MODEL 8000 IPG, ITEM # 165920
Industrial Portable Generator
M165920F
P r o v e n P e r f o r m a n c e
OWNER’S MANUAL
Any Questions, Comments, or Problems?
Call Customer Service at 1-800-270-0810
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
Item Number
Maximum Output
Continuous Output
Voltage
165920
8000 Watts (W)
6600 Watts (W)
120 / 240 Volt (V)
Phase
Single phase (4-wire)
Frequency
56.5 - 63.3 Hertz (Hz)
Power Factor
Engine
1.0 p.f.
13 HP Honda GX390
Engine Speed
Fuel Type
3390 - 3798 RPM
Unleaded gasoline
Fuel Capacity
Oil Capacity
Starting Method
120 VReceptacle
6.5 gallons (24.6 L)
1.16 US quarts (1.1 L)
Electric Start / Recoil
(2) 20 Amp (A) duplex GFCI (NEMA 5-20R)
(1) 30 Amp (A) twistlock (NEMA L5-30R)
(1) 50 Amp (A) straight blade (NEMA 5-50R)
30 Amp (A) twistlock (NEMA L14-30R)
(2) 20 Amp (A) Thermal, push to reset
(1) 30 Amp (A) Thermal, push to reset
(1) 50 Amp (A) Thermal, push to reset
(1) 30 Amp (A) Magnetic, 2 Pole
Receives 10 Ga. wire or fork terminal
Use a 12-volt battery with an amperage rating
of at least 18Ah (Amp-Hour).
120/240 VReceptacle
Circuit Breaker
Grounding Post
Battery Requirements
Dimensions
Length
Width
Height
Dry Weight
Gross Weight
31.75” (80.6 cm)
23.63” (60.0 cm)
22.25” (56.5 cm)
225 lb (103 kg)
280 lb (128 kg)
MACHINE COMPONENT IDENTIFICATION
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1 (Ref. 1-7)
Ref. Description
00576
Ref. Description
1
2
3
4
5
6
7
Air Cleaner
Starting/Stopping Instructions
Oil Drain Plug
Control Panel
Gas Cap with Gauge
6.5 Gallon Gas Tank
Super Silent Muffler
8
9
Generator Head
Battery Box
Vibration Isolation Mount
Recoil
Fuel Shut-Off Valve
Choke Lever
Electric Stop/Start Switch
10
11
12
13
14
Figure 2 (Ref. 8-14)
fig. 01810
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Reference 14 - Electric Start/Stop Switch. The
engine key is located on the engine. Always locate this
switch and be familiar with its location before operating the
generator.
GENERATOR FEATURE
Reference 1 - Air Cleaner. Refer to your Honda
engine manual for air cleaner care.
Reference 15 and 16 – Reserved for future use.
Reference 2 - Starting/Stopping Instructions.
Reference 3 - Oil Drain Plug. Refer to your Honda
engine manual for oil change recommendations.
Reference 4 - Control Panel. See Fig. 3 for details.
Reference 5 - Gas Cap with Gauge. The gas cap is
extra large, creating a large hole for refueling. You can
monitor the fuel level without removing the cap by using
the fuel level indicator built into the gas cap.
Reference 6 - 6.5-Gallon Gas Tank. Large tank
allows for extended run capabilities. ALWAYS allow room
for gasoline expansion by not filling the gas tank
completely full.
CONTROL PANEL IDENTIFICATION
Figure 3 (Ref. 17-30)
Ref. Description
01937
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Full Power Switch
Voltmeter
Hour Meter
120V/240V-30ATwist-lock Receptacle
Grounding Post
120V-30A Twist-lock Receptacle
120V-50A Straight Blade Receptacle
120V-20A Duplex Receptacle
120V-20A GFCI Duplex Receptacles
20A Circuit Breaker
30A Circuit Breaker
50A Circuit Breaker
Reference 7 - Super Silent Muffler. 4 dB less than
Honda’s standard muffler.
Reference 8 - Generator Head.
The electricity
producing part of the generator.
