• Addressable conventional technology
• Alarm temperature 75°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Extremely flat design
• Sealed electronics
Description
The Thermal Max Detector HT-11004 recognises a ma- detector can be addressed individually, thus allowing to
ximum temperature of 75°C as sign of fire. It complies display the detector address, as well as an assigned
with Class BS and can be used up to a room height of element text, on a suitable fire detection control panel.
6m.
A detector fault is indicated by a yellow flashing of the
Addressable conventional technology is used for alarm multicoloured status LED.
transmission to the fire detection control panel. By The detector can be attached to various bases and it
means of the optional Address Module NG60-1, each can be protected against theft.
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 65µA (quiescent)
typ. 75°C
max. +65°C (continuous operation)
-40°C to +80°C (no condensation or icing)
0 – 98% (no condensation)
100 × 36 (mm)
white
Weight
70g
Approval
VdS G204036
Order number
Order name
242033
Thermal Max Detector/Conv./ORBIS/Apo HT-11004
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
HT-11004_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED