LG Electronics Air Conditioner A3UC363FA0LMU360CE User Manual |
LG
LG
Multi Type Air Conditioner
SERVICE MANUAL
MODEL
• Indoor Unit:
Room Type
Art Cool Type
AMNH093D4A0(LMN090HE)
AMNC093D4A0(LMN090CE)
AMNH123DEA0(LMN120HE)
AMNC123DEA0(LMN120CE)
AMNH093APM0(LMAN090HNS)
AMNC093APM0(LMAN090CNS)
AMNH123APM0(LMAN120HNS)
AMNC123APM0(LMAN120CNS)
• Outdoor Unit: A3UH363FA0(LMU360HE)
A3UC363FA0(LMU360CE)
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Download from Www.Somanuals.com. All Manuals Search And Download.
Model Number Nomenclature
Model Number Nomenclature
Indoor Unit
09
AMN
H
3
D
4
A
0
Serial Number
Function
A : Basic, L : Nano Plasma + Auto Clean(Wall Mounted)
C: Plasma(Ceiling Cassette), G: Low Static Motor
ART COOL(DELUXE) Type Front Panel Color
B : Blue, D : Wood, M : Metal, R : Mirror, W : White
Chassis Name
Indoor Unit Type
Wall mounted split
D : D- look type
M : M- look type
Artcool type
L : L- look type G : G- look type
N : N- look type
A : standard/wide type D : Deluxe type
B : Ceiling Concealed Duct
V : Ceiling & Floor(Convertible)
Electrical Rating
3: 1Ø, 208~230V, 60Hz
Nominal Cooling Capacity in Btu/h
Ex) 9,000 Btu/h '09', 12,000 Btu/h '12'
Model Type
H: Heat Pump C: Cooling Only
MPS Variable Multi System Indoor Unit
Outdoor Unit
A3U
H
36
3
F
A
0
Serial Number
Function
A : Basic
Multi Type
F : Free Joint Multi Type
Electrical Ratings
3: 1Ø, 208~230V, 60Hz
Nominal Cooling Capacity in Btu/h
Ex) 24,000 Btu/h '24', 36,000 Btu/h '36'
Model Type
H: Heat Pump C: Cooling Only
R-410A MPS Variable Multi System Outdoor Unit
And No. of Connectable Indoor Units
Ex) A3U : Connectable max. 2 Indoor Units
Service Manual 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Model Number Nomenclature
Combination table
Cooling
Heating
Combination(k Btu)
Operation
Capacity (Btu/h)
Total Unit-A Unit-B Unit-C Total
9000
12 12000
Capacity (Btu/h)
Unit-A Unit-B Unit-C Total
COP
Input Current EER
(W) (A) (Btu/h.w)
Input Current
(W)
(A)
A
9
B
C
(Btu/h.w) (w/w)
9
9000 1320
12000 1320
18000 2180
21000 2200
24000 2200
5.9
5.9
9.8
9.9
9.9
6.8
9.1
8.3
9.5
10.9
7.4
8.2
9.0
9.8
9000
9000
12000
18000
21000
24000
1550
1410
2160
2160
2160
7.0
5.8
8.5
1.7
2.5
2.4
2.8
3.3
1 UNIT
2 UNIT
12
9
12000
6.3
9.8
9.8
9.8
9
18
21
9000
9000
9000 9000
9000 12000
12000 12000
8.3
9
12
12
9
9000 12000
9.7
12
9
24 12000 12000
11.1
9
27
30
33
9000
9000
9000 9000 27000 3650 16.5
9000 12000 30000 3650 16.5
9000 9000
9000
27000
3300
3340
3340
3340
14.9
15.0
15.0
15.0
8.2
9.0
2.4
2.6
2.9
3.2
9
9
12
12
12
9000 9000 12000 30000
9000 12000 12000 33000
12000 12000 12000 36000
3 UNIT
9
12
12
9000 12000 12000 33000 3650 16.5
9.9
12
36 12000 12000 12000 36000 3680 16.6
10.8
Notes :
1.Cooling Capacity is based on : indoor temp. 26.7°C(80.1°F)DB, 19.4°C(66.9°F)WB; outdoor temp. 35°C(95°F)DB, 23.9°C(75°F)WB
2.Heating Capacity is based on : indoor temp. 21.1°C(70°F)DB, 15.6°C(60.1°F)WB; outdoor temp. 8.3°C(46.9°F)DB, 6.1°C(43°F)WB
3.The total ability of connected a indoor unit is up to 24k Btu/h
Symbols Used in this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the
air conditioner.
NOTICE
This symbol indicates special notes.
4 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
WARNING
CAUTION This symbol indicates the possibility of injury or damage to properties only.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
■ Installation
Do not use a defective or under-
rated circuit breaker. Use this
appliance on a dedicated circuit.
For electrical work, contact the
dealer, seller, a qualified electrician,
or an Authorized Service Center
Always ground the product.
.
• There is risk of fire or electric
shock.
• Do not disassemble or repair the
product. There is risk of fire or
electric shock.
• There is risk of fire or electric
shock.
Install the panel and the cover
of control box securely.
Always install a dedicated cir-
cuit and breaker.
Use the correctly rated break-
er or fuse.
• There is risk of fire or electric
shock.
• Improper wiring or installation may • There is risk of fire or electric
cause fire or electric shock shock.
Service Manual 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not modify or extend the
power cable.
Do not install, remove, or re-
install the unit by yourself
(customer).
Be cautious when unpacking
and installing the product.
• There is risk of fire or electric
• There is risk of fire, electric shock, • Sharp edges could cause injury.
shock.
explosion, or injury.
Be especially careful of the case
edges and the fins on the con-
denser and evaporator.
For installation, always con-
tact the dealer or an
Do not install the product on a Be sure the installation area
defective installation stand.
does not deteriorate with age.
Authorized Service Center.
• There is risk of fire, electric shock, • It may cause injury, accident, or
• If the base collapses, the air condi-
tioner could fall with it, causing
property damage, product failure,
and personal injury.
explosion, or injury.
damage to the product.
Do not let the air conditioner
run for a long time when the
humidity is very high and a
door or a window is left open.
Take care to ensure that
power cable could not be
pulled out or damaged during
operation.
Do not place anything on the
power cable.
• Moisture may condense and wet or • There is risk of fire or electric
• There is risk of fire or electric
damage furniture.
shock.
shock.
6 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not plug or unplug the
power supply plug during
operation.
Do not touch(operate) the
product with wet hands.
Do not place a heater or other
appliances near the power
cable.
• There is risk of fire or electric
• There is risk of fire or electrical
• There is risk of fire and electric
shock.
shock.
shock.
Do not allow water to run into
electric parts.
Do not store or use flammable Do not use the product in a
gas or combustibles near the
product.
tightly closed space for a long
time.
• It may cause There is risk of fire,
failure of the product, or electric
shock.
• There is risk of fire or failure of
product.
• Oxygen deficiency could occur.
Gasolin
When flammable gas leaks,
turn off the gas and open a
window for ventilation before
turn the product on.
If strange sounds, or small or
smoke comes from product.
Turn the breaker off or discon- If possible, remove the prod-
Stop operation and close the
window in storm or hurricane.
nect the power supply cable.
uct from the window before
the hurricane arrives.
• Do not use the telephone or turn
switches on or off. There is risk of
explosion or fire
• There is risk of electric shock or
fire.
• There is risk of property damage,
failure of product, or electric shock.
Service Manual 7
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not open the inlet grill of the product
during operation. (Do not touch the elec-
trostatic filter, if the unit is so equipped.)
When the product is soaked
(flooded or submerged), contact not enter the product.
an Authorized Service Center.
Be cautious that water could
• There is risk of physical injury,
• There is risk of fire or electric
• There is risk of fire, electric shock,
electric shock, or product failure.
shock.
or product damage.
Ventilate the product from time to time when
operating it together with a stove, etc.
Turn the main power off when cleaning or
maintaining the product.
• There is risk of fire or electric shock.
• There is risk of electric shock.
When the product is not be used for a long time, dis-
connect the power supply plug or turn off the breaker.
Take care to ensure that nobody could step on
or fall onto the outdoor unit.
• There is risk of product damage or failure, or unintend- • This could result in personal injury and product dam-
ed operation.
age.
CAUTION
■ Installation
Always check for gas (refrigerant) leak-
age after installation or repair of product.
Install the drain hose to ensure that
water is drained away properly.
Keep level even when
installing the product.
• Low refrigerant levels may cause
failure of product.
• A bad connection may cause water • To avoid vibration or water leak-
leakage. age.
90°
8 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not install the product
where the noise or hot air
from the outdoor unit could
damage the neighborhoods.
Use two or more people to lift
and transport the product.
Do not install the product
where it will be exposed to
sea wind (salt spray) directly.
• It may cause a problem for your
neighbors.
• Avoid personal injury.
• It may cause corrosion on the
product. Corrosion, particularly on
the condenser and evaporator fins,
could cause product malfunction or
inefficient operation.
■ Operational
Do not expose the skin directly to cool air for
long periods of time.
(Don't sit in the draft.)
Do not use the product for special purposes,
such as preserving foods, works of art, etc. It
is a consumer air conditioner, not a precision
refrigeration system.
• This could harm to your health.
• There is risk of damage or loss of property.
Do not block the inlet or outlet Use a soft cloth to clean. Do
Do not touch the metal parts of
the product when removing the
air filter. They are very sharp!
of air flow.
not use harsh detergents, sol-
vents, etc.
• It may cause product failure.
• There is risk of fire, electric shock, • There is risk of personal injury.
or damage to the plastic parts of
the product.
Service Manual 9
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Precautions
Do not step on or put anyting
on the product. (outdoor
units)
Always insert the filter secure- Do not insert hands or other
ly. Clean the filter every two
weeks or more often if neces-
sary.
objects through the air inlet or
outlet while the product is
operated.
• There is risk of personal injury and • A dirty filter reduces the efficiency
• There are sharp and moving parts
failure of product.
of the air conditioner and could
cause product malfunction or dam-
age.
that could cause personal injury.
Do not drink the water drained Use a firm stool or ladder
Replace the all batteries in the
remote control with new ones
of the same type. Do not mix
old and new batteries or dif-
ferent types of batteries.
from the product.
when cleaning or maintaining
the product.
• It is not sanitary and could cause
• Be careful and avoid personal
• There is risk of fire or explosion
serious health issues.
injury.
Do not recharge or disassemble the batteries.
Do not dispose of batteries in a fire.
If the liquid from the batteries gets onto your
skin or clothes, wash it well with clean water.
Do not use the remote if the batteries have
leaked.
• They may burn or explode.
• The chemicals in batteries could cause burns or other
health hazards.
10 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Dimensions
Indoor Unit
1. Split Type Indoor
2. Art Cool Type Indoor Unit
W
D
H
H
D
W
Pipe Hole
Hanger Hole
Fix Hole
Installation plate
Split Type
ARTCOOL Type
SP3
Model
S4
SE
Dimension
9 kBtu/h
840
12 kBtu/h
9 kBtu/h
12 kBtu/h
W
H
mm
mm
mm
895
282
165
570
568
129
270
D
153
Service Manual 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Outdoor Unit
W
Gas side
3-way valve
Liquid side
2-way valve
L9
L7
L6
L8
MODEL
UE2 36k
DIM
W
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
870
1038
320
360
340
25
H
D
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
1035
25
546
160
160
44
64.5
50
12 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Specifications
Product Specifications
Indoor Unit
Indoor Unit Type
Wall Mounted
Model
AMNC093D4A0(LMN090CE)
AMNH093D4A0(LMN090HE) AMNC123DEA0(LMN120CE) AMNH123DEA0(LMN120HE)
Nominal Cooling Capacity
Nominal Heating Capacity
Air Circulation
■
kcal/h(W)
Btu/h
2,267(2,637)
2,267(2,637)
9,000
3,023(3,516)
3,023(3,516)
12,000
9,000
12,000
■
kcal/h(W)
Btu/h
-
2,267(2,637)
9,000
-
3,023(3,516)
12,000
-
8.2(289)
-
9.4(332)
H/M/L
CMM(CFM)
°C
8.2(289)
9.4(332)
Setting temperature range(cool/heat)
18~30
16~30
18~30
16~30
Fan motor
Output
W
15
15
15
15
Model
DL-88430LGIF
DC36
DL-88430LGIF
DC36
DL-88430LGIF
DC36
DL-88430LGIF
DC36
Input
V
A
Running Current
Type
0.15
0.15
0.15
0.15
Fan
Cross Flow Fan
1/3.74(95)
31 / 29 / 22
Thermistor
0.197(5.0)
20
Cross Flow Fan
1/3.74(95)
31 / 29 / 22
Thermistor
0.197(5.0)
20
Cross Flow Fan
1/3.74(95)
36 / 32 / 29
Thermistor
0.197(5.0)
18
Cross Flow Fan
1/3.74(95)
36 / 32 / 29
Thermistor
0.197(5.0)
18
No. Used / Diameter
EA/inch(mm)
dBA
Noise Level (Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
inch(mm)
Fins per inch
No. of Rows & Column
2R,15C
2R,15C
2R,15C
2R,15C
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
l/h
-
1.1
-
1.2
inch(mm)
kg(lbs)
33.0*10.6*6.0(840*270*153)
7(15.4)
33.0*10.6*6.0(840*270*153)
7(15.4)
35.2*11.1*6.5(895*282*165)
9.5(20.9)
35.2*11.1*6.5(895*282*165)
9.5(20.9)
Piping Connection
Liquid
inch(mm)
inch(mm)
mm
1/4 (6.35)
3/8 (9.52)
20
1/4 (6.35)
3/8 (9.52)
20
1/4 (6.35)
3/8 (9.52)
20
1/4 (6.35)
3/8 (9.52)
20
Gas
Drain hose (ID Ø)
Packing Dimension (W*H*D)
inch(mm)
20/40ft(hi-c)
35.7*13.1*8.8(906*332*223)
440/910 (1091)
35.7*13.1*8.8(906*332*223)
440/910 (1091)
38.3*9.1*14.6(973*231*372)
353/719 (792)
38.3*9.1*14.6(973*231*372)
353/719 (792)
Stuffing Quantity
With(Without) S/Parts
Indoor Unit Type
Model
Artcool
AMNC093APM0(LMAN090CNS)
AMNH093APM0(LMAN090HNS)
AMNC123APM0(LMAN120CNS)
AMNH123APM0(LMAN120HNS)
Nominal Cooling Capacity
Nominal Heating Capacity
Air Circulation
■
kcal/h(W)
Btu/h
2,267(2,637)
2,267(2,637)
9,000
3,023(3,516)
3,023(3,516)
12,000
9,000
12,000
■
kcal/h(W)
Btu/h
-
2,267(2,637)
9,000
-
3,023(3,516)
12,000
-
7.5(264)
18~30
-
8.5(300)
18~30
H/M/L
CMM(CFM)
°C
7.5(264)
16~30
8.5(300)
16~30
Setting temperature range(cool/heat)
Fan motor
Output
W
24
24
24
24
Model
DL-89812LGIB
DL-89812LGIB
DL-89812LGIB
DL-89812LGIB
No. of Poles
Input
V
A
DC36
1.5
DC36
1.5
DC36
1.5
DC36
1.5
Running Current
Type
Fan
Turbo Fan
1/24.32(617.7)
37 / 31 / 27
Thermistor
0.197(5.0)
20
Turbo Fan
1/24.32(617.7)
37 / 31 / 27
Thermistor
0.197(5.0)
20
Turbo Fan
1/24.32(617.7)
43 / 39 / 31
Thermistor
0.197(5.0)
20
Turbo Fan
1/24.32(617.7)
43 / 39 / 31
Thermistor
0.197(5.0)
20
No. Used / Diameter
EA/inch(mm)
dBA
Noise Level (Sound Press,1m) H/M/L
Temperature controller
Coil
Tube Size (OD)
inch(mm)
Fins per inch
No. of Rows & Column
2R,20C
2R,20C
2R,20C
2R,20C
Dehumidification Rate
Dimensions (W*H*D)
Net Weight
l/h
-
1.1
-
1.4
inch(mm)
kg(lbs)
22.4*22.4*5.1(570*568*129)
9(19.84)
22.4*22.4*5.1(570*568*129)
9(19.84)
22.4*22.4*5.1(570*568*129)
9(19.84)
22.4*22.4*5.1(570*568*129)
9(19.84)
Piping Connection
Liquid
inch(mm)
inch(mm)
mm
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
Gas
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Drain hose (ID Ø)
20
20
20
20
Packing Dimension (W*H*D)
Stuffing Quantity With(Without) S/Parts
inch(mm)
20/40ft(hi-c)
26.2*25.7*9.1(665*653*231)
237/534(239/539)
26.2*25.7*9.1(665*653*231)
237/534(239/539)
26.2*25.7*9.1(665*653*231)
237/534(239/539)
26.2*25.7*9.1(665*653*231)
237/534(239/539)
Note : 1.
■
See the page "Combination Table"
2. Due to our policy of innovation some specifications may be changed without notification.
Service Manual 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Specifications
Outdoor Unit - Multiple piping models
A3UC363FA0(LMU360CE)
A3UH363FA0(LMU360HE)
Model
9,000~36,000
9,000~36,000
Cooling Capacity■
Btu/hr
W
2637~10,550
2637~10,550
2267~9071
2267~9071
kcal/hr
Btu/hr
W
-
9,000~36,000
Heating Capacity■
-
2637~10,550
-
2267~9071
kcal/hr
W
1320~3680
1320~3680
Input■
Cooling
Heating
Cooling
Heating
-
1410~3340
W
5.9~16.6
5.9~16.6
Running Current■(208/230V)
Power Supply
A
-
6.3~15.0
A
1,208/230,60
1,208/230,60
Ø,V,Hz
3
3
Max. Number of Connectable Indoor Units
Rotary
Rotary
Compressor
(Constant)
Type
GK141K
GK141K
Model
2 Pole Induction(PSC)
2 Pole Induction(PSC)
Motor Type
Quantity
1
1
Ea
W
1430
1430
Motor Input
Oil Charge
Oil Type
350Å}10
350Å}10
cc
FVC68D
FVC68D
35 / 370
35 / 370
Capacitor
µF/Vac
External Type
External Type
O.L.P Type(model name)
Type
Rotary
Rotary
Compressor
(Constant)
GJ230K
GJ230K
Model
2 Pole Induction(PSC)
2 Pole Induction(PSC)
Motor Type
Quantity
1
1
Ea
W
2370
2370
Motor Input
Oil Charge
Oil Type
700±10
7000±10
cc
FVC68D
FVC68D
50 / 400
50 / 400
Capacitor
µF/Vac
g(oz)
Internal Type
Internal Type
O.L.P Type(model name)
Charge
2400
2400
Refrigerant charge
Coil
R410A
R410A
Type
L.E.V
L.E.V
Control
0.276(7.0)
0.276(7.0)
Tube Size (OD)
Fins per inch
No. of Rows & Column/No.
Model
inch(mm)
18
18
2R,48C
2R,48C
ARC286B01 * 2
ARC286B01 * 2
Fan motor
Fan
102
102
Output
W
2/370
2/370
Capacitor
µF/Vac
Propeller
Propeller
Type
2 / 15.7(400)
2 / 15.7(400)
No. Used / Diameter
Discharge
Outdoor
EA/inch(mm)
Side / Top
Side
Side
63(2225)
63(2225)
Air Circulation
CMM(CFM)
51
51
Noise Level(H/L) at 230V Sound Press,1m
dB(A)
1
1/4 (6..35) * 3EA
1/4 (6..35) * 3EA
SVC Valve
Liquid
Gas
inch(mm)
3/8 (9.52) * 3EA
3/8 (9.52) * 3EA
34.3*41.7*12.6 (870*1060*320)
34.3*41.7*12.6 (870*1060*320)
Dimensions
Net Weight
W*H*D
Outdoor
inch(mm)
kg(lbs)
m
80(176)
80(176)
45
45
Max. Interunit Piping Length Total of Each Room
For One Room
15
15
m
7.5
7.5
Max. Installation
Height Difference
Packing Dimension
Stuffing Quantity
Indoor Unit~Outdoor Unit
Indoor Unit~Indoor Unit
W*H*D
m
7.5
41.1*44.9*17.3 (1045*1140*440)
51/111
7.5
41.1*44.9*17.3 (1045*1140*440)
51/111
m
inch(mm)
20/40ft
Notes: 1. Capacities are based on the following conditions:
Cooling: -Indoor Temperature 26.7°C(80.1°F)DB/19.4°C66.9°F)WB
-Outdoor Temperature 35°C(95°F)DB/23.9°C(75°F)WB
-Interconnecting Piping Length 7.5m
-Level Difference of Zero.
Heating: -Indoor Temperature 21.1°C(70°F)DB/15.6°C(60.1°F)WB
-Outdoor Temperature 8.3°C(46.94°F)DB/6.1°C(42.98°F)WB
-Interconnecting Piping Length 7.5m
-Level Difference of Zero.
2. Capacities are Net Capacities.
3.
■
: See the page "Combination Table"
4. Due to our policy of innovation some specifications may be changed without notification.
14 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installation
Read carefully, and then follow step by step.
Installation Parts
Installation plate
Type "A" screw and plastic anchor
Remote Control Holder
Type "B" screw
Installation Tools
Figure
Name
Figure
Name
Screw driver
Electric Drill
Ohmmeter
Hexagonal wrench
Measuring Tape, Knife
Hole Core Drill
Ammeter
Gas Leak Detector
Thermometer,
Level
Spanner
Torque wrench
Flaring Tool Set
Service Manual 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Select the best location
Indoor unit
1. Do not have any heat or steam near the unit.
More than 5cm
(2.0 inch)
2. Select a place where there are no obstacles in front
of the unit.
More than 5cm
(2.0 inch)
3. Make sure that condensation drainage can be conve-
niently routed away.
More than 2.3m
(90.6 inch)
4. Do not install near a doorway.
5. Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
More than 5cm
(2.0 inch)
6. Use a stud finder to locate studs to prevent unneces-
sary damage to the wall.
More than 10cm
More than 50cm
CAUTION: Install the indoor unit
on the wall where the height from
the floors more than 2.3m(7.5ft).
More than 50cm
More than 2m
Outdoor unit
1. If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat radia-
tion from the condenser is not restricted.
more than 30cm
(11.8 inch)
2. Ensure that the spaces indicated by arrows around
front, back and side of the unit.
more than 30cm
(11.8 inch)
3. Do not place animals and plants in the path of the
warm air.
4. Take the air conditioner weight into account and
select a place where noise and vibration are mini-
mum.
more than 70cm
(27.6 inch)
5. Select a place so that the warm air and sound from
the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be
sure to level the unit. Ensure the roof structure and
anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
16 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Piping length and elevation
Multi Piping Type
Max Elevation
between each
indoor unit and out-
door unit (h1)
Max total length of
all pipes
(A+B/A+B+C)
Max elevation
between indoor
units (h2)
Max length of each Min length of each
Capacity(Btu/h)
36k
pipe (A/B/C)
pipe (A/B/C)
45m(150ft)
15m(50ft)
3m(10ft)
7.5m(25ft)
7.5m(25ft)
Pipe Size
Indoor Capacity
(Btu/h)
Gas
Liquid
Standard Length
Additional Refrigerant
9K
3/8"
3/8"
1/4"
1/4"
7.5m(25ft)
7.5m(25ft)
20g/m(0.32oz/ft)
20g/m(0.32oz/ft)
12K
A
h2
h2
B
h1
C
h1
h1
CAUTION: Capacity is based on standard length and maximum allowance length is on the
basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).
Service Manual 17
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Fixing Installation Plate(Standard Type)
The wall you select should be strong and solid enough to
prevent vibration
Installation Plate
1. Mount the installation plate on the wall with
type "A" screws. If mounting the unit on a concrete wall,
use anchor bolts.
• Mount the installation plate horizontally by aligning the
centerline using a level.
Chassis
Hook
Type "A" screw
2. Measure the wall and mark the centerline. It is also
important to use caution concerning the location of the
installation plate-routing of the wiring to power outlets is
through the walls typically. Drilling the hole through the
wall for piping connections must be done safely.
Installation plate
B
Distance (mm)
D
CHASSIS
(Grade)
A
B
C
D
A
C
Ø70mm
Ø70mm
S4
SE
50
65
105
110
59
85
105
110
Left rear piping
Right rear piping
18 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Preparing work for Installation (Artcool Type Only)
Open panel front
1. First, push the front panel backward and lift it up to remove the two screws.
2. The moment of lifting the both lower parts of panel front, you can hear sound this panel came out, In this time panel front is
separated
3. After pull down this panel a bit, and separate connecting wire with product.
Panel Front
Connector
Remove cover pipe and cover side
1. Remove two screws(for fixing cover pipe)
2. Pull up the cover side of desired connecting direction, then cover
side is separated.
3. In case of connecting direction is left or right, path through the
hole of cover side.
Pipe hole
CAUTION: After removing the pipe hole, cut the
burr for safety.
NOTICE
When connecting pipe path through rear
wall, don’t remove the hole.
Drain hose junction
1. Remove the rubber stopple of desired direction of
drainage.
2. As the following picture, Insert drain hose in the
handle of drain pan, and join drain hose and con-
necting hose.
Adhesive
Only one
desiring direction
Connecting
part
Drain
hose
rubber cap
Service Manual 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
■ Sticking the installation guide map and
fixing Indoor unit
1. Put an Installation Guide Map on the desired
surface.
7. Drill the piercing part for connecting pipe as
diameter 50mm. (In case of piercing rear surface)
INSTALLATION GUIDE MAP
Refer to No. 5 on this page when making a hole in the wall.
2. Make a hole with diameter of 6mm and depth of
8. First, Drive the two points of the upper parts by
screws. (Leave 10mm for hanging product)
30-35mm when piercing a screw point.
INST
AIIA
TION G
UIDE MAP
INST
ALLA
TION GU
3. Drive the fore plastic anchors into drilled points.
IN
S
T
A
L
L
A
9. Drive the lower parts after facing the hole of
product with plastic anchors, and fix completely
the upper screws.
T
IO
N
G
U
ID
E
M
A
P
Plastic anchors
Plastic anchors
4. Hang the hole of product at the upper screws.
(In this time, Remove the map)
In case of nothing wrong in the matter,
connect the pipe and the wire.
(Installation manual reference)
INST
ALLA
(Falling attention)
TION GUIDE MAP
Hanger hole
(Rear side of
product)
■ Drill a hole in the wall
5. Check the fixed product with light power.
• Drill the piping hole with a ø50mm hole core drill. Drill
the piping hole at either the right or the left with the hole
slightly slanted to the outdoor side.
WALL
Indoor
Outdoor
6. Look at suited horizon by horizontal meter on
the horizontal setting line, and Fix lightly the
map by adhesive tape.
IN
S
T
A
L
L
A
T
Horizontality
IO
N
G
U
ID
E
M
A
P
20 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
Flaring Work and Connection of Piping
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
Copper
pipe
Slanted Uneven Rough
90°
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5m (5.0ft) longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section of
pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction
as you remove burrs in order to avoid dropping burrs into the
tubing.
Pipe
Reamer
Point down
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Flare nut
Copper tube
Flaring work
• Carry out flaring work using flaring tool as shown below.
• Firmly hold copper pipe in a die in the dimension shown in the
table above.
Outside diameter
A
Handle
Yoke
mm
Ø6.35
inch
1/4
mm
0~0.5
0~0.5
Bar
Bar
Ø9.52
3/8
Cone
Copper pipe
Clamp handle
Red arrow mark
Service Manual 21
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
Check
Smooth all round
1. Compare the flared work with the figure by.
Inside is shiny without scratches
2. If a flared section is defective, cut it off and do flaring work
again.
= Improper flaring =
Inclined Surface Cracked Uneven
damaged
thickness
Even length
all round
Connecting the Piping
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by)
and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in
the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction
of rear right.
2. Insert the connecting cable into the indoor unit from the out-
door unit through the piping hole.
• Do not connect the cable to the indoor unit.
•
Make a small loop with the cable for easy connection later.
Drain hose
3. Tape the tubing, drain hose, and the connecting cable. Be
sure that the drain hose is located at the lowest side of the
bundle. Locating at the uper side can cause drain pan to
overflow inside the unit.
Drain hose
If the drain hose is routed inside the room, insulate the hose
with an insulation material* so that dripping from "sweat-
ing"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Tape
Connecting
pipe
Drain hose
Connecting cable
Loop
Gas side piping
Connecting
cable
Liquid side piping
Drain hose
22 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the installa-
tion plate.(Engage the two hooks of the rear top of the
indoor unit with the upper edge of the installation plate.)
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
Connecting
cable
Drain hose
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
Connecting the piping to the indoor unit and drain hose
to drain pipe.
1. Align the center of the pipes and sufficiently tighten the
flare nut by hand.
2. Tighten the flare nut with a wrench.
Indoor unit tubing
Flare nut Pipes
Outside diameter
Torque
.
mm
Ø6.35
Ø9.52
inch
1/4
3/8
kg m
Open-end wrench (fixed)
1.8
4.2
Flare nut
Wrench
Connection pipe
3. When extending the drain hose at the indoor unit, install
the drain pipe.
Indoor unit tubing
Drain pipe
Indoor unit drain hose
Vinyl tape(narrow)
Wrap the insulation material around the connecting por-
tion.
Adhesive
1. Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together
with vinyl tape so that there may be no gap.
Plastic bands
Insulation material
2. Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
Indoor unit pipe
Wrap with vinyl tape
Connection pipe
Vinyl tape (wide)
Connecting cable
3. Bundle the piping and drain hose together by wrapping
them with vinyl tape for enough to cover where they fit into
the rear piping housing section.
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
Service Manual 23
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
For left rear piping
1. Route the indoor tubing and the drain hose to the required
piping hole position.
1
2
Connecting
cable
2. Insert the piping, drain hose, and the connecting cable into
the piping hole.
3. Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection
later.
Drain pipe
4. Tape the drain hose and the connecting cables.
5. Indoor unit installation
• Hang the indoor unit from the hooks at the top of the
installation plate.
• Insert the spacer etc. between the indoor unit and the
installation plate and separate the bottom of the indoor
unit from the wall.
Indoor unit
Spacer
Installation plate
8cm
Connecting the piping to the indoor unit and the drain
hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the
flare nut by hand.
Indoor unit tubing
Flare nut Pipes
2. Tighten the flare nut with a wrench.
Outside diameter
Torque
.
mm
Ø6.35
Ø9.52
inch
1/4
3/8
kg m
1.8
4.2
Open-end wrench (fixed)
Flare nut
Wrench
Connection pipe
3. When extending the drain hose at the indoor unit, install
the drain pipe.
Indoor unit tubing
Drain hose
Indoor unit drain hose
Vinyl tape (narrow)
Adhesive
24 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
Wrap the insulation material around the connecting por-
tion.
Plastic bands
Insulation material
1. Overlap the connection pipe heat insulation and the indoor
unit pipe heat insulation material. Bind them together with
vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping hous-
ing section with vinyl tape.
Indoor
unit piping
Connection
pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Connecting cable
Drain hose
3. Bundle the piping and drain hose together by wrapping
them with cloth tape over the range within which they fit
into the rear piping housing section.
Pipe
Vinyl tape(narrow)
Wrap with
vinyl tape(wide)
Reroute the pipings and the drain hose across the back
of the chassis.
Indoor unit installation
1. Remove the spacer.
Piping for
passage through
piping hole
2. Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
3. Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
Connecting
cable
Drain hose
Service Manual 25
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
■ Panel Assembly(Art Cool Type only)
1. First, Check the side cover assembly exactly, Fix
power cord in the bottom groove of cover side
left.
2. Assemble connecting lead wire with controller
and first fix the upper part of panel front, then
match the lower part of panel front
Panel Front
Connector
3. Drive two screws.
26 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
Installation Information. For left piping. Follow the instruction below.
Good case
• Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
• Following bending type from right to left may cause damage to the tubing.
Service Manual 27
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
REMOTE CONTROL PREPARATION(OPTIONAL)
HOW TO MOUNT ONTO A WALL
HOW TO INSERT BATTERIES
Remove the battery cover from the remote con-
troller.
• Slide the cover according to the arrow direction.
• Do not use rechargeable batteries,
such batteries differ from standard dry
cells in shape, dimensions, and per-
formance.
• Romove the batteries from the remote
controller if the air conditioner is not
going to be used for some long time.
Insert the two batteries.
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
28 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Flaring Work and Connection of Piping
Outdoor
Align the center of the pipings and sufficiently tighten the flare
nut by hand.
Finally, tighten the flare nut with torque wrench until the
wrench clicks.
Outdoor unit
• When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow on the wrench.
Outside diameter
Torque
.
mm
Ø6.35
inch
1/4
kg m
A-UNIT
Gas side piping
1.8
4.2
Ø9.52
3/8
B-UNIT
Liquid side piping
C-UNIT
Torque wrench
Service Manual 29
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the Cable between Indoor Unit and Outdoor Unit
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are
the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the electrical diagram behind the front panel of Indoor Unit.
The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.
RECOMMAND:
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring to the wiring diagram.
RECOMMAND: Provide a circuit breaker
Main power source
between power source and the outdoor
unit as shown below.
Air
Circuit Breaker
Conditioner
Use a circuit breaker
or time delay fuse.
RECOMMAND: The power cord connected to the outdoor unit should be complied with the following
specifications (ETL recognized and CSA certified).
AWG14
Line voltage (208~230V)
The power connecting cable connected to the indoor and outdoor unit should be complied with the
following specifications (ETL recognized and CSA certified).
AWG18
Low voltage (below 40V)
RECOMMAND: When using the separate wire as the power cord, please fix the separate wire into the
control box panel by using tie wrap as the fixture.
30 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the Outdoor unit.
1. Remove the cover control from the unit by loosening the
screw.
Outdoor unit
Connect the wires to the terminals on the control board
individually as the following.
Terminal block
Over 5mm
2. Secure the cable onto the control board with the holder
(clamper).
Holder for
power supply
cord
3. Refix the cover control to the original position with the
screw.
Power supply
cable
36k Outdoor side
A-UNIT
B-UNIT
C-UNIT
1
2
3
4
1
2
3
4
1
2
3
4
Cover control
Connecting
cable
Connecting cable(Low voltage)
L
N
1
2
3
4
1
2
3
4
1
2
3
4
Terminal BLOCK
Terminal BLOCK
Terminal BLOCK
Power Source
208/230V AC
(High voltage)
Indoor A-UNIT
Indoor B-UNIT Indoor C-UNIT
NOTICE
:
1. Separately wire the high and low voltage line.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).
3. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit.
(For example, Type SJO-WA)
WARNING:
• Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of
wire and wiring method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
Service Manual 31
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the Cable between Indoor Unit and Outdoor Unit
Connection method of the connecting cable(Example)
(1) Remove two-caps on the conduit panel.
(2) Make a hole appropriate for the passage of connection cable
through on cap by tool.
(for low voltage line)
Terminal
block
(3) Pass the connecting cable through the hole.
(4) Properly connect the cable on the terminal block.
(5) Fix the connection cable with cord clamp provided on the unit
not to have strain at the terminal when the connection cable is
pulled outside up to a 35 pound weight.
Cord clamp
Cap(Reuse)
G
Lock nut
(6) Wind the vinyl tape round the connecting cable for sealing
between the surface of the connection cable and cap.
(7)Finally, Fix the cap to the conduit panel.
Hole
(for low voltage line)
Cap(Remove)
Taping
WARNING: Loose wiring may cause the termi-
nal to overheat or result in unit malfunction. A
fire hazard may also exist. Therefore, be sure
all wiring is tightly connected.
(for sealing)
Power supply line Conduit panel
(1ø, 230/208V)
Low voltage line
(connecting cable)
When connecting each power wire to the corresponding terminal,
follow instructions "How to connect wiring to the terminals" and
fasten the wire tightly with the fixing screw of the terminal plate.
High voltage
Strand wire
How to connect wiring to the terminals
■■For strand wiring
Round
terminal
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the strand wiring about
10mm(3/8").
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a round terminal fastener or pliers, securely clamp
each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
Low voltage
Loosening the
terminal block
screw
Fastening the
wire tightly
Connecting cable
32 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting the Cable between Indoor Unit and Outdoor Unit
CAUTION: Provide a circuit breaker between power source and the unit as shown
below.
Main power source
Air
Fuse or breaker
Model
36k
Power source
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
Conditioner
Capacity
1Ø, 230/208V
40A
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board
individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec-
tively.
Connecting cable
2. Attach the Grille onto the cabinet.
• Grasp the lower left and right side of the Grille and
engage four tabs on the top inside edge of the chassis.
• Press the Grille toward the chassis until it will be back into
place.
Service Manual 33
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Checking the drainage
To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain exit.
Drain piping
1. The drain hose should point downward for easy drain flow.
Downward slope
2. Do not make drain piping.
Accumulated
drain water
Do not raise
Less than
50mm gap
Tip of drain hose
dipped in water
Air
Water
leakage
Water
leakage
Water
leakage
Waving
Ditch
34 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Forming the piping
Form the piping by wrapping the con-
necting portion of the indoor unit with
insulation material and secure it with
Seal a small
opening around
the pipings with
gum type sealer.
Taping
Drain hose
two kinds of vinyl tape.
• If you want to connect an additional drain hose, the end
of the drain outlet should be routed above the ground.
Secure the drain hose appropriately.
Plastic
band
Pipings
Connecting
cable
In cases where the outdoor unit is
installed below the indoor unit perform
the following.
1. Tape the piping, drain hose and connecting cable from
Power supply
cord
down to up.
2. Secure the tapped piping along the exterior wall using
saddle or equivalent.
• Trap is required to prevent water from entering
into electrical parts.
In cases where the Outdoor unit is
installed above the Indoor unit perform
the following.
1. Tape the piping and connecting cable from down to up.
2. Secure the taped piping along the exterior wall. Form a
trap to prevent water entering the room.
Seal a small opening
around the pipings
with gum type sealer.
Trap
3. Fix the piping onto the wall by saddle or equivalent.
Trap
Service Manual 35
Download from Www.Somanuals.com. All Manuals Search And Download.
Air Purging and Evacuation
Air Purging and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensi-
ble gas and moisture in the system.
Checking method
1. Do a leakage test of all joints of the tubing(both indoor and
outdoor) and both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off the soap with a
clean cloth.
Preparation
• Check that each tube(both liquid and gas side tubes) between
the indoor and outdoor units have been properly connected and
all wiring for the test run has been completed. Remove the ser-
2. After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is
reduced to normal, disconnect the hose from the cylinder.
vice valve caps from both the gas and the liquid side on the out-
door unit. Check that both the liquid and the gas side service
valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges) and dry nitro-
gen gas cylinder to this service port with charge hoses.
Indoor unit
CAUTION: Be sure to use a manifold
valve for leak testing.
The high side manifold valve must always
be kept closed.
Outdoor unit
• Pressurize the system to no more than 150 P.S.I.G. with dry
nitrogen gas and close the cylinder valve when the gauge
reading reached 150 P.S.I.G. Next, test for leaks with liquid
soap.
CAUTION: To avoid nitrogen entering the
refrigerant system in a liquid state, the top
of the cylinder must be higher than its bottom
when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
Manifold valve
Pressure
Lo
Hi
gauge
Charge hose
NOTICE
:
Leakage test shoud be done for each indoor
unit connection set, separately.
Nitrogen gas
cylinder(in vertical
standing position)
36 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking the Drainage, Forming the Pipings and Long Pipe Setting
Evacuation
1. Connect the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit.
Confirm the "Lo" knob of the manifold valve is open. Then,
run the vacuum pump.
Indoor unit
The operation time for evacuation varies with tubing length
and capacity of the pump. The following table shows the
time required for evacuation.
Required time for evacuation when 30 gal/h vacuum
pump is used
Outdoor unit
If tubing length is longer
than 10m (33 ft)
If tubing length is less
than 10m (33 ft)
10 min. or more
15 min. or more
2. When the desired vacuum is reached, close the "Lo" knob
of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid
side valve counter-clockwise to fully open the valve.
Manifold valve
2. Turn the valve stem of gas side valve counter-clockwise to
fully open the valve.
Pressure
gauge
Lo
Hi
3. Loosen the charge hose connected to the gas side service
port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side ser-
vice port and fasten the flare nut securely with an
adjustable wrench. This process is very important to pre-
vent leakage from the system.
Open
Close
5. Replace the valve caps at both gas and liquid side service
valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready for test running.
Vacuum pump
NOTICE
: Repeat evacuation procedure for each indoor
unit.
Service Manual 37
Download from Www.Somanuals.com. All Manuals Search And Download.
Charging
Charging
■ Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor
line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant
charge has to be adjusted.
■ Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added
or removed based on 20g(0.22oz) of R-410A per meter(foot).
Max Elevation
Max total length Max length of
Min length of
each pipe
(A/B/C)
Max elevation
between indoor
units (h2)
Additional
Refrigerant
between each indoor
unit and outdoor unit
(h1)
Capacity (Btu/h)
36k
of all pipes
(A+B+C)
each pipe
(A/B/C)
45m(150ft)
15m(50ft)
3m(10ft)
7.5m(25ft)
7.5m(25ft)
20g/m(0.22oz/ft)
Example: A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge
adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.
38 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Test Running
Test Running
Split, Art Cool Type
1. Check that all tubing and wiring have been properly con-
Bolt
nected.
2. Check that the gas and liquid side service valves are
fully open.
1) Prepare remote controller
Remove the battery cover by pulling it according to
the arrow direction.
Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
Reattach the cover by pushing it back into position.
Tubing connection
4) Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of
air.
3. Ensure the difference between the intake temperature
and the discharge is more than 8°C(46°F) (Cooling) or
reversely (Heating).
Outside ambient
TEMP.
The pressure of the gas side
service valve.
Refrigerant
R-410A
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the sys-
tem is not going to be used for a long time.
35°C (95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
2) Precautions in test run
Intake temperature
■ The initial power supply must provide at least 90% of
the rated voltage.
Otherwise, the air conditioner should not be operated.
Discharge air
■ For test run, carry out the cooling operation firstly
even during heating season. If heating operation is
carried out firstly, it leads to the trouble of compres-
sor. Then attention must be paid.
■ Carry out the test run more than 5 minutes without
fail. (Test run will be cancelled 18 minutes later auto-
matically)
Discharge
temperature
Intake temperature
■ The test run is started by pressing timer cancel button
five times continuously. (Room type)
Discharge air
■ To cancel the test run, press any button.
3) Settlement of outdoor unit
■ Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
■ When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
■ In the case when the vibration of the unit is conveyed to
the hose, secure the unit with an anti-vibration rubber.
Discharge
temperature
Service Manual 39
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Operation
Function of control
1. MAIN UNIT FUNCTION
• DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
■ Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(32.9°F) below the setting temp, the compressor and the outdoor
fan stop.
• When it reaches 0.5°C(32.9°F) above the setting temp, they start to operate again.
Compressor ON Temp
Compressor OFF Temp
■■Setting Temp+0.5°C(32.9°F)
■ Setting Temp-0.5°C(31.1°F)
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
■ Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8°F) ≤ Intake Air Temp
■■ 25°C(77°F)
24°C(75.2°F) ≤ Intake Intake Air Temp<26°C(78.8°F)
18°C(64.4°F) ≤ Intake Intake Air Temp<24°C(75.2°F)
Intake Air Temp<18°C(64.4°F)
■■ Intake Air Temp-1°C(30.2°F)
■■ Intake Air Temp-0.5°C(31.1°F)
■■ 18°C(64.4°F)
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
■ Setting Temp+0.5°C(32.9°F)
Compressor OFF Temp. ■ Setting Temp-0.5°C(31.1°F)
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■ Heating Mode Operation
• When the intake air temp reaches +3°(37.4°F)…above the setting temp, the compressor is turned off. When
below the setting temp, the compressor is turned on.
Compressor ON Temp.
■ Setting Temp.
Compressor OFF Temp. ■ Setting Temp.+3°C(37.4°F)
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68°F), when above
27°C(80.6°F) , it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68°F) and
40 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
27°C(80.6°F), it operates with Super-Low(while in sleep mode, with the medium airflow speed).
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4°F), when above
35°C(95°F) , it operates with the low airflow speed.
• While in defrost control, the indoor is outdoor fans are turned off.
■ Defrost Control(Heating)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes
passed from starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C(59°F) even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes
passed from ending of the first defrost and more than 4 minutes operation of compressor.
■ Fuzzy Operation
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C(75.2°F) ≤ Inatake Air Temp
21°C(69.8°F) ≤ Inatake Air Temp<24°C(75.2°F)
Inatake Air Temp<21°C(69.8°F)
■ Fuzzy Operation for Cooling
■ Fuzzy Operation for Dehumidification
■ Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(32.9°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(32.9°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp
Compressor OFF Temp
■ Setting Temp +0.5°C(32.9°F)
■ Setting Temp + 0.5°C(32.9°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8°F)≤ Intake Air Temp
■ 25°C(77°F)
24°C(75.2°F)≤ Intake Air Temp<26°C(78.8°F)
22°C(71.6°F)≤ Intake Air Temp<24°C(75.2°F)
18°C(64.4°F)≤ Intake Air Temp<22°C(71.6°F)
Intake Air Temp<18°C(64.4°F)
■ Intake Air Temp + 1°C(33.8°F)
■ Intake Air Temp + 0.5°C(32.9°F)
■ Intake Air Temp
■ 18°C(64.4°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper-
ature.
Service Manual 41
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(32.9°F) or more
below the setting temp, the compressor is turned off. When 0.5°C(32.9°F) or more above the setting temp, the
compressor is turned on.
Compressor ON Temp
Compressor OFF Temp
■ Setting Temp + 0.5°C(32.9°F)
■ Setting Temp+0.5°C(32.9°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C(78.8°F) ≤ Intake Air Temp
■ 25°C(77°F)
24°C(75.2°F) ≤ Intake Air Temp<26°C(78.8°F)
22°C(71.6°F) ≤ Intake Air Temp<24°C(75.2°F)
18°C(64.4°F) ≤ Intake Air Temp<22°C(71.6°F)
Intake Air Temp<18°C(64.4°F)
■ Intake Air Temp+1°C(33.8°F)
■■ Intake Air Temp+0.5°C(32.9°F)
■ Intake Air Temp
■ 18°C(64.4°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37.4°F) or more
above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned
on.
Compressor ON Temp
Compressor OFF Temp
■ Setting Temp
■ Setting Temp + 3°C(37.4°F)
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C(68°F)≤Intake Air Temp
Intake Air Temp<20°C(68°F)
■ Intake Air Temp + 0.5°C(32.9°F)
■ 20°C(68°F)
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
■■Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or power (auto) by the input of the airflow
speed selection key on the remote control.
■ On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
■■Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
42 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
• If the appliance is on pause at the time set by the timer, the pause continues.
■■Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.
■■Sleep Timer Operation
• When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli-
ance operation, the operation of the appliance stops.
• While the appliance is on pause, the sleep timer mode cannot be input.
• While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature
increases by 1°C(33.8°F). After another 30 min elapse, it increases by 1°C(33.8°F) again.
• When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
• When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to
the medium.
■■Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
■■Chaos Natural Wind Mode
• When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air-
flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
■■Jet Cool Mode Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
• In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64.4°F)
.
• When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
■■Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Service Manual 43
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
■ Forced Operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched to the Auto Restarting (or test operation) position or switched from the remote control
position to the forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
• In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the opera-
tion condition is set according to the intake air temperature as follows.
24°C(75.2°F)≤Intake Air Temp
21°C(69.8°F)≤Intake Air Temp<24°C(75.2°F)
Intake Air Temp<21°C(69.8°F)
■ Cooling Mode Operation, 22°C(71.6°F), High Speed
■ Dehumidification Operation, 23°C(73.4°F), High Speed
■ Heating Mode Operation, 24°C(75.2°F), High Speed
■ Buzzer Sounding Operation
• When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
• When the appliance-pause key is input by the remote control, the long "beep—" sounds.
44 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Function of Indoor Unit
Split Type Indoor Unit
Operation ON/OFF by Remote controlle
r
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 seconds at the starting.
Time Delay Safety Control
• Restarting is delayed for approx. 3 minutes.
Indoor Fan Speed Control
• High, Med, Low, Chaos, Jet Cool
Operation indication Lamps (LED)
On/Off
Sleep Mode : Lights up during Sleep Mode Auto operation.
Timer : Lights up during Timer operation.
Defrost Mode: Lights up during Defrost Mode or Hot Start operation (Heat pump model only)
: Lights up during the system operation.
Outdoor unit
operation
: Lights up during outdoor unit operation.(Cooling model only)
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature
indicator
• Cooling
• Dehumidification : 18°C~30°C(64°F~86°F)
• Heating : 16~30°C(60°F~86°F)
: 18°C~30°C(64°F~86°F)
• AI : Auto Operation
• Po : Jet Cool
• Lo : Test Mode
: The function illustrates its dynamic mode by using a multiple lighting system. (Optional)
Plasma
Soft Dry Operation Mode
• Intermittent operation of fan at low speed.
Sleep Mode Auto Control
Deice (defrost) control (Heating)
• Both the indoor and outdoor fan
stops during deicing.
• Hot start after deice ends.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
Hot-start Control (Heating)
• The fan is switched to intermittent or irregular operation
• The indoor fan stops until the
evaporator piping temperature will
be reached at 27°C(80.6°F).
•
The fan speed is automatically switched from high to low speed.
* Airflow Direction Control
• The louver can be set at the desired position or swing
up and down automatically.(Model base)
"Wall Mounted Type is standard"
* Functions is dependent on model type.
Service Manual 45
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Art Cool Type Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
• Room temperature sensor. (THERMISTOR)
Room temperature control
• Maintains the room temperature in accordance with the Setting Temp.
Starting Current Control
• Indoor fan is delayed for 5 sec at the starting.
Time Delay Safety Control
• Restarting is inhibited for approx. 3 minutes.
Indoor Fan Speed Control
• High, Med, Low, CHAOS, JET COOL
Operation indication Lamps (LED)
On/Off
: Lights up during the system operation.
: Lights up during Sleep Mode Auto operation.
: Lights up during Timer operation.
Sleep Mode
Timer
Defrost Mode
: Lights up during Defrost Mode or
Hot Start operation.(Heat pump model only)
Outdoor unit
operation
: Lights up during outdoor unit operation.(Cooling model only)
Desire temperature For cooling,dehumidification,heating modes it display Destired temperature
indicator
• Cooling
• Dehumidification : 18°C~30°C(64°F~86°F)
• Heating : 16~30°C(60°F~86°F)
: 18°C~30°C(64°F~86°F)
• AI : Auto Operation
• Po : Jet Cool
• Lo : Test Mode
PLASMA
: Indicate PLASMA purifier operation.
Soft Dry Operation Mode
PLASMA
• Intermittent operation of fan at low speed.
• The function will be operated while in any
operation mode with selecting the function.
• The function is to be stopped while it is
operating with selecting the function.
Sleep Mode Auto Control
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Defrost(Deice) control (Heating)
Natural Air Control by CHAOS Logic
• Both the indoor and outdoor fan stops dur-
• The fan is switched to intermittent or irregular operatio
n
ing defrosting.
•
The fan speed is automatically switched from high to low speed.
Hot-start Control (Heating)
Airflow Direction Control
• The indoor fan stops until the
evaporator pipe temperature will be reached
at 28°C(82.4°F).
• The louver can be set at the desired position or swing
up and down automatically.
46 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Function of Outdoor Unit
Outdoor Unit
Two Comp algorithm
• Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.
Operating Step
• Compressor step varies considering condition such as room temp,outdoor temp, operating room
number,Temp gap between room temp and set temp and so on.
LEV Control
• LEV pulse is modulated to keep constant superheat or subcooling.
Out door Fan Control
• Outdoor fan operates at High or Off to respond to the load condition.
R/Valve Control(Heating Model Only)
• Convert R/Valve to change cooling to heating, heating to cooling.
Defrost Function
• After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -
5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min
cooing mode.
• To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to
Oil Return System
• In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.
Comp Overload Protection
• To protect comp from being overload, protector will turn off the comp.
High Pressure Protction
• If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A
Service Manual 47
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Remote Control Operation
The Remote Controller transmits the signals to the system.
START/STOP BUTTON
Operation starts when this button is pressed and stops when
the button is pressed again.
1
Signal transmitter
OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
2
3
(Cooling Only)
(Heat Pump)
ROOM TEMPERATURE
SETTING BUTTONS
Used to select the room temperature.
INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps
low, medium, high and CHAOS.
4
5
6
5
6
1
3
JET COOL
Used to start or stop the speed cooling/heating.
(Speed cooling/heating operates super high fan speed.)
4
CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired
up/down airflow direction.
10
2
7
CANCEL
9
SET
ON
OFF
AUTO CLEAN
16
11
8
13
ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
7
8
9
12
17
18
15
°C/°F
TIME SETTING BUTTONS
Used to adjust the time.
14
TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel
the Timer operation.
SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
10
11
12
13
14
15
Flip-up door
(opened)
AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
Operation Mode
ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
Cooling Operation
PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
Auto Operation
RESET BUTTON
Initialize remote controller.
Healthy Dehumidification Operation
2nd F Button
Heating Operation
Used prior to using modes printed in blue at the bottom of buttons.
AUTO CLEAN
Used to set Auto Clean mode.
•
Cooling Model( ), Heat Pump Model(
)
16
17
˚C TO ˚F SWITCHING BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (NOT ON
ALL MODELS)
18
Used to set the desired horizontal airflow direction.
48 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Disassembly
Indoor Unit
Split Type Indoor Unit
Disconnect the unit from power supply before mak-
ing any checks.
Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
• Set the up-and-down air discharge louver to open
position (horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it
straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Earth
Conductor
Service Manual 49
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
2. To remove the Control Box.
• Remove securing screws.
• Pull the control box out from the chassis
carefully.
Screw
3. To remove the Discharge Grille.
• Unhook the discharge grille and pull the
discharge grille out from the chassis carefully.
4. To remove the Evaporator.
• Remove 3 screws securing the evaporator(at the
left 2EA in the Eva Holder, at the right 1EA).
• When repair, do not damage the Caution label.
50 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
• Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator
toward you until the tab is clear of the slot.
5. To remove the Motor Cover
• Remove 2 securing screw.
• Pull the motor cover out from the chassis
carefully.
Motor cover
6. To remove the Cross-Flow Fan
• Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Bearing
• Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the
cross-flow fan.
Cross-flow fan
• Remove the left end of the cross-flow fan from
the self-aligning bearing.
Service Manual 51
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
Art Cool Type Indoor Unit
CAUTION: Disconnect the unit from
power supply before making any
checks.
Be sure the power switch is set to
“OFF”.
1. To remove the Grille from the Chassis.
- Pull the grille bottom, the remove 2 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting
wire with product.
Panel Front
Connector
Step Motor Connectors
2. To remove the Control Box.
- Before removing the control box, be sure to
disconnect the wires from PWB.
Sensor Connector
- Pull the cover control out from the control box
and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.
4Way/Fan Connector
Motor
Comp Connector
Power Connector
Power Connector
Comp Connector
Connector
52 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Disassembly
3) To remove the Evaporator.
- Remove 4 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.
4) Before removing the Turbo Fan.
- Remove the securing screws from the chassis.
- Pull the pipe cover, top cover and the air guide.
Air Guide
Top Cover
Pipe Cover
5) To remove the Motor.
Bracket
- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the
chassis and lift up the motor mount and the brack-
et.
Turbo Fan
Bolt
Motor Mount
Service Manual 53
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Schematic Diagram
Electronic Control Device
1. Indoor Unit
1) Split Type
54 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
2) Art Cool Type
R D
R D
O R
O R
B L P K Y L
B L P K Y L
FG
5V
AVdd1
AVss
R D
R D
O R Y L P K B L
O R Y L P K B L
Service Manual 55
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
2. Outdoor Unit
56 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Service Manual 57
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Wiring Diagram
1. Room Type Indoor Unit -S4/SE chassis
2. Art Cool Type Indoor Unit
3. Outdoor Unit
1. A3UH363FA0(LMU360HE)
2. A3UC363FA0(LMU360CE)
58 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
Components Locations
1. Indoor Unit
MAIN P.C.B ASM
1) Split Type
• TOP VIEW
PCB :6870A90409B
ASSY:6871A20771
6871A20782
• BOTTOM VIEW
Service Manual 59
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
2) Art Cool Type
• TOP VIEW
• BOTTOM VIEW
60 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
2. Display ASSEMBLY
1) Split Type (6871A20680)
2) Art Cool Type (6871A20462)
TOP VIEW
BOTTOM VIEW
Service Manual 61
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
3. Outdoor Unit
1) Component side
62 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Schematic Diagram
2) Solder side
Service Manual 63
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Troubleshooting Guide
Refrigeration Cycle Diagram
1. A3UH363FA0(LMU360HE)
OUTDOOR UNIT
Ø9.52
Room C
High pressure S/W
Ø9.52
Field Piping
Gas
Room B
Ø9.52
Room A
Header
Th3
Th1
Th2
Heat
Exchanger
LEV-C
LEV-B
Ø6.35
Room C
Ø6.35
Room B
Ø6.35
Room A
Field Piping
Liquid
LEV-A
Refrigerant Flow
Cooling
Th1: Discharge thermistor
Th2: Discharge thermistor
Th3: Outdoor temperature thermistor
2. A3UC363FA0(LMU360CE)
OUTDOOR UNIT
Ø9.52
Room C
Ø9.52
Field Piping
Room B
Gas
Ø9.52
Room A
High pressure S/W
Header
Th3
Th1
Th2
Heat
Exchanger
LEV-C
Ø6.35
Room C
LEV-B
LEV-A
Ø6.35
Field Piping
Room B
Liquid
Ø6.35
Room A
Th4
Refrigerant Flow
Cooling
Heating
Th1: Discharge thermistor
Th2: Discharge thermistor
Th3: Outdoor temperature thermistor
Th4: Defrost thermistor
64 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Self-diagnosis Function
■ Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
LED1 LED2
Indoor Error
Error code
Description
MPS Variable
LED1
LED2
Indoor Status
00
01
02
05
06
07
10
No Error
ON
Indoor Room Thermistor Error
Indoor In-Piping Error
1 time
2 times
5 times
6 times
7 times
OFF
OFF
OFF
OFF
OFF
OFF
Communication Error between In and Out
Indoor Out-Piping Error
Differnt mode operation
Indoor fan motor locked error
1 times
Outdoor Error
Error code
Description
MPS Variable
LED1(Red)
LED2(Green) Indoor Status
33
44
45
47
51
D-Pipe High(Normal)
3 times
4 times
4 times
4 times
5 times
3 times
4 times
5 times
7 times
1 times
OFF
OFF
OFF
OFF
OFF
Outdoor Air Thermistor Error(Open/Short)
Cond Pipe Thermistor Error(Open/Short)
Const. D-Pipe Thermistor Error(Open/Short)
Capcity Error(High/Low)
Service Manual 65
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
Temp. difference
Current
: approx. 0°C(32°F)
: less than 80% of
rated current
All amount of refrigerant leaked out.
Check refrigeration cycle.
Temp. Difference
Operating Current
Temp. difference
Current
: approx. 8°C(46.4°F)
: less than 80% of
rated current
Refrigerant leakage
Clog of refrigeration cycle
Defective compressor
Temp. difference
Current
: less than 8°C(46.4°F)
: near the rated cur-
rent
Excessive amount of refrigerant
Temp. difference : over 8°C(46.4°F)
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure
(Compared with
the normal value)
Temperature
(Compared with
the normal value)
Cause of Trouble
Description
High
Defective compressor
Current is low.
Higher
Lower
Normal
Excessive amount of
refrigerant
High pressure does not quickly
rise at the beginning of operation.
Insufficient amount of
refrigerant(Leakage)
Clogging
Current is low.
Higher
Notice:
2
1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
66 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Electronic Parts Troubleshooting Guide
■ Refer to electronic contorol device drawing & schematic diagram.
The Product doesn’t operate at all.
Trouble 1
Turn off the main power and wait until LED on outdoor PCB is off.
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
NO
YES
• Primarily, the operating condi-
tion of Micom is O.K.
Check the voltage of power(AC208V/AC230V, 60Hz).
• The voltage of main power.
• The voltage applied to the unit.
• The connecting method of Indoor/Outdoor connecting cable (each color)
• The P.W.B. Ass'y
(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)
• Check CN-DISP1
The operation check of the P.C.B. Ass'y
Specification
1) AC230V ± 30V
Remedy
Procedure
1) Replace
1) The input voltage of power trans-
former.
: Check the rated voltage
power transfomer.
2) 15V ± 1.5V
2) Replace
2) The output voltage of power
transformer.
power transfomer.
3) DC12V
4) DC5V
3) Replace IC01D.
4) Replace IC02D.
5) Replace IC01A.
3) IC01D(7812)
4) IC02D(7805)
5) IC01A(KIA7036)
5) The voltage of micom pin 29
: DC4.5V↑
Service Manual 67
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Product doesn't operate with the remote controller.
Trouble 2
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
Caused by other parts except
Caused by the remote controller.
the remote controller
When the mark (
) is displayed in LCD
Check the contact of CN-DISP 1 connector
screen, replace battery.
When the detect switch (double key) inside the
remote controller door is fault, it is impossible to
operate temperature regulating(■ / ■) and wind
speed selecting.
Check DISP PWB Ass'y
-Voltage between CN1 ■■- ■■: DC +5V
Check the Display PWB Ass'y
• Check receiver ass'y
68 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
The Compressor/Outdoor Fan are don't operate
Trouble 3
Turn on the main power.
Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1°C at least.
When in air circulation mode, compressor/outdoor fan is stopped.
Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.
• Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 ,
75 , 76 , 77 ).
• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).
Check the Relay(RY-PWR, RY-START) for driving Compressor.
• Check the voltage between brown and blue cable of terminal to connect the Outdoor
(About AC208V / 230V).
• Check the related circuit of relay in Outdoor PCB Ass'y.
Check Point
Comp. ON
DC 5V
Comp. OFF
DC 0V
Between Micom(No. 50,51) and
GND
Between IC01M(No. 10) and
GND
DC 1V↓
DC 12V
Turn off main power.
Check the electrical wiring diagram of Outdoor side.
Check the open or short of connecting wires between Indoor and Outdoor.
