Lennox International Inc Air Conditioner CONDENSING UNITS User Manual

INSTALLATION  
INSTRUCTIONS  
E 2011 Lennox Industries Inc.  
Dallas, Texas, USA  
Merit® Series 14ACX Units  
CONDENSING UNITS  
506645−01  
07/11  
Litho U.S.A.  
Supersedes 11/10  
TABLE OF CONTENTS  
Typical Unit Parts Arrangement . . . . . . . . . . . . . . . . . . . 3  
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . 3  
Operating Manifold Gauge Set and Service Valves . . . 4  
Recovering Refrigerant from Existing System . . . . . . . 6  
Removing and Installing Louvers . . . . . . . . . . . . . . . . . . 8  
New or Replacement Line Set . . . . . . . . . . . . . . . . . . . . . 9  
Flushing Line Set and Indoor Coil . . . . . . . . . . . . . . . . 14  
Installing Indoor Metering Device . . . . . . . . . . . . . . . . 15  
Leak Test Line Set and Indoor Coil . . . . . . . . . . . . . . . 16  
Evacuating Line Set and Indoor Coil . . . . . . . . . . . . . 17  
Servicing Unit Delivered Void of Charge . . . . . . . . . . . 22  
Start−Up and Performance Checklist . . . . . . . . . . . . . . 30  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
who have jurisdiction before installation.  
WARNING  
Improper installation, adjustment, alteration, service or  
maintenance can cause personal injury, loss of life, or  
damage to property.  
Installation and service must be performed by a licensed  
professional installer (or equivalent) or a service agency.  
IMPORTANT  
The Clean Air Act of 1990 bans the intentional venting of  
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.  
Approved methods of recovery, recycling or reclaiming  
must be followed. Fines and/or incarceration may be  
levied for noncompliance.  
Shipping and Packing List  
IMPORTANT  
This unit must be matched with an indoor coil as  
specified in Lennox Engineering Handbook. Coils  
previously charged with HCFC−22 must be flushed.  
Check the unit for shipping damage and listed times below  
are intact. If damaged, or if parts are missing, immediately  
contact the last shipping carrier.  
1 ꢀ Assembled outdoor unit  
1 ꢀ Refrigerant flow control kit (fixed orifice)  
1 ꢀ Liquid line filter drier  
NOTICE TO INSTALLER  
General  
UNIT PLACEMENT  
It is critical for proper unit operation to place outdoor unit on an  
elevated surface as described in Unit Placement section on page 7.  
14ACX Air Conditioners, which will also be referred to in  
this instruction as the outdoor unit, uses HFC−410A  
refrigerant. This outdoor unit must be installed with a  
matching indoor unit and line set as outlined in the Lennox  
14ACX Engineering Handbook.  
BRAZING LINE SET TO SERVICE VALVES  
It is imperative to follow the brazing technique illustrated starting on  
page 11 to avoid damaging the service valve’s internal seals.  
This outdoor unit is designed for use in systems that use  
one of the following refrigerant metering devices:  
S
S
Thermal expansion valve (TXV)  
Fixed orifice  
07/11  
506645−01  
Page 1  
*2P0711*  
*P506645-01*  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Typical Unit Parts Arrangement  
NOTE ꢀ Plumbing layout and compressor type may vary between model sizes.  
CONTROL  
THERMAL SWITCH  
COMPRESS0R (B1)  
(S173) (−036 AND  
−060 ONLY)  
DUAL RUN  
CAPACITOR  
(C12)  
GROUND LUG  
DISCHARGE LINE  
COMPRESSOR  
HARNESS  
CONNECTION  
CONTACTOR  
(K1)  
OUTDOOR COIL  
CUTOUT FOR HIGH  
VOLTAGE CONDUIT  
CONTROL WIRE  
LOOP  
CRANKCASE HEATER  
SEE NOTE  
THERMOSTAT (S40)  
CRANKCASE HEATER  
SEE NOTE  
(HR1)  
SUCTION LINE SERVICE VALVE  
LIQUID LINE SERVICE VALVE  
HIGH PRESSURE SWITCH (S4)  
NOTE ꢀ− −041, −047, −048, −059 and −060 only are equipped with crankcase thermostat (S40) and  
crankcase heater (HR1).  
Figure 1. Typical Unit Parts Arrangement  
Model Number Identification  
14 AC X 024 −  
13  
230  
Minor Revision Number  
Nominal SEER  
Unit Type  
Voltage  
230 = 208/230V−1phase−60hz  
Cooling Capacity Tons  
AC = Air Conditioner  
018 = 1.5  
024 = 2  
030 = 2.5  
036 = 3  
041 = 3.5  
042 = 3.5  
047 = 4  
048 = 4  
059 = 5  
060 = 5  
Refrigerant  
X = R−410A  
Page 3  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CAUTION  
IMPORTANT  
Physical contact with metal edges and corners while  
applying excessive force or rapid motion can result in  
personal injury. Be aware of, and use caution when  
working near these areas during installation or while  
servicing this equipment.  
To prevent stripping of the various caps used, the  
appropriately sized wrench should be used and fitted  
snugly over the cap before tightening.  
When servicing or repairing HVAC components, ensure  
the fasteners are appropriately tightened. Table 1 provides  
torque values for fasteners.  
Table 1. Torque Requirements  
Operating Manifold Gauge Set and  
Service Valves  
Parts  
Recommended Torque  
Service valve cap  
Sheet metal screws  
Machine screws #10  
Compressor bolts  
Gauge port seal cap  
8 ft.− lb.  
11 NM  
16 in.− lb.  
28 in.− lb.  
90 in.− lb.  
8 ft.− lb.  
2 NM  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
who have jurisdiction before installation.  
3 NM  
10 NM  
11 NM  
TORQUE REQUIREMENTS  
USING MANIFOLD GAUGE SET  
When servicing or repairing heating, ventilating, and air  
conditioning components, ensure the fasteners are  
appropriately tightened. Table 1 lists torque values for  
fasteners.  
When checking the system charge, only use a manifold  
gauge set that features low loss anti−blow back fittings.  
Manifold gauge set used with HFC−410A refrigerant  
systems must be capable of handling the higher system  
operating pressures. The gauges should be rated for use  
with pressures of 0 − 800 psig on the high side and a low  
side of 30" vacuum to 250 psig with dampened speed to  
500 psi. Gauge hoses must be rated for use at up to 800  
psig of pressure with a 4000 psig burst rating.  
IMPORTANT  
Only use Allen wrenches of sufficient hardness (50Rc −  
Rockwell Harness Scale minimum). Fully insert the  
wrench into the valve stem recess.  
Service valve stems are factory−torqued (from 9 ft−lbs for  
small valves, to 25 ft−lbs for large valves) to prevent  
refrigerant loss during shipping and handling. Using an  
Allen wrench rated at less than 50Rc risks rounding or  
breaking off the wrench, or stripping the valve stem  
recess.  
OPERATING SERVICE VALVES  
The liquid and vapor line service valves are used for  
removing refrigerant, flushing, leak testing, evacuating,  
checking charge and charging.  
Each valve is equipped with a service port which has a  
factory−installed valve stem. Figure 2 provides information  
on how to access and operating both angle and ball service  
valves.  
See the Lennox Service and Application Notes #C−08−1  
for further details and information.  
Page 4  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operating Angle Type Service Valve:  
1. Remove stem cap with an appropriately sized wrench.  
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back  
the stem out counterclockwise as far as it will go.  
SERVICE PORT CAP  
SERVICE PORT CORE  
(VALVE STEM SHOWN  
CLOSED) INSERT HEX  
WRENCH HERE  
TO INDOOR  
UNIT  
(VALVE STEM SHOWN OPEN)  
INSERT HEX WRENCH HERE  
SERVICE PORT  
CORE  
STEM CAP  
TO OUTDOOR UNIT  
ANGLE−TYPE SERVICE VALVE  
(FRONT−SEATED CLOSED)  
ANGLE−TYPE SERVICE VALVE  
(BACK−SEATED OPENED)  
When service valve is OPEN, the service port is  
open to linE set, indoor and outdoor unit.  
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN  
TO THE LINE SET AND INDOOR UNIT.  
To Access Service Port:  
Operating Ball Type Service Valve:  
A service port cap protects the service port core from contamination and  
serves as the primary leak seal.  
1. Remove stem cap with an appropriately sized wrench.  
2. Use an appropriately sized wrenched to open. To open valve,  
rotate stem counterclockwise 90°. To close rotate stem  
clockwise 90°.  
1. Remove service port cap with an appropriately sized wrench.  
2. Connect gauge set to service port.  
3. When testing is completed, replace service port cap and tighten as  
follows:  
TO INDOOR UNIT  
1/6 TURN  
S
S
With torque wrench: Finger tighten and  
torque cap per table 1.  
12  
6
1
5
11  
10  
Without torque wrench: Finger tighten and  
use an appropriately sized wrench to turn  
an additional 1/6 turn clockwise.  
2
TO OPEN ROTATE STEM  
COUNTERCLOCKWISE 90°.  
9
3
BALL (SHOWN  
CLOSED)  
4
8
7
VALVE  
TO CLOSE ROTATE STEM  
STEM  
Reinstall Stem Cap:  
CLOCKWISE 90°.  
Stem cap protects the valve stem from damage and serves as the  
primary seal. Replace the stem cap and tighten as follows:  
SERVICE PORT  
1/12 TURN  
SERVICE PORT  
CORE  
S
S
With Torque Wrench: Finger tighten and  
then torque cap per table 1.  
12  
6
1
5
11  
10  
SERVICE PORT  
CAP  
Without Torque Wrench: Finger tight-  
en and use an appropriately sized  
wrench to turn an additional 1/12 turn  
clockwise.  
2
9
3
STEM CAP  
4
TO OUTDOOR  
UNIT  
8
7
NOTE ꢀ A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.  
Figure 2. Angle and Ball Service Valves  
Page 5  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Recovering Refrigerant from Existing System  
Use the following procedure to recover refrigerant from an existing system (indoor coil, line set and outdoor unit).  
CONNECT MANIFOLD GAUGE SET  
DISCONNECT POWER  
Disconnect all power to the existing outdoor unit at the service  
Connect a gauge set, clean recovery cylinder and a recovery  
machine to the service ports of the existing unit. Use the  
instructions provided with the recovery machine to make the  
connections.  
1
2
disconnect switch or main fuse box/breaker panel.  
MAIN FUSE BOX/BREAKER PANEL  
MANIFOLD GAUGES  
RECOVERY MACHINE  
SERVICE  
DISCONNECT  
SWITCH  
LOW  
HIGH  
OUTDOOR UNIT  
CLEAN RECOVERY  
CYLINDER  
RECOVERING REFRIGERANT  
Remove existing HCFC−22 refrigerant using one of the following procedures:  
3
IMPORTANT ꢀ Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,  
and/or long line sets.  
METHOD 1:  
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing  
HCFC−22 to flush the system.  
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of  
refrigerant.  
METHOD 2:  
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the  
system.  
The following devices could prevent full system charge recovery into the outdoor unit:  
S
S
S
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.  
Compressor can stop pumping due to tripped internal pressure relief valve.  
Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets  
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.  
Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and  
internal seals.)  
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the  
main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.  
Perform the following task:  
A
B
Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.  
Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit  
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.  
NOTE ꢀ It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.  
C
D
When the low side system pressures reach 0 psig, close the vapor line valve.  
Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.  
Figure 3. Refrigerant Recovery Procedure  
Page 6  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
MINIMUM CLEARANCE  
ABOVE UNIT  
CLEARANCE ON ALL SIDES ꢀ INCHES (MILLIMETERS)  
6 (152)  
ACCESS PANEL  
NOTES:  
48 (1219)  
S
Clearance to one of the other three  
sides must be 36 inches (914mm).  
30 (762)  
12 (305)  
S
Clearance to one of the remaining  
two sides may be 12 inches  
(305mm) and the final side may be  
6 inches (152mm).  
LINE SET  
CONNECTIONS  
36 (914)  
MINIMUM CLEARANCE BETWEEN  
TWO UNITS  
ACCESS PANEL  
24 (610)  
LINE SET  
CONNECTIONS  
Figure 4. Installation Clearances  
DETAIL B  
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees  
(or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.  
DETAIL A  
INSTALL UNIT AWAY  
FROM WINDOWS  
DISCHARGE AIR  
BUILDING  
STRUCTURE  
MOUNTING  
SLAB  
TWO 90_ ELBOWS INSTALLED IN LINE SET  
WILL REDUCE LINE SET VIBRATION  
GROUND LEVEL  
Figure 5. Placement, and Slab Mounting  
Consider the following when positioning the unit:  
New Unit Placement  
S
Some localities are adopting sound ordinances based  
on the unit’s sound level registered from the adjacent  
property, not from the installation property. Install the  
unit as far as possible from the property line.  
See Unit Dimensions on page 2 for sizing mounting slab,  
platforms or supports. Refer to figure 4 for mandatory  
installation clearance requirements.  
POSITIONING CONSIDERATIONS  
S
When possible, do not install the unit directly outside  
a window. Glass has a very high level of sound  
transmission. For proper placement of unit in relation  
to a window see the provided illustration in figure 5,  
detail A.  
CAUTION  
In order to avoid injury, take proper precaution when  
lifting heavy objects.  
Page 7  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PLACING UNIT ON SLAB  
When installing unit at grade level, the top of the slab  
should be high enough above grade so that water from  
higher ground will not collect around the unit. The slab  
should have a slope tolerance as described in figure 5,  
detail B.  
NOTICE  
Roof Damage!  
This system contains both refrigerant and oil. Some  
rubber roofing material may absorb oil and cause the  
rubber to swell when it comes into contact with oil. The  
rubber will then bubble and could cause leaks. Protect  
the roof surface to avoid exposure to refrigerant and oil  
during service and installation. Failure to follow this  
notice could result in damage to roof surface.  
ROOF MOUNTING  
Install the unit at a minimum of 4 inches (102 mm) above  
the surface of the roof. Ensure the weight of the unit is  
properly distributed over roof joists and rafters. Redwood  
or steel supports are recommended.  
Removing and Installing Louvers  
WARNING  
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:  
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel,  
nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).  
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown  
around and battered.  
PANEL B  
PANEL C  
When removing the unit panels. Remove panel A first, then B, C and  
finally D. When reinstalling panels, reverse that order starting with panel  
D, C, B and finally A.  
REMOVAL  
WARNING  
PANEL A  
STEP 1  
TO REMOVE PANEL,  
PANEL D  
REMOVE MOUNTING  
SCREWS SECURING  
PANEL TO THE UNIT.  
INSTALLATION  
STEP 1  
STARTING WITH PANEL D,  
INSERT PANEL UNDER UNIT  
TOP CAP LIP AND LIFT  
TOP CAP  
PANEL A  
SLIGHTLY TO CLEAR SIDE LIP  
OF PANEL FROM BASE.  
STEP 2  
SLIGHTLY LIFT PANEL A IN  
ORDER TO CLEAR SIDE  
LIPS OF PANEL FROM  
BASE OF UNIT.  
STEP 2  
MOVE PANEL IN TOWARDS UNIT.  
ALIGN LEFT/RIGHT SIDE LIPS OF  
PANEL WITH GROOVE INSERTS  
ALONG LEFT/RIGHT SIDE OF UNIT.  
STEP 3  
TILT PANEL OUT SLIGHTLY  
AND PULL DOWNWARD  
TO REMOVE.  
SIDE  
GROOVE  
REPEAT STEPS 1, 2 AND  
3 TO REMOVE PANELS B,  
C AND FINALLY D.  
STEP 3  
SECURE PANEL, WITH  
MOUNTING SCREWS.  
REPEAT STEPS 1 AND 2 TO  
INSTALL PANELS C, B AND  
FINALLY A.  
PANEL A  
BASE  
PANEL D  
Figure 6. Louvers  
Page 8  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Recommended topping−off POE oils are Mobil EAL  
ARCTIC 22 CC or ICI EMKARATEt RL32CF.  
New or Replacement Line Set  
This section provides information on new installation or  
replacement of existing line set. If a new or replacement  
line set is not required, then proceed to Brazing  
Connections on page 11.  
MATCHING WITH NEW OR EXISTING INDOOR COIL  
AND LINE SET  
The RFC1−metering line consisted of a small bore copper  
line that ran from condenser to evaporator coil. Refrigerant  
was metered into the evaporator by utilizing  
temperature/pressure evaporation effects on refrigerant in  
the small RFC line. The length and bore of the RFC line  
corresponded to the size of cooling unit.  
Field refrigerant piping consists of liquid and suction lines  
from the outdoor unit (braze connections) to the indoor unit  
coil (flare or braze connections). Use Lennox L15 (braze,  
non−flare) series line set, or use field−fabricated refrigerant  
lines as listed in table 2.  
If the 14ACX is being used with either a new or existing  
indoor coil which is equipped with a liquid line which served  
as a metering device (RFCI), the liquid line must be  
replaced prior to the installation of the 14ACX unit.  
Typically a liquid line used to meter flow is 1/4" in diameter  
and copper.  
NOTE − When installing refrigerant lines longer than 50  
feet, see the Lennox Refrigerant Piping Design and  
Fabrication Guidelines, CORP. 9351−L9, or contact  
Lennox Technical Support Product Applications for  
assistance.  
To obtain the correct information from Lennox, be sure to  
communicate the following points:  
LIQUID LINE FILTER DRIER INSTALLATION  
The filter drier (one is shipped with each 14ACX unit) must  
be field installed in the liquid line between the outdoor unit’s  
liquid line service valve and the indoor coil’s metering  
device (fixed orifice or TXV) as illustrated in figure 7. This  
filter drier must be installed to ensure a clean,  
moisture−free system. Failure to install the filter drier will  
void the warranty. A replacement filter drier is available  
from Lennox. See Brazing Connections page 11 for  
special procedures on brazing filter drier connections to  
the liquid line.  
S
S
Model (14ACX) and size of unit (e.g. −060).  
Line set diameters for the unit being installed as listed  
in table 2 and total length of installation.  
S
Number of elbows and if there is a rise or drop of the  
piping.  
If refrigerant lines are routed through a wall, seal and  
isolate the opening so vibration is not transmitted to the  
building. Pay close attention to line set isolation during  
installation of any HVAC system. When properly isolated  
from building structures (walls, ceilings. floors), the  
refrigerant lines will not create unnecessary vibration and  
subsequent sounds.  
BRAZE CONNECTION POINTS  
IMPORTANT  
Mineral oils are not compatible with HFC−410A. If oil  
must be added, it must be a Polyol ester oil.  
LIQUID  
LINE  
LIQUID LINE  
LINE  
SERVICE VALVE  
LIQUID LINE  
FILTER DRIER  
The compressor is charged with sufficient Polyol ester oil  
for line set lengths up to 50 feet. Recommend adding oil to  
system based on the amount of refrigerant charge in the  
system. No need to add oil in system with 20 pounds of  
refrigerant or less. For systems over 20 pounds − add one  
ounce of every five pounds of refrigerant.  
OUTDOOR  
UNIT  
Figure 7. Typical Liquid Line Filter Drier Installation  
Table 2. Refrigerant Line Set ꢀ Inches (mm)  
Valve Field Size Connections  
Model Number  
Recommended Line Set  
Liquid Line  
Suction Line  
Liquid Line  
Suction Line  
L15 Series Line Sets  
14ACX−018−230  
14ACX−024−230  
14ACX−030−230  
14ACX−036−230  
14ACX−041−230  
14ACX−042−230  
14ACX−047−230  
14ACX−048−230  
14ACX−059−230  
14ACX−060−230  
L15−41 ꢀ 15 feet to 50 feet (4.6 meters to  
15 meters)  
3/8 in. (10 mm)  
3/4 in. (19 mm)  
3/8 in. (10 mm)  
3/4 in. (19 mm)  
L15−65 ꢀ 15 feet to 50 feet (4.6 meters to  
15 meters)  
3/8 in. (10 mm)  
3/8 in. (10 mm)  
7/8 in. (22 mm)  
3/8 in. (10 mm)  
3/8 in. (10 mm)  
7/8 in. (22 mm)  
1−1/8 in. (29 mm)  
1−1/8 in. (29 mm)  
Field Fabricated  
NOTE ꢀ Some applications may required a field provided 7/8" to 1−1/8" adapter  
Page 9  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
IMPORTANT ꢀ Refrigerant lines must not contact structure.  
LINE SET  
Line Set Isolation ꢀ The following illustrations are  
examples of proper refrigerant line set isolation:  
INSTALLATION  
REFRIGERANT LINE SET ꢀ INSTALLING  
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)  
NOTE ꢀ Insulate liquid line when it is routed through areas where the  
surrounding ambient temperature could become higher than the  
temperatureof the liquid line or when pressure drop is equal to or greater  
than 20 psig.  
REFRIGERANT LINE SET ꢀ TRANSITION  
FROM VERTICAL TO HORIZONTAL  
ANCHORED HEAVY NYLON  
IMPORTANT ꢀ Refrigerant lines must not contact wall  
WIRE TIE OR AUTOMOTIVE  
MUFFLER-TYPE HANGER  
AUTOMOTIVE  
MUFFLER-TYPE HANGER  
OUTSIDE WALL  
LIQUID LINE  
VAPOR LINE  
WALL  
STUD  
WIRE TIE  
INSIDE WALL  
STRAP  
WOOD BLOCK  
BETWEEN STUDS  
STRAP LIQUID LINE TO  
VAPOR LINE  
NON−CORROSIVE  
METAL SLEEVE  
WIRE TIE  
LIQUID LINE  
NON−CORROSIVE  
METAL SLEEVE  
WOOD BLOCK  
WIRE TIE  
VAPOR LINE − WRAPPED  
IN ARMAFLEX  
STRAP  
REFRIGERANT LINE SET ꢀ INSTALLING  
HORIZONTAL RUNS  
SLEEVE  
To hang line set from joist or rafter, use either metal strapping material  
or anchored heavy nylon wire ties.  
WIRE TIE (AROUND  
VAPOR LINE ONLY)  
VAPOR LINE WRAPPED  
WITH ARMAFLEX  
8 FEET (2.43 METERS)  
OUTSIDE  
WALL  
STRAPPING  
MATERIAL (AROUND  
VAPOR LINE ONLY)  
FLOOR JOIST OR  
LIQUID  
LINE  
ROOF RAFTER  
TAPE OR  
WIRE TIE  
8 FEET (2.43 METERS)  
PVC  
PIPE  
CAULK  
NON−CORROSIVE  
METAL SLEEVE  
FIBERGLASS  
INSULATION  
STRAP THE VAPOR LINE TO THE JOIST  
OR RAFTER AT 8 FEET (2.43 METERS)  
INTERVALS THEN STRAP THE LIQUID  
LINE TO THE VAPOR LINE.  
TAPE OR  
WIRE TIE  
NOTE ꢀ Similar installation practices should be used if line set is  
to be installed on exterior of outside wall.  
FLOOR JOIST OR  
ROOF RAFTER  
Figure 8. Line Set Installation Guidelines  
Page 10  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brazing Connections  
line set connections to service valves.  
IMPORTANT  
Connect gauge set low pressure side to vapor line  
service valve and repeat procedure starting at  
paragraph 4 for brazing the liquid line to service port  
valve.  
IMPORTANT  
Polyol ester (POE) oils used with HFC−410A  
refrigerant absorb moisture very quickly. It is very  
important that the refrigerant system be kept closed  
as much as possible. DO NOT remove line set caps  
or service valve stub caps until you are ready to make  
connections.  
IMPORTANT  
Allow braze joint to cool before removing the wet rag  
from the service valve. Temperatures above 250ºF can  
damage valve seals.  
WARNING  
IMPORTANT  
Use silver alloy brazing rods with 5% minimum silver  
alloy for copper−to−copper brazing. Use 45% minimum  
alloy for copper−to−brass and copper−to−steel brazing.  
Danger of fire. Bleeding the refrigerant  
charge from only the high side may result  
in pressurization of the low side shell and  
suction tubing. Application of a brazing  
torch to a pressurized system may result  
in ignition of the refrigerant and oil  
mixture − Check the high and low  
pressures before applying heat.  
WARNING  
Fire, Explosion and Personal Safety  
Hazard.  
WARNING  
Failure to follow this warning could  
result in damage, personal injury or  
death.  
When using a high pressure gas such as  
dry nitrogen to pressurize a refrigeration  
or air conditioning system, use a  
regulator that can control the pressure  
down to 1 or 2 psig (6.9 to 13.8 kPa).  
Never use oxygen to pressurize or  
purge refrigeration lines. Oxygen,  
when exposed to a spark or open  
flame, can cause fire and/or an ex-  
plosion, that could result in property  
damage, personal injury or death.  
CAUTION  
Brazing alloys and flux contain materials which are  
hazardous to your health.  
Avoid breathing vapors or fumes from brazing  
operations. Perform operations only in well−ventilated  
areas.  
Wear gloves and protective goggles or face shield to  
protect against burns.  
Wash hands with soap and water after handling brazing  
alloys and flux.  
Page 11  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CAP AND CORE REMOVAL  
CUT AND DEBUR  
Cut ends of the refrigerant lines square (free from nicks or dents)  
and debur the ends. The pipe must remain round. Do not crimp end  
of the line.  
Remove service cap and core from  
both the suction / vapor and liquid line  
service ports.  
2
1
CUT AND DEBUR  
SERVICE PORT  
CAP  
SERVICE  
PORT  
CORE  
LINE SET SIZE MATCHES  
SERVICE VALVE CONNECTION  
SERVICE  
PORT  
CORE  
SERVICE VALVE  
CONNECTION  
SERVICE  
PORT CAP  
COPPER TUBE  
STUB  
LIQUID LINE SERVICE  
VALVE  
SUCTION / VAPOR LINE  
SERVICE VALVE  
REDUCER  
LINE SET SIZE IS SMALLER  
THAN CONNECTION  
DO NOT CRIMP SERVICE VALVE  
CONNECTOR WHEN PIPE IS  
SMALLER THAN CONNECTION  
REFRIGERANT LINE  
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE  
VALVES  
3
Flow regulated nitrogen (at 1 to 2 psig) through the low−side refrigeration gauge set into the liquid line service port valve, and out of the suction /  
vapor line service port valve.  
A
B
C
Connect gauge set low pressure side to  
liquid line service valve (service port).  
USE REGULATOR TO FLOW  
NITROGEN AT 1 TO 2 PSIG.  
LOW  
HIGH  
Connect gauge set center port to bottle of  
nitrogenwith regulator.  
Remove core from valve in suction / vapor  
line service port to allow nitrogen to escape.  
ATTACH  
GAUGES  
B
SUCTION / VAPOR SERVICE PORT MUST BE  
OPEN TO ALLOW EXIT POINT FOR NITROGEN  
SUCTION /  
VAPOR LINE  
SERVICE  
VALVE  
C
VAPOR LINE  
OUTDOOR  
UNIT  
INDOOR  
UNIT  
NITROGEN  
LIQUID LINE SERVICE  
VALVE  
WHEN BRAZING LINE SET TO  
SERVICE VALVES, POINT FLAME  
AWAY FROM SERVICE VALVE.  
LIQUID LINE  
A
Figure 9. Brazing Procedures  
Page 12  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WRAP SERVICE VALVES  
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use  
additionalwater saturated cloths underneath the valve body to protect the base paint.  
4
FLOW NITROGEN  
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and  
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections  
5
6
BRAZE LINE SET  
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water  
saturated cloths must remain water saturated throughout the brazing and cool−down process.  
LIQUID LINE SERVICE VALVE  
WHEN BRAZING LINE SET TO  
SERVICE VALVES, POINT FLAME  
AWAY FROM SERVICE VALVE.  
IMPORTANT ꢀ Allow braze joint to cool. Apply  
additional water saturated cloths to help cool brazed  
joint. Do not remove water saturated cloths until piping  
has cooled. Temperatures above 250ºF will damage  
valve seals.  
WATER SATURATED  
CLOTH  
LIQUID LINE  
WARNING  
SUCTION / VAPOR LINE  
SERVICE VALVE  
1. FIRE, PERSONAL INJURY, OR PROPERTY  
DAMAGE will result if you do not wrap a water  
saturated cloth around both liquid and suction line  
service valve bodies and copper tube stub while  
brazing in the line set! The braze, when complete,  
must be quenched with water to absorb any residual  
heat.  
WHEN BRAZING LINE SET TO  
SERVICE VALVES, POINT FLAME  
AWAY FROM SERVICE VALVE.  
2. Do not open service valves until refrigerant lines and  
indoor coil have been leak−tested and evacuated.  
Refer to procedures provided in this supplement.  
SUCTION / VAPOR LINE  
WATER SATURATED  
CLOTH  
PREPARATION FOR NEXT STEP  
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both  
services valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step  
in preparing the unit.  
7
Figure 10. Brazing Procedures (continued)  
Page 13  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Flushing Line Set and Indoor Coil  
Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering  
Device on page 15.  
TYPICAL EXISTING FIXED ORIFICE  
REMOVAL PROCEDURE (UNCASED  
COIL SHOWN)  
TYPICAL EXISTING EXPANSION VALVE REMOVAL  
PROCEDURE (UNCASED COIL SHOWN)  
OR  
1B  
1A  
STUB END  
TWO PIECE PATCH PLATE  
(UNCASED COIL ONLY)  
LIQUID LINE  
ORIFICE  
HOUSING  
CHECK  
EXPANSION  
VALVE  
DISTRIBUTOR TUBES  
LIQUID LINE ORIFICE HOUSING  
DISTRIBUTOR  
TUBES  
®
TEFLON  
RING  
®
TEFLON RING  
FIXED ORIFICE  
BRASS NUT  
®
TEFLON  
RING  
SENSING  
LINE  
DISTRIBUTOR  
ASSEMBLY  
DISTRIBUTOR  
ASSEMBLY  
EQUALIZER  
LINE  
REMOVE AND DISCARD  
®
WHITE TEFLON SEAL  
(IF PRESENT)  
LIQUID LINE ASSEMBLY  
(INCLUDES STRAINER)  
LIQUID LINE  
ASSEMBLY WITH  
BRASS NUT  
A
B
On fully cased coils, remove the coil access and plumbing panels.  
Remove any shipping clamps holding the liquid line and distributor as-  
sembly.  
MALE EQUALIZER  
LINE FITTING  
VAPOR  
LINE  
C
Using two wrenches, disconnect liquid line from liquid line orifice hous-  
ing. Take care not to twist or damage distributor tubes during this pro-  
cess.  
LIQUID  
LINE  
SENSING BULB  
A
B
On fully cased coils, remove the coil access and plumbing panels.  
D
E
Remove and discard fixed orifice, valve stem assembly if present and  
®
Teflon washer as illustrated above.  
Remove any shipping clamps holding the liquid line and distributor  
assembly.  
Use a field−provided fitting to temporary reconnect the liquid line to the  
indoor unit’s liquid line orifice housing.  
C
Disconnect the equalizer line from the check expansion valve  
equalizer line fitting on the vapor line.  
D
E
Remove the vapor line sensing bulb.  
CONNECT GAUGES AND EQUIPMENT FOR  
FLUSHING PROCEDURE  
Disconnect the liquid line from the check expansion valve at the liquid  
line assembly.  
2
INVERTED HCFC−22  
GAUGE  
MANIFOLD  
F
Disconnect the check expansion valve from the liquid line orifice  
housing.Take care not to twist or damage distributor tubes during this  
process.  
CYLINDER CONTAINS  
CLEAN HCFC−22 TO BE  
USED FOR FLUSHING.  
A
®
G
H
Remove and discard check expansion valve and the two Teflon rings.  
LOW  
HIGH  
1
Use a field−provided fitting to temporary reconnect the liquid line to the  
indoor unit’s liquid line orifice housing.  
NEW  
OUTDOOR  
UNIT  
VAPOR LINE  
SERVICE VALVE  
FLUSHING LINE SET  
The line set and indoor unit coil must be flushed with at least the  
same amount of clean refrigerant that previously charged the  
system. Check the charge in the flushing cylinder before  
proceeding.  
OPENED  
CLOSED  
3
EXISTING  
INDOOR  
UNIT  
B
LIQUID LINE SERVICE  
VALVE  
A
Set the recovery machine for liquid recovery and start the  
recovery machine. Open the gauge set valves to allow the  
recovery machine to pull a vacuum on the existing system line  
TANK  
RETURN  
set and indoor unit coil.  
B
B
Invert the cylinder of clean HCFC−22 and open its valve to allow  
liquid refrigerant to flow into the system through the vapor line  
valve. Allow the refrigerant to pass from the cylinder and through  
the line set and the indoor unit coil before it enters the recovery  
machine.  
C
INLET  
D
RECOVERY  
CYLINDER  
DISCHARGE  
RECOVERY MACHINE  
C
D
After all of the liquid refrigerant has been recovered, switch the  
recovery machine to vapor recovery so that all of the HCFC−22  
vapor is recovered. Allow the recovery machine to pull down to 0  
the system.  
A
Inverted HCFC−22 cylinder with clean refrigerant to the vapor service  
valve.  
B
C
HCFC−22 gauge set (low side) to the liquid line valve.  
HCFC−22 gauge set center port to inlet on the recovery machine with an  
empty recovery tank to the gauge set.  
Close the valve on the inverted HCFC−22 drum and the gauge  
set valves. Pump the remaining refrigerant out of the recovery  
machine and turn the machine off.  
D
Connect recovery tank to recovery machines per machine instructions.  
Figure 11. Removing Metering Device and Flushing  
Page 14  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing Indoor Metering Device  
This outdoor unit is designed for use in systems that use  
either an fixed orifice (RFC) (included with outdoor unit), or  
expansion valve metering device (purchased separately)  
at the indoor coil.  
coil. In applications where an uncased coil is being  
installed in a field−provided plenum, install the expansion  
valve in a manner that will provide access for field servicing  
of the expansion valve. Refer to below illustration for  
reference during installation of expansion valve unit. .  
See the Lennox 14ACX Engineering Handbook for  
approved expansion valve kit match ups. The expansion  
valve unit can be installed internal or external to the indoor  
After installation of the indoor coil metering device,  
proceed to Leak Test Line Set and Indoor Coil on page 16.  
1/2 Turn  
A
B
Remove the field−provided fitting that temporary  
reconnectedthe liquid line to the indoor unit’s distributor  
assembly.  
INDOOR EXPANSION VALVE INSTALLATION  
TWO PIECE  
12  
PATCH PLATE  
(Uncased Coil Shown)  
1
11  
10  
®
(UNCASED  
STUB  
END  
2
Install one of the provided Teflon rings around the  
stubbed end of the expansion valve and lightly lubricate  
LIQUID LINE  
ORIFICE  
COIL ONLY)  
9
3
EXPANSION  
VALVE  
4
8
®
the connector threads and expose surface of the Teflon  
ring with refrigerant oil.  
HOUSING  
5
7
6
DISTRIBUTOR  
TUBES  
®
TEFLON  
RING  
C
D
E
Attach the stubbed end of the expansion valve to the  
liquid line orifice housing. Finger tighten and use an  
appropriatelysized wrench to turn an additional 1/2 turn  
clockwise as illustrated in the figure above, or 20 ft−lb.  
®
®
Place the remaining Teflon washer around the other  
end of the expansion valve. Lightly lubricate connector  
TEFLON  
RING  
SENSING  
LINE  
®
threads and expose surface of the Teflon ring with  
refrigerantoil.  
DISTRIBUTOR  
ASSEMBLY  
EQUALIZER  
LINE  
Attach the liquid line assembly to the expansion valve.  
Finger tighten and use an appropriately sized wrench to  
turn an additional 1/2 turn clockwise as illustrated in the  
figure above or 20 ft−lb.  
LIQUID LINE  
ASSEMBLY WITH  
BRASS NUT  
SENSING BULB INSTALLATION  
A
Attach the vapor line sensing bulb in the proper  
orientationas illustrated to the right using the clamp and  
screws provided.  
1/8 Turn  
MALE EQUALIZER LINE  
FITTING (SEE  
VAPOR  
LINE  
EQUALIZER LINE  
INSTALLATION FOR  
FURTHER DETAILS)  
NOTE ꢀ Confirm proper thermal contact between vapor line  
and expansion bulb before insulating the sensing bulb once  
installed.  
12  
1
5
11  
10  
2
LIQUID LINE  
9
3
4
8
B
Connect the equalizer line from the expansion valve to  
the equalizer vapor port on the vapor line. Finger tighten  
the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.  
7
Sensing bulb insulation is required if  
mountedexternal to the coil casing. sensing  
bulb installation for bulb positioning.  
6
ON LINES SMALLER THAN  
7/8", MOUNT SENSING  
BULB AT EITHER THE 3 OR  
9 O’CLOCK POSITION.  
VAPOR LINE  
EQUALIZER LINE INSTALLATION  
A
Remove and discard either the flare seal cap or flare nut  
with copper flare seal bonnet from the equalizer line port  
on the vapor line as illustrated in the figure to the right.  
12  
BULB  
BULB  
B
Remove and discard either the flare seal cap or flare nut  
with copper flare seal bonnet from the equalizer line port on  
the vapor line as illustrated in the figure to the right.  
FLARE SEAL CAP  
FLARE NUT  
VAPOR LINE  
ON 7/8" AND LARGER LINES,  
MOUNT SENSING BULB AT  
EITHER THE 4 OR 8 O’CLOCK  
POSITION. NEVER MOUNT ON  
BOTTOM OF LINE.  
COPPER FLARE  
SEAL BONNET  
OR  
12  
MALE BRASS EQUALIZER  
LINE FITTING  
BULB  
BULB  
NOTE ꢀ NEVER MOUNT ON BOTTOM OF LINE.  
VAPOR LINE  
Figure 12. Installing Indoor Expansion Valve  
Page 15  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Leak Test Line Set and Indoor Coil  
IMPORTANT  
The Environmental Protection Agency (EPA) prohibits  
the intentional venting of HFC refrigerants during  
maintenance, service, repair and disposal of appliance.  
Approved methods of recovery, recycling or reclaiming  
must be followed.  
IMPORTANT  
Leak detector must be capable of sensing HFC  
refrigerant.  
After completing the leak testing the line set and indoor coil  
as outlined in figure 13, proceed to Evacuating Line Set  
and Indoor Coil on page 17.  
IMPORTANT  
WARNING  
If this unit is being matched with an approved line set  
or indoor unit coil which was previously charged with  
mineral oil, or if it is being matched with a coil which  
was manufactured before January of 1999, the coil  
and line set must be flushed prior to installation. Take  
care to empty all existing traps. Polyol ester (POE) oils  
are used in Lennox units charged with HFC−410A  
refrigerant. Residual mineral oil can act as an  
insulator, preventing proper heat transfer. It can also  
clog the expansion device, and reduce the system  
performance and capacity.  
When using a high pressure gas such as  
dry nitrogen to pressurize a refrigeration  
or air conditioning system, use a  
regulator that can control the pressure  
down to 1 or 2 psig (6.9 to 13.8 kPa).  
WARNING  
Refrigerant can be harmful if it is inhaled. Refrigerant  
must be used and recovered responsibly.  
Failure to properly flush the system per the  
instructions below will void the warranty.  
Failure to follow this warning may result in personal injury  
or death.  
CONNECT GAUGE SET  
A
Connect an HFC−410A manifold gauge set high pressure  
hose to the vapor valve service port.  
LOW  
HIGH  
MANIFOLD GAUGE SET  
1
NOTE ꢀ Normally, the high pressure hose is connected to  
the liquid line port. However, connecting it to the vapor port  
better protects the manifold gauge set from high pressure  
damage.  
OUTDOOR UNIT  
B
With both manifold valves closed, connect the cylinder of  
HFC−410A refrigerant to the center port of the manifold gauge  
set.  
NOTE ꢀ Later in the procedure,  
the HFC−410A container will be  
replaced by the nitrogen  
container.  
A
B
TO VAPOR  
SERVICE VALVE  
NITROGEN  
HFC−410A  
TEST FOR LEAKS  
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the  
following procedure to test for leaks:  
2
A
With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve  
on the HFC−410A cylinder (vapor only).  
B
Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A  
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder  
and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.  
C
D
Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.  
Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set  
and the indoor unit.  
E
F
After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak  
detector.  
After leak testing disconnect gauges from service ports.  
Figure 13. Leak Test  
Page 16  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Evacuating Line Set and Indoor Coil  
CONNECT GAUGE SET  
NOTE ꢀ Remove cores from service valves (if not already done).  
LOW  
HIGH  
1
A
Connect low side of manifold gauge set  
with 1/4 SAE in−line tee to vapor line  
service valve  
B
C
D
Connect high side of manifold gauge  
set to liquid line service valve  
OUTDOOR  
UNIT  
MANIFOLD  
GAUGE SET  
A34000 1/4 SAE TEE WITH  
SWIVEL COUPLER  
Connect micron gauge available  
connector on the 1/4 SAE in−line tee.  
Connect the vacuum pump (with  
vacuum gauge) to the center port of the  
manifold gauge set. The center port  
line will be used later for both the  
HFC−410A and nitrogen containers.  
A
500  
MICRON  
GAUGE  
C
TO VAPOR  
SERVICE VALVE  
NITROGEN  
HFC−410A  
B
VACUUM PUMP  
TO LIQUID LINE  
SERVICE VALVE  
D
EVACUATE THE SYSTEM  
RECOMMEND  
MINIMUM 3/8" HOSE  
A
B
Open both manifold valves and start the vacuum pump.  
Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).  
2
NOTE ꢀ During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure  
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.  
NOTE ꢀ The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of  
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.  
C
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:  
S
S
S
S
S
S
S
Close manifold gauge valves  
Close valve on vacuum pump  
Turn off vacuum pump  
Disconnect manifold gauge center port hose from vacuum pump  
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.  
Open manifold gauge valves to break the vacuum in the line set and indoor unit.  
Close manifold gauge valves.  
D
E
Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the  
dry nitrogen from the line set and indoor unit.  
Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the  
absolutepressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump  
and closing the manifold gauge valves.  
When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an  
F
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and  
indoor unit.  
Perform the following:  
G
1/6 TURN  
S
S
S
Close manifold gauge valves.  
Shut off HFC−410A cylinder.  
12  
1
5
11  
7
2
4
10  
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core  
tool while maintaining a positive system pressure.  
9
3
8
S
Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.  
6
Figure 14. Evacuating System  
Page 17  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
defined as any gas that will not condense under  
temperatures and pressures present during operation of  
an air conditioning system. Non−condensables and water  
suction combine with refrigerant to produce substances  
that corrode copper piping and compressor parts.  
WARNING  
Danger of Equipment Damage. Avoid deep vacuum  
operation. Do not use compressors to evacuate a  
system. Extremely low vacuums can cause internal  
arcing and compressor failure. Damage caused by  
deep vacuum operation will void warranty.  
IMPORTANT  
Use a thermocouple or thermistor electronic vacuum  
gauge that is calibrated in microns. Use an instrument  
capable of accurately measuring down to 50 microns.  
CAUTION  
Brazing alloys and flux contain materials which are  
hazardous to your health.  
Electrical  
In the U.S.A., wiring must conform with current local codes  
and the current National Electric Code (NEC). In Canada,  
wiring must conform with current local codes and the current  
Canadian Electrical Code (CEC).  
Avoid breathing vapors or fumes from brazing  
operations. Perform operations only in well ventilated  
areas.  
Refer to the furnace or air handler installation instructions  
for additional wiring application diagrams and refer to unit  
nameplate for minimum circuit ampacity and maximum  
overcurrent protection size.  
Wear gloves and protective goggles or face shield to  
protect against burns.  
Wash hands with soap and water after handling brazing  
alloys and flux.  
24VAC TRANSFORMER  
Use the transformer provided with the furnace or air  
handler for low-voltage control power (24VAC − 40 VA  
minimum)  
Evacuating the system of non−condensables is critical for  
proper operation of the unit. Non−condensables are  
INSTALL THERMOSTAT  
SIZE CIRCUIT AND INSTALL SERVICE  
DISCONNECT SWITCH  
Install room thermostat (ordered separately) on an inside wall  
approximatelyin the center of the conditioned area and 5 feet (1.5m) from  
the floor. It should not be installed on an outside wall or where it can be  
affected by sunlight or drafts.  
Refer to the unit nameplate for minimum circuit ampacity, and maximum  
fuse or circuit breaker (HACR per NEC). Install power wiring and properly  
sized disconnect switch.  
MAIN FUSE BOX/  
BREAKER PANEL  
THERMOSTAT  
SERVICE  
DISCONNECT  
SWITCH  
5 FEET  
(1.5M)  
NOTE ꢀ 24VAC, Class II circuit connections are made in the control  
panel.  
NOTE ꢀ Units are approved for use only with copper conductors.  
Ground unit at disconnect switch or to an earth ground.  
WARNING  
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and  
local codes.  
Line voltage is present at all components when unit is not in operation on units with single-pole contactors.  
Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power  
supplies.  
Page 18  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SINGLE PHASE  
ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING  
HIGH VOLTAGE  
HIGH VOLTAGE / GROUND WIRES  
CONNECTIONS  
(CONTACTOR)  
B
Any excess high voltage field wiring should be trimmed and  
secured away from any low voltage field wiring. To facilitate a  
conduit, a cutout is located in the bottom of the control panel.  
Connect conduit to the control panel using a proper conduit fitting.  
CONTROL  
WIRING  
LOW VOLTAGE CONTROL WIRING  
NOTE ꢀ Wire tie provides low voltage control wire strain relief and to  
maintain separation of field installed low and high voltage circuits.  
GROUND  
HIGH VOLTAGE  
FIELD WIRING  
NOTE ꢀ For proper voltages, select thermostat wire (control wires)  
gauge per table above.  
LOW VOLTAGE  
FIELD WIRING  
HIGH VOLTAGE  
FLEXIBLE  
CONDUIT  
FACTORY  
WIRING  
NOTE ꢀ Do not bundle any excess 24VAC control wires inside  
control panel.  
INDOOR UNIT  
THERMOSTAT  
Install low voltage wiring from outdoor to indoor unit and from thermostat  
to indoor unit as illustrated.  
A
POWER  
R
GROMMET AND  
WIRE TIE  
R
A
Run 24VAC control wires through hole with grommet and secure with  
provided wire tie.  
HEAT  
OUTDOOR  
UNIT  
W
Y
B
Make 24VAC thermostat wire connections. Locate the two wires from the  
contactor and make connection using field provided wire nuts:  
W1  
YELLOW  
COOLING  
S
S
Yellow to Y1  
Y1  
Y
G
C
Black to C (common)  
INDOOR  
BLOWER  
WIRE RUN LENGTH  
AWG# INSULATION TYPE  
G
C
BLACK  
LESS THAN 100’ (30 METERS) 18  
MORE THAN 100’ (30 METERS) 16  
TEMPERATURE RATING  
35ºC MINIMUM.  
COMMON  
C
Figure 15. Typical Field Wiring Diagram  
Page 19  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HIGH PRESSURE SWITCH  
(S4) ꢀ LIQUID LINE  
CRANKCASE HEATER (HR1)  
CRANKCASE THERMOSTAT (S40)  
Figure 16. Typical Factory Wiring Diagram (Copeland Compressor)  
Page 20  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
THERMAL PROTECTION  
SWITCH (S5 OR S173)  
HIGH PRESSURE SWITCH  
(S4) ꢀ LIQUID LINE  
CRANKCASE HEATER (HR1)  
CRANKCASE THERMOSTAT (S40)  
Figure 17. Typical Factory Wiring Diagram (Interlink Compressor)  
Page 21  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Inspect all factory− and field−installed wiring for loose  
connections.  
Servicing Units Delivered Void of Charge  
If the outdoor unit is void of refrigerant, clean the system  
using the procedure described below.  
3. After evacuation is complete, open the liquid line and  
suction line service valve stems (Operating Service  
(contained in outdoor unit) into the system.  
1. Leak check system using procedure outlined in this  
instruction.  
4. Replace the stem caps and tighten to the value listed  
in table 1.  
2. Evacuate the system using procedure outlined in this  
instruction.  
5. Check voltage supply at the disconnect switch. The  
voltage must be within the range listed on the unit’s  
nameplate. If not, do not start the equipment until you  
have consulted with the power company and the  
voltage condition has been corrected.  
3. Use nitrogen to break the vacuum and install a new  
filter drier in the system.  
4. Evacuate the system again using procedure outlined  
in this instruction.  
6. Connect manifold gauge set for testing and charging  
using figure 18 as a guideline.  
5. Weigh in refrigerant using procedure outlined under  
Start−Up and Charging Procedures.  
7. Set the thermostat for a cooling demand. Turn on  
power to the indoor indoor unit and close the outdoor  
unit disconnect switch to start the unit.  
6. Monitor the system to determine the amount of  
moisture remaining in the oil. It may be necessary to  
replace the filter drier several times to achieve the  
required dryness level. If system dryness is not  
verified, the compressor will fail in the future.  
8. Recheck voltage while the unit is running. Power must  
be within range shown on the unit nameplate.  
9. Check system for sufficient refrigerate using the  
procedures outlined in under System Refrigerant.  
Unit Start−Up  
System Refrigerant  
IMPORTANT  
If unit is equipped with a crankcase heater, it should be  
energized 24 hours before unit start−up to prevent  
compressor damage as a result of slugging.  
This section outlines procedures for:  
1. Connecting gauge set for testing and charging;  
2. Checking and adjusting indoor airflow;  
3. Adding or removing refrigerant.  
1. Rotate fan to check for binding.  
GAUGE SET  
MANIFOLD GAUGE SET  
CONNECTIONS FOR TESTING AND CHARGING  
HIGH  
LOW  
SUCTION LINE  
SERVICE PORT  
CONNECTION  
B
OUTDOOR UNIT  
AClose manifold gauge set valves and connect  
the center hose to a cylinder of HFC−410A.  
Set for liquid phase charging.  
REFRIGERANT TANK  
BConnect the manifold gauge set’s low pressure  
side to the suction line service port.  
CHARGE IN  
LIQUID PHASE  
A
CConnect the manifold gauge set’s high  
pressure side to the liquid line service port.  
DIGITAL SCALE  
DPosition temperature sensor on liquid line near  
liquid line service port.  
TEMPERATURE SENSOR  
(LIQUID LINE)  
C
TO LIQUID  
LINE SERVICE  
VALVE  
D TEMPERATURE  
SENSOR  
Figure 18. Manifold Gauge Set Setup and Connections  
Page 22  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CHECKING AIR FLOW AT INDOOR COIL  
Check airflow using the Delta−T (DT) process using the illustration in figure 19.  
DT  
Temp.  
of air  
entering  
indoor  
coil ºF  
1. Determine the desired DTꢀMeasure entering air temper-  
ature using dry bulb (A) and wet bulb (B). DT is the intersect-  
ing value of A and B in the table (see triangle).  
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15  
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14  
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13  
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12  
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10  
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10  
2. Find temperature drop across coilꢀMeasure the coil’s dry  
bulb entering and leaving air temperatures (A and C). Tem-  
A
perature Drop Formula: (T  
) = A minus C.  
Drop  
Wet−bulb ºF  
57 58 59 60 61 62 63 64 65 66 67 68 69 70  
B
3. Determine if fan needs adjustmentꢀIf the difference between  
the measured T and the desired DT (T DT) is within  
Drop  
Drop  
+3º, no adjustment is needed. See examples: Assume DT =  
15 and A temp. = 72º, these C temperatures would necessi-  
tate stated actions:  
A
T
Drop  
C
72º  
19º  
53º  
Cº  
T
DT  
=
ºF ACTION  
Drop  
19  
B
air flow  
air flow  
53º  
58º  
62º  
15  
15  
15  
=
=
=
4
Increase the airflow  
DRY  
BULB  
DRY  
BULB  
64º  
14  
−1 (within +3º range) no change  
10  
−5 Decrease the airflow  
WET  
BULB  
INDOOR  
COIL  
All temperatures are  
expressed in ºF  
4. Adjust the fan speedꢀSee indoor unit instructions to in-  
crease/decrease fan speed.  
Changing air flow affects all temperatures; recheck tempera-  
tures to confirm that the temperature drop and DT are within  
+3º.  
Figure 19. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart  
START: Determine how refrigerant is metered  
WHEN TO CHARGE?  
Which  
metering  
device?  
S
S
Best during warm weather  
Can charge in colder weather by determining  
best charge method? Determine by:  
A
B
Metering device type  
Outdoor ambient temperature  
RFC  
TXV  
REQUIREMENTS:  
S
S
S
S
Sufficient heat load in structure  
65ºF  
(18.3ºC) and  
Above  
40ºF  
(4.4ºC) and  
Above  
39ºF  
(3.8ºC) and  
Below  
64ºF  
(17.7ºC) and  
Below  
Indoor temperature between 70-80ºF (21−26ºC)  
Manifold gauge set connected to unit  
Thermometers:  
to measure outdoor ambient temperature  
to measure liquid line temperature  
to measure suction line temperature  
APPROACH OR  
SUBCOOLING  
WEIGH-IN  
SUPERHEAT  
WEIGH-IN  
Figure 20. Determining Charge Method  
Page 23  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WEIGH IN (RFC AND TXV)  
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE  
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the  
unit. To calculate the total refrigerant charge:  
Adjust amount. for variation  
in line set length listed on  
line set length table below.  
nameplate  
Amount specified on  
Total charge  
+
=
Refrigerant Charge per Line Set Length  
Ounces per 5 feet (g per 1.5 m)  
Liquid Line  
adjust from 15 feet (4.6 m) line set*  
Set Diameter  
3/8" (9.5 mm)  
3 ounce per 5’ (85 g per 1.5 m)  
*If line length is greater than 15 ft. (4.6 m), add this amount. If  
line length is less than 15 ft. (4.6 m), subtract this amount.  
NOTE ꢀ Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the  
temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.  
NOTE ꢀ The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.  
Figure 21. Using HFC−410A Weigh In Method  
65ºF (18.3ºC)  
USE WEIGH-IN METHOD  
2. Compare unit pressures with table 4, Normal Operating  
Pressures.  
and Above  
Weigh-in or remove refrigerant  
based upon line length  
3. Set thermostat to call for heat (must have a cooling load  
between 70-80ºF (21−26ºC).  
ABOVE or  
BELOW  
4. Connect gauge set.  
64ºF  
(17.7ºC) and  
Below  
5. When heat demand is satisfied, set thermostat to call for  
cooling.  
6. Allow temperatures and pressures to stabilize.  
7. Record outdoor ambient temperature:  
AMBº =_________  
If value is greater than shown (high  
approach), add refrigerant; if less  
than shown (liquid temperature too  
close to ambient temperature, low  
approach), remove refrigerant.  
If refrigerant is added or  
removed, retest to confirm  
that unit is properly charged.  
8. Record liquid line temperature:  
LIQº = __________  
9. Subtract to determine approach (APPº):  
LIQº_____ − AMBº _____ = APPº_____  
10. Compare results with table below.  
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])  
ºF (ºC)*  
65 (18)  
75 (24)  
85 (29)  
95 (35)  
105 (41)  
115 (45)  
−018  
−024  
−030  
−036  
−041  
−042  
−047  
−048  
−059/−060  
8 (4.4)  
9 (5.0)  
9 (5.0)  
9 (5.0)  
9 (5.0)  
9 (5.0)  
4 (2.2)  
5 (2.8)  
6 (3.3)  
5 (2,8)  
3 (1.7)  
3 (1.7)  
2 (1.1)  
4 (2.2)  
4 (2.2)  
4 (2.2)  
4 (2.2)  
3 (1.7)  
2 (1.1)  
4 (2.2)  
6 (3.3)  
5 (2.8)  
5 (2.8)  
4 (2.2)  
2 (1.1)  
5 (2.8)  
8 (4.4)  
7 (3.9)  
6 (3.3)  
6 (3.3)  
3 (1.7)  
3 (1.7)  
4 (2.2)  
4 (2.2)  
4 (2.2)  
5 (2.8)  
6 (3.3)  
6 (3.3)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
9 (5.0)  
9 (5.0)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
7 (3.9)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
9 (5.0)  
*Temperature of air entering outdoor coil.  
Figure 22. HFC−410A Approach TXV Charge  
Page 24  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
65ºF (18.3ºC)  
and above  
USE WEIGH-IN METHOD  
2. Compare unit pressures with table 4, Normal  
OperatingPressures.  
Weigh-in or remove refrigerant  
based upon line length  
3. Set thermostat to call for heat (must have a cooling load  
between 70-80ºF (21−26ºC)  
ABOVE or  
BELOW  
64ºF (17.7ºC)  
and below  
4. Connect gauge set  
5. Measure outdoor ambient temperature  
6. When heat demand is satisfied, set thermostat to call for  
cooling  
BLOCK OUTDOOR COIL: [sometimes necessary with lower  
temperatures] Use cardboard or plastic sheet to restrict the  
airflow through the outdoor coil to achieve pressures from  
325−375psig (2240−2585 kPa). Higher pressures are needed  
to check charge. Block equal sections of air intake panels and  
move coverings sideways until the liquid pressure is in the  
above noted ranges.  
7. Allow temperatures and pressures to stabilize.  
NOTE − If necessary, block outdoor coil to maintain 325  
− 375 psig.  
8. Record liquid line temperature:  
CARDBOARD OR  
PLASTIC SHEET  
LIQº = ______  
9. Measure liquid line pressure and use the value to  
If value is MORE than shown,  
remove refrigerant.  
If refrigerant is added or  
removed, verify charge using  
the Approach Method.  
SATº = ______  
10. Subtract to determine subcooling (SCº):  
SATº_____ − LIQº _____ = SCº _____  
11. Compare results with table below.  
If value is LESS  
than shown, add  
refrigerant.  
MORE or  
LESS  
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])  
ºF (ºC)*  
−018  
−024  
−030  
−036  
13 (7.2)  
−041  
9 (5.0)  
−042  
10 (5.6)  
−047  
−048  
−059/−060  
8 (4.4)  
7 (3.9)  
8 (4.4)  
7 (3.9)  
6 (3.3)  
6 (3.3)  
65 (18)  
75 (24)  
85 (29)  
95 (35)  
105 (41)  
115 (45)  
10 (5.6)  
6 (3.3)  
6 (3.3)  
6 (3.3)  
10 (5.6)  
10 (5.6)  
10 (5.6)  
7 (3.9)  
8 (4.4)  
9 (5.0)  
9 (5.0)  
10 (5.6)  
11 (6.1)  
8 (4.4)  
6 (3.3)  
6 (3.3)  
7 (3.9)  
8 (4.4)  
6 (3.3)  
6 (3.3)  
6 (3.3)  
6 (3.3)  
6 (3.3)  
5 (2.8)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
7 (3.9)  
9 (5.0)  
7 (3.9)  
8 (4.4)  
9 (5.0)  
10 (5.6)  
7 (3.9)  
7 (3.9)  
7 (3.9)  
7 (3.9)  
6 (3.3)  
7 (3.9)  
8 (4.4)  
8 (4.4)  
8 (4.4)  
7 (3.9)  
*Temperature of air entering outdoor coil.  
Figure 23. HFC−410A Subcooling TXV Charge  
Page 25  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START: Measure outdoor ambient temperature  
USE WEIGH-IN METHOD  
39ºF  
(3.8ºC) and  
Below  
2. Compare unit pressures with table 4, Normal  
OperatingPressures.  
3. Use SUPERHEAT to correctly charge unit or to  
verify the charge is correct.  
Weigh-in or remove refrigerant  
based upon line length  
ABOVE or  
BELOW  
4. Set thermostat to call for heat (must have a cooling  
load between 70-80ºF (21−26ºC)  
40ºF  
(4.4ºC) and  
Above  
5. Connect gauge set.  
6. When heat demand is satisfied, set thermostat to  
call for cooling.  
SUPERHEAT RFC  
7. Allow temperatures and pressures to stabilize.  
SHº (Superheat) Values (+/−5ºF)  
Wet Bulb (air entering indoor coil)  
8. Measure the suction line pressure and use the use  
value to determine saturation temperature (table  
3):  
ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76  
40 15 18 20 23 26 29 32 34 38 41 43 46 48 51  
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49  
SATº =_________  
9. Record suction line temperature:  
VAPº =_________  
50  
11 14 16 19 22 25 28 31 34 37 39 42 44 47  
10. Subtract to determine superheat (SHº):  
VAPº − _____ SATº ______ = SHº______  
55  
9
7
-
12 14 17 20 23 27 30 33 36 38 40 42 44  
10 12 15 18 21 24 27 30 33 35 38 40 43  
60  
65  
6
-
-
-
-
-
-
-
-
-
-
10 13 16 19 21 24 27 30 33 36 38 41  
11. Record the wet bulb temperature (air entering  
indoor coil):  
70  
-
7
-
-
-
-
-
-
-
-
-
10 13 16 19 21 24 27 30 33 36 39  
WB =_______  
75  
-
6
-
-
-
-
-
-
-
-
9
5
-
12 15 18 21 24 28 31 34 37  
80  
-
8
-
-
-
-
-
-
-
12 15 18 21 25 28 31 35  
12. Record outdoor ambient temperature.  
13. Compare results with table to the left.  
85  
-
8
5
-
11 15 19 22 26 30 33  
90  
-
-
9
6
-
13 16 20 24 27 31  
10 14 18 22 25 29  
95  
-
-
100  
105  
110  
115  
-
-
-
8
5
-
12 16 21 24 28  
NOTE − Do not attempt to charge system where a  
dash appears, system could be overcharged.  
Superheat is taken at suction line service port.  
Suction line superheat must never be less than 5ºF  
at the suction line service port.  
-
-
-
-
9
6
-
13 17 22 26  
11 15 20 25  
If  
refrigerant  
is  
-
-
-
-
REMOVED, retest to  
confirm that unit is  
properly charged.  
-
-
-
-
-
8
14 18 24  
* Dry−bulb temperature (ºF) of entering outdoor ambient air.  
If refrigerant is  
ADDED, retest to  
confirm that unit is  
properly charged.  
If value is LESS than  
shown, then REMOVE  
refrigerant.  
If value is MORE  
than shown, then  
ADD refrigerant.  
MORE or  
LESS  
Figure 24. HFC−410A Superheat RFC Method  
Table 3. HFC−410A Temperature ꢀ Pressure (Psig)  
°F  
°C  
Psig  
°F  
°C  
Psig  
−40  
−35  
−30  
−25  
−20  
−15  
−10  
−5  
−40.0  
−37.2  
−34.4  
−31.7  
−28.9  
−26.1  
−23.3  
−20.6  
−17.8  
−15.0  
−12.2  
−9.4  
11.6  
14.9  
18.5  
22.5  
26.9  
31.7  
36.8  
42.5  
48.6  
55.2  
62.3  
70.0  
78.3  
87.3  
96.8  
107  
60  
65  
15.6  
18.3  
21.1  
23.9  
26.7  
29.4  
32.2  
35.0  
37.8  
40.6  
43.3  
46.1  
48.9  
170  
185  
201  
217  
235  
254  
274  
295  
317  
340  
365  
391  
418  
70  
75  
80  
85  
90  
95  
0
100  
105  
110  
115  
120  
5
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
−6.7  
−3.9  
125  
130  
135  
140  
145  
150  
51.7  
54.4  
57.2  
60.0  
62.8  
65.6  
446  
476  
507  
539  
573  
608  
−1.1  
1.7  
4.4  
118  
7.2  
130  
10.0  
12.8  
142  
155  
Page 26  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 4. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)  
Use this table to perform maintenance checks; it is not a procedure for charging the  
system. Minor variations in these pressures may be due to differences in installations.  
Significant deviations could mean that the system is not properly charged or that a  
problem exists with some component in the system.  
IMPORTANT  
Model  
−018  
−024  
−030  
−036  
−041  
−042  
−047  
−048  
−059/−060  
**Temp.  
5F (5C)  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Liquid /  
Suction  
Expansion Valve (TXV)*  
65 (18)  
70 (21)  
75 (24)  
80 (27)  
85 (29)  
90 (32)  
95 (35)  
100 (38)  
105 (41)  
110 (43)  
115 (45)  
230 / 138  
244 / 139  
265 / 140  
286 / 140  
307 / 142  
330 / 143  
351 / 144  
380 / 144  
407 / 145  
436 / 146  
466 / 147  
225 / 135  
242 / 137  
260 / 138  
282 / 140  
304 / 141  
326 / 142  
351 / 142  
376 / 144  
403 / 145  
433 / 145  
463 / 147  
226 / 129  
241 / 131  
259 / 134  
281 / 138  
301 / 140  
324 / 141  
348 / 142  
372 / 143  
399 / 144  
428 / 145  
456 / 146  
238 / 132  
254 / 135  
273 / 138  
293 / 140  
316 / 142  
340 / 143  
366 / 144  
392 / 145  
420 / 147  
449 / 148  
480 / 149  
233 / 142  
239 / 142  
256 / 143  
278 / 144  
299 / 145  
321 / 145  
343 / 146  
366 / 147  
389 / 148  
421 / 149  
452 / 151  
236 / 138  
253 / 140  
273 / 141  
296 / 142  
318 / 143  
341 / 144  
366 / 146  
392 / 147  
417 / 148  
445 / 149  
475 / 151  
233 / 139  
252 / 140  
272 / 141  
294 / 142  
315 / 142  
338 / 144  
361 / 144  
387 / 144  
413 / 145  
442 / 148  
465 / 148  
238 / 136  
256 / 138  
277 / 139  
299 / 140  
320 / 139  
343 / 140  
369 / 141  
395 / 142  
422 / 144  
450 / 146  
481 / 148  
239 / 133  
258 / 135  
278 / 136  
300 / 137  
323 / 138  
346 / 139  
370 / 140  
396 / 142  
415 / 143  
449 / 145  
476 / 147  
Fixed Orifice (RFC)*  
65 (18)  
70 (21)  
75 (24)  
80 (27)  
85 (29)  
90 (32)  
95 (35)  
100 (38)  
105 (41)  
110 (43)  
115 (46)  
232 / 124  
248 / 127  
267 / 131  
286 / 135  
307 / 138  
328 / 141  
351 / 143  
375 / 146  
400 / 148  
426 / 150  
457 / 153  
228 / 125  
244 / 127  
261 / 131  
284 / 134  
303 / 137  
325 / 140  
347 / 142  
370 / 144  
394 / 146  
420 / 148  
447 / 150  
229 / 128  
243 / 129  
261 / 132  
284 / 135  
305 / 138  
327 / 140  
349 / 142  
372 / 144  
396 / 146  
422 / 148  
449 / 150  
241 / 131  
258 / 134  
277 / 136  
298 / 139  
321 / 141  
342 / 143  
366 / 145  
392 / 147  
416 / 149  
446 / 151  
480 / 152  
228 / 131  
245 / 135  
263 / 138  
284 / 141  
306 / 144  
327 / 146  
348 / 148  
372 / 149  
395 / 151  
424 /153  
453 / 155  
248 / 135  
266 / 138  
285 / 141  
305 / 143  
327 / 145  
349 / 147  
372 / 149  
396 / 150  
421 / 152  
447 / 153  
476 / 154  
232 / 125  
249 / 129  
268 / 133  
286 / 136  
312 / 140  
332 / 142  
357 / 144  
379 / 146  
406 / 149  
430 / 150  
460 / 152  
240 / 126  
260 / 129  
281 / 133  
301 / 135  
324 / 138  
346 / 140  
371 / 142  
395 / 144  
420 / 146  
447 / 148  
473 / 150  
244 / 125  
263 / 128  
281 / 131  
303 / 134  
324 / 136  
347 / 139  
370 / 141  
394 / 143  
418 / 145  
444 / 146  
471 / 147  
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.  
**Temperature of the air entering the outside coil.  
Page 27  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
temperature falls to 151−187°F (66°C−86°C), and the  
compressor is re−energized. This single−pole, single−throw  
(SPST) bi−metallic switch is wired in series with the 24V Y  
input signal to control compressor operation.  
System Operation  
UNIT COMPONENTS  
Crankcase Heater (HR1) and Thermostat Switch  
(S40) (−041 through −060 models only)  
IMPORTANT  
These models are equipped with either a 40 or 70 watt  
belly−band type crankcase heater. HR1 prevents liquid  
from accumulating in the compressor. HR1 is controlled by  
a single−pole, single−throw thermostat (SPST) switch  
Some scroll compressor have internal vacuum protector  
that will unload scrolls when suction pressure goes  
below 20 psig. A hissing sound will be heard when the  
compressor is running unloaded. Protector will reset  
when low pressure in system is raised above 40 psig. DO  
NOT REPLACE COMPRESSOR.  
When liquid line temperature drops below 50°F the  
thermostat closes energizing HR1. The thermostat will  
open, de−energizing HR1 once liquid line temperature  
reaches 70° F.  
High Pressure Switch (S4)  
14ACX units are equipped with a high-pressure switch that  
is located in the liquid line of the compressor as illustrated  
in figure on page 2 and figure 25 for the location of the  
manual reset button..  
Maintenance  
DEALER  
Maintenance and service must be performed by a qualified  
installer or service agency. At the beginning of each  
cooling season, the system should be checked as follows:  
Outdoor Unit  
1. Outdoor unit fan motor is pre−lubricated and sealed.  
No further lubrication is needed.  
MANUAL RESET  
BUTTON  
2. Visually inspect all connecting lines, joints and coils for  
evidence of oil leaks.  
3. Check all wiring for loose connections.  
4. Check for correct voltage at unit (unit operating).  
5. Check amp draw on outdoor fan motor.  
Motor Nameplate:_________ Actual:__________.  
6. Inspect drain holes in coil compartment base and  
clean if necessary.  
NOTE - If insufficient cooling occurs, the unit should be  
gauged and refrigerant charge should be checked.  
Figure 25. High Pressure Switch (S4) Manual Reset  
The switch is a Single Pole, Single Throw (SPST),  
manual−reset switch which is normally closed and  
removes power from the compressor when discharge  
pressure rises above factory setting at 590 + 10 psi. The  
manual−reset button can be identified by a red cap that is  
press to preform the reset function.  
Outdoor Coil  
Clean and inspect outdoor coil (may be flushed with a  
water hose). Ensure power is off before cleaning.  
NOTE ꢀ It may be necessary to flush the outdoor coil  
more frequently if it is exposed to substances which are  
corrosive or which block airflow across the coil (e.g., pet  
urine, cottonwood seeds, fertilizers, fluids that may contain  
high levels of corrosive chemicals such as salts)  
Thermal Protection Switch (S173) ꢀ Compressor  
Mounted  
Some units are equipped with a compressor mounted  
normally closed temperature switch that prevents  
compressor damage due to overheating caused by  
internal friction. The switch is located on top of the  
compressor casing (see figure 1). This switch senses the  
compressor casing temperature and opens at 239−257°F  
(115°C−125°C) to shut off compressor operation. The  
auto−reset switch closes when the compressor casing  
Sea Coast ꢀ Moist air in ocean locations can carry salt,  
which is corrosive to most metal. Units that are located  
near the ocean require frequent inspections and  
maintenance. These inspections will determine the  
necessary need to wash the unit including the outdoor coil.  
Consult your installing contractor for proper  
intervals/procedures for your geographic area or service  
contract.  
Page 28  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Indoor Unit  
1. Clean or change filters.  
S
Keep shrubbery trimmed away from the unit and  
periodically check for debris which collects around the  
unit.  
2. Lennox blower motors are prelubricated and  
permanently sealed. No more lubrication is needed.  
Routine Maintenance  
In order to ensure peak performance, your system must be  
properly maintained. Clogged filters and blocked airflow  
prevent your unit from operating at its most efficient level.  
3. Adjust blower speed for cooling. Measure the pressure  
drop over the coil to determine the correct blower CFM.  
Refer to the unit information service manual for pressure  
drop tables and procedure.  
1. Air Filter ꢀ Ask your Lennox dealer to show you  
where your indoor unit’s filter is located. It will be either  
at the indoor unit (installed internal or external to the  
cabinet) or behind a return air grille in the wall or  
ceiling. Check the filter monthly and clean or replace  
it as needed.  
4. Belt Drive Blowers − Check belt for wear and proper  
tension.  
5. Check all wiring for loose connections.  
6. Check for correct voltage at unit. (blower operating)  
7. Check amp draw on blower motor.  
2. Disposable Filter ꢀ Disposable filters should be  
replaced with a filter of the same type and size.  
Motor Nameplate:_________ Actual:__________.  
NOTE If you are unsure about the filter required for your  
system, call your Lennox dealer for assistance.  
Indoor Coil  
1. Clean coil if necessary.  
3. Reusable Filter ꢀ Many indoor units are equipped  
with reusable foam filters. Clean foam filters with a  
mild soap and water solution; rinse thoroughly; allow  
filter to dry completely before returning it to the unit or  
grille.  
2. Check connecting lines, joints and coil for evidence of  
oil leaks.  
3. Check condensate line and clean if necessary.  
NOTE The filter and all access panels must be in place  
any time the unit is in operation.  
HOMEOWNER  
Cleaning of the outdoor unit’s coil should be performed by  
a trained service technician. Contact your dealer and set  
up a schedule (preferably twice a year, but at least once a  
year) to inspect and service your outdoor unit. The  
following maintenance may be performed by the  
homeowner.  
4. Indoor Unit ꢀ The indoor unit’s evaporator coil is  
equipped with a drain pan to collect condensate  
formed as your system removes humidity from the  
inside air. Have your dealer show you the location of  
the drain line and how to check for obstructions. (This  
would also apply to an auxiliary drain, if installed.)  
Thermostat Operation  
See the thermostat homeowner manual for instructions on  
how to operate your thermostat.  
IMPORTANT  
Sprinklers and soaker hoses should not be installed  
where they could cause prolonged exposure to the  
outdoor unit by treated water. Prolonged exposure of the  
unit to treated water (i.e., sprinkler systems, soakers,  
waste water, etc.) will corrode the surface of steel and  
aluminum parts and diminish performance and longevity  
of the unit.  
Preservice Check  
If your system fails to operate, check the following before  
calling for service:  
S
S
S
S
S
S
Verify room thermostat settings are correct.  
Verify that all electrical disconnect switches are ON.  
Check for any blown fuses or tripped circuit breakers.  
Verify unit access panels are in place.  
Outdoor Coil  
Verify air filter is clean.  
The outdoor unit must be properly maintained to ensure its  
proper operation.  
If service is needed, locate and write down the unit  
model number and have it handy before calling.  
S
S
S
Please contact your dealer to schedule proper  
inspection and maintenance for your equipment.  
Accessories  
For update−to−date information, see any of the following  
publications:  
Make sure no obstructions restrict airflow to the  
outdoor unit.  
S
S
S
Lennox 14ACX Engineering Handbook  
Lennox Product Catalog  
Grass clippings, leaves, or shrubs crowding the unit  
can cause the unit to work harder and use more  
energy.  
Lennox Price Book  
Page 29  
14ACX SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start−Up and Performance Checklist  
Job Name  
Job Location  
Installer  
Job no.  
City  
Date  
State  
City  
State  
Unit Model No.  
Serial No.  
Service Technician  
Nameplate Voltage  
Rated Load Ampacity  
Compressor  
Outdoor Fan  
Maximum Fuse or Circuit Breaker  
Electrical Connections Tight?  
Indoor Blower RPM  
-
Indoor Filter clean?  
-
Supply Voltage (Unit Off)  
S.P. Drop Over Indoor (Dry)  
Suction Pressure  
Outdoor Coil Entering Air Temp.  
Refrigerant Charge Checked?  
Discharge Pressure  
-
-
Refrigerant Lines: Leak Checked? - Properly Insulated?  
Service Valves: Fully Opened? - Caps Tight?  
-
-
Outdoor Fan Checked?  
Thermostat  
Voltage With Compressor Operating  
Calibrated? - Properly Set? - Level?  
-
Page 30  
506645−01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

Krell Industries Stereo Amplifier MDA 300 500 User Manual
KTM Motorcycle 85 SX User Manual
LG Electronics Printer Accessories LG D686 User Manual
LG Electronics Range LRG3093SB User Manual
Linear Pressure Washer XR 16 User Manual
Logitech Radio 930 000101 User Manual
Lucent Technologies Telephone 108522426 User Manual
Makita Trimmer UH5530 User Manual
Marantz DVD Player DV4400 User Manual
Memorex Cordless Telephone MPH6925 User Manual