Lux Products Battery Charger TX9600TS User Manual

TX9600TS  
SMART TEMP® UNIVERSAL  
7-DAY PROGRAMMABLE TOUCHSCREEN THERMOSTAT  
(FOR BOTH CONVENTIONAL AND HEAT PUMP SYSTEMS)  
INSTALLATION AND OPERATING INSTRUCTIONS  
52106  
IMPORTANT!  
• Please read all of these instructions carefully before beginning  
installation.  
• Label every wire terminal designation on your existing thermostat  
wiring before removing your old thermostat.  
• Ignore the color of the wires since they may not comply with any  
standard. Please connect wires using the terminal letter  
designations.  
Thank you for your confidence in our product. To obtain the best results  
from your investment, please read and follow the installation procedures  
carefully, and one step at a time. This will save you time and minimize the  
chance of damaging either the thermostat or possibly your heating and  
cooling system. These instructions may contain information beyond that  
which may be required for your particular installation.  
SYSTEM COMPATIBILITY . . . . . . . . . 2  
FEATURES . . . . . . . . . . . . . . . . . . . 3  
TOOLS YOU MAY NEED . . . . . . . . . . . 3  
MOUNTING LOCATION . . . . . . . . . . . 4  
REMOVE OLD THERMOSTAT . . . . . . . 4  
INSTALL THERMOSTAT BASE . . . . . . . 5  
WIRING INFORMATION . . . . . . . . . . . 6  
WIRING DIAGRAMS . . . . . . . . . . . . . 8  
HARDWARE SETUP OPTIONS . . . . . . 17  
COMPLETE THE INSTALL . . . . . . . . . 19  
FRONT PANEL ITEMS . . . . . . . . . . . 19  
OPERATING INSTRUCTIONS . . . . . . . 20  
TEMPERATURE PROGRAMS . . . . . . . 23  
ADVANCED FEATURES . . . . . . . . . . 24  
BATTERY REPLACEMENT . . . . . . . . . 32  
TECHNICAL ASSISTANCE . . . . . . . . . 33  
LIMITED WARRANTY . . . . . . . . . . . 33  
MERCURY NOTICE . . . . . . . . . . . . . 33  
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only.  
Energizer® is a registered trademark of Eveready Battery Company, Inc.  
DURACELL® is a registered trademark of The Gillette Company, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2011 LUX PRODUCTS CORPORATION. ALL RIGHTS RESERVED  
FEATURES:  
1 or 2-Heat / 1-Cool, 7-day programming  
Universal Compatibility for all system types  
Each day of the week can be programmed separately  
Easy to use, touchscreen menu operation  
User-selectable periods per day (2 or 4)  
User-selectable programmable or non-programmable operation  
LuxLight® EL (Electro-Luminescent) lighted display  
Energy usage monitor  
Programmable air filter life timer  
Programmable keypad lockout for unauthorized users  
Manual temperature hold  
Adjustable vacation hold (1 to 30 days)  
Temporary temperature override  
Adjustable temperature differential / cycle-rate  
Adjustable 2nd heat stage Offset setting  
User temperature calibration  
Adjustable heat/cool set temperature limit stops  
Smart recovery  
Dual-powered (battery and/or 24-volt system powered)  
Battery-free memory storage  
F/C temperature display  
12/24-hour clock display  
5/2-minute selectable time delay for equipment protection  
TOOLS YOU MAY NEED:  
Screwdrivers  
Wire Stripper  
Wire Cutter  
Drill with assorted drill bits (new installations only)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
MOUNTING LOCATION:  
On replacement installations, mount the new thermostat in place of the old  
one unless the conditions listed below suggest otherwise. On new  
installations, please follow these general guidelines:  
1. Mount the thermostat on an inside wall, about 5 ft. (1.5m) above the floor.  
2. Do not locate the thermostat where air circulation is poor such as in a  
corner, alcove, or behind a door that is normally left open.  
3. Do not locate the thermostat where unusual heating or cooling conditions  
may be present, such as: direct sunlight, above a lamp, television, or  
radiator, or on a wall next to an exterior door or window.  
4. Do not locate in a damp environment, as this can lead to corrosion that  
may shorten thermostat life.  
5. If painting or construction work is still ongoing, cover the thermostat  
completely or wait until this work is complete before installation.  
WARNING:  
All wiring must conform to the local codes and ordinances that are in your  
particular location.  
REMOVE OLD THERMOSTAT:  
1. Turn OFF the electricity to all heating and cooling  
components. Do not turn the electricity back on  
until all work is completed.  
2. Remove the front portion of your old thermostat to  
expose the wiring connections.  
F
OF  
3. Write down the letters printed near each wire  
terminal that is used, and also the color of each  
wire that is connected to it. Self-adhesive wire  
labels are also enclosed.  
4. Carefully remove the wires one at a time, and bend them in a manner so  
that they do not fall back inside the wall. Do not allow bare wire ends to  
touch each other.  
5. Loosen the mounting screws for the old thermostat and carefully remove  
it from the wall.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
INSTALL THERMOSTAT BASE:  
Large Indentation:  
Front Housing Release  
Mode  
Switches  
THERMOSTAT TOP VIEW  
1. Strip wire insulation leaving only 3/8 in. (9.5mm) bare wire ends, and  
clean off any corrosion present.  
2. Fill the wall opening with non-combustible insulation to prevent drafts  
from affecting the thermostat’s normal operation.  
3. Route the wires through the opening in the new thermostat base plate, and  
hold the base against the wall. Try to line up the screw holes from the  
prior thermostat, and install the mounting screws.  
4. If the previous holes cannot be used, hold the thermostat base against the  
wall so that it appears straight and level (position the base for best  
appearance) and mark for the new screw holes. Attach the base to the  
wall using the screws provided (use the supplied plastic anchors if needed  
when mounting to a soft material such as drywall).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
WIRING INFORMATION:  
CONNECTING THE WIRES:  
When attaching the wires to the thermostat, please ensure that the bare wire  
ends are held ALL the way into the terminal block while the screw is being  
tightened.  
WIRING BASE PLATE NOTICE:  
This thermostat model is part of a family of similar models that have the  
same general visual appearance. Even though this base plate may look the  
same as base plates from other models, the wiring connections may have  
different terminal letters for different purposes. Please do not interchange  
the back plates and/or thermostat front halves of other similar looking  
models. Doing so may cause undesired heating and/or cooling operation to  
occur.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
WIRING DIAGRAM NOTES:  
(Important, please read all notes before connecting wires)  
If the information provided in the following wiring diagrams does not  
clearly represent or match your system, please refer to the “TECHNICAL  
ASSISTANCE” section of this manual, and contact us before removing any  
of your existing thermostat wiring.  
All of the dashed wires shown in the wiring diagrams are either optional,  
or their usage depends upon your specific system type or brand. For  
example: Diagram #1 shows the fan wire as optional. If your system does  
not have a fan, than this terminal will not be used.  
Terminal letters shown in black represent typical wiring applications.  
Depending upon the brand of your specific system or thermostat, your  
terminal letters may not match exactly. Terminal letters shown in gray  
represent other possible wiring designations that you might see on your  
existing thermostat terminals.  
The optional “C” terminal is used for powering the thermostat by the 24-  
volt system, using the System Common wire. This can be used alone, or  
in addition to installing batteries as a backup. NOTE: connecting the  
System Common wire to the thermostat is not necessary for heating and  
cooling to function properly.  
If your old thermostat has both a “Y” and “C” wire present, then “C” is  
most likely a System Common wire.  
For Heat Pump systems, you will use either the “O” terminal or the “B”  
terminal on this thermostat, but not both. If your old thermostat has both  
an “O” and a “B” wire present, then “B” is likely a System Common wire  
and may be connected to the “C” terminal. Connecting a System Common  
wire to this thermostat’s “B” terminal may damage the thermostat, and  
also your heating and cooling system.  
Some Heat Pump systems have a wire for AUX electric heat (usually W2),  
and also a separate wire for Emergency electric heat (usually E). This  
thermostat uses the W2 terminal for both AUX and Emergency Heat. Tape  
off your “E” wire, and confirm that all components function without it.  
If replacing an old thermostat that has a mechanical clock, there may be  
two wires labeled as “C” for the clock power. Tape off these wires and do  
not connect them to the “C” terminal of this thermostat.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
WIRING DIAGRAMS:  
DIAGRAM  
SYSTEM TYPE / DESCRIPTION  
PAGE #  
#1  
#2  
#3  
#4  
#5  
#6  
#7  
#8  
CONVENTIONAL: HEATING .............................................8  
1-STAGE OR 2-STAGE  
2, 3, 4, 5 WIRES  
CONVENTIONAL: HEATING .............................................9  
3-WIRE ZONE VALVE  
3, 4 WIRES  
CONVENTIONAL: COOLING............................................10  
1-STAGE  
3, 4 WIRES  
CONVENTIONAL: HEATING AND COOLING...........................11  
1-STAGE HEAT  
4, 5 WIRES  
CONVENTIONAL: HEATING AND COOLING...........................12  
2-STAGE HEAT  
5, 6 WIRES  
CONVENTIONAL: HEATING AND COOLING...........................13  
TWO-TRANSFORMERS  
5, 6 WIRES  
HEAT PUMP:  
HEAT PUMP:  
HEATING AND COOLING...........................14  
SINGLE-STAGE ONLY  
4, 5 WIRES  
HEATING AND COOLING...........................15  
WITH AUX / EMERGENCY HEAT  
5, 6 WIRES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
2, 3, 4, 5 WIRES  
#1  
1-STAGE OR 2-STAGE, HEATING ONLY  
(INCLUDING MILLIVOLT) (2-WIRE HEAT USE “RH” & “W1”)  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
FAN WIRE  
MAY NOT BE  
PRESENT IN  
ALL SYSTEMS  
G
F
R
W2  
W
C
X
RH  
V
W1  
4
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
STAGE  
2
STAGE  
SYSTEM 24V  
TRANSFORMER  
FAN  
1
HEATER  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3, 4 WIRES  
#2  
HOT WATER HEATING ONLY  
(WITH A 3-WIRE ZONE VALVE)  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
R
A
W
C
X
RH  
V
W1  
4
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
CLOSE  
OPEN  
SYSTEM 24V  
TRANSFORMER  
3-WIRE ZONE VALVE  
OPEN = Heat On  
CLOSE = Heat Off  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3, 4 WIRES  
#3  
1-STAGE, COOLING ONLY  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
Y
Y1  
6
R
C
X
RC  
V
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
SYSTEM 24V  
TRANSFORMER  
AIR  
CONDITIONER  
FAN  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4, 5 WIRES  
#4  
CONVENTIONAL (NON HEAT PUMP)  
1-STAGE HEATING AND 1-STAGE COOLING  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
Y
Y1  
6
R
W
C
X
RH  
RC  
V
W1  
4
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
AIR  
CONDITIONER  
SYSTEM 24V  
TRANSFORMER  
FAN  
HEATER  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5, 6 WIRES  
#5  
CONVENTIONAL (NON HEAT PUMP)  
2-STAGE HEATING AND 1-STAGE COOLING  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
Y
Y1  
6
R
W2  
W
C
X
RH  
RC  
V
W1  
4
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
STAGE  
2
STAGE  
1
AIR  
CONDITIONER  
SYSTEM 24V  
TRANSFORMER  
FAN  
HEATER  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5, 6 WIRES  
#6  
1-STAGE HEATING AND 1-STAGE COOLING  
WITH TWO SEPARATE 24V TRANSFORMERS  
Factory RH-RC Jumper Wire REMOVED  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
Y
RC  
RH  
W
C
X
Y1  
6
R
V
R
V
W1  
4
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
AIR  
CONDITIONER  
COOL 24V  
TRANSFORMER  
HEAT 24V  
TRANSFORMER  
FAN  
HEATER  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SINGLE-STAGE HEAT PUMP SYSTEM  
WITH NO AUX OR EMERGENCY HEAT  
4, 5 WIRES  
#7  
** Use “O” or “B”  
Terminals, Never Both  
CUSTOMER INSTALLED Y-W1 Jumper Wire  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
O
Y
Y1  
6
R
C
X
RC  
V
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
REVERSING  
VALVE  
SYSTEM 24V  
TRANSFORMER  
FAN  
HEAT PUMP  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5, 6 WIRES  
2-HEAT / 1-COOL, HEAT PUMP SYSTEM  
WITH AUX AND EMERGENCY HEAT  
#8  
** Use “O” or “B”  
Terminals, Never Both  
CUSTOMER INSTALLED Y-W1 Jumper Wire  
Factory RH-RC Jumper Wire Installed  
G
B
O
Y
RC  
RH  
W2  
A
W1  
C
G
F
O
Y
R
W2  
C
X
Y1  
6
RC  
V
W3  
W
B*  
O
P
T
I
O
N
A
L
SYSTEM COMMON  
REVERSING  
VALVE  
SYSTEM 24V  
TRANSFORMER  
AUX / EMERG.  
