| M010901   Issue 5, revised 04/99   Catalogue section 75   R The Generator Controls Division of   KEYSTART 9700 series   MANUAL START ENGINE CONTROLLER WITH   AUTOMATIC FAULT PROTECTION SHUTDOWN   The Keystart 9700 range provides for the manual starting and   stopping of a standby engine - a generator, pump or other   application - with automatic monitoring and shutdown of the   engine in the event of a fault.   The 9700 series is pin compatible with the Autostart range:   this allows the use of standard wiring for both manual and   automatic control panels, simplifying panel design and   permitting easy upgrades from a manual to fully automatic   control system.   Key features   · · Keyswitch operation for enhanced security   Up to four fault inputs, configurable for use with contacts   which open or close on fault, with wiring to +ve or –ve DC   · Options for overspeed protection (magnetic pickup or   AC alternator driven) and preheat/auxiliary control.   · · · Pin compatible with Autostart 705, 710, 720 and 730 series.   96 x 96mm DIN standard, front panel mounted case   Switchable 12 or 24 V DC power supply   Product Specifications   Operation   Power supply:   The Keystart is powered from the engine battery or similar   low voltage DC source. A switch at the rear allows for 12V   or 24V operation.   Operating voltage:   Steady state   Brown out / cranking   Current consumption   (12V setting)   9 – 20 V DC   <= 5V for 2 secs   (24V setting)   18 – 33 V DC   <= 10V for 2 secs   Control of the Keystart and engine is by use of a 3 or 4   position keyswitch on the front facia:-   < 150mA   Inputs:   STOP Removes power from the Keystart, stopping the   Fault switch inputs:-   + ve input defined as:   – ve input defined as:   Speed sensing inputs:-   Magnetic pickup   AC alternator   selectable: open or closed, + ve or – ve   80% to 100% of +ve DC supply   –1V to +2V w.r.t –ve DC supply   engine and resetting a latched fault condition.   RUN   Energises the Keystart’s RUN relay (enabling   the engine fuel or ignition). The fault ‘override’   timer begins as soon as the key is turned (or   spring returns) to this position. Once the engine   is fully running, Keystart monitors for faults and   shuts down the engine if a fault is detected.   10 – 60 VAC peak, < 2300 to > 3400 Hz.   90 – 350 VAC rms, < 50 to > 60 Hz. nom.   Outputs:   (all ratings for resistive load)   Run relay output   volt-free SPCO relay contacts   16 A max. @ 24V DC   START Maintains fuel to the engine, and activates the   START output (used for controlling the starter   motor circuit). This position is spring-biased to   return to the RUN position when the operator   releases the key.   Start output   + ve DC (switched)   16 A max. @ 24V DC   + ve DC (switched)   15 A max. @ 24V DC   Auxiliary/preheat output   Alarm output   AUX   (optional: 'A' models only) Provides a switched   +ve DC output, used for preheat circuits or   auxiliary control (remote power up) of Keystart.   – ve DC (open collector transistor)   300mA max. @ 33V DC max.   To suit 0 – 1 mA, 75 Ohm meter,   output = 0.75mA at rated engine speed   Tachometer / calibration   The key is common to all Keystarts and is removable   only in the STOP position.   Adjustable settings:   Fault Override timer   Overspeed trip level   < 10 to > 30 secs.   < 100 to >130 % of calibrated speed   The front facia also has five LED and pictogram indicators   for the display of engine fault status:-   General:   Low Oil Pressure   Overall dimensions (w x h x d)   Panel cut-out size   Weight   Operating ambient temperature   Case sealing   Vibration   Chemical/fire   96 x 96 x 130 mm   DIN 92 x 92 mm   High Engine Temperature   Overspeed (or Plant Fail on non-overspeed units)   Charge Fail   approx. 500 g   –10oC to +55oC   IP22   1G, 50 Hz to 5 kHz.   case: glass filled Noryl,   self extinguishing, non-dripping.   facia: polycarbonate   Plant Fail   In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.   Download from Www.Somanuals.com. All Manuals Search And Download.   |