MGE UPS Systems Power Supply 40 150kVA User Manual

w w w. m g e u p s . c o m  
u
Load  
Load Protected  
Alarms Battery  
0%  
p
n  
%
KVA  
Load  
KA2  
KA1  
UPS  
Input  
load  
K3N  
QF1  
ı
Í
EMERGENCY  
POWER OFF  
fault  
COMET  
M
G
E
M S  
U
P
S
S
Y
S
T
E
Comet 40-150kVA  
Uninterruptible Power Supply  
Installation and User Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Comet  
40 - 150kVA  
Installation and User Manual  
Revision History  
Comet 40-150kVA UPS Installation and User Manual 86-160310-00  
Revision:  
A00  
B00  
C00  
D00  
E00  
Initial Release  
ECN#: 289-91  
ECN#: 290-30  
ECN#: 002456  
ECN#: 004466  
03/1997  
01/1998  
07/1998  
02/2002  
08/2005  
Copyright © 2005 MGE UPS SYSTEMS, INC.  
All rights reserved. Printed in U.S.A.  
MGE UPS SYSTEMS, INC.  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
(714) 557-1636  
Customer Care Center:  
1-800-438-7373 (Hours: 24/7)  
86-160310-00 E00  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
– This manual contains important instructions for the  
Comet 40-150kVA that must be followed during operation and maintenance of the equipment.  
WARNING  
Opening enclosures expose hazardous voltages. Always refer service to qualified  
personnel only.  
ATTENTION  
WARNUNG!  
L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours que le  
service ne soit fait que par des personnes qualifiees.  
Das öffnen der Gehäuse legen gefährliche Spannungen bloss.  
Service sollte immer nur von qualifizierten Personal durchgeführt werden.  
WARNING  
As standards, specifications, and designs are subject to change, please ask for confirma-  
tion of the information given in this publication.  
ATTENTION  
WARNUNG!  
Comme les normes, spécifications et produits peuvent changer, veuillez demander  
confirmation des informations contenues dans cette publication.  
Normen, Spezifizierungen und Pläne unterliegen Anderungen. Bitte verlangen Sie eine  
Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.  
NOTE  
This equipment has been tested and found to comply with the limits for a Class A digital  
device, pursuant to part 15 of the FCC rules. These limits are designed to provide  
reasonable protection against harmful interference when the equipment is operated in a  
commercial environment.  
This equipment generates, uses, and can radiate radio frequency energy and, if not  
installed and used in accordance with the instruction manual, may cause harmful interfer-  
ence to radio communications. Operation of this equipment in a residential area is likely to  
cause harmful interference in which case the user will be required to correct the  
interference at user's own expense.  
WARNING  
To reduce the risk of fire or electric shock, install in a controlled indoor environment free of  
conductive contaminants.  
This equipment is intended only for installations in a RESTRICTED ACCESS LOCATION.  
ATTENTION  
Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente intérieure  
contrôlée en température et humidité et sans contaminants conducteurs.  
Ce matériel est destiné seulement pour des installations dans un EMPLACEMENT  
RESTREINT D'ACCES.  
WARNUNG!  
Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das Gerät in  
einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfähigen  
Verunreinigungen, installiert werden. Dieses Gerät ist nur für die Installation an einem  
Ort mit qeingeschränkter Zugangserlaubnis vorgesehen.  
Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF STANDORT  
bestimmti.  
ii  
Important Safety Instructions  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
WARNING  
ATTENTION  
WARNUNG!  
HIGH LEAKAGE CURRENT. Earth connection essential before connecting  
supply.  
COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant le  
raccordement au reseau.  
Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung herstellen.  
Certification Standards - Three Phase UPS  
IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability.  
FCC Part 15, Subpart J, Class A.  
UL/cUL 1778, Standard for Uninterruptible Power Supply Equipment.  
NEMA PE 1 - Uninterruptible Power Systems.  
NFPA 70 - National Electrical Code.  
ISO 9001.  
Safety of Persons  
The UPS has its own internal power source (the battery). Consequently, the power outlets may be  
energized even if the UPS is disconnected from the AC power source.  
The UPS must be properly grounded.  
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the  
directives listed below must be observed:  
- Never burn the battery (risk of explosion).  
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).  
- Comply with all applicable regulations for the disposal of the battery.  
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.  
Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal  
objects, use tools with insulated handles.  
- Do not lay tools or metal parts on top of batteries.  
Product Safety  
A protection circuit breaker must be installed upstream and be easily accessible.  
The UPS can be disconnected from the AC power source by opening the input circuit breaker.  
UPS must be connected to a nearby power source that is easily accessible.  
Never block the ventilation grates of the UPS.  
The UPS must be installed in a controlled environment.  
Special Precautions  
The UPS connection instructions and operation described in the manual must be followed in the indicated  
order.  
Check that the indications on the rating plate correspond to your AC powered system and to the actual  
electrical consumption of all the equipment to be connected to the UPS.  
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be  
energized for a period of 24 hours, at least once every 3 months (for a normal storage temperature less  
than 25°C). This charges the battery, thus avoiding possible irreversible damage.  
86-160310-00 E00  
Certification Standards and Safety of Persons  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
(This page left blank intentionally)  
iv  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
section  
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i  
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .ii  
Certification Standards - Three Phase UPS . . . . . . . . . . . . . . . . . . . .iii  
Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii  
Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii  
Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii  
CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . .c iv  
Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi  
Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi  
Section 1  
System Description and Specifications  
1.0  
1.1  
1.2  
1.3  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1  
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1  
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 3  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8  
1.3.1 AC Input Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9  
1.3.2 AC Output Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9  
1.3.3 DC Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9  
1.3.4 Mechanical Specifications (UPS Cabinet Only) . . . . . . . . . . . . .1 — 10  
1.3.5 Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10  
1.3.6 DB15 Connector Pinouts and Designations . . . . . . . . . . . . . . . .1 — 10  
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 11  
1.4.1 UPS Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 11  
1.4.2 Software and Communication Package . . . . . . . . . . . . . . . . . . .1 — 11  
1.4  
Section 2  
Installation  
2.0  
2.1  
2.2  
2.3  
2.4  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1  
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1  
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1  
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
Prerequisite to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
2.4.1 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
2.4.2 Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3  
2.4.3 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3  
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.5.1 Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.5  
86-160310-00 E00  
Contents  
c i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
section  
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
Section 2  
Section 3  
Installation (continued)  
2.6  
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.6.1 Main AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.6.2 Bypass AC Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4  
2.6.3 Remote Emergency Power Off (REPO) . . . . . . . . . . . . . . . . . . .2 — 4  
2.6.4 AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5  
2.6.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5  
Operation  
3.0  
3.1  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
3.1.1 Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
3.1.2 Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . . .3 — 1  
3.1.3 Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . . .3 — 2  
Graphical User Interface, Controls and Indicators . . . . . . . . . . . .3 — 2  
Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5  
3.3.1 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5  
3.3.2 Powering Up the Comet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5  
Inverter Manual Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5  
Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3.5.1 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3.5.2 Operation on Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3.5.3 Battery Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3.5.3.1 Return to AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6  
3.5.4 Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7  
Emergency Shutdown Using EPO/REPO . . . . . . . . . . . . . . . . . .3 — 8  
Forced Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8  
Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8  
3.8.1 From Normal Maintenance Bypass Mode . . . . . . . . . . . . . . . . . .3 — 8  
3.8.2 From Maintenance Bypass to Normal Mode . . . . . . . . . . . . . . . .3 — 9  
Shutdown Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10  
3.9.1 Inverter Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10  
3.9.2 Powering Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10  
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10  
3.2  
3.3  
3.4  
3.5  
3.6  
3.7  
3.8  
3.9  
3.10  
Section 4  
Maintenance  
4.0  
4.1  
4.2  
4.3  
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
Battery Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1  
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2  
c ii  
Contents  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figures  
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
1-1: Comet 40-80kVA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1-2: Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1  
1-3: Single Line Diagram for the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . .1 — 2  
1-4: Single Line Diagram for the Comet 100-150kVA . . . . . . . . . . . . . . . . . . .1 — 2  
1-5: Front View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4  
1-6: Rear View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5  
1-7: Front View of the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6  
1-8: Front View of Communications Components for  
the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7  
1-9: Pinouts on the DB15 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10  
2-1: The Comet 100-150kVA on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2  
3-1: Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
3-2: Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1  
3-3: Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2  
3-4: Comet Front Panel GUI, Controls and Indicators . . . . . . . . . . . . . . . . . .3 — 3  
3-5: Output Current Overload Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7  
3-6: Output Power Overload Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7  
Tables  
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page  
1-1: Comet 40-150kVA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8  
1-2: UPS Manager Dry Contact Interface . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10  
2-1: Recommended upstream protective device sizing * . . . . . . . . . . . . . . . .2 — 3  
MGE Warranty & Proprietary Rights for Three Phase Products  
MGE Standard Three Phase Warranty  
Proprietary Rights Statement  
Warranty and Product Registration  
User Information  
Product Information  
Warranty Extension (Warranty+)  
Customer Care Center - Three Phase Products  
Technical Support and Product Services  
Who to Contact  
Scheduling Field Service Engineer Support  
Return Policy for Repair of Three Phase Products (RGA)  
Glossary  
Reorder Form  
86-160310-00 E00  
Contents  
c iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
CAUTION: Record All Serial Numbers!  
RECORD ALL SERIAL NUMBERS FOR THE COMET UPS AND ACCESSORIES.  
THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.  
KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL  
NUMBERS IF SERVICE IS REQUIRED!  
UPS SERIAL NUMBER: _______________________________________________________  
BATTERY SERIAL NUMBER: ___________________________________________________  
ADDITIONAL MODULES SERIAL NUMBERS:  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
____________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
______________________________  
NOTES:  
c iv  
CAUTION: Record All Serial Numbers!  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
(This page left blank intentionally)  
86-160310-00 E00  
c v  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
Symbol Usage  
This manual uses five icon symbols with text to convey important information and tips.  
WARNING  
CAUTION  
Information provided to protect the user and service personnel against safety  
hazards and/or possible equipment damage.  
Information provided to protect the user and service personnel against possible  
equipment damage.  
ELECTRICAL Information provided to protect the user and service personnel against possible  
electrical hazard and equipment damage.  
IMPORTANT  
NOTE  
Information provided as an operating instruction, or as an operating tip.  
Information provided as an operating tip or an equipment feature.  
Section Descriptions  
1
System Description and Specifications  
Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,  
available options, and system specifications.  
2
Installation  
Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures;  
prerequisites to installation; installation procedures; and startup procedures.  
3
Operation  
Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on  
battery, and bypass operation, with descriptions of the control and display indicators.  
NOTE  
For details on the Graphical User Interface (GUI) display, please refer to  
manual 86-160316-00.  
4
Maintenance  
Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about  
replacement parts, and customer service.  
A Glossary provides definitions of abbreviations and terms used in this manual.  
NOTE  
This manual provides technical information required for operation and  
maintenance of the Comet 40-150kVA Uninterruptible Power System (UPS).  
Please read this manual before operating the Comet 40-150kVA equipment.  
Please retain this manual for future reference.  
c vi  
Symbol Usage and Section Descriptions  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Description and Specifications  
1.0  
1.1  
Scope  
Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,  
available options, and system specifications.  
General Description  
The Comet family consists of compact, high-efficiency Uninterruptible Power Systems which are available in power  
ratings from 40-150kVA, and are optimized for compatibility with nonlinear computer-type loads. Computer-aided  
UPS diagnostics and modular construction assure that any required service can be identified and completed rapidly.  
Remote system monitoring, remote annunciation of UPS performance signals and communication capabilities allow  
total control of the UPS by its user. See Figures 1-1 and 1-2.  
The Comet UPS and its auxiliary equipment are designed for installation in a room where humidity and temperature  
can be controlled. The recommended and maximum environmental parameters are listed in the Specifications  
section of this document.  
Figure 1-1: Comet 40-80kVA.  
Figure 1-2: Comet 100-150kVA.  
Setup  
Load  
Load Protected  
Alarms Battery  
0%  
Setup  
Load  
Inputs  
Main  
%
KVA  
Load  
Load Protected  
Aams Battery  
0%  
Inputs  
Main  
%
KVA  
Load  
KA2  
KA1  
UPS  
Input  
load  
KA2  
KA1  
K3N  
UPS  
Input  
load  
QF1  
K3N  
QF1  
Í
ı
ı
Í
EMERGENCY  
POWER OFF  
EMERGENCY  
POWER OFF  
fault  
fault  
COMET  
COMET  
M
G
E
M S  
U
P
S
S
Y
S
T
E
M
G
E
M S  
U
P
S
S
Y
S
T
E
86-160310-00 E00  
System Description and Specifications  
1 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
Figure 1-3, and 1-4 show single-line diagrams of a typical UPS system installation. During normal operation,  
utility power (Main Input) is supplied to the UPS Rectifier where it is converted to DC voltage. The Inverter  
converts the DC voltage from the Rectifier to three-phase regulated AC voltage, which supplies the critical load.  
During power failure conditions, the Inverter is supplied by the stored energy in the batteries, and the load is  
powered continuously with no disruption.  
Figure 1-3: Single Line Diagram for the Comet 40-80kVA.  
UPS CABINET  
STATIC SWITCH  
KA2  
BYPASS  
AC INPUT  
SR1  
(OPTIONAL)  
KA1  
K3N  
TO  
CRITICAL  
LOAD  
MAIN  
AC INPUT  
INPUT  
FUSES  
OUTPUT  
FUSES  
RECTIFIER  
INVERTER  
QF1  
BATTERY  
CABINET  
BATTERY  
Figure 1-4: Single Line Diagram for the Comet 100-150kVA.  
UPS CABINET  
STATIC SWITCH  
KA2  
BYPASS  
AC INPUT  
SR1  
KA1  
K3N  
TO  
CRITICAL  
LOAD  
MAIN  
AC INPUT  
INPUT  
FUSES  
OUTPUT  
FUSES  
RECTIFIER  
INVERTER  
QF1  
BATTERY  
CABINET  
BATTERY  
1 — 2  
System Description and Specifications  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.2  
Major Components  
The following is a description of the cabinets and major components. Refer to Figures 1-5 to 1-8.  
UPS Cabinet  
Converts the input AC power to direct current and charges the battery. DC power  
is converted back to clean AC power by the inverter for the critical load. Section  
3 describes the operation in detail.  
Auxiliary Cabinet  
Battery Cabinet  
Performs the voltage conversion for the input AC and/or bypass AC using step-  
up and/or step-down transformers.  
The battery cabinet stores energy for use by the Inverter. The stored energy is  
utilized in the event that the AC input power from the utility source fails, or falls  
outside of acceptable tolerances. The internal Battery Charger maintains the  
charge of the battery system. The DC output voltage of the charger is tempera-  
ture regulated to ensure an optimal charge voltage. If a customer supplied battery  
system is to be used, an external battery charger may be necessary.  
The standard battery system is housed in a separate enclosure. For systems where  
additional back-up time is required, up to two (2) additional battery cabinets are  
available.  
A standard battery cabinet is available in an adjacent configuration or a stand-  
alone configuration. Adjacent battery cabinets are attached to the right side of the  
UPS using c-brackets provided with the cabinet. Stand-alone battery cabinets  
are remote from the UPS. Refer to the battery cabinet installation drawing for  
more details. An external battery system can also be supplied by the customer.  
Rectifier  
Inverter  
Converts the AC input voltage from the utility source into a DC voltage, supplying  
the Inverter.  
Converts the DC voltage supplied from either the Rectifier or the battery system into  
a three-phase AC voltage. An AC output filter is used to achieve a computer-grade  
sinewave output voltage waveform, with a total harmonic distortion of less than 2%  
under linear-load conditions.  
Static Switch  
Transfers the load between the Inverter output and the bypass AC source without  
interrupting the supply of power to the load, allowing the load to continue  
operation in the event of a UPS fault. The Static Switch circuit assures that  
voltage from the UPS output cannot be fed back to the utility input lines.  
Battery System  
Stores energy for use by the Inverter. The stored energy is utilized in the event  
that the AC input power from the utility source fails, or falls outside of acceptable  
tolerances. The internal Battery Charger maintains the charge of the battery  
system. The DC output voltage of the charger is temperature regulated to ensure  
an optimal charge voltage. If a customer supplied battery system is to be used,  
an external battery charger may be necessary.  
86-160310-00 E00  
System Description and Specifications  
1 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
Figure 1-5: Front View of the Comet 40-80kVA.  
1
2
(KA1) Input Contactor  
(K3N) Output Contactor  
3
(KA2) Bypass Input Contactor (Optional)  
(F1, F2, F3) Input Fuses  
(F4, F5, F6) Output Fuses  
(SR1) Rotary Switch  
4
5
6
7
Rectifier/Static Switch Assembly  
Inverter Assembly  
8
9
Feedback PCA  
10  
11  
12  
13  
14  
15  
16  
17  
DC Power Supply PCA  
Interconnect PCA  
High-Frequency Power Supply PCA  
(FU1-FU6) Power Supply Fuses  
Teleservice Receptacles (J1-J2) & Fuse (FU13)  
Heatsink Cooling Fans  
(TB3) Separate Bypass Input Terminal Block  
Battery Connections  
18  
19  
(TB1) Main Input Terminal Block  
(TB2) Output Terminal Block  
(SR2) Fan Control Switch  
(FU7-FU12) Fan and Teleservice Fuses  
Ground Busbar  
20  
21  
22  
23  
24  
25  
DETAIL BEHIND ITEM 25  
A
Neutral Busbar  
01  
Bottom of Top-Entry Channel  
Battery Charger  
04  
05  
02  
1 — 4  
System Description and Specifications  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 1-6: Rear View of the Comet 40-80kVA.  
TOP ENTRY  
CONDUIT LANDING  
TOP ENTRY  
CHANNEL  
T1 INPUT  
TRANSFORMER  
(OPTIONAL)  
T2 OUTPUT  
TRANSFORMER  
(OPTIONAL)  
86-160310-00 E00  
System Description and Specifications  
1 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
Figure 1-7: Front View of the Comet 100-150kVA.  
1
2
(KA1) Input Contactor  
(K3N) Output Contactor  
(KA2) Bypass Input  
(F1, F2, F3) Input Fuses  
(F4, F5, F6) Output Fuses  
(SR1) Rotary Switch  
Rectifier  
3
4
5
6
7
8
Static Switch  
9
Inverter Assembly  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
Chopper Assembly  
Interconnect PCA  
Ground Busbar  
Neutral Busbar (option)  
Charger PCA  
Heatsink Cooling Fans  
DC Cap Modules  
(TB5) Control Terminal Block  
(FU1-FU21) Control Fuses  
Power Supplies Assembly  
1 — 6  
System Description and Specifications  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 1-8: Front View of Communications Components for the Comet 100-150kVA.  
TOP CONDUIT LANDING FOR  
CABLE ACCESS TO PCA'S  
COMMUNICATION  
PCAs  
BOTTOM CONDUIT LANDING  
86-160310-00 E00  
System Description and Specifications  
1 — 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
1.3  
Specifications  
The Comet 40-150kVA UPS systems are rated for various input and output voltages (see Table 1-1). When  
different input and/or output voltages are specified, optional transformers provide step up/down functions as  
required.  
Table 1-1: Comet 40-150kVA Specifications.  
INPUT  
INPUT  
OUTPUT OUTPUT  
CURRENT  
(on UPS/  
TOTAL  
WIDTH  
(in/mm)  
NET  
WEIGHT  
(lb/kg)  
HEAT  
LOSS  
(Btu/hr  
VOLTAGE VOLTAGE CURRENT  
(VAC)  
(VAC)  
(Amperes)  
on bypass)  
)
(Amperes)  
40kVA/32 kW  
50kVA/40 kW  
65kVA/52 kW  
80kVA/64 kW  
100kVA/80 kW  
208  
220  
480  
480  
600  
208  
220  
480  
480  
600  
208  
220  
480  
480  
600  
208  
220  
480  
480  
600  
208  
220  
480  
480  
600  
600  
208  
220  
208  
480  
208  
208  
220  
208  
480  
208  
208  
220  
208  
480  
208  
208  
220  
208  
480  
208  
208  
220  
208  
480  
600  
208  
208  
220  
208  
480  
600  
208  
208  
220  
208  
480  
600  
208  
111  
105  
111  
48  
102/111  
96/105  
43/111  
32.75/832  
32.75/832  
32.75/832  
32.75/832  
60.00/1524  
32.75/832  
32.75/832  
32.75/832  
32.75/832  
60.00/1524  
32.75/832  
32.75/832  
32.75/832  
32.75/832  
60.00/1524  
32.75/832  
32.75/832  
32.75/832  
32.75/832  
60.00/1524  
69.50/1765  
69.50/1765  
42.75/1086  
42.75/1086  
96.00/2438  
69.50/1765  
69.50/1765  
69.50/1765  
42.75/1086  
42.75/1086  
96.00/2438  
69.50/1765  
69.50/1765  
69.50/1765  
42.75/1086  
42.75/1086  
69.50/1765  
96.00/2438  
1760/800  
1760/800  
1360/617  
880/400  
13500  
13500  
12135  
8220  
43/48  
111  
139  
131  
139  
60  
35/111  
2820/1279  
1760/800  
1760/800  
1360/617  
880/400  
13500  
16873  
16873  
15169  
10276  
16873  
17552  
17552  
15433  
11328  
17552  
21603  
21603  
21603  
13992  
21603  
28300  
28300  
22278  
15420  
28300  
28300  
38247  
38247  
30662  
20804  
38247  
38247  
50759  
50759  
41560  
26351  
50759  
50759  
127/139  
120/131  
54/139  
54/60  
139  
180  
170  
180  
78  
44/139  
162/180  
153/170  
70/180  
70/78  
2820/1279  
2115/960  
2115/960  
1590/721  
970/440  
180  
222  
210  
222  
96  
57/180  
200/222  
190/210  
86/222  
86/96  
2910/1320  
2115/960  
2115/960  
1590/721  
970/440  
222  
278  
263  
278  
120  
96  
70/222  
256/278  
242/263  
109/278  
109/120  
89/96  
2910/1320  
3400/1543  
3400/1543  
2450/1112  
1460/662  
3700/1678  
3400/1543  
3400/1543  
3400/1543  
2450/1112  
1460/662  
3700/1678  
3400/1543  
3400/1543  
3400/1543  
2450/1112  
1460/662  
3700/1678  
3400/1543  
278  
347  
328  
347  
150  
120  
347  
417  
394  
417  
180  
145  
417  
91/278  
316/347  
298/328  
134/347  
134/150  
109/120  
109/347  
378/417  
375/394  
160/417  
160/180  
131/145  
131/417  
125kVA/100 kW 208  
220  
480  
480  
600  
600  
150kVA/120 kW 208  
220  
480  
480  
600  
600  
(See notes that follow)  
1 — 8  
System Description and Specifications  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
NOTES:  
1. Total width, weight, and heat loss are for system line-up excluding battery cabinets.  
2. Data does not include battery data; refer to the installation drawings supplied with your equipment.  
Consult the installation drawings provided with your equipment.  
1.3.1  
AC Input Ratings  
Voltage  
480 VAC, + 12%, -15%  
Frequency  
Phases  
60 Hz 4%  
3 Ø (phase sequence must be A, B, C, clockwise)  
3 wires plus ground (480-480 VAC only)  
Approximately 0.98 at full load  
Wires  
Power factor  
Current (on UPS/ on BYPASS) @ 480 VAC  
40kVA  
50kVA  
65kVA  
80kVA  
100kVA  
125kVA  
150kVA  
43A/48A  
54A/60A  
70A/78A  
86A/96A  
109A/120A  
134A/150A  
160A/180A  
1.3.2  
AC Output Ratings  
Voltage (inverter only)  
480 1% VAC (steady-state conditions)  
480 5% VAC (transient conditions from 0% to 100% or 100% to 0%)  
Frequency  
Phases  
60 Hz 0.1% (free-running)  
3 Ø (phase sequence must be A, B, C, clockwise)  
Wires  
3 wires plus ground (480-480 VAC only)  
0.8  
Power factor  
Current @ 480 VAC  
40kVA  
50kVA  
65kVA  
78A  
80kVA  
96A  
100kVA  
120A  
125kVA  
150A  
150kVA  
180A  
48A  
60A  
Total harmonic  
distortion (THD)  
<2% (linear load)  
<3% (for 100% non-linear load with a crest factor of less than 3.0)  
Dynamic regulation  
1% for balanced load  
2.5% for 100% unbalanced load  
Dynamic response  
Overload  
5% for 100% step load change  
105% - 110% of rated current for 10 minutes  
>110% - 130% of rated current for 1 minute  
>130% - 150% of rated current for 10 seconds  
>150% of rated current for 0.15 seconds  
1.3.3  
DC Ratings  
Battery voltage (25° C)  
float:  
nominal:  
minimum:  
490 Vdc  
432 Vdc  
360 Vdc  
Maximum Current at cut-off voltage  
40kVA  
50kVA  
65kVA  
154 ADC  
80kVA  
100kVA  
235 ADC  
125kVA  
150kVA  
96 ADC  
120 ADC  
189 ADC  
294 ADC  
353 ADC  
86-160310-00 E00  
System Description and Specifications  
1 — 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
1.3.4  
Mechanical Specifications (UPS Cabinet Only)  
Height  
Width  
Depth  
66.70 in/1694 mm  
32.75 in/832 mm  
33.42 in/823 mm  
Weight at 480 VAC in and 480 VAC out  
40/50kVA  
65/80kVA  
100-150kVA  
880 lbs/400 kg  
970 lbs/440 kg  
1460 lbs/662 kg  
1.3.5  
Environmental Specifications  
Temperature  
Operating:  
0° C to 30° C (32° F to 86° F) continuous  
15°C(60°F) to <25° C (<77° F) recommended  
40° C (104° F) up to 8 hrs at 75% load  
Non-operating  
and storage:  
-30° C to 70° C (-22° F to 158° F)  
Humidity  
Altitude  
0 to 95% non-condensing  
<3000 ft. (1000m), up to 6000 ft. (<2000 m) @ 28° C (82°F) maximum  
1.3.6  
DB15 Connector Pinouts and Designations  
The UPS Manager connector enables communication with the most common computer systems (AS/400,  
NOVELL, etc.), or with the optional "UPS Manager UM1" software.  
Table 1-2: UPS Manager Dry Contact Interface.  
UPS Manager Dry Contact Interface (DB15)  
Operation on Inverter  
Softunor (DB9)  
Diagnostics (for MGE Customer Care Center use only)  
Operation on Bypass  
Operation on Battery  
Low Battery Shutdown Warning  
UPS Remote Inverter Shutdown  
Figure 1-9: Pinouts on the DB15 Connector.  
