Jotul Stove F 3 User Manual

Jøtul F 3 CB  
Woodstove  
....................................  
InstallationandOperatingInstructionsforUSA  
InstallationetfonctionnementpourCanada  
....................  
Safety notice: If this solid fuel room heater is not properly installed, a house fire may result. For  
your safety,follow the installation directions. Contact local building or fire officials about restrictions  
and installation inspection requirements in your area. Kindly save these instructions for future  
reference.  
Avis de sécurité: Une installation non appropriée de ce poêle de chauffage risque de provoquer un  
incendie. Assurez votre sécurité en respectant les directives d’installation suivantes. Consultez les  
autorités locales du bâtiment ou de la prévention des incendies au sujet des restrictions et exigences  
relatives aux inspections d’installations dans votre région.  
Tested and listed by ITS Intertek Testing Services, Middleton,Wisconsin.  
Tested to U.S. Standards: ANSI/UL 1482, Canadian Standards: CAN/ULC-S627-M93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARDS  
NOTICES  
·
BE SURE TO READ THIS ENTIRE  
MANUAL BEFORE YOU INSTALL OR USE  
YOUR NEW JØTUL F 3 CB WOOD STOVE.  
The F 3 CB wood stove has been tested and listed  
to;  
U.S. Standards: ANSI/UL 737 and ANSI/UL 1482.  
Canadian Standards: CAN/ULC-S627-M93  
·
IF THIS ROOM HEATER IS NOT  
PROPERLY INSTALLED, A HOUSE FIRE  
MAY RESULT. TO REDUCE THE RISK OF  
FIRE, FOLLOW THE INSTALLATION  
INSTRUCTIONS. FAILURE TO FOLLOW  
THESE INSTRUCTIONS MAY RESULT IN  
PROPERTY DAMAGE, BODILY INJURY, OR  
EVEN DEATH.  
Tests performed by ITS, Intertek Testing Services,  
Middleton, WI  
Manufactured by Jøtul A.S.A., P.O. Box 135  
Fredrikstad, Norway  
Distributed by Jøtul NorthAmerica, P.O. Box 1157  
400 Riverside Street  
·
·
Jøtul recommends that you have your new Jøtul  
F 3 CB installed by a professional installer of solid  
fuel burning appliances.  
Portland, ME 04104  
This heater meets the U.S. Environment Protection  
Agency’s Emissions limits for wood heaters  
manufactured and sold after July 1, 1990.  
EXTREMELY HOT WHILE IN OPERATION!  
KEEP CHILDREN, CLOTHING AND  
FURNITURE AWAY. CONTACT MAY  
CAUSE SKIN BURNS.  
Under specific test conditions, this heater has shown  
heat output at rates ranging from 11,500 to 43,500  
BTU’s per hour.  
·
Avoid creating a low pressure condition in the  
room where the stove is operating. Operating an  
exhaust fan or a clothes dryer could create a low  
pressure area, causing poisonous gases to come  
out of the stove into the room.  
The Jøtul F 3 CB wood is ONLY listed to burn  
wood . Do not burn any other fuels.  
JØTUL F 3 CB WOODSTOVE  
You can prevent low pressure conditions by  
providing adequate combustion air within 24” but  
not closer than 12” from the stove. Or, simply  
install the optional outside air manifold system,  
which allows the direct connection of air from  
outside the house to the stove.  
When installing, operating and maintaining your  
Jøtul F 3 CB woodstove, follow the guidelines  
presented in these instructions, and make them  
available to anyone using or servicing the stove.  
A number of areas require a building permit to install  
a solid fuel burning appliance. In the U.S., the  
National Fire ProtectionAssociation’s Code, NFPA  
211, Standards for Chimneys, Fireplaces, Vents  
and Solid Fuel Burning Appliances, or similar  
regulations, may apply to the installation of a solid  
fuel burning appliance in your area.  
·
·
Do not use chemicals or fluids to start the fire.  
Some fuels will, during combustion, separate  
carbon monoxide and generate it in the burn  
chamber. Carbon monoxide is toxic, so please  
follow the guidelines in this manual for proper  
operation of your Jøtul F 3 CB.  
If you for some reason experience smoke “roll-  
out” from the stove, it may activate smoke  
detectors if installed in the house.  
In Canada, the guideline is established by the CSA  
Standard, CAN/CSA-B365-M93, Installation  
Code for Solid-Fuel-Burning Appliances and  
Equipment. Always consult your local building  
inspector or authority having jurisdiction to  
determine what regulations apply in your area.  
DO NOT CONNECT THIS STOVE TO ANY  
AIR DISTRIBUTION DUCT OR SYSTEM.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
REAR EXIT VENTING  
INSTALLATION  
When rear exit venting is desired it will be necessary  
to “knock-out” the vent hole from the rear casting.  
IFTHISSOLIDFUELROOMHEATERISNOTPROPERLY  
INSTALLEDAHOUSEFIREMAYRESULT.FORYOUR  
SAFETY, FOLLOWTHEINSTALLATIONDIRECTIONS.  
CONTACTTHELOCALBUILDINGORFIREOFFICIALS  
ABOUT RESTRICTIONS AND INSTALLATION  
INSPECTION REQUIREMENTS IN YOUR AREA.  
Remove the top casting of the stove by removing the  
two 3mm set screws that secures the top to the sides.  
The set screws are located on the outside of the stove  
on the top of each side panel.  
Reminder:  
Using a 10mm wrench remove the double rear  
heatshields from the back of the stove. Remove the  
front door to avoid damage to the glass. Reminder:  
loss of the door washer will result in improper door  
alignment when reinstalling the door.  
Your local officials have final authority in  
determining if a proposed installation is acceptable.  
Any requirement, that is requested by the local  
authority having jurisdiction, that is not specifically  
addressedinTHISmanual,defaultstoNFPA211,  
and local codes in the U.S. or in Canada, CAN/  
CSA-B365-M and local codes.  
Using a claw hammer or a small sledge hammer  
strike the CENTER of the 6” “knock-out” disc from  
the OUTSIDE of the stove. The “knock-out” disc  
will break into four wedges and may need to be tapped  
INSTALLING THE VENTING  
The F 3 CB can be vented from the top, the rear or out. Touch up any remaining sharp edges with a file  
from either the right or left side. Follow the or hand grinder.  
instructions below for the desired venting location.  
NOTE: The IVORY F 3 CB’s ARE REAR  
TOP EXIT VENTING  
VENTED FROM THE FACTORY. IT IS NOT  
NECESSARY TO “KNOCK-OUT” THE REAR  
When top exit venting is desired, use a 3mm allen CASTING OF THE STOVE. HOWEVER, IF TOP  
wrench to remove the two set screws that secure EXIT IS DESIRED IT IS NECESSARY TO  
the top casting to the sides of the stove and lift off INSTALL A SMOKE OUTLET COVER ON THE  
the top casting. Lay the top casting on a flat surface REAR OUTLET OF THE STOVE.  
upside down and remove the 10mm bolt from the  
traverse bar and remove the smoke outlet cover.  
Reinstall the top casting, be sure to secure with the  
two set screws that were removed. See figure 1.  
SPACERS  
UPSIDE DOWN  
STOVE PIPE STOP  
TOP CASTING  
HEATSHIELD WITH  
LISTING LABEL  
SHOULD BE  
INSTALLED ON THE  
OUTSIDE  
FIGURE2  
Reinstall the top casting and front door, remembering  
the washer. The two rear heatshields MUST be  
reinstalled on the stove. Remove the metal cover  
plates from the heatshields and reinstall. Reminder:  
there is a small nut used as a spacer between the two  
heatshields. See figure 2.  
TRAVERSE BAR SECURING  
STOVE PIPE STOP  
SMOKE OUTLET COVER  
TO TOP CASTING  
FIGURE1  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SIDE EXIT VENTING  
STOVE PIPE  
CHIMNEY CONNECTOR  
If venting through the side is desired it will be  
necessary to remove the top casting. Using a 3mm  
allen wrench remove the two set screws that secure  
to the top to the side panels. Remove the front door  
to avoid damage to the glass. Reminder: loss of the  
door washer will result in improper door alignment  
when reinstalling the door.  
The chimney connector is a single walled pipe used  
to connect the stove to the chimney. For use with the  
F 3 CB the chimney connector MUST be 6” in  
diameter, with a minimum thickness of 24 gauge black  
steel.  
Aluminum and Galvanized steel pipe is not acceptable  
for use with the F 3 CB. These materials cannot  
withstand the extreme temperatures of a wood fire  
and can give off toxic fumes when heated.  
Using a claw hammer or a small sledge hammer strike  
the CENTER of the 6” “knock-out” disc from the  
INSIDE of the stove. The “knock-out” disc will break  
into four wedges and may need to be tapped out.  
Touch up any remaining sharp edges with a file or  
hand grinder. Reinstall the front door, remembering  
the washer and the top casting.  
Each chimney connector or stove pipe section must  
be installed to the stove flue collar and to each other  
with the male (crimped) end toward the stove. See  
figure 5.  
INSTALLING THE STOVE PIPE ADAPTER  
This prevents any amount of condensed or liquid  
creosote from running down the outside of the pipe  
or the stove top. All joints, including the flue collar  
connection must be secured with three sheet metal  
screws to ensure that the sections do not separate.  
After the appropriate flue outlet in the stove has been  
established the stove pipe adapter (included with every  
stove) must be installed so that standard stove pipe  
can be installed onto the stove.  
Insert the end of the adapter with the four holes into  
the stove. These holes allow the adaptor to be  
attached to the stove’s internal collar, using the nuts  
and bolts provided with the stove. See figure 3.  
crimped end installed  
toward the stove  
FIGURE5  
DIRECTION INTO  
THE STOVE  
For the best performance the chimney connector  
should be as short and direct as possible, with no more  
than two 90° elbows. The maximum horizontal run is  
36” and a recommended total length of stove pipe  
should not exceed 10 feet. Always slope horizontal  
runs upward ¼” per foot toward the chimney.  
FIGURE3  
The adaptor should be inserted into the stove until the  
bead on the adapter is flush with the top, back or side  
casting. Now the adaptor is ready to accept single or  
double walled stove pipe. See figure 4.  
No part of the chimney connector may pass through  
an attic or roof space, closet or other concealed space,  
or through a floor or ceiling. All sections of the  
chimney connectors must be accessible for cleaning.  
Where passage through a wall or partition of  
combustible construction is desired, the installation  
must conform with NFPA 211 or CAN/CSA-B365,  
and is also addressed in this manual.  
Each joint of chimney connector or stove pipe must  
be secured with at least three sheet metal screws to  
ensure that the sections do not seperate.  
ADAPTOR BEAD  
SHOULD BE FLUSH  
WITH STOVE  
DO NOT CONNECT THIS UNIT TO A  
CHIMNEY FLUE SERVICING ANOTHER  
APPLIANCE.  
FIGURE4  
Do not use the connector pipe as a chimney.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHIMNEY REQUIREMENTS  
Masonry Chimneys  
There are two types of chimneys suitable for the  
F 3 CB:  
When installing the F 3 CB into a masonry chimney  
you must conform to all of the following guidelines:  
1. A code- approved masonry chimney with a flue  
liner.  
·
·
The masonry chimney must have a fireclay liner  
or equivalent, with a minimum thickness of  
5/8” and must be installed with refractory mortar.  
There must be at least ½” air space between  
the flue liner and chimney wall.  
2. A prefabricated chimney complying with the  
requirements for Type HT (2100°F) chimneys  
per UL 103 or ULC S629.  
The fireclay flue liner must have a nominal size  
of 8” X 8”, and should not be larger than  
8”X 12”. If a round fireclay liner is to be used it  
must have a minimum inside diameter of 6” and  
not larger than 8” in diameter. If a chimney with  
larger dimensions is to be used, it should be  
relined with an appropriate liner that is code  
approved.  
The chimney size should not be less than the cross-  
sectional area of the flue collar, and not more than  
three times greater than the cross-sectional area of  
the flue collar.  
When selecting a chimney type and the location for  
the chimney in the house, keep this in mind: it is the  
chimney that makes the stove work, NOT the stove  
that makes the chimney work. This is because a  
chimney actually creates a suction, called “draft”  
which pulls air through the stove.  
·
The masonry wall of the chimney, if brick or  
modular block, must be a minimum of 4” nominal  
thickness. A mountain or rubble stone wall must  
be at least 12” thick.  