Service Manual 69
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
When indoor Fan does not operate.
Trouble 4
When indoor Fan does not operate.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in
Indoor unit corresponds to values in the Table of page 69
Does the voltage of terminal of CN-DC/DC CONNECTOR in
Check connecting condition of the CN-MOTOR CON-
Indoor unit corresponds to the values in the table of page 56
NECTOR
Do the voltage of terminal of
Check the pattern and the
CN-DC/DC CONNECTOR in
condition of Indoor unit PWB
Outdoor unit corresponds to the
Ass'y.
Check the interference of Indoor Fan.
values in the table of page 56
NO
Check the connecting condi-
Check the patterns and the
tion and disconnection of
Check the motor of Indoor Fan
conditions of outdoor unit
connecting wires between
PWB Assy's.
Indoor and Outdoor unit.
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F.
(At that times, Defrost indicator is turned on)
70 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
When the louver does not operate.
When Vertical Louver does not operate.
Trouble 5
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands
Normal
• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
+
• Confirm that there is DC 12V between pin (RED) of CN-UP/DOWN and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 60 , 61 , 62 and 63 of MICOM
- Between 2 , 3 , 4 and 5 of IC01M
- Between 12 , 13 , 14 , 15 of IC01M
- Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts in
the rotation radial of the Vertical Louver
Service Manual 71
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Error Code
■ Trouble Shooting
Error
code
Title
Cause of error
• Open / Short
• Soldered poorly
• Internal circuit error
Check point & Normal condition
Normal resistor : 10KΩ / at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
01
02
06
Indoor air sensor
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 5KΩ/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
Indoor inlet pipe sensor
Indoor outlet pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 5KΩ/ at 25°C (Unplugged)
Normal voltage : 2.5Vdc / at 25°C (plugged)
10KΩ
2.5Vdc
Ω
V
Check the resistance / voltage
■ Check Point
1. Unplug the sensor on Indoor unit PCB.
2. Estimate the resistance of each sensor
3. If the resistance of the sensor is 10KΩ/5KΩ at 25°C, then sensor is normal
4. If the resistance of the sensor is 0 KΩ or ∞, then sensor is abnormal. ■ Change the sensor.
5. Plug the sensor on Indoor unit PCB and Power ON.
6. Estimate the voltage of each sensor.
7. If the voltage of the sensor is 2.5Vdc / at 25°C, then sensor is normal.
8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. ■ Repair or Change the PCB
72 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Error
code
Title
Cause of error
Check point & Normal condition
• Power input AC 230V.(Outdoor, Indoor)
• The connector for transmission is disconnected.
• The connecting wires are misconnected.
• The GND 1,2 is not connected at main GND.
• The communication line is shorted at GND.
• Transmission circuit of outdoor PCB is abnormal.
• Transmission circuit of indoor PCB is abnormal.
Communication
(Indoor ■ Outdoor)
05 / 53
• Communication poorly
■ Check Point
1. Check the input power AC 230V.(Outdoor, Indoor)
2. Check the communication wires are correctly connected.
■ Adjust the connection of wire
■ Confirm the wire of "Live", "Neutral".
3. Check the resistance between communication line and GND.(Normal : Over 2MΩ)
4. Check the connector for communication is correctly connected.
5. Check the connection of GND1, GND2, and main GND.
6. If one indoor unit is operated normally, outdoor PCB is no problem.
■ Check the another indoor unit.
* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.
Service Manual 73
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Error
code
Title
Cause of error
Check point & Normal condition
• Check the discharge pipe sensor.
• Check the install condition for over load.
• Check the leakage of refrigerent.
• Check the SVC V/V open.
• Discharge sensor
temp. high
33
D-Pipe Temp. High
COMP OFF
115°C(239°F)
LEV OPEN(16PULSE/MIN)
100°C(212°F)
LEV OPEN(10PULSE/MIN)
95°C(203°F)
NORMAL
A3UH363FA0(LMU360HE)/A3UC363FA0(LMU360CE)
■ Check Point
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerent.
4. Check the constant compressor.
Error
code
Title
Cause of error
Check point & Normal condition
• Over Capacitor com-
bination
• Check the indoor unit capacity.
• Check the combination table
51
Capacitor error
■ Check Point
1. Check the indoor unit capacity.
2. Check the combination table.
■ In the tropical model case
■ single cycle has no error for over capacity.
74 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide
Error
code
Title
Cause of error
• Open / Short
• Soldered poorly
• Internal circuit error
Check point & Normal condition
Normal resistor : 10KΩ / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
44
45
47
Outdoor air sensor
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 5KΩ/ at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Condensor pipe sensor
D-Pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 200KΩ/ at 25°C(77°F) (Unplugged)
Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)
Ω
Ω
Check the resistance
■ Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance is 0V or 5Vdc, then sensor is abnormal
Service Manual 75
Download from Www.Somanuals.com. All Manuals Search And Download.
2-way, 3-way Valve
2-way, 3-way Valve
2-way Valve (Liguid Side)
3-way Valve (Gas Side)
Valve cap
Hexagonal wrench
(4mm)
Open position
Closed position
Flare nut
Flare nut
Open position
Pin
Closed position
To
To
piping
piping
Service
port cap
Service
port
connection
connection
To outdoor unit
To outdoor unit
Works
Shaft position
Shaft position
Service port
Shipping
Closed
Closed
Closed
(with valve cap)
(with valve cap)
(with cap)
Air purging
Open
Closed
Open
(Installation)
(counter-clockwise)
(clockwise)
(push-pin or with
vacuum pump)
1.
2.
Operation
Open
Open
Closed
(with valve cap)
(with valve cap)
(with cap)
Pumping down
(Transfering)
Closed
Open
Open
(clockwise)
(counter-clockwise)
(connected
manifold gauge)
Evacuation
(Servicing)
Open
Open
Open
Open
Open
Open
Open
Open
Open
3.
4.
(with charging
cylinder)
Gas charging
(Servicing)
Open
(with charging
cylinder)
Pressure check
(Servicing)
Open
5.
6.
(with charging
cylinder)
Gas releasing
(Servicing)
Open
(with charging
cylinder)
76 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
2-way, 3-way Valve
(1) Pumping down
Liquid side
Indoor unit
Outdoor unit
Close
2-Way
valve
Gas side
Open
3-Way
valve
Liquid side
Indoor unit
Close
2-Way
valve
Gas side
Open
3-Way
valve
manifold gauge
Low-
handle
(CLOSE)
Hi- handle
(CLOSE)
• Procedure
6. Operate the air conditioner at the cooling cycle
1. Confirm that both the gas side and liquid side
valves are set to the open position.
2
and stop it when the gauge indicates 1kg/cmg.
- Remove the valve stem caps and confirm that the
valve stems are in the raised position.
7. Immediately set the gas side valve to the closed
position.
- Do this quickly so that the gauge ends up indicat-
- Be sure to use a hexagonal wrench to operate
the valve stems.
ing 1kg/
g.
8. Disconnect the charge set, and mount the liquid
side and gas side valve caps and the service port
nut.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then con-
nect the manifold gauge to the service port of the
gas side valve.
- Use torque wrench to tighten the service port nut
to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m)
- Connect the hose of the gauge with the push pin
to the service port.
- Be sure to check for gas leakage.
4. Air purging of the charge hose.
- Open the Low-handle valve on the gauge
slightly to air purge from the hose.
5. Set the liquid side valve to the closed position.
• Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.
Service Manual 77
Download from Www.Somanuals.com. All Manuals Search And Download.
2-way, 3-way Valve
(2) Evacuation
(All amount of refrigerant leaked)
Liquid side
Indoor unit
Outdoor unit
Open
2-Way
valve
Gas side
Open
3-Way
valve
Liquid side
Indoor unit
Open
2-Way
valve
Gas side
Open
3-Way
valve
manifold gauge
Vacuum pump
Low-
handle
(OPEN)
Hi- handle
(OPEN)
• Procedure
6. Disconnect the charge hose from the vacuum
pump.
1. Confirm that both the liguid side valve and gas
side valve are set to the opened position.
- Vacuum pump oil.
If the vacuum pump oil becomes dirty or deplet-
ed,replenish as needed.
2. Connect the vaccum pump to the center hose of
the manifold gauge.
3. Connect the service port of the gas side valve to
the low side of the gauge.
7. Mount the valve caps and the service port caps.
4. Evacuation for approximately one hour.
- Confirm that the gauge needle has moved
toward-76 cmHg (vacuum of 4 mmHg or less).
5. Close the Low handle of the gauge turn off the
vacuum pump, and confirm that the gauge needle
does not move(approximately 5 minutes after
turning off the vacuum pump).
78 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
2-way, 3-way Valve
(3) Gas Charging
(After Evacuation)
Liquid side
Indoor unit
Outdoor unit
Open
2-Way
valve
Gas side
Open
3-Way
valve
Liquid side
Indoor unit
Open
2-Way
valve
Gas side
Open
3-Way
valve
manifold gauge
Charging
cylinder
Low-handle
(OPEN)
Hi- handle
(OPEN)
Check valve
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect-
ed from the vacuum pump to the valve at the
bottom of the cylinder.
4. Immediately disconnect the charge hose from
the gas side valve's service port.
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
-
Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air. (Be careful of the liquid refrigerant). The
procedure is the same if using a gas cylinder.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the speci-
fied amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
Service Manual 79
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
Exploded View & Replacement Parts List
Indoor Unit
S4, SE chassis
135311
152302-1
152302-2
135301
131410
733010
152313
342800
354210
359011
135312
135500
159901
346810
35211B
268712
135516
352150
147582
146811
263230-2
263230-1
268714
668713
267110
249951
80 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
Parts List (S4, SE chassis)
PART No.
S4 chassis
SE chassis
SVC
CODE
LOCATION
DESCRIPTION
No.
AMNH093D4A0 AMNC093D4A0 AMNH123DEA0 AMNC123DEA0
(LMN090HE)
(LMN090CE)
(LMN120HE)
(LMN120CE)
131410 CHASSIS ASSEMBLY
135311 GRILLE ASSEMBLY,FRONT(INDOOR)
135301 GRILLE,FRONT
3141A20019C
3531A14003K
3530A10253A
5230A20051B
5230A20051D
3531A11307A
5990A20069A
4758A30052A
4681A20055A
6871A20680D
3551A20156B
4681AR2295L
5231A20040A
4995A20831A
6871A20782A
6871A20989A
6323AQ3226T
6323A20004A
6711A20128C
4280A20004B
5421A20222C
5211A21363E
5251A20011B
5901A20017F
3301A20020C
3550A30262A
3141A20019C
3531A14003K
3530A10253A
5230A20051B
5230A20051D
3531A10307V
5990A20069A
4758A30052A
4681A20055A
6871A20680F
3551A20156B
4681AR2295L
5231A20040A
4995A20831A
6871A20782A
6871A20989D
6323AQ3226T
6323A20004A
6711A20128A
4280A20004B
5421A20222C
5211A21363E
5251A20011B
5901A20017F
3301A20020C
3550A30262A
3141A20034A
3531A18015A
3530A10287A
5230A20064A
5230A20064A
3531A11362A
5990A20068A
4758A30057A
4681A20055A
6871A20680D
3551A20156B
4681AR2295L
5231A20040K
4995A20831A
6871A20782A
6871A20989B
6323AQ3226T
6323A20004A
6711A20128C
4280A20004B
5421A20282A
5211A15008A
5251A20011G
5901A20017H
3301A20020A
3550A30315A
3141A20034A
3531A18015A
3530A10287A
5230A20064A
5230A20064A
3531A11362B
5990A20068A
4758A30057A
4681A20055A
6871A20680F
3551A20156B
4681AR2295L
5231A20040K
4995A20831A
6871A20782A
6871A20989C
6323AQ3226T
6323A20004A
6711A20128A
4280A20004B
5421A20282A
5211A15008A
5251A20011G
5901A20017H
3301A20020A
3550A30315A
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
152302-1 FILTER,AIR
152302-2 FILTER,AIR
135312 GRILLE ASSEMBLY,DISCHARGE(INDOOR)
159901 LOUVER,HORIZONTAL
147582 LOUVER,VERTICAL
146811 MOTOR,DC
268712 PCB ASSEMBLY,DISPLAY
135516 COVER ASSEMBLY,MOTOR
346810 MOTOR,DC
152313 FILTER ASSEMBLY,DEODORIZER
249951 CASE ASSEMBLY,CONTROL(INDOOR)
268714 PCB ASSEMBLY,MAIN
668713 PCB ASSEMBLY(OPTION PCB)
263230-1 THERMISTOR,NTC
263230-2 THERMISTOR,NTC
267110 REMOTE CONTROLLER ASSEMBLY
342800 BEARING
354210 EVAPORATOR ASSEMBLY,FINAL
35211B TUBE ASSEMBLY,TUBING
352150 HOSE ASSEMBLY,DRAIN
359011 FAN ASSEMBLY,CROSS FLOW
733010 PLATE ASSEMBLY,INSTALLATION
135500 COVER
NOTE) Please ensure GCSC since these parts may be changed depending upon the buyer's request.
*
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 81
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
SP3 Chassis Art Cool Type
82 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
Parts List (SP3 chassis)
PART No.
SVC
CODE
LOCATION
DESCRIPTION
AMNH093APM0 AMNC093APM0 AMNH123APM0 AMNC123APM0
(LMAN090HNS) (LMAN090CNS) (LMAN120HNS) (LMAN120CNS)
No.
131410 CHASSIS ASSEMBLY
3141A20030C
3141A20030C
3531A21035T
3531A20212K
5230A20032A
6871A20462B
6871A20259B
6871A20363D
3550A20123C
3550A20124B
3550A20060A
3551A20031H
4758A20014B
4681A20055A
5983A20007F
4995A20832A
6871A20387M
6323A20004N
3141A20030C
3531A21035N
3531A20212K
5230A20032A
6871A20462A
6871A20259B
6871A20363D
3550A20123C
3550A20124B
3550A20060A
3551A20031H
4758A20014B
4681A20055A
5983A20007F
4995A20832D
6871A20387M
6323A20004N
6323AQ3226T
6711A20128F
3087A30004A
4681A20047B
4960A20016A
5211AR7066F
5251AR1222R
5421A20072A
5900A00003A
3141A20030C
3531A21035T
3531A20212K
5230A20032A
6871A20462B
6871A20259B
6871A20363D
3550A20123C
3550A20124B
3550A20060A
3551A20031H
4758A20014B
4681A20055A
5983A20007F
4995A20832C
6871A20387N
6323A20004N
6323AQ3226T
6711A20083R
3087A30004A
4681A20047B
4960A20016A
5211AR7066F
5251AR1222R
5421A20072A
5900A00003A
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A21035N
135314 GRILLE ASSEMBLY,INLET
152302 FILTER, AIR
3531A20212K
5230A20032A
6871A20462A
6871A20259B
6871A20363D
3550A20123C
3550A20124B
3550A20060A
3551A20031H
4758A20014B
4681A20055A
5983A20007F
268712 PCB ASSEMBLY,DISPLAY
268717-1 PCB ASSEMBLY,SUB
268717-2 PCB ASSEMBLY,SUB
135500-1 COVER
135500-2 COVER
135500-3 COVER
135515 COVER ASSEMBLY,TOP(INDOOR)
147581 LOUVER,HORIZONTAL
146811 MOTOR,DC
159830 FILTER ASSEMBLY,AIR CLEANER
249951 CASE ASSEMBLY,CONTROL(INDOOR) 4995A20832B
268714 PCB ASSEMBLY 6871A20387K
263230-2 THERMISTOR,NTC(ROOM+IN PIPE) 6323A20004N
263230-1 THERMISTOR,NTC(OUT PIPE) 6323AQ3226T 6323AQ3226T
267110 REMOTE CONTROLLER ASSEMBLY 6711A20128F
6711A20083R
3087A30004A
4681A20047B
4960A20016A
5211AR7066F
330870 PAN ASSEMBLY,DRAIN
346810 MOTOR,UNCLASSIFIED
349600 BRACKET,MOTOR
3087A30004A
4681A20047B
4960A20016A
5211AR7066F
35211B TUBE ASSEMBLY,TUBING
352150 HOSE ASSEMBLY,DRAIN
354210 EVAPORATOR ASSEMBLY,FIRST
359012 FAN,TURBO
5251AR1222R 5251AR1222R
5421A20072A
5900A00003A
5421A20072A
5900A00003A
NOTE) Please ensure GCSC since these parts may be changed depending upon the buyer's request.
*
(GCSC WEBSITE http://biz.LGservice.com)
Service Manual 83
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
Outdoor Unit
A3UH363FA0(LMU360HE), A3UC363FA0(LMU360CE)
84 Multi type Air Conditioner
Download from Www.Somanuals.com. All Manuals Search And Download.
Exploded View & Replacement Parts List
Parts List (A3UH363FA0(LMU360HE), A3UC363FA0(LMU360CE))
PART No.
LOCATION
No.
SVC
CODE
DESCRIPTION
A3UH363FA0(LMU360HE) A3UC363FA0(LMU360CE)
135301
135314
GRILLE,DISCHARGE
3530A20006G
3530A10176B
6323A20028A
6323A20026A
3041AP2741H
3551A10044G
3H03266H
3530A20006G
3530A10176B
6323A20028A
6323A20026A
3041AP2741H
3551A10044H
3H03266H
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
GRILLE,REAR
263230-1
263230-2
430410
THERMISTOR, NTC
THERMISTOR, NTC
BASE ASSEMBLY, OUTDOOR
COVER ASSEMBLY,CONTROL(OUTDOOR)
COVER ASSEMBLY,TOP(OUTDOOR)
PANEL ASSEMBLY,FRONT(OUTDOOR)
BARRIER ASSEMBLY,OUTDOOR
MOTOR ASSEMBLY,OUTDOOR
ACCUMULATOR ASSEMBLY(MECH)
TUBE ASSEMBLY,CONDENSER IN
TUBE ASSEMBLY, CONDENSER OUT
TUBE ASSEMBLY, REVERSING
TUBE ASSEMBLY, SUCTION(OUTDOOR)
CONDENSER ASSEMBLY, BENDING
FAN ASSEMBLY, PROPELLER
COIL ASSEMBLY, REVERSING VALVE
CASE ASSEMBLY,CONTROL(OUTDOOR)
PWB(PCB) ASSEMBLY,MAIN(AC)
PWB(PCB) ASSEMBLY,MAIN(OUTDOOR)
PANEL ASSEMBLY, SIDE
435511
435512
437211
3721A10109C
4791A10019B
4681AR1392X
4848A20006L
5211A11010A
5211A12001A
AJR30111101
AJR30125001
5403A20168A
5901A10033A
3A02028Z
3721A10109C
4791A10019B
4681AR1392X
4848A20006L
5211A11010A
5211A12001A
AJR30111101
AJR30125001
5403A20168C
5901A10033A
-
447910
546810
548490
552112
552113
552116
552117
554031
559010
561410
649950
4995A00002H
6871A20500B
6871A20479E
3721A10110A
3721A10111C
5220A20001K
2H02479J
4995A00002H
6871A20500B
6871A20479E
3721A10110A
3721A10111C
5220A20001K
2H02479J
668711-1
668711-2
137213-1
137213-2
552203-1
552203-2
554160-1
554160-2
561411-1
561411-2
561411-3
W0CZZ-1
W0CZZ-2
567502
PANEL ASSEMBLY, SIDE
VALVE,SERVICE
VALVE,SERVICE
COMPRESSOR
2520UHGK2AA
TBZ30111701
6877A20050A
6877A20050B
6877A20050C
0CZZA20007Q
2H01451S
2520UHGK2AA
TBZ30111701
6877A20050A
6877A20050B
6877A20050C
0CZZA20007Q
2H01451S
COMPRESSOR
DRAWING,ASSEMBLY(EEV COIL)
DRAWING,ASSEMBLY(EEV COIL)
DRAWING,ASSEMBLY(EEV COIL)
CAPACITOR,FILM,BOX
CAPACITOR,FILM,BOX
O.L.P
6750U-L048A
6750U-L048A
NOTE) Please ensure GCSC since these parts may be changed depending upon the buyer's request.
*
(GCSC WEBSITE http://biz.LGservice.com)
Solenoid(Coil Assembly, Reverse) is only for heat pump model.
Service Manual 85
Download from Www.Somanuals.com. All Manuals Search And Download.
May, 2006
Printed in Korea
P/No.: 3828A20474C
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Kyocera All in One Printer 500ci Series User Manual
LaCie DVD Player LaCinema Classic User Manual
Lasko Fan X30400 User Manual
LG Electronics Cell Phone 840H User Manual
LG Electronics Home Theater System BH6730S User Manual
Linksys Network Card WMP54GR User Manual
Makita Planer 10170 User Manual
Mattel Video Games 2448 0929 A User Manual
Meridian America Switch AC11 User Manual
Midland Radio Car Stereo System 120 320 CHANNEL UHF HIGH BAND MOBILE User Manual