®
CLEAN • FRESH • AIR
OPERATION AND
INSTALLATION MANUAL
ConCtornot alAinsir 15
IMPORTANT - PLEASE READ THIS
MANUAL BEFORE INSTALLING UNIT
CAUTION
Before installation, careful consideration must be given to
how this system will operate if connected to any other piece
of mechanical equipment, i.e. a forced air furnace or air
handler, operating at a higher static. After installation, the
compatibility of the two pieces of equipment must be
confirmed by measuring the airflow’s of the Heat Recovery
Ventilator (HRV) or Energy Recovery Ventilator (ERV) by
using the balancing procedure found in this manual.
For Models:
95MAX
155MAX
200MAX
MAXTOP
195DCS
300DCS
It is always important to assess how the operation of any
HRV/ERV may interact with vented combustion equipment
(ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
200ERV
200ERVD
NEVER install a ventilator in a situation where its normal
operation, lack of operation or partial failure may result
in the backdrafting or improper functioning of vented
combustion equipment!!!
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
Installing Contractor
Telephone / Contact
Serial Number
Installation Date
Model
* LEAVE FOR HOMEOWNER
NOTE: Due to ongoing research and product development, specifications,
ratings and dimensions are subject to change without notice.
TI-84R-NE
0112
Download from Www.Somanuals.com. All Manuals Search And Download.
ERV Quest ions & Answers
What is the difference between an HRV
and damp situation. In fact, about 2/3 of the energy
used by the air conditioner system is to remove
moisture. Therefore, when ventilating in the summer,
less moisture brought into the home means less work
for the air conditioner, and energy savings for you.
and an ERV?
The core in an HRV (Heat Recovery Ventilator)
transfers heat from one air stream to the other. This is
called sensible heat. The term ERV (Energy Recovery
Ventilator) is usually used to describe a unit with an
enthalpic core that transfers moisture as well as heat
from one air stream to the other. This (moisture
transfer) is called latent heat.
During the winter, an ERV recovers some humidity
from the exhaust air, reducing the need for humidification
,
if the required ventilation rate would make the home
too dry.
Enthalpic - what does it mean?
Enthalpy is the term used to describe the energy
content of air. This energy is a combination of the
sensible and latent heat. Therefore, a core which
transfers energy is called an enthalpic core.
What's the difference between this type of
core and a rotary type?
Here's a list of characteristics of the fixed plate core.
1. No rotating parts, so maintenance is easy and the
unit lasts a long time.
2. It is very flexible in terms of installation.
3. The core can easily be changed.
4. Because the supply and exhaust air streams are
completely separate, there is very little cross
leakage of any dust or germs.
Is an ERV better than an HRV?
NOT NECESSARILY!! In cold climates such as most
of North America, an HRV works better than an ERV.
This is because the air inside the home during the
winter months will be more humid than the outside air.
An ERV would transfer the latent heat (humidity) from
the exhaust air back into the incoming airstream. This
will aggravate moisture problems in the home and
encourage the growth of mold and mildew. If the air in
the home is too dry for comfort, an ERV will not help. A
humidifier should be used to increase the humidity to
a comfortable level.
Can the core become clogged with dust?
Because the surface of the core is a turbulent flow
area, dust sticks to it easily; however, because the
inside of the element is a laminar flow area, virtually no
dust sticks to it.
Where do you use an ERV instead
of an HRV?
An ERV is recommended for warm, humid areas with
heavy air conditioning use. As there is no defrost in an
ERV it is not recommended for areas where the
temperature drops below -4˚C (25˚F).
What is the maintenance?
About once a year you should use a vacuum cleaner
to remove the dust from the core's surface. DO NOT
WASH WITH WATER!!
Is an air filter needed?
To prevent clogging of the core, an air filter should
always be installed on the supply and exhaust sides of
the core.
Why transfer moisture in the summer
(cooling season)?
The enthalpic core will allow moisture to be transferred
from a humid air flow to a dry air flow. This property is
useful in the cooling season if an air conditioning
system is used to lower the indoor humidity. You will
then have dry, cool air in the exhaust of the ERV, and
warm humid air in the supply stream. With these
conditions, the ERV will be able to transfer the
moisture and heat of the supply air to the exhaust air.
In this way, the ERV will supply to the home air which
is cooler and drier than outside. Remember that an
ERV is not a dehumidifier, and on its own will not take
moisture out of the air.
How much ventilation do I need?
During seasons when your windows and doors are
closed, the ERV should operate continuously when
the dwelling is occupied, and either continuously or
intermittently when not occupied.
For most installations the ERV will normally be set to
operate continuously on low speed with the option of
going to high speed as the need arises. For example;
if you are entertaining and there is a large number of
people present (some may be smoking), the unit
should be switched to high speed.
So why use an ERV?
A properly operating air conditioner will not only lower
the temperature in your house, but will also lower the
humidity level. This prevents an uncomfortable cold
Your ERV may be equipped with automatic or manual
switches, but all ERVs will have a manual speed
control override.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 95MAX
PERFORMANCE
HVI CERTIFIED
ENGINEERING DATA
Net supply airflow in cfm (L/s) against external static pressure
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
E.S.P
cfm
89
78
64
36
L/s
@ 0.1” (25 Pa)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
(42)
(37)
(30)
(17)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, .8 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
Maximum Temperature Recovery
74%
80%
MOUNTING THE HRV - Four threaded inserts at corners of the
cabinet designed to accept PVC reinforced polyester straps that are
supplied with the unit.
Sensible Effectiveness
@ 64 cfm (30 L/s) (CSA C439M)
Sensible Efficiency
@ 64 cfm (30 L/s)
32˚F (0˚C)
75%
75%
DEFROST - Recirculating defrost system.
Sensible Efficiency
@ 64 cfm (30 L/s) -13˚F (-25˚C)
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
VAC @ 60HZ
120
35
CONTROLS - ControlAir 15
WATTS / Low speed
WATTS / High speed
Amp rating
136
0.8
WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs. (25.4 kg)
DIMENSIONS 95MAX inches (mm)
18.5"
(470 mm)
Hanging
straps (4)
knockout for
side mounting of
EXHAUST return port
6" round collar
Threaded
inserts (4)
at corners
converted to oval
18.5"
(470 mm)
EXHAUST
Stale Air
to outside
SUPPLY
Fresh air
5" round collar
Removably
Heat Recovery
Core
from outside
5" round collar
EXHAUST
Return air
from building
SUPPLY
Fresh air
to building
6" round
(conv. to oval)
collar
minimum
18 inches (459 mm)
required for
Choice of port location
Knockouts on top and
side of unit (use 1 only)
6" round (conv. to oval)
collar supplied
service access
Drain Pan
Drain spout
16"
(406 mm)
FRONT
SIDE
TOP
OPTIONS
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150 mm)
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-186 Weatherhoods, Two - 5” (125 mm)
c/w 1/4” (6 mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: ________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: ________________________________
TI-113-NE
0103
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 155MAX
PERFORMANCE
Net supply airflow in cfm (L/s) against external static pressure
HVI CERTIFIED
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
E.S.P
cfm
169
161
150
130
56
L/s
@ 0.1” (25 Pa)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
(80)
(76)
(71)
(61)
(26)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.0 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
Maximum Temperature Recovery
Sensible Effectiveness
83%
76%
@ 64 cfm (30 L/s)
(CSA C439M)
DEFROST - Recirculating damper defrost system.
Sensible Efficiency
@ 64 cfm (30 L/s)
32°F (0OC)
70%
70%
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
Sensible Efficiency
@ 64 cfm (30 L/s) -13°F (-25OC)
VAC @ 60HZ
120
49
CONTROLS - ControlAir 15
WATTS / Low speed
WATTS / High speed
Amp rating
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)
120
1.0
DIMENSIONS 155MAX inches (mm)
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FILTERS
RECIRCULATING
DEFROST
DAMPER
BLOWERS
MOTOR
CORE
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
32 5/8"
(828)
14 3/4"
(375)
CONDENSATE DRAINS
*All Duct Connections 6" (150mm)
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150 mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150 mm)
99-186 Weatherhoods, Two - 6” (150 mm)
c/w 1/4” (6 mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad.
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-92-NE
0103
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 200MAX
PERFORMANCE
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
232 (109)
223 (105)
215 (102)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.
195
189
(92)
(89)
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are
supplied with the unit.
Maximum Temperature Recovery
81%
74%
Sensible Effectiveness
@ 117 cfm (55 L/s) (CSA C439M)
DEFROST - Recirculating damper defrost system.
Sensible Efficiency
@ 117 cfm (55 L/s) 32˚F (0˚C)
65%
66%
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
Sensible Efficiency
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
@ 117 cfm (55 L/s) -13˚F (-25˚C)
VAC @ 60HZ
120
87
CONTROLS - ControlAir 15
WATTS / Low speed
WATTS / High speed
Amp rating
WEIGHT 71 lbs. (32.5 kg SHIPPING WEIGHT 73 lbs. (33.5 kg)
164
1.4
DIMENSIONS 200MAX inches (mm)
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FILTERS
RECIRCULATING
DEFROST
DAMPER
BLOWERS
MOTOR
CORE
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
for servicing unit.
32 5/8"
(828)
14 3/4"
(375)
CONDENSATE DRAINS
*All Duct Connections 6" (150mm)
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
PROJECT: __________________________________________
Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-99-NE
0103
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Model MAXTOP
PERFORMANCE
ENGINEERING DATA
HVI CERTIFIED
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
196
(93)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
188
178
165
149
(89)
(84)
(78)
(71)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
Maximum Temperature Recovery
Sensible Effectiveness
@ 117 cfm (55 L/s )
80%
72%
MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
(CSA C439M)
Sensible Efficiency
DEFROST - Recirculating damper defrost system.
@ 117 cfm (55 L/s) 32OF (0°C)
64%
70%
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
Sensible Efficiency
@ 67 cfm (31 L/s) -13OF (-25°C)
VAC @ 60HZ
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
120
74
WATTS / Low speed
WATTS / High speed
Amp rating
CONTROLS - ControlAir 15
164
1.4
WEIGHT 87 lbs. (39.5 kg) SHIPPING WEIGHT 89 lbs. (40.5 kg)
DIMENSIONS MAXTOP inches (mm)
ALL DUCT CONNECTIONS
ARE 6" (150 mm)
CONTROLS
7 1/2"
(191 mm)
STALE AIR
EXHAUST
FRESH AIR
SUPPLY
TO BUILDING
25 1/2 "
(648 mm)
SUPPLY OF
FRESH AIR
STALE AIR
RETURN FROM
BUILDING
18"
(457 mm)
¤
22 1/2"
(572 mm)
26 1/2"
(673 mm)
*Service Clearance
25" (635 mm)
DRAIN
CONNECTION
FRONT VIEW
SIDE VIEW
TOP VIEW
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-100-NE
0103
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 195DCS
PERFORMANCE
ENGINEERING DATA
HVI CERTIFIED
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. The two cores are arranged for highly efficient counter
current airflow.
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
203
(96)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
191
182
167
155
(90)
(86)
(79)
(73)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.5 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
Maximum Temperature Recovery
Sensible Effectiveness
@ 117 cfm (55 L/s)
88%
88%
MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
(CSA C439M)
Sensible Efficiency
DEFROST - Damper defrost system.
@ 117 cfm (55 L/s) 32OF (0°C)
80%
77%
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
Sensible Efficiency
@ 117 cfm (55 L/s) -13°F (-25OC)
VAC @ 60HZ
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
120
100
173
1.5
WATTS / Low speed
WATTS / High speed
Amp rating
CONTROLS - ControlAir 15
WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg)
DIMENSIONS 195DCS inches (mm)
METAL CLASPS
FILTER
MOTOR
STALE AIR
FROM INSIDE
STALE AIR
TO OUTSIDE
Ports
6" (150 mm)
Ports
7" (178 mm)
FILTER
BLOWERS
*NOTE:
Front clearance
FRESH AIR
FROM OUTSIDE
FRESH AIR
TO INSIDE
of 25 inches (635 mm)
is recommended
for servicing unit.
49"
(1245)
DEFROST
DAMPER
14 3/4"
(375)
CONDENSATE
DRAINS
DEFROST AIR
FROM INSIDE
99-160 Duct Heater w/ Electronic SCR Thermostat,
1 Kw, 7” (178 mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-161 Duct Heater w/ Electronic SCR Thermostat,
2 Kw, 7” (178 mm)
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-186 Weatherhoods, Two - 6” (150 mm)
c/w 1/4” (6mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad.
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-101-NE
0112
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 300DCS
ENGINEERING DATA
PERFORMANCE
Net supply airflow in cfm (L/s) against external static pressure
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams The two cores are arranged for highly efficient counter
current airflow.
HVI CERTIFIED
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
265 (125)
260 (123)
250 (118)
235 (111)
220 (104)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 2.9 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
Maximum Temperature Recovery
Sensible Effectiveness
@ 117 cfm (55 L/s)
90%
90%
(CSA C439M)
DEFROST - Damper defrost system.
Sensible Efficiency
@ 117 cfm (55 L/s) 32°F (0OC)
79%
75%
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
Sensible Efficiency
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
@ 117 cfm (55 L/s) -13°F (-25OC)
VAC @ 60HZ
120
150
333
2.9
WATTS / Low speed
WATTS / High speed
Amp rating
CONTROLS - ControlAir 15
WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg )
DIMENSIONS 300DCS inches (mm)
METAL CLASPS
FILTER
MOTOR
STALE AIR
FROM INSIDE
STALE AIR
TO OUTSIDE
Ports
6" (150 mm)
Ports
7" (178 mm)
FILTER
BLOWERS
*NOTE:
Front clearance
FRESH AIR
FROM OUTSIDE
FRESH AIR
TO INSIDE
of 25 inches (635 mm)
is recommended
for servicing unit.
49"
(1245)
DEFROST
DAMPER
14 3/4"
(375)
CONDENSATE
DRAINS
DEFROST AIR
FROM INSIDE
99-160 Duct Heater w/ Electronic SCR Thermostat,
1 Kw, 7” (178 mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-161 Duct Heater w/ Electronic SCR Thermostat,
2 Kw, 7” (178 mm)
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad.
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad.
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and
a 5 year replacement parts warranty.
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-102-NE
0112
10
Download from Www.Somanuals.com. All Manuals Search And Download.
®
Model 200ERV
CLEAN • FRESH • AIR
PERFORMANCE
ENGINEERING DATA
Net supply airflow in cfm (L/s) against external static pressure
LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water
vapour between the two airstreams. It is easily removed for
cleaning or service.
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
214 (101)
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
206
193
184
170
(97)
(91)
(87)
(80)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
High speed - 120 VAC, 182 Watts.
FILTERS - Washable air filters in exhaust and supply air streams.
Sensible Effectiveness
@127cfm (60 L/s)
67%
MOUNTING THE ERV - Four threaded inserts at corners of case
designed to accept four PVC reinforced polyester straps that are
supplied with the unit.
(CSA C439M)
Sensible Efficiency 32°F (0°C)
Total Efficiency
60%
55%
CASE - Twenty gauge prepainted galvanized steel (G60) for
superior corrosion resistance. Insulated to prevent exterior
condensation.
VAC @ 60HZ
120
70
CONTROLS - ControlAir 15
WATTS / Low speed
WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 65 lbs. (29.6 kg)
DIMENSIONS 200ERV inches (mm)
*
All Duct Connections 6"(150mm)
ENTHALPIC CORE
MOTOR
STALE AIR
FROM INSIDE
FRESH AIR
TO INSIDE
FILTERS
BLOWERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
for servicing unit.
31"
(787)
14 3/4"
(375)
WARRANTY
OPTIONS
Units carry a 5 year warranty on the energy recovery core and
replacement parts.
99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)
99-105 Deluxe Programmable Control includes
Programmable Time Clock, Dehumidistat
All units conform to CSA and UL standards.
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to
accept remotely mounted Control Pad
ERVs are not recommended for regions where the
design temperature is below 25°F (-4°C)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
TI-98E
0105
11
Download from Www.Somanuals.com. All Manuals Search And Download.
®
Model 200ERVD
CLEAN • FRESH • AIR
ENGINEERING DATA
LATENT RECOVERY/MOISTURE TRANSFER CORE
PERFORMANCE
Net supply airflow in cfm (L/s) against external static pressure
The cross-flow energy recovery core transfers heat and water vapour
between the two airstreams. It is easily removed for cleaning or service.
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
214 (101)
MOTORS AND BLOWERS - Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
High speed - 120 VAC, 182 Watts.
@ 0.2” (50 Pa)
@ 0.3” (75 Pa)
@ 0.4” (100 Pa)
@ 0.5” (125 Pa)
206
193
184
170
(97)
(91)
(87)
(80)
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV - Four threaded inserts at corners of case
designed to accept four PVC reinforced polyester straps that are
supplied with the unit.
Sensible Effectiveness
@127cfm (60 L/s)
67%
(CSA C439M)
DEFROST - Damper defrost system.
Sensible Efficiency 32°F (0°C)
Total Efficiency
60%
55%
CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
DRAIN CONNECTIONS - Two - 1/2” (12mm) O.D.
CONTROLS - ControlAir 15
VAC @ 60HZ
120
70
WATTS / Low speed
WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 65 lbs. (29.6 kg)
DIMENSIONS 200ERVD inches (mm)
FRESH AIR
FROM OUTSIDE
ENTHALPIC
CORE
*
All Duct Connections 6"(150mm)
MOTOR
DAMPER
STALE AIR
TO OUTSIDE
DEFROST
PORT
FILTERS
BLOWERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
FRESH AIR
TO INSIDE
STALE AIR
FROM HOUSE
for servicing unit.
3
31"
14
/4"
(787)
(375)
CONDENSATE DRAINS
OPTIONS
WARRANTY
99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)
99-105 Deluxe Programmable Control includes
Programmable Time Clock, Dehumidistat
Units carry a 5 year warranty on the energy recovery core and
replacement parts.
All units conform to CSA and UL standards.
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad.
ERVs are not recommended for regions where the
design temperature is below 25°F (-4°C)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
DATE: __________________________
511 McCormick Blvd.
London, Ontario N5W 4C8
Ph: (519) 457-1904
PROJECT: __________________________________________
Fx: (519) 457-1676
Email: [email protected]
MECHANICAL CONTRACTOR: _____________________________
12
TI-200ERVD
0105
Download from Www.Somanuals.com. All Manuals Search And Download.
FUNCTION & CONTROL
Operat ing t he Cont rolAir 15
Self Test
Each time the HRV/ERV is powered/energized the self
test function will automatically initiate. During the self
test the HRV/ERV will cycle through all the speeds
available (1-5), test the damper motor operation and will
default back to the previous mode/speed selection,
(factory default is Speed 1). Total self test duration is
approximately 1 min. 30 sec.
Plugging in the HRV/ERV energizes the unit. A self test
function will be performed every time the HRV/ERV is
energized (refer to “Self Test” for more details). After
the self test has completed successfully the HRV/ERV
will default to Speed 1. This is the factory default
setting. Follow the instructions found on the HRV/ERV
door to select desired mode and speed, or refer to the
instructions found on the following page.
Aut omat ic Defrost Operat ion
(Not on all models)
Control Module
The advanced technology of the digital microprocessor
automatically activates the defrost system only as it is
needed. To be an efficient heat recovery device, the
HRV/ERV must effectively provide for core defrost as well
as providing efficient heat exchange. As outdoor
conditions cool, the temperature sensor (thermistor) tracks
the supply air temperature. The thermistor then sends its
signal to the microprocessor (circuit board) which initiates
only the defrost cycle time required to clear the core. On
recirculating defrost models, the core is defrosted when
the supply air port is automatically blocked off and exhaust
air is redirected back through the HRV/ERV. On damper
defrost models, the core is defrosted when the supply air
port is automatically blocked off and the warm air
surrounding the HRV/ERV is drawn in through the defrost
port. The mode indicator will flash RED during the defrost
cycle. This dramatic advance makes more energy
available for recovery as the unit spends less time in
defrost mode. By optimizing the defrost cycle, the
HRV/ERV combines money saving performance with a
well designed and reliable control system.
Control Pad
Cont rolAir 15
Exploded view
Glossary
Removing and relocat ing t he
Cont rol Pad
DEFROST MODE - to ensure reliable operation during cold
weather, the HRV/ERV will automatically cycle through its
defrost mode as needed. (not on all models)
The Control Pad can be removed and installed in a
remote location (100’ wire length max). The Control Pad
can be installed in a 2x4 box with a “Decora” type cover
plate or can be installed in the optional “Ventilation
Dehumidistat” or “Air Sentry”. When the Control Pad is
installed in a remote location, all optional controls will still
be wired to the Control Module on the HRV/ERV. When
remotely mounted on its own, the Control Pad is wired to
the Control Module by 3 wire (min. 20 gauge). Connect
the colour coded terminals to the corresponding terminals
on the Control Module. When the Control Pad is remotely
mounted in the Ventilation Dehumidistat or Air Sentry,
refer to optional controls page for wiring requirements.
DEHUMIDISTAT - a control device that senses the amount of
moisture in the air and will activate high speed fan operation
when the air moisture level exceeds the control setting. The
optimum air moisture level (or relative humidity [Rh]) in the
typical home is in the range of 30 to 40% Rh.
RESET - whenever resetting of the HRV/ERV is required,
simply disconnect power for 30 seconds.
STANDBY MODE - the HRV/ERV is energized and waiting for fan
operation to be initiated by a remote device or manual override.
THERMISTOR - the HRV/ERV's temperature sensor which
measures electrical resistance in a known manner, as
outdoor temperatures fluctuate.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
To select mode of operat ion for Cont rolAir 15
Press and hold the fan selection button on the Control Pad. After 5 seconds the control will
begin to cycle each mode holding each for 2 seconds. Release the button when the desired
mode of operation is reached.
Modes of Operation
LED Indication
OFF
No LED’s illuminated HRV/ERV is off, no controls will
initiate operation.
Standby / On
20 On / 40 Off
Steady Green LED and Yellow LED to indicate speed
HRV/ERV will run at speed selected in ventilation mode.
Standby mode is indicated by no speed indicator
illuminated. Optional remote controls will override standby
or selected speed into high speed.
Flashing Green LED and Yellow LED to indicate speed.
HRV/ERV will operate in ventilation mode at speed selected
for 20 minutes and OFF for 40 minutes.
Recirculation
*Note: Not available on all models
Steady Red LED and Yellow LED to indicate Speed.
HRV/ERV will operate in recirculate mode at the selected
speed. Optional remote controls will override unit into high
speed ventilate mode.
To select speed
Momentarily press fan selection button and release. HRV/ERV will move into next speed.
OFF is indicated by no yellow LED illuminated. Speed 1 is the first yellow LED. Speed five is
indicated by a flashing speed 4 LED.
