LST Smoke Alarm LC216 Series User Manual

Extinguishing Control Panel  
Series LC216  
• Actuation and monitoring of up to  
127 extinguishing systems or 127  
flooding zones  
• Fully integrated into Fire Detection  
Control Panel Series BC216  
• Individual control panel or flexibly  
expandable control panel network  
• Suitable for all system sizes  
• Optional hardware redundancy  
• EN 54, EN 12094-1, VdS certified  
Fire is a permanent threat to life and property. There- ted within LST premises, thus guaranteeing flexible and  
fore, immediate response to a fire is imperative. The reliable individual solutions.  
main objective of the Extinguishing Control Panels Se-  
ries LC216 is to alarm and to react in time and, conse- Using a 32-bit multiprocessor system, the Extinguishing  
quently, save lives and protect property. For decades Control Panels Series LC216 ensure topmost efficiency  
LST have focused their aims to undertaking unrivaled and speed – prerequisites for saving lives and minimi-  
efforts in order to realize new innovations in the security zing damage to property.  
area. Research, development and production are loca-  
Description  
The Extinguishing Control Panel Series LC216 is an  
extended Fire Detection Control Panel Series BC216  
with additional functions for the control of extinguishing  
systems. Nevertheless, all functions of the fire detec-  
tion control panel remain intact. Therefore, a combined  
use as fire detection and extinguishing control panel is  
provided as standard.  
are interconnected via the Global Security System  
Network GSSnet and thereby form a decentralised  
extinguishing control system. Each extinguishing sys-  
tem can control up to 32 flooding zones, and each  
LCnet sectional control panel can administrate up to  
8 flooding zones. A maximum of 127 flooding zones  
can be controlled by an Extinguishing Control Panel  
LCnet216.  
The Extinguishing Control Panels Series LC216 compri-  
se the following types of control panels:  
The Extinguishing Control Panel Series LC216 fulfils  
• The Extinguishing Control Panel LC216-1 for an extin- all compulsory requirements as well as the options of  
guishing system with one flooding zone according to EN 12094-1, EN 54-2 and EN 54-4 and is VdS certi-  
EN 12094-1 or with up to 8 flooding zones without fied.  
compliance to EN 12094-1.  
• The networked Extinguishing Control Panel LCnet216 The networked Extinguishing Control Panel LCnet216  
for up to 127 extinguishing systems. The LCnet216 can be easily implemented with a redundant design of  
consists of several sectional control panels, which the extinguishing control.  
0786–CPD–20267  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
LC216_DBL_LST_EN_0806.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features  
The extinguishing control function is fully integrated into  
the Fire Detection Control Panel Series BC216. The Ex-  
cific functions for the actuation of the extinguishing  
system.  
tinguishing Control Panel Series LC216 comprises the • For the actuation of valves or signalling equipment,  
following additional features:  
various types of actuation are available, which can  
be assigned to any outputs of the control panel or  
to an ADM control module. The activation of these  
actuations is timed according to EN 12094-1.  
• The Extinguishing Control Panel LC216-1 serves for  
the actuation of an extinguishing system with up to  
8 flooding zones. By means of the networked Extin-  
guishing Control Panel LCnet216, up to 127 extingu- • The condition of flooding zones or extinguishing sys-  
ishing systems can be actuated. Each extinguishing  
system can control up to 32 flooding zones, each  
LCnet sectional control panel can administrate up to  
8 flooding zones. A maximum of 127 flooding zones  
tems can be output by the status outputs of the con-  
trol panel or via ADM modules. Furthermore, status  
LEDs can be freely parameterised as optical conditi-  
on display.  
can be controlled by an Extinguishing Control Panel • Depending on the size of the flooding zone and the  
LCnet216.  
capacity of the extinguishing agent cylinders, for  
each flooding zone the actuation of further flooding  
zones can be unblocked or blocked.  
• All zones with automatic fire detectors or manual call  
points can be used for the actuation of the extinguis-  
hing system. The respective detectors and detector • In the appropriate authorisation level, a flooding zone  
zones are assigned to the individual flooding zones  
by defining combinations and dependencies.  
