Johnson Controls Humidifier AVC Series User Manual

INSTALLATION MANUAL  
SINGLE PIECE  
VARIABLE SPEED AIR HANDLERS  
ISO 9001  
Certified Quality  
Management System  
MODELS: AV*(C) SERIES  
LIST OF SECTIONS  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .7  
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . .7  
REQUIRED CONTROL SET-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
AIRFLOW AND COMFORT SETTING SELECTION . . . . . . . . . . . . 12  
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
LIST OF FIGURES  
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Return Duct Attachment & Component Location . . . . . . . . . . . . . . . . .3  
Dimensions & Duct Connection Dimensions . . . . . . . . . . . . . . . . . . . .4  
Condensate Deflector on Vertical Drain Pan . . . . . . . . . . . . . . . . . . . .4  
Condensate Deflecctor on Horizontal Drain Pan Edge . . . . . . . . . . . .5  
S-Clip Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Duck Work Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
TXV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Proper Bulb Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Air Handler Control Board – Communications Connections . . . . . . . . 7  
Cooling Models with and without Electric Heat Wiring . . . . . . . . . . . . 8  
Two-Stage Heat Pump Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Air Handler with Communicating AC or HP . . . . . . . . . . . . . . . . . . . . 9  
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
LIST OF TABLES  
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Low Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Heat Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Comfort Setting Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Physical and Electrical Data - Cooling Only (60 Hz) . . . . . . . . . . . . . . . . 12  
Electrical Data - Cooling Only (60 Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Conversion Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Electrical Data - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Electrical Data - (For Single Source Power Supply) -  
Copper Wire - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Electrical Data - (For Multi-Source Power Supply) -  
Copper Wire - 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Electrical Data - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Electrical Data - (For Single Source Power Supply) -  
Copper Wire - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Electrical Data - (For Multi-Source Power Supply) -  
Copper Wire - 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
Air Handler Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
CAUTION indicates a potentially hazardous situation, which, if not  
avoided may result in minor or moderate injury. It is also used to  
alert against unsafe practices and hazards involving only property dam-  
age.  
SECTION I: GENERAL  
The AV single piece air handler provides the flexibility for installation in  
any upflow, downflow, or horizontal application.  
These versatile models may be used for cooling or heat pump operation  
with or without electric heat.  
A BRAND LABEL (available from Distribution) may be applied to the  
center of the blower access panel on AVG models.  
Improper installation may create a condition where the operation of  
the product could cause personal injury or property damage.  
Improper installation, adjustment, alteration, service or maintenance  
can cause injury or property damage. Refer to this manual for assis-  
tance or for additional information, consult a qualified contractor,  
installer or service agency.  
The unit can be positioned for bottom return air in the upflow position,  
top return air in the downflow position, and right or left return in the hor-  
izontal position.  
Top and side power wiring and control wiring, accessible screw termi-  
nals for control wiring, easy to install drain connections and electric  
heaters all combine to make the installation easy, and minimize installa-  
tion cost.  
SECTION II: SAFETY  
This product must be installed in strict compliance with the installation  
instructions and any applicable local, state, and national codes  
including, but not limited to building, electrical, and mechanical codes.  
This is a safety alert symbol. When you see this symbol on  
labels or in manuals, be alert to the potential for personal  
injury.  
Understand and pay particular attention to the signal words DANGER,  
WARNING, or CAUTION.  
FIRE OR ELECTRICAL HAZARD  
Failure to follow the safety warnings exactly could result in serious  
injury, death or property damage.  
DANGER indicates an imminently hazardous situation, which, if not  
avoided, will result in death or serious injury.  
WARNING indicates a potentially hazardous situation, which, if not  
avoided, could result in death or serious injury.  
A fire or electrical hazard may result causing property damage, per-  
sonal injury or loss of life.  
536636-UIM-D-1211  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
NOTICE  
In severe high humidity, high temperature indoor unit environments,  
an accessory insulation blanket is available to supplement the stan-  
dard cabinet insulation. Insulate with UPG Kit: 1VJ0117 for B cabi-  
nets, 1VJ0121 for C cabinets or 1VJ0124 on D cabinets or seal  
completely with adequate fiberglass insulation using vapor barrier on  
the outside.  
When an evaporator coil is installed in an attic or above a finished  
ceiling, an auxiliary drain pan should be provided under the coil as is  
specified by most local building codes.  
UPFLOW  
DOWNFLOW  
HORIZONTAL RIGHT  
HORIZONTAL LEFT  
FIGURE 1: Typical Installation  
6. Re-install coil assembly on downflow bracket.  
7. Re-attach front drain pan, hold down bracket.  
8. Re-attach tubing connection panel.  
DOWNFLOW AND HORIZONTAL CONVERSION  
(AV ONLY)  
These air handler units are supplied ready to be installed in a upflow  
and right hand horizontal position. If unit requires left hand positioning,  
the unit must have the coil assembly repositioned.  
9. For horizontal applications, rotate air handler 90º into desired ori-  
entation.  
10. Re-position drain plugs as necessary based on air handler orienta-  
tion.  
1. Remove blower, coil, and filter access panels.  
11. Re-position and replace access panels.  
12. For downflow installations, the cladding should be reconfigured so  
that the grille and circuit breaker covers having logos and/or black  
coloring are at the top of the unit on the coil access panel. See  
below.  
NOTICE  
Conversion must be made before brazing the refrigerant connections  
to the coil.  
For downflow and horizontal left installations, follow steps 2 - 8.  
2. Remove tubing connection panel.  
13. Apply branding label to air handler in recessed area provided on  
blower access panel cladding. This label should be applied after  
the air handler is placed in its proper orientation so the label is  
right side up.  
3. Remove front drain pan, hold down bracket.  
4. Slide coil assembly out of air handler.  
5. Rotate cabinet 180º so blower outlet is facing down.  
FRONT VIEW  
BLOWER  
COMPARTMENT  
COIL COMPARTMENT  
(Access panel removed)  
VERTICAL  
DRAIN PAN  
HORIZONTAL  
DRAIN PAN  
SIDE VIEW  
REFRIGERANT LINE  
CONNECTIONS  
HORIZONTAL  
SECONDARY DRAIN  
HORIZONTAL  
PRIMARY DRAIN  
PRIMARY DRAIN  
UPFLOW 3/4”  
THREADED  
ALTERNATE  
DRAIN CONNECTIONS  
UPFLOW/DOWNFLOW  
RETURN AIR  
DUCT  
DUCT WORK MAY  
BE FASTENED  
CAUTIOUSLY WITH  
FILTER DOOR  
SCREWS TO THE  
SIDES AND REAR OF UNIT  
WHEN ATTACHING DUCT WORK WITH  
SCREWS - KEEP SCREWS WITHIN 5/8”  
OF SIDES AND BACK OF AIR HANDLER  
SECONDARY DRAIN  
UPFLOW 3/4” THREADED  
FIGURE 2: Return Duct Attachment & Component Location  
Johnson Controls Unitary Products  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
CLADDING CONFIGURATION FOR DOWNFLOW  
INSTALLATION (IF USED)  
NOTICE  
To reconfigure the cladding parts, remove the grille by pulling gently at  
the top. Once the grille is removed, the circuit breaker cover can also be  
removed. Remove the gray, non-branded grille and circuit breaker  
cover from the cladding on the coil access panel. Next, remove the  
black and/or branded grille and circuit breaker cover from the blower  
access panel. Install these pieces into the coil access panel cladding so  
they are at the top of the air handler. Install the gray, non-branded grille  
and circuit breaker cover in the blower access panel cladding.  
If a heat kit with a circuit breaker is installed in the air handler, the cir-  
cuit breaker cover cladding must be removed to gain access to the  
sheet metal cover plate. Some local codes may require that the circuit  
breaker remain visible. If so, do not re-install circuit breaker cover  
cladding.  
F
10-3/8”  
J
K
TOP OUTLET  
DIMENSIONS  
CLADDING  
CIRCUIT  
BREAKER  
PANEL  
18-9/32”  
BLOWER  
E
COMPARTMENT  
BOTTOM INLET  
A
DIMENSIONS  
DRAIN CONNECTIONS  
FOR UPFLOW AND  
DOWNFLOW APPLICATIONS  
D
REFRIGERANT  
FIGURE 3: Dimensions & Duct Connection Dimensions  
TABLE 1: Dimensions  
Wiring Knockouts1  
Refrigerant  
Connections  
Line Size  
Dimensions (Inches)  
Models  
AV  
A
B
C
J
K
D
E
F
Height  
46  
Width  
17 1/2  
21  
Depth  
Power  
Control  
Liquid  
Vapor  
24B  
36C  
48D  
60D  
12-3/8  
17-1/8  
22-1/8  
22-1/8  
13-29/32 14-19/32  
17-13/32 18-3/32  
20-29/32 21-19/32  
20-29/32 21-19/32  
3/4”  
7/8”  
7/8”  
7/8’  
21-1/2  
(w/o cladding)  
22-1/2  
7/8” (1/2”)  
1 3/8” (1”)  
1 23/32” (1 1/4”)  
52  
7/8” (1/2”)  
3/8”  
57  
24 1/2  
24 1/2  
(with cladding)  
57  
1. Actual size (Conduit size).  
SUCTION FEEDER TUBE CONDENSATE  
DEFLECTOR  
Horizontal Left or Right  
Use an appropriate tool to pry out water deflector with two or three s-  
clips from the vertical drain pan. See Figure 4. Relocate the deflector  
with s-clips on the Horizontal Drain Pan lined up to the coil support  
brackete. See Figure 5. This positions the deflector below the feeder  
tubes to channel the condensate to the drain pan.  
UPFLOW OR DOWNFLOW  
No action required. See Figure 4.  
NOTICE  
The condensate deflector should be installed in the s-clip section  
which is inside the drain pan edge. See Figure 6.  
S-CLIPS (3)  
VERTICAL  
DRAIN PAN  
CONDENSATE  
DEFLECTOR  
FIGURE 4: Condensate Deflector on Vertical Drain Pan  
4
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
ers and never fastened directly to the structure. This unit is not  
designed for non-ducted (freeblow) applications. Size outlet plenum or  
transition to discharge opening sizes shown in Figure 3.  
Duct work should be fabricated and installed in accordance with local  
and/or national codes. This includes the standards of the National Fire  
Protection Association for Installation of Air-Conditioning and Ventilat-  
ing Systems, NFPA No. 90B.  
DUCT WORK TRANSITION  
FEEDER  
TUBES  
Duct work that is not designed to match the supply air opening can  
cause turbulence inside the plenum box. This turbulence can change  
the air flow patterns across the heat kit limit switch. If the factory sug-  
gested transition can not be fabricated, it is recommended a block off  
plate (approximately 8” in height and running the full width of the ple-  
num) be attached to the supply opening Please refer to Figure 7 as a  
visual aid. The use of this block off plate will keep better air circulation  
across the limit switch.  
CONDENSATE  
DEFLECTOR  
S-CLIPS ON HORIZONTAL PAN  
FIGURE 5: Condensate Deflecctor on Horizontal Drain Pan Edge  
DEFLECTOR  
DRAIN PAN  
WALL  
S-CLIP  
FIGURE 6: S-Clip Installation  
RECOMMENDED  
TRANSITION  
SUGGESTED LOCATION  
OF BLOCK OFF PLATE  
DUCT CONNECTIONS  
FIGURE 7: Duck Work Transition  
The above suggestions will not alleviate problems caused by improper  
installation. When receiving intermittent fault codes pertaining to the  
limit switch, always double check your airflow CFM, motor speed and  
static pressures.  
Use 1/2" screws to connect ductwork to bottom of unit. Longer screws  
will pierce the drain pan and cause leakage. If pilot holes are drilled,  
drill only though field duct and unit bottom flange.  
Air supply and return may be handled in one of several ways best  
suited to the installation. See Figure 3 for dimensions for duct inlet and  
outlet connections.  
AIR FILTERS  
Air filters must be field supplied. A 1" filter access rack has been built  
into the unit. See Figure 3. Remove filter access cover shown. Install  
proper size filter. Standard 1" size permanent or throw away filter may  
be used, or, permanent washable filters are available using model num-  
bers: 1PF0601, 602, 603BK. See Table 8 for filter size.  
The vast majority of problems encountered with combination heating  
and cooling systems can be linked to improperly designed or installed  
duct systems. It is therefore highly important to the success of an instal-  
lation that the duct system be properly designed and installed.  
Use flexible duct collars to minimize the transmission of vibration/noise  
into the conditioned space. If electric heat is used, non-flammable  
material must be used.  
Equipment should never be operated without filters.  
Where return air duct is short, or where sound may be a problem,  
sound absorbing glass fiber should be used inside the duct. Insulation  
of duct work is a must where it runs through an unheated space during  
the heating season or through an uncooled space during the cooling  
season. The use of a vapor barrier is recommended to prevent absorp-  
tion of moisture from the surrounding air into the insulation.  
HORIZONTAL SUSPENSION (AV ONLY)  
For suspension of these units in horizontal applications, it is recom-  
mended to use angle steel support brackets with threaded rods, sup-  
porting the units from the bottom, at the locations shown in Figure 8.  
When an evaporator coil is installed in an attic or above a finished ceil-  
ing, an auxiliary drain pan should be provided under the air handler as  
is specified by most local building codes.  
The supply air duct should be properly sized by use of a transition to  
match unit opening. All ducts should be suspended using flexible hang-  
Johnson Controls Unitary Products  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
SUSPENSION SUPPORT LOCATIONS FOR HORIZONTAL APPLICATIONS  
COIL UNDER PRESSURE.  
MIN. 3/8”  
Relieve pressure by depressing schrader core. Coil may have factory  
installed TXV or may require orifice or TXV to be added. See outdoor  
unit documentation for correct orifice or TXV to be used. Refer to coil  
nameplate for TXV identification for this unit.  
THREADED ROD  
MIN. 1-1/2” x 1-1/2”  
Angle Recommended  
length 26” minimum with  
2” clearance on both  
sides of Air Handler  
NOTICE  
The coil should be open to the air for no more than 2 minutes to keep  
moisture and contaminates from entering the system. If the coil can-  
not be installed into the refrigeration system in that time, the ends  
should be temporarily closed or plugged. For a short term delay, use  
masking tape over the ends of the copper tubing to close the tube to  
the air. For a longer term delay, use plugs or caps. There is no need  
to purge the coil if this procedure is followed.  
1-1/2  
2
YY  
WW  
XX  
Dimension  
Units  
(Nominal Tons)  
WW  
20  
XX  
46  
52  
57  
24B  
36C  
REFRIGERANT LINE CONNECTION  
24  
AV*48D, 60D  
28  
FIGURE 8: Typical Horizontal Installation  
Coil is under inert gas pressure. Relieve pressure from coil by  
depressing schrader core.  
TXV METERING DEVICES  
If the model (C) number is of the following format: 4F, 4G, 4H, 4J,  
and 4K will have the coil with R410A TXV metering device installed at  
the factory.  
If the model (C) number is of the 3X model series:  
Dry nitrogen should always be supplied through the tubing while it is  
being brazed, because the temperature required is high enough to  
cause oxidation of the copper unless an inert atmosphere is provided.  
The flow of dry nitrogen should continue until the joint has cooled.  
Always use a pressure regulator and safety valve to insure that only  
low pressure dry nitrogen is introduced into the tubing. Only a small  
flow is necessary to displace air and prevent oxidation.  
The coil will require an orifice or R410A TXV to be installed in the field.  
Refer to installation manual with TXV kit. It is recommended to install a  
orifice or TXV kit prior to brazing line sets.  
VAPOR  
LINE  
THERMAL  
EXPANSION  
VALVE BULB  
(Required insulation  
Connect lines as follows:  
LIQUID  
LINE  
not shown for clarity)  
NOTICE  
Route the refrigerant lines to the coil in a manner that will not obstruct  
service access to the coil, air handling system, or filter.  
THERMAL  
EXPANSION  
VALVE  
1. Suction and liquid line connections are made outside the cabinet.  
Leave the tubing connection panel attached to the cabinet with the  
tubes protruding through it. Coil access panel should be removed  
for brazing. The lines are swedged to receive the field line set  
tubes.  
TXV  
EQUALIZER  
LINE  
DISTRIBUTOR BODY  
FIGURE 9: TXV  
2. Cut the end of the suction tube using a tube cutter. Place the tube  
cutter as close as possible to the end of the tube to allow more  
space for the connection and brazing of the suction line.  
3. Remove the heat shield from the Customer Packet, soak in water,  
and install over coil tubing to prevent overheating of cabinet.  
4. Wrap a water soaked rag around the coil connection tubes inside  
the cabinet to avoid damaging the TXV bulb.  
Please refer to Outdoor Unit Tech Guide to verify which metering device  
is installed in this coil and that this is a valid system match for the AC or  
HP unit installed.  
The temperature sensing bulb is attached to the coil suction header  
line.  
SCREW  
5. Remove grommets where tubes exit the cabinet to prevent burning  
them during brazing.  
6. Purge refrigerant lines with dry nitrogen. Follow outdoor unit braz-  
ing instructions.  
7. Braze the suction and liquid lines.  
TXV BULB  
(Cover completely  
with insulation)  
8. Remove the heat shield.  
9. Re-attach the grommets to the lines carefully to prevent air leak-  
age.  
10. Attach the coil access panel to the cabinet.  
NUT  
SUCTION LINE  
CLAMP  
FIGURE 10: Proper Bulb Location  
Refer to Outdoor unit Installation Manual for evacuation, leak check and  
charging instructions.  
Lines should be sound isolated by using appropriate hangers or strap-  
ping.  
All evaporator coil connections are copper-to-copper and should be  
brazed with a phosphorous-copper alloy material such as Silfos-5 or  
equivalent. DO NOT use soft solder.  
6
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
For Upflow, Downflow and Horizontal right hand applications the kits  
can be installed without modification.  
DRAIN CONNECTIONS  
All drain lines should be trapped a minimum of three inches, should be  
pitched away from unit drain pan and should be no smaller than the coil  
drain connection.  
Field modification is required for Horizontal left hand airflow application  
only. Follow instructions with heater kits for modification.  
NOTICE  
If a heat kit with a circuit breaker is installed in the air handler, the cir-  
cuit breaker cover cladding must be removed to gain access to the  
sheet metal cover plate. Some local codes may require that the circuit  
breaker remain visible. If so, do not re-install circuit breaker cover  
cladding.  
Threaded drain connection should be hand-tightened, plus no more  
than 1/16 turn.  
Route the drain line so that it does not interfere with accessibility to the  
coil, air handling system or filter and will not be exposed to freezing  
temperatures. See Figures 2 and 3 for drain connection locations.  
SECTION V: LOW VOLTAGE CONTROL  
CONNECTIONS  
NOTICE  
This air handler can be connected to the wall thermostat and outdoor air  
conditioner or heat pump using either conventional low voltage (24  
VAC) thermostat wiring OR using four-wire digital communications wir-  
ing. To use conventional low voltage wiring, see the section below enti-  
tled “Conventional Low Voltage Control Wiring”. To use four-wire  
communications control wiring, see the section below entitled “Control  
Wiring using Communicating Controls”.  
When the coil is installed in an attic or above a finished ceiling, an  
auxiliary drain pan should be provided under the coil if specified by  
local building codes.  
Coils should be installed level or pitched slightly toward the drain end.  
Suggested pitch should not exceed 1/4 inch per foot of coil.  
The coil is provided with a secondary drain that should be trapped and  
piped to a location that will give the occupant a visual warning that the  
primary drain is clogged. If the secondary drain is not used it must be  
capped. When an exterior secondary drain pan is used that secondary  
drain should br piped to a location that will give the occupant a visual  
warning that the primary drain is clogged.The drain pan connections are  
designed to ASTM Standard D 2466 Schedule 40. Use 3/4" PVC or  
steel threaded pipe. Since the drains are not subject to any pressure it  
is not necessary to use Schedule 40 pipe for drain lines.  
The Communicating System consists of several intelligent communicat-  
ing components including the Communicating Thermostat Control  
(touch-screen wall thermostat), variable speed air handler, air condi-  
tioner (15 and 18 SEER premium air conditioners) or heat pump (13, 15  
and 18 SEER premium heat pumps), which continually communicate  
with each other via a four-wire connection called the A-R-Gnd or C-B  
bus. Commands, operating conditions, and other data are passed con-  
tinually between components over the A-R-Gnd or C-B bus. See Figure  
13. The result is a new level of comfort, versatility, and simplicity.  
DO NOT use teflon tape, “pipe dope” or other sealants. The use of a  
sealant may cause damage and premature failure of hte drain pan  
In order to use this air handler in full communications (COMM) mode, it  
MUST be installed with the matching touch-screen Communicating  
Control (wall thermostat) and an outdoor air conditioner or heat pump  
with a fully communicating control.  
SECTION IV: ELECTRIC HEATER  
INSTALLATION  
This air handler may also be used along with the Communicating Ther-  
mostat Control and a non-communicating outdoor air conditioner  
through the addition of a communicating Outdoor Aux Control board to  
the outdoor unit. This system allows full communication between the air  
handler and thermostat and limited communication to the outdoor unit.  
If the air handler requires electric heat, install the electric heat kit  
according to the installation instructions included with the kit. After  
installing the kit, mark the air handler nameplate to designate the heater  
kit that was installed. If no heater is installed, mark the name plate  
appropriately to indicate that no heat kit is installed.  
This air handler may also be used along with the Communicating Ther-  
mostat Control and a non-communicating outdoor air conditioner or  
heat pump using COMM between the air handler and thermostat and  
conventional 24V wiring to the outdoor unit. This system allows full  
communication between the air handler and thermostat but no digital  
communication with the outdoor unit. See Figure 14.  
The HEAT/ENABLE jumper (See Figure 10) must be moved to the  
HEAT position to enable operation of the heater.  
Use only 4HK heater kits, as listed on Air Handler name plate and in  
these instructions. Use data from Tables 10 and 13 for information on  
required minimum motor speed tap to be used for heating operation,  
maximum over-current protection device required and minimum electri-  
cal supply wiring size required – for listed combination of Air Handler  
and Heater Kit.  
HUMIDIFIER OUT PUT  
HEAT ENABLE JUMPER  
EAC OUTPUT  
AC/HP JUMPER  
HUMIDSTAT  
JUMPER  
BLOWER SPEED  
JUMPERS  
SPARE JUMPER  
CONTINUOUS FAN JUMPER  
THERMOSTAT CONNECTIONS  
FIGURE 11: Air Handler Control Board – Communications Connections  
Johnson Controls Unitary Products  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
CONVENTIONAL LOW VOLTAGE CONTROL WIRING  
(24 VAC)  
TABLE 2: Low Voltage Connections  
Terminal Signal  
Comment  
The 24 volt power supply is provided by an internally wired low voltage  
transformer which is standard on all models, However, if the unit is con-  
nected to a 208 volt power supply, the low voltage transformer must be  
rewired to the 208 volt tap. See the unit wiring label.  
R
G
24 VAC power (fused)  
Continuous Fan operation  
Second or full stage  
compressor operation  
Y/Y2  
Y1  
First stage compressor  
operation  
Not used with outdoor units  
having one stage compressors.  
Field supplied low voltage wiring can exit the unit on the top right hand  
corner or the right hand side panel. Refer to Figure 3.  
W2  
W1  
Second stage heat operation  
First stage heat operation  
Remove desired knockout and pierce foil faced insulation to allow wir-  
ing to pass through. Use as small of a hole as possible to minimize air  
leakage.  
24 VAC will be present at this  
terminal when the MODE  
jumper is in the AC position.  
This is normal.  
O
Reversing valve operation  
Humidity switch input  
Install a 7/8” plastic bushing in the selected hole and keep low voltage  
wiring as short as possible inside the control box.  
24 VAC will be present at this  
terminal when the HUM STAT  
jumper is in the NO position.  
This is normal.  
To further minimize air leakage, seal the wiring entry point at the outside  
of the unit.  
HUM  
The field wiring is to be connected at the screw terminals of the control  
board. Refer to Figure 11 and 12.  
This terminal is a connection  
point only and does not affect  
air handler control operation.  
Connection point for  
heat pump fault indicator  
X/L  
COM  
24 VAC common  
NOTICE  
.All wiring must comply with local and national electrical code require-  
ments. Read and heed all unit caution labels.  
The low voltage connections may be connected to the screw terminals  
or the quick connect terminals. The screw terminals and the quick con-  
nect terminals are physically connected on the control board.  
NOTICE  
It is possible to vary the amount of electric heat turned on during the  
defrost cycle of a heat pump. Standard wiring will only bring on the  
first stage of electric heat during defrost. See Heat Output and Limit  
Connections and Table 5 for additional information on heat during  
defrost cycle.  
Air Handler Control Wiring  
Typical A/C - Cooling only Applications  
Air Handler Control Wiring  
Typical A/C with Electric Heat Applications  
AIR HANDLER  
AIR HANDLER  
THERMOSTAT  
1 - STAGE  
BOARD  
THERMOSTAT  
1 - STAGE  
BOARD  
AIR CONDITIONING  
AIR CONDITIONING  
R
G
R
G
R
G
Y
R
G
Y
Y / Y2  
Y
Y / Y2  
Y
W1  
W2  
C
Y1  
Y1  
W2  
W2  
W2  
*
*
W1  
O
W1  
O
HUMIDISTAT  
HUMIDISTAT  
W1  
C
HUM  
X / L  
COM  
HUM  
X / L  
COM  
C
C
FIGURE 12: Cooling Models with and without Electric Heat Wiring  
* Optional dehumidification humidistat switch contacts open on humidity rise.  
NOTES:  
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.  
2. Remove humidistat jumper on air handler control board.  
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.  
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.  
8
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
.
CONTROL WIRING - Air Handler & UPG HP Systems  
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”  
Conventional Application - Not Hot Heat Pump  
AIR HANDLER  
BOARD  
2 - STAGE SCROLL  
HEAT PUMP  
THERMOSTAT  
R
G
R
G
R
Y2  
Y2  
Y / Y2  
Y1  
Y2 OUT  
Y1  
Y1  
W2 OUT  
W2  
W1  
E
W1 OUT  
W
O
W
O
O
*
HUM  
X / L  
COM  
BS  
X / L  
C
HUMIDISTAT  
X / L  
C
FIGURE 13: Two-Stage Heat Pump Wiring  
* Optional dehumidification humidistat switch contacts open on humidity rise.  
NOTES:  
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.  
2. Remove humidistat jumper on air handler control board.  
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.  
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board  
CONTROL WIRING USING COMMUNICATING  
CONTROLS  
HUMIDITY SWITCH INPUT  
The air handler control is designed to work with a humidity control that  
closes when the humidity is below the set-point. The control is open  
when the humidity is above the set-point. This humidity control may be  
referred to as a humidistat or a dehumidistat.  
Use the wiring diagram below to connect the air handler control, Com-  
municating Control (wall thermostat) and communicating outdoor unit.  
Be sure that all of the “A” terminals are connected together, all of the “B”  
terminals are connected together, all of the “GND” or “C” terminals are  
connected together and all of the “R” terminals are connected together.  
See Figure 13. When using a fully communicating system, the large  
screw terminals (C, G, R, etc.) on the air handler control are not used.  
The four small screw terminals in the terminal block on the end of the air  
handler control should be used.  
The humidity switch controls both humidification and de-humidification  
operation of the control. The control provides humidification using the  
HUM OUT relay output and de-humidification by lowering the blower  
speed. This is accomplished using the de-humidification input of the  
motor for variable speed models. The humidity switch should be con-  
nected to the R and HUM terminals of the control. See Figures 11 and  
12.  
Touch Screen  
Communicating  
Control  
Air Handler  
Communicating  
Control  
Air Conditioner/Heat Pump  
Communicating Control  
The 24 volt power supply is provided by an internally wired low voltage  
transformer which is standard on all models, However, if the unit is con-  
nected to a 208 volt power supply, the low voltage transformer must be  
rewired to the 208 volt tap. See the unit wiring label.  
A+  
R
A+  
R
A+  
R
Field supplied low voltage wiring can exit the unit on the top right hand  
corner or the right hand side panel. Refer to Figure 3.  
C
C
C
Remove desired knockout and pierce foil faced insulation to allow wir-  
ing to pass through. Use as small of a hole as possible to minimize air  
leakage.  
B-  
B-  
B-  
Install a 7/8” plastic bushing in the selected hole and keep low voltage  
wiring as short as possible inside the control box.  
R
G
To further minimize air leakage, seal the wiring entry point at the outside  
of the unit.  
Y/Y2  
Y1  
The field wiring is to be connected at the screw terminals of the control  
board. Refer to Figures 11 or 12.  
W2  
W1  
O
NOTICE  
All wiring must comply with local and national electrical code require-  
ments. Read and heed all unit caution labels.  
HUM  
X/L  
COM  
NOTICE  
It is possible to vary the amount of electric heat turned on during the  
defrost cycle of a heat pump. Standard wiring will only bring on the  
first stage of electric heat during defrost. See Heat Output and Limit  
Connections and Table 5 for additional information on heat during  
defrost cycle.  
FIGURE 14: Air Handler with Communicating AC or HP  
Johnson Controls Unitary Products  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
The low voltage connections may be connected to the screw terminals  
or the quick connect terminals. The screw terminals and the quick con-  
nect terminals are physically connected on the control board.  
Mode Jumper  
The MODE jumper configures the control to operate properly with an air  
conditioner (AC position) or heat pump (HP position). With the jumper in  
the AC position, the control will energize the O terminal with 24 VAC  
continually. With the jumper in the HP position, the O input signal is  
received from the room thermostat.  
TABLE 3: Low Voltage Connections  
Terminal Signal  
Comment  
R
G
24 VAC power (fused)  
If the jumper is not present, the control will operate as if the jumper is in  
the HP position.  
Continuous Fan operation  
Second or full stage  
compressor operation  
Y/Y2  
Y1  
SPARE Jumper  
First stage compressor  
operation  
Not used with outdoor units  
having one stage compressors.  
The control includes a spare jumper that can be used if a jumper is lost.  
The SPARE jumper does not have any effect on the operation of the  
control.  
W2  
W1  
Second stage heat operation  
First stage heat operation  
Airflow and Comfort Setting Jumpers  
24 VAC will be present at this  
terminal when the MODE  
jumper is in the AC position.  
This is normal.  
See separate section.  
O
Reversing valve operation  
Humidity switch input  
Status and Fault Codes  
24 VAC will be present at this  
terminal when the HUM STAT  
jumper is in the NO position.  
This is normal.  
The control includes an LED that displays status and fault codes. These  
codes are shown in Table 4. The control will display the fault codes until  
power is removed from the control or the fault condition is no longer  
present.  
HUM  
This terminal is a connection  
point only and does not affect  
air handler control operation.  
Connection point for  
heat pump fault indicator  
X/L  
TABLE 4: Fault Codes  
LED1 (RED)  
Fault or Status Condition  
COM  
24 VAC common  
Flash Code  
SECTION VI: REQUIRED CONTROL  
SET-UP  
Status  
No power to control  
OFF  
2s ON/2s OFF  
Rapid Flash  
ON  
Normal operation  
Control in test mode  
Control failure  
The following steps must be taken at the time of installation to insure  
proper system operation.  
Limit Faults  
Limit switch currently open (not in lockout)  
Multiple limit openings with no call for heat  
Multiple limit openings during one call for heat  
Single long duration limit opening  
Multiple long duration limit openings  
Fan failure  
1
2
3
4
5
6
1. Consult system wiring diagram to determine proper thermostat  
wiring for your system.  
2. If heat kit is installed, change HEAT/NO HEAT jumper from NO  
HEAT to HEAT position.  
3. If a humidistat is installed, change HUM STAT jumper from NO to  
YES.  
Wiring Related Faults  
Simultaneous call for heating and cooling  
Internal Control Faults  
7
9
4. Set the MODE jumper to A/C (Air Conditioner) or HP (Heat Pump)  
position depending on the outdoor unit included with the system.  
Control recovered from internal event  
5. Set airflow and comfort setting jumper to proper positions.  
FUNCTIONALITY AND OPERATION  
Jumper Positions  
External Relay Outputs  
The control includes two outputs to drive external relays having 24 VAC  
coils. The outputs have a maximum rating of 1.0 Amp pilot duty at 24  
VAC.  
HEAT/NO HEAT Jumper  
The HEAT/NO HEAT jumper configures the control for heat kit opera-  
tion. The jumper must be in the HEAT position if a heat kit is installed  
with the air handler.  
HUM OUT  
The HUM OUT output can be used to drive an external relay or solenoid  
(24 VAC coil) to control a humidifier. The output is energized when the  
HUM input is energized, the HUM STAT is in the YES position, and the  
control has a thermostat call for heating (heat pump or electric heat).  
With the jumper in the NO HEAT position, the control will not energize  
the heat relay outputs or sense the limit switch input.  
If the jumper is not present, the control will operate as if the jumper is in  
the HEAT position. If the jumper is not present and a heat kit is not pres-  
ent, the control will sense an open limit condition and the blower will run  
continuously.  
EAC  
The EAC output can be used to drive an external relay (24 VAC coil) to  
control an electronic air cleaner. The output is energized whenever the  
blower relay on the control is energized.  
Hum Stat Jumper  
The HUM STAT jumper configures the control to monitor the humidity  
switch input. With the jumper in the NO position, the control will ener-  
gize the HUM terminal with 24 VAC continually. With the jumper in the  
YES position, the control will monitor the HUM input to control the HUM  
OUT output to control an external humidifier.  
Heat Output and Limit Connections  
The control is connected to the heater relays and limit switch using the  
6-pin connector. The relay outputs and the limit switch signal are 24  
VDC.  
The control energizes the heat relays and senses the limit switch input  
as shown in Table 5 when the HEAT ENABLE jumper is in the HEAT  
position.  
If the jumper is not present, the control will operate as if the jumper is in  
the YES position.  
10  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
Hard Lockout  
TABLE 5: Heat Relays  
The control has a hard lockout condition during which the control will  
keep all heat outputs de-energized until power is removed from the con-  
trol. The control de-energizes the blower five minutes after entering the  
hard lockout condition.  
Input  
W1  
Heat Relay Output  
HT1  
W2  
HT1 and HT2  
HT1 and HT2 and HT3  
W1 and W2  
If the limit switch closes and re-opens during the one hour soft lockout  
period, the control will enter a hard lockout condition and continue to  
indicate a fault code 5.  
The control energizes the first stage of electric heat immediately, the  
second stage 10 seconds after the call for second stage heat, and the  
third stage 20 seconds after the call for third stage heat.  
If the limit switch opens twice when no call for electric heat is present  
(fault code 2), the control will enter a hard lockout condition.  
Depending on the heat kit installed in the air handler, the control pro-  
vides the flexibility to configure the amount of heat delivered with the  
first stage heating call. As an example, when the control’s W1 input is  
connected to the room thermostat’s first stage heat signal, a call for first  
stage heat will energize one heating element (HT1). If the control’s W2  
input is connected to the room thermostat’s first stage heat signal, a call  
for first stage heat will energize two heating elements (HT1 and HT2).  
With either configuration, the control will energize three heating ele-  
ments (HT1, HT2, and HT3) when it receives a first and second stage  
heat input from the thermostat.  
If the limit switch opens multiple times soon after a soft lockout reset  
(fault code 6), the control will enter a hard lockout condition.  
Wiring Related Faults  
If the control receives a simultaneous call for heating and cooling (fault  
code 7), the control will perform both heating and cooling operations.  
SECTION VII: LINE POWER  
CONNECTIONS  
Power may be brought into the unit through the supply air end of the  
unit (top when unit is vertical) or the left side panel. Use the hole appro-  
priate to the unit’s orientation in each installation to bring conduit from  
the disconnect. The power lead conduit should be terminated at the  
electrical control box. Refer to Tables 11, 12, 14 and 15 to determine  
proper wire sizing. To minimize air leakage, seal the wiring entry point at  
the outside of the unit.  
Limit Switch and Lockout Operation  
Limit Switch Operation  
If the HEAT ENABLE jumper is in the HEAT position and the limit switch  
opens (fault code 1), the control will immediately de-energize all electric  
heat relay outputs and energize the blower (if it wasn’t already ener-  
gized). When the limit switch closes, the control will re-energize electric  
heat according to the thermostat inputs using normal timings.  
All electrical connections to air handlers must be made with copper con-  
ductors. Direct connection of aluminum wiring to air handlers is  
not approved.  
Fan On Lock Condition  
If the limit switch opens multiple times during a single call for electric  
heat (fault code 3) or if the limit switch opens for a long duration (fault  
code 4), the control will energize the blower until power is removed from  
the control. The control will cycle the heat outputs on and off as the limit  
re-closes and opens. The constant fan operation will signal the home-  
owner that a problem has occurred and a service call is required.  
If aluminum conductors are present, all applicable local and national  
codes must be followed when converting from aluminum to copper con-  
ductors prior to connection to the air handler.  
If wire other than uncoated (non-plated), 75° C ambient, copper wire is  
used, consult applicable tables of the National Electic Code (ANSI/  
NFPA 70). The chosen condutor and connections all must meet or  
exceed the amperage rating of the overcurrent protector (circuit breaker  
or fuse) in the circuit.  
Soft Lockout  
If the limit switch opens for a second long duration period during a sin-  
gle call for heat (fault code 5), the control will keep the blower locked on  
and lock out the heat outputs for one hour. The control will only reset  
this one hour lockout when the power is removed from the control. After  
the one hour period has passed, the control will re-energize electric  
heat according to the thermostat inputs using normal timings. The  
blower will remain locked on from the first long duration limit opening.  
Additionally, existing aluminum wire within the structure must be sized  
correctly for the application according to National Electric Code and  
local codes. Caution must be used when sizing aluminum rather than  
copper conductors, as aluminum conductors are rated for less current  
than copper conductors of the same size.  
ELECTRIC HEAT  
WITHOUT CIRCUIT BREAKER  
3 PHASE (10 - 15 KW)  
1 PHASE ELECTRIC HEAT  
WITH CIRCUIT BREAKER  
AS SHIPPED FROM FACTORY  
SINGLE SOURCE  
TYPICAL WIRING WITHOUT ELECTRIC HEAT  
GND.  
LUG  
GND. LUG  
GND.  
LUG  
GND. LUG  
(2.5 - 25 KW) - 25 KW SHOWN  
POWER  
SUPPLY  
GND. LUG  
GND.  
LUG  
POWER  
SUPPLY  
1 PHASE ELECTRIC HEAT  
WITH CIRCUIT BREAKER  
& BREAKER BAR REMOVED  
TERMINAL  
BLOCK  
ELECTRIC HEAT  
WITHOUT CIRCUIT BREAKER  
SINGLE SOURCE (2.5 - 10 KW)  
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN  
GND. LUG  
POWER  
SUPPLY  
GND.  
LUG  
GND.  
LUG  
GND. LUG  
(JUMPER BAR)  
POWER  
SUPPLY 1  
MAY BE 1, 2, OR 3  
CIRCUIT BREAKERS  
POWER  
SUPPLY 2  
POWER  
SUPPLY  
POWER  
SUPPLY 3  
POWER WIRING (208/230-1-60)  
TERMINAL  
BLOCK  
MAY BE 1, 2, OR 3  
CIRCUIT BREAKERS  
CONNECT TRANSFORMER LEADS WITH  
WIRE NUTS (TYPICAL ALL HEAT KITS)  
FIGURE 15: Line Power Connections  
Johnson Controls Unitary Products  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
Fan Only CFM:  
SECTION VIII: AIRFLOW AND COMFORT  
SETTING SELECTION  
When the connection is made from "R" to "G", the fan only mode is acti-  
vated. In this mode, the airflow will depend on the position of the CONT  
Fan jumper. In the “H” position, the blower will deliver 85-90% of full  
capacity. In the “M” position, the blower will deliver 60-65% of full  
capacity. In the “L” position, the blower will deliver 30-35% of full capac-  
ity.  
AIRFLOW SELECTION  
The airflow and comfort setting selection jumpers must be set properly  
at the time of installation for proper system operation. Place jumpers in  
the proper locations based on the information shown in Table 16 and  
Figure 11.  
Blower Ramp-Up /Ramp-Down:  
Inputs to air handler control board are passed to the motor which deter-  
mines the target CFM to be delivered. The following inputs will produce  
the CFM per the appropriate table and selected tap settings.  
To minimize the sound made by the blower when it speeds up or slows  
down, the blower will slowly ramp up or down from one speed to  
another. Changes in blower speed during A/C or heat pump heating  
can take up to 30 seconds. Changes in blower speed during electric  
strip heating can take up to 15 seconds.  
NOTICE  
Incorrect airflow and comfort settings may result in decreased system  
efficiency and performance.  
COMFORT SETTINGS  
TABLE 6: Comfort Setting Selection  
These variable speed air handlers are designed to deliver constant air-  
flow (CFM) regardless of the external static pressure (ESP) in the duct-  
work. Therefore, if too many supply registers are closed, a filter  
becomes clogged, or there is a restriction in the ductwork, the motor will  
automatically operate at a higher speed to compensate for the higher  
ESP. This may result in a higher operating sound level.  
DELAY TAP  
COMFORT SETTING  
Normal  
A
B
C
D
Humid  
Dry  
Temperate  
To Set Cooling Airflow:  
Refer to the outdoor unit technical guide for the recommended airflow  
with the matching evaporator coil. Refer to Table 16 for the possible  
high speed cooling and heat pump airflow selections.  
Normal  
The normal setting provides a ramp-up from zero airflow to full capacity  
and a ramp-down from full capacity back to zero airflow.  
Find the recommended system airflow in Table 16 for the installed air  
handler model.  
Humid  
The humid setting is best-suited for installations where the humidity is  
frequently very high during cooling season, such as in the southern part  
of the country. On a call for cooling, the blower will ramp up to 50% of  
full capacity and will stay there for two minutes, then will ramp up to  
82% of full capacity and will stay there for five minutes, and then will  
ramp up to full capacity, where it will stay until the wall thermostat is sat-  
isfied.  
Select the COOL airflow you need from Table 16. Set the COOL and  
ADJUST Jumpers on the control as indicated in Table 16.  
To Set Heat Pump Airflow:  
The heat pump airflow setting is the same as the cooling airflow setting.  
No additional airflow setting is required. However, you must set the  
MODE jumper to the HP position for proper system operation (See Fig-  
ure 11).  
Dry  
To Set Electric W1 Heat Airflow:  
The dry setting is best suited to parts of the country where excessive  
humidity is not generally a problem, where the summer months are usu-  
ally dry. On a call for cooling the motor will ramp up to full capacity and  
will stay there until the thermostat is satisfied. At the end of the cooling  
cycle, the blower will ramp down to 50% of full capacity where it will stay  
for 60 seconds. Then it will ramp down to zero.  
The blower speed required for 1st stage electric heat is different than  
cooling. Refer to Table 16 for the possible CFM selections. Refer to  
Table10 for the minimum required airflow for the electric heater  
installed. Find the desired airflow in Table 16 for low heat. Set the HEAT  
jumper on the control as indicated in Table 16.  
Temperate  
To Set W2 Electric Heat Airflow:  
The temperate setting is best suited for most of the country, where nei-  
ther excessive humidity nor extremely dry conditions are the norm. On  
a call for cooling, the motor will ramp up to 63% of full capacity and will  
stay there for 90 seconds, then will ramp up to full capacity. At the end  
of the cooling cycle, the motor will ramp down to 63% of full capacity  
and will stay there for 30 seconds, then will ramp down to zero.  
Airflow for any W2 input, which is for Stages 2 & 3 of electric heat, is the  
indicated CFM for high heat tap selection on Table 16.  
DO NOT change the ADJUST tap position on the control as this will  
change your cooling airflow previously selected.  
SECTION IX: UNIT DATA  
TABLE 7: Physical and Electrical Data - Cooling Only (60 Hz)  
Models  
24B  
10 x 7  
1/3  
36C  
10 x 7  
1/2  
48D  
10 x 10  
3/4  
60D  
10 x 10  
1
Blower - Diameter x Width  
HP  
Motor  
Nominal RPM  
1200  
1200  
1200  
1200  
Voltage  
Amps  
230  
Full Load (230)  
Type  
2.8  
4.3  
5.5  
7.0  
DISPOSABLE OR PERMANENT  
Filter1  
Size  
16 x 20 x1  
1PF0601BK  
140/134  
20 x 20 x1  
1PF0602BK  
170/164  
22 x 20 x1  
1PF0603BK  
AV - 196/185  
22 x 20 x1  
1PF0603BK  
AV - 199/188  
Permanent Type Kit  
Shipping/Operating Weight (lbs.)  
1. Field Supplied.  
12  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
TABLE 8: Electrical Data - Cooling Only (60 Hz)  
Total Motor Amps  
Minimum Circuit Ampacity  
60 Hertz  
Max. O.C.P.  
Amps/Type1  
Minimum Wire  
Size A.W.G.  
Models  
60 Hertz  
208V  
3.2  
230V  
2.8  
208V  
4.0  
230V  
3.5  
24B  
36C  
48D  
60D  
15  
15  
15  
15  
14  
14  
14  
14  
4.7  
4.3  
5.9  
5.4  
6.1  
5.0  
7.6  
6.9  
7.8  
7.0  
9.7  
8.8  
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
TABLE 9: Conversion Table  
kW & MBH Conversions - for Total Power Input Requirement  
208V  
FOR 230V  
220V  
240V  
240V  
240V  
.751  
.918  
.840  
OPERATION MULTIPLY  
TABULATED kW & MBH BY  
TABLE 10: Electrical Data - 208/230-1-60  
Total Heat1  
kW Staging  
W2 Only  
Heater  
Models  
Max.  
Static  
Min.  
Speed Tap  
kW  
MBH  
W1 Only  
W1 & W2  
Models*  
208v 230v 208v 230v 208v 230v 208v 230v 208v 230v  
4HK*6500206  
4HK*6500506  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
Heat-D  
Heat-D  
Heat-C  
Heat-B  
Heat A  
Heat-A  
Heat-C  
Heat-C  
Heat-C  
Heat C  
Heat-C  
Heat-A  
Heat-D  
Heat-C  
Heat-C  
Heat C  
Heat-C  
Heat-B  
Heat-B  
Heat-B  
Heat-D  
Heat-D  
Heat-C  
Heat C  
Heat-C  
Heat-C  
Heat-C  
Heat-C  
1.9  
3.6  
2.5  
4.8  
6.4  
8.5  
1.9  
3.6  
2.8  
3.6  
3.3  
3.6  
3.6  
2.8  
3.6  
3.3  
3.6  
3.3  
3.6  
2.8  
3.6  
3.3  
3.6  
3.3  
3.6  
3.6  
3.6  
2.8  
3.6  
3.3  
3.6  
3.3  
3.6  
3.6  
2.5  
4.8  
3.75  
4.8  
4.3  
4.8  
4.8  
3.75  
4.8  
4.3  
4.8  
4.4  
4.8  
3.75  
4.8  
4.3  
4.8  
4.4  
4.8  
4.8  
4.8  
3.75  
4.8  
4.3  
4.8  
4.4  
4.8  
4.8  
1.9  
3.6  
5.6  
7.2  
6.5  
7.2  
3.6  
5.6  
7.2  
6.5  
7.2  
6.6  
3.6  
5.6  
7.2  
6.5  
7.2  
6.6  
7.2  
10.8  
3.6  
5.6  
7.2  
6.5  
7.2  
6.6  
7.2  
10.8  
2.5  
4.8  
7.5  
9.6  
8.7  
9.6  
4.8  
7.5  
9.6  
8.7  
9.6  
8.8  
4.8  
7.5  
9.6  
8.7  
9.6  
8.8  
9.6  
14.4  
4.8  
7.5  
9.6  
8.7  
9.6  
8.8  
9.6  
14.4  
1.9  
3.6  
2.5  
4.8  
12.3  
19.2  
24.6  
33.3  
36.9  
12.3  
19.2  
24.6  
33.3  
36.9  
45.1  
12.3  
19.2  
24.6  
33.3  
36.9  
45.1  
49.2  
61.5  
12.3  
19.2  
24.6  
33.3  
36.9  
45.1  
49.2  
61.5  
16.4  
25.6  
32.8  
44.4  
49.1  
16.4  
25.6  
32.8  
44.4  
49.1  
60.1  
16.4  
25.6  
32.8  
44.4  
49.1  
60.1  
65.5  
81.9  
16.4  
25.6  
32.8  
44.4  
49.1  
60.1  
65.5  
81.9  
4HK*6500806  
5.6  
7.5  
5.6  
7.5  
24B  
4HK*6501006  
7.2  
9.6  
7.2  
9.6  
4HK16501306  
4HK165N1506  
4HK*6500506  
4HK*6500806  
9.8  
13  
9.8  
13  
10.8  
3.6  
14.4  
4.8  
10.8  
3.6  
14.4  
4.8  
5.6  
7.5  
5.6  
7.5  
4HK*6501006  
36C  
7.2  
9.6  
7.2  
9.6  
4HK16501306  
9.8  
13  
9.8  
13  
4HK16501506  
4HK16501806  
4HK*6500506  
4HK*6500806  
4HK*6501006  
10.8  
13.2  
3.6  
14.4  
17.6  
4.8  
10.8  
13.2  
3.6  
14.4  
17.6  
4.8  
5.6  
7.5  
5.6  
7.5  
7.2  
9.6  
7.2  
9.6  
4HK16501306  
9.8  
13  
9.8  
13  
48D  
4HK16501506  
10.8  
13.2  
14.4  
18.0  
3.6  
14.4  
17.6  
19.2  
24.0  
4.8  
10.8  
13.2  
14.4  
18.0  
3.6  
14.4  
17.6  
19.2  
24  
4HK16501806  
4HK16502006  
4HK16502506  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4.8  
5.6  
7.5  
5.6  
7.5  
7.2  
9.6  
7.2  
9.6  
4HK16501306  
9.8  
13  
9.8  
13  
60D  
4HK16501506  
10.8  
13.2  
14.4  
18.0  
14.4  
17.6  
19.2  
24.0  
10.8  
13.2  
14.4  
18.0  
14.4  
17.6  
19.2  
24.0  
4HK16501806  
4HK16502006  
4HK16502506  
1. See conversion Table 9.  
*
May be 0 (no breaker) or 1 (with breaker).  
Johnson Controls Unitary Products  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
TABLE 11: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-1-60  
Field Wiring  
Heater  
Heater  
Models*  
Max. O.C.P. Amps/Type1  
Models  
Amps  
240V  
Min. Circuit Ampacity  
75°C Wire Size - AWG  
208V  
15.28  
25.67  
37.85  
47.33  
62.6  
230V  
16.53  
28.50  
42.63  
53.50  
71.3  
208V  
20  
230V  
20  
208V  
12  
10  
8
230V  
12  
10  
8
4HK*6500206  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501306  
4HK165N1506  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501306  
4HK16501506  
4HK16501806  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501306  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
4HK*6500506  
4HK*6500806  
4HK*6501006  
4HK16501306  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
10.4  
20.0  
31.3  
40.0  
54.2  
60.0  
20.0  
31.3  
40.0  
54.2  
60.0  
73.3  
20.0  
31.3  
40.0  
54.2  
60.0  
73.3  
80.0  
100.0  
20.0  
31.3  
40.0  
54.2  
60.0  
73.3  
80.0  
100.0  
30  
30  
45  
45  
24B  
50  
60  
8
6
70  
80  
4
2
69.00  
27.54  
39.73  
49.21  
64  
78.50  
30.38  
44.50  
55.38  
72.8  
70  
90  
4
3
30  
35  
10  
8
10  
8
45  
45  
50  
60  
8
6
36C  
70  
80  
4
2
70.88  
85.32  
29.29  
41.48  
50.96  
66.4  
80.38  
97.00  
31.88  
46.00  
56.88  
75.2  
70  
90  
4
3
90  
100  
35  
4
3
35  
8
8
45  
50  
8
8
60  
60  
6
6
70  
80  
4
2
48D  
72.63  
87.07  
94.29  
115.96  
31.42  
43.60  
53.08  
68.4  
81.88  
98.50  
106.88  
131.88  
33.75  
47.88  
58.75  
77.2  
90  
90  
3
3
90  
100  
125  
150  
35  
3
2
100  
125  
35  
3
1
1
1/0  
8
8
45  
50  
8
8
60  
60  
6
6
70  
80  
4
2
60D  
74.75  
89.19  
96.42  
118.08  
83.75  
100.38  
108.75  
133.75  
90  
90  
3
3
90  
110  
125  
150  
3
2
100  
125  
3
1
1
1/0  
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
May be 0 (no breaker) or 1 (with breaker).  
*
TABLE 12: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-1-60  
Max. O.C.P. Amps/Type1  
Circuit  
Min. Circuit Ampacity  
75°C Wire Size - AWG  
Heater  
Models  
Circuit  
2nd  
Circuit  
Models  
1st  
3rd  
1st  
2nd  
3rd  
1st  
2nd  
3rd  
208/230  
208/230  
208/230  
208/230 208/230 208/230 208/230 208/230 208/230  
4HK16501306  
4HK165N1506  
4HK16501306  
4HK16501506  
4HK16501806  
4HK16501306  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
4HK16501306  
4HK16501506  
4HK16501806  
4HK16502006  
4HK16502506  
43.1/48.6  
47.5/53.5  
41.7/47.9  
48.5/55.4  
44.9/51.2  
42.9/49.1  
51.0/56.9  
47.4/52.7  
51.0/56.9  
51.0/56.9  
43.9/50.1  
53.1/58.8  
49.5/54.6  
53.1/58.8  
53.1/58.8  
19.5/22.5  
21.7/25.0  
22.4/25.0  
21.7/25.0  
39.8/45.8  
23.6/26.2  
21.7/25.0  
39.8/45.8  
43.4/50.0  
43.4/50.0  
24.6/27.2  
21.7/25.0  
39.8/45.8  
43.4/50.0  
43.4/50.0  
45/50  
50/60  
50/50  
50/60  
45/60  
50/50  
60/60  
50/60  
60//60  
60/60  
50/60  
60/60  
50/60  
60/60  
60/60  
20/25  
25/25  
30/30  
25/25  
40/50  
30/30  
25/25  
40/60  
45/50  
45/50  
30/30  
25/25  
40/60  
45/50  
45/50  
6/6  
8/6  
6/6  
8/6  
8/8  
6/6  
6/6  
6/6  
6/6  
6/6  
6/6  
6/6  
6/6  
6/6  
6/6  
12/10  
10/10  
12/10  
10/10  
8/8  
24B  
36C  
12/10  
10/10  
8/6  
48D  
60D  
8/8  
21.7/25.0  
25/25  
8/8  
10/10  
10/10  
10/10  
8/6  
8/8  
21.7/25.0  
25/25  
8/8  
10/10  
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
14  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
TABLE 13: Electrical Data - 208/230-3-60  
Total Heat1  
MBH  
kW Staging  
W2 Only  
208V 230V 208V 230V 208V 230V 208V 230V 208V 230V  
Min.  
Speed  
Tap  
Heat Kit -  
Models  
Max.  
