TECHNICAL & SERVICE MANUAL
CZ-RD515U
WIRED REMOTE CONTROLLER
Model No.
Product Code No.
1 852 361 14
CZ-RD515U
REFERENCE NO. SM700883
Download from Www.Somanuals.com. All Manuals Search And Download.
Warning
If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.
Prohibit
If refrigerant gas leaks during the work, ventilate the room.
If refrigerant gas catches fire, harmful gas may be generated.
Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle.
If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle,
which may cause a unit breakdown."
Prohibit
When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in
a well-ventilated place after sufficiently recovering the refrigerant gas.
Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.
When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet,
gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.
When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit.
Insufficient strength of the installation location and incomplete installation work may cause an injury due to
the unit falling.
When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children.
If a child swallows a battery, make sure that the child gets immediate medical attention.
Caution
Do not wash the air conditioner with water, as this may cause an electric shock or fire.
Prohibit
For the repair work in places with high humidity or moisture, make sure to ground the unit.
Failure to do so may cause an electric shock.
Confirm that the component attachment position, wiring condition, soldering condition and connector connection
are normal.
If not, it may cause overheating or fire.
Confirm that the temperature around the compressor is not too high, and then perform the repair work.
Failure to do so may cause a burn.
Perform welding work in a place with good ventilation.
If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.
If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it.
Failure to do so may cause an injury due to the unit falling.
When the cleaning is to be performed, make sure to turn off the power and pull out the plug.
Touching the fan that is rotating at high speed may result in an injury.
When the indoor unit is to be removed, do not place it on an incline.
Doing so may cause wet furniture because water left inside may trickle down.
Prohibit
Prohibit
Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.
After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more.
Any insulation error may cause an electric shock.
After repairs, make sure to check the drainage of the indoor unit.
Inappropriate drainage may cause wet furniture and floors due to water leakage.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Page
SAFETY PRECAUTIONS ...............................................................................................................
TABLE OF CONTENTS ......................................................................................................................
1. SPECIFICATIONS .........................................................................................................................
2. APPLICABLE INDOOR UNITS .....................................................................................................
3. FUNCTIONS .................................................................................................................................
2
4
5
6
6
4. SELF-DIAGNOSTICS ...................................................................................................................
4-1. Self-Diagnostics Procedure ...................................................................................................
4-2. Self-Diagnostics Table (Ceiling Cassette Type) .....................................................................
4-3. Self-Diagnostics Table (Wall Mounted Type 1) ......................................................................
7
7
8
9
4-4. Self-Diagnostics Table (Wall Mounted Type 2) ...................................................................... 10
APPENDIX A Operating Instructions .......................................................................................... A-1
APPENDIX B INSTALLATION INSTRUCTIONS ........................................................................... A-2
(CZ-RD515U)
APPENDIX C INSTALLATION INSTRUCTIONS ........................................................................... A-3
(Installing the Connection Kit for Wall Mounted Type 1)
APPENDIX D INSTALLATION INSTRUCTIONS ........................................................................... A-4
(Installing the Connection Kit for Wall Mounted Type 2)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
1. SPECIFICATIONS
Item
Signal Transmission Method
Power Source
Description
Dedicated Remote Controller Cable
DC5V supplied from Indoor Unit
Display Panel Type
Temperature
Liquid Crystal
Set Temperature Indication (68 °F to 86 °F)
Six Directions Indication
AM and PM 12-Hour Indication (Minute Indication Unit: 1 minute)
Displayed when indoor unit sensor is in use
AUTO, HEAT, DRY and FAN Operation
Airflow Direction
Display Items
Time
Temperature Sensor
Functions
NOTE
2
2
NOTE
Operation Section
Push Switch
Detection using the Sensor in the Remote Controller or
Indoor Unit Temperature Sensor
Room Temperature Detection
(The detection result is transmitted to the indoor unit every 5 minutes)
NOTE
1. When the indoor unit is modified from one for wireless remote controller to that for
wired remote controller, some of the functions becomes unavailable.
Therefore, before such modification, make sure to receive an approval of the client.
Also, the self-diagnostics procedure is changed.
• Unavailable Functions : Refer to "3. FUNCTIONS".
• Self-Diagnostics Procedure : Refer to "4. SELF-DIAGNOSTICS".
2. The mode change or SINGLE/MULTI change-over operation is performed using the slide switch
located inside the rear of the remote controller.
Refer to "APPENDIX B : INSTALLATION INSTRUCTIONS" for details.
70.0
16.5
5
Download from Www.Somanuals.com. All Manuals Search And Download.
2. APPLICABLE INDOOR UNITS
(1) Ceiling cassette type
Model No.
CS-KE12NB41, CS-KE18NB4UW, CS-KS12NB41, CS-KS18NB4UW
(2) Wall mounted type 1
The connection kit "CZ-RC515U" is required for the installation.
NOTE
CS-KE18NKU, CS-KE24NKU
CS-KS18NKU, CS-KS24NKU
Model No.
CS-MKE7NKU, CS-MKE9NKU, CS-MKE12NKU, CS-MKE18NKU, CS-MKE24NKU
CS-MKS7NKU, CS-MKS9NKU, CS-MKS12NKU, CS-MKS18NKU, CS-MKS24NKU
(3) Wall mounted type 2
The connection kit "CZ-RC515UA" is required for the installation.
NOTE
Model No.
CS-KE30NKU, CS-KE36NKU, CS-KS30NKU, CS-KS36NKU
3. FUNCTIONS
When the unit is modified from one for wireless remote controller to that for wired remote controller,
the following functions become unavailable.
(1) Ceiling Cassette Type
• Remote Controller
• High Power Operation
(2) Wall Mounted Type
• Remote Controller
• High Power Operation
• Quiet Operation
6
Download from Www.Somanuals.com. All Manuals Search And Download.
4. SELF-DIAGNOSTICS
4-1. Self-Diagnostics Procedure
< Clock display >
Test run mode
PROCEDURE
After turning on power to the air conditioner, use the remote
controller and follow the steps below to execute
self-diagnostics.
Self-diagnostics mode
Step 1: Press and hold the remote controller NIGHT SET
BACK (NSB) button and 1 HR TIMER button. Then,
press and hold the ACL (reset) button with a pointed
object such as the tip of a pen. After 5 seconds,
release ACL button first, then release NIGHT SET
BACK (NSB) and 1 HR TIMER buttons, "oP-1" (test
run) appears, blinking in the remote controller clock
display area.
Step 2: Next, press the 1 HR TIMER button once to change
the display from "oP-1" to "oP-3" (self-diagnostics).
(The display continues to blink.)
ON/OFF
operation button
Step 3: Finally press the ON/OFF button to engage
self-diagnostics mode.
NIGHT SETBACK
button
• The self-diagnostics function utilizes the 3 indicator lamps
on the main unit, in combinations of ON lamps, blinking
lamps, and OFF lamps, to report the existence of sensor
trouble or a protective operation. (The lamps blink or
remain ON for 5 seconds, then turn OFF for 2 seconds.)
Self-diagnostics is completed when the buzzer sounds 3
short beeps.
1 HR.TIMER
button
• A maximum of 3 self-diagnostics reports are displayed, for
5 seconds each, beginning with the most recent report.
Following this display the lamps turn OFF. In order to view
the self-diagnostics results again, press the ON/OFF button
again.
ACL (Reset)
button
• The 3 lamps remain OFF if no trouble has occurred.
<IMPORTANT> After self-diagnostics is completed, be sure
to press the ACL (reset) button to return to
normal mode. The air conditioner will not
operate if this is not done.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
4-2. Self-Diagnostics Table (Ceiling Cassette Type)
INDOOR UNIT
OPERATION button
OPERATION lamp
TIMER lamp
HIGH POWER lamp
REMOTE CONTROL receiver
Since the indications cover various units, the corresponding parts listed below may not be present in some models.
....
....
....
ON
INDICATION ON INDOOR UNIT
OFF
BLINKING
HIGH
OPERATION
TIMER
POWER
CODE
S01
DIAGNOSIS CONTENTS
POSSIBLE MALFUNCTION
(1) OPEN OR SHORT CIRCUIT IN SENSOR
(2) POOR CONTACT AT CONNECTOR OR OPEN
CIRCUIT AT TERMINAL PRESS-FIT LOCATION.
(3) I/D PCB FAILURE (I/D = INDOOR)
ROOM TEMP. SENSOR TROUBLE
I/D HEAT EXCHANGER TEMP.
SENSOR TROUBLE
S02
(1) OPEN OR SHORT CIRCUIT IN SENSOR
(2) POOR CONTACT AT CONNECTOR OR OPEN
CIRCUIT AT TERMINAL PRESS-FIT LOCATION
(3) O/D PCB FAILURE (O/D = OUTDOOR)
COMPRESSOR TEMP. SENSOR
TROUBLE
S04
S05
O/D HEAT EXCHANGER TEMP.
SENSOR TROUBLE
O/D AIR TEMP. SENSOR TROUBLE
O/D CURRENT SENSOR ERROR
S06
S07
O/D PCB FAILURE
(1) MIS-WIRING (2) AC POWER FAILURE (3) BLOWN FUSE
(4) POWER RELAY FAILURE (5) I/D OR O/D PCB FAILURE
(6) O/D FAN MOTOR FAILURE (7) REACTOR FAILURE
I/D-O/D COMMUNICATION
TROUBLE
E01
E02
(SERIAL COMMUNICATION
TROUBLE)
(8) HIGH-PRESSURE SW FAILURE (9) OLR FAILURE (10) MAGNETIC COIL FAILURE
(1) HIC OR POWER TR FAILURE (2) O/D FAN NOT OPERATING
(3) INSTANTANEOUS POWER STOPPAGE (4) SERVICE VALVE NOT OPENED
(5) O/D FAN BLOCKED (6) CONTINUOUS OVERLOAD OPERATION
(7) COMPRESSOR FAILURE (8) O/D PCB FAILURE
HIC CIRCUIT TROUBLE
POWER TR CIRCUIT TROUBLE
O/D UNIT EXTERNAL ROM
TROUBLE
(1) EXTERNAL ROM DATA FAILURE (2) O/D PCB FAILURE
E03
E04
(1) INSTANTANEOUS POWER STOPPAGE (2) HIC OR POWER TR FAILURE
(3) O/D PCB FAILURE
CURRENT PEAK CUT
PAM CIRCUIT TROUBLE
(1) O/D PCB FAILURE
(2) O/D POWER VOLTAGE TROUBLE
E05
E06
E07
E08
ACTIVE CIRCUIT TROUBLE
(1) ELECTRIC EXPANSION VALVE FAILURE (2) CHOKED CAPILLARY TUBE
(3) INSUFFICIENT GAS (4) CONTINUOUS OVERLOAD OPERATION
(5) O/D FAN NOT OPERATING (6) O/D PCB FAILURE
COMPRESSOR
DISCHARGE TEMP.
OVERHEATING PREVENTION
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) I/D PCB FAILURE
I/D FAN OPERATION TROUBLE
4-WAY VALVE SWITCHING
TROUBLE
ZERO-CROSS TROUBLE
(1) 4-WAY VALVE FAILURE (HEAT PUMP MODEL ONLY)
(2) O/D PCB FAILURE
(1) SERVICE VALVE NOT OPENED (2) INSUFFICIENT GAS
(1) OPEN PHASE (2) O/D PCB FAILURE
GAS-LOSS PREVENTION
E09
E10
DC COMPRESSOR DRIVE
CIRCUIT TROUBLE
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) O/D PCB FAILURE
E11
E12
O/D DC FAN OPERATION TROUBLE
(1) MIS-WIRING (2) BLOWN FUSE
(3) POWER RELAY FAILURE (4) O/D PCB FAILURE
(5) COMPRESSOR FAILURE
O/D SYSTEM COMM FAILURE,
OLR OPERATION, O/D POWER
OPEN PHASE, O/D FREEZING
(1) I/D FAN SYSTEM TROUBLE (2) INSUFFICIENT GAS
(3) OPERATION AT LOW TEMPERATURE
FREEZING-PREVENTION OPERATION
FLOAT SWICTH (FS) IS ACTIVED.
E13
TIMER
LAMP
BLINKING (3 SEC. INTERVAL)
(1) DRAIN PUMP FAILURE (2) FS FAILURE (3) CHOKED DRAIN HOSE
8512-5261-99100-1
8
Download from Www.Somanuals.com. All Manuals Search And Download.
4-3. Self-Diagnostics Table (Wall Mounted Type 1)
INDOOR UNIT
(1) OPERATION lamp
(2) TIMER lamp
(3) QUIET lamp
OPERATION button
REMOTE CONTROL receiver
Since the indications cover various units, the corresponding parts listed below may not be present in some models.
....
....
....
ON
INDICATION ON INDOOR UNIT
OFF
BLINKING
POSSIBLE MALFUNCTION
QUIET
(3)
TIMER
(2)
OPERATION
(1)
CODE
S01
DIAGNOSIS CONTENTS
(1) OPEN OR SHORT CIRCUIT IN SENSOR
ROOM TEMP. SENSOR TROUBLE
(2) POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT
TERMINAL PRESS-FIT LOCATION (FOR HUMIDITY SENSOR,
THIS REPRESENTS SHORT-CIRCUIT DETECTION ONLY.)
(3) I/D PCB FAILURE (I/D = INDOOR)
I/D HEAT EXCHANGER
S02
TEMP. SENSOR TROUBLE
HUMIDITY SENSOR TROUBLE
S03
COMPRESSOR TEMP. SENSOR
TROUBLE
S04
S05
(1) OPEN OR SHORT CIRCUIT IN SENSOR
(2) POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT
TERMINAL PRESS-FIT LOCATION
O/D HEAT EXCHANGER
TEMP. SENSOR TROUBLE
(3) O/D PCB FAILURE (O/D = OUTDOOR)
O/D AIR TEMP. SENSOR TROUBLE
O/D CURRENT SENSOR ERROR
S06
S07
O/D PCB FAILURE
(1) MIS-WIRING (2) AC POWER FAILURE (3) BLOWN FUSE
(4) POWER RELAY FAILURE (5) I/D OR O/D PCB FAILURE
(6) O/D FAN MOTOR FAILURE (7) REACTOR FAILURE
I/D-O/D COMMUNICATION TROUBLE
(SERIAL COMMUNICATION TROUBLE)
E01
E02
(8) HIGH-PRESSURE SW FAILURE (9) OLR FAILURE (10) MAGNETIC COIL FAILURE
(1) HIC OR POWER TR FAILURE (2) O/D FAN NOT OPERATING
(3) INSTANTANEOUS POWER STOPPAGE (4) SERVICE VALVE NOT OPENED.
(5) O/D FAN BLOCKED (6) CONTINUOUS OVERLOAD OPERATION
(7) COMPRESSOR FAILURE (8) O/D PCB FAILURE
HIC CIRCUIT TROUBLE
POWER TR CIRCUIT TROUBLE
(1) EXTERNAL ROM DATA FAILURE (2) O/D PCB FAILURE
O/D UNIT EXTERNAL ROM TROUBLE
CURRENT PEAK CUT
E03
E04
(1) INSTANTANEOUS POWER STOPPAGE (2) HIC OR POWER TR FAILURE
(3) O/D PCB FAILURE
PAM CIRCUIT TROUBLE
(1) O/D PCB FAILURE
(2) O/D POWER VOLTAGE TROUBLE
E05
E06
ACTIVE CIRCUIT TROUBLE
(1) ELECTRIC EXPANSION VALVE FAILURE (2) CHOKED CAPILLARY TUBE
(3) INSUFFICIENT GAS (4) CONTINUOUS OVERLOAD OPERATION
(5) O/D FAN NOT OPERATING (6) O/D PCB FAILURE
COMPRESSOR DISCHARGE TEMP.
OVERHEATING PREVENTION
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) I/D PCB FAILURE
I/D FAN OPERATION TROUBLE
E07
E08
(1) 4-WAY VALVE FAILURE (HEAT PUMP MODEL ONLY)
(2) O/D PCB FAILURE
4-WAY VALVE SWITCHING TROUBLE
ZERO-CROSS TROUBLE
(1) SERVICE VALVE NOT OPENED (2) INSUFFICIENT GAS
(1) OPEN PHASE (2) O/D PCB FAILURE
GAS-LOSS PREVENTION
E09
E10
DC COMPRESSOR DRIVE
CIRCUIT TROUBLE
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) O/D PCB FAILURE
E11
E12
O/D DC FAN OPERATION TROUBLE
O/D SYSTEM COMM FAILURE,
OLR OPERATION, O/D POWER
OPEN PHASE, O/D FREEZING
(1) MIS-WIRING (2) BLOWN FUSE (3) POWER RELAY FAILURE
(4) O/D PCB FAILURE (5) COMPRESSOR FAILURE
(1) I/D FAN SYSTEM FAILURE (2) INSUFFICIENT GAS
(3) OPERATION AT LOW TEMPERATURE
FREEZING-PREVENTION OPERATION
E13
8FA2-5251-11100-2
9
Download from Www.Somanuals.com. All Manuals Search And Download.
4-4. Self-Diagnostics Table (Wall Mounted Type 2)
INDOOR UNIT
(1) OPERATION lamp
(2) TIMER lamp
OPERATION
TIMER
(3)
ON/OFF
Since the indications cover various units, the corresponding parts listed below may not be present in some models.
.... .... ....
INDICATION ON INDOOR UNIT
OFF
BLINKING
ON
TIMER OPERATION
ALARM
CODE
ERROE
CODE
...
..
.
DIAGNOSIS CONTENTS
POSSIBLE MALFUNCTION
(3)
(2)
(1)
F10
S01
S02
S03
(1) OPEN OR SHORT CIRCUIT IN SENSOR
ROOM TEMP. SENSOR TROUBLE
(2) POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT
TERMINAL PRESS-FIT LOCATION (FOR HUMIDITY SENSOR,
THIS REPRESENTS SHORT-CIRCUIT DETECTION ONLY.)
(3) I/D PCB FAILURE (I/D = INDOOR)
I/D HEAT EXCHANGER
TEMP. SENSOR TROUBLE
F02
F13
HUMIDITY SENSOR TROUBLE
COMPRESSOR TEMP. SENSOR
TROUBLE
F04/F12
S04
S05
(1) OPEN OR SHORT CIRCUIT IN SENSOR
(2) POOR CONTACT AT CONNECTOR OR OPEN CIRCUIT AT
TERMINAL PRESS-FIT LOCATION
O/D HEAT EXCHANGER
TEMP. SENSOR TROUBLE
F09/F12-F18
F08/F21-F24
F27
(3) O/D PCB FAILURE (O/D = OUTDOOR)
O/D AIR TEMP. SENSOR TROUBLE
O/D CURRENT SENSOR ERROR
S06
S07
O/D PCB FAILURE
(1) MIS-WIRING (2) AC POWER FAILURE (3) BLOWN FUSE
(4) POWER RELAY FAILURE (5) I/D OR O/D PCB FAILURE
(6) O/D FAN MOTOR FAILURE (7) REACTOR FAILURE
I/D-O/D COMMUNICATION TROUBLE
(SERIAL COMMUNICATION TROUBLE)
E05
P26
E01
(8) HIGH-PRESSURE SW FAILURE (9) OLR FAILURE (10) MAGNETIC COIL FAILURE
(1) HIC OR POWER TR FAILURE (2) O/D FAN NOT OPERATING
(3) INSTANTANEOUS POWER STOPPAGE (4) SERVICE VALVE NOT OPENED.
(5) O/D FAN BLOCKED (6) CONTINUOUS OVERLOAD OPERATION
(7) COMPRESSOR FAILURE (8) O/D PCB FAILURE
HIC CIRCUIT TROUBLE
POWER TR CIRCUIT TROUBLE
E02
E03
(1) EXTERNAL ROM DATA FAILURE (2) O/D PCB FAILURE
O/D UNIT EXTERNAL ROM TROUBLE
F31
P16
(1) INSTANTANEOUS POWER STOPPAGE (2) HIC OR POWER TR FAILURE
(3) O/D PCB FAILURE
E04 CURRENT PEAK CUT
PAM CIRCUIT TROUBLE
(1) O/D PCB FAILURE
(2) O/D POWER VOLTAGE TROUBLE
P07
P03
E05
ACTIVE CIRCUIT TROUBLE
(1) ELECTRIC EXPANSION VALVE FAILURE (2) CHOKED CAPILLARY TUBE
(3) INSUFFICIENT GAS (4) CONTINUOUS OVERLOAD OPERATION
(5) O/D FAN NOT OPERATING (6) O/D PCB FAILURE
COMPRESSOR DISCHARGE TEMP.
OVERHEATING PREVENTION
E06
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) I/D PCB FAILURE
P01
P19
I/D FAN OPERATION TROUBLE
E07
E08
(1) 4-WAY VALVE FAILURE (HEAT PUMP MODEL ONLY)
(2) O/D PCB FAILURE
4-WAY VALVE SWITCHING TROUBLE
ZERO-CROSS TROUBLE
(1) SERVICE VALVE NOT OPENED (2) INSUFFICIENT GAS
(1) OPEN PHASE (2) O/D PCB FAILURE
P15
P29
GAS-LOSS PREVENTION
E09
E10
DC COMPRESSOR DRIVE
CIRCUIT TROUBLE
(1) FAN MOTOR FAILURE (2) CONNECTOR CONTACT FAILURE
(3) O/D PCB FAILURE
E11 O/D DC FAN OPERATION TROUBLE
O/D SYSTEM COMM FAILURE,
P22
E07/P04/P05
P20/P27
(1) MIS-WIRING (2) BLOWN FUSE (3) POWER RELAY FAILURE
(4) O/D PCB FAILURE (5) COMPRESSOR FAILURE
OLR OPERATION, O/D POWER
OPEN PHASE, O/D FREEZING
E12
(1) I/D FAN SYSTEM TROUBLE (2) INSUFFICIENT GAS
(3) OPERATION AT LOW TEMPERATURE
P11
FREEZING-PREVENTION OPERATION
E13
8FA2-5251-12500-1
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX A Operating Instructions
CZ-RD515U
(852-6-4181-230-00-1)
A-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
Wired Remote Controller
CZ-RD515U
Model No.
This wired remote controller is designed for
both the “COOL/DRY/HEAT Model” and
“COOL/DRY Model” indoor unit.
Once the wired remote controller is
connected, the wireless remote controller
cannot be used.
Before operating the unit, read these operating instructions thoroughly and keep them for future reference.
Panasonic Corporation
1006 Kadoma, Kadoma City, Osaka, Japan
85264181230001
CV6233187877
Download from Www.Somanuals.com. All Manuals Search And Download.
FEATURES
• Microprocessor Controlled Operation
The interior compartment of the remote controller contains several
features to facilitate automatic operation, easy logically displayed
for easy use.
• Air Sweep Control
This function moves a flap up and down in the air outlet, directing
air in a sweeping motion around the room and providing comfort in
every corner.
• 24-Hour ON or OFF Timer
This timer can be set to automatically turn the unit on or off at any
time within a 24 hour period.
• Automatic Restart Function for Power Failure
Even when power failure occurs, preset programmed operation
can be reactivated once power resumes.
• Automatic Switching between Cooling and Heating
This unit automatically switches between cooling operation and
heating operation according to the difference between the room
temperature and the temperature setting.
(This function is available only for “Single use” of COOL/DRY/
HEAT Model.)
• 1-Hour OFF Timer
This timer can be set to automatically turn off the unit at any time
after one hour.
• Night Setback
This function saves energy by controlling operation to provide a
quieter operating sound than normal.
• Hot Start Heating System
Right from the start, the air is warm and comfortable. This system
prevents any cold blasts at the beginning while the heat pump is
warming up, or even defrosting.
• Automatic and 3-step Fan Speed
Auto/High/Medium/Low
(This function is available only for COOL/DRY/HEAT Model.)
NOTE
• Since the wired remote controller is designed to be commonly used for various air conditioners, some of the functions of the wireless
remote controller supplied with the indoor unit cannot be used.
• “Single use” means that only one indoor unit is connected with one outdoor unit in a one-unit-to-one-unit configuration.
• “Multiple use” (i.e. Flexi-Multi system) means that two or more indoor units are connected with one outdoor unit in a multiple-unit-to-one-unit
configuration.
CONTENTS
Page
FEATURES......................................................................................................................................... 2
PRODUCT INFORMATION ................................................................................................................ 2
SAFETY PRECAUTIONS................................................................................................................... 2
INSTALLATION LOCATION ................................................................................................................ 3
ELECTRICAL REQUIREMENTS........................................................................................................3
SAFETY INSTRUCTIONS.................................................................................................................. 3
REMOTE CONTROLLER................................................................................................................... 4
OPERATION WITH THE REMOTE CONTROLLER........................................................................... 7
1. Automatic Operation (only for COOL/DRY/HEAT Model) .................................................... 7
2. Manual Operation................................................................................................................ 7
3. Adjusting the Fan Speed .....................................................................................................8
4. Fan Only.............................................................................................................................. 8
5. Night Setback Mode ............................................................................................................ 8
SPECIAL REMARKS.......................................................................................................................... 8
SETTING THE TIMER........................................................................................................................ 9
USING THE 1-HOUR OFF TIMER...................................................................................................10
ADJUSTING THE AIRFLOW DIRECTION .......................................................................................10
PRODUCT INFORMATION
SAFETY PRECAUTIONS
If you have problems or questions concerning your wired
remote controller, you will need the following information.
The following symbols used in this manual, alert you
to potentially dangerous conditions to users, service
personnel or the appliance:
Model No. __________________________________
Date of purchase _____________________________
Dealer’s address _____________________________
Phone number _______________________________
This symbol refers to a hazard or unsafe
practice which can result in severe
personal injury or death.
This symbol refers to a hazard or unsafe
practice which can result in personal
CAUTION
injury or product or property damage.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION LOCATION
• To prevent possible hazards from insulation failure,
the unit must be grounded.
We recommend that this wired remote controller be
installed properly by qualified installation technicians
in accordance with the Installation Instructions
provided with the unit.
• Do not clean inside the indoor and outdoor units by users.
Engage authorized dealer or specialist for cleaning.
• In case of malfunction of this appliance, do not repair by
yourself. Contact to the sales dealer or service dealer for a
repair.
• Refrigerant gas leakage may cause fire.
• Do not install this wired remote
controller where there are fumes or
flammable gases, or in an extremely
humid space such as a greenhouse.
• Do not install the wired remote
controller where excessively high
heat-generating objects are placed.
• For safety, be sure to turn the air conditioner off and
also to disconnect the power before cleaning.
• Pull off the power plug from a receptacle, or switch off the
breaker, or switch off the power disconnecting mean to
isolate the air conditioner from the main power supply in
case of emergency.
Avoid:
To protect the air conditioner from heavy corrosion, avoid installing
the outdoor unit where salty sea water can splash directly onto it or
in sulphurous air near a spa.
CAUTION
• Do not turn the air conditioner on and off from the power
mains switch. Use the ON/OFF operation button.
• Do not stick anything into the air outlet of the outdoor unit.
This is dangerous because the fan is rotating at high
speed.
• Do not touch the air inlet or the sharp aluminum fins
of the outdoor unit. You may get injured.
• Keep the fire alarm and the air outlet at least 1.5m away from
the unit.
ELECTRICAL REQUIREMENTS
1. All wiring must conform to the local electrical codes.
Consult your dealer or a qualified electrician for details.
2. Each unit must be properly grounded with a ground (or
earth) wire or through the supply wiring.
3. Wiring must be done by a qualified electrician.
• Do not let children play with the air conditioner.
• Do not cool or heat the room too much if babies or invalids
are present.
NOTE
• Do not sit or step on the unit. You may fall down
accidentally.
• Do not stick any object into the FAN CASE.
You may be injured and the unit may be damaged.
Pull off the power plug from a receptacle, or switch off the breaker, or
switch off the power disconnecting mean to isolate the air conditioner
from the main power supply when not in use for a long time.
SAFETY INSTRUCTIONS
• Read this Instruction Manual carefully before using
this air conditioner. If you still have any difficulties
or problems, consult your dealer for help.
• This air conditioner is designed to give you
comfortable room conditions. Use this only for its
intended purpose as described in this Instruction
Manual.
NOTICE
• This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including
interference that may cause undesired operation.
• This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15 of
the FCC Rules.
These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio
communications. However, there is no guarantee that
interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference
by one or more of the following measures:
• Confirm to authorized dealer or specialist on usage of
specified refrigerant type.
Using of refrigerant other than the specified type may cause
product damage, burst and injury etc.
• Never touch the unit with wet hands.
• Never use or store gasoline or other flammable vapor or
liquid near the air conditioner — it is very dangerous.
• Do not use this appliance in a potentially explosive
atmosphere.
• This air conditioner has no ventilator for intaking fresh air
from outdoors. You must open doors or windows frequently
when you use gas or oil heating appliances in the same
room, which consume a lot of oxygen from the air.
Otherwise there is a risk of suffocation in an extreme case.
• Do not swallow the battery.
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for
help.
• After removing the battery from remote controller, keep it
away from the reach of children. The battery can cause
death by suffocation if swallowed.
• FCC Caution: To assure continued compliance, follow the
attached installation instructions. Any changes or modifications
not expressly approved by the party responsible for compliance
could void the user's authority to operate this equipment.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOTE CONTROLLER
NOTE
The descriptions on the AUTO ( ) or HEAT ( ) operation mode are only for the “COOL/DRY/HEAT Model,” and not for the
“COOL/DRY Model.”
Display
Information on the operating conditions is displayed while the remote
controller is switched on. If the unit is turned off, only the mode that was set
previously is still displayed.
Temperature setting buttons (TEMP.)
Press the
button to increase the set temperature.
Press the
button to reduce the set temperature.
The temperature setting changes by 2 °F each time one of the TEMP. buttons
is pressed.
FAN SPEED selector button
: The air conditioner automatically decides the fan speeds.
: High fan speed
: Medium fan speed
: Low fan speed
NIGHT SETBACK button
For details, see “5. Night Setback Mode”. When you press this button in the
HEAT, DRY or COOL mode, the
mark appears in the display, and the
remote controller will automatically adjust the set temperature to save energy.
FLAP button
Press this button either to select the setting of the airflow direction to one of
the six possible positions manually or to select the sweep function which
moves the flap up and down automatically.
: The airflow direction can be set manually. (six positions)
: The flap moves up and down automatically.
NOTE
When you press the FLAP button, the air flow direction will be changed one by
one as follows.
SWEEP
ACL button (ALL CLEAR)
Timer and Present Time setting buttons
First, press the SET button to select the mode (ON, OFF and Present Time
settings) you want.
Each time you press the ‘‘HH’’ button, the hours advance by one.
(PM0, PM1.....PM11, AM0, AM1.....AM11)
When you press the ACL button while the
operation button is ON, all settings are cleared.
Press the ACL button if the air conditioner is not
operating correctly.
Each time you press the ‘‘MM’’ button, the minutes advance by one when
setting Present Time and by ten when setting ON and OFF Time.
SET button
For details, see “SETTING THE TIMER”.
Press this button to select the mode you want to program.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
ON/OFF operation button
This button is for turning the air conditioner on and off.
MODE selector button
Use this button to select AUTO, HEAT, DRY, COOL or FAN mode.
(AUTO)
: When this setting is selected, the air conditioner calculates the difference between the
thermostat setting and the room temperature and automatically switches to the ‘‘COOL’’ or
‘‘HEAT’’ mode as appropriate. (This function is available only for “Single use” of COOL/DRY/
HEAT Model.)
(HEAT)
(DRY)
(COOL)
(FAN)
: The air conditioner makes the room warmer.
: The air conditioner reduces the humidity in the room.
: The air conditioner makes the room cooler.
: The air conditioner works only as a circulation fan except for “Multiple use” of COOL/DRY/
HEAT Model.
1 HR. TIMER button (1-HOUR OFF TIMER)
: When you press this button, regardless of whether the unit is operating or stopping, the unit operates for
one hour and then shuts down.
TIMER SELECT button
No display :The timer does not operate.
:
:
The air conditioner starts at the set time.
The air conditioner stops at the set time.
:
The air conditioner stops and starts, or starts and stops, at the set times every day.
Sensor
A temperature sensor inside the remote controller senses the room temperature.
SENSOR button
When you press this button (use a small-tipped object such as a ballpoint pen), the
mark will disappear at the
display. And the room temperature is detected by the sensor which is built into the remote controller and the air
conditioner is controlled accordingly.
NOTE
If the remote controller is located near a heat source, such as a space heater or in direct sunlight, press the
SENSOR button to switch to the sensor on the indoor unit.
NOTE
The indoor fan runs continuously when the system is in normal operation. It does not turn off when the desired room temperature is
reached. If Night Set Back mode is selected, the fan will turn off intermittently during cooling operation in order to control air flow.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
REMOTE CONTROLLER (DISPLAY)
Displayed when indoor unit sensor
is in use
Displayed when operating NIGHT
SETBACK mode
Displayed when setting
temperature
Displayed when temperature is
shown
Displayed when setting timer
Symbols
(3) Temperature setting
(1) Operation mode
60 – 86 °F..............................
AUTO .....................................
(only for COOL/DRY/HEAT
Model)
HEAT......................................
(only for COOL/DRY/HEAT
Model)
When set to 80 °F
temperature indication ...........
(4) Timer
24-hour clock with ON/OFF
program Timer .......................
MILD DRY ..............................
COOL.....................................
FAN ........................................
ON Timer. ..............................
OFF Timer. ............................
1-hour OFF Timer..................
(5) NIGHT SETBACK..................
(2) Fan speed
Automatic operation ...............
HIGH .....................................
MEDIUM.................................
LOW.......................................
(6) Flap angle indication..............
Sweep indication....................
6
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION WITH THE REMOTE CONTROLLER
1. Automatic Operation
2. Manual Operation
(only for COOL/DRY/HEAT Model)
• Single use
This unit automatically switches between cooling operation and
heating operation according to the difference between the room
temperature and the temperature setting.
• Multiple use
The air conditioner calculates the difference between the
thermostat setting and room temperature, and automatically
determines the mode to operate under cooling or heating. Then,
the air conditioner continuously operates under the mode selected
at initial operation.
STEP 2
STEP 3
STEP 1
STEP 4
STEP 5
Check that the circuit breaker on the power panel is
turned on.
NOTE
STEP 2
STEP 1
If the automatic operation settings of the unit do not
meet your needs, press the setting buttons as
described below and change the settings as desired.
STEP 1
Press the MODE selector button
and select the desired mode.
For heating operation
Check that the circuit breaker on the power panel is
turned on.
o
o
o
o
NOTE
For dehumidifying operation
For cooling operation
For fan only operation
(No Fan mode in “Multiple use” of
COOL/DRY/HEAT Model)
Once
mode is selected and the unit is preset by
following the steps below, you can have the air
conditioner automatically bring the room to the desired
temperature simply by pressing the ON/OFF operation
button.
STEP 2
STEP 3
To start the air conditioner, press the ON/
OFF operation button.
Press the TEMP. setting buttons to change
the temperature setting to the desired
temperature.
STEP 1
STEP 2
Press the MODE selector button to
Press the ON/OFF operation button.
.
Adjustable temperature range:
86 °F max.
60 °F min.
To stop the air conditioner, press the ON/OFF operation
button again.
STEP 4
STEP 5
Set the FAN SPEED selector button to the
setting you want.
Press the FLAP button and set the airflow
direction as desired.
(Refer to “ADJUSTING THE AIRFLOW
DIRECTION” on page 10.)
To change the temperature setting; press the
temperature setting buttons and change the setting to
the desired temperature.
NOTE
To stop the air conditioner, press the ON/OFF
operation button again.
• Choose the best position in the room for the remote
controller, which also acts as the sensor for room
comfort and transmits the operating instructions.
Once you’ve found this best position, always keep the
remote controller there.
NOTE
• This appliance has a built-in 5-minute time delay
circuit to ensure reliable operation. When the
operation button is pressed, the compressor will start
running within three minutes. In the event of power
failure, the unit will stop.
• The display on the remote controller shows the setting
temperature and not the room temperature.
• When multiple indoor units are used and units in other
rooms are already operating, they will be operating
with the same mode as the operating indoor units.
(only for “Multiple use” of COOL/DRY/HEAT Model)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
A. In Cooling and DRY Mode: ( and
)
3. Adjusting the Fan Speed
A. Automatic fan speed
Simply set the FAN SPEED selector button to the
position.
This automatically sets the best fan speed for the room
temperature.
B. Manual fan speed
When the night setback mode is selected, the air conditioner
automatically raises the temperature setting 2 °F when 30 minutes
have passed after the selection was made, and then another 2 °F
after another 30 minutes have passed, regardless of the indoor
temperature when night setback was selected. This enables you
to save energy without sacrificing comfort. This function is
convenient when gentle cooling is needed.
If you want to adjust fan speed manually during operation,
just set the FAN SPEED selector button as desired. [
, or
,
]
2 °F
4. Fan Only
Setting
temperature
2 °F
30 min.
30 min.
STEP 2
STEP 1
Press the NIGHT
SETBACK button
Time
STEP 3
B. In Heating Mode: (
)
(only for COOL/DRY/HEAT Model)
When the night setback mode is selected, the air conditioner
automatically lowers the temperature setting 4 °F when 30
minutes have passed after the selection was made, and then
another 4 °F after another 30 minutes have passed, regardless of
the indoor temperature when night setback was selected. This
enables you to save energy without sacrificing comfort. This
function is convenient when gentle heating is needed.
If you want to circulate air without any temperature
control, follow these steps:
STEP 1
Press the MODE selector button to switch to
the fan mode
Setting
temperature
4 °F
.
4 °F
STEP 2
STEP 3
Press the ON/OFF operation button.
Press the FAN SPEED selector button to
select the fan speed of your choice (
or ).
,
30 min.
30 min.
Time
Press the NIGHT
SETBACK button
There is no FAN only function in “Multiple use” of
COOL/DRY/HEAT Model.
NOTE
5. Night Setback Mode
SPECIAL REMARKS
Power failure during operation
In the event of power failure, the unit will stop. When the power is
resumed within 8 hours, the unit will restart automatically in
approximately five minutes, or 15 minutes in “Multiple use” of COOL/
DRY/HEAT Model on AUTO mode by the remote controller.
Remote Controller
The remote controller sends the setting condition to the air
conditioner regularly at five minute intervals.
Remote Controller Display
If the display malfunctions, press the ACL button.
This resets the remote controller back to the initial settings.
Make the settings again.
Night Setback Mode is used for saving energy.
Press the NIGHT SETBACK button while unit is operating.
The
mark appears in the display.
To release the night setback function, press the NIGHT SETBACK
button again.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
3. How to set the ON time
(Example) To start operation at 7:10 am.
SETTING THE TIMER
ON TIME
Present time
Indication
Operation
1. Press the SET button once.
The timer
indication alone
flashes and the previous set-
time is only displayed.
2. • Press the HH button until
AM 7 is displayed.
The display will change
automatically back to show the
present time after about 10 sec.
1. How to set the present time
(Example) To set to 9:10 pm.
• Press the MM button until
10 is displayed.
3. Press the TIMER SELECT
The present time and
displayed.
are
button once to set ON time.
To cancel the setting, press the TIMER SELECT button three times.
4. How to set daily ON/OFF repeat timer
Operation
Indication
(Example) To start operation at 7:10 am. and stop the air conditioner
at 11:30 pm.
1. Press the SET button three
The time indication alone
flashes.
times.
2. • Press the HH button until
PM 9 is displayed.
The display will flash for 10 sec.
and automatically stop flashing
except for the “ : ” symbol.
• Press the MM button until
10 is displayed.
2. How to set the OFF time
(Example) To stop the air conditioner at 11:30 pm.
Present time
ON TIME
OFF TIME
Programmed
daily ON / OFF
OFF TIME
Present time
9:10 pm.
Present time
7:10 am.
ON
11:30pm.
OFF
Operation
Indication
1. Press the SET button twice.
The timer
indication alone
flashes and the previous set-
time is only displayed.
2. • Press the HH button until
PM 11 is displayed.
The display will change
automatically back to show the
present time after about 10 sec.
Operation
Indication
Set the timer ON/OFF times as The present time PM 9:10 and
shown in 2 and 3.
• Press the MM button until
30 is displayed.
are displayed.
3. Press the TIMER SELECT
The present time and
button twice to set OFF time. displayed.
are
To cancel the setting, press the TIMER SELECT button once.
NOTE
To cancel the setting, press the TIMER SELECT button twice.
You can check the timer ON/OFF times after you have set them by
pressing the SET button.
5. Backup function
Even if the main power supply to the unit is turned off, the remote
controller will store the previous settings in its internal memory for up
to 8 hours. If the power is not turned back on within 8 hours, the
previous settings will be lost. In this case, the mode settings must be
reset by the user.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
USING THE 1-HOUR OFF
TIMER
ADJUSTING THE AIRFLOW
DIRECTION
The vertical airflow can be adjusted by moving the flap with the
remote controller. Do not move the flap with your hands. Confirm that
the remote controller has been turned on. Use the FLAP button to
set either the sweep function or one of the six airflow direction
settings.
1. 1-Hour OFF Timer
This function causes the unit to operate for one hour and then
stop, regardless of whether the unit is on or off when this
button is pressed.
A. Sweep function
The flap starts moving
up and down to deliver
air over the sweep
range.
The
indicator in the display indicates that this function is
operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1
HR. TIMER button.
B. Setting the airflow manually
appears in the display.
SWEEP
Referring to the above
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the
unit to stop operating, and then press the ON/OFF operation button
again.
The 1-Hour Timer function is now cancelled and the unit operates
normally.
illustration, use the
FLAP button to set the
airflow direction within
the range used during
the heating, cooling, or
dehumidifying
COOL
DRY
FAN
SWEEP
HEAT
operation.
NOTE
• If, while the 1-Hour Timer function is operating, the 1HR. TIMER
button is pressed once to cancel the function and then again, the
unit continues to operate for one hour from that point in time and
then stops.
• It is not possible to use the OFF Timer and 1-Hour OFF Timer
together. Whichever function is set last takes precedence. If the 1
HR. TIMER button is pressed while the TIMER OFF function
operates, the OFF Timer is cancelled and the unit will stop
operating one hour later.
NOTE
• The flap automatically closes when the unit is off.
• During the heating operation, the fan speed will be very low and the
flap will be in the horizontal position (position ) until the air being
blown out of the unit begins to warm. Once the air warms up, the
flap position and fan speed change to the settings specified with
the remote controller.
CAUTION
2. Operation together with the daily ON/OFF
repeat timer
• Use the FLAP button on the remote controller to adjust the
position of the flap. If you move the flap by hand, the flap
position according to the remote controller and the actual
flap position may no longer match. If this should happen,
shut off the unit, wait for the flap to close, and then turn on
the unit again; the flap position will now be normal again.
• Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip
down.
The 1-Hour OFF Timer setting is given priority over the DAILY ON/
OFF REPEAT setting.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX B INSTALLATION INSTRUCTIONS
(CZ-RD515U)
CZ-RD515U
(852-6-4190-592-00-0)
A-2
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
Wired Remote Controller
In order to install this wired remote controller onto a wall-mounted model, the connection kit
IMPORTANT
(CZ-RC515U or CZ-RC515UA), which must be purchased separately, is required.
Once the wired remote controller is connected, the wireless remote controller cannot be used.
Table 1
Parts supplied with the remote controller
See Table 1.
Parts
Figure
Q'ty
Parts
Figure
Q'ty
26.2 ft. (8m)
Wired
remote
controller
Wire
harness
Remote controller installation guidelines
1
1
Installation location
Mount the remote controller 3.3 to 4.9 ft. (1 to 1.5
meters) off the floor where it can sense the average
temperature of the room.
5/32 15/16"
(4 25mm)
Machine
screws
Instruction
manual
2
2
2
1
1
Do not mount the remote controller in a place
exposed to direct sunlight or where it is exposed to
outside air such as near a window.
5/32 15/16"
(4 25mm)
Tapping
screws
Installation
Instructions
Do not mount the remote controller behind a curtain or
other object so that it is separated from the air circula-
tion of the room.
Mount the remote controller inside the room being air
Spacers
conditioned.
Switching the room temperature sensor
Room temperature sensors are separately incorporated in both the indoor unit and the remote controller. Either sensor can
be used to sense the room temperature. The indoor unit sensor is usually used.
If you wish the remote controller to sense the room temperature, press the SENSOR button with a ballpoint pen or tool with
a small tip. (Refer to Fig. 9 on page 4 to locate the SENSOR button.)
How to install the remote controller
IMPORTANT
The remote controller is set to “Cool/Dry/Heat model” at
the time of shipment from the factory. If the purchased air
conditioner is a COOL/DRY model, follow the instructions
on the label and change the switch on the reverse side of
the remote controller unit to “Cool/Dry model”. (Fig. 1)
The remote controller is also set to “Single” at the time of
shipment from the factory. For multiple use, set the
switch on the reverse side of the remote controller unit to
“Multi”. (Fig. 1)
After all work is completed, if any switches have been
changed, then be sure to press the ACL (Reset) button.
(Refer to Fig. 9 on page 4 to locate the ACL (Reset) but-
ton.)
Fig. 1
CV6233187884
85264190592000 2011
Download from Www.Somanuals.com. All Manuals Search And Download.
A. Installing with in-wall junction box
In-wall junction box (locally purchased)
(1) Install the junction box (locally purchased) into the wall.
(Figs. 2-a and 3)
(2) Pass the wire harness through the junction box and
conduit. (Fig. 3)
Tab
(3) Insert a flathead screwdriver into the 5 tab locations
and disconnect the back plate of the remote controller by
lifting up slightly. (Fig. 2-b)
2-3/8"
(60mm)
Back
plate
The tabs are thin; take care not to chip them.
Fig. 2-a
Fig. 2-b
(4) Pass the wire harness connector through the cord open-
ing on the back plate of the remote controller.
from the indoor unit
Use nippers or a similar tool to cut out the slots for the
remote controller back plate screws. Insert the spacers
and use the machine screws to install the remote con-
troller back plate. (Fig. 3)
In-wall junction box
(5) Insert the connector into the PCB of the remote controller
unit, and wrap the wire harness around the hook. (Fig. 4)
Opening
Wire harness
(6) Store the excess wire harness inside the junction box,
then hook the remote controller unit onto the top of the
back plate and install the remote controller unit.
(7) To remove the remote controller unit after it has been
installed, insert a flathead screwdriver into the slot on the
bottom of the case and turn it. (Fig. 5)
Wall
Spacers
Back plate
Machine
screws
B. Installing directly onto the wall
Remote
controller
(1) Insert a flathead screwdriver into the 5 tab locations and
disconnect the back plate of the remote controller by lift-
ing up slightly. (Fig. 2-b)
Fig. 3
The tabs are thin; take care not to chip them.
PCB
(2) Use tapping screws to directly fasten the remote con-
troller back plate onto the wall. (Fig. 6)
(3) Insert the connector into the PCB of the remote controller
unit, and wrap the wire harness around the hook. (Fig. 4)
Hook
Slot
(4) Use nippers or a similar tool to cut out the slot on the top
of the remote controller unit. Pass the wire harness
through the slot, then hook the remote controller unit
onto the top of the back plate and install the remote con-
troller unit.
Connector
Fig. 4
Fig. 5
(5) In order to conceal the exposed wiring, use a wire cover
(locally purchased) or similar means.
NOTE
Wire harness
Cut out
When installing the remote controller back plate, be sure
that it is flat and straight. Do not over-tighten the installa-
tion screws.
Install the remote controller away from all sources of elec-
Wall
trical noise.
Back plate
Install a noise filter or take other appropriate action if elec-
Tapping
screws
trical noise affects the power supply circuit of the unit.
Remote
controller
Fig. 6
2
Download from Www.Somanuals.com. All Manuals Search And Download.
7P IND and 4P RC
wiring connector
5P FLAP
wiring connector
How to wire the remote controller
Ceiling
panel
(1) Turn OFF the power and remove the ceiling panel
air-intake grille. (Refer to 3-6-1 Before Installing the
Ceiling Panel in the Installation Instructions supplied
with the indoor unit.)
(2) Remove the 3 power box cover screws and 2 control
box cover screws, then remove both covers. At this
time, take care not to drop the covers. (Fig. 7)
Control
box
cover
(3) Disconnect the 7P (IND) terminal and 4P (RC) termi-
nal of the 7P IND and 4P RC wiring connectors and
the 5P terminal of the 5P FLAP wiring connector
from the control box PCB connectors (IND, RC,
FLAP). Disconnect each wiring connector from the
clamp that fastens it. (Fig. 7)
Power box cover
Indicator
(4) Remove the ceiling panel. (To remove the ceiling
panel, follow the steps for 3-6 How to Install the
Ceiling Panel in the reverse order. Refer to the
Installation Instructions supplied with the indoor unit.)
Fig. 7
Fig. 8-a
Indicator
7P IND and 4P RC
wiring connector
5P FLAP
7P IND and 4P RC
wiring connector wiring connector
Ceiling
panel
Clamps
Wire harness
Remote
controller
4P
7P
5P FLAP
wiring
connector
Control PCB
Putty
Terminal cover
Wire harness
Indicator
Wire harness
Clamping strap
Fig. 8-b
Fig. 8
(5) Remove the terminal cover screws, then remove the cover. At this time, take care not to drop the cover. (Fig. 8)
(6) Pull in the wire harness from the remote controller as shown in Fig. 8-b.
Remove the putty before wiring. After wiring, make sure to restore the putty.
(7) Insert the wire harness 4P terminal into the control box PCB connector (RC). (Fig. 8-a)
(8) Install the terminal cover. Then install the ceiling panel. (Refer to 3-6 How to Install the Ceiling Panel in the
Installation Instructions supplied with the indoor unit.)
(9) Insert only the 7P (IND) terminal of the 7P IND and 4P RC wiring connector into the connector (IND) on the control
box PCB. Store the 4P terminal inside the control box. (Fig. 8-a)
(10) Next, insert the 5P terminal of the 5P FLAP wiring connector into the connector (FLAP) on the control box PCB.
(Fig. 8-a)
(11) When the connections are completed, fasten the wire harness and each wiring connector with the clamps.
(12) Install the power box cover and control box cover.
(13) Install the air-intake grille. (Refer to 3-6 How to Install the Ceiling Panel in the Installation Instructions supplied
with the indoor unit.)
3
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Test Run the Air Conditioner
After turning on the power of the air conditioner, use the
remote controller and follow the steps below to conduct
the test run.
(1) Set the remote controller in Test Run mode. (Fig. 9)
a)Press and hold the NIGHT SETBACK button and
the 1HR. TIMER button.
ON/OFF
operation button
b)Then press and hold the ACL (Reset) button with
a pointed object such as the tip of a pen. After 5
seconds, release the ACL button first.
NIGHT SETBACK
button
1 HR.TIMER
button
c)Then release the NIGHT SETBACK and 1HR.
TIMER buttons.
d)
appears and “oP-1” blinking in the remote
controller clock display area. (Fig. 10)
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 9)
ACL (Reset)
button
SENSOR button
This starts the fan producing uncooled forced air
with the 3 indicator lamps (OPERATION lamp,
TIMER lamp, and HIGH POWER lamp) on the
main unit blinking. (Fig. 11)
Fig. 9
After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cooling
mode test run is unaffected by the room tempera-
ture.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 9)
Fig. 10
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to return
to normal mode. (Fig. 9)
“ ” and “oP-1” will disappear from the remote
controller clock display area.
NOTE
Troubleshooting:
In the event that the green OPERATION lamp is blink-
ing upon powering up the system, an error condition
exists. In this case, refer to the self-diagnostics proce-
dure which can be seen by opening the air-intake grille.
OPERATION button
OPERATION lamp
TIMER lamp
HIGH POWER lamp
IMPORTANT
REMOTE CONTROL receiver
Fig. 11
After the test run is completed, be sure to press the
ACL (Reset) button to return to normal mode. The air
conditioner will not operate correctly if this is not done.
WI1011-0
Printed in China
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX C INSTALLATION INSTRUCTIONS
Installing the Connection Kit
(
)
for Wall-Mounted Models
CZ-RC515U
(852-6-4190-590-00-0)
A-3
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
Connection Kit
Parts included in the package
See Table 1.
Table 1
Parts
Figure
Q'ty
Parts
Figure
Q'ty
Parts
Figure
Q'ty
Truss-head Phillips
5/32 13/32"
Tapping
screw
Clamping
strap
1
1
(4 10mm
)
Wire
(with a
1
7-3/32"(180mm
)
noise filter)
Clamp
Label
2
1
Wire tube
1
Top cover
Installation
instructions
1
Installing the connection kit
A. 7000 BTU, 9000 BTU, and 12000 BTU inverter models
(1) Remove the air intake grille.
Screw
Tab
(2) Remove the terminal cover. Pull out the thermistor, then remove the grille.
For details on steps (1) and (2), refer to the Installation Instructions
Screw
included in the outdoor unit package.
(3) Disengage the top cover from the tabs on the sides of the component
box, then pull the cover toward you to remove it. (Fig. 1)
(To disengage the tabs, pull the sides of the top cover sideways and out-
ward from the component box.)
Component box
P.C. board
(4) Remove the 4 component box
Fig. 1
Connector (10P)
installation screws. (Fig. 1)
(5) Disconnect the indicator-side connec-
tor (10P) of the wires that connect the
indicator and component box (Fig. 2a).
Then disconnect the connector on the
component box side (10P) and remove
the wires. (Lifting the P.C. board up
slightly will make this work easier.)
(Fig. 2b)
Indicator
Connector (10P)
Fig. 2a
Fig. 2b
Connector 2
(10P)
Connector 3
(4P)
(6) After removing the wires, insert
Connector 1 of the wires (Fig. 3a) that
were included in the kit package into
the indicator (Fig. 2a), then insert
Connector 2 into the component box.
(Fig. 2b)
Holder
Noise filter
At this time, pass the wires through so
that they are held inside the 2 holders
on the sides of the component box.
(Fig. 3b)
Fig. 3b
Connector 1
(10P)
Fig. 3a
CV6233187907
85264190590000 2011
Download from Www.Somanuals.com. All Manuals Search And Download.
(7) Feed the wire harness that was included in the wired remote controller package
into the right lower rear of the unit and route it to the component box. (Fig. 4a)
Component box
Wire harness
When feeding the wire harness through the opening, be careful of the motor
cable and be sure to feed the wire harness and motor cable together through
the opening. (Fig. 4b)
Be careful not to damage the wire harness when installing the conduit during
unit installation work.
Motor cable
Opening
Wire harness
Fig. 4a
Fig. 4b
Connector 3
(4P)
Connector 3
(4P)
(8) Cut the wire tube that was included in the kit package to a length
Connector (4P)
of approximately 4 inches (100 mm), then feed the wire harness
through it. Then connect Connector 3 (Fig. 3a) to the wire harness
connector (4P). (Fig. 4c)
Wire harness
Wire tube
(9) Take the wires (Fig. 3a) and use a wire clamp to bind together the
Connector (4P)
wire for the noise filter and the wire for the thermistor (Fig. 5a). Then
position them so that the noise filter is contained within the space of
the component box. (Fig. 5b)
Fig. 4c
Noise filter
Wire tube
Component box
Clamp
Clamp
Clamping strap
Screw
Thermistor
Wire harness
Fig. 5a
Fig. 5b
Fig. 6a
(10) Pass the wire tube through the clamping strap, and temporarily fasten in place with the screw.
Next, use a clamp and bind the wires together immediately above the clamping strap, and
fasten in place with the screw in order to prevent pulling on the wire harness. (Fig. 6a)
Install the wire tube so that the wires cannot be damaged by the edge of the metal plate.
(Fig. 6a)
When re-installing the grille, confirm that there is no slack in the wire harness wires.
(11) Tighten the 4 screws to install the component box, taking care not to pinch any of the wires,
then install the top cover. (Fig. 6b)
(12) Route the wire harness out through the small cut-out located at the bottom right side of the
indoor unit frame. (Fig. 7a)
Self-diagnostic label
Wire harness
(13) Apply the label that was included in
<
Completion drawing
>
Air intake grille
the package at a location close to
the self-diagnostic label applied to
the air intake grille. (Fig. 7b)
Fig. 6b
Label
(14) Refer to the Installation Instructions
that were included in the outdoor
unit package and re-install the
Cut-out
grille, thermistor, terminal cover,
and air intake grille.
Fig. 7a
Fig. 7b
2
Download from Www.Somanuals.com. All Manuals Search And Download.
B. 18000 BTU and 24000 BTU inverter models
(1) Remove the air intake grille.
(2) Remove the terminal cover. Pull out the thermistor, then remove the grille.
For details on steps (1) and (2), refer to the Installation Instructions included in
the outdoor unit package.
(3) Disengage the top cover from the tabs on the sides of the component box, then
pull the cover toward you to remove it. (Fig. 1)
(To disengage the tabs, pull the sides of the top cover sideways and outward
from the component box.)
(4) Disconnect the indicator-side connector (10P) of the wires that connect the indi-
cator and component box (Fig. 2a). Then disconnect the connector on the com-
ponent box side (10P) and remove the wires. (Lifting the P.C. board up slightly
will make this work easier.) (Fig. 2b)
(5) After removing the wires, insert Connector 1 of the wires (Fig. 3a) that were
included in the kit package into the indicator (Fig. 2a), then insert Connector 2
into the component box. (Fig. 2b)
< Completion drawing >
At this time, pass the wires through so that they are held inside the 2 holders on
the sides of the component box. (Fig. 3b)
Fig. 8
(6) Feed the wire harness that was included in the wired remote controller package
into the right lower rear of the unit. (Fig. 4a)
Be careful not to damage the wire harness when installing the conduit during
unit installation work.
(7) Pass the wire harness through the wire tube that was included in the kit package.
Then connect Connector 3 (Fig. 3a) to the wire harness connector (4P). (Fig. 4c)
(8) Take the wires (Fig. 3a) and use a wire clamp to bind together the wire for the
noise filter and the wire for the thermistor (Fig. 5a). Then position them so that
the noise filter is contained within the space of the component box. (Fig. 5b)
(9) Pass the wire tube through the clamping strap, and temporarily fasten in place
with the screw. Next, use a clamp and bind the wires together immediately above
the clamping strap, and fasten in place with the screw in order to prevent pulling
on the wire harness. (Fig. 6a)
Install the wire tube so that the wires cannot be damaged by the edge of the
metal plate. (Fig. 6a)
When re-installing the grille, confirm that there is no slack in the wire harness
wires.
(10) Install the top cover on the component box. (Fig. 8)
(11) Route the wire harness out through the small cut-out located at the bottom right
side of the indoor unit frame. (Fig. 7a)
(12) Apply the label that was included in the package at a location close to the self-
diagnostic label applied to the air intake grille. (Fig. 7b)
(13) Refer to the Installation Instructions that were included in the outdoor unit pack-
age and re-install the grille, thermistor, terminal cover, and air intake grille.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
How to Test Run the Air Conditioner
After turning on the power of the air conditioner, use the
remote controller and follow the steps below to conduct
the test run.
(1) Set the remote controller in Test Run mode. (Fig. 9)
a) Press and hold the NIGHT SETBACK button and
the 1HR. TIMER button.
ON/OFF
operation button
b) Then press and hold the ACL (Reset) button with
a pointed object such as the tip of a pen. After 5
seconds, release the ACL button first.
NIGHT SETBACK
button
c) Then release the NIGHT SETBACK and 1HR.
TIMER buttons.
1 HR.TIMER
button
d)
appears with “oP-1” blinking in the remote
controller clock display area. (Fig. 10)
(2) Start Cooling mode test run by pressing the
ON/OFF operation button of the remote controller.
(Fig. 9)
ACL (Reset)
button
SENSOR button
This starts the fan producing uncooled forced air
with the 3 indicator lamps (OPERATION lamp,
TIMER lamp, and QUIET lamp) on the main unit
blinking. (Fig. 11)
Fig. 9
After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cooling
mode test run is unaffected by the room tempera-
ture.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 9)
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to return
to normal mode. (Fig. 9)
Fig. 10
“ ” and “oP-1” will disappear from the remote
controller clock display area.
NOTE
OPERATION lamp
TIMER lamp
Troubleshooting:
QUIET lamp
In the event that the green OPERATION lamp is blink-
ing upon powering up the system, an error condition
exists. In this case, refer to the self-diagnostics proce-
dure on the inside of the air-intake grille.
IMPORTANT
After the test run is completed, be sure to press the
ACL (Reset) button to return to normal mode. The air
conditioner will not operate correctly if this is not done.
Fig. 11
WI1011-0
Printed in Japan
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX D INSTALLATION INSTRUCTIONS
Installing the Connection Kit
for Wall Mounted Type 2
(
)
CZ-RC515UA
(852-6-4190-591-00-0)
A-4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION INSTRUCTIONS
Connection Kit
ꢀ Parts included in the package
See Table 1.
Table 1
Parts
Figure
Q'ty
Parts
Figure
Q'ty
Parts
Figure
Q'ty
Truss-head Phillips
5/32 13/32"
Tapping
screw
Clamping
strap
Noise filter
1
1
1
(4 10mm
)
Installation
instructions
Label
1
Clamp
2
1
ꢀ Installing the connection kit
Ta b
ꢁRQꢀWRSꢃ
(1) Remove the air intake grille.
ꢀ)RUꢀWKHꢀGHWDLOVꢀRIꢀVWHSꢀꢁꢂꢃꢄꢀUHIHUꢀWRꢀWKHꢀ,QVWDOODWLRQꢀ
,QVWUXFWLRQVꢀWKDWꢀZHUHꢀSURYLGHGꢀZLWKꢀWKHꢀRXWGRRUꢀXQLWꢅ
(OHFWULFDOꢀER[ꢀFRYHU
ꢁꢆꢃ 'LVHQJDJHꢀWKHꢀWDEꢀRQꢀWKHꢀERWWRPꢀRIꢀWKHꢀHOHFWULFDOꢀER[
FRYHUꢄꢀWKHQꢀOLIWꢀXSꢀWKHꢀFRYHUꢀDQGꢀGLVHQJDJHꢀWKHꢀWDEꢀRQꢀWKH
WRSꢀRIꢀWKHꢀFRYHUꢅꢀ7KHQꢀUHPRYHꢀWKHꢀHOHFWULFDOꢀER[ꢀFRYHUꢅ
ꢁ)LJꢅꢀꢂꢃ
ꢁꢇꢃ 'LVFRQQHFWꢀ&RQQHFWRUꢀꢂꢀꢁꢈ3ꢃꢄꢀ&RQQHFWRUꢀꢆꢀꢁꢉ3ꢃꢄꢀDQGꢀ
&RQQHFWRUꢀꢇꢀꢁꢊ3ꢃꢀIURPꢀWKHꢀ3&ꢀERDUGꢀꢁ3&%ꢃꢅꢀꢁ)LJꢅꢀꢆꢃ
Ta b
ꢁꢋꢃ 'UDZꢀWKHꢀ3&%ꢀDSSUR[LPDWHO\ꢀKDOIꢌZD\ꢀRXWꢀRIꢀWKHꢀHOHFWULFDO
ER[ꢅꢀ:KHQꢀGUDZLQJꢀLWꢀRXWꢄꢀSXVKꢀWKHꢀUHWDLQHUꢀWDEꢀWKDWꢀIDVꢌ
WHQVꢀWKHꢀ3&%ꢀLQꢀSODFHꢀVOLJKWO\ꢀWRZDUGꢀWKHꢀRXWVLGHꢅꢀꢁ)LJꢅꢀꢇꢃ
(on bottom)
Fig. 1
Draw the PCB out carefully so that
CAUTION
the wiring inside the electrical box
does not damage the capacitor, IC,
or other components.
&RQQHFWRUꢀꢂ
3&%
3&%
&RQQHFWRUꢀꢆ
2. Draw out halfway
Retainer tab
&RQQHFWRUꢀꢇ
1. Push to side slightly
(OHFWULFDOꢀER[
(OHFWULFDOꢀER[
Fig. 2
Fig. 3
85264190591000 2011
CV6233187891
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢁꢊꢃ 0RYHꢀWKHꢀMXPSHUꢀFDSꢀWRꢀ:'ꢀꢁ)LJꢅꢀꢋꢃꢄꢀWKHQꢀFRQQHFWꢀWKHꢀQRLVHꢀILOWHUꢀ&RQQHFWRUꢀ$ ꢁꢇ3ꢃꢀWRꢀWKHꢀ3&%ꢀVRFNHWꢀꢁ/$03ꢌꢂꢃ
DQGꢀFRQQHFWꢀWKHꢀRWKHUꢀQRLVHꢀILOWHUꢀ&RQQHFWRUꢀ%ꢀꢁꢋ3ꢃꢀWRꢀWKHꢀZLUHꢀKDUQHVVꢀFRQQHFWRUꢀꢁꢋ3ꢃꢀRQꢀWKHꢀZLUHGꢀUHPRWHꢀ
FRQWUROOHUꢅꢀꢁ)LJꢅꢀꢊꢃ
&RQQHFWRUꢀ$ꢀꢁꢇ3ꢃ
3&%
3&%
6RFNHWꢀꢁ/$03ꢌꢂꢃ
ꢁꢇ3ꢃ
&RQQHFWRUꢀ%ꢀꢁꢋ3ꢃ
-XPSHUꢀFDS
&RQQHFWRUꢀ%
ꢁꢋ3ꢃ
:'
:LUHꢀ
:LUHꢀKDUQHVV
KDUQHVV
1RLVHꢀILOWHU
Fig. 4
Fig. 5
ꢁꢍꢃ ,QVHUWꢀWKHꢀ3&%ꢀEDFNꢀLQWRꢀLWVꢀRULJLQDOꢀORFDWLRQꢀLQꢀWKHꢀHOHFWULFDOꢀER[ꢅ
ꢁꢈꢃ 5HFRQQHFWꢀWKHꢀWKUHHꢀFRQQHFWRUVꢀWKDWꢀZHUHꢀUHPRYHGꢀLQꢀVWHSꢀꢁꢇꢃꢅ
ꢁꢎꢃ 3DVVꢀWKHꢀZLUHꢀKDUQHVVꢀIURPꢀWKHꢀZLUHGꢀUHPRWHꢀ
FRQWUROOHUꢀWKURXJKꢀWKHꢀFODPSLQJꢀVWUDSꢄꢀDQGꢀWLJKWHQꢀWKH
FODPSLQJꢀVWUDSꢀVFUHZꢅꢀꢁ)LJꢅꢀꢍꢃ
Wire harness
Screw
To wired remote controller
Clamping strap
Fig. 6
2
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢁꢉꢃ ,QVHUWꢀWKHꢀQRLVHꢀILOWHUꢀLQWRꢀWKHꢀHOHFWULFDOꢀER[ꢄꢀWKHQꢀIDVWHQꢀWKHꢀQRLVHꢀILOWHUꢀ&RQQHFWRUꢀ%ꢀZLUHꢀDQGꢀWKHꢀZLUHꢀKDUQHVVꢀRIꢀWKH
ZLUHGꢀUHPRWHꢀFRQWUROOHUꢀDVꢀVKRZQꢀLQꢀWKHꢀILJXUHꢅꢀꢁ)LJꢅꢀꢈꢃ
ꢁꢂꢏꢃ ,QꢀRUGHUꢀWRꢀSUHYHQWꢀSXOOLQJꢀRQꢀWKHꢀKDUQHVVꢄꢀIDVWHQꢀWKHꢀSDUWꢀLPPHGLDWHO\ꢀDERYHꢀWKHꢀVWUDSꢀZLWKꢀDꢀFODPSꢅꢀꢁ)LJꢅꢀꢎꢃꢀ
NOTE
$IWHUꢀIDVWHQLQJꢄꢀFXWꢀDZD\ꢀWKHꢀH[FHVVꢀSDUWꢀRIꢀWKHꢀFODPSꢅ
Wire harness
Clamp
&ODPS
1RLVHꢀILOWHU
Fig. 8
:LUHꢀKDUQHVV
$LUꢌLQWDNHꢀJULOOH
Fig. 7
6HOIꢌGLDJQRVWLFV
label
ꢁꢂꢂꢃ 5HLQVWDOOꢀWKHꢀHOHFWULFDOꢀER[ꢀFRYHUꢅ
/DEHO
ꢁ6XSSOLHGꢃ
ꢁꢂꢆꢃ $SSO\ꢀWKHꢀVXSSOLHGꢀODEHOꢀFORVHꢀWRꢀWKHꢀVHOIꢌGLDJQRVꢌ
WLFVꢀODEHOꢀRQꢀWKHꢀLQVLGHꢀRIꢀWKHꢀUHPRYHGꢀDLUꢌLQWDNH
JULOOHꢅꢀꢁ)LJꢅꢀꢉꢃ
,QVLGHꢀDLUꢌLQWDNHꢀJULOOH
Fig. 9
ꢁꢂꢇꢃ 5HLQVWDOOꢀWKHꢀDLUꢌLQWDNHꢀJULOOHꢅ
ꢀ)RUꢀWKHꢀGHWDLOVꢀRIꢀVWHSꢀꢁꢂꢇꢃꢄꢀUHIHUꢀWRꢀWKHꢀ,QVWDOODWLRQ
,QVWUXFWLRQVꢀWKDWꢀZHUHꢀSURYLGHGꢀZLWKꢀWKHꢀRXWGRRU
XQLWꢅ
Open hole
:KHQꢀLQVWDOOLQJꢀWKHꢀDLUꢌLQWDNHꢀJULOOHꢄꢀLQVWDOOꢀLWꢀVRꢀWKDW
WKHꢀZLUHꢀKDUQHVVꢀIRUꢀWKHꢀZLUHGꢀUHPRWHꢀFRQWUROOHU
HPHUJHVꢀIURPꢀWKHꢀVPDOOꢀRSHQꢀKROHꢀRQꢀWKHꢀULJKWꢀVLGH
RIꢀWKHꢀJULOOHꢅꢀꢁ)LJꢅꢀꢂꢏꢃ
Wire harness
Fig. 10
3
Download from Www.Somanuals.com. All Manuals Search And Download.
ꢀ How to Test Run the Air Conditioner
$IWHUꢀWXUQLQJꢀRQꢀWKHꢀSRZHUꢀRIꢀWKHꢀDLUꢀFRQGLWLRQHUꢄꢀXVHꢀWKH
UHPRWHꢀFRQWUROOHUꢀDQGꢀIROORZꢀWKHꢀVWHSVꢀEHORZꢀWRꢀFRQGXFW
WKHꢀWHVWꢀUXQꢅ
ꢁꢂꢃ 6HWꢀWKHꢀUHPRWHꢀFRQWUROOHUꢀLQꢀ7HVWꢀ5XQꢀPRGHꢅꢀꢁ)LJꢅꢀꢂꢂꢃ
Dꢃ 3UHVVꢀDQGꢀKROGꢀWKHꢀ1,*+7 6(7%$&.ꢀEXWWRQꢀDQG
ON/OFF
WKHꢀꢂ+5ꢅꢀ7,0(5ꢀEXWWRQꢅ
operation button
Eꢃ 7KHQꢀSUHVVꢀDQGꢀKROGꢀWKHꢀ$&/ ꢁ5HVHWꢃꢀEXWWRQꢀZLWK
DꢀSRLQWHGꢀREMHFWꢀVXFKꢀDVꢀWKHꢀWLSꢀRIꢀDꢀSHQꢅꢀ$IWHUꢀꢊ
VHFRQGVꢄꢀUHOHDVHꢀWKHꢀ$&/ EXWWRQꢀILUVWꢅ
NIGHT SETBACK
button
Fꢃ 7KHQꢀUHOHDVHꢀWKHꢀ1,*+7 6(7%$&.ꢀDQGꢀꢂ+5ꢅ
1 HR.TIMER
button
7,0(5ꢀEXWWRQVꢅ
Gꢃ
DSSHDUVꢀZLWKꢀ´R3ꢌꢂµꢀEOLQNLQJꢀLQꢀWKHꢀUHPRWHꢀ
FRQWUROOHUꢀFORFNꢀGLVSOD\ꢀDUHDꢅꢀꢁ)LJꢅꢀꢂꢆꢃ
ꢁꢆꢃ 6WDUWꢀ&RROLQJꢀPRGHꢀWHVWꢀUXQꢀE\ꢀSUHVVLQJꢀWKH
21ꢐ2))ꢀRSHUDWLRQꢀEXWWRQꢀRIꢀWKHꢀUHPRWHꢀFRQWUROOHUꢅ
ꢁ)LJꢅꢀꢂꢂꢃ
ACL (Reset)
button
SENSOR button
7KLVꢀVWDUWVꢀWKHꢀIDQꢀSURGXFLQJꢀXQFRROHGꢀIRUFHGꢀDLU
ZLWKꢀWKHꢀꢇꢀLQGLFDWRUꢀODPSVꢀꢁ23(5$7,21ꢀODPSꢄ
7,0(5ꢀODPSꢄꢀDQGꢀ ꢃꢀRQꢀWKHꢀPDLQꢀXQLWꢀEOLQNLQJꢅ
ꢁ)LJꢅꢀꢂꢇꢃ
Fig. 11
$IWHUꢀꢇꢀPLQXWHVꢄꢀWKHꢀV\VWHPꢀVKLIWVꢀLQWRꢀFRROLQJ
RSHUDWLRQꢄꢀDQGꢀFRROꢀDLUꢀZLOOꢀVWDUWꢀWRꢀEHꢀIHOWꢅꢀ&RROLQJ
PRGHꢀWHVWꢀUXQꢀLVꢀXQDIIHFWHGꢀE\ꢀWKHꢀURRPꢀWHPSHUDꢌ
WXUHꢅ
ꢁꢇꢃ 3UHVVꢀWKHꢀ21ꢐ2))ꢀRSHUDWLRQꢀEXWWRQꢀRIꢀWKHꢀUHPRWH
FRQWUROOHUꢀDJDLQꢀWRꢀVWRSꢀWKHꢀWHVWꢀUXQꢅꢀꢁ)LJꢅꢀꢂꢂꢃ
Fig. 12
ꢁꢋꢃ )LQDOO\ꢀSUHVVꢀWKHꢀ$&/ ꢁ5HVHWꢃꢀEXWWRQꢀRIꢀWKHꢀUHPRWH
FRQWUROOHUꢀWRꢀUHOHDVHꢀLWꢀIURPꢀ7HVWꢀ5XQꢀPRGHꢀWRꢀUHWXUQ
WRꢀQRUPDOꢀPRGHꢅꢀꢁ)LJꢅꢀꢂꢂꢃ
´ µꢀDQGꢀ´R3ꢌꢂµꢀZLOOꢀGLVDSSHDUꢀIURPꢀWKHꢀUHPRWH
FRQWUROOHUꢀFORFNꢀGLVSOD\ꢀDUHDꢅ
OPERATION lamp
TIMER lamp
NOTE
7URXEOHVKRRWLQJꢑ
,QꢀWKHꢀHYHQWꢀWKDWꢀWKHꢀJUHHQꢀ23(5$7,21ꢀODPSꢀLVꢀEOLQNLQJ
XSRQꢀSRZHULQJꢀXSꢀWKHꢀV\VWHPꢄꢀDQꢀHUURUꢀFRQGLWLRQꢀH[LVWVꢅ
,QꢀWKLVꢀFDVHꢄꢀUHIHUꢀWRꢀWKHꢀVHOIꢌGLDJQRVWLFVꢀSURFHGXUHꢀRQ
WKHꢀLQVLGHꢀRIꢀWKHꢀDLUꢌLQWDNHꢀJULOOHꢅ
Fig. 13
IMPORTANT
$IWHUꢀWKHꢀWHVWꢀUXQꢀLVꢀFRPSOHWHGꢄꢀEHꢀVXUHꢀWRꢀSUHVVꢀWKHꢀ$&/
ꢁ5HVHWꢃꢀEXWWRQꢀWRꢀUHWXUQꢀWRꢀQRUPDOꢀPRGHꢅꢀ7KHꢀDLUꢀFRQGLꢌ
WLRQHUꢀZLOOꢀQRWꢀRSHUDWHꢀFRUUHFWO\ꢀLIꢀWKLVꢀLVꢀQRWꢀGRQHꢅ
WI1011-0
Printed in Japan
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
DC1111-0
Download from Www.Somanuals.com. All Manuals Search And Download.
|