| AC Power   For Business-Critical Continuity™   Liebert® GXT3™ UPS 230V 700VA-3000VA   User Manual   Download from Www.Somanuals.com. All Manuals Search And Download.   TABLE OF CONTENTS   IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1   SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1   GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3   PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4   Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   1.3.1 Appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   1.3.2 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   1.5.1 Mains (AC) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   1.5.2 Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   1.5.3 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   1.5.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   1.5.5 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8   INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9   Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   Preparation for Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   2.3.1 Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10   2.4.1 Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10   2.4.2 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12   Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15   2.5.1 Connecting to AC Mains and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15   2.5.2 Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15   Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16   2.6.1 Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16   2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables . . . . . . . . . . . 16   OPERATION AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17   Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   3.1.1 On/Alarm Silence/Manual Battery Test button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   3.1.2 Standby/Manual Bypass button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18   3.2.1 Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18   3.2.2 UPS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19   i Download from Www.Somanuals.com. All Manuals Search And Download.   OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20   Startup Checklist for the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20   Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21   Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21   COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22   Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22   5.1.1 Liebert MultiLink. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22   USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23   5.2.1 Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23   Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24   5.3.1 Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24   5.3.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25   5.3.3 On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25   5.3.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25   MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26   Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26   6.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26   Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27   Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Checking UPS Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   Checking UPS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28   TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29   UPS Symptoms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   7.1.1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   7.1.2 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32   SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33   9.1   Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37   ii   Download from Www.Somanuals.com. All Manuals Search And Download.   FIGURES   Figure 1   Liebert GXT3-700RT230 - GXT3-3000RT230 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   Rear panel components, Liebert GXT3 230V 2000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   Rear panel components, Liebert GXT3 230V 3000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10   Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10   Rotate the operation and display panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11   Tower installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11   Figure 10 Pulling inner member from each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12   Figure 11 Installing rear member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13   Figure 12 Installing front member of each bracket assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13   Figure 13 Fastening rear member and front member together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13   Figure 14 Installing inner members . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14   Figure 15 Installing rack-mount ears. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14   Figure 16 Insert the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14   Figure 17 Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   Figure 18 Battery level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18   Figure 19 Load level indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18   Figure 20 Terminal Block Communication pin layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24   Figure 21 Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26   Figure 22 Disconnecting the battery plug and battery connector (front view). . . . . . . . . . . . . . . . . . . . . . . . 27   Figure 23 Pulling out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27   Figure 24 Battery level indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   Figure 25 Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32   TABLES   UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   Specification of input circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15   Functions of the On/Alarm Silence/Manual Battery Test button . . . . . . . . . . . . . . . . . . . . . . . . . 17   Functions of the Standby/Manual Bypass button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   UPS status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19   Output voltage option, all models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23   Replacement battery pack model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26   Indicator descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29   Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   Table 10 Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30   Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . 33   Table 13 Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35   Table 14 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35   Table 15 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36   iii   Download from Www.Somanuals.com. All Manuals Search And Download.   iv   Download from Www.Somanuals.com. All Manuals Search And Download.   IMPORTANT SAFETY PRECAUTIONS   WARNING   injury or death.   ! Observe all cautions and warnings in this manual. Failure to do so may result in serious   Refer all UPS and battery service to properly trained and qualified service personnel. Do not   attempt to service this product yourself.   Opening or removing the cover may expose you to lethal voltages within this unit even when   it is apparently not operating and the input wiring is disconnected from the electrical source.   Never work alone.   SAVE THESE INSTRUCTIONS   This manual contains important safety instructions that must be followed during the installation and   maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or   operate this UPS.   UPS Safety Notes   The UPS contains no user-serviceable parts except the internal battery pack. Do not remove the   cover. Removing the cover may result in electric shock and will invalidate any implied warranty.   The UPS has an internal battery, so the output receptacles of the UPS may carry live voltage even if   the UPS is not connected to mains input power.   Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure   that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage,   presenting an electric shock hazard.   To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.   When the UPS is connected to an IT power distribution system, the short-circuit protection device   must be installed on the neutral line.   Install and use the UPS in the following environments:   • Temperature: 0°C to 40°C (32 - 104°F); relative humidity: 0% to 95%, non-condensing)   • Out of direct sunlight   • Away from heat source   • Stable surface, not subject to vibrations or shocks   • Away from dust and other particulates   • Away from corrosive substances, salts and flammable gases   Keep the air inlet and outlet of the UPS unobstructed. Poor ventilation will increase the UPS internal   temperature and can shorten the life of the UPS and its batteries.   