LG Electronics Furnace 395CAV User Manual

installation instructions  
395CAV  
Series G  
and operating instructions  
UPFLOW GAS-FIRED  
INDUCED-COMBUSTION FURNACES  
Cancels: II 395C-40-9  
II 395C-40-10  
1-96  
NOTE: Read the entire instruction manual before starting the  
installation.  
This symbol indicates a change since the last issue.  
CANADIAN GAS ASSOCIATION  
Index  
Page  
ama  
®
A PPROVED  
R
SAFETY CONSIDERATIONS.....................................................1  
Clearances From Combustible Materials.................................1  
Dimensional Drawing...............................................................2  
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS  
PROCEDURE........................................................................2-3  
INTRODUCTION..........................................................................3  
LOCATION....................................................................................3  
General ......................................................................................3  
Location Relative to Cooling Equipment ................................3  
Hazardous Locations.................................................................3  
AIR FOR COMBUSTION AND VENTILATION...................3-5  
Unconfined Space.....................................................................4  
Confined Space......................................................................4-5  
FILTER ARRANGEMENT .......................................................5-6  
LEVELING LEGS (IF REQUIRED).........................................5-6  
GAS PIPING...............................................................................6-7  
ELECTRICAL CONNECTIONS ..................................................7  
115-v Wiring.............................................................................7  
24-v Wiring...............................................................................7  
Accessories................................................................................7  
VENTING ......................................................................................7  
START-UP, ADJUSTMENT, AND SAFETY CHECK.........7-14  
General...................................................................................7-8  
Sequence Of Operation .......................................................8-11  
Heating Mode............................................................................9  
Cooling Mode......................................................................9-11  
Continuous Blower Mode.......................................................11  
Heat Pump Mode....................................................................11  
Start-Up Procedures................................................................11  
Adjustments .......................................................................11-14  
Set Gas Input Rate ............................................................11-13  
Set Temperature Rise..............................................................13  
Set Thermostat Heat Anticipator............................................14  
Check Safety Controls .................................................................14  
Checklist.......................................................................................14  
and .2-M95 Natural Gas and Propane Installation Codes (NSC-  
NGPIC). Wear safety glasses and work gloves. Have fire extin-  
guisher available during start-up and adjustment procedures and  
service calls.  
.
Recognize safety information. This is the safety-alert symbol  
When you see this symbol on the furnace and in instructions or  
manuals, be alert to the potential for personal injury.  
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies a hazard which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage.  
These instructions cover minimum requirements and conform to  
existing national standards and safety codes. In some instances,  
these instructions exceed certain local codes and ordinances,  
especially those that may not have kept up with changing residen-  
tial construction practices. We require these instructions as a  
minimum for a safe installation.  
TABLE 1—MINIMUM CLEARANCES FROM  
COMBUSTIBLE MATERIALS (IN.)  
UNIT SIZE  
045 AND 070 091-155  
Sides  
Single-Wall Vent  
1
0
0
0
Type B-1 Double-Wall Vent  
Back  
Plenum Top  
Vent  
0
0
1
1
Single-Wall Vent  
6
6
Type B-1 Double-Wall Vent  
Single-Wall Vent  
1
1
Front  
6
6
Type B-1 Double-Wall Vent  
Service  
3
3
30  
30  
SAFETY CONSIDERATIONS  
NOTES:  
Installing and servicing heating equipment can be hazardous due to  
gas and electrical components. Only trained and qualified person-  
nel should install, repair, or service heating equipment.  
1. Provide 30-in. front clearance for servicing. An open door in front of the unit  
can meet this requirement.  
2. A minimum clearance of 3 in. must be provided in front of the unit for  
combustion air and proper operation.  
Untrained personnel can perform basic maintenance functions  
such as cleaning and replacing air filters. All other operations must  
be performed by trained service personnel. When working on  
heating equipment, observe precautions in the literature, on tags,  
and on labels attached to or shipped with the unit and other safety  
precautions that may apply.  
Follow all safety codes. In the United States, follow all safety  
codes including the National Fuel Gas Code (NFGC) NFPA No.  
54-1992/ANSI Z223.1-1992. In Canada, refer to the current  
edition of the National Standard of Canada CAN/CGA-B149.1-  
—1—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. If you touch ungrounded objects (recharge your body with  
static electricity), firmly touch furnace again before touch-  
ing control or wires.  
I. LOCATION  
A. General  
5. Use this procedure for installed and uninstalled (un-  
grounded) furnaces.  
CAUTION: Do not install furnace in a corrosive or  
contaminated atmosphere. Make sure all combustion and  
circulating air requirements are met, in addition to all  
local codes and ordinances.  
6. Before removing a new control from its container, dis-  
charge your body’s electrostatic charge to ground to protect  
the control from damage. If the control is to be installed in  
a furnace, follow items 1 through 5 before bringing the  
control or yourself into contact with the furnace. Put all  
used AND new controls into containers before touching  
ungrounded objects.  
CAUTION: Do not use this furnace during construction  
when adhesives, sealers, and/or new carpets are being  
installed. If the furnace is required during construction,  
use clean outside air for combustion and ventilation.  
Compounds of chlorine and fluorine when burned with  
combustion air form acids which cause corrosion of the  
heat exchangers and metal vent system. Some of these  
compounds are found in paneling and dry wall adhesives,  
paints, thinners, masonry cleaning materials, and many  
other solvents commonly used in the construction pro-  
cess.  
7. An ESD service kit (available from commercial sources)  
may also be used to prevent ESD damage.  
INTRODUCTION  
The Model 395CAV, Series G Furnace is available in sizes 45,000  
through 155,000 Btuh input capacities.  
The design of the upflow gas-fired furnace is A.G.A./C.G.A.  
certified for natural and propane gas and for installation on  
combustible flooring, in alcoves, attics, basements, closets, or  
utility rooms. The design of this furnace line is not A.G.A./C.G.A.  
certified for installation in mobile homes, recreation vehicles, or  
outdoors.  
Before installing the furnace, refer to the current edition of the  
NFGC. Canadian installations must be installed in accordance with  
NSCNGPIC and all authorities having jurisdiction. For further  
information, the NFGC is available from National Fire Protection  
Association Inc., Batterymarch Park, Quincy, MA 02269; Ameri-  
can Gas Association, 1515 Wilson Boulevard, Arlington, VA  
22209; or from Literature Distribution.  
Excessive exposure to contaminated combustion air will  
result in safety and performance related problems.  
This furnace must be installed so the electrical components are  
protected from water. This furnace shall not be installed directly on  
carpeting, tile, or any combustible material other than wood  
flooring.  
Locate furnace as close to the chimney/vent and as near the center  
of the air distribution system as possible. The furnace should be  
installed as level as possible.  
When a furnace is installed so that the supply ducts carry air to  
areas outside the space containing the furnace, the return air must  
also be handled by a duct(s) sealed to the furnace casing and  
terminating outside the space containing the furnace.  