Reference 9 - Battery Box. Warning: Always wear
safety glasses when working on or near the battery.
The battery box provides protection for the battery and will
accept a standard lawn tractor size battery (Group U1-7).
The engine requires a 12-volts battery, with a minimum
rating of 18Ah (Amp-Hour). When installing the battery,
always connect the red colored (“positive” or “+”) cable
first. When disconnecting the battery, always remove the
black colored (“negative” or “-”) cable first.
Main Line Circuit Breaker 30A
Idle Control On/Off Switch
Reference 17 - Full Power Switch. The switch
reconnects the two generator windings from parallel (120V
only) to series (120/240V).
WARNINGSulfuric acid is a corrosive poison.
Avoid contact with skin, eyes or clothing. Always wear
safety gl asses.
•
120V Only: Allows all 6600 watts (55A) to be used in
any combination of 120 volt receptacles. The
120/240V 30A twist-lock receptacle is 120V only at this
time.
120/240V : Allows all 6600 watts to be used for 240V.
However, only half the power or 3300 watts (27.5A),
can be used at any one 120V receptacle. 120V output
can total 6600 watts.
Reference 10 - Vibration Isolation Mounts. The
engine and generator are mounted on rubber cylinders
that absorb most of the engine vibration. This feature
eliminates the tendency of the machine to “walk” which is
common in engine powered equipment.
Reference 11 - Recoil. Grasp firmly when starting
engine.
Reference 12 - Gas Line Valve. The engine is
equipped with an ON-OFF valve located on the left side of
the recoil. ALWAYS keep this valve closed when the
generator is not in use.
Reference 13 - Choke Lever. Used during cold
starts. Refer to the starting/stopping instructions and the
Honda engine manual for usage.
•
Reference 18 - Voltmeter. Voltmeter needle should
be in green area during all generator load conditions.
Reference 19 - Hour Meter.
Allows for better
maintenance scheduling of generator.
Reference 20 - 120/240V 30A Receptacle. This
receptacle is a NEMA L14-30P twist-lock device, and is
capable of drawing 30 amps. This receptacle accepts only
NEMA L14-30P plugs. Use this receptacle if installing a
transfer switch.
Reference 21 - Grounding Post.
Ground the
generator via the grounding post, to a copper pipe or rod
RE CEPTA CLES
that is driven down until it reaching moist soil.
IDLE CO NTR OL
References 22-25 - 120V Receptacles.
The
generator has a control panel with:
•
Reference 22
receptacle, capable of drawing 30 amps. This
-
One NEMA L5-30R twist-lock
HO UR M ETE R
receptacle accepts a NEMA L5-30P plug.
G
H
@
H
?
4
Download from Www.Somanuals.com. All Manuals Search And Download.
engine operation and maintenance always refer to the
Honda engine owner’s manual furnished with the
generator (Honda refers to the 13 HP engine as a GX390).
NorthStar is constantly improving its products. The
specifications outlined herein are subject to change
without prior notice or obligation. The purchaser and/or
user shall assume liability of any modification and/or
alterations on this equipment from original design and
manufacture.
•
•
Reference 23 - One straight-blade 120V receptacle
capable of drawing 50 amp, NEMA 5-50R. This
accepts a NEMA 5-50P plug.
Reference 24 - One duplex (two receptacles in a
common housing) 120V straight-blade receptacle
capable of drawing 20 amp, National Electrical
Manufacturer’s Association (NEMA) part number 5-
20R. This receptacle accepts a NEMA numbers 5-
15P or 5-20P plugs. This receptacle is GFCI protected
by reference 25. To reset this receptacle, press the
reset button on item 25.
Before using, the user shall determine the suitability of
this product for its intended use and assumes liability
therein.
•
•
Reference 25 – One duplex (two receptacles in a
common housing) 120V GFCI
straight-blade
receptacles capable of drawing 20 amps, National
Electrical Manufacturer’s Association (NEMA) number
5-20R. This receptacle accepts a NEMA number 5-
15P or 5-20P plug. This receptacle has a test and
reset button located on the receptacle face.
ALWAYS use grounded male plugs. The neutral line
of the generator is mechanically grounded to the
frame. Matching NEMA male plugs must always be
used.
ANSI SAFETY DEFINITIONS
DANGER indicates an imminently hazardous
situation which, if not avoided, will result in death or
serious injury. This signal word is to be limited to the most
extreme situations.
WARNING indicates
a
potentially hazardous
situation which, if not avoided, could result in a death or
serious injury.
WARNING Contact a licensed electrician to
wire electrical plugs and/or cord-sets. Improper wiring
could result in a fire or electrical shock.
References 26-29 - Circuit Breakers. This portable
generator has:
CAUTION indicates
a
potentially hazardous
situation, which if not avoided, may result in minor or
moderate injury. It may also be used to alert against
unsafe practices.
•
•
•
•
Reference 26 - 1 - 20 amp (A) push-to-reset circuit
breaker
Reference 27 - 1 - 30 amp (A) push-to-reset circuit
breaker
Reference 28 - 2 - 50 amp (A) push-to-reset circuit
breaker
Reference 29 - 1 - 30 amp (A) magnetic 2-pole main
circuit breaker to protect against electrical overloads.
RULES FOR SAFE OPERATIONS
Safety precautions are essential when operating this
generator. Respectful and cautious operation will
considerably lessen the possibilities of a personal injury.
This manual will warn of specific personal injury potential,
and these will be designated by the symbol:
Reference 30 - Idle Control On/Off Switch. This
feature senses the load on the generator. With no load on
the generator the engine speed drops to idle. This saves
fuel and lengthens engine life. When a load is applied, the
engine speed returns to 3600 - 3780 RPMs. Turning the
switch off disables the sensing device and the generator will
run at 3600 - 3750 RPM whether or not a load is applied.
Note: When the engine is idling, it is normal for the
voltmeter needle to be in the red range.
Low Oil Shutdown. The Honda engine is protected
against damage resulting from low oil level. As the oil falls
below the safe level, the engine automatically shuts off (the
engine stop switch remains in the on position). The engine
will not start until the oil is refilled to above the safe level.
WARNING This generator is equipped with a
grounding post, located on the control panel for your
protection. Always complete the grounding path from the
generator to a copper pipe/rod that is driven into moist
earth, to prevent electrical shock.
ALWAYS use electrical cords that are in good
condition. Worn, bare, frayed or otherwise damaged cords
can cause electric shock.
NEVER operate the generator, or handle any electrical
equipment while standing in water, while barefoot, while
hands are wet or while in the rain or snow. Electric shock
may result.
ALWAYS use a ground fault circuit interrupter (GFCI)
in damp or highly electrical conductive areas and on
construction job-sites to prevent electric shock.
INTRODUCTION
Before starting your generator, thoroughly study the
instructions and cautions in this manual to assure you are
fully acquainted with the operation of all components of
this generator. Proper preparation, operation and
maintenance will result in operator safety, best
performance and long life of the generator. For detailed
5
Download from Www.Somanuals.com. All Manuals Search And Download.
ALWAYS remove the spark plug or spark plug wire
before working on the engine or generator, to prevent
accidental starting.
NEVER install your generator inside confined areas.
Inside installation can cause health hazards or death.
ALWAYS provide adequate ventilation. Do not operate
generator in any enclosed or narrow space. Engines
consume oxygen and give off deadly carbon monoxide
poisonous gas. Improper ventilation will cause damage to
generator and possible injury to people.
NEVER touch hot muffler, hot exhaust manifold or
engine cooling fins.
DANGER Remember, exhaust fumes are
deadly carbon monoxide gas, and must be vented to the
outside where there are no people.
Cooling air of
sufficient amounts must be allowed to flow in and
exhausted out to ensure proper cooling of the engine and
generator head.
ALWAYS remove all oil or gasoline deposits and
accumulated dirt from generator and immediate area.
Keep generator head and engine clean.