Several factors affect draft: chimney height, cross-  
sectional area (size), and temperature of the chimney,  
as well as the proximity of surrounding trees or  
buildings.  
·
·
A newly-built chimney must conform to local  
codes and in their absence must recognize  
national regulations.  
As a result, a short masonry chimney on the exterior  
of a house will give the poorest performance. This  
is because it can be very difficult to warm the  
chimney thereby creating inadequate draft. In  
extremely cold northern areas it may be necessary  
to reline the chimney or extend its height to help  
establish draft.  
When using an existing chimney, it must be  
inspected by a professional licensed chimney  
sweep, fire official, or code officer, to ensure  
that the chimney is in proper working order.  
·
·
No other appliance can be vented into the same  
flue.  
Oppositely, a tall masonry chimney inside the house  
is easier to keep warm and will perform the best.  
An airtight clean-out door should be located at  
the base of the chimney.  
The following guidelines give the necessary chimney  
requirements based on the national code (ANSI-  
NFPA 211for the US. And CSA CAN-B365 for  
Canada). However, many local codes differ from  
the national code to take into account climate,  
altitude, or other factors. It is important that you  
check with your local building officials to find out  
what codes apply in your area before installing your  
new F 3 CB.  
Prefabricated Chimneys  
If a prefabricated metal chimney is to be used it  
must be a chimney type that is tested and listed for  
use with solid fuel burning appliances. High  
Temperature (HT) Chimney Standard UL 103 for  
the U.S. and High Temperature Standard ULC  
S-629 for Canada.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
The manufacturer’s installation instructions must be WALL PASS-THROUGHS  
followed precisely. Always maintain the proper  
clearance to combustibles as established by the pipe When your installation unavoidably requires the  
manufacturer. This clearance is usually a minimum chimney connector to pass through a combustible wall  
of 2”, although it may vary by manufacturer or for to reach the chimney, always consult your local  
certain chimney components.  
building officials, and be sure any materials to be used  
have been tested and listed for wall pass-throughs.  
Chimney Height  
In the U.S.  
Whether a masonry chimney or prefabricated metal  
chimney is used it must be the required height above  
the roof line.  
The National Fire ProtectionAssociation’s publication,  
NFPA 211, Standard for Chimneys, Fireplaces,  
Vents and Solid Fuel Burning Appliances permits  
four methods for passing through a combustible wall.  
Before proceeding with any method be sure to consult  
with your local building officials to discuss any local  
code requirements.  
The requirement is:  
The chimney must be at least 3 feet higher than the  
highest point where it passes through the roof and at  
least 2 feet higher than the highest part of the roof or  
structure that is within 10 feet of the chimney,  
measured horizontally. See figure 6.  
Common Method  
When passing through a combustible wall to a  
masonry chimney this method requires the removal  
of all combustible materials from at least 12” around  
the chimney connectors proposed location. With a 6”  
round liner the minimum area required would be 31”  
x 31” square.  
The space is then filled with at least 12” of brick  
around a fireclay liner. Remember, the liner must be  
ASTM C35 or equivalent, with a minimum wall  
thickness of 5/8”.  
It is important to remember to locate the pass-through  
at least 18” from the ceiling for proper clearance to  
combustibles.  
FIGURE6  
It will be necessary to cut wall studs, install headers,  
and construct a sill frame to maintain the proper  
dimensions and to support the weight of the brick.  
Chimneys shorter than 14 feet may not provide  
adequate draft. This could result is smoke spilling  
into the room from the stove when loading the stove,  
or when the door is open. In addition, inadequate  
draft can cause back puffing, which is a build up of  
gases inside the firebox.  
The bricks must be solid brick with a minimum of  
3 ½ “ thick (4” nominal).  
Refractory mortar must be used at the junction of the  
chimney and the pass-through liner. The pass-through  
liner must not penetrate the chimney liner beyond the  
inner surface of the chimney liner. Use extreme care  
when constructing the hole in the chimney liner, the  
tiles can shatter easily. See figure 7.  
Other times, chimney height can create excessive  
draft which can cause high stove temperatures and  
short burn times. Excessive drafts can be corrected  
by installing a butterfly damper. If you suspect you  
have a draft problem, consult your dealer.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Consult your local building inspector, authorized Jøtul  
Dealer, NFPA 211 in the U.S. or CAN/CSA-B635  
in Canada for other approved wall pass-through  
methods.  
CONNECTING TO THE CHIMNEY  
Masonry Chimney  
When installing a F 3 CB into a masonry chimney  
through a “thimble”(the opening through the chimney  
wall to the flue), the thimble must be lined with ceramic  
tile or metal and be securely cemented in place.  
The chimney connector/stove pipe must slide  
completely inside the thimble to the inner surface or  
the flue liner. It may be necessary to make use of a  
thimble sleeve (a pipe with a slightly smaller diameter  
than standard stove pipe). This special pipe can be  
easily installed into a thimble. See figure 8.  
FIGURE7  
In Canada  
The Canada the standard has been established by the  
Canadian Standard Association. The installation must  
conform to CAN/CSA-B365, Installation Code for  
Solid Fuel Burning Appliances and Equipment.  
Before proceeding be sure to consult your local  
building inspector.  
Make sure the connector pipe or thimble sleeve does  
not protrude into the flue liner, thereby restricting the  
area the smoke has to flow through. This bottle-neck  
will have a negative affect on the chimney system.  
The chimney connector should be sealed at the thimble  
with refractory cement and the stove pipe leading to  
the stove should have a minimum of three screws.  
Common Method  
This method requires the removal of all combustible  
materials from at least 18” (457mm) around the  
chimney connector’s proposed location. With a 6”  
round liner the minimum area required would be  
43” x 43” square.  
DO NOT CONNECT THIS STOVE TO A  
CHIMNEY FLUE SERVICING ANOTHER  
APPLIANCE OF ANY KIND.  
Connector pipe shall  
be flush with the  
It is important to remember to locate the pass-through  
at least 25” from the ceiling to maintain the proper  
clearance to combustibles.  
inside of the flue tile  
The space that is cleared of combustible materials  
must then remain empty. Sheet metal panels can then  
be used to cover the area. However, when using a  
panel on both sides of the wall each cover must be  
installed on noncombustible spacers at least 1” from  
the wall. If one panel of sheet metal is to be used it  
may be installed flush to the wall.  
Stove pipe  
connector  
Flue tile  
SEE SECTION 5.3.1 and 5.3.2 of CAN/CSA -  
B365-M91.  
Thimble  
FIGURE8  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hearth-mount into a Masonry Fireplace  
Fireplace installation must also observe the proper  
clearances to surrounding trim and mantels (addressed  
The F 3 CB may be installed into a masonry fireplace in clearance section of this manual). In addition,  
provided the opening is a minimum of 28 1/2” high. fireplace installations must also adhere to the floor  
The short leg package reduces the stove’s height by protection guidelines specified in the following section.  
2 1/4”.  
When installing the F 3 CB into a masonry fireplace,  
code requires that the fireplace damper plate be  
removed or securely fixed in the open position. A  
connector pipe must then extend from the stove’s flue  
exit through the damper area of the fireplace and into  
the chimney tile liner. See figure 9.  
The inside area of the flue liner must not be less than  
the area of the stove’s flue exit, and cannot be more  
than three times greater than the cross sectional area  
FIGURE  
10  
of the stove’s flue exit.  
Prefabricated Chimneys  
If the chimney liner is too large to accommodate the  
stove, an approved relining system must be installed  
to resize the flue.  
When installing the F 3 CB to a prefabricated metal  
chimney always follow the pipe manufacture’s in-  
structions and be sure to use the components that are  
required. This usually includes some type of “smoke  
pipe adapter” that is secured to the bottom section of  
the metal chimney and allows the chimney pipe to be  
secured to it with three sheet metal screws.  
See figures 10 and 11.  
A new sheet metal damper block-off plate must be  
installed around the connector pipe at the damper  
frame and sealed with the proper sealant (usually  
High-Temp Silicone).  
TILE LINER  
CONNECTOR EXTENDS  
TO FIRST FLUE TILE  
DAMPER OPENING IS  
SEALED WITH SHEETMETAL  
PLATE AND SEALANT  
FIGURE9  
FIGURE11  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
CLEARANCES TO COMBUSTIBLES  
Floor Protection  
Clearances to walls and ceilings  
The following clearances have been tested to UL and  
ULC standards and are the minimum clearances  
specifically established for the Jøtul F 3 CB.  
Floor protection under the F 3 CB woodstove, must  
be one of the following:  
The following charts and diagrams give the required  
clearances you must maintain when installing the F 3  
CB near combustible surfaces.  
1. Any non combustible material with an insulative  
R value of 1.1.  
A combustible surface is anything that can burn (i.e.  
sheet rock, wall paper, wood, fabrics etc.). These  
surfaces are not limited to those that are visible and  
also include materials that are behind non-combustible  
materials.  
2. Any UL, ULC or WH hearth board or  
prefrabricated non-combustible material.  
The bottom heatshield (standard equipment) is  
required in all installations.  
If you are not sure of the combustible nature of a  
Individual sections of floor protection must be material, consult your local fire officials.  
mortared together to prevent sparks from falling  
Remember: “Fire Resistant” materials are considered  
through to combustible materials. Any carpeting must  
combustible; they are difficult to ignite, but will burn.  
be removed from under the floor protection.  
Also “Fire-rated” sheet rock is also considered  
combustible.  
In the U.S.and Canada  
Contact your local building officials about restrictions  
and installation requirements in your area.  
The F 3 CB must be installed on a non-combustible  
surface extending a minimum of 18” (460mm) in front  
of the stove and 8” (200mm) on the remaining sides  
of the stove (measured from side and back panels).  
Using Shields to Reduce Clearances  
Pipe shields: When using listed pipe shields to reduce  
the connector clearance to combustibles, it must start  
1” above the lowest exposed point of the connect  
pipe and extend vertically a minimum of 25” above  
the top surface of the stove.  
This will result in a minimum floor protection of  
41 D X 39 W See figure 12.  
In a rear vent installation the floor protection must  
also extend under the stove pipe a minimum of 2”  
(50mm) beyond either side of the pipe.  
Double wall pipe: Listed double wall pipe is an  
acceptable alternative to connector pipe heatshields.  
Wall-Mounted Protection: When reducing clearances  
through the use of wall mounted protection:  
8”  
200mm  
In the U.S. refer to NFPA 211, Standard for  
Chimneys, Fireplaces, Vents and Solid Fuel  
Burning Appliances, for acceptable materials,  
proper sizing and construction guidelines.  
8”  
200mm  
8”  
200mm  
41”  
DEEP  
In Canada, refer to CAN/CSA-B365, Installation  
Code for Solid-Fuel Burning Appliances and  
Equipment, also for acceptable materials, proper  
sizing and construction guidelines.  
18”  
460mm  
front  
Stove mounted Rear Heatshield is standard equipment  
on all F 3 CB woodstoves. NO OTHER STOVE  
MOUNTED HEAT SHIELD MAY BE USED.  
39”  
WIDE  
FIGURE12  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F 3 CB WOODSTOVE CLEARANCES*  
STOVE CLEARANCES  
TOP VENT/VERTICAL  
UNPROTECTED SURFACES  
PROTECTED SURFACES  
per NFPA 211 or CAN/CSA-B365-M  
SIDE  
24"  
REAR  
25"  
CORNER SIDE  
REAR  
14"  
CORNER  
10"  
Rear heatshield with  
Single wall pipe  
18"  
10"  
610 mm  
635 mm  
460 mm  
255 mm  
355 mm  
255 mm  
Rear heatshield with  
18"  
10"  
14"  
6"  
6"  
6"  
Double wall pipe or shields 460 mm  
255 mm  
355 mm  
150 mm  
150 mm  
150 mm  
STOVE CLEARANCES  
UNPROTECTED SURFACES  
PROTECTED SURFACES  
REARVENT/HORIZONTAL  
per NFPA 211 or CAN/CSA-B365-M  
SIDE  
24”  
REAR  
25”  
CORNER SIDE  
REAR  
25”  
CORNER  
18”  
Rear heatshield with  
Single wall pipe  
20”  
10”  
610 mm  
635 mm  
510 mm  
255 mm  
635 mm  
460 mm  
Rear heatshield with  
18”  
14”  
17”  
6”  
6”  
6”  
Double wall pipe or shields 460 mm  
355 mm  
430 mm  
150 mm  
150 mm  
150 mm  
CONNECTOR  
CLEARANCES  
UNPROTECTED SURFACE  
PROTECTED SURFACE  
per NFPA 211 or CAN/CSA-B365-M  
Single wall pipe-vertical installations  
Double wall pipe-vertical installations  
Single wall pipe-horizontal installations  
Double wall pipe-horizontal installations  
18" (460mm)  
pipe mfgr. listing  
18” (460mm)  
6" (150mm)  
pipe mfgr. listing  
9” (230mm)  
pipe mfgr. listing  
pipe mfgr. listing  
VERY IMPORTANT:  
MANTEL CLEARANCES  
Top Vent - Vertical: assumes the connector pipe  
runs from the top of the stove and travels vertically.  