Installation must conform to the regulations of the serving gas  
supplier and the local building, heating, and plumbing codes in  
effect in the area in which the installation is made, or in the  
absence of local codes with the requirements of the NFGC.  
Provide ample space for servicing and cleaning. Always comply  
with the minimum fire protection clearances shown on the unit  
rating plate.  
CAUTION: Application of this furnace should be in-  
doors with special attention given to vent sizing and  
material, gas input rate, air temperature rise, and unit  
sizing. Improper installation or misapplication of the  
furnace can require excessive servicing or cause prema-  
ture component failure.  
B. Location Relative to Cooling Equipment  
The cooling coil must be installed parallel with or on the  
downstream side of the unit to avoid condensation in the heat  
exchangers. When installed parallel with a furnace, dampers or  
other means used to control the flow of air must prevent chilled air  
from entering the unit. If the dampers are manually operated, they  
must be equipped with means to prevent operation of either unit  
unless the damper is in the full-heat or full-cool position.  
This furnace is designed for a minimum continuous return-air  
temperature of 60°F db or an intermittent operation down to 55°F  
db such as when used with a night setback thermostat. Return-air  
temperature must not exceed a maximum of 85°F db.  
C. Hazardous Locations  
WARNING: Improper installation, adjustment, alter-  
ation, service, maintenance, or use can cause carbon  
monoxide poisoning, explosion, fire, electrical shock, or  
other conditions which may cause personal injury or  
property damage. Consult a qualified installer, service  
agency, local gas supplier, or your distributor or branch  
for information or assistance. The qualified installer or  
agency must use only factory-authorized and listed kits or  
accessories when modifying this product. Failure to  
follow this warning can cause electrical shock, fire,  
personal injury, or death.  
When the furnace is installed in a residential garage, it must be  
installed so that the burners and ignition source are located at least  
18 in. above the floor. The furnace should be protected from  
physical damage by vehicles. When a furnace is installed in public  
garages, airplane hangars, or other buildings having hazardous  
atmospheres, the unit must be installed in accordance with the  
recommended good practice requirements of the National Fire  
Protection Association, Inc.  
II. AIR FOR COMBUSTION AND VENTILATION  
Provisions for adequate combustion and ventilation air must be  
provided in accordance with Section 5.3 of the NFGC, Air for  
Combustion and Ventilation, or applicable provisions of the local  
building codes.  
For accessory installation details, refer to the applicable instruction  
literature.  
NOTE: Remove all shipping brackets and materials before  
operating the furnace.  
Canadian installations must be installed in accordance with NSC-  
NGPIC and all authorities having jurisdiction.  
—3—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: Air for combustion must not be contami-  
nated by halogen compounds, which include fluoride,  
chloride, bromide, and iodide. These elements are found  
in aerosol sprays, detergents, bleaches, cleaning solvents,  
salts, air fresheners, and other household products.  
SUPPLY  
AIR  
VENT THROUGH ROOF  
All fuel-burning equipment must be supplied with air for combus-  
tion of the fuel. Sufficient air MUST be provided to ensure there  
will not be a negative pressure in the equipment room or space. In  
addition, a positive seal MUST be made between the furnace  
cabinet and the return-air duct to prevent pulling air from the  
burner area and draft safeguard opening.  
12MAX  
1 SQ IN.  
PER 1000  
BTUH IN DOOR  
*
OR WALL  
CAUTION: The operation of exhaust fans, kitchen ven-  
tilation fans, clothes dryers, or fireplaces could create a  
NEGATIVE PRESSURE CONDITION at the furnace.  
Make-up air MUST BE PROVIDED for the ventilation  
devices, in addition to that required by the furnace.  
UNCONFINED  
SPACE  
INTERIOR  
HEATED  
SPACE  
6MIN  
(FRONT) †  
1 SQ IN.  
PER 1000  
The requirements for combustion and ventilation air depend upon  
whether the furnace is located in an unconfined or confined space.  
BTUH IN DOOR  
*
OR WALL  
A. Unconfined Space  
An unconfined space must have at least 50 cubic ft for each 1000  
Btuh of input for all the appliances (such as furnaces, clothes  
dryer, water heaters, etc.) in the space.  
12MAX  
RETURN AIR  
For Example:  
395CAV FURNACE  
INPUT BTUH  
MINIMUM SQ FT WITH  
7-1/2 FT CEILING  
* Minimum opening size is 100 square in. with  
minimum dimensions of 3-In.  
Minimum of 3-In. when type-B1 vent is used.  
44,000  
66,000  
293  
440  
587  
733  
880  
1026  
88,000  
A89012  
110,000  
132,000  
154,000  
Fig. 2—Air For Combustion and Ventilation (Inside Air)  
For Example:  
395CAV FURNACE  
INPUT BTUH  
FREE AREA PER OPENING  
(SQ IN.)  
If the unconfined space is constructed unusually tight, air for  
combustion and ventilation MUST come from either the outdoors  
or spaces freely communicating with the outdoors. Combustion  
and ventilation openings must be sized the same as for a confined  
space. A minimum opening with a total of at least 1 sq in. per 5000  
Btuh of total input rating for all equipment must be provided.  
Return air must not be taken from the room unless an equal or  
greater amount of air is supplied to the room.  
44,000  
66,000  
100  
100  
100  
110  
132  
154  
88,000  
110,000  
132,000  
154,000  
B. Confined Space  
b. If the building is constructed unusually tight, a perma-  
nent opening directly communicating with the outdoors  
should be provided. This opening shall have a minimum  
free area of 1 sq in. per 5000 Btuh of total input rating  
for all equipment in the enclosure.  
A confined space has volume less than 50 cu ft per 1000 Btuh of  
the total input rating for all appliances installed in that space. A  
confined space MUST have 2 permanent openings, 1 within 12 in.  
of the ceiling and the other within 12 in. of the floor. (See Fig. 2.)  
NOTE: In determining the free area of an opening, the blocking  
effect of the louvers, grilles, and screens must be considered. If the  
free area of a louver or grille design is unknown, it may be  
assumed that wood louvers have a 20 percent free area, and metal  
louvers or grilles have a 60 percent free area. Screens, when used,  
must not be smaller than 1/4-in. mesh. Louvers and grilles must be  
constructed so they cannot be closed.  
c. If the furnace is installed on a raised platform to provide  
a return-air plenum, and return air is taken directly from  
the hallway or space adjacent to the furnace, all air for  
combustion must come from outdoors.  
2. All air from outside the structure:  
a. If combustion air is taken from outdoors through vertical  
ducts, the openings and ducts MUST have at least 1 sq  
in. of free area per 4000 Btuh of the total input for all  
equipment within the confined space. (See Fig. 3.)  
The size of the openings depends upon whether the air comes from  
inside or outside of the structure.  