NEVER operate the generator under the following
conditions:
LOAD APPLICATION
It is important to determine the total electrical load
before it is connected to the generator. The two major
factors in determining the life of a generator head are heat
build-up, caused by overloading the generator and
corrosive contaminants that can attack the wiring
insulation. If the generator is overloaded, the wires
become excessively hot and cause the insulation to break
down, reducing its ability to resist corrosive contaminants.
Over time the effectiveness of the insulation is eliminated
and a dead short can result.
A. Excessive change in engine speed, slow or
fast.
B. Overheating in load connecting devices.
C. Sparking or arcs from generator.
D. Loss of electrical output.
E. Damaged receptacles.
F. Engine misfire.
G. Excessive vibration.
H. Enclosed compartments, or confined areas.
I. Flame or smoke.
J. Rain, snow or wet conditions.
K. Operator non-attendance.
L. Excessive overload of generator.
M. Wire with too small a gauge for the load.
Always compare the generator nameplate data with
that of the equipment to be used to ensure that watts,
volts, amperage, and frequency requirements are suitable
for operating equipment. The wattage listed on the
equipment nameplate is its rated output. However, some
equipment may require three to ten times more wattage
than its rating on the nameplate, as the wattage is
influenced by the equipment efficiency, power factor and
starting system. NOTE: If wattage is not given on
equipment nameplate, approximate wattage may be
determined by multiplying nameplate voltage by nameplate
amperage.
WARNING Check fuel system on a regular
basis. Look for signs of leaks, deterioration, chafed or
spongy fuel hose, loose or missing fuel hose clamps,
damaged fuel tank or a defective fuel shut-off valve.
Correct any defects before operation.
VOLTS X AMPS = WATTS
Example: 120V X 5A = 600W
WARNING Keep the fire extinguisher close
by your generator and be familiar on how to use it.
Consult your local fire department for correct extinguisher
type.
When connecting
a
resistive load such as
incandescent lights, heaters or common electric power
tools, a capacity of up to the generator full rated wattage
output can be used.
When connecting a resistive-inductive load such as a
fluorescent or mercury light, transformers or inductive
coils, a capacity of up to 0.6 times the generators full rated
output can be used.
Always allow the generator to reach operating speed
before a load is applied.
INSTALLATION
OUTDOORS: Choose locations where the generator
will not be exposed to rain, snow or direct sunlight.
Position the generator on secure, level ground so it will not
tip or slide down a hill. Place the generator so that the
exhaust fumes will not be directed towards people.
The installation site must be free from water, moisture,
or dust. All electrical components should be protected
from excessive moisture or the insulation system will
deteriorate and result in grounding or shorting out the
generating system.
STARTING ELECTRIC MOTORS
Electric motors require much more current (amps) to
start than to run. Some motors, particularly low cost split-
phase motors, are very hard to start and require 5 to 7
times more current to start than to run. Capacitor motors
are easier to start and usually require 2 to 4 times more
current to start than to run. Repulsion-Induction motors
Foreign matters, such as dust, dirt, sand, lint, or
abrasive materials can cause damage to the generator
head and engine if allowed into its cooling system.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
are the easiest to start and require 1.5 to 2.5 times more to
start than to run.
20
30
40
50
4800
7200
9600
12000
125’
60’
30’
75’
35’
15’
*
50’
25’
10’
*
25’
10’
*
Most fractional motors take about the same amount of
current to run them whether they are of Repulsion-
Induction (RI), Capacitor (Cap), or Split-Phase (SP) type.
The following chart shows the approximate current
required to start and run various types and sizes of 120
volt 60 cycle electric motors under various conditions.
15’
*
*Not recommended
CAUTION: Equipment damage can result from the low
voltage caused by using an extension cord with a small
wire size.
Use this chart to estimate the total load on your
generator.
