• Suitable for automatic detectors
in ADM loop technology with
System Sensor/200 protocol
• Dual-isolator unit
• Screw terminals for secure
connection of multiple wires
• Terminals for connection of remote
indicator
• Mechanical theft protection can be
activated
Description
The Isolator Detector Base B524IEFT-1 is designed to
accommodate intelligent fire detectors Series 200 and
500 for use in ADM loops with System Sensor/200
protocol.
Due to its robust multi-wire screw terminals, the detec-
tors can be wired with ease, thus achieving a secure
and durable connection. The base also provides a pos-
sibility for the easy connection of remote indicators.
A dual-isolator unit is integrated into the detector base,
which reliably disconnects the loop in case of a short
circuit. With the dual design, the input side or the out-
put side isolator – depending on the location of the
short circuit – interrupts the connection to the faulty
loop segment. Therefore the detector remains in ope-
ration.
The base is designed for surface mounting in dry
rooms. For special applications a range of accesso-
ries (for moist room, false ceiling or flush installation)
is available.
A mechanical theft protection of the detector can
optionally be activated at the detector base.
Specifications
Current consumption
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
max. 100µA (quiescent)
-30°C to +70°C
0 – 93% (no condensation)
102 × 26 (mm)
cream
Weight
70g
Approval
VdS G200100
Order number
Order name
246013
Isolator Detector Base/Anal./500/200/SS B524IEFT-1
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
B524IEFT-1_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|