HEAT  
FAN  
HEAT PUMP  
NOTE: THE BLACK TERMINAL LETTERS ARE TYPICAL, GRAY TERMINAL LETTERS ARE BRAND SPECIFIC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HARDWARE SETUP OPTIONS:  
On the thermostat’s circuit board, there is a row of DIP switches, labeled #1  
through #8. The position of these switches will change how the thermostat  
operates, and also how information is conveyed to you on the LCD display  
screen. If you make any changes to these options, the changes are not  
recognized unless you either: change the position of the HEAT/OFF/COOL  
mode switch, or press the “HW RST” (Hardware Reset) button on the circuit  
board. The use of this button is further  
described in the “ADVANCED FEATURES”  
section of this manual.  
These option switches are very small and  
should be moved carefully using objects  
such as: eyeglass screwdriver, fine-point  
pen, toothpick, or similar. The listing  
below describes the available choices for  
each option switch:  
SWITCH #1 (SYSTEM): [OFF/RIGHT = FURN, default] This setting is used for  
the majority of all heating systems that are not heat pumps. Examples for  
this setting would be: natural gas furnace, hot water baseboard heat, and oil  
heat. [ON/LEFT = HP] Use this setting if you have a heat pump unit (which  
looks just like an outside air conditioning unit, but is used for both cooing  
and heating).  
SWITCH #2 (TYPE): [OFF/RIGHT = PROG, default] The thermostat controls  
the room temperature by following temperature program periods that you set  
up based upon your daily routine. [ON/LEFT = MAN] The thermostat  
operates manually just like a mechanical or non-programmable model. This  
method of operation is very basic and only shows the room temperature and  
set temperature; there are no temperature programs, days of the week, or  
clock times.  
SWITCH #3 (PERIODS): [OFF/RIGHT = 4, default] The thermostat uses four  
temperature program periods in both heating and cooling (MORN, DAY, EVE,  
and NITE). Each period has a separate start time and a set temperature.  
[ON/LEFT = 2] The thermostat operates in the same manner as above,  
however there are only two temperature program periods for heating and  
cooling (DAY and NITE). This may be more convenient if you are typically  
home during the day, and only need the set temperature to be different while  
you are sleeping.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
SWITCH #4 (SCALE): [OFF/RIGHT = F, default] All temperature values are  
displayed using the Fahrenheit scale. [ON/LEFT = C] This setting displays all  
temperature values using the Celsius scale.  
SWITCH #5 (TIME): [OFF/RIGHT = 12 HR, default] This setting displays the  
clock times and temperature program period start time values on the screen  
using US standard AM and PM values. [ON/LEFT = 24 HR] This setting  
displays the clock and temperature program period start time values on the  
screen using the 24 HR military-time format (17:30 hours, 22:00 hours,  
without using AM/PM).  
SWITCH #6 (DELAY): [OFF/RIGHT = 5 MIN, default] This sets the minimum  
length of time that Heat or Cool must remain either On or Off, before it will  
automatically switch to the alternate On or Off state. This internal delay  
prevents rapid cycling of your system and provides equipment protection  
particularly for cooling units. The 5-minute setting is fine for most  
applications. [ON/LEFT = 2 MIN] If you feel that your system may need to  
cycle more frequently than the thermostat is allowing, then you may use the  
2-minute setting.  
SWITCH #7 (RECOVERY): [OFF/RIGHT = DISABLE, default] The Early  
Recovery feature affects how the thermostat transitions from an energy  
saving setback (DAY and NITE) program period, to a comfort (MORN and  
EVE) program period temperature, when it is following the daily temperature  
programs. When this is disabled, the thermostat makes a set temperature  
change at the beginning of an upcoming period's start time. [ON/LEFT =  
ENABLE] The Early Recovery feature will calculate the capability of your  
system and turn on the heating or cooling early so that the temperature in  
your home reaches the desired set point as close as possible to the start of  
the period. During the time that the thermostat is performing a recovery, the  
words “IN RECOVERY” will be shown, alternating at the top of the display  
with the current system mode.  
SWITCH #8 (BATTERY MONITOR): [OFF/RIGHT = ON, default] This setting,  
regularly monitors the battery level, and shows “LOW BAT” on the screen if  
the batteries need to be replaced. Use this setting at all times when  
batteries are present in the thermostat. [ON/LEFT = OFF] This setting only  
applies if you are NOT physically using batteries in the thermostat, and are  
powering the thermostat entirely from the system (“C” wire terminal).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
GAS / ELEC SLIDE SWITCH (FAN OPERATION):  
This switch is a physical component by itself on  
the circuit board, and is much larger than the  
DIP switches listed above. [DOWN = GAS,  
default] This setting lets the heating system  
control the blower fan automatically by itself.  
Systems that would typically use the “GAS”  
setting would be: natural gas, propane, or oil  
furnaces. This setting has no effect upon Cool  
mode operation. [UP = ELEC/HP] This setting  
runs the system’s blower fan when heat is called  
BATTERY  
GAS  
ELEC  
for, and is required for heating systems that do not control their own fan  
while the thermostat is in HEAT mode. Heat pump systems, and units with  
an electric heating element typically require this setting.  
COMPLETE THE INSTALL:  
Once the hardware options are set, install two new Energizer® or DURACELL®  
"AA" size alkaline batteries. Ensure that the batteries are installed in the  
proper direction as per the markings shown in the battery tray. If the  
batteries were already installed before changing the hardware setup options,  
change the position of the HEAT/OFF/COOL System Mode switch to accept  
the new hardware option switch settings.  
FRONT PANEL ITEMS:  
These two items below are both located on the right side of the thermostat  
housing.  
HEAT / OFF / COOL, SYSTEM MODE SWITCH: Set this switch to HEAT to  
control your heating system, and COOL to control your cooling system. The  
OFF position will disable both the heating and cooling units.  
AUTO / ON, FAN MODE SWITCH: When this switch is in AUTO, the blower fan  
(if present in your system) will automatically cycle on and off by itself while  
heating or cooling is running. When in the ON position, the blower fan will  
run constantly with or without a demand for heating or cooling, even when  
the System Mode switch is in the OFF position.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
NOTE: The Fan Mode switch only works if your system provides a wire for  
the thermostat’s “G” wire terminal, to control a blower fan. The Fan Mode  
switch has no effect in systems that do not have a blower fan (such as a hot  
water radiator system).  
OPERATING INSTRUCTIONS:  
TOUCHSCREEN MENU CONTENTS:  
SET DAY/TIME  
SET/REVIEW “HEAT/COOL” PROGRAMS (not present in OFF mode)  
SET/REVIEW FILTER USAGE  
REVIEW “HEAT/COOL” ENERGY USAGE (not present in OFF mode)  
SET/REVIEW SWING VALUE  
SET KEYBOARD LOCK CODE (not present in OFF mode)  
SET “HEAT/COOL” TEMPERATURE STOP (not present in OFF mode)  
TEMPERATURE SETBACK (not present in OFF mode)  
SET DAY AND TIME: Press the MENU button. The first menu item shown is  
“SET DAY/TIME”, press the OK button. With the day flashing, press UP or  
DOWN to set the day of the week. Press NEXT and the clock time will start  
flashing. Use UP or DOWN to set the time, making sure the AM/PM  
indication is correct. Holding the UP or DOWN buttons will make the clock  
digits scroll rapidly. Press the EXIT button to return to the Normal Run  
screen.  
HEATING AND COOLING: Basic operation of your heating or cooling system  
can be obtained by choosing either HEAT or COOL on the System Mode  
switch. Touch the Set Temperature digits on the screen and they will begin  
to flash. While they are flashing, the UP and DOWN buttons will be shown  
also, which you can use to adjust the current Set Temperature. When the  
thermostat is first powered up, it will follow a default temperature routine  
that is preset from the factory (shown below), until the clock has been set.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
PERIOD  
HEAT MODE  
COOL MODE  
MORN 6:00 AM 70 °F (21 °C) 6:00 AM 78 °F (26 °C)  
DAY  
EVE  
8:00 AM 62 °F (17 °C) 8:00 AM 82 °F (28 °C)  
6:00 PM 70 °F (21 °C) 6:00 PM 78 °F (26 °C)  
NITE 10:00 PM 62 °F (17 °C) 10:00 PM 75 °F (24 °C)  
There are on-screen indicators to show you when the thermostat is calling  
for heating or cooling to occur. In the Heat mode switch position, a flame  
will be present on the screen. A steady flame means that the thermostat is  
not calling for your heating system to run, while a flashing flame means that  
your heating system should be currently running. In the Cool mode switch  
position, a snowflake will be present on the screen. A steady snowflake  
means that the thermostat is not calling for your cooling system to run,  
while a flashing snowflake means that your cooling system should be  
currently running.  
EMERGENCY HEAT: (Heat Pump Configuration Only). While in normal Heat  
mode, one single press of the EMER button will activate Emergency Heat  
mode. While in Emergency Heat, the top of the screen will change from  
“Heat Mode” to show “Emer Heat”. A single press of the EMER button again  
will end Emergency Heat, and return back to normal Heat mode. If a power  
loss occurs while in Emergency Heat mode, the thermostat will continue to  
remain in Emergency Heat mode even after the power comes back on.  
Emergency Heat mode will prevent the first stage of your heat pump system  
from turning on, and use only the “W2” heat terminal (Auxiliary Heat) as the  
primary heating source. This will not only prevent the heat pump from  
wasting energy if outdoor temperatures are too low to support efficient  
operation, but it could also prevent damage to the heat pump if outside  
temperatures are below the manufacturer’s recommendations. As every heat  
pump has different operating characteristics, you should refer to your heat  
pump literature to determine when to disable the heat pump and run in  
Emergency Heat mode.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
LCD DISPLAY BACKLIGHT: The display screen is lighted to assist viewing at  
nighttime, or in locations with low light levels. A press of any area on the  
touch panel will light the display for approximately 10 seconds. Any screen  
presses that occur while the light is on will reset the 10-second timer,  
causing the screen to remain illuminated for an additional 10 seconds.  
TEMPERATURE OVERRIDE: While in the Normal Run screen, the set  
temperature can be temporarily changed by pressing the Set Temperature  
digits, then pressing the UP or DOWN buttons. The set temperature will  
return to the programmed value stored in memory when the start time of the  
next upcoming program period is reached (Morn, Day, Eve, Nite). While a  
Temporary Override is in effect, the words “HEAT OVRRIDE” or “COOL  
OVRRIDE” will be shown in the display screen. An Override may be  
cancelled by either pressing the HOLD button two times, or by moving the  
mode switch to OFF, pausing briefly, then switching back to the HEAT or  
COOL position. When in the Normal Run mode, the display should say either  
“HEAT MODE” or “COOL MODE”.  
MINIMUM RUN TIME: The thermostat has a default internal time delay of 5  
minutes between load-on and load-off activations to prevent heating or  
cooling system damage, which can occur from very frequent cycling. If  
heating or cooling does not turn on right away with a manual change in set  
temperature, please wait at least 5 minutes and the system should resume  
normal operation.  
TEMPERATURE HOLD: A Temperature Hold is used for maintaining a fixed set  
temperature. Once a Hold is initiated, the thermostat will maintain the set  
temperature indefinitely. A Hold may be used for days, weeks, or even  
months at a time, as long as the thermostat has adequate power. To enter  
Hold mode: press the HOLD button one time and the words “HEAT HOLD” or  
“COOL HOLD” will appear in the display. To cancel a Hold, press the HOLD  
button one more time. If a mains power failure occurs during a Temperature  
Hold, the thermostat will continue to remain in Hold mode even after the  
power comes back on.  
NOTE: If you plan to leave the thermostat in Hold mode for an extended  
duration (unattended), it is advisable to install new Energizer® or  
DURACELL® "AA" size alkaline batteries prior to leaving to ensure reliable  
operation of your heating and cooling system.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
22  
STATIC NOTICE: This thermostat is protected against normal static electric  
discharges, however to minimize the risk of damaging the unit in extremely  
dry weather, please touch a grounded metal object before touching your  
thermostat.  
TEMPERATURE PROGRAMS:  
By default, this thermostat has 4 separate program periods for both Heat and  
Cool mode, they are: MORN, DAY, EVE, and NITE. Each period ends at the  
start time of the following period. The heat programs are set in HEAT mode,  
and the cool programs are set in COOL mode.  
NOTE: If the thermostat is configured to use only 2 periods per day instead  
of 4 (HARDWARE SETUP OPTIONS), the thermostat will only use the DAY  
and NITE periods. The MORN and EVE periods will not be visible on the  
screen.  
The following examples are shown using Heat mode. Programming in Cool  
mode is done in the same exact manner with the System Mode switch in the  
Cool position.  
SET TEMPERATURE PROGRAMS: Press the MENU button, then press the  
SCROLL button until “SET/REVIEW HEAT PROGMS” is shown, then press the  
OK button to enter the programming screen. Use the UP and DOWN buttons  
to adjust the start time for the MORN period, then press the NEXT button to  
advance. Use the UP and DOWN buttons to adjust the set temperature for  
the MORN period, then press the NEXT button to advance. Now adjust the  
start time and set temperature for the DAY period, pressing the NEXT button  
after each to advance. Continue with these same steps to adjust the start  
times and set temperatures for the EVE and NITE program periods.  
When the NITE period is finished the thermostat will advance to Tuesday,  
with the MORN period start time flashing. Perform the same steps that you  
used for setting the Monday periods, pressing the NEXT button to advance  
through each flashing value.  
PROGRAM COPY FEATURE: The Copy feature allows you to copy all of the  
program information from any one single day, to any other day of the week.  
To copy heat programs, the thermostat must be in Heat mode, and to copy  
cool programs, the thermostat must be in Cool mode. Emergency Heat (heat  
pump configurations only) uses the Heat temperature program. While in a  
temperature programming screen, press the “COPY” button one time. The  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
words “COPY PROGRAM” will flash briefly at the top of the screen, followed  
by “FROM” and “TO”. Under the word “FROM” will be a flashing day of the  
week. Using the UP and DOWN buttons, select the day that you want to copy  
from. Press the NEXT button one time. Your copy from day should now be  
on steady with the day under the word “TO” flashing. Use the UP and DOWN  
buttons to select the day that you would like to copy to. A single short press  
of the COPY button will perform the copy, and the day flashing under the  
word “TO” will have advanced to the next following day. You may continue  
to perform short single presses of the COPY button to keep copying from the  
original source day to the remaining days, one after the other. Specific days  
may be skipped by pressing the UP button, to advance past them while they  
are flashing under the word “TO”. Press the EXIT button to return to the  
Normal Run screen.  
ADVANCED FEATURES:  
TEMPERATURE SWING SETTING, OFFSET SETTING, AND TEMPERATURE  
CALIBRATION:  
NOTE: The Swing setting, Offset setting, and Calibration settings need to be  
performed in a timely manner, as the thermostat will timeout and  
automatically exit these adjustment screens after approximately 10 seconds  
without a button press.  
SWING DESCRIPTION: A thermostat works by turning your heating or  
cooling system on and off whenever the room temperature varies from the  
desired set-point temperature. The amount of this variation is called the  
Swing. Generally your system should cycle on about 3 to 6 times per hour.  
A smaller swing number makes the system cycle more frequently, so the  
room temperature is more precise and constant. A larger swing number will  
make the system remain on for a longer duration each time and decreases  
the number of cycles per hour. There is only one Swing setting, and this  
determines the cut-in and cut-out points for both the first and second stages  
(if present), in both Heat mode and Cool mode. The swing setting range is  
between #1 and #9 (0.25°F to 2.25°F, in 0.25°F degree increments (or 0.14°C  
to 1.25°C, in 0.14°C degree increments for Celsius)). Swing number 1 is the  
default setting.  
OFFSET DESCRIPTION: This setting is shown as a number of degrees, and is  
similar in nature to the Swing however this only effects the operation of the  
second (auxiliary) heating stage, if present. The setting range for Offset is  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24  
from 0°F to 9°F degrees (0°C to 5°C degrees). When set to 0 degrees, the  
second heating stage is completely disabled while in regular Heat mode  
(Emergency Heat mode will still function for heat pump configurations). The  
Offset value will determine the number of degrees from the set point that will  
be required for the second heating stage to turn on. This setting can be  
used to conserve energy in situations where the second heating stage is  
more costly to operate when compared to the first stage.  
71  
70  
69  
68  
67  
66  
Cut-In / Cut-Out  
(1st Stage)  
70˚F Set  
Temperature  
Swing  
Setting=  
#2 (+/- 0.5˚F)  
Offset **  
Setting=  
4˚F degrees  
(2nd Stage) **  
Cut-In / Cut-Out  
65  
DEGREES (F)  
** = Only applies if a second  
heat stage is present  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
TEMPERATURE CALIBRATION DESCRIPTION: The internal temperature  
sensor in this thermostat is accurately calibrated at the factory, and in most  
cases, alterations to this setting should not be needed. The Temperature  
Calibration feature allows you to manually offset the measured temperature  
by as much as plus or minus 5°F (3°C) degrees from its original value. This  
feature can be useful to match or synchronize this thermostat to another one  
or more, if multiple thermostats are used in the same home.  
TO CHANGE THE SWING, OFFSET, AND CALIBRATION: Press the MENU  
button, then press the SCROLL button until “SET/REVIEW SWING VALUE” is  
shown on the screen, then press the OK button. The words “ADJUST VALUE  
SWING” will appear at the top of the screen, along with a single flashing  
digit. Use the UP and DOWN buttons to change the number value from #1 to  
#9. Press the NEXT button to accept the Swing setting and proceed to the  
Offset setting.  
After the Swing value has been accepted, the words “ADJUST VALUE  
OFFSET” will appear at the top of the screen, along with a single flashing  
temperature digit. Use the UP and DOWN buttons to change the number  
value between 0°F and 9°F degrees (0°C to 5°C). The 0° (zero) degree  
setting will disable the 2nd heating stage while in regular Heat mode. Press  
the NEXT button to accept the Offset setting and proceed to the Calibration  
setting.  
After the Offset value has been accepted, the words “ADJUST VALUE CAL”  
will appear at the top of the screen, along with a single flashing temperature  
digit. Use the UP and DOWN buttons to change the number value between  
–5°F and +5°F (–3°C and +3°C). The 0° (zero) degree setting is the default  
value, and will not alter the displayed room temperature from the measured  
reading. Press the NEXT button to accept the Calibration setting and return  
back to the Swing setting. You can keep pressing the NEXT button to review  
your three setting values, or press the EXIT button to return to the Normal  
Run screen.  
SETBACK FEATURE: The setback feature is similar to both a Temperature  
Override and a Temperature Hold, in that both are used to maintain a fixed  
set temperature instead of following a programmed daily routine. A Setback  
can be considered the same as a Temperature Override, which can last for a  
longer duration that you can adjust from 1-12 hours, or 1-30 days. By  
default, when a Setback is activated in Heat mode, the set temperature used  
Download from Www.Somanuals.com. All Manuals Search And Download.  
26  
will be 5F (3C) degrees lower than the current set temp. For Cool mode, the  
set temperature used will be 5F (3C) degrees higher than the current set  
temp.  
NOTE: The Setback settings need to be performed in a timely manner, as the  
thermostat will timeout and automatically exit these adjustment screens after  
approximately 10 seconds without a button press.  
TO START A SETBACK: Press the MENU button, then press the SCROLL  
button until “TEMPERATURE SETBACK” is shown, then press the OK button.  
The words “OVERRIDE LEFT” will appear at the top of the screen, along with  
two digits and the word “HRS”. Use the UP and DOWN buttons to set the  
duration for how long you would like to maintain a fixed set temperature  
(from 1 to 12 hours). If you would like to set the duration for longer than 12  
hours, keep pressing the UP button. The display will change from “HRS” left  
to “DAYS” left, with an available duration of 1 to 30 days. Once you have  
selected your desired Setback duration, press the NEXT button to advance.  
The display will change from “OVERRIDE LEFT” left to “OVERRIDE  
TEMPERATURE”. Use the UP and DOWN buttons to select your desired Set  
Temperature that will be used during the Setback duration. Once complete,  
press the NEXT button to accept the setting and return to the Normal Run  
screen.  
TO CANCEL A SETBACK: A Setback can be cancelled by either pressing the  
HOLD button two times, or by moving the mode switch to OFF, pausing  
briefly, then switching back to the HEAT or COOL position. When in the  
Normal Run mode, the display should say either “HEAT MODE” or “COOL  
MODE”.  
TEMPERATURE LIMIT STOPS: There are two independent set temperature  
limit stops: a maximum heat set temperature, and a minimum cool set  
temperature. These stops do not prevent a user from performing normal  
actions like Temperature Override or Hold. The Heat Limit Stop prevents the  
set temperature from being adjusted higher than the heat limit setting. The  
Cool Limit Stop prevents the set temperature from being adjusted lower than  
the cool limit setting. Each of these temperature stops is user adjustable in  
one-degree increments, and these settings are protected by a selectable 2-  
digit code to prevent unauthorized tampering. By default, this 2-digit code is  
“00”, and the temperature stops can be used as-is with this code.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
NOTE: The Temperature Limit Stop settings need to be performed in a timely  
manner, as the thermostat will timeout and automatically exit the setting  
screens after approximately 10 seconds without a button press.  
The following examples are shown for setting the maximum set temperature  
for Heat mode. Setting the Temperature Limit Stop for Cool mode is done in  
the same exact manner with the System Mode switch in the Cool position,  
and instead you will be setting the minimum set temperature for cooling.  
Once a Temp Stop Lock Code has been selected, this same code is used for  
both Heat and Cool temp stops.  
TO SET THE TEMPERATURE LIMIT STOP: Press the MENU button, then press  
the SCROLL button until “SET HEAT TEMP STOP” is shown, then press the  
OK button. The words “ENTER CODE” and “TEMP STOP” will appear at the  
top of the screen, along with two digits at the left. Use the UP and DOWN  
buttons to enter the current Temp Stop Lock Code (“00” by default). Press  
the NEXT button to advance. If the code entered does not match the current  
Temp Stop Lock Code, the words “WRONG CODE” will flash briefly, and you  
may try to enter the correct code again. If the current code has been entered  
correctly, you will have the ability to change the desired Temp Stop Lock  
Code to something else. The words “SET CODE” and “TEMP STOP” will  
appear at the top of the screen, along with two digits at the left. Use the UP  
and DOWN buttons to enter the desired Temp Stop Lock Code to be used,  
and press the NEXT button to advance.  
The words “SET HEAT RANGE STOP” will appear at the top of the screen,  
along with two large temperature digits in the middle. Use the UP and  
DOWN buttons to adjust the desired maximum heat set temperature value (or  
minimum set temperature value for Cool mode). Once complete, press the  
NEXT button to accept the setting and return to the Normal Run screen.  
IF YOU FORGET YOUR TEMPERATURE STOP LOCK CODE: The code can be  
reset to the factory default “00” by performing the following steps. Start  
with the System Mode switch in either the Heat or Cool positions, then  
change to the OFF position. Press and hold the HOLD, NEXT, and OK buttons  
all at the same time for at least 10 seconds. The screen will briefly show  
“00” on the screen to confirm that the Temp Stop Lock Code has been  
successfully reset to the factory default of “00”.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
28  
KEYPAD LOCKOUT: You can lock the touch-panel buttons to prevent  
unauthorized tampering of your thermostat settings.  
NOTE: These keypad lock instructions need to be performed in a timely  
manner, as the thermostat will timeout and automatically exit the keypad lock  
screens and return to the Normal Run screen after approximately 10 seconds  
without a button press.  
TO LOCK THE KEYPAD: The System Mode switch must be in either the Heat  
or Cool position. Press the MENU button, then press the SCROLL button  
until “SET KEYBOARD LOCK CODE” is shown, then press the OK button. The  
words “ENTER CODE” will appear at the top of the screen, along with four  
digits at the left. Select a 4-digit code that you would like to use for locking  
the thermostat. Press the UP and DOWN buttons to change each digit  
individually, using the NEXT button to cycle through which digit is selected.  
Pressing the OK button will lock the thermostat touch panel using the 4-digit  
code that is shown on the screen, and return to the Normal Run screen with  
a padlock shown to confirm that the thermostat is now locked.  
TO UNLOCK THE KEYPAD: Press the padlock icon, and the words “UNLOCK  
KEYBOARD?” will appear at the top of the screen. Press OK to proceed with  
entering the unlock code (or press the EXIT button to cancel). The words  
“ENTER CODE” will appear at the top of the screen, along with four digits at  
the left. You will need to enter the proper unlock code that was used for  
initially locking the thermostat. Press the UP and DOWN buttons to change  
each digit individually, using the NEXT button to cycle through which digit is  
selected. With the correct lock code entered on the screen, pressing the OK  
button will unlock the thermostat. If the code entered does not match the  
current keypad lock code, the words “WRONG CODE” will flash briefly, and  
you may try to enter the correct code again.  
IF YOU FORGET YOUR KEYPAD LOCK CODE: The following steps can regain  
access to the thermostat. Remove the front portion of the thermostat from  
the wall, and briefly press the “HW RST” HARDWARE RESET button on the  
thermostat circuit board. More information about the use of this button is  
described later in this section.  
AIR FILTER MONITOR: In most systems that use a blower fan and air ducts,  
there is an air filter that is either replaceable or requires cleaning. The filter  
is usually located in the air handler, where the blower fan is. This  
thermostat feature assists you with keeping track of proper maintenance  
and/or periodic replacement intervals for your system’s filter.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
The Air Filter Monitor counts the duration of filter usage that has occurred,  
since the last time the Filter Monitor has been reset. This feature is for  
information purposes only, and does not affect the operation of your heating  
or cooling equipment, or the thermostat. When the filter usage duration has  
expired, the words “CHANGE FILTER” will appear at the top of the display  
screen, alternating with the current DAY and PERIOD.  
TO ACCESS FILTER INFORMATION: Press the MENU button, then press the  
SCROLL button until “SET/REVIEW FILTER USAGE” is shown, then press the  
OK button. The words “FILTER USAGE COUNT” will appear at the top of the  
screen, along with the total number of hours that have elapsed since the last  
time the filter counter was reset. Press the NEXT button to advance.  
The words “FILTER USAGE RESET?” will appear at the top of the screen. To  
reset the filter counter to the start of the current limit setting press the OK  
button. Press the NEXT button to advance.  
The words “ADJUST VALUE FILTER LIMIT” will appear at the top of the  
screen. This shows the current setting value for how many filter run time  
hours can elapse before showing “CHANGE FILTER” in the Normal Run  
screen. The adjustment range for this setting is from 0 hours to 2000 hours,  
with 720 hours as the default. A filter limit setting of 0 (zero) hours will  
disable the filter monitor feature. Once complete, press the EXIT button to  
save all settings and return to the Normal Run screen.  
NOTE: Air filters are sold based upon how many days they are rated for. One  
day of filter run time is actually considered only 8 hours (not a full 24, since  
your heating and/or cooling system only runs for approximatly one third of  
the time). For a “90-day” filter, use a limit setting of 720 hours should be  
used, and for a “30-day” filter, a limit setting of 240 should be used.  
ENERGY USAGE MONITOR: Your thermostat contains a timer, which records  
the amount of “on-time” for your heating and cooling systems. There are  
three records that can be displayed for both Heat and Cool modes:  
1) The amount of system run time so far for today.  
2) The amount of system run time for yesterday.  
3) The total cumulative system run time since the timer was reset.  
The Heat Energy Usage information is shown while the System Mode switch  
is in the Heat position, and the Cool Energy Usage information is shown  
while the System Mode switch is in the Cool position. The following  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30  
examples are shown for viewing the Energy Usage while in Heat mode.  
Viewing the Cool mode information is done in the same exact manner in Cool  
mode.  
