• Addressable conventional technology
• Alarm temperature 78°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Thermal Max Detector ECO1004T recognises a
maximum temperature of 78°C as sign of fire. It com-
plies with Class BS and can be used up to a room
height of 6m.
means of the Address Module NG58-1, each detector
can be addressed individually.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it
can be protected against theft.
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. By
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 75µA (quiescent)
typ. 78°C
max. +60°C
-30°C to +70°C (continuous operation)
5 – 95% (no condensation)
102 × 40.5 (mm)
white
Weight
70g
Approval
VdS G202042
Order number
Order name
242047
Thermal Max Detector/Conv./1000/SS ECO1004T
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
ECO1004T_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|