Powerware Network Card SOLA 4000 User Manual

Uninterruptible Power Supply  
SOLA 4000  
OPERATING MANUAL  
JUE 401263  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Manual  
Safety Instructions  
SAFETY INSTRUCTIONS  
The unit must be used as intended. Follow the instructions given in  
the Operating Manual.  
Dangerous voltages are present inside the unit.  
Installation and use of this equipment must comply to all national  
and local regulations and procedures.  
To prevent overheating do not obstruct the flow of air for ventila-  
tion openings to the unit.  
The components inside the unit are not repairable by the user. The  
user must not open the UPS cabinet or auxiliary cabinets or re-  
move any protective covers from inside the UPS cabinet.  
This equipment must be installed and serviced by qualified person-  
nel.  
The unit contains Lead-Acid batteries which must be disposed of  
correctly, in compliance with the local regulations.  
To completely isolate the equipment, the switches IRP, IRE,  
IBY,IUG and IB must be switched off, the input supply and the  
battery supply must be isolated from the UPS and the output  
isolated from other modules if the unit is part of a multi-module  
system. For 10-30kVA units with an internal battery, intermediate  
links must be removed in order to isolate the battery in sections of  
a safe working voltage.  
High leakage current: connect protective earth before power  
supply cables.  
JUE 401263  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Manual  
Safety Instructions  
Earth leakage protection: this device has a high leakage current  
towards protective earthing. The maximum earth leakage current is  
300 mA. When setting the threshold of the earth leakage circuit  
breaker installed upstream from this equipment consider this  
amount of current and that due to the loads.  
All primary power switches installed downstream of the UPS must  
be labelled as follows: "Isolate UPS (Uninterruptible Power Supply)  
before working on this circuit.  
The unit is provided with the E.P.O. (Emergency Power Off)  
function. This function is activated by pressing simultaneously the  
two push buttons on the bottom part of the Front Panel. This  
function provides UPS disconnection from the load and from the  
battery. Dangerous voltages will still be present inside the unit, if a  
shunt-trip of the input supply switch is not provided for.  
During electrolysis, batteries release hydrogen gas. There is a risk  
of an explosion if the amount of hydrogen in the battery room  
becomes too high. Ensure appropriate ventilation of the battery  
room according to the standard EN50091-1, to prevent the risk of  
an explosion.  
JUE 401263  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401264  
SOLA 4000 - General System Description  
Chapters  
Figures  
1
UPS ASSEMBLY  
2
1.1 Features  
2
3
3
4
4
4
6
6
7
7
FIG. 1.1 UPS Block-Diagram  
3
3
3
4
4
1.2 UPS System Structure  
1.3 Rectifier/Battery Charger  
1.4 Battery (Accumulator)  
1.5 Inverter  
FIG. 1.2 Rectifier Block-Diagram  
FIG. 1.3 12-Pulse Rectifier Block-Diagram  
FIG. 1.4 Inverter Block-Diagram  
FIG. 1.5 Static Switches Block-Diagram  
1.6 Static Switches  
FIG. 1.6 Maintenance Bypass Block-Diagram 6  
1.7 Maintenance Bypass  
1.8 Hot-Standby Systems  
1.9 Parallel-Redundant Systems  
1.10 Parallel Systems  
FIG. 1.6.1 Wall-mounted Maintenance Bypass  
Block-Diagram  
6
FIG. 1.7 Hot-Standby Operation Block-Diagram  
6
FIG. 1.8 Parallel Operation Block-Diagram  
FIG. 2.1 SOLA 4000 Operating Panel  
7
8
2
OPERATING PANEL  
2.1 Functional Description  
2.2 Remote Monitoring  
8
8
8
8
2.3 Emergency Power Off  
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
04.02.97  
20.06.97  
ISSUED  
See Rev. Doc. JSE401440  
M. Porpora  
T. Boon  
04.02.97  
A4  
1
8
A
T. Boon  
JUE 401264  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
1
UPS ASSEMBLY  
1.1 Features  
CE This equipment complies to the essential requirements of Euro-  
pean Directives 89/336/EEC and 73/23/EEC, and complies to  
EN50091-2 (1995) and EN50091-1 (1991) standards.  
UPS Function The uninterruptible power supply (UPS) is connected between the  
consumer's critical equipment (the load) and supply mains. Its  
function is to guarantee a continuous and conditioned power supply  
to the load. Even in the case of a total blackout it will supply the  
load for a predetermined time (autonomy time). In addition, the  
UPS provides the following advantages in comparison with conven-  
tional supply systems (mains, motor generator sets, etc.):  
Better Output Power Characteristics The UPS output voltage control of frequency and amplitude guar-  
antees consistent and stabilised output power. Mains voltage  
fluctuations and frequency changes that are usually present in  
electricity supply systems do not affect the UPS output voltage.  
Uncoupling from Mains Distortion By using double energy conversion from ac to dc and back to ac  
and using an isolation transformer in the inverter output, all mains  
distortions are filtered out. Therefore, all loads connected to the  
UPS system are protected against mains disturbances that can be  
present in industrial electricity supply systems. This is especially  
important for sensitive electronic devices, e.g. computer systems,  
control systems, medical equipment.  
During long term or short term ac mains supply interruption, the  
UPS system guarantees continuous supply to the connected loads  
by means of a battery. The battery is connected to the rectifier  
output and the inverter input of the UPS system. In normal opera-  
tion the inverter (which feeds the load) is fed by the rectifier. In  
case of a mains failure, the connected battery automatically feeds  
the inverter. Thus the load is supplied without interruption. How-  
ever, the load can only be supplied by the battery for a certain time  
(autonomy time, see chapter 1.4 "Battery"). If longer autonomy  
times are required, we recommend the use of a Diesel Generator  
Set. In this case the battery autonomy time only has to be sufficient  
for the time span between mains failure and full operating capacity  
of the Diesel-Generator-Set.  
Complete Protection against  
Mains Failures  
This is a class A product.  
In a domestic environment, this product may cause radio  
interference, in which case, the user may be required to take  
additional measures.  
JUE 401264  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
1.2 UPS System Structure  
The basic SOLA 4000 power supply unit is an ac/dc/ac converter;  
the block diagram: Figure 1.1 illustrates six essential functional  
components:  
• Rectifier/battery charger (6 pulse) (RECT.)  
• Battery (BATT.)  
• Inverter (INV.)  
• Static inverter switch (SSI)  
• Static bypass (SSB)  
• Maintenance bypass (IBY)  
All components are located in a single housing. They are explained  
in detail on the following pages.The control electronics of the  
rectifier, inverter and static bypass sections are completely inde-  
pendent of each other. i.e. a failure in any one section will not  
cause a failure in another section.  
1.3 Rectifier/Battery Charger  
In the standard configuration the charger is a three phase/6 pulse  
rectifier that converts ac voltage to dc voltage. No isolation trans-  
former is used and the rectifier is connected to the mains via the  
commutation chokes which reduce the mains distortion created by  
the rectifier. The dc output of the rectifier feeds the inverter and the  
battery. The battery is connected to the rectifier through a satura-  
tion choke which reduces ac ripple current to the battery, thus  
ensuring the maximum battery life-time.  
The rectifier is designed to feed both the inverter at maximum load  
conditions and simultaneously the battery with maximum charging  
current. Normally, the battery voltage is constantly regulated at 432  
V dc (floating charge, maintenance-free lead battery, 2.25 volts per  
cell). The rectifier's recharge characteristic is of the I/U type. This  
means that the recharging current limitation is accomplished by  
reduction of the dc voltage, thus assuring that the batteries will not  
be damaged by excessive charging currents.  
A 12-pulse rectifier is optional and requires the addition of a sec-  
ond rectifier bridge inside the UPS cabinet and a phase shifting  
transformer in a separate cabinet.  
FIG. 1.3 - 12-pulse Rectifier Block-Diagram  
JUE 401264  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
1.4 Battery (Accumulator)  
The battery supplies power in case of a short interruption or a total  
breakdown of the ac mains supply. In case of a rectifier failure (no  
dc voltage output), the load will be fed by the battery.  
The battery is only capable of feeding the load for a certain time  
(autonomy time), depending on battery capacity and actual load.  
The number of cells within the battery depends on the battery type  
and may also vary due to specific customer requirements. The  
standard number is 192 cells for lead-acid batteries and 300 cells  
for NiCd batteries. The battery capacity (Ah) depends on the UPS  
output power and the required autonomy time. The battery of 10-  
30kVA units is installed inside the UPS cabinet as standard. For  
40-120kVA units (or 10-30kVA units with extended battery au-  
tonomy), batteries are installed in external battery cabinets.  
1.5 Inverter  
The inverter converts dc voltage supplied by the rectifier or battery  
to ac voltage of a precisely stabilised amplitude and frequency that  
is suitable for power supply to most sophisticated electrical equip-  
ment.  
The inverter output voltage is generated by sinusoidal pulse width  
modulation (PWM). The use of a high carrier frequency for the  
PWM and a dedicated ac filter circuit consisting of the transformer  
and capacitors, ensure a very low distortion of the output voltage  
(THD<1% on linear loads).  
Every phase voltage of the inverter output is controlled separately,  
thus ensuring constant and equal UPS output voltages even with  
highly unbalanced loads.  
The inverter is designed specifically for the application of today's  
loads i.e. The output harmonic distortion will be maintained at low  
levels due to a unique adaptive correction technique, even with the  
application of highly distorted loads.  
The inverter control logic restricts the maximum output current to  
150% of the nominal current in case of a short circuit. In case of  
overload (up to 125% of the nominal current), the output voltage is  
maintained constant. For higher currents the output voltage is  
reduced, however, this will only occur if the bypass supply is not  
available. Otherwise the UPS will switch to bypass operation for  
currents higher than 110% of the nominal current.  
The inverter IGBT transistors are fully protected from severe short  
circuits by means of a desaturation monitor or "electronic fuse".  
1.6 Static Switches  
The block diagram illustrates the two static switch sections that use  
thyristors as switching elements. During normal UPS operation,  
SSI is closed and SSB is open, thus connecting the load to the  
inverter output.  
JUE 401264  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
During overload or inverter failure conditions, SSI is switched off  
and SSB is switched on, providing power supply from a backup  
source (mains, output of another UPS system, diesel generator  
set....). By always actuating both switches together for a short  
period, an uninterrupted power supply during the switching is  
ensured. This is an essential condition to reliably meet all power  
supply requirements for connected sensitive equipment.  
The control for each static switch (SSB and SSI) is performed  
totally independently of each other, thus ensuring that a failure in  
one static switch does not affect the other.  
The voltage and frequency of the bypass line have to be within  
set tolerance limits, and the inverters have to be synchronised  
with the bypass line.  
Switching Conditions, Inverter - Bypass  
Under inverter failure conditions:  
(i) the UPS switches to bypass operation, for a single unit. (SSB  
switches on, and SSI off).  
(ii) for hot-standby units, the load is commutated to the second  
inverter, and will switch to bypass only when no inverter is ready to  
take the load.  
(iii) in parallel systems, all units switch to bypass operation together  
only if the load is more than the rated value for the remaining on-line  
units.  
If the conditions above for the bypass line and synchronisation  
are not met:  
• the inverter will continue to operate with reduced output voltage  
under overload conditions, or  
• the inverter will stop if an inverter failure occurs.  
In this second case, the system will:  
(i) commutate to a second standby-inverter in the case of a hot-  
standby system  
(ii) the remaining inverters will take the load in the case of a  
parallel-redundant system or,  
(iii) the UPS will commutate to the bypass supply with a very short  
interruption of 10msec if the supplies are not synchronised, for the  
case of a single UPS unit.  
Under overload conditions, all UPS modules present will  
switch to the bypass supply, and remain in bypass until the  
overload is removed.  
Switching Conditions, Bypass - Inverter a) The UPS switches automatically back to inverter operation  
when inverter voltage and frequency are within tolerance limits,  
the overload has been removed and the inverter is synchro-  
nised with the bypass line (SSI switches on and SSB off).  
b) If the UPS unsuccessfully attempts five times within 3 minutes  
to switch to inverter operation, the UPS remains in bypass  
operation and signals an alarm. After pressing the reset-button  
once to reset the audible alarm, it should be pressed a second  
time to automatically switch back to inverter operation.  
c) If the UPS remains blocked on bypass operation and a mains  
failure occurs, the UPS will switch automatically to inverter  
operation if the inverter voltage and frequency are within  
tolerance and the inverter is synchronised to the mains.  
JUE 401264  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
1.7 Maintenance Bypass  
The maintenance bypass function is to supply power directly to the  
connected load during UPS maintenance. The bypass consists  
essentially of one switch IBY.  
With SOLA 4000 series UPS systems, switching from different  
operating modes to maintenance bypass can be performed without  
interruption. With the maintenance bypass on, the UPS system  
may be completely switched off, thus permitting maintenance work  
to be carried out safely ( there will only be voltage at the input and  
output terminals and their connections to the circuit-breakers).  
In order to prevent erraneous switching of the maintenance bypass  
switch IBY that could possibly cause parallel connection of the  
bypass line and the inverter line, IBY is electronically intercon-  
nected with the static inverter switch SSI. Thus, during actuation of  
IBY, switch SSB will be closed and switch SSI opened automati-  
cally, preventing parallel operation of the maintenance bypass  
network and the inverter.  
As an option, an external wall-mounted no-break maintenance  
bypass switch (see FIG. 1.6.1) may be supplied by SOLA.This  
switch provides simple one-step transfer to maintenance bypass  
(version 1) without the possibility of erraneous switching and  
without interruption to the load.For the version 2 type maintenance  
bypass, an additional position is provided in order to completely  
isolate the UPS with the one bypass switch.In this way, the UPS  
may be isolated totally from all supply by switching off the input  
supply to the UPS.  
1.8 Hot-Standby Systems  
A hot-standby UPS system basically consists of two (or more)  
single UPS units which operate independently of each other. Any  
one unit can be feeding the load at any time.  
• All units are continuously in operation; but only one is supplying  
the load, at any one time.  
• In case of a failure in the unit currently supplying the load,  
another unit is ready to takeover the load without an interrup-  
tion on the output side. i.e. the load is still supplied with condi-  
tioned and stabilised power.  
• The load is supplied by the static bypass, only if there is no  
inverter ready in the system to takeover the load.  
JUE 401264  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
1 UPS Assembly  
1.9 Parallel-Redundant Systems  
A parallel UPS system consists of 2 to 8 single UPS units con-  
nected in parallel, sharing the load current equally. Each unit has an  
individual static bypass, thus ensuring also redundancy of the static  
bypasses in a redundant system, i.e. if one static bypass should fail,  
the bypass system will still be available.  
There is no common electronic device for the parallel system. Each  
unit has its own parallel-operation electronics that controls all of its  
functions, thus ensuring perfect redundancy.  
1.10 Parallel Systems  
This is identical to the configuration in section 1.9 except that the  
rated load is normally equal to the rating of the UPS and there is  
therefore no redundant unit. UPS units of different kVA ratings may  
be connected in parallel in this configuration, proportionally sharing  
the load.  
Note that the parallel configuration is identical to the parallel-  
redundant configuration if the load is reduced to a value such that  
the system minus one (or more) units is capable of supplying the  
reduced load. Therefore one (or more) units become redundant and  
the control is identical.  
FIG. 1.8 - Parallel Operation - Block Diagram  
JUE 401264  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - General System Description  
2 Operating Panel  
2
OPERATING PANEL  
2.1 Functional Description  
The operating panel is the user-interface of the UPS. It offers the  
following functions:  
• Indication of important data (actual load, battery charging  
status, battery autonomy during the "BACK UP" phase)  
• Protective functions ( Battery Running Down, Battery Test)  
• Indication of the UPS operating mode  
• Alarm signalling (audible and visual)  
• Start push button  
• Reset function after retransfer blocked condition  
Emergency-Power-Off function  
The panel can be subdivided in four functional sections:  
1. Block diagram with status LEDs  
2. Battery autonomy and charging status  
3. Percentage of load supplied  
4. E.P.O. push-button  
2.2 Remote Monitoring  
The operating panel provides an option to communicate with a  
computer through RS232 and RS485 interfaces. The RS232 serial  
interface communicates with a PC or mainframe computer, with a  
SNMP protocol (SEC). With the RS485 interface it is possible to  
transmit all necessary data up to a distance of 400m or to connect  
a remote monitoring panel.  
2.3 Emergency Power Off  
In case of emergency it is possible to switch off the entire UPS  
system. This is done by simultaneously pressing the "Emergency  
Power Off" (E.P.O.) push-buttons located on the operating panel.  
This function provides UPS disconnection from the load and the  
battery, when a separate shunt-trip battery circuit breaker is in-  
stalled.  
In the case of parallel and hot-standby configurations, activating  
E.P.O on one unit, automatically switches OFF the entire system  
(when IUG is closed on that unit).  
JUE 401264  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401265  
SOLA 4000 - Installation and Initial Start-Up  
Chapters  
Figures  
1
INSTALLATION  
3
1.1 Mechanical Installation  
3
FIG.1.1.1 Moving the UPS 10-60kVA units  
FIG.1.1.2 10-60kVA UPS floor space  
FIG.1.1.3 80-120kVA UPS floor space  
FIG.1.1.4 AC001 transformer cabinet  
FIG.1.1.5 AC002 transformer cabinet  
FIG.1.1.6 10-60kVA UPS room size  
FIG.1.1.7 80-120kVA UPS room size  
FIG.1.1.8 80-120kVA UPS room size  
3
4
4
4
4
5
6
7
1.2 Electrical Installation  
8
1.3 Install. of Additional Optional Cabinets 13  
1.4 Installation of an External Maintenance  
Bypass  
16  
18  
20  
21  
22  
22  
23  
1.5 CPNET Interface Card  
1.6 Remote Emergency Power off  
1.7 Diesel - Generator Operation  
1.8 Common Alarm Contacts  
1.9 Remote Reset  
FIG.1.2.1 UPS connection diagram, version 1 9  
FIG.1.2.2 UPS connection diagram, version 2 11  
FIG.1.3.1 UPS connection diagram, with input  
1.10 Installation of Hot-Standby Systems  
1.10.1Installation of the Interconnection Cable 25  
1.11 Installation of Parallel Systems 26  
1.11.1Installation of the Interconnection Cable 29  
1.12 Battery Installation 30  
1.12.1Installation of the Internal Batteries SOLA  
and output transformers  
13  
FIG.1.3.2 UPS connection diagram, with bypass  
input transformer  
13  
FIG.1.3.3 UPS connection diagram, with THD  
filters  
14  
15  
15  
FIG.1.3.4 Installation of 12-pulse units without  
galvanic isolation  
4000 10-30kVA  
30  
1.12.2Installation of External Batteries  
32  
FIG.1.3.5 Installation of 12-pulse units with  
galvanic isolation  
FIG.1.4.1 External maintenance bypass switch,  
2
3
INITIAL START- UP  
38  
version 1  
16  
2.1 Start-Up Procedure  
38  
FIG.1.4.2 External maintenance bypass switch,  
version 2  
17  
FIG.1.6.1 Connection of remote EPO with N.C.  
ADDITIONAL START- UP  
contact  
20  
PROCEDURE FOR MULTI-UNIT  
FIG.1.6.2 Connection of remote EPO witn N.O.  
SYSTEMS  
42  
contact  
20  
FIG.1.6.3 Connection of remote emergency  
power off - input and battery circuit  
breaker trip circuit  
3.1 Start-Up Procedure for  
Hot-standby Systems  
42  
43  
20  
3.2 Start-Up Procedure  
for Parallel Systems  
FIG.1.7.1 Connection for diesel generator  
operation - syncronisation disable 21  
FIG.1.7.2 Connection for diesel generator  
operation - second level current  
limitation  
21  
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
04.02.97  
See Rev. Doc. JSE401479 08.08.97  
See Rev. Doc. JSE401490  
See Rev. Doc. JSE401547 23.09.97  
M. Porpora  
ISSUED  
04.02.97  
A4  
1
44  
B
C
D
M. Porpora  
M. Porpora  
T. Boon  
01.09.97  
T. Boon  
JUE 401265  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
SOLA 4000 - Installation and Initial Start-Up  
FIG.1.8.1 Connec. of remote common alarm 22  
Figures  
FIG.1.9.1 Connection of remote reset  
22  
FIG.1.10.1Interconnection of hot-standby units  
with integrated maintenance bypasses  
and separate bypass terminals  
23  
FIG.1.10.2Interconnection of hot-standby units  
with external maintenance bypass and  
separate bypass terminals.  
24  
FIG.1.10.3Interconnection of control BUS cable  
for hot-standby units  
25  
FIG.1.11.1Interconnection of parallel units with  
integrated maintenance bypasses and  
separate bypass terminals.  
27  
FIG.1.11.2Interconnection of parallel units with  
common maintenance bypass and  
separate bypass terminals  
28  
29  
FIG.1.11.3Location of connectors on the  
IBYBP-CP pcb  
FIG.1.11.4Interconnection of control BUS cables  
between parallel units  
29  
FIG.1.12.1Internal battery connections  
31  
FIG.1.12.2B3/38: battery tray in the first level 32  
FIG.1.12.3B3/38: batt. trays in the second and the  
third level  
32  
32  
33  
34  
35  
35  
36  
FIG.1.12.4Battery cabinet B3/38  
FIG.1.12.5B3/38:switch IB and terminals  
FIG.1.12.6B3/38 internal electrical connec.  
FIG.1.12.7Battery cabinet B3/65  
FIG.1.12.8B3/65:switch IB and terminals  
FIG.1.12.9B3/65 internal electrical connec.  
FIG.1.12.10UPS with additional batt. cabinet 37  
JUE 401265  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1
INSTALLATION  
1.1 Mechanical Installation  
Equipment Delivery and Storage After delivery, check equipment for any damage that may have  
occurred during shipment. The shipper and your SOLA agency  
must be notified in writing about damages due to shipment, includ-  
ing a detailed description of visual defects. If you do not wish to  
install the equipment immediately, please observe the following  
storage recommendations:  
• Store equipment in a vertical position in a well conditioned  
room, protected against humidity. Do not store the equipment  
in close proximity to frequently used passageways and keep it  
away from movable parts.  
• If the UPS system is already unpacked, please ensure storage  
in a clean environment protected from dust, away from heat  
sources.  
Handling the UPS System The UPS can be simply lifted and moved by means of a lifting  
truck or a fork lifter for 80-120kVA units. For 10-60kVA units,  
remove the front side and rear side base sheets and attach two  
angle irons with 8MA bolts to the right front and rear side of the  
UPS. The UPS can now be moved with a lifting fork. Remove the  
angle irons when the UPS is set in the correct position.  
Caution: Secure equipment against being knocked over  
Setting Up The UPS system should be installed in a dry, clean and lockable  
room. Provisions have to be made to remove heat created by the  
system. Under all installation conditions, the unrestricted flow of  
cooling air must be assured.  
JUE 401265  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Weight  
Weight Weight Static  
Type  
SOLA  
4000  
without with  
Battery Battery  
Load  
-
[kg]  
[kg] [kg/m²]  
10  
15  
310  
597  
1277(*)  
1277(*)  
1330(*)  
1362(*)  
1026  
310  
335  
350  
480  
520  
810  
840  
870  
597  
20  
622  
30  
637  
40  
-
-
-
-
-
60  
1112  
80  
1176  
100  
120  
1219  
1263  
TAB. 1.1.1 UPS weight  
Floor Space Required  
FIG. 1.1.2 10-60kVA UPS floor space  
FIG. 1.1.3 80-120kVA UPS floor space  
JUE 401265  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Room Size for 10-60 kVA UPS  
FIG. 1.1.6 UPS 10-60kVA room size  
JUE 401265  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Room Size for 80-120 kVA UPS with  
auxiliary AC001 cabinet  
AC001 cabinets are used for SOLA 4000 units with 12 pulse  
chargers without galvanic separation and with THD Filters.  
FIG. 1.1.7 UPS 80-120kVA room size  
JUE 401265  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Room Size for 80-120 kVA UPS with  
auxiliary AC002 cabinet  
AC002 cabinets are used for SOLA 4000 units with 12 pulse  
chargers with galvanic separation and with auxiliary transformers.  
FIG. 1.1.8 UPS 80-120kVA room size  
JUE 401265  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.2 Electrical Installation  
This equipment must be installed by qualified service person-  
nel.  
Switch off IRP, IRE, IB, IUG, IBY circuit breakers to completely  
isolate the equipment.  
Earth leakage protection: this device has high leakage current  
towards protective earthing. Earth leakage circuit breakers  
shouldn't be installed upstream from this equipment or a correct  
threshold should be set.  
High leakage current - it is essential to connect the protective  
earth before connecting the power supply.  
All primary power switches installed remotely from the UPS area  
must be fitted with the following label: "Isolate uninterruptible  
power supply (UPS) before working on this circuit".  
General  
All electrical connections must be made in accordance with local  
standards and all input terminals (1-L1, 1-L2, 1-L3 and, if existing,  
4-L1, 4-L2, 4-L3) must be protected by external fuses. The tables  
give recommended values for fuse sizes and cable cross-sections.  
These may vary, depending on local standards. They are valid for  
voltages 380/220 V, 400/230 V and 415/240 V. Ensure clockwise  
connection of conductors L1, L2 and L3 at input and output termi-  
nals.  
If possible, install battery cables separately from other power  
cables in order to avoid possible RF interference. Before wiring,  
open all system switches (IRP, IRE, IBY, IUG) plus the battery  
switch (IB).  
JUE 401265  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Version 1 SOLA 4000 with Common Input  
for Rectifier and Bypass  
FIG. 1.2.1 UPS connection diagram, version 1  
(*) Note: Internal Battery only for 10-30kVA units  
(**) Note: Customer supplied input fuses - see table 1.2.1  
JUE 401265  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Version 1 SOLA 4000 with Common Input for  
Rectifier and Bypass  
Input Cables / Fuses  
Type  
Input Input  
earth  
cable  
[mm²]  
SOLA cables fuses  
4000  
[mm²]  
[A]  
10  
15  
4x10  
4x10  
4x16  
4x25  
4x35  
4x35  
4x70  
4x70  
4x120  
25  
35  
16  
16  
16  
25  
25  
25  
50  
50  
70  
20  
50  
30  
63  
40  
100  
125  
160  
200  
250  
60  
80  
100  
120  
TAB.1.2.1 UPS input cables  
and fuses, version 1  
Output / Battery Cables and Max. Cur-  
rent Ratings for Battery Overcurr. pro-  
tection  
Type  
SOLA  
4000  
Battery  
cables  
[mm²]  
Max. inv. input  
current  
(Vdc=320V)  
Output cables  
[mm²]  
10  
15  
2x16  
2x16  
2x25  
2x25  
2x35  
2x50  
2x70  
2x95  
2x120  
4x10  
4x10  
4x16  
4x35  
4x25  
4x35  
4x50  
4x70  
4 x120  
25  
40  
20  
50  
30  
75  
40  
100  
150  
200  
250  
300  
60  
80  
100  
120  
TAB.1.2.2 UPS output cables and fuses, version 1  
JUE 401265  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Version 2 SOLA 4000 with Separate Inputs  
for Rectifier and Bypass  
FIG. 1.2.2 UPS connection diagram, version 2  
(*) Note: Internal Battery only for 10-30kVA units  
(**) Note: Customer supplied rectifier input fuses - see table 1.2.5  
(***) Note: Customer supplied bypass input fuses - see table 1.2.5  
JUE 401265  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Version 2 SOLA 4000 with Separate Inputs  
for Rectifier and Bypass  
Input Cables  
Rect. Bypass earth  
Type  
cables cables cable  
SOLA  
[mm²] [mm²] [mm²]  
4000  
10  
15  
3x10  
3x10  
3x16  
3x25  
3x25  
3x35  
3x50  
3x70  
3x120  
4x10  
4x10  
4x16  
4x25  
4x25  
4x35  
4x50  
4x70  
4x120  
16  
16  
16  
25  
25  
25  
50  
50  
70  
20  
30  
40  
60  
80  
100  
120  
TAB. 1.2.3 UPS input cables, version 2  
Input Fuses  
Rect. Bypass Fuses  
Type  
Fuses  
[A]  
[A]  
SOLA  
4000  
10  
15  
25  
35  
25  
35  
20  
50  
50  
30  
63  
63  
40  
100  
100  
125  
160  
200  
100  
125  
160  
200  
250  
60  
80  
100  
120  
TAB. 1.2.4 UPS input fuses, version 2  
Output / Battery Cables  
Type  
SOLA  
4000  
Battery  
cables  
[mm²]  
Max. inv. input  
current  
(Vdc=320V)  
Output cables  
[mm²]  
10  
15  
2x16  
2x16  
2x25  
2x25  
2x35  
2x50  
2x70  
2x95  
2x120  
4x10  
4x10  
4x16  
4x35  
4x25  
4x35  
4x50  
4x70  
4 x120  
25  
40  
20  
50  
30  
75  
40  
100  
150  
200  
250  
300  
60  
80  
100  
120  
TAB. 1.2.5 UPS output cables and fuses, version 2  
JUE 401265  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.3 Installation of additional optional cabi-  
nets  
SOLA 4000 with input and output transformers for voltage adaption  
FIG. 1.3.1 UPS connection diagram, with input and output transformers to adapt the  
UPS to the on-site voltage.  
SOLA 4000 with isolation transformer of the bypass supply  
FIG. 1.3.2 UPS connection diagram, with bypass input transformer to isolate the  
neutral line (** 4-N may be connected to the supply neutral or earth or left discon-  
nected.)  
(*) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
SOLA 4000 with THD filters  
FIG. 1.3.3 UPS connection diagram, with THD filters  
(*) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
SOLA 4000 with 12-pulse charger / rectifier  
FIG. 1.3.4 Installation of 12-pulse units without galvanic isolation  
SOLA 4000 with 12-pulse charger / rectifier and galvanic isolation of the input sup-  
ply.  
FIG. 1.3.5 Installation of 12-pulse units with galvanic isolation  
(*) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.4 Installation of an External Maintenance  
Bypass  
When an external maintenance bypass is installed, a normally  
open, voltage free contact must be available. This contact must be  
connected to the connector M4, Pin1 and Pin 2 at the top left hand  
corner of the mother board for the inverter/bypass electronics  
(IBYBP-CP see figure 1.10.3).  
If the standard SOLA no-break wall-mounted maintenance bypass  
switch is used (optional) in the MB3 cabinet, a normally open  
contact is provided.For the version 2 maintenance bypass (3  
position), an additional contact is provided which automatically  
isolates the UPS system (EPO) when switched to the "UPS ISO-  
LATED" position (see FIG 1.4.2).  
FIG.1.4.1 External Maintenance Bypass Switch Version 1 (2 position)  
JUE 401265  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG.1.4.2 External Maintenance Bypass Switch Version 2 (3 position)  
Note1: For Hot-Standby or parallel systems, it is sufficient to  
feed one contact into one unit only, however they may be  
connected in parallel at M4 (of IBYBP-CP) Pin1 and Pin 2 for  
all units. In this case separate terminals may be provided  
within the MB3 cabinet (see FIG. 1.9.2 and 1.10.2)  
Note2: The cable used must be twisted pair, with a total shield.  
This shield must be grounded at one end (the cabinet of the  
UPS may be used).  
JUE 401265  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.5 CPNET Interface Card  
The CPNET interface card is used for remote signalling of four  
standard alarm conditions by means of voltage-free contacts in  
programmable configurations.  
1.5.1 Installation  
The CPNET interface card is a small pcb that is installed directly  
underneath the CPU/NCP pcb, inside the front door of the UPS  
cabinet.  
It is connected to the UPS via the connector CN1 on the CPNET  
pcb to CN10 on the CPU/NCP pcb.  
It can be connected to remote devices via two different connectors:  
• CN2, a 9 pin sub-D connector for standard computer connec-  
tion. The following interface cables are available (see also  
JUE 300 599):  
- IBM AS-400  
- Novell  
- 3-COM  
- Banyan Vines  
• M1, a terminal block for individual configurations.  
1.5.2 Functions  
Contacts for the following alarm conditions are available:  
Inverter Operation (N)  
Bypass Operation (B)  
Mains Failure (MF)  
Battery Low (BL)  
(CN1, pin 6)  
(CN1, pin 8)  
(CN1, pin 5)  
(CN1, pin 7)  
By means of the DIP switch SW1, the single relays and output pins  
can be configured for each requirement.  
SW1  
INTERFACE  
1
0
0
0
0
0
0
0
2
0
0
0
0
1
0
0
3
0
0
1
0
1
1
1
4
1
0
0
0
0
0
0
5
0
-
6
1
-
7
1
0
-
8
0
1
-
IBM-AS400  
NOVEL  
-
-
3-COM  
-
-
-
-
BANYAN-VINES  
BORRI VIKING  
BORRI SIDEKICK  
AMERICAN POWER  
-
-
0
0
0
1
1
1
-
-
-
-
TAB. 1.5.2.1 Programming of the CP-NET pcb  
Note: Maximum rating of relay contacts: 250Vac, 6A (only when using  
connector M1)  
JUE 401265  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Pin  
CN2  
Pin  
M1  
BORRI  
VIKING SIDEKICK  
BORRI  
AMERICAN  
POWER  
AS400 NOVEL 3-COM BANYAN-VINES  
Not Used  
1
2
3
4
5
6
7
8
9
1
2
N
-
MF*  
MF  
-
MF*  
MF  
MF*  
MF  
MF*  
MF  
3
MF  
MF  
MF  
4
Common  
5
BL  
B
BL  
MOK  
BOK  
-
BL  
BL  
BL  
BL  
MOK  
BOK  
-
BL  
MOK  
BOK  
-
6
-
BOK  
-
-
BOK  
-
MOK  
BOK  
BL*  
7
BOK  
-
8
9
0 V  
Not Used  
10  
TAB. 1.5.2.2 Allocation of the pins for the output connectors CN1 and M1 for the various programming  
configurations of TAB. 1.5.2.1  
Key to table 1.5.2.2 (when contact is closed with respect to pin 4).  
N:  
Inverter Operation  
B:  
Bypass Operation  
MF:  
BL:  
MF*:  
BL*:  
Mains Failure  
Battery Low  
0V when mains failure, -12V when mains OK  
-12V when battery low, otherwise +12V  
MOK: Mains OK  
BOK: Battery not low  
JUE 401265  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.6 Remote Emergency Power off  
A Remote Emergency Power Off may be connected to the system.  
The connection terminals are M4 Pin 5 and Pin 6, using a nor-  
mally-open, voltage-free contact as a pushbutton.(See FIG. 1.6.1.  
and FIG 1.6.2.)  
FIG. 1.6.1 Connection of Remote EPO with N.C. contact  
FIG. 1.6.2 Connection of Remote EPO with N.O. contact  
Note 1: The cable used must be twisted pair, with a total shield. This  
shield must be grounded at one end (the cabinet of the UPS may  
be used).  
Note 2: For Hot-Standby or parallel systems, it is sufficient to feed  
one contact into one unit only, however they may be connected in  
parallel at M4 (of IBYBP-CP) Pin5 and Pin 6 for all units (N/O) only  
or series for (N/C).  
Note 3: To completely isolate the UPS system from all voltage with  
the emergency power off (EPO), it is necessary to install trippable  
circuit breaker on the input supply (to terminals 1-L1, 1-L2, 1-L3  
and 4-L1, 4-L2, 4-L3 and 4-N if installed).  
The trip coil is then connected to the terminal M1 on the CPU/NCP  
pcb located inside the front door of the cabinet. A normally open or  
normally closed voltage-free contact is available.  
Note 4: The N.C. contact can only be used for IBYBP-CP  
motherboards in rev. 0A and following.  
FIG. 1.6.3 Connection of Remote Emergency Power Off - Input and battery circuit  
breaker trip circuit.  
Nominal Rating of Contacts  
125 V  
30 V  
0,5 A  
2 A  
60 W  
60 W  
@
@
TAB. 1.6.1 Nominal Rating of contacts for the input breaker trip circuit.  
JUE 401265  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.7 Diesel - Generator Operation  
During diesel generator operation, if the frequency of the diesel-  
generator, with UPS and load connected, is unstable, it is advisable  
to disconnect the synchronisation of the inverter. This is achieved  
with a normally-open, voltage-free contact (which closes during  
diesel-generator operation) and is connected to the connector M4  
Pin 7 and Pin 8 as follows:  
FIG. 1.7.1 Connection for Diesel Generator Operation (connector M4) - synchronisa-  
tion disable.  
Note1: For Hot-Standby or parallel systems, it is sufficient to feed  
one contact into one unit only, however they may be connected in  
parallel at M4 Pin7 and Pin 8 for all units  
If it is necessary to reduce the current supplied by the diesel-  
generator, then a second voltage-free contact (again normally  
open) is required and must to be connected to the connector M8,  
Pin 1 and Pin 2 on the rectifier electronic mother board (RBPHC16)  
see FIG.1.7.2  
FIG. 1.7.2 Connection for Diesel Generator Operation (connector M8) - second level  
current limitation.  
Note 1: The cable used in both cases must be twisted pair, with a  
total shield.This shield must be grounded at one end (the cabinet  
of theUPS may be used).  
Note 2: The cable for current limitation must be connected to all units  
for parallel or hot-standby units, using separate voltage-free  
contacts.  
JUE 401265  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.8 Common Alarm Contacts  
As a standard feature, contacts are provided for a remote common  
alarm.The connector is located on the control p.c.b for the front  
operating panel (CPU/NCP), located inside the front door of the  
UPS.  
FIG. 1.8.1 Connection of Remote Common Alarm  
Nominal Rating of Contacts  
125 V  
30 V  
0,5 A  
2 A  
60 W  
60 W  
@
@
TAB. 1.8.1 Nominal Rating of contacts for the common alarm.  
Note 1: As an option a pcb CP-NET is available, providing more  
contacts, compatible with most common configurations (eg AS400,  
Novell etc.)  
A Remote panel may also be purchased with identical functions to  
the front operating panel.  
Note 2: To achieve a single common alarm for parallel or hot-  
standby units, the contacts of each unit may be interconnected in  
parallel (normally - open) or series (normally - closed).  
1.9 Remote Reset  
The UPS system may be reset remotely with the connection of  
contacts ( a push-button) to the terminal M4 as shown:  
FIG.1.9.1 Connection of Remote Reset  
Note: The cable used must be twisted pair, with a total shield.  
This shield must be grounded at one end (the cabinet of the  
UPS may be used).  
JUE 401265  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.10 Installation of Hot-Standby Systems  
For hot-standby systems the units must be connected together as  
shown in the FIG. 1.10.1 or FIG. 1.10.2  
Note: The installation for each unit must be performed in accordance  
to the installation of single units as described in the previous  
sections. Additionally to this, the outputs must be connected in  
parallel as shown in FIG. 1.10.1 or in FIG.1.10.2  
FIG. 1.10.1 Interconnection of hot-standby units with integrated  
maintenance bypasses and separate bypass terminals.  
(*) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG. 1.10.2 Interconnection of hot-standby units with external maintenance bypass and  
separate bypass terminals.  
(*) Note: The internal maintenance bypass (IBY) may or may not be installed in this con-  
figuration.  
(**) Note: This cable must be twisted pair, total shield (refer. to section 1.4)  
(***) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.10.1 Installation of the Interconnection Cable  
The supplied cable must be connected between the units within the  
system. This must be connected at either of the connectors CN12  
or CN13 on the mother-board of the Inverter/Bypass electronics  
(IBYBP-CP) and the other end of the cable is connected to either  
CN12 or CN13 on the mother-board of the Inverter/Bypass elec-  
tronics (IBYBP-CP) of the other unit(s).  
Note: If the unit is to be added to one already installed stand-alone  
unit which has not been previously tested in a hot-standby configu-  
ration, the supports and mounting screws to mount the cable to the  
p.c.b are supplied with the cable. They must be mounted at both  
sides of the selected connector in order to fix the cable securely to  
the connector with the supplied screws.  
FIG. 1.10.3 Interconnection of control BUS cable for hot-standby units  
JUE 401265  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.11 Installation of Parallel Systems  
Up to a total of 8 units may be installed together in the one parallel  
system.  
Note: The installation for each unit must be performed in accord-  
ance to the installation of single units as described in the previous  
sections. Additionally to this, the outputs must be connected in  
parallel as shown in FIG. 1.11.1 or in FIG.1.11.2  
Care must be taken with the installation of the bypass line and in  
particular, that the cables from the point of common coupling of the  
input supply to the terminals 1-L1, 1-L2, 1-L3 (or 4-L1, 4-L2, 4-L3,  
4-N if an optional separate bypass input is installed), are of equal  
length. Likewise, the output cables from the output terminals (5-L1,  
5-L2, 5-L3, 5-N) to the point of common coupling on the load side  
must be of equal length.  
JUE 401265  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG. 1.11.1 Interconnection of parallel units with integrated maintenance bypasses and separate bypass  
terminals.  
(*) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG. 1.11.2 Interconnection of parallel units with common maintenance bypass and separate bypass  
terminals.  
(*) Note: The internal maintenance bypass may or may not be installed in this configuration.  
(**) Note: This cable must be twisted pair, total shield (refer to section 1.4)  
(***) Note: Internal Battery only for 10-30kVA units  
JUE 401265  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.11.1 Installation of the Interconnection Cables  
There are two interconnection cables supplied with the units for  
each additional unit to the first unit. These cables must be con-  
nected between the units as shown in FIG. 1.11.4 One cable is  
connected to either CN12 or CN13 (the other end being connected  
to the corresponding connector of another unit), and the other  
cable is connected to either of CN10 or CN11, again with the other  
end connected to the corresponding connector of another unit. In  
this way, all units will be interconnected by two cables in a BUS-  
Communication system (Daisy-chain connection).  
Note: If the unit is to be added to one already installed stand-alone  
unit which has not been previously tested in a parallel configura-  
tion, the supports and mounting screws to mount the cable to the  
p.c.b are supplied with the cables. They must be mounted at both  
sides of the selected connectors in order to fix the cables securely  
to the connectors with the supplied screws.  
FIG. 1.11.3 Location of connectors on the IBYBP-CP pcb.  
FIG. 1.11.4 Interconnection of control BUS cables between parallel units  
JUE 401265  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.12 Battery Installation  
Battery Installation must be in accordance with local safety  
standards.  
General The batteries are charged. The installation should only be made by  
appropriately qualified personnel. The screw connections between  
the batteries should be tightened with a torque wrench (max. 7  
Nm).  
1.12.1 Installation of Internal batteries  
SOLA 4000 (10-30kVA)  
Internal Battery (24Ah) Installation  
• Place five battery blocks on the trays of the first level.  
• Place nine battery blocks on the trays of the second, third and  
fourth level.  
• Interconnect the blocks in series (see FIG.1.12.1)  
Warning: after assembly there is a voltage of 67,5 V on the first  
level, and 121,5 V on the second, third and fourth levels.  
1° LEVEL  
2° LEVEL  
3° LEVEL  
4° LEVEL  
JUE 401265  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Internal Electrical Connections  
Cable (1) n° 3; L = 280 mm; diameter 16 mm2  
Cable (2) n° 8; L = 420 mm; diameter 16 mm2  
Cable (3) n° 4; L = 490 mm; diameter 16 mm2  
Cable (4) n° 2; L = 650 mm; diameter 16 mm2  
Support (CA1) n° 4; See Fig. CA1  
Support (CA2) n° 9; See Fig. CA2  
FIG. 1.12.1 Internal Battery connections.  
Copper bars for battery connection Two copper plates diam. 0,5 mm. are used.  
CA1  
CA2  
JUE 401265  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
1.12.2 Installation of External Batteries  
External Battery (38 Ah) Installation 38 Ah external batteries are installed in a B3/38 battery cabinet. To  
assemble the battery cabinet:  
• Place four battery blocks on the trays of the first level (see FIG.  
1.12.2).  
• Place six battery blocks on the trays of the second and third  
levels (see FIG. 1.12.3).  
• Interconnect the blocks in series (block 1 / negative pole ==>  
block 2 / positive pole,....)  
Warning: after assembly there is a voltage of 48 V on the first  
level, and 72 V on the second and third levels.  
• If necessary secure with strapping (against vibrations).  
• Insert the trays into the battery cabinet as shown in FIG. 1.12.4  
FIG. 1.12.3 B3/38: battery trays in the  
second and the third level  
FIG. 1.12.4 Battery cabinet B3/38  
JUE 401265  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Important: Open battery switch IB before connecting the cables.  
• Place the trays with the  
batteries on the correspond-  
ing levels in the UPS.  
• Connect the battery blocks  
of the various levels to the  
battery switch IB, and IB to  
the terminals, as shown in  
FIG. 1.12.5 and FIG. 1.12.6  
Ensure appropriate ventilation of the battery room according to the  
standard EN50091-1, to prevent the risk of an explosion.  
JUE 401265  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG. 1.12.6 B3/38 internal electrical connections  
JUE 401265  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
External Battery (65 Ah) Installation 65 Ah external batteries are installed in a B3/65 battery cabinet. To  
assemble the battery cabinet:  
• Remove the battery switch IB and the terminals.  
• Insert the battery blocks from the front and rear sides.  
Warning: after assembly there is a voltage of 192 V at the front  
and rear side.  
• Remount the battery switch IB and the terminals.  
Important: Open battery switch IB before connecting the cables.  
• Connect the battery blocks on the various levels to the battery  
switch IB, and IB to the terminals, as shown in FIG. 1.12.8 and  
FIG. 1.12.9  
FIG. 1.12.7 Battery cabinet B3/65  
FIG. 1.12.8 B3/65: switch IB and terminals  
JUE 401265  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
FIG. 1.12.9 B3/65 internal electrical connections  
JUE 401265  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
1 Installation  
Connection Between UPS and Additional  
Battery Cabinets  
Important: Open all battery switches IB before connecting the  
cables. Observe the indicated wiring polarity.  
• For UPS systems with external batteries: connect the external  
batteries as shown in FIG. 1.12.10  
• After wiring, check that the external battery is connected with  
correct polarity.  
FIG. 1.12.10 UPS with additional battery cabinet  
Connection of Auxiliary Contacts  
For the standard battery cabinet, the terminals C1, C2, C3 and C4  
are connected to the corresponding terminals in the UPS cabinet  
as in FIG. 1.12.10.  
If a battery is installed without standard cabinet(s), then a voltage-  
free auxiliary contact (normally closed) should be provided, along  
with a dc shunt trip circuit, for the battery circuit breaker / fuse  
switch. The auxiliary contact is connected to the terminals C1 and  
C2. The shunt trip circuit is connected in series with C3 and C4 and  
the appropriate number of batteries in order to achieve the rated  
shunt trip coil voltage.  
JUE 401265  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
2 Initial Start-Up  
2
INITIAL START-UP  
2.1 Start-Up Procedure  
With the Start-Up procedure the correct installation of the UPS  
according to the previous section is checked. It must be carried out  
by specialised personnel.  
General  
Safety precautions according to the appropriate local safety stand-  
ards must be applied.  
Should problems arise during the Start-Up Procedure, call for  
service assistance.  
For carrying out the Start-Up Procedure you need a 3 1/2 digit  
voltmeter with 1% accuracy, an AC/DC clip-on ammeter and a  
small screwdriver for potentiometers (only when necessary).  
Preparation  
The installation of the UPS must have been carried out according  
to the previous section.  
• Check that the ventilation system of the UPS room is ready to  
operate.  
• Check that all switches IRP, IRE, IUG, IBY, IB are open and  
the load is off.  
A: Rectifier Power Supply Check  
• Switch on the external mains supply to the UPS.  
• Check that the supply voltage at terminals 1-L1, 1-L2, 1-L3 is  
within ±10% of the UPS rated voltage.  
• Close IRP.  
Does the display on the CPHC16 -R pcb for the rectifier give the  
?
indication "P"?  
yes The phase rotation at the input is incorrect.  
• Open IRP, switch off the external mains supply and exchange  
any two of the cables at input terminals 1-L1, 1-L2, 1-L3.  
• Return to A.  
no The rectifier supply voltage is o.k. and the rectifier will automati-  
cally start to operate.  
• Wait until the Data Monitor Panel / NCP is illuminated  
• Press the START push-button on the front of panel (or the push  
button PB2 on the top of ICP card) the inverter will start and  
after approximately 10s the green led L16 will be permanently  
lit.  
• Press the push-button PB3 on the bottom of ICP card:  
after few seconds the three green leds on SS/FY card will be lit.  
One led is flashing:  
- green LED 3 flashing:  
"Battery switch open". Note that when  
using the external battery cabinet this function is desabled.  
NOTE: If the battery switch indication is not blinking then the connections to C1  
and C2 in the battery cabinet are not correct. Refer to the section "Installation".  
JUE 401265  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
2 Initial Start-Up  
B: Inverter Voltage Adjustment  
• On the SS/FY pcb, measure the voltage at the screws Inverter  
R, Inverter S, Inverter T with respect to the neutral terminal 5-  
N.  
Does this voltage correspond to the desired voltage?  
?
no  
• Adjust the voltage to the desired value individually for each  
phase using P3, P4 and P5 on the ICT-2 pcb.  
NOTE: If the inverter output voltage is changed, the value at  
TP1 (adjusted with P1) on the ICP pcb should be checked. (6V  
corresponds to nominal voltage). Note also that for parallel  
systems, if the voltage is changed here, the current sharing will  
also be affected. Therefore, change voltage settings ONLY IF  
ABSOLUTELY NECESSARY. Small variations of the voltage will not  
affect system performance. The UPS is already pre-calibrated  
in the factory with nominal load.  
yes  
• Continue with C  
C: Inverter free-run frequency check  
• Insert a pin d=2mm in the red test point S1 on the ICP pcb. The  
red LED LD3 on the ICP pcb must be permanently lit. The  
inverter frequency is now free-running without the internal  
oscillator.  
• On the SS/FY pcb, measure the inverter frequency on the  
screws Inverter R, S or T with respect to neutral.  
• Check that the frequency is set at the required value (50/60 Hz  
+/- 0,1 Hz). It can be adjusted with P1 on the ICT-2 pcb. Re-  
move the pin from S1. The inverter now synchronises with the  
internal oscillator.  
• Make sure that the batteries have been installed according to  
the instructions for installation.  
With an external battery cabinet B3/38:  
• Measure the battery voltage in the battery cabinet at the battery  
switch between cables:  
- -290 (-) and -1 (+)  
- +1 (-) and +4 (+)  
With an external battery cabinet B3/65:  
• Measure the battery voltage in the battery cabinet at the battery  
switch between cables:  
- -290 (-) and -1 (+)  
- +1 (-) and +2 (+)  
Does this voltage have positive polarity?  
?
no  
• Open IRP, wait for 5-10 minutes, and then reconnect the  
battery cables at the terminals which lead to the switch(es)  
where the wrong polarity was detected.  
• Return to D.  
yes  
• Check the voltage between the battery terminals B+ and B-.  
The value of this voltage should be already set according to the  
amount of batteries installed.  
• Close battery switch IB.  
The alarm "battery switch open" stops.  
JUE 401265  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
2 Initial Start-Up  
• If your unit has separate supplies for the rectifier and bypass  
(terminals 4-L1, 4-L2, 4-L3, 4-N), switch on the external supply  
for the bypass. Check that the bypass supply voltage at termi-  
nals 4-L1, 4-L2, 4-L3, 4-N is within ±10% of the nominal input  
voltage.  
If there are no separate input terminals then the bypass input is  
the same as that checked previously for the rectifier input.  
• Close IUG.  
• Close IRE.  
Does the display on the CPHC16 -S pcb for the bypass give the  
?
indication "P"?  
yes  
• Open IRE and exchange any two of the cables at the bypass  
input terminals 4-L1, 4-L2, 4-L3.  
• Return to E.  
no  
• Are the status LEDs (green) 1, 2, 3, 14, 16, 17, 19, 26, on the  
operating panel continuously on?  
no: Check that the mains frequency is in tolerance.  
OK?  
yes: Is the pcb CPHC16 -S for the bypass  
correctly functioning? The display should be  
rotating clockwise.  
no: Call for service assistance.  
yes: Check again the input supply. Check  
that it is in accordance with the UPS  
rating label.  
no: The mains frequency must be within  
tolerance in order for the bypass to be  
availabe  
Continue with F.  
yes:  
• Check that the green LED LD1 on the ICT-2 pcb is permanently  
F: Synchronisation Check  
lit and there is no "S" indication on the bypass electronics.  
• On the SS/FY pcb, measure the voltage between the screws  
Bypass R and Inverter R. Then repeat for the other two phases.  
Are the voltages < 25Vac?  
?
no  
• If the voltage is continuously fluctuating from 0 to 400V there is  
a synchronisation problem. Switch off IRE and call for service  
assistance.  
If the voltage is slightly higher but relatively constant and the  
default values have been re-entered using the serial interface  
on the CPHC16 -S p.c.b., then the synchronisation may need to  
be re-adjusted. This can be easily confirmed by comparing the  
two sinewaves for a possible phase difference.  
Are the two waveforms phase-shifted?  
yes: The synchronisation must be re-adjusted using the serial  
interface of the CPHC16 -S pcb and the PSRS232 and a  
portable computer.  
JUE 401265  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
2 Initial Start-Up  
no:  
The difference is probably due to distortion of the mains  
voltage (the inverter voltage is an almost perfect  
sinewave)  
Continue with G  
yes:  
Continue with G  
COMMUTATION TO THE BYPASS  
G: Static Switch Commutation Check  
Press the pushbutton on the CPHC16-S pcb for the bypass.  
The static switch SSB will switch on and SSI will switch off, as  
indicated on the front panel and on the SS/FY pcb (red LEDs).  
COMMUTATION TO INVERTER  
Press the pushbutton PB3 at the bottom of the ICP pcb. The  
static switch SSI will switch on and SSB will switch off, as  
indicated on the front panel and the SS/FY pcb (green LEDs).  
H: Battery Charging Current Limitation  
Check  
• Connect the load and open IRP.  
The load is now supplied only by the batteries.  
• Discharge the batteries for about 2 minutes at nominal UPS  
load or longer if the connected load is smaller than nominal  
UPS load  
• Close IRP again.  
• After 30 seconds, measure the battery voltage.  
Is the battery voltage lower than the set floating charge voltage?  
?
no The rectifier is not yet in battery current limitation. In order to check  
the battery current limitation you must discharge the batteries for a  
longer period.  
• Return to H.  
yes The battery current limitation can now be checked according to the  
battery installed. Standard setting is 10% of the battery capacity.  
• Measure the battery recharging current with a dc clip-on amme-  
ter.  
Is this approximately 10% of the battery Ah capacity?  
?
no Check the settings of the dipswitch S1 on the CPHC16 -R pcb for  
the rectifier according to JUE400899 programming of PCBs (V2.0  
or later). Otherwise, the battery charging current may need to be  
adjusted using the RS232 connector on the CPHC16-R pcb and a  
portable computer. This must be performed by first discharging the  
battery by switching off IRP, connecting the PC and adjusting the  
charging current. The battery must remain connected through-  
out the procedure.  
Return to H.  
yes THE START-UP PROCEDURE HAS BEEN SUCCESSFULLY COMPLETED NOW.  
JUE 401265  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
3 Additional Start-Up Proced. for Multi-Unit Systems  
3
ADDITIONAL START-UP PROCED. FOR  
MULTI-UNIT SYSTEMS  
3.1 Start-Up Procedure for Hot -standby Sys-  
tems  
Repeat the procedure of section 2 for the second unit in the system  
(with the first unit off).  
Ensure that the interconnecting BUS cable is connected according  
to section 1.9.1 and FIG 1.9.3.  
J
• Switch off the inverter at the second unit with PB2 at the top of  
the ICP pcb. The unit will transfer to the bypass supply.  
• Switch on IRP of the first unit.  
• Ensure that the switch IUG of this unit is off.  
• Switch on IRE of the first unit.  
After approx. 10 seconds the display will flash with a "U" indica-  
tion and static bypass switch SSB will be closed.  
• Measure across the output switch IUG from input to output of  
each phase.  
Is this voltage less than 2V a.c for all three phases?  
?
no  
The output power interconnections are incorrect and must be  
reconnected correctly. Switch off both units and the mains  
supply and recheck the connections.Return to J  
yes  
Continue  
• Close IUG of the first unit. The two static bypasses (SSB) are  
now connected in parallel.  
• Close the battery switch of the first unit.  
• Start the unit by pressing "START" on the front operating panel.  
when the inverter is synchronised, the unit will transfer the  
inverter to the output (SSI closes and both SSB switches switch  
off).  
• Press "START" on the operating panel of the second unit.  
The inverter will start and become ready (check that the green LED  
LD6 on the ICP pcb is illuminated) but the static switch SSI will not  
close.  
• Check the commutation of the inverters by pressing PB2 at the  
top of the ICP pcb on the unit currently with SSI closed.  
• Restart the inverters (with PB2 on ICP or with "START").  
THE SYSTEM IS NOW IN NORMAL OPERATION AND THE HOT-STANDBY START-UP  
HAS BEEN SUCCESSFULLY COMPLETED.  
JUE 401265  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
3 Additional Start-Up Proced. for Multi-Unit Systems  
3.2 Start-Up Procedure for Parallel Systems  
Repeat the procedure of section 2 individually for all units in the  
system, with the the other units off.  
Ensure that the interconnecting BUS cables are connected accord-  
ing to section 1.10.1 and FIG 1.10.3.  
• Open IRP, IRE, IB and IUG of the last unit checked with the  
procedure in section 2.  
K
• Ensure that no load is connected to the system output.  
• Ensure that all IUG switches are open.  
• Switch on the IRE switches of all units. Wait until all units give  
a flashing "U" indication on the display of the CPHC16-S pcb.  
• Close IUG on one unit only.  
• At each unit in turn:  
Measure across the output switch IUG from input to output of each  
phase.  
Is this voltage less than 2V.a.c for all three phases for every unit?  
?
The output power interconnections are incorrect and must be  
reconnected correctly. Switch off all units and the mains supply  
and recheck the connections.  
no  
Return to K  
yes  
Continue.  
• Close the IUG switches on all units. The static bypasses (SSB)  
will now be connected in parallel for all units.  
• Close IRP of all units.  
• When the front operating panel is initialised on all units (after 3  
beeps), close the battery switches of the respective units.  
• Press the "START" pushbutton on any one unit. The inverter  
will start and when synchronised to the bypass supply, transfer  
to the system output and all static bypass switches (SSB) will  
open.  
• Press the "START" pushbutton on each successive unit in the  
system, each time checking that the SSI closes on the unit and  
that the system operates in parallel operation.  
• Commutations to the bypass/inverter supplies may be checked  
by pressing the pushbutton on the CPH16 -S pcb and PB3 at  
the bottom of the ICP pcb.  
• Apply a load to the UPS system and check for correct sharing  
of the load currents on each phase. If stand-alone units have  
been converted for parallel operation, the current sharing needs  
to be checked and is best performed with a load as close as  
possible  
JUE 401265  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Installation and Initial Start-Up  
3 Additional Start-Up Proced. for Multi-Unit Systems  
to the nominal load. Measure the currents at the output of each  
module on phase T. If this current varies by more than ± 1% for  
this module, fine adjustment can be made with P1 on the IPR  
pcb.  
Check the currents at the output of each module on phase S.  
These currents must be balanced to within ± 1% by finely  
adjusting the inverter voltage of phase S (P4 on ICT-2). i.e. If  
the module is supplying more current than the system average,  
the inverter voltage of this module must be reduced slightly.  
Repeat for phase R currents by finely adjusting the R phase  
inverter voltage of this module with P3 on the ICT-2 pcb until  
the currents on the phase R of all modules are equal to within  
± 1%.  
• THE SYSTEM START-UP HAS NOW BEEN SUCCESSFULLY COMPLETED.  
JUE 401265  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401266  
SOLA 4000 - Operation  
Chapters  
1
2
OPERATING MODES  
2
5
OPERATING INSTRUCTIONS 11  
1.1 General  
2
5.1 Switching On the UPS System/from  
Maintenance Bypass  
11  
13  
1.2 Led Indication  
3
5.2 Switching Off the UPS System/to  
Maintenance Bypass  
5.3 Switching On any one unit within a  
System (Parallel and Hot-standby Sys-  
tems)  
OPERATING MODES STAND-  
ALONE UNIT  
4
14  
2.1 Normal Operation  
4
4
5
5
5
5.4 Switching Off any one unit within a  
System (Parallel and Hot-standby Sys-  
tems)  
2.2 Battery Operation  
15  
16  
2.3 Bypass Operation  
5.5 Emergency Power Off  
2.4 Maintenance Bypass Operation  
2.5 Standby Operation  
Figures  
3
OPERATING MODES HOT-  
STANDBY OPERATION  
6
3.1 Normal Operation  
6
6
6
7
7
FIG. 2.1 Normal Operation  
4
4
3.2 Operation with an Inverter Failure  
3.3 Battery Operation  
FIG. 2.2 Battery Operation  
FIG. 2.3 Bypass Operation  
5
3.4 Bypass Operation  
FIG. 2.4 Maintenance Bypass Operation  
FIG. 2.5 Standby Operation  
5
3.5 Maintenance Bypass Operation  
5
FIG. 3.1 Normal Operation  
6
FIG. 3.2 Operation with an Inverter failure  
FIG. 3.3 Battery Operation  
6
4
OPERATING MODES PARALLEL  
AND PARALLEL/REDUNDANT  
6
FIG. 3.4 Bypass Operation  
7
OPERATION  
8
FIG. 3.5 Maintenance Bypass Operation  
FIG. 4.1 Normal Operation  
7
4.1 Normal Operation  
8
8
4.2 Partial Load Operation  
4.3 Battery Operation  
8
FIG. 4.2 Partial Load Operation  
FIG. 4.3 Battery Operation  
8
9
9
4.4 Operation with an Inverter Failure  
4.5 Bypass Operation  
9
FIG. 4.4 Operation with an Inverter Failure  
FIG. 4.5 Bypass Operation  
9
10  
10  
10  
10  
4.6 Maintenance Bypass Operation  
FIG. 4.6 Maintenance Bypass Operation  
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
04.02.97  
20.06.97  
23.09.97  
ISSUED  
See Rev. Doc. JSE 401440  
See Rev. Doc. JSE 401547  
M. Porpora  
T. Boon  
04.02.97  
A4  
1
16  
A
B
T. Boon  
T. Boon  
JUE 401266  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
1 Operating Modes  
1
OPERATING MODES  
1.1 General  
There are four different operating modes of the standard stand-  
alone on-line UPS-system (5 for hot-standby and 6 for parallel  
systems), ensuring uninterrupted power supply of the load under all  
conditions. Transitions between these operating modes are per-  
formed without interruption of the power supply to the load.  
• In "Normal Operation" any failure, internal or external, will  
transfer the UPS system either to "battery operation", to "by-  
pass operation" for a stand-alone UPS or to "operation with an  
inverter failure" for parallel and hot-standby systems.  
Security concept  
• In "Battery Operation" or "Bypass Operation", with a stand-  
alone UPS system, an additional failure may interrupt the  
power supply to the load, depending on the kind of failure. In  
both operating modes the UPS signals a failure condition  
(audible and visual alarm) to indicate that any additional failure  
bears the risk of interrupting the power supply to the load.  
• As additional security, a second UPS unit may be added and  
connected in parallel with the original unit, in a hot-standby  
configuration. Therefore, in the case of a failure of one inverter,  
the second inverter will take over the load. This system re-  
quires the occurrence of 3 or 4 simultaneous failures (the  
bypass can be also redundant) before the load is interrupted.  
Any number of units can be connected together in this way, the  
addition of each unit providing the addition of 1 or 2 additional  
security factors. The interconnection of the SOLA 4000 in this  
way requires a special cable available from your local distribu-  
tor.  
• Parallel Operation is used to provide redundancy in the same  
way as for hot-standby units above and / or an increased  
capacity to supply the load, the parallel units exactly sharing  
the load requirement.  
• "Maintenance Bypass Operation" is used to supply the load  
directly from mains during maintenance or repair work.  
Warning: Even in case of a total blackout, the UPS will continue to  
supply power to the load, therefore all necessary precautions  
against direct and indirect accidental contact as specified in na-  
tional and local safety standards must be followed.  
JUE 401266  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
1 Operating Modes  
1.2 LED Indication  
The block diagram of the UPS, with integrated LEDs, allows a  
quick check of the UPS operating status.  
LED 1 MAINS PRESENT  
LED 2 RECTIFIER  
LED 3 BATTERY SWITCH  
LED 4 BATTERY DISCHARGING  
LED 5 BATTERY CHARGING  
LED 14 BYPASS POWER SUPPL
LED 15 MAINTENANCE BYPASS S
LED 16 INVERTER  
LED 17 LOAD FED by INVERTER  
LED 18 LOAD FED by BYPASS  
POWER SUPPLY  
LED 19 LOAD IS SUPPLIED  
LED 27 BATTERY TEST  
LED 28 E.P.O.  
LED 26 BYPASS AVAILABLE  
LED 29 COMMON ALARM  
LED 30 BOOST CHARGE  
JUE 401266  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
2 Operating Modes Stand-alone Unit  
2
OPERATING MODES STAND-ALONE  
UNIT  
2.1 Normal Operation  
"Normal Operation" is the standard operating mode of the UPS  
• Mains power is present.  
• The rectifier converts ac power to dc power which charges the  
batteries and feeds the inverter.  
• The inverter converts this dc power to ac power used to feed  
the connected load.  
2.2 Battery Operation  
The "Battery Operation" mode is activated by a mains failure or  
rectifier failure  
• The rectifier supplies no power.  
• The battery supplies the required dc power to the inverter.  
• The inverter supplies ac power to the load as described above.  
• Power will only be supplied to the load for a certain period of  
time depending on the battery capacity and the amount of load  
applied.  
JUE 401266  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
2 Operating Modes Stand-alone Unit  
2.3 Bypass Operation  
The "Bypass Operation" mode is activated by an inverter failure or  
an overload  
• The rectifier supplies dc power only to the battery.  
• The static inverter switch SSI opens automatically after the  
static bypass switch SSB is closed.  
• The load is supplied directly from the mains through the static  
bypass line.  
2.4 Maintenance Bypass Operation  
The "Maintenance Bypass Operation" mode is used to supply the  
load directly from the mains during maintenance or repair work.  
• In this mode, the individual functional components are com-  
pletely separated from the load.  
• Power for the load is supplied directly from the mains through  
the switch IBY.  
2.5 Standby Operation  
If an appropriately programmmed IPR pcb is inserted in the control  
electronic of the stand-alone unit, as an option, this mode of  
operation is possible.  
• If the load is completely switched off, the inverter and the  
inverter static switch SSI, switch off and the UPS commutates  
to the bypass supply (SSB closes), thus saving power when the  
UPS is not needed.  
• When the load is again switched on, the inverter automatically  
switches on and the inverter static switch SSI will commutate  
the load to the protected inverter supply.  
JUE 401266  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
3 Operating Modes Hot-Standby Operation  
3
OPERATING MODES HOT-STANDBY  
OPERATION  
3.1 Normal Operation  
"Normal Operation" is the standard operating mode of the hot-  
standby system.  
• Mains power is present.  
• The rectifiers of all units convert ac power to dc power which  
charges the batteries and feeds the inverters.  
• The inverters convert this dc power to ac power.  
• The inverter of one unit feeds the connected load.  
• The inverter of the other unit(s) is working in standby mode,  
ready to takeover the load if there is a failure in the unit supply-  
ing the load.  
• All units in the system are identical and operate completely  
independently of each other.  
3.2 Operation with an Inverter Failure  
"Operation with an Inverter Failure" is the operating mode of the  
hot-standby system after a failure has occurred in one unit.  
• Mains power is present.  
• The static inverter switch of the failed unit opens automatically  
and the static inverter switch of an other unit is closed.  
• The rectifier of that unit converts ac power to dc power which  
charges the battery and feeds the inverter. The inverter then  
converts this dc power to ac power used to feed the connected  
load.  
• The static bypasses within all units remain ready to supply the  
load in case of any additional failure(s) or overload.  
3.3 Battery Operation  
The "Battery Operation" mode is activated by a mains failure or  
rectifier failure.  
• The rectifiers of all units supply no power.  
• The batteries of all units supply the required dc power to the  
inverter of each unit.  
• The inverter of one unit continues to supply ac power to the  
load.  
• The inverter(s) of the other unit(s) are operating in standby  
mode, ready to takeover the load, without interruption.  
JUE 401266  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
3 Operating Modes Hot-Standby Operation  
• If an additional failure in the first unit occurs, or when the  
battery of that unit is exhausted, the inverter of another unit will  
takeover the load, continuing in battery operation until the  
mains returns or the second battery is exhausted.  
3.4 Bypass Operation  
The "Bypass Operation" mode is activated by an overload or by  
inverter failures in all units or by a manual commutation.  
• The rectifiers supply dc power only to the batteries.  
• The static inverter switch SSI of the unit supplying the load  
opens automatically after the static bypass switch SSB is  
closed.  
• The load is supplied directly from the mains through the static  
bypass.  
• If the transition to "Bypass Operation" was caused by a tempo-  
rary overload, the UPS system returns automatically to "Normal  
Operation", any inverter may takeover the load, when the load  
returns to within tolerance.  
3.5 Maintenance Bypass Operation  
"Maintenance Bypass Operation" is used to supply the load directly  
from mains during maintenance or repair work.  
• In this mode, the individual functional components of all units  
are completely separated from the load.  
• Power for the load is supplied directly from the mains through  
the switch IBY.  
JUE 401266  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
4 Operating Modes Parallel and Parallel/Redundant  
Operation  
4
OPERATING MODES PARALLEL AND  
PARALLEL/REDUNDANT OPERATION  
4.1 Normal Operation  
"Normal Operation" is the standard operating mode of the UPS if  
the system load is at its nominal value or the system is pro-  
grammed in a way that all units remain on-line. Otherwise see  
section 4.2.  
• Mains power is present  
• The rectifiers convert a.c. power to d.c. power used to charge  
the batteries and feed the inverters  
• The inverters convert this d.c. power to a.c. power used to feed  
the connected load  
• All units are sharing the load current uniformly. This is accom-  
plished by means of the optional parallel-operation-electronic  
pcb (IPR).  
• All units operate completely independently of each other, each  
unit supplying its respective share of the load.  
4.2 Partial Load Operation  
Single inverters that are not needed to supply the load can be  
switched off automatically, thus saving energy and increasing  
system efficiency.  
• The load is supplied by the remaining inverters  
• All rectifiers will continue to operate, charging also the batteries  
of the units whose inverters have been switched off  
• The system can be easily programmed for the minimum  
number of units which must supply the load at any time.  
• When the load is reduced, the units will individually decide  
which one is to switch off automatically.  
• The system may be programmed so that there will always be  
one redundant unit on-line.  
• If the load is again increased, or in the case of an inverter  
failure, the unit(s) which have been switched off will automati-  
cally switch on again to share the load.  
• If the mains supply fails, all inverters will switch on and connect  
to the load in parallel operation in order to maximise the battery  
autonomy time, (see section 4.3)  
JUE 401266  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
4 Operating Modes Parallel and Parallel/Redundant  
Operation  
4.3 Battery Operation  
The "Battery Operation" mode is activated by a mains failure or  
rectifier failure  
• The rectifiers supply no power  
• The batteries supply the required d.c. power to the inverters  
• The inverters supply a.c. power to the load as described in 4.1  
• Power will only be supplied to the load for a certain period of  
time depending on the battery capacity  
• If there were stand-by units switched off at the time of the  
mains failure, all units will automatically switch ON in order to  
extend the battery autonomy time.  
4.4 Operation with an Inverter Failure  
This operating mode is activated by a failure in one or more invert-  
ers.  
• As long as the load is not too great for the remaining units, the  
parallel system will stay in UPS (inverter) operation mode,  
otherwise see 4.5.  
• The static inverter-switch(es) (SSI) of the defective unit(s) will  
open automatically, separating them from the load-busbar  
• The rectifier(s) of the defective unit(s) will supply d.c. power to  
the battery (batteries) only if the respective rectifier is not  
defective.  
JUE 401266  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
4 Operating Modes Parallel and Parallel/Redundant  
Operation  
4.5 Bypass Operation  
The "Bypass Operation" mode is activated by a multiple inverter  
failure or overload  
• If the load is greater than 110% of the load capacity of all  
available inverters, the static bypasses of all individual units  
will connect the load with the mains directly  
• All inverter output switches (SSI) will open, inverters may  
continue to operate  
• The rectifiers continue to charge the batteries  
• If the load is reduced to 100% or less of the load capacity of all  
available inverters, the system switches automatically back to  
normal operation  
• All bypasses always switch on together.  
• If a standby unit was off at the time of the inverter failure/  
overload, it will automatically switch ON and all units take-over  
the load.The operation then becomes as in paragraph 4.1  
(when there was an overload) or as in paragraph 4.4 (when an  
inverter failure occurred).  
4.6 Maintenance Bypass Operation  
The "Maintenance Bypass Operation" mode is used to supply the  
load directly from mains during maintenance or repair work.  
• During this mode, the individual functional components are  
completely separated from the load (e.g. for maintenance work)  
• Power for the load will be supplied directly from mains through  
internal or external power switch(es) (IBY)  
Note: If the 3-position maintenance bypass cabinet MB3/2 is  
installed, the UPS system may be totally isolated from all  
supply by switching to the 3rd position "UPS ISOLATED".  
Again the load will be supplied through the maintenance bypass  
switch.  
JUE 401266  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
5
OPERATING INSTRUCTIONS  
5.1 Switching On the UPS System / from  
Maintenance Bypass  
Initial UPS Operating Mode:  
The UPS is switched off, the load may or may not be supplied by  
maintenance bypass, IBY and all other power switches are open.  
Operating Steps:  
A:  
• Switch on the external mains supply for the UPS; both the  
rectifier input and the bypass input when separate supplies are  
provided.  
• Open the UPS front door or the part necessary to allow access  
to the switches IRP, IRE, IUG and IBY.  
IBY:  
IRP:  
If the b ypass switch IBY, is not already on, close it now (for  
parallel systems with internal maintenance bypasses see Note  
1 page11) The load is now supplied by the maintenance by-  
pass.  
• Close the IRP switch.  
The rectifier starts and the UPS performs a self-test.  
The UPS operating panel will beep 3 times and test all the  
LEDs. The audible alarm may continue beeping and can be  
muted by pressing "RESET" once.  
IUG:  
IRE:  
IB:  
• Close the IUG switch.  
• Close the IRE switch.  
• Close the battery switch IB.  
Repeat A above, for all units within the system (Hot-standby and  
Parallel systems).  
• Check that the LEDs for the bypass and the output are illumi-  
nated.  
B:  
IBY:  
• Open the IBY switch inside all units (or within the External  
Maintenance Bypass cabinet if installed).  
RESET:  
START:  
• Press the pushbutton "RESET" on the operating panel of any  
unit.  
• Press the pushbutton "START" on the operating panel of all  
units within the system. The inverter(s) will start and will switch  
over to take the load when ready (SSI closes).  
Note: The pushbuttons "START" and "RESET" must be depressed  
for about 1 sec.  
JUE 401266  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
Final UPS Operating Mode:  
The UPS is now in normal operating mode, as described in chapter  
"2.1. Stand-alone unit", "3.1 Hot standby systems" or "4.1 Parallel  
systems". The green LEDs (L1, L2, L5, L3, L16, L17, L26, L19) on  
the operating panel(s) must be illuminated (but not flashing).  
Should a problem arise during the Switching On, please follow the  
instructions in JUE 401066, Initial Start-up.  
Note 1: For Parallel Systems.  
If the bypass is off, the output is not supplied and the system has  
multiple internal maintenance bypasses and the load is connected,  
the load may be excessive for one bypass only. In this case, it is  
better to switch off the load or proceed further without switching on  
IBY (the static bypasses will only switch on together when enough  
are ready to take the load.)  
JUE 401266  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
5.2 Switching Off the UPS System / to Main-  
tenance Bypass  
Initial UPS Operating Mode:  
The UPS is in any operating mode described in the previous  
sections "Operating Modes" (except maintenance bypass opera-  
tion). All power switches except IBY are closed, and the load is fed  
either through the inverter or the static bypass.  
Operating Steps:  
A:  
• Make sure that the LEDs 14 and 26 "Bypass Power Supply  
O.K." and "Bypass available" are illuminated and not flashing.  
CPHC16-S:  
IBY  
• Press the pushbutton on the CPHC16 -S pcb to commutate to  
the bypass supply.  
The UPS or all UPS modules (Hot-standby, parallel) switch to  
"Bypass Operation" mode. The yellow LED 18 lights up.  
• After LED 18 is illuminated, close the IBY switch.  
The load is now supplied by the static bypass and the maintenance  
bypass in parallel. If more than one IBY switch is present, close all  
switches.  
IUG:  
IB:  
B:  
• Open the IUG switch.  
• Open the battery switch IB.  
• Open the IRE switch.  
• Open the IRP switch.  
IRE:  
IRP:  
After opening the IRP switch the display is only powered by the DC  
capacitors and will fade out within a few minutes.  
C:  
• Repeat the steps in B for all units present.  
Note: If the optional SOLA external maintenance bypass switch  
(MB3/2 - version 2) is installed, it is not necessary to perform  
step B if the switch is switched directly to position 3 "UPS  
ISOLATED" in step A  
.
JUE 401266  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
5.3 Switching On any one unit within a Sys-  
tem (Parallel and Hot-standby Systems)  
Initial UPS Operating Mode  
The UPS module was switched off using the procedure in section  
5.4, all of the power switches in this module are in the off position,  
the load is supplied by the remaining unit(s) within the system.  
• If this UPS module has an input supply separate to the other  
units in the system, switch on the external mains supply for this  
UPS module; both the rectifier input and bypass input when  
separate supplies are provided.  
• Open the UPS front door, or the part necessary to allow access  
to the switches IRP, IRE, IUG.  
WARNING: ENSURE THAT THE IUG AND IRE SWITCHES ARE OPEN.  
IRP:  
IUG:  
• Close the IRP switch. The rectifier starts and the UPS performs  
a self test. The UPS Operating Panel will beep 3 times and test  
all the LEDs. The audible alarm may continue beeping and can  
be muted by pressing "RESET" once.  
• Close the IUG switch.  
NOTE: IN ORDER NOT TO AFFECT SYSTEM PERFORMANCE, IT IS IMPOR-  
TANT TO CLOSE IUG NOW.  
IRE:  
IB:  
• Close the IRE switch.  
• Close the battery switch IB.  
IPR:  
S1  
• If present, ensure that the micro switch S1 at the bottom of the  
IPR pcb is in the AUTO position.  
START:  
• Press the pushbutton "START" on the Operating Panel. The  
inverter will start. The LED 16 will flash red and 10 seconds  
later will turn green and be permanently lit.  
RESET:  
• Press the pushbutton "RESET" on the Operating Panel.If not  
already on, the green LED 17 will turn on and the LED 29 must  
switch off.  
The UPS module is now in normal operating mode, connected in  
parallel with the remaining units in the system (parallel systems,  
section 4.1 or 4.2) or ready to take over the load in the case of an  
.
inverter failure (hot-standby systems, section 3.1)  
JUE 401266  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
5.4 Switching Off / any one Unit within a Sys-  
tem (Parallel and Hot-standby Systems)  
Initial UPS Operating Mode:  
The UPS is in any operating mode described in the previous  
sections "Operating Modes". All power switches except IBY are  
closed, and the load is fed either through the inverter or the static  
bypass.  
IPR:  
S1  
• At the bottom of the IPR pcb (if present), switch the  
microswitch S1 to the manual position.  
ICP:  
PB2  
• At the top of the ICP pcb, press the pushbutton PB2.  
IRE:  
IUG:  
• Open the IRE switch.  
• Open the IUG switch.  
NOTE: IN ORDER NOT TO AFFECT SYSTEM PERFORMANCE, IUG MUST BE  
OPENED AT THIS MOMENT.  
IB:  
• Open the battery switch IB.  
IRP:  
• Open the IRP switch.  
The rectifier voltage will slowly discharge and all the LED(s) on the  
front panel will switch off. When all the LED(s) on all the internal  
pcbs are off, the UPS module is free from voltage except at the  
inputs of IRP, IRE and IBY and at the outputs of IUG and IBY and  
at the respective terminals.  
If this UPS module has an input supply separate to the other units  
in the system, the input supply switch(es) to this module may now  
be opened.  
Final UPS Operating Mode:  
The UPS module is now shut down. The load is supplied by the  
remaining module(s) within the system.  
Attention! Even when the input supply to the UPS module is  
isolated, there will still be voltage present at the output terminals  
and the output of the switches IUG and IBY (from the remaining  
modules within the UPS system).  
JUE 401266  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operation  
5 Operating Instructions  
5.5 Emergency Power Off  
Operating Steps:  
• To activate the Emergency Power Off, press simultaneously  
the two pushbuttons in the E.P.O. section of the operating  
panel (For hot-standby and parallel systems, the operation  
needs to be performed at one unit only).  
Attention! This operation will remove all supply to the load.  
Emergency Shut Down:  
When E.P.O. is activated, all static switches SSI and SSB and the  
battery switch(es) IB (when connected with a trip circuit) are  
opened, the rectifier(s) and inverter(s) are switched off. The Data  
Monitor Panel / NCP will lose supply when the internal DC filter  
capacitors discharge.  
Attention! Although the load is no longer supplied by the UPS, the  
input and output switches are still closed. Voltage is still present in  
the UPS unless the input circuit breaker(s) have a shunt trip circuit  
connected with the EPO circuit (see JUE 401066 "Installation and  
Initial Start-up", section 1.5).  
Reset after Activating E.P.O.  
• To restart the UPS press the RESET push-button PL2 located  
on the CPU / NCP pcb inside the front door of the UPS. This  
releases the EPO circuit and the rectifier will restart.  
RESET:  
Note that if the input switch(es) were automatically tripped, it is  
sufficient to reclose the switch(es) without the need to press the  
reset pushbutton above.  