• Input signals for the actuation of the extinguishing  
system can be received through zone inputs in con-  
ventional or ADM technology, as well as via fire briga-  
de interface inputs.  
can be operated at the display and operating unit of  
the fire detection control panel. In addition to disab-  
lements, enablements and toggling between manual  
and automatic mode, it is also possible to test the  
signalling equipment for pre-alarm and evacuation  
alarm.  
The ADM technology allows to connect detectors, • The Extinguishing Control Panel Series LC216 can  
signalling devices as well as monitor and control mo-  
dules in intelligent analogue ring bus technology. A  
safe supply of the loop elements is achieved through  
the redundant cable path. Therefore, standard fire  
detection cable can be used for wiring.  
• Various zone and input types, such as „Emergency  
hold device“, „Manual mode“, „Extinguishing medium  
active“ or „Reset extinguishing system“ provide spe-  
be comfortably parameterised via PC by using the  
Windows Parameter Setup Software PARSOFT. The  
clear user interface allows an almost self-explanato-  
ry definition of the system configuration and thereby  
minimizes the requirement for training. The entered  
parameters can be loaded into the control panel after  
an automatic verification for technical correctness.  
Advanced features  
In addition to all compulsory functions of EN 12094-1, • Manual only mode  
the extinguishing control panel fulfils the following opti- • Triggering signals to equipment within the system  
ons of this standard:  
• Extinguishing signals to spare cylinders  
• Triggering of equipment outside the system  
• Emergency abort device  
• Control of extended discharge  
• Release of the extinguishing media for selected floo-  
ding zones  
• Delay of extinguishing signal  
• Signal representing the flow of extinguishing agent  
• Monitoring of the status of components  
• Emergency hold device  
• Control of flooding time  
• Initiation of secondary flooding  
Redundant design  
The Extinguishing Control Panel Series LC216 can be A redundant design of the extinguishing control panel  
optionally implemented with a hardware-redundant de- can be implemented by means of the fire detection  
sign. A redundant design is required according to the control panel modules in 19“ slide-in technology. The  
standard EN 12094-1 for fixed gas extinguishing sys- parameterisation of the redundant extinguishing control  
tems, if one sectional control panel actuates more than panel is fully supported by the Parameter Setup Softwa-  
one extinguishing area.  
re PARSOFT.  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
LC216_DBL_LST_EN_0806.PDF • PAGE 3  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Extinguishing control licence  
The extinguishing control function is enabled in the or LCnet sectional control panel can be used for the  
Extinguishing Control Panel LC216-1 and in any LCnet actuation of up to 8 flooding zones.  
sectional control panel by installing an appropriately pa- The options circuit is part of the Extinguishing Cont-  
rameterised options circuit. This control panel LC216-1 rol/8-Area Licence LC216-8LB.  
Specifications  
Extinguishing Control Panel LC216-1  
Number of extinguishing systems  
Number of flooding zones  
1
max. 8  
Extinguishing Control Panel LCnet216  
Number of extinguishing systems per sectional control panel  
Total number of extinguishing systems  
1
max. 127  
max. 8  
max. 32  
max. 127  
Number of flooding zones per sectional control panel  
Number of flooding zones per extinguishing system  
Total number of flooding zones  
Extinguishing control licence for 8 flooding zones  
Approvals  
CE marking  
0786–CPD–20267  
VdS G206046  
VdS G206089  
as pure extinguishing control panel  
as combined fire detection and extinguishing control panel  
FT 14/423/06 (Austria)  
Order number  
Order name  
218024  
Extinguishing Control/8-Area Licence LC216-8LB  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
LC216_DBL_LST_EN_0806.PDF • PAGE 4  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LG Electronics Doll AN WF500 User Manual
LG Electronics Home Theater System AR805TS User Manual
Life Fitness Elliptical Trainer CT9500 User Manual
Magic Chef Microwave Oven MCP13E1ST User Manual
Makita Drill 6227D User Manual
Marantz Computer Monitor PD4240D User Manual
Marshall Amplification Musical Instrument Amplifier MF350 User Manual
M Audio Musical Instrument eKeys49 User Manual
Maytag Cooktop MGC4430BD User Manual
Melissa Trimmer 638 136 142 User Manual