WARNING:
IF THE INFORMATION IN THESE INSTRUCTIONS
ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-
SION MAY RESULT CAUSING PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE VICIN-
ITY OF THIS OR ANY OTHER APPLIANCE.
INSTALLATION:
INSTALLATION AND SERVICE MUST BE PER-
FORMED BY A QUALIFIED INSTALLER, SERVICE
AGENCY OR LICENSED GAS SUPPLIER.
THIS PRODUCT MUST BE INSTALLED BY A
LICENSED PLUMBER OR GAS-FITTER WHEN
INSTALLED IN THE COMMONWEALTH OF
MASSACHUSETTS.
A CARBON MONOXIDE (CO) DETECTOR SHALL
BE INSTALLED IN THE SAME ROOM AS THE
APPLIANCE.
Jøtul GF 400 DV
Sebago
Gas Heater
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCHES.
• DO NOT USE THE PHONE IN YOUR BUILDING.
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
NEIGHBOR’S PHONE.
• FOLLOW YOUR GAS SUPPLIER’S INSTRUCTIONS.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER,
CALL THE FIRE DEPARTMENT.
AVERTISSEMENT:
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUC-
TIONS DANS CETTE NOTICE POUR REDUIRE AU
MINIMUM LE RISQUE D’INCENDIE OU POUR EVITER
TOUT DOMMAGE MATERIEL, TOUTE BLESSURE OU
MORTALIT’E.
NE PAS ENTREPOSER NI UTILISER D’ESSENCE NI
OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE
DE CET APPAREIL OU DE TOUT AUTRE APPAREIL.
Installation
and
Operation
Instructions
L’INSTALLATION LE SERVICE DOIVENT ETRE
EXECUTES PAR UN INSTALLATEUR QUALIFIE,
AGENCE DE SERVICE OU LE FOURNISSEUR DE
GAZ.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.
• NE PAS TENTER D’ALLUMER L’APPAREIL
• NE TOUCHEZ A AUCUM NTERRUPTEUR.
• NE PAS VOUS SERVIR DES TELEPHONES SE
TROUVANT DANS LE BATIMENT OU VOUS VOUS
TROUVEZ.
• APPELEZ IMMEDIATEMENT VOTRE FOURNISSEUR
DE GAZ CHEZ UN VOISIN. SUIVEZ LES INSTRUC-
TIONS DU FOURNISSEUR.
• SI VOUS NE POUVEZ REJOINDRE LE
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES
INCENDIES.
Download from Www.Somanuals.com. All Manuals Search And Download.
Jøtul GF 400 DV
Sebago
Direct Vent Gas Heater
Manufactured and Distributed by:
Jøtul A.S.A.
Table of Contents
Service Tools .............................................. 3
Specifications ........................................... 4
General Information ............................... 5
Safety Information .................................. 6
Installation Requirements
Fredrikstad, Norway
Jøtul North America
55 Hutcherson Dr.
Gorham, Maine 04038-2634
Location ................................................. 6
Hearth Protection .............................. 6
Clearances ............................................ 7
Mantel & Trim ..................................... 7
Alcove..................................................... 7
Vent Requirements ................................. 8
Adding Restriction.............................. 8
Vertical Termination .......................... 9
Co-linear Termination .................. 12
Coaxial Chimney Conversion..... 13
Horizontal Termination................... 14
Vent Terminal Clearances ............... 15
Mobile Home Installation ................... 16
Fuel Conversion...................................... 16
Gas Connection ...................................... 18
Gas Pressure............................................ 19
High Altitude Adjustment .................. 19
Air Shutter Adjustment ....................... 20
Wall Thermostat .................................... 20
Remote Control ...................................... 20
Log Set Installation ............................... 21
System Check.......................................... 22
Operation................................................. 23
Maintenance........................................... 24
Glass Replacement ............................ 24
M.E.A. 369-04-E
Test Standards
This appliance complies
with National Safety
standards and is tested
and listed by Intertek
Testing Services of
Middleton, Wisconsin to
ANSI Z21.88-2002 •
CSA 2.33-M02 and CAN/CGA 2.17--M91,
CSA P.4 -01.2 for Canada.
DO NOT ATTEMPT TO ALTER OR MODIFY THE
CONSTRUCTION OF THE APPLIANCE OR ITS
COMPONENTS. ANY MODIFICATION OR ALTER-
ATION WILL VOID THE WARRANTY, CERTIFICA-
TION AND LISTING OF THIS APPLIANCE.
Optional Blower Installation .............. 25
Optional Brick Kit Installation ........... 27
Illustrated Parts Breakdown ............... 28
Replacement Parts List......................... 29
Lighting Instructions ............ Back Cover
THIS PRODUCT MUST BE INSTALLED
BY A LICENSED PLUMBER OR
GAS-FITTER WHEN INSTALLED IN THE
COMMONWEALTH OF MASSACHUSETTS.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
GF 400 DV Sebago
Specifications
Specifications
28 1/2”
724 mm
Input Rates
Natural Gas
32,000 BTU/hr. maximum input
18,000 BTU/hr. minimum input
Propane
26 1/2”
673 mm
32,000 BTU/hr. maximum input
16,000 BTU/hr. minimum input
Inlet Pressure:
MIN
MAX
13”
330 mm
Natural Gas:
Propane:
5.0 WC (1.24 kPa)
12.0 WC (2.99 kPa) 14.9 WC (3.71 kPa)
7.0 WC (1.74 kPa)
Manifold Pressure: MIN
MAX
Natural Gas:
Propane:
1.2 WC (.30 kPa)
2.9 WC (.722 kPa)
3.8 WC (.95 kPa)
11.0 WC (2.74 kPa)
26 1/2”
673 mm
Piezo Ignitor / Standing Pilot
C
L
Suggested Tools for
Installation and Service
• External regulator (for Propane only)
• Piping which complies with local code
• Manual shutoff valve (T-Handle in Massachusetts)
• Sediment trap - if required by code
• Tee joint
28 1/2”*
724 mm
25 1/2”*
647 mm
19 5/8”
500 mm
• Pipe wrench
• Pipe sealant
• 10 mm open end wrench
• 1/2”, 7/16” open end wrench or deep socket
• Phillips head screwdriver
• Flat head screwdriver
• 1/4” nut driver
29”
737 mm
• 4 mm allen wrench
• Gloves
• Safety glasses
• Torx T20 screwdriver
• Leak test solution
• Reciprocating Saw
19 1/2”
495 mm
• Power Drill
*For height with 6” Legs, subtract 2 1/4”
4
Download from Www.Somanuals.com. All Manuals Search And Download.
General Information
THIS HEATER MUST BE INSTALLED AND MAINTAINED
Glass Panel
BY A QUALIFIED SERVICE AGENCY.
Do not operate this appliance with the glass
front removed, cracked, or broken. Replacement
of the glass should be done by a licensed or
qualified service person. Only remove glass for
routine service. Always handle glass carefully.
The installation and repair of this appliance must be
done by a qualified service person. Failure to
properly install and maintain this heater could result
in an unsafe or hazardous installation, which may
result in a fire, explosion, property damage, personal
injury or loss of life.
This appliance should be inspected before use and at
least annually. More frequent cleaning may be
required due to excessive lint from carpeting,
bedding material, etc. It is imperative that control
compartments, burners, and circulating air passage-
ways of the appliance be kept clean.
Unpacking your stove
1. Remove the Top Plate of the stove by simply lifting it
straight off of the stove body.
2. To open the firebox, disengage the two Glass Frame
Latches located on top of the firebox. Pull each handle
forward to clear the latch from the notch in the
frame.
THIS APPLIANCE MUST NOT BE CONNECTED TO A
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.
The installation must conform to local codes. Your
local Jøtul dealer can assist you in determining what
is required in your area for a safe and legal installa-
tion. Some areas require a permit to install a gas
burning appliance. Always consult your local
Glass Frame
Latch
building inspector, or authority having jurisdiction,
to determine what regulations apply in your area.
CODE COMPLIANCE : Your local officials have final
authority in determining if a proposed installation is
acceptable. Any requirement that is requested by
the local authority having jurisdiction, that is not
specifically addressed in this manual, defaults to
local code. In the absence of local codes, the installa-
tion requirements must comply with the current
National codes. In the U.S., these requirements are
established in the National Fuel Code, ANSI
3. Familiarize yourself with the installation require-
ments specified in this manual, before beginning the
installation.
Z223.1.(NFPA 54). In Canada, the codes have been
established in CAN/CGA B149 Fuel Installation Code.
