
1−2
1−3
1−3
1−4
1−4
1−4
1−4
1−4
1−5
1−5
1−5
1−6
1−6
1−6
1−7
1−7
1−8
1.1.1
Installation Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customer Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Advanced Battery Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2
1.1.3
1.1.4
1.1.5
1.2
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1
Field Installed UPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inherent Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sync Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Distributed Bypass System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
1.2.3
1.2.4
1.2.5
1.3
1.4
1.5
1.6
1.7
1.8
1.9
Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols, Controls, and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2−1
Section I – Installation
3
4
UPS Installation Plan and Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3−1
3.1
3.2
Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3−1
3−1
3.2.1
Environmental and Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS System Power Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS System Interface Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Distributed Bypass Power Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3−1
3.2.2
3.2.3
3.2.4
3−8
3−19
3−20
3−21
3.3
Inspecting and Unpacking the UPS Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS System Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4−1
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
Preliminary Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unloading the UPS Sections from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanically Joining the Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrically Connecting the Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Installed UPM Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery System Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Distributed Bypass Tie Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing UPS External and Battery Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4−1
4−1
4−5
4−8
4−16
4−16
4−16
4−16
4−16
4−23
4.8.1
4.8.2
External Power Wiring Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
i
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
4.9
Installing Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4−26
4−26
4−31
4−33
4−34
4−37
4−37
4−37
4.9.1
4.9.2
4.9.3
TB1, TB2, and TB3 Connections (Other than TB1 Battery Interface Connections) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TB1 Battery Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X−Slot Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.10 Installing a REPO Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.11 Installing Options, Accessories, and Distributed Bypass Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.12 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.13 Completing the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Installing Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−1
5.1
5.2
5.3
5.4
5.5
5.6
Installing an Optional Powerware Hot Sync CAN Bridge Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing Distributed Bypass Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing an Optional Remote Monitor Panel II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing an Optional Relay Interface Module II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing an Optional Supervisory Contact Module II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessory Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−1
5−4
5−9
5−11
5−13
5−15
Section II – Operation
6 Understanding UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6−1
6.1
6.2
UPS System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6−1
6−2
6.2.1
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6−2
6.2.2
6.2.3
6.2.4
6−2
6−3
6−4
6.3
6.4
Single UPS Unit System Oneline Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multiple UPS Distributed Bypass System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6−6
6−12
6−12
6−13
6−14
6−15
6−17
6.4.1
Multiple UPS Parallel System Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bypass Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.2
6.4.3
6.4.4
6.5
Multiple UPS Distributed Bypass System Oneline Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
UPS Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7−1
7.1
UPS Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7−1
7−2
7−2
7−2
7−3
7−3
7−4
7−5
7−5
7−6
7−8
7−10
7.1.1
7.1.2
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2
Using the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.1
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the LCD and Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mimic Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Menu Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Status Screen and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Off Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.2
7.2.3
7.2.4
7.2.5
7.2.6
7.2.7
7.2.8
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
7.3
Single UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7−11
7−11
7−12
7−12
7−14
7−14
7−15
7−15
7−16
7−16
7−17
7−18
7−20
7−20
7−21
7−21
7−23
7−23
7−24
7−24
7−25
7−25
7−26
7−27
7.3.1
7.3.2
7.3.3
7.3.4
7.3.5
7.3.6
7.3.7
7.3.8
7.3.9
Starting the UPS in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS in Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Normal to Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Bypass to Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Normal to Bypass Mode and Shut Down UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single UPM Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS and Critical Load Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.10 Using the UPS LOAD OFF Pushbutton or Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.11 Using the Remote Emergency Power−off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multiple UPS Distributed Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4
7.4.1
7.4.2
7.4.3
7.4.4
7.4.5
7.4.6
7.4.7
7.4.8
7.4.9
Starting the Distributed Bypass System in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the Distributed Bypass System in Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPSs UPMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Normal to Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Bypass to Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer from Normal to Bypass Mode and Shut Down all UPSs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single UPM Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS and Critical Load Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.10 Using the UPS LOAD OFF Pushbutton or Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.11 Using the Remote Emergency Power−off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8−1
8.1
8.2
X−Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
eNotify Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8−1
8−2
8−2
8−2
8−3
8−3
8−4
8−4
8−5
8−7
8−7
8−7
8−9
8−10
8.2.1
8.2.2
eNotify Service Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing eNotify Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3
8.4
8.5
Powerware LanSafe Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.5.1
8.5.2
Display UPS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Event History Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.6
8.7
8.8
8.9
Building Alarm Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Purpose Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Monitor Panel II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Interface Module II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.10 Supervisory Contact Module II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
UPS Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9−1
9.1
9.2
Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performing Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9−1
9−2
9−2
9−2
9−5
9−5
9−5
9−5
9−6
9−6
9.2.1
DAILY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MONTHLY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ANNUAL Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BATTERY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2.2
9.2.3
9.2.4
9.2.5
9.3
9.4
9.5
Installing Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recycling the Used Battery or UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
10 Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10−1
10.1 Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.1 UPS Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.2 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.3 UPS Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10−1
10−1
10−1
10−2
10−2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W−1
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
iv
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
List of Figures
Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 1-2. Powerware 9395 Three UPM UPS (650–825 kVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-1. UPS Cabinet Dimensions (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-2. UPS Cabinet Dimensions (Right Side View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-3. ISBM Section Dimensions (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-4. UPM Section Dimensions (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-5. ISBM Section Dimensions (Top View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-6. ISBM Section Dimensions (Bottom View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-7. UPM Section Dimensions (Top View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-8. ISBM Section Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-9. UPM Section Center of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-10. Remote EPO Switch Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-11. UPS Cabinet as Shipped on Pallet (ISBM Section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-12. UPS Cabinet as Shipped on Pallet (UPM Section) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-1. Removing the ISBM Section Left Side Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-2. Removing the ISBM Section Right Side Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-3. Removing the UPM Section Left Side Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-4. Removing the UPM Section Right Side Shipping Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-5. Section Joining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-6. ISBM and UPM Sections Joined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-7. ISBM Section to UPM Section Joining Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-8. ISBM Section Intercabinet Power Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-9. ISBM Section Input Power Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-10. ISBM Section Battery Input Power Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-11. ISBM Section Output Power Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-12. UPS Intercabinet Interface Harness Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-13. Pl1 Interface Board Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-14. J39 Location on Pl1 Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-15. ISBM Section Debris Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-16. UPM Section Debris Shields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-17. Distributed Bypass Wire Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-18. ISBM Section Conduit and Wire Entry Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-19. ISBM Section Power Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-20. ISBM Section Power Terminal Detail AA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-21. ISBM Section Power Terminal Detail BB – Common Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-22. ISBM Section Power Terminal Detail CC – Separate Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-23. ISBM Section Interface Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-24. Interface Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-25. Typical Alarm Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-26. Terminal Blocks TB1, TB2, and TB3 Connector Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-27. Typical Battery Interface Connection – Common Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-28. Typical Battery Interface Connection – Separate Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-29. X−Slot Communication Bays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-30. REPO Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-31. Normally−Open REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-32. Normally-Closed REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 4-33. Normally-Closed and Normally-Open REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1−2
1−3
3−3
3−3
3−4
3−4
3−5
3−5
3−5
3−6
3−6
3−7
3−22
3−23
4−2
4−3
4−4
4−5
4−6
4−7
4−8
4−11
4−12
4−13
4−13
4−14
4−15
4−15
4−17
4−17
4−19
4−20
4−21
4−22
4−24
4−25
4−27
4−29
4−29
4−30
4−32
4−32
4−33
4−34
4−35
4−36
4−37
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
v
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Figure 5-1. Powerware Hot Sync CAN Bridge Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-3. Distributed Bypass System Can and Pull−Chain Simplified Interface Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-5. Distributed Bypass Pull−Chain Wiring without MOBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-6. Distributed Bypass Pull−Chain Wiring with MOBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring . . . . . . . . . . . . . . . . . . . . . .
Figure 5-9. J1, J2, J3, and J4 15−Pin D−Sub Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-10. Supervisory Contact Module II Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-11. Supervisory Contact Module II TB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-12. Remote Monitor Panel II Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-13. Relay Interface Module II Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5-14. Supervisory Contact Module II Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-1. Main Elements of the UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-2. Path of Current Through the UPS in Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-3. Path of Current Through the UPS in Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-4. Path of Current Through the UPS in Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-5. Four UPM UPS System, Dual-Feed, Common Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-6. Four UPM UPS System, Output Dual-Feed, Separate Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-7. Three UPM UPS System, Dual-Feed, Common Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-8. Three UPM UPS System, Dual-Feed, Separate Battery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-9. Simplified Dual−Feed UPS with Maintenance Bypass Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-10. Path of Current through the UPSs in Normal Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-11. Path of Current through the UPSs in Bypass Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-12. Path of Current through the UPSs in Battery Mode – Distributed Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-13. Typical Distributed Bypass System (1+1 and 2+0 Configurations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-14. Typical Distributed Bypass System (2+1 and 3+0 Configurations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6-15. Typical Distributed Bypass System (3+1 and 4+0 Configurations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-1. UPS Controls and Indicators – ISBM Section Shown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-2. UPS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-3. Parts of the LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-4. Main Menu and Mimic Screen (Normal Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-5. Typical System Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-6. Load Off Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 7-7. REPO Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8-1. Optional X−Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8-2. Sample Event History Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8-3. Remote Monitor Panel II Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8-4. Relay Interface Module II Customer Interface Connectors J1 through J4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8-5. Supervisory Contact Module II Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-1. ISBM Section Air Filter Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-2. UPM Section Air Filter Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-3. FI−UPM Air Filter Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5−1
5−3
5−5
5−5
5−6
5−7
5−10
5−10
5−12
5−13
5−14
5−15
5−16
5−17
6−1
6−3
6−4
6−5
6−7
6−8
6−9
6−10
6−11
6−13
6−14
6−16
6−18
6−19
6−20
7−1
7−2
7−4
7−5
7−8
7−10
7−19
8−2
8−6
8−7
8−9
8−10
9−3
9−4
9−5
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
vi
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1Table 1
Chapter 1
Introduction
®
Eaton’s Powerware 9395 uninterruptible power supply (UPS) is a true online,
continuous−duty, transformerless, double−conversion, solid−state, three−phase system,
providing conditioned and uninterruptible AC power to protect the customer’s load
from power failures.
The Powerware 9395 Four UPM UPS (1000–1100 kVA) contains three sections: an
integrated system bypass module (ISBM) rated for a maximum of 1100 kVA, an
Uninterruptible Power Module (UPM) section containing three UPMs, and a Field
Installed UPM (FI−UPM). Each UPM is rated for a maximum of 275 kVA for a total
maximum of 1100 kVA.
The Powerware 9395 Three UPM UPS (650–825 kVA) contains two sections: an
ISBM rated for a maximum of 1100 kVA (to provide future upgradability) and an UPM
section containing three UPMs. Each UPM is rated for a maximum of 275 kVA for a
total maximum of 825 kVA. The FI−UPM is not supplied as standard, but is available as
an option to provide upgradeability to a maximum of 1100 kVA.
The UPS is available as a single unit or an optional multiple unit distributed bypass
The Powerware 9395 online power protection system is used to prevent loss of
valuable electronic information, minimize equipment downtime, and minimize the
adverse effect on production equipment due to unexpected power problems.
The Powerware 9395 UPS continually monitors incoming electrical power and
removes the surges, spikes, sags, and other irregularities that are inherent in
commercial utility power. Working with a building’s electrical system, the UPS
system supplies clean, consistent power that sensitive electronic equipment requires
for reliable operation. During brownouts, blackouts, and other power interruptions,
batteries provide emergency power to safeguard operation.
The UPS is housed in a free-standing cabinet, divided into two sections to facilitate
shipping. The sections match in style and color and have safety shields behind the
doors for hazardous voltage protection. The FI−UPM matches the UPS in style and
NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page W−1 become void. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (usually a two−week notice is
required) to reserve a preferred startup date.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−1
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
ISBM SECTION
UPM SECTION
FI−UPM
Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA)
1.1
UPS Standard Features
The UPS has many standard features that provide cost-effective and consistently
reliable power protection. The descriptions in this section provide a brief overview of
the UPS standard features.
1.1.1
Installation Features
Each UPS section is shipped separately. The sections are mechanically and electrically
joined at the installation site.
Sections can be permanently bolted to the floor.
Power wiring can be routed through the top or bottom of the cabinet with
connections made to easily accessible terminals. Control wiring is routed through the
top of the cabinet and must be installed in accordance with Class 1 wiring methods.
1.1.2
Control Panel
The control panel, located on the front of the UPS, contains a liquid crystal display
(LCD) and pushbutton switches to control the operation of the UPS and to display the
additional information.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−2
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
ISBM SECTION
UPM SECTION
Figure 1-2. Powerware 9395 Three UPM UPS (650–825 kVA)
1.1.3
Customer Interface
S
Building Alarm Monitoring – Up to five inputs in the UPS are available to connect the
facility’s alarm system contacts. Some system configurations may limit the
number of inputs available. The UPS uses these inputs to monitor the building
additional information.
S
S
Alarm Contact – One alarm contact is provided for connection to equipment at the
facility, such as a light, an audible alarm, or a computer terminal. The equipment
ꢀCommunication," for additional information.
X−Slot Communication Bays – Four communication bays are standard equipment.
®
One to four optional X−Slot connectivity cards can be installed in the UPS module
at any time. X−Slot cards are quickly installed at the front of the UPS and are
1.1.4
Advanced Battery Management
A three−stage charging system increases battery service life by optimizing recharge
time, and protects batteries from damage due to high current charging and inverter
ripple currents. Charging at high currents can overheat and damage batteries.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−3
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
1.1.5
Power Management Software
®
Powerware LanSafe Power Management Software is bundled as part of the
additional information.
1.2
Options and Accessories
Contact an Eaton sales representative for information about the following options.
1.2.1
Field Installed UPM
A Field Installed UPM (FI−UPM) provides upgradability for the Powerware 9395 Three
UPM UPS. The FI−UPM may be installed at any time in the future when power needs
change. The module cabinet is installed on the left side of the ISBM section and is
wired directly to the UPS. No input or output wiring changes are needed for a capacity
increase if the original installation was wired with increased capacity in mind.
Operation remains the same as the original UPS.
1.2.2
Inherent Redundancy
To deliver greater reliability, the Powerware 9395 UPS can be configured by an
authorized Eaton Customer Service Engineer for inherent redundancy. When
configured, the UPS automatically becomes redundant if the load is at or below the
capacity of the UPMs minus the capacity of one UPM. Under normal conditions the
UPMs in the UPS share the load equally. If one or more UPMs becomes unavailable
and the load is at or below the capacity of remaining UPMs, the remaining UPMs
supply the load instead of transferring to bypass.
If the capacity of the UPMs falls below the redundancy level or the load increases
above redundancy level, but is still able to maintain the load, a loss of redundancy
alarm is sounded. If the load exceeds the capacity of remaining UPMs, the UPS
transfers to bypass.
1.2.3
Sync Control
An optional Powerware 9395 Sync Control maintains the critical load outputs of two
separate single module Powerware 9395 UPS systems in synchronization. This option
facilitates the uninterrupted transfer of the load from one load bus to another by
means of transfer switches. The Sync Control is housed in a wall-mounted panel that
can be located between the UPS units for easy wiring.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−4
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
1.2.4
Distributed Bypass System
There are two types of redundancy: UPS based (based on the number of UPS units)
and UPM based (based on the number of UPMs). Each UPS contains three or four
UPMs.
A distributed bypass UPS system with two to five UPS units can be installed to
provide a capacity and/or redundant system. This load sharing system provides more
capacity than a single UPS, and can provide backup, depending on the load and
configuration. In addition, when one UPM is taken out of service for maintenance or is
not operating properly, a redundant UPM continues to supply uninterrupted power to
®
the critical load. A Powerware Hot Sync Controller Area Network (CAN) Bridge Card
provides connectivity and operational mode control. The distributed bypass system
consists of two to five UPS units each with a parallel CAN card, and a
customer−supplied tie cabinet or load distribution panel to act as a tie point. The tie
cabinet should contain Module Output Breakers (MOBs) with dual auxiliary contacts
for control of the system.
1.2.5
Monitoring and Communication
S
Remote Monitor Panel II (RMP II) – An optional RMP II contains backlit status
indicators and a local horn, allowing monitoring of the operational status and alarm
condition of the UPS from virtually any location within the facility.
S
S
Relay Interface Module II (RIM II) – An optional RIM II uses relay contact closures to
indicate the UPS operating status and alarm condition.
Supervisory Contact Module II (SCM II) – An optional SCM II establishes an interface
between the UPS system equipment and the customer’s monitor.
S X−Slot Cards – Optional X−Slot cards support several protocols, such as SNMP,
®
HTTP, IBM AS/400 , and Modbus .
®
®
S
eNotify Remote Monitoring and Diagnostics Service – An optional service that provides
24/7 remote monitoring of 43 alarms, temperature/humidity and battery charge
information, daily heartbeat check, and monthly report. The service also provides
customer notification of significant alarms, remote diagnostics, and dispatch of
technicians. A ConnectUPS−X Web/SNMP Card is required in an X−Slot
communication bay. An optional Powerware Environmental Monitoring Probe
(EMP) is required for temperature/humidity monitoring.
communication features.
1.3
Battery System
Although not provided with the UPS, a battery system is required to provide
emergency short term−backup power to safeguard operation during brownouts,
blackouts, and other power interruptions. The battery system should be equipped
with lead-acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a
common battery system, single and multiple UPMs are powered from one common
battery source. In a separate battery system, multiple UPMs are each powered from
separate battery sources.
UPMs in distributed bypass and parallel systems must use a separate battery system.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided
by the UPS, but is not required for normal operation.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−5
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
1.4
Basic System Configurations
The following basic UPS system configurations are possible:
S Single UPS with three common battery UPMs, a common battery FI−UPM, and a
standalone common battery system with a battery disconnect (four UPM
configuration)
S Single UPS with three common battery UPMs, and a standalone common battery
system with a battery disconnect (three UPM configuration)
S Single UPS with three separate battery UPMs, a separate battery FI−UPM, and a
standalone separate battery system with a battery disconnect for each UPM (four
UPM configuration)
S Single UPS with three separate battery UPMs and a standalone separate battery
system with a battery disconnect for each UPM (three UPM configuration)
S Distributed bypass system with two to five UPSs and a customer−supplied
tie cabinet
The UPS system configuration can be enhanced by adding optional accessories such
as a Remote Emergency Power−off (REPO) control, RMP II, or X−Slot communication
cards.
1.5
Using This Manual
This manual describes how to install and operate the Powerware 9395
1000–1100 kVA UPS. Read and understand the procedures described in this manual
to ensure trouble−free installation and operation. In particular, be thoroughly familiar
The information in this manual is divided into sections and chapters. The system,
options, and accessories being installed dictate which parts of this manual should be
Read through each procedure before beginning the procedure. Perform only those
procedures that apply to the UPS system being installed or operated.
1.6
Conventions Used in This Manual
This manual uses these type conventions:
S
Bold type highlights important concepts in discussions, key terms in procedures,
and menu options, or represents a command or option that you type or enter at a
prompt.
S Italic type highlights notes and new terms where they are defined.
S Screen typerepresents information that appears on the screen or LCD.
Icon
Description
Information notes call attention to important features or instructions.
Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
[Keys]
In this manual, the term UPS refers only to the UPS cabinet and its internal elements.
The term UPS system refers to the entire power protection system – the UPS
cabinet, the battery system, and options or accessories installed.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−6
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
1.7
Symbols, Controls, and Indicators
The following are examples of symbols used on the UPS or accessories to alert you
to important information:
RISK OF ELECTRIC SHOCK − Observe the warning associated with the risk of electric
shock symbol.
CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for
additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the
trash. This product contains sealed, lead-acid batteries and must be disposed of
properly. For more information, contact your local recycling/reuse or hazardous waste
center.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse
or hazardous waste center.
1.8
For More Information
Refer to the Powerware 9390 and 9395 Sync Control Installation and Operation
Manual for the following additional information:
S Installation instructions, including site preparation, planning for installation, and
wiring and safety information. Detailed illustrations of the cabinet with dimensional
and connection point drawings are provided.
S Operation, including controls, functions of the standard and optional features,
procedures for using with the UPS, and information about maintenance.
Refer to the Powerware 9395 Field Installed UPM Mechanical Installation Manual for
the following additional information:
S Mechanical installation instructions, including site preparation, planning for
mechanical installation, and safety information.
S Detailed illustrations of the cabinet, including dimension and pallet removal
drawings.
Visit www.powerware.com or contact an Eaton service representative for information
on how to obtain copies of these manuals.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−7
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
1.9
Getting Help
If help is needed with any of the following:
S Scheduling initial startup
S Regional locations and telephone numbers
S A question about any of the information in this manual
S A question this manual does not answer
Please call the Eaton Help Desk for Powerware products at:
United States:
Canada:
1−800−843−9433 or 1−919−870−3028
1−800−461−9166 ext 260
Call your local service representative
All other countries:
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
1−8
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 2Table 2
Chapter 2
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of
the UPS and batteries. Read all instructions before operating the equipment and save this manual for future
reference.
The UPS is designed for industrial or computer room applications, and contains safety shields behind the
door and front panels. However, the UPS is a sophisticated power system and should be handled with
appropriate care.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED
SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING
The UPS is powered by its own energy source (batteries). The output terminals may carry live voltage
even when the UPS is disconnected from an AC source.
S
S
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled,
indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95% maximum). The system is not intended for
outdoor use.
S
S
Ensure all power is disconnected before performing installation or service.
Batteries can present a risk of electrical shock or burn from high short-circuit current. The following
precautions should be observed: 1) Remove watches, rings, or other metal objects; 2) Use tools with
insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Wear rubber gloves and boots.
S
S
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting
to alter wiring can cause injury.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
CAUTION
S
Installation or servicing should be performed by qualified service personnel knowledgeable of UPS and
battery systems, and required precautions. Keep unauthorized personnel away from equipment. Consider
all warnings, cautions, and notes before installing or servicing equipment. DO NOT DISCONNECT the
batteries while the UPS is in Battery mode.
S
S
S
Replace batteries with the same number and type of batteries as originally installed with the UPS.
Disconnect the charging source prior to connecting or disconnecting terminals.
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting
any part of a grounded battery can cause a risk of electric shock. An electric shock is less likely if you
disconnect the grounding connection before you work on the batteries.
S
S
S
Proper disposal of batteries is required. Refer to local codes for disposal requirements.
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to protect
personnel from dangerous voltages inside the unit.
S
Do not install or operate the UPS system close to gas or electric heat sources.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
2−1
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
S
The operating environment should be maintained within the parameters stated in this manual.
Keep surroundings uncluttered, clean, and free from excess moisture.
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.
CAUTION
To prevent damage to the wiring channel and wiring in the UPS cabinet base when lifting or moving the
cabinet:
S
S
Lift and move the cabinet using only the front or rear forklift slots.
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
AVERTISSEMENT!
Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de
haute intensité. Prendre les précautions nécessaires.
S
S
Pour le replacement, utiliser le même nombre et modéle des batteries.
ATTENTION!
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans
votre localité.
S
S
Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
2−2
Download from Www.Somanuals.com. All Manuals Search And Download.
Section I
Installation
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 3Table 3
Chapter 3
UPS Installation Plan and Unpacking
Use the following basic sequence of steps to install the UPS:
7. Have authorized service personnel perform preliminary operational checks and
start up the system.
NOTE Startup and operational checks must be performed by an authorized Eaton Customer Service
Engineer, or the warranty terms specified on page W−1 become void. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (usually a two−week notice is
required) to reserve a preferred startup date.
3.1
3.2
Creating an Installation Plan
Before installing the UPS system, read and understand how this manual applies to the
Preparing the Site
For the UPS system to operate at peak efficiency, the installation site should meet
the environmental parameters outlined in this manual. If the UPS is to be operated at
an altitude higher than 1500m (5000 ft), contact an Eaton service representative for
important information about high altitude operation. The operating environment must
meet the weight, clearance, and environmental requirements specified.
3.2.1
Environmental and Installation Considerations
The UPS system installation must meet the following guidelines:
S The system must be installed on a level floor suitable for computer or electronic
equipment.
S The system must be installed in a temperature and humidity controlled indoor area
free of conductive contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−1
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
For Field Installed UPM (FI−UPM) weights and dimensions, refe to the Powerware
Table 3-1. UPS Cabinet Weights
Weight
kg (lb)
Model
Section
Shipping
1850 (4078)
1590 (3505)
1850 (4078)
1590 (3505)
Installed
1750 (3858)
1482 (3267)
1750 (3858)
1482 (3267)
ISBM
UPM
ISBM
UPM
Powerware 9395−1100/1000
Powerware 9395−1100/1100
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
457.2 mm (18") minimum clearance for ventilation
914.4 mm (36") working space
None Required
From Right Side of Cabinet 152.4 mm (6") working space
From Left Side of Cabinet None Required
The basic environmental requirements for operation of the UPS are:
S Ambient Temperature Range:
0–40°C (32–104°F)
S Recommended Operating Range: 20–25°C (68–77°F)
S Maximum Relative Humidity:
95%, noncondensing
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation
Input/Output
Voltage
Heat Rejection
BTU/hr ꢀ 1000 (kg−cal/hr)
Ventilation Required for Cooling Air Exhaust
Model
Rating
Powerware 9395−1100/1000
Powerware 9395−1100/1100
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
1000 kVA
1100 kVA
650 kVA
750 kVA
825 kVA
480/480
480/480
480/480
480/480
480/480
195 (49127)
215 (54040)
127 (31933)
146 (36845)
161 (40530)
Approximately 3020 liter/sec (6400 cfm)
Approximately 2265 liter/sec (4800 cfm)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−2
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Dimensions are in millimeters [inches].
Figure 3-1. UPS Cabinet Dimensions (Front View)
Dimensions are in millimeters [inches].
Figure 3-2. UPS Cabinet Dimensions (Right Side View)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−3
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Figure 3-3. ISBM Section Dimensions (Front View)
Figure 3-4. UPM Section Dimensions (Front View)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−4
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Front
Dimensions are in millimeters [inches].
Figure 3-5. ISBM Section Dimensions (Top View)
Front
Dimensions are in millimeters [inches].
Figure 3-6. ISBM Section Dimensions (Bottom View)
Front
Dimensions are in millimeters [inches].
Figure 3-7. UPM Section Dimensions (Top View)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−5
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
CG
CG
Dimensions are in millimeters [inches].
Figure 3-8. ISBM Section Center of Gravity
CG
CG
Dimensions are in millimeters [inches].
Figure 3-9. UPM Section Center of Gravity
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−6
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
0.87
[0.22]
115.8
[4.56]
88.9
[3.50]
114.3
[4.50]
95.3
[3.57]
(Square)
1.57
[0.40]
Needed to
remove key
Front View
1/2" Knockout Pattern
(Typical 5 Sides)
Dimensions are in millimeters [inches].
Figure 3-10. Remote EPO Switch Dimensions
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−7
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
3.2.2
UPS System Power Wiring Preparation
Read and understand the following notes while planning and performing the
installation:
S Refer to national and local electrical codes for acceptable external wiring practices.
S To allow for future kVA upgrades, consider installing a derated UPS using wiring
and external overcurrent protection breakers sized for a fully rated UPS.
S To allow for a future upgrade, install a three UPM model using conductors and
external overcurrent protection breakers sized the same as a fully rated 1100 kVA
model.
S For external wiring, use 90°C copper or aluminum wire. Wire sizes listed in
temperature greater than 30°C, higher temperature wire and/or larger size wire
may be necessary. Wire sizes are based on using the specified breakers.
S Wire ampacities are chosen from Table 310−16 of the NEC. Specification is for
copper wire with a 90°C rating.
S Material and labor for external wiring requirements are to be provided by
designated personnel.
S If installing a maintenance bypass, a minimum of two separate feeds with
upstream feeder breakers, or a single feed with two upstream feeder breakers,
must be provided: one for the UPS or rectifier input breaker (RIB) (if installed) and
one for the maintenance bypass input. DO NOT use a single feed or a single feeder
breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass
input breaker (BIB) is installed in the maintenance bypass and a single−feed UPS is
being installed, a single feed to the maintenance bypass is acceptable for supplying
both the UPS and the bypass.
S The bypass feed into this equipment uses three or four wires. The rectifier feed
into this equipment uses three wires. The phases must be symmetrical about
ground (from a Wye source) for proper equipment operation.
S If the load requires a neutral, a bypass source neutral must be provided. If the load
does not require a neutral and there is no neutral conductor connected at the
bypass input, a neutral to ground bonding jumper must be installed. DO NOT install
copper wire.
S The ISBM and UPM sections are shipped with debris shields covering the
ventilation grills on top of the sections. Do not remove the debris shields until
installation is complete. However, remove the shields before operating the UPS.
Once the debris shields are removed, do not place objects on the ventilation grills.
S In a common battery system, single and multiple UPMs are powered from one
common battery source. In a separate battery system, multiple UPMs are each
powered from separate battery sources.
S A Field Installed UPM (FI−UPM) is always designated as UPM 4.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−8
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
For four UPM external wiring requirements, including the minimum AWG size of
copper wiring only.
For three UPM external wiring requirements, including the minimum AWG size of
copper wiring only. Because of the future upgradability to a fully rated 1100 kVA UPS
with the addition of the FI−UPM, the UPS wiring is specified only for 1100 kVA in
Table 3-4. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100
– Common Battery
Units
Rating 50/60 Hz
Basic Unit Rating
kVA
kW
1000
909
1100
1000
Input and Output Voltage
Volts
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Amps
1280
1500
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
B
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
AC Input to UPS Bypass (Four Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(5)
AC Input to UPS Bypass (Five Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
C
D
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(6)
DC Input from Battery Disconnect to UPS
Total Amps
2000
2203
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(8)
500
(9)
AC Output to Critical Load (Four Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(5)
AC Output to Critical Load (Five Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
–
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(6)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
250
(1)
2500
(1)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−9
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Table 3-5. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000, and 9395−1100/1100
– Separate Battery
Units
Rating 50/60 Hz
Basic Unit Rating
kVA
kW
1000
909
1100
1000
Input and Output Voltage
Volts
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Amps
1280
1500
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
B
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
AC Input to UPS Bypass (Four Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(5)
AC Input to UPS Bypass (Five Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
C
D
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(6)
DC Input from Each Battery Disconnect to Each UPS UPM
Amps per UPM
551
551
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(5)
AC Output to Critical Load (Five Wire)
Amps
1203
1323
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
–
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(6)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
250
(1)
250
(1)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−10
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and
9395−1100/825 – Common Battery
Units
Rating 50/60 Hz
Basic Unit Rating
kVA
kW
650
591
750
682
825
750
Input and Output Voltage
Volts
480/480
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Amps
891
1028
1130
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
B
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Four Wire)
Amps
782
902
992
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Five Wire)
Amps
782
1280
782
902
992
1600
992
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
C
D
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
DC Input from Battery Disconnect to UPS
Total Amps
1502
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
AC Output to Critical Load (Four Wire)
Amps
902
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Output to Critical Load (Five Wire)
Amps
782
902
992
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
–
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
4/0
(1)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−11
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Table 3-7. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and
9395−1100/825 – Separate Battery
Units
Rating 50/60 Hz
Basic Unit Rating
kVA
kW
650
591
750
682
825
750
Input and Output Voltage
Volts
480/480
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Amps
891
1028
1130
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
B
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Four Wire)
Amps
782
902
992
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Five Wire)
Amps
782
551
782
902
992
551
992
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
C
D
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
DC Input from Each Battery Disconnect to Each UPS UPM
Amps per UPM
551
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
AC Output to Critical Load (Four Wire)
Amps
902
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Output to Critical Load (Five Wire)
Amps
782
902
992
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
–
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
4/0
(1)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−12
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Tightening Torque
Terminal Function
Terminal
Function
Bus Landing
Stud
Nm (lb ft)
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
Phase A
3 – stud mounting
12 (8.3)
M8
E1A (UPM 4 – Four UPM Model)
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
Phase B
Phase C
3 – stud mounting
3 – stud mounting
12 (8.3)
12 (8.3)
M8
M8
AC Input to UPM Section
E2A (UPM 4 – Four UPM Model)
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
Phase A
Phase B
Phase C
Neutral
3 – stud mounting
3 – stud mounting
3 – stud mounting
3 – stud mounting
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
M8
M8
M8
M8
M8
M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
AC Output from UPM Section
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
6 – stud mounting
(2 per UPM)
Positive
Negative
DC Input to UPM Section
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
6 – stud mounting
(2 per UPM)
Table 3-9. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
Flat Washer
M8
36
180500036−080
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
Conical Washer
Nut
M8
M8
36
36
180500037−080
180200001−05
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−13
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Terminals E1 through E12 are 2-hole busbar mountings for standard NEMA 2-hole
barrel lugs. The power wiring connections for this equipment are rated at 90°C. See
Corporation.
power cable terminals inside the UPS.
Table 3-10. UPS External Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Terminal Function
Terminal
Function
Bolt Size
E1
E2
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Battery (+)
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
6 – 2 bolt mounting
16 – 2 bolt mounting
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
M12
M12
M12
M12
M12
M12
M12
M12
M12
M12
AC Input to UPS Rectifier
E3
E6
E7
AC Input to Bypass
E8
E9
E10
E11
E4
AC Output to Critical Load
DC Input from Battery or Battery
Disconnect to UPS – Common
Battery
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
E5
E4
E5
E4
E5
E4
E5
E4
Battery (−)
Battery (+)
Battery (−)
Battery (+)
Battery (−)
Battery (+)
Battery (−)
Battery (+)
16 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
4 – 2 bolt mounting
M12
M12
M12
M12
M12
M12
M12
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI−UPM)
E5
E12
Battery (−)
Neutral
4 – 2 bolt mounting
12 – 2 bolt mounting
15 – 1 bolt mounting
M12
M10
M10
Input and Output Neutral
Customer Ground
22 (16)
22 (16)
Ground
Ground
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−14
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Table 3-11. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 25 mm
15
Ground
180190078−087
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
Bolt, Grade 5
Flat Washer
M12 x 50 mm
M10
98
15
180190078−115
180500036−100
180500036−120
180500037−100
180500037−120
Ground
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
Flat Washer
M12
196
15
Conical Washer
Conical Washer
M10
Ground
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
M12
98
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
Nut
M12
98
180200001−07
Table 3-12. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part
Size
Quantity
Manufacturer
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Thomas & Betts
Part Number
54862BE
54864BE
54866BE
54868BE
54870BE
54872BE
54874BE
54876BE
TBM14M
15506
Notes
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
14 Ton
Long Barrel 2-Hole Lug
As required
Copper wire only
Manual Hydraulic Crimp Tool
Die Set
1
1
N/A
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−15
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same
conduit. Neutral and ground must be run in the same conduit as the phase
conductors.
Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one ground conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
Table 3-13. Power Cable Conduit Requirements
Number of Wires Minimum Conduit
Number of
Conduits
UPS Model
Voltage
Terminal
in Conduit
Trade Size
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
4
5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
5
3
480 Vac
Powerware 9395−1100/1000
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
3
Battery
(Positive, Negative, Ground)
DC
See Note
AC Input to UPS Rectifier
(A, B, C, Ground)
4
4
5
3
5
5
6
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
3
480 Vac
Powerware 9395−1100/1100
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
3-1/2
Battery
(Positive, Negative, Ground)
DC
See Note
AC Input to UPS Rectifier
(A, B, C, Ground)
4
4
5
3
4
4
5
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
3
3
480 Vac
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
Battery
(Positive, Negative, Ground)
DC
See Note
NOTE Select conduit taking into consideration the DC input wire sizes listed in Table 3-4, Table 3-5, Table 3-6, or Table 3-7 starting on page 3−9, the DC
terminations listed in Table 3-10 on page 3−14, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−16
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
External overcurrent protection and disconnect are not provided by this product, but
page 3−9 for wiring requirements. If an output lockable disconnect is required, it is to
be supplied by the customer.
Table 3-14. Recommended Input Circuit Breaker Ratings
Input Rating
UPS Model
Load Rating
80% Rated
100% Rated
80% Rated
100% Rated
80% Rated
480V
2000A
1600A
2000A
1600A
1600A
Powerware 9395−1100/1000
Powerware 9395−1100/1100
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
100% Rated
1200A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
The line-to-line unbalanced output capability of the UPS is limited only by the full load
Table 3-6, or Table 3-7 starting on page 3−9 . The recommended line-to-line load
unbalance is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches
are to be provided by the customer. Module Output Breakers (MOBs) are to be
output, and MOB circuit breakers.
Table 3-15. Recommended Bypass, Output, and MOB Circuit Breaker Ratings
Output Rating
UPS Model
Load Rating
80% Rated
100% Rated
80% Rated
100% Rated
80% Rated
480V
1600A
1600A
2000A
1600A
1600A
Powerware 9395−1100/1000
Powerware 9395−1100/1100
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
100% Rated
1000A
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−17
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required
by NEC or local codes. The battery disconnect switch should be installed between the
battery and the UPS.
External DC input overcurrent protection and disconnect switch is to be provided by
rated circuit breakers satisfying the criteria for both. Recommended disconnect size is
based on a maximum full load discharge time less than 3 hours. For longer discharge
times a larger disconnect may be required.
Table 3-16. Recommended DC Input Battery Disconnect Ratings – Common Battery
Input Rating
UPS Model
480V
Powerware 9395−1100/1000
Powerware 9395−1100/1100
2500A
3000A
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
2000A
Table 3-17. Recommended DC Input Battery Disconnect Ratings – Separate Battery
Input Rating
(each UPM)
UPS Model
480V
Powerware 9395−1100/1000
Powerware 9395−1100/1100
700A
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage
drop of more than 1% of nominal DC voltage at rated battery current.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−18
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
3.2.3
UPS System Interface Wiring Preparation
Control wiring for features and options should be connected at the customer interface
terminal blocks located inside the UPS.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
Read and understand the following notes while planning and performing the
installation:
S Use Class 1 wiring methods (as defined by the NEC) for interface wiring up to 30V.
The wire should be rated at 24V, 1A minimum.
S Use Class 2 wiring methods (as defined by the NEC) for interface wiring from 30V
to 600V. The wire should be rated at 600V, 1A minimum and 12 AWG maximum.
S Use twisted-pair wires for each input and return or common.
S All interface wiring and conduit is to be provided by the customer.
S When installing external interface wiring (for example, building alarm, relay output,
battery breaker trip, and X−Slot) to the UPS interface terminals, conduit must be
installed between each device and the UPS cabinet.
S Install the interface wiring in separate conduit from the power wiring.
S When installing internal interface wiring to X−Slot terminals, route the wiring
through the internal opening in the X−Slot communication bay.
S All building alarm inputs or remote features require an isolated normally-open
contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm
input and common terminal. All control wiring and relay and switch contacts are
customer-supplied.
S The building alarms can be programmed to display the alarm functional name.
S LAN and telephone drops for use with X−Slot connectivity cards must be provided
by the customer.
S The UPS battery aux signal wiring from the UPS must be connected to the battery
disconnect device.
S A supplemental 48 Vdc shunt trip signal for the battery disconnect device is
provided, but is not required for normal operation.
S Battery aux and 48 Vdc shunt trip wiring should be a minimum of 18 AWG.
S The REPO feature opens all contactors in the UPS cabinet and isolates power from
your critical load. Local electrical codes may also require tripping upstream
protective devices to the UPS.
S The REPO switch must be a latching−type switch not tied to any other circuits.
S A jumper wire must be connected between pins 1 and 2 on TB1, if the
normally-closed REPO contact is not used.
S REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−19
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
S The REPO switch wiring must be in accordance with NEC Article 725 Class 2
requirements.
S The maximum distance between the REPO and the UPS cannot exceed
150 meters (500 feet).
S Alarm relay contacts have a maximum current rating of 5A and a switched voltage
rating of 30 Vac and 28 Vdc.
S Alarm relay wiring should be a minimum of 22 AWG.
3.2.4
Distributed Bypass Power Wiring Preparation
Read and understand the following notes while planning and performing the
installation:
S All distributed bypass UPS rectifier inputs must come from one source and all
bypass input feeds must come from one source.
S Distributed bypass UPS input wiring size requirements and output wiring size
requirements from the UPSs to the tie cabinet or distribution panel are the same as
S If the load requires a neutral, a bypass source neutral must be provided. If the load
does not require a neutral and there is no neutral conductor connected at the
bypass input, a neutral to ground bonding jumper must be installed. Install neutral
conductors from the UPSs to the common point of connection (tie cabinet), and
then install a system neutral to ground bonding jumper. The bonding jumper must
be copper wire. DO NOT install both a source neutral and a bonding jumper.
If the recommended system neutral bonding jumper installation method cannot be
accomplished, each UPS should have a separate neutral to ground bonding jumper
UPS neutral bonding jumper wire sizes. The bonding jumper must be copper wire.
DO NOT install both a source neutral and a bonding jumper.
S The UPS cannot be installed in a high−resistance ground application.
on page 3−17 lists the recommended rating for the MOBs.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−20
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
3.3
Inspecting and Unpacking the UPS Cabinets
The UPS cabinet is divided into two sections palleted separately for shipping. The
protected with outer protective packaging material.
WARNING
The UPS sections are heavy (see Table 3-1 on page 3−2). If unpacking and unloading instructions are not
closely followed, the cabinets may tip and cause serious injury.
CAUTION
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the
cabinet:
S
S
Lift and move the UPM section using only the front or rear forklift slots.
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION
Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service
representative immediately.
NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 3−2 for cabinet weight).
2. Use a forklift or pallet jack to move the packaged cabinets to the installation site,
or as close as possible, before unpacking. If possible, move the cabinets using
the pallet. Insert the forklift or pallet jack forks from the right side of the pallet
(facing the cabinet), between the supports on the bottom of the pallet (see
Figure 3-8 and Figure 3-9 on page 3−6 for the UPS cabinet center of gravity
measurements). If the cabinets must be moved using the cabinet front or rear
fork lift slots, see the caution statement at the beginning of this procedure.
CAUTION
Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.
NOTE The ISBM and UPM sections are shipped with debris shields covering the ventilation grills on top of
the sections (see Figure 4-15 on page 4−17). Do not remove the debris shields until installation is complete.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−21
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
4. Remove the protective covering from the cabinets.
5. Remove the packing material, and discard or recycle in a responsible manner.
6. Inspect the contents for any evidence of physical damage, and compare each
item with the Bill of Lading. If damage has occurred or shortages are evident,
contact an Eaton service representative immediately to determine the extent of
the damage and its impact on further installation.
NOTE While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful
contaminants. Failure to store and protect the UPS properly may void your warranty.
Figure 3-11. UPS Cabinet as Shipped on Pallet (ISBM Section)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−22
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS INSTALLATION PLAN AND UNPACKING
This page intentionally left blank.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
3−24
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 4Table 4
Chapter 4
UPS System Installation
4.1
Preliminary Installation Information
WARNING
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
installation notes.
S Do not tilt the cabinets more than "10° during installation.
S Remove the conduit landing plates to add conduit landing holes as required. Plate
material is 16 gauge steel (1.5 mm/0.06" thick).
S If perforated floor tiles are required for ventilation, place them in front of the UPS.
4.2
Unloading the UPS Sections from the Pallet
The ISBM and UPM sections are bolted to separate wooden pallets supported by
wood skids. To remove the pallets:
WARNING
The UPS sections are heavy (see Table 3-1 on page 3−2). If unpacking and unloading instructions are not
closely followed, the cabinets may tip and cause serious injury.
CAUTION
S
S
Do not tilt cabinets more than 10° from vertical.
Lift the cabinets only with a forklift or damage may occur.
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the
cabinet:
S
S
Lift and move the UPM section using only the front or rear forklift slots.
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−1
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
NOTE For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 3−2 for cabinet weight).
1. If not already accomplished, use a forklift or pallet jack to move the ISBM and
UPM sections to the installation area, or as close as possible, before unloading
from the pallets. If possible, move each section using the pallet. Insert the forklift
or pallet jack forks from the right side of the pallet (facing the cabinet), between
page 3−6 for the ISBM and UPM section center of gravity measurements). If the
sections must be moved using the cabinet front or rear fork lift slots, see the
caution statements at the beginning of this procedure.
2. Remove the three bolts securing the left side shipping bracket to the cabinet and
Remove the left side shipping bracket.
3. Remove the three bolts securing the right side shipping bracket to the cabinet
Remove the right side shipping bracket.
Front Door
Pallet
Shipping Bracket
Bolts
Shipping Bracket
Bolts
Left Side Shipping
Bracket
Figure 4-1. Removing the ISBM Section Left Side Shipping Bracket
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−2
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
ISBM Removable
Front Panels
Pallet
Shipping Bracket
Bolts
Right Side Shipping
Bracket
Shipping Bracket
Bolts
Figure 4-2. Removing the ISBM Section Right Side Shipping Bracket
4. Using a forklift (see the caution statement at the beginning of this procedure),
raise the cabinet until the cabinet bottom clears the pallet by approximately
3 mm (1/8").
5. Pull the pallet from under the cabinet. Discard or recycle the pallet and shipping
brackets in a responsible manner.
6. Carefully lower the cabinet until the cabinet base contacts the floor.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−3
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
UPM Removable
Front Panels
Pallet
Shipping Bracket
Bolts
Wireway Panel
Shipping Bracket
Bolts
Left Side Shipping
Bracket
Figure 4-3. Removing the UPM Section Left Side Shipping Bracket
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−4
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Pallet
Shipping Bracket
Bolts
Right Side Shipping
Bracket
Shipping Bracket
Bolts
Figure 4-4. Removing the UPM Section Right Side Shipping Bracket
4.3
Mechanically Joining the Sections
NOTE The following procedure permits the UPS sections to be installed in a location where there is limited
space to slide the sections together from the sides.
NOTE For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the
section (see Table 3-1 on page 3−2 for cabinet weight).
1. Using a forklift, move the UPM section to the final installed location.
2. Remove one top screw and two bottom screws securing the UPM section
panel hanger brackets at the top of the cabinet.
3. Remove the screws securing the top and bottom internal safety shield panels
and remove the panels. Retain the hardware for later use.
4. Remove the screws securing the corner channel and remove the channel (see
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−5
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Left Top Panel
Left Middle Panel
Interior Left
Side Panel
Corner Channel
UPM Section
Wireway Panel
Figure 4-5. Section Joining
5. Remove the screws securing the left top panel and remove the panel (see
6. Remove the screws securing the left middle panel and remove the panel (see
CAUTION
Use care during installation to protect components mounted on the right side of the ISBM section and the
intercabinet wiring harnesses attached to the left side UPM section from damage.
NOTE Clearance between the ISBM and the UPM sections must be less than 1/2" so that joining brackets
can be installed.
7. Using a forklift with the forks in the front forklift slots, position the ISBM section
adjacent to the left side of the previously installed UPM section. Verify that the
ISBM section right side is against the UPM section left side and the front of the
hardware.
hardware.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−6
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
UPM Wireway
(Power wiring harnesses
are coiled in this area.)
Figure 4-6. ISBM and UPM Sections Joined
hardware.
NOTE Three flat cabinet joining brackets are provided in the hardware kit for securing the ISBM and UPM
11. Locate the hardware kit (packed inside a drawstring bag tied to the left middle
panel of the UPM section). Locate two flat brackets and screws from the
hardware kit. Align the holes in the flat brackets over holes in the top rear and
top front of the ISBM and UPM sections. Secure the brackets with the screws
12. Locate one flat bracket and screws from the hardware kit. Align the holes in the
flat bracket over holes in the front base of the ISBM and UPM sections. Secure
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−7
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Screw from Kit
Screw from Kit
Screw from Kit
Screw from Kit
Back
Bracket from Kit
ISBM
Section Top
UPM
Section Top
Bracket from Kit
ISBM
Section Top
UPM
Section Top
Front
Top View Front Bracket
Top View Rear Bracket
Bracket from Kit
ISBM Section Base
UPM Section Base
Front View Base Bracket
Screw from Kit
Screw from Kit
Figure 4-7. ISBM Section to UPM Section Joining Brackets
4.4
Electrically Connecting the Sections
page 4−2).
2. Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.
3. Remove the screws securing the ISBM section right bottom internal safety
shield panel and remove the panel to gain access to the internal input, output,
and battery terminals. Retain the hardware for later use.
NOTE AC and DC input intercabinet power wiring harnesses are supplied coiled and secured in the UPM
4. Locate the AC and DC input intercabinet power wiring harnesses (long cables
labeled xG1, xG2, and xG3). Remove wire ties as necessary and uncoil the
cables.
5. Locate the 1G1, 1G2, 2G1, 2G2, 3G1, and 3G2 power wiring harnesses. Route
these harnesses through the wiring access in the right side panel of the ISBM
terminal locations.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−8
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the
first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the second lug with
the raised barrel portion facing the front of the cabinet.
6. Locate the intercabinet wiring terminal hardware kit packed on the bottom right
side of the ISBM section.
on page 3−13), connect phase A, B, and C cable lug connections to the AC Input
page 3−8 for wiring and termination requirements.
NOTE In Step 8, route the wiring harnesses in the area as shown in Figure 4-8 on page 4−11 to provide
operating clearance for the bypass breaker CB4 charging handle.
8. Locate the 1G3, 2G3, and 3G3 power wiring harnesses. Route these harnesses
through the wiring access in the right side panel of the ISBM section to the DC
Input to UPMs terminals. See Figure 4-8 on page 4−11 for terminal locations.
NOTE When connecting the UPM battery cables, verify the cables are connected to the correct terminals .
9. Using hardware from the intercabinet wiring terminal hardware kit (see
page 3−8 for wiring and termination requirements.
NOTE AC output intercabinet power wiring harnesses are supplied attached to the interior left side panel
10. Locate the 1G4, 1G5, 2G4, 2G5, 3G4, and 3G5 power wiring harnesses. Remove
the front two columns of wire ties securing the cables to facilitate routing cables
locations.
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the
first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the second lug with
the raised barrel portion facing the front of the cabinet.
11. Using hardware from the intercabinet wiring terminal hardware kit (see
page 4−13 to connect the correct cable lug to the proper terminals. See
paragraph 3.2.2 on page 3−8 for wiring and termination requirements.
12. Install the remaining hardware (three washers, conical washers, and nuts) onto
the AC Input to UPMs terminals designated for the four UPM model and secure
the hardware (see Figure 4-9 on page 4−12). This hardware is used by an Eaton
Customer Service Engineer to install a Field Installed UPM (FI−UPM).
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−9
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
13. Locate the ground braid in the bottom left front corner of the UPM section. The
ground braid is secured at the factory to the UPM section ground bolt. Route the
ground braid through the wiring access in the right side panel of the ISBM
section to the ground bolt in the ISBM section.
14. Connect the ground braid to the ISBM section ground bolt and secure.
NOTE Four intercabinet interface wiring harnesses are supplied coiled inside the protective cage on the
harnesses with the J50, J51, J61, and J70 connectors attached. Remove the
wire ties securing the harnesses and carefully remove the harnesses from the
protective cage. If necessary, loosen the screws securing the protective cage.
16. Locate the mating P50 connector in the UPM section wireway (see B in
Figure 4-12 on page 4−14) and connect the P50 connector to the J50 connector.
17. Locate the mating P51 connector in the UPM section wireway (see B in
Figure 4-12 on page 4−14) and connect the P51 connector to the J51 connector.
18. Locate the mating P61 connector in the UPM section wireway (see B in
Figure 4-12 on page 4−14) and connect the P61 connector to the J61 connector.
19. Locate the mating P70 connector in the UPM section wireway (see B in
Figure 4-12 on page 4−14) and connect the P70 connector to the J70 connector.
NOTE One intercabinet interface cable is supplied coiled against the left side panel of the UPM section
CAN cable. Remove the wire ties securing the cable to the interior left side panel
of the UPM section. Route this cable through the round wiring access in the right
21. In the ISBM section, locate the J39 inverter CAN connector on the Pl1 interface
board and connect the RJ−45 CAN cable connector to the J39 connector (see
22. Dress the interface harnesses and secure in place with wire ties as necessary to
prevent wire damage.
23. When all wiring is complete, reinstall the safety shield panels removed in
previous steps.
24. Reinstall the front wireway panel.
27. If installing a tie cabinet or distribution panel for a distributed bypass system,
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−10
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
AC Input Breaker CB1
Phase A
AC Output
from UPMs
for detail.)
Phase B
Phase C
Neutral from UPMs
Phase C
Phase B
Phase A
AC Input to UPMs
(See Figure 4-9
for detail.)
Bypass Breaker CB4
CB4 Charging Handle
Route wiring harnesses in this
area below the bypass breaker
CB4 charging handle to provide
operating clearance for the
handle.
–
(E5)
DC Input to UPMs
+
DC Input to UPMs (E4)
Figure 4-8. ISBM Section Intercabinet Power Terminal Locations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−11
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
UPM 4 (FI−UPM) Four UPM Model
UPM 1 Cable 1G1 & 1G2 Orange
UPM 2 Cable 2G1 & 2G2 Orange
UPM 3 Cable 3G1 & 3G2 Orange
Phase A (E1A)
UPM 1 Cable 1G1 & 1G2 Brown
UPM 2 Cable 2G1 & 2G2 Brown
UPM 3 Cable 3G1 & 3G2 Brown
Phase B (E2A)
Phase B (E2A)
UPM 4 (FI−UPM) Four UPM Model
UPM 4 (FI−UPM) Four UPM Model
UPM 1 Cable 1G1 & 1G2 Yellow
UPM 2 Cable 2G1 & 2G2 Yellow
Phase C (E3A)
UPM 3 Cable 3G1 & 3G2 Yellow
AC Input to UPMs
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised
barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet.
Figure 4-9. ISBM Section Input Power Terminal Detail
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−12
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Cable 1G3 Black
Cable 1G3 Black
Cable 1G3 Red
Cable 1G3 Red
–
+
+
+
UPM 1 (1E4A)
UPM 2 (2E4A)
UPM 3 (3E4A)
UPM 1 (1E5A)
Cable 2G3 Black
Cable 2G3 Black
Cable 2G3 Red
Cable 2G3 Red
UPM 2 (2E5A)
–
– DC Input to UPMs
DC Input to UPMs
+
Cable 3G3 Black
Cable 3G3 Black
Cable 3G3 Red
Cable 3G3 Red
–
UPM 3 (3E5A)
Figure 4-10. ISBM Section Battery Input Power Terminal Detail
UPM 1 Cable 1G4 & 1G5 Orange
Phase A (E9A)
Phase B (E10A)
Phase C (E11A)
UPM 2 Cable 2G4 & 2G5 Orange
UPM 3 Cable 3G4 & 3G5 Orange
UPM 1 Cable 1G4 & 1G5 Brown
UPM 2 Cable 2G4 & 2G5 Brown
UPM 3 Cable 3G4 & 3G5 Brown
AC Output
from UPMs
UPM 1 Cable 1G4 & 1G5 Yellow
UPM 2 Cable 2G4 & 2G5 Yellow
UPM 3 Cable 3G4 & 3G5 Yellow
UPM 1 Cable 1G4 & 1G5 Gray
UPM 2 Cable 2G4 & 2G5 Gray
UPM 3 Cable 3G4 & 3G5 Gray
Neutral from
UPMs (E12A)
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised
barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet.
Figure 4-11. ISBM Section Output Power Terminal Detail
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−13
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Protective Cage
Location of J50,
J51, J61, and J70
Coiled Harnesses
Wiring Access
Location of P61
Harness
Front
Front
UPM Wireway
Location of P50,
P51, and P70
Harnesses
Location of RJ−45
Coiled CAN Cable
B
A
ISBM Section Right Side View
UPM Section Left Side View
Figure 4-12. UPS Intercabinet Interface Harness Locations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−14
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Pl1 Interface Board
Front
ISBM Section Right Side Inside View
Figure 4-13. Pl1 Interface Board Location
Pl1 Interface Board
J39 Inverter CAN Connector
Figure 4-14. J39 Location on Pl1 Interface Board
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−15
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.5
Field Installed UPM Installation
NOTE FI−UPM installation is not applicable to a three UPM model.
If installing a four UPM model, install the FI−UPM using the instructions in the
Powerware 9395 Field Installed UPM Mechanical Installation Manual, listed in
installing a battery system; otherwise, proceed to paragraph 4.7 to complete the
wiring of the UPS.
4.6
4.7
4.8
Battery System Installation
If installing a battery system, install the customer−supplied battery system according
to the battery and battery system manufacturer’s instructions and all applicable codes
and regulations, including the National Electrical Code (NEC), Article 480. After the
battery system is installed, proceed to paragraph 4.7 if installing a distributed bypass
Distributed Bypass Tie Cabinet Installation
If installing a distributed bypass system, install the customer−supplied tie cabinet or
distribution panel according to the tie cabinet or distribution panel manufacturer’s
instructions and all applicable codes and regulations, including the National Electrical
complete the wiring of the UPS.
Installing UPS External and Battery Power Wiring
NOTE The ISBM and UPM sections are shipped with debris shields covering the ventilation grills on top of
remove the shields before operating the UPS. Once the debris shields are removed, do not place objects on
the ventilation grills.
NOTE Remove the ISBM section top or bottom conduit landing plate to drill or punch conduit holes (see
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require
a neutral and there is no neutral conductor connected at the bypass input, a neutral to ground bonding jumper
neutral bonding jumper wire sizes. Bonding jumper must be copper wire.
Use the procedures in the following paragraphs to connect the external and battery
power wiring.
4.8.1
External Power Wiring Installation
To install wiring to connections:
1. Remove one top screw and two bottom screws securing each ISBM section left
and right front panel (see Figure 4-2 on page 4−3). Lift the panels straight up to
remove them from the panel hanger brackets at the top of the cabinet.
2. Remove the screws securing the top and bottom internal safety shield panels
and remove the panels to gain access to the input, output, and battery terminals.
Retain the hardware for later use.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−16
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Ventilation Grill Debris Shield
(Remove shield before operating system.)
ISBM Section
Front
Ventilation Grill Debris Shields
(Remove shields before operating system.)
UPM Section
Front
Figure 4-15. ISBM and UPM Section Debris Shields
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−17
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Top Entry Conduit Landing for AC
Input and Output, and DC Input
(Remove panel to drill or punch
conduit holes.)
TOP VIEW
Front
Interface Entry Conduit Landings for TB1
through TB3 Wiring and X−Slot Connections
(Remove panels to drill or punch conduit holes.)
Front
BOTTOM VIEW
Bottom Entry Conduit Landing for AC
Input and Output, and DC Input
(Remove panel to drill or punch
conduit holes.)
Figure 4-16. ISBM Section Conduit and Wire Entry Locations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−18
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
3. Route the input and output cables through either the top or bottom of the cabinet
information and terminal locations.
Top Access Wiring. Remove the top conduit plate from the top of the ISBM
section. Identify all conduit requirements and mark their location. Drill and punch
all conduit holes in the top conduit plate prior to mounting on the ISBM section.
Install the conduit plate and install all conduit runs into the plate. Pull wiring
through conduit into the ISBM section wiring area.
Bottom Access Wiring. Remove the bottom conduit plate from the inside bottom
of the ISBM section. Identify all conduit requirements and mark their location.
Drill and punch all conduit holes in the bottom conduit plate prior to mounting on
the ISBM section. Install the conduit plate and install all conduit runs into the
plate. Pull wiring through conduit into the ISBM section wiring area.
Locate the external wiring terminal hardware kit packed on the bottom left side
of the ISBM section.
page 3−15), connect phase A, B, and C rectifier input power wiring from the utility
on page 3−8 for wiring and termination requirements.
page 3−15), connect phase A, B, and C, and Neutral (if required) bypass input
power wiring from the utility source to the bypass input terminals and neutral
termination requirements.
CAUTION
Distributed bypass system wiring length should be in accordance with Figure 4-17, to ensure approximately
equal current sharing when in Bypass mode.
page 3−15), connect phase A, B, and C, and Neutral power wiring from the output
and neutral terminals of each UPS unit to the customer−supplied tie cabinet or
load distribution panel. See paragraph 3.2.2 on page 3−8 for wiring and
termination requirements.
page 3−15), connect phase A, B, and C, and Neutral (if required) power wiring
from output terminals and neutral terminals to the critical load. See
paragraph 3.2.2 on page 3−8 for wiring and termination requirements.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−19
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
UPS 1
UPS 2
UPS 3
UPS 4
Bypass Input to UPS Units
1A
2A
3A
4A
Battery
Battery
Output from UPS Units
1B
Battery
2B
3B
4B
Battery
NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For proper
operation the following must be true:
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B
NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference
between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%.
Figure 4-17. Distributed Bypass Wire Length
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−20
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
AC Input to UPS Rectifier
(A, B, C)
AC Input to UPS Bypass
(A, B, C)
(See Figure 4-19 for
Detail AA.)
Phase C (E11)
AC Output to
Phase B (E10)
Critical Load
Phase A (E9)
DC Input from Battery +
(E4)
A
B
C
DC Input from Battery –
(E5)
N
Neutral
(E12)
ISBM
Figure 4-18. ISBM Section Power Terminal Locations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−21
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Ground Terminals
Front
‘
Phase C (E3)
Phase B (E2)
Phase A (E1)
AC Input to
UPS Rectifier
Phase A (E6)
Phase B (E7)
Phase C (E8)
AC Input to
UPS Bypass
Section A–A
Figure 4-19. ISBM Section Power Terminal Detail AA
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−22
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.8.2
Battery Power Wiring
CAUTION
When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10,
ꢀProduct Specifications," for maximum battery charger currents.
To install wiring to connections:
NOTE An installed FI−UPM is always designated as UPM 4.
1. Route the battery cables between the ISBM section and the battery system or
wiring access information and terminal locations.
page 3−15), connect the positive, negative, and ground DC power wiring from the
battery system or disconnect to the ISBM section battery and ground terminals.
on page 3−8 for wiring and termination requirements.
page 3−15), connect the positive, negative, and ground DC power wiring from the
battery systems or disconnects to the ISBM section battery and ground
paragraph 3.2.2 on page 3−8 for wiring and termination requirements.
6. After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
8. When all wiring is complete, reinstall the top and bottom safety shield panels
hardware.
secure with the retained hardware.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−23
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
DC Input from Battery +
(E4)
Front
DC Input from Battery
–
(E5)
Section B–B
Figure 4-20. ISBM Section Power Terminal Detail BB – Common Battery
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−24
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
DC Input from Battery +
DC Input from Battery +
DC Input from Battery +
DC Input from Battery +
(UPM 3)
(E4)
(E4)
(E4)
(E4)
(UPM 2)
(UPM 1)
(UPM 4 – FI−UPM)
Front
DC Input from Battery
DC Input from Battery
(UPM 4 – FI−UPM)
(UPM 1)
–
–
(E5)
(E5)
(E5)
(E5)
DC Input from Battery –
DC Input from Battery
(UPM 2)
–
(UPM 3)
Section B–B
Figure 4-21. ISBM Section Power Terminal Detail CC – Separate Battery
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−25
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.9
Installing Interface Connections
WARNING
Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected.
Use the procedures in the following paragraphs to connect the TB1, TB1 Battery,
TB2, and TB3 interface connections.
4.9.1
TB1, TB2, and TB3 Connections (Other than TB1 Battery Interface
Connections)
NOTE When installing interface wiring for TB1, TB2, and TB3 connections, conduit must be installed
between each device and the UPS cabinet.
NOTE Interface wiring must be installed from the top of the UPS cabinet.
To install wiring to connections:
1. Verify the UPS system is turned off and all power sources are removed. See
2. If not already opened, unfasten the front door latch and swing the door open (see
3. If not already removed, remove the door. Remove the retaining screw located
inside the door at the bottom hinge pivot point, then lift the door off. Retain the
hardware for later use.
4. Terminal block TB3 is accessible on the left side of the X−Slot communication
bay. To gain access to terminal block TB1, TB2, and the left interface entry
conduit landing plates, remove the screws securing the top internal safety shield
5. Remove the interface entry conduit landing plates to drill or punch holes (see
6. Reinstall the interface entry plates and install the conduit.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
7. To locate the appropriate terminals and review the wiring and termination
8. Route and connect the wiring.
the X−Slot connections only, proceed to paragraph 4.9.3; otherwise, proceed to
10. Reinstall the top internal safety shield panel and secure with the retained
hardware.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−26
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
hardware.
12. Close the door and secure the latch.
X−Slot Communication Bays
TB1 and TB2
for detail.)
TB3
page 4−30 for terminal
assignments.)
ISBM
Figure 4-22. ISBM Section Interface Terminal Locations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−27
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Table 4-1. TB1, TB2, and TB3 Interface Connections
Terminal TB1
Name
REPO NC
Description
1
2
3
4
5
6
7
8
9
Input: Normally-closed dry contact used to activate UPS EPO from a remote switch.
REPO Return
REPO NO
Input: Normally-open dry contact used to activate UPS EPO from a remote switch.
REPO Return
Battery Aux
Input: Normally-open contact used to indicate when UPS battery breaker is open or
closed.
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
Output Contactor K3 NC Aux
Output: Contacts used to open battery breaker or disconnect.
Output: Normally-closed contact opens when output contactor closes.
Output Contactor K3 NC Aux
Common
10
Terminal TB2
Name
Pull Chain
Description
1
Output: Backup control for parallel operation.
2
Pull Chain Common
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
Not Used
3
Output: General purpose normally−closed (NC) relay contact.
Output: General purpose normally−open (NO) relay contact.
4
5
6
7
8
Not Used
9
Not Used
10
Not Used
Terminal TB3
Name
Description
1
2
3
4
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
Building Alarm 2 Return
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Building Alarm 3
Default: Charger Off
5
6
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for charger off.
Building Alarm 3 Return
Building Alarm 4
Default: On Generator
7
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for on generator.
8
Building Alarm 4 Return
Building Alarm 5
Default: Maintenance Bypass
9
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for maintenance bypass.
10
Building Alarm 5 Return
NOTE ꢀReturnꢀ indicates connection to electronics circuit ground. ꢀCommon" indicates connection to common side of isolated relay contact.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−28
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
X−Slot Communication Bays
TB1
for terminal
assignments.
TB2
Figure 4-23. Interface Terminal Detail
TB2
3
Alarm Relay NC
4
Alarm Relay Common
Alarm Relay NO
Alarm Relay
5
6
Alarm Relay Common
NOTE Alarm relay contacts have a maximum current rating of 5A and a
switched voltage rating of 30 Vac and 28 Vdc.
NOTE Alarm relay normally−open and normally−closed return terminals
are separated on the terminal board but are electrically in common.
NOTE Do not directly connect relay contacts to the mains related
circuits. Reinforced insulation to the mains is required.
NOTE Alarm relay wiring should be a minimum of 22 AWG.
Figure 4-24. Typical Alarm Relay Connection
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−29
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
UPS
REPO NC
REPO Return
REPO NO
REPO Return
1
Battery Aux
Battery Aux Common
TB1
Battery Shunt Trip +
Battery Shunt Trip –
Output Contactor K3 NC Aux
Output Contactor K3 NC Aux Common
10
1
Pull Chain
Pull Chain Common
Alarm Relay NC
Alarm Relay Common
Alarm Relay NO
Alarm Relay Common
TB2
10
UPS
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
1
Building Alarm 2 Return
Building Alarm 3
TB3
Building Alarm 3 Return
Building Alarm 4
Building Alarm 4 Return
Building Alarm 5
10
Building Alarm 5 Return
NOTE All building alarm inputs require an isolated normally−open or normally−closed contact or switch (rated at 24 Vdc, 20 mA minimum)
connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either
normally−open or normally−closed contacts. All control wiring and relay and switch contacts are customer-supplied.
NOTE The building alarms can be programmed to display the alarm functional name.
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally−closed REPO contact is not used.
Figure 4-25. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−30
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.9.2
TB1 Battery Interface Connections
To install wiring to connections:
1. Verify the UPS system is turned off and all power sources are removed. See
page 4−2).
3. Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.
4. To gain access to terminal block TB1 and the interface entry conduit landing
plate, remove the screws securing the top internal safety shield panel and
5. To locate the appropriate terminals and review the wiring and termination
NOTE When installing shunt trip and battery aux interface wiring to the UPS interface terminals, conduit
must be installed between the UPS and battery system.
6. Remove the left interface entry conduit landing plate to drill or punch holes (see
7. Reinstall the interface entry plate and install the conduit.
8. Route the shunt trip (optional) and battery aux wiring from the battery
access information and terminal locations.
9. Connect the wiring to the TB1 terminals.
10. Reinstall the top internal safety shield panel and secure with the retained
hardware.
hardware.
13. Close the door and secure the latch.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−31
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Battery
Disconnect
UPS
TB1
5
6
Battery Aux
Battery Aux Common
7
8
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
48 Vdc
ST
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
Figure 4-26. Typical Battery Interface Connection – Common Battery System
UPM 1
Battery
Disconnect
UPM 2
Battery
Disconnect
UPM 3
Battery
Disconnect
UPM 4
Battery
Disconnect
UPS
TB1
Battery Aux
5
6
Battery Aux Return
7
8
48 Vdc Battery Shunt Trip +
ST
ST
ST
ST
48 Vdc
48 Vdc Battery Shunt Trip −
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
Figure 4-27. Typical Battery Interface Connection – Separate Battery System
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−32
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.9.3
X−Slot Connections
NOTE LAN and telephone drops for use with X−Slot cards must be provided by the customer.
NOTE When installing external wiring to X−Slot cards, conduit must be installed to the UPS cabinet. When
installing internal wiring to X−Slot terminals, route the wiring through the internal opening in the X−Slot
communication bay.
For installation and setup of an X−Slot card, contact an Eaton service representative
To install wiring to connections:
1. If not already installed, install the LAN and telephone drops.
page 4−2).
3. Remove the right interface entry conduit landing plate to drill or punch holes (see
4. Reinstall the interface entry plate and install the conduit.
5. Route and install the LAN, telephone, and other cables to the appropriate X−Slot
bay locations.
6. Close the door and secure the latch.
7. Refer to the manual supplied with the X−Slot card for operator instructions.
X−Slot Communication Bay 1
X−Slot Communication Bay 2
X−Slot Communication Bay 3
X−Slot Communication Bay 4
Figure 4-28. X−Slot Communication Bays
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−33
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
4.10 Installing a REPO Switch
A latching−type Remote Emergency Power−off (REPO) switch can be used in an
emergency to shut down the UPS and remove power to the critical load from a
NOTE Before installing a REPO switch, verify that the UPS was installed according to the instructions in
NOTE When installing the REPO switch, you must install conduit between the device and the UPS cabinet
for wiring the switch.
NOTE Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes
NOTE The REPO switch must be a normally−open or normally−closed latching-type switch not tied into any
other circuits.
NOTE This procedure is intended to be used for the installation of the Eaton Corporation−supplied REPO
switch. If installing another manufacturer’s switch, use this procedure only as a guide.
NOTE The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
To Install a REPO switch:
1. Verify the UPS system is turned off and all power sources are removed. See
2. Securely mount the REPO switch. Recommended locations include operator’s
consoles or near exit doors. See Figure 3-10 on page 3−7 for enclosure
dimensions and wiring knockouts.
page 4−2).
4. Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.
REPO Switch (Front View)
Contact Block (Back View, Faceplate Removed)
Figure 4-29. REPO Switch
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−34
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
5. To gain access to terminal block TB1 and the interface entry conduit landing
plate, remove the screws securing the top internal safety shield panel and
6. Remove the left interface entry conduit landing plate to drill or punch holes (see
7. Reinstall the interface entry plate and install conduit.
8. To locate the appropriate terminals and review the wiring and termination
10. If the normally−closed REPO TB1 connection in the UPS is not used, connect a
jumper wire between pins 1 and 2 on TB1.
11. If you are installing multiple REPO switches, wire additional switches in parallel
with the first REPO.
Table 4-2. REPO Wire Terminations
From REPO Station(s)
Switch Contact Block
(Either Block)
To Customer Interface
Terminal Board TB1 in
UPS Cabinet
Wire Size
Tightening Torque
3 NO
4 NO
TB1-3
TB1-4
Twisted Wires (2)
14–22 AWG
(0.75–4.0 mm )
7 lb in
(0.8 Nm)
2
1 (NC)
2 (Return)
UPS TB1
3 (NO)
3
REPO
Switch
(NO)
Twisted
Wires
4
4 (Return)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching−type switch not tied to any other circuits.
NOTE REPO normally−open and normally−closed return terminals are separated on
the terminal board but are electrically in common.
Figure 4-30. Normally−Open REPO Switch Wiring
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−35
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
12. If required, install wiring from the REPO switch to the trip circuitry of the
upstream protective devices. A second contact block is provided on the REPO
accordance with NEC Article 725 Class 2 requirements.
13. Reinstall the top internal safety shield panel and secure with the retained
hardware.
hardware.
15. Close the door and secure the latch.
using another manufacturer’s switch.
1
1 (NC)
REPO
Switch
(NC)
Twisted
Wires
2
2 (Return)
UPS TB1
3 (NO)
4 (Return)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching−type switch not tied to any other circuits.
NOTE REPO normally−open and normally−closed return terminals are separated on
the terminal board but are electrically in common.
Figure 4-31. Normally-Closed REPO Switch Wiring
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−36
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
1 (NC)
REPO
Switch
(NC)
2 (Return)
UPS TB1
3 (NO)
REPO
Switch
(NO)
Twisted
Wires
4 (Return)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching−type switch not tied to any other circuits.
NOTE REPO normally−open and normally−closed return terminals are separated on
the terminal board but are electrically in common.
Figure 4-32. Normally-Closed and Normally-Open REPO Switch Wiring
4.11 Installing Options, Accessories, and Distributed Bypass Control Wiring
ꢀInstalling Options and Accessories."
4.12 Initial Startup
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on page W−1 become void. This
service is offered as part of the sales contract for the UPS. Contact an Eaton service
representative in advance (usually a two−week notice is required) to reserve a
preferred startup date.
4.13 Completing the Installation Checklist
The final step in installing the UPS system is completing the following Installation
Checklist. This checklist ensures that you have completely installed all hardware,
cables, and other equipment. Complete all items listed on the checklist to ensure a
smooth installation. Make a copy of the Installation Checklist before filling it out, and
retain the original.
After the installation is complete, an Eaton Customer Service Engineer must verify
the operation of the UPS system and commission it to support the critical load. The
service representative cannot perform any installation tasks other than verifying
software and operating setup parameters. Service personnel may request a copy of
the completed Installation Checklist to verify all applicable equipment installations
have been completed.
NOTE The Installation Checklist MUST be completed prior to starting the UPS system for the first time.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−37
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Installation Checklist
- All packing materials and restraints have been removed from each cabinet.
- Each cabinet in the UPS system is placed in its installed location.
- Joining brackets are installed between the ISBM and UPM sections.
- Intercabinet power wiring is installed between the ISBM and UPM sections.
- Intercabinet interface wiring is installed between the ISBM and UPM sections.
- A cabinet grounding/mounting kit is installed between the ISBM and UPM sections.
- All conduits and cables are properly routed to the UPS and any ancillary cabinets.
- All power cables are properly sized and terminated.
- Neutral conductors are installed or bonded to ground per requirements.
- Battery cables are terminated on E4 (+) and E5 (–).
- Battery aux contact signal wiring is connected from the UPS to the battery disconnect.
- Battery shunt trip signal wiring is connected from the UPS to the battery disconnect. (OPTIONAL)
- LAN and telephone drops are installed.
- All telephone and LAN connections have been completed.
- A ground conductor is properly installed.
- Air conditioning equipment is installed and operating correctly.
- The area around the installed UPS system is clean and dust-free. (It is recommended that the UPS be installed on a
level floor suitable for computer or electronic equipment.)
- Adequate workspace exists around the UPS and other cabinets.
- Adequate lighting is provided around all UPS equipment.
- A 120 Vac service outlet is located within 7.5 meters (25 feet) of the UPS equipment.
- The REPO device is mounted in its installed location and its wiring is terminated inside the UPS cabinet.
- The normally−closed (NC) Emergency Power−off contact (pins 1 and 2 on TB1) is jumpered if not used.
- Alarm relays and building alarms are wired appropriately. (OPTIONAL)
- A remote battery disconnect is mounted in its installed location and its wiring is terminated inside the UPS.
(OPTIONAL)
- Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL)
- The debris shields covering the UPS cabinet ventilation grills are removed.
- Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−38
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Distributed Bypass Installation Checklist
- Each cabinet in the distributed bypass system is placed in its installed location.
- All conduits and cables are properly routed to the UPS cabinets and to the tie cabinet or distribution panel.
- All power cables are properly sized and terminated.
- Neutral conductors are installed or bonded to ground as per requirements.
- A ground conductor is properly installed.
- Controller Area Network (CAN) wiring between the UPS cabinets is properly installed.
- Pull−chain wiring between the UPS cabinets is properly installed.
- Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets.
- Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−39
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS SYSTEM INSTALLATION
Notes
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
4−40
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 5Table 5
Chapter 5
Installing Options and Accessories
5.1
Installing an Optional Powerware Hot Sync CAN Bridge Card
As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card,
control of a parallel system. In addition, this card can be used to connect optional
system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface
Module II, or a Supervisory Contact Module II to the UPS.
Plug−in Terminal
Block J3
Figure 5-1. Powerware Hot Sync CAN Bridge Card
NOTE Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN cards are
not supported and will cause system conflicts.
To install the card:
1. Verify the UPS system is turned off and all power sources are removed. See
page 4−2).
3. Install the Powerware Hot Sync CAN Bridge Card into an open X−Slot
Figure 4-28 on page 4−33 for X−Slot communication bay locations.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−1
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
4. Read and understand the following notes while planning and performing the
wiring installation:
S Conduit must be installed between the UPS cabinet and the device for signal
wiring. Conduit must be installed between the device and the power source
for power wiring. Install the signal wiring in separate conduit from the power
wiring.
S Conduit and wiring between the UPS and the device are to be supplied by the
customer.
S Maximum distance between the UPS cabinet and the device is not to exceed
150 meters (500 feet).
S Use Class 1 wiring methods (as defined by the NEC) for interface and power
wiring up to 30V. The wire should be rated at 24V, 1A minimum.
S Use Class 2 wiring methods (as defined by the NEC) for interface and power
wiring from 30 to 600V.
S Signal wiring should be a minimum of 22 AWG and a maximum of 14 AWG.
The wire should be twisted pair, rated for 5A maximum. Power wiring should
be a minimum of 22 AWG and a maximum of 14 AWG. The wire should be
rated for 1A minimum.
S Use only 75°C copper wire.
S 120 Vac for the RMP II, RIM II, or SCM II should be provided from the critical
bus by facility planners or the customer.
5. Install wiring from the Powerware Hot Sync CAN Bridge Card in accordance with
the following instructions:
To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−2
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status
Alarm
Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections
Table 5-1. Powerware Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
Name
Alarm
Description
1
2
Programmable UPS alarm. Activated by a remote dry contact closure.
Alarm Return
3
Alarm Relay NC Normally-closed contact opens when UPS is on bypass.
Alarm Relay Com Bypass contact return.
4
5
Alarm Relay NO Normally-open contact closes when UPS is on bypass.
TX
6
RMP II, RIM II, and SCM II connections.
TX
7
8
CAN L
9
Can H
Shield
CAN input for parallel operation.
10
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−3
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
5.2
Installing Distributed Bypass Control Wiring
NOTE When installing external wiring to the Powerware Hot Sync CAN Bridge Card, conduit must be
installed to the UPS cabinet. When installing internal wiring to the Powerware Hot Sync CAN Bridge Card
terminals, route the wiring through the internal opening in the X−Slot communication bay.
NOTE When installing interface wiring for the parallel system pull chain, conduit must be installed
between UPSs.
To install distributed bypass control wiring:
1. Verify the UPS system is turned off and all power sources are removed. See
3. Terminal block TB3 is accessible on the left side of the X−Slot communication bay
(see Figure 4-22 on page 4−27). To gain access to terminal block TB1, TB2, and
the left interface entry conduit landing plates, remove the screws securing the
top internal safety shield panel and remove the panel. Retain the hardware for
later use.
4. Remove the interface entry conduit landing plates to drill or punch holes (see
5. Reinstall the interface entry plates and install the conduit.
6. To locate the appropriate terminals and review the wiring and termination
8. If a tie cabinet with Module Output Breakers (MOBs) is being wired, proceed to
9. Route and install distributed bypass system pull−chain wiring between the UPS
cabinets. See Figure 5-5 and Table 5-3 on page 5−6 for wiring information.
11. Route and install distributed bypass system pull−chain wiring between the UPS
page 5−8 for wiring information.
NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an
authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
12. Reinstall the top internal safety shield panel and secure with the retained
hardware.
13. Close the door and secure the latch.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
CAN
Pull Chain
UPS 1
UPS 2
UPS 3
UPS 4
(If Installed)
(If Installed)
NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Figure 5-3. Distributed Bypass System Can and Pull−Chain Simplified Interface Wiring
Shielded Twisted Pair
Shielded Twisted Pair
Shielded Twisted Pair
UPS 2
CAN Bridge Card J3
UPS 1
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
NOTE External CAN connections between UPSs require shielded twisted pair wire.
Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs
Table 5-2. CAN Bridge Card Wiring Terminations
To
To
From
To
UPS 3 CAN Bridge Card
(If Installed)
UPS 4 CAN Bridge Card
(If Installed)
UPS 1 CAN Bridge Card
UPS 2 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–8 (L)
J3–9 (H)
J3–8 (L)
J3–9 (H)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
J3–10 (Shield)
J3–10 (Shield)
J3–10 (Shield)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Twisted Pair
Twisted Pair
Twisted Pair
TB1
TB1
TB1
TB1
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
7
8
7
8
7
8
9
9
9
9
10
10
10
10
TB2
TB2
TB2
TB2
1
2
3
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
Twisted Pair
4
Twisted Pair
Twisted Pair
Twisted Pair
5
6
7
8
7
8
7
8
7
8
9
9
9
9
10
10
UPS 2
10
10
UPS 1
UPS 3
(If Installed)
UPS 4
(If Installed)
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts.
Figure 5-5. Distributed Bypass Pull−Chain Wiring without MOBs
Table 5-3. Pull−Chain Wiring Terminations
To
UPS 3
(If Installed)
To
UPS 4
(If Installed)
From
UPS 1
To
UPS 2
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Shielded Twisted Pair
Shielded Twisted Pair
Shielded Twisted Pair
Twisted Pair
Twisted Pair
Twisted Pair
Twisted Pair
UPS 1
CAN Bridge Card J3
UPS 2
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
Customer−Supplied Tie Cabinet
MOB 3
MOB 1
MOB 2
MOB 4
NC
NO
NC
NO
NC
NO
NC
NO
COM
COM
COM
COM
COM
COM
COM
AUX 1
AUX 2
AUX 1
AUX 2
AUX 1
AUX 2
AUX 1
AUX 2
NC
NO
NC
NO
NC
NO
NC
NO
COM
TB1
TB1
TB1
TB1
7
8
7
8
9
7
8
9
7
8
9
9
10
10
10
10
TB2
TB2
TB2
TB2
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
6
7
8
6
7
8
6
7
8
6
7
8
9
9
9
9
10
10
UPS 2
10
10
UPS 1
UPS 3
(If Installed)
UPS 4
(If Installed)
NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position.
NOTE If MOB contacts have pigtail leads, use the same wire gauge to connect to UPS and use the correct crimp connections for the wire gauge.
NOTE External CAN connections between UPS cabinets require shielded twisted pair wire.
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts.
NOTE Always confirm contact operation prior to wiring.
Figure 5-6. Distributed Bypass Pull−Chain Wiring with MOBs
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Table 5-4. Pull−Chain Wiring Terminations with MOBs
From
To
Function
UPS 1 CAN Bridge Card J3–1 (Alarm)
UPS 1 CAN Bridge Card J3–2 (Alarm Return)
UPS 1 TB2–1 (Pull Chain)
MOB 1 Aux 1 NC
MOB Open Alarm
MOB 1 Aux 1 Com
MOB 1 Aux 2 NO
Pull Chain
UPS 1 TB2–2 (Pull Chain Common)
UPS 2 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 2 CAN Bridge Card J3–1 (Alarm)
UPS 2 CAN Bridge Card J3–2 (Alarm Return)
UPS 2 TB2–1 (Pull Chain)
MOB 2 Aux 1 NC
MOB Open Alarm
MOB 2 Aux 1 Com
MOB 2 Aux 2 NO
Pull Chain
UPS 2 TB2–2 (Pull Chain Common)
UPS 3 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 3 CAN Bridge Card J3–1 (Alarm)
UPS 3 CAN Bridge Card J3–2 (Alarm Return)
UPS 3 TB2–1 (Pull Chain)
MOB 3 Aux 1 NC
MOB Open Alarm
MOB 3 Aux 1 Com
MOB 3 Aux 2 NO
Pull Chain
UPS 3 TB2–2 (Pull Chain Common)
UPS 4 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 4 CAN Bridge Card J3–1 (Alarm)
UPS 4 CAN Bridge Card J3–2 (Alarm Return)
UPS 4 TB2–1 (Pull Chain)
MOB 4 Aux 1 NC
MOB 4 Aux 1 Com
MOB 4 Aux 2 NO
MOB Open Alarm
Pull Chain
MOB 1 Aux 2 Com
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com
Pull Chain MOB Common
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
5.3
Installing an Optional Remote Monitor Panel II
To install RMP II wiring:
1. Verify the UPS system is turned off and all power sources are removed. See
NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the wall. Do not
use hollow wall anchors.
for mounting hole locations.
NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the
device and the UPS cabinet.
4. Remove the ISBM cabinet top right interface conduit landing plate to drill or
5. Reinstall the conduit landing plate.
RMP II knockout hole location.
Powerware Hot Sync CAN Bridge Card terminal location and wiring information,
wiring information.
NOTE 120 Vac for the RMP II should be supplied from the critical bus by facility planners or the customer.
9. Close the front door and secure the latch.
instructions.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−9
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Ground
Terminal
Terminal TB1
Signal Connections
from the UPS
Terminal TB3
120 Vac Power
Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations
Ground Terminal
Neutral
120 Vac from
Critical Bus
Line
UPS Can Card J3
RMP II, RIM II, or SCM II
Twisted Pair
Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring
Table 5-5. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
To
Tightening Torque
Nm (lb in)
Remarks
RMP II, RIM II, or SCM II
J3–6 (TX)
J3–7 (TX)
N/A
TB1–5 (RDX*)
TB1–4 (RDX)
TB3 Line
0.9 (8)
0.9 (8)
Use twisted pair
0.9 (8)
N/A
TB3 Neutral
Ground Terminal
0.9 (8)
N/A
2.7 (24) Maximum
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−10
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton
Customer Service Engineer. Contact an Eaton service representative to schedule a date.
11. To check the operation of the RMP II, ensure that the UPS is supplying the load
via inverter or bypass. If the indicators on the RMP II show the appropriate
status, then it is operating correctly.
If the communication link between the UPS and the RMP II is not present, the
RMP II performs a self-test (all indicators flash and the horn beeps at one-second
intervals). If the self−test occurs, check all harness connectors and the fuse for
proper seating. If all connections are secure but the RMP II continues to self-test,
replace the fuse with the spare included in the hardware kit. If a fuse
replacement does not correct the problem, contact an Eaton service
representative for verification that the RMP II is working correctly.
12. To test the indicator lamps, press and hold the horn silence pushbutton for
three seconds. All lamps should illuminate, and the horn sounds continuously
until you release the pushbutton.
5.4
Installing an Optional Relay Interface Module II
To install RIM II wiring:
1. Verify the UPS system is turned off and all power sources are removed. See
NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the wall. Do not
use hollow wall anchors.
for mounting hole locations.
NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the
device and the UPS cabinet.
4. Remove the ISBM cabinet top right interface conduit landing plate to drill or
5. Reinstall the conduit landing plate.
RIM II knockout hole location.
Powerware Hot Sync CAN Bridge Card terminal location and wiring information,
wiring information.
NOTE 120 Vac for the RIM II should be supplied from the critical bus by facility planners or the customer.
9. Close the front door and secure the latch.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−11
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
instructions.
NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton
Customer Service Engineer. Contact an Eaton service representative to schedule a date.
11. Contact an Eaton service representative for verification and testing of the RIM II
and its connections prior to making connections with J1 through J4 (see
You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.
Table 5-6. J1 through J4 Interface Connectors
Status
J1 through J4
Description
UPS AVAILABLE
Pins 1 and 12
Contacts are closed when the UPS is operating in Normal mode
or ready to supply the load.
UPS OFFLINE
Pins 3 and 13
Pins 5 and 14
Pins 6 and 15
Contacts are open when the UPS is offline. Contacts are closed
when the UPS is operating in Normal mode.
BATTERY WEAK
UTILITY FAILURE
Contacts are closed when approximately two minutes of battery
time remains before the critical load is lost.
Contacts are closed when Utility Failure is detected.
15−Pin D-Sub
Connectors
Figure 5-9. J1, J2, J3, and J4 15−Pin D−Sub Connectors
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−12
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
5.5
Installing an Optional Supervisory Contact Module II
To install SCM II wiring:
1. Verify the UPS system is turned off and all power sources are removed. See
NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the wall. Do not
use hollow wall anchors.
for mounting hole locations.
NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the
device and the UPS cabinet.
4. Remove the ISBM cabinet top right interface conduit landing plate to drill or
5. Reinstall the conduit landing plate.
SCM II knockout hole location.
Powerware Hot Sync CAN Bridge Card terminal location and wiring information,
wiring information.
NOTE 120 Vac for the SCM II should be supplied from the critical bus by facility planners or the customer.
Terminal TB3
120 Vac Power
Ground
Terminal
Terminal TB2 Customer
Supervisory Contact Interface
Terminal TB1 Signal
Connections from the UPS
Figure 5-10. Supervisory Contact Module II Terminal Location
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−13
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton
Customer Service Engineer. Contact an Eaton service representative to schedule a date.
9. Install wiring between the SCM II terminal block TB2 and the monitoring
terminal assignments.
10. Close the front door and secure the latch.
instructions.
System Normal
No Redundancy
On Generator
Bypass Not Available
On Battery
UPS Alarm
On Bypass
Shutdown Imminent
Figure 5-11. Supervisory Contact Module II TB2
NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
NOTE Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of supplying
contact current.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−14
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
5.6
Accessory Mounting Dimensions
the SCM II.
Knockouts Provided
on Five Surfaces
Flush Mount using #10 Pan Head Screws.
(Mount with vent holes facing up.)
Surface Mount using #10 Pan
Head Screws for Hanging.
(Mount with vent holes facing up.)
Dimensions are in millimeters [inches].
Figure 5-12. Remote Monitor Panel II Dimensions
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−15
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Knockouts Provided
on Five Surfaces
Flush Mount using #10 Pan Head Screws.
(Mount with vent holes facing up.)
Surface Mount using #10 Pan
Head Screws for Hanging.
(Mount with vent holes facing up.)
Dimensions are in millimeters [inches].
Figure 5-13. Relay Interface Module II Dimensions
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−16
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
Knockouts Provided
on Five Surfaces
Flush Mount using #10 Pan Head Screws.
(Mount with vent holes facing up.)
Surface Mount using #10 Pan
Head Screws for Hanging.
(Mount with vent holes facing up.)
Dimensions are in millimeters [inches].
Figure 5-14. Supervisory Contact Module II Dimensions
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING OPTIONS AND ACCESSORIES
This page intentionally left blank.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
5−18
Download from Www.Somanuals.com. All Manuals Search And Download.
Section II
Operation
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 6Table 6
Chapter 6
Understanding UPS Operation
6.1
UPS System Overview
The Powerware 9395 UPS is a continuous−duty, solid-state, transformerless (at
480 Vac), three−phase, true online system that provides conditioned and
uninterruptible AC power to the UPS system’s output and critical load.
The basic system consists of a rectifier, battery converter, inverter,
monitoring/operation control panel, integrated communication server, and digital
Battery
Battery
Breaker
Battery System
Battery
Contactor
K2
Battery
Converter
Input
Breaker
CB1
(optional)
Input
Contactor
K1
Output
Contactor
K3
AC Input to
Rectifier/
Charger
Rectifier
Inverter
Power Module
Digital
Metering
Backfeed
Protection
Contactor
K5
AC Output
to Critical
Load
AC Input to
Bypass
Static
Switch
Bypass Breaker (CB4)
UPS Cabinet
Figure 6-1. Main Elements of the UPS System
ꢀProduct Specifications," the UPS uses a backup battery supply to maintain power to
the critical load for a specified period of time or until the utility power returns. For
extended power outages, the UPS allows you to either transfer to an alternative
power system (such as a generator) or shut down your critical load in an orderly
manner.
The emergency bypass consists of a momentary−duty static switch, a wraparound
bypass breaker, and a backfeed protection contactor K5. The bypass breaker is
located in parallel with the static switch. The backfeed protection contactor is located
in series with the static switch. Bypass breaker CB4 is used for manual transfers to
bypass without using the static switch. The static switch is armed and ready during
both types of transfers.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−1
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
6.2
Single UPS
A single UPS operates independently to support an applied load from the inverter,
providing conditioned and uninterruptible AC power to the critical load from the output
of the module. During an outage, the inverter continues to operate, supporting power
to the load from the battery supply. If the unit requires service, applied loads are
transferred to the internal bypass, continuous−duty static switch either automatically
or manually. With the exception of a battery cabinet, no other cabinets or equipment
are required for the single UPS to successfully support its applied loads.
6.2.1
Modes
The Powerware 9395 UPS supports a critical load in three different modes of
operation:
S In Normal mode, the critical load is supplied by the inverter, which derives its
power from rectified utility AC power. In this mode, the battery charger also
provides charging current for the battery, if needed.
S In Bypass mode, the critical load is directly supported by utility power.
S In Battery mode, the battery provides DC power, which maintains inverter
operation. The battery supports the critical load.
The UPS can automatically use all three modes, as required. The following paragraphs
describe the differences in the three UPS operating modes, using block diagrams to
show the power flow during each mode of operation.
6.2.2
Normal Mode
is operating in Normal mode.
During normal UPS operation, power for the system is derived from a utility input
source through the rectifier input contactor K1. The front panel displays ꢀNormal,"
indicating the incoming power is within voltage and frequency acceptance windows.
Three−phase AC input power is converted to DC using IGBT devices to produce a
regulated DC voltage to the inverter. When contactor K2 is closed the battery is
charged directly from the regulated rectifier output through a buck or boost DC
converter, depending on the system voltage and the size of the battery string
attached to the unit.
The battery converter derives its input from the regulated DC output of the rectifier
and provides either a boosted or bucked regulated DC voltage charge current to the
battery. The battery is always connected to the UPS and ready to support the inverter
should the utility input become unavailable.
The inverter produces a three−phase AC output to a customer’s load without the use
of a transformer. The inverter derives regulated DC from the rectifier and uses IGBT
devices and pulse−width modulation (PWM) to produce a regulated and filtered AC
output. The AC output of the inverter is delivered to the system output through the
output contactor K3.
If the utility AC power is interrupted or is out of specification, the UPS automatically
switches to Battery mode to support the critical load without interruption. When utility
power returns, the UPS returns to Normal mode.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−2
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
Bypass
Breaker
(CB4)
Static
Bypass Input
K5
Input
Breaker
(CB1
Switch
Rectifier
Input
Output
Rectifier
Inverter
K1
K3
Battery
Converter
Main Power Flow
Trickle Current
Energized
K2
Breakers
Contactors
Closed
Open
Battery
Breaker
Battery
Breaker
De−Energized
Battery
Figure 6-2. Path of Current Through the UPS in Normal Mode
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode.
The UPS automatically returns to Normal mode when the overload condition is
cleared and system operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and
remains in that mode until the failure is corrected and the UPS is back in service.
6.2.3
Bypass Mode
The UPS automatically switches to Bypass mode if it detects an overload, load fault,
or internal failure. The UPS can also be transfered from Normal mode to Bypass mode
manually. The bypass source supplies the commercial AC power to the load directly.
operating in Bypass mode.
CAUTION
The critical load is not protected while the UPS is in Bypass mode.
In Bypass mode, the output of the system is provided with three−phase AC power
directly from the system input. While in this mode, the output of the system is not
protected from voltage or frequency fluctuations or power outages from the source.
Some power line filtering and spike protection is provided to the load but no active
power conditioning or battery support is available to the output of the system in the
Bypass mode of operation.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−3
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
The internal bypass is comprised of a solid−state, silicon−controlled rectifier (SCR)
static switch (SSW), a motorized wraparound bypass breaker CB4, and a backfeed
protection contactor K5. The static switch is rated as a momentary−duty device that is
used instantaneously anytime the inverter is unable to support the applied load. The
static switch is wired in series with the backfeed protection contactor, and CB4 is
wired in parallel with this combination. Together they are wired in parallel with the
rectifier and inverter.
The static switch, being an electronically−controlled device, can be turned on
immediately to pick up the load from the inverter while bypass breaker CB4 closes
and inverter output contactor K3 opens to isolate the inverter. When breaker CB4
closes, the static switch stops conducting. The backfeed protection contactor is
normally always closed, ready to support the static switch unless the bypass input
source becomes unavailable.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than
operator intervention, the UPS automatically attempts to transfer back to Normal
mode (up to three times within a ten minute period). The fourth transfer locks the
critical load to the bypass source and requires operator intervention to transfer.
Bypass
Breaker
(CB4)
Static
Bypass Input
Input
Breaker
(CB1
K5
Switch
Rectifier
Input
Output
Rectifier
Inverter
K1
K3
Battery
Converter
Main Power Flow
Trickle Current
Energized
K2
Breakers
Contactors
Closed
Open
Battery
Breaker
De−Energized
Battery
Figure 6-3. Path of Current Through the UPS in Bypass Mode
6.2.4
Battery Mode
The UPS automatically transfers to Battery mode if a utility power outage occurs, or if
the utility power does not conform to specified parameters. In Battery mode, the
battery provides emergency DC power that the inverter converts to AC power.
operating in Battery mode.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−4
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
During a utility power failure, the rectifier no longer has an AC utility source from
which to supply the DC output current required to support the inverter. The input
contactor K1 opens and the battery instantaneously supplies energy to the battery
converter. The converter either bucks or boosts the voltage so that the inverter can
support the customer’s load without interruption. If bypass is common with the
rectifier input, the backfeed protection contactor K5 also opens. The opening of
contactors K1 and K5 prevent system voltages from bleeding backwards through the
static switch and rectifier snubber components and re−entering the input source.
Bypass
Breaker
(CB4)
Static
Bypass Input
K5
Input
Breaker
(CB1
Switch
Rectifier
Input
Output
Rectifier
Inverter
K1
K3
Battery
Converter
Main Power Flow
Trickle Current
Energized
K2
Breakers
Contactors
Closed
Open
Battery
Breaker
De−Energized
Battery
Figure 6-4. Path of Current Through the UPS in Battery Mode
If the input power fails to return or is not within the acceptance windows required for
normal operation, the battery continues discharging until a DC voltage level is reached
where the inverter output can no longer support the connected loads. When this
event occurs, the UPS issues another set of audible and visual alarms indicating
SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output
can be supported for only two minutes before the output of the system shuts down.
If the bypass source is available, the UPS transfers to bypass instead of shutting
down.
If at any time during the battery discharge the input power becomes available again,
contactors K1 and K5 close and the rectifier begins to supply DC current to the
converter and inverter. At this point, the unit returns to Normal mode. Depending on
the total load and the duration of the battery discharge, battery current limit alarms
may be seen for a short time due to the current required to recharge the battery.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−5
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
6.3
Single UPS Unit System Oneline Configurations
The system oneline drawings in this section show the simplified internal structure of
the UPS, battery supply, and basic maintenance bypass.
Voltage
Oneline Drawing
UPS Model
System Type
Input
Output
9395−1100/1000
9395−1100/1100
Single Unit Four UPM – Reverse Transfer
Dual-Feed Common Battery System
480
480
9395−1100/1000
9395−1100/1100
Single Unit Four UPM – Reverse Transfer
Dual-Feed Separate Battery System
480
480
480
480
9395−1100/650
9395−1100/750
9395−1100/825
Single Unit Three UPM – Reverse Transfer
Dual-Feed Common Battery System
9395−1100/650
9395−1100/750
9395−1100/825
Single Unit Three UPM – Reverse Transfer
Dual-Feed Separate Battery System
480
480
480
480
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
Simplified Dual−Feed UPS with Maintenance
Bypass Panel
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−6
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
AC Input to
Bypass
3 or 4 Wire A−B−C
Rotation
Battery Aux
AC Input to
UPS Rectifier
3 Wire A−B−C
Rotation
Building Alarms
Alarm Relays
48V Battery
Shunt Trip
Bypass
Breaker
(CB4)
X−Slot
Interface
Remote EPO
B
E6, E7,
E8, E12
A
E1, E2, E3
Interface Board
Static
Switch
Input Breaker
(CB1)
(optional)
Fuse
Backfeed
Contactor (K5)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Rectifier
Rectifier
Rectifier
Rectifier
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
AC Output
to Critical
Load
E9,
E10,
E11,
E12
D
Battery
Converter
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
Fuse
Fuse
Fuse
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
UPM 4
UPM 1
UPM 2
UPM 3
UPS CABINET
E4. E5
FI−UPM CABINET
C
Battery
Breaker
BATTERY SYSTEM
(Not supplied with the UPS)
Service Connector
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-5. Four UPM UPS System, Dual-Feed, Common Battery System
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−7
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
AC Input to
Bypass
3 or 4 Wire A−B−C
Rotation
Battery Aux
AC Input to
UPS Rectifier
3 Wire A−B−C
Rotation
Building Alarms
Alarm Relays
48V Battery
Shunt Trip
Bypass
Breaker
(CB4)
X−Slot
Interface
Remote EPO
B
E6, E7,
E8, E12
A
E1, E2, E3
Interface Board
Static
Switch
Input Breaker
(CB1)
(optional)
Fuse
Backfeed
Contactor (K5)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Rectifier
Rectifier
Rectifier
Rectifier
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
Inverter
Output
Contactor
(K3)
AC Output
to Critical
Load
E9,
E10,
E11,
E12
D
Battery
Converter
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
Fuse
Fuse
Fuse
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
UPM 4
UPM 1
E4. E5
UPM 2
E4. E5
UPM 3
UPS CABINET
E4. E5
FI−UPM CABINET
C
C
C
C
Battery
Breaker
Battery
Breaker
Battery
Breaker
Battery
Breaker
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
Service Connector
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-6. Four UPM UPS System, Output Dual-Feed, Separate Battery System
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−8
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
AC Input to
Bypass
3 or 4 Wire A−B−C
Rotation
Battery Aux
AC Input to
UPS Rectifier
3 Wire A−B−C
Rotation
Building Alarms
Alarm Relays
48V Battery
Shunt Trip
Bypass
Breaker
(CB4)
X−Slot
Interface
Remote EPO
B
E6, E7,
E8, E12
A
E1, E2, E3
Interface Board
Static
Switch
Input Breaker
(CB1)
(optional)
Fuse
Backfeed
Contactor (K5)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Rectifier
Rectifier
Rectifier
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Inverter
Output
Inverter
Output
Inverter
Output
Contactor
(K3)
Contactor
(K3)
Contactor
(K3)
AC Output to
Critical Load
E9, E10,
E11, E12
D
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
Fuse
Fuse
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
UPS
CABINET
UPM 1
UPM 2
UPM 3
E4. E5
C
Battery
Breaker
BATTERY SYSTEM
(Not supplied with the UPS)
Service Connector
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-7. Three UPM UPS System, Dual-Feed, Common Battery System
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−9
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
AC Input to
Bypass
3 or 4 Wire A−B−C
Rotation
Battery Aux
AC Input to
UPS Rectifier
3 Wire A−B−C
Rotation
Building Alarms
Alarm Relays
48V Battery
Shunt Trip
Bypass
Breaker
(CB4)
X−Slot
Interface
Remote EPO
B
E6, E7,
E8, E12
A
E1, E2, E3
Interface Board
Static
Switch
Input Breaker
(CB1)
(optional)
Fuse
Backfeed
Contactor (K5)
Input
Contactor
(K1)
Input
Contactor
(K1)
Input
Contactor
(K1)
Rectifier
Rectifier
Rectifier
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Inverter
Output
Inverter
Output
Inverter
Output
Contactor
(K3)
Contactor
(K3)
Contactor
(K3)
AC Output to
Critical Load
E9, E10,
E11, E12
D
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
Fuse
Fuse
Battery Contactor (K2)
Battery Contactor (K2)
Battery Contactor (K2)
UPS
CABINET
UPM 1
E4. E5
UPM 2
E4. E5
UPM 3
E4. E5
C
C
C
Battery
Breaker
Battery
Breaker
Battery
Breaker
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
Service Connector
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-8. Three UPM UPS System, Dual-Feed, Separate Battery System
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−10
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
AC Input
AC Input
To UPS
Rectifier
Input
To UPS
Bypass
Input
RIB
BIB
MBP
MIS
CRITICAL LOAD
DISTRIBUTION UNIT
Output
from
UPS
MAINTENANCE
BYPASS PANEL
(Provided by Others)
Backfeed
Contactor
Static
Switch
K5
Output
Contactor
K3
UPS
Battery
Breaker
BATTERY SYSTEM
RIB:
Rectifier Input Breaker
BIB:
Bypass Input Breaker
MIS:
MBP:
Maintenance Isolation Breaker
Maintenance Bypass Breaker
NOTE If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a single feed with two
upstream feeder breakers, must be provided: one for the UPS or rectifier input breaker (RIB) (if installed) and one for the maintenance bypass
input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass input
breaker (BIB) is installed in the maintenance bypass and a single−feed UPS is being installed, a single feed to the maintenance bypass is
acceptable for supplying both the UPS and the bypass.
Figure 6-9. Simplified Dual−Feed UPS with Maintenance Bypass Panel
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−11
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
6.4
Multiple UPS Distributed Bypass System
Distributed bypass parallel operation extends the normal operation of Powerware
9395 UPSs by offering increased capacity and/or redundant capability. The parallel
system continues to maintain power to the critical loads during commercial electrical
power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency
conditions.
The output of the system is normally supplied by several Uninterruptible Power
Modules (UPMs) contained in each UPS. Multiple UPMs are connected with their
outputs in parallel (tied together) to provide a load level greater than the rating of one
UPM and/or for redundancy. The paralleled UPMs supply the output load with
protected power as long as the load does not exceed the combined rating of the
paralleled UPMs.
The power system is redundant as long as one of the UPMs can be disconnected
from the output bus and the remaining UPMs can continue to supply power to the
load without exceeding their ratings.
When the load is being supplied by the UPMs, the system output bus is continuously
monitored for an overvoltage or undervoltage condition. If an out of limits condition is
detected, the paralleled UPMs transfer the load to bypass using the UPS static
switches.
Communication is required between the UPSs for system metering and mode
control. System level communication and control are accomplished using a Controller
Area Network (CAN). A single building alarm in each UPS, connected to the other
UPSs in parallel and tied to the bypass contactor auxiliary contacts in each UPS, are
used for a secondary communication path. This arrangement ensures bypass control
even if the CAN bus is lost.
The system is paralleled for redundancy (1+1) in a system where two UPMs are
paralleled together and the load is less than the supporting capability of one of the
UPMs. The system is paralleled for capacity (2+0) if both UPMs in a system are
required to support the load.
A parallel capacity system can also be redundant (2+1), as long as there is always one
or more UPMs online than required to support the load.
6.4.1
Multiple UPS Parallel System Modes
Similar to the single UPS system, the Powerware 9395 UPS parallel system supports
a critical load in three different modes of operation. The standard operation
modes are:
S In Normal mode, the paralleled UPMs supply the critical load with clean, filtered
power. Each UPM battery charger also provides charging current for the battery if
needed.
S In Battery mode, the battery provides DC power, which maintains UPM operation.
The UPM batteries support the critical load.
S In Bypass mode, the critical load is directly supported by utility power through the
continuous−duty static bypass switch in each UPS.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−12
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
The UPSs continually monitor themselves and the incoming utility power and
automatically switch between these modes as required, without operator
intervention, except when manually switching to Bypass mode. The sophisticated
detection and switching logic inside the UPSs ensures that operating mode changes
are automatic and transparent to the critical load, while internal monitoring systems
indicate the current mode of operation. The UPSs switch operating modes in
response to these system events:
S A command is an intervention that is externally initiated by an operator or by some
site action. A command causes the UPSs to switch operating modes; it usually
does not require any further action.
S A notice is a minor system event that may or may not require attention.
S An alarm is a system event that requires immediate intervention.
The following paragraphs describe the differences in the three parallel system
operating modes, using block diagrams to show the power flow during each mode of
operation.
6.4.2
Normal Mode – Distributed Bypass
In Normal mode, utility AC power is supplied to the UPSs. Each UPS then conditions
the incoming AC power and provides clean, regulated AC power to tie cabinet or
distribution panel for parallel systems up to four modules. The applied load is shared
equally among the available UPMs in the system.
operating in Normal mode.
Bypass Input
UPS Input
Tie Cabinet
UPS 1 Output
UPS 1
Battery
UPS 2 Output
UPS 2
Battery
Battery
UPS 3 Output
UPS 3
UPS 4 Output
UPS 4
Battery
Breakers
Closed
Output to
Critical Load
Main Power Flow
Open
Figure 6-10. Path of Current through the UPSs in Normal Mode – Distributed Bypass
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−13
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
If the utility AC power is interrupted or is out of specification, the UPSs automatically
switch to Battery mode to support the critical load without interruption. When utility
power returns, the UPSs return to Normal mode.
If the UPSs become overloaded or unavailable, the distributed bypass system
switches to Bypass mode. The distributed bypass system automatically returns to
Normal mode when the overload condition is cleared and system operation is
restored within specified limits.
6.4.3
Bypass Mode – Distributed Bypass
In Bypass mode, the output of the system is provided with three−phase AC power
directly from the bypass input. While in this mode, the output of the system is not
protected from fluctuations, spikes, or power outages from the source. No battery
support is available to the output of the system in the Bypass mode of operation.
The distributed bypass system automatically switches to Bypass mode if it detects a
UPS system overload or load fault.
If one UPS becomes unavailable, the distributed bypass system dynamically updates
the redundancy calculation to determine if the remaining UPSs can support the load.
If the load can be supported, the system does not switch to bypass.
operating in Bypass mode.
Bypass Input
UPS Input
Tie Cabinet
UPS 1 Output
UPS 1
Battery
Battery
Battery
UPS 2 Output
UPS 2
UPS 3 Output
UPS 3
UPS 4 Output
UPS 4
Battery
Breakers
Closed
Output to
Critical Load
Main Power Flow
Open
Figure 6-11. Path of Current through the UPSs in Bypass Mode – Distributed Bypass
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−14
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
In a distributed bypass system, each UPS operates similar to a single UPS, but in
parallel with each other. The bypass source for the load is derived from the bypass
input of one, two, three, or four UPSs, depending on the system configuration,
through the internal static switches. If a module is taken offline, the other modules
remain online to support the load. If more modules than can support the load must be
taken offline, the load must be transferred to maintenance bypass or shut down.
The distributed bypass system can be transferred from Normal mode to Bypass mode
manually. However, the distributed bypass system automatically switches to Bypass
mode whenever the UPSs can no longer supply the critical load. If the distributed
bypass system transfers to Bypass mode from Normal mode due to an output voltage
deviation, the distributed bypass system automatically attempts to return to Normal
mode (up to three times within a 10-minute period). After three transfer attempts or
an overload, the system locks the critical load to the bypass source and requires
operator intervention to transfer.
Bypass mode is a normal operating mode, not an alarm condition. However, if the
distributed bypass system is unable to return to Normal mode following an automatic
transfer to Bypass mode, an alarm condition is recorded.
Bypass may also be used when the UPSs or UPMs in the system must be shut down
to perform routine maintenance or repairs.
In the Parallel Redundant (N+1) arrangement, the bypass circuitry in each UPS
operates to support the applied loads on bypass. If the UPSs are in NORMAL and one
UPS trips offline, the remaining UPSs do not go to bypass as long as they have the
capacity to support the load.
In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to
bypass, the remaining UPSs also go to bypass.
6.4.4
Battery Mode – Distributed Bypass
The UPSs transfer to Battery mode automatically if a utility power outage occurs, or if
the utility power does not conform to specified parameters. In Battery mode, the
battery provides emergency DC power that the inverter converts to AC power.
when operating in Battery mode.
While in Battery mode, the UPSs sound an audible horn, illuminate a visual indicator
lamp on the front panel (System Normal, On Battery), and create an entry into the
alarm event history. As the battery discharges, the boost converter and inverter
constantly make minute adjustments maintaining a steady output. The UPSs remain
in this operating mode until the input power to the rectifier is again within the
specified voltage or frequency acceptance windows.
If the input power fails to return or is not within the acceptance windows required for
normal operation, the battery continues discharging until a DC voltage level is reached
where the inverter output can no longer support the shared loads. When this event
occurs, each UPS issues another set of audible and visual alarms that indicate a
two−minute SHUTDOWN IMMINENT warning. Unless the system has a valid AC
input soon, redundant UPMs begin shutting down until there are no longer enough
UPMs online to support the connected load. When this event occurs, the system
shuts down. If the bypass source is available, the system transfers to bypass instead
of shutting down.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−15
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
Bypass Input
UPS Input
Tie Cabinet
UPS 1 Output
UPS 1
UPS 2
UPS 3
UPS 4
Battery
Battery
Battery
UPS 2 Output
UPS 3 Output
UPS 4 Output
Battery
Breakers
Closed
Open
Output to
Critical Load
Main Power Flow
Figure 6-12. Path of Current through the UPSs in Battery Mode – Distributed Bypass
If at any time during the battery discharge the input power becomes available again,
the rectifier begins to supply DC current to the inverter. At this point, the UPS returns
to Normal mode. If at any time during the battery discharge the AC input power
becomes available again, each rectifier turns on, assumes the inverter load from the
batteries, and begins recharging the batteries. Depending on the total load and the
duration of the battery discharge, battery and rectifier input current limit alarms may
be seen for a short time due to the current required to recharge the batteries.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−16
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
6.5
Multiple UPS Distributed Bypass System Oneline Configurations
The distributed bypass system oneline drawings in this section show the simplified
internal structure of the UPS, battery supply, and basic maintenance bypass in a
multiple UPS configuration. These onelines do not show each UPM in the UPSs, but
represent each UPS in the distributed bypass system. The internal structure of each
Voltage
Oneline Drawing
UPS Model
System Type
Input
Output
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
Multiple UPS – Distributed Bypass
1+1 and 2+0 Configurations
480
480
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
Multiple UPS – Distributed Bypass
2+1 and 3+0 Configurations
480
480
480
480
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
Multiple UPS – Distributed Bypass
3+1 and 4+0 Configurations
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−17
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
A
B
A
B
*
*
*
*
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
E8
E12
UPS 2
UPS 1
Fuse
Fuse
CB1
(optional)
CB1
(optional)
K1
K1
CB4
CB4
Rectifier
Rectifier
Static
Switch
Static
Switch
Fuse
Fuse
Fuse
Fuse
K5
K5
Fuse
Fuse
Inverter
Inverter
K3
K3
Battery
Converter
Battery
Converter
Fuse
K2
Fuse
K2
C
C
E4. E5
Battery Breaker
E4. E5
Battery Breaker
TIE
E9,
E9,
CABINET
(Optional)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
E10,
E11,
E12
E10,
E11,
E12
MOB 1
MOB 2
D
D
A – AC Input to UPS Rectifier
B – AC Input to Bypass
C – DC Input from Battery
D – UPS AC Output to Tie Cabinet
E – Output to Critical Load
E
* – Overcurrent Protection provided by customer
*
AC Output to
Critical Load
NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral
conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-13. Typical Distributed Bypass System (1+1 and 2+0 Configurations)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−18
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
A
B
A
B
A
B
*
*
*
*
*
*
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
UPS 3
UPS 2
UPS 1
Fuse
Fuse
Fuse
E8
E12
CB1
(optional)
CB1
(optional)
CB1
(optional)
K1
K1
K1
CB4
CB4
CB4
Rectifier
Rectifier
Rectifier
Static
Switch
Static
Switch
Static
Switch
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
K5
K5
K5
Fuse
Fuse
Fuse
Inverter
Inverter
Inverter
K3
K3
K3
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
K2
Fuse
K2
Fuse
K2
C
C
C
E4. E5
Battery Breaker
E4. E5
Battery Breaker
E4. E5
Battery Breaker
TIE
E9,
E9,
E9,
CABINET
(Optional)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
E10,
E11,
E12
E10,
E11,
E12
E10,
E11,
E12
MOB 1
MOB 2
D
D
D
MOB 3
A – AC Input to UPS Rectifier
B – AC Input to Bypass
C – DC Input from Battery
D – UPS AC Output to Tie Cabinet
E – Output to Critical Load
E
* – Overcurrent Protection provided by customer
*
AC Output to
Critical Load
NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral
conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-14. Typical Distributed Bypass System (2+1 and 3+0 Configurations)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−19
Download from Www.Somanuals.com. All Manuals Search And Download.
UNDERSTANDING UPS OPERATION
A
B
A
B
A
B
A
B
*
*
*
*
*
*
*
*
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
E8
E12
E1
E2
E3
E6
E7
E8
E12
UPS 4
UPS 3
UPS 2
UPS 1
Fuse
Fuse
Fuse
Fuse
CB1
(optional)
CB1
(optional)
CB1
(optional)
CB1
(optional)
K1
K1
K1
K1
CB4
CB4
CB4
CB4
Rectifier
Rectifier
Rectifier
Rectifier
Static
Switch
Static
Switch
Static
Switch
Static
Switch
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
K5
K5
K5
K5
Fuse
Fuse
Fuse
Fuse
Inverter
Inverter
Inverter
Inverter
K3
K3
K3
K3
Battery
Converter
Battery
Converter
Battery
Converter
Battery
Converter
Fuse
K2
Fuse
K2
Fuse
K2
Fuse
K2
C
C
C
C
E4. E5
Battery Breaker
E4. E5
Battery Breaker
E4. E5
Battery Breaker
E4. E5
Battery Breaker
TIE
E9,
E9,
E9,
E9,
CABINET
(Optional)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
BATTERY SYSTEM
(Not supplied
with the UPS)
E10,
E11,
E12
E10,
E11,
E12
E10,
E11,
E12
E10,
E11,
E12
MOB 1
MOB 2
D
D
D
D
MOB 3
MOB 4
A – AC Input to UPS Rectifier
B – AC Input to Bypass
C – DC Input from Battery
D – UPS AC Output to Tie Cabinet
E – Output to Critical Load
E
* – Overcurrent Protection provided by customer
*
AC Output to
Critical Load
NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral
conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
Figure 6-15. Typical Distributed Bypass System (3+1 and 4+0 Configurations)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
6−20
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 7Table 7
Chapter 7
UPS Operating Instructions
This section describes how to operate the UPS.
NOTE Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has
been performed by authorized service personnel. The preliminary startup verifies all electrical
interconnections to ensure the installation was successful and the system operates properly.
NOTE Read this section of the manual and have thorough knowledge of UPS operation before attempting
to operate any of the controls.
NOTE The UPS displays two minutes of battery runtime at the initial startup. After a 24−hour charging
period, the UPS automatically runs a battery test and the correct battery runtime displays.
7.1
UPS Controls and Indicators
The controls and indicators identified and described in this section are used to control
Control Panel
AC Input Breaker CB1
(optional)
ISBM
Figure 7-1. UPS Controls and Indicators – ISBM Section Shown
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−1
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.1.1
Control Panel
The control panel is used to set up and control the UPS, and to monitor UPS
7.1.2
Circuit Breaker
Optional circuit breaker (CB1) is used to control the AC input to the UPS rectifier.
NOTE CB1 is supplied with an extension handle to assist in operating the breaker. This handle can not be
installed permanently and must be removed for the front door to close. Self−stick hook and loop fastener
strips are provided tied to the handle for mounting the handle in a convenient location (such as next to the
breaker on the bottom internal safety shield panel) when not in use. Remove the backing from each strip and
attach one strip to the handle and the other strip to any smooth surface.
7.2
Using the Control Panel
The following paragraphs describe the UPS control panel, including controls and
located on the front door of the UPS.
3
PRESS ANY KEY TO CONTINUE
1
2
Figure 7-2. UPS Control Panel
The control panel consists of:
S A liquid crystal display (LCD) (1)
S A horizontal row of pushbutton switches (2)
The following paragraphs describe using the UPS control panel to monitor the UPS.
See paragraph 7.3 for use of the operational controls.
When the UPS powers up, the screen displays the Eaton | Powerware logo as shown
panel pushbutton once.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−2
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.2.1
Status Indicators
The four symbols on the right side of the control panel are status indicators. These
colored light emitting diode (LED) lamps, work with the alarm horn to let you know
the operating status of the UPS.
Table 7-1. Status Indicators
Indicator
Status
Description
On
Off
On
The UPS is operating normally. The power module is supplying power to the critical load.
The UPS is turned off.
Green
Yellow
The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the Normal indicator
also remains illuminated.
On
On
The UPS is in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not
illuminated when the system is in Bypass mode.
Yellow
Red
The UPS has an active alarm and requires immediate attention. The LCD shows the highest priority active
alarms. All alarms are accompanied by an audible horn. To silence the horn, press any control panel
pushbutton once. The Alarm indicator may be illuminated along with other indicators.
Flashing
There is a new UPS alarm condition. The indicator flashes until acknowledged by pressing any control
panel pushbutton once.
7.2.2
System Events
When the UPS system is running in Normal mode, it continually monitors itself and
the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to
let you know exactly what event caused the change from Normal mode. System
events on the UPS can be indicated by horns, lights, messages, or all three.
Select EVENTS from the menu bar on the main menu screen to look at the active
events screen. This screen shows any currently active alarms, notices, or commands.
S
S
System Event Horns – The system event horn beeps to alert an operator that an
event needing attention is taking place. The horn cycles at a half−second rate.
System Event Indicators – The status indicators on the UPS control panel work with
the event horn to let the operator know when the is operating in any mode other
than normal. Only the ON indicator is visible during normal UPS system operation.
The other indicators illuminate to indicate alarms or events. When an alarm occurs,
first check these indicators to see what type of event has taken place. For
S
System Event Messages – When a system event occurs, a message appears on the
LCD in the UPS status area. This message is also written to the Active Events Log
and may be added to the History Log. The messages are divided into four
categories: alarms, notices, status, and commands.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−3
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.2.3
Using the LCD and Pushbuttons
The LCD on the control panel provides an operator interface with the UPS system.
A
B
ALARM: INPUT AC UNDER VOLTAGE
INPUT
BATT
UPS
STSW
SETUP
OUTPUT
BYPASS
EVENTS
C
D
METERS
CONTROLS
LOAD OFF
Figure 7-3. Parts of the LCD
A
The UPS status area automatically scrolls between the Powerware model number, current date and time,
active alarms, active notices, and load percent and battery runtime for the UPS. The top line of display blinks
while scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible
horn. To silence the horn, press any control panel pushbutton once. Shown is a typical alarm message. For
B
C
The information area contains data about UPS status and operations.
The menu bar lists the titles of the available screens. To select a screen, press the pushbutton underneath the
desired screen.
D
Each navigation pushbutton function depends on the screen displayed. Use the pushbuttons to select menu
screens or scroll through available screens. The LCD options above the pushbuttons indicate each
pushbutton’s function.
You can use the LCD and the pushbuttons to:
After approximately 30 minutes, the display screen darkens. To restore the screen,
press any pushbutton once.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−4
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.2.4
Using the Menu
The UPS menu bar allows you to display data in the information area to help you
Table 7-2. Display Function Menu Map
Menu Option Description
EVENTS
METERS
Displays the list of Active System Events and a historical log of system events.
Displays performance meters for the system or critical load.
CONTROLS Displays the System Status screen.
SETUP
Allows you to set the display contrast, set the date and time for the time stamp,
configure the UPS serial communication ports, and view the firmware version numbers.
LOAD OFF
ESC
De−energizes the critical load and powers down the UPS.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
Return arrow acknowledges or executes a command, or saves a setting.
Up and down arrows scroll through screens and lists or highlight settings.
Left and right arrows select or adjust settings displayed on the screen.
7.2.5
Mimic Screen
the Events, Meters, Controls, or Setup screens, press the ESC pushbutton on the
current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real-time
graphical representation of the operating status of the system.
TIME: 11 : 35 : 43
INPUT
DATE: 06 / 25 / 2008
UPS
BATT
STSW
CONTROLS
SETUP
OUTPUT
BYPASS
EVENTS
LOAD OFF
METERS
Figure 7-4. Main Menu and Mimic Screen (Normal Mode)
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−5
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.2.6
Display Menu Operation
Table 7-3. Display Menu Operation
Function
Subfunction
Operation
Events
Press the EVENTS pushbutton on the main menu bar or History menu bar to display a listing of
all system events that are currently active. The most recent event is listed first. As events clear,
they are removed from the Active System Events listing. To scroll through the events, press the
up or down arrow pushbutton on the menu bar.
User History
Press the HISTORY pushbutton on the Active Events menu bar to display the User History Log.
The User History Log lists up to 2048 events in chronological order, with the most recent event
listed last (once 2048 is reached, the earliest event is overwritten). The end of the log (the most
recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the up or down arrow pushbutton on the menu bar. To return to the Active Events
screen, press the EVENTS pushbutton on the menu bar.
Service History
The Service History Log is for service personnel and is password protected. If the customer
needs access to the log, contact an Eaton service representative.
Press the SERVICE pushbutton on the User History menu bar to display the Service History Log.
The Service History Log lists up to 2048 events in chronological order, with the most recent event
listed last (once 2048 is reached, the earliest event is overwritten). The end of the log (the most
recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the up or down arrow pushbutton on the menu bar. To return to the User History
screen, press the USER pushbutton on the menu bar. To return to the Active Events screen,
press the EVENTS pushbutton on the menu bar.
Meters–UPS
Meters–UPM
The Meter screens show the UPS meter readings for the unit. The default voltage displayed on
these screens is phase−to−neutral. However, an authorized Eaton Customer Service Engineer
can change the screens to display the voltage phase−to−phase (A−B, B−C, C−A). Press the
METERS pushbutton on the main menu bar to display the Meter screens. To scroll through the
meter screens, press the up or down arrow pushbutton on the menu bar. The current UPS
readings are displayed in the information area of the screen.
Output–UPS
Output–UPM 1, 2, 3, 4
The Output screen shows output voltage (phase-to-neutral), output current (each phase), and
frequency being supplied by the UPS, as well as the kVA, kW, and power factor measurements.
Input–UPS
Input–UPM
The Input screen shows input voltage (phase-to-neutral), input current (each phase), and
frequency of the incoming utility source, as well as the kVA, kW, and power factor
measurements.
Bypass
The Bypass screen shows the bypass input voltage (phase-to-neutral), input current (each
phase), and frequency of the incoming utility source, as well as the kVA, kW, and power factor
measurements.
Battery–UPS
Battery–UPM
The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of
battery time remaining, and battery temperature. Battery temperature must be set up by an
authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%,
Check Battery is displayed.
Statistics
The Statistics screen displays the hours on line and the total kW hours used.
Output Current–UPS
Output Current–UPM
The Output Current screen displays a real-time bar graph of the output current of the UPS. The
graph shows the current for each phase.
Output Power – UPM
Function Selection
The Output Power screen displays the power in kW and kVA for each UPM.
System Level 0 Setup
This screen can be used to set the screen contrast, show the firmware versions installed,
identify the unit type and enter a password to access Level 1 functions. Press the SETUP
pushbutton on the main menu bar to display the System Setup Level 0 Screen. No password is
necessary to access Level 0 functions. Use the up or down arrow pushbutton to highlight the
setup function screen desired, then press the SELECT pushbutton to display the function screen.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−6
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
Function
Subfunction
Operation
Contrast Adjust
Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust screen.
Use the left or right arrow pushbutton to adjust the contrast for the LCD. When the contrast
adjustment is complete, press the SAVE pushbutton. Once the setting is saved, the System
Setup screen displays. To return to the System Setup screen without saving the setting, press
the return arrow pushbutton.
Firmware Versions
The Versions screen provides the firmware version numbers installed on the UPS. Select
VERSIONS from the System Setup Level 0 menu to display the Versions screen. To scroll
through the firmware types, press the up or down arrow pushbutton on the menu bar. To return
to the System Setup screen, press the return arrow pushbutton.
Identification
Password
The Unit Type screen provides the model, CTO, and serial numbers of the UPS unit. Select UNIT
TYPE from the System Setup Level 0 menu to display the Unit Type screen. To return to the
System Setup screen, press the return arrow pushbutton.
System Level 1 Setup
The System Setup Level 1 screen can be used to set the UPS date and time, set the serial ports,
change the Level 1 password, and log out of Level 1. In addition, the Level 0 functions are
available. A password is required to access the Level 1 functions. To enter the password, select
ENTER PASSWORD from the System Setup Level 0 menu to display the Enter Password screen.
Use the left or right arrow pushbutton to select the password character position. Use the up or
down arrow pushbutton to change the password character. Once the password is entered,
press the DONE pushbutton. The System Setup Level 1 menu screen is displayed. The default
password is L1.
Function Selection
Change Password
Use the up or down arrow pushbutton to highlight the setup function screen desired, then press
the SELECT pushbutton to display the function screen. The Level 1 screen times out after
60 minutes or can be logged out at any time by selecting the LOG OUT function from the menu
screen.
The Change Password screen allows the System Setup Level 1 password to be changed. Select
CHANGE PASSWORD from the System Setup Level 1 menu to display the Change Password
screen. Use the left or right arrow pushbutton to select the password character position. Use the
up or down arrow pushbutton to change the password character. Once the new password is
entered, press the DONE pushbutton. The Change Password Save screen is displayed.
Change Password Save
Time Format
The Change Password Save screen lets you save the new password, retry another password, or
abort the password change. Press SAVE, RETRY, or ABORT. If SAVE or ABORT is pressed, the
action is completed, and the System Setup screen displays. If RETRY is pressed, the Change
Password screen is redisplayed.
The Time Format Setup screen allows the selection of either month/day/year or day/month/year
formats for display on the screen and for logging events in the Event and History Logs. Select
DATE AND TIME from the System Setup Level 1 menu to display the Time Format Setup screen.
Use the up or down arrow pushbutton to highlight the desired format, then press the SELECT
pushbutton to display the Set Date and Time screen. To return to the System Setup screen, press
the return arrow pushbutton.
Set Date and Time
MM/DD/YYYY
The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be
set in the month/day/year format. The date and time information is used for display on the screen
and for logging events in the Event and History Logs. Use the left or right arrow pushbutton to
highlight the setting to be changed. Use the up or down arrow pushbutton to make the change.
When finished making changes, use the left or right arrow pushbutton to highlight SAVE and the
up or down arrow pushbutton to select YES. To complete the save function and return to the
System Setup screen, select the return arrow pushbutton.
Set Date and Time
DD/MM/YYYY
The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be
set in the day/month/year format. The date and time information is used for display on the screen
and for logging events in the Event and History Logs. Use the left or right arrow pushbutton to
highlight the setting to be changed. Use the up or down arrow pushbutton to make the change.
When finished making changes, use the left or right arrow pushbutton to highlight SAVE and the
up or down arrow pushbutton to select YES. To complete the save function and return to the
System Setup screen, select the return arrow pushbutton.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−7
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
Function
Subfunction
Operation
Com Port Selection
The Com Port Setup screen allows selection of the serial COM port to set up. Select COM PORT
SETUP from the System Setup Level 1 menu to display the COM Port Setup screen. Use the up or
down arrow pushbutton to highlight the the COM port to be set up, then press the SELECT
pushbutton. To return to the System Setup screen, press the return arrow pushbutton.
Com Port Setup
The COM Setup screen is used to change and save the settings for the selected serial
communication port. The COM port number selected from the COM Port Setup screen displays.
If the changes are not wanted, use the ABORT pushbutton to return to the COM Port Setup
screen. Use the up or down arrow pushbutton to highlight the setting to be changed. Use the
return arrow pushbutton to toggle through the values for the setting to make the change. Press
SAVE or ABORT. Once the action is completed, the COM Port Setup screen is displayed.
Control
See paragraph 7.2.7 for details.
7.2.7
System Status Screen and Controls
Press the CONTROLS pushbutton on the main menu bar to display the System Status
screen. Normal operation, transfer to bypass, charger control, UPM startup and
shutdown and LOAD OFF commands are controlled through this screen. In addition,
the screen displays the current status of the UPS and indicates whether the UPS is in
Maintenance Bypass or Bypass, and the state of the UPM and battery charger.
Use the or pushbutton on the System Status menu bar to highlight the
command screen desired, then press the CONTROLS pushbutton to display the
command menu screen.
UPS operation.
the command menu screens.
SYSTEM STATUS
: SHUTDOWN
: AVAILABLE
UPS
BYPASS
: OFF
: OFF
MAINTENANCE BYPASS
CHARGER
UPM: OFFLINE
CONTROLS
ESC
Figure 7-5. Typical System Status Screen
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−8
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
Table 7-4. Typical System Status Messages
Function
Message
UPS
Shutdown; Bypass; Online
Off; On; Available
Off; On
Bypass
Maintenance Bypass
Charger
Charger Off; Charging
UPM (during startup)
DC Starting, Charger Off; DC Starting, Close Battery
Breaker; Inverter Starting; Inverter Syncing; Ready; Online
UPM 1
UPM 2
Offline; Shutdown, Charger Off; Ready; Ready, Charging;
Online, Charger Off; Online, Charging
UPM 3
UPM 4 (not displayed on three UPM model)
Table 7-5. Command Menu Operation
Function
Subfunction
Operation
UPS Control Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Normal
Go to Bypass
Load Off
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Bypass Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Go to Bypass
Go to Normal
Load Off
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command.
Charger On
Charger Off
Turns the battery charger on.
Turns the battery charger off
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then press the
CONTROLS pushbutton to execute the command.
UPM On
Turns the UPM on without transferring the load to Normal mode. The Load is on bypass.
Transfers the load to bypass and turns the UPM off.
Turns the UPM on and transfers the load to Normal mode.
Turns the battery charger on.
UPM Off
UPM Go to Normal
Charger On
Charger Off
Turns the battery charger off
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−9
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.2.8
Load Off Screen
selected from the main menu bar, the UPS Control Command screen, or the Bypass
Control Command screen. This screen allows the LOAD OFF process to be aborted if
the LOAD OFF pushbutton was pressed accidentally. For Load Off procedures, see
HOLD LOAD OFF BUTTON FOR 3 SECONDS
TO TURN OFF LOAD
CANCEL
LOAD OFF
Figure 7-6. Load Off Screen
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−10
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3
Single UPS Operation
NOTE A Field Installed UPM (FI−UPM) is always designated as UPM 4.
7.3.1
Starting the UPS in Normal Mode
To start the UPS system:
1. If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
2. Close the UPS input feeder circuit breaker.
3. Close the UPS Bypass input feeder circuit breaker.
4. Observe the UPS control panel display becoming active, indicating logic power.
5. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
6. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
7. Close the battery breaker.
8. If the UPS contains input breaker CB1, close input breaker CB1.
9. On the System Status screen, select the UPS command.
10. Press the CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
11. On the UPS Control Command screen, select GO TO NORMAL.
12. Press the SELECT pushbutton on the UPS Command menu bar.
If Auto Bypass is enabled (factory default), the critical load is immediately
supplied by the bypass source, in Bypass mode, until the inverter turns on and
the UPS transfers to Normal mode. The status indicator on the UPS control panel
indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS
output remains off until the UPS transfers to Normal mode.
13. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
ONLINE, CHARGING
The rectifier and inverter turn on. The inverter continues to ramp up to full
voltage.
Once the inverter reaches full voltage, the UPS output contactor K3 closes and
the static switch turns off. Power is now supplied to the critical load in Normal
mode. It takes approximately one minute for the UPS to achieve Normal mode.
The NORMAL status indicator is illuminated. The UPS status indicates ONLINE.
The UPM status indicates ONLINE, CHARGING.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−11
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3.2
Starting the UPS in Bypass Mode
If the inverter output of the UPS is not available and the critical load needs to be
energized:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
2. Close the UPS input feeder circuit breaker.
3. Close the UPS Bypass input feeder circuit breaker.
4. Observe the UPS control panel becoming active, indicating logic power.
5. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
6. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
7. If the UPS contains input breaker CB1, close input breaker CB1.
8. On the System Status screen, select the BYPASS command.
9. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
10. On the Bypass Control Command screen, select GO TO BYPASS.
11. Press the SELECT pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source, in Bypass mode.
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The
UPM status indicates SHUTDOWN, CLOSE BATTERY.
7.3.3
Starting the UPMs
To start the power module without transferring the critical load to Normal mode:
1. If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
2. Close the UPS input feeder circuit breaker.
3. Close the UPS Bypass input feeder circuit breaker.
4. Observe the UPS control panel becoming active, indicating logic power.
5. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
6. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
7. If the UPS contains input breaker CB1, close input breaker CB1.
8. On the System Status screen, select the UPM command.
9. On the UPS Control Command screen, select the UPM 1 command.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−12
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
10. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
11. On the UPM 1 Control Command screen, select UPM ON.
12. Press the SELECT pushbutton on the UPM 1 Command menu bar.
13. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 1 rectifier and inverter turn on.
If the Inherent Redundancy option is enabled, a loss of redundancy alarm will be
15. Observe the following messages are displayed sequentially on the
UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 2 rectifier and inverter turn on.
17. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 3 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
19. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 4 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
NOTE To transfer to Normal mode after starting individual UPMs, follow the procedure in paragraph 7.3.5 .
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−13
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3.4
Transfer from Normal to Bypass Mode
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
4. On the Bypass Control Command screen, select GO TO BYPASS.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
The UPS transfers to Bypass mode and the critical load is immediately supplied
by the bypass source. If the bypass source is not available, the power module
remains on and an alarm sounds.
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The
UPM status indicates READY. The power module remains on.
WARNING
Power is present inside the UPS cabinet sections.
7.3.5
Transfer from Bypass to Normal Mode
To transfer the critical load to Normal mode:
1. If not already closed, close the battery breaker.
2. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
3. On the System Status screen, select the UPS command.
4. Press the CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
5. On the UPS Control Command screen, select GO TO NORMAL.
6. Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Normal mode. If the power module is not available, the
system remains on bypass and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates ONLINE.
The UPM status indicates ONLINE.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−14
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3.6
Transfer from Normal to Bypass Mode and Shut Down UPS
To transfer the critical load to Bypass mode and shut down the UPS:
1. Transfer the critical load to bypass by performing the procedure in
2. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
3. On the System Status screen, select the UPM command.
4. On the UPS Control Command screen, select the UPM 1 command.
5. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
6. On the UPM 1 Control Command screen, select UPM OFF.
7. Press the SELECT pushbutton on the UPM 1 Command menu bar.
The UPM status indicates SHUTDOWN. The input, output, and battery contactors
open, and the power module is turned off. The bypass source supplies the critical
load.
WARNING
Power is present inside the UPS cabinet sections.
7.3.7
Single UPM Shutdown
To shutdown a single UPM:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the the UPM Command. The UPS Control
Command screen is displayed.
3. On the UPS Control Command screen, select the the UPM to shutdown.
4. Press the CONTROLS pushbutton on the System Status menu bar. The UPM
Control Command screen is displayed.
5. On the UPM Control Command screen, select UPM OFF.
6. Press the SELECT pushbutton on the UPM Command menu bar.
The UPM status indicates SHUTDOWN. The input, output, and battery contactors
open, and the power module is turned off. The remaining UPMs supply the
critical load.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−15
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3.8
UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load:
1. Turn off all equipment that is being powered by the UPS.
The input, output, battery, and bypass backfeed contactors open, and the power
module is turned off.
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
3. If the UPS contains input breaker CB1, open the UPS input breaker CB1.
4. Open the UPS input and bypass feeder circuit breakers.
7.3.9
Charger Control
To turn the battery charger on:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the CHARGER command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Charger
Control Command screen is displayed.
4. On the Charger Control Command screen, select CHARGER ON.
5. Press the SELECT pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the CHARGER command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Charger
Control Command screen is displayed.
4. On the Charger Control Command screen, select CHARGER OFF.
5. Press the SELECT pushbutton on the Charger Command menu bar.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−16
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.3.10 Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS LOAD OFF controls the UPS output by
powering down the UPS and de-energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the LOAD OFF pushbutton:
1. Press the LOAD OFF pushbutton.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2. To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
To use the LOAD OFF command:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select either the UPS or the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4. On the Control Command screen, select LOAD OFF.
5. Press the SELECT pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−17
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
6. To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
CAUTION
Do not attempt to restart the system after the Load Off until the cause of the shutdown has been identified
and cleared.
7. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
7.3.11 Using the Remote Emergency Power−off Switch
A UPS emergency power−off is initiated by the REPO pushbutton switch. In an
emergency, you can use this switch to control the UPS output. The REPO switch
de-energizes the critical load and powers down the UPS immediately, without asking
for verification.
The UPS, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You should use
this feature only when you want to de-energize the critical load.
NOTE The following instructions are for the Eaton−supplied REPO switch. If a customer−supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions provided with the
switch.
To use the REPO switch:
1. Firmly push the red pushbutton until it locks into place. The switch latches into
The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately, without
asking for verification.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−18
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the
supplied key and rotate clockwise until the red pushbutton releases (see
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
Activated
Pushbutton locked into place
Deactivated
Unlock pushbutton to release
Figure 7-7. REPO Operation
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−19
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.4
Multiple UPS Distributed Bypass Operation
7.4.1
Starting the Distributed Bypass System in Normal Mode
To start the distributed bypass system:
1. If the UPSs contain input breakers (CB1), verify that all input breakers are open.
2. Close all Module Output Breakers (MOBs).
3. Close all UPS input feeder circuit breakers.
4. Close all UPS Bypass input feeder circuit breakers.
5. Observe the UPS control panel displays becoming active, indicating logic power.
6. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System
Status screen is displayed.
7. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
8. Close all battery breakers.
9. If the UPSs contain input breakers (CB1), close all input breakers.
10. On the System Status screen, select the UPS command.
11. Press the CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
12. On the UPS Control Command screen, select GO TO NORMAL.
13. Press the SELECT pushbutton on the UPS Command menu bar.
If Auto Bypass is enabled (factory default), the critical load is immediately
supplied by the bypass source in Bypass mode from all UPSs, until the inverter
turns on and the UPSs transfer to Normal mode. The status indicator on the UPS
control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled,
the UPS outputs remain off until the UPSs transfer to Normal mode.
14. Verify the following messages display sequentially on the UPS status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
ONLINE, CHARGING
The rectifier and inverter turn on. The inverter continues to ramp up to full
voltage.
Once the inverter reaches full voltage, all UPS output contactors (K3) close and
the bypass circuits open. Power is now supplied to the critical load in Normal
mode from all UPSs. It takes approximately one minute for the UPSs to achieve
Normal mode.
The NORMAL status indicator is illuminated. The UPS status indicates ONLINE.
The UPM status indicates ONLINE, CHARGING.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−20
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.4.2
Starting the Distributed Bypass System in Bypass Mode
If the inverter output of the distributed bypass system is not available and the critical
load needs to be energized:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. If the UPSs contain input breakers (CB1), verify that all input breakers are open.
2. Close all MOBs.
3. Close all UPS input feeder circuit breakers.
4. Close all UPS Bypass input feeder circuit breakers.
5. Observe the UPS control panel displays becoming active, indicating logic power.
6. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System
Status screen is displayed.
7. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
8. If the UPSs contain input breakers (CB1), close all input breakers.
9. On the System Status screen, select the BYPASS command.
10. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
11. On the Bypass Control Command screen, select GO TO BYPASS.
12. Press the SELECT pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source in Bypass mode
from all UPSs.
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The
UPM status indicates SHUTDOWN, CLOSE BATTERY.
7.4.3
Starting the UPSs UPMs
To start the power modules without transferring the critical load to Normal mode:
1. If the UPSs contain input breakers (CB1), verify that all input breakers are open.
2. Close all UPS input feeder circuit breakers.
3. Close all UPS Bypass input feeder circuit breakers.
4. Observe the UPS control panel displays becoming active, indicating logic power.
5. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System
Status screen is displayed.
6. On the System Status screen, verify the UPS status is SHUTDOWNand the UPM
status is OFFLINE.
7. If the UPSs contain input breakers (CB1), close all input breakers.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−21
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
8. On the System Status screen, select the UPM command.
9. On the UPS Control Command screen, select the UPM 1 command.
10. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
11. On the UPM 1 Control Command screen, select UPM ON.
12. Press the SELECT pushbutton on the UPM 1 Command menu bar.
13. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 1 rectifier and inverter turn on.
If the Inherent Redundancy option is enabled, a loss of redundancy alarm will be
15. Observe the following messages are displayed sequentially on the
UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 2 rectifier and inverter turn on.
17. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 3 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
19. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 4 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−22
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
NOTE To transfer to Normal mode after starting individual UPMs, follow the procedure in paragraph 7.4.5 .
7.4.4
Transfer from Normal to Bypass Mode
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System
Status screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
4. On the Bypass Control Command screen, select GO TO BYPASS.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
All of the UPSs transfer to Bypass mode and the critical load is immediately
supplied by the bypass source from all UPSs. If the bypass source is not
available, the power module remains on and an alarm sounds.
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The
UPM status indicates READY. The power module remains on.
WARNING
Power is present inside the UPS cabinet sections.
7.4.5
Transfer from Bypass to Normal Mode
To transfer the critical load to Normal mode:
1. If not already closed, close the battery breaker.
2. On any UPS, press the CONTROLS pushbutton on the main menu bar. The System
Status screen is displayed.
3. On the System Status screen, select the UPS command.
4. Press the CONTROLS pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
5. On the UPS Control Command screen, select GO TO NORMAL.
6. Press the SELECT pushbutton on the UPS Command menu bar.
All of the UPSs transfer to Normal mode. If the power module is not available,
the system remains on bypass and an alarm sounds.
The NORMAL status indicator is illuminated. The UPS status indicates ONLINE.
The UPM status indicates ONLINE.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−23
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.4.6
Transfer from Normal to Bypass Mode and Shut Down all UPSs
To transfer the critical load to Bypass mode and shut down all UPSs:
1. Transfer the critical load to bypass by performing the procedure in
2. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
3. On the System Status screen, select the UPM command.
4. On the UPS Control Command screen, select the UPM 1 command.
5. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
6. On the UPM 1 Control Command screen, select UPM OFF.
7. Press the SELECT pushbutton on the UPM 1 Command menu bar.
The UPM status indicates SHUTDOWN. The input, output, and battery contactors
open, and the power module is turned off. The bypass source supplies the critical
load.
WARNING
Power is present inside the UPS cabinet sections.
7.4.7
Single UPM Shutdown
To shutdown a single UPM:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the the UPM Command. The UPS Control
Command screen is displayed.
3. On the UPS Control Command screen, select the the UPM to shutdown.
4. Press the CONTROLS pushbutton on the System Status menu bar. The UPM
Control Command screen is displayed.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−24
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
5. On the UPM Control Command screen, select UPM OFF.
6. Press the SELECT pushbutton on the UPM Command menu bar.
The UPM status indicates SHUTDOWN. The input, output, and battery contactors
open, and the power module is turned off. The remaining UPMs supply the
critical load.
7.4.8
UPS and Critical Load Shutdown
To perform maintenance or service on the critical load, shut down power to the load:
1. Turn off all equipment that is being powered by the distributed bypass system.
The input, output, battery, and bypass backfeed contactors open, and the power
module is turned off.
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
3. If the UPSs contain input breakers (CB1), open all UPS input breakers.
4. Open all of the UPSs input and bypass feeder circuit breakers.
7.4.9
Charger Control
To turn the battery charger on:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the CHARGER command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Charger
Control Command screen is displayed.
4. On the Charger Control Command screen, select CHARGER ON.
5. Press the SELECT pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1. Press the CONTROLS pushbutton on the main menu bar. The System Status
screen is displayed.
2. On the System Status screen, select the CHARGER command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Charger
Control Command screen is displayed.
4. On the Charger Control Command screen, select CHARGER OFF.
5. Press the SELECT pushbutton on the Charger Command menu bar.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−25
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
7.4.10 Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS LOAD OFF controls the UPSs outputs
by powering down the UPS and de-energizing the critical load.
The UPSs (including Bypass) remain off until restarted.
NOTE The UPS Load Off controls each UPS independently and does not shutdown the whole distributed
bypass system. To immediately shutdown the whole system, use the REPO switch (see paragraph 7.4.11).
To use the LOAD OFF pushbutton:
1. Press the LOAD OFF pushbutton on the UPS to shutdown.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2. To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off on the UPSs.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
4. Restart the UPS after pressing the LOAD OFF pushbutton by following the
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
To use the LOAD OFF command:
1. Press the CONTROLS pushbutton on the main menu bar of the UPS to be
shutdown. The System Status screen is displayed.
2. On the System Status screen, select either the UPS or the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4. On the Control Command screen, select LOAD OFF.
5. Press the SELECT pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−26
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
6. To shut down the UPS, press LOAD OFF from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press CANCEL.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off on all UPSs.
7. If another UPS is to be shutdown, proceed to that UPS and repeat
CAUTION
Do not attempt to restart the system after the Load Off until the cause of the shutdown has been identified
and cleared.
8. Restart the UPS after pressing the LOAD OFF pushbutton by following the
WARNING
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
7.4.11 Using the Remote Emergency Power−off Switch
A UPS emergency power−off is initiated by the REPO pushbutton switch. In an
emergency, you can use this switch to control the UPS output. The REPO switch
de-energizes the critical load and powers down the UPSs immediately, without asking
for verification.
The UPS, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You should use
this feature only when you want to de-energize the critical load.
NOTE The following instructions are for the Eaton−supplied REPO switch. If a customer−supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions provided with the
switch.
To use the REPO switch:
1. Firmly push the red pushbutton until it locks into place. The switch latches into
The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately, without
asking for verification on all UPSs.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−27
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS OPERATING INSTRUCTIONS
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the
supplied key and rotate clockwise until the red pushbutton releases (see
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
7−28
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 8Table 8
Chapter 8
Communication
This chapter describes the communication features of the Powerware 9395 UPS and
provides information about connecting hardware and using Terminal mode. For
page 4−26. For location of the customer interface panels and terminals see
8.1
X−Slot Cards
The Powerware 9395 UPS has four standard, factory-installed X−Slot communication
bays. See Figure 4-22 on page 4−27 for bay locations. The UPS is compatible with the
S Modbus Card – provides direct integration of UPS information (meters and status)
to a Building Management System (BMS) using the Modbus RTU protocol.
S ConnectUPS−X Web/SNMP Card – provides remote monitoring through a Web
browser interface, e-mail, and a network management system (NMS) using SNMP;
connects to a twisted-pair Ethernet (10/100BaseT) network. It has a built−in
switching hub that allows three additional network devices to be connected to the
network without the requirement of additional network drops.
NOTE The Modem Card cannot be installed in X−Slot 2.
S Modem Card – provides ꢀout-of-band" remote notification and monitoring using
modem communication directly to cell phones and pagers.
S Relay Interface Card (AS/400) – has isolated dry contact (Form−C) relay outputs for
UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass when
interfacing with IBM AS/400 computers, other relay connected computers, and
industrial applications.
S Industrial Relay Card (IRC) – indicates the operating status of the UPS system
using the customer’s monitoring equipment. The IRC uses four isolated
normally−open or normally−closed dry relay contacts to indicate the UPS status.
Normal, Bypass, Battery, and Alarm modes can be monitored.
S Powerware Hot Sync CAN Bridge Card – provides connectivity for operational
mode control and metering of a parallel system at any UPM in the system. In
addition, this card can be used to connect optional system monitoring devices,
such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or
a Supervisory Contact Module II (SCM II) to the UPS.
®
S Power Xpert Gateway Card – provides a data gateway from the UPS to the Power
Xpert software; provides remote monitoring through a Web browser interface,
e−mail, and a network management system using SNMP; connects to a
twisted−pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the PDU’s parameters to a Building Management System (BMS). It
has a built−in switching hub that allows one additional network device to be
connected to the network without the requirement of an additional network drop.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−1
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
LAN and telephone drops for use with X−Slot connectivity cards must be provided by
facility planners or the customer.
For installation and setup of an X−Slot card, contact an Eaton service representative
(see page 1−8). Refer to the manual supplied with the X−Slot card for user instructions.
ConnectUPS−X Web/SNMP Card
Modbus Card
Modem Card
Powerware Hot Sync
CAN Bridge Card
Relay Interface Card
Industrial Relay Card
Power Xpert Gateway Card
Figure 8-1. Optional X−Slot Cards
8.2
eNotify Service
The Powerware 9395 UPS supports Eaton’s eNotify Service. eNotify Service is
included at no charge during the first year of operation (warranty period), and also
with the purchase of an Eaton PowerTrust Support Agreement after the initial
warranty expires. eNotify and support agreement availability or specific features may
vary by market; for more information, refer to: www.powerware.com/enotify/.
8.2.1
eNotify Service Features
The eNotify Service provides proactive monitoring and a monthly report detailing the
ongoing health of your Powerware 9395 UPS:
S Proactive monitoring, called Anomaly Detection, automatically analyzes the status
of the Powerware 9395 UPS on a daily basis. All data gathered from the unit,
current and historical, is analyzed at the Customer Reliability Center (CRC) for
trending issues. A set of factors, or rules, compared against your UPS’s data can
indicate a potential impending failure and trigger an appropriate anomaly
notification to a CRC Analyst. Critical events are checked for additional anomalies.
Through this service, the CRC can take pre−emptive, corrective action to ensure
the highest level of availability of your Powerware 9395 UPS.
S The Customer Monitoring Report delivers information about Eaton’s analysis of
your Powerware 9395 UPS on a monthly basis. Depending on the model, the
report provides detailed information about voltages, loads, external factors such as
temperature and humidity, the attached batteries, and system availability. All of
these factors contribute to the Relative Health Index (RHI) score that allows you to
compare your unit’s health relative to Eaton’s optimum Powerware UPS operating
levels.
8.2.2
Installing eNotify Service
A quick start guide and self−installation wizard tool are available on both the Software
Suite CD included with the Powerware 9395 UPS documentation and on the Web at:
www.powerware.com/enotify/. For the latest updates, installation tips, and
information on connecting eNotify, visit the eNotify Web page. For installation support
or questions about the eNotify Service, contact crctriagegroup@eaton.com.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−2
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
The eNotify Service relies on a ConnectUPS−X Web/SNMP Card (or Power Xpert card)
installed with the UPS sending one−way status and event e−mails to Powerware
Remote Monitoring servers that analyze and store the data. Those servers also take
the appropriate actions of sending notifications and reports. The ConnectUPS Card
gathers information from the UPS directly and from any external sensors that are
attached. The card also records all events that are generated by the UPS. This data is
stored within the non−volatile memory logs on the ConnectUPS Card.
The eNotify Service runs on common protocols and transport mechanisms, making
the connectivity between the Powerware 9395 UPS and the Powerware Remote
Monitoring servers easy to set up. By using common e−mail transport mechanism,
you do not have to open your network to proprietary or potentially unsecure protocols
and transports.
8.3
Powerware LanSafe Power Management Software
Each Powerware 9395 UPS ships with LanSafe Power Management Software. To
install the Powerware LanSafe software, see the instructions accompanying the
Software Suite CD.
Powerware LanSafe software uses an RS−232 serial link to communicate with the
UPS. The software provides up−to−date graphics of UPS power and system data and
power flow, a complete record of critical power events, and notification of important
UPS or power information. With custom views for monitoring status and metering
information, various user groups can select the most useful view for their specific
needs.
8.4
Remote Notification
For connection and setup of a modem, or to enable Remote Notify and Call Home
Remote Notification allows the UPS to use a standard off-the-shelf PC modem as a
telephone interface. The features provided by this option are:
S Call to a remote terminal or pager based on programmable events and alarms
S Four separate, programmable notification groups (phone numbers)
S Automatic answering (user−configurable) for access to the Terminal mode of
the UPS
S Remote and local ability to clear Call Out alarms and events
S Error detection and correction for misconfigured and disconnected modems.
Remote Notification provides the user with the option of receiving alarms and notices
at a remote location. Using the Terminal mode, the user calls the UPS to perform
basic monitoring. In the event of a UPS alarm or notice, the user is notified at the
remote location. The UPS calls through the modem to the user’s computer or pager
and leaves a message.
Remote Notification is an extension of the Terminal mode with the additional support
algorithms necessary to control an external modem. Connection to the UPS is made
when a user calls the UPS on the phone. The user has exactly the same capabilities
as if using a terminal connected directly to an RS−232 port.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−3
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
Remote Notification differs from the basic Terminal mode with the addition the
following functions:
S Call Answer
The Call Answer function allows the user to call into the UPS from a remote
location and enter Terminal mode.
S Call Out
The Call Out function allows the UPS to be configured to call either a remote
computer or numeric paging service over the phone line. Call Out allows the UPS
to call a remote computer and leave a one-line descriptive message of the alarm or
notice condition. Numeric paging support allows the UPS to call a paging service
and send numeric messages.
S Housekeeping
The Housekeeping function maintains the link between the UPS and modem.
8.5
Terminal Mode
In Terminal mode, the user can request the following functions:
NOTE The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key
combination, hold down the Escape key and press the indicated letter key.
S [ESC] [A] displays the Active Alarms.
S [ESC] [H] displays the Event History.
S [ESC] [N] displays the Node Bits Setup.
S [ESC] [Q] Quit.
8.5.1
Display UPS Control Panel
When this function is invoked, a facsimile of the UPS control panel is displayed on the
terminal screen. All controls are functional and can control the UPS remotely. The only
exception is the Load Off control which requires the operator to press and hold the
local control for two seconds to shut down the UPS.
To remotely control the UPS or view UPS information, use the Escape key legend to
control the function normally controlled by the control panel softkeys. See
paragraph 7.2 on page 7−2, ꢀUsing the Control Panel," for instructions on navigating
the control panel.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−4
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
8.5.2
Event History Log
This key sequence prints the entire Event History Log of the UPS at the time the data
is requested. The printout begins with the oldest alarm entry in the queue and ends
with the most recent. Any alarms that occur while the Event History Log is printing
are included in chronological order.
The Event History Log lists up to 500 system events in chronological order with the
In this mode, system events are continually logged through the serial port to the
device connected to the port.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
MM DD YYYY HH:MM:SS.hh KYWD MESSAGE <CR> <LF>
Where
MM
Equals
Month (2 digits)
DD
Day (2 digits)
YYYY
HH
Year (4 digits)
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hh
Hundredths of Second (3 digits)
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
System Diagnostic Information
Carriage Return Character (ASCII 13)
Line Feed (ASCII 10)
KYWD
Message
<CR>
<LF>
An alarm message is prefixed by the word ꢀCLEAR" whenever an alarm is entered
into the Event History Log with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can press
[Esc] [H] to print the entire log with a firmware version header. The log in Terminal
mode is always in English.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−5
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
MODEL: POWERWARE 9395
CTO: TF12710000000
SERIAL:
MCU DSP:
70.81.14
MCU BOOTLOADER:
80.40
MCU PLD:
1.00
PMF 1 DSP:
80.81.14
PMF 1 BOOTLOADER:
PMF 1 PLD: 1.00
XSLOT CAN BRIDGE:
80.40
0.00
1.12
CSB DSP:
70.81.14
CSB BOOTLOADER:
DISPLAY:
1.06
TIME: 19:17:16 DATE: 03/23/2099
03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)
03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)
03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)
03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)
03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)
03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)
03/16/2099 21:25:25.850 N011: OUTPUT UNDER OR OVER FREQ OK (PM1)
...
03/23/2099 18:59:20.225 A199: BATTERIES DISCONNECTED (PM1)
ACTIVE ALARMS:
11 NOTICE: OUTPUT UNDER OR OVER FREQ (PM1)
12 ALARM: REMOTE EMERGENCY POWER OFF (MCU)
102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1)
103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1)
104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1)
Figure 8-2. Sample Event History Log
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−6
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
8.6
8.7
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as
smoke detectors or overtemperature alarms. The customer interface terminals for
external connections are located inside the UPS. You should use twisted−pair wires
for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
General Purpose Relay Contact
One general purpose relay contact is provided as a standard feature on the UPS. The
alarm contact is located inside the UPS on the customer interface terminal board.
You can use a normally−closed or normally−open contact. If the state of the contact
changes from the state you specify as normal, a signal is issued. You can connect this
contact to equipment at your facility (such as a light or an alarm bell) to let you know
when an alarm is active on the UPS. This feature is useful if the UPS is located in a
remote area where the UPS horn may not be heard immediately.
CAUTION
Contacts should not be operated in excess of 30 Vac @ 5A maximum.
8.8
Remote Monitor Panel II
As an option, an Remote Monitor Panel II (RMP II) can be installed to monitor the
operation of the UPS system from virtually any location within the facility, up to
150m (500 ft) from the UPS. The RMP II contains backlit status indicators and a local
horn. The RMP II can be flush-mounted or surface-mounted on a desktop, or secured
Figure 8-3. Remote Monitor Panel II Front Panel
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−7
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
Table 8-1. RMP II Status Indicators
SYSTEM NORMAL
The UPS is energized (either with utility power or battery backup) and is
supplying conditioned power to the critical load.
NO REDUNDANCY
This indicator applies only to parallel systems when one cabinet is not
functioning.
ON GENERATOR
The UPS input and bypass are being supplied by the power from the
generator instead of from the utility power.
ON BYPASS
The bypass source is supplying the critical load. Usually this means that
the UPS is not energized. The load is not protected in Bypass mode, and a
horn sounds after 30 seconds.
UPS ALARM
The UPS system is issuing an alarm. Conditions that affect the current UPS
mode are indicated by the indicators and horn on the UPS.
ON BATTERY
The UPS battery backup is supplying the critical load. The utility power is
either interrupted or out of specification. The SYSTEM NORMAL indicator
is also illuminated.
BYPASS UNAVAILABLE
The UPS system is in Normal mode, but a bypass source is not within
specification. A horn sounds after 30 seconds.
SHUTDOWN IMMINENT
The UPS is preparing to shut down because the UPS is in Battery mode
and the DC voltage is approaching its low limit. This indicator is
accompanied by a horn.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−8
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
8.9
Relay Interface Module II
An optional Relay Interface Module II (RIM II) uses relay contact closures to indicate
the operating status and alarm condition of the UPS system. The module uses a serial
interface line and may support up to eight critical loads. The RIM II can be
shows the RIM II with its four 15-pin connectors labeled J1 through J4.
Figure 8-4. Relay Interface Module II Customer Interface Connectors J1 through J4
Table 8-2. Customer Interface Connectors
Status
J1 through J4
Description
UPS AVAILABLE
Pins 1 and 12
Contacts are closed when the UPS is operating in Normal mode
or ready to supply the load.
UPS OFFLINE
Pins 3 and 13
Pins 5 and 14
Pins 6 and 15
Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode.
BATTERY WEAK
UTILITY FAILURE
Contacts are closed when approximately two minutes of battery
time is remaining before the critical load is lost.
Contacts are closed when Utility Failure is detected.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−9
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATION
8.10 Supervisory Contact Module II
An optional Supervisory Contact Module II (SCM II) establishes an interface between
the UPS system and the customer’s monitor. This interface allows the customer to
monitor operational status of the UPS system equipment. The SCM II can be
shows the SCM II.
Figure 8-5. Supervisory Contact Module II Enclosure
Table 8-3. SCM II Status Indicators and Connections
Indication
TB2 Connections
SYSTEM NORMAL
NO REDUNDANCY
ON GENERATOR
BYPASS NOT AVAILABLE
ON BATTERY
TB2-1 through TB2-3
TB2-4 through TB2-6
TB2-7 through TB2-9
TB2-10 through TB2-12
TB2-13 through TB2-15
TB2-16 through TB2-18
TB2-19 through TB2-21
TB2-22 through TB2-24
UPS ALARM
ON BYPASS
SHUTDOWN IMMINENT
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
8−10
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 9Table 9
Chapter 9
UPS Maintenance
The components inside the UPS cabinet are secured to a sturdy metal frame.
All repairable parts and assemblies are located for easy removal, with very little
disassembly. This design allows authorized service personnel to perform routine
maintenance and servicing quickly.
You must schedule periodic performance checks of your UPS system to keep it
running properly. Regular routine checks of operation and system parameters enable
your system to function efficiently for many trouble-free years.
9.1
Important Safety Instructions
Remember that your UPS system is designed to supply power EVEN WHEN
DISCONNECTED FROM THE UTILITY POWER. The UPS module interiors are unsafe until
the DC power source is disconnected and the electrolytic capacitors are discharged.
After disconnecting the utility power and the DC power, authorized service personnel
should wait at least five minutes for capacitor bleedoff before attempting internal
access to the UPS module.
WARNING
Servicing and maintenance should be performed by qualified service personnel only.
S
S
LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open or protective
panels removed. Do not make any assumptions about the electrical state of any cabinet in the UPS
system.
Because each battery string is an energy source in itself, opening the battery circuit
breaker does not de-energize the voltage within the battery string. DO NOT ATTEMPT
TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE
ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs
service, contact an Eaton service representative.
If the string requires service, refer to the battery manufacturer’s operating manual for
instructions on battery maintenance or contact an Eaton service representative.
Observe these precautions when working on or around batteries:
S Remove watches, rings, or other metal objects.
S Use tools with insulated handles.
S Wear rubber gloves and boots.
S Do not lay tools or metal parts on top of batteries.
S Disconnect the charging source prior to connecting or disconnecting terminals.
S Determine if the battery is inadvertently grounded. If it is, remove the source of the
ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock is reduced if such grounds are removed during
installation and maintenance.
S When replacing batteries, use the same number of sealed, lead-acid batteries.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−1
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS MAINTENANCE
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Do not dispose of batteries in a fire. Batteries may explode when exposed to
flame.
S Do not open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
9.2
Performing Preventive Maintenance
The UPS system requires very little preventive maintenance. However, the system
should be inspected periodically to verify that the units are operating normally and
that the batteries are in good condition.
9.2.1
DAILY Maintenance
Perform the following steps daily:
1. Check the area surrounding the UPS system. Ensure the area is not cluttered,
allowing free access to the unit.
2. Ensure the air intakes (vents on the front door or panels) and the exhaust
openings (on top of the UPM section) are not blocked.
3. Ensure the operating environment is within the parameters specified in
4. Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an
alarm lamp is illuminated or the Normal status indicator is not illuminated, contact
an Eaton service representative.
9.2.2
MONTHLY Maintenance
Perform the following steps monthly:
2. Check the UPS air filters (located behind the front panels) and wash or replace as
filter sizes are 12" 20" 0.25" and the UPM section filter sizes are
20" 44" 0.25". Contact an Eaton service representative for replacement filters.
To remove the filters:
a. Remove one top screw and two bottom screws securing each UPM section
it from the panel hanger bracket at the top of the cabinet.
b. Remove one top screw and two bottom screws securing each ISBM section
it from the panel hanger bracket at the top of the cabinet.
c. Pull the foam filters over the screw heads on the cabinet mounted studs and
remove the filters from the cabinet.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−2
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS MAINTENANCE
ISBM Air Filters
Figure 9-1. ISBM Section Air Filter Locations
CAUTION
Verify washed filters are thoroughly dry before reinstalling.
d. Push the washed or new foam filters over the screw heads on the cabinet
mounted studs until seated against the cabinet.
the retained hardware.
the retained hardware.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−3
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS MAINTENANCE
UPM Air Filters
Figure 9-2. UPM Section Air Filter Locations
3. If the UPS is a four UPM model, check the Field Installed UPM (FI−UPM) air filter
for the filter location. The FI−UPM filter size is 20" 44" 0.25". Contact an Eaton
service representative for replacement filter. To remove the filter:
a. Remove one top screw and two bottom screws securing the FI−UPM front
panel (refer to the Powerware 9395 Field Installed UPM Mechanical
Installation Manual). Lift the panel straight up to remove it from the panel
hanger bracket at the top of the cabinet.
b. Pull the foam filter over the screw heads on the cabinet mounted studs and
remove the filter from the cabinet.
CAUTION
Verify washed filter is thoroughly dry before reinstalling.
c. Push the washed or new foam filter over the screw heads on the cabinet
mounted studs until seated against the cabinet.
retained hardware.
4. Record maintenance results and any corrective actions in a suitable log.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−4
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS MAINTENANCE
FI−UPM Air Filter
Figure 9-3. FI−UPM Air Filter Location
9.2.3
9.2.4
PERIODIC Maintenance
Periodic inspections of the UPS should be made to determine if components, wiring,
and connections exhibit evidence of overheating. Particular attention should be given
to bolted connections. Maintenance procedures should specify that the bolted
connections be retorqued to values listed in this manual.
ANNUAL Maintenance
Annual preventive maintenance should be performed only by authorized service
personnel familiar with maintenance and servicing of the UPS system. Contact an
Eaton service representative for more information about service offerings.
9.2.5
BATTERY Maintenance
Contact an Eaton service representative for battery maintenance. Battery replacement
and maintenance should be performed only by authorized service personnel.
9.3
Installing Batteries
NOTE There is no manual DC disconnect device within the UPS.
Install batteries in accordance with the battery and battery system manufacturer’s
instructions.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−5
Download from Www.Somanuals.com. All Manuals Search And Download.
UPS MAINTENANCE
9.4
Recycling the Used Battery or UPS
Contact your local recycling or hazardous waste center for information on proper
disposal of the used battery or UPS.
WARNING
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is
required. Refer to your local codes for disposal requirements.
S
S
S
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
A battery can cause electrical shock, burn from high short-circuit current, or fire. Observe proper
precautions.
ATTENTION!
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre les
précautions qui s’imposent.
S
S
S
Pour le remplacement, utiliser le même nombre et modéle des batteries.
L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries
and must be disposed of properly. For more information, contact your local recycling/reuse or hazardous
waste center.
CAUTION
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your
local recycling/reuse or hazardous waste center.
9.5
Maintenance Training
A basic training course, available from Eaton Corporation, gives you a competent
working knowledge of the UPS system operation and teaches you how to perform
first level corrective maintenance. For more information about training and other
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
9−6
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 10Table 10
Chapter 10
Product Specifications
10.1 Model Numbers
The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.
Models
Power Rating
1000 kVA
1100 kVA
650 kVA
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Powerware 9395−1100/1000 (four UPM)
Powerware 9395−1100/1100 (four UPM)
Powerware 9395−1100/650 (three UPM)
Powerware 9395−1100/750 (three UPM)
Powerware 9395−1100/825 (three UPM)
750 kVA
825 kVA
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2 Specifications
10.2.1 UPS Input
Operating Input Voltage
480 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current
models.
models.
Reduced for Generator
Adjustable
Input Current Harmonic Content
Power Factor
5% THD at full load
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
480 Vdc
Battery Voltage
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
10−1
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT SPECIFICATIONS
10.2.2 UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
"1% (10% to 100% load)
Output Voltage Adjustment
(Nominal +/–3%)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content 1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
models.
models.
Output Voltage Balance
3% for 100% maximum load imbalance (linear load)
3° for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
Output Transients
"5% (10% to 100% load)
"0.1 Hz free running
+10% to −10% "3%
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
1 Hz per second maximum
0.9 pF Leading
0.8 pF Lagging
Overload Capability
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
10.2.3 UPS Environmental
Operating Temperature
0 to 40°C (32 to 104°F) without derating. The recommended
operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self-discharge)
Relative Humidity (operating and 5% to 95% maximum noncondensing
storage)
Acoustical Noise
EMI Suppression
76 dB at a 1m distance, A weighted
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse
without damage and with no disturbance or adverse effect to the
critical load.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
10−2
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
®
LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE UPS PRODUCTS
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, a Delaware Corporation (ꢀEaton").
LIMITED WARRANTY: This limited warranty (this ꢀWarranty") applies only to the original end−user (the ꢀEnd−User") of the Powerware Three−Phase UPS
Products (the ꢀProduct") and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Eaton for resale to an
End−User.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in the fifty (50) United States and the
District of Columbia is twelve (12) months from the date of Product start−up or eighteen (18) months from the date of Product shipment, whichever occurs
first, for parts coverage and 90 days from the date of Product start−up for labor coverage. The period covered by this Warranty for Product installed [and
currently located] outside of the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product start−up or eighteen (18)
months from the date of Product shipment, whichever occurs first, for parts coverage.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Powerware three−phase UPS electronics, Eaton−built accessories, and
Powerware−built battery cabinets (individually and collectively, the "Warranted Items") are free from defects in material and workmanship. If, in the
opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton’s sole obligation will be to repair or replace such
defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton. The Warranted Item will be repaired or replaced
onsite at the End−User’s location or such other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. All parts
replaced by Eaton shall become the property of Eaton.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store
the Product before installation, including the "trickle charge" of batteries no later than the date indicated on the packaging; (b) shipping and delivery of
the Product if shipping is FOB Factory; (c) neglect, accident, fire, flood, lightning, vandalism, acts of God, Customer’s neglect, abuse, misuse,
misapplication, incorrect installation; (d) repair or alteration not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer
Service Engineer or Agent; or (e) improper testing, operation, maintenance, adjustment, or any modification of any kind not authorized in writing by Eaton
personnel or performed by an authorized Eaton Customer Service Engineer or Agent.
This Warranty is not valid: (a) unless an authorized Eaton Customer Service Engineer (in the USA) or Agent (outside of the USA) performs startup and
commissioning of the Product; (b) if the Product is moved to a new location by someone other than an authorized Eaton Customer Service Engineer (in the
USA) or Agent (outside of the USA); or (c) if the Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced
pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof. Labor warranty is not
provided for Product located outside of the fifty (50) United States or the District of Columbia. Any equipment, parts, or materials included in the
Product and not manufactured by Eaton are warranted solely by the manufacturer of such equipment, parts, or materials and are not included as
part of this Warranty. Batteries are not warranted by Eaton.
THIS WARRANTY IS THE END−USER’S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER EXPRESSED OR IMPLIED
GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE
EXPRESSLY DISCLAIMED).
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special, or consequential damages of any kind or type
whatsoever, or based on any claim or cause of action, however denominated. Eaton shall not be responsible for failure to provide service or parts due to
causes beyond Eaton’s reasonable control. In no case will Eaton’s liability under this Warranty exceed the replacement value of the Warranted Items.
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product in a normal way, follow the Product’s
installation, operation and maintenance manual, and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Eaton’s obligations under this Warranty are expressly conditioned upon receipt by Eaton of all payments due to it (including
interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance with the contract
terms under which the Product is sold, Eaton shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall
continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this
Warranty, including without limitation site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement
equipment, installation, materials, freight charges, travel expenses, or labor of Eaton representatives outside the terms of this Warranty will be borne by
the End−User.
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800−843−9433. Outside of the USA, call your local Eaton
sales or service representative, or call the Eaton Customer Reliability Center in the USA at 919−870−3028. For comments or questions about this Limited
Factory Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
W−1
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
This page intentionally left blank.
EATON Powerware® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com
W−2
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
*1642017641*
164201764 1
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Peavey Stereo Amplifier PV 1500 User Manual
Perle Systems Network Card 5500152 23 User Manual
Philips Projector SV20 Impact User Manual
Pioneer GPS Receiver AVIC F700BT User Manual
Pioneer Stereo System VSX 36TX User Manual
Polaroid Projector PV330 User Manual
Polycom Webcam 3725 22724 003 A User Manual
Poulan Tiller 172498 User Manual
Pride Mobility Mobility Aid Jazzy 1650 2EHD User Manual
PYLE Audio Car Video System PLVW1045R User Manual