TO VIEW THE ENERGY USAGE TIMERS: Press the MENU button, then press  
the SCROLL button until “REVIEW HEAT ENERGY USAGE” is shown, then  
press the OK button. The words “TODAYS ENERGY USAGE” will appear at  
the top of the screen, along with the amount of heating system runtime  
(displayed as “HH:MM”, for hours and minutes). Use the NEXT button to  
cycle between Today’s Usage, Yesterday’s Usage, and the Total Cumulative  
Usage for heat mode. NOTE: For the Total Cumulative Usage, the timer will  
record up to a maximum of 99 hours and 59 minutes, then the display will  
change to “HHHH” for hours only, without the colon in the center.  
Pressing NEXT after the Total Cumulative Usage will show the words “TOTAL  
USAGE RESET?” at the top of the screen. Pressing OK at this screen will  
clear the Heat Energy Usage timer, and start back at 0 (zero). Press the EXIT  
button to return to the Normal Run screen.  
HARDWARE RESET: The Hardware Reset button (labeled  
“HW RST”) is a small round push button that is located  
HW  
RST  
towards the right side of the circuit board, just below the  
battery holder. Pressing this button will cause the LCD  
display screen to become fully populated, the heating and  
cooling load relays to cycle off, read the position of the  
Hardware Setup Option switches, and will perform an internal system check  
of the thermostat components. If your thermostat appears to be acting in an  
erratic manner, pressing the Hardware Reset button may remedy this  
behavior. The temperature programs are not erased when a hardware reset  
is performed, however the clock will have to be changed to match the  
current day and time.  
SOFTWARE RESET: The Software Reset button (labeled  
“SW RST”) is a small round push button that is located  
SW  
RST  
towards the right side of the circuit board, just below the  
battery holder. A Software Reset is used to erase all  
heating and cooling temperature programs, and any user-  
adjustable software values such as: Swing, Offset, and  
Calibration, to their original factory default values. To perform a Software  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
Reset, press and hold the Software Reset button for at least 5 seconds. The  
LCD display screen will become fully populated, then return to normal. The  
thermostat will still retain the current day and time even after a Software  
Reset has been performed.  
COMPRESSOR PROTECTION BYPASS: This optional feature permits the  
installer or service technician to temporarily disable the built in compressor  
protection delays. This is most useful for diagnosing and testing the heating  
and cooling systems after installation is complete, and should not be used  
during normal operation. To activate this feature, start with the System  
Mode switch in either the Heat or Cool positions, then change to the OFF  
position. Press and hold the OK button for at least 5 second. The  
thermostat will give a single beep sound to confirm that this feature has  
been activated. All compressor protection delays (in all modes of operation)  
will be disabled for 5 minutes. After the 5-minute duration has expired, the  
thermostat will return to normal operation automatically.  
BATTERY REPLACEMENT:  
This thermostat is powered by two “AA” Alkaline batteries. The batteries  
should be replaced AT LEAST once per year to ensure reliable operation (or  
sooner, if the “LO-BATTERY” icon appears at the bottom of the display  
screen). The batteries are located on the back of the thermostat, at the top  
of the circuit board. The front portion of the thermostat can be removed  
from the back half by pulling straight outwards on the top and bottom of the  
thermostat housing, at the large indentations that are present in the center  
of the top and bottom edges.  
When installing new batteries, we recommend using only brand new  
Energizer® or DURACELL®, “AA” size alkaline batteries. Please observe the  
polarity markings shown in the battery compartment to ensure proper  
installation. When finished, line up the front of the thermostat to the base,  
and firmly press together to securely latch the front and back halves together  
properly.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
32  
TECHNICAL ASSISTANCE:  
If you have any problems installing or using this thermostat, please carefully  
and thoroughly review the instruction manual. If you require assistance,  
please contact our Technical Assistance department at 856-234-8803 during  
regular business hours between 8:00AM and 4:30PM Eastern Standard Time,  
Monday through Friday. You can also receive technical assistance online  
troubleshooting guides, answers to the most common technical questions,  
and also permits you to email your questions to our technical support staff  
at your convenience.  
LIMITED WARRANTY:  
If this unit fails because of defects in materials or workmanship within three  
years of the date of original purchase, LUX will, at its option, repair or  
replace it. This warranty does not cover damage by accident, misuse, or  
failure to follow installation instructions. Implied warranties are limited in  
duration to three years from the date of original purchase. Some states do  
not allow limitations on how long an implied warranty lasts, so the above  
limitation may not apply to you. Please return malfunctioning or defective  
units to the location from which the purchase was made, along with proof of  
purchase. Please refer to “TECHNICAL ASSISTANCE” before returning  
thermostat. Purchaser assumes all risks and liability for incidental and  
consequential damage resulting from installation and use of this unit. Some  
states do not allow the exclusion of incidental or consequential damages, so  
the above exclusion may not apply to you. This warranty gives you specific  
legal rights and you may also have other rights, which vary from state to  
state. Applicable in the U.S.A. and Canada only.  
MERCURY WARNING AND RECYCLING NOTICE:  
Mercury is considered to be a hazardous material. If this product is  
replacing a thermostat that contains mercury in a sealed tube, contact your  
local waste management authority for instructions regarding recycling and  
proper disposal. It may be unlawful in your state to place it in the trash.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
LUX  
FAN  
AUTO  
ON  
MENU  
˚
F
PM  
˚
F
SET  
HEAT  
OFF  
COOL  
Mt. Laurel, New Jersey 08054, USA  
856-234-8803  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34  

KTI Networks Network Card KG 500F User Manual
Learning Resources Baby Toy LER 2420 User Manual
Lochinvar Heat Pump SBN1000 User Manual
Magic Chef Refrigerator MCBR980W User Manual
Marantz Flat Panel Television PDxx01 User Manual
Mattel Motorized Toy Car Y9172 0920 User Manual
McCulloch Chainsaw MS1432 User Manual
Melissa Blender 646 067 User Manual
Melissa Hot Beverage Maker 245 066 User Manual
Middleby Marshall Oven PS740E User Manual