DB15 -pin  
connector  
5
PIJO PC board  
Operation on Inverter  
NO  
NC  
8
Operation on  
Bypass  
NO  
NC  
Breaking  
6
capacity of  
contacts is:  
P = 3va  
V = 30VDC max.  
I = 100mA max.  
10  
8
7
6
5
4
3
2
1
NO  
NC  
9
Operation on Battery  
11  
15 14 13 12 11 10  
9
13  
Low Battery Shutdown Warning  
7
NO  
NC  
12  
14  
UPS Remote Inverter Shutdown  
(3 to 15 VDC voltage signal)  
4
1
GROUND  
Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the  
load transfers to bypass after a predetermined time (typically 2 minutes).  
1 — 10  
System Description and Specifications  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
1.4  
Options and Accessories  
Options are available for the Comet 40-150kVA UPS’s. Most options must be specified at the time of the original  
order for factory installation. Some options can be field installed; contact your MGE Sales Representative for  
further information.  
Auxiliary Cabinet  
The auxiliary cabinet may provide one or both of the following options: an input  
bypass step up/down transformer, and an output distribution panel. An output  
distribution panel provides connection points for distribution of AC power to  
computers and other equipment. Also available are external maintenance bypass  
cabinets.  
Extended Battery Cabinets Up to two Extended Battery Cabinets are available to provide extra back-up time  
during power outage.  
1.4.1  
UPS Options  
These options are internal to the Comet.  
Isolated Redundant System This option is used to connect the static switch and maintenance bypass to a  
reserve UPS source for redundancy  
UPS without Standard  
Battery Subsystem  
(External Batteries)  
This option allows for the connection of a customer-supplied battery system to  
the UPS.  
Communication Options  
Communication options may be used simultaneously on the Comet, thus  
enabling communication with a wide number of computers and control devices.  
Monitor Plus  
Contact 5  
Mini terminal for control and display of system parameters. This option can be in-  
stalled locally or remotely.  
This option offers communication of five different signals via dry relay contacts:  
Load on UPS  
Load on Bypass  
Operation on Battery  
Low Battery Shutdown Warning  
Summary Alarm (major or minor faults)  
U-Talk  
This option manages an RS232 serial interface using an ASCII protocol.  
This option enables remote monitoring of the Comet.  
JBUS/RS485  
1.4.2  
Software and Communication Package  
Solution-Pac  
Automatic file shutdown during power outage or severe brownout for stand-  
alone systems.  
Automatic file shutdown for network servers plus additional monitoring and  
network communication functions.  
Automatic file shutdown with user-friendly control panel and advanced  
decision-making functions for Windows. This package includes an easy to  
use load.  
86-160310-00 E00  
System Description and Specifications  
1 — 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMET 40-150kVA  
1 — 12  
Chaptername  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
(This page left blank intentionally)  
1 — 13  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
2.0  
Scope  
Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures; prerequisites  
to installation; installation procedures; and startup procedures.  
CAUTION  
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10  
days before they are required on-site. If the startup of the product is critical to  
maintaining your schedule, please call the MGE toll free telephone number at  
1-800-438-7373 for assistance.  
2.1  
Receiving  
Before accepting the shipment from the freight carrier, inspect the exterior surfaces of shipping container(s),  
packaging, and equipment for damage that may have occurred during transit. If the shipping containers or  
equipment show evidence of damage, note the damage on the receiving document (bill of lading) prior to  
signing for receipt of equipment. Verify that the equipment nameplate corresponds with the equipment ordered.  
Damage claims should be filed directly with the carrier. Replacements for damaged components can be ordered  
by calling 1-800-438-7373.  
2.2  
Handling  
Any equipment shipped on a shipping pallet is intended for handling by a pallet jack or a fork lift truck. Move  
the equipment to its intended location while still mounted on its pallet, and remove the equipment from the pallet  
when it is near its final location. See Figure 2-1.  
The Comet UPS and optional auxiliary cabinets have heavy-duty casters to allow the equipment to be moved  
into position easily once they have been unloaded from the shipping truck. Once the UPS is in its final position,  
the leveling jacks on all four-bottom corners should be lowered to secure the cabinet in place. Refer to the  
installation drawings that were shipped with the cabinets.  
Battery cabinet weighing less than 3000 lbs. are equipped with casters for ease of handling on site. For  
shipment, these cabinets are mounted on pallets to prevent movement on ramps and other inclined surfaces.  
A forklift (4000 lbs capacity or greater) is required to remove the battery cabinet from its pallet. The 42" battery  
cabinets should be lifted from the side only. For battery cabinets weighing more than 3000 lbs., no casters are  
provided, and therefore must be moved by forklift only.  
86-160310-00 E00  
Installation  
2 — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
If the equipment is to be stored for more than three months before installation, it should be unpacked and  
connected to an AC input source to allow the batteries to be recharged. Refer to the installation instructions that  
follow, and the installation drawings.  
Figure 2-1: The Comet 100-150kVA on Pallet.  
2.3  
Storage  
If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location  
that is protected against rain, splashing water, chemical agents, etc. The equipment should be covered with a  
tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.  
IMPORTANT  
Batteries should be stored no longer than three (3) months at approximately 25°C  
(77° F) prior to recharging. Too high or too low a temperature will damage batteries.  
Exceeding the recommended ambient storage temperature will reduce back-up time  
and may adversely affect life.  
2.4  
Prerequisite to Installation  
This section provides more information for a successful and efficient installation of the Comet 40-150kVA.  
Installation of equipment must be handled by skilled technicians and electrician's familiar with the requirements  
of high energy electrical equipment. The installation must comply with the requirements of the National  
Electrical Code (NEC, ANSI/NFPA 70, latest issue) and with local codes and requirements as applicable. We  
strongly recommend contracting MGE Customer Support Services for startup. Do not allow unqualified  
personnel to handle or operate the equipment.  
2.4.1  
Environmental  
The Comet 40-150kVA UPS is intended for use in an environment where control of temperature and humidity is  
provided. The maximum operating and recommended environmental parameters are provided in the Specifications  
section of this document.  
The Comet UPS generates heat and exhausts air through the top portion of its enclosure. Heat loss data is  
provided in Table 1-1.  
Consult the installation drawings provided with your equipment.  
2 — 2  
Installation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
2.4.2  
Mechanical  
The Comet UPS can be mounted on a raised computer room floor, or flush-mounted on a concrete floor. All  
floors must be level. On a raised floor, conduits can be run below the floor, with cut-outs made in the floor tiles  
as shown on the installation drawings.  
Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The  
Comet requires at least 36 inches top clearance for ventilation.  
2.4.3  
Electrical  
Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and  
upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70,  
latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the  
installation drawings supplied with the equipment. The Comet 480/480V UPS is not a separately-derived source.  
The Comet 208/208V UPS is a separately derived source. The neutral must be grounded on a separately derived  
source (like the Comet 208/208V UPS).  
CAUTION  
The customer supplied upstream protective device shall open in one cycle  
when 10 times the output rated current is applied or in the event of an output  
short circuit when the unit is working on “Static Switch.”  
Refer to the upstream circuit breaker manufacturer’s characteristic curves for  
proper trip settings.  
Table 2-1: Recommended upstream protective device sizing *.  
INPUT VOLTAGE  
40kVA  
150A  
150A  
70A  
50kVA  
175A  
175A  
80A  
65kVA  
225A  
225A  
100A  
80kVA  
300A  
300A  
125A  
100kVA  
350A  
125kVA  
450A  
150kVA  
500A  
208  
220  
480  
350A  
450A  
500A  
150A  
200A  
225A  
600  
60A  
70A  
80A  
100A  
125A  
150A  
200A  
* Size determined using nominal input currents.  
86-160310-00 E00  
Installation  
2 — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
2.5  
Installation Procedures  
The steps to be followed are:  
Placement of the UPS and associated equipment.  
Connection of input power, output power, and control cables.  
Installation of UPS equipment must be handled by skilled technicians and electrician's familiar with the special  
requirements of high-energy electrical equipment. We strongly recommend contracting MGE Customer Support  
Services for start-up of the installed Comet UPS system. Do not allow unqualified personnel to handle or  
operate the Comet UPS.  
Refer to the installation drawings for proper placement and connections of auxiliary cabinets.  
2.5.1  
Placement  
Move the Comet UPS, battery cabinets (if any), and auxiliary cabinets (if any), to their final location (see Figure  
2-2). For cabinets installed adjacent to each other, alignment is critical to properly install the mechanical and  
cable interconnections. Allow at least 36 inches clearance above all cabinets for maintenance and cooling.  
Figure 2-2: Placement of UPS and other Cabinets.  
For side and rear clearances,  
refer to each cabinet's  
installation drawing  
BATTERY  
AUX  
CAB  
UPS  
CABINET(s)  
36" recommended  
2.6  
Connections  
Electrical connections and cabinet interconnection will vary depending upon the configuration of your Comet  
UPS system. Refer to Figures 2-3 & 2-4 and to the installation drawings supplied with your equipment.  