Hardware Bag Contents
• Fuel Conversion Kit - LP................................ 155351
Installer l’appareil selon les codes ou reglements
locaux, ou, en l’absence de tels reglements, selon les
Codes d’installation CAN/CGA-B149.
• Ember Bag , 4 oz. ............................................ 129123
DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN
UNDER WATER. Call a qualified service technician to
inspect the heater and to replace any part of the
control system and any gas control which may have
been under water.
THIS FIREPLACE IS SHIPPED FROM
THE FACTORY FOR USE WITH
NATURAL GAS ONLY. IF USE WITH
PROPANE IS DESIRED, THE APPLIANCE
MUST FIRST BE CONVERTED USING
THE FUEL CONVERSION KIT
Ne pas se servir de cet appareil s’il a ete’ plonge dans
l’eau, completement ou en partie. Appeler un
technicien qualifie pour inspecter l’appareil et
remplacer toute partie du syste’me de controle et
toute commande qui ont ete plonges dans l’eau.
PROVIDED, #155351. CONVERSION
SHOULD BE MADE BEFORE THE
APPLIANCE IS INSTALLED. SEE PG. 16.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Safety Information
Location
During normal operation, the GF 400 DV Sebago gas
stove will reach high surface temperatures. Therefore:
In selecting a location for the stove, consider the
following points:
1) Heat distribution
2) Vent termination requirements
3) Gas supply line routing
4) Traffic areas, furniture, draperies, etc.
Due to the high operating temperatures, this appli-
ance should be located out of traffic areas and away
from furniture and draperies.
The GF 400 DV Sebago may be located on or near
conventional construction materials, however, proper
clearance to combustibles must be maintained in order
to provide adequate air circulation around the appliance.
Also, it is important to provide adequate access around
the stove for servicing and proper operation.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to
avoid burns and/or clothing ignition.
The clearance and hearth specifications listed in this
manual are the minimum requirements for combustible
material. A combustible material is anything that can
burn (i.e. sheet rock, wall paper, wood, fabrics etc.). These
surfaces are not limited to those that are visible and also
include materials that may be located behind non-
combustibles.
Young children should be supervised while they are in
the same room as the GF 400 DV Sebago gas stove.
Clothing or other flammable materials should not be
placed ON or NEAR the GF 400 DV Sebago gas stove.
Surveiller les enfants. Garder les vetements, les
meubles, l’essence ou autres liquides a vapeur
inflammables loin de l’appareil.
If you are not sure of the combustible nature of a
material, consult your local fire officials. Remember,“Fire
Resistant” materials are considered combustible: they
are difficult to ignite, but will burn. Also,“fire-rated”
sheet rock is considered combustible.
NEVER store or use gasoline or any other flammable
vapors or liquids in the vicinity of the GF 400 DV
Sebago gas stove.
Hearth Requirements
The GF 400 DV Sebago gas stove CANNOT be installed
directly on carpeting, vinyl, linoleum or Pergo®.
Never burn any other materials in your GF 400 DV
Sebago gas stove, it is strictly designed for use with
natural gas or propane fuel ONLY.
If this appliance will be installed on any combustible
material OTHER THAN WOOD, a floor pad must be
installed that is either metal or wood, or a listed hearth
pad. This floor protection must extend the full width
and depth of the appliance. It is not necessary to remove
carpeting, vinyl or linoleum from underneath the floor
protection. See fig. 1.
·Any safety screen, glass or guard removed for servic-
ing the appliance must be replaced prior to operating
the appliance.
Figure 1. Minimum Hearth Protection.
14”
(356 mm)
27”
(686 mm)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove
to Combustibles: See figs. 2-4.
Rear:
2” (51 mm)
2”
(51 mm)
To Rear Wall
Ceiling:
Corner:
Sides:
32 1/4” (819 mm)
2” (51 mm)
3” (76 mm)
3”
(76 mm)
3”
(76 mm)
Minimum Clearances from the Vent Pipe to
Combustibles:
Figure 3. Parallel Installation Clearances.
Horizontal Run:
Off the top of the pipe
2” (51 mm)
Off the sides and bottom 1” (25 mm)
Vertical Run:
2”
51 mm
All sides
1” (25 mm)
Minimum Ceiling or Alcove Height
2”
51 mm
Max. Mantel Depth
12.5
10.25
8
Figure 4. Corner Clearances.
5.75
Min. Mantel Depth
Max. Top Trim Depth = 1
3.5
2 (5.1cm)
Alcove Installation
Maximum Alcove Depth: 24” (61 cm)
Minimum Alcove Width: 31 3/4” (80.6 cm)
Minimum Ceiling Height: 61” (155 cm)
Figure 2. Mantel and Trim Clearance specifications.
Back of bottom plate is flush with the fireplace face.
Subtract 2 1/4” with Short Legs.
With Short Legs (6”) :
59” (150 cm)
Alcove dimensions result from test
configurations, not stove clearance
specifications.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting Requirements
Vent Restriction
The GF 400 DV Sebago is equipped with Restrictor Plates
which enable you to regulate the flow of incoming
combustion air and exhaust gas. The plates prevent
overly strong draft that can cause poor combustion and
weak flame picture. Follow the guidelines below, and on
the following pages, to determine the correct restrictor
plate setting for your particular installation configura-
tion.
The Jøtul GF 400 DV Sebago gas stove may be installed
with a vertical or horizontal termination and must
conform to the configuration requirements described
below.
This appliance is approved for use with vent systems
from the following manufacturers:
• Simpson Dura-Vent GS
• Amerivent Corporation
• Security Vent Ltd.
• Selkirk Metalbestos
Intake Air Restrictor
Use parts of one manufacturer only - DO NOT MIX
VENT COMPONENTS FROM DIFFERENT MANUFACTURERS
IN THE SAME SYSTEM.
This plate is located at the rear of the firebox behind the
burner plate. It is set in a CLOSED position at the factory
and should be left there for most vent configurations.
It should be opened only for snorkel terminations and
some short run horizontal terminations as specified on
the following pages. To adjust the Air Restrictor to the
OPEN position, locate and loosen the wing nut under the
burner and push it back as far as it will go. See Fig. 6.
Installation of any components not manufactured or
approved by Jøtul or failure to meet all clearance require-
ments will void all warranties and could result in prop-
erty damage, bodily injury, or serious fire.
The approved vent configurations described in this
manual are derived from extensive testing under con-
trolled laboratory conditions. Gas appliance performance
can be negatively affected by variables present in the
installation environment, i.e: atmospheric pressure,
strong prevailing winds, adjacent structures and trees,
snow accumulation, etc. These conditions should be
taken into consideration by the installer and stove owner
when planning the vent system design.
Exhaust Restrictor
The Exhaust Restrictor is an adjustable shutter located at
the top of the firebox. It is adjusted by moving a pivot
pin into one of four positions. It is set in the FULLY OPEN
position at the factory. See Fig. 7.
Use the chart in Table 1 to determine the correct
position for your installation and follow the instructions
below to adjust it if necessary.
IMPORTANT
• JOINT SEALING REQUIREMENT: APPLY A 1/8” BEAD OF
HIGH-
Additional restriction may be needed depending the
overall vent height. Use Simpson Dura-Vent Restrictor
Disk #929.
TEMPERATURE (750°F) SEALANT TO THE MALE SEC-
TION OF THE INNER VENT PIPE. THE CEMENT SHOULD
FORM A SEAL BETWEEN THE INNER
AND OUTER PIPES.
Adjusting Exhaust Restrictor Plate:
1. Remove the Top Plate.
2. Locate the pivot pin at the left side of the firebox top.
Loosen the wing nut on the pivot pin and push the pin
to the left to disengage it from the current setting
position. Move the pin toward the rear and then right
to engage it in the appropriate position indicated on
the firebox. See fig. 7.
• NEVER MODIFY ANY VENTING
COMPONENT, OR USE ANY DAM-
AGED VENTING PRODUCT.
• THE GAS APPLIANCE AND VENT
S
SYSTEM MUST BE VENTED
E
A
L
A
N
DIRECTLY TO THE OUTSIDE OF
T
3. Tighten the lock nut and replace the Top Plate.
THE BUILDING AND NEVER
ATTACHED TO A CHIMNEY
SERVING A SOLID FUEL OR
GAS BURNING APPLIANCE.
Fig. 5.
EACH DIRECT VENT GAS APPLIANCE
MUST HAVE ITS OWN SEPARATE VENT SYSTEM.
COMMON VENT SYSTEMS ARE PROHIBITED.
• IF VENTING SYSTEM IS DISASSEMBLED FOR ANY
REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED
FOR THE INITIAL INSTALLATION.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
FRONT
LEG
BACK
LEG
Push the
Pivot Pin into
the slot
Default
Factory
Setting is
“D”
Fully Closed
A
B
C
D
Fully Open
Figure 6. Adjusting the Air Inlet Restrictor plate - View is
from the right side of the stove.
Vertical Vent Termination
The Jøtul GF 400 DV Sebago can be vertically vented
through a ceiling or to a roof termination with the
following guidelines:
A
B
C
D
The termination should fall within the shaded areas
of the grids depicted in the Vent Window diagrams on
the pages 10-11.
Front of
Stove
Maximum Vertical run should not exceed 35 ft. (10.66 m).
Minimum Vertical run must be at least 8 ft. (2.43 m).
Max. Colinear Horizontal run is 2 ft. (61 cm).
Figure 7. Adjusting the Exhaust Restrictor plate - Top Plate
removed. Viewed from front of stove.
Vent Terminus Clearance: In no case shall any dis-
charge opening on the cap be less than 18 in. (610
mm) horizontally from the roof surface.
Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or
promote down-draft occurances. Increasing the
height of the vent may alleviate these conditions.
Horizontal Overhang
18.
min.
18.
min.
Use Wall Straps to support an offset pipe run at three
Lowest Discharge
Opening
feet intervals to avoid excessive stress on the offsets.
Termination
Cap
Elbows: Four 45°, or two 90° elbows may be used. Do
not include the 45° elbow attached to the stove.
Whenever possible use 45° elbows instead of 90°
elbows as they are less restrictive to exhaust gas and
intake air flow.
18 min.
A firestop is required at every floor. The opening
should be framed to 10" X 10" inside dimension.
Any venting that is exposed above the first floor,
regardless of attic space or living space, must be
enclosed. Always maintain the required 1" clearance
from all sides of the vertical vent system.
Figure 8. Vertical vent termination height above roof.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Vent Termination Zones - Natural Gas
Vertical
Termination for
COLINEAR VENT
35 Ft.
(10.67 m)
Horizontal and Vertical
Terminations for COAXIAL VENT
35 Ft.
(10.67 m)
30 Ft.
(9.14 m)
Up to four 45° or
two 90° elbows
permitted in
addition to the
starter elbow.
25 Ft.
(7.62 m)
A
B
25 Ft.
(7.62 m)
20 Ft.
(6.10 m)
A
B
15 Ft.
(4.57 m)
B
12 Ft.
(3.65 m)
C
Min. Vertical
Termination
D
8 Ft.
(2.43 m)
Minimum
Vertical
5 Ft.
Termination
(1.52 m)
8 Ft.
(2.43 m)
Min. Rise
2 Ft.
(.60 m)
5 Ft.
(1.52 m)
10 Ft.
(3.05 m)
15 Ft.
20 Ft.
(6.09 m)
27 Ft.
(8.22m)
(4.57 m)
HORIZONTAL RUN
2 Ft.
• ALL VENTING MUST TERMINATE (END) WITHIN ONE OF
THE SHADED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION
THAT CORRESPONDS TO THE VENT TERMINATION AREA
IN THE DIAGRAM ABOVE.
(16 cm)
HORIZONTAL RUN
• VENTING MUST TERMI-
NATE (END) WITHIN THE
SHADED AREA.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO
COMBUSTIBLES.
• Adjust the Exhaust
Restrictor to position B
for any NG colinear
termination.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the restrictor to the corresponding
position as shown in Figure 7, page 9.
Figure 9. Coaxial Vent Termination Window / NG
Figure 10 . Colinear Termination / NG
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Vent Termination Zones - Propane
Vertical
Termination for
COLINEAR VENT
35 Ft.
(10.67 m)
35 Ft.
(10.67 m)
Horizontal and Vertical
Terminations for COAXIAL VENT
30 Ft.
(9.14 m)
Up to four 45° or
two 90° elbows
permitted in
25 Ft.
(7.62 m)
addition to the
starter elbow.
25 Ft.
(7.62 m)
A
20 Ft.
(6.10 m)
C
B
15 Ft.
(4.57 m)
D
12 Ft.
(3.65 m)
D
B
8 Ft.
(2.43 m)
Minimum
Vertical
Termination
8 Ft.
(2.43 m)
5 Ft.
(1.52 m)
OPEN AIR INLET
RESTRICTOR
Min. Rise
2 Ft.
(.60 m)
27 Ft.
(8.22m)
5 Ft.
(1.52 m)
10 Ft.
(3.05 m)
15 Ft.
(4.57 m)
20 Ft.
(6.09 m)
HORIZONTAL RUN
2 Ft.
(16 cm)
• VENTING MUST TERMINATE (END) WITHIN ONE OF THE DESIG-
NATED AREAS. ZONE “A” IS FOR VERTICAL TEMINATIONS ONLY.
• VENTING MUST
TERMINATE (END)
WITHIN THE SHADED
AREA.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRE-
SPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM
ABOVE.
• OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND
UNDER. SEE FIG. 6, PAGE 9.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.
• Adjust the Exhaust
Restrictor to position C
for a straight vertical
colinear termination.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installa-
tion and fuel type, then adjust the stove restrictor plate to the
corresponding position as shown in Figure 7, page 9.
• Adjust the Exhaust
Restrictor to position D
for a vertical colinear
termination with
maximum 2 ft. offset.
Figure 11. Coaxial Vent Termination Window / LP
Figure 12 . Colinear Termination / LP
11
Download from Www.Somanuals.com. All Manuals Search And Download.
High Wind Cap
Exhaust Gas
Co-linear Vent Installation
Max. Co-linear
Height - 35 ft.
(10.66 m)
Intake Air
The GF 400 DV Sebago may be vented through a ma-
sonry or Class A prefabricated chimney using a Co-linear
Flexible Vent system approved for use with a solid-fuel
burning fireplace. When installed in the manner de-
scribed below, this system can improve the performance
of the appliance in cold climate situations, as well as
simplify the vent installation. See fig. 13.
Min. Co-linear
Height - 10 ft.
(3.05 m)
These installation requirements must be followed:
1. Use the guidelines for Co-linear Vent Termination
appropriate for your gas type on pages 10 - 11.
1. Prior to the installation the chimney flue must be
thoroughly cleaned and inspected by a qualified
chimney service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
The Air
Intake Flex
pipe must
extend
beyond the
damper.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
The chimney
must be sealed
off from the
room by a steel
plate at the
damper area.
4. No appliance can be installed into a chimney flue
Dual 3”Flex
Liners
serving any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET
BEYOND THE DAMPER AREA OF THE FIREPLACE.
6. If the intake flex duct does not extend the full length
of the chimney and connect to both the unit and the
termination cap, A METAL BLOCK OFF PLATE MUST BE
CONSTRUCTED AND INSTALLED ABOVE THE UNIT
PRIOR TO THE END OF THE INTAKE FLEX AND MUST
COMPLETELY SEAL THE CHIMNEY FLUE FROM THE
ROOM.
Max. offset
24”
(609 mm)
Figure 13. Co-linear Adaptor installed through a masonry
chimney. Components shown may differ somewhat from
manufacturer to manufacturer.
Consult with the local code authority having juris-
diction before proceeding with this type of installation.
Refer to the vent manufacturer’s instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUC-
TIONS PROVIDED WITH EACH VENT COMPONENT.
29”
to top of
Co-linear
25 1/2”
Adapter.
to center
of flue collar
Figure 14. Simpson Dura-Vent #923GCL Co-linear Adaptor
is shown - other manufacturer’s components may differ.
Subtract 2 1/4” for Short Legs.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Vertical
Termination
Cap
Exhaust
Gas
Masonry or Prefabricated Chimney
Conversion
The GF 400 DV Sebago is approved for use with listed
chimney conversion kits from any of the manufacturers
listed on page 8. These kits are for use in a masonry
chimney or a prefabricated solid fuel listed chimney. See
fig. 15.
Cap Adaptor-
included in
#934 Kit
Intake Air
4” Flex Pipe
not included
in kit
These installation requirements must be followed:
1. Use the guidelines for Coaxial Vent Termination
appropriate for your gas type on pages 11 - 12.
Use standard
2. In masonry chimney, a fireclay liner or listed steel
liner, must be present the entire length of the chim-
ney.
vent pipe from
stove to
Support/Wall
Thimble Cover
thimble from
the same
manufacturer
3. Chimney height should not exceed 35 ft. (10.66 m).
4. The liner must have an inside dimension of 6” round
or greater.
5. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm). Prefabricated chimneys must be
listed for the specific Chimney Conversion Kit you
choose.
Figure 15. Vent System through a masonry chimney using a
chimney conversion kit. May also be used in listed
prefabricated chimneys. Drawing is for illustrative purposes
only - DO NOT VENT TWO APPLIANCES INTO A SINGLE
CHIMNEY.
IMPORTANT NOTICE
THE USE OF AN EXISTING CHIMNEY
AS AN AIR INTAKE IS NOT COVERED
UNDER THE ANSI Z21.88-1999-CSA
2.33-M99 TEST METHODS AND RE-
SULTING ITS/WHI PRODUCT CERTIFI-
CATION. THE CODE AUTHORITY
HAVING JURISDICTION MUST BE
CONSULTED PRIOR TO PROCEEDING
WITH THIS INSTALLATION METHOD.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
12 in.
(305 mm)
Horizontal Termination
C
L
Any horizontal termination must fall within the
shaded portion of the vent window graph illustrated
in figs. 9 or 11. For Snorkel Terminations, see below.
24 in.
Snorkel
(305 mm)
Any horizontal termination except a snorkel termination,
must include:
14”
355 mm
Max.
1)
2)
Minimum rise of 2 ft.
Minimum horizontal run of 12 in. when vertical
run is less than 8 ft.
57”
(1448 mm)
2)
3)
4)
Maximum rise of 35 ft.
Maximum horizontal run of 27 ft.
No more than four 45° or two 90° Elbows
12”
Vent
Pipe or
less
25 1/2 in.
Snorkel
(648 mm)
Follow all termination clearance guidelines as speci-
fied in fig. 19.
Figure 16.
The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
2 1/2" or less. It must also maintain 12" clearance
from projections exceeding 2 1/2". See fig. 20.
• Minimum vent for horizontal termination.
• 14” Maximum horizontal run directly off rear of stove
with 14” Snorkel termination.
Wall Cut-out Opening: A minimum 10" X 10" (250 mm x
250 mm) square hole is required for proper pipe clear-
ances through a combustible wall. Use a listed wall
thimble for the wall penetration.
36 in.
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.
Snorkel
Max.
6 ft.
183 cm
(915 mm)
Any horizontal run of vent must have a 1/4" rise for
every foot of run toward the termination cap. NEVER
ALLOW THE VENTING TO RUN DOWNWARD FROM
STOVE TO TERMINATION; DOWNWARD VENT RUNS
TRAP HEAT AND CAUSE HIGH TEMPERATURES TO
DEVELOP WITHIN THE VENT THAT COULD START A
FIRE.
Install a Vinyl Siding Standoff between the vent
termination and an exterior wall covered by vinyl
siding material to prevent potential heat damage to
the siding.
Figure 17. Maximum Horizontal and Vertical Run with 36”
Snorkel Termination.
Do not recess the termination cap into a wall or
siding.
Max.
14”
45° Elbow
355 mm
Snorkel Terminations
See Note F
Fig. 20
THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN
FOR ANY SNORKEL TERMINATION. See Fig. 6, pg. 9.
With a 14” Snorkel:
The horizontal run made directly off the rear of the
stove into a 14” snorkel cap should include no more
than a single 12” straight section as shown in fig. 17.
One 45° Elbow may be used for a corner installation as
shown in fig. 18.
12 in.
Straight Pipe
Wall Thimble
and Trim Collar
With a 36” Snorkel:
The maximum horizontal run may be no more than
6 ft. (182 cm.)
Figure 18. Corner Installation with 14” Snorkel Termination.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Horizontal Termination Clearance
Figure 19. Vent Terminal Clearances - National Fuel Gas Code.
L = 1 Clearance above paved sidewalk or a paved driveway
located on public property: 7 feet (2.1 m) min.
A = Clearance above grade, veranda, porch , deck, or
balcony : 12 inches (30 cm) minimum.
M = Clearance under veranda, porch, deck, or balcony:
B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa-
tion on the window.
12 inches (30 cm) minimum. 2
*
In accordance with CSA B149 Installation Codes.
C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensa-
tion on the window.
** In accordance with the current ANSI Z223.1/NFFPA 54,
National Fuel Gas Code. Note: Local Codes and Regulations may
require different clearances.
1 A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.
2
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
2 1/2
12
305
mm
64 mm
H = *Not to be installed within 15 feet (4.5 m) above a
meter/regulator assembly within 3 feet (90 cm)
horizontally from the center-line of the regulator.
3
76 mm
I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.
J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizon-
tally, U.S. / *6 feet (1.83 m) minimum / CAN
Figure 20. Termination Clearance to overhangs
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Mobile Home Installation
Fuel Conversion
The GF 400 DV Sebago can be installed for use in a
mobile home in the U.S. and Canada provided:
The GF 400 DV Sebago gas stove is shipped from the
factory equipped to burn NATURAL GAS only. If PROPANE
gas is to be used as fuel, the appliance must first be
converted for use with propane. Use Propane Conversion
Kit 155351, supplied with the appliance.
1. The stove is secured to the floor of the mobile home.
Use Jøtul Floor Bracket Kit #154388.
2. Provision must be made to secure an electrical ground
Order and install NG Conversion Kit 155352 to
change back to use with natural gas.
between the stove and the mobile home chassis.
3. The stove is installed in accordance with Title 24 CFR,
Part 3280- Manufactured Home Construction and
Safety Standard, in the U.S. In Canada, comply with
CSA Z240.4, Gas Equipped Recreational Vehicles and
Mobile Housing.
WARNING:
THE CONVERSION KIT IS TO BE
INSTALLED BY AN AUTHORIZED JØTUL
SERVICE TECHNICIAN IN ACCORDANCE
WITH THE MANUFACTURER’S
4. Always contact your local officials about installation
restrictions and requirements in your area.
INSTRUCTION AND ALL CODES AND
REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD
RESULT IN SERIOUS INJURY OR
PROPERTY DAMAGE. THE QUALIFIED
AGENCY PERFORMING THIS WORK
ASSUMES RESPONSIBILITY FOR THIS
CONVERSION.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTERMARKET PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES. THIS
APPLIANCE IS ONLY FOR USE WITH THE TYPE
OF GAS THAT IS INDICATED ON THE STOVE’S
RATING PLATE. A GAS CONVERSION KIT IS
PROVIDED WITH THE GF 400 SEBAGO DIRECT
VENT GAS STOVE.
IN CANADA:
THE CONVERSION SHALL BE CARRIED
OUT IN ACCORDANCE WITH THE RE-
QUIREMENTS OF THE PROVINCIAL AU-
THORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIRE-
MENTS OF THE CAN1-B149.1 AND .2
INSTALLATION CODE.
CET APPAREIL PEUT ETRE INSTALLE DANS
UN MAISON PREFABRIQUEE (MOBILE) DEJA
INSTALLEE A DEMEURE SI LES REGLEMENTS
LOCAUX LE PERMETTENT. CET APPAREIL
DOIT ETRE UTILISE UNIQUEMENT AVEC LES
TYPES DE GAS INDIQUES SUR LA PLAQUE
SIGNALETIQUE. NE PAS L’UTILISER AVEC
D’AUTRES GAS SAUF SI UN KITDE CONVER-
SION CERTIFIE EST INSTALLE.
Tools required:
• 1/2” open ended wrench or deep-well socket, Torx T20
or slotted screwdriver, 4 mm allen wrench.
Conversion Kit Contents:
• 1, regulator tower labeled for propane
• 3, regulator tower screws
• 1, burner orifice (#33 for NG, 1.65 mm for LPG)
• 1, pilot orifice (#51 for NG, #30 for LPG)
• Label A - to be completed and applied to
the back of the stove
• Label B - apply to the stove’s Rating Plate
• Small valve label - apply to valve body
Conversion instructions are also shipped in the stove
with the conversion kit.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Fuel Conversion Procedure
Refer to fig. 47, Illustrated Parts Breakdown, to identify
part numbers below.
Air
Shutter
Wingnut
Open
Close
1. Turn off gas supply to stove.
2. Remove the stove Top Plate (41).
3. Disengage the two Glass Frame Latches at the top of
the firebox. See illustration on page 5. Carefully lift
the glass panel up and out of the stove.