1. All air from inside the structure:  
b. If combustion air is taken from the outdoors through  
horizontal ducts, the openings and ducts MUST have at  
least 1 sq in. of free area per 2000 Btuh of the total input  
for all equipment within the confined space.  
a. Each opening MUST have at least 1 sq in. of free area  
per 1000 Btuh of the total input for all equipment within  
the confined space, but not less than 100 sq in. per  
opening. (See Fig. 2.)  
—4—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Example:  
WARNING: Do not install the furnace on its back;  
safety control operation will be adversely affected. Never  
connect return-air ducts to the back of the furnace. A  
failure to follow this warning can cause a fire, personal  
injury, or death.  
395CAV FURNACE FREE AREA PER OPENING ROUND PIPE  
INPUT BTUH  
(SQ IN.)  
(IN. DIA)  
44,000  
11.0  
4
5
6
6
7
7
66,000  
16.5  
88,000  
22.0  
110,000  
132,000  
154,000  
27.5  
33.0  
III. FILTER ARRANGEMENT  
38.5  
The factory-supplied filter(s) is shipped in the blower compart-  
ment. Determine location for the filter and relocate filter retaining  
wire if necessary. See Fig. 4 for side return application and Fig. 5  
for bottom return application. See Table 3 to determine correct  
filter size for desired filter location. Table 3 indicates filter size,  
location, and quantity shipped with the furnace.  
For Example:  
395CAV FURNACE FREE AREA PER OPENING ROUND PIPE  
INPUT BTUH  
(SQ IN.)  
(IN. DIA)  
44,000  
22.0  
6
7
WASHABLE  
FILTER  
66,000  
33.0  
88,000  
44.0  
8
110,000  
132,000  
154,000  
55.0  
9
66.0  
10  
10  
FILTER  
RETAINER  
77.0  
c. When ducts are used, they must be of the same cross-  
sectional area as the free area of the openings to which  
they connect. The minimum dimension of rectangular  
ducts must not be less than 3 in. (See Fig. 3.)  
1 SQ IN.  
PER 4000  
DUCTS  
BTUH*  
TO  
OUTDOORS  
A93045  
Fig. 4—Side Filter Arrangement  
(Control Removed for Clarity)  
For bottom air-return applications, filter may need to be cut to fit  
some furnace casing widths. A bottom closure panel is factory  
installed in the bottom of the furnace. When bottom return inlet is  
desired, remove and discard the bottom closure panel. Remove  
side clip(s) and install in hole. Two sets of hardware are needed for  
furnaces in 24-1/2-in. wide casings using 2 filters for bottom  
return. All hardware is provided for filter installation.  
12MAX  
1 SQ IN.  
PER 2000  
BTUH*  
D
12″  
MAX  
VENT  
A
THROUGH  
ROOF  
F
SUPPLY  
AIR  
1 SQ IN.  
PER  
4000  
BTUH*  
NOTE: Furnaces with a 17-1/2-in. wide casing require an addi-  
tional procedure when locating the filter for bottom return-air  
application. Field fabricate a sheet metal filler strip 1 X 3 X 24-1/2  
in. and install it along side of the filter as shown in Fig. 5. Drive  
2 screws through the casing side and into the filler strip to secure  
it in place. Filter should rest on the top of the filler strip when  
installed.  
DUCTS  
TO  
OUTDOORS  
1 SQ IN.  
PER  
4000  
BTUH*  
1 SQ IN.  
PER 2000  
BTUH*  
WARNING: Never operate unit without a filter or with  
filter access door removed. Failure to follow this warning  
can cause fire, personal injury, or death.  
E
G
B
12″  
MAX  
12MAX  
C
12MAX  
IV. LEVELING LEGS (IF REQUIRED)  
When the furnace is used with side inlet(s) and leveling legs are  
required, refer to Fig. 6, and install field-supplied, corrosion-  
resistant 5/16-in. machine bolts and nuts.  
RETURN AIR  
DUCT  
TO  
OUTDOORS  
1 SQ IN.  
PER 4000  
BTUH*  
NOTE: The maximum length of the bolt should not exceed 1-1/2  
in.  
*Minimum dimensions of 3-In.  
NOTE: Use any of the following  
1. Lay furnace on its back. Locate and drill 5/16-in. diameter  
hole in each bottom corner of furnace as shown in Fig. 6.  
combinations of openings:  
A & B C & D D & E F & G  
2. Install nut on bolt and install bolt and nut in hole. (Install  
flat washer if desired.)  
A89013  
Fig. 3—Air For Combustion and Ventilation  
(Outside Air)  
3. Install another nut on other side of furnace base. (Install flat  
washer if desired.)  
—5—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2412-IN. WIDE  
516″  
1712-IN. WIDE  
CASINGS ONLY:  
CUT AND FOLD  
CASINGS ONLY:  
INSTALL FIELD-SUPPLIED  
FILTER FILLER STRIP  
UNDER FILTER.  
FACTORY-PROVIDED  
FILTERS AS SHOWN  
TO DESIRED SIZE.  
516″  
1 34″  
3  
1
24 / ″  
2
1 34″  
1″  
516″  
516″  
1 34″  
1 34″  
A89014  
Fig. 6—Leveling Leg Installation  
TABLE 4—MAXIMUM CAPACITY OF PIPE*  
NOMINAL IRON INTERNAL  
LENGTH OF PIPE (FT)  
PIPE SIZE  
(IN.)  
DIAMETER  
(IN.)  
WASHABLE  
FILTER  
10  
20  
30  
97  
40  
82  
50  
73  
1/2  
3/4  
0.622  
0.824  
1.049  
1.380  
1.610  
175  
360  
680  
120  
250  
465  
200 170 151  
375 320 285  
770 660 580  
1
1-1/4  
1-1/2  
1400 950  
2100 1460 1180 990 900  
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a  
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table  
10-2 NFPA 54-1992.  
CAUTION: If a flexible connector is required or al-  
lowed by the authority having jurisdiction, black iron  
pipe shall be installed at the gas valve and extend a  
minimum of 2 in. outside the furnace casing.  
FILTER  
RETAINER  
FILTER  
SUPPORT  
A96030  
Fig. 5—Bottom Filter Arrangement  
(Control Removed for Clarity)  
Piping should be pressure tested in accordance with local and  
national plumbing and gas codes before the furnace has been  
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas  
supply pipe must be disconnected from the furnace and capped  
before the pressure test. If the test pressure is equal to or less than  
0.5 psig (14-in. wc), turn off electric shutoff switch located on the  
gas valve before the test. It is recommended that the ground joint  
union be loosened before pressure testing. After all connections  
have been made, purge the lines and check for leakage with  
regulated gas supply pressure.  
TABLE 3—FILTER INFORMATION (IN.)  
FILTER SIZE*  
Side Return Bottom Return  
FURNACE  
CASING WIDTH  
FILTER TYPE  
14-3/16  
17-1/2  
21  
(1) 16 X 25 X 1† (1) 14 X 25 X 1  
(1) 16 X 25 X 1† (1) 16 X 25 X 1  
(1) 16 X 25 X 1 (1) 20 X 25 X 1†  
(2) 16 X 25 X 1† (1) 24 X 25 X 1  
Cleanable  
Cleanable  
Cleanable  
Cleanable  
24-1/2  
* Filters can be field modified by cutting the frame as marked and folding to the  
desired size. Alternate sizes can be ordered from your distributor or dealer.  
† Factory-provided with the furnace.  
Install a sediment trap in the riser leading to the furnace. The trap  
can be installed by connecting a tee to the riser leading from the  
furnace. Connect a capped nipple into the lower end of the tee. The  
capped nipple should extend below the level of the gas controls.  
(See Fig. 7.)  
Apply joint compound (pipe dope) sparingly and only to the male  
threads of each joint. The compound must be resistant to the action  
of propane gas.  
4. Adjust outside nut to provide desired height, and tighten  
inside nut to secure arrangement.  
V. GAS PIPING  
An accessible manual shutoff valve MUST be installed upstream  
of the furnace gas controls and within 72 in. of the furnace. A  
1/8-in. NPT plugged tapping, accessible for test gage connection,  
MUST be installed immediately upstream of the gas supply  
connection to the furnace and downstream of the manual shutoff  
valve. Place ground joint union between the gas control manifold  
and the manual shutoff valve.  
Gas piping must be installed in accordance with national and local  
codes. Refer to the current edition of the NFGC. Canadian  
installations must be installed in accordance with NSCNGPIC and  
all authorities having jurisdiction.  
Refer to Table 4 for the recommended gas pipe size. Risers must  
be used to connect to the furnace and the meter.  
—6—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS  
WARNING: The cabinet MUST have an uninterrupted  
or unbroken ground according to NEC, ANSI/NFPA  
70-1996 and Canadian Electrical Code, CSA C22.1 or  
local codes to minimize personal injury if an electrical  
fault should occur. This may consist of electrical wire or  
conduit approved for electrical ground when installed in  
accordance with existing electrical codes. Do not use gas  
piping as an electrical ground. Failure to follow this  
warning could result in electrical shock, fire, or death.  
SUPPLY  
MANUAL  
SHUTOFF  
VALVE  
(REQUIRED)  
The auxiliary junction box (J-box) can be moved to the left-hand  
side of the furnace when a left-side power supply is desired.  
Remove the 2 screws holding the auxiliary J-box. Mount the J-box  
on the left-hand side of the furnace (holes have been pre-drilled in  
casing). When moved, tuck the wiring harness behind the clip  
provided to keep extra wire lengths out of the way.  
SEDIMENT  
TRAP  
UNION  
NOTE: Proper polarity must be maintained for 115-v wiring. If  
polarity is incorrect, control board fault code indicator light will  
flash rapidly and the furnace will not operate.  
B. 24-v Wiring  
Make field 24-v connections at the 24-v terminal strip. (See Fig.  
9.) Connect terminal Y as shown in Fig. 8 for proper cooling  
operation. Use only AWG No. 18, color-coded, copper thermostat  
wire.  
A89417  
Fig. 7—Typical Gas Pipe Arrangement  
The 24-v circuit contains an automotive-type, 3-amp fuse located  
on the main control board. Any direct shorts during installation,  
service, or maintenance could cause this fuse to blow. If fuse  
replacement is required, use ONLY a 3-amp fuse of identical size.  
WARNING: Use the proper length of pipes to avoid  
stress on the gas control manifold. Failure to follow this  
warning can result in a gas leak, causing fire, explosion,  
personal injury, or death.  
C. Accessories  
1. Electronic Air Cleaner (EAC)  
Two spring clamp terminals (for 12 gage maximum, solid  
or stranded wire), marked EAC-1 and EAC-2 are provided  
for EAC connection. (See Fig. 9.) These terminals are  
energized with 115-v, (1-amp maximum) during blower  
motor operation. To connect EAC power leads to furnace  
control center, strip approximately 1/8 in. of insulation from  
wire. Open terminal by depressing switch arm with a  
screwdriver or finger, and insert wire as shown in Fig. 10.  
CAUTION: Connect the gas pipe to the furnace using a  
backup wrench to avoid damaging gas controls.  
WARNING: Never purge a line into a combustion  
chamber. Never use matches, candles, flame, or other  
sources of ignition for the purpose of checking leakage.  
Use a soap-and-water solution to check for leakage.  
Failure to follow this warning can cause a fire, explosion,  
personal injury, or death.  
2. Humidifier (HUM)  
Screw terminals (HUM and Com) are provided for 24-v  
humidifier connection. The terminals are energized with  
24-v 0.5-amp maximum after inducer motor prepurge  
period.  
NOTE: A field-supplied, 115-v controlled relay connected to  
EAC terminals may be added if humidifier operation is desired  
during blower operation.  
VI. ELECTRICAL CONNECTIONS  
A. 115-v Wiring  
VII. VENTING  
Refer to the National or Local Installation Code such as; National  
Fuel Gas Code Z223.1-1992, or the Canadian Installation Code,  
CAN B149.1- and .2-M95, for proper vent sizing and installation  
requirements. Use the enclosed Venting Tables for Category I  
Fan-Assisted Furnaces for a quick, easy reference. The horizontal  
portion of the venting system shall maintain a minimum of 1/4-in.  
upward slope per linear ft and it shall be rigidly supported every 5  
ft or less with hangers or straps to ensure that there will be no  
movement after installation.  
Refer to the unit rating plate or Table 5 for equipment electrical  
requirements. The control system requires an earth ground for  
proper operation.  
CAUTION: Do not connect aluminum wire between  
disconnect switch and furnace. Use only copper wire.  
Make all electrical connections in accordance with the National  
Electrical Code (NEC) ANSI/NFPA 70-1996 and local codes or  
ordinances that might apply. For Canadian installations, all elec-  
trical connections must be made in accordance with CSA C22.1  
Canadian Electrical Code, or authorities having jurisdiction.  
VIII. START-UP, ADJUSTMENT, AND SAFETY CHECK  
A. General  
NOTE: Proper polarity must be maintained for 115-v wiring. If  
polarity is incorrect, control board fault indicator light will flash  
rapidly and furnace will not operate.  
—7—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-VOLT WIRING  
FIELD 115-, 208/230-, 460-VOLT WIRING  
FACTORY 24-VOLT WIRING  
FACTORY 115-VOLT WIRING  
NOTE 2  
THERMOSTAT  
TERMINALS  
W
C
R
G
Y
FIVE  
WIRE  
FIELD-SUPPLIED  
FUSED DISCONNECT  
THREE-WIRE  
HEATING-  
ONLY  
208/230- OR  
460-VOLT  
THREE  
PHASE  
W
R
BLK  
BLK  
WHT  
WHT  
208/230-  
VOLT  
SINGLE  
PHASE  
GND  
GND  
G
AUXILIARY  
J-BOX  
115-VOLT FIELD-  
SUPPLIED  
FUSED  
DISCONNECT  
C
Y
GND  
NOTE 1  
CONTROL  
CONDENSING  
UNIT  
BOX  
TWO  
WIRE  
24-VOLT  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y-terminal as shown for proper operation.  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced, use  
same type or equivalent wire.  
FURNACE  
A95241  
Fig. 8—Heating and Cooling Application Wiring Diagram  
TABLE 5—ELECTRICAL DATA  
OPERATING  
MAXIMUM  
VOLTS—  
HERTZ—  
PHASE  
MAXIMUM  
MINIMUM  
MAXIMUM  
WIRE LENGTH (FT)‡  
FUSE OR  
HACR-TYPE CKT  
BKR AMPS†  
VOLTAGE RANGE  
Maximum* Minimum*  
127 104  
UNIT SIZE  
UNIT AMPS  
WIRE GAGE  
024045  
036045  
024070  
036070  
042091  
048091  
036110  
048111  
060111  
048135  
060135  
060155  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
115—60—1  
6.0  
8.3  
14  
14  
14  
14  
14  
14  
14  
14  
12  
14  
12  
12  
47  
34  
47  
32  
31  
27  
35  
28  
31  
28  
33  
31  
15  
15  
15  
15  
15  
15  
15  
15  
20  
15  
20  
20  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
5.9  
8.7  
9.0  
10.4  
8.0  
10.1  
14.4  
10.1  
13.3  
14.0  
* Permissible limits of the voltage range at which the unit operates satisfactorily.  
† Time-delay fuse is recommended.  
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.  
The furnace must have a 115-v power supply properly connected  
and grounded. Proper polarity must be maintained for correct  
operation. Thermostat wire connections at R, W, C, and Y must be  
made at the 24-v terminal block on the control board. The gas  
service pressure must not exceed 0.5 psig (14-in. wc), but must be  
no less than 0.16 psig (4.5-in. wc).  
The blower compartment door must be in place to complete the  
115-v circuit to the furnace.  
B. Sequence of Operation  
CAUTION: Furnace control must be grounded for  
proper operation, or control will lockout. Control is  
grounded through green wire routed to gas valve and  
burner bracket screw.  
CAUTION: This furnace is equipped with a manual  
reset limit switch or fuse link in the gas control area. The  
switch or fuse link opens and shuts off power to the gas  
valve if a flame rollout or overheating condition occurs in  
the gas control area. DO NOT bypass the switch. Correct  
inadequate combustion air supply problem and reset the  
switch or replace the fuse link.  
Using the schematic diagram shown in Fig. 11, follow the  
sequence of operation through the different modes. Read and  
follow the wiring diagram very carefully.  
NOTE: If there is a power interruption and any thermostat call,  
the control initiates a 90-sec blower only on period before starting  
another cycle.  
Before operating the furnace, check each manual reset switch for  
continuity. If necessary, press the button to reset the switch.  
—8—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER OFF DELAY  
ADJUSTMENT SWITCH  
24V THERMOSTAT  
TERMINALS  
G
R
Y
W
Com  
24V  
TEST/TWIN  
HUMIDIFIER TERMINAL  
(24-VAC 0.5 AMP MAX)  
HUM  
LED OPERATION &  
DIAGNOSTIC LIGHT  
HARNESS CONNECTOR  
SEC-1  
24V TRANSFORMER SEC-2  
SPARE 1  
3-AMP FUSE  
COOL  
HEAT  
BLOWER SPEED  
SELECTION TERMINALS  
SPARE 2  
EAC 1 (BLACK)  
EAC-ELECTRONIC AIR CLEANER  
TERMINALS (115-VAC 1.5 AMP MAX)  
115-VAC (L1)  
POWER  
EAC 2 (WHITE)  
115-VAC (L2) NEUTRAL  
CONNECTION  
SUPPLY  
HOT SURFACE  
INDUCER MOTOR  
CONNECTOR  
IGNITOR  
CONNECTOR  
A93052  
Fig. 9—Control Board  
d. HUM terminal is energized with the gas valve. See  
accessories in the Electrical Connections section.  
e. Flame-sensing—When burner flame is sensed, the con-  
trol begins the blower on delay period and continues  
holding the gas valve open. If burner flame is not sensed,  
the control closes the gas valve and repeats ignition  
cycle.  
NOTE: Ignition sequence will repeat 3 additional time before a  
lockout occurs. Lockout automatically resets after 3 hrs, or can be  
manually reset by turning 115v off (not at thermostat) for 3 sec  
minimum, then on again.  
f. Blower on delay—Forty sec after burner flame is proven,  
the blower motor is energized on heating speed. Simul-  
taneously, the humidifier and electronic air cleaner  
terminals (HUM and Com for humidifier, EAC-1 and  
EAC-2 for electronic air cleaner) are energized. If jumper  
is on pin 6 and pin 9, blower on delay is 60 sec.  
A93053  
Fig. 10—EAC Terminals on Control Board  
1. Heating mode  
g. Blower off delay—When the thermostat is satisfied, the  
circuit between R-W is broken, de-energizing the gas  
valve stopping gas flow to the burners. The blower  
motor and EAC remain energized 90, 135, 180, or 225  
sec (depending on the blower off-time selection). The  
furnace is factory set for a 135-sec blower off delay.  
When the wall thermostat "calls for heat," the R-W circuit  
closes. The furnace control performs a self-check, verifies  
the pressure switch contacts are open, and starts inducer  
motor.  
a. Prepurge period—As the inducer motor comes up to  
speed, the pressure switch contacts close to begin a  
15-sec prepurge period.  
h. Post-purge—The inducer motor remains energized 5 sec  
after the burners are extinguished. If jumper is on pin 6  
and pin 9, the post-purge period is 15 sec.  
b. Ignitor warm-up—At the end of the prepurge period, the  
ignitor is energized for a 17-sec ignitor warm-up period.  
c. Ignition sequence—When the ignitor warm-up period is  
completed, the gas valve opens, permitting gas flow to  
the burners where it is ignited. After 5 sec, the ignitor is  
de-energized and a 2-sec flame-sensing period begins.  
2. Cooling mode  
When the thermostat "calls for cooling," R-G and R-Y  
circuits close. The R-Y circuit starts the outdoor condensing  
—9—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A N T R  
P M 5 A 1 .  
W H T  
W H T  
K
K
B L  
B L  
K
B L  
—10—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
unit and the combined R-Y and R-G circuits start the  
furnace blower motor on cooling speed. The EAC-1 termi-  
nal is energized with 115v when the blower is operating on  
cooling speed.  
This feature helps diagnose a system problem in case of a  
component failure. To initiate component test procedure,  
short (jumper) the TEST 1/4-in. quick connect terminal on  
control board (adjacent to diagnostic light) and the Com  
terminal on thermostat connection block for approximately  
2 sec. (See Fig. 9.)  
When the thermostat is satisfied, R-G and R-Y circuits are  
broken. The furnace blower and EAC continue operating on  
cooling speed for an additional 90 sec.  
NOTE: Component test feature will not operate if any thermostat  
signal is present at control board.  
3. Continuous blower mode  
Component test sequence is as follows.  
NOTE: EAC-1 terminal is energized with 115v whenever blower  
operates.  
a. Momentarily jumper TEST and Com terminals until  
LED goes off.  
When the R-G circuit is made, the blower motor operates on  
heating speed. During a call for heat, the blower stops,  
allowing the furnace heat exchangers to heat up more  
quickly, then restarts at the end of the 40-sec blower on  
delay period. If jumper is on pin 6 and pin 9, the blower on  
delay is 60 sec.  
b. LED will display previous fault 4 times.  
c. Inducer motor operates for 10 sec, then stops.  
d. Hot surface ignitor is energized for 15 sec, then de-  
energized.  
e. Blower motor operates on cooling speed for 10 sec, then  
stops.  
The blower reverts to continuous operation after the heating  
cycle is completed.  
f. Blower motor operates on heating speed for 10 sec, then  
stops.  
When the thermostat "calls for cooling," the blower oper-  
ates on cooling speed. When the thermostat is satisfied, the  
blower operates an additional 90 sec before reverting back  
to continuous operation on heating speed.  
3. To operate furnace, follow procedures on operating instruc-  
tions label attached to furnace.  
4. Heat pump mode  
4. With furnace operating, set thermostat below room tem-  
perature and observe that furnace goes off. Set thermostat  
above room temperature and observe that furnace restarts.  
When installed with a heat pump, the furnace control  
automatically changes the timing sequence to avoid long  
blower off time during demand defrost cycles. When the  
W-Y or W-Y-G thermostat inputs are received at the same  
time, the control changes the blower to heating speed or  
starts the blower if it was off, and begins a heating cycle.  
The blower remains on until the end of the prepurge period,  
then shuts off until the end of the ignition warm-up and trial  
for ignition periods (a total of 24 sec). The blower then  
comes back on at heating speed.  
D. Adjustments  
1. Set gas input rate.  
There are 2 methods of adjusting the gas input rate. The  
preferred method is by using Table 6 and following the  
instructions in item a. The second method is by clocking the  
gas meter and using the instructions in item b.  
The gas valve regulator has been nominally set at 3.5-in. wc  
for natural gas. When adjusting input rate, do not set  
manifold pressure above 3.8-in. wc or below 3.2-in. wc.  
When the W input signal disappears, the control begins the  
normal inducer post-purge period and the blower changes to  
cooling speed after a 1-sec delay. If the W-Y-G signals  
disappear at the same time, the blower remains on for the  
selected heating blower off delay period and the inducer  
goes through its normal post-purge period. If the W-Y  
inputs should disappear, leaving the G signal input, the  
control goes into continuous blower and the inducer re-  
mains on for the normal post-purge period.  
a. Check gas input rate using Table 6.  
(1.) Obtain average yearly heat value for local gas  
supply.  
(2.) Obtain average yearly specific gravity for local gas  
supply.  
(3.) Verify furnace model. Table 6 can only be used for  
model 395CAV Furnaces.  
Anytime the control senses false flame, the control locks  
out of the heating mode. This occurs because the control  
cannot sense the W input due to the false flame signal, and  
as a result, sees only the Y input and goes into cooling  
mode, blower off delay. All other control functions remain  
in standard format.  
(4.) Check and verify orifice size in furnace. NEVER  
ASSUME THE ORIFICE SIZE. ALWAYS  
CHECK AND VERIFY.  
(5.) Find natural gas heat value and specific gravity in  
Table 6.  
NOTE: EAC-1 terminal is energized whenever blower operates.  
HUM terminal is only energized when gas valve is energized  
(6.) Follow heat value and specific gravity lines to point  
of intersection. Find orifice size and manifold pres-  
sure settings for proper operation at given natural  
gas conditions.  
C. Start-up Procedures  
1. Purge gas lines—After all connections have been made,  
purge the lines and check for leaks.  
EXAMPLE:  
Heat value 1070  
Btu/cu ft specific gravity 0.58  
Therefore; Orifice No. 44*  
WARNING: Never purge a line into a combustion  
chamber. Never use matches, candles, flame, or other  
sources of ignition for the purpose of checking leakage.  
Use a soap-and-water solution to check for leakage.  
Failure to follow this warning can cause fire, explosion,  
personal injury, or death.  
Manifold pressure 3.3-in. wc  
*The furnace is shipped with No. 43 orifices.  
Therefore, in this example all main burner orifices must be  
changed and manifold pressure must be adjusted.  
2. Component test—The furnace control board allows all  
components, except gas valve, to be run for a short period  
of time.  
(7.) Proceed to item c to adjust manifold pressure.  
—11—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 6—MODEL 395CAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT RATE  
(Tabulated Data Based on Altitude Up to 2000 Ft and 22,000 Btuh Per Burner)  
SPECIFIC GRAVITY OF NATURAL GAS  
GAS  
HEAT  
0.56  
0.58  
0.60  
0.62  
0.64  
0.66  
0.68  
0.70  
0.72  
VALUE  
(BTU/CU FT)  
Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld Orf Mnfld  
No. Press. No. Press. No. Press. No. Press. No. Press. No. Press. No. Press. No. Press. No. Press.  
41  
42  
3.2  
3.6  
41  
42  
3.3  
3.7  
41  
42  
40  
3.4  
3.8  
3.2  
41  
40  
3.5  
3.3  
41  
39  
40  
3.7  
3.2  
3.4  
41  
39  
40  
3.8  
3.3  
3.5  
39  
40  
3.4  
3.6  
38  
39  
40  
3.2  
3.5  
3.7  
38  
39  
40  
3.3  
3.6  
3.8  
860  
875  
890  
905  
42  
3.4  
41  
42  
3.2  
3.6  
41  
42  
3.3  
3.7  
41  
42  
40  
3.4  
3.8  
3.2  
41  
40  
3.5  
3.3  
41  
39  
40  
3.6  
3.2  
3.4  
41  
39  
40  
3.8  
3.3  
3.5  
39  
40  
3.3  
3.6  
38  
39  
40  
3.2  
3.4  
3.7  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.6  
41  
42  
3.3  
3.7  
41  
42  
3.4  
3.8  
41  
40  
3.5  
3.2  
41  
40  
3.6  
3.3  
41  
39  
40  
3.7  
3.2  
3.4  
41  
39  
40  
3.8  
3.3  
3.5  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.6  
41  
42  
3.3  
3.7  
41  
42  
3.4  
3.8  
41  
40  
3.5  
3.2  
41  
40  
3.6  
3.3  
41  
39  
40  
3.7  
3.2  
3.4  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.5  
41  
42  
3.3  
3.7  
41  
42  
3.4  
3.8  
41  
40  
3.5  
3.2  
41  
40  
3.6  
3.3  
920  
935  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.5  
41  
42  
3.3  
3.7  
41  
42  
3.4  
3.8  
41  
40  
3.5  
3.2  
43  
3.6  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.5  
41  
42  
3.3  
3.6  
41  
42  
3.4  
3.7  
950  
43  
3.4  
43  
3.6  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.5  
41  
42  
3.3  
3.6  
965  
44  
43  
3.8  
3.3  
42  
3.5  
43  
3.6  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
41  
42  
3.2  
3.5  
980  
44  
43  
3.7  
3.2  
44  
43  
3.8  
3.4  
43  
3.5  
43  
3.6  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
42  
3.4  
995  
44  
3.6  
44  
43  
3.7  
3.3  
44  
43  
3.8  
3.4  
43  
3.5  
43  
3.6  
43  
3.7  
43  
3.8  
42  
3.2  
42  
3.3  
1010  
1025  
1040  
1055  
1070  
1085  
1100  
44  
3.5  
44  
43  
3.6  
3.2  
44  
43  
3.7  
3.3  
43  
3.4  
43  
3.5  
43  
3.6  
43  
3.7  
43  
3.8  
43  
3.2  
44  
3.4  
44  
3.5  
44  
43  
3.6  
3.2  
44  
43  
3.7  
3.3  
43  
3.4  
43  
3.5  
43  
3.6  
43  
3.7  
43  
3.8  
44  
3.3  
44  
3.4  
44  
3.5  
44  
43  
3.6  
3.2  
44  
43  
3.8  
3.3  
43  
3.4  
43  
3.5  
43  
3.6  
43  
3.7  
44  
3.2  
44  
3.3  
44  
3.4  
44  
3.5  
44  
43  
3.7  
3.2  
44  
43  
3.8  
3.3  
43  
3.4  
43  
3.5  
43  
3.6  
45  
3.8  
44  
3.2  
44  
3.3  
44  
3.4  
44  
3.6  
44  
43  
3.7  
2.3  
44  
43  
3.8  
3.3  
43  
3.4  
43  
3.5  
45  
3.7  
45  
3.8  
3.4  
44  
3.2  
44  
3.4  
44  
3.5  
44  
3.6  
44  
43  
3.7  
3.2  
44  
43  
3.8  
3.3  
43  
3.4  
b. Check gas input rate by clocking gas meter.  
EXAMPLE:  
(1.) Obtain average yearly heat value for local gas  
supply.  
Btu heating input = Btu/cu ft X cu ft/hr  
Heating value of gas = 1070 Btu/cu ft  
Time for 1 revolution of 2 cu ft dial = 72 sec  
Gas rate = 100 X 1070 = 107,000 Btuh  
(2.) Check and verify orifice size in furnace. NEVER  
ASSUME THE ORIFICE SIZE. ALWAYS  
CHECK AND VERIFY.  
(8.) Measured gas input should not exceed gas input on  
unit rating plate.  
CAUTION: DO NOT redrill burner orifices. Improper  
drilling (burrs, out of round, etc.) can cause excessive  
burner operating noise and misdirection of burner flames.  
This could result in flame impingement on burners and  
heat exchanger surfaces, leading to potential failures.  
(9.) Proceed to item c to adjust manifold pressure.  
c. Adjust gas input.  
(1.) Remove regulator adjustment seal cap. (See Fig.  
12.)  
(3.) Turn off all other gas appliances and pilots.  
(4.) Start furnace and let run for 3 minutes.  
(2.) Turn adjusting screw counterclockwise to decrease  
input. Turn screw clockwise to increase input. DO  
NOT set manifold pressure less than 3.2-in. wc or  
more than 3.8-in. wc for natural gas. Make any  
major adjustments by changing main burner ori-  
fices.  
(5.) Measure time (in sec) for gas meter to complete 1  
revolution.  
(6.) Refer to Table 7 for cu ft of gas per hr.  
(7.) Multiply gas rate (cu ft/hr) by heating value (Btu/cu  
ft).  
—12—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 7—GAS RATE CU FT/HR  
BURNER FLAME  
SIZE OF  
TEST DIAL  
SIZE OF  
TEST DIAL  
BURNER  
SECONDS  
FOR 1  
REVOLUTION  
SECONDS  
FOR 1  
REVOLUTION  
1
2
5
1
2
5
cu ft cu ft cu ft  
360 720 1800  
327 655 1636  
300 600 1500  
277 555 1385  
257 514 1286  
240 480 1200  
225 450 1125  
212 424 1059  
200 400 100  
189 379 947  
180 360 900  
171 343 857  
164 327 818  
157 313 783  
150 300 750  
144 288 720  
138 277 692  
133 267 667  
129 257 643  
124 248 621  
120 240 600  
116 232 581  
113 225 563  
109 218 545  
106 212 529  
103 206 514  
100 200 500  
cu ft cu ft cu ft  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
98  
100  
102  
104  
106  
108  
72  
71  
69  
68  
67  
65  
64  
63  
62  
61  
60  
58  
56  
54  
53  
51  
50  
48  
47  
46  
45  
44  
43  
42  
41  
40  
39  
38  
38  
37  
36  
35  
35  
34  
33  
144 360  
141 355  
138 346  
136 340  
133 333  
131 327  
129 321  
126 316  
124 310  
122 305  
120 300  
116 290  
112 281  
109 273  
106 265  
103 257  
100 250  
MANIFOLD  
Fig. 13—Burner Flame  
A89020  
97  
95  
92  
90  
88  
86  
84  
82  
80  
78  
76  
75  
74  
72  
71  
69  
68  
67  
243  
237  
231  
225  
220  
214  
209  
205  
200  
196  
192  
188  
184  
180  
178  
173  
170  
167  
e. Canadian installations only—The Canadian ratings are  
approved for altitudes up to 2000 ft for natural and  
propane gases. High-altitude ratings are from 2000 ft to  
4500 ft above sea level. See Table 8 for nominal burner  
orifice size. High-altitude rating includes a 10 percent  
derate as required by Canadian standards.  
97  
95  
92  
90  
88  
86  
84  
82  
80  
78  
76  
75  
73  
195 486  
189 474  
185 462  
180 450  
176 439  
172 429  
167 419  
164 409  
160 400  
157 391  
153 383  
150 375  
147 367  
TABLE 8—CANADIAN ORIFICE SIZE  
SEA LEVEL  
0—2000 FT  
HIGH ALTITUDE  
2000—4500 FT  
GAS  
Natural  
43  
54  
44  
55  
Propane  
110  
112  
116  
120  
33  
32  
31  
30  
65  
64  
62  
60  
164  
161  
155  
150  
2. Set temperature rise.  
Furnace must operate within range of temperature rise  
specified on the unit rating plate. Determine the air tem-  
perature rise as follows.  
