DetectorRelayBase
• Suitable for automatic detectors in
conventional technology
• Relay output with dry change-over
contact
• Screw terminals for secure
connection of multiple wires
• Test contact for examining the
detector line without detectors
• Mechanical theft protection can be
activated
Description
The Detector Relay Base ECO1000BREL24L with inte-
grated relay output is designed for the easy connection
of automatic detectors Series ECO1000. Due to its ro-
bust multi-wire screw terminals, the detectors can be
wired with ease, thus achieving a secure and durable
connection.
During construction work (or when the detector has
been removed) the detector line can be connected
through via an auxiliary contact, which is integrated
into the base. With that, the whole wiring of the detec-
tor line can be examined without risking contamination
of the detectors. The contact is automatically opened
by installing the detector.
The relay output is activated through the alarm activati-
on of the inserted detector and remains active until the
alarm is reset on the fire detection control panel. The
application has to comply with the guidelines in the LST
Connection of Detectors.
The base is designed for surface mounting in dry
rooms. A mechanical theft protection of the detector
can optionally be activated at the detector base.
Specifications
Operating voltage
Current consumption
Contact rating
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
1µA (quiescent), 30mA (active)
1A at 30VDC
-30°C to +70°C
5 – 93% (no condensation)
102.5 × 33 (mm)
white
Weight
70g
Order number
Order name
246141
Detector Relay Base/Conv./1000/SS ECO1000BREL24L
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
ECO1000BREL24L_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED