VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
For main and standby power supplies.
Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
LC-R061R3P
Dimensions (mm)
Terminal type: Faston 187
+
-
+
-
+
-
+
-
3.819 0.039 (97 1)
0.945 0.039 (24 1)
0.165 (4.2)
0.165 (4.2)
3.656 (92.9)
0.925 (23.5)
3.799 (96.5)
Photo/Label for reference only.
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note)
Specifications
Nominal Voltage
Rated Capacity (20 hour rate)
Length
6V
1.3Ah
7.2
6.9
6.6
6.3
6.0
5.7
5.4
5.1
4.8
4.5
4.2
3.9
3.819 inches (97.0 mm)
Width
0.945 inches (24.0 mm)
1.969 inches (50.0 mm)
Dimensions
Height
Total Height
Approx. mass
2.165 inches (55.0 mm)
.661 lbs. (0.30 kg)
0.065A
0.13A
0.26A
1.3A
Standard Terminals
and Resin
UL94HB Faston 187
LC-R061R3P
0
1
2
4
6
8 10
20
40 60
2
4
6
8 10
20
40
(Minute)
(Hour)
Duration of discharge
Characteristics
20 hour rate (65mA)
1.3Ah
1.2Ah
1.05Ah
0.85Ah
(Note)
Duration of discharge vs. Discharge current
10 hour rate (120mA)
5 hour rate (210mA)
1 hour rate (850mA)
Capacity (note)
77˚F (25˚C)
30
20
15
1.5 hour rate discharge
Cut-off voltage 5.25 V
Fully charged battery
77˚F (25˚C)
0.6A
10
Approx. 50mΩ
Internal Resistance
Temperature
dependency
of capacity
102%
100%
85%
104˚F (40˚C)
77˚F (25˚C)
32˚F (0˚C)
5
4
3
(20 hour rate)
65%
5˚F (-15˚C)
2
Residual capacity
after standing 3 months
Residual capacity
after standing 6 months
Residual capacity
after standing 12 months
91%
82%
64%
1.5
104˚F (40˚C)
77˚F (25˚C)
Self discharge
77˚F (25˚C)
1
50
40
30
20
Cycle use
initial current
0.52 A or smaller
32˚F (0˚C)
(Repeating
use)
Charge
Method
(Constant
Voltage)
7.25V to 7.45V
(per 6V cell 25˚C)
10
5˚F (-15˚C)
Control voltage
initial current
0.195 A or smaller
5
3
Trickle use
6.8V to 6.9V
(per 6V cell 25˚C)
Control voltage
30
50
100
300 500
1
3
5
10
(Note) The above characteristics data are average values obtained
within three charge/discharge. Cycles not the minimum values.
(mA)
Discharge current
(A)
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to
Download from Www.Somanuals.com. All Manuals Search And Download.
modification without notice. Contact Panasonic for the latest information.
|