• Press the pushbutton at the front of the CPHC16-R pcb at the  
right side of the UPS control electronic.  
IB:  
• After the front panel is illuminated, close IB.  
• Repeat for all units in the system.  
• Press the "RESET" button for one second on the operating  
panel.  
• Press the "START" button for one second on the operating  
panel and repeat for all units in the system (if multiple units are  
present).  
Final UPS Operating Mode:  
The UPS is returned to normal operation, and all power switches  
except IBY are closed.  
JUE 401266  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401267  
SOLA 4000 - Operating Panel  
Chapters  
Figures  
1
FUNCTIONS  
2
1.1 Indication of Important Data  
2
2
3
3
3
4
FIG. 2.1 LED Indication  
5
9
1.2 Battery Monitoring  
FIG. 3.1 RS232 connection cable  
FIG. 4.3 Layout of the CPU/NCP pcb  
FIG. 5.1 Setting of DIP1  
1.3 UPS Operating Mode Indication  
1.4 Alarm Signalling  
16  
19  
1.5 Remote Monitoring  
1.6 Emergency Power Off  
Tables  
2
3
LED INDICATION  
5
TAB 4.1 Setting of SW1 - UPS rating  
TAB 4.2 Setting of SW1  
14  
14  
COMMUNICATION WITH A PC 9  
3.1 Connection to PC  
3.2 SNMP mode  
3.3 Service Mode  
3.4 Alarms  
9
10  
10  
11  
13  
13  
TAB 4.3 Setting of SW1 - Nominal Voltage 14  
TAB 4.4 Setting of SW2 15  
3.5 UPS status  
3.6 Metering  
4
5
PANEL SETTINGS  
14  
4.1 DIP Switch Settings  
14  
4.2 Location of DIP switches and pushbuttons  
on the CPU/NCP pcb  
16  
REMOTE PANEL  
17  
5.1 General  
17  
17  
18  
19  
5.2 Installation  
5.3 Functions  
5.4 DIP-switch settings  
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
04.02.97  
20.06.97  
01.09.97  
ISSUED  
See Rev. Doc. JSE 401440  
See Rev. Doc. JSE 401490  
M. Porpora  
T. Boon  
04.02.97  
A4  
1
19  
A
B
T. Boon  
M. Porpora  
JUE 401267  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
1 Functions  
1
FUNCTIONS  
1.1 Indication of Important Data  
Actual Load The actual load of the UPS is indicated as a percentage of its  
nominal load capacity.  
Battery Charging Status While the battery is being charged (green LED 5 on), the actual  
charging status of the battery is indicated as a percentage of the  
nominal battery capacity.  
Battery Autonomy While the battery is being discharged (yellow LED 4 on), the actual  
battery autonomy is indicated as a percentage of the nominal  
battery autonomy.  
1.2 Battery Monitoring  
Low Battery The Low Battery alarm indicates that only 20% of the battery  
autonomy is left. The colour of the LEDs for battery autonomy  
indication changes from green to red. In addition the alarm buzzer  
beeps.  
The SOLA 4000 UPS automatically performs a battery test every  
30 days.  
Battery Test  
Whenever the test shows that the battery is damaged or its capac-  
ity is reduced, the red LED "BATTERY TEST", located on the  
operating panel is illuminated and the buzzer beeps.  
This test is of vital importance, since it monitors the battery, warn-  
ing of possible failures caused by reduced battery autonomy due to  
defective batteries.  
However this function can be deactivated with DSW2 - 3 on the  
CPU/NCP pcb inside the UPS front door. In this case the LED  
"BATTERY TEST" is off.  
JUE 401267  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
1 Functions  
1.3 UPS Operating Mode Indication  
On the operating panel a block diagram of the UPS is shown. The  
operating mode of the UPS is indicated with LEDs integrated into  
the block diagram.  
LED Off If a LED is not illuminated at all, the corresponding section is not  
active.  
If a LED is continually illuminated (green), the corresponding  
section is o.k.  
LED On, Green  
LED Flashing, Green If a LED is flashing (green), the corresponding section is not o.k.,  
but the power supply to the load is not currently endangered.  
LED On, Yellow The corresponding section is OK, but it is not the nominal working  
condition of UPS.  
LED Flashing, Red If a LED is flashing (red), the corresponding section is not o.k., and  
the power supply to the load is endangered.  
1.4 Alarm signalling  
By the UPS Alarms are signalled by the UPS using LEDs and an audible alarm:  
• Status LEDs signal an alarm by flashing.  
• The integrated buzzer signals an alarm by beeping.  
• The buzzer can be muted by pressing "Alarm Reset" at the  
operating Panel. The LEDs continue flashing when the alarm  
condition is still active.  
There are two different types of alarm signals:  
• The flashing LED is green and the buzzer beeps slowly if the  
power supply to the load is not currently endangered (common  
alarm flashing - yellow).  
• The flashing LED is red and the buzzer beeps fast if the power  
supply to the load is endangered (common alarm is flashing  
red).  
1.5 Remote Monitoring  
The operating panel provides an option to communicate with a  
computer through RS232 and RS485 interfaces. The RS232 serial  
interface communicates with a PC or mainframe computer, with a  
SNMP protocol (SEC). With the RS485 interface it is possible to  
transmit all necessary data up to a distance of 400m or to connect  
a remote monitoring panel.  
JUE 401267  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
1 Functions  
1.6 Emergency Power Off  
In case of emergency it is possible to switch off the complete UPS  
system. This is done by simultaneously pressing the "EMER-  
GENCY POWER OFF" (E.P.O.) push-buttons located on the  
operating panel. This function provides UPS disconnection from  
the load and galvanically isolates the UPS from the battery.  
In the case of parallel and hot-standby configurations, activating  
EPO on one unit automatically switches OFF the entire system  
(when IUG is closed on that unit).  
When E.P.O. is activated, dangerous voltages will still be present  
within the UPS cabinet unless the input supply circuit breaker(s)  
have a shunt trip circuit connected with the EPO circuit (see JUE  
401066 section 1.5).  
JUE 401267  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
2 LED Indication  
2
LED INDICATION  
The block diagram of the UPS, with integrated LEDs, allows a  
quick check of the UPS operating status.  
FIG. 2.1 - LED Indication  
JUE 401267  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
2 LED Indication  
MAINS PRESENT  
LED 1  
• Green LED is continually illuminated = Mains O.K.(rectifier).  
• Green LED flashing slowly + BUZZER beeping slowly (approx.  
every 2 sec.) = Mains is not O.K.  
RECTIFIER  
• LED off = Rectifier is not supplied  
• Green LED is continually illuminated = Mains and rectifier O.K.  
• Red LED flashing fast + BUZZER beeping fast (every sec.) =  
Rectifier failure  
LED 2  
LED 3  
BATTERY SWITCH  
• Green LED is continually illuminated = Battery switch closed  
• Green LED flashing fast + BUZZER beeping fast (every sec.) =  
Battery switch open  
BATTERY DISCHARGING  
• Yellow LED is continually illuminated = Battery feeding inverter  
• Otherwise LED is off.  
LED 4  
LED 5  
BATTERY CHARGING  
• Green LED is continually illuminated = Battery charging  
• Otherwise LED is off.  
LED 14 BYPASS POWER SUPPLY  
• Green LED is continually illuminated = Mains O.K.(Bypass  
supply).  
• Green LED flashing slowly + BUZZER beeping slowly = Mains  
out of order or not present, or IRE open.  
LED 15 MAINTENANCE BYPASS SWITCH  
• Red LED is continually illuminated = Maintenance bypass  
switch closed  
Note: For parallel and hot-standby systems, it may be any  
maintenance bypass within the system that is closed.  
• Otherwise LED is off.  
LED 16 INVERTER  
• Green LED is continually illuminated = Inverter O.K.  
• Red LED flashing fast + BUZZER beeping fast = Inverter  
failure  
• LED is off = inverter is switched off.  
LED 17 LOAD FED BY INVERTER  
• Green LED is continually illuminated = Load fed by inverter  
• Red LED flashing and can be reset with the "RESET"  
pushbutton; buzzer beeping = Retransfer blocked  
• Otherwise LED is off.  
JUE 401267  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
2 LED Indication  
LOAD FED BY BYPASS POWER SUPPLY  
LED 18  
• Yellow LED is continually illuminated = Load fed by static  
bypass  
• Otherwise LED is off.  
LOAD IS SUPPLIED  
LED 19  
LED 27  
• Green LED is continually illuminated = Load fed either by  
inverter or by static bypass and IUG is closed  
• Otherwise LED is off.  
BATTERY TEST  
This test is only performed if the batteries are fully charged. Other-  
wise the test is skipped and performed in the following month.  
• LED off = BATTERY TEST function not active  
• Green LED is continually illuminated = BATTERY TEST func-  
tion activated, but UPS is not performing the test  
• Green LED flashing slowly = BATTERY TEST running  
• Red LED flashing fast + BUZZER beeping fast = BATTERY  
TEST failed. Test battery capacity.  
E.P.O.  
LED 28  
LED 26  
• Red LED is continually illuminated = E.P.O. has been activated  
Note: For parallel and hot-standby systems, EPO may be have  
been activated at any unit.  
STATIC SWITCH  
• Green LED continually illuminated = Bypass available  
• Green LED flashing = Bypass not synchronised but the mains  
is OK  
• LED off = Mains not OK  
BATTERY INDICATOR  
LEDs  
a) During the charging phase (green LED L5 ON)  
• Green LEDs continuously illuminated indicate the actual battery  
autonomy as a percentage of the nominal battery autonomy,  
depending on the actual load and battery charging status.  
b) During the discharging phase (yellow LED 4 ON)  
• If, during the discharging phase, the actual battery autonomy  
goes below 20% autonomy, the system signals the alarm "Low  
Battery ".  
- The BUZZER beeps continually.  
- The colour of the "battery indicator" LEDs changes from green to  
red.  
• The actual autonomy is signalled by the flashing of the corre-  
sponding LED.  
• When the LED corresponding to 0% autonomy starts flashing:  
- The buzzer beeps continually and cannot be muted.  
- The inverter will cease to operate soon.  
JUE 401267  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
2 LED Indication  
LOAD PERCENTAGE  
The actual load is indicated by LEDs as a percentage of the nomi-  
nal load.  
• All LEDs off  
=> Actual load = 0 - 10%  
• Green LED 20% cont. illumin. => Actual load = 10 - 30%  
• Green LED 40% cont. illumin. => Actual load = 30 - 50%  
• Green LED 60% cont. illumin. => Actual load = 50 - 70%  
• Green LED 80% cont. illumin. => Actual load = 70 - 90%  
• Green LED 100% cont. illumin. => Actual load = 90 - 100%  
• Red LED 125% cont. illumin. => Actual load = 100 - 125%  
- The UPS is in an overload condition.  
- The buzzer is beeping continually and cannot be muted.  
COMMON ALARM  
LED 29  
• Red LED continually illuminated and BUZZER beeping fast =  
any of the following conditions:  
- Inverter Failure  
- Battery Switch Open  
- Low Battery  
- Rectifier Failure  
- Paralleling Fault  
- Inverter not synchronised (with the bypass supply or internal  
oscillator)  
- Retransfer blocked  
- Overtemperature  
- Battery Test Failed  
- Inverter not Feeding and bypass off (not active for hot-  
standby)  
- Bypass system not available (but bypass of this unit is avail-  
able when more than one bypass is installed)  
• Yellow LED continually illuminated and BUZZER beeping  
slowly = any of the following conditions:  
- Mains Failure (rectifier)  
- Mains Failure (bypass)  
- Battery Discharging  
- Bypass not available  
- Overload  
- Load on Bypass (SSB closed)  
- Inverter not synchronised (with the bypass supply )  
- Auxiliary Alarm  
• Otherwise the LED is off  
BOOST CHARGE  
LED 30  
• Green LED on = Boost charge active  
• Otherwise LED is off.  
JUE 401267  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
3 Communication with a PC  
3
COMMUNICATION WITH A PC  
3.1 Connection to PC  
The UPS is connected to the PC via the RS232 interface. The  
respective connector is the female 9-pin sub-D connector on the  
CPU/ NCP pcb on the inside of the UPS front door. At the PC a  
serial port is used which can either be a male 9-pin sub-D connec-  
tor or a male 25-pin sub-D connector.  
Cable Specification For connecting the PC and UPS use twisted pair, 24 AWG shielded  
cable. Connect the shield to ground at the PC and at the UPS.  
FIG. 3.1 - RS232 connection Cable  
JUE 401267  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
3 Communication with a PC  
3.2 SNMP MODE  
With DIP7 of SW2 in the ON position, the UPS can be monitored  
and controlled from a remote location by a PC through a SNMP  
protocol converter. In this mode, software packages such as  
Ò
SMARTMON from Systems Enhancement Corporation may be  
directly applied using a P.C.  
The software runs on PCs with the following Operating systems:  
MICROSOFT WINDOWS  
MICROSOFT WINDOWS FOR WORKGROUPS  
MICROSOFT WINDOWS 95  
MICROSOFT WINDOWS NT  
IBM OS/2  
The software allows:  
- UPS monitoring  
- Event logging  
- Broadcasting  
- Paging  
- E - Mail (only for Windows 95)  
The use of a modem for remote monitoring is also possible.  
The UPS can be connected to a LAN and monitored through an  
SNMP protocol.  
An external Hardware interface is required to perform the protocol  
conversion from SEC protocol to SNMP protocol.  
3.3 Service Mode  
This mode is intended as a test mode and is used during testing /  
maintenance of all units. It is activated by setting DIP 7 of SW2 in  
the OFF position.  
PC Requirements  
• A program is available for testing / service purposes.  
• The communication parameters must be set as follows:  
BAUD  
PARITY  
BITs  
=
=
=
=
1200  
OFF  
8
STOP BITs  
1
JUE 401267  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
3 Communication with a PC  
3.4 Alarms  
With a connected PC, the following alarms are realised (SNMP and  
service modes):  
Rectifier Failure The Rectifier mains is in order but a failure is present within the  
rectifier.  
Inverter Failure The inverter is ON but the inverter voltage or inverter conditions  
are not in order.  
Battery Switch OFF The battery switch is OFF  
The inverter has attempted unsuccesfully to take over the load at  
least 5 times within 3 minutes.  
Retransfer blocked  
To reset, press the "RESET" pushbutton a second time after  
muting the alarm.  
Overtemperature The inverter/rectifier components are operating at an excessive  
temperature. This can be due to extreme environmental conditions  
or a failure within the inverter or rectifier sections.  
If the bypass is available the UPS transfers immediately to the  
bypass supply (in the case of a hot-standby system, the second  
unit takes over the load, in the case of a parallel system the re-  
maining inverters take over the load). If the bypass or another  
inverter is not available then the UPS will continue to supply the  
load for a further 10 minutes before shutting down.  
Mains Failure The mains is not present or not within the specified voltage and  
frequency tolerances.  
Inverter not Feeding The inverter is not feeding the load and the bypass static switch,  
SSI is OFF.  
The mains or rectifier has failed and the batteries are  
discharging.This alarm is activated at a battery voltage of approx.  
360Vdc.  
Battery Discharging  
Low Battery The remaining battery capacity during discharge has been calcu-  
lated to be less than 20% of the nominal capacity.  
Battery Test Failed The routine battery test has detected a decrease in capacity of the  
battery. The battery must be checked.  
Paralleling Fault The inverter has failed to regulate correctly in parallel operation  
with another inverter (parallel systems only).  
Bypass not Available The bypass mains supply is OK but the bypass is not available to  
take the load if the inverter fails (the inverter is not synchronised or  
is blocked externally).  
JUE 401267  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
3 Communication with a PC  
For systems with multiple static bypasses (hot-standby and paral-  
lel/redundant), if the bypass of this unit is available, but the bypass  
system is not available, the UPS system cannot transfer to the  
bypass supply, due to the fact that there may be insufficient by-  
passes available within the system.  
Overload The UPS is overloaded by more than the nominal output load  
current  
Load on Bypass The UPS system load is being supplied by the bypass supply.  
Inverter not synchronised The inverter is not synchronised to the bypass supply.  
Auxiliary Alarm This alarm consists of a series of system alarms and includes the  
following:  
Oscillator failure  
A failure has occurred in the oscillator circuit or a loss of  
synchronism with another oscillator of another unit within the  
system.  
IUG monitoring failure  
An error has occurred within the monitoring circuit of the output  
switch (disabled for single units).  
Static switch failure (SSI)  
A failure has occurred within the monitoring circuit of the  
inverter output static switch.  
Static switch failure (SSB)  
A failure has occurred within the monitoring circuit of the  
bypass static switch.  
Missing or incorrect bypass trip signal (parallel and hot-  
standby systems)  
An indifference has occurred within the bypass trip logic of this  
unit and the remainder of the system.  
System not redundant (parallel /redundant systems)  
If the inverter of the unit signalling this alarm fails, the system  
must transfer to the bypass supply.  
SSI-ON generator failure (parallel/redundant systems)  
A failure or loss of synchronism has occurred with the SSI ON  
pulse generator on IPR pcb and may occur during start-up of a  
unit in a parallel system. To reset press "START" and then  
"RESET".  
To determine which of the alarm(s) are present refer to the section  
"PCB Description" JUE 401069.  
JUE 401267  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
3 Communication with a PC  
3.5 UPS status  
Additionally to the above alarms, the following status conditions are  
realised:  
Boost Charge The rectifier is re-charging the battery with a boost charge (accord-  
ing to DIN 41773).  
The output switch (IUG) is OFF and the load is not supplied by this  
unit.  
Output Switch OFF  
Service Bypass ON The load is supplied by any of the maintenance bypass(es).  
3.6 Metering  
With a connected PC, the following measurements can be realised  
(SNMP and service modes):  
Vout(R)  
Vout(S)  
Vout(T)  
Vinv  
(UPS output voltage phase R)  
(UPS output voltage phase S)  
(UPS output voltage phase T)  
(Inverter output voltage - average of the three  
phases).  
I(R)  
(UPS output current phase R)  
I(S)  
(UPS output current phase S)  
I(T)  
(UPS output current phase T)  
Pout%  
Aut%  
(UPS output kVA in % of nom. kVA)  
(Battery autonomy in % of nom. autonomy)  
JUE 401267  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
4 Panel Settings  
4
PANEL SETTINGS  
4.1 DIP Switch Settings  
With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside  
the front door , the operating parameters can be set according to  
actual conditions.  
Note: The following settings apply only with the software V2.0 or  
later.  
DIP Switch SW1  
UPS RATING  
Dip 1 Dip 2 Dip 3 Dip 4  
(KVA)  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
10  
15  
OFF  
ON  
20  
ON  
30  
OFF  
ON  
OFF  
OFF  
ON  
40  
ON  
60  
OFF  
ON  
ON  
80  
ON  
ON  
100  
120  
OFF  
OFF  
OFF  
TAB. 4.1 - Setting of SW1 - UPS rating  
DIP Switch SW1  
DIP Switch SW1  
Nominal Voltage  
DIP 5 CONFIGURATION  
DIP 7 DIP 8 Vnom  
OFF  
ON  
Not Hot-standby  
Hot-Standby  
OFF  
ON  
OFF  
OFF  
ON  
120  
220  
230  
240  
DIP 6  
BYPASS - LINE  
OFF  
ON  
OFF  
ON  
Installed  
ON  
Not installed  
TAB. 4.2 - Setting of SW1  
TAB. 4.3 - Setting of SW1  
Nominal Voltage  
JUE 401267  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
4 Panel Settings  
DIP Switch SW2  
Dip 1  
AUDIBLE ALARM  
Audible alarm  
ENABLED  
OFF  
ON  
Audible alarm  
DISABLED  
AUTONOMY  
ALARM  
Dip 2  
OFF  
Autonomy alarm  
ENABLED  
Autonomy alarm  
DISABLED  
ON  
Dip 3  
OFF  
BATTERY TEST  
Battery test  
DISABLED  
Battery test  
ENABLED  
ON  
DIP 4 TIME CONSTANT  
FAST  
OFF  
ON  
NORMAL  
DIP 5  
OFF  
ON  
DIP 6  
OFF  
ON  
FREQUENCY  
60 Hz  
50 Hz  
REMOTE  
ACCESS  
DIP 7  
Service mode  
SNMP mode  
OFF  
ON  
Forced Battery  
Test  
(If DIP3=ON)  
DIP 8  
OFF  
ON  
Forced batt. test  
OFF  
Forced batt. test  
ON  
TAB 4.4 Setting of SW2  
JUE 401267  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
4 Panel Settings  
4.2 Location of DIP-switches and  
pushbuttons on the CPU/NCP pcb  
The CPU/NCP pcb is located inside the front door at the UPS  
cubicle.  
FIG. 4.3Layout of the CPU/NCP pcb  
PL1  
PL2  
Microprocessor RESET  
Emergency Power Off (E.P.O.) RESET  
JUE 401267  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
5 Remote Panel  
5
REMOTE PANEL  
5.1 General  
The Remote Panel is used for remote monitoring of SOLA 4000  
systems for distances of up to 400m. It is connected by cable via a  
RS485 interface. It can be installed in a control room and provides  
the same user interface as the local operating panel.  
Only the E.P.O. function is not implemented.  
5.2 Installation  
The Remote Panel is connected to the UPS by a shielded cable  
4x0.5mm of max. 400m length with 9-pole sub-D connectors.  
9-pole male sub-D connector,  
fits in the UPS local panel  
9-pole male sub-D connector, fits  
in the remote panel  
The Remote Panel is mounted in a box (270x160x80mm).  
The Remote Panel is supplied by an external power supply 220/  
230/240 Vac, 50 Hz (which must be connected to the output of the  
UPS).  
The connection between the UPS and the Remote Panel is pro-  
vided by a Keyboard 5-Wire Jack.  
For the Remote Panel housing the same colour is used as for the  
SOLA 4000 cabinets.  
JUE 401267  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
5 Remote Panel  
5.3 Functions  
The Remote Panel provides the same LED indications as the  
SOLA 4000 operating panel. Alarms are indicated by flashing LEDs  
and an integrated buzzer. The alarms can be muted directly at the  
Remote Panel by pressing the "Alarm Reset" push-button.  
General  
The buzzer can be deactivated by setting switch 2 of DIP1 to the  
Off position. The inverter can be switched on from the remote  
panel but cannot be switched off.  
Automatic alarm phone calls The Remote Panel can be connected to an external modem  
through the RS232 DB9 connector, in order to perform an auto-  
matic phone call to one or two programmed phone numbers (corre-  
sponding to Computers in host Mode), in case of one of the below  
listed alarm conditions:  
• RETRANSFER BLOCKED  
• BATTERY TEST FAILURE  
• INVERTER FAILURE  
• LOAD ON BYPASS  
• RECTIFIER FAILURE  
The automatic call feature is enabled by setting switch 3 of DIP1 to  
the ON position.  
One computer can receive alarm messages from 8 different Re-  
mote Panels. The Remote Panels (and hence the connected UPS)  
can be identified by a number from 1 to 8 which is binarily pro-  
grammed by setting the switches 6,7 and 8 of DIP1.  
In case of an alarm at a certain UPS the corresponding Remote  
Panel calls the computer and transmits a two line alarm message  
(ASCII characters) with the following structure:  
UPS x  
x =1...8 identifies the UPS  
Alarm condition One or more of the above listed alarms  
Programming of phone numbers In case of an alarm one or two phone numbers may be called  
automatically, i.e. the UPS status may be monitored by one com-  
puter only or by two different computers. With switch 4 of DIP1 the  
number of computers to be called can be set.  
To program the phone numbers to be called connect a PC with a  
serial interface to the RS232 DB9 connector on the rear side of the  
Remote Panel and run a terminal program.  
Type  
P1XXXXX...X[CR] to program the first phone number (XXXXX...X)  
P2YYYYY...Y[CR] to program the second phone number (YYYYY...Y)  
Each phone number may contain up to 20 digits.  
To read programmed phone numbers from the panel type  
N1[CR]  
The Remote Panel responds with the first number:  
N1=XXXXX...X  
N2[CR]  
The Remote Panel responds with the second number:  
N2=YYYYY...Y  
The programmed numbers are stored in an EEPROM and are thus  
protected against power failures and CPU resets.  
JUE 401267  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Operating Panel  
5 Remote Panel  
Communication timing When an alarm condition occurs, the Remote Panel calls the first  
programmed number.  
If the line is busy and only one number is to be called, the Remote  
Panel waits for 5 minutes and, if the alarm condition is still present,  
it tries to call the number again. This procedure will be repeated  
until the connection has been established or the alarm condition  
ends.  
If the line is busy and two numbers are to be called, the second  
number will be called. If this line is also busy the first number will  
be tried again and so on.  
After a successful connection the Remote Panel will normally hold  
the line for five minutes. Any additional alarm messages that are  
activated during that time will be displayed automatically at the  
computer display and one minute will be added to the remaining  
connection time. The maximum connection time is, however,  
limited to ten minutes.  
If during the connection all alarms are deactivated, the Remote  
Panel sends the following messages:  
UPSx  
followed by:  
UPS OK  
and the remaining connection time is set to one minute.  
5.4 DIP-switch settings  
DIP Switch DIP1  
switch 1  
ON  
Not used  
OFF  
switch 2  
ON  
Local buzzer  
active  
OFF  
not active  
switch 3  
ON  
Automatic call  
active  
OFF  
not active  
switch 4  
ON  
Phone numbers  
two phone numbers  
one phone number  
Not used  
OFF  
switch 5  
ON  
-
OFF  
-
UPS number for  
identification  
sw. 6 sw. 7 sw. 8  
ON  
OFF  
ON  
ON  
ON  
ON  
ON  
1
2
3
4
5
6
7
8
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
FIG. 5.1 - Setting of DIP1  
JUE 401267  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401268  
SOLA 4000 - PCB Description  
Chapters  
Figures  
1
UPS CONTROL LOGIC  
1.0 UPS Control Logic  
1.1 Legend of symbols used  
1.2 Rectifier  
2
2
FIG. 1.1 - IF/PS - R front view  
FIG. 1.2 - CPHC16 - R front view  
FIG. 1.3 - ICP front view  
3
4
2
3
6
1.3 Inverter  
5
FIG. 1.4 - ICT-2 front view  
FIG. 1.5 - IPS-500 front view  
FIG. 1.6 - IPR front view  
7
1.4 Bypass  
10  
8
9
FIG. 1.7 - IF/PS - S front view  
FIG. 1.8 - CPHC16 - S front view  
11  
12  
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
20.06.97  
23.09.97  
See Rev. Doc. JSE 401440  
See Rev. Doc. JSE 401547  
A
B
T. Boon  
T. Boon  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
1
UPS CONTROL LOGIC  
1.0 UPS Control Logic  
The UPS Control logic is situated in the centre of the front part of  
the UPS. It consists of one rack with 7-8 PCBs (depending on the  
system configuration). On the covers of the rack, the various  
potentiometers, test points and LEDs are briefly labelled.  
A more detailed explanation is given in this chapter.  
1.1 Legend of symbols used  
LED (light emitting diode)  
- GREEN: normal condition  
- RED: alarm condition.  
- YELLOW: warning  
Potentiometer  
Test Point  
- For adjustment  
(only for qualified personnel)  
- Requires a pin 2mm for  
measurement.  
Test point/switch  
Pushbutton  
- Insertion of a 2mm Pin disables  
the described function  
- Performs a reset or switching  
operation  
Micro switch  
- Switch from manual to auto  
matic mode  
JUE 401268  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
1.2 Rectifier  
The rectifier control logic consists of two PCBs.  
IF/PS - R Rectifier electronic power supply  
• input voltage sensing  
• rectifier electronics power supply  
Rectifier control and regulation  
CPHC16 - R  
• rectifier output voltage regulation  
• rectifier output current limitation  
• soft-start control  
• battery charging current limitation  
• generation of the thyristor firing pulses  
• input voltage monitoring (phase rotation, mains failure)  
• control for parallel rectifiers (with a common battery)  
• 12-pulse rectifier control  
• Second level current limitation for diesel-generators.  
• Boost charging according to DIN 41773.  
• Thermal compensation.  
IF/PS - R Front View FIG. 1.1 illustrates the LEDs of the IF/PS - R PCB which are  
accessible from the front.  
PSPA  
+ 12V analog circuits power supply OK  
PSPP  
+ 16V microprocessor power supply unregulated  
PSPA1  
+ 12V interfaces power supply  
+ 15V auxiliary LEM power supply (illuminated only for 12  
pulse configuration)  
+ 15  
- 15V auxiliary LEM power supply (illuminated only for 12 pulse  
configuration)  
- 15  
JUE 401268  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
CPHC16 - R Front View FIG. 1.2 illustrates the display, switches and connectors of the  
CPHC16 - R PCB which are accessible from the front.  
- 7 segment display for diagnostics (see table below)  
DIAGNOSTICS  
- Reset max. Vdc pushbutton: press when the character "4" is  
displayed or the central segment is blinking.  
RESET MAX. Vdc  
- Reset Boost Charge Alarm  
- Reset after EPO (V2.1)  
RS 232  
- RS232 connector (male)  
RS 485  
- RS485 connector (female)  
Priority  
Indication  
Diagnostics  
1
2
8
2
E²PROM failure  
Fuse blown  
3
C
P
3
Mains not OK  
Wrong phase rotation  
Overtemperature  
Overvoltage  
4
5
6
4
7
Ø
9
Pulse release missing  
Rectifier failure  
Fan failure  
8
9
6
10  
L
--  
Overload  
Boost charge  
(when blinking)  
Has left the boost  
charge due to a given  
time limit but the  
"--"  
battery was not  
completely charged.  
Reset with "RESET  
max. Vdc" above.  
JUE 401268  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
In normal condition the display shows a red seg-  
ment rotating clockwise. During the starting phase,  
a blinking central segment "-" is displayed. During  
parameter acquisition through the serial interface,  
the character "A" is displayed. If more than one  
alarm is present, only the one with the higher  
priority is displayed.  
1.3 Inverter  
The inverter control logic consists of three PCBs (four for parallel  
systems).  
ICP Inverter control  
• control for the inverter static switch (SSI)  
• temperature monitoring  
• inverter monitoring and protection  
• hot-standby control  
• quartz oscillator  
• fan monitoring  
• inverter electronic power supply monitor  
ICT-2 Inverter regulation  
• inverter output voltage regulation  
• inverter output current limitation  
• short-circuit protection  
• inverter soft start control  
• inverter-bypass synchronisation  
• inverter-oscillator synchronisation  
• synchronisation monitor:  
IPS - 500 Inverter electronic power supply  
• inverter electronic power supply  
• inverter input voltage monitoring  
• generation of the battery-discharging alarm  
JUE 401268  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
Inverter control and regulation (parallel configuration)  
• parallel regulation of up to 8 inverters  
• system control for up to 8 inverters (together with ICP pcb)  
• cold-standby control  
• load monitoring  
PB2 Inv. ON / OFF  
LD1 PSP OK  
• redundancy monitoring  
ICP Front View FIG. 1.3 illustrates the LEDs and switches of the ICP PCB which  
LD3 Osc. Failure  
are accessible from the front.  
- Push to switch the inverter ON/OFF  
PB1 Reset  
- Inv. electronic power supply in order: green LED is illuminated  
- Defect in the internal quartz oscillator: red LED is illuminated  
LD9 Inverter OK  
LD8 Inverter volts OK  
- RESET  
LD2 Retr. blocked  
LD4 Overtemperature  
- Inverter in order: green LED is illuminated  
LD5 SSI failure  
- Inv. voltage within tolerance (within +/- 10% of Vnom): green  
LED is illuminated  
LD6 Inverter ready  
- Retransfer to inv. operation is blocked after 5 attempts within 3  
minutes: red LED is illuminated  
- Overtemperature within the inv. section: red LED is illuminated  
LD7 IUG failure  
- The inverter static switch has failed to switch ON/OFF: red LED  
is illuminated  
S1 Osc. Block.  
- All conditions are in order for a retransfer of the load to the inv.  
(for hot-standby units, the inv. is ready in case of a failure to  
the on-line inv.): green LED is illuminated  
S2 Inverter Monit. Block.  
TP1 INV. Volts  
Vnom=6V  
P1 INV. Volts  
tol.adjust  
- A failure within the monitoring of the output switch: red LED is  
illuminated  
- Disable the quartz oscillator  
PB3 SSI ON  
- Disable inverter voltage monitoring  
JUE 401268  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
- Proportional to the inv. voltage. 6V º nominal inverter voltage  
- Inv. voltage tolerance adjust for 6V at TP1 with nom. voltage  
- Push to switch ON the inverter output static switch (SSI)  
P1 Freq.  
Offset  
P5 ΦT Volts  
ICT-2 Front View  
FIG. 1.4 illustrates the potentiometers, LEDs and test points of  
the ICT-2 PCB which are accessible from the front.  
P4 ΦS Volts  
P3 ΦR Volts  
P2 Manual Test  
- Frequency offset adjustment (when synchronisation is blocked  
at TP5)  
LD5 Overload Φ  
- Inverter voltage adjustment phase T  
- Inverter voltage adjustment phase S  
T
LD4 Overload Φ S  
- Inverter voltage adjustment phase R  
LD3 Overload Φ R  
LD2 Pulse Release  
- Inverter voltage adjustment during test operation (jumpers JP1,  
JP2, JP3 in position 2,3)  
LD1 Synch. OK  
- Overload on phase T: red LED is illuminated  
- Overload on phase S: red LED is illuminated  
- Overload on phase R: red LED is illuminated  
- Pulse release: green LED is illuminated  
TP5  
TP4 Inom= 6V  
TP3 Inom= 4V ΦT  
- Synchronisation OK: green LED is illuminated  
TP2 Inom= 4V ΦS  
TP1 Inom= 4V ΦR  
- Synchronisation block  
P8 Inom ΦT  
P7 Inom ΦS  
P6 Inom ΦR  
- Test point: test voltage = 6Vdc at full load  
- Test point: test voltage = 4Vdc at full load on phase T  
- Test point: test voltage = 4Vdc at full load on phase S  
JUE 401268  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
IPS-500 Front View  
FIG. 1.5 illustrates the potentiometers, LEDs and test points of the  
IPS-500 which are accessible from the front.  
- Test point: test voltage = 4Vdc at full load on phase R  
LAS Power - ON  
- Current limitation adjustment phase T. Adjust for 4Vdc at TP3  
- Current limitation adjustment phase S. Adjust for 4Vdc at TP2  
- Current limitation adjustment phase R. Adjust for 4Vdc at TP1  
DF1 Power Supply OK  
TP15 PSP +12V  
TP3 0 V  
- Power ON:green LED is illuminated  
- Power supply OK: green LED is illuminated  
- Electronics supply voltage +12V  
- Electronics ground  
TP17 PSP-1 + 26V  
TP18 PSP-A + 24V  
Test  
LUV PSP OK  
- Electronics supply voltage +26V  
- Electronics supply voltage +24V  
LVI DC Volts OK  
RV4 DC Over  
Voltage  
- Jumper for test operation (suppression of inverter input voltage  
monitoring signal)  
RV3 DC Under  
Voltage  
- Power supply OK: green LED is illuminated  
- Inv. input voltage in tolerance: green LED is illuminated other-  
wise blinking  
- Adjustment of overvoltage monitoring threshold for the inverter  
input voltage.  
- Adjustment of undervoltage monitoring threshold for the in-  
verter input voltage.  
JUE 401268  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
IPR front view  
FIG. 1.6 illustrates the LEDs, potentiometers, switches and test  
sleeves of the IPR pcb that are accessible from the front.  
- Parallel Operation On: This inverter is connected with another  
or more inverters to the output in parallel.  
LD1 Parall.Operat  
LD2 Red not ok  
- Redundancy Not OK: Redundant units only.The load has in-  
creased or an inverter is off so that if this unit fails, the system  
must transfer to the bypass supply.  
- Parallel Fault: A fault has occurred with the regulation of the  
inverter in parallel with another inverter.  
LD3 Parallel Fault  
LD4 Pulse gen. Fail  
- SSI pulse generator failure: A failure or loss of synchronism has  
occurred within the SSI ON pulse generator. To reset press PB3  
and then PB1 on the ICP pcb.  
- Reference current for parallel regulation 6Vrms = nominal cur-  
rent of the system (0.8 p.f.).  
TP1 Iref= 6Vrms  
TP2 Iout=6Vrms  
- Inverter output current for parallel regulation 6Vrms = nominal  
current of this unit (0.8 p.f.).  
TP3 Ierror  
- Difference current for parallel regulation  
TP4 Iload= 8V  
- Output current of this unit. 8Vdc = nominal load current of this  
unit (0,8 p.f.)  
- System output current. 8Vdc = nominal load current on the sys-  
tem (0.8 p.f.)  
TP5 Isyst= 8V  
TP6 Ired  
- Redundancy current. 8Vdc = nominal load current on the re-  
mainder of the system (without this unit, 0.8 p.f.)  
TP7 Pout=6V  
TP8 Psyst= 6V  
- Power of this unit. 6Vdc = nominal load power on this unit  
- Power of the system. 6Vdc = nominal load power on the system  
- Output voltage phase T  
TP9  
TP10  
- Output voltage phase R-S  
P1 Iref  
P2 Iout  
- Adjust for 6Vrms at TP1 with nominal load current (0.8 p.f.)  
- Adjust for 6Vrms at TP2 with nominal load current (0.8 p.f.)  
- Adjust for 8Vdc at TP4 with nominal load current (0.8 p.f.)  
- Adjust for 8Vdc at TP5 with nominal load current (0.8 p.f.)  
- Adjust for 6Vdc at TP7 with nominal load  
P3 Iload  
P4 Isyst  
P5 Pout  
P6 Psyst  
- Adjust for 6Vdc at TP8 with nominal load  
Manual  
- Manual: manual switching on/off of the inverter permitted  
S1  
- Auto: inverter will automatically switch on/off depending on the  
load applied and the internal programming of IPR pcb.  
Auto  
JUE 401268  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
1.4 Bypass  
The bypass static switch control logic consists of two PCBs.  
IF/PS - S Bypass monitoring and power supply  
• bypass electronic power supply  
• mains voltage sensing  
CPHC16 - S Bypass control  
• switching control of the static bypass switch SSB  
• interface with the inverter or multiple inverters  
• mains frequency monitoring  
• mains voltage and phase rotation monitoring  
• generation of synchronisation signal  
• interface with multiple static bypasses  
• UPS output voltage monitoring  
• majority control for multiple static bypasses (parallel and hot  
standby systems)  
• synchronisation monitor: mains - UPS output  
JUE 401268  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
FIG. 1.7 illustrates the LEDs of the IF/PS - S PCB which are  
accessible from the front.  
IF/PS - S Front View  
+12V analog circuits power supply OK: green LED is illumi-  
PSPA  
PSPP  
nated  
+16V microprocessor power supply OK: green LED is illumi-  
nated  
+12V interfaces power supply OK: green LED is illuminated  
PSPA1  
JUE 401268  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - PCB Description  
1 UPS Control Logic  
FIG. 1.8 illustrates the display, switches and connectors of the  
CPHC16 - S PCB which are accessible from the front.  
CPHC16 - S Front View  
DIAGNOSTICS  
Bypass  
7 segment display for diagnostics (see table below)  
Manual transfer to bypass pushbutton  
RS 232  
RS232 connector (male)  
RS 485  
RS485 connector (female)  
In normal condition the display shows a red seg-  
ment rotating clockwise.If more than one alarm is  
present, only the one with the higher priority  
is displayed.  
Priority  
Indication  
Diagnostics  
1
2
3
4
5
6
7
8
9
8
F
E²PROM failure  
Bypass Fuses Blown or IRE open  
Phase failure  
C
P
l
O
L
Incorrect phase rotation  
Bypass square wave generation error  
Output out of tolerance  
Overload  
4
Mains frequency out of tolerance  
Mains voltage out of tolerance  
H
Auxiliary power supply failure on the  
SS/FY pcb  
10  
6
11  
12  
13  
14  
15  
16  
17  
18  
b
S
d
E
9
Bypass blocked  
Bypass not synchronised  
SSB failure  
Bypass system not available  
Missing or false bypass trip signal  
EPO activated  
7
U
--  
IUG open  
SSB on  
JUE 401268  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents of JUE 401269  
SOLA 4000 - Technical Data  
Figures  
1
SYSTEM DATA  
2
FIG. 1.1 - System Data  
2
2
3
4
RECTIFIER DATA  
3
FIG. 2.1 - Rectifier Data  
3
BATTERY DATA  
4
FIG. 3.1 - Battery Data  
4
INVERTER DATA  
5
FIG. 4.1 - Inverter Data  
5
We reserve the right to modify the contents of this document without notice. BEST POWER- BORRI ELETTRONICA INDUSTRIALE S.r.l Via 8 Marzo Soci, Bibbiena (AREZZO)  
04.02.97  
20.06.97  
04.02.97  
ISSUED  
See Rev. Doc. JSE 401440  
M. Porpora  
A4  
1
5
A
T. Boon  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Technical Data  
1 System Data  
Type SOLA 4000  
30 40 60  
On-line (double conversion)  
Technical Data / System Data  
10  
15  
20  
80  
100 120  
System configuration  
Nominal input voltage  
Nominal input frequency  
Nominal output voltage  
Nominal output frequency  
3Ph+N x 380 ÷ 415 V Tolerance: ± 10%  
50 / 60 Hz Tolerance: ± 10%  
380 / 400 / 415 Vac (adjustable)  
50 / 60 Hz  
Output voltage distortion (THD) linear load  
non linear load at 100% of Pn and C.F. = 3  
< 1%  
< 4%  
Output voltage regulation with load between 0 and  
100%  
± 1% (balanced or unbalanced)  
Output frequency regulation  
- synchronisation with mains  
- free running  
± 0,5 / 1 / 2 Hz (selectable with software)  
± 0,01 %  
Rated output power, power factor = 0.8  
Rated output power, power factor = 1  
[kVA]  
[kW]  
10  
8
15  
12  
20  
16  
30  
24  
40  
32  
60  
48  
80  
64  
100 120  
80 96  
Efficiency  
- 50% load  
- 100% load  
[%]  
[%]  
> 88 > 88 > 88 > 88 > 90 > 90 > 90 > 90 > 90  
> 90 > 90 > 90 > 90 > 91 > 91 > 91 > 91 > 91  
Losses at nominal load, charged battery <= [kW]  
0,8  
1,2  
1,6  
2,4  
3,2  
4,8  
6,4  
8
9,6  
Overload capacity  
- Inverter  
125 % 10 minutes, 150 % 1 minute  
- Static bypass switch (SSB)  
2000 % 20 msec, 200 % 1 minute, 150 % continuous  
Permissible inverter output voltage variation for  
bypass switching  
± 10%  
Design standards  
Insulation test for 60s  
Cabinet protection  
IEC 146-4, EN50091-1, IEC 950  
2,0 kV  
IP 20 acc. to IEC 529, IEC 944 (excl. air exit)  
Ambient temperature  
- operating temperature  
- storage temperature  
0 .. 40 °C  
0 .. 85 °C (excluding battery)  
Permissible relative humidity  
< 95 % UR (non condensing)  
Maximum altitude above sea level at full load  
< 2000 m. Higher altitudes require power derating or  
increased cooling  
RFI suppression  
EMC standard satisfied with EN50091-2 (1995) class A -  
IEC801-2 - IEC801-3 - IEC801-4  
Audible noise level at 1 meter  
<= (dBA)  
58  
58  
58  
58  
60  
60  
61  
61  
62  
FIG. 1.1 - System Data  
JUE 401269  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Technical Data  
2 Rectifier Data  
Type SOLA 4000  
30 40 60  
Technical Data / Rectifier Data  
10  
15  
20  
80  
100  
120  
Input voltage  
Tolerance  
with reduced output (DC) voltage  
refer to system data  
refer to system data  
-20 %  
Input frequency  
Tolerance  
refer to system data  
± 10 %  
Rated input power with charged battery  
-
[kVA]  
10,8  
16,4 24,6 32,7 49,2  
13,5 20 26,9 39,8 53,5  
16  
21,3  
32  
42,7 64,1 84,8  
106  
127,4  
193  
Rated input current with charged battery  
(380 V)  
[A]  
65 97,5 128,5 160,7  
Maximum input power  
-
[kVA]  
80  
105  
132  
201  
158  
Maximum input current, input voltage = 380 V  
-
[A]  
20,5 30,8 40,8 61,2 81,5 122 160,5  
~ 0,83 lag.  
241  
Input power factor  
( nom. load, input voltage = 380V)  
Output control characteristics  
I/U characteristic, boost charge possible  
Rated output voltage  
- Lead-Acid batteries  
- Ni-Cd batteries  
432 V/DC  
436 V/DC  
(depending on number of cells)  
Soft start  
~ 10 sec.  
Floating voltage regulation with load between 0 1 %  
and 100%  
Output voltage ripple with battery disconnected  
RMS 1 %  
7,5  
Max. batt. recharging current with nom. load  
5
10  
15  
20  
30  
40  
50  
60  
-
[A]  
Complies with battery manufacturer's recommendations,  
standard setting approximately 10% of rated battery capacity  
Battery charging current limitation  
IG. 2.1 - Rectifier Data  
JUE 401269  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Technical Data  
3 Battery Data  
Charger input voltage  
30 40 60  
10  
15  
20  
80  
100 120  
Technical Data / Battery Data  
Input charging voltage  
3 x 400 V  
3 x 380 V  
3 x 415 V  
Number of cells (standard)  
Lead-Acid open  
Lead-Acid maintenance free  
Ni-Cd  
192  
192  
300  
192  
192  
300  
192  
192  
300  
Floating-voltage  
Lead-Acid open  
Lead-Acid mainten. free** 2,25 V/Cell [VDC]  
Ni-Cd  
2,25 V/Cell [VDC]  
432  
432  
426  
432  
432  
426  
432  
432  
426  
1,42 V/Cell [VDC]  
Boost charge voltage  
Lead-Acid open  
Ni-Cd  
2,4 V/Cell  
1,54 V/Cell*** [VDC]  
[VDC]  
462  
462  
462  
462  
462  
462  
Lead-Acid maintenance free (no boost charge)  
Minimum battery voltage  
Lead-Acid  
1,69 V/Cell [VDC]  
325  
325  
325  
Recommended charging current (adjustable)  
Protection  
10 % of rated battery capacity  
- Batt. protection disconnector switch****  
- Automatic shutdown of the inverter at min. DC voltage  
Permissible DC voltage range  
[VDC]  
min. 320V . . . . . . . . . . . . max. 462V  
Maximum battery discharging current  
(Vdc=320V, nominal load)  
27  
40  
54  
80 107,5  
161,2 212,5 266 319  
Environmental temperature  
follow battery manufacturer's instruction  
** At 20° C room temperature  
*** Maximum voltage/cell  
**** Battery disconnector fuse for free standing battery optional  
FIG. 3.1 - Battery Data  
JUE 401269  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLA 4000 - Technical Data  
4 Inverter Data  
Type SOLA 4000  
30 40 60  
320 - 480 V/DC  
Technical Data / Inverter Data  
10  
15  
20  
80  
100  
120  
Permissible input DC voltage range  
Input power at rated load  
-
[kW]  
8,7  
27  
13  
40  
12,4  
54  
26  
80  
35,1 52,7 70,3 87,9 105,5  
107,5 161,2 212,5 266 319  
Inverter input current at 320 Vdc and rated  
load  
[A]  
[A]  
Nominal output current at rated load  
(380V, cos phi = 0,8)  
15,2 22,7 30,3 45,5 60,8 91,3 121,7 152,1 182,1  
Nominal output current (380V, cos phi = 1,0)  
-
[A]  
12,1 18,1 24,2 36,4 48,6  
73  
97,4  
122  
146  
Efficiency at 80% load  
-
[%]  
> 92 > 92 > 92 > 92 > 92 > 93 > 93 > 93  
> 93  
Load power factor range  
- at nominal load  
0,7 - 0,8 ind.  
- at reduced load  
0,5 ind. - 0,5 cap.  
Output voltage  
refer to system data  
Output voltage distortion (THD)  
Output voltage adjustment range  
refer to system data  
± 10% of programmable nominal value  
Phase displacement  
- balanced load  
- 100 % unbalanced load  
120° ± 1%  
120° ± 1%  
Voltage tolerances  
- static, balanced load  
± 1 %  
± 1 %  
± 4 %  
± 5 %  
- static, 100% unbalanced load  
- dynamic, 50% load step  
- dynamic, 100% load step  
Voltage transient recovery time  
Short circuit current  
<= 50 ms within ± 2% of nominal voltage  
150 % of nominal current  
± 2,5 Hz  
Max. freq. range for synchr. of the inv. with  
the mains  
Max. frequency variation during  
synchronisation  
± 1 Hz/sec.  
FIG. 4.1 - Inverter Data  
JUE 401269  
108  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pelco Computer Accessories VMX200 User Manual
Pelco Home Security System Not ICS110 CW User Manual
Philips DVD Player MDV411SL User Manual
Philips Hair Dryer HP8195 00 User Manual
Philips Microphone SBCM D110 User Manual
Philips Portable DVD Player DVD941 User Manual
Pioneer Cell Phone CD HF1 User Manual
Plasmon Computer Hardware FS3102 User Manual
Pride Mobility Motorcycle NFMANU2058 User Manual
Promise Technology Network Card SX4300 User Manual