• ADM loop technology with
System Sensor/200 protocol
• 10 independent inputs with
monitoring for wire breakage and
short circuit
• Status LED for each input
• Setting of module address via
decadic rotary switches
• Mounting in surface mounting box
Description
The addressable Monitor Module IM-10 provides 10 addresses on the ADM loop. During commissioning, the
independent inputs and serves for the line-monitored base address, i.e., the lowest one of the 10 addresses,
integration of contact detectors, such as manual call is set by means of decadic rotary switches.
points, sprinkler system contacts or supervising con-
tacts, into the bidirectional communication on the ADM The optional steel sheet Surface Mounting Box
loop with System Sensor/200 protocol.
M200SMB-MM accommodates one Monitor Module
The Monitor Module IM-10 occupies 10 consecutive IM-10 or Control Module CR-6.
Specifications
Operating voltage
Current consumption
Ambient temperature
Dimensions L × W × H
Weight
Supply through loop voltage
approx. 3.5mA (quiescent)
0°C to +50°C
172 × 147 × 25 (mm)
500g
Order number
249115
Order name
Monitor Module 10xSurv.In/Anal./200/SS IM-10
Surface Mounting Box
Ambient temperature
Dimensions L × W × H
Colour
0°C to +50°C
285 × 225 × 62 (mm)
cream
Weight
2kg
Order number
249117
Order name
Surface Mounting Box for Multimodule/SS M200SMB-MM
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
IM-10_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED