Liebert PowerSure PSA UPS
GUIDE SPECIFICATIONS
350VA to 1000VA
Single - Phase Uninterruptible Power Supply Systems
1.0
GENERAL
1.1
1.2
SUMMARY
This specification defines the electrical and mechanical characteristics and requirements for a continuous-
duty single-phase, solid-state, uninterruptible power system. The uninterruptible power system, hereafter
referred to as the UPS, will provide high-quality AC power for sensitive electronic equipment loads.
STANDARDS
The UPS is designed in accordance with the applicable sections of the current revision of the following
documents. Where a conflict arises between these documents and statements made herein, the statements
in this specification will govern.
120V Units
UL 1778, c-UL listed (to CSA 22.2 No. 107.1)
FCC Part 15, Subpart B, Class B
ANSI C62.41, Category A, Level 3 (IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria A
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-6, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1A
230V Units
EN50091-1-1, TUV/GS listed, CE compliance mark
EN50091-2, Class B
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6
EN61000-4-4, Level 4, Criteria A
EN61000-4-5, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1 A
1.3.
SYSTEM DESCRIPTION
1.3.1
Modes of Operation
The UPS is designed to operate as a line-interactive system in the following modes:
A. Normal - The critical AC load is continuously supplied with filtered power. The battery
charger maintains a float-charge on the battery.
1
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
127 VAC nominal: single phase, 2-wire-plus-ground: 90 ─ 150 VAC (±3VAC),
Buck compensation: 141VAC (±3VAC)
Boost1 compensation: 113VAC (±3VAC)
Boost2 compensation: 100VAC (±3VAC)
220 VAC nominal: single phase, 2-wire-plus-earth: 155 ─ 270 VAC (±6VAC)
Buck compensation: 243 VAC (±6VAC)
Boost1 compensation: 197 VAC (±6VAC)
Boost2 compensation: 174 VAC (±6VAC)
230 VAC nominal: single phase, 2-wire-plus-earth: 163 ─ 282 VAC (±6VAC)
Buck compensation: 254 VAC (±6VAC)
Boost1 compensation: 207 VAC (±6VAC)
Boost2 compensation: 183 VAC (±6VAC)
240 VAC nominal: single phase, 2-wire-plus-earth: 171 ─ 291 VAC (±6VAC)
Buck Compensation: 265 VAC (±6VAC)
Boost1 compensation: 215 VAC (±6VAC)
Boost2 compensation: 191 VAC (±6VAC)
B. Frequency: The UPS automatically senses the input frequency and operates within the
following frequency specifications without drawing power from the batteries.
50 Hz Applications: 46.5 ─ 53.5 Hz (±0.1 Hz)
60 Hz Applications: 56.5 ─ 63.5 Hz (±0.1 Hz)
C. Surge Protection: The 120 VAC units can withstand input surges of up to 570J without
damage per criteria listed in IEEE C62.41, Category A, Level 3. The 230 VAC units can
withstand input surges of up to 660J without damage per criteria listed in EN61000-4-5,
Level 3, Criteria A.
D. Input Connections: The 120 VAC units have an attached input cord 6.0 feet (1.8 meters) in
length, measured between the inside edges of the connectors. The attached input cord has a
NEMA 5-15 plug.
1.3.3.2 AC Output
A. Voltage Configuration:
120 VAC units: 110/120/127 VAC, 60/50 Hz, single-phase, 2-wire-plus-ground.
120VAC ± 8% (Battery mode)
230 VAC units: 220/230/240 VAC, 50/60 Hz, single phase, 2-wire-plus-earth.
230 VAC ±8% (Battery mode)
B. Voltage Regulation: ±10% steady state.
C. Frequency Regulation: +0.1Hz synchronized to utility / mains.
+0.5Hz free running or on battery operation.
D. Load Power Factor Range: 0.6 lagging to 1.0 (unity).
E. Inverter Overload Capability: Overload Warning (visual and audible alarms) occurs
between 100%─109% of rated capacity, continuous duty. Shutdown occurs at the following
levels:
>110 ─ 120%; after 120 seconds (Normal mode)
>120 ─ 150%; after 15 seconds (Normal mode)
>150% - short-circuit; after 5 seconds (Normal mode)
>110%; after 2 cycles (Battery mode)
3
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
F. Voltage Transient Response: ±15% in Normal mode for 0-100-0% loading of the UPS
rating, ±5% in Battery mode for 20-100-20% loading of the UPS rating.
G. Transient Recovery Time: To within ±8% of nominal voltage in < 2 cycles.
H. Efficiency: >95% (Normal mode)
>90% (Buck/Boost mode)
I. Output Power Cords: The 230 VAC units have two (2) detachable IEC-320-C14 output
power cords measuring 2m (6.6 ft) in length.
1.4
ENVIRONMENTAL CONDITIONS
A. Ambient Temperature
Operating: 32oF ─ 104oF (0oC ─ 40oC) for altitudes 0 ─ 5,000 ft. (0 ─ 1500 meters) above sea
level
32°F ─ 86°F (0°C ─ 30°C) for altitudes 5000 ft ─ 10,000 ft (1500 ─ 3000 meters)
above sea level.
77o F (25oC) for optimum battery performance
Storage: 5°F ─ 104°F (-15°C ─ 40°C) with batteries
5oF ─ 122oF (-15oC ─ 50oC) without batteries
68oF (20oC) for optimum battery storage.
B. Relative Humidity
0 ─ 95% non-condensing.
C. Altitude:
3,000 m (10,000 ft. max.), without power derating when operated within the temperature specified
in section 1.4.A.
D. Audible Noise
Noise generated by the UPS during normal operation does not exceed 40dB when measured at 1
meter from the surface of the UPS, “A” weighted.
E. Electrostatic Discharge
The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000-4-2,
level 3, Criteria A without damage and without affecting the connected load. The 230 VAC units
are able to withstand an electrostatic discharge compliant to EN61000-4-2, level 3, Criteria A
without damage and without affecting the connected load.
1.5
USER ACCESSORIES AND PACKAGING
The specified UPS system is supplied with one (1) user's manual. The manual includes installation
drawings and instructions, a functional description of the equipment, safety precautions, illustrations,
operating procedures, and general maintenance guidelines. The UPS is also supplied with one (1)
Multilink™ software CD, one (1) Multilink serial cable (10-ft; 3m), one (1) USB cable (6-ft; 1.8m), one (1)
RJ-11 cord (7-ft; 2.1m) and one (1) warranty card (120V models only). The package of the 230 VAC units
also includes two (2) output power cords (2m; 6.6 ft). The package meets the requirements of ISTA
Procedure 1A.
1.6
WARRANTY
The manufacturer warrants the UPS against defects in materials and workmanship for two (2) years. The
warranty covers all parts. An optional one (1) or three (3) year extended warranty is available from the
manufacturer.
4
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
1.7
QUALITY ASSURANCE
1.7.1
Manufacturer Qualifications
Liebert Corporation provides more than twenty years experience in the design, manufacture, and
testing of solid-state UPS systems and the company is certified to ISO 9001.
1.7.2
Factory Testing
Before shipment, the product is tested to assure compliance with the specification.
2.0
PRODUCT
2.1
FABRICATION
All materials and components making up the UPS are new, of current manufacture, and have not been in
prior service except as required during factory testing. All relays are provided with dust covers.
2.1.2
Wiring
Wiring practices, materials, and coding are in accordance with the requirements of the standards
listed in section 1.2. All wiring is copper.
2.1.3
Cabinet
The UPS unit comprised of: TVSS & EMI/RFI Filters, Bi-Directional Converter, Automatic
Voltage Regulator and Battery consisting of the appropriate number of sealed battery cells; is
housed in a mini-tower NEMA type 1 enclosure. The UPS cabinet is injection-molded standard
color. Dimensions and weights are:
UNIT
UNIT DIMENSIONS
W x D x H in (mm)
120 VAC UNITS
WEIGHT
230 VAC UNITS
WEIGHT
lbs (kg)
16.8 (7.6)
17.2 (7.8)
20.7 (9.4)
29.7 (13.5)
kg (lbs)
7 (15.4)
350VA
500VA
650VA
4.6 x 7.7 x 8.7 (116 x 196 x 222)
4.6 x 7.7 x 8.7 (116 x 196 x 222)
4.6 x 14.1 x 8.7 (116 x 358 x 222)
7.4 (16.3)
9.1 (20.1)
13.2 (19.1)
1000VA 4.6 x 14.1 x 8.7 (116 x 358 x 222)
2.1.4
Cooling
The UPS is convection cooled.
2.2
COMPONENTS AND OPERATION
2.2.1 Input Protection
The UPS has built-in protection against undervoltage, overcurrent, and overvoltage conditions
including low-energy lightning surges introduced on the primary input power source. The UPS is
provided with an input circuit protector. The 120 VAC UPS models withstand input surges
without damage per criteria listed in IEEE C62.41, Category A, Level 3 and the 230 VAC UPS
models withstand input surges without damage per criteria listed in EN61000-4-5, Level 3,
Criteria A. Additionally, the UPS is supplied with one pair of Data Line Protection Connectors
to provide phone, fax or modem line surge protection via RJ-45 connectors. These Data Line
Protection Connectors provide transmission for 10/100 Base-T Ethernet connection.
5
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2.2
Bi-Directional Converter
2.2.2.1 General
The Bi-Directional Converter incorporates solid-state devices and control circuitry to
convert AC power to regulated DC power for battery charging; and convert DC power
from the battery to regulated and conditioned stepped-sinewave AC power for supporting
the critical load. The Bi-Directional Converter is a pulse width modulated (PWM)
design. The Bi-Directional Converter operates in the following modes:
1.
In Normal mode of operation, the Bi-Directional Converter maintains the
battery system at a float charge.
2.
In Battery mode of operation, the Bi-Directional Converter converts DC power
from the battery to regulated and conditioned stepped-sinewave AC power for
supporting the critical load.
3.
In the recharge mode of operation, the Bi-Directional Converter converts AC
power to regulated DC power to recharge the battery.
2.2.2.2 Battery Recharge
The UPS contains a battery recharge rate designed to prolong battery life. The battery is
constant voltage charged to recharge and maintain the battery in a fully charged state.
Recharge time is 6 hours maximum to 90% rated capacity after discharge into full
resistive load.
2.2.2.3 Bi-Directional Converter DC Protection
The following DC shutdown levels protect the UPS:
DC Overvoltage Shutdown
DC Undervoltage Shutdown (End of Discharge)
DC Undervoltage Warning (Low Battery Reserve)
2.2.2.4 Output Protection
For output faults including short circuits and overloads, the UPS is protected by the input
circuit protector during Normal mode and by electronic current limiting during Battery
mode.
2.2.2.5 Overload
The UPS is capable of supplying power for overloads exceeding 100% and up to 110%
of full load rating, continuously. A visual indicator and audible alarm indicate overload
operation. For greater current demands, the UPS employs circuit protector and electronic
current-limiting protection to prevent damage to components. The UPS is self-protecting
against any magnitude of connected output overload. The UPS control logic senses and
disconnects the UPS from the critical AC load and clears the protective circuit breaker
during Normal mode.
2.2.2.6 Output Frequency
An oscillator controls the output frequency of the UPS. The oscillator maintains the
output frequency to + 0.5 Hz of nominal when not synchronized to the utility/mains
source.
2.2.2.7 Battery Over-Discharge Protection
To prevent battery damage due to excessive discharge levels, the UPS control logic
automatically monitors the battery voltage and load level and switches off the output at
the predetermined battery shutdown voltage set point.
6
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2.3
Display and Controls
2.2.3.1 General
The UPS is provided with a microprocessor-based unit status and control display
designed for convenient and reliable user operation. The status and alarm indicators are
displayed on a status indicator display.
2.2.3.2 System Indicators
There are three (3) status indicators on the front of the UPS (Utility, Battery and Fault)
and one (1) on the rear (Site Wiring Fault):
The Utility Indicator illuminates when the UPS is operating and supplying
power to connected loads: green indicates Normal mode, amber denotes
Buck/Boost mode.
The Battery Indicator illuminates to indicate the UPS is operating on battery
(green) or to signify a battery warning (amber).
The Fault Indicator illuminates when the UPS detects a problem: red for an
internal UPS fault, green for overload and over-temperature conditions.
The Site Wiring Fault Indicator on the rear panel illuminates red when the UPS
detects a line-neutral reversal or a poor neutral-ground bond.
2.2.3.3 On/Off Controls
UPS start-up and shutdown operations are accomplished by the "On/Off/Alarm Silence"
push button located on the front panel of the UPS. Depressing the button for more than
0.5 sec will start-up the UPS and to turn the UPS off the button will need to be depressed
for more than 2 sec
2.2.3.4 On-Line Battery Test
The UPS is provided with an automatic biweekly battery test feature. The test ensures
the capability of the battery to supply power to the inverter while loaded. If the battery
fails the test, the UPS will display a warning to indicate the batteries need replaced. The
battery test feature is user accessible via Multilink.
2.2.4
2.2.5
Internal Battery
Valve regulated, non-spillable, lead-acid cells are used as a stored-energy source for the specified
UPS system. The battery is housed internal to the UPS cabinet, and sized to support the inverter at
rated load and power factor, with ambient temperature of 77 F (25 C) for a minimum of 5
minutes reserve time. The expected life of the battery is 3 - 5 years or 250 complete discharge
cycles.
o
o
Output Distribution
Output distribution is integral to the UPS and is located on the rear of the unit.
UNIT
120 VAC UNITS
230 VAC UNITS
(4) NEMA 5-15R (orange) Battery
350VA,500 backup + surge protection;
(4) IEC-320-C13 (orange) Battery backup
+ surge protection;
VA,650VA (2) NEMA 5-15R (black) surge (2) IEC-320-C13 (black) Surge protection
protection only
only
1000VA
(6) NEMA 5-15R (orange) Battery
backup + surge protection;
(2) NEMA 5-15R (black) surge
protection only
(6) IEC-320-C13 (orange) Battery backup
+ surge protection;
(2) IEC-320-C13 (black) Surge protection
only
7
PowerSure PSA
350 – 1000VA
Guide Specification
Download from Www.Somanuals.com. All Manuals Search And Download.
SL-23271 8/03
2.2.6
Communications
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications
with a computer system running MultiLink™ software. The DB-9 is capable of supplying serial
communication, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and
shutdown software, is shipped with the UPS, along with a 10-ft. (3m) DB-9 cable required for
running MultiLink.
The UPS can signal “on battery” and “low battery” using opto-couplers. When the UPS is
operating in Battery mode, it can receive a signal from the host computer system that will shut
down the UPS (after gracefully shutting down the operating system on the host computer system)
when the remaining battery run time is low. The timing of the signal depends on MultiLink’s
configuration settings. This shutdown signal (5-12VDC) must have a duration of at least 1.5
seconds for the UPS to be shut down. The UPS communicates via serial communications using
Liebert ESP II protocol.
The PowerSure PSA has a USB interface port for communication that will work with the built-in
Microsoft Power Manager software on the user’s PC, if the PC is so equipped. It will provide UPS
status and manages the automatic orderly shutdown of the computer. The UPS (USB)
communications meets HID standard, version 1.11. All USB models are compatible with
Microsoft Windows 2000, Windows XP and Mac OS 10.2 or later. All USB models ship with a 6-
ft. (1.8m) USB cable.
The pin out configuration of the DB9 connector is:
Pin
1
2
3
4
Assignment Description
Low Battery (open collector)
UPS TxD (typical RS-232 levels)
UPS RxD (typical RS-232 levels)
Battery Mode Shutdown (5-12V)
Common
5
6
7
8
Any Mode Shutdown (short to pin 5)
Low Battery (open emitter)
AC Fail (open emitter)
9
AC Fail (open collector)
Maximum voltage and current on Pins 1, 7, 8, and 9 is 55VDC; 10.0 mA.
8
PowerSure PSA
350 – 1000VA
Guide Specification
SL-23271 8/03
Download from Www.Somanuals.com. All Manuals Search And Download.
|