CAUTION  
Before making any electrical connections, verify that all battery disconnect  
circuit breaker (QF1) are in the “off” position. Customer-supplied upstream  
protective devices and distribution circuits should be OFF.  
2.6.1  
Main AC Input  
The connections to be made are the three phases, and ground cables from the utility AC power source to the  
UPS. The main AC input cables are terminated at the "Main Input" Terminal Block (TB1) for 40-80kVA and the  
input busbars for 100-150kVA. Complete wiring instructions for your installation are provided on the installation  
drawings supplied with the equipment.  
2.6.2  
Bypass AC Input (Optional)  
The connections to be made are the three phases, and ground cables from the bypass AC input power source  
to the UPS. The bypass AC input cables are terminated at the "Bypass Input" Terminal Block (TB3) for 40-80kVA  
and the bypass busbars for 100-150kVA. This option provides a separate AC input source for bypass operation.  
2.6.3  
Remote Emergency Power Off (REPO)  
The control connections are available for "Remote Emergency Power Off" (REPO) through a customer-supplied  
normally closed pushbutton. With REPO connected, the jumper on the "REPO" terminal blocks must be removed.  
2 — 4  
Installation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
2.6.4  
AC Output  
The connections to be made are the three phases, and ground cables from the load source to the UPS. The  
output cables are terminated at the Output Terminal Block (TB2) for 40-80kVA, and the output busbars for 100-  
150kVA.  
Load cables must be run separately from all other cables (power supply or computer-system interconnection  
cables). They should not pass near interference-emitting equipment or sensitive loads.  
2.6.5  
Battery  
The connections to be made are the positive, negative, and ground cables from the battery cabinet to the UPS.  
These are terminated at the appropriate connections in the UPS cabinet (see Figures 2-3 and 2-4). Additionally,  
control wires and temperature sensors in the battery cabinet must be terminated. Refer to the battery cabinet  
installation drawings for more details.  
Figure 2-3: Connections for Comet 40-80kVA UPS.  
Separate Bypass  
Input Terminal  
Block TB3  
Main Input  
Terminal Block  
TB1  
Output  
Terminal Block  
TB2  
Fan Control  
Switch  
Fan and  
Teleservice Fuses  
FU7-FU12  
Battery  
Connections  
SR2  
(Optional)  
Ground Busbar  
Neutral Busbar  
Figure 2-4: Connections for Comet 100-150kVA UPS.  
OUTPUT  
C4  
B4  
A4  
OPT  
C5  
B5  
A5  
-
+
BYPASS  
INPUT  
C3  
B3  
A3  
BATT.  
86-160310-00 E00  
Installation  
2 — 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMET 40-150kVA  
2 — 6  
Chaptername  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
(This page left blank intentionally)  
2 — 7  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
3.0  
3.1  
Scope  
Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on battery,  
and bypass operation, with descriptions of the control and display indicators.  
Power Flow  
3.1.1  
Power Flow, For Normal Operation  
During normal operation the AC input source supplies the Rectifier, which converts the incoming AC power to  
DC. The rectifier in turn supplies the Inverter, which converts DC power to AC to supply the attached load (see  
Figure 3-1).  
Figure 3-1: Power Flow, For Normal Operation.  
STATIC SWITCH  
BYPASS  
INPUT  
(OPTIONAL)  
RECTIFIER  
INVERTER  
MAIN  
INPUT  
TO LOAD  
BATTERY  
3.1.2  
Power Flow, For On Battery Operation  
When AC input power fails, the UPS goes to on-battery operation. DC power is supplied from the UPS battery  
system to the inverter, which converts battery power (DC) to AC power to supply the attached load (see Figure  
3-2).  
Figure 3-2: Power Flow, For On Battery Operation.  
STATIC SWITCH  
BYPASS  
INPUT  
(OPTIONAL)  
RECTIFIER  
INVERTER  
MAIN  
INPUT  
TO LOAD  
BATTERY  
86-160310-00 E00  
Operation  
3 —1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
3.1.3  
Power Flow, For Bypass Operation  
Should there be an internal fault in the UPS, the load will automatically be transferred to the "Static Switch".  
(If bypass AC input is within tolerance). The load is supplied without interruption while the UPS is bypassed (see  
Figure 3-3).  
Figure 3-3: Power Flow, For Bypass Operation.  
STATIC SWITCH  
BYPASS  
INPUT  
(OPTIONAL)  
RECTIFIER  
INVERTER  
MAIN  
INPUT  
TO LOAD  
BATTERY  
3.2  
Graphical User Interface, Controls and Indicators  
The Graphical User Interface (GUI) display, controls and indicators are located on the front panel in the upper  
left-hand corner of the Comet UPS, and consist of the following: (See Figure 3-4 for arrangement.)  
A Graphical User Interface (GUI) display.  
An alert buzzer.  
Four (4) LED's which indicate the overall operating status of the UPS.  
An “Inverter ON”, an “Inverter OFF”, and an “EPO” pushbutton.  
Three (3) control keys.  
The basic Comet indications consist of the following:  
Normal operation (load protected)  
Battery power is not available (load not protected)  
Downgraded operation (fault)  
Danger of a break in the supply of power to the load (load not protected)  
Operation on battery power  
When the buzzer is activated it will provide an audible warning to the operator by sounding a pulsed “beep”  
when any of the following conditions occur:  
The load is supplied directly by AC input power via the "Static Switch".  
The Inverter is operating on battery power.  
Any operating faults or change in operating status.  
It beeps softly and slowly for minor faults and during Inverter operation on battery power. When the low battery  
shutdown warning level has been reached, the sound volume and the frequency of the beeps increase.  
In the event of an Inverter shutdown, a continuous alarm is emitted. A buzzer reset key is provided on the front  
panel. Detection of a new fault will reactivate the buzzer.  
3 —2  
Operation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Figure 3-4: Comet Front Panel GUI, Controls and Indicators.  
1
Setup  
Load  
Load Protected  
Alarms Battery  
0%  
% KVA  
Load  
Inputs  
Main  
KA2  
KA1  
UPS  
Input  
load  
K3N  
QF1  
3
5
7
8
Í
ı
2
EMERGENCY  
POWER OFF  
4
6
9
11  
fault  
10  
7
8
1
2
3
4
5
6
Inverter ON (green) pushbutton  
Inverter OFF (gray) pushbutton  
Fault Reset Key  
Graphical User Interface (GUI) Display  
Emergency Power Off Switch  
Load Not Protected (red) LED  
Fault (yellow) LED  
9
10  
11  
Security Key  
Buzzer Reset Key  
Battery Status (yellow) LED  
Load Protected (green) LED  
NOTE  
For details on the Graphical User Interface (GUI) display, please refer to  
manual 86-160316-00.  
86-160310-00 E00  
Operation  
3 —3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
Graphical User  
Interface Display  
This display provides specific information concerning normal UPS operation as  
well as faults.  
Emergency Power Off  
This red Emergency Power Off (EPO) pushbutton is used to stop the unit during  
an emergency situation only. All power is removed from the load.  
Load not protected LED  
This red LED turns on when any of these conditions occur:  
Direct supply of power to the load by AC input power via the "Static Switch"  
because of Inverter shutdown (voluntary or following an overload or an  
internal fault).  
Battery power is not available. Battery circuit breaker is in the "OFF" position  
or battery not connected.  
Fault LED  
This yellow LED indicates an operating fault or an environmental fault. However,  
the load continues to be supplied by the Inverter.  
Battery Status LED  
This yellow LED indicates:  
Inverter operation on battery power following an AC input failure or detection  
of an AC input voltage outside of tolerances.  
It flashes to indicate that the low battery shutdown warning level has been  
reached.  
If the LED flashes when the system is not on battery power, battery  
conditions should be checked.  
Load protected LED  
This green LED indicates that the Comet is operating normally. The load is  
protected and supplied via the Inverter output. Bypass Switch SR1 must be in the  
"NORMAL" position.  
Inverter on  
Inverter off  
This green pushbutton is used to start the inverter.  
This gray pushbutton is used to stop the inverter.  
Fault Reset  
This key clears the faults stored in memory. Clearing of alarms in memory is  
accepted only after the alarm conditions themselves have been corrected.  
Security Key  
Buzzer Reset  
This key enables forced operation. The security key must be held down while the  
desired function is executed. Refer to the Forced Transfer section.  
This key allows the user to silence the buzzer after a particular alarm. However,  
the buzzer will sound if another alarm occurs.  
3 —4  
Operation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.3  
Startup Procedures  
3.3.1  
Preliminary Checks  
Check the settings of the protection devices.  
Verify that the battery circuit breaker(s) are in the "OFF" position.  
Verify that the Manual Bypass Switch SR1 is set to the “NORMAL” position.  
Verify that the fan switch (SR2) is set to the “ON” position.  
Check that the ventilation system is not blocked (air entry through the bottom front and exhaust through the top).  
Check that there is a minimum of 36 inches clearance at the front and top for ventilation.  
Check that the Comet no longer rests on its 4 wheels (lifting levelers in place).  
Check that the load-circuit breaker(s) (where applicable) are in the "OFF" position.  
3.3.2  
Powering Up the Comet  
CAUTION  
As soon as AC input power is supplied to the Comet (customer supplied up-  
stream circuit breaker is in the “ON” position), the load is initially supplied  
via the “Static Switch.” The Graphical User Interface (GUI) display will begin  
to startup.  
Apply AC input power to the unit by closing the upstream circuit breaker.  
Put the battery circuit breaker(s) in the “ON” position.  
The buzzer sounds.  
The status LED's go on.  
The rectifier starts up.  
The cooling fans startup.  
The inverter automatically starts up, except if the system is in “manual startup” mode (optional).  
If the transfer conditions (AC input power within tolerances) are correct, the Inverter comes on line and supplies  
the load. The green "Load Protected" LED goes on.  
3.4  
Inverter Manual Startup  
Typically, the Inverter is configured for automatic startup mode. For manual startup mode configuration, contact  
MGE Customer Support Services.  
For manual startup:  
Press the green "Inverter ON" pushbutton.  
The green "Load Protected" LED flashes.  
The Inverter starts and if the transfer conditions are correct, the load is transferred to the Inverter.  
The red "Load Not Protected" LED goes off.  
The green "Load Protected" LED goes on.  
The GUI display indicates Load Protected.  
86-160310-00 E00  
Operation  
3 —5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
3.5  
Operating Procedures  
3.5.1  
Normal Operation  
The AC input power is present.  
The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.  
The power drawn by the load is supplied by AC input power via the Rectifier and Inverter modules. The Battery  
Charger float charges or recharges the battery.  
The GUI display indicates “Load Protected”.  
3.5.2  
Operation on Battery Power  
When AC input power fails or is out of tolerance, the Rectifier shuts down and the battery supplies the power  
required by the Inverter to supply the load. The battery discharges.  
The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.  
The user is warned of operation on battery power by the buzzer and by the yellow "Battery Status" LED. This  
information is also available via the standard UPS MANAGER DB15 connector.  
3.5.3  
Battery Duration  
During an AC input power failure, the duration of Inverter operation on battery power depends on:  
The rated capacity of the battery.  
The power drawn by the load.  
The battery temperature.  
The charge level of the battery.  
The age of the battery.  
The real backup time, which depends on the actual load, may be greater if the Inverter operates at less than  
full rated load. It is possible, during operation on battery power, to increase the battery backup time by reducing  
the power drawn by the load (shedding of non-priority load).  
A low battery shutdown warning signal is available via the standard UPS MANAGER DB15 connector for remote  
indications. It warns the user of upcoming battery shutdown at a user-determined level of remaining power.  
On the UPS itself, the buzzer beeps louder and more rapidly, and the yellow "Battery Status" LED flashes  
rapidly.  
The end of battery power occurs when the battery reaches shutdown level. At this point, the Inverter shuts down  
and the UPS goes into "Stand-By" mode. Load is no longer supported. If the input AC power does not return to  
within tolerance within approximately 2 hours, the unit will shutdown.  
Once input AC power returns, the batteries begin their charging cycle. It takes approximately 10 hours of online  
operation to restore 10 minutes of backup time.  
3.5.3.1 Return to AC Power  
When the AC input power failure ends or power returns to within tolerances:  
If the end of battery backup power was not reached, the Comet returns to normal operating mode.  
If the end of battery backup power was reached and unit is in "Standby" mode, the Rectifier and the Inverter  
automatically start up (the inverter must be manually started if the system is in manual startup mode).  
If the end of "Stand-By" mode was reached, follow the Startup procedure.  
3 —6  
Operation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
3.5.4  
Overload  
When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal  
mode of operation is automatic, following elimination of the overload.  
The Inverter can handle a continuous overload for a given duration depending on the size of the output current  
overload (see Figure 3-5) or the output power overload (see Figure 3-6).  
When an overload occurs:  
The buzzer sounds.  
The yellow "Fault" LED goes on.  
The Inverter shuts down at the end of its corresponding overload time.  
The load is supplied by AC input power via the "Static Switch".  
The green "Load Protected" LED goes off.  
The red "Load Not Protected" LED goes on.  
The operating status of the UPS is provided by the GUI display. If the overload continues during operation via  
the "Static Switch", the supply of power to the load is interrupted after a specified time.  
When the Comet shuts down because of a continuous overload, the "Fault Reset" key must be pressed prior to  
return to normal operation and after elimination of the overload.  
Figure 3-5: Output Current Overload Curve.  
time  
10 mn  
1 mn  
10 s  
1 s  
rated load  
current  
0.15 s  
1.3  
1.9  
I (A)  
1.5  
1.05 1.1  
1.7  
3
Figure 3-6: Output Power Overload Curve.  
time  
1 mn  
10 s  
1 s  
rated load  
power  
0.3 s  
1.3  
1.1  
1.9  
1.5  
1.7  
2
P (kw)  
86-160310-00 E00  
Operation  
3 —7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
3.6  
Emergency Shutdown Using EPO/REPO  
CAUTION  
Pressing the “Emergency Power Off” (EPO) or “Remote Emergency Power Off”  
(REPO) pushbutton disconnects the attached load. The EPO is to be used during  
emergency situations only, where a hazard to personnel or equipment exists, such  
as during a fire. DO NOT USE THE EPO TO TURN THE UPS ON OR OFF.  
Follow the procedures listed in this section for turning the Inverter on and off.  
During an emergency situation, such as a fire in the computer or electrical room, the UPS and all downstream  
devices can be instantly shut down by pressing the EPO pushbutton on the front panel of the UPS cabinet, or  
by pressing the "Remote Emergency Power Off" (REPO) optional pushbutton.  
The EPO or REPO pushbuttons should not be used for normal shutdown of the equipment.  
If the EPO pushbutton has been pressed, it must be reset by pressing it again and by pressing the "Fault Reset"  
key on the front panel to allow the UPS to restart.  
3.7  
Forced Transfer  
CAUTION  
Using the forced transfer functions will cause the load to experience a power  
interruption for a minimum of 500 milliseconds. Be certain that the load can  
tolerate this interruption.  
Forced transfer is required if bypass input is out of tolerance. The load can be transferred from the Inverter  
output to the bypass input source, or back, with a power interruption of 500 milliseconds.  
Transferring the Load to Bypass Input From Inverter  
On the front panel, press the "Security" key and hold it while pressing the gray "Inverter OFF" pushbutton for 3  
seconds.  
Transferring the Load to Inverter From Bypass Input  
On the front panel, press the "Security" key and hold it while pressing the green "Inverter ON" pushbutton for 3  
seconds.  
3.8  
Maintenance Bypass  
This procedure assumes that the UPS is operating normally, with the attached load supplied via the Inverter.  
3.8.1  
From Normal Maintenance Bypass Mode  
1. Stop the Inverter by pressing the gray "Inverter OFF" pushbutton on the UPS front panel for approximately three  
(3) seconds. The audible alarm will sound; silence the alarm by pressing the "Buzzer Reset" pushbutton. If the  
transfer conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.  
Refer to the "Forced Transfers" section for more information.  
2. Switch the battery circuit breaker QF1 to the "OFF" position.  
NOTE  
The battery circuit breaker QF1 will automatically trip open if left in the “ON”  
position when the UPS is placed in the Maintenance Bypass mode.  
3. Turn the manual bypass switch to the "TRANSFER" position, then to the "BYPASS" position.  
4. All indicating LED's go off.  
3 —8  
Operation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
NOTE  
The cooling fans will remain operational when the UPS is placed on  
Maintenance Bypass mode to prevent the optional input/output transformers  
inside the UPS from overheating. If it is necessary to de-energize the fans,  
move the fan control switch (SR2) to the “OFF” position.  
CAUTION  
In this mode of operation, the UPS is ready for maintenance, but voltage is  
still present on terminal blocks and various internal components.  
Now the UPS is ready for maintenance.  
3.8.2 From Maintenance Bypass to Normal Mode  
WARNING  
Failure to follow the proper Startup sequence will result in load loss. After  
SR1 is set to “TRANSFER,” it takes the UPS five (5) to six (6) \seconds to test  
the input power before turning on the “Static Switch”. During this time, the  
load is still supplied by the Maintenance Bypass line, and moving SR1 to  
“NORMAL” will result in interruption of power to the load.  
1. Move the fan control switch (SR2) to the “ON” position if the cooling fans were de-energized during  
maintenance.  
2. Turn the manual bypass switch SR1 to the "TRANSFER" position.  
3. Wait for the GUI display to go on (at least 5 seconds).  
4. Turn the Inverter off by pressing the gray "Inverter OFF" pushbutton on the front panel for approximately  
3 seconds if your Comet has been programmed to automatically restart.  
CAUTION  
ALWAYS turn the Inverter off before rotating the Manual Bypass Switch (SR1).  
5. Close the battery disconnect circuit breaker(s) QF1.  
6. Turn the manual bypass switch SR1 to the "NORMAL" position.  
7. Turn the Inverter on by pressing the green “Inverter ON" pushbutton on the front panel. If the transfer  
conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.  