Automatic Defrost
During cold outdoor conditions the HRV/ERV will occasionally go into an automatic defrost
function, which will prevent ice from forming on the core. Defrost is indicated by a flashing Red
LED indicator.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Cont rolAir 15
OPTIONAL REMOTE CONTROLS
PROGRAMMABLE VENTILATION CONTROLLER (PVC)
NEW! AIR SENTRY™ AIR QUALITY SENSOR
LOCATION: Hallway, kitchen, office
& work place (connect 1/unit only)
• Advanced digital remote.
• Digital dehumidistat.
LOCATION: Kitchen, basement,
work place (connect 1/unit only).
• Digital Air Quality Monitor.
• Status light indicates fan speed.
• Increases ventilation to remove
odours and contaminants.
™
ENTRY
IR Q
IGITAL A
IR S
A
ENSOR
UALITY S
D
• Full fan speed control.
•
•
AIR SENTRY™ Air Quality Sensor built-in.
Recirculation mode (on compatible
HRV/ERVs).
• Among gases detected are
FAN SPEED INDICATOR
cigarette smoke and formaldehyde.
• 100' (30 m) maximum wire length.
• Knockout designed to accept Control
Pad when remotely mounted.
• 7 day, 24 hour programmable timer.
• Digital display and status lights.
• 100' (30 m) maximum wire length.
PART NO. 99-109
Connects to RED, GREEN and YELLOW terminals.
PART NO. 99-105
Connects to RED, ORANGE, GREEN and YELLOW terminals.
*NOTE: This device is NOT compatible with the PVC.
*NOTE: This device is NOT compatible with the Air Sentry.
NEW! VENTILATION DEHUMIDISTAT
Cont rolAir 15
LOCATION: Central location in house.
• Dehumidistat activates high speed
TION
over-ride when humidity level in home
VENTILA
T
A
DEHUMIDIST
Control Module
Control Pad
• All controls wire to
matching colour on
the Control Module.
exceeds setting.
• Knockout designed to accept Control
Pad when remotely mounted, giving full
HRV/ERV functionality & control from
remote location.
• Control Pad can be
removed and mounted
in a remote location.
•
Control Pad mounts
in a 2”x 4” box or can
be mounted in the
optional Ventilation
Dehumidistat or
PART NO. 99-250
Connects to BLACK, RED, GREEN and YELLOW terminals.
Air Sentry.
*Replaces 99-116 DVC & 99-230 VRD.
*Only compatible with ControlAir 15 electronics.
• Full fan speed control.
•
Three Modes of Operation
- Standby/ON
- 20 ON / 40 OFF
-
Recirculation
(on compatible HRV/ERVs)
DIGITAL ELECTRONIC TIMER (DET)
LOCATION: Bathrooms & kitchen
•
•
Connect up to 8 on 300' (91 m) wire max.
If a PVC or Air Sentry is used, connect
up to 5 on 300' wire max.
• Touch pad operation.
• 20/40/60 minute status lights.
• Compact wall mount unit.
• Mounts in 2x4 box.
•
Shown with “decora” cover plate (99-107W).
PART NO. 99-104
*See individual control instructions for more details.
Connects to RED, GREEN and YELLOW terminals.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
0011
USING THE DEHUMIDISTAT
Some models have a built-in dehumidistat (an
optional remote wall mount dehumidistat can be
installed, see Optional Remote Controls), to
control harmful, excess humidity during the
heating season. The dehumidistat operates in
% of RH (relative humidity) with 80 being high
and 20 being low. The average person is
comfortable between 30-45%.
exceeds the set point on the control. Once the
humidity in the house is reduced, the HRV/ERV
will revert back to its previous setting.The
dehumidistat should be set to off for all seasons
except the heating season.
Note: If your HRV/ERV is equipped with an internal
and an external dehumidistat, the internal one can be
turned off and not used.
The dehumidistat will overide the ventilator to
high speed when the moisture level in the home
Internal Dehumidistat with External Control Knob
16
Download from Www.Somanuals.com. All Manuals Search And Download.
DIMENSIONS 95MAX inches (mm)
18.5"
(470 mm)
Hanging
straps (4)
knockout for
Threaded
side mounting of
inserts (4)
EXHAUST return port
at corners
6" round collar
converted to oval
18.5"
(470 mm)
EXHAUST
Stale Air
SUPPLY
Fresh air
to outside
5" round collar
Removably
Heat Recovery
Core
from outside
5" round collar
EXHAUST
Return air
from building
SUPPLY
Fresh air
minimum
Choice of port location
Knockouts on top and
side of unit (use 1 only)
6" round (conv. to oval)
collar supplied
to building
18 inches (459 mm)
6" round
required for
(conv. to oval)
service access
collar
Drain Pan
Drain spout
16"
(406 mm)
FRONT
SIDE
TOP
95 MAX Port Specificat ions
In order to make the 95 Max as space efficient as
possible, the INDOOR supply and return ports are
converted from round to oval shape. Overall size of the
port remains the same. Simply bend a standard duct
fitting to the correct shape, and attach to the oval port
using the same method as for a round port.
The 95 Max Heat Recovery Ventilator (HRV) has been
designed to allow the installer to choose between two
possible positions on the cabinet for the INDOOR
EXHAUST (return from building) port. Illustrations in this
manual show standard (side mounted) port location . The
same specifications apply to both 95 Max setups,
regardless of which port position is selected.
(6 inch)
diameter
Same Circumference
Round port bent to oval
¤
HEAEVE
NTIL
HRVs
)
¤
HEAVERY
NTILA
HRs
)
SIDE MOUNTED PORT
standard location
TOP MOUNTED PORT
alternate location
95 MAX Air Flow
Variable Port Location
Stale air enters the FRONT RIGHT side port. The air will
pass down the front half of the core, then up the back half
of the core and out the RIGHT REAR port.
Variable Port Location / Installation (Model 95 Max only)
The exhaust return port collar is not factory installed.
Installer may choose either side mounted or alternate top
mounted port by simply removing one of the two knock-out
plates and attaching a port collar (supplied). To remove
knock-out plate, insert a utility knife into the knock-out
slits and trace them completely to puncture protective film
underneath. Then, cut the solid tabs between the slits, using
tin snips or side cutters, and remove the knock-out plate. If
any protective film still blocks the opening, remove it now.
Fresh outdoor air will enter the LEFT REAR port and
pass down the back half of the core. It will then pass up
the front half of the core, and out the LEFT FRONT port.
This unique configuration allows the air to actually travel
through the core twice, making the 95 MAX almost as
efficient as a double core unit.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Location
The HRV/ERV must be located in a heated space where it will
be possible to conveniently service the unit. Typically the
HRV/ERV would be located in the mechanical room or an
area close to the outside wall where the weatherhoods will be
mounted. If a basement area is not convenient or does not
exist, a utility or laundry room may be used
Connecting Appliances to the HRV/ERV
It is not recommended that any of the following appliances be
connected to the HRV/ERV:
• clothes dryer
• range top
• stovetop fan
Attic installations are not normally recommended due to:
A) the complexity of work to install
• central vacuum system
B) freezing conditions in the attic
Lint, dust or grease will collect in the HRV/ERV, damaging
the unit.
C) difficulty of access for service and cleaning
NOTE: Connecting any of these to the HRV/ERV will
invalidate your warranty.
Sufficient clearance at the front of the access door is required
for servicing the air filters and core. A minimum of 25" (635
mm) clearance is recommended so the door can be opened.
Four PVC reinforced polyester hanging straps are provided
for hanging the HRV/ERV from the basement floor joists.
Installing the Drain Line and P-Trap (not on all models)
When defrosting, the HRV/ERV may produce some
condensation. This water should flow into a nearby drain, or
be taken away by a condensate pump. The HRV/ERV and all
condensate lines must be installed in a space where the
temperature is maintained above the freezing point.
Mounting
The hanging straps should be attached to the unit at the top
end corners (mounting screws are already located on the
HRV/ERV case). Securely fasten the other end of the
straps to the floor joists with wide head nails (not
supplied), making sure the unit is level. The straps are
designed to reduce the possibility of noise, resonance or
harmonics; therefore using the full length of the strap between
the HRV/ERV and the floor joists is recommended.
At the bottom of the cabinet there are prepunched hole for the
drain pan connectors (see below). Insert the drain spout
through the hole in the drain pan. Do not forget the “O Ring”
which seals the connector to the pan. REMEMBER TO HAND
TIGHTEN ONLY the washer and lock nut which hold the drain
connector in place.
Electrical
Construct a P-Trap using the plastic tee connector. Cut two
The HRV/ERV should be plugged into a standard designated
(120VAC) electrical outlet with ground. It is not recommended
that an extension cord be used for this appliance. If further
wiring is required, then a licensed electrician should make all
electrical connections. It is recommended that a separate 15
amp/120 volt circuit be used.
the “T”
lengths of hose and connect each piece to an end of
fitting, then connect the other ends to the two drain
spouts. Allow the "T" fitting to point upwards, and
connect the drain line. Tape or fasten base to avoid
any kinks. This creates a “trap” which will hold some
condensate and prevent odours from being drawn up
the hose and into the fresh air supply of the HRVERV
.
WARNING:
In order to prevent electric shock when cleaning or servicing
the HRV/ERV, it is extremely important to confirm the
polarity of the power line that is switched by the safety
(disconnect) switch. The hot line (black) is the proper line to
be switched. To confirm the proper polarity, use a voltmeter
or test lamp to ensure there is no power after the switch
when the door is open. Check between that point and ground
(on the cabinet). This must be done as dwellings are
occasionally wired improperly. Always make sure that the
HRV/ERV is properly grounded.
PRE-PUNCHED HOLES (2)
DRAIN PAN
DRAIN PAN
DRAIN
SPOUT
DRAIN
SPOUT
TAPE
TEE
CONNECTOR
TO DRAIN
Forming t he "P" Trap
18
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING AIR DUCTS
To minimize air flow restriction, the flexible insulated duct that
connects the two outside weatherhoods to the HRV/ERV
should be stretched tightly and be as short as possible.
A well designed and installed ducting system will allow the
HRV/ERV to operate at its maximum efficiency.
Always try to keep duct runs as short and straight as possible.
See Installation Diagrams for various installation options.
Twisting or folding the duct will severely restrict air flow. See
below for the recommended connection of flexible insulated
ducts to the the outside weatherhoods and the HRV/ERV.
Out side Weat herhoods
The fixed covered hoods have a built-in bird screen with a
1/4" (6 mm) mesh to prevent foreign objects from entering
the ductwork.
WEATHERHOOD INSTALLATION
BELT OF OUTSIDE WALL
INSULATED FLEXIBLE
DUCTING
THERMAL COLLAR
HOOD
Locat ing t he Int ake
Weat herhood
•
Should be located upstream (if there are prevailing winds)
from the exhaust outlet
•
•
At least 6' (2 m) from the exhaust weatherhood
At least 6' (2 m) away from dryer vents and furnace
exhaust (medium or high efficiency furnaces)
A minimum of at least 6' (2 m) from driveways, oil fill
pipes, gas meters, or garbage containers
1/ Thermal Collar slides over galvanized
sleeve of Weatherhood.
2/ Fasten Thermal Collar to Belt.
•
•
BIRD
SCREEN
3/ Slide the Insulated Flexible Ducting over
At least 18" (457 mm) above the ground,
the Weatherhood’s galvanized sleeve and
fasten it to the Thermal Collar.
4/ Hood is hinged to allow for easy access
for cleaning of bird screen.
or above the depth of expected snow accumulation
At least 3' (1 m) from the corner of the building
Do not locate in a garage, attic or crawl space
•
•
Warmside Duct ing
To maximize airflow in the ductwork system, all ducts should
be kept short and have as few bends or elbows as possible.
Forty-five degree elbows are preferred to 90° elbows. Use
“Y” tees instead of 90° elbows whenever possible.
Locat ing t he Exhaust
Weat herhood
•
•
At least 6' (2 m) from the ventilation air intake
At least 18" (457 mm) above ground or above the depth
of expected snow accumulation
All duct joints must be fastened with screws, rivets or duct
sealant and wrapped with a quality duct tape to prevent
leakage. We recommend aluminum foil duct tape.
•
•
At least 3' (1 m) away from the corner of the building
Not near a gas meter, electric meter or a walkway
where fog or ice could create a hazard
•
Not into a garage, workshop or other unheated space
Galvanized ducting from the HRV/ERV to the living areas
in the house is recommended whenever possible, although
flexible duct can be used in moderation if necessary.
When installing the weatherhood, its outside perimeter
must be sealed with exterior caulking.
To avoid possible noise transfer through the ductwork
system, a short length (approximately 12 " or 300 mm) of non-
metallic flexible insulated duct should be connected between
the HRV/ERV and the supply/ exhaust ductwork system.
Installing the ducting from the
weatherhoods to the HRV/ERV
The inner and outer liners of the flexible insulated duct must
be clamped to the sleeve of the weatherhoods (as close to
the outside as possible) and the appropriate port on the
HRV/ERV. It is very important that the fresh air intake line
be given special attention to make sure it is well sealed. A
good bead of high quality caulking (preferably acoustical
sealant) will seal the inner flexible duct to both the
HRV/ERV port and the weatherhood prior to clamping.
The main supply and return lines to/from the HRV/ERV
must be 6 inches (150 mm) minimum. Branch lines to the
individual rooms may be as small as 4 inches (100 mm),
but 5 inch (125 mm) lines are preferred .
All ducts running through attics and unheated spaces must
be sealed and insulated to code.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
SUPPLY AIR DUCTING
In homes without a forced air furnace, fresh air should be
supplied to all bedrooms and living areas, excluding
bathrooms, kitchen and utility areas. It should be supplied
from high wall or ceiling locations. Grilles that diffuse the air
comfortably such as the Techgrille™ are recommended.
Dampers and Grilles
The use of balancing dampers and/or adjustable grilles to
balance the flow rates into various rooms is recommended.
We suggest TECHGRILLE™ air diffusers.
• The TECHGRILLE™ is available in 4", 5", 6" and 8" (100,
125, 150 and 200 mm) sizes.
If the floor is the only option available, then special care
should be taken in locating grilles. Areas such as under
baseboard heaters will help to temper the air. Also optional
inline duct heaters are available for mounting in the supply
duct work to add heat if required.
• The TECHGRILLE™ is a round, fully adjustable grille,
which provides superior, quiet air distribution.
In homes with a forced air furnace, you may want to connect
the HRV/ERV to the furnace ductwork (see information below).
AIR FLOW
SUPPLY
Direct Connection to Furnace Ductwork
Should you wish to hard duct the supply air directly into the
cold air return of the furnace, remember to check the air
flow balance of the HRV/ERV with the furnace fan both
"ON" and "OFF" to determine that it does not imbalance the
unit more than 10%. Also, it is advisable to include a short
length of fabric flex duct or other non-metallic connector in
this hard ducted line in order to keep the HRV/ERV
separately grounded (electrically) from the furnace. This will
avoid a possible shock hazard to service people if a short to
ground develops in one of the devices.
AIR FLOW
EXHAUST
Indirect Connect ion t o Ductwork
If permitted by local codes, an indirect connection may be
made between the HRV/ERV supply duct and the furnace
return plenum. The fresh air from the unit may be directed
at a grille installed in the cold air return duct of the furnace.
The fresh air supply outlet from the unit should be no closer
than 4 inches (100 mm) and no more than 12 inches (300
mm) from the grille.
Techgrille Air Diffusers
We recommend the use of high mounted wall returns with
grilles. The exhaust air duct from the kitchen should never be
connected to a range hood. Instead, the exhaust grille
should be mounted high on the wall at least 4 feet (1.2 m)
horizontally away from the stove. A "flip-up", 6" X 10" (150 X
250 mm) rectangular kitchen grille with removable grease
filter is available (Part No. 10-002).
St ale Air Exhaust Syst em
The stale air exhaust system is used to draw air from the
points in the house where the worst air quality problems
occur. It is recommended that return air ducts are installed
in the bathroom, kitchen, and laundry room. Additional
return air ducts from strategic locations (i.e. greenhouse,
atrium, swimming pool, sauna, etc.) may be installed. Also,
the furnace return duct may be used to exhaust from. In this
method, the exhaust air is not ducted back to the HRV/ERV
with "dedicated lines" from bathrooms, kitchens, etc.
Instead, the exhaust air is drawn out of the cold air return of
the forced air furnace. This method has become popular
and provides good ventilation when installed in accordance
with the instructions. The furnace blower must be running
w hen the unit is operating for this system to
be effective.
Dampers should be located just prior to the HRV/ERV to
balance the stale air exhausted out of the house with a fresh
air supply entering the house.
Removable
filter
Kit chen Grille
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Inst allat ion Diagrams
Example diagram only - duct configuration may
change depending on model
Partially Dedicated System
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN
(Stale air drawn from key areas of home)
EXHAUST AIR from various parts of home.
i.e. bathrooms (if required), kitchens (if required).
Return Air
3’ min.
recommended
Outdoors
Cool Air
Return
*Unit is normally balanced on HIGH speed
with furnace blower ON.
Forced Air
Furnace
NOTES:
1. Furnace blower may be required to operate when HRV/ERV is on to provide good air distribution.
2. Weatherhood arrangement is for drawing purposes only. 6' (2 m) minimum separation required.
18" (460 mm) above grade minimum.
3. Due to the differences in pressure between the HRV/ERV and the equipment it is being
connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing
procedure found in the installation manual.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Example diagram only - duct configuration
may change depending on model
Simplified Installation
Option 1
(Return/Return Method)
Note: Option 1 is the preferred / recommended method
when doing a simplified installation.
DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
RETURN AIR
→ ꢀ
40" (1m) MINIMUM
3’ min.
recommended
Outdoors
Cool Air
Return
Forced Air
Furnace
NOTES:
1. Furnace blower may be required to operate when ventilation from HRV/ERV is required.
The furnace should be set to run continuously or interlocked with HRV/ERV.
2. A minimum separation of 40 inches (1 m) is required between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent
exhausting any fresh air.
4. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required.
Eighteen inches (460 mm) above grade minimum.
5. Due to the differences in pressure between the HRV/ERV and the equipment it is being
connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing
procedure found in the installation manual.
*Unit is normally balanced on HIGH speed
with furnace blower ON.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Example diagram only - duct configuration may
change depending on model
Simplified Installation
Option 2
(Supply/Return Method)
It may be necessary to
form an elbow in the supply
side ducting as shown
DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE
RETURN AIR
3’ min.
recommended
3’ min.
recommended
Outdoors
Forced Air
Furnace
Cool Air
Return
NOTES:
1. Furnace blower may be required to operate when ventilation from HRV/ERV is required.
The furnace should be set to run continuously or interlocked with HRV/ERV.
2. The exhaust air connection should be upstream of the supply air connection to prevent
exhausting any fresh air.
3. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required.
Eighteen inches (460 mm) above grade minimum.
4. Due to the differences in pressure between the HRV/ERV and the equipment it is being
connected to, the HRV/ERV's airflow must be confirmed on site, using the balancing
procedure found in the installation manual.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Example diagram only - duct configuration may
change depending on model
Fully Dedicated System
Please Note: It is the responsibility of the installer to ensure all ductwork is sized and
installed as designed to ensure the system will perform as intended. All air movement
devices have a performance curve. The amount of air (CFM) that an HRV/ERV will deliver is
directly related to the total external static pressure (E.S.P.) of the system. Static pressure is
a measure of resistance imposed on the blower by length of duct work/number of fittings
used in duct work, duct heater etc.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
PITOT TUBE AIR FLOW BALANCING
It is necessary to have balanced air flows in an HRV/ERV. The volume
of air brought in from the outside must equal the volume of air exhausted
by the unit. If the air flows are not properly balanced, then;
• The HRV/ERV may not operate at its maximum efficiency
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly
For general balancing it is sufficient to move the pitot tube around in
the duct and take an average or typical reading. Repeat this procedure
in the other (supply or return) duct. Determine which duct has the high-
est airflow (highest reading on the gauge). Then damper that airflow
back to match the lower reading from the other duct. The flows should
now be balanced. Actual airflow can be determined from the gauge
reading. The value read on the gauge is called the velocity pressure.
The Pitot tube comes with a chart that will give the air flow velocity
based on the velocity pressure indicated by the gauge. This velocity
will be in either feet per minute or metres per second. To determine the
actual airflow, the velocity is multiplied by the cross sectional area of the
duct being measured.
• Failure to balance HRV/ERV properly may void warranty
Excessive positive pressure may drive moist indoor air into the external
walls of the building where it may condense (in cold weather) and
degrade structural components. May also cause key holes to freeze up.
Excessive negative pressure may have several undesirable effects.
In some geographic locations, soil gases such as methane and radon
gas may be drawn into the home through basement/ground contact
areas. Excessive negative pressure may also cause the backdrafting of
vented combustion equipment.
This is an example for determining the airflow in a 6" duct.
The Pitot tube reading was 0.025 inches of water.
From the chart, this is 640 feet per minute.
The 6" duct has a cross sectional area of
The airflow is then:
=
[3.14
x
(6"÷12)2]÷4
Read the Application Warning on the front of this manual!
= 0.2 square feet
Prior to balancing, ensure that:
640 ft./min.
X
0.2 square feet = 128 cfm
1. All sealing of the ductwork system has been completed.
2. All of the HRV/ERV's components are in place and functioning properly.
3. Balancing dampers are fully open.
For your convenience, the cross sectional area of some common
round duct is listed below:
4. Unit is on HIGH speed.
DUCT DIAM. (inches)
CROSS SECTION AREA (sq. ft.)
5. Air flows in branch lines to specific areas of the house should be
adjusted first prior to balancing the unit. A smoke pencil used at the
grilles is a good indicator of each branch line's relative air flow.
6. After taking readings of both the stale air to the HRV/ERV duct and
fresh air to the house duct, the duct with the lower CFM ([L/s]
velocity) reading should be left alone, while the duct with the higher
reading should be dampered back to match the lower reading.
7. Return unit to appropriate fan speed for normal operation
5
6
7
0.14
0.20
0.27
The accuracy of the air flow reading will be affected by how close to
any elbows or bends the readings are taken. Accuracy can be
increased by taking an average of multiple readings as outlined in the
literature supplied with the Pitot tube.
BALANCING PROCEDURE
Pitot tube and gauge
The following is a method of field balancing an HRV/ERV using a Pitot tube,
advantageous in situations when flow stations are not installed in the duct-
work. Procedure should be performed with the HRV/ERV on high speed.
DUCT
AIR
The first step is to operate all mechanical systems on high speed, which
have an influence on the ventilation system, i.e. the HRV/ERV itself and
the forced air furnace or air handler if applicable. This will provide the
maximum pressure that the HRV/ERV will need to overcome, and allow
for a more accurate balance of the unit.
Pitot Tube Air Flow
Balancing Kit
c/w magnehelic gauge,
Pitot tube, hose and
FLOW
Pitot tube
Magnehelic gauge
carry case.
PART NO. 99-167
Drill a small hole in the duct (about 3/16"), three feet downstream of
any elbows or bends, and one foot upstream of any elbows or bends.
These are recommended distances but
the actual installation may limit the
amount of straight duct.
Place pitot tube a minimum of 18" from blower or elbows
The Pitot tube should be connected to a
magnehelic gauge or other manometer
capable of reading from 0 to 0.25 in. (0-
62 Pa) of water, preferably to 3 digits of
resolution. The tube coming out of the
top of the pitot is connected to the high
pressure side of the gauge. The tube
coming out of the side of the pitot is con-
nected to the low pressure or reference
side of the gauge.
Outdoors
Pitot
tube
Magnehelic
gauge
Pitot
tube
Note: Duct connections may vary,
depending on model.
Magnehelic
gauge
Insert the Pitot tube into the duct; point-
ing the tip into the airflow.
0102
25
Download from Www.Somanuals.com. All Manuals Search And Download.
BALANCING COLLAR INSTRUCTIONS
Push and turn with slotted
screwdriver. Damper
automatically locks when
pressure is released.
When connecting ductwork
to the collar, take note where
screws are located. Screws
should be located no further
than 1/2” from outside edge
of collar, so as not to impede
operation of the damper.
Hard/Rigid
ducting
1/2”
Installations where the HRV is ducted directly to
the return of a furnace may require additional
dampening on the fresh air to building duct.
This is due to the high return static pressures
found in some furnace installations.
Insulated flexible
ducting
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Maint enance Rout ine for HRV
(for ERV, see following page)
1. Inspect Exterior Hoods at least once a month.
Make sure exhaust and fresh air supply hoods are not
blocked or restricted by leaves, grass, or snow. In winter, it
is especially important to make sure snow is not blocking
the hoods or that frost has not built up on the wire mesh
(bird screen).
6. Clean Duct Work if Required
The duct work running to and from the HRV may
accumulate dirt. Wipe and vacuum the duct once every
year. You may wish to contact a Heating/Ventilation
company to do this.
7. General Maintenance - Twice a Year
WARNING: Blockage of hoods may cause an imbalance.
Wipe down the inside of the cabinet with a damp cloth to
remove dirt, bugs and debris that may be present.
2. Clean Air Filters (clean twice a year)
The standard filters equipped with your HRV are removable
and washable.
8. Cleaning the Fans
Fans may accumulate dirt causing an imbalance and/or
a) simply open access door and slide core out
b) remove filter clips
excessive vibration of the HRV. A reduction in the air flow
may also occur. In new construction this may result within
the first year due to heavy dust and may occur periodically
after that over time depending on the outdoor conditions.
c) once clips are removed filters can be taken off the core
to be rinsed with water or a combination of mild soap
and water. Do not clean in the dishwasher
d) to re-assemble, place clean filter(s) (wet or dry) back
into their positions against the core and return clips to
their original position
• unplug the HRV and open the service door
• remove the core
• remove ducting (metal and/or flexible insulated type)
from the red and/or blue ports which are connected
immediately inline with the fan assembly
• use a small brush, such as an old toothbrush or pipe
cleaner, and insert first
e) slide core back into its’ original position
3. Clean Core Twice a Year
a) open access door.
b) carefully grip ends of core and pull evenly outward.
Core may be snug, but will slide out of the channel
c) once removed from the cabinet remove filters
d) wash core in warm soapy water (do not use dishwasher)
e) install the clean filters
(a) through the large opening of the fan
assembly and then
(b) through the smaller opening in the end
of the fan assembly.
• scrub individual fan blades until clean. Avoid
moving or damaging balancing flat weight, clip is
usually found on one or more of the fan blades
• vacuum and wipe
f) install clean core
Note: Core installation label on the outer end of the core.
To install the clean core:
• reassemble making sure ducting is reattached firmly
and insulation and moisture barrier are sealed
and taped
a) first mount the bottom flange of the core guide into the
bottom H channel approximately 1/4” (6mm)
b) mount the left or right side flange of the core guide
approximately 1/4” (6mm) followed by the other side
c) mount the top flange of the core guide into the top H
channel approximately 1/4” (6mm).
Before attempting this task, thought should be given
to having a qualified service technician complete the
service work.
d) with all four corners in place and the core straight and
even, push hard in the centre of the core until the core
stops on the back of the cabinet.
NOTE: Core will appear to stick out from cabinet
approximately 1/8” (3mm). This is designed this way so
that the access door will fit tight against the core.
4. Motors - Maintenance Free
5. Drain (condensate) Line - Clean once a year
Inspect drain line, drain spout and “P” trap for blockage,
mould or kinks. Flush with warm soapy water and replace
if worn, bent or unable to clean.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Maint enance Rout ine for ERV
(for HRV, see previous page)
1. Inspect Exterior Hoods at least once a month
Make sure exhaust and fresh air supply hoods are not
blocked up or restricted by leaves, grass, or dirt.
5. Clean Duct Work if Required
The duct work running to and from the ERV may
accumulate dirt. Wipe and vacuum the duct once every
year. You may wish to contact a Heating/Ventilation
company to do this.
WARNING: Blockage of hoods may cause an imbalance.
2. Clean Air Filters Four Times a Year
The standard filters equipped with your ERV are
removable and washable.
6. General Maintenance - Twice a Year
Wipe down the inside of the cabinet with a damp cloth to
remove dirt, bugs and debris that may be present.
a) simply open access door and slide core out
b) remove filter clips.
7. Cleaning the Fans
c) once clips are removed filters can be taken off the core to
be rinsed with water or a combination of soap and water.
d) to assemble, place clean dry filters back into their positions.
e) install core to its original position
Fans may accumulate dirt causing an imbalance and/or
excessive vibration of the ERV. A reduction in the air flow
may also occur. In new construction this may result within
the first year due to heavy dust and may occur periodically
after that over time depending on the outdoor conditions.
3. Clean Core Twice a Year
a) open access door
• unplug the ERV and open the service door
• remove the core
b) carefully grip ends of core and pull evenly outward
Core may be snug, but will slide out of the channel
c) once removed from the cabinet remove filters
d) vacuum core to remove dust from core surface.
DO NOT WASH!!
• remove ducting (metal and/or flexible insulated type)
from the red and/or blue ports which are connected
immediately inline with the fan assembly
• use a small brush, such as an old toothbrush or pipe
cleaner, and insert first
re) install the clean, dry filters
r f) install clean core
(a) through the large opening of the fan
assembly and then
NOTE: Core installation label on the outer end of the core.
(b) through the smaller opening in the end
of the fan assembly.
To install the clean core:
a) first mount the bottom flange of the core guide into the
bottom H channel approximately 1/4" (6 mm)
b) mount the left or right side flange of the core guide
approximately 1/4" (6 mm) followed by the other side
c) mount the top flange of the core guide into the top H
channel approximately 1/4" (6 mm)
• scrub individual fan blades until clean. Avoid
moving or damaging balancing flat weight, clip is
usually found on one or more of the fan blades
• vacuum and wipe
• reassemble making sure ducting is reattached firmly
and insulation and moisture barrier are sealed
and taped
d) with all four corners in place and the core straight and
even, push hard in the center of the core until the
core stops on the back of the cabinet.
Before attempting this task, thought should be given
to having a qualified service technician complete the
service work.
NOTE: Core will appear to stick out from cabinet approximately
1/8" (3 mm). This is designed this way so that the access door
will fit tight against the core.
4. Motors - MAINTENANCE FREE
28
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING YOUR HRV/ ERV SYSTEM
SYMPTOM
CAUSE
SOLUTION
Poor Air Flows
• 1/4” (6 mm) mesh on the outside hoods is plugged
• filters plugged
• clean exterior hoods or vents
• remove and clean filter
• core obstructed
• remove and clean core
• house grilles closed or blocked
• dampers are closed if installed
• poor power supply at site
• ductwork is restricting HRV/ERV
• improper speed control setting
• HRV/ERV airflow improperly balanced
• check and open grilles
• open and adjust dampers
• have electrician check supply voltage at house
• check duct installation
• increase the speed of the HRV/ERV
• have contractor balance HRV/ERV
Supply air feels cold
• poor location of supply grilles, the airflow may irritate
the occupant
• locate the grilles high on the walls or under the baseboards,
install ceiling mounted diffuser or grilles so as not to directly
spill the supply air on the occupant (eg. over a sofa)
• turn down the HRV/ERV supply speed. A small duct heater
(1kw) could be used to temper the supply air
• placement of furniture or closed doors is restricting the
movement of air in the home
• outdoor temperature extremely cold
• if supply air is ducted into furnace return, the furnace fan
may need to run continuously to distribute ventilation
air comfortably
Dehumidistat is not Operating
• improper low voltage connection
• external low voltage is shortened out by a staple or nail
• check dehumidistat setting it may be on OFF
• check that the correct terminals have been used
• check external wiring for a short
• set the dehumidistat at the desired setting
Humidity Levels are too High
• dehumidistat is set too high
• set dehumidistat lower
Condensation is appearing on the windows
• HRV/ERV is undersized to handle a hot tub, indoor pool, etc.
• lifestyle of the occupants
• cover pools, hot tubs when they are not in use
• avoid hanging clothes to dry, storing wood and venting clothes
dryer inside. Heating wood may have to be moved outside
• vent crawl space and place a vapour barrier on the floor
of the crawl space
• moisture coming into the home from an unvented or
unheated crawl space
• moisture is remaining in the washroom and kitchen areas
• ducts from the washroom should be sized to remove moist
air as effectively as possible, use of a bathroom fan for
short periods will remove additional moisture
• on humid days, as the seasons change, some condensation
may appear but the homes air quality will remain high with
some HRV/ERV use
• condensation seems to form in the spring and fall
• HRV/ERV is set at too low a speed
• increase speed of the HRV/ERV
Humidity Levels are too Low
• dehumidistat control set too low
• blower speed of HRV/ERV is too high
• lifestyle of occupants
• set dehumidistat higher
• decrease HRV/ERV blower speed
• humidity may have to be added through the use of humidifiers
• have a contractor balance HRV/ERV airflows
• HRV/ERV air flows may be improperly balanced
HRV/ERV and / or Ducts Frosting up
• Note: minimal frost build-up is expected on cores before
unit initiates defrost cycle functions
• HRV/ERV air flows are improperly balanced
• malfunction of the HRV/ERV defrost system
• have HVAC contractor balance the HRV/ERV
• using the self-test feature at the Base Module, press the fan
control symbol, the damper defrost unit should cycle its full
travel when working properly.
Condensation or Ice Build Up in Insulated Duct to
the Outside
• incomplete vapour barrier around insulated duct
• a hole or tear in outer duct covering
• tape and seal all joints
• tape any holes or tears made in the outer duct covering
• ensure that the vapour barrier is completely sealed
Water in the bottom of the HRV/ERV
• drain pans plugged
• improper connection of HRV/ERVs drain lines
• HRV/ERV is not level
• ensure O-Ring on drain nozzle sits properly
• look for kinks in line
• check water drain connections
• drain lines are obstructed
• make sure water drains properly from pan
• HRV/ERV heat exchange core is not properly installed
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Technical Bullet in
When using the ControlAir 15 relay contacts to initiate blower operation on a
furnace, certain thermostats will initiate the outdoor cooling condenser when
R and G are closed.
Use this wiring configuration to stop the ControlAir15 relay contacts from initializing
the condenser unit. This problem can occur at the thermostat because the Y terminal
is connected to the G terminal internal to the stat. When R and G are closed at the fur-
nace (by dehumidistat or relay) 24 Volts is sent to G at thermostat. 24 Volts is then
sent through Y which will initiate outdoor condenser.
MICRO PROCESSOR BOARD
CONTROLAIR 15
P4
P2
THERMIST0R
YEL
GRN
ORN
RED
BLK
TO DISABLE
RECIRCULATION
REMOVE SEL2
INTERNAL
DEHUMIDISTAT
SEL2
P5
REMOVE SEL1
FOR R-2000
SEL1
DRY
T1
T2
T6
N/C
COMMON
N/O
CONTACT
WARNING
750 ma
MAX FUSE
P1
T7
T8
CHASSIS
P3
T15
P6
T9
1
2
T10
T11
T12
T13
T14
T5
T4
T3
FAN O/P
G W Y
R
Thermostat
LEGEND
HIGH VOLTAGE
G W Y C
R
Furnace
12V LOW VOLTAGE
FIELD INSTALLED
LOW VOLTAGE
TB-102-NE
0009
30
Download from Www.Somanuals.com. All Manuals Search And Download.
RESIDENTIAL WIRING DIAGRAM
MICRO PROCESSOR BOARD
P4
P2
THERMIST0R
TO DISABLE
RECIRCULATION
REMOVE SEL2
INTERNAL
DEHUMIDISTAT
SEL2
Note:
YEL
GRN
ORN
RED
BLK
P5
REMOVE SEL1
FOR R-2000
All control connections
are labeled by colour.
Connect to corresponding
colour with low voltage wire
( 20 gauge minimum).
SEL1
DRY
T1
T2
T6
N/C
COMMON
N/O
CONTACT
A dry contact closure
between red & black will
initiate high speed override.
CONTROLAIR 15
SEE
DEFROST
DETAIL
WARNING
750 ma
MAX FUSE
120V
POWER SUPPLY
CORD
P1
DOOR SWITCH
T7
BLK
T8
CHASSIS
P3
T15
AUTO-
TRANS
FORMER
P6
T9
1
2
T10
T11
T12
T13
T14
T5
T4
T3
GRN
WHITE
BLACK
FAN O/P
SEE MOTOR DETAIL
FAN MOTOR DETAILS
WHITE
BLK
GRN
LEGEND
HIGH VOLTAGE
Note:
If any of the original
wire as supplied with
the unit must be replaced,
use only TEW certified wire
12V LOW VOLTAGE
FIELD INSTALLED
12V LOW VOLTAGE
FAN MOTOR
IMPORTANT: Control Low Voltage is 12VAC
DO NOT CONNECT EXTERNAL POWER SOURCES TO UNIT
DIRECT MOUNTED CAPACITOR
AUTO-TRANSFORMER DETAIL
DEFROST DETAILS
PLUG IN CONNECTOR
P5
95 MAX ONLY
PCB PLUG - IN
4
1
2
3
PCB PLUG - IN
1
2
5
6
AUTO
TRANSFORMER
1
2
PLUG IN
CONNECTOR
P1
P1
BLK
BLK
P6
P5
ORANGE
ORANGE
RED
3
1
2
4
3
4
RED
PIN 1 - BLACK
PIN 2 - ORANGE
PIN 3 - RED
PIN 1 - RED
P1
P6
BI-DIRECTIONAL
DAMPER MOTOR
PIN 2 - ORANGE
PIN 3 - BLACK
PIN 4 - SPARE
PIN 1 - BLUE
PIN 4 - RED
PIN 1 - GREEN
PIN 2 - YELLOW PIN 5 - WHITE
PIN 3 - BROWN PIN 6 - BLACK
PIN 2 - GREEN
PIN 4 - SPARE
TI-89A-NE
0102
31
Download from Www.Somanuals.com. All Manuals Search And Download.
511 McCormick Blvd.
London, Ontario N5W 4C
Ph: (519) 457-1904
Fx: (519) 457-1676
Email: [email protected]
Download from Www.Somanuals.com. All Manuals Search And Download.
|