Starting Amps
RI type Cap type SP type
120V, 60 Hz Motors
Hp motor Running
Watts
For Determining Generator Load Requirements
1/6
1/4
1/3
1/2
1
1 1/2
2
525
700
875
1175
1925
2400
2900
4075
6750
7-11
9-15
9-18
12-23
14-29
20-40
32-64
40-80
48-96
68-136
112-224
16-22
22-32
26-35
NA
NA
NA
NA
NA
NA
Device
Running Watts
1700 (a)
500
Air Conditioner (12,000 Btu)
Battery Charger (20 Amp)
Belt Sander (3”)
Chain Saw
Circular Saw (6-1/2”)
Coffee Maker
Compressor (1 HP)
Compressor (3/4 HP)
Compressor (1/2 HP)
Curling Iron
Dishwasher
Edge Trimmer
Electric Nail Gun
Electric Range (one element)
Electric Skillet
11-18
15-25
24-40
30-50
36-60
51-85
84-140
1000
1200
900
1000
2000 (a)
1800 (a)
1400 (a)
700
1200
500
1200
1500
1250
800 (b)
1200 (a)
1200
1100
875
3
5
The figures given above are for an average load such
as a blower or fan. If the electric motor is connected to a
hard starting load such as an air compressor, it will require
more starting current. If it is connected to a light load or no
load such as a power saw, it will require less starting
current. The exact requirement will also vary with the
brand or design of the motor.
Generators respond to severe overloading differently
than the power line. When overloaded, the engine is not
able to supply enough power to bring the electric motor up
to operating speed. The generator responds to the high
initial starting current, but the engine speed drops sharply.
The overload may stall the engine. If allowed to operate at
very low speeds, the electric motor starting winding will
burn out in a short time. The generator head winding
might also be damaged.
Freezer
Furnace Fan (1/3HP)
Hair Dryer
Hand Drill (1”)
Hand Drill (1/2”)
Hand Drill (3/8”)
Hand Drill (1/4”)
Hedge Trimmer
Home Computer
Impact Wrench
500
250
450
150
500
Running the generator under these conditions may
result in damage to the generator stator as well as the
motor windings. Because the heavy surge of current is
required for only an instant, the generator will not be
damaged if it can bring the motor up to speed in a few
seconds. If difficulties in starting a motor are experienced,
turn off all other electrical loads and if possible reduce the
load on the electric motor.
Load Requirements, continued
Jet Pump
800 (a)
Lawn Mower
1200
100
700
Light Bulb
Microwave Oven
Milk Cooler
1100 (a)
Oil Burner on Furnace
Oil Fired Space Htr (140,000 Btu)
Oil Fired Space Htr (85,000 Btu)
Oil Fired Space Htr (30,000 Btu)
Oven
300
400
225
150
EXTENSION CORDS
4500
When electric power is to be provided to various loads
at some distance from the generator, extension cords can
be used. These cords should be sized to allow for
distance in length and amperage so that the voltage drop
between the set and point of use is held to a minimum.
Paint Sprayer, Airless (1/3 HP)
Paint Sprayer, Airless (handheld)
Radio
Refrigerator
Slow Cooker
600 (a)
150
200
600 (b)
200
Submersible Pump (1-1/2 HP)
Submersible Pump (1 HP)
Submersible Pump (1/2 HP)
Sump Pump
Table Saw (10”)
Television
2800 (a)
2000 (a)
1500 (a)
600 (a)
2000 (a)
500
Current/Power Maximum Extension Cord Length
Amps
at
Load
(watts)
#10
Ga.
#12
Ga.
#14
Ga.
#16
Ga.
240V
Cord
Cord
Cord
Cord
10
2400
250’
150’
100’
75’
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Toaster
Vacuum cleaner
VCR
Water Heater
Weed Trimmer
1000
250
70
3000
500
Load
Output
Frequency
Percent of
Generator
Output
0 %
50 %
100 %
Speed
(RPM)
Generator
Voltage at 120V
Receptacle
(Hz)
3780
3600
3480
63.0
60.0
58.0
129V
120V
112V
(a) Hard-starting motors require 3 to 5 times the rated
running watts.
(b) These loads may require up to 15 minutes to
restart due to its normal build up of compressor head
pressure.
NOTE: For extremely hard to start loads such as air
conditioners and air compressors, consult the equipment
dealer to determine the maximum wattage.
Output voltage should periodically be checked to
ensure continued proper operation of the generating plant
and appliances, it can be checked with a portable meter.
Frequency can be checked using an electric clock with a
sweep second hand. Timed against a wristwatch or a
stopwatch the clock should be correct within +/- 2 seconds
per minute. A qualified technician should do all speed
setti ng adjustm ents.
PRE-START PREPARATIONS
BEFORE STARTING
Your generator has been thoroughly tested prior to
shipment from the factory. However, damage can occur
during shipping, so be sure to check for damaged parts or
loose or missing nuts and bolts. If problems occur, call
Customer Service at 1-800-270-0810.
1. Make sure the generator is positioned on firm level
surface.
2. Check the crankcase for oil and maintain at a proper
level.
3. Check fuel level and fill tank with fresh unleaded
gasoline. Never fill fuel tank completely to the top. Always
wipe up and remove any spilled gasoline.
4. Make sure that the exhaust fumes are directed
away from people.
GROUNDING - All units must be grounded. Drive a
3/4” or 1” copper pipe or rod into the ground close to the
generator. The pipe/rod must penetrate moist earth.
Connect an approved ground clamp to the pipe. Run a no.
12 Ga. wire from the clamp to the generator grounding
post located on the control panel. Do not connect to a
water pipe or a ground used by a radio system.
CAUTION: The engine has been shipped without oil.
Fill the crankcase with oil before trying to start. Low oil
shutdown prevents your generator from starting without
sufficient oil.
STARTING - MANUAL
1. Disconnect all loads to generator.
2. Turn gas line valve to ON position.
3. Turn key to the ON position.
OPERATING SPEED
The generator must be run at the correct speed in
order to produce the proper electrical voltage and
frequency. The speed of the engine was carefully adjusted
at the factory so that the generator produces the proper
voltage and frequency.
The output voltage should be checked to ensure the
generator is working properly before connecting a load to
the generator. Failure to do so could result in damage to
equipment plugged into the unit and possible injury to the
individual.
4. For cold engine, move choke lever to full choke
position, for warm engine, move choke lever to half choke
or to RUN position.
5. Firmly grasp recoil handle and pull.
6. When engine starts, move choke lever to RUN
position.
7. Loads may now be connected to generator.
All engines have a tendency to slow down when a load
is applied. When the electrical load is connected to the
generator, the engine is more heavily loaded, and as a
result the speed drops slightly. This slight decrease in
speed, together with the voltage drop within the generator
itself, results in a slightly lower voltage when the generator
is loaded to its full capacity than when it is running with no
load. The slight variation has no appreciable effect in the
operation of motors, lights and most appliances. Electronic
equipment and clocks will be affected if correct RPM is not
maintained. See Load vs. Output chart.
STARTING - ELECTRIC
1. Disconnect all loads to generator.
2. Turn gas line valve to ON position.
3. For cold engine, move choke lever to full choke
position, for warm engine, move choke lever to half choke
or to RUN position.
4. Turn key to start position.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
5. When engine starts, move choke lever to RUN
position.
without an isolating, UL approved transfer switch, installed
by a licensed electrician.
6. Loads may now be connected to generator.
STOPPING
1. Disconnect all loads to generator.
2. Place key to the OFF position.
3. Turn gas line valve to OFF position.
ENGINE CARE
Refer to your Honda Owner’s Manual for proper care
and maintenance.
NOTE: When changing the oil on a hot engine, the oil
might overshoot the oil drain hole on the generator base.
GENERATOR CARE
The generator head is a 2-pole, 3600-RPM, 60-Hz,
brushless, revolving field and synchronous type with one
sealed ball bearing. The rotor of the generator head is
directly connected to the engine crankshaft and the stator
is rigidly coupled to the engine casting via the generator
head casting.
Exercising the Generator - The generator should
be operated every four weeks. This is accomplished by
starting the engine and applying a load for 10 to 15
minutes.
