Panasonic Smoke Alarm 6367 User Manual

Fire alarm systems  
Duct detector  
chamber  
6367  
Only one pipe is required  
Simple installation  
For conventional as well as analog and addressable systems  
A ventilation duct with a width > 0.6 m  
(diameter) requires an 1.5 or 2.8 m venturi  
pipe (6371-15 / -28), ended outside the duct.  
General  
The Uniguard Duct detector chamber 6367  
is used when smoke is to be detected in a  
ventilation duct. Both the "venturi pipe" and  
the housing, where a smoke detector is to be  
placed, are especially designed for optimum  
airflow through the detector. The housing is  
made of grey ABS and the venturi pipe is  
made of aluminium. Supplied with two  
compression glands for cable entry.  
See figure on the opposite page.  
Air flow indicator  
A built-in air flow indicator gives a  
confirmation that the air from the ventilation  
duct is flowing through the venturi pipe and  
the detector. If not, a booster fan 6373 is  
available as an option.  
6367 can be used in conventional as well as  
analog fire alarm systems, depending on the  
detector placed inside the housing.  
Accessories  
Bracket 6372, to be used when 6367 shall be  
mounted on a round ventilation duct. See  
figure on the opposite page.  
The Photoelectric smoke detector 4352,  
plugged in the base 2324, is used in a  
conventional system (zone line input). An  
attached space ring (11 mm) is required  
between the base and the housing.  
Booster fan 6373, to be used when the air  
flow indicator is indicating no or very small  
air flow. The fan shall be mounted inside  
the housing and connected to the terminal  
block. External power supply (24 V AC, 50  
mA) is required.  
The Analog photoelectric smoke detector  
4301, plugged in the analog base 3312, is  
used in an analog and addressable system.  
An attached space ring (19 mm) is required  
between the base and the housing.  
Filter 6374, can be used in an extremely  
dirty environment, as in a saw mill, a timber  
yard, etc. The filter shall be placed inside  
the housing, in a slot just before the detector.  
Venturi pipe 6371  
The venturi pipe is available in three lengths  
and can easily be shortened to suit the  
ventilation duct. An attached plug is to be  
placed in the end of the pipe.  
Product applications  
The Duct detector chamber can be used in  
the systems EBL500 / 512 / 128 / 1000 /  
2000. It is intended for indoor use and in  
dry premises.  
A ventilation duct with a width < 0.6 m  
(diameter) requires a 0.6 m venturi pipe  
(6371-06), ended inside the duct.  
Panasonic Electric Works Fire & Security Technology Europe AB  
Citadellsvägen 23, SE-211 18 Malmö, Sweden  
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99  
Download from Www.Somanuals.com. All Manuals Search And Download.  

National Instruments Network Card AT E Series User Manual
NEC Flat Panel Television LCD6520L BK AV User Manual
NETGEAR Network Router CG3000Dv2 User Manual
Nu Vu Food Saver AMP 12 User Manual
Omega Computer Hardware OME A822PG User Manual
Omnimount Indoor Furnishings OM10328 User Manual
Outback Power Systems Battery Charger GTFX2524 User Manual
Palsonic TV DVD Combo TFTV2035BK User Manual
Panasonic Switch AV HS400AN User Manual
Partner Tech Chainsaw P33XT User Manual