Static  
kW  
W1 Only  
W1 + W2  
Three Phase  
24B  
36C  
4HK06501025  
4HK06501025  
4HK06501525  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501525  
4HK06501825  
4HK16502525  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
0.5  
Heat-B  
Heat-C  
7.2  
7.2  
9.6  
9.6  
24.6  
24.6  
36.9  
24.6  
36.9  
44.7  
24.6  
36.9  
44.7  
61.4  
32.8  
32.8  
49.1  
32.8  
49.1  
58.7  
32.8  
49.1  
58.7  
81.4  
7.2  
7.2  
9.6  
9.6  
7.2  
7.2  
9.6  
9.6  
7.2  
7.2  
9.6  
9.6  
Heat-C 10.8  
Heat-C 7.2  
14.4  
9.6  
10.8  
7.2  
14.4  
9.6  
10.8  
7.2  
14.4  
9.6  
10.8  
7.2  
14.4  
9.6  
48D  
Heat-C 10.8  
Heat-B 12.9  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
10.8  
12.9  
7.2  
14.4  
17.2  
9.6  
Heat-C  
7.2  
Heat-C 10.8  
Heat-B 12.9  
Heat-C 18.0  
14.4  
17.2  
24.0  
10.8  
12.9  
9.0  
14.4  
17.2  
12.0  
10.8  
12.9  
18.0  
14.4  
17.2  
24.0  
10.8  
12.9  
18.0  
14.4  
17.2  
24.0  
60D  
1. See conversion Table 9.  
TABLE 14: Electrical Data - (For Single Source Power Supply) - Copper Wire - 208/230-3-60  
Field Wiring  
Max. O.C.P.1 Amps/Type  
Heater  
Amps  
240V  
Heat Kit -  
Three Phase  
Models  
Min. Circuit Ampacity  
75°C Wire Size - AWG  
208V  
28.5  
30.4  
42.9  
31.3  
43.8  
51.0  
33.8  
48.8  
46.3  
230V  
32.4  
34.3  
48.8  
35.1  
49.6  
58.0  
37.6  
56.9  
52.1  
208V  
30  
230V  
35  
208V  
10  
10  
8
230V  
24B  
36C  
4HK06501025  
4HK06501025  
4HK06501525  
4HK06501025  
4HK06501525  
4HK06501825  
4HK06501025  
4HK06501825  
4HK06501525  
23.1  
23.1  
34.7  
23.1  
34.7  
41.4  
23.1  
41.4  
34.7  
8
8
8
8
8
6
8
6
6
30  
35  
45  
50  
35  
35  
8
48D  
60D  
45  
50  
8
60  
60  
6
35  
40  
8
50  
60  
8
50  
60  
8
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
TABLE 15: Electrical Data - (For Multi-Source Power Supply) - Copper Wire - 208/230-3-60  
Max. O.C.P.1 Amps/Type  
Circuit  
Minimum Circuit Ampacity  
75°C Wire Size - AWG  
Heater  
Model  
Models  
1st  
2nd  
3rd  
1st  
2nd  
208/230  
25/30  
3rd  
1st  
2nd  
208/230  
10/10  
8/8  
3rd  
208/230  
32.5/36.0  
41.0/44.9  
208/230  
22.4/25.9  
31.3/36.1  
208/230  
208/230  
35/40  
208/230  
208/230  
8/8  
208/230  
4HK06501825  
4HK16502525  
60D  
45/45  
35/40  
8/8  
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.  
Johnson Controls Unitary Products  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
TABLE 16: Air Handler Air Flow Data  
HIGH/LOW SPEED COOLING AND HEAT PUMP AIRFLOW  
m3/min  
CFM  
24B  
JUMPER SETTINGS  
36C  
24B  
36C  
High  
1088  
830  
948  
716  
854  
612  
637  
531  
542  
462  
474  
461  
Low  
707  
542  
617  
465  
556  
462  
460  
460  
462  
462  
460  
464  
High  
1387  
1151  
1201  
1009  
1086  
953  
Low  
905  
753  
783  
657  
703  
622  
588  
493  
540  
460  
494  
461  
High  
30.8  
23.5  
26.8  
20.3  
24.2  
17.3  
18.0  
15.0  
15.3  
13.1  
13.4  
13.1  
Low  
20.0  
15.3  
17.5  
13.2  
15.7  
13.1  
13.0  
13.0  
13.1  
13.1  
13.0  
13.1  
High  
39.3  
32.6  
34.0  
28.6  
30.7  
27.0  
25.5  
21.3  
23.5  
18.6  
21.3  
16.6  
Low  
25.6  
21.3  
22.2  
18.6  
19.9  
17.6  
16.6  
14.0  
15.3  
13.0  
14.0  
13.1  
COOL Tap  
ADJ Tap  
A
B
A
B
A
C
B
D
C
D
C
D
B
B
A
A
C
B
C
B
A
A
C
C
901  
754  
831  
657  
751  
588  
48D  
60D  
48D  
60D  
JUMPER SETTINGS  
High  
2138  
1759  
2009  
1612  
1773  
1530  
1459  
1359  
1388  
1221  
1244  
1118  
Low  
1442  
1162  
1311  
1052  
1166  
989  
High  
2364  
1962  
2123  
1763  
1905  
1777  
1580  
1596  
1583  
1413  
1412  
1277  
Low  
1545  
1271  
1374  
1146  
1237  
1158  
1021  
1030  
1019  
929  
High  
60.5  
49.8  
56.9  
45.6  
50.2  
43.3  
41.3  
38.5  
39.3  
34.6  
35.2  
31.6  
Low  
40.8  
32.9  
37.1  
29.8  
33.0  
28.0  
26.8  
25.1  
25.6  
22.8  
22.9  
20.2  
High  
66.9  
55.5  
60.1  
49.9  
53.9  
50.3  
44.7  
45.2  
44.8  
40.0  
40.0  
36.2  
Low  
43.7  
36.0  
38.9  
32.4  
35.0  
32.8  
28.9  
29.2  
28.8  
26.3  
26.2  
23.8  
COOL Tap  
ADJ Tap  
A
B
A
B
A
C
B
D
C
D
C
D
B
B
A
A
C
B
C
B
A
A
C
C
947  
886  
904  
806  
808  
926  
715  
841  
HIGH/LOW SPEED ELECTRIC HEAT AIRFLOW  
m3/min  
CFM  
JUMPER SETTINGS  
24B  
48D  
36C  
24B  
36C  
High  
1088  
954  
Low  
828  
714  
614  
523  
High  
1387  
1228  
1151  
923  
Low  
908  
804  
756  
609  
High  
30.8  
27.0  
23.5  
19.2  
Low  
23.4  
20.2  
17.4  
14.8  
High  
39.3  
34.8  
32.6  
26.1  
Low  
25.7  
22.8  
21.4  
17.2  
HEAT Tap  
ADJ Tap  
Any  
A
B
C
D
Any  
829  
Any  
678  
60D  
48D  
60D  
JUMPER SETTINGS  
High  
2111  
1858  
1480  
1250  
Low  
1417  
1252  
985  
High  
2363  
2174  
1868  
1387  
Low  
1488  
1252  
1061  
823  
High  
59.8  
52.6  
41.9  
35.4  
Low  
40.1  
35.4  
27.9  
23.8  
High  
66.9  
61.5  
52.9  
39.3  
Low  
42.1  
35.4  
30.0  
23.3  
HEAT Tap  
ADJ Tap  
Any  
A
B
C
D
Any  
Any  
840  
Any  
1. Airflow at nominal voltage, bottom return at 0.5 external static pressure, tested without filter installed, dry coil conditions.  
2. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure  
3. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static.  
4. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.  
5. Both the COOL and the ADJUST tap must be set to obtain the cooling airflow desired (CFM).  
6. The ADJ tap does not affect the HEAT tap setting.  
7. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65% of high speed).  
8. Dehumidification speed is 85% of jumper selected COOL tap and ADJUST tap.  
9. When operating in both heat pump and electric heat modes, the airflow (CFM) will be per HEAT Tap CFM values only.  
10. At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air  
cleaners. Consult the instructions for the electronic air cleaner for further details.  
11. Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 Flashes is 1200 CFM) – blinks are approximate +/- 10% of actual CFM.  
16  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
536636-UIM-D-1211  
LUBRICATION  
The bearings of the blower motor are permanently lubricated.  
SECTION X: MAINTENANCE  
Filters must be cleaned or replaced when they become dirty. Inspect at  
least once per month. The frequency of cleaning depends upon the  
hours of operation and the local atmospheric conditions. Clean filters  
keep unit efficiency high.  
CONDENSATE DRAINS  
During the cooling season check the condensate drain lines to be sure  
that condensate is flowing from the primary drain but not from the sec-  
ondary drain. If condensate ever flows from the secondary drain the unit  
should be promptly shut off and the condensate pan and drains cleaned  
to insure a free flowing primary drain.  
COIL CLEANING  
If the coil needs to be cleaned or replaced, it should be washed with  
Calgon CalClean (mix one part CalClean to seven parts water). Allow  
solution to remain on coil for 30 minutes before rinsing with clean water.  
Solution should not be permitted to come in contact with painted sur-  
faces.  
Johnson Controls Unitary Products  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SECTION XI: WIRING DIAGRAM  
FIGURE 16: Wiring Diagram  
Subject to change without notice. Published in U.S.A.  
536636-UIM-D-1211  
Copyright © 2011 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 536636-UIM-C-1010  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  
Download from Www.Somanuals.com. All Manuals Search And Download.  

iOptron Camcorder Accessories 7200 User Manual
Jade Range Range JCR 1 User Manual
Jenn Air Printer Accessories AR141 User Manual
Jensen Car Stereo System VM8514 User Manual
Johnson Hardware TV Mount 200 User Manual
JVC Car Speaker CS V6942 User Manual
Kawasaki Drill 691170 User Manual
Kenmore Refrigerator 25344723101 User Manual
Kicker Car Speaker RMB6 User Manual
KitchenAid Washer KAWS700J KAWS750J KAWS850J KAWS855J User Manual