(3.) When correct input is obtained, replace regulator  
seal cap. Main burner flame should be clear blue,  
almost transparent. (See Fig. 13.)  
a. Place duct thermometers in return and supply ducts as  
near furnace as possible. Be sure thermometers do not  
"see" heat exchangers so that radiant heat will not affect  
thermometer readings. This is particularly important  
with straight-run ducts.  
ON AND  
OFF SWITCH  
GAS  
b. When thermometer readings stabilize, subtract return-air  
temperature from supply-air temperature to determine  
temperature rise.  
PRESSURE  
REGULATOR  
ADJUSTMENT  
c. Adjust air temperature rise by adjusting blower speed.  
Increase blower speed to reduce temperature rise. De-  
crease blower speed to increase temperature rise.  
WARNING: Disconnect the electrical power before  
changing the speed tap. A failure to follow this warning  
can cause personal injury.  
INLET  
PRESSURE TAP  
MANIFOLD  
PRESSURE TAP  
d. To change blower motor speed selections for heating  
mode, remove blower motor lead from control board  
HEAT terminal. (See Fig. 11.) Select desired blower  
motor speed lead from 1 of the other terminals and  
relocate it to HEAT terminal. See Table 9 for lead color  
identification. Reconnect original lead on SPARE termi-  
nal.  
A95618  
Fig. 12—Redundant Automatic Gas Control Valve  
d. High altitude—In the United States gas input on rating  
plate is for altitudes up to 2000 ft. Ratings for altitudes  
over 2000 ft must be 4 percent less for each 1000 ft  
above sea level. To obtain the adjusted altitude rating,  
adjust the manifold pressure (see item c) and replace the  
main burner orifices as needed. Refer to National Fuel  
Gas Code Appendix F, Table F-4 for proper orifice  
sizing at high altitudes.  
CAUTION: Recheck temperature rise. It must be within  
limits specified on unit rating plate. Recommended op-  
eration is at midpoint of rise or above.  
—13—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 9—SPEED SELECTOR  
The preferred method of checking the limit control is to  
gradually block off the return air after the furnace has been  
operating for a period of at least 5 minutes. As soon as the  
limit has shut off the burners, the return-air opening should  
be unblocked. By using this method to check the limit  
control, it can be established that the limit is functioning  
properly and operates if there is a motor failure.  
FACTORY-  
ATTACHED TO  
COLOR  
Black  
SPEED  
High  
Cool  
Yellow (When  
present)  
Medium-High  
Spare  
Blue  
Red  
Medium-Low  
Low  
Heat  
Spare  
COM  
2. Check draft safeguard switch.  
White  
Common  
The purpose of this control is to permit the safe shutdown  
of the furnace during certain blocked vent conditions.  
3. Set thermostat heat anticipator.  
a. Disconnect power to furnace and remove vent connector  
from furnace outlet collar. Be sure to allow time for vent  
pipe to cool down before removing.  
The thermostat heat anticipator must be set to match the  
amp draw of the electrical components in the R-W circuit.  
Accurate amp draw readings can be obtained at thermostat  
subbase terminals R and W. Fig. 14 illustrates an easy  
method of obtaining the actual amp draw. The amp reading  
should be taken after the blower motor has started. See the  
thermostat manufacturer’s instructions for adjusting the  
heat anticipator and for varying the heating cycle length.  
b. Restore power to furnace and set room thermostat above  
room temperature.  
c. After normal start-up, allow furnace to operate for 2  
minutes, then block flue outlet 100 percent. Furnace  
should cycle off within 2 minutes.  
d. Remove blockage and reconnect vent pipe to furnace  
outlet collar.  
NOTE: When using an electronic thermostat, set the cycle rate for  
3 cycles per hr.  
e. Wait 5 minutes and then reset draft safeguard switch.  
3. Check pressure switch.  
THERMOSTAT SUBBASE  
TERMINALS WITH  
THERMOSTAT REMOVED  
This control proves operation of draft inducer blower.  
a. Turn off 115-v power to furnace.  
HOOK-AROUND  
VOLT/AMMETER  
b. Remove control door and disconnect inducer motor lead  
wires from wire harness.  
R
Y
W
G
c. Turn on 115-v power to furnace.  
d. Set thermostat to "call for heat" and wait 1 minute. When  
pressure switch is functioning properly, hot surface  
ignitor should NOT glow and control center diagnostic  
light flashes a 31 fault. If hot surface ignitor glows when  
inducer motor is disconnected, shut down furnace im-  
mediately. Determine reason pressure switch did not  
function properly and correct condition.  
10 TURNS  
e. Turn off 115-v power to furnace.  
f. Reconnect inducer motor wires, replace control door, and  
turn on 115-v power.  
FROM UNIT 24-VOLT  
TERMINAL BLOCK  
5.0 AMPS ON AMMETER  
10 TURNS AROUND JAWS  
F. Checklist  
= 0.5 AMPS FOR THERMOSTAT SETTING  
EXAMPLE:  
1. Put away tools, instruments, and clean up debris.  
2. Verify manual reset switches have continuity.  
A80201  
Fig. 14—Amp Draw Check With Ammeter  
E. Check Safety Controls  
3. Ensure blower and control access doors are properly in-  
stalled.  
The flame sensor, gas valve, and pressure switch were all checked  
in the Start-up Procedures section as part of normal operation.  
4. Cycle test furnace with room thermostat.  
5. Check operation of accessories per manufacturer’s instruc-  
tions.  
1. Check primary limit control.  
This control shuts off the combustion control system and  
energizes the circulating-air blower motor if the furnace  
overheats.  
6. Review User’s Manual with owner.  
7. Leave literature packet near furnace.,  
—14—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your  
knowledge of the equipment discussed in this manual, including:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs is available, using popular  
video-based formats and materials. All include video and/or slides, plus companion  
book.  
Classroom Service Training plus "hands-on" the products in our labs can mean  
increased confidence that really pays dividends in faster troubleshooting, fewer  
callbacks. Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-962-9212  
[ ] Packaged Service Training  
[ ] Classroom Service Training  
A94328  
—15—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 1996 BDP Co. • P.O. Box 70 • Indianapolis, IN 46206  
Printed in U.S.A.  
395c4010  
Catalog No. BDP-3339-518  
—16—  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Leica Microscope Magnifier M125 B User Manual
Lexmark Flat Panel Television P N 18B0113 User Manual
LG Electronics Flat Panel Television 0910 REV04 User Manual
Logitech Video Game Keyboard K830 User Manual
Lopi Stove ASTM E 1509 95 User Manual
Magnavox DVD VCR Combo 1VMN26713A User Manual
Marshall electronic Computer Monitor QV171 HDSDI User Manual
M Audio Speaker BX5 User Manual
Melissa Styling Iron 235 012 User Manual
Memorex TV DVD Combo MVD2009CB User Manual