FRONT
LEG
BACK
LEG
4. If installed, remove the Embers and Log Set using care
Figure 21. Locate and remove the Air Shutter wingnut
from under the right side of the stove.
not to damage the fragile log parts.
5. Lift out the Burner Skirt (33). Tilt the skirt at an angle
to clear the firebox sides and front.
6. Reach under the stove and remove the Air Shutter
wingnut from its stud. As you face the right side, it is
the one closest to you. See fig. 21.
Air Shutter
7. Lift out the Burner Plate: NOTE: There are no screws
securing the Burner to the floor of the firebox. Pull the
Air Shutter forward and lift the burner together with
shutter up and out of the stove as a unit. See fig. 22.
8. Change the Main Burner Orifice. See fig. 23. Using a
½” open ended wrench or deep-well socket remove
the burner orifice from its brass elbow housing and
replace with the appropriate orifice supplied in the kit.
#33 for NG
Burner Plate
Figure 22. Remove the Air Shutter and Burner as a unit.
1.65 mm for LPG
9. Replace the Air Shutter with its gasket and push it all
the way back to allow replacement of the Burner
Plate.
10. Replace the Burner Plate. Engage the Air Inlet Tube
with the Air Shutter and burner orifice. Properly seated,
the burner plate will be engaged at its front corners
with the two support brackets located at the front of
the firebox.
Brass Elbow
• Replace the wingnut loosely on the air shutter stem
under the stove. Air shutter adjustment will be done last.
Burner
Orifice
11. CHANGE THE PILOT ORIFICE: From within the firebox,
remove the Pilot Head by pulling it straight up from
the pilot base. See fig. 25.
Figure 23. Change the Burner Orifice.
Using the 4 mm allen wrench that is included with
the conversion kit, unscrew the pilot orifice (counter-
clockwise). Replace with the appropriate orifice:
# 51 for natural gas
#30 for propane gas
12. Tighten orifice into the base of the pilot assembly. To
prevent bypass leaks, be sure the orifice is secured
tightly and flush with the base. Replace pilot head by
pushing it down onto the pilot base.
Air Shutter
Air Inlet
Tube
Opening
Dimension
13. Replace the Variable Regulator. Using a Torx T-20
screwdriver, remove the three screws from the front
of the valve regulator. See fig. 26.
Burner Plate
Figure 24. Air Shutter Setting
17
Download from Www.Somanuals.com. All Manuals Search And Download.
NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
14. Remove the Regulator Tower, Gasket, white plastic
disk, and Spring.
Correct gas pressure is essential for efficient and safe
operation of this appliance. Correct gas pressure
must be established at the time of installation. For
more details, see the Gas Pressure section of this
manual (page 19).
15. Install the new regulator: Be sure the new gasket is
properly positioned and tighten screws securely.
16. Install the identification labels to the stove so that they
can be seen by any person that may be servicing the stove.
Label A: apply to back of stove.
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE
INSIDE BACK COVER OF THIS MANUAL WHEN LIGHT-
ING YOUR STOVE.
Label B: apply to stove’s rating plate.
Small valve Label: apply to valve.
17. Reassemble the stove, apply gas to the system and
check for leaks using a soapy water solution.
18. Adjust the Air Shutter:
Gas Supply Connection
CAUTION! USE WORKGLOVES. SURFACES MAY BE HOT!
You will need to adjust the shutter to the position
that supplies the correct amount of air mixture to
achieve the best flame picture with your particular
installation. Start with the shutter stem at the
midway position in the slot in the bottom of the
stove. See fig. 21. Pushing the stem back will restrict
air, while pushing it forward will open the shutter.
Too much air will produce a lighter flame, while too
little will promote long, dark flames and may pro-
mote sooting. Make adjustments in small incre-
ments. With some experimentation, you will find the
shutter position that works best for your installation.
Connect the gas supply line to the stove, before
installing the optional Blower.
If the blower will be installed, use a 45° elbow off the
control valve to create clearance required for the blower
installation.
The gas supply line connection is made to the left side of
the valve. The gas supply line should be 3/8" npt with a
1/2" diameter supply, or the appropriate size to provide
sufficient gas pressure to the valve regardless of the
input setting.
The use of Flexible Gas Appliance Connectors is
acceptable in many areas in the U.S. However, Canadian
methods vary depending on local code.
ALL INSTALLATIONS MUST COMPLY WITH LOCAL
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST
COMPLY WITH THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR
CAN-B149.
Pilot Head
Orifice
Retainer
Clip
All codes require a gas shut-off valve (gas cock) and
union, to be installed in the supply line, and in the same
room as the appliance. This allows for the disconnection
of the stove for servicing and maintenance. See fig. 27.
Pilot Base
Figure 25. Pilot orifice removal and replacement.
Regulator
Tower
Remove black
gasket
Apply small
label here
Figure 26. Regulator assembly.
Figure 27. Supply valve coupling.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
A T-HANDLE GAS COCK IS REQUIRED IN
MASSACHUSETTS TO COMPLY WITH
CODE 248CMR.
Secure all joints tightly using appropriate tools and
sealing compounds. For propane units be sure to use
compounds that are propane resistant. Turn on gas
supply and test for gas leaks using a soapy water solution.
Never use an open flame to check for leaks.
A
E
Figure 28. Pressure test points.
Leak test:
1. Mix a 50-50 solution of water and dish
soap.
2. Light appliance- see lighting instructions
on the inside back cover of this manual
or on the stove’s rating plate.
INLET GAS PRESSURES
(inches water column)
MIN
MAX
3. Brush or spray all joints and connections
with the soapy water solution.
NATURAL GAS 5.0
7.0
PROPANE
12.0
14.9
4. If bubbles appear at any connection or
seam or a gas odor is detected, immedi-
ately turn gas control knob to the OFF
position.
The appliance and its appliance main gas
valve must be disconnected from the gas supply
piping system during any pressure testing on
that system at test pressures in excess of 1/2 psig
(3.5 kPa).
5. Tighten or reconnect the leaking joint
and retest for any gas leaks.
The appliance must be isolated from the gas
supply line by closing its individual manual gas
shut-off valve (gas cock) during any pressure
testing of the gas supply piping system that is
equal to or exceeds pressures of 1/2 psig (3.5
kPa).
Gas Pressure
MANIFOLD PRESSURES
(inches water column)
Correct gas pressure is essential for efficient and safe
operation of the GF 400 DV Sebago gas stove. It is
important that the correct pressure is established at
the time of the installation. Proper gas pressure
provides a consistent flow of gas to the appliance and
is instrumental in checking for gas leaks.
MIN
MAX
NATURAL GAS 1.2
3.8
11.0
PROPANE
2.9
Pressure Test: Attach a manometer to the appro-
priate test point on the valve. See fig. 28. The gauge
connections are located on the front of the valve
under the On/Off/Pilot- knob. Gauge connections are
identified by:
E - for Inlet or Supply Pressure (the amount of
gas coming to the valve.)
High Altitude Adjustment
Installations located at altitudes from 2000 - 4500 ft.
(610 m -1370 m) DO NOT require adjustment for alti-
tude. DO NOT DERATE THIS APPLIANCE FOR ALTITUDE.
A - for Manifold Pressure (the amount of gas that
is coming out of the valve to the burner.)
ALWAYS TEST PRESSURES WITH VALVE CONTROL
KNOB SET ON HIGH.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Flame Appearance / Air Shutter
Adjustment
Optional Wall Thermostat or
Remote Control
The GF 400 DV Sebago gas stove is shipped from the
factory equipped to burn Natural gas with the air shutter
set at the halfway position. Please be aware, however,
that this initial setting may not provide the optimal flame
picture in your particular installation. No single setting
will be appropriate for all vent configurations, fuel types,
or installation environments. The air shutter setting can
also be adjusted to achieve the desired flame appearance.
Flame appearance is a matter of individual preference,
however, most people enjoy a warm yellowish flame.
Use only a 750 millivolt DC two-wire circuit thermostat
with this appliance. The thermostat should be placed in
the same room as the heater, typically 5 feet off the
floor. Avoid drafty areas or any area that may affect the
accuracy of the thermostat.
The thermostat should be connected to the GF 400
DV Sebago using a minimum of 16 gauge wire with a
maximum length of 25 feet of wire.
Connect the two thermostat wire leads to the two
lower terminals on the terminal block located directly
above the ignitor button. Do not overtighten the
connections. IT IS NOT NECESSARY TO DISCONNECT
ANY OTHER WIRES. See Fig. 30.
Too much air - the appliance will generate a flame
that is blue and transparent, or an “anemic” flame.
Too little air - the appliance may generate very long
yellow flames resulting in soot. Sooting produces black
deposits on the logs, on the inside walls of the appliance,
and potentially, on the exterior termination cap. Sooting
is caused by incomplete combustion and lack of combus-
tion air entering the air shutter opening.
For thermostatic operation, the On/Off/T-Stat
switch on the back of the stove must be in the T-stat
position, and the pilot light must be running, as it is the
power source for the thermostat.
At the thermostat, the two wires should be con-
nected to the two connection screws on the thermostat
base plate per the manufacturer’s instructions.
To adjust the air shutter: CAUTION! USE WORKGLOVES.
SURFACES MAY BE HOT!
1. Reach under the right side of the stove and loosen the
wingnut located closest to you. See fig. 29. Slide the
wingnut stem forward to open the air shutter and
increase air. Slide the shutter stem back to decrease
the air supply.
Remote Control
When using a remote, the remote receiver should be
wired to the terminal block the same way the thermo-
stat would be. See the instructions above.
2. Tighten the wingnut to secure the shutter at the
Follow the operating instructions included with the
Remote Control unit.
desired setting.
3. Operate the burner for 30 minutes on the HIGH setting,
observing the flame continuously. If the flame appears
weak, slow, or sooty, adjust the air shutter to a more
open position as described above until the flame is as
desired. Make adjustments in small increments and
allow the burner to settle in before making further
adjustment
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION
WHEN SERVICING THE CONTROLS. WIRING
ERRORS CAN CAUSE IMPROPER OR DANGEROUS
OPERATION. ALWAYS VERIFY PROPER OPERA-
TION AFTER SERVICING THE APPLIANCE.
WARNING: AIR SHUTTER ADJUSTMENTS SHOULD ONLY
BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE
TECHNICIAN.
ROCKER
SWITCH
THERMOPILE
ON
TH
TP
OFF
FRONT
LEG
Open
Close
STAT
TH
TP
OPTIONAL
THERMOSTAT
or
REMOTE
CONTROL
VALVE
BACK
LEG
TERMINAL
BLOCK
Figure 29.
Loosen the wingnut to adjust the air shutter stem.
Figure 30. Accessory wiring diagram.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Log Set Installation
NOTE: If appropriate, install the optional Antique Brick
Panel Kit before assembling the logset.
The GF 400 DV Sebago logset must be installed before
operating the burner. The logset includes five log pieces,
packaged inside the firebox, and a quantity of ember
stones packaged in the Miscellaneous Parts bag.
To install the log set, remove the packaging and place the
parts inside the firebox as illustrated in figs 32-37. Do
not handle the log set with your bare hands. Always
wear gloves to prevent skin irritation from the ceramic
fibers.
Figure 34. Install Left Log
The ember stones realistically simulate glowing coals
when the burner is operating. These should be spread
evenly over the burner plate and around the logs. DO NOT
OBSTRUCT THE PILOT ASSEMBLY OPENING. See fig. 37.
NOTE: You do not need to use all the ember stones.
With experimentation, you will find the arrangement
and quantity of embers that works best with your stove.
Depending upon the characteristics of your installation,
it is possible that too many ember stones can promote
sooting on the logs. Adjust the quantity of ember stones
as appropriate to maintain the best overall flame
picture.
Figure 35. Install Middle Log
THE CERAMIC FIBER LOGS AND GLOWING EMBERS CAN
IRRITATE YOUR SKIN. GENTLY WASH YOUR HANDS WITH
WARM SOAPY WATER AFTER HANDLING THE LOGS.
Figure 36. Install Crossover Log
Figure 32. Install Right Log
Pilot
Opening
DO NOT
OBSTRUCT
Figure 33. Install Rear Log
Figure 37. Install Ember Stones
21
Download from Www.Somanuals.com. All Manuals Search And Download.
System Check
1
(25mm)
3/8
(8mm)
Min.
1. PURGING THE GAS LINE: When lighting the appli-
ance for the first time, it will take a few moments to
clear the gas line of air. Once this purge is complete,
the appliance will operate as described in the
lighting instructions. See the inside back cover of
this manual or the stove Rating Plate attached the
bottom of the stove. Subsequent burner starts will
not require purging the gas line unless the supply
line is shut off.
1/8
(3mm)
Min.
2. PILOT FLAME: You can monitor the pilot flame
through the view port located at the rear of the
Right Log. See fig. 36. The pilot flame should be
steady - not lifting or floating. The flame should be
blue in color around the pilot hood, with traces of
yellow toward the outer edges.
Figure 37. Proper pilot flame appearance.
The pilot flame should engulf the top 3/8” of the
thermopile (to generate millivolt current) and the
top 1/8” of the thermocouple. The pilot flame
should project out of the pilot hood 1” at all three
ports. See fig. 37.
CAUTION:
DO NOT ATTEMPT TO ALTER THE FLAME
APPEARANCE BY POSITIONING THE GAS
VALVE CONTROL IN ANY OTHER POSITION
OTHER THAN THE FULL “ON” POSITION.
3. BURNER ADJUSTMENT: This stove is equipped with a
variable gas control valve that allows easy adjust-
ment of the flame height appearance and heat
output. To adjust the flame between the HI and
LOW setting, rotate the HI/LOW knob, located in the
center of the valve face. Flame height will adjust
approximately 1” to 2” between the LOW and HIGH
settings. See fig. 38.
NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK
LOG PLACEMENT IF ANY SOOT OR SMOKE IS
PRESENT. IF SOOT OR SMOKE PERSISTS, THE AIR
SHUTTER MAY NEED TO BE ADJUSTED.
See Air Shutter/Flame Appearance section of this
manual for proper air shutter settings and adjust-
ments. Note: the more offsets there are in the vent
system, the greater the need for an air shutter
adjustment. See page 20.
WARNING:
Figure 38. Flame appearance on the “high” setting after
approximately 15 to 20 minutes burning.
AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE
PERFORMED BY A QUALIFIED PROFESSIONAL
SERVICE TECHNICIAN.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Familiarize yourself with the controls of the GF 400 DV
Sebago. Make sure that anyone else using the appliance
is also familiar with the controls and operation proce-
dures. Always follow the Lighting Instructions on the
inside back cover of this manual and also located on the
Rating Plate attached to the back of the stove.
1. Once the pilot is lit, burner operation is controlled by
the rocker switch located at the left rear corner of the
stove. Use the T-STAT position for the optional thermo-
static or remote control functions. See fig. 39.
2. During the first few fires, you may notice odor and/or
smoke from the stove. This is normal and results from
burn-off of manufacturing residue and curing of
materials. You may find it helpful to provide addi-
tional ventilation and fresh air to alleviate this condi-
tion.
3. Condensation may occur on the glass upon each
lighting of the appliance. This “fog” will disappear as
the appliance heats up.
Figure 39. Burner Switch and Optional Blower Controls
4. Keep the controls and the area under the appliance
free of debris, vacuum this area frequently. Always
keep the appliance area clear and free from combus-
tible materials, gasoline and other flammable liquids.
If a vacuum is used during any service on the stove,
ALWAYS be sure the stove is cold and there are NO hot
embers.
5. Remember, this appliance has a continuous burning
pilot flame. Exercise caution when using products
having combustible vapors. Always shut-off gas
supply while servicing the stove.
6. CAUTION: DO NOT OPERATE THIS APPLIANCE WITH
THE GLASS REMOVED CRACKED OR BROKEN.
Replacement of the glass should be done by a licensed
or qualified service person. Use only replacement
glass provided by your authorized Jøtul dealer. Never
use any substitute materials.
WARNING: OBSERVE CAUTION WITH THE GLASS. THE
GLASS PANEL MAY SHATTER UNEXPECTEDLY IF STRUCK
WITH AN OBJECT. ALWAYS HANDLE THE GLASS PANEL
WITH CARE. WHEN SERVICING THE STOVE ALWAYS
PULL THE GLASS ASSEMBLY STRAIGHT UP FOR RE-
MOVAL.
7. Clean the glass only when necessary. Wipe surface
with a clean, damp soft cloth. Follow with a dry, soft
towel as desired. Take care not to scratch the glass
surface.
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE
GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
FOR REPLACEMENT, USE ONLY JØTUL
CERAMIC GLASS PANEL 220089. DO NOT
USE ANY OTHER TYPE OF GLASS WITH
THIS APPLIANCE.
Maintenance
Your Jøtul GF 400 DV Sebago and its venting system
should be inspected before use and at least annually by
a qualified service technician.
Glass Panel or Gasket Removal
Use the form on page 30 to keep a maintenance
history of your stove.
1. Lift the Top Plate off of the stove.
2. Release the two Glass Frame Latches. Pull each latch
handle forward forward to disengage the latch from
the notches in the glass frame.
IMPORTANT:
ALWAYS TURN OFF THE GAS SUPPLY TO THE
FIREPLACE AND UNPLUG THE FORCED AIR
BLOWER BEFORE ANY SERVICE WORK IS
PERFORMED ON THE FIREPLACE.
3. Lift the glass frame all the way up and out of the top
of the stove. Lay this assembly on a flat surface,
protecting the frame from scratches using a blanket
or towel.
3. The glass panel is held in place by four compression
clips. Use a screwdriver or small pliers to pry these up
off the edge of the glass retaining walls. See fig. 40.
Annual Cleaning
Vent System
4. Remove the old gasket material. See fig. 41.
The entire vent system, including the chimney, should
be inspected and cleaned every year. If the intake and
exhaust venting is disassembled for any reason, it
should be reassembled and sealed according to the
manufacturer’s instructions provided at the initial
installation.
Glass Clips
Burner and Logset
Periodically inspect the Firebox, Valve Compartment,
Convection Airways and optional Blower to BE CERTAIN
THAT THE FLOW OF COMBUSTION AND VENTILATION
AIR IS UNOBSTRUCTED.
Figure 40. Use small pliers to pry the clips off of the glass
panel frame.
The firebox should be vacuumed annually to remove
any surface build up. Use a soft brush attachment and
handle the logs carefully as they are fragile. Be sure to
vacuum or wipe off the pilot assembly and burner
surfaces.
Glass Panel or Gasket Replacement
1. Wrap the new gasketing material evenly around the
edge of the glass, peeling back the protective strip to
expose the adhesive as you go. Press the adhesive side
down onto the glass surface. Do not stretch the
gasket.
Glass Care
Clean the glass only when necessary. Wipe the surface
with a clean, dampened, soft cloth. Follow with a dry,
soft towel. Take care not to scratch the glass surface.
2. Place the gasketed glass within the frame and press
each of the retainer clips back into place on the
retainer walls.
WARNING:
DO NOT USE ABRASIVE CLEANERS ON THE
GLASS. NEVER CLEAN THE GLASS WHEN IT
IS HOT.
Gasket Inspection
It is important that the glass gasket be inspected at
least annually. Examine the ribbon gasket for signs of
deterioration and make sure the gasket has a positive
seal. Replace the gasket if necessary. Refer to the
replacement parts list on page 29.
Figure 41. Wrap the gasket around the glass panel.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Optional Blower # 156000
6
Connect the gas supply line to the stove,
before installing the Blower.
Use a 90° Elbow off the control valve to create
7
5
8
clearance required for the blower installation.
11
1
1. Unpack and check the contents of the blower kit.
Contact your dealer if any damage is evident or
parts are missing. See fig. 42.
2
3
9
7
2. Attach the Snapstat Bracket to the studs located in
the middle of the firebox floor using the two M6
hex nuts and a 10 mm wrench. See fig. 43.
4
3. Attach the Blower Bracket to the stove using the
10
two M6 flange head hex bolts as shown in fig. 43.
4. Attach the Duct Deflectors using the two #7 x 1/2”
screws together with the finger guard mounting
screws already in place. See #7 and #11 in fig. 42.
Contents
1. Blower
2. Mounting Bracket
3. Snapstat Wire Harness
4. Control Switch Wire Harness
5. Snapstat
6. Snapstat Bracket
Tools Required
• 10 mm wrench
* short phillips screwdriver
* Safety Glasses
* Work Gloves
5. Install the Blower with the duct openings oriented
up and forward. See fig. 44. Feed the wire harness
through the bracket opening and secure the blower
to the bracket with the wingscrew.
6. Attach either Snapstat wire connector to either
7. Blower Duct Deflector (2)
8. M6 Hex Head Flange Nuts (2)
Snapstat terminal. See fig. 44.
9. M6 x 12 Hex Head Flange Bolts (2)
10. M6 x 12 Wingscrew
11. #7 x 1/2” phillips screw (2)
7. Install the Snapstat by sliding it all the way into the
slot in the bottom of the Snapstat Bracket as shown
in figs. 42 and 44.
Figure 42. Blower Kit Components
8. Connect the male wire harness connector to the
female wire harness connector already installed in
the stove. See fig. 44.
9. Connect power cord to outlet.
Hex Head
Flange Bolts
THIS BLOWER MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH
LOCAL CODES OR, IN THE ABSENCE OF
LOCAL CODES, WITH THE CURRENT
ANSI/NFPA 70, NATIONAL ELECTRICAL
CODE OR CSA C22.1-CANADIAN
ELECTRICAL CODE.
Snapstat
Bracket
Hex Head
Flange Nuts
THIS UNIT IS SUPPLIED WITH A
THREE-PRONG (GROUNDING) PLUG
FOR PROTECTION AGAINST SHOCK
HAZARD AND SHOULD BE PLUGGED
DIRECTLY INTO A PROPERLY
GROUNDED THREE-PRONG
Blower Bracket
Figure 43. Attach Snapstat and Blower Brackets.
RECEPTACLE. DO NOT CUT OR
REMOVE THE GROUNDING PRONG
FROM THE PLUG.
ALWAYS DISCONECT THE POWER
SUPPLY WHEN PERFORMING ANY
SERVICE ON THE FIREPLACE INSERT.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 44. Attach Blower to the Mounting
Bracket with the wingscrew and connect
wires to Snapstat and female control
quickconnect.
Snapstat
Connectors
Male
Quickconnector
to Female
Quickconnector
Wingscrew
Blower Operation
The optional variable-speed blower will enhance heat
circulation around the firebox and out into the room.
The blower is controlled by a heat activated switch
(snapstat) that will ONLY function when the control
switch is in AUTO setting. After the fire has been
burning for a time, the snapstat will react to the heat
and activate the blower. Fan speed may be manually
adjusted with the rheostat knob. If the burner turns off,
the blower will be shut off automatically when the
stove cools down.
Blower Speed
Control
If automatic blower circulation is not desired, place
the blower control switch in the MANUAL position.
Figure 45. Blower Controls
BLOWER
G
W
BK
BK
BK
BK
W
G
P
P
BK
BL
BK
BK
RHEOSTAT
GY
POWER
SUPPLY
SNAPSTAT
BR
P
P
P
P = QuickConnector Pin
BL
GY BR
SWITCH
MANUAL OFF AUTO
Figure 46. Blower Wiring Diagram
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Right Panel
220600
Left Panel
220601
Optional Antique Brick
Panel Kit 155375
Rear Panel 220599
Tools Required: Safety glasses and gloves
Figure 47. Brick Kit Contents
1. Remove the Top Plate. Simply lift if up off of the
stove body. It is not fastened.
2. Remove the Glass Frame. Disengage the two
compression latches located at the top of the
firebox and lift the glass frame up and off of the
stove. See Fig. 1.
Glass Frame
Latch
3. Remove the Logset.
These parts are not fastened. Simply lift them out
of the firebox. You do not have to remove the
embers.
4. Install the Rear Panel.
Tilt the Rear Panel top first to slide behind the
exhaust baffle and position it up against the back
wall.
5. Install the Side Panels. Tilt each panel, bottom
edge first, into position against the side walls. The
panels will stand on their own against the wall.
Push them back against the Rear Panel.
Figure 48. Release the glass frame latches.
6. Reinstall the Logset.
Exhaust Baffle
See page 21. BE CERTAIN THAT NO EMBERS ARE
BLOCKING THE PILOT ASSEMBLY OPENING.
7. Replace the Glass Frame.
Slide the frame down the slot in the front of the firebox.
Be sure to push the frame into the slot in the bottom to
ensure it is fully seated. The gasket at the top of the
frame should be flush with the top of the firebox.
Pull the compression latches out to engage with the top
lip of the glass frame.
8. Replace the Top Plate.
Figure 49. Install the Rear Panel to fit behind baffle.
Figure 50. Install the Side Panels.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
GF 400 DV Sebago
Illustrated Parts
Breakdown
42
35
40
38
56 36
45
44
43
41
39
37
34
33
1
32
31
64
2
3
30
29
28
27
49
4
25
54
51
52
55
26
56
53
5
24
6
23
22
7
8
63
58
59
60
61
62
57
9
10
11
48
17
46
47
19 20
50
21
12
13
14
15
16
18
Figure 51. Illustrated Parts Breakdown - GF400 DV Sebago
Side-mount Valve shown.
