| 	
		 INSTALLATION   
					INSTRUCTIONS   
					DIRECT VENT   
					MERIT™ PLUS SERIES   
					VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS   
					P/N 850,043M REV. E 06/2008   
					This appliance may be installed in an aftermarket perma-   
					nently located, manufactured home (USA only) or mobile   
					home, where not prohibited by local codes. This appliance   
					is only for use with the type of gas indicated on the rating   
					plate. This appliance is not convertible for use with other   
					gases, unless a certified kit is used.   
					MODELS   
					Millivolt Models   
					Electronic Models   
					MPLDV-30NM   
					MPLDV-30PM   
					MPLDV-35NM-2   
					MPLDV-35PM-2   
					MPLDV-40NM   
					MPLDV-40PM   
					MPLDV-45NM   
					MPLDV-45PM   
					MPLDV-30NE   
					MPLDV-35NE-2   
					MPLDV-40NE   
					MPLDV-45NE   
					In the Commonwealth of Massachusetts:   
					• Installation must be performed by a licensed plumber or   
					gas fitter.   
					See Table of Contents for location of additional   
					Commonwealth of Massachusetts requirements.   
					WARNING: IF THE INFORMATION IN THIS MANUAL   
					ISNOTFOLLOWEDEXACTLY,AFIREOREXPLOSION   
					MAY RESULT CAUSING PROPERTY DAMAGE, PER-   
					SONAL INJURY OR LOSS OF LIFE.   
					INSTALLER: Leave this manual with the appliance.   
					CONSUMER: Retain this manual for future reference.   
					AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE   
					LESINSTRUCTIONSDONNÉDANSCETTENOTICEPOUR   
					RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU   
					POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE   
					BLESSURE OU LA MORT.   
					FOR YOUR SAFETY: Do not store or use gasoline   
					or other flammable vapors or liquids in the vicin-   
					ity of this or any other appliance.   
					FOR YOUR SAFETY: What to do if you smell gas:   
					POURVOTRESÉCURITÉ: Nepasentreposerni utiliser   
					d'essenceni d'autrevapeursouliquidesinflammables   
					dans le voisinage de cet appareil ou de tout autre   
					appareil.   
					• DO NOT light any appliance.   
					• DO NOT touch any electrical switches.   
					• DO NOT use any phone in your building.   
					• Immediately call your gas supplier from a   
					neighbor’s phone. Follow your gas suppliers   
					instructions.   
					POURVOTRESÉCURITÉ: Quefairesi voussentezune   
					odeur de gaz:   
					• Ifyourgassuppliercannotbereached, call the   
					fire department.   
					• Ne pas tenter d'allumer d'appareil.   
					• Netouchezàaucuninterrupteur. Nepasvousservir   
					des téléphones se trouvant dans le batiment où   
					vous vous trouvez.   
					• Evacuez la piéce, le bâtiment ou la zone.   
					• Appelez immédiatement votre fournisseur de gaz   
					depuis un voisin. Suivez les instructions du   
					fournisseur.   
					Installation and service must be performed by a   
					qualified installer, service agency or the gas   
					supplier.   
					OTL Report No. 116-F-47-5   
					US   
					• Si vous ne pouvez rejoindre le fournisseur de gaz,   
					appelez le service dos incendies.   
					A French manual is available upon request. Order Form Number   
					850,043CF.   
					L'installationetservicedoitêtreexécutéparunqualifié   
					installeur, agencedeserviceoulefournisseurdegaz.   
					Ce manuel d’installation est disponible en francais, simplement   
					en faire la demande. Numéro de la pièce 850,043CF.  
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Provide adequate clearances around air open-   
					ings and adequate accessibility clearance for   
					service and proper operation. Never obstruct   
					the front openings of the appliance.   
					Cet appareil peut être installé dans un   
					maison préfabriquée (É.-U. seulement)   
					ou mobile déjà installée à demeure si   
					les réglements locaux le permettent.   
					Cet appareil doit être utilisé uniquement   
					avec les types de gaz indiqués sur la   
					plaque signalétique. Ne pas l'utiliser   
					avec d'autres gaz sauf si un kit de con-   
					version certifié est installé.   
					Installations at Altitudes of 0 to 4500 ft.-   
					Unitsaretestedandapprovedforelevations   
					of 0 to 4500 feet (0 to 1372 meters).   
					Installations at Altitudes above 4500 ft.-   
					For elevations above 4500 feet (1372   
					meters), install the unit according to the   
					regulations of the local authorities having   
					jurisdictionand, intheUSA, thelatestedition   
					oftheNational Fuel GasCode(ANSIZ223.1)   
					or, in Canada, the latest edition of the   
					CAN1-B149.1 and .2 codes.   
					Theseappliancesaredesignedtooperateon   
					natural or propane gas only.   
					Millivolt And Electronic Models -   
					Millivolt and Electronic models come standard   
					with the manually-modulated gas valve; flame   
					appearanceandheatoutputcanbecontrolledat   
					the gas valve.   
					Test gage connections are provided on the   
					front of the millivolt and electronic gas control   
					valve (identified IN for the inlet and OUT for the   
					manifold side). A 1/8" NPT test gage connec-   
					tion is provided at the inlet and outlet side of   
					the electronic gas control valve.   
					Table1 showstheunits' gasorificesizefor   
					the elevations indicated.   
					Input of millivolt and electronic models is   
					shown in the following table:   
					The millivolt appliances are manually controlled   
					andfeatureasparkignitor(piezo)thatallowsthe   
					appliance's pilot gas to be lit without the use of   
					matches or batteries. This system provides   
					continuedserviceintheeventofapoweroutage.   
					Minimum inlet gas pressure to these appli-   
					ances is 5.0 inches water column (1.24 kPa)   
					for natural gas and 11 inches water column   
					(2.74kPa)forpropaneforthepurposeofinput   
					adjustment.   
					Millivolt And Electronic Models with   
					Manually-Modulated Gas Valve   
					Natural Gas   
					Propane Gas   
					Input   
					Input   
					Model No.   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					rate   
					(BTU/H)   
					Model No.   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					rate   
					(BTU/H)   
					Elevation   
					Feet   
					(meters)   
					Maximum inlet gas supply pressure to these   
					appliances is 10.5 inches water column (2.61   
					kPa) for natural gas and 13.0 inches water   
					column (3.23 kPa) for propane.   
					13,000   
					to   
					10,000   
					11,500   
					to   
					9,000   
					Orifice size   
					Nat. Prop.   
					Model   
					No.   
					#61   
					(0.039")   
					19,000   
					to   
					15,000   
					18,000   
					to   
					14,000   
					MPLDV30 0.070"   
					#45   
					MPLDV35   
					These appliances must be isolated from the   
					gas supply piping system (by closing their   
					individual manual shut-off valve) during any   
					pressure testing of the gas supply piping sys-   
					tem at test pressures equal to or less than 1/2   
					psig (3.5 kPa).   
					0.048"   
					#54   
					(0.082")   
					0-4500   
					(0-1372)   
					25,000   
					to   
					18,500   
					21,500   
					to   
					16,500   
					#41   
					MPLDV40   
					(0.096") (0.055")   
					#40 #53   
					(0.098") (0.0595")   
					26,000   
					to   
					25,000   
					to   
					MPLDV45   
					20,000   
					19,000   
					Table 1   
					These appliances and their individual shut-off   
					valves must be disconnected from the gas   
					supply piping system during any pressure   
					testingofthatsystematpressuresinexcessof   
					1/2 psig (3.5 kPa).   
					All Models -   
					Donotusetheseappliancesifanyparthasbeen   
					under water. Immediately call a qualified, pro-   
					fessional service technician to inspect the ap-   
					pliance and to replace any parts of the control   
					system and any gas control which have been   
					under water.   
					Maximum manifold pressure is 3.5 in. w.c.   
					(0.87 kPa) for natural gas and 10 in. w.c.   
					(2.49 kPa) for LP/Propane gas.   
					Theseappliancesmustnotbeconnectedtoa   
					chimney or flue serving a separate solid fuel   
					burning appliance.   
					Efficiencies%   
					Natural Gas   
					Steady   
					Propane   
					Ne pas se servir de cet appareil s'il a été plongé   
					dans l'eau, complètement ou en partie. Appeler   
					untechnicienqualifiépourinspecterl'appareilet   
					remplacertoutepartiedusystèmedecontrôleet   
					toute commande qui ont étéplongés dans l'eau.   
					Models   
					Steady   
					State   
					P4   
					AFUE P4   
					AFUE   
					State   
					These heater rated appliances are intended   
					for use as supplemental heaters only. Using   
					these appliances as a primary heat source   
					may void the manufacturers warranty.   
					MPLDV30 58   
					MPLDV35 60   
					MPLDV40 58   
					MPLDV45 58   
					65   
					63   
					63   
					64   
					65   
					58   
					62   
					57   
					60   
					66   
					65   
					67   
					66   
					64   
					63   
					65   
					64   
					65   
					67   
					67   
					This appliance may be installed in an af-   
					termarket permanently located, manufac-   
					tured home (USA only) or mobile home,   
					where not prohibited by local codes. This   
					appliance is only for use with the type of   
					gas indicated on the rating plate. This ap-   
					pliance is not convertible for use with other   
					gases, unless a certified kit is used.   
					Carbon Monoxide Poisoning: Early signs of   
					carbon monoxide poisoning are similar to   
					the flu with headaches, dizziness and/or   
					nausea. If you have these signs, obtain fresh   
					air immediately. Turn off the gas supply to   
					the appliance and have it serviced by a   
					qualified professional, as it may not be op-   
					erating correctly.   
					Note: Powerventingofdirect ventfireplaces   
					may result in the reduction of efficiencies by   
					as much as ten percent. Consider this in   
					making any venting and heating decisions in   
					any installation application.   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				WARNING: FAILURE TO COMPLY WITH   
					THE INSTALLATION AND OPERATING   
					INSTRUCTIONS PROVIDED IN THIS   
					DOCUMENTWILLRESULTINANIMPROP-   
					ERLY INSTALLED AND OPERATING   
					APPLIANCE, VOIDING ITS WARRANTY.   
					ANY CHANGE TO THIS APPLIANCE AND/   
					OR ITS OPERATING CONTROLS IS DAN-   
					GEROUS. IMPROPERINSTALLATIONOR   
					USE OF THIS APPLIANCE CAN CAUSE   
					SERIOUSINJURYORDEATHFROMFIRE,   
					BURNS, EXPLOSION OR CARBON MON-   
					OXIDE POISONING.   
					AL VENT   
					TION   
					HORIZONT   
					APPLICA   
					APPLICATION   
					HORIZONTAL VENT   
					VERTICAL VENT   
					(Top Vent   
					Application)   
					HORIZONTAL VENT   
					(Top Vent   
					Application)   
					RECESSED   
					INSTALLATION   
					HORIZONTAL VENT   
					APPLICATION   
					Typical Locations   
					Figure 2   
					WARNING: CHILDREN AND ADULTS   
					SHOULD BE ALERTED TO THE HAZARDS   
					OFHIGHSURFACETEMPERATURES.USE   
					CAUTION AROUND THE APPLIANCE TO   
					AVOID BURNS OR CLOTHING IGNITION.   
					YOUNG CHILDREN SHOULD BE CARE-   
					FULLYSUPERVISEDWHENTHEYAREIN   
					THE SAME ROOM AS THE APPLIANCE.   
					Shelf Height inches (mm)   
					Top Vent   
					Model No.   
					Secure Vent   
					44 3/4 (1132)   
					46 3/4 (1188)   
					51 3/4 (1314)   
					Secure Flex   
					44 3/4 (1132)   
					46 3/4 (1188)   
					51 3/4 (1314)   
					MPLDV30   
					MPLDV35   
					MPLDV40/MPLDV45   
					WARNING: DO NOT PLACE CLOTHING   
					OR OTHER FLAMMABLE MATERIALS   
					ON OR NEAR THIS APPLIANCE.   
					Do not insulate the   
					space between the   
					appliance and the   
					area above it.   
					AVERTISSEMENT: SURVEILLER LES   
					ENFANTS. GARDER LES VÊTEMENTS,   
					LES MEUBLES, L'ESSENCE OU AUTRES   
					LIQUIDES À VAPEUR INFLAMMABLES À   
					COTE DE L'APPAREIL.   
					Shelf Height   
					(see table)   
					LOCATION   
					Shelf Above Fireplace With Top Venting   
					Figure 3   
					In selecting the location, the aesthetic and   
					functional use of the appliance are primary   
					concerns. However, vent system routing to the   
					exterior and access to the fuel supply are also   
					important. Consideration should be given to   
					traffic ways, furniture, draperies, etc., due to   
					elevated surface temperatures (Figure 2 ).   
					*Note: 3 in. (76mm) above any horizontal/   
					inclined vent component for the MPLDV30   
					inallcases,andfortheMPLDV35,MPLDV40   
					& MPLDV45, when the vent center line is   
					greater than 48" (1219 mm) above the fire-   
					place top wrapper surface. Increase this   
					clearance to 5" (127 mm) for the MPLDV35,   
					MPLDV40 & MPLDV45, when the vent cen-   
					terlineislessthan48"(1219mm)abovethe   
					fireplace top wrapper surface.   
					1 in. (25.4 mm)   
					0 in. (0 mm) spacers   
					BACK   
					1 in. (25.4 mm)**   
					0 in. (0 mm) spacers   
					SIDES   
					The location should also be free of electrical,   
					plumbingorotherheating/airconditioningduct-   
					ing. These direct vent appliances are uniquely   
					suited for installations requiring a utility shelf   
					positioned directly above the fireplace. Utility   
					shelveslikethesearecommonlyusedforlocat-   
					ing television sets and decorative plants.   
					TOP SPACERS   
					FLOOR   
					0 in. (0 mm)   
					0 in. (0 mm)   
					From Bottom of   
					Unit to Ceiling   
					64 in. (1626 mm)   
					1 in. (25.4 mm)*   
					**Note: See page 6, step 1 for clearance   
					requirements to the nailing flange located at   
					each side of the unit and any screw heads   
					adjacent to it.   
					VENT   
					SERVICE CLEARANCES   
					FRONT   
					3 Feet. (0.9 meters)   
					Table 2   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Toprovideforthelowestpossibleshelfsurface   
					the venting attached to the top vent should be   
					routed in a way to minimize obstructions to the   
					use of the space above the appliance. Do not   
					insulatethespacebetweentheapplianceand   
					the area above it. Refer to Figure 3. The   
					minimumheightfromthebaseoftheappliance   
					totheundersideofcombustiblematerialsused   
					to construct a utility shelf in this fashion is   
					shown in the table in Figure 3.   
					Massachusetts And New York City, NY   
					Requirements   
					Vertical Vent Termination Clearances   
					Terminatesingle ventcapsrelativetobuilding   
					components according to Figure 4.   
					These appliances are approved for installation   
					in the following USA locations listed in the   
					following:   
					Terminate multiple vent terminations accord-   
					ing to the installation codes listed at the top of   
					this page.   
					Massachusetts:   
					These fireplaces are approved for installation   
					in the US state of Massachusetts if the follow-   
					ing additional requirements are met-   
					TERMINATION HEIGHTS FOR VENTS ABOVE   
					FLAT OR SLOPED ROOFS   
					Horizontal Overhang   
					The appliance should be mounted on a fully   
					supported base extending the full width and   
					depth of the unit. The appliance may be located   
					on or near conventional construction materi-   
					als. However, if installed on combustible mate-   
					rials, such as carpeting, vinyl tile, etc., a metal   
					or wood barrier covering the entire bottom   
					surface must be used.   
					2 FT   
					• Installation and repair must be done by a   
					plumber or gas fitter licensed in the Common-   
					wealth of Massachusetts.   
					• The flexible gas line connector used shall not   
					exceed 36 inches (92 centimeters) in length.   
					• The individual manual shut-off must be a T-   
					handle type valve.   
					Vertical   
					Wall   
					MIN.   
					2 FT MIN.   
					Lowest   
					Discharge   
					Opening   
					Vent   
					Termination   
					H*   
					Storm Collar   
					Flashing   
					X 
					12   
					Roof Pitch is X/12   
					MassachusettsHorizontal VentRequirements   
					1 inch (25.4 mm) Minimum   
					Clearance to Combustibles   
					APPLIANCE AND VENT CLEARANCES   
					Concentric   
					Vent Pipe   
					*H = MINIMUM HEIGHT FROM ROOF TO   
					LOWEST DISCHARGE OPENING OF VENT   
					In the Commonwealth of Massachusetts, hori-   
					zontal terminations installed less than seven   
					(7) feet above the finished grade must comply   
					with the following additional requirements:   
					Refer To Table 2 for approved clearances to   
					combustibles for the models covered in this   
					manual,withthefollowingexception:Whenthe   
					unit is installed with one side flush with a wall,   
					the wall on the other side of the unit must not   
					extend beyond the front edge of the unit. In   
					addition, when the unit is recessed, the side   
					walls surrounding the unit must not extend   
					beyond the front edge of the unit. See Figure 2.   
					H 
					Roof Pitch   
					(feet)   
					Flat to 6/12   
					1.0   
					1.25   
					1.5   
					• A hard wired carbon monoxide detector with   
					analarmandbatteryback-upmustbeinstalled   
					on the floor level where the gas fireplace is   
					installed. Thecarbonmonoxidedetectormust   
					comply with NFPA 720, be ANSI/UL 2034   
					listed and be ISA certified.   
					Over 6/12 to 7/12   
					Over 7/12 to 8/12   
					Over 8/12 to 9/12   
					Over 9/12 to 10/12   
					Over10/12 to 11/12   
					Over 11/12 to 12/12   
					2.0   
					2.5   
					3.25   
					4.0   
					Maintain a minimum 1" (25 mm) clearance   
					to combustible materials for all vertical   
					vent elements.   
					• Ametal or plasticidentificationplatemust be   
					permanently mounted to the exterior of the   
					building at a minimum height of eight (8) feet   
					above grade and be directly in line with the   
					horizontal termination. The sign must read, in   
					print size no less than one-half (1/2) inch in   
					size, GAS VENT DIRECTLY BELOW. KEEP   
					CLEAR OF ALL OBSTRUCTIONS.   
					Figure 4   
					Clearancesfor horizontal vent elementsare   
					1" (25 mm) at the sides and 1" (25 mm) on   
					the bottom. Clearances above horizontal   
					vent elementsare3"(76mm) for all models   
					and all applications. Exception: Clearance   
					is 5" (127 mm) for MPLDV35, MPLDV40 &   
					MPLDV45, when the center line of the hori-   
					zontal run is less than 48" (1219 mm) above   
					the fireplace top wrapper surface.   
					Horizontal Vent Termination Clearances   
					The horizontal vent termination must have a   
					minimum of 3" (76 mm) clearance to any over-   
					headcombustibleprojectionof2-1/2"(64mm)   
					or less. See Figure 5. For projections exceed-   
					ing2-1/2" (64mm),seeFigure5. Allhorizontal   
					terminations may be located as close as 6"   
					(152mm) to any (non-combustible and com-   
					bustible) exterior sidewall. This distance may   
					be decreased to 2" (51mm) for non-combus-   
					tible exterior sidewalls only, if the SV4.5HT-2   
					termination is used. For additional vent loca-   
					tion restrictions, refer to Figure 8 on page 7.   
					New York City, NY:   
					These fireplaces are approved for installation   
					in New York City in the US state of New York.   
					VENT TERMINATION CLEARANCES   
					Theseinstructionsshouldbeusedasaguide-   
					line and do not supersede local codes in any   
					way. Install vent according to local codes,   
					these instructions, the current National Fuel   
					Gas Code (ANSI-Z223.1) in the USA or the   
					current standards of CAN/CGA-B149.1 and -   
					B149.2 in Canada.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TYPICAL INSTALLATION SEQUENCE   
					Horizontal Vent Termination Clearances   
					The typical sequence of installation follows,   
					however,eachinstallationisuniqueresultingin   
					variations to those described.   
					Combustible Projection   
					2-1/2 inches or less in length   
					All horizontal terminations   
					Combustible Projection greater   
					than 2-1/2 inches in length   
					may be located as close as   
					6” (152mm) to any   
					(non-combustible and   
					combustible) exterior   
					sidewall. This distance   
					may be decreased to 2”   
					(51mm) for non-n-   
					combustible exterior   
					sidewalls only, if the   
					SV4.5HT-2 termination   
					is used.   
					Seethepagenumbersreferencesinthefollow-   
					ing steps for detailed procedures.   
					Ventilated   
					Soffit   
					Unventilated   
					Soffit   
					Step1. (page 6) Construct the appliance fram-   
					ing. Position the appliance within the framing   
					and secure with nailing brackets.   
					3"   
					(76 mm)   
					18"   
					(457 mm)   
					12"   
					(305 mm)   
					Step 2. (page 6) Route gas supply line to   
					Termination Kit   
					appliance location.   
					Step 3. (page 10) Install the vent system   
					and exterior termination. Install additional   
					restrictor, if needed.   
					Termination Kit   
					Figure 5 - Side Elevation View   
					Step 1. FRAMING   
					Step 4. (page 21) Field Wiring   
					a. Millivolt Appliances – The operating control   
					switch is factory installed.   
					Unit   
					Nailing Flange   
					b. Electronic Appliances – Connect 120 Vac   
					electrical power to the appliance receptacle.   
					FrametheseappliancesasillustratedinFigure9   
					onpage8, unlesstheapplianceistobeinstalled   
					in a corner.   
					Step 5. (page 22) Make connection to gas   
					supply.   
					Side   
					Framing   
					See Figure 10 on page 8 for corner framing   
					installations. All framing details must allow for a   
					minimum clearance to combustible framing mem-   
					bers as shown in Table 2 on page 4.   
					Nailing Flanges Are   
					Provided At All Four   
					Corners At 5/8” , 1/2”   
					And Flush Settings   
					Step 6. (page 23) Install the logs and glow-   
					ing embers.   
					Left Side Top Corner of Fireplace Shown   
					(Right Side Requirements the Same)   
					Step7. (page23)Checkoutapplianceoperation.   
					Iftheapplianceistobeelevatedabovefloorlevel,   
					asolidcontinuousplatformmustbeconstructed.   
					Headers may be in direct contact with the appli-   
					ance top spacers but must not be supported by   
					themornotchedtofitaroundthem. Allconstruc-   
					tionabovetheappliancemustbeselfsupporting,   
					DONOTusetheapplianceforstructuralsupport.   
					Unit Being Secured By Its Nailing Flanges   
					To The Framing   
					Step 8. (page 23) Install glass door frame   
					assembly.   
					Note: The nailing flanges, combustible members   
					and screw heads located in areas directly adjacent   
					to the nailing flanges, are EXEMPT from the 1”   
					clearance to combustible requirements for the   
					firebox outer wrapper. Combustible framing may be   
					in direct contact with the nailing flanges and may   
					be located closer than 1” from screw heads and the   
					firebox wrapper in areas adjacent to the nailing   
					flanges. Frame the opening to the exact dimensions   
					specified in the framing details of this manual.   
					Step 9. (page 24) Adjust burner to ensure   
					proper flame appearance.   
					The fireplace should be secured to the side framing   
					members using the unit's nailing flanges - one top   
					and bottom on each side of the fireplace front. See   
					Figure 6. Use 8d nails or their equivalent.   
					DETAILED INSTALLATION STEPS   
					The appliance is shipped with all gas controls   
					and components installed and pre-wired. Re-   
					move the shipping carton, exposing the front   
					glassdoor. Removethebottompanelbylifting   
					and pulling it towards the front.   
					Unit Being Secured by Its Nailing   
					Flanges to the Framing   
					Step 2. ROUTING GAS LINE   
					Figure 6   
					Route a 1/2" (13 mm) gas line along the inside   
					of the left side framing as shown in Figure 7.   
					Gas lines must be routed, constructed and   
					made of materials that are in strict accordance   
					with local codes and regulations.   
					Left Side   
					Front Corner of   
					Fireplace Framing   
					Openthetwolatches(locatedunderthefirebox   
					floor) securing the glass door. Remove the   
					door by tilting it outward at the bottom and   
					liftingitup.Setthedoorasideprotectingitfrom   
					inadvertentdamage.SeeFigure39onpage23.   
					All appliances are factory-equipped with a flex-   
					ible gas line connector and 1/2 inch shutoff   
					valve. (See step 6 on page 22).   
					6-1/2"   
					(165 mm)   
					2-1/4"   
					(57 mm)   
					4-3/4"   
					(121 mm)   
					Figure 7   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS   
					NOTE: Local Codes Or Regulations   
					May Require Different Clearances.   
					* 
					See Item D in the Text Below.   
					P 
					V 
					N 
					N 
					NOTE: Location Of The Vent Termination   
					Must Not Interfere With Access To The   
					Electrical Service.   
					Center Line   
					Exterior Wall   
					Inside   
					of Termination   
					Corner Detail   
					O 
					*18”   
					V 
					G 
					V 
					Q 
					Horizontal   
					Termination   
					18”   
					Inside Corner   
					Detail D   
					Ventilated Soffit   
					A 
					= 9” in U.S.   
					= 12” in Canada   
					A 
					H 
					3 ft.   
					X 
					B 
					B 
					B 
					D 
					C 
					C 
					A 
					A 
					V 
					V 
					V 
					Fixed   
					Closed   
					Window   
					Operable   
					Window   
					L 
					V 
					3 ft.   
					V 
					F 
					V 
					J 
					M 
					C 
					B 
					B 
					C 
					V 
					I 
					A 
					X 
					V 
					= Air Supply Inlet   
					= Vent Termination   
					= Area where Termination is not Permitted   
					Canadian Installation*   
					US Installation**   
					12 inches (30cm)**   
					6 inches (15cm) for appliances   
					< 10,000 Btuh (3kW), 9 inches (23cm)   
					for appliances > 10,000 Btuh (3kW) and   
					< 50,000 Btuh (15kW), 12 inches (30cm)   
					for appliances > 50,000 Btuh (15kW)**   
					A = Clearance above grade, veranda, porch, deck, or balcony. 12 inches (30cm)*   
					B = Clearance to window or door that may be opened.   
					C = Clearance to permanently closed window   
					6 inches (15cm) for appliances   
					< 10,000 Btuh (3kW), 12 inches (30cm)   
					for appliances > 10,000 Btuh (3kW)   
					12 inches (305mm) recommended to   
					prevent window condensation   
					9 inches (229mm) recommended to   
					prevent window condensation   
					D = Vertical clearance to ventilated soffit located above the   
					termination within a horizontal distance of 18 inches (458mm)   
					from the center line of the termination   
					18 inches (458mm)   
					18 inches (458mm)   
					E = Clearance to unventilated soffit***   
					12 inches (305mm)   
					12 inches (305mm)   
					F = Clearance to outside corner   
					G = Clearance to inside corner   
					5 inches (12.7cm) minimum   
					6 inches (15.2cm) minimum   
					5 inches (12.7cm) minimum   
					6 inches (15.2cm) minimum   
					H = Clearance to each inside of center line extended above   
					meter/regulator assembly   
					I = Clearance to service regulator vent outlet   
					3 feet (91cm) within a height of 15 feet   
					above the meter/regulator assembly*   
					3 feet (91cm)*   
					3 feet (91cm) within a height of 15 feet   
					above the meter/regulator assembly**   
					3 feet (91cm)**   
					J = Clearance to nonmechanical air supply inlet to building or 6 inches (15cm) for appliances   
					6 inches (15cm) for appliances   
					the combustion air inlet to any other appliance   
					< 10,000 Btuh (3kW), 12 inches (30cm)   
					for appliances > 10,000 Btuh (3kW)   
					< 10,000 Btuh (3kW), 9 inches (23cm)   
					for appliances > 10,000 Btuh (3kW) and   
					< 50,000 Btuh (15kW), 12 inches (30cm)   
					for appliances > 50,000 Btuh (15kW)**   
					K = Clearance to a mechanical air supply inlet   
					6 feet (1.83m)*   
					3 feet (91cm) above if within 10 feet   
					(3m) horizontally**   
					L = Clearance above paved sidewalk or paved diveway located 7 feet (2.13m)‡   
					on public property   
					7 feet (2.13m)‡   
					M = Clearance under veranda, porch, deck or balcony   
					N = Depth of Alcove (Maximum)   
					12 inches (30cm)*‡   
					6 feet (1.83m)*   
					12 inches (30cm)‡   
					6 feet (1.83m)**   
					O = Clearance to Termination (Alcove)   
					P = Width of Alcove (Minimum)   
					6 inches (15.2mm)*   
					3 feet (91cm)*   
					6 inches (15.2mm)**   
					3 feet (91cm)*   
					Q = Clearance to Combustible Above (Alcove)   
					18 inches (457mm)*   
					18 inches (457mm)**   
					* In accordance with the current CSA-B149.1 National Gas And Propane Installation Code.   
					** In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes.   
					*** Clearance required to vinyl soffit material - 30 inches (76cm) minimum.   
					‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both   
					dwellings.   
					*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:   
					Figure 8   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIREPLACE FRAMING SPECIFICATIONS   
					Framing should be   
					constructed of 2 x 4   
					or larger lumber.   
					10-1/2   
					267   
					Model No.   
					MPLDV30   
					A 
					B 
					C 
					D 
					38   
					( 
					) 
					in.   
					30 9/16 40 3/4   
					786 1035   
					35 9/16 40 3/4   
					903 1035   
					40 9/16 45 3/4   
					1030 1162   
					45 9/16 45 3/4   
					1157 1162   
					16 1/2   
					419   
					mm   
					in.   
					965   
					38   
					16 1/2   
					419   
					*7   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					(178)   
					5-1/8   
					(130)   
					mm   
					in.   
					965   
					43   
					**12-1/8   
					(308)   
					16 1/2   
					419   
					mm   
					in.   
					1092   
					43   
					16 1/2   
					419   
					mm   
					1092   
					D 
					B 
					*9" (229 mm) For MPLDV-35, 40 & 45   
					**14-1/8" (359 mm) For MPLDV-35, 40 & 45   
					C 
					1/2 A   
					A 
					Inches (mm)   
					C is the required framing depth   
					dimension when the finish material   
					(drywall) thickness is 1/2 in. (13mm).   
					Figure 9   
					Framing   
					A 
					Note: The appliance 45° collar can be rotated about its axis to align for   
					corner installation. Remove interfering corner spacer. This spacer is   
					used for shipping only.   
					Model No.   
					MPLDV30   
					B 
					C 
					37   
					D 
					E 
					in. 30 1/4 52 1/4   
					mm 768 1327   
					14 7/64 26 1/8   
					358 664   
					940   
					b 
					in. 35 1/4 57 1/4 40 1/2 15 7/8 28 5/8   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					*D   
					mm 896   
					in. 40 1/4 62 1/4   
					mm 1022 1581   
					1454   
					1029   
					44   
					403   
					17 5/8 31 1/8   
					448 791   
					727   
					7 (178)   
					1118   
					in. 45 1/4 67 1/4 47 1/2 19 3/8 33 5/8   
					*C   
					May Be   
					Removed   
					May Be   
					Removed   
					mm 1149   
					1708   
					1207   
					492   
					854   
					a 
					*E   
					A 
					*B   
					Back wall of chase/enclosure   
					(including any finishing materials)   
					Note-   
					*These dimensions occur when one 45 degree elbow   
					is connected directly to the appliance collar.   
					Inches   
					(millimeters)   
					Venting requirements for corner installations - the horizontal vent length   
					“ a” to “ b,” must not exceed 28 inches (711 mm)   
					Corner Framing with Square Termination (SV4.5HT-2)   
					Figure 10   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FIREPLACE SPECIFICATIONS   
					F 
					G 
					6 5/8   
					(168)   
					TOP VIEW   
					E 
					17   
					(432)   
					1 
					(25.4)   
					3 5/16 (100 mm)   
					13 11/64   
					(335)   
					10   
					(254 mm)   
					A 
					B 
					C 
					H 
					D 
					2 9/32   
					(58)   
					4 3/4   
					(121)   
					FRONT VIEW   
					RIGHT SIDE VIEW   
					LEFT SIDE VIEW   
					Unit Dimensions   
					Model No.   
					MPLDV30   
					A 
					B 
					C 
					D 
					E 
					F 
					G 
					H 
					in. 40 1/2 37 1/2 20 5/8 24 1/8 30 1/4 19 3/4   
					mm 1029 953 534 613 768 502   
					9 7/8   
					251   
					27 1/4   
					692   
					in. 40 1/2 37 1/2 20 5/8 29 1/8 35 1/4 24 3/4 12 3/8 27 1/4   
					mm 1029 953 534 740 895 629 314 692   
					in. 45 1/2 42 1/2 25 5/8 34 1/8 40 1/4 29 3/4 14 7/8 32 1/4   
					mm 1156 1080 651 867 1022 756 378 819   
					in. 45 1/2 42 1/2 25 5/8 39 1/8 45 1/4 34 3/4 17 3/8 32 1/4   
					mm 1156 1080 651 994 1149 883 441 819   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					Figure 11   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The vent system may not service multiple   
					appliances, and must never be connected to a   
					flueservingasolidfuelburningappliance. The   
					vent pipe is tested to be run inside an enclos-   
					ingwall (suchasachase). Thereisnorequire-   
					ment for inspection openings in the enclosing   
					wall at any of the joints in the vent pipe.   
					Step 3. INSTALL THE VENT SYSTEM   
					General Information   
					SV4.5CGV-1   
					Termination   
					SV4.5FA OR   
					SV4.5FB Flashing   
					AND SV4.5SC   
					STORM COLLAR   
					Theseinstructionsshouldbeusedasaguide-   
					line and do not supersede local codes in any   
					way. Install vent according to local codes,   
					these instructions, the current National Fuel   
					Gas Code (ANSI-Z223.1) in the USA or the   
					current standards of CAN/CGA-B149.1 and -   
					B149.2 in Canada.   
					1" (25.4 mm)   
					Minimum   
					Clearance to   
					Combustibles   
					Select Venting System - Horizontal or Vertical   
					With the appliance secured in framing, deter-   
					mine vent routing and identify the exterior   
					termination location. The following sections   
					describe vertical (roof) and horizontal (exterior   
					wall) vent applications. Refer to the section   
					relating to your installation. A list of approved   
					ventingcomponentsisshowninthetableson   
					page 26.   
					*SV4.5VF   
					Firestop/Spacer   
					These fireplaces are designed, tested   
					and listed for operation and installation   
					with, andonlywith, SecureVent™ Direct   
					Vent System Components, Secure Flex™   
					FlexibleVentComponentsmanufactured   
					by Security Chimneys International and   
					Z-FLEX™ Model GA Venting Systems   
					listed to UL1777 and ULCS635 manufac-   
					tured by Flexmaster Canada Limited.   
					Theseapprovedventsystemcomponents   
					are labeled for identification. DO NOT   
					use any other manufacturer's vent com-   
					ponents with these appliances.   
					40' Max.   
					SV4.5L6/12/24/36/48   
					Vent Sections   
					(12.2 M)   
					6' Min.   
					(1.8 M)   
					VERTICAL TERMINATION SYSTEMS (ROOF)   
					*When using Secure Flex,   
					use Firestop/Spacer   
					SF4.5VF   
					Figures 13, 17 and 23 through 25 on pages   
					12, 14 and 15 and their associated Vertical   
					Vent Tablesillustratethevariousvertical vent-   
					ing configurations that are possible for use   
					with these appliances. Secure Vent pipe ap-   
					plications are shown in these figures; Secure   
					Flex pipe may also be used.   
					Thesefireplacesmustbeventeddirectly   
					to the outside.   
					Figure 13   
					AVerticalVentTablesummarizeseachsystem’s   
					minimumandmaximumverticalandhorizontal   
					length values that can be used to design and   
					install the vent components in a variety of   
					applications.   
					Determine the venting for the appliance. If the   
					vent run will include at least 8 feet of vertical   
					rise, then install the second restrictor in the   
					appliance collar before connecting any vent   
					(RefertoFigure12). Placethesecondrestric-   
					tor inside the fixed restrictor.   
					Vertical (Offset) Installation   
					Analyze the vent routing and determine the   
					quantities of vent sections and number of   
					elbows required. Refer to Vertical Vent Fig-   
					ures and Tables on page 14 and 15 to select   
					the type of vertical installation desired. Vent   
					sections are available in net lengths of 4-1/2"   
					(114 mm), 10-1/2" (267 mm), 22-1/2" (572   
					mm), 34-1/2" (876 mm) and 46-1/2" (1181   
					mm). Refer to the Vent Section Length Chart   
					on page 11 for an aid in selecting length   
					combinations. Elbows are available in 90° and   
					45° configurations. Refer to Figure 18 for the   
					SV4.5E45 and SV4.5E90 elbow dimensional   
					specifications.   
					Both these vertical vent systems terminate   
					through the roof. The minimum vent height   
					above the roof and/or adjacent walls is speci-   
					fiedinANSIZ223.1-(latestedition)(InCanada,   
					the current CAN-1 B149 installation code) by   
					major building codes. Always consult your   
					local codes for specific requirements. A gen-   
					eral guide to follow is the Gas Vent Rule (refer   
					to Figure 4 on page 6 ).   
					Note: The second restrictor is included within   
					the firebox.   
					Fixed Restrictor   
					Exhaust Vent   
					Vertical (Straight) Installation   
					Determine the number of straight vent sec-   
					tionsrequired.4-1/2"(114mm),10-1/2"(267   
					mm), 22-1/2" (572 mm), 34-1/2" (876 mm)   
					and 461/2" (1181 mm) net section lengths   
					are available. Plan the vent lengths so that a   
					joint does not occur at the intersection of   
					ceiling or roof joists. Refer to the Vent   
					Section Length Chart.   
					Second Restrictor (For Vertical Vent Only)   
					Figure 12   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Where required, a telescopic vent section   
					(SV4.5LA) maybeusedtoprovidetheinstaller   
					withanoptionininstallingintightand confined   
					spaces or where the vent run made up of fixed   
					length pieces develops a joint in a undesirable   
					location, or will not build up to the required   
					length. The SV4.5LA Telescopic Vent Section   
					has an effective length of from 1-1/2" (38 mm)   
					to 7-1/2" (191 mm).   
					VENT SECTION LENGTH CHART   
					VENT SECTION LENGTH CHART   
					Nominal   
					T 
					O 
					T 
					A 
					L 
					T 
					O 
					T 
					A 
					L 
					Nominal Section   
					6 
					12   
					24   
					36   
					48   
					Section Length   
					(inches)   
					6 
					12   
					24   
					36   
					48   
					Length (inches)   
					Net Section   
					4-1/2 10-1/2 22-1/2 34-1/2 46-1/2   
					Number of Vent Sections   
					Net Section   
					Length (inches)   
					4-1/2 10-1/2 22-1/2 34-1/2 46-1/2   
					Number of Vent Sections   
					Length (inches)   
					Height of Vent   
					Height of Vent   
					Q 
					T 
					Q 
					T 
					inches   
					144   
					ft   
					inches   
					4.5   
					ft   
					Y 
					Y 
					12   
					1 
					0 
					1 
					0 
					0 
					1 
					0 
					0 
					1 
					0 
					0 
					0 
					1 
					0 
					1 
					1 
					2 
					0 
					0 
					1 
					0 
					0 
					1 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					5 
					5 
					5 
					0 
					0 
					0 
					5 
					6 
					6 
					3 
					3 
					3 
					3 
					0 
					0 
					0 
					4 
					4 
					4 
					0 
					0 
					0 
					4 
					4 
					5 
					5 
					5 
					6 
					6 
					4 
					5 
					5 
					7 
					6 
					7 
					0.375   
					0.75   
					1 
					2 
					0 
					1 
					0 
					0 
					1 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					1 
					2 
					1 
					2 
					9 
					150   
					12.5   
					10.5 0.875   
					15 1.25   
					19.5 1.625   
					21 1.75   
					154.5 12.875   
					160.5 13.375   
					172.5 14.375   
					0 
					0 
					The SV4.5LA is fitted with a locking inclined   
					channel end (identical to a normal vent sec-   
					tion component) and a plain end with 3 pilot   
					holes. Slip the plain end over the locking   
					channel end of a standard SV4.5 vent com-   
					ponent the required distance and secure with   
					three #8 x 3/8" screws.   
					2 
					1 
					0 
					0 
					3 
					0 
					0 
					1 
					0 
					0 
					1 
					2 
					0 
					2 
					3 
					0 
					1 
					0 
					1 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					2 
					1 
					3 
					3 
					1 
					3 
					177   
					183   
					186   
					14.75   
					15.25   
					15.5   
					22.5 1.875   
					25.5 2.125   
					31.5 2.625   
					34.5 2.875   
					37.5 3.125   
					190.5 15.875   
					196.5 16.375   
					205.5 17.125   
					Maintain a minimum 1" (25 mm) clearance   
					to combustible materials for all vertical   
					vent elements.   
					43.5 3.625   
					0 
					0 
					0 
					1 
					2 
					0 
					0 
					0 
					1 
					2 
					0 
					2 
					0 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					3 
					2 
					1 
					3 
					207   
					17.25   
					45   
					3.75   
					211.5 17.625   
					46.5 3.875   
					49.5 4.125   
					217.5 18.125   
					229.5 19.125   
					232.5 19.375   
					0 
					0 
					0 
					1 
					0 
					1 
					0 
					0 
					0 
					0 
					1 
					1 
					0 
					0 
					0 
					1 
					0 
					1 
					0 
					0 
					1 
					0 
					1 
					0 
					0 
					1 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					6 
					6 
					0 
					0 
					5 
					5 
					0 
					0 
					0 
					0 
					0 
					6 
					0 
					6 
					6 
					6 
					0 
					0 
					7 
					7 
					7 
					0 
					0 
					8 
					8 
					0 
					9 
					9 
					7 
					7 
					Clearancesfor horizontal vent elementsare   
					1" (25 mm) at the sides and 1" (25 mm) on   
					the bottom. Clearances above horizontal   
					vent elementsare3"(76mm) for all models   
					and all applications. Exception: Clearance   
					is 5" (127 mm) for MPLDV35, MPLDV40 &   
					MPLDV45, when the center line of the hori-   
					zontal run is less than 48" (1219 mm) above   
					the fireplace top wrapper surface.   
					51   
					4.25   
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					1 
					0 
					0 
					0 
					0 
					0 
					1 
					1 
					0 
					1 
					0 
					2 
					0 
					0 
					0 
					0 
					1 
					0 
					2 
					0 
					0 
					0 
					0 
					0 
					2 
					1 
					2 
					3 
					0 
					3 
					0 
					0 
					0 
					1 
					2 
					0 
					1 
					0 
					0 
					0 
					1 
					0 
					0 
					2 
					0 
					2 
					2 
					1 
					0 
					0 
					0 
					2 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					1 
					1 
					1 
					2 
					0 
					2 
					2 
					3 
					2 
					4 
					3 
					2 
					4 
					3 
					3 
					2 
					4 
					3 
					2 
					4 
					3 
					0 
					5 
					55.5 4.625   
					237   
					19.75   
					0 
					6 
					57   
					66   
					4.75   
					5.25   
					241.5 20.125   
					7 
					7 
					246   
					252   
					264   
					276   
					279   
					20.5   
					21   
					7 
					8 
					67.5 5.625   
					7 
					8 
					69   
					72   
					5.75   
					6 
					22   
					7 
					8 
					23   
					8 
					8 
					73.5 6.125   
					79.5 6.625   
					23.25   
					0 
					6 
					280.5 23.375   
					283.5 23.625   
					289.5 24.125   
					301.5 25.125   
					310.5 25.875   
					8 
					9 
					Thestarterelbowmaynotbeusedifa45degree   
					vent run is required directly off of the unit.   
					Refer to Detail - Figure 17.   
					81   
					90   
					6.75   
					7.5   
					0 
					7 
					0 
					7 
					91.5 7.625   
					0 
					7 
					93   
					96   
					7.75   
					8 
					9 
					9 
					A. Attach Supplied 45 Degree Starter Elbow -   
					Slip the plain end with 3 mounting holes over   
					the locking channel end of the appliance collar   
					and secure with three screws.   
					315   
					26.5   
					9 
					10   
					7 
					97.5 8.125   
					102 8.5   
					103.5 8.625   
					325.5 27.125   
					0 
					2 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					3 
					3 
					2 
					0 
					0 
					4 
					3 
					4 
					330   
					336   
					345   
					27.5   
					28   
					0 
					8 
					0 
					8 
					108   
					114   
					117   
					9 
					28.75   
					10   
					10   
					0 
					10   
					11   
					8 
					B. Support The Elbows - Support the starter   
					elbow and the vertical portions of the venting   
					system with support bracket as shown in   
					Figure 23 - Detail A, on page 14. Do not use   
					the starter elbow anywhere else in the vent   
					system if not used on the appliance collar.   
					SV4.5 rigid and flex components can be used   
					directly off the collar. Do not return to rigid   
					sections after using flex sections in a vent run.   
					9.5   
					9.75   
					0 
					1 
					1 
					0 
					1 
					0 
					0 
					0 
					1 
					2 
					0 
					1 
					0 
					0 
					0 
					0 
					0 
					0 
					0 
					5 
					0 
					1 
					1 
					6 
					0 
					0 
					0 
					0 
					0 
					3 
					3 
					3 
					0 
					4 
					0 
					4 
					2 
					0 
					0 
					0 
					0 
					0 
					0 
					3 
					0 
					4 
					6 
					5 
					4 
					5 
					6 
					4 
					3 
					5 
					349.5 29.125   
					372 31   
					118.5 9.875   
					126 10.5   
					376.5 31.375   
					379.5 31.625   
					418.5 34.875   
					0 
					9 
					11   
					0 
					11   
					9 
					130.5 10.875   
					135 11.25   
					423   
					465   
					35.25   
					38.75   
					0 
					10   
					0 
					10 10   
					138   
					11.5   
					139.5 11.625   
					142.5 11.875   
					C. Frame ceiling opening - Use a plumb line   
					from the ceiling above the appliance to lo-   
					cate center of the vertical run. Cut and/or   
					frameanopening,10-1/2"x10-1/2" (267mm   
					x 267mm) inside dimensions, about this   
					center mark (Figure 14 ).   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				To attach a vent component to the 45 degree   
					starter elbow, align the dimpled end over the   
					elbow, adjusting the radial alignment until the   
					four locking dimples are aligned with the inlet   
					of the four inclined channels on the collar   
					(refer to Figure 15 ).   
					This seating position is indicated by the   
					alignment of the arrow and dimple as shown   
					in Figure 16.   
					10 1/2” Min.   
					(267 mm)   
					10 1/2” Min.   
					(267 mm)   
					F. Install firestop/spacer at ceiling - When   
					usingSecureVent,useSV4.5VFfirestop/spacer   
					at ceiling joists; when using Secure Flex, use   
					SF4.5VFfirestop/spacer.Ifthereislivingspace   
					above the ceiling level, the firestop/spacer   
					must be installed on the bottom side of the   
					ceiling. If attic space is above the ceiling, the   
					firestop/spacer must be installed on the top   
					side of the joist.   
					Push the vent component against the starter   
					elbow until it fully engages, then twist the   
					component clockwise, running the dimples   
					down and along the incline channels until they   
					seat at the end of the channels.   
					The unitized design of the Secure Vent com-   
					ponents will engage and seal both the inner   
					and outer pipe without the need for sealant or   
					screws. If desired a #6 x 1/2" screw may be   
					used at the joint, but it is not required as the   
					pipe will securely lock when twisted.   
					Route the vent sections through the framed   
					openingandsecurethefirestop/spacerwith8d   
					nails or other appropriate fasteners at each   
					corner. Remember to maintain 1" (25 mm)   
					clearance to combustibles, framing mem-   
					bers, and attic or ceiling insulation when   
					runningvertical chimneysections. Atticinsu-   
					lation shield (96K94) may be used to obtain   
					the required clearances indicated here. See   
					installation accessories table on page 25.   
					Figure 14   
					D. Attach vent components to 45 degree   
					starter elbow - Secure Vent SV4.5 direct vent   
					system components are unitized concentric   
					pipe components featuring positive twist lock   
					connections (see Figure 15 ).   
					Note: Always use the starter elbow directly   
					at the appliance 45° collar unless rigid   
					straightpipeofflexpipeisused, asshownin   
					Figure 17.   
					All of the appliances covered in this document   
					are fitted with collars having locking inclined   
					channels. The dimpled end of the vent compo-   
					nents fit over the appliance collar to create the   
					positive twist lock connection.   
					E. Attachventcomponentstoeachother-Other   
					vent sections may be added to the previously   
					installed section in accordance with the require-   
					ments of the vertical vent figures and tables. To   
					add another vent component to a length of vent   
					run, align the dimpled end over the inclined   
					channel end of the previously installed section,   
					adjusting the radial alignment until the four   
					locking dimples are aligned with the inlets of the   
					four incline channels of the previous section.   
					Push the vent component against the previous   
					section until it fully engages, then twist the   
					componentclockwiserunningthedimplesdown   
					and along the incline channels until they seat at   
					the end of the channels.   
					G. Support the vertical vent run sections -   
					Note - Proper venting support is very impor-   
					tant. The weight of the vent must not be   
					supported by the fireplace in any degree.   
					First Vent   
					Component   
					Support the vertical portion of the venting   
					system every 8 feet (2.4m) above the fireplace   
					vent outlet. One method of support is by utiliz-   
					ing field provided support straps (conven-   
					tional plumber's tape). Secure the plumber's   
					tape to the framing members with nails or   
					screws.   
					Align the dimple (four places)   
					with the opening of the locking   
					incline channel on appliance   
					collar. Twist vent component   
					clockwise to engage and seal.   
					Dimple   
					Locking   
					Incline Channel   
					45 degree starter elbow   
					Vent / 45 Degree Starter   
					Elbow Connection   
					Figure 15   
					Arrow   
					Align the dimple (four places) of the   
					upper vent section with the opening of   
					the locking incline channel on the   
					lower vent section. Twist vent   
					Blocking   
					component clockwise to engage and   
					seal until arrow and dimple align.   
					Support Straps   
					(Plumber’s tape)   
					Dimple   
					Rigid Or Flex   
					Venting   
					Components May   
					Be Connected   
					Directly To The 45   
					Degree Collar.   
					Locking   
					Incline Channel   
					Connected   
					Vent Sections   
					8 feet (2.4 m)   
					Maximum   
					Arrow   
					Vent / Vent Section   
					Connection   
					Arrow   
					Detail   
					Figure 16   
					1 inch   
					(25.4 mm)   
					minimum   
					clearance to   
					combustibles   
					Figure 17   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				H. Frame roof opening - Identify location for   
					vent at the roof. Cut and/or frame opening per   
					Roof Framing Chart and Figure 19.   
					Loop the tape around the vent, securing the   
					ends of the tape to the framing. If desired,   
					sheet metal screws #6 x 1/2" length may be   
					used to secure the support straps to the vent   
					pipe. Refer to Figure 17.   
					Storm   
					Collar   
					H. Change vent direction to horizontal/in-   
					clined run - At transition from or to a horizon-   
					tal/inclined run, install the SV4.5E45 and   
					SV4.5E90 elbows in the same manner as the   
					straight vent sections. The elbows feature a   
					twist section to allow them to be routed about   
					the center axis of their initial collar section to   
					align with the required direction of the next   
					vent run element. Twist elbow sections in a   
					clockwise direction only so as to avoid the   
					possiblity of unlocking any of the previously   
					connected vent sections. See Figure 18.   
					C 
					D 
					Figure 21   
					Framing Dimensions for Roof   
					L. Installtheverticaltermination-Thefinalstep   
					involves installation of the SV4.5CGV-1 Vertical   
					Termination. Extend the vent sections to the   
					height as shown in the "Vertical vent termination   
					section" on page 6. The SV4.5CGV-1 Vertical   
					Termination (Figure 22 ) installs in the exact   
					same fashion as any other Secure Vent section.   
					Align the termination over the end of the previ-   
					ouslyinstalledsection,adjustingtheradialalign-   
					ment until the four locking dimples of the termi-   
					nation are aligned with the inlets of the four   
					inclinechannelsofthelastventsection. Pushthe   
					terminationdownuntilitfullyengages,thentwist   
					the termination clockwise running the dimples   
					down and along the incline channels until they   
					seat at the end of the channels.   
					Pitch   
					0/12   
					C 
					D 
					10-1/2 in. 10-1/2 in.   
					(267 mm) (267 mm)   
					6/12   
					10-1/2 in.   
					(267 mm) (305 mm)   
					12 in.   
					8-1/8"   
					(206 mm)   
					4-13/16"   
					(122 mm)   
					12/12   
					10-1/2 in. 17-3/4 in.   
					(267 mm) (451 mm)   
					Swivel Joint   
					Swivel Joint   
					(360° swivel)   
					(360° swivel)   
					Figure 19   
					SV4.5E45   
					SV4.5E90   
					(45° Elbow)   
					(90° Elbow)   
					J. Install the roof flashing - Extend the vent   
					sectionsthroughtheroofstructure. Installthe   
					roof flashing over the vent section and posi-   
					tion such that the vent column rises vertically   
					(use carpenters level) (Figure 20 ). Nail along   
					perimeter to secure flashing or adjust roofing   
					to overlap the flashing edges at top and sides   
					only and trim where necessary. Seal the top   
					and both sides of the flashing with waterproof   
					caulking.   
					Figure 18   
					I. Continueinstallationofhorizontal/inclined   
					sections - Continue with the installation of the   
					straight vent sections in horizontal/inclined   
					run as described in Step E. Install support   
					straps every 5' (1.52 m) along horizontal/   
					inclinedventrunsusingconventionalplumber’s   
					tape. It is very important that the horizontal/   
					inclined run be maintained in a straight (no   
					dips) and slightly elevated plane in a direc-   
					tion away from the fireplace 1/4" per foot (20   
					mm per meter) which is ideal, though rise per   
					foot run ratios that are smaller are acceptable   
					all the way down to at or near level.   
					It is important to maintain the required clear-   
					ances to combustibles at the top and bottom   
					for all horizontal/inclined runs.   
					Figure 22   
					Maintain a minimum 1" (25 mm) clearance   
					to combustible materials for all vertical   
					vent elements.   
					Figure 20   
					If the vent system extends more than 5' (1.5   
					m) above the roof flashing, stabilizers may be   
					necessary. Additional screws may be used at   
					section joints for added stability. Guide wires   
					may be attached to the joint for additional   
					support on multiple joint configurations.   
					K. Install the storm collar - Install the storm   
					collar, supplied with the flashing, over the   
					vent/flashing joint. See Figure 21. Loosen   
					the storm collar screw. Slide collar down until   
					it meets the top of the flashing. Tighten the   
					adjustingscrew.Applynon-combustiblecaulk-   
					ing or mastic around the circumference of the   
					joint to provide a water tight seal.   
					Clearancesfor horizontal vent elementsare   
					1" (25 mm) at the sides and 1" (25 mm) on   
					the bottom. Clearances above horizontal   
					vent elementsare3"(76mm) for all models   
					and all applications. Exception: Clearance   
					is 5" (127 mm) for MPLDV35, MPLDV40 &   
					MPLDV45, when the center line of the hori-   
					zontal run is less than 48" (1219 mm) above   
					the fireplace top wrapper surface.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VERTICAL VENT FIGURES/TABLES   
					Note: Secure Vent (rigid vent pipe) is shown in the figures; Secure Flex (flexible vent pipe) may   
					also be used.   
					WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS   
					OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.   
					Note: It is very important that the horizontal/inclined run be maintained in a straight (no dips)   
					and recommended to be in a slightly elevated plane, in a direction away from the fireplace of   
					1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller   
					are acceptable all the way down to at or near level.   
					Note:SV4.5VF(SecureVent),SF4.5VF(SecureFlex)firestop/spacermustbeusedanytimeventpipe   
					passes through a combustible floor or ceiling. SV4.5HF (Secure Vent) or SF4.5HF (Secure Flex)   
					must be used anytime vent pipe passes through a combustible wall. For the MPLDV35/40/45, with   
					a center line lower than 48" (1219 mm) above the fireplace top wrapper surface, use SV4.5HF5 or   
					SF4.5HF5. In all cases the firestop/spacer provided with the termination may be used with the   
					termination, frame to 5" clearance where applicable.   
					Note: Two 45 degree elbows may be used in   
					placeof one90degreeelbow. Thesameriseto   
					run ratios, as shown in the venting figures for   
					90 elbows, must be followed if 45 degree   
					TABLE A   
					H Maximum   
					V Minimum   
					(meters)   
					elbows are used.   
					H 
					(meters)   
					feet   
					5 
					feet   
					(1.524)   
					(3.048)   
					(4.572)   
					(6.096)   
					(0.305)   
					(0.610)   
					(0.914)   
					(1.219)   
					1 
					2 
					3 
					4 
					10   
					15   
					20   
					* 
					Ceiling   
					*Ceiling   
					Firestop/Spacer   
					(SV4.5VF)   
					Firestop/Spacer   
					(SV4.5VF)   
					V + H = 40 feet (12.2 m) Max.   
					H = 20 feet (6.096 meters) Max.   
					**Wall   
					Firestop/Spacer   
					40 feet   
					(12.2 meters)   
					Maximum   
					Detail View   
					V 
					Support   
					Bracket   
					*When using Secure Flex,   
					use Firestop/Spacer   
					SF4.5VF   
					Support   
					Bracket   
					**Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure Flex respectively.   
					Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using Secure Vent or Secure Flex on horizontal   
					vent runs for the MPLDV35/40/45 with a center line lower than 48” (1219 mm) above the fireplace   
					top wrapper surface. In all cases the firestop/spacer provided with the termination may be used   
					with the termination, frame to 5” clearance where applicable.   
					* 
					When using Secure   
					Flex, use   
					Firestop/Spacer   
					SF4.5VF   
					Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical   
					vent will be required.   
					Note: Install second restrictor in any run   
					having more than 8 ft. of vertical rise.   
					This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet   
					of (H) horizontal run, up to a maximum horizontal run of 20 feet.   
					Figure 23 - Top Vent - STRAIGHT   
					Figure 24 - Top Vent - TWO 90 DEGREE ELBOWS   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VERTICAL VENT FIGURES/TABLES   
					(continued)   
					TABLE B   
					*Ceiling   
					V Minimum   
					(meters)   
					(0.305)   
					H +   
					feet   
					H 
					1 Maximum   
					Firestop/Spacer   
					(SV4.5VF)   
					V 
					**Wall   
					Firestop/Spacer   
					(meters)   
					(1.524)   
					(3.048)   
					(4.572)   
					(6.096)   
					feet   
					1 
					5 
					(0.610)   
					10   
					15   
					20   
					2 
					H 
					(0.914)   
					3 
					(1.219)   
					4 
					H + H = 20 feet (6.096 m) Max.   
					1 
					H 
					+ H + H = 40 ft. (12.192 m) Max.   
					V 
					1 
					1 
					Example: If 20 feet of (H) horizontal vent run is   
					needed, then 4 feet minimum of (V) vertical vent   
					will be required.   
					*When using Secure Flex,   
					use Firestop/Spacer   
					SF4.5VF   
					Support   
					Bracket   
					This table shows a 1 (V) to 5 (H) ratio. For every   
					1 foot of (V) vertical, you are allowed 5 feet of (H)   
					horizontalrun,uptoamaximumhorizontalrunof   
					20 feet.   
					Detail View   
					**Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure   
					Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using   
					Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35/40/45   
					with a center line lower than 48” (1219 mm) above the fireplace top wrapper   
					surface. In all cases the firestop/spacer provided with the termination may   
					be used with the termination, frame to 5” clearance where applicable.   
					Figure 25 - Top Vent - THREE ELBOWS   
					HORIZONTAL (OUTSIDE WALL)   
					TERMINATION SYSTEM   
					B. Support The Elbows - Support the starter   
					C. Plan the vent run -   
					elbow and the horizontal portions of the vent-   
					ing system with support bracket as shown in   
					Figure 29 to 32.   
					Analyze the vent routing and determine the   
					types and quantities of sections required   
					4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"   
					(572 mm), 34-1/2" (876 mm) and 46-1/2"   
					(1181 mm) net section lengths are available.   
					Plan the vent lengths so that a joint does not   
					occur at the intersection of ceiling or roof   
					joists. Make allowances for elbows as indi-   
					cated in Figure 18 on page 13.   
					Figures 26, and Figures 29 to 32 on pages 18   
					and 19 and their associated Horizontal Vent   
					Table illustrate the various horizontal venting   
					configurations that are possible for use with   
					these appliances. Secure Vent pipe applica-   
					tions are shown in these figures; Secure Flex   
					pipe may also be used. A Horizontal Vent Table   
					summarizeseachsystem’sminimumandmaxi-   
					mum vertical and horizontal length values that   
					can be used to design and install the vent   
					components in a variety of applications.   
					Both of these horizontal vent systems terminate   
					through an outside wall. Building Codes limit or   
					prohibit terminating in specific areas. Refer to   
					Figure 8 on page 7 for location guidelines.   
					SecureVent SV4.5direct vent systemcompo-   
					nents are unitized concentric pipe compo-   
					nents featuring positive twist lock connection,   
					(refer to Figure 15 and 16 on page 12). All of   
					the appliances covered in this document are   
					fittedwithcollarshavinglockinginclinedchan-   
					nels. The dimpled end of the vent components   
					fit over the appliance collar to create the posi-   
					tive twist lock connection.   
					Maintain a minimum 1" (25 mm) clearance   
					to combustible materials for all vertical   
					vent elements.   
					A. Attach Supplied 45 Degree Starter Elbow   
					- Slip the plain end with 3 mounting holes over   
					the locking channel end of the appliance collar   
					and secure with three screws.   
					Clearancesfor horizontal vent elementsare   
					1" (25 mm) at the sides and 1" (25 mm) on   
					the bottom. Clearances above horizontal   
					vent elementsare3"(76mm) for all models   
					and all applications. Exception: Clearance   
					is 5" (127 mm) for MPLDV35, MPLDV40 &   
					MPLDV45, when the center line of the hori-   
					zontal run is less than 48" (1219 mm) above   
					the fireplace top wrapper surface.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				D. Frame exterior wall opening -   
					TYPICAL HORIZONTAL VENT INSTALLATION   
					Locate the center of the vent outlet on the   
					exterior wall according to the dimensions   
					shown in Figure 9 on page 8.   
					Support   
					Brackets   
					Horizontal / Inclined Run   
					Building   
					Support   
					Framing   
					SV4.5 HT-2   
					Termination   
					SV4.5E90   
					Elbow   
					Cut and/or frame an opening, 10-1/2" x 12-1/8"   
					(267 mm x 308mm) inside dimensions, about   
					this center.   
					Exterior   
					Wall   
					SV4.5L6/12/24/36/48   
					Vent Sections   
					E. Frameceilingopening-Iftheverticalroute   
					is to penetrate a ceiling, use plumb line to   
					locatethecenterabovetheappliance. Cutand/   
					or frame an opening, 10-1/2" x 10-1/2" (267   
					mm x 267 mm) inside dimensions, about this   
					center (refer to Figure 14 on page 11 ).   
					Ceiling   
					Vertical   
					Rise   
					Firestop/Spacer   
					Support Bracket Spacing   
					Every 5 ft (1.52 m)   
					SV4.5 HT-2   
					Termination   
					See Figure 17 on page 12 for   
					vertical vent section support.   
					Exterior   
					Wall   
					F. Attach vent components to starter elbow -   
					To attach a vent component to the the starter   
					elbow, align the dimpled end over the collar,   
					adjusting the radial alignment until the four   
					locking dimples are aligned with the inlets of   
					the four incline channels on the collar (refer to   
					Figure 15 on page 12).   
					Fireplace   
					Figure 26   
					If there is living space above the ceiling level,   
					the firestop/ spacer must be installed on the   
					bottom side of the ceiling. If attic space is   
					above the ceiling, the firestop/ spacer must be   
					installed on the top side of the joist. Route the   
					vent sections through the framed opening and   
					secure the firestop/spacer with 8d nails or   
					other appropriate fasteners at each corner.   
					Install support straps every 5 ft. (1.52 m)   
					along horizontal/inclined vent runs using con-   
					ventional plumber’s tape. See Figure 26, it is   
					very important that the horizontal/inclined   
					run be maintained in a straight (no dips) and   
					recommended to be in a slightly elevated   
					plane, in a direction away from the fireplace   
					of 1/4" rise per foot (20 mm per meter) which   
					is ideal, though rise per foot run ratios that are   
					smallerareacceptableallthewaydowntoator   
					near level. Use a carpenter’s level to measure   
					fromaconstantsurfaceandadjustthesupport   
					straps as necessary.   
					Push the vent component against the elbow   
					untilitfullyengages,thentwistthecomponent   
					clockwise,runningthedimplesdownandalong   
					the incline channels until they seat at the end   
					of the channels. The unitized design of the   
					SecureVentcomponentswill engageandseal   
					both the inner and outer pipe elements with   
					the same procedure. Sealant and securing   
					screws are not required.   
					Remember to maintain 1" (25 mm) clearance   
					tocombustibles, framingmembers, andattic   
					or ceiling insulation when running vertical   
					chimney sections.   
					Note: A 90 or 45 degree elbow may not be   
					directly attached to the appliance elbow   
					collar.   
					It is important to maintain the required clear-   
					ances to combustibles at the top and bottom   
					for all horizontal/inclined runs.   
					I. Support the vertical run sections -   
					On the vertical run, support the venting sys-   
					tem every 8 feet (2.4m) above the fireplace   
					vent outlet with field provided support straps   
					(Plumber's tape).   
					G. Attach vent components to each other -   
					Other vent sections may be added to the pre-   
					viously installed section in accordance with   
					the requirements of the vent tables.   
					Maintain a minimum 1" (25 mm) clearance   
					to combustible materials for all vertical   
					vent elements.   
					Attachthestrapstotheventpipeandsecureto   
					the framing members with nails or screws.   
					See Figure 17 on page 12.   
					To add another vent component to a length of   
					vent run, align the dimpled end of the compo-   
					nent over the inclined channel end of the   
					previously installed section, adjusting the ra-   
					dial alignment until the four locking dimples   
					are aligned with the inlets of the four incline   
					channels of the previous section.   
					Clearancesfor horizontal vent elementsare   
					1" (25 mm) at the sides and 1" (25 mm) on   
					the bottom. Clearances above horizontal   
					vent elementsare3"(76mm) for all models   
					and all applications. Exception: Clearance   
					is 5" (127 mm) for MPLDV35, MPLDV40 &   
					MPLDV45, when the center line of the hori-   
					zontal run is less than 48" (1219 mm) above   
					the fireplace top wrapper surface.   
					J. Change vent direction - At transition from   
					or to a horizontal/inclined run, install the   
					SV4.5E45 and SV4.5E90 elbows in the same   
					manner as the straight vent sections. The   
					elbows feature a twist section to allow them   
					to be routed about the center axis of their   
					initial collar section to align with the required   
					direction of the next vent run element. Twist   
					elbowsectionsinaclockwisedirectiononly   
					so as to avoid the possiblity of unlocking   
					any of the previously connected vent sec-   
					tions. See Figure 18 on page 13.   
					Pushtheventcomponentagainsttheprevious   
					section until it fully engages, then twist the   
					component clockwise running the dimples   
					down and along the incline channels until they   
					seat at the end of the channels.This seating   
					position is indicated by the alignment of the   
					arrow and dimple as shown in Figure 16 on   
					page 12.   
					L. Assemble vent run to exterior wall - If not   
					previously measured, locate the center of the   
					vent at the exterior wall. Prepare an opening   
					as described in Step D. Assemble the vent   
					system to point where the terminus of the last   
					section is within 7 in. (178 mm) to 11-1/4 in.   
					(286 mm) inboard of the exterior surface to   
					which the SV4.5 HT-2 termination is to be   
					attached, see Figure 28.   
					K. Continueinstallationofhorizontal/inclined   
					sections- Continuewiththeinstallationofthe   
					straight vent sections in horizontal/inclined   
					run as described in Step F.   
					H. Install firestop/spacer at ceiling -   
					WhenusingSecureVent,useSV4.5VFfirestop/   
					spaceratceilingjoists;whenusingSecureFlex,   
					use SF4.5VF firestop/spacer.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				If the terminus of the last section is not within   
					this distance, use the telescopic vent section   
					SV4.5LA, as the last vent section. For wall   
					thicknesses greater than that shown in Figure   
					28, refer toTable3onpage18. Thistablelists   
					the additional venting components needed (in   
					addition to the termination and adapter) for a   
					particular range of wall thicknesses.   
					Firestop/Spacer provided with the   
					termination shown on the exterior   
					side of the wall. It may also be   
					installed on the interior side.   
					SV4.5 HT-2   
					Termination   
					**7"   
					10-1/2"   
					(267 mm)   
					(178)   
					**12-1/8"   
					(308 mm)   
					5-1/8"   
					(130 mm)   
					**3” (76 mm)   
					M. Attach termination adapter - Attach the   
					adapter (SV4.5RCH - provided with the termi-   
					nation) to the vent section or telescoping vent   
					section), elbow as shown in Figure 27 in the   
					same manner as any SV4.5 vent component   
					(refer to Step F).   
					for MPLDV30/35   
					6 to 48 inch   
					1"   
					(25.4 mm)   
					Vent Section,   
					Telescopic vent   
					section on Elbow   
					Note: Centerline of Vent Piping is   
					NOT the Same as the Centerline of   
					the Frame Opening.   
					N. Install Firestop/Spacer at exterior wall -   
					When using the square termination, install   
					the SV4.5HF (Secure Vent) or SF4.5HF (Se-   
					cure Flex) Firestop/Spacer over the open-   
					ing at the exterior side of the framing (long   
					side up) as shown in Figure 27, and fasten   
					into place. Ensure 5" clearance is main-   
					tained by framing above the vent run for   
					MPLDV35/40/45 when center line of the   
					run is lower than 48" (12119 mm) above   
					the fireplace top wrapper surface.   
					Adapter   
					SV4.5RCH   
					See Figure 9 on page 8   
					for Min. Distance to Base   
					of Appliance.   
					**Increase these dimensions by 2” (51mm) for MPLDV35/40/45   
					with horizontal vent runs with center lines lower than 48”   
					(1219mm) above the fireplace for wrapper surface.   
					Base of Appliance   
					Installing the Square Horizontal Termination (SV4.5HT-2)   
					Figure 27   
					*Use silicone caulking to   
					seal the top and sides of   
					the termination, up to the   
					underlayment, stucco, or   
					masonry wall surface.   
					Maximum wall thickness   
					10 in.(254 mm)**   
					(The Firestop/Spacer may also be installed   
					over the opening at the interior side of the   
					framing.)   
					Interior Surface of   
					Finished Wall   
					Exterior Surface of Siding   
					Exterior Surface of   
					Framing   
					Maximum Extent of   
					Vent Run Sections   
					Relative to Exterior   
					Surface of Framing   
					Siding   
					*Caulk   
					O. Install the desired termination -   
					6 in. to 9-1/4 in.   
					(152 to 235 mm)**   
					Last Vent Section. Use   
					Tel escopi c Vent   
					Section (SV4.5LA), If   
					Necessary   
					1. Install thesquaretermination(SV4.5HT-2)-   
					For the last step , from outside the exterior wall,   
					slide the collars of the termination onto the   
					adapter (the outer over the outer and the inner   
					insidetheinner)untiltheterminationseatsagainst   
					the exterior wall surface to which it will be   
					attached. Orient the housing of the termination   
					with the arrow pointed upwards. Secure the   
					termination to the exterior wall. The horizontal   
					termination must not be recessed into the   
					exterior wall or siding by more than the 1-1/4"   
					(32 mm) as shown in Figure 28.   
					SV4.5HT-2   
					Square Termination   
					*Caulk   
					SV4.5HT-2   
					Square Termination   
					Adapter   
					SV4.5RCH   
					1-1/4" Maximum Recess of   
					Square Termination into   
					Exterior Finishing Material   
					**For thicknesses greater   
					than 10” , see Table 3.   
					Stucco   
					SVHRK Snorkel Cap –The snorkel cap is de-   
					signed to be fitted into a basement window box.   
					The SVHRK cap is for use with flex vent. The   
					vertical distance between the inlet and outlet of   
					the cap is 28 in. (711 mm). pipe.   
					Venting Connection and Exterior Wall Recessing of the   
					Horizontal Square Termination (SV4.5HT-2).   
					Figure 28   
					Horizontal terminations have been designed to perform in a wide range of weather   
					conditions. Our terminations meet or exceed industry standards.   
					IMPORTANT: The vent termination is   
					hotwhileinoperationandforaperiodof   
					time following use of the fireplace. To   
					prevent contact with hot surfaces, we   
					recommend the use of a Termination   
					Guard. This can be purchased at your   
					local dealer.   
					When selecting the locations of your horizontal terminations, do not place the   
					termination where water from eaves and adjoining rooflines may create a heavy flow   
					of cascading water onto the termination cap. If the cap must be placed where the   
					possibility of cascading water exists, it is the responsibility of the builder to direct the   
					water away from the termination cap by using gutters or other means.   
					Take care to carefully follow the installation instructions for the termination, including   
					the use of silicone caulking where required.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				HORIZONTAL VENT FIGURES/TABLES   
					Note: Secure Vent components (rigid vent pipe and terminal) are   
					shown in the figures; Secure Flex components (flexible vent pipe and   
					terminal) may also be used.   
					The SV4.5HF or SF4.5HF firestop provided with each termination can be   
					usedasshowninFigure29 whenfittedattheexteriorwalladjacenttothe   
					termination.   
					Note: Two45degreeelbowsmaybeusedinplaceofone90degreeelbow.   
					The same rise to run ratios, as shown in the venting figures for 90 degree   
					elbows, must be followed if 45 degree elbows are used.   
					WARNING: UNDER NO CIRCUMSTANCES MAY SEPA-   
					RATE SECTIONS OF CONCENTRIC FLEXIBLE VENT PIPE   
					BE JOINED TOGETHER.   
					Note: It is very important that the horizontal/inclined run be main-   
					tained in a straight (no dips) and recommended to be in a slightly   
					elevated plane, in a direction away from the fireplace of 1/4" rise per   
					foot(20mmpermeter)whichisideal, thoughriseperfootrunratiosthat   
					are smaller are acceptable all the way down to at or near level.   
					TABLE 3   
					Venting Components Required for Various Exterior Wall   
					Thicknesses, When Using The Square Termination (SV4.5HT-2)   
					Note: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer   
					must be used anytime vent pipe passes through a combustible floor or   
					ceiling. Lennox MPLDV35"/40" & 45" models require 5" clearances to   
					combustibles above horizontal vent runs when the centerline of the   
					horizontal vent run is at or below 48" (1219 mm) above the fireplace top   
					wrapper. In all other instances, with these three models and with the   
					MPLDV30 in all instances, the clearance to combustibles above horizon-   
					tal vent runs is 3". Please note that to facilitate the 5" clearance when   
					required, we have two 5" clearance firestops. The SV4.5HF5 is for use   
					with rigid (Secure Vent™ ) and the SF4.5HF5 is for use with (Secure   
					Flex™ ). These firestops should be used whenever horizontal vent runs   
					meetingtheuserequirementsdetailedabove, penetratewallsseparating   
					occupied rooms in a house.   
					Exterior Wall Thickness   
					Venting Components Required   
					inches (mm)   
					Termination Kit Only   
					6 to 9-1/4 (152 to 235)   
					Termination Kit and 6 in. Vent   
					Section (SV4.5L6)   
					10-1/2 to 13-3/4 (267 to 349)   
					Termination Kit and 12 in. Vent   
					Section (SV4.5L12)   
					16-1/2 to 19-3/4 (419 to 502)   
					11 to 19-3/4 (279 to 502)   
					Termination Kit and Telescopic   
					Section (SV4.5LA 2 to 7-12 in.)   
					& 6 in. vent section (SV4.5L6)   
					Each of our horizontal terminations are shipped with a standard 3"   
					clearancehorizontalfirestop. InALLcasesthisfirestopmaybeusedatthe   
					exterior wall regardless of any circumstances that may require the 5"   
					clearance to combustibles above the horizontal vent component. The   
					firestop provided with the termination is not specific for use with any   
					particular clearance height.   
					SV4.5HF/SF4.5HF   
					Firestop   
					SV4.5HF/SF4.5HF   
					Firestop   
					Stud   
					Framing   
					Stud   
					Framing   
					Top   
					Spacer   
					Top   
					Spacer   
					5”   
					3”   
					1”   
					1”   
					1”   
					1”   
					1”   
					1”   
					3” Clearance   
					5” Clearance   
					Figure 29   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				*Use Firestop/Spacer SV4.5HF or SF4.5HF   
					when using Secure Vent or Secure Flex   
					respectively. Use Firestop/Spacer SV4.5HF5   
					or SF4.5HF5 when using Secure Vent or   
					Secure Flex on horizontal vent runs for the   
					MPLDV35/40/45 with a center line lower than   
					48” (1219 mm) above the fireplace top   
					wrapper surface. In all cases the   
					Example: If 20 feet of (H)   
					horizontalventrunisneeded,   
					then 4 feet minimum of (V)   
					vertical vent will be required.   
					TABLE C   
					H Maximum V Minimum   
					(meters)   
					(1.524)   
					(3.048)   
					(4.572)   
					(6.096)   
					(meters)   
					(0.305)   
					(0.610)   
					(0.914)   
					(1.219)   
					feet   
					5 
					feet   
					1 
					This table shows a 1 (V) to 5   
					(H) ratio. For every 1 foot of   
					(V) vertical, you are allowed   
					5 feet of (H) horizontal run,   
					up to a maximum horizontal   
					run of 20 feet.   
					firestop/spacer provided with the termination   
					may be used with the termination, frame to   
					5” clearance where applicable.   
					10   
					15   
					20   
					2 
					3 
					4 
					V + H = 40 feet (12.2 m) Max.   
					H = 20 ft. (6.096 m) Max.   
					H 
					H 
					Support   
					Bracket   
					V 
					*Wall   
					Firestop/Spacer   
					**Wall   
					Firestop/Spacer   
					*Ceiling   
					Firestop/Spacer   
					(SV4.5VF)   
					H = 28 inches (711 mm) Maximum   
					*When using Secure Flex, use   
					Firestop/Spacer SF4.5VF   
					Square termination (SV4.5HT-2) shown.   
					**Use Firestop/Spacer SV4.5HF or SF4.5HF when using   
					Secure Vent or Secure Flex respectively. Use   
					Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using   
					Secure Vent or Secure Flex on horizontal vent runs for   
					the MPLDV35/40/45 with a center line lower than 48”   
					(1219 mm) above the fireplace top wrapper surface.   
					In all cases the firestop/spacer provided with the   
					termination may be used with the termination, frame   
					to 5” clearance where applicable.   
					Figure 31 - Top Vent - ONE 90 DEGREE ELBOW -   
					CONNECTION DIRECTLY AT APPLIANCE   
					Support   
					Bracket   
					Square termination (SV4.5HT-2) shown.   
					See Table 3 as an aid in venting component selection   
					for a particular range of exterior wall thicknesses.   
					Figure 30 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW   
					CONNECTION NOT DIRECTLY AT APPLIANCE   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				HORIZONTAL VENT FIGURES/TABLES (CONTINUED)   
					**Wall   
					Firestop/Spacer   
					TABLE D   
					V Minimum   
					(meters)   
					H 
					feet   
					5 
					+ H1 Maximum   
					H 
					(meters)   
					(1.524)   
					(3.048)   
					(4.572)   
					(6.096)   
					feet   
					1 
					2 
					3 
					4 
					(0.305)   
					(0.610)   
					(0.914)   
					(1.219)   
					H 
					1 
					V*   
					10   
					15   
					20   
					***Note - When using   
					Secure Flex, use   
					**Wall   
					Firestop/Spacer   
					Firestop/Spacer SF4.5VF   
					H 
					V + + H = 40 feet (12.2 m) Max.   
					1 
					**Use Firestop/Spacer SV4.5HF or SF4.5HF when   
					using Secure Vent or Secure Flex respectively. Use   
					Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using   
					Secure Vent or Secure Flex on horizontal vent runs   
					for the MPLDV35/40/45 with a center line lower than   
					48” (1219 mm) above the fireplace top wrapper   
					surface. In all cases the firestop/spacer provided   
					with the termination may be used with the   
					H 
					+ H = 20 ft. (6.096 m) Max.   
					***Ceiling   
					Firestop/Spacer   
					(SV4.5VF)   
					1 
					Example: If 20 feet of (H) horizontal vent run   
					isneeded, then4feetminimumof(V)vertical   
					vent will be required.   
					Support Bracket   
					* 
					To Top Surface Of   
					Fireplace   
					termination, frame to 5” clearance where applicable.   
					This table shows a 1 (V) to 5 (H) ratio. For   
					every 1 foot of (V) vertical, you are allowed 5   
					feet of (H) horizontal run, up to a maximum   
					horizontal run of 20 feet.   
					Square termination (SV4.5HT-2) shown.   
					See Table 3 on page 18 as an aid in venting component selection for a particular range   
					of exterior wall thicknesses.   
					Figure 32 - Top Vent - TWO 90 DEGREE ELBOWS - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE   
					**When using Secure Flex, use   
					Firestop/Spacer SF4.5VF   
					H 
					TABLE E   
					V 
					H 
					+ H1 Maximum   
					+ V   
					1 Minimum   
					1 
					(meters)   
					(0.305)   
					(0.610)   
					(0.914)   
					(1.219)   
					(meters)   
					feet   
					1 
					feet   
					5 
					(1.524)   
					(3.048)   
					(4.572)   
					(6.096)   
					**Ceiling   
					Firestop/Spacer   
					(SV4.5VF)   
					10   
					15   
					20   
					2 
					3 
					4 
					H 
					***Wall   
					Firestop/Spacer   
					H 
					+ H = 20 feet (6.096 m) Max.   
					1 
					V 
					1 
					V 
					H 
					+ V + + H = 40 ft. (12.192 m) Max.   
					1 
					1 
					Example: If 20 feet of (H) horizontal vent   
					run is needed, then 4 feet minimum of (V)   
					vertical vent will be required.   
					V*   
					***Use Firestop/Spacer SV4.5HF   
					or SF4.5HF when using Secure   
					Vent or Secure Flex respectively.   
					Use Firestop/Spacer SV4.5HF5   
					or SF4.5HF5 when using Secure   
					Vent or Secure Flex on horizontal   
					vent runs for the MPLDV35/40/45   
					with a center line lower than 48”   
					(1219 mm) above the fireplace   
					top wrapper surface. In all cases   
					the firestop/spacer provided with   
					the termination may be used with   
					the termination, frame to 5”   
					This table shows a 1 (V) to 5 (H) ratio. For   
					every 1 foot of (V) vertical, you are allowed   
					5 feet of (H) horizontal run, up to a maxi-   
					mum horizontal run of 20 feet.   
					**Ceiling   
					Firestop/Spacer   
					(SV4.5VF)   
					***Wall   
					Firestop/Spacer   
					Support Bracket   
					*To Top Surface   
					Of Fireplace   
					clearance where applicable.   
					Square termination (SV4.5HT-2) shown.   
					See Table 3 on page 18 as an aid in venting component selection for a particular range of exterior wall thicknesses.   
					Figure 33 - Top Vent - THREE 90 DEGREE ELBOWS - ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				VERTICAL OR HORIZONTAL VENTING USING   
					SECURE FLEX KITS AND COMPONENTS   
					FLEX VENT   
					NOTE: OUTER PIPE IS PULLED AWAY TO   
					SHOW THE DETAIL OF THE INNER PIPE   
					Secure Flex venting kits and components may   
					be used in any venting application where rigid   
					Secure Vent (SV4.5) direct vent components   
					can be used. All restrictions, clearances and   
					allowancesthatpertaintotherigidpipingapply   
					to the flexible venting. Secure Flex kits may   
					notbemodified;also, undernocircumstances   
					may separate sections of flex pipe be joined   
					together. Secure Flex kits may be added to the   
					end of a vent run made up of rigid Secure Vent   
					(SV4.5) vent sections provided that doing so   
					does not violate any of the venting length,   
					height, routing, horizontal to vertical ratio re-   
					quirements or clearance considerations de-   
					tailed in this manual.   
					SECURING SCREW   
					(3 PLACES EQUIDISTANT   
					JUST BELOW GEAR CLAMP)   
					Apply ONLY MIL-PAC BLACK HIGH   
					TEMPERATURE SEALANT (Catalog No.   
					10K81) to the outside surface of both   
					collars of the adapter (be especially   
					careful to fill the grooves of the outer   
					collar to be covered by the flexible   
					pipe) and slide flexible pipe over   
					inner and outer adapter collars.   
					GEAR   
					CLAMPS   
					1-3/4 in. (44 mm)   
					Flexible Pipe and   
					Adapter Outer   
					1-3/4 in. (44 mm)   
					Flexible Pipe and   
					Adapter Inner   
					Collar Overlap   
					SecureFlexkitscomewithanincludedadapter   
					that can be fitted to the appliance collar or the   
					inclined channel end of the last Secure Vent   
					(SV4.5) vent section in a rigid system in the   
					exact same fashion as any other Secure Vent   
					section. Align the dimpled end of the adapter   
					over the previously installed section or appli-   
					ance collar, adjusting the radial alignment until   
					the four locking dimples of the adapter are   
					aligned with the inlets of the four incline chan-   
					nels of the last vent section or collar. Push on   
					the adapter until it fully engages, then twist the   
					adapter clockwise running the dimples down   
					and along the incline channels until they seat at   
					the end of the channels.   
					Collar Overlap   
					Adapter   
					(SV4.5RF)   
					SECURING SCREW   
					(3 PLACES EQUIDISTANT   
					JUST BELOW GEAR CLAMP)   
					Attach Adapter to Appliance   
					Collar, or Secure Vent Sections   
					Figure 34   
					SV4.5HF (Secure Vent) or SF4.5HF (Secure   
					Flex) must be used anytime vent pipe passes   
					through a combustible wall. For the   
					MPLDV35/40/45withacenterlinelower than   
					48" (1219 mm) above the fireplace top wrap-   
					persurfaceuseSV4.5HF5orSV4.5HF5. Inall   
					cases the firestop/spacer provided with the   
					termination may be used with the termina-   
					tion, frame to 5" clearance where applicable.   
					2. ApplyabeadofMill-PacBlack(700°F)high   
					temperature sealant - Catalog No. 10K81) to   
					the outer adapter collar; to the grooves of the   
					collar which extend approximately 1 inch from   
					theendandtotheflatsurface,approximately1-   
					3/8 inches from the end.   
					3. Pull and extend the outer flexible vent pipe.   
					4. Slide the outer flex pipe over the adapter   
					collar. Ensure the flexible vent pipe com-   
					pletely engages the adapter collar to a dis-   
					tance of 1-3/4 inches from the end, and that   
					it is free from damage or tears.   
					Attach the flexible vent to the adapter as   
					follows (also see Figure 34 ):   
					A. Install the Inner Flex Pipe -   
					1. Installthesmall gearclamplooselyaroundthe   
					innerflexibleventpipe,pushitbackoutoftheway.   
					2. Apply a bead of Mill-Pac Black (700°F)   
					high temperature sealant - Catalog No.   
					10K81) to the inner adapter collar, approxi-   
					mately 1/2 inch from the end.   
					See the appropriate sections and figures   
					shown throughout the venting section for   
					their installation requirements.   
					5. Slide the gear clamp down and tighten it   
					fully to secure the flexible vent to the adapter   
					outer collar approximately 3/4 inch from the   
					end of the flex.   
					Flexible Vent Section   
					6. Install three screws 120 degrees apart   
					through the flexible vent pipe and into the   
					adapter collar just below the gear clamp to   
					provide additional security to the connection.   
					3. Pull and extend the inner flexible vent pipe.   
					4. Slide the inner flex pipe over the adapter   
					collar.Ensuretheflexibleventpipecompletely   
					engages the adapter collar to a distance of 1³⁄₄   
					inches from the end, and that it is free from   
					damage or tears.   
					C. Route Flex Vent -   
					Ensure that the flex vent is properly routed to   
					provide the required clearance. Do Not allow   
					theflexibleventtobendinaradiustighterthan   
					5" (127 mm). Refer to Figure 35. Support   
					horizontal sections of flex with metal straps at   
					2 foot (0.61 m) intervals.   
					5. Slide the gear clamp down and tighten it   
					fully to secure the flexible vent to the adapter   
					inner collar approximately 3/4 inch from the   
					end of the flex.   
					6. Install three screws 120 degrees apart   
					through the flexible vent pipe and into the   
					adapter collar just below the gear clamp to   
					provide additional security to the connection.   
					5" (127 mm)   
					Radius Minimum   
					Figure 35   
					E. Attach Flex Vent to Termination -   
					D. Install Firestop/Spacers at ceilings and walls -   
					When Secure Flex penetrates a wall or ceil-   
					ing, a firestop/spacer is required: use SV4.5   
					(Secure Vent), SF4.5 (Secure Flex) firestop/   
					spacer anytime vent pipe passes through a   
					combustible floor or ceiling.   
					Secure Flex components can be purchased   
					separately and attached to bulk lengths of   
					Secure Flex flexible tubing cut to size at the   
					jobsite. SecuretheflexibleventtotheSecure   
					Flex terminations in the same manner (see   
					Figure 34) as it was attached to the adapter.   
					B. Install the Outer Flex Pipe -   
					1. Install the large gear clamp loosely around   
					the outer flexible vent pipe, push it back out of   
					the way.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Note: Secure Flex vent must be attached to   
					Secure Flex terminations only. DO NOT   
					substitute Secure Vent terminations or the   
					Secure Vent adapter for Secure Flex compo-   
					nents. The collars of Secure Flex termina-   
					tions and adapters have a different circum-   
					ference than that used with the Secure Vent   
					pipe. Additionally, Secure Flexcomponents   
					have an extended length center tube for use   
					in attaching the flexible vent.   
					4.Ifanoptionalcontrolswitchisinstalled,turn   
					the appliance-mounted ON/OFF burner con-   
					trol switch to the OFF position.   
					Optional wall-mounted switch, thermostat, or   
					one of the optional remote control kits may   
					also be used. The appliance mounted ON/OFF   
					switch needs to be relocated onto the optional   
					style view door, if used.   
					B. Electronic Wiring (See Figure 37 ) –   
					Note: The electronic appliance must be con-   
					nected to the main power supply.   
					7. If wall-mounted ON/OFF control or thermo-   
					stat is to be used, mount it in a convenient   
					location on a wall near the fireplace.   
					1. Route a 3-wire 120Vac 60Hz 1ph power   
					supply to the appliance junction box.   
					8. If an optional control is to be used, wire it in   
					the low voltage circuit as shown in Figure 37.   
					Step 4. FIELD WIRING   
					2. Remove the electrical inlet cover plate from   
					the side of the unit by removing the plate's   
					securing screws. See Figure 11 on page 9.   
					Note: The supplied 15 feet of 2 conductor wire   
					has one end of each conductor connected to the   
					gas valve circuit and the other end of each   
					conductor placed loose inside the bottom com-   
					partment.   
					Caution: Label all wires prior to disconnec-   
					tion when servicing controls. Wiring errors   
					can cause improper and dangerous opera-   
					tion. Verifyproperoperationafterservicing.   
					3. Removethe coverplate'sknockoutandthen   
					feed the power supply wire through the knock-   
					out opening and into the unit junction box.   
					Refer to Section A for millivolt appliances and   
					Section B for electronic appliances. The gas   
					valve is set in place and pre-wired at the   
					factory on both models.   
					9. If an optional control switch is installed,   
					turn the appliance-mounted ON/OFF burner   
					control switch to the OFF position.   
					4. Connect the black power supply wire to the   
					lower outlet's red pigtail lead and the white   
					power supply wire to the common terminal of   
					the outlet as shown in Figure 37.   
					A. Millivolt Wiring (See Figure 36 ) –   
					10. After the wiring is complete, replace the   
					cover plate.   
					1. Appliance-mounted ON/OFF burner control   
					switch (rocker switch) is factory installed be-   
					hind the bottom panel. Optional wall-mounted   
					switch, thermostat, or one of the optional   
					remote control kits may also be used.   
					5.Connectthegroundsupplywiretothepigtail   
					lead attached to outlet's green ground screw.   
					Note: No batteries to be installed in the   
					battery holder until a power outage, or if the   
					appliance is to be operated solely with two   
					(2) "D" batteries.   
					6. Appliance-mounted ON/OFF burner control   
					switch (rocker switch) is factory installed be-   
					hind the bottom panel.   
					2. If wall-mounted ON/OFF control or thermo-   
					stat is selected mount it in a convenient loca-   
					tion on a wall near the fireplace.   
					120 VAC   
					INTERMITTENT ELECTRONIC WIRING DIAGRAM   
					SPARK TO PILOT IGNITOR   
					BK   
					GR   
					W 
					3. Wire the control switch within the millivolt   
					controlcircuit usingthe15feetof2conductor   
					wire supplied with the unit.   
					BK   
					Note: The supplied 15 feet of 2 conductor   
					wire has one end of each conductor con-   
					nected to the gas valve circuit and the other   
					end of each conductor placed loose inside   
					the bottom compartment.   
					IGNITOR MODULE   
					3V   
					JUNCTION BOX   
					BLACK (IGNITOR)   
					BLACK (SENSOR)   
					TRANSFORMER 3V   
					Caution: Do Not connect the optional wall   
					switch to a 120V power supply.   
					WIRING DIAGRAM MILLIVOLT GAS VALVES   
					THERMOPILE   
					BLACK   
					TO WALL   
					SWITCH OR   
					THERMOSTAT   
					APPLIANCE- MOUNTED   
					ON/OFF SWITCH   
					ORANGE (THTP)   
					BLACK (TP)   
					BATTERY BACK-UP   
					TP-TH   
					T O P I L   
					HI   
					LO   
					TP   
					TH   
					RED   
					GREEN (TH)   
					BROWN   
					GAS VALVE   
					BK/W(1)   
					BK/W(1)   
					BROWN   
					Figure 37   
					WALL-MOUNTED ON/OFF SWITCH (OPTIONAL)   
					THERMOSTAT (OPTIONAL)   
					Figure 36   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				IMPORTANT: Ground supply lead must   
					be connected to the wire attached to the   
					green ground screw located on the out-   
					let box. See Figure 37. Failure to do so   
					will result in a potential safety hazard.   
					The appliance must be electrically   
					groundedinaccordancewithlocal codes   
					or, in the absence of local codes, the   
					National Electrical Code, ANSI/NFPA70-   
					(latest edition). (In Canada, the current   
					CSA C22-1 Canadian Electrical Code.)   
					Gas Line Access Plate Not Installed   
					At The Factory. It Is Included In   
					The Installation Instruction Bag.   
					Step 5. CONNECTING GAS LINE   
					Gas   
					Supply   
					Line   
					ON/OFF   
					Switch   
					All codes require a shut-off valve mounted in   
					the supply line. The orientation of the shut-   
					off valve should face the front, as shown in   
					Figure 39. Figure 38 illustrates the method   
					for connecting the gas supply.   
					Gas Valve   
					Piezo Ignitor   
					Shut-Off Valve   
					(Orientation   
					Air Shutter   
					Adjustment Arm   
					As Shown)   
					Figure 39   
					The flex-line method is acceptable in the U.S.,   
					however,Canadianrequirementsvarydepend-   
					ing on locality. Installation must be in compli-   
					ance with local codes.   
					These appliances come from the factory with   
					the gas line access plate removed to provide   
					full access to the end of the gas flex line.   
					Secure all joints tightly using appropriate   
					tools and sealing compounds (ensure pro-   
					pane resistant compounds are used in pro-   
					pane applications).   
					As designed, the glass door needs to be   
					opened to access the open gas access area.   
					Route a hard pipe from the left to a spot   
					directly below the access plate opening.   
					Theseappliancesareequippedwithagasflex   
					line for use in connecting the unit to the gas   
					line. A gas flex line is provided to aid in   
					attaching the direct vent appliance to the gas   
					supply.   
					Turn on gas supply and test for gas leaks,   
					using a gas leak test solution (also referred to   
					as bubble leak solution).   
					Note: Usingasoapywater solution(50%dish   
					soap, 50% water) is an effective leak test   
					solution but it is not recommended, because   
					the soap residue that is left on the pipes/   
					fittingscanresultincorrosionovertime. Never   
					use an open flame to check for leaks.   
					Bring the shutoff valve on the end of the flex   
					line over to the hard pipe and tighten with   
					wrenches from above through the firebox   
					opening.   
					The gas flex line can only be used where local   
					codes permit. See Figure 38 for flex line   
					description. The flex line is rated for both   
					natural and propane gas. A manual shut off   
					valve is also provided with the flex line.   
					If required, access the valve by removing the   
					lower control compartment panel (see Figure   
					39 ) by lifting and pulling the panel forward.   
					The millivolt and electronic control valve has a   
					3/8" (10 mm) NPT thread inlet port.   
					A. Light the appliance (refer to the lighting   
					instructions label in the control compartment   
					or in the Homeowner's Care and Operation   
					Instructions).   
					The gas control valve is located in the lower   
					control compartment.   
					B. Brush all joints and connections with the   
					gas leak test solution to check for leaks. If   
					bubbles are formed, or gas odor is detected,   
					turn the gas control knob to the “OFF” posi-   
					tion. Either tighten or refasten the leaking   
					connection and retest as described above.   
					Flex Line Connector   
					3/8" NPT x 3/8"   
					Flare Fitting   
					1/2" x 3/8" Flare   
					Shut-Off Valve   
					Gas   
					Stub   
					Gas   
					Valve   
					C. When the gas lines are tested and leak free,   
					be sure to rinse off the leak testing solution.   
					3/8" Flex Tubing   
					D. When the gas lines are tested and leak free,   
					observe the individual tongues of flame on the   
					burner. Make sure all ports are open and   
					producing flame evenly across the burner. If   
					any ports are blocked, or partially blocked,   
					clean out the ports.   
					Figure 38 - GAS CONNECTION   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					23   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Millivolt Appliance Checkout   
					Step 6. INSTALLING THE LOGS, GLOW-   
					ING EMBERS AND VOLCANIC STONES   
					Step 8. INSTALLING THE GLASS DOOR   
					AND OPTIONAL HOOD   
					The pilot flame should be steady, not lifting or   
					floating. Flame should be blue in color with   
					traces of orange at the outer edge.   
					Remove the gas line access plate and gasket   
					from the provided plastic bag and install them   
					over the opening, using the provided screws   
					(4) as shown in Figure 39.   
					To access the glass door securing latches,   
					first open the lower control compartment   
					door (Figure 42 ) by lifting and pulling the   
					bottom panel forward.   
					The top 3/8" (10 mm) at the pilot generator   
					(thermopile) and the top 1/8" min (tip) of the   
					quick drop out thermocouple should be en-   
					gulfed in the pilot flame.   
					Retrieve the glass door. Visually inspect the   
					gasket on the backside of the frame. Gasket   
					surface must be clean, free of irregularities and   
					seated firmly.   
					Refer to Figure 43 and loosen the set screw   
					for the venturi air shutter. Manually actuate   
					the air shutter through several cycles. Set the   
					air shutter to 3/32" before placing the logs.   
					The flame should project 1" (25 mm) beyond   
					the hood at all three ports (Figure 40 ). Re-   
					place logs if removed for pilot inspection.   
					Positionthedoorinfrontofthefireboxopening   
					with the bottom of the door held away from the   
					fireplace (Figure 42 ). Hook the top flange of   
					thedoorframeoverthetopofthefireboxframe.   
					Let the bottom of the door frame swing gently   
					in towards the fireplace ensuring that the gas-   
					ket seats evenly as the door frame draws shut.   
					Fasten the two latches located underneath the   
					firebox floor to the door's vee-flange. Close   
					both the latches securely.   
					The logs are packaged in a carton located   
					within the firebox. One plastic bag of glowing   
					embers and volcanic stones are located in the   
					bottom compartment. Refer to the Log Set   
					Placement Supplement for detailed place-   
					ment instructions for the logs, glowing em-   
					bers and volcanic stones.   
					To light the burner; turn “ON” the remote wall   
					switch and rotate the gas valve control knob   
					counterclockwise to the “ON” position (“ON”   
					will be at the bottom side of the valve).   
					Hood Ignitor Rod   
					MILLIVOLT   
					Proper log and twig placement is critical to   
					encourage outstanding flame appearance and   
					prevent sooting. These fires are designed to   
					provide a rich orange/red glow on the logs.   
					Ensure the bottom of the rear log is fully seated   
					and pulled as far forward as the pins will al-   
					low. Refer to the Log Set Placement   
					Supplement for detailed instructions.   
					Thermocouple   
					If desired, install the optional hood. Note the   
					location of the three clips inside the top air   
					channel above the door. The clips are equally   
					spaced on the top surface of the air channel   
					opening. Use a screwdriver to open the clips   
					slightly if needed. Engage the back edge of the   
					eyebrow into the clips to secure.   
					3/8" Min   
					(9 mm)   
					Pilot   
					Nozzels   
					Note: Logsetupisbydesignasymmetric. The   
					fire is intentionally positioned off center to   
					provide a natural fire look.   
					Thermopile   
					Figure 40   
					Step 7. CHECKINGAPPLIANCEOPERATION   
					Electronic Appliance Checkout   
					Withgaslineinstalledruninitialsystemcheck-   
					out before closing up the front of the unit.   
					Follow the pilot lighting instructions provided   
					in the Homeowner's Care and Operation In-   
					structions. For piezo ignitor location see Fig-   
					ure 39 on page 23 (millivolt appliances only).   
					To light the burner, turn ‘ON’ the unit mounted   
					On/Off switch or the optional remote wall   
					switch. Ensure the ignitor lights the pilot. The   
					pilot flame should engulf the flame rod as   
					shown in Figure 41.   
					Burner   
					Assembly   
					Note: Lighting Instructions are also found on   
					the literature tag tied to the gas piping next to   
					the gas valve. To access the tag, open the   
					lowercontrolcompartmentdoor(Figure39 on   
					page 23 ) by pulling the panel forward.   
					ELECTRONIC   
					Door   
					Sensor   
					Ignitor   
					Pilot   
					Hood   
					Assembly   
					Gas Line Access Panel   
					Bottom Panel   
					When first lighting the appliance, it will take   
					a few minutes for the line to purge itself of   
					air. Once purging is complete, the pilot and   
					burner will light and operate as indicated in   
					the instruction manual. Subsequent lighting   
					of the appliance will not require such purg-   
					ing. Inspect the pilot flame (remove logs, if   
					necessary, handling carefully).   
					Figure 42 -   
					INSTALLING THE GLASS DOOR   
					WARNING: HANDLE THIS GLASS WITH   
					EXTREME CARE! THE GLASS PANEL IS   
					SUSCEPTIBLE TO DAMAGE — DO NOT   
					SCRATCH WHILE HANDLING OR WHILE   
					RE-INSTALLING THE GLASS DOOR   
					FRAME.   
					Figure 41   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					24   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The adjustment rod and associated adjustable   
					air shutter is patented technology. Flame ad-   
					justments can be made quickly and accurately   
					to taste without the need of disassembling the   
					appliance and waiting for 30 minutes after   
					each adjustment.   
					WARNING: DO NOT OPERATE APPLI-   
					ANCE WITH THE GLASS FRONT RE-   
					MOVED, CRACKED OR BROKEN. RE-   
					PLACEMENT OF THE GLASS SHOULD   
					BEDONEBYALICENSEDORQUALIFIED   
					SERVICE TECHNICIAN.   
					CAUTION: THE AIR SHUTTER DOOR   
					AND NEARBY APPLIANCE SURFACES   
					ARE HOT. EXERCISE CAUTION TO   
					AVOID INJURY WHILE ADJUSTING   
					FLAME APPEARANCE.   
					Propane models may exhibit a flame pattern   
					that may candle or appear stringy. If this is   
					problematic or persists as the appliance is   
					continually operated, adjust the air shutter   
					closedasdescribedinthepreviousparagraphs.   
					Operatetheapplianceforaperiodoftimeasthe   
					effect diminishes, ensuring that the appliance   
					does not develop sooty flames.   
					To adjust the flame, rotate the lever arm up or   
					down (rod located in the lower control area).   
					Position the air shutter to the factory setting as   
					shown in the table in Figure 43. Allow the   
					burner to operate for at least 20 minutes.   
					Step 9. BURNER ADJUSTMENTS   
					Flame Appearance and sooting   
					Proper flame appearance is a matter of taste.   
					Generally, mostpeoplepreferthewarmglowof   
					a yellow to orange flame. Appliances operated   
					with air shutter openings that are too large will   
					exhibit flames that are blue and transparent.   
					These weak, blue and transparent flames are   
					termed anemic. If the air shutter opening is too   
					small sooting may develop.   
					Air Shutter Rod   
					Air   
					Adjustment   
					Arm   
					When satisfied that the appliance operates   
					properly, proceed to finish the installation.   
					Leave the control knob in the ON position and   
					theremoteswitchOFF.Closethelowercontrol   
					compartment door.   
					Venturi   
					Sooting is indicated by black puffs developing   
					at the tips of very long orange flames. Sooting   
					results in black deposits forming on the logs,   
					appliance inside surfaces and on exterior sur-   
					facesadjacent tothevent termination. Sooting   
					is caused by incomplete combustion in the   
					flames and lack of combustion air entering the   
					air shutter opening. To achieve a warm yellow   
					to orange flame with an orange body that does   
					notsoot, theshutteropeningmustbeadjusted   
					between these two extremes.   
					FINISHING REQUIREMENTS   
					Wall Details   
					Valve   
					Complete finished interior wall. To install the   
					appliance facing flush with the finished wall,   
					positionframeworktoaccommodatethethick-   
					ness of the finished wall (Figure 44 )   
					MAIN BURNER   
					FACTORY SHUTTER OPENING SETTING   
					Natural Gas Propane Gas   
					Models   
					inches (mm) inches (mm)   
					MPLDV30 3/32 (2.38)   
					MPLDV35 1/16 (1.6)   
					MPLDV40 1/4 (6.35)   
					MPLDV45 1/4 (6.35)   
					3/16 (4.76)   
					1/4 (6.35)   
					3/8 (9.5)   
					This Area Must   
					Combustible   
					Remain Clear   
					Finished Wall   
					of Combustible   
					Materials   
					Materials   
					No smoke or soot should be present. These   
					logs are designed to be involved in the fire.   
					Flameswillimpingethetoptipsoftherightand   
					left logs.   
					1/2 (12.7)   
					3-1/2" Min   
					(89 mm)   
					Combustible   
					materials not   
					allowed   
					Figure 43   
					If the logs are properly positioned and sooting   
					conditions exist, the air shutter opening on the   
					main burner tube should be adjusted. Normally,   
					the more offsets in the vent system, the greater   
					the need for the air shutter to be opened further.   
					below this   
					point on   
					the face of the   
					appliance.   
					CAUTION: DO NOT BEND THE AIR SHUTTER   
					ROD. MAKESURETHEAIRSHUTTERMOVES   
					WHEN THE LEVER ARM IS OPERATED.   
					Top of   
					Appliance   
					Spacer   
					10" Min   
					(254 mm)   
					Burner Adjustment   
					Note: When first operating the air shutter   
					adjustment lever arm observe the air shutter.   
					If it is not moving, open the glass, ensure the   
					air shutter screw is loose and adjust by hand   
					through a couple of cycles, to break the adhe-   
					sion of paint, if required. Close door and   
					adjust with the lever as needed.   
					Top of Door Frame   
					Optional Hood   
					WARNING: AIR SHUTTER ADJUST-   
					MENT SHOULD ONLY BE PER-   
					FORMED BY A QUALIFIED PROFES-   
					SIONAL SERVICE TECHNICIAN.   
					Figure 44   
					A hearth extension is not required with this   
					appliance. If ahearthextensionisused, donot   
					block the lower control compartment door.   
					Any hearth extension used is for appearance   
					onlyanddoesnothavetoconformtostandard   
					hearth extension installation requirements.   
					Observe the flame continuously. If it appears   
					weak or sooty as previously described, adjust   
					the air shutter by rotating the adjustment arm   
					upordown(refertoFigure39)untiltheflame   
					appearance is as desired.   
					IMPORTANT:ENSURETHATTHEFRONT   
					GLASSPANELISINPLACEANDSEALED   
					DURING ADJUSTMENT.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					25   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Note: Combustible wall finish materials and/or surround materials must not be allowed to be placed in direct contact with the area defined   
					by the appliance front face (black sheet metal). Never allow combustible materials to overlap the appliance front face. See Figure 44   
					on page 25. Combustible mantle materials may be placed in front of non-combustible facing materials, as shown in Figure 45.   
					Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must   
					not cover any portion of the glass or hood; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel up   
					to the installed hood.   
					Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 45. Mantels constructed of non-   
					combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood.   
					Combustible materials may project beyond the   
					sides of the fireplace opening as long as they   
					are kept within the shaded areas illustrated in   
					Figure 46.   
					MANTEL CLEARANCES   
					Inches (mm)   
					12 (305) MANTEL   
					10 (254) MANTEL   
					8 (203) MANTEL   
					6 (152) MANTEL   
					4 (102) MANTEL   
					2 (51) MANTEL   
					Combustible Materials   
					Allowed In Shaded   
					Top View Of   
					Area “ Safe Zone”   
					Fireplace   
					12"   
					18   
					5"   
					(457)   
					45°   
					16   
					(406)   
					17"   
					14   
					TOP OF   
					APPLIANCE   
					(356)   
					12   
					(305)   
					Min. Distance   
					To Protected   
					Side Wall   
					8-1/4"   
					10   
					(254)   
					8 
					Side   
					Wall   
					(203)   
					Side   
					Wall   
					Min. Distance To   
					Unprotected Side Wall   
					14"   
					Figure 46   
					Figure 45   
					COLD CLIMATE INSULATION   
					For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is   
					especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line   
					holesandotheropeningsshouldbecaulkedorstuffedwithunfacedfiberglassinsulation. Incoldclimates,ifthefireplaceisbeinginstalledonacement   
					slab, a sheet of plywood or other raised platform can be placed underneath to prevent conducting cold up into the room. It also helps to sheetrock   
					inside surfaces and tape for maximum air tightness and caulk firestops.   
					INSTALLATION ACCESSORIES   
					Listed Secure Flex™Components   
					Listed Secure Vent™Components   
					Cat.   
					No.   
					Model   
					No.   
					Description   
					Cat.No.   
					Model No. Description   
					**94L10 SV4.5HTSS Horizontal Small Square   
					Termination with   
					10K81 SFMP   
					Mil Pac Black Hi-Temperature   
					Sealant   
					t 
					n 
					a 
					l 
					a 
					e 
					S 
					Firestop/Spacer (96K80)   
					and Adapter (74L61)   
					89L40 SFMP-12 Mil Pac Black Hi-Temperature   
					Sealant - Bulk Pack 12   
					91L66 SF-GC4-6 Gear Clamp 4.5in. (114 mm) for   
					**98L27 SV4.5HTSSL Horizontal Small Square-   
					Long Termination with   
					Flex (6 pieces)   
					91L67 SF-GC7-6 Gear Clamp 7.5 in. (190.5 mm)   
					for Flex (6 pieces)   
					Firestop/Spacer (96K80)   
					and Adapter (74L61)   
					H2248   
					SF4.5HF Firestop/Spacer - 10 Pack   
					**May be used with 30" and 35" models only.   
					Horizontal (3-1-1 spacing)   
					H2249   
					SF4.5VF Firestop/Spacer - 10 Pack   
					Vertical (1-1-1 spacing)   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					26   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION ACCESSORIES CONTINUED   
					Listed Secure Vent™Components   
					Model No. Description   
					Listed Secure Flex™Components   
					Cat.   
					No.   
					Model   
					No.   
					Cat.No.   
					Description   
					H1968   
					SV4.5HT-2 Horizontal Square Termination   
					with Firestop/Spacer (96K80)   
					and Adapter (74L61)   
					These termination kits include firestop/spacer, gear clamps and flex adapter.   
					H1969 SF4.5HT-2 Horizontal Square Termination   
					without Flex   
					77L87 SFKIT12   
					77L88 SFKIT18   
					77L89 SFKIT24   
					77L90 SFKIT36   
					77L91 SFKIT48   
					56L74 SFVT30   
					Flex Square Term. with 12 in.   
					(305 mm of *compressed Flex   
					Flex Square Term. with 18 in.   
					(457 mm) of *compressed Flex   
					Flex Square Term. with 24 in.   
					(610 mm) of *compressed Flex   
					Flex Square Term. with 36 in.   
					(914 mm) of *compressed Flex   
					Flex Square Term. with 48 in.   
					(1219 mm) of *compressed Flex   
					Vertical Termin. for Flex (flat to   
					6/12) with Flex Adapter, section   
					of rigid vent, roof support collar   
					assembly, roof flashing and   
					storm collar.   
					H2152   
					SV4.5CGV-1 Vertical Termination   
					H4687   
					H4716   
					SV4.5CTS Chase Top Term. Square   
					SV4.5CTS-B Chase Top Term. Square, Blk   
					H4717 SV4.5CTS-TC Terra Cotta Termination   
					77L70   
					SV4.5L6 6 inch (152 mm) Vent Section   
					12 inch (305 mm) Vent   
					Section   
					77L71   
					SV4.5L12   
					24 inch (610 mm) Vent   
					Section   
					77L72   
					77L73   
					77L74   
					SV4.5L24   
					36 inch (914 mm) Vent   
					Section   
					SV4.5L36   
					48 inch (1219 mm) Vent   
					SV4.5L48   
					Section   
					56L75 SFVT45   
					Vertical Termin. for Flex (6/12 to   
					12/12) with Flex Adapter section   
					of rigid vent, roof support collar   
					assembly, roof flashing and   
					storm collar.   
					77L75   
					77L76   
					SV4.5LA Telescopic Section   
					SV4.5E45 45 Degree Elbow   
					60L10 SF-18   
					98K03 SF-12   
					18 ft. (5.49 m) *compressed Flex   
					12 ft.(3.66 m) *compressed Flex   
					77L77   
					SV4.5E90 90 Degree Elbow   
					Cat. No. Model No. Description   
					These termination kits include firestop/spacer, gear clamps and flex adapter.   
					The following flashings come packaged with a storm collar.   
					77L78   
					77L79   
					77L80   
					77L81   
					SV4.5F Flat Roof Flashing   
					**94L09 SF-HTSS   
					Horizontal Small Square   
					Termination without Flex   
					SV4.5FA 1/12 to 7/12 Adjust. Flashing   
					SV4.5FB 7/12 to 12/12 Adjust. Flashing   
					SV4.5SC6 Storm Collars (6 collars/box)   
					**94L04 SFKIT12SS Flex Small Square Term. with   
					12 in. (305 mm of   
					*compressed Flex   
					**94L05 SFKIT18SS Flex Small Square Term. with   
					H6183   
					H6184   
					H2247   
					96K93   
					SV4.5HF5 Firestop/Spacer Horizontal   
					(5-1-1 spacing)   
					SF4.5HF5 Firestop/Spacer Flex Horizontal   
					(5-1-1 spacing)   
					SV4.5VF Firestop/Spacer - 10 Pack   
					Vertical (1-1-1 spacing)   
					SV4.5SU Support Strap   
					18 in. (457 mm) of   
					*compressed Flex   
					**94L06 SFKIT24SS Flex Small Square Term. with   
					24 in. (610 mm) of   
					*compressed Flex   
					**94L07 SFKIT36SS Flex Small Square Term. with   
					36 in. (914 mm) of   
					*compressed Flex   
					**94L08 SFKIT48SS Flex Small Square Term. with   
					96K94   
					SV4.5RSA Attic Insulation Shield   
					SV4.5SP Support Plate   
					48 in. (1219 mm ) of   
					*compressed Flex   
					96K92   
					87L02   
					Cat. No. Model No. Description   
					H1988 CTSA-33   
					H1985 CTSO-33   
					H1987 CTSO-44   
					H1986 CTSO-46   
					H5820 4.5HTSK   
					Chase Top Shroud Kit,   
					Arch Top 3 x 3   
					Chase Top Shroud Kit,   
					Open Top 3 x 3   
					Chase Top Shroud Kit,   
					Open Top 4 x 4   
					Chase Top Shroud Kit,   
					Open Top 4 x 6   
					SV4.5 Termination Guard   
					HGS   
					99L03 SV4.5HRK36 Horizontal Riser Kit 36"   
					99L02 SV4.5HRK14 Horizontal Riser Kit 14"   
					Termnation Shroud Kit   
					*All compressed flex vents can be expanded up to two times.   
					**May be used with 30" and 35" models only.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					27   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				GAS CONVERSION KITS   
					WARNING: THIS CONVERSION KIT SHALL BE   
					AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION   
					INSTALLED BY A QUALIFIED SERVICE AGENCY IN SERAINSTALLÉPARUNEAGENCEQUALIFIÉEDESERVICE   
					ACCORDANCE WITH THE MANUFACTURER'S IN- CONFORMÉMENTAUXINSTRUCTIONSDUFABRICANTET   
					STRUCTIONS AND ALL APPLICABLE CODES AND   
					TOUTES EXIGENCES ET CODES APPLICABLES DE   
					REQUIREMENTS OF THE AUTHORIZED HAVING L'AUTORISÉSAVOIRLAJURIDICTION. SIL'INFORMATION   
					JURISDICTION. IF THE INFORMATION IN THESE DANS CETTE INSTRUCTION N'EST PAS SUIVIE   
					INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A   
					EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE   
					FIRE, EXPLOSION OR PRODUCTION OF CARBON PROTOXYDEDECARBONEPEUTRÉSULTERLEDOMMAGES   
					MONOXIDE MAY RESULT CAUSING PROPERTY CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE   
					DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.   
					PERSONNELLEDEVIE. L'AGENCEQUALIFIÉEDESERVICE   
					THE INSTALLATION IS NOT PROPER AND COM- EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET   
					PLETEUNTILTHEOPERATIONOFTHECONVERTED ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET   
					APPLIANCE IS CHECKED AS SPECIFIED IN THE   
					COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL   
					OWNERINSTRUCTIONSSUPPLIEDWITHTHEKIT. CONVERTIESTCHÉQUESUIVANTLESCRITÈRESÉTABLIS   
					THE QUALIFIED SERVICE AGENCY PERFORMING DANS LES INSTRUCTIONS DE PROPRIÉTAIRE   
					THIS INSTALLATION ASSUMES RESPONSIBILITY   
					FOR THIS CONVERSION.   
					PROVISIONNÉES AVEC L'ÉQUIPEMENT.   
					In Canada:   
					Millivolt Appliances   
					Step 4. SIT Systems - Refer to Figure 48 on   
					Natural To Propane Gas Conversion Kit   
					Models No. Unit Type Catalog No.   
					THE CONVERSION SHALL BE CARRIED OUT   
					INACCORDANCEWITHTHEREQUIREMENTS   
					OF THE PROVINCIAL AUTHORITIES HAVING   
					JURISDICTION AND IN ACCORDANCE WITH   
					THE REQUIREMENTS OF THE CAN1-B149.1   
					AND .2 INSTALLATION CODE.   
					page 29 and the instructions provided with   
					the kit. Using a Torx T20, remove and discard   
					thethreepressureregulatormountingscrews.   
					Remove the pressure regulator, spring, pop-   
					pet, diaphragm and bushing. Discard all   
					removed components.   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					millivolt   
					millivolt   
					H6163   
					H6975   
					H6177   
					85L69   
					H6166   
					H6973   
					H6168   
					H6169   
					millivolt   
					millivolt   
					LA CONVERSION DEVRA ÊTRE EFFECTUÉE   
					CONFORMÉMENT AUX RECOMMANDATIONS   
					DES AUTORITÉS PROVINCIALES AYANT   
					JURIDICTION ET CONFORMÉMENT AUX   
					EXIGENCES DU CODE D'INSTALLATION CAN1-   
					B149.1 ET.2.   
					electronic   
					electronic   
					electronic   
					electrnoic   
					Ensure the rubber gasket installed on the back   
					of the replacement pressure regulator is prop-   
					erly positioned and install the new pressure   
					regulator using the new screws supplied with   
					the kit. Tighten screws to 25 In. lb. torque.   
					Gas conversion kits are available to adapt your   
					appliance from the use of one type of gas to the   
					useofanother. Thesekitscontainalltheneces-   
					sary components needed to complete the task   
					including labeling that must be affixed to en-   
					sure safe operation.   
					Burner Assembly   
					Propane to Natural Gas Conversion Kit   
					Model No.   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					MPLDV30   
					MPLDV35   
					MPLDV40   
					MPLDV45   
					Unit Type Catalog No.   
					millivolt   
					millivolt   
					H6165   
					H6968   
					85L59   
					85L62   
					H6170   
					H6974   
					H6172   
					H6173   
					millivolt   
					Kitpartnumbersarelistedhere andthefollowing   
					steps detail the conversion procedure.   
					Orifice   
					Gas Valve   
					millivolt   
					Assembly   
					electronic   
					electronic   
					electronic   
					electronic   
					Step 1. Turn off the gas supply to the appliance.   
					Step 2. Carefully remove the logs. Exercise   
					care so as not to break the logs.   
					Step 3. Refer to Figure 47.   
					Remove the burner assembly with attached   
					venturi tube.   
					Air Adjustment   
					Arm   
					Figure 47   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					28   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Pressure-Tap   
					(Inlet)   
					Pilot Stage   
					Terminal   
					Pilot Gas   
					Outlet   
					Pressure   
					Regulator   
					Ground   
					(TP)   
					P I L O T   
					HI   
					LO   
					Supply   
					Gas Inlet   
					Remove   
					These   
					Components   
					Gas Outlet   
					To Burner   
					Figure 48   
					Step 5. Attach manometer to the manifold   
					side pressure test fitting and verify manifold   
					pressurereads3.5incheswatercolumn(0.87   
					kPa) for natural gas, and 10.0 inches water   
					column (2.49 kPa) for propane gas.   
					Burner Stage   
					Terminal   
					Regulator   
					Mounting Screw   
					Pressure-Tap   
					(Manifold)   
					Figure 50   
					Step 6. Refer to Figure 49 and remove the   
					pilot hood assembly to access the hexed pilot   
					orifice. Remove and replace the orifice with   
					the one provided with the kit.   
					ELECTRONIC   
					Orifice size   
					Model No.   
					Sensor   
					Ignitor   
					Pilot   
					Hood   
					Natural Propane   
					#61   
					0.070"   
					MPLDV-30   
					MPLDV-35   
					MPLDV-40   
					MPLDV-45   
					(0.039")   
					#45   
					0.048"   
					(0.082")   
					#41   
					#54   
					(0.046") (0.055")   
					Pilot   
					Orifice   
					#40   
					#53   
					(0.098") (0.595")   
					Figure 49   
					Note: If the ignitor is damaged, a replacement   
					kit is available, order Catalog Number 87L54.   
					Electronic Appliances   
					Figure 51   
					Step 7. Dexen Electronic Valves -   
					Figure 52   
					See Figure 50 and the instructions provided   
					with the kit. Remove and discard the two   
					pressure regulator mounting screws. Re-   
					move the pressure regulator and diaphragm.   
					Discard all removed components. Ensure the   
					provided diaphragm is installed properly onto   
					thereplacement pressureregulator andinstall   
					the new pressure regulator using the new   
					screws supplied with the kit. Tighten screws.   
					All Models   
					Step 9. Reassemble the remaining compo-   
					nents by reversing the procedures outlined in   
					theprecedingsteps. Usepipejointcompound   
					orTeflontapeonallpipefittingsbeforeinstall-   
					ing (ensure propane resistant compounds are   
					used in propane applications, do not use pipe   
					joint compounds on flare fittings).   
					Step 8. (Refer to Figure 47 on page 28 )   
					A. Remove the orifice from the manifold and   
					replace it with the one provided in the kit. See   
					the following table for orifice sizes for natural   
					andpropanemodels. Figure52 illustratesthe   
					orifice.   
					See Figure 51 and replace the pilot orifice   
					as follows: Remove pilot hood assembly to   
					access the phillipped pilot orifice. Remove   
					and replace the orifice with the one pro-   
					vided with the kit. Exercise extreme care   
					to prevent damage to or breakage of the   
					ignitor assembly.   
					B. Retrievetheburnerandslidetheventuritube   
					over the orifice. Set the shutter adjusting   
					opening as shown in Figure 43, page 25.   
					Step 10. Attach the conversion label provided   
					in the conversion kit to the rating plate on the   
					appliance.   
					Step 11. Turn on gas supply and test for gas   
					leaks.   
					NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.   
					29   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.   
					30   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.   
					31   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.   
					Consult your local distributor for fireplace code information.   
					Printed in U.S.A. © 2007 by Lennox Hearth Products   
					1110 West Taft Avenue • Orange, CA 92865   
					P/N 850,043M REV. E 06/2008   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |