User ’s Guide
e-mail: info@omega.com
RD260A RECORDER
Instr uction Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
Thank you for purchasing the OMEGA industrial strip-chart recorder.
The RD260A recorder comforms to the EMC standard as follows.
EM1 EN55011: class A
EMS EN50082-2
To take full advantage of numerous capabilities and to operate this instrument correctly
and efficiently, please read this Instruction Manual before use.
This manual describes both Pen and Dot-printing models of the SR1000 recorder.
NOTE
• The contents of this manual is the subject to change without notice.
• All reasonable effort has been made to ensure the accuracy of the contents of this
manual. However, if you find any ambiguous descriptions, please inform OMEGA.
• All rights reserved. No part of this manual may be reproduced or transmitted in any
form.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY PRECAUTIONS
This recorder is developed to satisfy and to be used under the following conditions:
• The recorder is a component type instrument to be installed on an instrumentation
panel or rack.
• The recorder complies with EN61010-1.
• The recorder conforms to EN55011 (EMI) Group 1, Class A (for commercial and
industrial use).
• This instrument complies with Installation (over-voltage) Category II.
The following safety precautions must be observed during all phases of operation,
maintenance, and repair of the recorder. If this instrument is used in a manner not
specified in this manual, the protection provided by this instrument may be impaired.
Also OMEGA assumes no liability for the customer’s failure to comply with these
requirement.
General definitions of safety symbols used on the recorder and in this manual.
Monitory symbol; the elements marked with this symbol alert the user to refer to the
instruction manual to avoid personal injury or recorder damage.
Protective grounding terminal; this terminal must be connected to the ground before
turning the power switch on.
High temperature; to avoid injury caused by hot surface, don’t touch the heats in.
Alternative current;
This manual uses the following signs for safety precautions:
A WARNING sign denotes a hazard. It calls attention to a procedure, practice,
condition or the like, which, if not correctly performed or adhered to, could result
in personal injury or death of personnel.
WARNING
A CAUTION sign denotes a hazard. It calls attention to a procedure, practice,
condition or the like, which, if not correctly performed or adhered to, could result
in damage to or destruction of part or all of the recorder.
Power Supply
CAUTION
Ensure the source voltage matches the specified power supply voltage before
turning on the power.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Protective Grounding
Make sure to connect the protective grounding to prevent an electric shock
before turning on the power.
WARNING
Necessity of Protective Grounding
Never cut off the internal or external protective grounding wire or disconnect the
wiring of protective grounding terminal. Doing so poses a potential shock.
Defects of Protective Grounding and Fuse
Do not operate the recorder when protective grounding or fuse might be
defective.
Fuse
To prevent a fire, use the fuse with specified ratings. Before replacing the fuse,
turn off the power and disconnect the power source. Do not use an off-
specification fuse or short circuit the fuseholder.
Do not Operate in an Explosive Atmosphere
Do not operate the recorder in the presence of flammable liquids or vapors.
Operation of any electrical instrument in such an environment constitutes a
safety hazard.
Keep Away from Live Circuits
Inside this recorder there are areas of high voltage; therefore, never touch the
interior when the power supply is connected. The recorder has replacable parts
and subassemblies; however, the replacement must be carried out only by
OMEGA service personnel or properly trained personnel only.
External Connection
Before connecting to measurement and control unit, connect the protective
grounding wire.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
HOW TO USE THIS MANUAL
Relationship between chapters and their purposes or timing to read is broken down in
the table below:
:Necessary to read
:Optional to read
Purchase
&
Installation Maintenance
Daily
Operation/
Setting
Renewing
Trouble-
shooting
Chapters
Safety Precautions
1
2
3
4
5
6
7
8
Before Installation
Installation
Component Names & Functions
Daily Operation
Data Setting Guides
SET Mode
SETUP Mode
Troubleshooting
For the specifications of this recorder, refer to the General Specification Sheet
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter1
CONTENTS
INTRODUCTION
.........................................................................................................
1
2
4
SAFETY PRECAUTIONS ........................................................................................................
HOW TO USE THIS MANUAL .......................................................................................
Chapter 1 BEFORE INSTALLATION
Chapter2
1.1 Handling Precautions ......................................................................... 1 - 1
1.2 Checking and Unpacking ................................................................... 1 - 2
1.2.1 Checking Accessories and Appearance............................................................ 1 - 2
1.2.2 Removing Packings........................................................................................... 1 - 3
1.2.3 Checking Model Codes ..................................................................................... 1 - 4
Chapter 2 INSTALLATION
2.1 Installation Site and Mounting Methods ............................................. 2 - 1
2.1.1 Installation Site .................................................................................................. 2 - 1
2.1.2 Mounting Methods ............................................................................................. 2 - 2
2.1.3 External Dimensions ......................................................................................... 2 - 3
2.2 Wiring ......................................................................................................... 2 - 4
Chapter3
!
2.2.1 Rear Panel Terminal Arrangement.................................................................... 2 - 4
2.2.2 Power Supply Wiring ......................................................................................... 2 - 5
2.2.3 Input Signal Wiring ............................................................................................ 2 - 6
2.2.4 Alarm Output Wiring (option) ............................................................................. 2 - 8
2.2.5 Remote Control Wiring (option) ......................................................................... 2 - 9
!
!
!
!
!
Chapter4
Chapter 3 COMPONENT NAMES AND FUNCTIONS
3.1 Front Panel......................................................................................... 3 - 2
3.2 Characters on the Display .................................................................. 3 - 4
Chapter 4 DAILY OPERATION/MAINTENANCE....................................................... 4 - 1
4.1 Switching Power On/Off ..................................................................... 4 - 1
4.2 Installing (or Replacing) Chart Paper ................................................. 4 - 2
4.3 Installing (or Replacing) Pens (Pen model)........................................ 4 - 4
4.4 Installing (or Replacing) Ribbon Cassette (Dot-printing model) ......... 4 - 6
4.5 Getting the Recording ........................................................................ 4 - 7
4.5.1 Starting/Stoping the Recording ......................................................................... 4 - 7
4.5.2 Feeding the Chart.............................................................................................. 4 - 7
4.5.3 Printing Samples ............................................................................................... 4 - 7
4.6 Getting a Digital Printout .................................................................... 4 - 8
4.6.1 Getting a List Printout ........................................................................................ 4 - 8
4.6.2 Getting a SET UP List Printout .......................................................................... 4 - 9
4.7 Selectting the Display......................................................................... 4 - 10
4.8 Maintenance....................................................................................... 4 - 11
4.8.1 Periodic Maintenance ........................................................................................ 4 - 11
4.8.2 Battery Replacement ......................................................................................... 4 - 12
Chapter5
Chapter6
!
4.8.3 Fuse Replacement ............................................................................................ 4 - 12
4.8.4 Cleaning the Carriage Shafts ............................................................................ 4 - 13
4.8.5 Calibration ......................................................................................................... 4 - 14
4.8.6 Pen-Position Adjustment (Pen model) .............................................................. 4 - 16
4.8.7 Dot-Position Adjustment (Dot-printing model) ................................................... 4 - 18
Chapter7
Chapter8
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 5 DATA SETTING GUIDES .......................................................................... 5 - 1
5.1 Various Modes ................................................................................... 5 - 2
5.1.1 OPERATION Mode ........................................................................................... 5 - 3
5.1.2 SET Mode ......................................................................................................... 5 - 4
5.1.3 SET UP Mode ................................................................................................... 5 - 5
5.2 Procedures to Enter Setting Data ...................................................... 5 - 7
Chapter 6 SET MODE ............................................................................................... 6 - 1
6.1 Setting Input Range and Recording Span (RANGE) ......................... 6 - 2
6.2 Setting Offsets (OFFST) .................................................................... 6 - 11
6.3 Setting Alarms (ALARM) .................................................................... 6 - 12
6.4 Assigning Units (UNIT)....................................................................... 6 - 14
6.5 Setting Chart Speed (CHART) ........................................................... 6 - 15
6.6 Setting Date/Time (CLOCK)............................................................... 6 - 16
6.7 Adjusting the Trend Recording Format
(TREND, Dot-printing model) ............................................................. 6 - 17
6.8 Assigning Tags (TAG) ........................................................................ 6 - 18
6.9 Setting Messages (MSG) ................................................................... 6 - 19
6.10 Setting Key-lock (KEY)....................................................................... 6 - 20
Chapter 7 SET UP MODE........................................................................................... 7 - 1
7.1 Setting the Output Relay to Energize/De-energize Upon Alarm (option) ...... 7 - 2
7.2 Setting Alarm Hysteresis On/Off ........................................................ 7 - 3
7.3 Setting A/D Integration Time (Pen model) ......................................... 7 - 4
7.4 Setting Upscale/Downscale TC Burnout ............................................ 7 - 5
7.5 Configuring the Input Filter (Pen model) ............................................ 7 - 6
7.6 Setting for Moving Average Calculations (Dot-printing model) .......... 7 - 7
7.7 Turning Offset Settings Protection On/Off.......................................... 7 - 8
7.8 Assigning Different Colors to Channels (Dot-printing model)............. 7 - 9
7.9 Setting Pen Offset Compensation On/Off (Pen model, /D1 option) ... 7 - 10
7.10 Turning Alarm Printing On/Off ............................................................ 7 - 11
7.11 Setting Periodic Printout On/Off ......................................................... 7 - 12
7.12 Turning Printing of Changes in Chart Speed On/Off .......................... 7 - 13
7.13 Turning Printing of Channel Numbers On/Off (Dot-printing model) ... 7 - 14
7.14 Selecting Channel Number or Tag ..................................................... 7 - 15
7.15 Changing the Temperature Unit (/D2 option) ..................................... 7 - 16
7.16 Changing Default Settings for REMOTE Operation (option) .............. 7 - 17
7.17 Turning the Settings Protection Function On/Off ............................... 7 - 18
7.18 Initializing Settings ............................................................................. 7 - 19
Chapter 8 TROUBLESHOOTING ............................................................................... 8 - 1
8.1 Error Code List ................................................................................... 8 - 1
8.2 Troubleshooting ................................................................................. 8 - 3
6
Download from Www.Somanuals.com. All Manuals Search And Download.
1.1 Handling Precautions
Chapter 1 BEFORE INSTALLATION
1.BEFOREINSTALLATION
This chapter describes the necessary preparations before handling the recorder; read
them for safe handling.
1.1 Handling Precautions
The recorder contains many plastic parts. To clean, use a soft, dry cloth. Do not use
chemicals such as benzene or thinner, since these may cause discoloration or damage.
Do not bring any objects charged with static electricity near the signal terminals. This
might cause malfunction.
Do not allow any volatile substances to the front glass or key panel. Do not allow
rubber or vinyl to remain in contact with the recorder for long periods.
Whenever the recorder is not used, turn the power switch off.
Turn the recorder power switch off as soon as any symptoms of malfunction such as
unusual sound, smell, or smoke yield from the recorder. Also turn the main power
switch off.
If a malfunction occurs, contact your sales representative or nearest service center.
1 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2 Checking and Unpacking
This recorder has been thoroughly inspected before shipment; however, when you
receive the recorder, check that all accessories are present and in the correct quantities.
Also check the external appearance of the recorder to ascertain that no damage has
occurred.
1.2.1 Checking Accessories and Appearance
The recorder should be accompanied by the accessories indicated in the following.
Check that all are present in the correct quantities. Also check the external appearance
of the recorder to ascertain that no damage has occurred.
Accessories
1
3
4
2
5
6
7
No. Name
Qty Remarks
1. Disposable felt pen
1-pen mode
1
2
3
1
1
1
Red
Red, green
Red, green, blue
Only for pen
model
2-pen model
3-pen model
2. Plotter pen
3. Ribbon cassette
4. Fuse
Only for dot-printing model
250V, 500mA, time-lag type
Recorders with a gray power switch
250V, 800mA, time-lag type
1
Recorders with a white power switch
5. Mounting brackets
6. Z-fold chart paper
7. Instruction manual
2
1
1
Approx. 16 m
Spare Parts
Name
Part No.
Qty
Remarks
Disposable felt pen (red)
Disposable felt pen (green)
Disposable felt pen (blue)
Plotter pen
RD260-01
RD260-02
RD260-03
RD260-PP
RD260-RC
3
3
3
3
1
Only for pen model
Ribbon cassette
Only for dot-printing model
Fuse
A1360EF
A1512EF
4
4
250V, 500mA, time-lag type
Recorders with a gray power switch
250V, 800mA, time-lag type
Recorders with a white power switch
Mounting brackets
Z-fold chart paper
B9900CW
RD260-ZFP
B9901AZ
2
6
1
Approx. 16 m
Only for dot-printing model
1 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2 Checking and Unpacking
1.2.2 Removing Packings
The internal assembly is secured in position by packings to safeguard against damages
during transit. When you unpack the recorder, remove the packings referring to the
following.
1.BEFOREINSTALLATION
(1) Remove the lock screw securing the interior of the recorder during transit.
(2) Open the front door, and open the display by pulling its left end after removing the
adhesive tape.
(3) Remove all packings.
Removing Lock Screw and Packings for Transit
Pen model
Display
Lock screw
Packing material
Dot-printing model
Display
Lock screw
Packing material
Please take care not to apply any undue pressure in an upward or downward
direction to the display. This might cause a strain on the hinges.
CAUTION
1 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2.3 Checking Model Codes
Check the model codes on the nameplate to make sure they are as specified by your
order.
The nameplate is visible after you remove the chart cassette and is as shown in the
figure below.
Nameplate
Checking Model Codes
1 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1 Installation Site and Mounting Methods
Chapter 2 INSTALLATION
This chapter describes the installation method of the recorder: selecting the installation
site, mounting and wiring methods. Read this chapter before installation.
2.1 Installation Site and Mounting Methods
2.1.1 Installation Site
The recorder should be installed according to the following conditions as close as
2.INSTALLATION
possible.
To use this recorder within domestic establishments and within establishments directly
connencted to a low voltage power supply network which supplies buildings used for
domestic purposes may cause malfunction of other eqipments. Please avoid using in
domestic environment.
Panel and rack mounting
The recorder is designed to be installed on an instrumentation panel or rack.
Well ventilated location
Install the recorder in a well ventilated site to prevent from internal temperature rise.
Avoid mechanical vibration
To install the recorder in a location susceptible to mechanical vibration will adversely
affect the mechanical parts and the quality of recording. Please choose an installation
site characterized by minimal mechanical vibration.
Horizontal installation
This recorder must be installed horizontally (however, mounting may be inclined up to
30˚ backward from vertical).
Avoid direct sunshine or heater radiation
The recorder will be adversely affected if the unit is exposed to direct sunlight or
installed near a heater. Choose a location near room temperature (23˚C) with minimal
temperature fluctuation.
Keep out of soot, steam, moisture, dust, corrosive gases
To expose the recorder to soot, steam, moisture, dust, corrosive gases, etc., will
adversely affect it.
Keep away from electro-magnetic fields
To use the recorder within strong electro-magnetic fields may cause malfunction.
Please avoid installing near electro-magnetic objects.
2 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1.2 Mounting Methods
(1) Mount the recorder on a steel panel whose thickness is at least 2 mm (and up to 26
mm).
(2) Insert the recorder into the panel-front face.
(3) Fix the recorder to the panel using the mounting brackets as shown below.
Adequate screw tightening torque is approximately 8 to 12 kg-cm. A pair of
mounting brackets can be applied to the recorder’s top and bottom, or to both side
faces. Remove the seals covering the holes for the brackets before attaching them.
A tightening torque exceeding the above-mentioned adequate values may
cause deformation of the recorder case or brackets.
CAUTION
Mounting bracket
Mounting
2 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
2.1 Installation Site and Mounting Methods
2.1.3 External Dimensions
Unit: mm
Unless otherwise specified, dimensional tolerance is ±3%;
however, for less than 10 mm, it is ±0.3 mm.
2.INSTALLATION
175 minimum
Panel Cutout and External Dimensions (Including Mounting Brackets)
NOTE A pair of mounting brackets should be used on the top and bottom, or on both
sides of the recorder.
2 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Wiring
!
Wiring should be done only after you have read this section. The section consists of the
following subsections:
2.2.1 Rear Panel Terminal Arrangement
2.2.2 Power Supply Wiring
2.2.3 Input Signal Wiring
2.2.4 Alarm Output Wiring
2.2.5 Remote Control Wiring
Make sure to fasten the wiring at the rear wall of the mounting panel and
employ some kind of strain relief between the rear wall and the recorder.
WARNING
2.2.1 Rear Panel Terminal Arrangement
Pen model
L
N
Power terminal
Optional terminals
Input terminals
Terminal screw: ISO M4, nominal length 6 mm
The terminal blocks can be detached from the case by removing
these screws for easy wiring.
Tighten the terminal screws properly to ensure proper contact.
Dot-printing model
Power terminal
Optional terminals
Input terminals
Terminal screw: ISO M4, nominal length 6 mm
The terminal blocks can be detached from the case by removing
these screws for easy wiring.
Tighten the terminal screws properly to ensure proper contact.
2 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Wiring
2.2.2 Power Supply Wiring
!
(1) The rated power supply voltage for the recorder is follows.
• 100 to 240 V AC
(2) Turn the recorder’s power switch off.
(3) Open the transparent cover of the power terminal after releasing the cover screw.
(4) Connect the power supply wires and the protective ground wire to the terminal.
(5) Cover the terminals with the transparent cover, and secure the screw.
Power supply wires
2.INSTALLATION
L
N
Protective grounding wire
Power Supply Wiring
• To prevent an electric shock, ensure the main power supply is turned off
before wiring.
WARNING
• To prevent fire, use 600 V PVC insulated wire (AWG18) for power and
ground wiring (cross sectional area of 0.83 mm2 or thicker, anti-galvanic
corrosion finish, insulation thickness should be more than 0.8 mm, insulation
resistance should be more than 50 M /Km at 20˚C, approved EN60 320
(VDE0625) ), or equivalent cables.
• Connect the protective grounding wire to the earth through grounding
resistance less than 100 before turning on the power.
• Use crimp-on lugs (for 4 mm screws) with insulation sleeves.
• To prevent an electric shock, cover the power terminals certainly with the
transparent cover.
• Make sure to apply a power switch near by with the following characteristic:
rated power current > 1A
rated rush current > 60A
fuse (s) of 2A to 15A is (are) necessary.
NOTE • Do not apply a power supply in the range from 132 V to 180 V AC. Doing so
might affect the measuring accuracy.
• To prevent an emission of electromagnetic disturbances, separate the power
supply wires from the other wires at least 0.1 m. Over 0.5 m is
recommended.
2 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2.3 Input Signal Wiring
!
(1) Turn off the recorder power switch.
(2) Remove the transparent cover for the input signal terminals.
(3) Connect the input signal wires to the terminals.
(4) Attach the cover on the terminals, and secure the screws.
It is recommended to use the crimp-on lugs (for 4 mm screws) with insulation sleeves
for lead wire ends, but they are not required for thermocouples (TC).
Crimp-On Lugs
Suggestions to minimize noise pickup:
• Separate the measuring-signal wires from power lines and grounding lines.
• It is desirable that the measuring object is not a noise source; if not, insulate it from
the measuring-signal wires and ground the object.
• It is recommended to use shielded wires to minimize noise pickup from an
electrostatic induction source. The shields are connected to the recorder’s grounding
terminal, if necessary. In that case, avoid two-point grounding.
• To minimize the noize from an electrostatic induction noise, twist the measuring
wires (a pair of wires) in short and equal intervals.
• The grounding line must have low resistance.
In case of using a thermocouple (TC), the recorder is equipped with a reference junction
compensator, so the ambient temperature around the recorder’s terminal board should
be kept as stable as possible.
• Cover the input terminals with the transparent cover.
• Do not use a large-diameter wire (cross sectional area of more than 0.5 mm2) because
it has a large radiation rate.
• Keep the ambient temperature as stable as possible; start/stop of a nearby fan affects
the temperature.
If input signal wires are connected to two or more receivers with parallel connection,
measured values sometimes affect each other. The following notes should be observed
for parallel connection:
• Ground each receiver at the same point.
• Do not turn on/off the power of a receiver while other receivers are in measuring
operation.
• A resistance temperature detector (RTD) cannot be used essentially in parallel
connection.
To prevent an electric shock, ensure the main power switch is turned off when
wiring.
WARNING
Do not apply inputs exceeding the rated range as follows to prevent the
recorder from damage:
CAUTION
• Maximum input voltage
±10 V DC for TC, and for the voltage range of 2 V DC or less
±30 V DC for the voltage range of 6 to 20 V DC
• Maximum common mode voltage
250 V AC rms (50/60 Hz)
• The installation of each input is Category II.
NOTE • To prevent an emission of electromagnetic disturbances, separate the input
wires from the other wires at least 0.1 m. Over 0.5 m is recommended.
2 - 6
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Wiring
Terminal Board
b
B
–
A
+
RTD
DC voltage, TC
B
b
–
A
+
1ch
2ch
3ch
4ch
5ch
6ch
1ch
2ch
3ch
2.INSTALLATION
Pen model
Dot-printing model
Wiring for Input Terminals
DC voltage inputs
TC input
Extension wires
+
+
(Example)The shunt resistor rating
is 250 Ω ±0.1% for the
current input of 4 to 20 mA.
2 - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2.4 Alarm Output Wiring (option)
!
NOTE The following settings are available only for the model with relay options (-A2,
-A4, -A6).
(1) Turn the power switch off.
(2) Remove the transparent cover of the optional terminals.
(3) Connect the alarm output wires to the optional terminals.
(4) Cover the terminals with the transparent cover and secure the screws.
Depending on the type (the number of outputs) of alarm relay options, the terminal
arrangement changes as shown in the following:
ALARM
ALARM
ALARM
NO
C
NC
NO
C
NC
NO
C
NC
1
2
1
2
1
2
NO
C
NC
NO
C
NC
NO
C
NC
NO
NO
C
C
NC
NC
NO
NO
NO
NO
C
C
C
C
NC
NC
NC
NC
3
4
3
4
5
6
!
!
!
-A2 option
(2 outputs)
- A4 option
(4 outputs)
-A6 option
(6 outputs)
Alarm Output Terminal Arrangements
Contact characteristics:
Output type
: Relay transfer contacts
Output capacity
: 250 V AC (50/60 Hz), 3 A
250 V DC, 0.1 A (resistive load)
Dielectric strength : 1500 V AC (50/60 Hz) for one minute between output terminals
and grounding terminals
To prevent an electric shock, ensure the main power switch is turned off before
wiring.
WARNING
NOTE To prevent an emission of electromagnetic disturbances, separate the alarm
output wires from the power supply and input wires at least 0.1 m. Over 0.5 m
is recommended.
2 - 8
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2.5 Remote Control Wiring (option)
!
NOTE The following settings are available only for the model with remote options (R1).
(1) Turn the power switch off.
(2) Remove the transparent cover of the optional terminals.
(3) Connect the wires for remote control to the optional terminals. The “C” is the
terminal common to other 1 to 5.
(4) Cover the terminals with the transparent cover and secure the screws.
2.INSTALLATION
Remote control terminals are arranged as follows:
REMOTE
1
2
3
4
5
C
!
Remote Control Terminal Arrangements
Input characteristics:
Input signal
Control functions and signal types:
• Recording start/stop
:
Dry contact, open-collector (TTL or transistor) signal
level
• Chart speed change
level
• Printout messages
Signal characteristics : ON voltage
trigger more than 250 msec
0.5 V or less (30 mA DC)
Leakage current in OFF state 0.25 mA or less
Signal duration 250 msec or more
Input types
:
:
Photocoupler isolation (one line common)
Internal isolated power source (5 V±5%)
500 V DC for one minute between input terminals and
grounding terminal.
Dielectric strength
To prevent an electric shock, ensure the main power switch is turned off before
wiring.
WARNING
NOTE • Use shielded cables for remote control signals to prevent noise pickup. The
shield should be grounded at the recorder’s terminal.
• To prevent an emission of electromagnetic disturbances, separate the remote
control wires from the power supply and input wires at least 0.1 m. Over 0.5
m is recommended.
2 - 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 3 COMPONENT NAMES AND
FUNCTIONS
This chapter describes the names of components, and outlines their functions.
3.COMPONENTNAMESANDFUNCTIONS
2
3
Tag plates
Use the recorder with units corresponding to each
channel directly written on these plates respectively.
3 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
3.1 Front Panel
➀
➀
ESC
RCD
ALM
RCD
DISP
PRINT
FEED
CH UP
➀
➀
➀
1. Power switch (push-button type)
Pressing the switch turns the power ON and OFF.
2. Key panel (push-key type)
The panel contains five keys.
[RCD] key
Pressing the key starts or stops the recording.
ESC
[DISP] key, [ESC] key
DISP
(DISP function)
Cycles through the modes of display in the order of
AUTO, MANUAL, DATE, TIME and OFF. Also
selects between the OPERATION and SET modes
pressing for three seconds.
(ESC function)
Exits from the menu in the middle of setting or selecting
procedures.
[PRINT] key, [ ] key
PRINT
(PRINT function) Conducts the list printout (see subsection 4.6.1) and the
SET UP list printout (see subsection 4.6.2).
(
function)
Selects setting parameters (numerics or command
codes). Selecting step is upward circulation.
[FEED] key, [ ] key
(FEED function) The chart is fed as long as this key is being pressed (see
FEED
subsection 4.5.2.)
(
function)
Changes the number of digits for setting numeric
values. The digit moves from high to low.
[CH UP] key, [ENT] key
CH UP
(CH UP function) Selects a channel for which the display shows the screen
in the MANUAL display mode.
(
function)
Makes a parameter entry or executes a function after
selecting parameters (numerals or command codes).
Pressing the key executes the settings.
3 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
3.1 Front Panel
3. Chart cassette
Contains a Z-fold chart (width: 100 mm, length: 16 m).
4. Status Display
RCD indicator : illuminated when recording of measurement values is in progress.
ALM indicator : will illuminate when an alarm occurs.
5. Data Display
This display shows the measurement values digitally. During entering settings, the
display will show these settings.
3.COMPONENTNAMESANDFUNCTIONS
3 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 Characters on the Display
The display consists of seven segmetns, and therefore characters exist which are
difficult to display.
Characters are presented on the display as shown in the following table.
Display
Alphabet
Display
A
B
N
C
O
D
P
E
F
G
S
H
T
h
I
J
K
X
L
l
Alphabet
M
Q
R
U
V
W
Y
Z
3 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
4.1 Switching Power On/Off
Chapter 4 DAILY OPERATION/
MAINTENANCE
This chapter describes the daily operation and maintenance of this recorder. Read this
chapter before operation.
4.1 Switching Power On/Off
The power switch is located at the lower right-hand corner of the front face behind the
door.
The switch is a push-button type. Press the switch to turn ‘ON’ the recorder and press
again to turn ‘OFF’.
After the power turns on, the recorder executes a self-diagnostic check for several
seconds before starting measurement and recording.
ON
4.DAILYOPERATION/MAINTENANCE
OFF
Power switch
NOTE • The warm-up time is approximately 30 minutes; however, after the initial start-
up, the recorder might need more time.