If top vented to a horizontal run, the stove position  
is dictated by the connector pipe clearances.  
A
B
C
Rear Vent - Horizontal: assumes the connector  
pipe extends from the rear of the stove and travels  
horizontally to the chimney. If rear vented to a  
vertical run, the stove position is dictated by the  
connector pipe clearances.  
D
Dimensions in Inches represent U.S. requirements.  
Dimensions in Millimeters represent Canadian  
requirements.  
A=ToptoMantel  
34”  
20”  
13”  
24’  
860mm  
510mm  
330mm  
610mm  
B = Top to Top Trim  
C = Side to Side Trim  
D = Side to Side Wall:  
WALL PROTECTION IS DISCUSSED IN FURTHER  
DETAIL ON PAGE 12 OF THIS MANUAL.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL SHIELDS FOR CLOSE CLEARANCE  
WALL SHIELD  
COMBUSTIBLE  
WALL  
&
Must be 30” wide and  
centered behind the  
stoveꢀꢁꢁ  
Must be 1” off the wall  
and 1” off the floor.  
With standard legs, the  
shield must be 32” high.  
With optional short legs,  
the shield must be 30”  
high.  
&20%867,%/(ꢀ  
:$//ꢀ  
WALL SHIELD  
The wall shield must extend a  
minimum of 4(1 02mm) p ast  
the side of the stove.  
Must be 1off the wall  
and 1off the floor.ꢀ  
With standard legs, the  
shield must be 40high.ꢀ  
With optional short legs,  
the shield must be 38”  
high.ꢀ  
The wall shield must extenda  
mini mu m of 4(102mm) past the  
Both shields MUST  
extend and join in the  
cornerꢁꢀ  
ash lip of the stove.  
&20%867,%/(:  
WALL  
WALL SHIELD  
The wall shield must  
extend a minimum of  
12(305mm) past the  
front corner of the stove.ꢀ  
Must be 1off the wall  
and 1off the floor.ꢀ  
With standard legs, the  
shield must be 40highꢁꢀ  
With the optional short  
legs, the shield must be  
38high.ꢀ  
Both shields must  
extend and join in the  
corner.ꢀ  
The wall shield must  
extend a minimum of 12(305mm)  
past the front corner of the stove.ꢀ  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM PROTECTED ALCOVE:  
NOTICE  
Accessories for woodstoves for clearance reduction have  
been developed by many manufacturers. If not following  
the methods of the installation codes, be sure that any  
accessory you choose has been tested by an independent  
laboratory and carries the laboratory’s testing mark.  
Make sure to follow all of the manufacturer’s  
instructions.  
Assumes-  
top exit, double wall pipe, and stove’s rear heatshield.  
Minimum alcove width = 35” (890mm)  
Maximum alcove depth = 24” (610mm)  
Height above the top of the stove = 40” (1015mm)  
Always contact your local building inspector or fire  
officials about restriction and requirements in your area.  
Reminder, it is the local officials who have final authority  
in the installations approval.  
In a PROTECTED alcove installation both side walls  
and rear wall must be protected per NFPA 211 or  
CAN/CSA-B365. The wall protection must be  
elevated 1” from the floor and at least 1” off the  
combustible wall to allow for an air-flow.  
ALCOVE  
The F 3 CB is approved for installations in an  
unprotected and protected ALCOVE provided the  
following guidelines are followed: Stoves must be  
positioned as shown in figures 13 or 14.  
6”  
150mm  
Alcove floor protection must be: a UL/ULC or WHI  
listed hearth board OR a non cmbustible material with  
a minimum R value of 1.1.  
35” min.  
890mm  
10”  
255mm  
MINIMUM UNPROTECTED ALCOVE:  
6”  
Assumes-  
150mm  
top exit, single wall pipe, and stove’s rear heatshield.  
FIGURE 14  
max. depth  
24” (610mm)  
Minimum alcove width = 71” (1805mm)  
Maximum alcove depth = 40” (1015mm)  
Height above the top of the stove = 68” (1730mm)  
24”  
610mm  
REAR EXITALCOVE INSTALLATIONS:  
Unprotected alcove: assumes single wall pipe and  
stove’s rear heatshield.  
71” min.  
(1805mm)  
25”  
635mm  
Minimum alcove width = 71” (1805 mm)  
Maximum alcove depth = 40” (1015mm)  
Alcove ceiling above top of stove = 68” (1730mm)  
24”  
610mm  
Protected alcove: assumes double wall pipe and  
stove’s rear heatshield.  
FIGURE 13  
max. depth  
40” (1015mm)  
Top vent/vertical- assumes the connector pipe is  
exiting off the top of the stove and traveling vertically.  
If top vented to any horizontal runs –the stove’s  
position is dictated by the connector pipe clearances.  
Minimum alcove width = 35” (890mm)  
Maximum alcove depth = 30” (760mm)  
Alcove ceiling above top of stove = 40” (1015mm)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING:  
DONOTINSTALLINABEDROOM/SLEEPING  
ROOM. THE STRUCTURAL INTEGRITY OF THE  
MOBILE HOME’S FLOOR, WALL, CEILING/ROOF  
MUST BE MAINTAINED.  
OPERATION  
Before building a fire in your new F 3 CB, please  
read the following section carefully and completely.  
FIGURE15  
Do Not Burn  
First this stove is designed to burn natural wood ONLY,  
wood that has been air-dried for a period of 6 to 14  
months will provide the cleanest most efficient heat.  
PRIMARY AIR CONTROL  
FAR LEFT = LESS AIR,  
START-UP AIR CONTROL  
Do not burn:  
LEFT = CLOSED POSITION  
RIGHT = OPEN POSITION  
DIMINISHING THE HEAT OUTPUT  
FAR RIGHT = INCREASES AIR  
SUPPLY AND HEAT OUTPUT.  
*Coal  
*Treated or painted wood  
*Chemical Chimney cleaners  
*Colored paper  
*Garbage  
*Cardboard  
*Solvents  
*Any synthetic fuel or logs  
When first starting a fire: the primary control lever  
should be at the far right position, and the start-up  
air lever should be in the far right position. This will  
allow for the maximum amount of air to enter the  
stove and assist in starting the fire quickly and most  
effectively.  
The burning of any of these materials can result in  
the release of toxic fumes. Never use gasoline,  
gasoline-type lantern fuel, kerosene, charcoal lighter  
fluid, or similar liquids to start or “freshen-up” the  
fire. Always keep such liquids away from the heater  
at all times.  
Once the fire is established the start-up air lever  
should be closed and the primary air lever  
should be adjusted according to the amount of  
heat desired.  
IMPORTANT  
NEVER BUILD OR ALLOW THE FIRE TO REST DIRECTLY  
ON THE GLASS. THE LOGS SHOULD ALWAYS BE SPACED  
AT LEAST ONE INCH FROM THE GLASS TO ALLOW FOR  
PROPER AIR FLOW WITHIN THE STOVE.  
Remember: the more air entering the stove the hotter  
the fire the shorter the burn time. Moving the primary  
air lever to the left reduces the air-flow into the stove  
which prolongs the fire at a lower heat output. See  
figure 15.  
Controls on the F 3 CB  
There are two air controls on the F 3 CB woodstove.  
Breaking in your new stove  
The primary air control lever is located on the front  
of the stove in the top right corner. The primary air  
lever controls the amount of air that enters the stove  
for combustion.  
Your new F 3 CB is constructed of cast iron and  
stove furnace cement. This type of construction  
requires the stove to be “broken-in” gradually so that  
heat expansion does not occur too quickly and cause  
damage.  
The start-up air control lever is located below the  
glass in the center of the front door. This control is  
for “start - up” air only and should not be used to  
freshen an existing fire or during refueling. Never  
leave the stove unattended while this control is open,  
overfiring could result which can damage the  
appliance. See figure 15.  
To monitor the stove’s temperature, Jøtul  
recommends the use of a magnetic stove-top  
thermometer, placed directly on the corner of the  
stove’s top plate.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Complete the following steps for the proper break-in with several sheets of crumbled newspaper placed  
procedure for the F 3 CB:  
directly on the grate. On top of the newspaper, place  
several pieces of small dry kindling (approx. 1” in  
1. Light a small fire, newspaper and kindling only, diameter) with two to three larger logs (approx. 3” to  
only allow the stove to reach a maximum surface 5” in diameter) on top.  
temperature of 200°. Burn for approximately 1  
hour.  
Light the fire and close the door, slowly building the  
2. Allow stove to cool to room temperature.  
fire by adding larger and larger logs. Close the start-  
3. Light a second fire, allowing the stove to reach up air contrlo lever after the fire is established  
a maximum temperature of 300° for 1 hour.  
4. Cool the stove to room temperature.  
and new fuel lights easily. Be sure to follow the  
break-in procedure before creating a fire that will  
5. Light a third fire and gradually allow the stove damage the stove.  
to reach a surface temperature of 400°  
6. Cool stove to room temperature. This Once the stove has reached a surface temperature  
completes the “break-in” procedure.  
range of between 400° and 600°, adjust the primary  
air control lever as necessary to generate the heat  
output and burn time desired.  
Never allow the stove to exceed a 400° surface  
temperature during any “break-in fire” with the  
exception of the last “break-in” fire.  
Jøtul recommends the use of a magnetic stove top  
thermometer to monitor the surface temperature of  
the stove. The optimum surface temperature range  
for the most efficient burn is between 400° and 600°.  
See figure 16 below for the optimum locations of a  
stove-top thermometer.  
Note: IT IS NORMAL for a new painted stove to  
emit an odor and even smoke during its first several  
fires. This is caused by the seasoning of the high  
temperature paint and will diminish with each fire and  
will eventually disappear. Opening a window or door  
to provide additional ventilation will reduce the odor  
as this process takes its course.  
NEVEROVERFIRETHESTOVE.  
IFANYPARTOFTHESTOVEORCHIMNEY  
GLOWS, YOU ARE OVERFIRING, AND A HOUSE  
FIRE OR SERIOUS DAMAGE TO THE STOVE OR  
CHIMNEYCOULDRESULT.IMMEDIATELYCLOSE  
DOWN THE AIR CONTROL IF YOU NOTICE THIS  
CONDITION.  
stove top  
thermometer  
stove top  
thermometer  
FIGURE16  
Adding Fuel  
Starting and Maintaining a Fire  
When reloading the stove while it is still hot and a  
bed of hot embers still exist, follow this reloading  
procedure:  
Burn only solid wood directly on the bottom  
grate of the stove, do not elevate the fire in any  
way.  
·
·
Always wear gloves when tending to the stove.  
Push the air control lever to the full open position  
(far right).  
The ash pan door on the stove must always be  
securely closed when the stove is in operation.  
·
·
Wait a few seconds before opening the door.  
Use a stove tool or poker to distribute the hot  
embers equally around the firebox.  
Burning the stove with the ashpan open will over-fire  
the stove and cause interior damage.  
·
·
·
Load the fuel, usually with smaller logs first.  
Close the door, be sure to latch the door tightly.  
Wait 5 – 10 minutes before adjusting the primary  
air to the desired heat output setting.  
With the primary air control lever and the start-up air  
control lever in the full open position (far right), start  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(If you have at least a 2” thick ember bed when The ashes should be placed in a metal container  
reloading, it may be possible to close the door equipped with a tight sealing lid. The container should  
and immediately adjust the air control setting).  
be placed on a noncombustible floor or on the ground,  
well away from all combustible materials, pending final  
disposal. If the ashes are disposed of by burial in soil  
or otherwise locally dispersed, they should be retained  
The Formation of Creosote  
When wood is burned slowly and at low temperatures, in the closed container until all cinders have thoroughly  
it produces tar and other organic vapors, which cooled.  
combine with moisture to form creosote. The slow  
moving smoke carries the creosote vapors, which  
Glass Care:  
condense in the cooler chimney flues, and this  
Cleaning: On occasion it will be necessary to clean  
creosote then sticks to the chimney walls.  
the carbon deposits and fly ash off of the glass. If the  
carbon and fly ash are allowed to remain on the glass  
The creosote that accumulates in the chimney is  
for an extended period of time it could eventually cause  
highly flammable and is the fuel of chimney fires. To  
the glass to become etched and cloudy. Any creosote,  
prevent chimney fires it is important to have the  
which might deposit on the glass, will burn off during  
chimney and chimney connector pipe inspected and/  
the next hot fire.  
or cleaned semi-annually. Aqualified chimney sweep  
The proper cleaning procedure is as follows:  
or other authorized service person can provide this  
service.  
1. Glass needs to be COMPLETELY COOL.  
2. Only use a cleaner that is specifically designed  
It is also important to remember that chimney size,  
for this purpose. The use of abrasives will damage  
temperature and height all affect draft which in turn  
the glass and ultimately leave the glass frosted.  
affects the formation of creosote. Be sure to follow  
3. Rinse and dry glass completely, before burning  
the installation and operation guidelines established  
your stove.  
in this manual.  
IMPORTANT:  
REPLACE GLASS ONLY WITHA CERAMIC  
MAINTENANCE  
GLASS PANEL SPECIFICALLY DESIGNED  
Ash remomal  
PROTECTION ALWAYS WEAR SAFETY  
GLOVES WHEN HANDLING THE ASH PAN.  
:
OF COURSE, FOR YOUR  
FOR THE JØTUL F 3 CB. DO NOT USE SUB-  
STITUTES. REPLACEMENT GLASS PAN-  
ELS CAN BE ORDERED THROUGH YOUR  
JØTUL DEALER.  
Ash removal will be required periodically depending  
on how frequently the stove is used. Conveniently,  
the F 3 CB is equipped with an ash pan assembly for  
easy ash removal, without the need for opening the  
front doors.  
Glass Removal: Always operate the doors slowly  
and cautiously to avoid cracking or breaking the glass.  
Never use the door to push wood into the firebox. If  
the glass becomes cracked or broken follow this  
procedure for replacement:  
The ash pan door is located under the front ashlip of  
the stove. To open the ash door insert the pin on the  
end of your specially designed ash tool into the hole  
on the ash door latch. Rotate the door  
counterclockwise to unlatch the door and clockwise  
to latch the door.  
NEVER OPERATE THE STOVE WITH A  
CRACKED OR BROKEN GLASS PANEL.  
1. Remove the door from the stove and place on a  
flat surface.  
2. Carefully remove all of the glass clips from the  
inside of the door.  
Remove the ash pan. When the stove is in operation  
always close the ash pan door before leaving to  
dispose of the ashes.  
3. Gently remove all pieces of the glass panel and  
gasketing.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Remove all remaining debris from the glass area  
using a wire brush.  
5. Apply a small bead of gasket/stove cement and  
the new gasket. Do not overlap the ends of the  
gasket rope.  
6. Center the new glass panel over the gasket and  
reinstall the glass clips. See figure 17.  
IMPORTANT: The side of the glass treated with an  
infrared coating (marked on the perimeter) should  
always be facing outward. It is extremely impor-  
tant to tighten the glass clips slowly and in a  
repeating pattern, like tightening the lugs on an  
automobile wheel.  
Gaskets  
Check door and window gaskets for tightness.  
To check the seal of the front doors, close and  
latch the doors on a dollar bill and slowly try to  
pull the dollar bill free. If it can be easily removed  
then the seal is too loose. Check several spots  
around the door, and repeat the procedure on the  
ash pan door as well.  
If gaskets need to be replaced, scrape out the old  
gasket and cement and clean the area with a wire  
brush. Apply a small bead of cement and push in  
the new gasket. After closing and latching the  
doors wipe clean, any excessive cement that has  
come from beneath the gasketing.  
7. It may be necessary to retighten the glass clips  
after the stove has be burned and the gasketing  
has been seated.  
door  
gasket  
GASKET LIST FOR THE F 3 CB  
glass  
Description  
Order #  
100038  
128213  
200024  
200028  
200024  
200028  
Size  
Length  
TopPlateGasket  
Ash Housing Gasket  
Ash Door Gasket  
Glass Gasket  
Door Gasket  
Air manifold Gasket  
3/8” LD  
sheet gasket  
¼” LD  
3/16” LD  
1/4” LD  
3/16”  
5'6”  
FIGURE17  
glass clips  
3'  
3’6”  
5'  
16”  
General Maintenance  
Like your car, regular maintenance prolongs the life The F 3 CB is designed to burn cleanly and efficiently  
of your appliance. The following procedures do not when used according to the guidelines expressed in  
take long and are generally inexpensive, but when these operating instructions. However, to maintain  
done consistently, increase the life of your appliance the proper performance, a yearly chimney inspection  
and in turn, increase your years of enjoyment.  
and cleaning in necessary. Failure to keep the chimney  
system free of creosote and build up could result in a  
At least once a year you should perform the following serious chimney fire.  
maintenance procedures:  
Thoroughly clean the stove. Enamel surfaces  
should be cleaned with soap and water.  
Empty stove of all soot and ashes. Only use a  
vacuum for this job if the vacuum is specifically  
designed for ashes.  
Inspect the stove; using a strong light inspect the  
stove inside and out for cracks or leaks. Replace  
all cracked parts and repair any cement leaks  
with furnace cement.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
MAINTENANCE LOG  
DATE:  
Many accessories have been manufactured for use  
with the Jøtul F 3 CB. ONLY USE ACCESSORIES  
THAT ARE SPECIFICALLY DESIGNED FOR  
THE JØTUL F 3 CB.  
SERVICEPERFORMED:  
Firescreen (part # 350168)  
BY:  
The F 3 CB has been approved for use as an open  
fireplace, with front door open. This feature is  
especially nice when the ambience of a fire is desired.  
Some care should be taken when operating the stove  
as a fireplace.  
DATE:  
SERVICEPERFORMED:  
·
·
·
Always have the firescreen in place, attached to  
the stove front.  
Never over load the stove, for the best appearance  
burn in the traditional three log configuration.  
Reminder, when burning the stove with the screen  
in place, you are sacrificing efficiency for  
aesthetics, and you will be consuming wood at a  
much faster rate.  
BY:  
DATE:  
SERVICEPERFORMED:  
WARNING: OPERATE YOUR JØTUL F 3 CB  
WITH THE FRONT DOOR FULLY OPEN AND  
THE FIRESCREEN IN PLACE OR FULLY  
CLOSED. A PARTIALLY OPENED DOOR MAY  
RESULT IN OVERFIRING. ALSO, IF THE  
DOOR IS LEFT PARTLY OPEN, GAS AND  
FLAME MAY BE DRAWN OUT OF THE STOVE  
OPENING, CREATING RISKS FROM BOTH FIRE  
AND SMOKE.  
BY:  
DATE:  
SERVICEPERFORMED:  
Floor Bracket Kit (part #750304)  
The optional Floor Bracket Kit can be used in the  
event the stove needs to be secured to the floor.  
Complete installation instructions and diagrams are  
supplied with each Floor Bracket Kit.  
BY:  
DATE:  
SERVICEPERFORMED:  
Stove-Top Thermometer (part # 5002)  
Jøtul recommends the use of a magnetic stove-top  
thermometer to monitor the surface temperature of  
the stove. The optimum surface temperature range  
for the most efficient, clean burn is between 400°  
and 600°.  
BY:  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXPLODED VIEW OF THE F 3 CB  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A:  
ALTERNATE FLOOR PROTECTION  
All floor protection materials must be non-combustible ie. metal,  
brick, stone, mineral fiber boards). Any combustible material  
may not be used.  
F 3 CB PARTS LIST  
The easiest means of determining if a proposed alternate floor  
material meets requirements listed in this manual is to follow this  
procedure.  
2
2B  
6
7
8
Inner rear heatshield  
Outer rear heatshield  
Smoke outlet cover  
Traverse bar  
Top plate with smoke cover  
Baffle plate  
R-value = thermal resistance  
k-value = thermal conductivity  
C-value = thermal conductance  
11  
12  
15  
22  
23  
24  
26  
28  
29  
31  
35  
37  
40  
42  
43  
45  
46  
51  
52  
55  
57  
59  
62  
64  
65  
70  
76  
73  
78  
79  
Air distributor  
Back plate  
Side plate  
Back burn plate  
Right burn plate  
Air deflector  
Sliding air vent  
Front plate  
Log retainer  
Door  
Hinge pin  
Start-up air vent  
Door handle complete  
Locking bar  
Glass  
Sparkscreen  
Ashlip  
1. Convert the specification to R-value;  
a. If R-value is given, no conversion is  
needed.  
b. If k-value is given with a required  
thickness (T) in inches: R=1/k X T.  
c. If C-value is given: R=1/C.  
2. Determine the R-value of the proposed alternate  
floor protector.  
a. Use the formula in Step 1 to convert  
values not expressed as “R”.  
b. For multiple layers, add R-values of each  
layer to determine overall R-value.  
3. If the overall R-value of the sustem is greater  
than the R-value of the specified floor protector,  
the alternate is acceptable.  
EXAMPLE:  
The specified floor protector should be 3/4” thick material with a  
k-factor of 0.84. The proposed alternate is 4” brick with a C-  
factor of 1.25 over  
1/8” mineral board witha k-factor of 0.29.  
Leg  
Step A. Use formula above to convert specifications to R-value.  
R=1/k X T= 1/.84 X .75 = .893  
Bottom plate  
Inner bottom plate  
Left burn plate  
Secondary air cover  
Flat ash housing gasket  
Ash housing  
Ashpan  
Ashpan door  
Stove tool  
Door latch  
Step B. Calculate R of proposed system.  
4” brick of C-1.25, therefore  
R brick = 1/C = 1/1.25 = 0.80.  
1/8” mineral board of k = 0.29 therefore  
R mineral board = 1/.29 X 0.125 = 0.431  
Total R = R brick + R mineral board=  
0.8 + 0.431=1.231  
Step C. Compare proposed system R = 1.231 to specified R of  
0.893. Since R is greater than required, the system is acceptable.  
Bottom heatshield  
Definitions:  
Thermal conductance =  
Btu  
=
W
(hr)(ft2)(F)  
(m2)(K)  
C =  
Thermal conductivity =  
Btu  
=
W
=
(Btu)  
(hr)(ft)(F)  
(hr)(ft2)(F)  
(m2)(K)  
k =  
Thermal resistance =  
Btu  
=
(m2)(K)  
W
=
(Btu)(inch)  
(hr)(ft2)(F)  
2
R =  
(hr)(ft )(F)  
FOR THE JØTUL F 3 CB WOOD STOVE REQUIRES  
FLOOR PROTECTION WITH A MINIMUM INSULATING  
R VALUE OF 1.1.  
ONLY USE REPLACEMENTS PARTS  
PROVIDED THROUGH YOUR  
AUTHORIZED JØTUL DEALER.  
ALCOVE INSTALLATION REQUIRE A MINIMUM R VALUE  
OF 1.1. (IF A UL/ULC or WHI LISTED HEARTH PAD IS NOT  
USED.)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Stoves and fireplaces must be installed to conform to local and national building regulations. Before preparing for the installation of  
the appliance, it is important that the instructions issued with the unit are carefully read and strictly adhered to. Jøtul pursue a policy of  
constant product development. Products supplied may therefore differ in specification, colour and type of accessories from those  
illustrated and described in the brochure.  
Jøtul vise sans cesse à améliorer ses produits. C’est pourquoi, il se réserve le droit de modifier les spcifications, couleurs etéquipement  
sans avis prélable  
Jøtul ASA  
P.O Box 1411  
N-1602 Fredrikstad, Norway  
Jøtul North America  
400 Riverside Street  
Portland, Maine 04104  
REV 2000.1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Indesit Washer Dryer PWDE 7125 W User Manual
Jabra Refrigerator JX10 User Manual
Jenn Air Cooktop JGC1430 JGC1536 User Manual
JVC DVD VCR Combo HR XVC29SU User Manual
Kenwood Stereo Amplifier KAC 819 User Manual
Keys Fitness Home Gym 835R User Manual
KitchenAid Cooktop KGCV566 User Manual
KitchenAid Dishwasher 4KUDA22OT User Manual
Kodak Camera Accessories E 2549 User Manual
Kodak Film Camera KE115 Zoom User Manual