Center-mounted valve uses same components.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
GF 400 DV Sebago Parts List
Cast Iron Parts
Matte Black
Blue Black Enamel Ivory Enamel
Green Enamel Jøtul Iron
Jøtul Iron Enamel
7.
9.
Left Side Plate
Bottom Plate
Legs, (4)
10391892
10396392
10192592
15565492
10421692
10391992
10396292
10391827
10396327
10192527
155660
10391829
10396329
10192529
155672
10391832
10396332
1092532
155666
10391885
10396385
10192585
15565485
10421685
10391985
10396285
10391846
10396346
10192546
15565446
10421646
10391946
10396246
14.
19.
23.
25.
41.
Front, Complete
Right Door
10421627
10391927
10396227
10421629
10391929
10396229
10421632
10391932
10396232
Right Side Plate
Top Plate
50.
Left Door
10421592
10421527
10421529
10421532
10421585
10421546
35.
36.
37.
38.
39.
40.
42.
43.
44.
45.
46.
47.
48.
Exhaust Restrictor .................................................... 220563
Exhaust Restrctor Gasket ....................................... 220583
Firebox Assembly ...................................................... 221194
Latch Assembly .......................................................... 220091
Relief Door Gasket .................................................... 129319
Relief Door .................................................................. 129640
Relief Door Guide ...................................................... 129499
Heat Fins, (4) ............................................................... 155653
Inner Shroud, Right .................................................. 220596
Inner Shroud, Left ..................................................... 220597
Ignitor Bracket ........................................................ 3902576
Ignitor ....................................................................... 3902573
Burner Orifice, NG #33 ............................................ 220641
Burner Orifice, LP 1.65mm .................................... 220638
Primary Air Shutter .................................................. 220790
Rheostat Knob ........................................................... 220709
Rocker Switch, (2) ...................................................... 220703
Rheostat ...................................................................... 220970
Retaining Collar ........................................................ 220717
Fender Washer ........................................................... 118023
Wingnut, (3) ............................................................... 117975
Wire Harness .............................................................. 156001
Control Door Hinge .................................................. 221176
Bolt, M6 x 20 Blk Hex Hd ........................................ 117117
Spacer, .375 o.d. x 3.172 .......................................... 118040
Washer, Fender .250 x 1.500 dia. .......................... 118029
Bolt, M6x100 Hex ..................................................... 117955
Spacer, .250 x .50 x .250 Alum, .............................. 117994
Spacer, .250 x .50 x .125 Alum, ............................. 118009
*Wire Harness Retainer ........................................... 220733
1.
Air Divider ................................................................... 220624
Simpson DuraVent Collar ....................................... 129126
Collar Gasket .............................................................. 129118
Wire Harness Assembly .......................................... 155397
Rating Plate ................................................................ 220613
Lanyard ........................................................................ 129159
Rear Shroud ................................................................ 220558
Valve Bracket .............................................................. 220352
Valve - NG ................................................................... 220520
Elbow, 3/8” Brass ...................................................... 129129
Terminal Block ........................................................... 129154
Bracket,Terminal Block ........................................... 220614
Gas Line, 5/16” Flex .................................................. 129390
Orifice Holder Assembly ......................................... 129668
Glass Frame Assembly ............................................. 155398
Glass Panel Replacement Kit ................................. 155553
Glass Pane, Ceramic ................................................. 220567
Glass Gasket, 7/16”Tadpole .................................. 129124
Glass Frame ........................................................... 12972592
Glass Clips, (4) ............................................................ 220042
Keeper, Door Latch .................................................... 220604
Control Door............................................................... 221188
Door Latch .................................................................. 220603
Log Set ......................................................................... 155378
Air Intake Gasket ....................................................... 220642
Air Intake Restrictor ................................................. 220602
Air Shutter Gasket .................................................... 220734
Pilot Assembly Gasket ............................................. 129670
Pilot Assembly Spacer ............................................. 220546
Pilot Assembly, w/NG orifice ................................. 129471
Pilot Orifice NG #51 ................................................. 129472
Pilot Orifice LP #30 .................................................. 129473
Jam Nut - Orifice Holder ......................................... 129152
Ferrule (2) .................................................................... 129463
Nut (2) .......................................................................... 129464
Pilot Line w/ Fitting .................................................. 129446
Thermocouple ........................................................... 129766
Electrode ..................................................................... 129765
Thermopile .............................................................. 3094527
Burner Assembly ....................................................... 155336
Burner Skirt ................................................................ 220582
Exhaust Baffle ............................................................ 220565
2.
3.
4.
5.
6.
8.
10.
11.
12.
13.
15.
16.
17.
18.
49.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
20.
21.
22.
24.
26.
27.
28.
29.
30.
31.
Accessories
Variable Speed Blower .................................. 156000
Brick Panel Kit.................................................. 155375
Wall Thermostat ............................................. 750003
Remote Control ............................................... 750002
Floor Bracket Kit ............................................. 750304
Fuel Conversion Kit to Propane .................. 156003
Fuel Conversion Kit to Natural Gas ........... 156004
32.
33.
34.
ALWAYS USE REPLACEMENTS PARTS
PROVIDED BY AN AUTHORIZED JØTUL
DEALER ONLY.
* Parts not illustrated
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Record the following information to help
your dealer determine what you will need for
parts and service.
GF 400 DV Sebago
MODEL NAME: ________________________
SERIAL NUMBER: ______________________
DATE OF PURCHASE: ___________________
PURCHASED FROM: ____________________
NAME OF INSTALLER: ___________________
TYPE OF FUEL: ________________________
WAS STOVE CONVERTED? _______________
NOTES:
RETAIN THIS MANUAL FOR REFERENCE
AND MAKE IT AVAILABLE TO ANYONE
USING OR SERVICING THE STOVE.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING.
WARNING:
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
• If your gas supplier cannot be reached, call the
fire department.
A. This appliance has a pilot which must be lit
by hand. When lighting the pilot, follow
these instructions exactly.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to repair
it. Call a qualified technician. Force or attempted
repair may result in a fire or explosion.
B. BEFORE LIGHTING, smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle to the floor.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS:
• Extinguish any open flame.
• Open windows.
• Do not light any appliance.
• Do not touch any electrical switches.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
7. Push in gas control knob slightly and turn counter-
clockwise
to“PILOT”.
2. Access the lower controls.
8. Push in control knob all the way and hold in.
Immediately light the pilot by triggering the spark
ignitor (push the red button repeatedly) until pilot
lights. Continue to hold the control knob in for
about one minute
3. Turn the stove ON/OFF switch to“OFF”, or set the
thermostat to lowest setting (if used).
4. Confirm that the gas supply line shut-off valve is open.
after the pilot lights.
Release knob and it
should spring back.
Control
Knob
The pilot should
remain lit. If it goes
out, repeat Steps 5
through 8.
Pilot Assembly
Control Valve
• If knob does not
return when released, stop and immediately call
your service technician or gas supplier.
5. Push in gas control knob slightly and turn clockwise
to“OFF”.
• If pilot will not stay lit after several tries, turn
the control knob to OFF and call your service
technician or gas supplier.
NOTE: Knob cannot be turned from“PILOT”to“OFF”
unless the knob is pushed in slightly. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow“B”in the safety information
above on this page. If you do not smell gas, go to the
next step.
9. Turn gas control knob counterclockwise
to“ON”.
10. Turn the stove ON/OFF switch to“ON”, or set
thermostat (if used) to desired temperature.
TO TURN OFF GAS TO THE APPLIANCE:
1. Turn ON/OFF switch to”OFF”. The pilot will remain lit for
3. Access the lower controls.
normal service.
4. Depress gas control knob slightly and turn clock-
2. For complete shutdown, turn ON/OFF switch to“OFF”.
wise
to“OFF”. Do not force.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
This appliance must be installed in conformance with local and national building regulations. Before
beginning the installation, it is important that the these instructions be carefully read and understood.
Jøtul maintains a policy of continual product development. Consequently, products may differ in
specification, color or type of accessories from those illustrated or described in various publications.
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les
specifications, couleurs etequipement sans avis prelable.
Jøtul AS
P.O. Box 1411
N-1602 Fredrikstad
Norway
Jøtul North America
55 Hutcherson Dr.
Gorham, ME 04038-2634
Download from Www.Somanuals.com. All Manuals Search And Download.
|