• If the input wiring is connected parallel with other equipment, do not turn the
power switch on/off to prevent fluctuations in measuring values.
4 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
4.2 Installing (or Replacing) Chart Paper
(1) Open the front door of the recorder.
(2) Check the recorder is not in recording state; but the power ON is allowed.
(3) Riffle the chart thoroughly before loading.
(4) While gently pressing the chart-cassette stoppers, located at both front ends of the
cassette, lift and draw the cassette out of the recorder case.
Stoppers
(5) Open the chart retainer backward on the cassette.
(6) Pull and open the front transparent chart guide.
Chart retainer
hart guide (transparent plastic plate)
(7) Load the chart paper into the chart compartment; the small perforations should be
at the left-hand. Make sure that the sprocket teeth of the chart drives are properly
engaged in the chart paper perforations. Take care not to load the chart paper
backwards.
Small perforations
4 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
4.2 Installing (or Replacing) Chart Paper
(8) Close the chart retainer.
(9) Close the chart guide (transparent plastic plate).
t be close the front transparent chart guide
re replace the chart paper compartment.
(10) Replace the chart cassette back into the recorder case; hang the knurls of the
cassette to the grooves of the case, and move the cassette to trap the stopper.
4.DAILYOPERATION/MAINTENANCE
(11) Press the [FEED] key on the key panel to assure that the chart moves two or more
folds smoothly into the chart receiver. If it moves unsteadily, do the installing
procedure again from step (4).
NOTE A red band with a ‘RENEW CHART’ notice appears when the chart nears to its
end (length of remaining chart is approximately 40 cm) to suggest you to
prepare a new chart.
If you replace the chart paper compartment back into the unit without closing
the front transparent chart guide, the lock tabs might be damaged.
CAUTION
4 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
4.3 Installing (or Replacing) Pens (Pen model)
Felt-tip pen
Simple replacement
(1) Open the front door, and check to see that the recording is OFF, but the power ON
is allowed.
(2) Pull and open the display around the hinge.
(3) Pull out the pen-cartridge by pulling the protruding part of the cartridge from the
pen holder.
Felt pen
Pen holder
1st pen: red,
2nd pen: green,
3rd pen: blue
(4) Remove the cap from a new felt-tip pen, and insert the pen firmly to the pen
holder.
(5) Press the [RCD] key to restart the recording.
• Do not press or pinch the felt tip to prevent deformation. Do not move the
pen holder up- or down-scale to protect the driving mechanism.
• Always make sure to remove the pen cap before installation.
CAUTION
Replacement under pen-replacement mode
When a pen is located at a place where its replacement is difficult to do, relocate the pen
by the following procedures:
(1) Check to see that the recording is OFF, but the power ON is necessary.
(2) Press the [PRINT] key, then press the [ ] key to display [
], and press
the [ENT] key.
(3) Press the [ ] key to display [
], and press the [ENT] key. The pens will
move near to the center of the scale where the pens can be easily replaced.
NOTE When the pens move, a line is drawn on the chart.
(4) Replace the pen according to the ‘Simple replacement’, (2), (3), and (4) described
above.
(5) After pen replacement the indicator shows [
], then press the [ENT] key.
(6) To restart recording, press the [RCD] key.
4 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
4.3 Installing (or Replacing) Pens (Pen model)
Plotter pen
(1) Open the front door, and check to see that the recording is OFF, but the power ON
is allowed.
(2) Pull and open the display around the hinge.
(3) Pull out the pen-cartridge by pulling the protruding part of the cartridge from the
pen holder.
Plotter pen
Pen holder
(4) Remove the cap from a new pen, and insert the pen firmly to the pen holder.
Always make sure to remove the pen cap before installation.
CAUTION
4.DAILYOPERATION/MAINTENANCE
4 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
4.4 Installing (or Replacing) Ribbon Cassette (Dot-printing model)
(1) Open the front door, and check that the power is switched OFF.
(2) Open the display by pulling its left end.
(3) Hold the printer carriage, and move it to the right.
(4) Hold the left-hand part of the ribbon cassette, and pull it out from the recorder case.
Ribbon cassette
Printer carriage
(5) Insert a new ribbon cassette into the cassette holder; first, insert the right-hand part,
next the left-hand part. Check that the cassette is properly engaged with the
cassette holder snap.
If the cassette is not engaged with the holder properly, turn the ribbon feeding knob
in the direction of the arrow to fit the peg to the driving hole of the holder.
(6) To check that the cassette is properly inserted, turn the left-hand knob in the
direction of the arrow a half or more turning.
(7) If the ribbon loosens, turn the knob in the direction of the arrow to tighten it.
(8) Turn the display back to the normal position.
• Improper insertion of the cassette may cause illegal-print color or damage to
the cassette.
CAUTION
4 - 6
Download from Www.Somanuals.com. All Manuals Search And Download.
4.5 Getting the Recording
4.5 Getting the Recording
4.5.1 Starting/Stoping the Recording
Press the [RCD] key to start or stop the recording.
4.5.2 Feeding the Chart
The chart paper is fed by pressing the [FEED] key as long as the key is pressed.
4.5.3 Printing Samples
Periodic printing
Date, channel numbers, measuring values,
Alarm printout
Channel number, alarm level, alarm
type, alarm occurrence/release are
printed; mark [ ] shows alarm
occurrence, [ ] shows release.
engineering units, printing colors (pen model),
scale (not printed during alarm printing), and
chart speed are printed.
Mark [ ] means there are escaping
*
POC ON mark ( )
data due to buffer memory overflow.
*
A mark ( ) is printed when pen offset
*
compensation function (option for Pen
model) is on.
Time tick cancel mark (!)
This mark is printed if a time tick is printed at
an improper location.
4.DAILYOPERATION/MAINTENANCE
Time tick (–)
Regardless of using the POC function (option for Pen model),
a time tick mark is printed corresponding
to the 1st pen location (Pen model).
Pen model Printing Sample
4 - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
4.6 Getting a Digital Printout
A digital printout can be any one of the following:
• List printout
• SET UP list printout
4.6.1 Getting a List Printout
A list printout includes the following setting values:
• Date/time/chart speed/2nd-chart speed/trend record interval (Dot-printing model)
• Channel number/range/span/scaling value/engineering unit
• Tag/offset value (if setting is on)
• Types of set alarms (if set)
• Message setting (if set up to 16 characters)
List printing is executed by the following procedure:
(1) Press the[PRINT] key.
(2) Press the [ ] (PRINT) key to call up the [
] display, then press the
[ENT] key.
(3) Press the [ ] key to select [
], press the [ENT] key, and list printing
will start.
When list printing starts, the display automatically returns to the screen that was on
display before the printing began.
NOTE • While list printing is executed, analog recording is interrupted; however,
measuring and alarm detecting activities continue.
• If an alarm occurs during list printout, the alarm printout starts just after the
analog recording restarts.
If you want to interrupt a list printing, proceed as follows:
(1) Press the [PRINT] key.
(2) Press the [ ] (PRINT) key to call up the [
] display, then press the
[ENT] key.
(3) Press the [ ] key to select [
], and press the [ENT] key. The list printing
will stop and the recorder will return to the state before starting the list printing.
When the OFFSET or
TAG setting is on in
SET UP mode, this is
printed.
Pen model Printing Sample
4 - 8
Download from Www.Somanuals.com. All Manuals Search And Download.
4.6 Getting a Digital Printout
4.6.2 Getting a SET UP List Printout
A SET UP list printout includes the setting values of the following printing functions:
• Digital printing
• Alarm setting
• Burnout function and others
SET UP list printing is executed by the following procedure:
(1) Press the [PRINT] key.
(2) Press the [ ] key to call [
(3) Indicate [ ] using the [ ] key, press the [ENT] key, and the SET UP
list printing will start.
] on the indicator, and press the [ENT] key.
When the SET UP list printing starts, the display automatically returns to the state
before starting the list printing procedure.
NOTE • While SET UP list printing is executed, analog recording is interrupted;
however, measuring and alarm detecting activities continue.
• If an alarm occurs during SET UP list printing, the alarm printout starts just
after the analog recording restarts.
If you require to interrupt a SET UP list printing, execute the following procedure:
(1) Press the [
] key.
(2) Press the [ ] key to call up the [
] display, and press the [ENT] key.
(3) Press the [ ] key to select [
], and press the [ENT] key. The SET UP list
printing will stop and the recorder will return to the state before starting the list
printing.
4.DAILYOPERATION/MAINTENANCE
If the recorder fitted with
the /D2 option, this is printed.
Dot-printing model Printing Sample
4 - 9
Download from Www.Somanuals.com. All Manuals Search And Download.
4.7 Selectting the Display
Five different displays can be selected. These are:
DISPLAY AUTO
Channel number and measured values will appear on the display.
When an alarm occurs, type of alarm will appear.
Every channel will be shown for approximately 2 sec. If the input is greater than the
upper limit of the recording span, – – – – will appear.
If the input is less than the lower limit of the recording span, – – – – – will appear.
Measured Value (5 digits)
Type of Alarm (1 digit)*
Channel Number(1 digit)
*Type of alarm
: high limit
: low limit
: high difference limit
: low difference limit
DISPLAY MAN (except for the 1-pen model)
Channel number, measured values and type of alarm when it occurs will appear on the
display for a specific channel only. This display looks the same as the AUTO display.
The display is updated every two seconds for Pen models and at every measurement
period for Dot-printing model. Using the [CH UP] key, the displayed channel number
will go up.
DISPLAY DATE
Date, including the year will appear on the display. Leap years are provided.
Year
Month
Day
DISPLAY TIME
Time will appear on the display.
Hours
Minutes
DISPLAY OFF
Displays other than status displays will be turned off.
Selecting a screen
Pressing the [DISP] key cycles through the screens in the following order:
AUTO: automatic-mode screen
MAN: manual-mode screen
DATE: date-mode screen
TIME: time-mode screen
OFF: off-mode screen
4 - 10
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8 Maintenance
4.8 Maintenance
The activities necessary to maintain the recorder in good operating condition are shown
below:
Periodic maintenance (see subsection 4.8.1)
Battery replacement (see subsection 4.8.2)
Fuse replacement (see subsection 4.8.3)
Cleaning plotter carriage shaft (see subsection 4.8.4)
Calibration (see subsection 4.8.5)
Pen adjustment (see subsection 4.8.6)
Printer carriage adjustment (see subsection 4.8.7)
Parts replacement (see subsection 4.8.8)
4.8.1 Periodic Maintenance
Check the following items periodically, and replace consumable parts, if necessary:
Are indication and recording normal?
If not, see chapter 8, “Troubleshooting”.
Are recorded lines or printed characters clear, not blurred?
To replace a felt-tip pen or a plotter pen of Pen model, see section 4.3 “Installing (or
Replacing) Pens”; also, see section 4.4 “Installing (or Replacing) Ribbon Cassette”
to replace the ribbon cassette of Dot-printing model.
Is chart-paper feeding smooth, not jammed?
If not, see chapter 8, “Troubleshooting”.
Is there enough chart paper left in the chart compartment?
Remaining chart length (cm) is printed on the left margin of the chart at intervals of
20 cm.
4.DAILYOPERATION/MAINTENANCE
See section 4.2 “Installing (or Replacing) Chart Paper”.
Is [
] illuminated?
If it is, see subsection 4.8.2, “Battery Replacement” as the lithium battery for
memory backup needs to be replaced.
Remaining chart length
Indication of Remaining Chart Length
4 - 11
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8.2 Battery Replacement
The [
] illumination indication shows lithium battery deterioration, which is
used for memory backup. The battery has a lifetime of approximately 10 years under
normal operation.
When [
] is illuminated, contact Omega Engineering.
Replacing the lithium battery can be dangerous. Do not attempt to replace the
battery; never disassemble the recorder for replacing the battery.
WARNING
4.8.3 Fuse Replacement
!
Replacing the fuse every two years is recommended as preventive maintenance.
Replacing procedure is as follows:
(1) Turn the power switch OFF.
(2) Take out the chart cassette; the fuse holder is found in the main unit.
Turn the fuse carrier counterclockwise to release it with the fuse.
(3) Change the fuse with a new one, and insert the carrier to the fuse holder turning it
clockwise for fixing.
Fuse Replacement
• To protect against personal injury, turn the power switch OFF and disconnect
the recorder from the main power line before replacing the fuse.
• To protect against an accident such as a fire, use only the specified fuse
WARNING
Fuse part number:
Original manufacturer:
A1360EF
Shelter
Littel
Original manufacturer’s product code: FST0034.524
313.500
Ratings:
250V AC T 0.5 A
250VACT 0.5 A
Recorders with a gray power switch
Fuse part number:
A1512EF
Original manufactturer:
wickmann-Werke GmbH
Original manufacturers product code: No.19195
Ratings:
250V AC T0.8A
Recorders with a white power switch
4.8.4 Cleaning the Carriage Shafts
4 - 12
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8 Maintenance
Pen model
To maintain proper recording functions, it is recommended to clean the plotter-carriage
shaft once a year.
Cleaning procedure is shown below:
Wipe the two shafts, the upside and downside ones for the plotter carriage, with a
piece of soft cloth or paper without fluffing.
If stains are persistent, use several drops of ethyl alcohol with the cloth or paper.
• Do not damage the plotter’s flexible-printed circuit when cleaning the shafts.
• The shafts do not require lubricating oil.
CAUTION
Flexible board
Plastic plate
Plotter carriage
shafts
Dot-printing model
4.DAILYOPERATION/MAINTENANCE
To maintain proper recording functions, it is recommended to lubricate the printer-
carriage shaft once a year.
Lubricating procedure is shown below:
(1) Wipe up dust or oil from the shaft of the printer carriage with a piece of soft cloth
or paper without fluffing.
(2) Take out the tube of lubricating oil from among the spare parts.
(3) Coat the shaft with a few small drops of lubricating oil, but remove excess oil with
a piece of soft cloth or paper without fluffing.
Shaft
4.8.5 Calibration
4 - 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibration is a comparing operation between standard inputs and measured values.
It is recommended to carry out a calibration once a year to assure the measuring
accuracy.
Required instruments for calibration
The instruments for calibration should have the required resolution. If necessary, ask
the sales office from whom you purchased the recorder about those instruments.
Recommended instruments
OMEGA model # CL511 calibrator
Calibration procedure
(1) Connect the instruments to the recorder; connecting the terminals is shown below.
Give enough warm-up time to the instruments (more than 30 minutes for the
recorder).
(2) Check that the ambient temperature and humidity are within the standard operating
conditions.
Standard operating conditions
Ambient temperature : 23±2˚C
Humidity
: 55±10% RH
Power supply
Power frequency
Warm-up time
: 90 to 132 V AC, or 180 to 250 V AC
: 50/60 Hz±0.1%
: 30 minutes or more
Mechanical vibration : Within the range not affecting recorder operation
However, when the calibration is conducted under normal operating conditions (see subsection 4.8.6),
check the accuracy influenced by the conditions.
Chart paper yields thermal expansion or shrinkage, sometimes resulting in differences from the
calibrated values.
Examples of expansion are shown below assuming the reference temperature 20˚C and humidity 65% RH:
Expansion at 85% RH ..... 0.4% or less
Expansion at 35% RH ..... 0.45% or less
(3) Input the standard signals equivalent to 0, 50, and 100% of the setting range of the
recorder, then check the difference error between input signals and measured
values.
If the error is not within the specified accuracy, contact OMEGA Engineering.
NOTE A reference input for a thermocouple (TC) signal needs temperature
compensation; the temperature at the recorder input terminal should be
measured to make voltage compensation (adding) due to the reference junction
temperature compensation.
Power terminals
Input terminals
(for DC Voltage or TC)
DC Voltage Signal for Pen model (same as Dot-printing model)
Temperature Measurement for Resistance Temperature Detector (RTD)
4 - 14
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8 Maintenance
Power terminal
L
N
Three lead wires should have the
same resistance values.
A
b
B
1
2
3
Decade resistance box
Input terminals
(for RTD)
Temperature Signal as RTD for Pen model
(for Dot-printing model, the wire connection exchanges between the terminal B and b.)
Temperature Compensation for Thermocouple Signal
Copper wires Thermocouple wires or extension wires Power terminals
L
4.DAILYOPERATION/MAINTENANCE
N
+
+
+
Meter
—
Couple
—
—
DC voltage standard
+
—
1
2
3
Copper wires
Thermocouple wires
Ice pieces packed to
maintain the
temperature at 0ßC
(reference junction compensator Model TRCIII)
Reference Junction Compensation for Thermocouple Input
A DC voltage generated by a thermocouple differs from a value calculated from the table of thermo-
electromotive force (EMF) because the table is based on the 0˚C reference temperature but the temperature at
the recorder input terminal is generally equal to the room temperature.
The recorder measures the temperature at the input terminal for compensation; when the input terminals are
shorted (equivalent to 0˚C of the thermocouple in the EMF table), the recorder indicates the temperature at the
input terminal.
For calibrating a recorder, an input voltage after the compensation (after subtraction of the compensating
voltage) should be applied to the recorder; an example is shown in (thTRCIII reference junction compensator
is used).
Reference Temperature Compensating Connection for Pen model (same as Dot-printing model)
4 - 15
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8.6 Pen-Position Adjustment (Pen model)
It is recommended to adjust pen positions on the chart at least once a year.
Adjusting procedure
(1) Turn the recorder power on and allow a warm-up time of more than 30 minutes.
(2) Check that the environmental conditions are within normal operating conditions.
Normal operating conditions
Power supply
Power frequency
: 90 to 132 V AC, or 180 to 250 V AC
: 50/60 Hz±2%
Ambient temperature : 0 to 50˚C
Ambient humidity
: 20 to 80% RH (under 5 to 40˚C)
Mechanical vibration : 10 to 60 Hz, 0.2 m/s2 or less
Mechanical shock
Magnetic field
External noise
: Not permitted
: 400 AT/m or less (DC and 50/60 Hz)
: Normal mode (50/60 Hz)
DC voltage ........ Noise peak value with signal is limited to 1.2 times
larger value than the measuring range.
TC signal ........... Noise peak value with signal is limited to 1.2 times
larger value than the measuring thermoelectromotive
force.
RTD signal ........ 50 mV or less
Common mode noise (50/60 Hz): 250 V AC rms or less for any range
Maximum noise voltage between channels (50/60 Hz):
Pen model, Dot-printing model.......................... 250 V AC rms or less
Mounting inclination : Backward 0 to 30˚
Chart paper yields thermal expansion or shrinkage, sometimes resulting in differences from the
calibrated values. Adjust the pen position, if necessary.
Examples of expansion are shown below assuming the reference temperature 20˚C and humidity 65% RH:
Expansion at 85% RH ..... 0.4% or less
Expansion at 35% RH ..... 0.45% or less
(3) To enter the SET UP mode, turn the power switch off, and turn on again while
pressing the [CH UP] ( ENT) key.
(4) Select [
] using the [ ] key, and press the [ENT] key.
(5) Select [
] (leftward movement) or [ ] (rightward movement) using
the [ ] key, and press the [ENT] key.
NOTE Adjust the pen positions in the order of NULL to FULL.
(6) Select the number of the channel to be adjusted using the [ ] key, and press the
[ENT] key.
(7) The selected pen moves leftward (for NULL) or rightward (for FULL). Increase or
decrease the setpoint value to make the pen accurately overlap the graduated line of
the chart.
The setting consists of a number of five digits.
Select the digit by pressing the [ ] key, and select a numeral by the [ ] key.
Setting range is 7950 to 11350 for NULL, 14500 to 19500 for FULL. Finally press
the [ENT] key after all codes are entered.
The pen will move after pressing the [ENT] key. The pen movement
corresponding to [1] is 0.0057 mm. Decreasing the numeral moves the pen
leftward, and increasing moves the pen rightward.
NOTE If the [ENT] key is pressed while setting the numeric codes, the indication
changes to [
], and the numeric codes already set remain valid.
However, they will become invalid if the [ESC] key is pressed.
4 - 16
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8 Maintenance
(8) The indicator displays [
], and the pen will move to the adjusted position.
Confirm the pen position and press the [ENT] key.
(9) The indicator returns to [
position adjustment again, press the [ENT] key and carry out step (6) again. When
another adjustmens are required, select [ ] or [ ] again by pressing
the [ ] key. In order to finish the adjustment, press the [ESC] key to return to the
] indication.
] or [
]. When you want to carry out the
[
(10) Before leaving the SET UP mode, its contents should be stored.
Select [
] by pressing the [ ] key, and press the [ENT] key.
(11) Select [
] to keep setting values valid, or select [
] to abort
them by pressing the [ ] key, and press the [ENT] key.
The SET UP mode finishes, and several seconds after, the mode returns to the
OPERATION mode.
4.DAILYOPERATION/MAINTENANCE
4 - 17
Download from Www.Somanuals.com. All Manuals Search And Download.
4.8.7 Dot-Position Adjustment (Dot-printing model)
It is recommended to adjust the position of dots at least once a year.
Adjusting procedure
(1) Turn the recorder power on and allow a warm-up time of more than 30 minutes.
(2) Check that the environmental conditions are within normal operating ranges (see
subsection 4.8.6).
(3) To enter the SET UP mode, turn the power switch off, and turn on again while
pressing the [CH UP] ( ENT) key.
(4) Select [
] by pressing the [ ] key, and press the [ENT] key.
(5) Select [
] (leftward movement) or [
] (rightward movement) or
[
] (movement toward the center of dotted line) by pressing the [ ] key,
and press the [ENT] key.
NOTE Selection and adjustment should be made in the order of HYS→NULL→FULL.
(6) First, the HYS should be adjusted. A zigzag line will be drawn in the center area
of the chart. When the line is as Figure a, increase the set value, but in case of
Figure b, decrease it.
The arrows show the moving
direction of the printer head.
Figure a
Figure b
The setting consists of a number of five digits.
Select the digit by pressing the [ ] key, and select a numeral by the [ ] key; the
setting range is –7 to 7. Finally press the [ENT] key after all codes are entered.
The dot position movement corresponding to [1] is 0.1 mm.
NOTE If the [ENT] key is pressed while setting the numeric codes, the indication
changes to [
], and the numeric codes already set stay valid.
However, pressing the [ESC] key turns them invalid.
(7) The indicator displays [
], and the dot carriage will move to the adjusted
position.
Confirm the dot carriage position and press the [ENT] key.
(8) The indication returns to [
] and recording stops. If the recording position is
illegal, press the [ENT] key and repeat step (6); if correct, press the [ ] key and
select [
] or [
].
(9) Next, the NULL and FULL should be adjusted. Increase or decrease the setpoint
value to make the dot position accurately overlap the graduated line of the chart.
The setting consists of is a number of five digits.
The setting range is 1 to 15 for NULL, and 970 to 1030 for FULL. Finally press
the [ENT] key after all codes are entered.
The dot position movement corresponding to [1] is 0.1 mm. Decreasing the
numeral moves the dot position leftward, and increasing moves it rightward.
4 - 18
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTE If the [ENT] key is pressed while setting the numeric codes, the indication
changes to [ ], and the numeric codes already set stay valid.
However, pressing the [ESC] key turns them invalid.
(10) The indicator displays [
], and the dot carriage will move to the adjusted
position.
Confirm the dot carriage position and press the [ENT] key.
(11) The indication returns to [
position adjustment again, press the [ENT]key and carry out step (9) again. When
another adjustments are required, select [ ], [ ] or [ ] again
by pressing the [ ] key. In order to finish the adjustment, press the [ESC] key to
return to the [ ] indication.
] or [
]. When you want to carry out the
(12) Before leaving the SET UP mode, its contents should be stored.
Select [
] by pressing the [ ] key, and press the [ENT] key.
(13) Select [
] to keep setting values valid, or select [
] to abort
them by pressing the [ ] key, and press the [ENT] key.
The SET UP mode finishes, and several seconds after, the mode returns to the
OPERATION mode.
4.DAILYOPERATION/MAINTENANCE
4 - 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 5 DATA SETTING GUIDES
This chapter describes the setting modes listed below.
Read this chapter before you enter settings for the first time.
5.1 Various Modes
5.1.1 OPERATION Mode
5.1.2 SET Mode
5.1.3 SET UP Mode
5.2 Procedures to Enter Setting Data
5.ATNGUIDES
5 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1 Various Modes
The recorder has three modes which are described below:
OPERATION mode
This is the mode for daily operation; when the power turns on, the recorder
automatically enters this mode. For details, see chapter 4 “DAILY OPERATION AND
MAINTENANCE”.
SET mode
In this mode, daily-used data such as alarm setpoints, date, and time are set. Pressing
the [DISP] key three seconds in the OPERATION mode changes the mode to the SET
mode.
SET UP mode
In this mode, you make settings for digital printing, alarm, burnout function and others,
also adjust the pen’s position or the position where the recorder prints dots. You can
enter this mode by turning the power on while pressing the [CH UP] ( ENT) key.
NOTE While in the SET UP mode, measurement, recording, and alarm detection are
not carried out.
Using the SETTINGS PROTECTION FUNCTION, you can protect your settings by
defining a password when you enter the SET or SET UP mode. For details on the
settings protection function, see section 7.17.
Turning the function off:
Power ON while pressing
the [CH UP] (↵ ENT) key.
Power ON
OPERATION
mode
SETUP mode
SET mode
Mode changes to the other by pressing
Leaving the SET UP mode
is done by SET UP END
procedure.
the [DISP] key for three seconds.
Turning the function on:
Power ON while pressing
the [CH UP] (↵ ENT) key.
Power ON
SETUP
QUIT
Password
OPERATION
mode
SETUP mode
SET mode
1
*
1
*
Password
DISP
Leaving the SET UP mode
is done by SET UP END
procedure.
3 sec.
*1 Mode changes to the other by pressing
the [DISP] key for three seconds.
5 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1 Various Modes
5.1.1 OPERATION Mode
Select from the following functions by pressing the appropriate keys on the key panel.
[PRINT] key
(Start/stop of list printing—see subsection 4.6.1)
(Start/stop of SET UP list printing—see subsection 4.6.2)
(Replacement of pens—Pen models only—see section 4.3)
(Selection from the modes of display—see section 4.7)
[DISP] key
5.ATNGUIDES
5 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1.2 SET Mode
This flow can be entered by pressing the [DISP] key for three seconds.
(Voltage input
setting and
Range
Span (L)
Span (R)
span setting)
(TC input setting and span
setting)
Type
Span (L)
Span (R)
(RTD input setting and
span setting)
Type
Span (L)
Span (R)
(Contact input setting)
(Designation of
difference computation)
Reference channel Span (L)
Span (R)
Range
Span (L)
Span (R)
(Scaling setting)
Scale (L)
Range
Scale (R)
Span (L)
Span (R)
(Square-root extraction setting)
Scale (L)
Scale (R)
(Skip: when there is no measurement, recording, or display of an
unused channel)
(Setting of offsets, when offset settings protection function is on)
Channel No.
Offset
Alarm point
Channel No.
Alarm level
*1
Alarm on/off
*1: displayed only when the
*1
range is set to differential
Type of alarm
computation.
(Alarm setting)
Relay No.
