S10 series
AUTOMATIC BATTERY CHARGERS
RATINGS TO 10 AMPS
The S10 is a constant potential, open-chassis battery
charger, suitable for use with either 12V DC or 24V DC,
lead acid or Ni-Cd systems. Although primarily designed
for the diesel generator market, the charger may be
configured for use in a wide range of unattended industrial
applications where standby power is required at all times.
Each unit consists of a transformer, rectifier and control
circuitry. The charger monitors the battery voltage and
delivers as much current as the cells require up to the
current limited maximum, giving a rapid recovery of charge.
Once the battery is fully charged, the charger provides a
low trickle charge to maintain the cells for an indefinite
period at a pre-set float voltage, without overcharging, plus
any additional current required to support a static load.
Product Specification
Power supply:
operating voltages
Also included is a range of on-board fault monitors
complete with volt free relay contacts for remote
alarm signalling.
240 V AC or 110 V AC (specify),
+/– 10%, 50/60 Hz.
Charging output:
nominal output voltage
voltage stability
current limit
Standard Features
see chart left
+/– 1% of nominal
1 – 10 Amps, factory set
+/– 2% of nominal
·
Boost function, operated by remote link.
Indication by amber LED.
current stability
·
Adjustable float and boost voltage levels to meet with
a range of battery types, static loads and operating
conditions. Standard calibrations are:-
Relay outputs:
charge fail and low battery volts
high battery volts
(ratings for resistive load)
volt free SPNC contacts
volt free SPNO contacts
all rated 5 A @ 30 V DC
BATTERY TYPE
FLOAT
BOOST
VOLTAGE VOLTAGE
General:
(V DC)
(VDC)
operating temperature
overall dimensions (h x l x d)
weight
–10 to +55 oC
185 x 145 x 155 mm
approx. 8.0 Kg
Lead acid (6 cells)
12 V Ni-Cd (9 cells)
Ni-Cd (10 cells)
Lead acid (12 cells)
24 V Ni-Cd (18 cells)
Ni-Cd (20 cells)
13.6
12.8
14.2
27.2
25.6
28.4
14.1
14.0
15.6
28.4
28.1
31.2
EMC emission/immunity
to EN50081-2/EN50082-2
Connection
high
low
F1, fuse type T, rating:
charge
fail
battery battery
volts volts
·
Adjustable current limit. Standard versions have a
10 Amp limit, but this may be adjusted downwards
where required (e.g. for lower capacity batteries).
S1012, 240V: 1.5A
110V: 3.15A
S1024, 240V: 3.15A
110V: 6.3A
1 2
3 4
5 6
·
·
Output short circuit protection.
L
7
8
F1
+
Protection against reverse polarity battery connection
via fuse and red warning LED.
AC
supply
battery
N
E
BCS
–
·
3 alarm monitoring circuits: 'charge fail', 'low battery
voltage' and 'high battery voltage', complete with
volt-free relay outputs and LED indicators. The low
battery voltage alarm features a fixed time delay of
approx. 60 secs. to inhibit the signalling of a fault
during normal battery loading (e.g. engine cranking).
9
10
Boost
switch/timer
Dimensions (mm)
Overall
Fixing Base
Electrical connection of the battery, boost and charge
monitoring relays is via ¼" blade terminals. The AC supply
is connected through separately mounted screw terminals.
When ordering, please specify:-
a) Product type (S10 series)
b) Nominal output voltage (12 or 24 V DC)
c) AC supply voltage (240 or 110 V)
d) Battery type (Lead-acid, or Ni-Cd and number of cells,
or special calibration requirements).
Frank W. Murphy Ltd.
Frank W. Murphy Ltd. en France
Frank W. Murphy Southern Division
Murphek Pty. Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89 PO Box 1819, Rosenberg, Texas 77471, USA
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
Direct usine Tel: + 44 1722 410697
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006
email: sales@fwmurphy.com
Since 1939
Pour service en Français, tél: + 44 1722 410697
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146
email: sales@fwmurphy.com
Frank W. Murphy Pte, Ltd.
Murphy Switch of California
Murphy de Mexico S.A. de C.V.
email: sales@fwmurphy.co.uk
No. 2 Tuas South Street 2, Sprintecs Building
PO Box 900788, Palmdale, California 93590, USA Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
02-01/02, Singapore 637895
Tel: + 1 805 272 4700 Fax: + 1 805 947 7570
email: sales@murphyswitch.com
San Luis Potosí, S.L.P. México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336
email: murmexsl@sanluis.podernet.com.mx
Tel: + 65 863 1398 Fax: + 65 863 0208
email: fwmsales@fwmurphy.com.sg
Download from Www.Somanuals.com. All Manuals Search And Download.
|