Jotul Electric Heater GF 400 DV User Manual

WARNING:  
IF THE INFORMATION IN THESE INSTRUCTIONS  
ARE NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-  
SION MAY RESULT CAUSING PROPERTY DAMAGE,  
PERSONAL INJURY OR LOSS OF LIFE.  
FOR YOUR SAFETY:  
DO NOT STORE OR USE GASOLINE OR OTHER  
FLAMMABLE VAPORS AND LIQUIDS IN THE VICIN-  
ITY OF THIS OR ANY OTHER APPLIANCE.  
INSTALLATION:  
INSTALLATION AND SERVICE MUST BE PER-  
FORMED BY A QUALIFIED INSTALLER, SERVICE  
AGENCY OR LICENSED GAS SUPPLIER.  
THIS PRODUCT MUST BE INSTALLED BY A  
LICENSED PLUMBER OR GAS-FITTER WHEN  
INSTALLED IN THE COMMONWEALTH OF  
MASSACHUSETTS.  
A CARBON MONOXIDE (CO) DETECTOR SHALL  
BE INSTALLED IN THE SAME ROOM AS THE  
APPLIANCE.  
Jøtul GF 400 DV  
Sebago  
Gas Heater  
WHAT TO DO IF YOU SMELL GAS:  
• DO NOT TRY TO LIGHT ANY APPLIANCE.  
• DO NOT TOUCH ANY ELECTRICAL SWITCHES.  
• DO NOT USE THE PHONE IN YOUR BUILDING.  
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A  
NEIGHBOR’S PHONE.  
• FOLLOW YOUR GAS SUPPLIER’S INSTRUCTIONS.  
• IF YOU CANNOT REACH YOUR GAS SUPPLIER,  
CALL THE FIRE DEPARTMENT.  
AVERTISSEMENT:  
ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUC-  
TIONS DANS CETTE NOTICE POUR REDUIRE AU  
MINIMUM LE RISQUE D’INCENDIE OU POUR EVITER  
TOUT DOMMAGE MATERIEL, TOUTE BLESSURE OU  
MORTALIT’E.  
NE PAS ENTREPOSER NI UTILISER D’ESSENCE NI  
OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE  
DE CET APPAREIL OU DE TOUT AUTRE APPAREIL.  
Installation  
and  
Operation  
Instructions  
L’INSTALLATION LE SERVICE DOIVENT ETRE  
EXECUTES PAR UN INSTALLATEUR QUALIFIE,  
AGENCE DE SERVICE OU LE FOURNISSEUR DE  
GAZ.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.  
• NE PAS TENTER D’ALLUMER L’APPAREIL  
• NE TOUCHEZ A AUCUM NTERRUPTEUR.  
• NE PAS VOUS SERVIR DES TELEPHONES SE  
TROUVANT DANS LE BATIMENT OU VOUS VOUS  
TROUVEZ.  
• APPELEZ IMMEDIATEMENT VOTRE FOURNISSEUR  
DE GAZ CHEZ UN VOISIN. SUIVEZ LES INSTRUC-  
TIONS DU FOURNISSEUR.  
• SI VOUS NE POUVEZ REJOINDRE LE  
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE DES  
INCENDIES.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jøtul GF 400 DV  
Sebago  
Direct Vent Gas Heater  
Manufactured and Distributed by:  
Jøtul A.S.A.  
Table of Contents  
Service Tools .............................................. 3  
Specifications ........................................... 4  
General Information ............................... 5  
Safety Information .................................. 6  
Installation Requirements  
Fredrikstad, Norway  
Jøtul North America  
55 Hutcherson Dr.  
Gorham, Maine 04038-2634  
Location ................................................. 6  
Hearth Protection .............................. 6  
Clearances ............................................ 7  
Mantel & Trim ..................................... 7  
Alcove..................................................... 7  
Vent Requirements ................................. 8  
Adding Restriction.............................. 8  
Vertical Termination .......................... 9  
Co-linear Termination .................. 12  
Coaxial Chimney Conversion..... 13  
Horizontal Termination................... 14  
Vent Terminal Clearances ............... 15  
Mobile Home Installation ................... 16  
Fuel Conversion...................................... 16  
Gas Connection ...................................... 18  
Gas Pressure............................................ 19  
High Altitude Adjustment .................. 19  
Air Shutter Adjustment ....................... 20  
Wall Thermostat .................................... 20  
Remote Control ...................................... 20  
Log Set Installation ............................... 21  
System Check.......................................... 22  
Operation................................................. 23  
Maintenance........................................... 24  
Glass Replacement ............................ 24  
M.E.A. 369-04-E  
Test Standards  
This appliance complies  
with National Safety  
standards and is tested  
and listed by Intertek  
Testing Services of  
Middleton, Wisconsin to  
ANSI Z21.88-2002 •  
CSA 2.33-M02 and CAN/CGA 2.17--M91,  
CSA P.4 -01.2 for Canada.  
DO NOT ATTEMPT TO ALTER OR MODIFY THE  
CONSTRUCTION OF THE APPLIANCE OR ITS  
COMPONENTS. ANY MODIFICATION OR ALTER-  
ATION WILL VOID THE WARRANTY, CERTIFICA-  
TION AND LISTING OF THIS APPLIANCE.  
Optional Blower Installation .............. 25  
Optional Brick Kit Installation ........... 27  
Illustrated Parts Breakdown ............... 28  
Replacement Parts List......................... 29  
Lighting Instructions ............ Back Cover  
THIS PRODUCT MUST BE INSTALLED  
BY A LICENSED PLUMBER OR  
GAS-FITTER WHEN INSTALLED IN THE  
COMMONWEALTH OF MASSACHUSETTS.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
GF 400 DV Sebago  
Specifications  
Specifications  
28 1/2”  
724 mm  
Input Rates  
Natural Gas  
32,000 BTU/hr. maximum input  
18,000 BTU/hr. minimum input  
Propane  
26 1/2”  
673 mm  
32,000 BTU/hr. maximum input  
16,000 BTU/hr. minimum input  
Inlet Pressure:  
MIN  
MAX  
13”  
330 mm  
Natural Gas:  
Propane:  
5.0 WC (1.24 kPa)  
12.0 WC (2.99 kPa) 14.9 WC (3.71 kPa)  
7.0 WC (1.74 kPa)  
Manifold Pressure: MIN  
MAX  
Natural Gas:  
Propane:  
1.2 WC (.30 kPa)  
2.9 WC (.722 kPa)  
3.8 WC (.95 kPa)  
11.0 WC (2.74 kPa)  
26 1/2”  
673 mm  
Piezo Ignitor / Standing Pilot  
C
L
Suggested Tools for  
Installation and Service  
• External regulator (for Propane only)  
• Piping which complies with local code  
• Manual shutoff valve (T-Handle in Massachusetts)  
• Sediment trap - if required by code  
• Tee joint  
28 1/2”*  
724 mm  
25 1/2”*  
647 mm  
19 5/8”  
500 mm  
• Pipe wrench  
• Pipe sealant  
• 10 mm open end wrench  
• 1/2”, 7/16” open end wrench or deep socket  
• Phillips head screwdriver  
• Flat head screwdriver  
• 1/4” nut driver  
29”  
737 mm  
• 4 mm allen wrench  
• Gloves  
• Safety glasses  
• Torx T20 screwdriver  
• Leak test solution  
• Reciprocating Saw  
19 1/2”  
495 mm  
• Power Drill  
*For height with 6” Legs, subtract 2 1/4”  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
THIS HEATER MUST BE INSTALLED AND MAINTAINED  
Glass Panel  
BY A QUALIFIED SERVICE AGENCY.  
Do not operate this appliance with the glass  
front removed, cracked, or broken. Replacement  
of the glass should be done by a licensed or  
qualified service person. Only remove glass for  
routine service. Always handle glass carefully.  
The installation and repair of this appliance must be  
done by a qualified service person. Failure to  
properly install and maintain this heater could result  
in an unsafe or hazardous installation, which may  
result in a fire, explosion, property damage, personal  
injury or loss of life.  
This appliance should be inspected before use and at  
least annually. More frequent cleaning may be  
required due to excessive lint from carpeting,  
bedding material, etc. It is imperative that control  
compartments, burners, and circulating air passage-  
ways of the appliance be kept clean.  
Unpacking your stove  
1. Remove the Top Plate of the stove by simply lifting it  
straight off of the stove body.  
2. To open the firebox, disengage the two Glass Frame  
Latches located on top of the firebox. Pull each handle  
forward to clear the latch from the notch in the  
frame.  
THIS APPLIANCE MUST NOT BE CONNECTED TO A  
CHIMNEY OR FLUE SERVING ANY OTHER APPLIANCE.  
The installation must conform to local codes. Your  
local Jøtul dealer can assist you in determining what  
is required in your area for a safe and legal installa-  
tion. Some areas require a permit to install a gas  
burning appliance. Always consult your local  
Glass Frame  
Latch  
building inspector, or authority having jurisdiction,  
to determine what regulations apply in your area.  
CODE COMPLIANCE : Your local officials have final  
authority in determining if a proposed installation is  
acceptable. Any requirement that is requested by  
the local authority having jurisdiction, that is not  
specifically addressed in this manual, defaults to  
local code. In the absence of local codes, the installa-  
tion requirements must comply with the current  
National codes. In the U.S., these requirements are  
established in the National Fuel Code, ANSI  
3. Familiarize yourself with the installation require-  
ments specified in this manual, before beginning the  
installation.  
Z223.1.(NFPA 54). In Canada, the codes have been  
established in CAN/CGA B149 Fuel Installation Code.  
Hardware Bag Contents  
• Fuel Conversion Kit - LP................................ 155351  
Installer l’appareil selon les codes ou reglements  
locaux, ou, en l’absence de tels reglements, selon les  
Codes d’installation CAN/CGA-B149.  
• Ember Bag , 4 oz. ............................................ 129123  
DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN  
UNDER WATER. Call a qualified service technician to  
inspect the heater and to replace any part of the  
control system and any gas control which may have  
been under water.  
THIS FIREPLACE IS SHIPPED FROM  
THE FACTORY FOR USE WITH  
NATURAL GAS ONLY. IF USE WITH  
PROPANE IS DESIRED, THE APPLIANCE  
MUST FIRST BE CONVERTED USING  
THE FUEL CONVERSION KIT  
Ne pas se servir de cet appareil s’il a ete’ plonge dans  
l’eau, completement ou en partie. Appeler un  
technicien qualifie pour inspecter l’appareil et  
remplacer toute partie du syste’me de controle et  
toute commande qui ont ete plonges dans l’eau.  
PROVIDED, #155351. CONVERSION  
SHOULD BE MADE BEFORE THE  
APPLIANCE IS INSTALLED. SEE PG. 16.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Information  
Location  
During normal operation, the GF 400 DV Sebago gas  
stove will reach high surface temperatures. Therefore:  
In selecting a location for the stove, consider the  
following points:  
1) Heat distribution  
2) Vent termination requirements  
3) Gas supply line routing  
4) Traffic areas, furniture, draperies, etc.  
Due to the high operating temperatures, this appli-  
ance should be located out of traffic areas and away  
from furniture and draperies.  
The GF 400 DV Sebago may be located on or near  
conventional construction materials, however, proper  
clearance to combustibles must be maintained in order  
to provide adequate air circulation around the appliance.  
Also, it is important to provide adequate access around  
the stove for servicing and proper operation.  
Children and adults should be alerted to the hazards  
of high surface temperatures and should stay away to  
avoid burns and/or clothing ignition.  
The clearance and hearth specifications listed in this  
manual are the minimum requirements for combustible  
material. A combustible material is anything that can  
burn (i.e. sheet rock, wall paper, wood, fabrics etc.). These  
surfaces are not limited to those that are visible and also  
include materials that may be located behind non-  
combustibles.  
Young children should be supervised while they are in  
the same room as the GF 400 DV Sebago gas stove.  
Clothing or other flammable materials should not be  
placed ON or NEAR the GF 400 DV Sebago gas stove.  
Surveiller les enfants. Garder les vetements, les  
meubles, l’essence ou autres liquides a vapeur  
inflammables loin de l’appareil.  
If you are not sure of the combustible nature of a  
material, consult your local fire officials. Remember,Fire  
Resistant” materials are considered combustible: they  
are difficult to ignite, but will burn. Also,fire-rated”  
sheet rock is considered combustible.  
NEVER store or use gasoline or any other flammable  
vapors or liquids in the vicinity of the GF 400 DV  
Sebago gas stove.  
Hearth Requirements  
The GF 400 DV Sebago gas stove CANNOT be installed  
directly on carpeting, vinyl, linoleum or Pergo®.  
Never burn any other materials in your GF 400 DV  
Sebago gas stove, it is strictly designed for use with  
natural gas or propane fuel ONLY.  
If this appliance will be installed on any combustible  
material OTHER THAN WOOD, a floor pad must be  
installed that is either metal or wood, or a listed hearth  
pad. This floor protection must extend the full width  
and depth of the appliance. It is not necessary to remove  
carpeting, vinyl or linoleum from underneath the floor  
protection. See fig. 1.  
·Any safety screen, glass or guard removed for servic-  
ing the appliance must be replaced prior to operating  
the appliance.  
Figure 1. Minimum Hearth Protection.  
14”  
(356 mm)  
27”  
(686 mm)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Stove and Vent Clearance  
Requirements  
Minimum Clearances from the Stove  
to Combustibles: See figs. 2-4.  
Rear:  
2” (51 mm)  
2”  
(51 mm)  
To Rear Wall  
Ceiling:  
Corner:  
Sides:  
32 1/4” (819 mm)  
2” (51 mm)  
3” (76 mm)  
3”  
(76 mm)  
3”  
(76 mm)  
Minimum Clearances from the Vent Pipe to  
Combustibles:  
Figure 3. Parallel Installation Clearances.  
Horizontal Run:  
Off the top of the pipe  
2” (51 mm)  
Off the sides and bottom 1” (25 mm)  
Vertical Run:  
2”  
51 mm  
All sides  
1” (25 mm)  
Minimum Ceiling or Alcove Height  
2”  
51 mm  
Max. Mantel Depth  
12.5”  
10.25”  
8”  
Figure 4. Corner Clearances.  
5.75”  
Min. Mantel Depth  
Max. Top Trim Depth = 1”  
3.5”  
2” (5.1cm)  
Alcove Installation  
Maximum Alcove Depth: 24” (61 cm)  
Minimum Alcove Width: 31 3/4” (80.6 cm)  
Minimum Ceiling Height: 61” (155 cm)  
Figure 2. Mantel and Trim Clearance specifications.  
Back of bottom plate is flush with the fireplace face.  
Subtract 2 1/4” with Short Legs.  
With Short Legs (6”) :  
59” (150 cm)  
Alcove dimensions result from test  
configurations, not stove clearance  
specifications.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting Requirements  
Vent Restriction  
The GF 400 DV Sebago is equipped with Restrictor Plates  
which enable you to regulate the flow of incoming  
combustion air and exhaust gas. The plates prevent  
overly strong draft that can cause poor combustion and  
weak flame picture. Follow the guidelines below, and on  
the following pages, to determine the correct restrictor  
plate setting for your particular installation configura-  
tion.  
The Jøtul GF 400 DV Sebago gas stove may be installed  
with a vertical or horizontal termination and must  
conform to the configuration requirements described  
below.  
This appliance is approved for use with vent systems  
from the following manufacturers:  
Simpson Dura-Vent GS  
• Amerivent Corporation  
• Security Vent Ltd.  
• Selkirk Metalbestos  
Intake Air Restrictor  
Use parts of one manufacturer only - DO NOT MIX  
VENT COMPONENTS FROM DIFFERENT MANUFACTURERS  
IN THE SAME SYSTEM.  
This plate is located at the rear of the firebox behind the  
burner plate. It is set in a CLOSED position at the factory  
and should be left there for most vent configurations.  
It should be opened only for snorkel terminations and  
some short run horizontal terminations as specified on  
the following pages. To adjust the Air Restrictor to the  
OPEN position, locate and loosen the wing nut under the  
burner and push it back as far as it will go. See Fig. 6.  
Installation of any components not manufactured or  
approved by Jøtul or failure to meet all clearance require-  
ments will void all warranties and could result in prop-  
erty damage, bodily injury, or serious fire.  
The approved vent configurations described in this  
manual are derived from extensive testing under con-  
trolled laboratory conditions. Gas appliance performance  
can be negatively affected by variables present in the  
installation environment, i.e: atmospheric pressure,  
strong prevailing winds, adjacent structures and trees,  
snow accumulation, etc. These conditions should be  
taken into consideration by the installer and stove owner  
when planning the vent system design.  
Exhaust Restrictor  
The Exhaust Restrictor is an adjustable shutter located at  
the top of the firebox. It is adjusted by moving a pivot  
pin into one of four positions. It is set in the FULLY OPEN  
position at the factory. See Fig. 7.  
Use the chart in Table 1 to determine the correct  
position for your installation and follow the instructions  
below to adjust it if necessary.  
IMPORTANT  
• JOINT SEALING REQUIREMENT: APPLY A 1/8” BEAD OF  
HIGH-  
Additional restriction may be needed depending the  
overall vent height. Use Simpson Dura-Vent Restrictor  
Disk #929.  
TEMPERATURE (750°F) SEALANT TO THE MALE SEC-  
TION OF THE INNER VENT PIPE. THE CEMENT SHOULD  
FORM A SEAL BETWEEN THE INNER  
AND OUTER PIPES.  
Adjusting Exhaust Restrictor Plate:  
1. Remove the Top Plate.  
2. Locate the pivot pin at the left side of the firebox top.  
Loosen the wing nut on the pivot pin and push the pin  
to the left to disengage it from the current setting  
position. Move the pin toward the rear and then right  
to engage it in the appropriate position indicated on  
the firebox. See fig. 7.  
• NEVER MODIFY ANY VENTING  
COMPONENT, OR USE ANY DAM-  
AGED VENTING PRODUCT.  
• THE GAS APPLIANCE AND VENT  
S
SYSTEM MUST BE VENTED  
E
A
L
A
N
DIRECTLY TO THE OUTSIDE OF  
T
3. Tighten the lock nut and replace the Top Plate.  
THE BUILDING AND NEVER  
ATTACHED TO A CHIMNEY  
SERVING A SOLID FUEL OR  
GAS BURNING APPLIANCE.  
Fig. 5.  
EACH DIRECT VENT GAS APPLIANCE  
MUST HAVE ITS OWN SEPARATE VENT SYSTEM.  
COMMON VENT SYSTEMS ARE PROHIBITED.  
• IF VENTING SYSTEM IS DISASSEMBLED FOR ANY  
REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED  
FOR THE INITIAL INSTALLATION.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
FRONT  
LEG  
BACK  
LEG  
Push the  
Pivot Pin into  
the slot  
Default  
Factory  
Setting is  
“D”  
Fully Closed  
A
B
C
D
Fully Open  
Figure 6. Adjusting the Air Inlet Restrictor plate - View is  
from the right side of the stove.  
Vertical Vent Termination  
The Jøtul GF 400 DV Sebago can be vertically vented  
through a ceiling or to a roof termination with the  
following guidelines:  
A
B
C
D
The termination should fall within the shaded areas  
of the grids depicted in the Vent Window diagrams on  
the pages 10-11.  
Front of  
Stove  
Maximum Vertical run should not exceed 35 ft. (10.66 m).  
Minimum Vertical run must be at least 8 ft. (2.43 m).  
Max. Colinear Horizontal run is 2 ft. (61 cm).  
Figure 7. Adjusting the Exhaust Restrictor plate - Top Plate  
removed. Viewed from front of stove.  
Vent Terminus Clearance: In no case shall any dis-  
charge opening on the cap be less than 18 in. (610  
mm) horizontally from the roof surface.  
Steep roofs, nearby trees, and predominantly windy  
conditions can contribute to poor draft and/or  
promote down-draft occurances. Increasing the  
height of the vent may alleviate these conditions.  
Horizontal Overhang  
18”.  
min.  
18”.  
min.  
Use Wall Straps to support an offset pipe run at three  
Lowest Discharge  
Opening  
feet intervals to avoid excessive stress on the offsets.  
Termination  
Cap  
Elbows: Four 45°, or two 90° elbows may be used. Do  
not include the 45° elbow attached to the stove.  
Whenever possible use 45° elbows instead of 90°  
elbows as they are less restrictive to exhaust gas and  
intake air flow.  
18” min.  
A firestop is required at every floor. The opening  
should be framed to 10" X 10" inside dimension.  
Any venting that is exposed above the first floor,  
regardless of attic space or living space, must be  
enclosed. Always maintain the required 1" clearance  
from all sides of the vertical vent system.  
Figure 8. Vertical vent termination height above roof.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent Termination Zones - Natural Gas  
Vertical  
Termination for  
COLINEAR VENT  
35 Ft.  
(10.67 m)  
Horizontal and Vertical  
Terminations for COAXIAL VENT  
35 Ft.  
(10.67 m)  
30 Ft.  
(9.14 m)  
Up to four 45° or  
two 90° elbows  
permitted in  
addition to the  
starter elbow.  
25 Ft.  
(7.62 m)  
A
B
25 Ft.  
(7.62 m)  
20 Ft.  
(6.10 m)  
A
B
15 Ft.  
(4.57 m)  
B
12 Ft.  
(3.65 m)  
C
Min. Vertical  
Termination  
D
8 Ft.  
(2.43 m)  
Minimum  
Vertical  
5 Ft.  
Termination  
(1.52 m)  
8 Ft.  
(2.43 m)  
Min. Rise  
2 Ft.  
(.60 m)  
5 Ft.  
(1.52 m)  
10 Ft.  
(3.05 m)  
15 Ft.  
20 Ft.  
(6.09 m)  
27 Ft.  
(8.22m)  
(4.57 m)  
HORIZONTAL RUN  
2 Ft.  
• ALL VENTING MUST TERMINATE (END) WITHIN ONE OF  
THE SHADED AREAS.  
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION  
THAT CORRESPONDS TO THE VENT TERMINATION AREA  
IN THE DIAGRAM ABOVE.  
(16 cm)  
HORIZONTAL RUN  
• VENTING MUST TERMI-  
NATE (END) WITHIN THE  
SHADED AREA.  
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO  
COMBUSTIBLES.  
• Adjust the Exhaust  
Restrictor to position B  
for any NG colinear  
termination.  
The circled letter designations in the vent diagram correspond  
to the Exhaust Restrictor Setting on the stove. First, determine  
which vent termination zone is appropriate for your installation  
and fuel type, then adjust the restrictor to the corresponding  
position as shown in Figure 7, page 9.  
Figure 9. Coaxial Vent Termination Window / NG  
Figure 10 . Colinear Termination / NG  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent Termination Zones - Propane  
Vertical  
Termination for  
COLINEAR VENT  
35 Ft.  
(10.67 m)  
35 Ft.  
(10.67 m)  
Horizontal and Vertical  
Terminations for COAXIAL VENT  
30 Ft.  
(9.14 m)  
Up to four 45° or  
two 90° elbows  
permitted in  
25 Ft.  
(7.62 m)  
addition to the  
starter elbow.  
25 Ft.  
(7.62 m)  
A
20 Ft.  
(6.10 m)  
C
B
15 Ft.  
(4.57 m)  
D
12 Ft.  
(3.65 m)  
D
B
8 Ft.  
(2.43 m)  
Minimum  
Vertical  
Termination  
8 Ft.  
(2.43 m)  
5 Ft.  
(1.52 m)  
OPEN AIR INLET  
RESTRICTOR  
Min. Rise  
2 Ft.  
(.60 m)  
27 Ft.  
(8.22m)  
5 Ft.  
(1.52 m)  
10 Ft.  
(3.05 m)  
15 Ft.  
(4.57 m)  
20 Ft.  
(6.09 m)  
HORIZONTAL RUN  
2 Ft.  
(16 cm)  
• VENTING MUST TERMINATE (END) WITHIN ONE OF THE DESIG-  
NATED AREAS. ZONE “A” IS FOR VERTICAL TEMINATIONS ONLY.  
• VENTING MUST  
TERMINATE (END)  
WITHIN THE SHADED  
AREA.  
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRE-  
SPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM  
ABOVE.  
• OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND  
UNDER. SEE FIG. 6, PAGE 9.  
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.  
• Adjust the Exhaust  
Restrictor to position C  
for a straight vertical  
colinear termination.  
The circled letter designations in the vent diagram correspond  
to the Exhaust Restrictor Setting on the stove. First, determine  
which vent termination zone is appropriate for your installa-  
tion and fuel type, then adjust the stove restrictor plate to the  
corresponding position as shown in Figure 7, page 9.  
• Adjust the Exhaust  
Restrictor to position D  
for a vertical colinear  
termination with  
maximum 2 ft. offset.  
Figure 11. Coaxial Vent Termination Window / LP  
Figure 12 . Colinear Termination / LP  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Wind Cap  
Exhaust Gas  
Co-linear Vent Installation  
Max. Co-linear  
Height - 35 ft.  
(10.66 m)  
Intake Air  
The GF 400 DV Sebago may be vented through a ma-  
sonry or Class A prefabricated chimney using a Co-linear  
Flexible Vent system approved for use with a solid-fuel  
burning fireplace. When installed in the manner de-  
scribed below, this system can improve the performance  
of the appliance in cold climate situations, as well as  
simplify the vent installation. See fig. 13.  
Min. Co-linear  
Height - 10 ft.  
(3.05 m)  
These installation requirements must be followed:  
1. Use the guidelines for Co-linear Vent Termination  
appropriate for your gas type on pages 10 - 11.  
1. Prior to the installation the chimney flue must be  
thoroughly cleaned and inspected by a qualified  
chimney service person.  
2. In a masonry chimney, a fireclay liner must be present  
the entire length of the chimney.  
The Air  
Intake Flex  
pipe must  
extend  
beyond the  
damper.  
3. Prefabricated chimneys must be UL 103 or ULC S-629  
listed and have a minimum INSIDE diameter of 6  
inches, (150 mm).  
The chimney  
must be sealed  
off from the  
room by a steel  
plate at the  
damper area.  
4. No appliance can be installed into a chimney flue  
Dual 3”Flex  
Liners  
serving any other appliance of any kind.  
5. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET  
BEYOND THE DAMPER AREA OF THE FIREPLACE.  
6. If the intake flex duct does not extend the full length  
of the chimney and connect to both the unit and the  
termination cap, A METAL BLOCK OFF PLATE MUST BE  
CONSTRUCTED AND INSTALLED ABOVE THE UNIT  
PRIOR TO THE END OF THE INTAKE FLEX AND MUST  
COMPLETELY SEAL THE CHIMNEY FLUE FROM THE  
ROOM.  
Max. offset  
24”  
(609 mm)  
Figure 13. Co-linear Adaptor installed through a masonry  
chimney. Components shown may differ somewhat from  
manufacturer to manufacturer.  
Consult with the local code authority having juris-  
diction before proceeding with this type of installation.  
Refer to the vent manufacturer’s instructions for  
specific installation requirements.  
WARNING: FAILURE TO POSITION THE PARTS AND  
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR  
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED  
FOR USE WITH THIS APPLIANCE MAY RESULT IN PROP-  
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO  
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES  
AS DEFINED IN THIS MANUAL AND IN THE INSTRUC-  
TIONS PROVIDED WITH EACH VENT COMPONENT.  
29”  
to top of  
Co-linear  
25 1/2”  
Adapter.  
to center  
of flue collar  
Figure 14. Simpson Dura-Vent #923GCL Co-linear Adaptor  
is shown - other manufacturer’s components may differ.  
Subtract 2 1/4” for Short Legs.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vertical  
Termination  
Cap  
Exhaust  
Gas  
Masonry or Prefabricated Chimney  
Conversion  
The GF 400 DV Sebago is approved for use with listed  
chimney conversion kits from any of the manufacturers  
listed on page 8. These kits are for use in a masonry  
chimney or a prefabricated solid fuel listed chimney. See  
fig. 15.  
Cap Adaptor-  
included in  
#934 Kit  
Intake Air  
4” Flex Pipe  
not included  
in kit  
These installation requirements must be followed:  
1. Use the guidelines for Coaxial Vent Termination  
appropriate for your gas type on pages 11 - 12.  
Use standard  
2. In masonry chimney, a fireclay liner or listed steel  
liner, must be present the entire length of the chim-  
ney.  
vent pipe from  
stove to  
Support/Wall  
Thimble Cover  
thimble from  
the same  
manufacturer  
3. Chimney height should not exceed 35 ft. (10.66 m).  
4. The liner must have an inside dimension of 6” round  
or greater.  
5. Prefabricated chimneys must be UL 103 or ULC S-629  
listed and have a minimum INSIDE diameter of 6  
inches, (150 mm). Prefabricated chimneys must be  
listed for the specific Chimney Conversion Kit you  
choose.  
Figure 15. Vent System through a masonry chimney using a  
chimney conversion kit. May also be used in listed  
prefabricated chimneys. Drawing is for illustrative purposes  
only - DO NOT VENT TWO APPLIANCES INTO A SINGLE  
CHIMNEY.  
IMPORTANT NOTICE  
THE USE OF AN EXISTING CHIMNEY  
AS AN AIR INTAKE IS NOT COVERED  
UNDER THE ANSI Z21.88-1999-CSA  
2.33-M99 TEST METHODS AND RE-  
SULTING ITS/WHI PRODUCT CERTIFI-  
CATION. THE CODE AUTHORITY  
HAVING JURISDICTION MUST BE  
CONSULTED PRIOR TO PROCEEDING  
WITH THIS INSTALLATION METHOD.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12 in.  
(305 mm)  
Horizontal Termination  
C
L
Any horizontal termination must fall within the  
shaded portion of the vent window graph illustrated  
in figs. 9 or 11. For Snorkel Terminations, see below.  
24 in.  
Snorkel  
(305 mm)  
Any horizontal termination except a snorkel termination,  
must include:  
14”  
355 mm  
Max.  
1)  
2)  
Minimum rise of 2 ft.  
Minimum horizontal run of 12 in. when vertical  
run is less than 8 ft.  
57”  
(1448 mm)  
2)  
3)  
4)  
Maximum rise of 35 ft.  
Maximum horizontal run of 27 ft.  
No more than four 45° or two 90° Elbows  
12”  
Vent  
Pipe or  
less  
25 1/2 in.  
Snorkel  
(648 mm)  
Follow all termination clearance guidelines as speci-  
fied in fig. 19.  
Figure 16.  
The horizontal termination cap must maintain a 3"  
clearance to any overhead combustible projections  
2 1/2" or less. It must also maintain 12" clearance  
from projections exceeding 2 1/2". See fig. 20.  
• Minimum vent for horizontal termination.  
• 14” Maximum horizontal run directly off rear of stove  
with 14” Snorkel termination.  
Wall Cut-out Opening: A minimum 10" X 10" (250 mm x  
250 mm) square hole is required for proper pipe clear-  
ances through a combustible wall. Use a listed wall  
thimble for the wall penetration.  
36 in.  
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.  
Snorkel  
Max.  
6 ft.  
183 cm  
(915 mm)  
Any horizontal run of vent must have a 1/4" rise for  
every foot of run toward the termination cap. NEVER  
ALLOW THE VENTING TO RUN DOWNWARD FROM  
STOVE TO TERMINATION; DOWNWARD VENT RUNS  
TRAP HEAT AND CAUSE HIGH TEMPERATURES TO  
DEVELOP WITHIN THE VENT THAT COULD START A  
FIRE.  
Install a Vinyl Siding Standoff between the vent  
termination and an exterior wall covered by vinyl  
siding material to prevent potential heat damage to  
the siding.  
Figure 17. Maximum Horizontal and Vertical Run with 36”  
Snorkel Termination.  
Do not recess the termination cap into a wall or  
siding.  
Max.  
14”  
45° Elbow  
355 mm  
Snorkel Terminations  
See Note F  
Fig. 20  
THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN  
FOR ANY SNORKEL TERMINATION. See Fig. 6, pg. 9.  
With a 14” Snorkel:  
The horizontal run made directly off the rear of the  
stove into a 14” snorkel cap should include no more  
than a single 12” straight section as shown in fig. 17.  
One 45° Elbow may be used for a corner installation as  
shown in fig. 18.  
12 in.  
Straight Pipe  
Wall Thimble  
and Trim Collar  
With a 36” Snorkel:  
The maximum horizontal run may be no more than  
6 ft. (182 cm.)  
Figure 18. Corner Installation with 14” Snorkel Termination.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Horizontal Termination Clearance  
Figure 19. Vent Terminal Clearances - National Fuel Gas Code.  
L = 1 Clearance above paved sidewalk or a paved driveway  
located on public property: 7 feet (2.1 m) min.  
A = Clearance above grade, veranda, porch , deck, or  
balcony : 12 inches (30 cm) minimum.  
M = Clearance under veranda, porch, deck, or balcony:  
B = Clearance to window or door that may be opened:  
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.  
We recommend 12in. minimum to prevent condensa-  
tion on the window.  
12 inches (30 cm) minimum. 2  
*
In accordance with CSA B149 Installation Codes.  
C = Clearance to permanently closed window:  
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN  
We recommend 12 in. minimum to prevent condensa-  
tion on the window.  
** In accordance with the current ANSI Z223.1/NFFPA 54,  
National Fuel Gas Code. Note: Local Codes and Regulations may  
require different clearances.  
1 A vent shall not terminate directly above a sidewalk or driveway  
which is located between two single family dwellings and serves  
both dwellings.  
D = Vertical clearance to ventilated soffit located above  
the terminal within a horizontal distance of 2 feet (60 cm)  
from the centerline of the terminal: 18 inches  
(46 cm) minimum.  
2
Only permitted if veranda, porch, deck, or balcony, is fully open  
on a minimum of two sides beneath the floor.*  
E = Clearance to unventilated soffit: 12 inches (46 cm)  
minimum.  
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12  
inches (30 cm) CAN. We strongly recommend 12 inches,  
particularly where windy conditions pevail.  
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12  
inches (30 cm) CAN. We strongly recommend 12 inches,  
particularly where windy conditions pevail.  
2 1/2”  
12 ”  
305  
mm  
64 mm  
H = *Not to be installed within 15 feet (4.5 m) above a  
meter/regulator assembly within 3 feet (90 cm)  
horizontally from the center-line of the regulator.  
3”  
76 mm  
I = Clearance to service regulator vent outlet:  
3 feet (91 cm) minimum.  
J = Clearance to nonmechanical air supply inlet to building  
or the combustion air inlet to any other appliance:  
12 inches (30 cm) minimum.  
K = Clearance to a mechanical air supply inlet:  
**Min. 3 feet (91 cm) above if within 10 feet horizon-  
tally, U.S. / *6 feet (1.83 m) minimum / CAN  
Figure 20. Termination Clearance to overhangs  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mobile Home Installation  
Fuel Conversion  
The GF 400 DV Sebago can be installed for use in a  
mobile home in the U.S. and Canada provided:  
The GF 400 DV Sebago gas stove is shipped from the  
factory equipped to burn NATURAL GAS only. If PROPANE  
gas is to be used as fuel, the appliance must first be  
converted for use with propane. Use Propane Conversion  
Kit 155351, supplied with the appliance.  
1. The stove is secured to the floor of the mobile home.  
Use Jøtul Floor Bracket Kit #154388.  
2. Provision must be made to secure an electrical ground  
Order and install NG Conversion Kit 155352 to  
change back to use with natural gas.  
between the stove and the mobile home chassis.  
3. The stove is installed in accordance with Title 24 CFR,  
Part 3280- Manufactured Home Construction and  
Safety Standard, in the U.S. In Canada, comply with  
CSA Z240.4, Gas Equipped Recreational Vehicles and  
Mobile Housing.  
WARNING:  
THE CONVERSION KIT IS TO BE  
INSTALLED BY AN AUTHORIZED JØTUL  
SERVICE TECHNICIAN IN ACCORDANCE  
WITH THE MANUFACTURER’S  
4. Always contact your local officials about installation  
restrictions and requirements in your area.  
INSTRUCTION AND ALL CODES AND  
REQUIREMENTS OF THE AUTHORITY  
HAVING JURISDICTION. FAILURE TO  
FOLLOW THESE INSTRUCTIONS COULD  
RESULT IN SERIOUS INJURY OR  
PROPERTY DAMAGE. THE QUALIFIED  
AGENCY PERFORMING THIS WORK  
ASSUMES RESPONSIBILITY FOR THIS  
CONVERSION.  
THIS APPLIANCE MAY BE INSTALLED IN AN  
AFTERMARKET PERMANENTLY LOCATED,  
MANUFACTURED (MOBILE) HOME, WHERE  
NOT PROHIBITED BY LOCAL CODES. THIS  
APPLIANCE IS ONLY FOR USE WITH THE TYPE  
OF GAS THAT IS INDICATED ON THE STOVE’S  
RATING PLATE. A GAS CONVERSION KIT IS  
PROVIDED WITH THE GF 400 SEBAGO DIRECT  
VENT GAS STOVE.  
IN CANADA:  
THE CONVERSION SHALL BE CARRIED  
OUT IN ACCORDANCE WITH THE RE-  
QUIREMENTS OF THE PROVINCIAL AU-  
THORITIES HAVING JURISDICTION AND  
IN ACCORDANCE WITH THE REQUIRE-  
MENTS OF THE CAN1-B149.1 AND .2  
INSTALLATION CODE.  
CET APPAREIL PEUT ETRE INSTALLE DANS  
UN MAISON PREFABRIQUEE (MOBILE) DEJA  
INSTALLEE A DEMEURE SI LES REGLEMENTS  
LOCAUX LE PERMETTENT. CET APPAREIL  
DOIT ETRE UTILISE UNIQUEMENT AVEC LES  
TYPES DE GAS INDIQUES SUR LA PLAQUE  
SIGNALETIQUE. NE PAS L’UTILISER AVEC  
D’AUTRES GAS SAUF SI UN KITDE CONVER-  
SION CERTIFIE EST INSTALLE.  
Tools required:  
• 1/2” open ended wrench or deep-well socket, Torx T20  
or slotted screwdriver, 4 mm allen wrench.  
Conversion Kit Contents:  
• 1, regulator tower labeled for propane  
• 3, regulator tower screws  
• 1, burner orifice (#33 for NG, 1.65 mm for LPG)  
• 1, pilot orifice (#51 for NG, #30 for LPG)  
• Label A - to be completed and applied to  
the back of the stove  
• Label B - apply to the stove’s Rating Plate  
• Small valve label - apply to valve body  
Conversion instructions are also shipped in the stove  
with the conversion kit.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fuel Conversion Procedure  
Refer to fig. 47, Illustrated Parts Breakdown, to identify  
part numbers below.  
Air  
Shutter  
Wingnut  
Open  
Close  
1. Turn off gas supply to stove.  
2. Remove the stove Top Plate (41).  
3. Disengage the two Glass Frame Latches at the top of  
the firebox. See illustration on page 5. Carefully lift  
the glass panel up and out of the stove.  
FRONT  
LEG  
BACK  
LEG  
4. If installed, remove the Embers and Log Set using care  
Figure 21. Locate and remove the Air Shutter wingnut  
from under the right side of the stove.  
not to damage the fragile log parts.  
5. Lift out the Burner Skirt (33). Tilt the skirt at an angle  
to clear the firebox sides and front.  
6. Reach under the stove and remove the Air Shutter  
wingnut from its stud. As you face the right side, it is  
the one closest to you. See fig. 21.  
Air Shutter  
7. Lift out the Burner Plate: NOTE: There are no screws  
securing the Burner to the floor of the firebox. Pull the  
Air Shutter forward and lift the burner together with  
shutter up and out of the stove as a unit. See fig. 22.  
8. Change the Main Burner Orifice. See fig. 23. Using a  
½” open ended wrench or deep-well socket remove  
the burner orifice from its brass elbow housing and  
replace with the appropriate orifice supplied in the kit.  
#33 for NG  
Burner Plate  
Figure 22. Remove the Air Shutter and Burner as a unit.  
1.65 mm for LPG  
9. Replace the Air Shutter with its gasket and push it all  
the way back to allow replacement of the Burner  
Plate.  
10. Replace the Burner Plate. Engage the Air Inlet Tube  
with the Air Shutter and burner orifice. Properly seated,  
the burner plate will be engaged at its front corners  
with the two support brackets located at the front of  
the firebox.  
Brass Elbow  
• Replace the wingnut loosely on the air shutter stem  
under the stove. Air shutter adjustment will be done last.  
Burner  
Orifice  
11. CHANGE THE PILOT ORIFICE: From within the firebox,  
remove the Pilot Head by pulling it straight up from  
the pilot base. See fig. 25.  
Figure 23. Change the Burner Orifice.  
Using the 4 mm allen wrench that is included with  
the conversion kit, unscrew the pilot orifice (counter-  
clockwise). Replace with the appropriate orifice:  
# 51 for natural gas  
#30 for propane gas  
12. Tighten orifice into the base of the pilot assembly. To  
prevent bypass leaks, be sure the orifice is secured  
tightly and flush with the base. Replace pilot head by  
pushing it down onto the pilot base.  
Air Shutter  
Air Inlet  
Tube  
Opening  
Dimension  
13. Replace the Variable Regulator. Using a Torx T-20  
screwdriver, remove the three screws from the front  
of the valve regulator. See fig. 26.  
Burner Plate  
Figure 24. Air Shutter Setting  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.  
14. Remove the Regulator Tower, Gasket, white plastic  
disk, and Spring.  
Correct gas pressure is essential for efficient and safe  
operation of this appliance. Correct gas pressure  
must be established at the time of installation. For  
more details, see the Gas Pressure section of this  
manual (page 19).  
15. Install the new regulator: Be sure the new gasket is  
properly positioned and tighten screws securely.  
16. Install the identification labels to the stove so that they  
can be seen by any person that may be servicing the stove.  
Label A: apply to back of stove.  
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE  
INSIDE BACK COVER OF THIS MANUAL WHEN LIGHT-  
ING YOUR STOVE.  
Label B: apply to stove’s rating plate.  
Small valve Label: apply to valve.  
17. Reassemble the stove, apply gas to the system and  
check for leaks using a soapy water solution.  
18. Adjust the Air Shutter:  
Gas Supply Connection  
CAUTION! USE WORKGLOVES. SURFACES MAY BE HOT!  
You will need to adjust the shutter to the position  
that supplies the correct amount of air mixture to  
achieve the best flame picture with your particular  
installation. Start with the shutter stem at the  
midway position in the slot in the bottom of the  
stove. See fig. 21. Pushing the stem back will restrict  
air, while pushing it forward will open the shutter.  
Too much air will produce a lighter flame, while too  
little will promote long, dark flames and may pro-  
mote sooting. Make adjustments in small incre-  
ments. With some experimentation, you will find the  
shutter position that works best for your installation.  
Connect the gas supply line to the stove, before  
installing the optional Blower.  
If the blower will be installed, use a 45° elbow off the  
control valve to create clearance required for the blower  
installation.  
The gas supply line connection is made to the left side of  
the valve. The gas supply line should be 3/8" npt with a  
1/2" diameter supply, or the appropriate size to provide  
sufficient gas pressure to the valve regardless of the  
input setting.  
The use of Flexible Gas Appliance Connectors is  
acceptable in many areas in the U.S. However, Canadian  
methods vary depending on local code.  
ALL INSTALLATIONS MUST COMPLY WITH LOCAL  
CODE OR IN THE ABSENCE OF LOCAL CODE, MUST  
COMPLY WITH THE MOST RECENT EDITION OF THE  
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR  
CAN-B149.  
Pilot Head  
Orifice  
Retainer  
Clip  
All codes require a gas shut-off valve (gas cock) and  
union, to be installed in the supply line, and in the same  
room as the appliance. This allows for the disconnection  
of the stove for servicing and maintenance. See fig. 27.  
Pilot Base  
Figure 25. Pilot orifice removal and replacement.  
Regulator  
Tower  
Remove black  
gasket  
Apply small  
label here  
Figure 26. Regulator assembly.  
Figure 27. Supply valve coupling.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A T-HANDLE GAS COCK IS REQUIRED IN  
MASSACHUSETTS TO COMPLY WITH  
CODE 248CMR.  
Secure all joints tightly using appropriate tools and  
sealing compounds. For propane units be sure to use  
compounds that are propane resistant. Turn on gas  
supply and test for gas leaks using a soapy water solution.  
Never use an open flame to check for leaks.  
A
E
Figure 28. Pressure test points.  
Leak test:  
1. Mix a 50-50 solution of water and dish  
soap.  
2. Light appliance- see lighting instructions  
on the inside back cover of this manual  
or on the stove’s rating plate.  
INLET GAS PRESSURES  
(inches water column)  
MIN  
MAX  
3. Brush or spray all joints and connections  
with the soapy water solution.  
NATURAL GAS 5.0  
7.0  
PROPANE  
12.0  
14.9  
4. If bubbles appear at any connection or  
seam or a gas odor is detected, immedi-  
ately turn gas control knob to the OFF  
position.  
The appliance and its appliance main gas  
valve must be disconnected from the gas supply  
piping system during any pressure testing on  
that system at test pressures in excess of 1/2 psig  
(3.5 kPa).  
5. Tighten or reconnect the leaking joint  
and retest for any gas leaks.  
The appliance must be isolated from the gas  
supply line by closing its individual manual gas  
shut-off valve (gas cock) during any pressure  
testing of the gas supply piping system that is  
equal to or exceeds pressures of 1/2 psig (3.5  
kPa).  
Gas Pressure  
MANIFOLD PRESSURES  
(inches water column)  
Correct gas pressure is essential for efficient and safe  
operation of the GF 400 DV Sebago gas stove. It is  
important that the correct pressure is established at  
the time of the installation. Proper gas pressure  
provides a consistent flow of gas to the appliance and  
is instrumental in checking for gas leaks.  
MIN  
MAX  
NATURAL GAS 1.2  
3.8  
11.0  
PROPANE  
2.9  
Pressure Test: Attach a manometer to the appro-  
priate test point on the valve. See fig. 28. The gauge  
connections are located on the front of the valve  
under the On/Off/Pilot- knob. Gauge connections are  
identified by:  
E - for Inlet or Supply Pressure (the amount of  
gas coming to the valve.)  
High Altitude Adjustment  
Installations located at altitudes from 2000 - 4500 ft.  
(610 m -1370 m) DO NOT require adjustment for alti-  
tude. DO NOT DERATE THIS APPLIANCE FOR ALTITUDE.  
A - for Manifold Pressure (the amount of gas that  
is coming out of the valve to the burner.)  
ALWAYS TEST PRESSURES WITH VALVE CONTROL  
KNOB SET ON HIGH.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flame Appearance / Air Shutter  
Adjustment  
Optional Wall Thermostat or  
Remote Control  
The GF 400 DV Sebago gas stove is shipped from the  
factory equipped to burn Natural gas with the air shutter  
set at the halfway position. Please be aware, however,  
that this initial setting may not provide the optimal flame  
picture in your particular installation. No single setting  
will be appropriate for all vent configurations, fuel types,  
or installation environments. The air shutter setting can  
also be adjusted to achieve the desired flame appearance.  
Flame appearance is a matter of individual preference,  
however, most people enjoy a warm yellowish flame.  
Use only a 750 millivolt DC two-wire circuit thermostat  
with this appliance. The thermostat should be placed in  
the same room as the heater, typically 5 feet off the  
floor. Avoid drafty areas or any area that may affect the  
accuracy of the thermostat.  
The thermostat should be connected to the GF 400  
DV Sebago using a minimum of 16 gauge wire with a  
maximum length of 25 feet of wire.  
Connect the two thermostat wire leads to the two  
lower terminals on the terminal block located directly  
above the ignitor button. Do not overtighten the  
connections. IT IS NOT NECESSARY TO DISCONNECT  
ANY OTHER WIRES. See Fig. 30.  
Too much air - the appliance will generate a flame  
that is blue and transparent, or an “anemic” flame.  
Too little air - the appliance may generate very long  
yellow flames resulting in soot. Sooting produces black  
deposits on the logs, on the inside walls of the appliance,  
and potentially, on the exterior termination cap. Sooting  
is caused by incomplete combustion and lack of combus-  
tion air entering the air shutter opening.  
For thermostatic operation, the On/Off/T-Stat  
switch on the back of the stove must be in the T-stat  
position, and the pilot light must be running, as it is the  
power source for the thermostat.  
At the thermostat, the two wires should be con-  
nected to the two connection screws on the thermostat  
base plate per the manufacturer’s instructions.  
To adjust the air shutter: CAUTION! USE WORKGLOVES.  
SURFACES MAY BE HOT!  
1. Reach under the right side of the stove and loosen the  
wingnut located closest to you. See fig. 29. Slide the  
wingnut stem forward to open the air shutter and  
increase air. Slide the shutter stem back to decrease  
the air supply.  
Remote Control  
When using a remote, the remote receiver should be  
wired to the terminal block the same way the thermo-  
stat would be. See the instructions above.  
2. Tighten the wingnut to secure the shutter at the  
Follow the operating instructions included with the  
Remote Control unit.  
desired setting.  
3. Operate the burner for 30 minutes on the HIGH setting,  
observing the flame continuously. If the flame appears  
weak, slow, or sooty, adjust the air shutter to a more  
open position as described above until the flame is as  
desired. Make adjustments in small increments and  
allow the burner to settle in before making further  
adjustment  
CAUTION:  
LABEL ALL WIRES PRIOR TO DISCONNECTION  
WHEN SERVICING THE CONTROLS. WIRING  
ERRORS CAN CAUSE IMPROPER OR DANGEROUS  
OPERATION. ALWAYS VERIFY PROPER OPERA-  
TION AFTER SERVICING THE APPLIANCE.  
WARNING: AIR SHUTTER ADJUSTMENTS SHOULD ONLY  
BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE  
TECHNICIAN.  
ROCKER  
SWITCH  
THERMOPILE  
ON  
TH  
TP  
OFF  
FRONT  
LEG  
Open  
Close  
STAT  
TH  
TP  
OPTIONAL  
THERMOSTAT  
or  
REMOTE  
CONTROL  
VALVE  
BACK  
LEG  
TERMINAL  
BLOCK  
Figure 29.  
Loosen the wingnut to adjust the air shutter stem.  
Figure 30. Accessory wiring diagram.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Log Set Installation  
NOTE: If appropriate, install the optional Antique Brick  
Panel Kit before assembling the logset.  
The GF 400 DV Sebago logset must be installed before  
operating the burner. The logset includes five log pieces,  
packaged inside the firebox, and a quantity of ember  
stones packaged in the Miscellaneous Parts bag.  
To install the log set, remove the packaging and place the  
parts inside the firebox as illustrated in figs 32-37. Do  
not handle the log set with your bare hands. Always  
wear gloves to prevent skin irritation from the ceramic  
fibers.  
Figure 34. Install Left Log  
The ember stones realistically simulate glowing coals  
when the burner is operating. These should be spread  
evenly over the burner plate and around the logs. DO NOT  
OBSTRUCT THE PILOT ASSEMBLY OPENING. See fig. 37.  
NOTE: You do not need to use all the ember stones.  
With experimentation, you will find the arrangement  
and quantity of embers that works best with your stove.  
Depending upon the characteristics of your installation,  
it is possible that too many ember stones can promote  
sooting on the logs. Adjust the quantity of ember stones  
as appropriate to maintain the best overall flame  
picture.  
Figure 35. Install Middle Log  
THE CERAMIC FIBER LOGS AND GLOWING EMBERS CAN  
IRRITATE YOUR SKIN. GENTLY WASH YOUR HANDS WITH  
WARM SOAPY WATER AFTER HANDLING THE LOGS.  
Figure 36. Install Crossover Log  
Figure 32. Install Right Log  
Pilot  
Opening  
DO NOT  
OBSTRUCT  
Figure 33. Install Rear Log  
Figure 37. Install Ember Stones  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Check  
1”  
(25mm)  
3/8”  
(8mm)  
Min.  
1. PURGING THE GAS LINE: When lighting the appli-  
ance for the first time, it will take a few moments to  
clear the gas line of air. Once this purge is complete,  
the appliance will operate as described in the  
lighting instructions. See the inside back cover of  
this manual or the stove Rating Plate attached the  
bottom of the stove. Subsequent burner starts will  
not require purging the gas line unless the supply  
line is shut off.  
1/8”  
(3mm)  
Min.  
2. PILOT FLAME: You can monitor the pilot flame  
through the view port located at the rear of the  
Right Log. See fig. 36. The pilot flame should be  
steady - not lifting or floating. The flame should be  
blue in color around the pilot hood, with traces of  
yellow toward the outer edges.  
Figure 37. Proper pilot flame appearance.  
The pilot flame should engulf the top 3/8” of the  
thermopile (to generate millivolt current) and the  
top 1/8” of the thermocouple. The pilot flame  
should project out of the pilot hood 1” at all three  
ports. See fig. 37.  
CAUTION:  
DO NOT ATTEMPT TO ALTER THE FLAME  
APPEARANCE BY POSITIONING THE GAS  
VALVE CONTROL IN ANY OTHER POSITION  
OTHER THAN THE FULL “ON” POSITION.  
3. BURNER ADJUSTMENT: This stove is equipped with a  
variable gas control valve that allows easy adjust-  
ment of the flame height appearance and heat  
output. To adjust the flame between the HI and  
LOW setting, rotate the HI/LOW knob, located in the  
center of the valve face. Flame height will adjust  
approximately 1” to 2” between the LOW and HIGH  
settings. See fig. 38.  
NO SMOKE OR SOOT SHOULD BE PRESENT. CHECK  
LOG PLACEMENT IF ANY SOOT OR SMOKE IS  
PRESENT. IF SOOT OR SMOKE PERSISTS, THE AIR  
SHUTTER MAY NEED TO BE ADJUSTED.  
See Air Shutter/Flame Appearance section of this  
manual for proper air shutter settings and adjust-  
ments. Note: the more offsets there are in the vent  
system, the greater the need for an air shutter  
adjustment. See page 20.  
WARNING:  
Figure 38. Flame appearance on the “high” setting after  
approximately 15 to 20 minutes burning.  
AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE  
PERFORMED BY A QUALIFIED PROFESSIONAL  
SERVICE TECHNICIAN.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Familiarize yourself with the controls of the GF 400 DV  
Sebago. Make sure that anyone else using the appliance  
is also familiar with the controls and operation proce-  
dures. Always follow the Lighting Instructions on the  
inside back cover of this manual and also located on the  
Rating Plate attached to the back of the stove.  
1. Once the pilot is lit, burner operation is controlled by  
the rocker switch located at the left rear corner of the  
stove. Use the T-STAT position for the optional thermo-  
static or remote control functions. See fig. 39.  
2. During the first few fires, you may notice odor and/or  
smoke from the stove. This is normal and results from  
burn-off of manufacturing residue and curing of  
materials. You may find it helpful to provide addi-  
tional ventilation and fresh air to alleviate this condi-  
tion.  
3. Condensation may occur on the glass upon each  
lighting of the appliance. This “fog” will disappear as  
the appliance heats up.  
Figure 39. Burner Switch and Optional Blower Controls  
4. Keep the controls and the area under the appliance  
free of debris, vacuum this area frequently. Always  
keep the appliance area clear and free from combus-  
tible materials, gasoline and other flammable liquids.  
If a vacuum is used during any service on the stove,  
ALWAYS be sure the stove is cold and there are NO hot  
embers.  
5. Remember, this appliance has a continuous burning  
pilot flame. Exercise caution when using products  
having combustible vapors. Always shut-off gas  
supply while servicing the stove.  
6. CAUTION: DO NOT OPERATE THIS APPLIANCE WITH  
THE GLASS REMOVED CRACKED OR BROKEN.  
Replacement of the glass should be done by a licensed  
or qualified service person. Use only replacement  
glass provided by your authorized Jøtul dealer. Never  
use any substitute materials.  
WARNING: OBSERVE CAUTION WITH THE GLASS. THE  
GLASS PANEL MAY SHATTER UNEXPECTEDLY IF STRUCK  
WITH AN OBJECT. ALWAYS HANDLE THE GLASS PANEL  
WITH CARE. WHEN SERVICING THE STOVE ALWAYS  
PULL THE GLASS ASSEMBLY STRAIGHT UP FOR RE-  
MOVAL.  
7. Clean the glass only when necessary. Wipe surface  
with a clean, damp soft cloth. Follow with a dry, soft  
towel as desired. Take care not to scratch the glass  
surface.  
WARNING: DO NOT USE ABRASIVE CLEANERS ON THE  
GLASS. NEVER CLEAN THE GLASS WHEN IT IS HOT.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR REPLACEMENT, USE ONLY JØTUL  
CERAMIC GLASS PANEL 220089. DO NOT  
USE ANY OTHER TYPE OF GLASS WITH  
THIS APPLIANCE.  
Maintenance  
Your Jøtul GF 400 DV Sebago and its venting system  
should be inspected before use and at least annually by  
a qualified service technician.  
Glass Panel or Gasket Removal  
Use the form on page 30 to keep a maintenance  
history of your stove.  
1. Lift the Top Plate off of the stove.  
2. Release the two Glass Frame Latches. Pull each latch  
handle forward forward to disengage the latch from  
the notches in the glass frame.  
IMPORTANT:  
ALWAYS TURN OFF THE GAS SUPPLY TO THE  
FIREPLACE AND UNPLUG THE FORCED AIR  
BLOWER BEFORE ANY SERVICE WORK IS  
PERFORMED ON THE FIREPLACE.  
3. Lift the glass frame all the way up and out of the top  
of the stove. Lay this assembly on a flat surface,  
protecting the frame from scratches using a blanket  
or towel.  
3. The glass panel is held in place by four compression  
clips. Use a screwdriver or small pliers to pry these up  
off the edge of the glass retaining walls. See fig. 40.  
Annual Cleaning  
Vent System  
4. Remove the old gasket material. See fig. 41.  
The entire vent system, including the chimney, should  
be inspected and cleaned every year. If the intake and  
exhaust venting is disassembled for any reason, it  
should be reassembled and sealed according to the  
manufacturer’s instructions provided at the initial  
installation.  
Glass Clips  
Burner and Logset  
Periodically inspect the Firebox, Valve Compartment,  
Convection Airways and optional Blower to BE CERTAIN  
THAT THE FLOW OF COMBUSTION AND VENTILATION  
AIR IS UNOBSTRUCTED.  
Figure 40. Use small pliers to pry the clips off of the glass  
panel frame.  
The firebox should be vacuumed annually to remove  
any surface build up. Use a soft brush attachment and  
handle the logs carefully as they are fragile. Be sure to  
vacuum or wipe off the pilot assembly and burner  
surfaces.  
Glass Panel or Gasket Replacement  
1. Wrap the new gasketing material evenly around the  
edge of the glass, peeling back the protective strip to  
expose the adhesive as you go. Press the adhesive side  
down onto the glass surface. Do not stretch the  
gasket.  
Glass Care  
Clean the glass only when necessary. Wipe the surface  
with a clean, dampened, soft cloth. Follow with a dry,  
soft towel. Take care not to scratch the glass surface.  
2. Place the gasketed glass within the frame and press  
each of the retainer clips back into place on the  
retainer walls.  
WARNING:  
DO NOT USE ABRASIVE CLEANERS ON THE  
GLASS. NEVER CLEAN THE GLASS WHEN IT  
IS HOT.  
Gasket Inspection  
It is important that the glass gasket be inspected at  
least annually. Examine the ribbon gasket for signs of  
deterioration and make sure the gasket has a positive  
seal. Replace the gasket if necessary. Refer to the  
replacement parts list on page 29.  
Figure 41. Wrap the gasket around the glass panel.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Blower # 156000  
6
Connect the gas supply line to the stove,  
before installing the Blower.  
Use a 90° Elbow off the control valve to create  
7
5
8
clearance required for the blower installation.  
11  
1
1. Unpack and check the contents of the blower kit.  
Contact your dealer if any damage is evident or  
parts are missing. See fig. 42.  
2
3
9
7
2. Attach the Snapstat Bracket to the studs located in  
the middle of the firebox floor using the two M6  
hex nuts and a 10 mm wrench. See fig. 43.  
4
3. Attach the Blower Bracket to the stove using the  
10  
two M6 flange head hex bolts as shown in fig. 43.  
4. Attach the Duct Deflectors using the two #7 x 1/2”  
screws together with the finger guard mounting  
screws already in place. See #7 and #11 in fig. 42.  
Contents  
1. Blower  
2. Mounting Bracket  
3. Snapstat Wire Harness  
4. Control Switch Wire Harness  
5. Snapstat  
6. Snapstat Bracket  
Tools Required  
• 10 mm wrench  
* short phillips screwdriver  
* Safety Glasses  
* Work Gloves  
5. Install the Blower with the duct openings oriented  
up and forward. See fig. 44. Feed the wire harness  
through the bracket opening and secure the blower  
to the bracket with the wingscrew.  
6. Attach either Snapstat wire connector to either  
7. Blower Duct Deflector (2)  
8. M6 Hex Head Flange Nuts (2)  
Snapstat terminal. See fig. 44.  
9. M6 x 12 Hex Head Flange Bolts (2)  
10. M6 x 12 Wingscrew  
11. #7 x 1/2” phillips screw (2)  
7. Install the Snapstat by sliding it all the way into the  
slot in the bottom of the Snapstat Bracket as shown  
in figs. 42 and 44.  
Figure 42. Blower Kit Components  
8. Connect the male wire harness connector to the  
female wire harness connector already installed in  
the stove. See fig. 44.  
9. Connect power cord to outlet.  
Hex Head  
Flange Bolts  
THIS BLOWER MUST BE ELECTRICALLY  
GROUNDED IN ACCORDANCE WITH  
LOCAL CODES OR, IN THE ABSENCE OF  
LOCAL CODES, WITH THE CURRENT  
ANSI/NFPA 70, NATIONAL ELECTRICAL  
CODE OR CSA C22.1-CANADIAN  
ELECTRICAL CODE.  
Snapstat  
Bracket  
Hex Head  
Flange Nuts  
THIS UNIT IS SUPPLIED WITH A  
THREE-PRONG (GROUNDING) PLUG  
FOR PROTECTION AGAINST SHOCK  
HAZARD AND SHOULD BE PLUGGED  
DIRECTLY INTO A PROPERLY  
GROUNDED THREE-PRONG  
Blower Bracket  
Figure 43. Attach Snapstat and Blower Brackets.  
RECEPTACLE. DO NOT CUT OR  
REMOVE THE GROUNDING PRONG  
FROM THE PLUG.  
ALWAYS DISCONECT THE POWER  
SUPPLY WHEN PERFORMING ANY  
SERVICE ON THE FIREPLACE INSERT.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 44. Attach Blower to the Mounting  
Bracket with the wingscrew and connect  
wires to Snapstat and female control  
quickconnect.  
Snapstat  
Connectors  
Male  
Quickconnector  
to Female  
Quickconnector  
Wingscrew  
Blower Operation  
The optional variable-speed blower will enhance heat  
circulation around the firebox and out into the room.  
The blower is controlled by a heat activated switch  
(snapstat) that will ONLY function when the control  
switch is in AUTO setting. After the fire has been  
burning for a time, the snapstat will react to the heat  
and activate the blower. Fan speed may be manually  
adjusted with the rheostat knob. If the burner turns off,  
the blower will be shut off automatically when the  
stove cools down.  
Blower Speed  
Control  
If automatic blower circulation is not desired, place  
the blower control switch in the MANUAL position.  
Figure 45. Blower Controls  
BLOWER  
G
W
BK  
BK  
BK  
BK  
W
G
P
P
BK  
BL  
BK  
BK  
RHEOSTAT  
GY  
POWER  
SUPPLY  
SNAPSTAT  
BR  
P
P
P
P = QuickConnector Pin  
BL  
GY BR  
SWITCH  
MANUAL OFF AUTO  
Figure 46. Blower Wiring Diagram  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Right Panel  
220600  
Left Panel  
220601  
Optional Antique Brick  
Panel Kit 155375  
Rear Panel 220599  
Tools Required: Safety glasses and gloves  
Figure 47. Brick Kit Contents  
1. Remove the Top Plate. Simply lift if up off of the  
stove body. It is not fastened.  
2. Remove the Glass Frame. Disengage the two  
compression latches located at the top of the  
firebox and lift the glass frame up and off of the  
stove. See Fig. 1.  
Glass Frame  
Latch  
3. Remove the Logset.  
These parts are not fastened. Simply lift them out  
of the firebox. You do not have to remove the  
embers.  
4. Install the Rear Panel.  
Tilt the Rear Panel top first to slide behind the  
exhaust baffle and position it up against the back  
wall.  
5. Install the Side Panels. Tilt each panel, bottom  
edge first, into position against the side walls. The  
panels will stand on their own against the wall.  
Push them back against the Rear Panel.  
Figure 48. Release the glass frame latches.  
6. Reinstall the Logset.  
Exhaust Baffle  
See page 21. BE CERTAIN THAT NO EMBERS ARE  
BLOCKING THE PILOT ASSEMBLY OPENING.  
7. Replace the Glass Frame.  
Slide the frame down the slot in the front of the firebox.  
Be sure to push the frame into the slot in the bottom to  
ensure it is fully seated. The gasket at the top of the  
frame should be flush with the top of the firebox.  
Pull the compression latches out to engage with the top  
lip of the glass frame.  
8. Replace the Top Plate.  
Figure 49. Install the Rear Panel to fit behind baffle.  
Figure 50. Install the Side Panels.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GF 400 DV Sebago  
Illustrated Parts  
Breakdown  
42  
35  
40  
38  
56 36  
45  
44  
43  
41  
39  
37  
34  
33  
1
32  
31  
64  
2
3
30  
29  
28  
27  
49  
4
25  
54  
51  
52  
55  
26  
56  
53  
5
24  
6
23  
22  
7
8
63  
58  
59  
60  
61  
62  
57  
9
10  
11  
48  
17  
46  
47  
19 20  
50  
21  
12  
13  
14  
15  
16  
18  
Figure 51. Illustrated Parts Breakdown - GF400 DV Sebago  
Side-mount Valve shown.  
Center-mounted valve uses same components.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GF 400 DV Sebago Parts List  
Cast Iron Parts  
Matte Black  
Blue Black Enamel Ivory Enamel  
Green Enamel Jøtul Iron  
Jøtul Iron Enamel  
7.  
9.  
Left Side Plate  
Bottom Plate  
Legs, (4)  
10391892  
10396392  
10192592  
15565492  
10421692  
10391992  
10396292  
10391827  
10396327  
10192527  
155660  
10391829  
10396329  
10192529  
155672  
10391832  
10396332  
1092532  
155666  
10391885  
10396385  
10192585  
15565485  
10421685  
10391985  
10396285  
10391846  
10396346  
10192546  
15565446  
10421646  
10391946  
10396246  
14.  
19.  
23.  
25.  
41.  
Front, Complete  
Right Door  
10421627  
10391927  
10396227  
10421629  
10391929  
10396229  
10421632  
10391932  
10396232  
Right Side Plate  
Top Plate  
50.  
Left Door  
10421592  
10421527  
10421529  
10421532  
10421585  
10421546  
35.  
36.  
37.  
38.  
39.  
40.  
42.  
43.  
44.  
45.  
46.  
47.  
48.  
Exhaust Restrictor .................................................... 220563  
Exhaust Restrctor Gasket ....................................... 220583  
Firebox Assembly ...................................................... 221194  
Latch Assembly .......................................................... 220091  
Relief Door Gasket .................................................... 129319  
Relief Door .................................................................. 129640  
Relief Door Guide ...................................................... 129499  
Heat Fins, (4) ............................................................... 155653  
Inner Shroud, Right .................................................. 220596  
Inner Shroud, Left ..................................................... 220597  
Ignitor Bracket ........................................................ 3902576  
Ignitor ....................................................................... 3902573  
Burner Orifice, NG #33 ............................................ 220641  
Burner Orifice, LP 1.65mm .................................... 220638  
Primary Air Shutter .................................................. 220790  
Rheostat Knob ........................................................... 220709  
Rocker Switch, (2) ...................................................... 220703  
Rheostat ...................................................................... 220970  
Retaining Collar ........................................................ 220717  
Fender Washer ........................................................... 118023  
Wingnut, (3) ............................................................... 117975  
Wire Harness .............................................................. 156001  
Control Door Hinge .................................................. 221176  
Bolt, M6 x 20 Blk Hex Hd ........................................ 117117  
Spacer, .375 o.d. x 3.172 .......................................... 118040  
Washer, Fender .250 x 1.500 dia. .......................... 118029  
Bolt, M6x100 Hex ..................................................... 117955  
Spacer, .250 x .50 x .250 Alum, .............................. 117994  
Spacer, .250 x .50 x .125 Alum, ............................. 118009  
*Wire Harness Retainer ........................................... 220733  
1.  
Air Divider ................................................................... 220624  
Simpson DuraVent Collar ....................................... 129126  
Collar Gasket .............................................................. 129118  
Wire Harness Assembly .......................................... 155397  
Rating Plate ................................................................ 220613  
Lanyard ........................................................................ 129159  
Rear Shroud ................................................................ 220558  
Valve Bracket .............................................................. 220352  
Valve - NG ................................................................... 220520  
Elbow, 3/8” Brass ...................................................... 129129  
Terminal Block ........................................................... 129154  
Bracket,Terminal Block ........................................... 220614  
Gas Line, 5/16” Flex .................................................. 129390  
Orifice Holder Assembly ......................................... 129668  
Glass Frame Assembly ............................................. 155398  
Glass Panel Replacement Kit ................................. 155553  
Glass Pane, Ceramic ................................................. 220567  
Glass Gasket, 7/16Tadpole .................................. 129124  
Glass Frame ........................................................... 12972592  
Glass Clips, (4) ............................................................ 220042  
Keeper, Door Latch .................................................... 220604  
Control Door............................................................... 221188  
Door Latch .................................................................. 220603  
Log Set ......................................................................... 155378  
Air Intake Gasket ....................................................... 220642  
Air Intake Restrictor ................................................. 220602  
Air Shutter Gasket .................................................... 220734  
Pilot Assembly Gasket ............................................. 129670  
Pilot Assembly Spacer ............................................. 220546  
Pilot Assembly, w/NG orifice ................................. 129471  
Pilot Orifice NG #51 ................................................. 129472  
Pilot Orifice LP #30 .................................................. 129473  
Jam Nut - Orifice Holder ......................................... 129152  
Ferrule (2) .................................................................... 129463  
Nut (2) .......................................................................... 129464  
Pilot Line w/ Fitting .................................................. 129446  
Thermocouple ........................................................... 129766  
Electrode ..................................................................... 129765  
Thermopile .............................................................. 3094527  
Burner Assembly ....................................................... 155336  
Burner Skirt ................................................................ 220582  
Exhaust Baffle ............................................................ 220565  
2.  
3.  
4.  
5.  
6.  
8.  
10.  
11.  
12.  
13.  
15.  
16.  
17.  
18.  
49.  
51.  
52.  
53.  
54.  
55.  
56.  
57.  
58.  
59.  
60.  
61.  
62.  
63.  
64.  
20.  
21.  
22.  
24.  
26.  
27.  
28.  
29.  
30.  
31.  
Accessories  
Variable Speed Blower .................................. 156000  
Brick Panel Kit.................................................. 155375  
Wall Thermostat ............................................. 750003  
Remote Control ............................................... 750002  
Floor Bracket Kit ............................................. 750304  
Fuel Conversion Kit to Propane .................. 156003  
Fuel Conversion Kit to Natural Gas ........... 156004  
32.  
33.  
34.  
ALWAYS USE REPLACEMENTS PARTS  
PROVIDED BY AN AUTHORIZED JØTUL  
DEALER ONLY.  
* Parts not illustrated  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Record the following information to help  
your dealer determine what you will need for  
parts and service.  
GF 400 DV Sebago  
MODEL NAME: ________________________  
SERIAL NUMBER: ______________________  
DATE OF PURCHASE: ___________________  
PURCHASED FROM: ____________________  
NAME OF INSTALLER: ___________________  
TYPE OF FUEL: ________________________  
WAS STOVE CONVERTED? _______________  
NOTES:  
RETAIN THIS MANUAL FOR REFERENCE  
AND MAKE IT AVAILABLE TO ANYONE  
USING OR SERVICING THE STOVE.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIGHTING INSTRUCTIONS  
FOR YOUR SAFETY, READ BEFORE LIGHTING.  
WARNING:  
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY  
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.  
• If your gas supplier cannot be reached, call the  
fire department.  
A. This appliance has a pilot which must be lit  
by hand. When lighting the pilot, follow  
these instructions exactly.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will  
not push in or turn by hand, do not try to repair  
it. Call a qualified technician. Force or attempted  
repair may result in a fire or explosion.  
B. BEFORE LIGHTING, smell all around the  
appliance area for gas. Be sure to smell next  
to the floor because some gas is heavier than  
air and will settle to the floor.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
WHAT TO DO IF YOU SMELL GAS:  
• Extinguish any open flame.  
• Open windows.  
• Do not light any appliance.  
• Do not touch any electrical switches.  
• Do not use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone.  
LIGHTING INSTRUCTIONS  
1. STOP! Read the safety information above.  
7. Push in gas control knob slightly and turn counter-  
clockwise  
toPILOT”.  
2. Access the lower controls.  
8. Push in control knob all the way and hold in.  
Immediately light the pilot by triggering the spark  
ignitor (push the red button repeatedly) until pilot  
lights. Continue to hold the control knob in for  
about one minute  
3. Turn the stove ON/OFF switch toOFF”, or set the  
thermostat to lowest setting (if used).  
4. Confirm that the gas supply line shut-off valve is open.  
after the pilot lights.  
Release knob and it  
should spring back.  
Control  
Knob  
The pilot should  
remain lit. If it goes  
out, repeat Steps 5  
through 8.  
Pilot Assembly  
Control Valve  
• If knob does not  
return when released, stop and immediately call  
your service technician or gas supplier.  
5. Push in gas control knob slightly and turn clockwise  
toOFF.  
• If pilot will not stay lit after several tries, turn  
the control knob to OFF and call your service  
technician or gas supplier.  
NOTE: Knob cannot be turned fromPILOTtoOFF”  
unless the knob is pushed in slightly. Do not force.  
6. Wait five (5) minutes to clear out any gas. If you then  
smell gas, STOP! FollowBin the safety information  
above on this page. If you do not smell gas, go to the  
next step.  
9. Turn gas control knob counterclockwise  
toON”.  
10. Turn the stove ON/OFF switch toON”, or set  
thermostat (if used) to desired temperature.  
TO TURN OFF GAS TO THE APPLIANCE:  
1. Turn ON/OFF switch toOFF”. The pilot will remain lit for  
3. Access the lower controls.  
normal service.  
4. Depress gas control knob slightly and turn clock-  
2. For complete shutdown, turn ON/OFF switch toOFF”.  
wise  
toOFF”. Do not force.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This appliance must be installed in conformance with local and national building regulations. Before  
beginning the installation, it is important that the these instructions be carefully read and understood.  
Jøtul maintains a policy of continual product development. Consequently, products may differ in  
specification, color or type of accessories from those illustrated or described in various publications.  
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les  
specifications, couleurs etequipement sans avis prelable.  
Jøtul AS  
P.O. Box 1411  
N-1602 Fredrikstad  
Norway  
Jøtul North America  
55 Hutcherson Dr.  
Gorham, ME 04038-2634  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Ives Door 698 U698 User Manual
JOBO Digital Photo Frame PDJ120 User Manual
JVC CRT Television HV 29LPZ A User Manual
JVC Speaker System UX S77 User Manual
JVC Stereo System 20981IEN User Manual
Keys Fitness Network Card RTM 8000 User Manual
KitchenAid Beverage Dispenser KUWO24LS User Manual
KitchenAid Microwave Oven KBMS1454R User Manual
KitchenAid Mixer KSM100PSER0 User Manual
Konica Minolta Camcorder Dimage A1 User Manual