Contact output
Channel
(Measuring unit setting)
(Chart feed speed setting)
Chart feed speed
First/second speed
(date and time setting)
year/month/day ('97 June 1)
hour/minute (12:00)
(Setting of dot-printing cycle in analog records) (Dot-printing model)
(Message setting)
(Key lock)
: Numeric value input
: Code input
5 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1 Various Modes
5.1.3 SET UP Mode
The SET UP mode can be entered by turning on the power while holding down the
[CH UP] ( ENT) key.
(Energizing/de-energizing)
(Alarm hysteresis)
(A/D integration time, Pen model)
(Upscale/downscale TC burnout)
(TC burnout ON/OFF)
(Setting of filter—Pen model)
Channel No.
(Setting of moving average—Dot-printing model)
Channel No.
5.ATNGUIDES
(On/off of offset settings protection)
(Setting of color of dots—Dot-printing model)
Channel No.
(Pen offset compesation, Pen model, option)
(Alarm printout)
(Periodic print)
to next page
5 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
(Setting of printing of changes in the chart speed)
(Setting of channel number printing—Dot-printing model)
(Tag setting)
(Temperature unit, option)
(Remote control, option)
(Setting protection function)
Password
(Pen-ZERO adjustment)
(Dot-ZERO adjustment)
(Pen-FULL adjustment)
(Dot-FULL adjustment)
(Dot-HYS adjustment)
Explanations for these are not in this manual.
Consult your purchasing source.
(Initialization of settings)
(Termination of SET UP mode)
5 - 6
Download from Www.Somanuals.com. All Manuals Search And Download.
5.2 Procedures to Enter Setting Data
5.2 Procedures to Enter Setting Data
Data setting is done by the four keys on the key panel which are referred to by the
marks on the keys.
ESC
RCD
DISP
PRINT
FEED
CH UP
ESC
DISP
[ESC] key : Cancels the already set data in the middle of a setting; after canceling, the
previous indication will be shown on the indicator.
PRINT
FEED
[
] key : Selects parameters of any setting, or selects any numeric characters in case of
ranges, alarms, offsets, date/time and so on.
[
] key : Moves the cursor to the next digit while entering parameters. Since there is
no backspace key provided, this key will move to the first digit after the last
digit.
CH UP
[ENT] key : Confirms a set value for entry. Pressing the key moves the indication to the
next setting display.
NOTE While in the SET mode, [RCD] key is effective. Pressing [RCD] key starts or
stops the recording.
5.ATNGUIDES
5 - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 6 SET MODE
This chapter describes the setting procedures in the SET mode.
6.1 Setting Input Range and Recording Span (RANGE)
6.2 Setting Offsets (OFFST)
6.3 Setting Alarms (ALARM)
6.4 Assigning Units (UNIT)
6.5 Setting Chart Speed (CHART)
6.6 Setting Date/Time (CLOCK)
6.7 Adjusting the Trend Recording Format (TREND,Dot-printing model)
6.8 Assigning Tags (TAG)
6.9 Setting Message (MSG)
6.10 Setting Key Lock (KEY)
6.SETMODE
6 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1 Setting Input Range and Recording Span (RANGE)
One of the following parameters can be set for every channel:
SKIP
Prevents the specified channel from being measured, recorded and displayed .
VOLT Measures and records DC-voltage.
TC
RTD
DI
Measures and records temperatures using Thermocouple.
Measures and records temperatures using Resistance Temperature Detector .
Accepts Digital Input (contact/voltage level) and performs ON/OFF
recording.
DELT
SCL
Performs difference computation between two channels which have same
input range.
Performs scaling on voltage measurements.
Scaling results in appending a different scale to the measured values.
SQRT
Takes the square root (
) of DC-voltage measured data.
NOTE Restrictions apply to the measurable types of input depending on the type of
recorder used. Check your recorder type as indicated on the nameplate (see
page 1-4 of the instruction manual for details on the nameplate), and then refer
to the following table.
Model Code
SR100x-B-1
SR100x-B-2
Measurable Type of Input
Voltage (VOLT), thermocouple (TC), contact (DI), SCL, SQRT
Resistance temperature detector (RTD)
6 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1 Setting Input Range and Recording Span (RANGE)
SKIP Setting
Unused channels can be skipped, which means that these channels will not be measured,
recorded or displayed.
Key operation
Indication
Description
Press the [DISP] key for three seconds to enter the SET mode.
ESC
DISP
Select the [
] display by using the [ ] key.
3 sec
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
].
PRINT
CH UP
ESC
[
] is displayed and the setting is completed.
CH UP
DISP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key to three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6.SETMODE
6 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Voltage Measurement Setting (VOLT Setting)
In the case that the measured signal is a DC-voltage, the range can be set as follows:
Key operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
3 sec
Select the [
] display by using the [ ] key.
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
].
PRINT
CH UP
Select the desired range using the [ ] keys and press the
[ENT] key.
PRINT
CH UP
VOLT Input Ranges
Range
Display
–20.00 to 20.00mV
–60.00 to 60.00mV
–200.0 to 200.0mV
–2.000 to 2.000V
–6.000 to 6.000V
–20.00 to 20.00V
Select the minimum value of the recording span (SPAN L)
using the [ ] and [ ] keys. Then press the [ENT] key.
PRINT
FEED
CH UP
The display which appears will allow you to enter the
maximum value of the recording span (SPAN R). Select it the
same way as for the minimum value and press the [ENT] key.
Note that the recording span cannot be beyond the input range,
nor can SPAN L be equal to SPAN R.
PRINT
FEED
CH UP
ESC
DISP
[
] is displayed and the setting is completed.
CH UP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
[
] and already set data will be aborted.
6 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1 Setting Input Range and Recording Span (RANGE)
Thermocouple and Resistance Temperature Detector Setting (TC, RTD Setting)
In the case that the measured signal is a TC (Thermocouple) or RTD (Resistance
Temperature Detector) the range can be set the same way as if it were a DC-voltage.
Key operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
3 sec
Select the [
] display by using the [ ] key.
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
], or [
].
PRINT
CH UP
Select the desired type (R, S, B, K, E, J, T, N, W, L, U in case
of TC, or PT, JPT in case of RTD) using the [ ] key and
press the [ENT] key.
PRINT
CH UP
TC Type Description and RTD Type Description
TC Type Description
Range
RTD Type Description
Range
0.0 to 1760.0°C
0.0 to 1760.0°C
0.0 to 1820.0°C
32 to 3200°F
32 to 3200°F
32 to 3308°F
(pt100Ω) –200.0 to 600.0°C –328.0 to 1112.0°F
(Jpt100Ω) –200.0 to 550.0°C –328.0 to 1022.0°F
–200.0 to 1370.0°C –328 to 2498.0°F
–200.0 to 800.0°C –328.0 to 1472.0°F
–200.0 to 1100.0°C –328.0 to 2012.0°F
–200.0 to 400.0°C –328.0 to 752.0°F
0.0 to 1300.0°C
32 to 2372°F
0.0 to 2315.0°C
32 to 4199°F
–200.0 to 900.0°C –328.0 to 1652.0°F
–200.0 to 400.0°C –328.0 to 752.0°F
(Fe-CuNi)
(Cu-CuNi)
Select the desired minimum value (SPAN L) and maximum
value of the recording span (SPAN R) in the same way as
described under ‘VOLT setting’.
Note that the recording span cannot be beyond the input range,
nor can SPAN L be equal to SPAN R.
PRINT
FEED
CH UP
6.SETMODE
ESC
DISP
[
] is displayed and the setting is completed.
CH UP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Digital Input Setting (DI Setting)
If a Digital Input (contact input/voltage level input) is being used, the setting can be
done as follows:
Key operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display by using the [ ] key.
3 sec
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
].
PRINT
CH UP
There are two types, namely LEVEL and CONTACT.
PRINT
CH UP
LEVL: (Level)
Records ON/OFF status of a voltage input
(0 to 2.4V is OFF (0), 2.4V and higher is
ON (1)).
CONT: (Contact) Records ON/OFF status of a contact (close
is ON (1), open is OFF (0)).
Select the desired type using the [ ] key and press the [ENT]
key.
ESC
[
] is displayed and the setting is completed.
CH UP
DISP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE • The above mentioned selections will result in a recording trace from 0mm to
100mm between the contact statuses OFF and ON, which is from the extreme
left side of the chart to the extreme right side.
• If you press the [ESC] key in the middle of setting, the indication returns to the
[
] and aiready set data will be aborted.
6 - 6
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1 Setting Input Range and Recording Span (RANGE)
Difference Computation Setting (DELT Setting)
To obtain the difference between the measured values of two channels, proceed as
follows.
Key Operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
3 sec
Select the [
] display by using the [ ] key.
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Note that channel No.1 cannot be of the ‘DELT’ type.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
].
PRINT
CH UP
The display which appears will allow you to enter a reference
channel number. Note that the reference channel number must
be lower than that of the channel being set. Therefore channel
PRINT
CH UP
No.1 cannot be of the [
] type.
Use the [ ] key to select the desired reference channel number.
Press the [ENT] key.
In case of VOLT the display which appears will show the same
minimum value of the recording span as of the reference
channel.
PRINT
FEED
CH UP
Use the [ ] and [ ] keys to select the minimum value
(SPAN L).
Press the [ENT] key.
Note that in case of VOLT, the input range of the DELT-channel
must be within the range of the reference channel. In case of TC,
RTD, the minimum/maximum span values can be found by
taking the ±value of the input range width. E.g. input range of
TC type L = –200 to 900°C: minimum/maximum span values
will be at ±1100°C. The difference in measured value from the
reference channel will be recorded on the DELT-channel.
6.SETMODE
The display which appears will show the same maximum value
of the recording span as of the reference channel.
Use the [ ] and [ ] keys to select the maximum value
(SPAN R) in the same way as described under ‘SPAN L
setting’. Note that SPAN L cannot be equal to SPAN R.
Press the [ENT] key.
PRINT
FEED
CH UP
ESC
DISP
[
] is displayed and the setting is completed.
CH UP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6 - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Scale Setting (SCL Setting)
To assign a different scale to the measured data, the range can be set as described
below. Note that the measured data which can get a different scale must be of the
voltage (VOLT). To assign a unit to this new scale, see section 6.4.
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display by using the [ ] key.
3 sec
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select [
Press the [ENT] key.
].
PRINT
CH UP
Select the desired range (using the [ ] key) and press the
[ENT] key.
PRINT
CH UP
The display which appears will allow you to enter the
minimum value of the recording span (SPAN L). Select the
desired minimum value using the [ ] and [ ] keys. Then
press the [ENT] key.
PRINT
FEED
CH UP
The display which appears will allow you to enter the
maximum value of the recording span (SPAN R). Select it the
same way as the minimum value and press the [ENT] key.
Note that SPAN L and SPAN R cannot be same.
PRINT
FEED
CH UP
This display allows you to enter the minimum value of the scale
(SCL L) corresponding to the minimum value of the recording
span (SPAN L). Select it using the [ ] and the [ ] keys. The
position of the decimal point can be moved using the [ ] key
in case [ ] is flashing. Note that the allowable range is –19999
to 20000. Then press the [ENT] key.
PRINT
FEED
CH UP
This display allows you to enter the desired maximum value of
the scale (SCL R) corresponding to the maximum value of the
recording span (SPAN R). Select it the same way as the
minimum value. Then press the [ENT] key. Note that the
decimal point will be in the same position as for SCL L. SCL L
and SCL R cannot be same.
PRINT
FEED
CH UP
ESC
[
] is displayed and the setting is completed.
CH UP
DISP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE • In this example, 0.000V input will be scaled to –100.0. 2.000V input will be
scaled to 100.0.
• If you press the [ESC] key in the middle of setting, the indication returns to the
[
] and already set data will be aborted.
6 - 8
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1 Setting Input Range and Recording Span (RANGE)
Setting to Obtain Square Root (SQRT Setting)
To obtain the square root of the measured value, proceed as follows:
Note that the measured data of which the square root can be taken, can only be of the
voltage type. To assign a unit, see section 6.4.
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display by using the [ ] key.
3 sec
Then press the [ENT] key.
PRINT
CH UP
Use the [ ] key to select the desired channel.
Press the [ENT] key.
PRINT
CH UP
PRINT
Use the [ ] key to select [
Press the [ENT] key.
].
CH UP
PRINT
Select the desired range (using the [ ] key) and press the
[ENT] key.
CH UP
The display which appears will allow you to enter the
minimum value of the recording span (SPAN L). Select the
desired minimum value using the [ ] and [ ] keys. Then
press the [ENT] key.
PRINT
FEED
CH UP
The display which appears will allow you to enter the
maximum value of the recording span (SPAN R). Select it the
same way as for the minimum value and press the [ENT] key.
Note that SPAN L and SPAN R cannot be same.
PRINT
FEED
CH UP
This display allows you to enter the minimum value of the
scale (SCL L) corresponding to the minimum value of the
recording span (SPAN L). Select it using the [ ] and the
PRINT
FEED
CH UP
[
] keys. The position of the decimal point can be moved
using the [ ] key in case [ ] is flashing. Note that the
allowable range is –19999 to 20000. Then press the [ENT]
key.
6.SETMODE
This display allows you to enter the maximum value of the
scale (SCL R) corresponding to the maximum value of the
recording range (SPAN R). Select it the same way as for the
minimum value. Then press the [ENT] key. Note that the
decimal point will be in the same position as for SCL L. SCL L
and SCL R cannot be same.
PRINT
FEED
CH UP
ESC
[
] is displayed and the setting is completed.
CH UP
DISP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6 - 9
Download from Www.Somanuals.com. All Manuals Search And Download.
EXPLANATION OF SQUARE ROOT:
This recorder uses the following square rooting-method:
Let us define the items as follows:
Vmin = minimum value of recording span (SPAN L)
Vmax= maximum value of recording span (SPAN R)
Fmin = minimum value of scale (SQRT SCL L)
Fmax = maximum value of scale (SQRT SCL R)
Vx = input voltage
Fx = scaling value
The relationship between Vx (input voltage) and Fx (scaling value) is as shown in the
graph below (the graph configuration is approximate).
F
c
F
max
b
) x 10%
) x 1%
(F
max
– F
min
F
min
a
b'
(V
– V
min
max
V
V
min
V
max
Between b and c in the graph, the following relation exists between Fx and Vx:
Vx – Vmin
Vmax – Vmin
Fx = (Fmax – Fmin
)
+ Fmin
And between a and b, the relation is:
10 (F
V
– F
)
max
min
F =
x
(V – V ) + F
min
min
x
– V
min
max
6 - 10
Download from Www.Somanuals.com. All Manuals Search And Download.
6.2 Setting Offsets (OFFST)
6.2 Setting Offsets (OFFST)
When recording and showing data using the current input as the reference, measured
values can be corrected within 10% of the span. For example, assume the reading is
1.998 V for the current level of input. If you want to change the reading to 2.000 V, set
0.002 V as the offset. This menu opens only when offset settings protection is turned
on in the SET UP mode.
Key operation
Indication
Discription
ESC
Enter the SET mode by pressing the [DISP] key for three
DISP
seconds. Using the [ ] key, show [
] and then
3 sec
press the [ENT] key.
PRINT
CH UP
Using the [ ] key, select the channel to be configured and
then press the [ENT] key. Configurable channels are those
whose measuring range is VOLT, TC, RTD or SCL.
PRINT
CH UP
Type the value of offset. Use the [ ] key to move through
the digits and the [ ] key to select a numeral. When setting
is complete, press the [ENT] key. Note that set the offset
within 10% of the recording span or scale.
PRINT
FEED
CH UP
ESC
DISP
[
] is displayed and the setting is then completed.
CH UP
3 sec
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6.SETMODE
6 - 11
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3 Setting Alarms (ALARM)
Alarms can be set on the measured data of any channel.
Up to four alarms (i.e. four levels) can be set on one channel.
After setting an alarm, and the measured value reaches the setpoint, the ALM LED will be
illuminated and an alarm printout will be made on the chart. (see subsection 4.5.3)
: High alarm
Occurs when a measuring value is over the alarm setpoint.
Occurs when a measuring value is under the alarm setpoint.
: Low alarm
: Difference high-limit alarm
Alarm is geneated when the difference between the measured
values of two channels is more than the alarm setting. (This
type of arlam can only be set when the corresponding channel
is of the DELT-type.)
: Difference low-limit alarm
Alarm is generated when the difference between the measured
values of two channels is less than the alarm setting. (This type
of alarm can only be set when the corresponding channel is of
the DELT-type.)
Key operation
Indication
Description
ESC
Enter the SET mode by pressing the [DISP] key for three
DISP
3 sec
seconds. Select [
] by pressing the [ ] key, and
press the [ENT] key.
PRINT
CH UP
Select a channel by the [ ] key, and press the [ENT] key.
PRINT
CH UP
Select an alarm level by the [ ] key, and press the [ENT]
key. Up to four levels can be set.
PRINT
CH UP
Select ON/OFF of the alarm settings by the [ ] key, and press
PRINT
CH UP
the [ENT] key. Setting [
] shows [
] and ends
this setting.
NOTE Alarm settings are automatically canceled on the affected channel, when any of
the following changes occur:
• the input type (VOLT, TC, etc.) or input range (2 V, etc.) is changed.
• decimal point for scalling and square root setting is changed.
• minimum or maximum value of the recording span is changed (in case of
scaling and square root setting).
• minimum or maximum value of the scale is changed (in case of scaling and
square root setting).
Difference alarm setting (
,
)are canceled when any of the following changes
occur:
• the reference channel is changed.
• the input type or range of the reference channel is changed.
Select a type of alarms by the [ ] key, and press the [ENT]
key.
PRINT
CH UP
6 - 12
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3 Setting Alarms (ALARM)
The display which appears will allow you to enter the alarm
value.
PRINT
FEED
Set the alarm value using the [ ] and [ ] keys. After
setting, press the [ENT] key.
CH UP
The decimal point is predetermined by the input range.
Relationship between Input Range and Decimal Points
Type of Input
–20.00 to 20.00 mV
Position of Decimal Point
XXX. XX
–60.00 to 60.00 mV
–200.0 to 200.0 mV
–2.000 to 2.000 V
–6.000 to 6.000 V
–20.00 to 20.00 V
XXX. XX
DC Voltage
XXXX. X
XX. XXX
XX. XXX
XXX. XX
XXXX. X
Thermocouple/RTD (˚C)
The following settings are available only for the model with
relay options (A2/A4/A6). For models without these options,
the alarm setting ends by pressing the [ENT] key until
[
] appears.
Determines whether the relay outputs a signal or not when an
alarm occurs.
Select ON/OFF by the [ ] key, and press the [ENT] key.
PRINT
CH UP
Sets the number of the relay after the alarm output ON is
selected. A numeric to be set is selected from I01 to I06 by the
PRINT
CH UP
[
] key. Then press the [ENT] key.
NOTE If a number larger than the available number of output relays is selected, the
alarm output will not implemented.
ESC
DISP
[
] is displayed and the setting is completed. Press
CH UP
3 sec
the [ENT] key to set another channel; or press the [DISP]
key for three seconds to return to the OPERATION mode.
NOTE • As a merged function, a combination of remote control option (- R) and alarm
output relay option is available to change the chart speed when an alarm
occurs.
6.SETMODE
• If you press the [ESC] key in the middle of setting, the indication returns to
the [
] and already set data will be aborted.
6 - 13
Download from Www.Somanuals.com. All Manuals Search And Download.
6.4 Assigning Units (UNIT)
When you are using scaling (SCL) or the square root setting (SQRT), it is possible to
assign a different unit to the scales. Units will appear in the periodic printout. Up to six
characters can be set.
The initial value is all spaces. To set, proceed as follows:
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display by using the [ ] key. Then press
3 sec
the [ENT] key.
PRINT
CH UP
Specify the desired channel using the [ ] key, and press the
[ENT] key. If the selected channel is not of the SCL or SQRT-
type, data entry will be ignored.
PRINT
CH UP
The maximum six characters of the unit can be set by the
described code (Example is given in parentheses).
PRINT
FEED
CH UP
corresponding code of the character (B)
sequential number of the character
you are setting (2nd)
channel number (1)
The code number can be selected using the [ ] key. After
setting both numbers of a code, press the [ ] key and the
sequential number of the to be set character will go up one.
After setting, press the [ENT] key.
[
] is displayed and the setting is completed.
ESC
CH UP
DISP
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
3 sec
Table of characters code.
NOTE
If you press the [ESC] key in the middle of setting, the
0
1
2
3
0
1
2
3
4
5
6
7
8
9
4
5
P
6
7
p
q
r
8
S
0
1
indication returns to the [
aborted.
] and already set data will be
P
A
B
C
D
E
F
Q
R
S
a
b
c
d
e
f
2
3
#
s
4
T
U
V
t
5
%
u
v
w
x
y
z
6
7
G W
g
h
i
8
(
)
H
I
X
Y
Z
9
A
B
C
D
E
F
J
j
*
+
K
L
M
N
O
k
l
µ
–
.
m
n
o
Ω
Ω
/
˚
S/P means ‘SPACE’.
6 - 14
Download from Www.Somanuals.com. All Manuals Search And Download.
6.5 Setting Chart Speed (CHART)
6.5 Setting Chart Speed (CHART)
Chart Speed (unit: mm/h)
10
90
15
100
20
120
25
150
30
160
40
180
50
200
60
240
75
300
80
360
375
3000
450
600
720
750
900
1200
7200
1500
9000
1800
2400
3600
4500
4800
5400
6000
10800 12000
The data for a dot-printing model (10 mm/h to 1500 mm/h) are shown within the bold border.
Key operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode,
DISP
and select [
] using the [ ] key. Then press the
3 sec
[ENT] key.
PRINT
CH UP
Using the [ ] key, select one of the two kinds of chart speed,
the No.1 and No.2 chart speeds. Then press the [ENT] key.
PRINT
CH UP
NOTE The No.2 chart speed identifies the chart speed which takes effect in case the
speed is changed by remote control (optional function).
For models without the remote control function, the setting of the No.2 chart
speed is invalid.
Select a numeric code referring to the table above using the
PRINT
CH UP
[
] key and press the [ENT] key.
NOTE Digital printing will not be carried out when the chart speeds are:
120 mm/h or more for a dot-printing model
When a pen model uses a fast chart speed such as 600 mm/h to 1500 mm/h,
the position error of the time tick of a periodic printout may become as large as
2 cm for 1500 mm/h.
[
] is dispalyed and the setting is completed.
ESC
CH UP
DISP
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
3 sec
6.SETMODE
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
[
6 - 15
Download from Www.Somanuals.com. All Manuals Search And Download.
6.6 Setting Date/Time (CLOCK)
Key operation
Indication
Description
ESC
Press the [DISP] key for three seconds to enter the SET mode,
DISP
and select [
] by pressing the [ ] key. Then press
3 sec
the [ENT] key.
PRINT
CH UP
First, set the year, month and day.
PRINT
FEED
The two digits on the left side of the display indicate the year.
The five digits on the right side of the display indicate the
month and day.
CH UP
After finishing the setting, press the [ENT] key.
Set the hour and minutes. After finishing, press the [ENT]
key. The seconds will be automatically set to 0.
PRINT
FEED
CH UP
ESC
[
] is displayed and the setting is completed.
DISP
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
3 sec
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
[
] and already set data will be aborted.
6 - 16
Download from Www.Somanuals.com. All Manuals Search And Download.
6.7 Adjusting the Trend Recording Format (TREND, Dot-printing model)
6.7 Adjusting the Trend Recording Format (TREND, Dot-printing
model)
This recorder prints in FIX or AUTO mode.
In FIX mode, dot printing is performed with a constant interval regardless of the chart
speed (approx. 20 sec).
AUTO mode is provided to prevent the chart from being damaged during repetitive dot
printing. This mode is useful for low chart speeds. The chart is protected from damage
because the printout timing changes with the chart speed (approx. 20 to 90 sec).
Single printout
(0.5mm dia.)
Repetitive dot
printing
FIX
AUTO
The initial value is ‘AUTO’. To set the trend recording mode, proceed as follows:
Key Operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display using the [ ] key, and press
3 sec
the [ENT] key.
PRINT
CH UP
Specify AUTO or FIX using the [ ] key. Then press the
[ENT] key.
PRINT
CH UP
ESC
[
] is displayed and the setting is completed. Press the
CH UP
DISP
[DISP] key for three seconds to return to the OPERATION
3 sec
mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
] and already set data will be aborted.
6.SETMODE
[
6 - 17
Download from Www.Somanuals.com. All Manuals Search And Download.
6.8 Assigning Tags (TAG)
The following setting enables you to set tags to be recorded instead of the usual channel
numbers. Tag will appear in the periodic printout, channel printout (Dot-printing model)
and in the alarm printout. One tag can be set for every channel. The maximum length is
seven characters. The initial value is all spaces.
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display by using the [ ] key. Then press
3 sec
the [ENT] key.
PRINT
CH UP
Specify the desired channel using the [ ] key, and press the
[ENT] key. If there are no tags set in the SET UP mode, data
entry will be ignored.
PRINT
CH UP
The maximum seven characters of the tag can be set by the
described code (Example is given in parentheses).
PRINT
FEED
CH UP
corresponding code of the character (B)
sequential number of the character
you are setting (2nd)
channel number (1)
The code number can be selected using the [ ] key. After
setting both numbers of a code, press the [ ] key and the
sequential number of the to be set character will go up one.
After setting, press the [ENT] key.
[
] is displayed and the setting is completed.
ESC
CH UP
DISP
Press the [ENT] key to set another channel; or press the
[DISP] key for three seconds to return to the OPERATION
mode.
3 sec
Table of characters code.
NOTE
If you press the [ESC] key in the middle of setting, the
0
1
2
3
0
1
2
3
4
5
6
7
8
9
4
5
P
6
7
p
q
r
8
indication returns to the [
] and already set data will
S
0
1
P
be aborted.
A
B
C
D
E
F
Q
R
S
a
b
c
d
e
f
2
3
#
s
4
T
U
V
t
5
%
u
v
w
x
y
z
6
7
G W
g
h
i
8
(
)
H
I
X
Y
Z
9
A
B
C
D
E
F
J
j
*
+
K
L
M
N
O
k
l
µ
–
.
m
n
o
Ω
Ω
/
˚
S/P means ‘SPACE’.
6 - 18
Download from Www.Somanuals.com. All Manuals Search And Download.
6.9 Setting Messages (MSG)
6.9 Setting Messages (MSG)
The following setting enables you to set the messages. Up to five messages can be set,
each of up to 16 characters. Printing out messages can only be done with the use of the
remote control option (-R), with which your recorder must be equipped. Messages can
not be printed out without this option.
Note that the printing of the messages will not be done when the chart speed is faster than
1500 mm/h (Pen model) or 100 mm/h (Dot-printing model) or when recording is OFF.
To set a message, proceed as follows:
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display using the [ ] key, and press the
3 sec
[ENT] key.
PRINT
CH UP
The display which appears will prompt you to specify which
message you want to set. Up to five messages can be set. Use
the [ ] key to specify message number and press the [ENT]
key.
PRINT
CH UP
The maximum sixteen characters of the message can be set by
the described code (Example is given in parentheses).
PRINT
FEED
CH UP
corresponding code of the character (B)
sequential number of the character
you are setting (2nd)
The code number can be selected using the [ ] key. After
setting both numbers of a code, press the [ ] key and the
sequential number of the to be set character will fo go up one.
After setting, press the [ENT] key.
ESC
[
] is diplayed and the setting is completed. Press the
CH UP
DISP
[ENT] key to set another message; or press the [DISP] key for
3 sec
three seconds to return to the OPERATION mode.
Table of characters codes.
NOTE
• If your recorder is equipped with the -R option, and you
want them to be triggered by remote control, the
messages must be assigned to the -R terminals.
• If you press the [ESC] key in the middle of setting, the
0
1
2
3
0
1
2
3
4
5
6
7
8
9
4
5
P
6
7
p
q
r
8
S
6.SETMODE
0
1
P
A
B
C
D
E
F
Q
R
S
a
b
c
d
e
f
2
indication returns to the [
be aborted.
] and already set data will
3
#
s
4
T
U
V
t
5
%
u
v
w
x
y
z
6
7
G W
g
h
i
8
(
)
H
I
X
Y
Z
9
A
B
C
D
E
F
J
j
*
+
K
L
M
N
O
k
l
µ
–
.
m
n
o
Ω
Ω
/
˚
S/P means ‘SPACE’.
6 - 19
Download from Www.Somanuals.com. All Manuals Search And Download.
6.10 Setting Key-lock (KEY)
The key-lock can be set to be either on or off for each key separately. Keys which can
be locked are the [RCD], [PRINT], and [FEED] keys.
Key operation
Indication
Discription
ESC
Press the [DISP] key for three seconds to enter the SET mode.
DISP
Select the [
] display using the [ ] key, and press the
3 sec
[ENT] key.
PRINT
CH UP
Select a key to be locked using the [ ] key and press the
[ENT] key.
PRINT
CH UP
Select [
] to turn the key-lock on or select [
]
PRINT
CH UP
to turn it off, using the [ ] key and press the [ENT] key.
ESC
[
] is displayed and setting is completed. Press the
CH UP
DISP
3 sec
[ENT] key to set another key; or press the [DISP] key for three
seconds to return to the Operation mode.
NOTE If you press the [ESC] key in the middle of setting, the indication returns to the
[
] and already set data will be aborted.
6 - 20
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 7 SET UP MODE
This chapter describes the Set Up Mode.
7.1 Setting the Output Relay to Energize/De-energize Upon Alarm (option)
7.2 Setting Alarm Hysteresis On/Off
7.3 Setting the A/D Integration Time (Pen model)
7.4 Setting Upscale/Downscale TC Burnout
7.5 Configuring the Input Filter (Pen Model)
7.6 Setting for Moving Average Calculations (Dot-printing model)
7.7 Turning Offset Settings Protection On/Off
7.8 Assigning Different Colors to Channels (Dot-printing model)
7.9 Setting Pen Offset Compensation On/Off (Pen model, /D1 option)
7.10 Turning Alarm Printing On/Off
7.11 Setting Periodic Printout On/Off
7.12 Turning Printing of Changes in Chart Speed On/Off
7.13 Turning Printing of Channel Numbers On/Off (Dot-printing model)
7.14 Selecting channel Number or Tag
7.15 Changing the Temperature Unit (/D2 option)
7.16 Changing Default Settings for REMOTE Operation (option)
7.17 Turning the Setting Protection Function On/Off
7.18 Initializing Settings
7.SETUPMODE
7 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
7.1 Setting the Output Relay to Energize/De-energize Upon Alarm (option)
NOTE The following settings are avairable only for the model with relay options (A1/A2/A3).
The alarm output relays can be selected to be energizing or de-energizing on alarm.
Using de-energizing, alarm output relay is activated either when an alarm occurs, or
when power off occurs (common for all relays). This enables simple monitoring of
power supply.
The initial value is ‘ENERG’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
Press the [ ] key until the display [
Use the [ ] key to select [
]. Press the [ENT] key.
] appears. Press the [ENT] key.
]. Press the [ENT] key. The
] or [
display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
7.2 Selecting Alarm Hysteresis On/Off
7.2 Setting Alarm Hysteresis On/Off
The alarm hysteresis is the difference between the levels of alarm occurrence and reset.
You can choose between two levels of hysteresis: 0% (=OFF) and approx. 0.5% of the
recording span (=ON) (common for all alarms).
The initial value is ‘ON’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Press the [ ] key until the display [
] appears. Press the [ENT] key.
Use the [ ] key to select ‘ON’ or ‘OFF’. Press the [ENT] key. The display
] appears.
[
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
NOTE Hysteresis setting is only valid for High and Low alarms. Hysteresis setting for
difference alarms will be ignored.
7.SETUPMODE
7 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
7.3 Setting A/D Integration Time (Pen model)
The purpose of the following setting is to specify which A/D integration time will be
used. Depending on the power supply, the integration time will affect the ability of
noise rejection and therefore the recording.
If the power supply of the recorder and of the measuring object are the same, the effect
of noise will be automatically minimized and the (initial) value of AUTO is the
recommended one.
If the power supplies are different, you should select from 50Hz or 60Hz integration
time. The choice depends on the power supply of the instrument with the highest noise
level.
There are three possibilities:
•
•
•
AUTO: integration time depends on the power supply of the recorder.
50Hz
60Hz.
The initial value is ‘AUTO’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select ‘AUTO’, ‘50’ or ‘60’ according to your situation using the [ ] key.
Then press the [ENT] key. The display [ ] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
7.4 Setting Upscale/Downscale TC Burnout
7.4 Setting Upscale/Downscale TC Burnout
The purpose of the following setting is to specify where the pens will move in the case
of a TC-burnout. You can choose from moving to the right (UP) or to the left (DOWN).
This is common for every channel. You can select ON or OFF for each channel.
The initial value is ‘UP’, and ‘OFF’ for every channel.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select [
The display [
] or [
] using the [ ] key. Press the [ENT] key.
] appears.
This burnout processing is ON/OFF selectable per channel.
Press the [ENT] key.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select the channel No. using the [ ] key for which you want to specify this burnout
processing. Then press the [ENT] key.
Select ‘ON’ or ‘OFF’. Then press the [ENT] key. The display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
7.5 Configuring the Input Filter (Pen Model)
Noise in the measured signal can be suppressed in the final measurement by using an
input filter. The purpose of this setting is to select for each channel whether or not to
use a filter, and if so, to select a time constant of damping.
A filter works as follows:
Input
Response curve
(Filter OFF)
Meas.
values
63.2%
Response curve
(Filter ON)
2, 5 or 10 sec.
when input filter is in use
If a filter is used, the response time can be selected from 2, 5 or 10 seconds.
You can choose from three filters:
•
•
•
2 seconds
5 seconds
10 seconds.
The initial value is ‘OFF’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select the channel No. using the [ ] key for which you want to specify a filter. Then
press the [ENT] key.
Use the [ ] key to select the type of filter you want to use. You can choose from
‘OFF’, ‘2’, ‘5’ or ‘10’. Press the [ENT] key. The display [
] will appear.
Press the [ENT] key to continue the setting for other channels. The filter setting has
been completed, but has not been stored yet.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 6
Download from Www.Somanuals.com. All Manuals Search And Download.
7.6 Setting for Moving Average Calculations (Dot-printing model)
7.6 Setting for Moving Average Calculations (Dot-printing model)
Noise in the measured signal can be suppressed in the final measurement by computing
a moving average. It is possible to record a moving average calculated over the previous
X samples, selectable from the previous 2 samples up to the previous 16 samples. The
purpose of the following setting is to select for each channel whether or not to compute
a moving average, and if so, over how many samples.
(One sampling period is five seconds.)
The initial value is ‘OFF’.
Example: (let us assume a moving average over five samples is selected)
Buffer data for
nth sample
Buffer data for
(n+1)th sample
Buffer data for
(n+2)th sample
1
2
3
4
5
10.0mV
5.0mV
new data
15.0mV
10.0mV
5.0mV
new data
10.0mV
15.0mV
10.0mV
5.0mV
0.0mV
–5.0mV
–10.0mV
0.0mV
erased
–5.0mV
erased
0.0mV
Average
0.0mV
5.0mV
8.0mV
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select the channel No. using the [ ] key for which you want to compute a moving
average. Then press the [ENT] key.
Use the [ ] key to select the number of samples. You can choose from ‘OFF’, ‘2’, ‘3’,
... up to ‘16’. Press the [ENT] key. The display [
] will appear.
Press the [ENT] key to continue the setting for other channels. The moving average
setting has been completed, but has not been stored yet.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 7
Download from Www.Somanuals.com. All Manuals Search And Download.
7.7 Turning Offset Settings Protection On/Off
Configure the recorder so changes can (on) or cannot (off) be made to the offset settings
in the SET mode. And in the list printing, if ON is set, the offset data are printed.
NOTE When protection is turned on, you can set an offset value must be set in the
SET mode. The initial value is ‘OFF’
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Using the [ ] key, select either ‘ON’ or ‘OFF’ and then press the [ENT] key. The
display [ ] will appear. The setting is then complete.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 8
Download from Www.Somanuals.com. All Manuals Search And Download.
7.8 Assigning Different Colors to Channels (Dot-printing model)
7.8 Assigning Different Colors to Channels (Dot-printing model)
You can assign any of the six provided colors to any channel. The initial setting is as
follows:
ch.1 = purple
ch.2 = red
ch.3 = green
ch.4 = blue
ch.5 = brown
ch.6 = black
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
Select the channel No. for which you want to change a color. Then press the [ENT] key.
Select the color. Then press the [ENT] key. The display [ ] will appear.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
]. Press the [ENT] key.
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 9
Download from Www.Somanuals.com. All Manuals Search And Download.
7.9 Setting Pen Offset Compensation On/Off (Pen model, /D1 option)
The POC function eliminates deviation (phase difference) between the pens on the time
axis. The following figure shows a side view of the recording status for the 2 pen model
(3 pen model is similar).
The initial value is ‘OFF’.
Reference pen (2nd pen)
1st pen
Front of Recorder
P
Recording chart
Chart feeding direction
Reference pen is
2nd pen for 2 pen model
3rd pen for 3 pen model
Recorder as Viewed from the Side
This figure shows that, in any pen recorder (in order to prevent collision between pens)
the pens must be offset by a distance P. Therefore, points recorded at the same time are
separated on the time axis.
In the case of Pen Offset Compensation, a delay memory is used to store measurement
data, equivalent to the time offset P of the pens (other than the reference pen).
The pens will start to record these stored data when the chart is fed by the amount of P
(time offset).
NOTE Immediately after the recording has been started, only the reference pen
operates normally. The other pens might not seem to operate correctly, but this
is due to the time offset.
When you stop the recording, the chart will stop and therefore data stored in the
delay memory will not be recorded anymore. Therefore, these data will be lost.
Note that an asterisk will be printed in the periodic printout when POC is ‘ON’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select ‘ON’ or ‘OFF’ using the [ ] key. Then press the [ENT] key. The display
] appears.
[
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 10
Download from Www.Somanuals.com. All Manuals Search And Download.
7.10 Turning Alarm Printing On/Off
7.10 Turning Alarm Printing On/Off
When alarms occur, the channel number, level, type of alarm and ON/OFF time can be
printed on the right side of the chart. It is selectable to get the ON/OFF time of alarms
(ON1), the ON time only (ON2) or to get no printout (OFF). Note that alarms will not
be printed when the chart speed exceeds 1800 mm/h (Pen model) or 120 mm/h (Dot-
printing model).
The initial value is ‘ON1’, and this setting is common for all channels.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select ‘ON1’ (ON/OFF time of alarms will be printed), ‘ON2’ (ON time only will be
printed) or ‘OFF’ (no alarm will be printed). Press the [ENT] key.
The display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 11
Download from Www.Somanuals.com. All Manuals Search And Download.
7.11 Setting Periodic Printout On/Off
The contents of the periodic printout can be selected from the following three:
ON1: Date/time, measured values, scale, and chart-feeding speed are printed.
ON2: Date/time and chart-feeding speed are printed.
OFF: No printout.
The default is set to ‘ON1’.
The relationship between the chart-feeding speed and the periodic printout interval is as
shown below.
Pen Model
Chart Speed
Dot-printing Model
Chart Speed
Periodic Printout Interval
Periodic Printout Interval
10 to 15mm/h
20 to 30mm/h
40 to 60mm/h
75 to 120mm/h
150 to 180mm/h
200 to 300mm/h
360 to 1500mm/h
1800mm/h or more
Every 8 hours
Every 4 hours
Every 2 hours
Every 1 hour
Every 30 minutes
Every 20 minutes
Every 10 minutes
No printout
10 to 15mm/h
20 to 30mm/h
40 to 75mm/h
80 to 100mm/h
120mm/h or more
Every 8 hours
Every 4 hours
Every 2 hours
Every 1 hour
No printout
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select ‘ON1’, ‘ON2’or ‘OFF’ using the [ ] key. Press the [ENT] key.
The display [ ] appear.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
NOTE If set, this printout appears on the chart with a certain regularity.
7 - 12
Download from Www.Somanuals.com. All Manuals Search And Download.
7.12 Turning Printing of Changes in Chart Speed On/Off
7.12 Turning Printing of Changes in Chart Speed On/Off
You can select the new chart speed printed on the chart when the chart speed changes.
Note that the chart speed will not be printed when the chart speed exceeds 1800 mm/h
(Pen model) or 120 mm/h (Dot-printing model).
The initial value is ‘OFF’.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Press the [ ] key until the display [
] will appear and press the [ENT] key. Use
the [ ] key to select ‘ON’ or ‘OFF’.
The display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 13
Download from Www.Somanuals.com. All Manuals Search And Download.
7.13 Turning Printing of Channel Numbers On/Off (Dot-printing model)
If turned on, this function prints each channel number next to the measured value at
approximately 25-mm intervals. The default value is ‘ON’.
Note that no channel number will be printed if the chart speed exceeds 120mm/h.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
]. Press the [ENT] key.
Use the [ ] key to select the display [
Using the [ ] key, select either ‘ON’ or ‘OFF’ and then press the [ENT] key. The
display [ ] will appear.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 14
Download from Www.Somanuals.com. All Manuals Search And Download.
7.14 Selecting channel Number or Tag
7.14 Selecting channel Number or Tag
You can select channel numbers or tags printed out in the periodic, channel (Dot-
printing model) and alarm printout.
• If you select ‘OFF’:
Channel numbers
• If you select ‘ON’:
Tags, and in the list printing these printed.
The initial value is ‘OFF’, and this setting is common for all channels.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select ‘ON’ or ‘OFF’ using the [ ] key.
Press the [ENT] key. The display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
NOTE If you choose “ON” for Tag Settings and execute list printing, you can check the
details on the tag defined in the SET mode.
(see page 4-8, “Pen model Printing Sample”.)
7.SETUPMODE
7 - 15
Download from Www.Somanuals.com. All Manuals Search And Download.
7.15 Changing the Temperature Unit (/D2 option)
For the TC or RTD type, the recorder will automatically append the temperature unit
(°C or °F).
The initial value is expressed in ‘°C’, and common for all channels.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select [
] (°C) or [
] (°F) using the [ ] key.
Press the [ENT] key. The display [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
NOTE When you change this setting, all settings in the SET mode will return to their
initial values.
7 - 16
Download from Www.Somanuals.com. All Manuals Search And Download.
7.16 Changing Default Settings for REMOTE Operation (option)
7.16 Changing Default Settings for REMOTE Operation (option)
This paragraph describes the way to change default settings for REMOTE operation.
NOTE The settings concerning the REMOTE option (/R1) are always accessible, and
data entry will be ignored if your instrument is not equipped with this option.
The /R1 option allows you to execute functions on this instrument by a remote trigger
(contact input).
The functions which can be executed by a remote trigger are:
•
•
•
start/stop the recording
change the chart speed to a preset second chart speed
have messages printed out (up to five messages)
However, the /R1 terminal has only five terminals, which means that only five functions
can be triggered. The printing out of one message takes up one terminal.
Initially the functions are assigned to the terminals as follows:
1: start/stop the recording [
] (Record)
2: change the chart speed to a preset second chart speed [
] (Chart Speed)
3: have message 1 printed out [
4: have message 2 printed out [
5: have message 3 printed out [
] (Message 1)
] (Message 2)
] (Message 3)
The purpose of this setting is to assign the to be triggered functions to the five terminals.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Use the [ ] key to select the terminal No. ([
] to [
]) ( /R1 has five
terminals.) Press the [ENT] key.
Use the [ ] key to select the function which you want to assign to that terminal. You
can choose from [ ] (start/stop recording), [ ] (second chart speed),
] (message No. 1, 2, 3, 4, 5). Press the [ENT] key. The display
[
[
] to [
] appears.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
NOTE If you select ‘start/stop recording,’ recording stops if the remote input terminal
is open and starts if the terminal is closed. If you press the [RCD] key during
the startup of remote-controlled recording, recording stops. In contrast, if you
press the [RCD] key during the shutdown of remote-controlled recording,
recording starts. You can start/stop remote-controlled recording even during
the start/stop sequence of recording based on the [RCD] key.
7.SETUPMODE
7 - 17
Download from Www.Somanuals.com. All Manuals Search And Download.
7.17 Turning the Settings Protection Function On/Off
You can protect your settings made in the SET or SET UP modes using a password.
• If you select ‘OFF’:
the choice does not affect operation in any mode.
• If you select ‘ON’:
you must type in a password to enter the SET or SET UP mode. The password
discussed here is one you set in the following procedure.
The initial value is ‘OFF.’
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Use the [ ] key to select ‘ON’ or ‘OFF’. Press the [ENT] key. In the case you
selected Off, the setting is completed.
Set a password in four-digits numerals using the [ ] key and the [ ] key. After
setting is finished, press the [ENT] key. The display [
NOTE Never forget the password.
Before leaving the SET UP mode, you have to store your new settings. Use the [ ] key
] appears.
to select the [
] display, and press the [ENT] key.
Select [
] to keep your new settings or [
] to abort the settings, and
press the [ENT] key. After a few seconds, the OPERATION mode will appear.
7 - 18
Download from Www.Somanuals.com. All Manuals Search And Download.
7.18 Initializing Settings
7.18 Initializing Settings
The settings which can be initialized concern the settings done in the SET mode only.
This initialization does not affect any settings in the SET UP mode.
SETTING PROCEDURE:
Enter the SET UP mode by turning ‘ON’ the power while pressing and holding the [CH
UP] ( ENT) key until the SET UP display appears.
Use the [ ] key to select the display [
]. Press the [ENT] key.
Select [
] or [
] using the [ ] key.
] appears.
Press the [ENT] key. The display [
When leaving the SET UP mode, and you want to initialize your settings. Select the
[
] display with the [ ] key and press the [ENT] key.
Select [
] to initialize or [ ] to abort initialization, and press the
[ENT] key. After a few seconds, the OPERATION mode will appear.
7.SETUPMODE
7 - 19
Download from Www.Somanuals.com. All Manuals Search And Download.
8.1 Error Code List
Chapter 8 TROUBLESHOOTING
This chapter describes the causes and recovering methods of recorder errors.
8.1 Error Code List
8.2 Troubleshooting
8.1 Error Code List
Error Codes
Meaning
Recovery
Memory error of input A/D converter (Dot-printing model)
Memory error of Xchannel input A/D converter (Pen model)
[No Xchannel recording (skipped)]
Calibration data error of input A/D converter (Dot-printing model)
Calibration data error of Xchannel input A/D converter (Pen model)
[No Xchannel recording (skipped)]
Main memory reading error
■
■
Main memory writing error
Contact OMEGA ENGINERRING.
A/D converter memory reading error
A/D converter memory writing error
Range memory reading error
System ROM failure
Main memory failure
Plotter card failure (Pen model)
Ribbon shift, ribbon feed failure (Dot-printing model)
Printer failure (Dot-printing model)
System failure
Entered value exceeds allowable setting range
Time setting error
Enter correct data.
Enter correct time.
Selection of channel that cannot be set
Wrong password
Type the correct channel number.
Type in the correct password.
Attempt to replace pen (
) while recording
Stop recording (See section 4.3.).
Change the reference channel number. See section 6.1.
Change the reference channel number. See section 6.1.
Change the reference channel number. See section 6.1.
Change the reference channel number. See section 6.1.
Change the span value. See section 6.1.
Change the span value. See section 6.1.
Select OFF for setting (See section 6.2).
Select OFF for setting (See section 6.3).
Change the measuring range or the channel.
Reference channel number larger than the channel with DELT setting
SKIP setting made to reference channel with DELT setting
DI setting made to reference channel with DELT setting
SCALE or SQRT setting made to reference channel with DELT setting
SPAN L same as SPAN R in value
8.TROUBLESHOOTING
SCL L same as SCL R in value
Attempt to set alarm to SKIPped channel
Attempt to set alarm to DI channel
Offset setting made to channel whose measuring range is not
VOLT, TC, RTD or SCL.
Value above 10% of recording span set as offset
Enter another value.
8 - 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Self-diagnostic Message Printout
Meanings
STORE SET UP SETTINGS AGAIIN
Check the settings to maintain the reliability of the internal data.
¥ Enter the SET UP mode, and select [
].
¥ Select [ ], and press the [ENT] key.
CONTACT YOUR NEAREST SALES
OR SERVICE CENTER
Failure occurs in nonvolatile storage.
Contact OMEGA customer service.
8 - 2
Download from Www.Somanuals.com. All Manuals Search And Download.
8.2 Troubleshooting
8.2 Troubleshooting
Recorder is completely inoperative
Is the power switch ON?
Does the switch
NO
NO
NO
NO
Turn the switch on properly
See section 4.1.
turn properly?
YES
Is the power supply
properly connected?
Connect the supply lines properly.
See subsection 2.2.2.
YES
Supply the power with specified
voltage/frequency.
Does the power
meet the specified rating?
YES
Contact OMEGA Engineering.
Is the fuse blown?
YES
Replace the fuse.
YES
See subsection 4.8.3.
Is the fuse blown
just after replaced?
NO
End
YES
Contact OMEGA Engineering.
8.TROUBLESHOOTING
8 - 3
Download from Www.Somanuals.com. All Manuals Search And Download.
¥ Errors exceed specified limits
¥ Measuring value indications fluctuate
¥ Pen/printer carriage goes off-scale at 0% or 100%.
Does input signal satisfy
the specifications?
NO
NO
Correct the input according to specifications
YES
¥ Separate the input signal wires from
the noise source.
¥ Ground the recorder.
¥ Ground the measuring object.
¥ Insulate TC from the measuring object.
¥ Use shielded cables for input signals.
Is the input free of noise?
YES
¥ Correctly attach the terminal cover.
¥ Check the wind from appliances such
as cooling fan.
¥ Decrease the temperature change
around the input terminals.
Are measures applied
to prevent ambient
temperature changes?
NO
NO
YES
¥ Check the wiring connection being
correct. (See subsection 2.2.3.)
¥ Attach the terminal block correctly.
¥ Tighten the terminal screws again.
¥ Insulate the RTD from grounding wire.
¥ Replace the TC if its wire is broken.
Are input wires correctly
connected to the terminals?
YES
¥ Halt the burnout function of other
instruments.
¥ Make one-point grounding together
with other instruments.
Is the recorder parallel
connected with other
instruments?
NO
¥ Cancel the parallel connection (for
example, use a double element TC).
YES
NO
Is pen position/dot-printing
position correctly adjusted?
Readjust the pen position/dot-printing position. See subsection 4.8.6, 4.8.7.
YES
Contact OMEGA Engineering.
8 - 4
Download from Www.Somanuals.com. All Manuals Search And Download.
Glitch is found other than the previously mentioned ploblems.
¥ Separate the input/communication
NO
signal wires from the noise source.
¥ Ground the recorder.
Is the input free of noise?
YES
¥ Use shielded cable for input/
communication signal.
¥ Attach an insulation transformer for
the power line.
¥ Use a power line filter.
¥ When an inductive load is used in the
alarm output line, insert a surge
suppressor into this line.
Contact OMEGA Engineering.
8.TROUBLESHOOTING
8 - 5
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANT Y/ DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in m aterials and workmanship for a
period of 25 months from date of purchase. OMEGA Warranty adds an additional one (1) m onth grace
period to the norm al two (2) year product war
ranty to cover handling and shipping tim e. This
ensures that OMEGA’s custom ers receive m axim um coverage on each product.
If the unit m alfunctions, it m ust be returned to the factory for evaluation. OMEGA’s Custom er Service
Department will issue an Authorized Return (AR) num ber imm ediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, includ-
ing but no t lim ited to m ishandling, im proper interfacing, o peration outside of design lim its,
im proper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; im proper specification; misapplication; m isuse or other operating
conditions outside of OMEGA’s control. Com ponents which wear are not warranted, including but not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be
as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE,
AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FIT-
NESS FOR
LIABILITY : The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this or der, whether based on contract, war ranty , negligence,
A
P AR TICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on hum ans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assum es no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indem nify
OMEGA and hold OMEGA harm less from any liability or dam age whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUEST S / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Custom er Service Departm ent. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUS TO MER S ERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR num ber should then be m arked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY RETURNS, please have the
following inform ation available BEFORE
contacting OMEGA:
FOR NON-W ARRANTY REPAIRS, consult OMEGA
for current repair charges. Have the following
inform ation available BEFORE contacting OMEGA:
1. Purchase Order number under which the prod-
uct was PURCHASED,
1. Purchase Order num ber to cover the COST
of the repair,
2. Model and serial num ber of the product under
warranty, and
3. Repair instructions and/or specific problem s
relative to the product.
2. Model and serial num ber of the product, and
3. Repair instructions and/or specific problem s
relative to the product.
OMEGA’s policy is to m ake running changes, not m odel changes, whenever an im provem ent is possible. This affords our
custom ers the latest in technology and engineering.
OMEGA is a registered tradem ark of OMEGA ENGINEERING, INC.
© Copyright 1998 OMEGA ENGINEERING, INC. All rights reserved. This docum ent m ay not be copied, photocopied, repro-
duced, translated, or reduced to any electronic m edium or m achine-readable form , in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
Download from Www.Somanuals.com. All Manuals Search And Download.
Wher e Do I Find Everything I Need for
Pr ocess Measurement and Control?
OMEGA…Of Course!
TEMPERATURE
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/ LEVEL
Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/ Paddlewheel Systems
Totalizers & Batch Controllers
pH/ CONDUCTIVITY
pH Electrodes, Testers & Accessories
Benchtop/ Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
HEATERS
Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
M3289/ 0299
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Miele Coffeemaker CVA 2652 User Manual
Miele Convection Oven H 5040 B User Manual
NeoDigitscom DVD Player X5000 HD User Manual
NeumannBerlin Microphone SM 69 User Manual
Nintendo Video Games 45496902841 User Manual
NordicTrack Treadmill NTL219051 User Manual
Oki Printer PAGE 8Z User Manual
Onkyo DVD Player DV S939 User Manual
Optimus Home Theater System 120 1746 User Manual
Palsonic CRT Television 7610WSPF User Manual