Keep liquid and other foreign objects away from the UPS.   In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher   may cause electric shock.   This UPS is not intended for use with life support and other designated critical devices. Maximum   load must not exceed that shown on the UPS rating label. This UPS is designed for data processing   equipment. If uncertain, consult your local dealer or Emerson Network Power® representative.   ® ™ 1 Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Battery Safety   CAUTION   ! ! Do not dispose of the battery in a fire. The battery may explode.   Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and   eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with   plenty of clean water and get medical attention.   CAUTION   A battery can present a risk of electrical shock and high short-circuit current. The following   precautions should be observed when working on batteries:   • Remove watches, rings and other metal objects.   • Use tools with insulated handles.   • Wear rubber gloves and boots.   • Do not lay tools or metal parts on top of batteries.   • Disconnect charging source prior to connecting or disconnecting battery terminals.   • Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove   the source of the ground. Contact with any part of a grounded battery can result in   electrical shock. The likelihood of such shock will be reduced if grounds are removed during   installation and maintenance (applicable to a UPS and a remote battery supply not having   a grounded supply circuit).   ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 series complies with the limits for a   Class A digital device. Operating this device in a residential area is likely to cause harmful   interference that users must correct at their own expense.   The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the   published technical standards. Continued compliance requires installation in accordance with these   instructions and use of accessories approved by Emerson®.   Information for the Protection of the Environment   UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic   cards, electronic components). The components removed must be taken to specialized collection and   disposal centers.   NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This   product has been supplied from an environmentally aware manufacturer that complies with the   Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE.   The “crossed-out wheelie bin” symbol at right is placed on this product to   encourage you to recycle wherever possible. Please be environmentally   responsible and recycle this product through your recycling facility at its end   of life. Do not dispose of this product as unsorted municipal waste. Follow   local municipal waste ordinances for proper disposal provisions to reduce the   environmental impact of waste electrical and electronic equipment (WEEE).   For information regarding the scrapping of this equipment, please browse   http://www.eu.emersonnetworkpower.com (“Products session” or   “Contact us” session) or call our worldwide technical support.   • Toll Free: 00 80011554499   • Toll Number Based in Italy: +39 0298250222   ® ™ Liebert GXT3   2 Download from Www.Somanuals.com. All Manuals Search And Download.   GLOSSARY OF SYMBOLS   Risk of electrical shock   Indicates caution followed by important instructions   ! AC input   AC output   Requests the user to consult the manual   i + - Indicates the unit contains a valve-regulated lead acid battery   PbH2SO4   Recycle   R DC voltage   Equipment grounding conductor   Bonded to ground   AC voltage   ON/Alarm Silence/Battery Test   OFF/Bypass   WEEE   ® ™ 3 Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Product Description   1.0 PRODUCT DESCRIPTION   The Liebert GXT3 is a compact, online uninterruptible power system (UPS) that continuously   conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers   and other sensitive electronic equipment with clean sine wave input power, 700VA to 3000VA at   230V.   Upon generation, AC power is clean and stable. However, during transmission and distribution it is   subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause   data loss and damage equipment.   The Liebert GXT3 protects equipment from these disturbances. The Liebert GXT3 continuously   charges its batteries from the mains, enabling it to supply power to connected loads, even when the   mains fail.   This section describes the UPS, its features, models, appearance and components, operating   principles and operating mode.   1.1   Features   The UPS includes the following features:   • Intelligent battery management to extend the battery life   • Operation and display panel with LED for monitoring load percentage and battery capacity   independently   • Flexible network management with Liebert MultiLink® software   • Fan fault self-inspection and automated diagnostic function   • Intelligent fan operation, automatically changing rotation speed depending on system   requirements, to decrease power consumption and noise   • Input circuit breaker to ease recovery from overloads   • CE mark and safety approval from CE   • Communication options: USB port, Liebert IntelliSlot port and terminal block communication   ® • Dry contacts for remote monitoring   • Input power factor greater than 0.99   • Output voltage selection function   1.2   Available Models   Table 1   Model   GXT3-700RT230   UPS models, power ratings   Nominal Power Rating   700VA/630W   GXT3-1000RT230   GXT3-1500RT230   GXT3-2000RT230   GXT3-3000RT230   1000VA/900W   1500VA/1350W   2000VA/1800W   3000VA/2700W   ® ™ Liebert GXT3   4 Download from Www.Somanuals.com. All Manuals Search And Download.   Product Description   1.3   Appearance and Components   1.3.1 Appearance   The Liebert GXT3 rack/tower models in various power ratings have the same general appearance,   receptacles each has.   Figure 1   Liebert GXT3-700RT230 - GXT3-3000RT230 UPS   Ventilation Slots   Operation and Display Panel   1.3.2 Rear Panel Features   The rear panel of the Liebert GXT3 has these features:   • USB port   • Cooling fan   • C19 output receptacle (GXT3-3000RT230 only)   • Six C13 output receptacles   • Input circuit breaker   • Liebert IntelliSlot®   • Communication terminal block   • Input receptacle   Figure 2   Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA models   Liebert IntelliSlot Port   C14 Input Receptacle   Input Circuit   Breaker   USB Port   External Battery   Connector   Terminal Block   Communication   C13 Output Receptacles   Cooling Fan   Figure 3   Rear panel components, Liebert GXT3 230V 2000VA models   Input Circuit   Breaker   C20 Input Receptacle   Liebert IntelliSlot Port   USB Port   External Battery   Connector   Terminal Block   Communication   C13 Output Receptacles   Cooling Fan   ® ™ 5 Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Product Description   Figure 4   Rear panel components, Liebert GXT3 230V 3000VA models   Output Circuit   Breakers   Input Circuit   Breaker   C20 Input Receptacle   Liebert IntelliSlot Port   USB Port   External Battery   Connector   C13 Output   Receptacles   Terminal Block   Communication   C19 Output   Receptacle   Cooling Fan   1.4   Major Components   Figure 5   Operating principle diagram   Input   Output   Dynamic   Bypass   TVSS & EMI/   RFI Filters   Rectifier/   PFC   L1   Inverter   L1   DC-to-DC   Converter   Battery   Charger   Battery   N G N G The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery   charger, DC-to-DC converter, battery, dynamic bypass and UPS output.   Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters   The Liebert GXT3 has surge protection and filters that protect the connected load from power surges   and sags, electromagnetic interference (EMI) and radio frequency interference (RFI). These features   can minimize any surges or interference present in the mains power. The filters also prevent surges   or interference generated by the UPS from adversely affecting other devices connected on the same   branch as the UPS.   ® ™ Liebert GXT3   6 Download from Www.Somanuals.com. All Manuals Search And Download.   Product Description   Rectifier/Power Factor Correction (PFC) Circuit   In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains   power to regulated DC power for use by the inverter while ensuring that the wave shape of the input   current used by the UPS is near ideal. Extracting this sine wave input current achieves two   objectives:   • Efficient power use by the UPS   • Reduced reflected harmonics   This results in cleaner power being available to other devices in the building that are not protected by   the UPS.   Inverter   In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC circuit to produce   precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from   the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online,   continuously generating clean, precise, regulated AC output power.   Battery Charger   The battery charger utilizes energy from the mains power and precisely regulates it to continuously   float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is plugged in,   even when the UPS is not turned On.   DC-to-DC Converter   The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for   the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage,   increasing reliability.   Battery   The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery   design life, operate the Liebert GXT3 in an ambient temperature of 0°C to 25°C (32°F to 77°F).   Optional external battery cabinets are available to extend battery run times.   Dynamic Bypass   The Liebert GXT3 provides an alternate path for mains power to the connected loads in the unlikely   event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature, or UPS   failure condition, the UPS automatically transfers the connected loads to bypass.   NOTE   The bypass power path does not protect the connected loads from disturbances on the mains.   1.5   Operating Mode   The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode,   Battery Recharge Mode and Frequency Converter Mode.   For the descriptions of operation mode indicators and control buttons, refer to 3.0 - Operation and   1.5.1 Mains (AC) Mode   During Mains (AC) Mode, the mains provides energy to the Liebert GXT3. The filters, PFC circuit and   inverter process this power to provide high-level power to connected loads. Meanwhile, the UPS   maintains the batteries in a fully charged state.   ® ™ 7 Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Product Description   1.5.2 Manual Bypass Mode   Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed and held for about   2 seconds while the Liebert GXT3 is in Mains (AC) Mode. Bypass operation is indicated by an audible   alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 -   Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to   the connected load.   NOTICE   Turning Off the UPS in Bypass Mode will result in loss of output power.   1.5.3 Battery Mode   The Liebert GXT3 enters Battery Mode when mains power fails or is outside acceptable values. The   battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC   power for the connected loads.   When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second   intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to   warn that the battery is getting low (this Low Battery Warning is user-configurable).   In Battery Mode, the AC Input indicator is Off and the Battery Level indicators illuminate to warn   that a mains problem has occurred. Each battery level indicator represents a 20% capacity level. As   NOTICE   Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power.   If the UPS is turned Off manually, it must be manually restarted after mains power returns.   If the UPS is turned Off by a communication signal or because the batteries are depleted, it   will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 -   1.5.4 Battery Recharge Mode   Once mains power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.   1.5.5 Frequency Converter Mode   All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can   be selected using the configuration program. Allowable frequency operating modes include:   • Auto Sensing - 50Hz or 60 Hz – Bypass Enabled   • Auto Sensing - 50Hz or 60 Hz – Bypass Disabled   • Frequency Converter - 50Hz – Bypass Disabled   • Frequency Converter - 60Hz – Bypass Disabled   NOTE   The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60 Hz – Bypass   Enabled.”   CAUTION   be present even when the AC input indicator is Off.   ! Do not touch the AC input receptacle when the UPS is operating. AC input voltages may still   ® ™ Liebert GXT3   8 Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   2.0 INSTALLATION   2.1   Unpacking and Inspection   Unpack the UPS and conduct the following checks:   • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and   your local dealer or Emerson® representative immediately.   • Check the accessories against the delivery list. If there is any discrepancy, contact your local   dealer or your Emerson representative immediately.   2.2   What’s Included   With GXT3 UPS   • Terminal Block Communication terminals   • Compact Disk with:   • Liebert MultiLink®   • Configuration Program   • User Manual   • USB Cable: one, 2m (6-1/2 ft.) long   • Mounting hardware, including screws and handles   • Plastic tower stand sets: 2 (four pieces)   • Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)   • for 700VA - 1500VA: (2) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long   • for 2000VA - 3000VA:   • (3) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long   • (1) CEE 7/7 (Schuko) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long   • (1) BS1363 (UK) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long   NOTE   The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two   spacers for tower configuration and one DC power cable.   2.3   Preparation for Installation   2.3.1 Installation Environment   • Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.   • Place the UPS in an area where airflow around the unit is unrestricted and away from water,   flammable liquids, gases, corrosives and conductive contaminants. Avoid direct sunlight.   NOTE   Operating the Liebert GXT3 in temperatures above 25°C (77°F) reduces battery life.   Installation Clearances   Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT3. Do not   obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces   ventilation and heat dissipation, shortening the service life of the Liebert GXT3.   ® ™ 9 Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   2.4   Mechanical Installation   The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use   considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery   cabinets.   NOTE   When installing the UPS or making input and output connections, comply with all relevant   safety codes and standards.   2.4.1 Tower Installation   To install the Liebert GXT3 as a tower:   Figure 6 Support bases   Spacers   Connectors   Support Bases   2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the   spacers delivered with the battery cabinet.   assembled support bases, one in the front and one in the rear.   4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3.   Figure 7   Remove the front plastic bezel cover   Front Plastic   Bezel Cover   b. Pull the operation and display panel, rotate it 90 degrees clockwise and snap it back into   ® ™ Liebert GXT3   10   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   Figure 8   Rotate the operation and display panel   Operation and Display Panel   Rotated Clockwise 90 Degrees   c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back   d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation   and display panel and logo have been rotated 90 degrees clockwise, which provides upright   viewing for users.   5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs   Figure 9   Tower installation   Liebert GXT3 UPS   Liebert GXT3 UPS and   External Battery Cabinet   Operation and   Display Panel   Rotated for   Tower Operation   Support Bases   Support Bases   ® ™ 11   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   2.4.2 Rack Installation   NOTE   • When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf,   brackets, or slide rails on each side. The factory-supplied rack-mount ears cannot support   the weight of the UPS. They are used to move the UPS into and out of the rack and attach the   UPS to the rack.   • Mounting hardware and slide rails are sold separately. Contact your local dealer or   Emerson® representative for these options and any assistance.   To install a Liebert GXT3 UPS in a rack:   1. Unpack the two bracket assemblies and mounting hardware from the rack-mounting kit   (P/N: RMKIT18-32). Bracket assembly includes inner member, front member and rear member.   They are interchangeable between left-hand and right-hand. Mounting hardware includes M4   screws and M5 screws.   2. Remove inner member of each bracket assembly by extending it to its outermost position,   depressing the retaining latch and then pulling the inner member from the bracket assembly (see   Figure 10 Pulling inner member from each bracket assembly   Bracket assembly   Retaining latch   Inner member   3. Determine the desired height and mounting position of the Liebert GXT3 inside the rack’s vertical   rails.   CAUTION   position.   ! Reduce risk of tipping the rack by installing the Liebert GXT3 in the lowest possible rack   4. Attach the rear member of each bracket assembly to the rack’s vertical rails with two factory-   ® ™ Liebert GXT3   12   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   Figure 11 Installing rear member of each bracket assembly   Vertical pole   M5 screw (4 pcs)   Rear member   Front member   5. Extend bracket assembly by sliding the front member forward until it touches the rack’s front   vertical rails (adjustable length: 18 inches to 32 inches).   6. Use two M5 screws to attach each front member onto the front vertical rails through the   installation holes. Make sure that the bracket assemblies are at the same mounting height on all   Figure 12 Installing front member of each bracket assembly   Front vertical pole   Front member   Rear member   M5 screw (4 pcs)   7. Fasten the rear and front members together using four M4 screws and four M4 nuts (M4 nuts   have been installed on the rear member before delivery) per bracket assembly, as shown in   Figure 13 Fastening rear member and front member together   Rear member   M4 screw (8 pcs)   M4 nut (8 pcs)   Front member   ® ™ 13   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   8. Fasten inner members pulled from the bracket assemblies in Step 2 to the UPS on both sides with   eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the   Figure 14 Installing inner members   Liebert GXT3 UPS   Inner Member   Retaining Latch   M4 screw, 8 pieces   Figure 15 Installing rack-mount ears   Liebert GXT3 UPS   Ear, 2 pieces   M4 Screw, 8 pieces   10. Insert the UPS, with inner members attached, into bracket assemblies by inserting top and   bottom edges of inner members into the top and bottom curved tracks of front members and   Figure 16 Insert the UPS   Insert   Front Member   Inner Member   NOTE   Ends of inner members are tapered to allow the rear of the UPS to be angled upward before   insertion, if space allows.   The UPS should move smoothly into the bracket assemblies. If not, recheck alignment of front   ® ™ Liebert GXT3   14   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   11. Through the rack-mount ears, use M5 screws provided in this kit to secure the front of the UPS to   the rack’s vertical rails to prevent the UPS from sliding out of position.   12. If optional Liebert external battery cabinets will be connected to the UPS, they can be placed all   on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as   those for the UPS.   NOTE   Up to four external battery cabinets can be connected to the Liebert GXT3. Each cabinet will   increase the battery recharge time.   2.5   Cable Connection   The Liebert GXT3 rear panel has an input receptacle and output receptacles. Refer to 1.3.2 - Rear   Panel Features for details. The battery cables are supplied with the battery cabinet.   2.5.1 Connecting to AC Mains and Loads   NOTE   Ensure that all the loads are turned Off.   Prepare an input power supply that is properly protected by a circuit breaker in accordance   with national and local electrical codes. The wall receptacle must be grounded.   Emerson® recommends installing an upstream circuit breaker of the same series as the Liebert   GXT3’s input circuit breaker. The upstream breaker should have a higher capacity than the   UPS input circuit breaker.   Table 2   Specification of input circuit breaker   Rated Circuit   Model   Breaker   10A   GXT3-700RT230   GXT3-1000RT230   GXT3-1500RT230   GXT3-2000RT230   GXT3-3000RT230   10A   10A   16A   16A   1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.   NOTE   1. Do not overload any one output receptacle.   2. Output cable length should not exceed 10m (32.8 ft).   3. Plug the input receptacle of the Liebert GXT3 into the input power connection.   2.5.2 Connecting Battery Cables   1. Switch Off the input breaker of the battery cabinet.   2. Take out the battery cable included with the battery cabinet.   3. Connect one end of the battery cable to the external battery connector on the rear panel of the   UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.   4. Switch On the battery breaker on the rear of the external battery cabinet.   5. Use the Configuration Program included with the UPS to specify the number of external battery   ® ™ 15   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Installation   2.6   Connecting Communication Cables   Communication cable connection includes USB and option card cables.   2.6.1 Connecting USB Communication Cables   1. Remove the USB communication cables from the accessories box.   2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert   3. Insert the other end of the USB communication cable to the USB port of the computer.   2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables   1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside.   2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws.   3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided   with the card.   To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual.   Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site:   ® ™ Liebert GXT3   16   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation and Display Panel   3.0 OPERATION AND DISPLAY PANEL   Figure 1).   Figure 17 Operation and display panel   Battery Level Indicators   Load Level Indicators   Fault Indicator   Bypass Indicator   Inverter Indicator   AC Input Indicator   Liebert® GXT3   AC Power System   3000VA   On/Alarm Silence/Manual   Battery Test Button   Standby/Manual Bypass Button   Battery Indicator   3.1   Control Buttons   The operation and display panel has two control buttons: the On/Alarm Silence/Manual Battery Test   button and the Standby/Manual Bypass button.   3.1.1 On/Alarm Silence/Manual Battery Test button   The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and   Table 3   Functions of the On/Alarm Silence/Manual Battery Test button   Function   Operation   Description   ON   Press the button once for 3 seconds   Press the button for at least half a second   To start up the UPS   1 2 Alarm silence   To silence alarms   Press the button for at least half a second while   operating in Mains (AC) Mode with no alarms present.   Manual Battery Test   To initiate a manual battery test   1. The low battery and bypass reminder alarms cannot be silenced.   2. After the alarm is silenced, UPS will reactivate the alarm system to alert of additional problems.   3.1.2 Standby/Manual Bypass button   The Standby/Manual Bypass button controls output power to connected load(s) and has two functions   Table 4   Functions of the Standby/Manual Bypass button   Function   Operation   Description   Press the button once and hold it for about   2 seconds.   To initiate a manual transfer of the connected   loads to the internal bypass, if available   Manual Bypass   Standby   Press the button twice within four seconds while To shut down the UPS and shut Off all power   the UPS is in Manual Bypass or Battery Mode.   to the connected loads   1. If the bypass is not available due to voltage or frequency, pressing this button once will be ignored.   2. Perform all necessary shutdown procedures on connected loads before turning Off the Liebert GXT3.   ® ™ 17   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation and Display Panel   3.2   Indicators   into two groups according to their applications: level indicators and UPS status indicators.   3.2.1 Level Indicators   Battery Level Indicators   The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate   the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%).   Figure 18 Battery level indicators   Charging   Discharging   0 - 20%   21 - 40%   41 - 60%   61 - 80%   81 - 100%   Flash OFF OFF OFF OFF   ON OFF OFF OFF OFF   ON Flash OFF OFF OFF   ON   ON   ON OFF OFF OFF   ON   ON Flash OFF OFF   ON   ON OFF OFF   ON   ON   ON Flash OFF   ON   ON   ON   ON   ON OFF   ON   ON   ON   ON Flash   ON   ON   ON   ON   ON   ON   ON   Fully   Charged   ON   ON   ON   ON   ON   ON   ON   Load Level Indicators   The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative   load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in   Figure 19 Load level indicators   0 - 25%   ON OFF OFF OFF OFF   26 - 50%   OFF OFF OFF   ON   ON   ON   ON   ON   ON   ON   ON   51 - 75%   76 - 100%   Overload   ON   ON   ON   OFF OFF   ON   ON   OFF   ON   ® ™ Liebert GXT3   18   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation and Display Panel   3.2.2 UPS Status Indicators   UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator,   Table 5   UPS status indicators   UPS Status   Indicator   Icon   Color   Description   Fault Indicator   Red   On if the UPS has detected a fault; Off if there is no fault   On when the mains input power is normal; Off during mains   failure; flashing when mains power is outside specifications   AC input Indicator   Battery Indicator   Inverter Indicator   Bypass Indicator   Green   Amber   Green   Amber   On when the battery is supplying power; Off when the battery   is not supplying power   On when the inverter is supplying power; Off when the   inverter is not supplying power   On when the bypass is supplying power; Off when the bypass   is not supplying power; flashing when mains power is outside   specifications   ® ™ 19   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation   4.0 OPERATION   This section describes checks to be made before starting the UPS, how to start the UPS, manual   battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the   UPS.   NOTE   The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost   during storage and shipping. To ensure that the battery has adequate reserve power to protect   the connected load, charge the battery for three hours before putting the UPS into service.   4.1   4.2   Startup Checklist for the Liebert GXT3   Before starting the UPS, perform these checks:   ___ 1. Check that the input plugs and loads are connected properly and reliably.   ___ 2. Check that the battery cable is connected properly.   ___ 3. Check that the communication cables are connected properly.   Starting the UPS   2. Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three   seconds.   After the button is pressed, the LEDs on the display will signal that the unit has initiated the   startup process.   3. Once the inverter LED has been illuminated, turn On the connected loads.   4. Check the status indicators to determine whether the Liebert GXT3 is operating normally.   5. Check the load level indicators to verify that the connected load does not exceed the UPS’s rated   capacity.   The UPS is now providing conditioned power to the loads.   4.3   Manual Battery Test   To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least   half a second while operating from mains power with no alarm conditions present.   • If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries   for 24 hours.   • Retest the batteries after 24 hours of charging.   • After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact   your local Emerson® representative or Emerson Network Power Channel Support.   • If none of the five Battery LEDs illuminate during a manual battery test, check the battery   connection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery   test again.   • If none of the five Battery LEDs illuminate during the second manual battery test, replace   batteries and contact your local Emerson representative or Emerson Channel Support.   4.4   Manual Bypass   Press the Standby/Manual Bypass button once while the UPS is in Mains (AC) Mode and hold it for   about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal   bypass is not available because of mains power problems, pressing this button once will be ignored.   Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other   ® ™ Liebert GXT3   20   Download from Www.Somanuals.com. All Manuals Search And Download.   Operation   4.5   4.6   Shut Down the Liebert GXT3   1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding   it for about 2 seconds.   If manual bypass is not available, disregard the first step.   2. Press the Standby/Manual Bypass button twice within four seconds, each time holding it for   about two seconds, to shut down the UPS. The UPS will shut down about 30 seconds after the   button is pressed.   Power to the connected loads is now Off.   Disconnecting Input Power from the Liebert GXT3   disconnect the input cable plug.   2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this   indicates that the power-off is complete.   3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external   battery cabinet.   After powering Off the UPS, the UPS ceases output and the load is powered Off.   ® ™ 21   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Communication   5.0 COMMUNICATION   This section describes UPS communication over the three types of communication connections on the   rear of the Liebert GXT3:   • Liebert IntelliSlot port   • USB port (standard B-type)   • Terminal Block Communication   CAUTION   should be segregated and run separate from all other power cables.   ! To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables   5.1   Liebert IntelliSlot Communication Cards   The Liebert IntelliSlot port accepts three optional cards:   • Liebert IntelliSlot SNMP Card   • Liebert IntelliSlot Relay Card   • Liebert IntelliSlot 485 Card.   The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the   network.   The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications   and delivers support for built-in shutdown for AS/400 systems.   The Liebert IntelliSlot 485 Card is used to connect the UPS and a BMS.   Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the   UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at:   5.1.1 Liebert MultiLink   Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the   event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.   Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot   SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS. An optional Liebert MultiLink   License Kit permits shutting down the UPS over a network.   For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and   Emerson® representative.   ® ™ Liebert GXT3   22   Download from Www.Somanuals.com. All Manuals Search And Download.   Communication   5.2   USB Port Communication   The standard B-type USB port is used to connect the UPS and network server or other computer   system using Liebert MultiLink®. The configuration program can be completed through the   communication port.   5.2.1 Configuration Program   Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users,   the factory default settings will be adequate. This section illustrates the features available for   modification, as well as the factory default setting.   The USB configuration program allows these features of the Liebert GXT3 to be changed:   • Enable/Disable Auto-Restart   • Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass   disabled   • Set the Low Battery Warning alarm time from 2 to 30 minutes   • Enable/Disable the Auto-Battery test   • Enable/Disable Auto-Restart after removing Remote shutdown   • Set the wiring mode of Remote shutdown   • Set the Auto-Enable output   • Set the Auto-Battery test to 7, 14, 21 or 28 days   • Select the number of external battery cabinets connected to the UPS to adjust the remaining run   time calculated by Emerson® software products   Table 6   Output voltage option, all models   Output Voltage Option   220VAC, 230VAC and 240VAC   Factory Default Setting   230VAC   NOTICE   The output voltage settings cannot be changed while the UPS is On and powering connected   loads.   NOTE   Programming the output voltage of a 230V model of the Liebert GXT3 to 220V automatically   and Watt ratings).   NOTE   • This program is compatible with UPS models beginning with ‘GXT3,’ as in   ‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.   ® ® ® • A computer running Windows 2000 , XP or Vista is required to set up and run the   configuration program.   ® ™ 23   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Communication   5.3   Terminal Block Communication   Figure 20 Terminal Block Communication pin layout   1 2 Any Mode   Shut Down   3 4 Battery Mode   Shut Down   5 6 Battery Mode   Low Battery   7 8 5.3.1 Any Mode Shutdown   The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,   inverter and static switch so that there is no power to the loads.   Any Mode Shutdown can be operated locally or remotely:   • Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2.   • Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and   mounted at a remote location.   NOTE   Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown,   depending on the settings in the configuration program.   A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.   The connection to the UPS for remote connection will be via terminal block connector.   Any Mode Shutdown wiring must conform to all national, regional and local wiring   regulations.   WARNING   ! When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1   and Pin 2, the Liebert GXT3’s output can turn On automatically and without warning if the   Pin 1 and Pin 2 connection is changed.   ® ™ Liebert GXT3   24   Download from Www.Somanuals.com. All Manuals Search And Download.   Communication   5.3.2 Battery Mode Shutdown   Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and   static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power   for the UPS will still be active.   Battery Mode Shutdown can be performed locally or remotely:   • Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4.   • Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and   mounted at remote location.   NOTE   Remote Power Off will be performed by NO contact.   A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.   The connection to the Liebert GXT3 for remote connection will be via terminal block connector.   Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes   and laws.   This signal must last for 1.5 seconds or longer.   A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute   shutdown timer. This timer cannot be stopped once triggered. If the mains power returns   during this countdown, the Liebert GXT3 will still shut down and must remain shut down for   10 seconds. Whether the UPS turns back On when the power is restored depends on the   auto-restart setting.   5.3.3 On Battery   On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power   from the battery this dry contact will be closed.   5.3.4 Low Battery   Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power   from the battery and has reached the Low Battery Warning time selected in the configuration   program, this dry contact will be closed.   NOTE   The rated values for the dry contacts for the On Battery and Low Battery signals are:   • Rated Voltage: 30V (AC or DC)   • Rated Current: 300mA   ® ™ 25   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Maintenance   6.0 MAINTENANCE   This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s   status and checking UPS functions.   WARNING   precautions should be observed before replacing the battery pack:   • Remove rings, watches and other metal objects.   • Use tools with insulated handles.   ! The battery can present a risk of electrical shock and high short circuit current. The following   • Do not lay tools or other metal objects on the batteries.   • If the battery kit is damaged in any way or shows signs of leakage, contact your local   Emerson® representative immediately.   • Do not dispose of batteries in a fire. The batteries may explode.   • Handle, transport and recycle batteries in accordance with local regulations.   6.1   Replacing the Internal Battery Pack   The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Refer to Table 7   for internal battery pack part numbers for Liebert GXT3 UPS:   Table 7   Replacement battery pack model numbers   Replacement Internal Battery   Quantity   Required   UPS Model Number   Pack Model Number   GXT3-5A48BATKIT   GXT3-5A48BATKIT   GXT3-7A48BATKIT   GXT3-9A48BATKIT   GXT3-9A72BATKIT   Liebert GXT3-700RT230   Liebert GXT3-1000RT230   Liebert GXT3-1500RT230   Liebert GXT3-2000RT230   Liebert GXT3-3000RT230   1 1 1 1 1 Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to   obtain the part number and pricing of the appropriate replacement battery pack.   6.1.1 Battery Replacement Procedures   1. Gently remove the front plastic bezel cover from the UPS.   3. Lay the battery door and screws aside for reassembly.   Figure 21 Removing the front plastic bezel cover and battery door   Battery Door   Screws, 6   Front Bezel   4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown   ® ™ Liebert GXT3   26   Download from Www.Somanuals.com. All Manuals Search And Download.   Maintenance   Figure 22 Disconnecting the battery plug and battery connector (front view)   Battery Connector   Battery Connector   5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in   Figure 23 Pulling out the battery   Internal Battery Pack   Battery   Handle   Pull Out with Battery Handle   6. Unpack the new internal battery pack. Take care not to destroy the packing.   Compare the new and old internal battery packs to make sure they are the same type and model.   Emerson® representative or Emerson Channel Support.   7. Line up and slide in the new internal battery pack.   8. Reconnect the battery plug and battery receptacle   9. Gently push the battery wire and internal battery pack back into the UPS.   10. Reattach the front battery door with the six screws.   11. Reattach the front plastic bezel cover to the UPS.   NOTE   The internal battery pack is hot-swappable. However, caution should be exercised because   during this procedure the load is unprotected from disturbances and power outages.   Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output   power and will drop the connected load.   6.2   Battery Charging   The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their   design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains   input power.   If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input   power for at least 24 hours every four to six months to ensure full recharge of the batteries.   ® ™ 27   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Maintenance   6.3   6.4   Precautions   Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper   use can result in electrical shock or fire. To ensure safety, observe the following precautions:   • Turn Off and unplug the Liebert GXT3 before cleaning it.   • Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.   • Never block or insert any objects into the ventilation holes or other openings of the UPS.   • Do not place the Liebert GXT3 power cord where it might be damaged.   Checking UPS Status   Emerson® recommends checking the UPS operation status every six months.   • Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?   • Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal   Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or   Emerson Channel Support.   • Check whether the battery is discharging. When the mains input is normal, the battery should   not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson   representative or Emerson Channel Support.   6.5   Checking UPS Functions   NOTE   UPS function check procedures may interrupt power supply to the connected load.   Emerson recommends checking the UPS functions once every six months.   Back up the load data before conducting the UPS functions check. Procedures are as follows:   1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.   2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators   are On and the UPS is operating normally.   3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode.   The UPS should initiate a battery self-test. Check to determine whether the battery is operating   normally. If not, stop and contact your local Emerson representative or Emerson Channel Support   ® ™ Liebert GXT3   28   Download from Www.Somanuals.com. All Manuals Search And Download.   Troubleshooting   7.0 TROUBLESHOOTING   This section indicates various UPS symptoms a user may encounter and provides a troubleshooting   guide in the event the UPS develops a problem. Use the following information to determine whether   external factors caused the problem and how to remedy the situation.   7.1   UPS Symptoms   The following symptoms indicate the Liebert GXT3 is malfunctioning:   • The relative indicators illuminate, indicating the UPS has detected a problem.   • An alarm buzzer sounds, alerting the user that the UPS requires attention.   7.1.1 Indicators   In addition to the fault indicator being illuminated, one or more of LED segments of battery level   indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 24. The   Figure 24 Battery level indicator   A B C D E Table 8   Indicator descriptions   Diagnosis/Audible alarm   Indicator   A - E   A On bypass from output overload (half-second beep every half-second)   On bypass due to overtemperature condition (1-second beep every 4 seconds)   On bypass due to DC bus overvoltage (1-second beep every 4 seconds)   On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)   On bypass due to PFC failure (1-second beep every 4 seconds)   B C D E On bypass due to inverter failure (1-second beep every 4 seconds)   UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery   charger failure) and continuous alarm   A&B   A&C   A&E   B&E   UPS failed battery test (2-second beep every 60 seconds)   Bypass feedback (1-second beep every 4 seconds)   Short circuit on the output   ® UPS shutdown by command from communication (USB port or Liebert IntelliSlot port) (no   audible)   C&E   Utility LED flash   L-N reverse   Battery Indicator   Flashing   Internal battery not connected (continuous horn); check battery connection, power down and   restart UPS   Bypass Indicator   Flashing   Mains power voltage or frequency is out of tolerance; bypass is unavailable   If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload   ends.   ® ™ 29   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Troubleshooting   7.1.2 Audible Alarm   An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS   Table 9   Audible alarm description   Condition   Alarm   Half-second beep every 10 seconds   Two half-second beeps every 5 seconds   1-second beep every 4 seconds   Continuous   Battery discharge   Low battery   UPS fault, load on bypass   UPS fault, no power to load   Overload   Half-second beep every half second   2-second beep every 60 seconds   Continuous   Battery replacement   Battery loss   Wiring problem (loss of proper grounding for UPS) Continuous   Bypass reminder 1-second beep every 2 minutes   7.2   Troubleshooting   In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the   fault persists, contact Emerson® Channel Support.   Table 10 Troubleshooting table   Problem   Cause   Solution   UPS fails to start when the   On/Alarm Silence/Manual   Battery Test button is pressed   Ensure UPS is Off. Disconnect all loads and ensure   nothing is lodged in output receptacles. Ensure loads   are not defective or shorted internally.   UPS is short-circuited or   overloaded   UPS is operating from battery mode. Ensure UPS is   securely plugged into the wall receptacle.   UPS is not plugged in   UPS is operating from battery mode. Save data and   close applications. Replace UPS input fuse, then restart   UPS.   UPS input protection fuse has   blown/opened   Battery indicator is illuminated   UPS is operating from battery mode. Save data and   Mains power is out of tolerance close applications. Ensure mains supply voltage is   within acceptable limits for UPS.   Keep UPS plugged in continuously at least 24 hours to   Batteries are not fully charged   recharge batteries.   Check load level indicator and reduce the load on the   UPS has reduced battery   backup time   UPS is overloaded   UPS.   Replace batteries. Contact your local dealer, Emerson   Batteries may not be able to   representative or Emerson Channel Support for   hold a full charge due to age   replacement battery kit.   Fault and Bypass indicators   and all LED segments of   battery level indicator are   illuminated   Check load level indicator and remove non-essential   UPS is overloaded or load is   loads. Recalculate the load and reduce number of loads   faulty   connected to UPS. Check load for faults.   Ensure UPS is not overloaded, ventilation holes are not   blocked and room ambient temperature is not   Fault and Bypass indicators   and diagnostic A indicator are   illuminated   UPS has been shut down due   excessive. Wait 30 minutes to allow UPS to cool, then   to temperature condition; load   restart UPS. If UPS cannot restart, contact your local   is on bypass power   ® dealer, Emerson representative or Emerson Channel   Support.   Fault and Bypass indicators   and diagnostic B indicator are   illuminated   UPS internal DC bus   overvoltage   UPS requires service. Contact your local dealer,   Emerson representative or Emerson Channel Support.   ® ™ Liebert GXT3   30   Download from Www.Somanuals.com. All Manuals Search And Download.   Troubleshooting   Table 10 Troubleshooting table (continued)   Problem   Cause   Solution   Fault and Bypass indicators   and diagnostic C indicator are   illuminated   UPS requires service. Contact your local dealer,   Emerson representative or Emerson Channel Support.   UPS DC/DC fault   ® Fault indicator and diagnostic   D indicator are illuminated   UPS PFC (Power Factor   Correction Circuit) fault   UPS requires service. Contact your local dealer,   Emerson representative or Emerson Channel Support.   Fault and Bypass indicators   and diagnostic E indicator are   illuminated   UPS requires service. Contact your local dealer,   Emerson representative or Emerson Channel Support.   UPS inverter fault   Fault indicator and diagnostic   A and C indicators are   illuminated   Replace batteries. Contact your local dealer, Emerson   representative or Emerson Channel Support.   UPS failed the battery test   Your UPS has received a signal or command from the   attached computer. If this was inadvertent, ensure the   communication cable used is correct for your system.   For assistance, contact your local dealer, Emerson   representative or Emerson Channel Support.   Fault and Bypass indicators   and diagnostic C and E   indicators are illuminated   UPS has been shut down by a   command from the   communications port(s)   UPS failure (includes dual-fan   failure, single-fan failure under   certain conditions and battery   charger failure) and continuous   alarm   Fault indicator and diagnostic   A and B indicators are   illuminated   Ensure fan is not blocked up. If the fault is not removed,   contact your local dealer, Emerson representative or   Emerson Channel Support.   UPS detected a line-to-neutral   reversal or a loss of proper   grounding for UPS; continuous   horn and UPS cannot start up   in standby status. This is active   only when power is first   AC input indicator is flashing.   Contact a qualified electrician to verify site wiring.   applied to the input. Once the   UPS is running, the AC input   indicator will flash, unless the   input wiring is correctly   changed.   Check battery connections, completely power down and   restart UPS.   NOTE: If the battery circuit opens while the UPS is   running, it will be detected when the next battery test is   performed.   Battery source is not available;   continuous horn.   Battery indicator is flashing.   Bypass indicator is flashing.   The AC input powers the PFC input and serves as the   bypass source. If the AC is present but the voltage or   frequency exceeds the acceptable range for safe   operation with a load, the bypass will be disabled and   this indicator will flash, indicating that the bypass is   unavailable.   Because the voltage or   frequency is outside   acceptable limits, the bypass is   disabled.   When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the   top panel of the Liebert GXT3.   ® ™ 31   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Battery Cabinet   8.0 BATTERY CABINET   Optional battery cabinets are available for the Liebert GXT3. The external battery connector and   Figure 25 Battery cabinet   Input Breaker   External Battery   Connector   WARNING   ! Do not contact the external battery connector and ground without wearing protective gloves   and clothing and taking other precautions against electrical shock. The battery loop and AC   input are not insulated, which may cause a dangerous voltage between the external battery   connector and ground.   NOTE   External battery connectors are wired in parallel. Either connector can be connected to the UPS   or to another battery cabinet.   NOTE   The length of the standard battery cable delivered with the battery cabinet is 0.65m (2.13ft).   ® ™ Liebert GXT3   32   Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   9.0 SPECIFICATIONS   Table 11   Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS   Product model   Parameters   GXT3-700RT230   700VA/630W   GXT3-1000RT230   1000VA/900W   Model Rating   Dimensions, D x W x H, mm (in)   Unit   497 x 430 x 85 (19.6 x 16.9 x 3.3)   Shipping   617 x 570 x 262 (24.3 x 22.4 x 10.3)   Weight, kg (lb)   Unit   16.8 (37)   20 (44)   Shipping   Input AC   Voltage Range (typical)   90% ~ 100% loading   70% ~ 90% loading   30% ~ 70% loading   0 ~ 30% loading   Frequency   230VAC nominal; variable based on output load   177VAC/280VAC   168VAC/280VAC   150VAC/280VAC   115VAC/280VAC   40Hz ~ 70Hz; Auto Sensing   C14   Input Power Receptacle   Output AC   AC-AC Efficiency   Output Receptacles   Voltage   > 88% AC-AC, minimum   C13 × 6   220/230/240VAC (user configurable); ±3%   50Hz or 60Hz   Frequency   Waveform   Sine wave   Mains (AC) Mode Overload   Internal Battery Charger   Charger Current   Battery   200% for 2 seconds; 150% for 1 minute with transfer to bypass   1.3   Type   Valve-regulated, nonspillable, lead acid   4 × 12V × 5.0Ah   Qty × V× Rating   Battery Mfr/Part#   Backup Time   YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245   3 hours to 90% capacity after full discharge with 100% load till UPS   auto-shutdown (Internal Batteries Only)   Recharge Time   Environmental Requirements   Storage Temp   Relative Humidity   Operating Elevation   Storage Elevation   -15ºC to +50ºC (5ºF to 122ºF)   0%RH to 95%RH, non-condensing   Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating   15,240 (50,000 ft.) maximum   < 46 dBA, at 1 meter (3.2ft) from the rear   < 43 dBA, at 1 meter (3.2ft) from the front or sides   Audible Noise   Agency   Safety   RFI/EMI   IEC/EN/AS 62040-1:2008, GS mark   IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A   IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)   ISTA Procedure 1A   Surge Immunity   Transportation   ® ™ 33   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230   Product model   GXT3-2000RT230   Parameters   GXT3-1500RT230   1500VA/1350W   GXT3-3000RT230   3000VA/2700W   Model Rating   2000VA/1800W   Dimensions, D x W x H, mm (in)   497 × 430 × 85   (19.6 x 16.9 x 3.3)   602 × 430 × 85   (23.7 x 16.9 x 3.3)   Unit   617 x 570 x 262   (24.3 x 22.4 x 10.3)   717 x 570 x 262   (28.2 x 22.4 x 10.3)   Shipping   Weight, kg (lb)   Unit   23.2 (51.1)   26 (57.3)   25.5 (56.1)   28 (61.7)   32.4 (71.4)   35 (77.2)   Shipping   Input AC   Voltage Range (typical)   90% ~ 100% loading   70% ~ 90% loading   30% ~ 70% loading   0 ~ 30% loading   Frequency   230VAC nominal; variable based on output load   177VAC/280VAC   196VAC/280VAC   184VAC/280VAC   161VAC/280VAC   115VAC/280VAC   168VAC/280VAC   150VAC/280VAC   115VAC/280VAC   40Hz ~ 70Hz; Auto Sensing   Input Power Receptacle   Output AC   C14   C20   AC-AC Efficiency   Output Receptacles   Voltage   > 88% AC-AC, minimum   C13 x 6   C13 x 6; C19 x 1   220/230/240VAC (user configurable); ±3%   50Hz or 60Hz   Frequency   Waveform   Sine wave   Mains (AC) Mode Overload   200% for 2 seconds;   150% for 55 seconds   200% for 2 seconds; 150% for 50 seconds   Internal Battery Charger   Charger Current   Battery   1.88   2.71   2.5   Type   Valve-regulated, nonspillable, lead acid   Qty × V× Rating   Battery Mfr/Part#   4 × 12V × 7.2Ah   4 × 12V × 9.0Ah   6 × 12V × 9.0Ah   Panasonic/UP-RW1236   CSB/ GP 1272   Panasonic/UP-RW1245   CSB/ HR 1234W F2   Backup Time   3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown   (Internal Batteries Only)   Recharge Time   Environmental Requirements   Operating Temp   0ºC to 40ºC (32ºF to 104ºF); Table 14 - Operating temperature parameters   -15ºC to +50ºC (5ºF to 122ºF)   Storage Temp   Relative Humidity   0%RH to 95%RH, non-condensing   Operating Elevation   Storage Elevation   Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating   15000m (50,000 ft.) maximum   < 45 dBA max. at 1 meter (3.2ft.) front and side < 48 dBA max. at 1 meter (3.2ft.) front and side   Audible Noise   < 46 dBA, at 1 meter (3.2ft.) rear   < 48 dBA, at 1 meter (3.2ft.) rear   Agency   Safety   RFI/EMI   IEC/EN/AS 62040-1:2008, GS mark   IEC/EN/AS 62040-2 2nd Ed. (Category C2) = CISPR22 Class A   IEC/EN 62040-2 2nd Ed. (IEC/EN 61000-4-5)   ISTA Procedure 1A   Surge Immunity   Transportation   ® ™ Liebert GXT3   34   Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   Table 13 Battery cabinet specifications   Model Number   Parameter   GXT3-48VBATT   GXT3-72VBATT   GXT3-700RT230, GXT3-1000RT230,   GXT3-1500RT230, GXT3-2000RT230 GXT3-3000RT230   Used w/UPS Model   Dimensions, D x W x H, mm (in)   497 × 430 × 85   (19.7 x 16.9 x 3.3)   602 × 430 × 85   (23.6 x 16.9 x 3.3)   Unit   617 x 570 x 262   (24.3x 22.4 x 10.3)   717 x 570 x 262   (28.2 x 22.4 x 10.3)   Shipping   Weight, kg (lb)   Unit   32 (70.5)   35 (77.2)   42 (92.6)   Shipping   46 (101.4)   Battery parameters   Type   Valve-regulated, nonspillable, lead acid   Qty × V× Rating   Battery Mfr/Part#   Backup Time   2 × 4 × 12V × 9.0Ah   2 × 6 × 12V × 9.0Ah   Panasonic/UP-RW1245 CSB/HR 1234W F2   Environmental   Operating Temperature   Storage Temperature   Relative Humidity   0ºC to 40ºC (32ºF to 104ºF)   -15ºC to +40ºC (19ºF to 104ºF)   0% to 95%, non-condensing   Operating Elevation   Storage Elevation   Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating   15000m (50,000 ft.) maximum   Agency   Safety   RFI/EMI   IEC/EN/AS 62040-1:2008, GS mark   FCC Part 15, Class A=CISPR22 Class B   IEC 62040-2 2nd Ed.: 2006   Surge Immunity   Transportation   ISTA Procedure 1A   Table 14 Operating temperature parameters   Ambient Temperature,   25-30 (77-86)   30-35 (86-95)   93%-86%   35-40 (95-104)   86%-79%   °C (°F)   Maximum Output Power   Factor Derating   100%-93%   @ Maximum Load   ® ™ 35   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   Table 15 Battery run times   Run Time, Minutes   Number of   Load Percent   Batteries/Cabinets   of Capacity   10%   20%   30%   40%   50%   60%   70%   80%   90%   100%   10%   20%   30%   40%   50%   60%   70%   80%   90%   100%   10%   20%   30%   40%   50%   60%   70%   80%   90%   100%   10%   20%   30%   40%   50%   60%   70%   80%   90%   100%   700VA   105   62   1000VA   1500VA   75   2000VA   3000VA   77   91   38   73   33   21   15   11   8 35   37   37   31   22   21   32   23   16   15   27   17   11   11   Internal Battery   22   14   10   8 18   11   6 6 6 15   9 5 5 5 13   8 4 4 4 11   6 4 3 3 307   183   150   131   109   98   214   153   124   100   79   194   131   96   166   121   79   41   38   34   30   25   21   17   306   159   133   105   81   67   40   38   36   33   331   202   157   138   120   99   80   70   60   40   182   123   79   72   53   Internal Battery   + 1 External Battery   Cabinet   41   46   66   38   38   81   41   35   31   72   38   32   26   63   36   27   21   41   34   23   18   374   314   212   186   160   149   139   128   112   105   480   341   319   225   206   187   163   155   148   141   337   216   166   152   136   121   104   93   310   185   148   126   103   83   311   160   134   105   81   Internal Battery   + 2 External Battery   Cabinets   68   72   52   62   47   79   40   43   71   38   38   480   322   219   191   161   151   140   128   112   105   339   225   184   154   139   123   105   93   335   205   157   139   120   100   81   Internal Battery   + 3 External Battery   Cabinets   71   79   62   71   51   ® ™ Liebert GXT3   36   Download from Www.Somanuals.com. All Manuals Search And Download.   Specifications   Table 15 Battery run times (continued)   Run Time, Minutes   Number of   Batteries/Cabinets   Load Percent   of Capacity   700VA   480   480   338   322   305   217   202   186   164   159   1000VA   1500VA   480   315   215   184   157   145   133   120   105   96   2000VA   3000VA   480   303   187   156   141   127   108   97   10%   20%   30%   40%   50%   60%   70%   80%   90%   100%   480   340   316   220   198   166   158   149   141   133   346   301   186   156   141   126   107   95   Internal Battery   + 4 External Battery   Cabinets   79   81   72   73   The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads   and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle   computers and monitors) or add optional external battery cabinets.   9.1   Product Warranty Registration   To register for warranty protection, visit the Quick Links section of the Liebert Web site at:   Click on Product Warranty Registration and fill in the form.   If you have any questions, contact Emerson® Channel Applications Engineering at:   North America: 800-222-5877   Outside North America: 00-800-1155-4499   ® ™ 37   Liebert GXT3   Download from Www.Somanuals.com. All Manuals Search And Download.   Ensuring The High Availability   Of Mission-Critical Data And Applications.   Emerson Network Power, a business of Emerson (NYSE:EMR),   is the global leader in enabling Business-Critical Continuity™   from grid to chip for telecommunication networks, data centers,   health care and industrial facilities. Emerson Network Power   provides innovative solutions and expertise in areas including   AC and DC power and precision cooling systems, embedded   computing and power, integrated racks and enclosures,   power switching and controls, infrastructure management,   and connectivity. All solutions are supported globally by local   Emerson Network Power service technicians. Liebert AC power,   precision cooling and monitoring products and services   from Emerson Network Power deliver Efficiency Without   Compromise™ by helping customers optimize their data center   infrastructure to reduce costs and deliver high availability.   Technical Support / Service   Web Site   Monitoring   800-222-5877   Outside North America: +00800 1155 4499   Single-Phase UPS & Server Cabinets   800-222-5877   Outside North America: +00800 1155 4499   Three-Phase UPS & Power Systems   800-543-2378   Outside North America: 614-841-6598   Environmental Systems   800-543-2778   Outside the United States: 614-888-0246   Locations   United States   1050 Dearborn Drive   P.O. Box 29186   Columbus, OH 43229   Europe   Via Leonardo Da Vinci 8   Zona Industriale Tognana   35028 Piove Di Sacco (PD) Italy   +39 049 9719 111   Fax: +39 049 5841 257   While every precaution has been taken to ensure the accuracy   and completeness of this literature, Liebert Corporation assumes no   responsibility and disclaims all liability for damages resulting from use of   this information or for any errors or omissions.   © 2010 Liebert Corporation   All rights reserved throughout the world. Specifications subject to change   without notice.   Asia   29/F, The Orient Square Building   F. Ortigas Jr. Road, Ortigas Center   Pasig City 1605   Philippines   +63 2 687 6615   ® Liebert is a registered trademark of Liebert Corporation.   All names referred to are trademarks   Fax: +63 2 730 9572   or registered trademarks of their respective owners.   SLI-23180_REV5_06-13   Emerson Network Power.   The global leader in enabling Business-Critical Continuity™   EmersonNetworkPower.com   AC Power   Connectivity   DC Power   Embedded Computing   Outside Plant   Racks & Integrated Cabinets   Embedded Power   Power Switching & Controls   Precision Cooling   Services   Infrastructure Management & Monitoring   Surge Protection   Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.   ©2010 Emerson Electric Co.   Download from Www.Somanuals.com. All Manuals Search And Download.   |