This will dry out any moisture that has
accumulated in the windings. If left, this moisture can
cause corrosion in the winding. Frequent operation of the
engine generator will also ensure that the set is operating
properly should it be needed in an emergency.
Generator Maintenance - The generator head is
brushless and maintenance free. Major generator service,
including installation or replacement of parts should be
performed only by a qualified electrical service technician.
USE ONLY NORTHSTAR APPROVED REPAIR PARTS
AVAILABLE AT 1-800-270-0810.
A. Bearing - The bearing used in these generators is a
heavy duty sealed ball bearing. They require no
maintenance or lubrication.
B. Receptacles - Quality receptacles have been
utilized. If a receptacle should become cracked or
otherwise damaged, replace it.
Using cracked or
damaged receptacles can be both dangerous to the
operator and destructive to the equipment.
WARNING, Stand-by Operation
If your generator is to be used as a standby electric
power source in case of utility failure, it must be installed
by a registered and licensed electrician and in compliance
with all applicable state and local electrical codes. Also,
local Fire Departments must be consulted concerning
proper and safe handling procedures for gasoline. NEVER
connect any generator to any existing electrical system
9
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Problem
Possible Causes
Possible Remedies
Engine will not start.
a) Low oil level.
b) Fouled spark plug.
c) Out of fuel.
a) Fill crankcase to proper oil level.
b) Clean or replace spark plug.
c) Fill fuel tank.
d) Stop switch in OFF position.
e) Battery has lost its charge.
d) Place switch in ON position.
e) Battery has low electrolyte and/or
needs to be charged or replaced.
a) Bring generator to a qualified
technician for adjustment.
b) Reduce the load. (See Load
Application section of this manual.)
c) Bring generator to a qualified
technician for inspection.
Voltage too low.
a) Engine speed too slow.
b) Generator is overloaded.
c) Idle control is malfunctioning.
Circuit breaker trips.
Voltage too high.
a) Defective load connected to generator.
b) Defective receptacle.
c) Generator overloaded.
a) Disconnect load.
b) Replace receptacle.
c) Reduce the load. (See Load
Application section of this manual.)
a) Bring generator to a qualified
technician for adjustment.
a) Engine speed too high.
Generator overheating. a) Generator is overloaded.
b) Insufficient ventilation.
a) Reduce the load. (See Load
Application section of this manual.)
b) Make sure there is at least 3 feet of
clearance on all sides of generator.
a) Disconnect load.
No output voltage.
a) Defective load connected to generator.
b) Broken or loose wire.
b) Bring generator to a qualified
technician for repair.
c) Defective receptacle.
d) Defective stator.
c) Replace receptacle.
d) Bring generator to a qualified
technician for repair.
e) Bring generator to a qualified
technician for repair.
e) Defective rotor.
f) Defective capacitor.
a) Generator is overloaded.
f) Bring generator to a qualified
technician for repair.
Engine lacks power.
a) Reduce the load. (See Load
Application section of this manual.)
b) Clean or replace air filter.
a) Place switch in ON position.
b) Check for 12 VDC at solenoid. Check
coil resistance, it should be 18.5Ω ±5%.
Check for sticking in mechanism and
solenoid. Replace idle assembly if
necessary.
b) Dirty air filter.
a) Switch is in OFF position.
b) Solenoid failure.
Idle control doesn’t
work.
c) Defective circuit board.
d) Defective capacitor.
c) Bring generator to a qualified
technician for repair.
d) Bring generator to a qualified
technician for repair.
e) Circuit breaker tripped
e) Reset circuit breaker.
f) Engine idle speed to low-engine will not
jump back to normal operating speed
unless idle on/off switch is placed in off
position.
f) Raise engine idle speed by turning
engine throttle stop screw. See
carburetor adjustment section of the
Honda Owner’s Manual. Turn stop
screw ½ turn clockwise.
Engine shuts off during a) Out of fuel.
operation. b) Low oil level.
a) Fill fuel tank.
Fill crankcase to proper oil level.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
|