Philips Work Light EL2 Series User Manual

EL2 Series Emergency Lighting EL2  
Page 1 of 1  
6 Volt 12 Watts Thermoplastic Housing  
The EL2 Series is an architectural grade two-head emergency light ideal for either wall or ceiling mounted applications. This product features  
innovative architectural styling and technologically advanced features.  
Lamp Head Photometrics (per Lamp)  
HORIZONTAL  
40  
.1  
35  
6.4"  
(16.3 cm)  
2.5"  
(6.4 cm)  
30  
25  
20  
15  
10  
5
.2  
.3  
.5  
0
6.7"  
(17.0 cm)  
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
FEET  
VERTICAL  
.1  
40  
35  
30  
25  
20  
15  
10  
5
.2  
.3  
.5  
1
0
-5  
-4  
-3  
-2  
-1  
0
1
2
3
4
5
FEET  
Complete Fixture consists of unit and two lamp heads. Lamp Head Photometrics (per lamp)  
How to Specify:  
EL2  
Model  
Series  
Enclosure  
Color  
Battery  
Options  
1
EL2  
W = White  
N = NiMH  
I = Infared Remote Sensor  
B = Black  
TD = Time Delay  
Code Compliance  
Features  
U.L. 924 listed, NFPA 101.  
1. Illumination: Two rotatable reflector assemblies with adjustable beam pat-  
terns. Unit includes 6 VDC, 6 watt halogen lamps housed in impact resistant  
lamp covers.*  
Options  
I = Infrared Remote Sensor1  
2. Housing: Impact resistant, injection molded UL 94-5VA flame retardant  
thermoplastic housing. UV-stabilized to resist discoloration. White finish is  
standard, black is optional.  
TD = Time Delay  
Note:  
1. For use with remote control which is ordered separately. Item number: IRemote  
3. Mounting: Unit is either ceiling or wall mountable.  
4. Standard Self-Testing/Self-Diagnostics: Unit runs an internal test every  
five seconds for secondary voltage, charge current, battery voltage, and LED  
illumination. Performs automatic 1 minute discharge test every 30 days and  
30 minute discharge test every 180 days meeting and exceeding UL 924 and  
NFPA 101 requirements. The Infrared Option allows a remote control to initi-  
ate a 5 second and 30 minute self-test in addition to the standard 1 minute  
and 90 minute manual test capability.  
Accessories  
IREMOTE - Infared Remote Control  
*Replacement Lamping: No. 784, T2.25, G-4 Two Pin Base, 6 Volt, 6 Watt  
Miniature Lamp.  
5. Electronics: 120/277 VAC dual voltage input. Microprocessor controlled  
charge, transfer and monitoring system.Charging system is complete with  
low voltage disconnect, AC lockout, and brownout protection. Includes an AC  
indicator/systems status lamp and manual test switch.  
6. Battery: Maintenance free, sealed nickel metal hydride battery with 10 year  
life and an operating temperature between 14°F (-10°C) and 113°F (45°C).  
NiMH battery is a non-toxic, environmentally friendly product which is recy-  
clable.  
Job Information  
Type:  
Job Name:  
Cat. No.:  
Lamp(s):  
Notes:  
7. Input Power Requirements:  
120 VAC- .103 amps, 11.3W,  
277 VAC- .044 amps, 11.6W  
Warranty  
Electronics: 3 years, Battery: 5 years full, 5 years pro-rata  
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710  
We reserve the right to change details of design, materials and finish.  
Lightolier is a Philips group brand  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Stereo Amplifier 646 063 User Manual
Pelco Security Camera c2485m a ml User Manual
Philips Computer Drive SPE2010CC User Manual
Philips Speaker System MMS 305 User Manual
Philips TV Cables SWA2416W User Manual
Philips Work Light Series T5 HO User Manual
Pioneer DJ Equipment RMX 1000 User Manual
Pioneer DVD Recorder D V D R E C O R D E R S A N D P L A Y E R S User Manual
Playskool Games 6138 User Manual
ProForm Home Gym PFEX38440 User Manual