Refer to the "Forced Transfers" section for more information.  
Now the UPS is in normal operating mode. The green "Load Protected" LED is illuminated on the front panel,  
and the operating status of the UPS is provided by the GUI display.  
86-160310-00 E00  
Operation  
3 —9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
3.9  
Shutdown Procedures  
3.9.1  
Inverter Shutdown  
Press and hold the gray "Inverter OFF" pushbutton for 3 seconds.  
The green “Load Protected” LED goes off.  
The red “Load Not Protected” LED goes on.  
The buzzer sounds.  
The Inverter stops if the transfer conditions are correct.  
The load is transferred and supplied via the "Static Switch".  
3.9.2  
Powering Down  
It is recommended not to power down the Comet for long periods because the battery should remained charged.  
However, to carry out a power down, proceed as follows:  
Shut down the Inverter.  
Put the battery circuit breaker in the "OFF" position.  
Put the upstream main circuit breaker in the "OFF" position.  
All the indicating LED's on the control panel go off.  
3.10  
Alarms  
Any state other than normal operation (green “Load Protected” LED on) is considered a fault by the diagnostics  
system.  
Before undertaking any servicing or other action, note the status of the different LED's and the GUI messages  
displayed on the panel.  
If an alarm is present and the load still functions, it is supplied via the "Static Switch", i.e. it is not protected.  
Table 3-1: Alarm Indications.  
status or action producing the indication  
inverter start-up phase prior to loadꢀ  
transfer. The "inverter on" button has  
been pressed.  
normal operation;  
load supplied by Comet UPS  
(SR1 in normal position)  
beep  
beep  
inverter shutdown following pressing of theꢀ  
"inverter off" button or a major fault;  
load supplied via the "static switch"ꢀ  
beep  
beep  
operation on battery power;ꢀ  
load supplied by Comet UPS  
beep  
beep  
end of battery power or battery should beꢀ  
checked  
beep  
beep  
minor fault;ꢀ  
(load continues to be supplied via inverter)  
UPS shutdown;ꢀ  
load supplied via maintenance bypassꢀ  
Legend of alarm indications table:  
buzzer off,  
light off,  
beep  
beep  
buzzer on,  
light on,  
light flashing  
3 —10  
Operation  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
4.0  
4.1  
Scope  
Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about  
replacement parts, and customer service.  
Battery Safety  
IMPORTANT SAFETY INSTRUCTIONS FOR SERVICING BATTERIES  
A. Servicing of batteries should be performed or supervised by personnel knowledgeable with batteries and  
the required precautions. Keep unauthorized personnel away from batteries.  
B. When replacing batteries, use the same model and manufacturer of batteries.  
C. CAUTION — Do not dispose of battery or batteries in a fire. The battery may explode.  
D. CAUTION — Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin  
and eyes. It may be toxic.  
E. CAUTION — A battery can present a risk of electrical shock and high short-circuit current. The following  
precautions should be observed when working with batteries:  
1. Remove watches, rings, or other metal objects.  
2. Use tools with insulated handles.  
3. Wear rubber gloves and boots.  
4. Do not lay tools or metal parts on top of batteries.  
5. Disconnect charging source prior to connecting or disconnecting battery terminals.  
6. Determine if ground faults exists. If so, remove the source of ground. Contact with any part of a grounded  
battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are  
removed during installation and maintenance.  
4.2  
Preventive Maintenance  
The following preventive maintenance routines should be considered the minimum requirements; your  
installation and site may require additional preventive maintenance to assure optimal performance from your  
installed Comet UPS and associated equipment. These routines should be performed twice a year (more often  
if required). We strongly recommend contracting MGE Customer Support Services for preventive and remedial  
maintenance at 1-800-438-7373.  
The technician or electrician performing preventive maintenance on the UPS must be familiar with the  
indicators, controls, and operation of the UPS.  
a. Isolate and de-energize all Comet UPS equipment for all maintenance operations. Lock and tag all upstream  
circuit breaker(s) during maintenance.  
b. Ensure that all equipment is clean and free of dust, dirt, and debris. The exterior of the UPS enclosure may  
be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.  
c. Clean/replace the air intake filters, exhaust plates, and the enclosure interior with a vacuum cleaner.  
d. Initiate the startup procedure, as described in Section 3.  
e. Test the main operating sequences as applicable to your installation (see Section 3).  
86-160310-00 E00  
Maintenance  
4 —1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
4.3  
Replacement Parts  
There are no user serviceable parts inside the Comet UPS.  
Three levels of replacement parts are available for the Comet. The three levels are designated A, B, and C. The  
level that you should keep on hand for your installation will vary depending on the type of maintenance planned  
on site, and the configuration of your UPS system.  
Having the replacement parts on hand will prevent any unacceptable delays (because of time involved obtaining  
spares) during critical periods, such as system startup. Any items used during start-up will be replaced by MGE  
at no charge. Contact MGE Customer Care Center at 1-800-438-7373 for specific recommendations.  
A description of each level is provided below:  
Level Description  
A
B
This level of replacement parts consists of consumable items, specifically power and control fuses.  
It is recommended to have these items on hand during installation of the UPS systems, including initial startup.  
This level of replacement parts is recommended when the user can tolerate short-duration UPS down-time  
to obtain replacement parts in the event of a major UPS failure. This level of replacement parts consists of  
consumable items, specifically power and control fuses, fans, and the most critical circuit board assemblies.  
C
This level of replacement parts is recommended when the user can tolerate only a minimum of down-time in  
the event of a major UPS failure. This level of replacement parts consists of consumable items, specifically  
power and control fuses, fans, and a significant set of circuit board assemblies.  
4 —2  
Maintenance  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MGE Warranty & Proprietary Rights Statement for Three Phase Products  
(Applicable within the United States, Canada and Mexico)  
MGE Standard Three Phase Warranty  
MGE UPS SYSTEMS, INC. (“MGE”) warrants three phase products it manufactures to be free from defects in  
materials and workmanship for a period of three hundred sixty five (365) days counting from the date of purchase by  
or for the first end user (“Purchaser”), or, if applicable, the date of MGE’s completion of initial startup of the subject  
product, provided however said warranty shall not exceed eighteen (18) months from the date of delivery of the  
subject product to Purchaser (the “Warranty Period”). MGE’s liability hereunder is limited to replacing or repairing at  
MGE’s factory or on the job site, at MGE’s option, any part or parts that are defective and reported to MGE during  
the Warranty Period. MGE shall have the sole right to determine if the parts are to be repaired at the job site or  
whether they are to be returned to the factory for repair or replacement. All items returned to MGE for repair or  
replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE’s Return Goods Authorization  
(“RGA”) prior to returning items. The conditions stated herein must be met for MGE’s warranty to be valid. MGE will  
not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misappli-  
cation of the subject product, for damage due to accident, abuse, or act of God (such as earthquake, flood, inclement  
weather, rain or fire), or relating to Purchaser’s failure to follow proper environmental conditions for the product.  
In no event shall MGE be liable for loss, damage, or expense directly or indirectly arising from the use of or any  
defects in the subject product, or from any other cause, except as expressly stated in this warranty. EXCEPT AS  
EXPRESSLY STATED IN THIS WARRANTY, MGE UPS SYSTEMS, INC. MAKES NO WARRANTIES, EXPRESS OR  
IMPLIED, INCLUDING ANY WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR  
PURPOSE OR USE OR NON-INFRINGEMENT. MGE is not liable for and Purchaser waives any right of action it  
has or may have against MGE for any consequential or special damages arising out of any breach of warranty, and  
for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its  
purchase or the use, operation or maintenance of the subject product. The warranty stated herein includes parts and  
labor; however, MGE will not be liable for any labor subcontracted or performed by Purchaser for preparation of the  
warranted item for return to MGE’s factory or for preparation work for field repair or replacement, and MGE will not  
be responsible to pay any invoice therefore.  
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a  
writing signed by an authorized officer of MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser  
but to no one else. Accessories supplied by MGE, but manufactured by others, carry any warranty the manufactur-  
ers have made to MGE, and which can be passed on to Purchaser.  
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any  
patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent.  
Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any  
patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to  
Purchaser’s specific design.  
Purchaser has not relied and shall not rely on any oral representation regarding any products sold hereunder and  
any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.  
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS  
SYSTEMS, INC. be responsible for consequential damages or for any other damages except as expressly stated  
herein.  
Proprietary Rights Statement  
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in  
which MGE UPS SYSTEMS, INC. retains any and all intellectual property rights, including exclusive rights of use  
and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce,  
print, manufacture or have made the article or articles shown herein. Such permission may be granted only by  
specific written authorization signed by an authorized officer of MGE UPS SYSTEMS, INC.  
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and  
MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein  
are owned by their respective companies and are referred to in an editorial fashion only.  
For Three Phase Warranty outside of the United States, Canada and Mexico, refer to Three Phase International  
Warranty.  
January 2005 Rev C00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty and Product Registration  
Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality  
requirements. We are pleased to have you join our increasing family of users.  
In order to maximize the value you receive from this product, and to ensure that you are kept informed of  
product or software updates, we recommend that you take a few minutes to register your new purchase.  
You may register online at the URL noted below. Should you not have Internet access, you may mail or fax  
this form back (attn: Warranty Registration) as indicated at the bottom of the page.  
Please be prepared with the following information to register and validate your product’s warranty, keep  
informed on software and product updates, and register your extension "Warranty+" if purchased with the  
product.  
User Information  
Last name  
First name  
Company name  
Address  
Zip code  
City  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
________________________________________  
State/Province  
Country  
Tel  
Fax  
Email  
Product Information  
Model  
________________________________________  
________________________________________  
Serial Number  
Date of purchase ________________________________________  
Warranty Extension (Warranty+)  
I have purchased a warranty extension (Warranty+)  
Reference: _____________________ Contract Number: _________________  
Thank you from all of us at MGE.  
MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA  
Tel: 714-557-1636  
Fax: 714-557-9788  
41-000154-53 Rev B02 8/2005  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MGE Customer Care Center - Three Phase Products  
Technical Support and Product Services  
?
Technical questions? If you encounter a problem while following the instructions in this manual, or have  
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS SYSTEMS,  
To insure that your questions are correctly answered, please obtain the serial number of the unit and include  
them in any discussions or correspondence.  
Serial number:  
_____________________________________________________________________  
Who To Contact  
Customer Care Center:  
1-800-438-7373 (Hours: 24/7)  
Customer FAQ  
or International calls:  
1-714-557-1636  
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that  
will provide responses to any questions that you might have.  
Scheduling Field Service Engineer Support  
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required  
on-site. If the startup of the product is critical to maintaining your schedule, please call the MGE toll free  
telephone number at 1-800-438-7373 for assistance.  
Return Policy for Repair of Three Phase Products (RGA)  
Should you require factory service for your equipment, contact MGE Customer Care Center and obtain a Return  
Goods Authorization (RGA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RGA  
number.  
Date:  
______________________________________________________  
RGA Number: ______________________________________________________  
Contact Name: ______________________________________________________  
Rev B00 8/2005  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
(This page left blank intentionally)  
W—4  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary  
Term used  
Definition / Meaning  
@
/
At.  
And/or.  
+/-  
Plus or Minus.  
Equal to or less than.  
#
Number.  
°C  
°F  
Ø
Degree Celsius.  
Degree Fahrenheit.  
Phase angle.  
Ohm; unit of resistance.  
Trade Mark.  
®
2nd  
Second.  
AC or ac  
Alternating current, also implies root-mean-square (rms).  
Temperature of surrounding air.  
Acoustical noise of surrounding environment.  
American National Standard Institute.  
American Wire Gauge.  
Electrical circuit interrupter.  
Ambient Temp.  
Ambient noise  
ANSI  
AWG  
Breaker  
BTU or Btu  
British thermal unit. Defined as the amount of heat required to raise the tempera-  
ture of one pound of water by 1°F.  
BYPASS  
See “Static Transfer switch”.  
BYPASS mode  
See “off-line mode”.  
Carrier  
C
The company or individual responsible for delivering goods from one location to another.  
Common.  
CB  
Circuit breaker.  
cm  
Centimeter.  
CSA  
dB  
Canadian Standards Association.  
Decibels.  
DC  
Direct current.  
Conduit  
A flexible or rigid tube enclosing electrical conductors.  
86-160310-00 E00  
Glossary  
G — 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
C.S.S.  
Customer Support Service.  
Current rating  
dBA  
The maximum current that a conductor or equipment can carry reliably without damage.  
Decibel Adjusted.  
dBrnC  
Decibel above reference noise.  
DC or dc  
Digital Meter  
Earth ground  
ECO Mode  
Direct current, or voltage.  
The LCD display on the front panel of inverter system.  
A ground circuit that has contact with the earth.  
Operating mode by which the load is supplied directly by the AC source if it is within the  
tolerances defined by the user. This mode reduces the consumption of electrical power.  
Electrician  
Refers to an installation electrician qualified to install heavy-duty electrical components in  
accordance with local codes and regulations. Not necessarily qualified to maintain or repair  
electrical or electronic equipment.  
FCC  
FET  
Freq.  
Federal Communications Commission.  
Field effect transistor.  
Frequency.  
Frequency slew rate  
The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).  
Ground (safety).  
GND  
Hz  
Hertz, frequency measurement unit, 1Hz is one cycle per second.  
See “on-line” mode.  
Inverter mode  
I
Current.  
IEC  
International Electrotechnical Commission.  
IEEE  
Institute of Electrical and Electronic Engineers.  
The input circuit from the building power panel to the equipment.  
An electrical circuit that generates an AC voltage source from a DC voltage source.  
Input branch circuit  
Inverter  
IGBT  
I/O  
Insulated gate bipolar transistors.  
Input/Output.  
I/T or IT  
Information Technology.  
KiloVolt-Ampere; is equal to 1000 Volt-Ampere.  
Line.  
kVA  
L
LCD  
Liquid-Crystal Display unit.  
Light Emitting Diode.  
Main AC input source.  
Bypass AC input source.  
Milliampere.  
LED  
Mains or Mains 1  
Mains 2  
mA  
MAX.  
Maximum.  
MCM  
Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in  
diameter. M is from Roman numerical system indicating 1000.  
G — 2  
Glossary  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation and User Manual  
Module  
N
Refers to individual power inverter module.  
Neutral.  
NC  
Normally closed.  
NO  
Normally open.  
NEC  
NEMA  
NFPA  
National Electrical Code.  
National Electrical Manufacturers Association.  
National Fire Protection Association.  
PF  
PN  
Power factor.  
Part number.  
On-line mode  
Off-line mode  
Inverter output power is the primary energy source to load.  
Inverter output is off, and the load connected at the inverter output receives power  
from utility line via a static transfer switch or maintenance bypass relay.  
OSHA  
Occupational Safety and Health Agency.  
PCA  
PCB  
PWM  
SCR  
Printed circuit assembly.  
Printed circuit board.  
Pulse Width Modulation.  
Silicon controlled rectifier.  
Shipping damage  
SPDT  
Any damage done to an article while it is in transit.  
Single Pole Double Throw.  
Static Transfer  
An solid state switching mechanism electronically controlled to pass AC power  
directly from the utility to an output load.  
Technician  
Refers to an electronic technician qualified to maintain and repair electronic  
equipment. Not necessarily qualified to install electrical wiring.  
Test connector  
DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer  
Support Service technician to access programmable and diagnostic features of the  
system.  
UL  
UPS  
V
Underwriter's Laboratories, Inc.  
Uninterruptible Power Supply or Uninterruptible Power System.  
Volts  
VA  
VA  
Volt amperes  
Volt-amps, unit for apparent power measurement, equal V x I.  
VAC or Vac  
VDC or Vdc  
Voltage of AC type.  
Voltage of DC type.  
ve  
Battery voltage.  
By way of.  
Via  
86-160310-00 E00  
Glossary  
G — 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Comet 40-150kVA  
(This page left blank intentionally)  
G — 4  
86-160310-00 E00  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reorder Form  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
Use this form to report any errors, omissions, or other problems you have experienced, or to order additional  
hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web  
site. Please contact your MGE UPS SYSTEMS, INC. Representative for assistance.  
NAME ____________________________________________________________________________________  
COMPANY _________________________________________________________________________________  
STREET ADDRESS ___________________________________________________________________________  
CITY ________________________________________ STATE __________________ ZIP __________________  
I would like to order______ (quantity @ $75.00 each) additional copies of the:  
Comet 40-150kVA  
Installation and User Manual  
86-160310-00 E00  
I would like to report the following problems with this document:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
w w w. m g e u p s . c o m  
Contact MGE  
United States  
MGE UPS SYSTEMS  
1660 Scenic Ave.  
Costa Mesa, CA 92626  
Tel: (714) 557-1636  
CCC: (800) 438-7373  
Fax: (714) 557-9788  
www: mgeups.com  
Canada  
MGE UPS SYSTEMS  
#9, 2789 Thamesgate Drive  
Mississauga, ON L4T 4E8  
Tel: (905) 672-0990  
(877) 672-0990  
Fax: (905) 672-7667  
www: mgeups.com  
Latin America and  
Other International  
MGE UPS SYSTEMS  
1660 Scenic Ave.  
Costa Mesa, CA 92626  
Tel: (714) 513-7831  
Fax: (714) 434-0199  
www: mgeups.com  
1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LG Electronics Cell Phone 9250 User Manual
Lightolier Work Light 24MHT4RF User Manual
Linksys Network Card USBBT100 User Manual
Loewe Flat Panel Television 3781 ZW 3981 ZW 32 6381 ZW 5381 ZW User Manual
Magnasonic Clock Radio MiC1000 User Manual
Makita Power Hammer hm0830 User Manual
Marantz CD Player CC3000 User Manual
Maxtor DVR ELX8 60 User Manual
Maytag Washer W10240518A User Manual
McCulloch Lawn Mower 532 43 86 30 User Manual