Multiquip Portable Generator DCA45SSI User Manual

ꢀ DCA45SSI  
MQ POWER Series Generator  
WhisperWatt™  
Prime Rating — 36 kW (45 kVA)  
standby Rating — 40 kW (50 kVA)  
Three-Phase, 60 Hertz, 0.8 PF  
45  
standaRd FEatuREs  
Heavy duty, 4-cycle, direct injection, diesel engine provides  
maximum reliability.  
Automatic start/stop control — automatically starts the  
generator set during a commercial power failure when used  
in conjunction with a transfer switch.  
Brushless alternator reduces service and maintenance  
requirements and meets temperature rise standards for Class  
H insulation systems.  
Complete generator analog instrumentation includes voltage  
regulator control, ammeter phase selector switch, voltmeter  
phase selector switch, AC voltmeter, AC ammeter, frequency  
meter, panel light, and circuit breaker.  
Open delta excitation design provides virtually unlimited  
excitation for maximum motor starting capability.  
Automatic voltage regulator (AVR) provides precise regulation.  
Automatic safety shutdown system monitors the water  
temperature, engine oil pressure, overspeed and overcrank.  
Warning lights indicate abnormal conditions.  
Electronic Governor Control — maintains frequency to within  
0.25% from no load to full load.  
Complete power panel. Fully covered;three-phase terminals  
and single phase receptacles allow fast and convenient  
hookup for most applications including temporary power  
boxes, tools and lighting equipment. The GFCI receptacles  
are NEMA 5-20, and the auxilillary outputs use CS6369 twist-  
lock receptacles.  
Full load acceptance of standby nameplate rating in one step  
(NFPA 110, para 5-13.2.6).  
Sound attenuated, weather resistant, steel housing provides  
operation at 65 dB(A) at 23 feet. Fully lockable enclosure  
allows safe unattended operation.  
Internal fuel tank with direct reading of fuel gauge.  
Simultaneous single and three phase power.  
Seven stage powder coat paint system provides durability  
and weather protection.  
Voltage selector switch offers the operator a wide range of  
voltages that are manually selectable. Fine tuning of the  
output voltage can be accomplished by adjusting the voltage  
regulator control knob to obtain the desired voltage.  
Fuel/water separator removes condensation from fuel for  
extended engine life. Panel mounted alarm light included.  
Complete engine analog instrumentation includes DC  
ammeter, oil pressure gauge, water temp. gauge, fuel level  
gauge, tachometer/hour meter, preheat indicator, emergency  
shutdown monitors.  
EPA emissions certified - Interim Tier 4 emissions compliant.  
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀ DCA45SSI  
MQ POWER Series Generator  
OPtiOnal gEnERatOR FEatuREs  
Battery charger — provides fully automatic and self-  
adjusting charging to the generator's battery system.  
Jacket Water Heater — for easy starting in cold weather  
climates.  
special Batteries — long life batteries provide extra engine  
cranking power.  
low coolant level shutdown provides protection  
from critically low coolant levels. Includes control panel  
warning light.  
spring isolaters — provides extra vibration protection for  
standby applications.  
gEnERatOR OutPut PanEl  
trailer Mounted Package — meets National Highway  
Traffic Safety Administration (NHTSA) regulations. Trailer is  
equipped with electronic or surge brakes with double or triple  
axle configuration.  
OPtiOnal cOntROl FEatuREs  
Emergency stop switch — when manually activated shuts  
down generator in the event of an emergency.  
audible alarm alerts operator of abnormal conditions  
OPtiOnal OutPut cOnnEctiOns  
cam-lok connectors — provides quick disconnect  
alternative to bolt-on connectors.  
Pin and sleeve connectors — provides industry standard  
connectors for all voltage requirements.  
Output cable — available in any custom length and size  
configuration.  
OPtiOnal FuEl cEll FEatuREs  
trailer Fuel tank — a second fuel cell located in the  
trailer allows for extended run time.  
sub-base Fuel cells (double Wall) — Additional fuel  
cell for extended runtime operation. Contains a leak sensor,  
low fuel level switch, and a secondary containment tank.  
UL142 listed.  
12 hours of minimum run time.  
24 hours of minimum run time.  
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ꢀ DCA45SSI  
MQ POWER Series Generator  
diMEnsiOns  
Weight  
Dry Weight  
Wet Weight  
2,227 lbs. (1,010 kg)  
2,464 lbs. (1,117 kg)  
Max. Lifting  
Point Capacity  
5,150 lbs. (2,335 kg)  
Generator can be placed on  
MQ Power Models TRLR70,  
TRLR70XF, TRLR75XF, and  
TRLR85XFTrailers.  
Manufactured by Denyo Co.  
Your Multiquip dealer is:  
MultiQuiP  
POST OFFICE BOx 6254  
CARSON, CA 90749  
310-537-3700 • 800-883-2551  
FAx: 310-604-3831  
© COPYRIGHT 2011 MULTIQUIP INC.  
DCA45SSIU4 Rev. #12 (08/23/11)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Refrigerator K 9457 iD User Manual
Milan Technology Network Card MIL C2113 User Manual
National Instruments Network Card NI PXI 7831R User Manual
NeumannBerlin Stereo Amplifier V442 User Manual
Niles Audio Universal Remote RCA HT User Manual
NuTone Ventilation Hood WS130AA User Manual
Olympus Carrying Case PPO 02 User Manual
Orbit Manufacturing Smoke Alarm ORBIT 6 RP 206 User Manual
Palsonic Flat Panel Television 6850PF User Manual
Panasonic Cordless Telephone KX TG6551BX User Manual