Lightolier Work Light C7P38MHA User Manual

Calculite® HID Adjustable Accent C7P38MHA  
Page 1 of 3  
7" Aperture, PAR38 Ceramic Metal Halide  
C7P38  
20" (508 mm) to  
30" (762 mm)  
1
5
8
1
3
4
2
9
6
7
10-5/8"  
(270 mm)  
20-1/4" (514 mm)  
Top View  
(Electronic Ballast)  
20" (508 mm) to  
30" (762 mm)  
11 7/8"  
(302 mm)  
Vertical Adjustment:  
3/4" (25 mm) to  
2 7/8" (73 mm)  
10-5/8"  
(270 mm)  
22-1/8" (562 mm)  
Top View  
(Magnetic Ballast)  
7" (178 mm) Dia.  
1 1/8" (29 mm) max.  
Ceiling Thickness  
5/8" (16 mm)  
8-3/8" (213 mm) Dia.  
Ceiling Cutout: 8” (203mm) Dia.  
Reflector Trim  
C7P38MHA CLW  
Frame-In Kit  
Lamp (Ceramic MH)  
Specular Clear, White Painted Flange.  
Specular Clear, Matching Flange.  
C7A70P38E1 Electronic 120V / C7A70P38E2 Electronic 277V 70W PAR38  
C7A10P38E1 Electronic 120V / C7A10P38E2 Electronic 277V 100W PAR38  
C7A15P38E1 Electronic 120V / C7A15P38E2 Electronic 277V 150W PAR38  
CLP  
CCDW Comfort Clear Diffuse, White Painted Flange.  
CCDP  
CCZW  
CCZP  
Comfort Clear Diffuse, Matching Flange.  
Champagne Bronze, White Painted Flange.  
Champagne Bronze, Matching Flange.  
C7A70P38U Magnetic 120V/277V  
C7A10P38U Magnetic 120V/277V  
C7A15P38U Magnetic 120V/277V  
70W PAR38  
100W PAR38  
150W PAR38  
Features  
Electrical (cont.)  
Ballast ANSI Code Voltage  
Max. Amps  
Input Watts  
78  
110  
167  
1. Reflector Trim: Low brightness,anodized aluminum with integral flange in  
painted white or polished to match inside of cone.  
70W MH M98/M143  
100W MH M90/M140  
150MWH M102  
120/277  
120/277  
120/277  
0.67/0.28  
0.90/0.43  
1.40/0.61  
2. Lamp Holder Assembly: Unitized optics insure alignment of lamp and aper-  
ture cone. Integral C-shaped media holder accepts up to two 4 3/4" media.  
3. Trim Adjustment Mechanism: Provides 45° vertical tilt, 360°+ horizontal  
rotation; lockable. Patented EZ-Aim Helical Drive System provides fast and  
accurate hot aiming with Philips screwdriver.  
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted,  
HX-HPF circuit type, high power factor, sound rating “B, -20° F minimum  
starting temperature, Type 1 Outdoor rating.  
4. Socket: Medium base porcelain socket with nickel plated screwshell,  
pulse rated.  
Ballast ANSI Code Voltage  
Max. Amps  
1.90/0.80  
2.40/1.10  
3.70/1.60  
Input Watts  
94  
125  
180  
70W MH M98/M143  
100W MH M90/M140  
150W MH M102  
120/277  
120/277  
120/277  
5. Frame Housing: Steel, 0.029" (22-Ga.), matte black finish.  
6. Frame Vertical Adjustment Mechanism: Accommodates mounting to vir-  
tually any ceiling system using pre-installed mounting bars, or 1/2" EMT tub-  
ing (by others). Single locking feature secures all adjustments. Alignment  
holes and markings allow fixture to be pre-set prior to installation. Final  
adjustment can be made from below from inside fixture.  
Options and Accessories  
Fuse (magnetic ballast): Add suffix F1 or F2 to Frame-In Kit (F1=120V, F2=277V).  
7. Mounting Bars: Galvanized steel, 0.048" (18-ga.), pre-installed telescoping  
bars extend to 30" long and lock securely into position. Built-in locking tabs  
provide positive attachment to common T-bar systems. Self-centering feature  
simplifies installation in 24" O.C. grid systems. Attaches to steel or wood  
joists without accessories.  
8. Retention Springs: Rust resistant springs secure trim for quick, tool-less  
installation.  
9. Ballast / Cover Assembly: Accessible from below and removable without  
tools for inspection and ballast replacement .  
10. Junction Box: 0.059" (16-ga.) galvanized steel. UL listed for 8 No. 12 AWG,  
90°C through branch circuit conductors. Allows inspection from below.  
11. Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not  
install insulation above nor within 3" (76mm) of any part of the luminaire.  
Chicago Plenum: Consult Factory.  
Labels: UL (Suitable For Damp Locations), CSA (magnetic ballast only), I.B.E.W.  
For 150W, install fixtures with minimum spacing: 2 feet from center-to-center  
of adjacent luminaries; 1/2 inch from top of luminaire to overhead building member;  
1 foot from luminaire center to side building member.  
Job Information  
Type:  
Job Name:  
Cat. No.:  
Lamp(s):  
Notes:  
Electrical  
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high power factor, T.H.D.  
<15%, thermally and transient protected, RMI/RFI complies with FCC part 18  
non-consumer limits, shut-down circuit at end of lamp life, sound rating "A",  
-5° F minimum starting temperature, Type 1 Outdoor rating.  
Lightolier a Genlyte Thomas Company  
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710  
We reserve the right to change details of design, materials and finish.  
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504  
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Clock CA85152 User Manual
La Crosse Technology Weather Radio 724 1710 User Manual
Locke Lawn Mower MP 3132 FP 3132 User Manual
Macsense Connectivity Network Card MPC 200 User Manual
Makita Impact Driver 6990DWDE User Manual
Makita Planer LXPK01 User Manual
Makita Power Screwdriver 6824N User Manual
Marshall electronic Microphone MXL2010 User Manual
Master Lock Electric Heater 100000 BTU Hr User Manual
Meyer Sound Car Speaker UP 4XP User Manual