Johnson Controls Furnace GG8SMP User Manual

INSTALLATION MANUAL  
RESIDENTIAL GAS FURNACE MODELS  
TG8S*MP, TGLS*MP, GG8S*MP, GGLS*MP  
(Single Stage Multi-position / Low NOx)  
LIST OF SECTIONS  
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . .19  
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26  
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . .28  
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . .28  
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
LIST OF FIGURES  
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Vertical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Coil Flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Horizontal Right Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Horizontal Left Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
PC Series Upflow Coil Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Horizontal Left or Right application (Right Shown) . . . . . . . . . . . . . . 7  
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Horizontal Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . 8  
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12  
Thermostat Chart - Single Stage AC with  
Single Stage PSC Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Thermostat Chart - Single Stage HP with  
Single Stage PSC Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . .15  
Single Wire Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . .16  
Single Wire Staging Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . .16  
Combustion Air Inducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Combustion Airflow Path Through The Furnace  
Casing to the Burner Compartment . . . . . . . . . . . . . . . . . . . . . . . . .17  
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . .18  
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29  
LIST OF TABLES  
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Coil Projection Dimensions - PC Series Coils . . . . . . . . . . . . . . . . . . 7  
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Recommended Filter Sizes (High Velocity 600 FPM) . . . . . . . . . . . . 9  
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Unconfined Space Minimum Area . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
Gas Rate (CU FT/HR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21  
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Blower Performance CFM - Any Position  
(without filter) - Bottom Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24  
Blower Performance CFM - Any Position  
(without filter) - Left Side Return . . . . . . . . . . . . . . . . . . . . . . . . . . . .25  
These high efficiency, compact units employ induced combustion, reli-  
able hot surface ignition and high heat transfer aluminized tubular heat  
exchangers. The units are factory shipped for installation in upflow or  
horizontal applications and may be converted for downflow applica-  
tions.  
DANGER indicates an imminently hazardous situation, which, if not  
avoided, will result in death or serious injury.  
WARNING indicates a potentially hazardous situation, which, if not  
avoided, could result in death or serious injury.  
CAUTION indicates a potentially hazardous situation, which, if not  
avoided may result in minor or moderate injury. It is also used to  
alert against unsafe practices and hazards involving only property dam-  
age.  
These furnaces are designed for residential installation in a basement,  
closet, alcove, attic, recreation room or garage and are also ideal for  
commercial applications. All units are factory assembled, wired and  
tested to assure safe dependable and economical installation and oper-  
ation.  
These units are Category I listed and may be common vented with  
another gas appliance as allowed by the National Fuel Gas Code.  
Improper installation may create a condition where the operation of  
the product could cause personal injury or property damage.  
Improper installation, adjustment, alteration, service or mainte-  
nance can cause injury or property damage. Failure to carefully  
read and follow all instructions in this manual can result in fur-  
nace malfunction, death, personal injury and/or property dam-  
age. Only a qualified contractor, installer or service agency should  
install this product.  
SECTION I: SAFETY  
This is a safety alert symbol. When you see this symbol on  
labels or in manuals, be alert to the potential for personal  
injury.  
Understand and pay particular attention to the signal words DANGER,  
WARNING, or CAUTION.  
356485-UIM-G-1211  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
COMBUSTION AIR QUALITY  
(LIST OF CONTAMINANTS)  
The furnace requires OUTDOOR AIR for combustion when the furnace  
is located in any of the following environments.  
CODES AND STANDARDS  
Follow all national, local codes and standards in addition to this installa-  
tion manual. The installation must comply with regulations of the serv-  
ing gas supplier, local building, heating, plumbing, and other codes. In  
absence of local codes, the installation must comply with the national  
codes listed below and all authorities having jurisdiction.  
Restricted Environments  
Commercial buildings  
In the United States and Canada, follow all codes and standards for the  
following, using the latest edition available:  
Buildings with indoor pools  
Furnaces installed in laundry rooms  
Furnaces installed in hobby or craft rooms  
Furnaces installed near chemical storage areas  
Chemical exposure  
STEP 1 -Safety  
US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and  
the Installation Standards, Warm Air Heating and Air Conditioning  
Systems ANSI/NFPA 90B  
The furnace requires OUTDOOR AIR for combustion when the furnace  
is located in an area where the furnace is being exposed to the follow-  
ing substances and / or chemicals.  
CANADA: CAN/CGA-B149.1 National Standard of Canada. Natu-  
ral Gas and Propane Installation Codes (NSCNGPIC)  
STEP 2 -General Installation  
Permanent wave solutions  
US: Current edition of the NFGC and NFPA 90B. For copies, con-  
tact the  
Chlorinated waxes and cleaners  
Chlorine based swimming pool chemicals  
Water softening chemicals  
National Fire Protection Association Inc.  
Batterymarch Park  
Quincy, MA 02269  
De-icing salts or chemicals  
or for only the NFGC, contact the  
American Gas Association,  
400 N. Capital, N.W.  
Carbon tetrachloride  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Washington DC 20001  
CANADA: NSCNGPIC. For a copy contact:  
Standard Sales, CSA International  
178 Rexdale Boulevard  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
Etobicoke, (Toronto) Ontario Canada M9W 1RS  
When outdoor air is used for combustion, the combustion air intake duct  
system termination must be located external to the building and in an  
area where there will be no exposure to the substances listed above.  
STEP 3 -Combustion and Ventilation Air  
US: Section 5.3 of the NFGC, air for Combustion and Ventilation  
CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply  
for Appliances  
STEP 4 -Duct Systems  
US and CANADA: Air Conditioning Contractors Association  
The furnace area must not be used as a broom closet or for any  
other storage purposes, as a fire hazard may be created. Never  
store items such as the following on, near or in contact with the fur-  
nace.  
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum  
cleaners or other cleaning tools.  
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors  
Association National Association (SMACNA), or American Soci-  
ety of Heating, Refrigeration, and Air Conditioning Engineers  
(ASHRAE) 1997 Fundamentals Handbook Chapter 32.  
STEP 5 -Acoustical Lining and Fibrous Glass Duct  
US and CANADA: Current edition of SMACNA and NFPA 90B as  
tested by UL Standard 181 for Class I Rigid Air Ducts  
2. Soap powders, bleaches, waxes or other cleaning com-  
pounds; plastic items or containers; gasoline, kerosene, ciga-  
rette lighter fluid, dry cleaning fluids or other volatile fluid.  
3. Paint thinners and other painting compounds.  
STEP 6 -Gas Piping and Gas Pipe Pressure Testing  
US: NFGC; chapters 2, 3, 4, & 9 and National Plumbing Codes  
CANADA: NSCNGPIC Part 5  
4. Paper bags, boxes or other paper products  
STEP 7 -Electrical Connections  
Never operate the furnace with the blower door removed. To  
do so could result in serious personal injury and/or equipment  
damage.  
US: National Electrical Code (NEC) ANSI/NFPA 70  
CANADA: Canadian Electrical Code CSA C22.1  
These instructions cover minimum requirements and conform to exist-  
ing national standards and safety codes. In some instances these  
instructions exceed certain local codes and ordinances, especially  
those who have not kept up with changing residential and non-HUD  
modular home construction practices. These instructions are required  
as a minimum for a safe installation.  
Johnson Controls Unitary Products  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
INSPECTION  
FOR FURNACES INSTALLED IN THE COMMON-  
WEALTH OF MASSACHUSETTS ONLY  
As soon as a unit is received, it should be inspected for possible dam-  
age during transit. If damage is evident, the extent of the damage  
should be noted on the carrier’s freight bill. A separate request for  
inspection by the carrier’s agent should be made in writing. Also, before  
installation, the unit should be checked for screws or bolts which may  
have loosened in transit. There are no shipping or spacer brackets  
which need to be removed from the interior of this unit.  
For all side wall horizontally vented gas fueled equipment installed in  
every dwelling, building or structure used in whole or in part for resi-  
dential purposes, including those owned or operated by the Com-  
monwealth and where the side wall exhaust vent termination is less  
than seven (7) feet above finished grade in the area of the venting,  
including but not limited to decks and porches, the following require-  
ments shall be satisfied:  
FURNACE LOCATION AND CLEARANCES  
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At  
the time of installation of the side wall horizontal vented gas  
fueled equipment, the installing plumber or gasfitter shall  
observe that a hard wired carbon monoxide detector with an  
alarm and battery back-up is installed on the floor level where  
the gas equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery operated or  
hard wired carbon monoxide detector with an alarm is installed  
on each additional level of the dwelling, building or structure  
served by the side wall horizontal vented gas fueled equipment.  
It shall be the responsibility of the property owner to secure the  
services of qualified licensed professionals for the installation of  
hard wired carbon monoxide detectors  
The furnace shall be located using the following guidelines:  
1. Where a minimum amount of air intake/vent piping and elbows will  
be required.  
2. As centralized with the air distribution as possible.  
3. Where adequate combustion air will be available (particularly  
when the appliance is not using outdoor combustion air).  
4. Where it will not interfere with proper air circulation in the confined  
space.  
Installation in freezing temperatures:  
1. Furnace shall be installed in an area where ventilation facilities  
provide for safe limits of ambient temperature under normal oper-  
ating conditions.  
a. In the event that the side wall horizontally vented gas  
fueled equipment is installed in a crawl space or an attic,  
the hard wired carbon monoxide detector with alarm and  
battery back-up may be installed on the next adjacent floor  
level.  
Improper installation in an ambient below 32ºF (0.0° C) could create  
a hazard, resulting in damage, injury or death.  
b. In the event that the requirements of this subdivision can  
not be met at the time of completion of installation, the  
owner shall have a period of thirty (30) days to comply with  
the above requirements; provided, however, that during  
said thirty (30) day period, a battery operated carbon mon-  
oxide detector with an alarm shall be installed.  
2. Do not allow return air temperature to be below 55º F (13° C) for  
extended periods. To do so may cause condensation to occur in  
the main heat exchanger, leading to premature heat exchanger  
failure.  
Clearances for access/service:  
Ample clearances should be provided to permit easy access to the unit.  
The following minimum clearances are recommended:  
2. APPROVED CARBON MONOXIDE DETECTORS. Each car-  
bon monoxide detector as required in accordance with the  
above provisions shall comply with NFPA 720 and be ANSI/UL  
2034 listed and IAS certified.  
1. Twenty-four (24) inches (61 cm) between the front of the furnace  
and an adjacent wall or another appliance, when access is  
required for servicing and cleaning.  
3. SIGNAGE. A metal or plastic identification plate shall be perma-  
nently mounted to the exterior of the building at a minimum  
height of eight (8) feet above grade directly in line with the  
exhaust vent terminal for the horizontally vented gas fueled  
heating appliance or equipment. The sign shall read, in print  
size no less than one-half (1/2) inch in size, "GAS VENT  
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-  
TIONS".  
2. Eighteen (18) inches (46 cm) at the side where access is required  
for passage to the front when servicing or for inspection or  
replacement of flue/vent connections.  
In all cases, accessibility clearances shall take precedence over clear-  
ances for combustible materials where accessibility clearances are  
greater.  
Installation in a residential garage:  
4. INSPECTION. The state or local gas inspector of the side wall  
horizontally vented gas fueled equipment shall not approve the  
installation unless, upon inspection, the inspector observes car-  
bon monoxide detectors and signage installed in accordance  
with the provisions of 248 CMR 5.08(2)(a)1 through 4.  
A gas-fired furnace for installation in a residential garage must be  
installed so the burner(s) and the ignition source are located not less  
than 18 inches (46 cm) above the floor, and the furnace must be located  
or protected to avoid physical damage by vehicles.  
Table 1: Unit Clearances to Combustibles (All Dimensions in Inches, and All Surfaces Identified with the Unit in an Upflow Configuration)  
Top  
Front  
Rear  
Left Side  
In. (cm)  
0 (0.0)  
Right Side  
In. (cm)  
0 (0.0)  
Flue  
Floor/  
Bottom  
Line  
Contact  
Application  
Closet  
Alcove  
Attic  
In. (cm) In. (cm) In. (cm)  
In. (cm)  
Upflow  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
6 (15.2) Combustible  
1 (2.5) Combustible  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
Upflow B-Vent  
Downflow  
0 (0.0)  
0 (0.0)  
1 (25.4)1  
6 (15.2)  
0 (0.0)  
0 (0.0)  
1 (25.4)1  
1 (2.5)  
Downflow B-Vent  
Horizontal  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
1 (2.5)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
0 (0.0)  
Yes  
No  
No  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Yes2  
Yes2  
6 (15.2) Combustible  
1 (2.5) Combustible  
Horizontal B-Vent  
1. Special floor base or air conditioning coil required for use on combustible floor.  
2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building  
joists, studs or framing.  
4
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
On all installations without a coil, a removable access panel is recom-  
mended in the outlet duct such that smoke or reflected light would be  
observable inside the casing to indicate the presence of leaks in the  
heat exchanger. This access cover shall be attached in such a manner  
as to prevent leaks.  
SECTION II: DUCTWORK  
DUCTWORK GENERAL INFORMATION  
The duct system’s design and installation must:  
1. Handle an air volume appropriate for the served space and within  
the operating parameters of the furnace specifications.  
DUCT FLANGES  
2. Be installed in accordance of National Fire Protection Association  
as outlined in NFPA standard 90B (latest editions) or applicable  
national, provincial, state, and local fire and safety codes.  
3. Create a closed duct system. For residential and Non-HUD Modu-  
lar Home installations, when a furnace is installed so that the sup-  
ply ducts carry air circulated by the furnace to areas outside the  
space containing the furnace, the return air shall also be handled  
by a duct(s) sealed to the furnace casing and terminating outside  
the space containing the furnace.  
Four flanges are provided to attach ductwork to the furnace. These  
flanges are rotated down for shipment. In order to use the flanges,  
remove the screw holding an individual flange, rotate the flange so it is  
in the upward position and reinstall the screw then repeat this for all 4  
flanges.  
If the flanges are not used, they must remain in the rotated down posi-  
tion as shipped.  
Factory  
installed  
For duct attachment,  
if needed.  
4. Complete a path for heated or cooled air to circulate through the  
air conditioning and heating equipment and to and from the condi-  
tioned space.  
The cooling coil must be installed in the supply air duct, down-  
stream of the furnace. Cooled air may not be passed over the heat  
exchanger.  
When the furnace is used with a cooling coil, the coil must be installed  
parallel with, or in the supply air side of the furnace to avoid condensa-  
tion in the primary heat exchanger. When a parallel flow arrangement is  
used, dampers or other means used to control airflow must be ade-  
quate to prevent chilled air from entering the furnace. If manually oper-  
ated, the damper must be equipped with means to prevent the furnace  
or the air conditioner from operating unless the damper is in full heat or  
cool position.  
FIGURE 1: Duct Attachment  
DUCTWORK INSTALLATION AND SUPPLY PLENUM  
CONNECTION - UPFLOW/HORIZONTAL  
Attach the supply plenum to the furnace outlet. The use of  
an approved flexible duct connector is recommended on all  
installations. This connection should be sealed to prevent  
air leakage. The sheet metal should be crosshatched to  
eliminate any popping of the sheet metal when the indoor  
fan is energized.  
When replacing an existing furnace, if the existing plenum is not the  
same size as the new furnace then the existing plenum must be  
removed and a new plenum installed that is the proper size for the new  
furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow  
may cause the limit controls not to operate as designed, or the limit con-  
trols may not operate at all.  
FLOOR BASE AND DUCTWORK INSTALLATION -  
DOWNFLOW  
The duct system is a very important part of the installation. If the duct  
system is improperly sized the furnace will not operate properly.  
The ducts attached to the furnace plenum, should be of sufficient size  
so that the furnace operates at the specified external static pressure  
and within the air temperature rise specified on the nameplate.  
Installations on combustible material or directly on any  
floors must use a combustible floor base shown in Figure 8.  
Follow the instructions supplied with the combustible floor  
base accessory. This combustible floor base can be  
replaced with a matching cooling coil, properly sealed to  
prevent leaks. Follow the instructions supplied with the  
cooling coil cabinet for installing the cabinet to the duct con-  
nector. Plug intake and vent pipe holes in bottom panel and  
move grommet to desired vent side exit.  
The minimum plenum height is 12” (30.5 cm). The furnace will not  
operate properly on a shorter plenum height. The minimum recom-  
mended rectangular duct height is 4 inches (10 cm) attached to the  
plenum.  
Downflow Air Conditioning Coil Cabinet  
The furnace should be installed with coil cabinet part number specifi-  
cally intended for downflow application. If a matching cooling coil is  
used, it may be placed directly on the furnace outlet and sealed to pre-  
vent leakage. For details of the coil cabinet dimensions and installation  
requirements, refer to the installation instructions supplied with the coil  
cabinet.  
The duct system must be properly sized to obtain the correct airflow  
for the furnace size that is being installed.  
Refer to Table 6 or the furnace rating plate for the correct rise range  
and static pressures.  
If the ducts are undersized, the result will be high duct static pres-  
sures and/or high temperature rises which can result in a heat  
exchanger OVERHEATING CONDITION. This condition can result  
in premature heat exchanger failure, which can result in personal  
injury, property damage, or death.  
Attach the air conditioning coil cabinet to the duct connector, and then  
position the furnace on top of the coil cabinet. The connection to the fur-  
nace, air conditioning coil cabinet, duct connector, and supply air duct  
must be sealed to prevent air leakage.  
COIL INSTALLATION  
If a matching cooling coil is used, it may be placed directly on the fur-  
nace outlet and sealed to prevent leakage. If thermoplastic evaporator  
‘A’ coil drain pans are to be installed in the upflow/horizontal configura-  
tion, then extra 2” minimum spacing may be needed to ensure against  
drain pan distortion.  
On all installations without a coil, a removable access panel is rec-  
ommended in the outlet duct such that smoke or reflected light  
would be observable inside the casing to indicate the presence of  
leaks in the heat exchanger. This access cover shall be attached in  
such a manner as to prevent leaks.  
Johnson Controls Unitary Products  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
For horizontal left hand applications no conversion is required to an MC  
coil when used with a downflow/horizontal furnace. A mounting plate,  
supplied with every coil should always be installed on the side desig-  
nated as top side. See Figures 4 & 5.  
COIL/FURNACE ASSEMBLY - MC/FC/PC SERIES  
COILS  
Mounting Plate  
Furnace  
FIGURE 5: Horizontal Left Application  
FURNACE ASSEMBLY - PC SERIES COILS  
These upflow coils are designed for installation on top of upflow fur-  
naces only.  
UPFLOW  
DOWNFLOW  
If the coil is used with a furnace of a different size, use a 45° transition  
to allow proper air distribution through the coil.  
FIGURE 2: Vertical Applications  
FURNACE ASSEMBLY - MC & FC SERIES COILS  
These coils are factory shipped for installation in either upflow or down-  
flow applications with no conversion.  
1. Position the coil casing over the furnace opening as shown in Fig-  
ure 6.  
2. Place the ductwork over the coil casing flange and secure.  
Position the coil casing over or under the furnace opening as shown in  
Figure 2 after configuring coil flanges as required see “Coil Flange” sec-  
tion below.  
3. Check for air leakage between the furnace and coil casing and  
seal appropriately.  
COIL FLANGE INSTALLATION  
The coils include removable flanges to allow proper fit up with furnaces  
having various inlet and outlet flange configurations. The two flanges  
are attached to the top of the coil in the factory during production. For  
proper configuration of flanges refer to Figure 3.  
Do not drill any holes or drive any screws into the front duct flange  
on the coil in order to prevent damaging coil tubing. See Figure 6  
C
(Min)  
D
Flexible  
Duct Collar  
Field  
Fabricated  
Ductwork  
Do not drill  
or Screw  
this flange  
FACTORY  
FLANGE  
LOCATION  
(Used for upflow  
or horizontal  
Upflow  
Coil  
right installations)  
ALTERNATE  
FLANGE LOCATION  
Upflow  
Furnace  
(Used for downflow or  
horizontal left installations)  
Alternate  
Drain Location  
Primary  
Drain  
Secondary  
Drain  
FIGURE 3: Coil Flange  
FIGURE 6: PC Series Upflow Coil Installation  
Table 2: Coil Projection Dimensions - PC Series Coils  
FURNACE ASSEMBLY - MC SERIES COILS ONLY  
MC coils are supplied ready to be installed in a horizontal position. A  
horizontal pan is factory installed. MC coils should be installed in all hor-  
izontal applications with the horizontal drain pan side down.  
COIL SIZE  
DIMENSION “C” INCH  
PC18  
PC24  
3-1/2  
4-1/2  
4-1/2  
5-1/2  
6-1/2  
9
Mounting Plate  
PC30, PC32, PC35  
PC42, PC43, PC36, PC37  
PC48  
Furnace  
PC60  
Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6  
FIGURE 4: Horizontal Right Application  
6
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
CRITICAL COIL PROJECTION  
The coil assembly must be located in the duct such that a minimum dis-  
tance is maintained between the top of the coil and the top of the duct.  
Refer to Table 2.  
RESIDENTIAL AND MODULAR HOME UPFLOW  
RETURN PLENUM CONNECTION  
Return air may enter the furnace through the side(s) or bottom depend-  
ing on the type of application. Return air may not be connected into the  
rear panel of the unit.  
COIL / FURNACE ASSEMBLY - HC SERIES COILS  
SIDE RETURN APPLICATION  
These coils are supplied ready to be installed in a right hand position or  
a left hand position. When used in conjunction with a horizontal furnace  
(blow through) application, the coil should be oriented with the opening  
of the “A” coil closest to the furnace. See Figure 7.  
Side return applications pull return air through an opening cut in the  
side of the furnace casing. This furnace is supplied with a bottom block-  
off panel that should be left in place if a side return is to be used. If the  
furnace is to be installed on a flat, solid surface, this bottom panel will  
provide an adequate seal to prevent air leakage through the unused  
bottom opening. However, if the furnace is to be installed on a surface  
that is uneven, or if it is to be installed on blocks or otherwise raised off  
the floor, it will be necessary to seal the edges of the bottom panel  
to the casing using tape or other appropriate gasket material to  
prevent air leakage.  
NOTICE  
Each coil is shipped with an external tie plate that should be used to  
secure the coil to the furnace. It should be installed on the back side  
of the coil using the dimpled pilot holes. See Figure 7.  
BOTTOM RETURN AND ATTIC INSTALLATIONS  
Bottom return applications normally pull return air through a base plat-  
form or return air plenum. Be sure the return platform structure or return  
air plenum is suitable to support the weight of the furnace.  
Use tie plate  
supplied with coil  
The internal bottom panel must be removed for this application.  
Attic installations must meet all minimum clearances to combustibles  
and have floor support with required service accessibility.  
DOWNFLOW APPLICATION  
Gas Furnace  
For downflow applications, the furnace must be turned upside-down so  
that the circulating air enters at the top and exits the furnace at the bot-  
tom. The combustion air inducer must be rotated 90° as shown in Fig-  
ure 22. DO NOT BLOCK COMBUSTION AIR INLET OPENINGS.  
FIGURE 7: Horizontal Left or Right application (Right Shown)  
DOWNFLOW DUCT CONNECTORS  
HORIZONTAL APPLICATION  
All downflow installations must use a suitable duct connector approved  
by the furnace manufacturer for use with this furnace. The duct connec-  
tors are designed to be connected to the rectangular duct under the  
floor and sealed. Refer to the instructions supplied with the duct con-  
nector for proper installation. Refer to the separate accessory parts list  
at the end of these instructions for the approved accessory duct con-  
nectors.  
FIGURE 9: Horizontal Application  
FURNACE  
This furnace may be installed in a horizontal position on either side  
as shown above. It must not be installed on its back.  
WARM AIR PLENUM  
WITH 1” FLANGES  
ATTIC INSTALLATION  
FIBERGLASS  
INSULATION  
Line contact only permissible  
between lines formed by the  
intersection of furnace top  
and two sides and building  
joists, studs or framing  
Supply  
Air  
Vent (Maintain  
required  
clearances to  
combustibles)  
FIBERGLASS TAPE  
UNDER FLANGE  
Filter rack  
must be a minimum  
distance  
of 18” (45.7 cm)  
from the  
furnace  
Sheet metal in  
front of furnace  
combustion air  
Openings is  
Gas Piping  
12”  
Recommended  
COMBUSTIBLE FLOOR  
BASE ACCESSORY  
12”  
30” MIN.  
Work Area  
FIGURE 8: Combustible Floor Base Accessory  
Return  
Air  
Sediment  
Trap  
FIGURE 10: Typical Attic Installation  
Johnson Controls Unitary Products  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
This appliance is certified for line contact when the furnace is installed  
in the horizontal left or right position. The line contact is only permissible  
between lines that are formed by the intersection of the top and two  
sides of the furnace and the building joists, studs or framing. This line  
may be in contact with combustible material. Refer to Figure 10.  
All six suspension points must be level to ensure proper and quiet fur-  
nace operation. When suspending the furnace, use a secure platform  
constructed of plywood or other building materials secured to the floor  
or ceiling joists. Refer to Figure 11 for details and additional information.  
When a furnace is installed in an attic or other insulated space,  
keep all insulating materials at least 12 inches (30.5 cm) away from  
furnace and burner combustion air openings.  
Support  
Rod  
Support  
Angle (x3)  
During installation, doors should remain on the furnace when  
moving or lifting.  
Maintain 6” minimum  
clearance between support  
rods and front of furnace  
When moving or handling this furnace prior to installation, always leave  
the doors on the furnace to provide support and to prevent damage or  
warping of the cabinet. When lifting the furnace, support the ends of the  
furnace rather than lifting by the cabinet flanges at the return air open-  
ings (bottom or sides) or supply air opening.  
FIGURE 11: Typical Suspended Furnace / Crawl Space Installation  
It is acceptable to use the primary heat exchanger tubes as a lifting  
point provided that the tubes are lifted at the front of the heat exchang-  
ers where attached to the vestibule panel. Do not use the top return  
bend of the heat exchangers as lifting points as the tubes may shift out  
of position or their location brackets/baffles.  
During installation, doors should remain on the furnace when  
moving or lifting.  
When moving or handling this furnace prior to installation it is recom-  
mended to leave the doors on the furnace to provide support and to  
prevent damage or warping of the cabinet. When lifting the furnace,  
support the ends of the furnace rather than lifting by the cabinet flanges  
at the return air openings (bottom or sides) or supply air opening.  
SUSPENDED FURNACE / CRAWL SPACE  
INSTALLATION  
The furnace can be hung from floor joists or installed on suitable blocks  
or pads. Blocks or pad installations shall provide adequate height to  
ensure that the unit will not be subject to water damage.  
It is acceptable to use the primary heat exchanger tubes as a lifting  
point provided that the tubes are lifted at the front of the heat exchang-  
ers where attached to the vestibule panel. Do not use the top return  
bend of the heat exchangers as lifting points as the tubes may shift out  
of position or their location brackets/baffles.  
Units may also be suspended from rafters or floor joists using rods, pipe  
angle supports or straps. In all cases, the furnace should be supported  
with rods, straps, or angle supports at three locations to properly sup-  
port the furnace. Place one support at the supply end of the furnace,  
one support located approximately in the center of the furnace near the  
blower shelf, and the third support should be at the return end of the fur-  
nace. Maintain a 6” (15.2 cm) minimum clearance between the front of  
the furnace and the support rods or straps.  
8
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
RIGHT SIDE  
FRONT  
LEFT SIDE  
Vent Connection  
Outlet  
Electrical  
Entry  
Vent  
Connection  
Outlet  
Electrical  
Entry  
Gas Pipe  
Entry  
Gas Pipe  
Entry  
33”  
23”  
Thermostat  
Wiring  
Thermostat  
Wiring  
14”  
A
28.5”  
29.5”  
1”  
1.5”  
4” Diameter  
Vent Connection  
Outlet  
.5”  
24.38”  
.5”  
.5”  
B
B
C
.5”  
20”  
24.25”  
SUPPLY END  
RETURN END  
FIGURE 12: Dimensions  
Table 3: Cabinet and Duct Dimensions  
Approximate  
Operating Weights  
Cabinet Dimensions (Inches)  
Nominal  
CFM (m3/min)  
BTUH (kW)  
Input  
Cabinet  
Size  
A
A (cm)  
36.8  
36.8  
36.8  
44.4  
53.3  
53.3  
44.4  
53.3  
53.3  
53.3  
53.3  
62.2  
B
B (cm)  
34.0  
34.0  
34.0  
41.6  
50.5  
50.5  
41.6  
50.5  
50.5  
50.5  
50.5  
59.4  
C
C (cm)  
26.2  
26.2  
26.2  
29.9  
34.5  
34.5  
29.9  
34.5  
34.5  
40.1  
40.1  
44.4  
Lbs  
89  
40 (11.7)  
60 (17.6)  
60 (17.6)  
80 (23.4)  
80 (23.4)  
80 (23.4)  
100 (29.3)  
100 (29.3)  
100 (29.3)  
120 (35.1)  
120 (35.1)  
130 (38.1)  
800 (22.7)  
1000 (28.3)  
1200 (34.0)  
1200 (34.0)  
1600 (45.3)  
2200 (62.3)  
1200 (34.0)  
1600 (45.3)  
2000 (56.6)  
1600 (45.3)  
2000 (56.6)  
2000 (56.6)  
A
A
A
B
C
C
B
C
C
C
C
D
14 1/2  
14 1/2  
14 1/2  
17 1/2  
21  
13 3/8  
13 3/8  
13 3/8  
16 3/8  
19 7/8  
19 7/8  
16 3/8  
19 7/8  
19 7/8  
19 7/8  
19 7/8  
23 3/8  
10.3  
10.3  
10.3  
11.8  
13.6  
13.6  
11.8  
13.6  
13.6  
15.8  
15.8  
17.5  
91  
94  
103  
114  
119  
108  
118  
122  
123  
129  
135  
21  
17 1/2  
21  
21  
21  
21  
24 1/2  
Table 4: Recommended Filter Sizes (High Velocity 600 FPM)  
SECTION III: FILTERS  
FILTER INSTALLATION  
All applications require the use of a field installed filter. All filters and  
mounting provision must be field supplied.  
CFM  
(m³/min)  
Cabinet  
Size  
Side  
(in)  
Bottom  
(in)  
800 (22.7)  
1000 (28.3)  
1200 (34.0)  
1200 (34.0)  
1600 (45.3)  
1600 (45.3)  
2000 (56.6)  
2200 (62.3)  
2000 (56.6)  
A
A
A
B
B
C
C
C
D
16 x 25  
16 x 25  
14 x 25  
14 x 25  
14 x 25  
16 x 25  
16 x 25  
20 x 25  
20 x 25  
20 x 25  
22 x 25  
Filters must be installed external to the furnace cabinet. DO NOT  
attempt to install filters inside the furnace.  
16 x 25  
16 x 25  
16 x 25  
NOTICE  
Single side return above 1800 CFM is approved as long as the filter  
velocity does not exceed filter manufacturer’s recommendation.  
16 x 25  
(2) 16 x 25  
(2) 16 x 25  
(2) 16 x 25  
1. Air velocity through throwaway type filters may not exceed 300 feet per min-  
ute (91.4 m/min). All velocities over this require the use of high velocity fil-  
ters.  
2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For  
CFM greater than 1800, you may use two side returns or one side and the  
bottom or one return with a transition to allow use of a 20x25 filter.  
Johnson Controls Unitary Products  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
SIDE RETURN  
Locate the “L” shaped corner locators. These indicate the size of the cut-  
out to be made in the furnace side panel. Refer to Figure 13.  
SECTION IV: GAS PIPING  
GAS SAFETY  
DANGER  
An overpressure protection device, such as a pressure regulator,  
must be installed in the gas piping system upstream of the furnace  
and must act to limit the downstream pressure to the gas valve so it  
does not exceed 0.5 PSI (14" w.c. (3.48 kPa). Pressures exceeding  
0.5 PSI (14” w.c. (3.48 kPa) at the gas valve will cause damage to  
the gas valve, resulting in a fire or explosion or cause damage to  
the furnace or some of its components that will result in property  
damage and loss of life.  
Front of  
Furnace  
Side of  
Furnace  
Corner  
Markings  
FIGURE 13: Side Return Cutout Markings  
Outlet  
Pressure  
Port  
Vent Port  
Install the side filter rack following the instructions provided with that  
accessory. If a filter(s) is provided at another location in the return air  
system, the ductwork may be directly attached to the furnace side  
panel.  
Inlet  
Outlet  
Wrench  
Boss  
Inlet  
Pressure  
Port  
Main Regulator  
Adjustment  
On/Off Switch  
(Shown in ON position)  
Some accessories such as electronic air cleaners and pleated  
media may require a larger side opening. Follow the instructions  
supplied with that accessory for side opening requirements. Do not  
cut the opening larger than the dimensions shown in Figure 12.  
FIGURE 14: Gas Valve  
HORIZONTAL APPLICATION  
Horizontal Filters  
Plan your gas supply before determining the correct gas pipe entry.  
Use 90-degree service elbow(s), or short nipples and conventional  
90-degree elbow(s) to enter through the cabinet access holes.  
All filters and mounting provision must be field supplied. All installa-  
tions must have a filter installed.  
GAS PIPING INSTALLATION  
Properly sized wrought iron, approved flexible or steel pipe must be  
used when making gas connections to the unit. If local codes allow the  
use of a flexible gas appliance connection, always use a new listed con-  
nector. Do not use a connector that has previously serviced another gas  
appliance.  
Any branch duct (rectangular or round duct) attached to the plenum  
must attach to the vertical plenum before the filter. The use of straps  
and / or supports is required to support the weight of the external filter  
box.  
Some utility companies or local codes require pipe sizes larger than the  
minimum sizes listed in these instructions and in the codes. The furnace  
rating plate and the instructions in this section specify the type of gas  
approved for this furnace - only use those approved gases. The instal-  
lation of a drip leg and ground union is required. Refer to Figure 15.  
Downflow Filters  
Downflow furnaces typically are installed with the filters located above  
the furnace, extending into the return air plenum or duct. Any branch  
duct (rectangular or round duct) attached to the plenum must attach to  
the vertical plenum above the filter height.  
Filter(s) may be located in the duct system external to the furnace using  
an external duct filter box attached to the furnace plenum or at the end  
of the duct in a return filter grille(s). The use of straps and/or supports is  
required to support the weight of the external filter box.  
NOTE: Ground Union maybe installed inside or outside unit.  
To Gas  
Supply  
Ground  
Union  
To Gas  
Supply  
External  
Manual  
Shut-off  
Valve  
To Gas  
Supply  
To Gas  
Supply  
External  
Manual  
Shut-off  
Valve  
Gas  
Valve  
To Gas  
Supply  
Ground  
Union  
Ground  
Union  
Drip Leg  
External  
Ground  
Union  
Manual  
Shut-off  
Valve  
Gas  
Valve  
Gas  
Pipe  
Gas  
Valve  
Drip  
Leg  
Drip  
Leg  
Drip  
Leg  
Drip  
Leg  
To Gas  
Supply  
Gas Pipe  
Ground  
Union  
Upflow  
Downflow  
Horizontal  
Drip Leg  
Configuration  
Configuration  
Configuration  
FIGURE 15: Gas Piping  
10  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
GAS ORIFICE CONVERSION FOR PROPANE (LP)  
This furnace is constructed at the factory for natural gas-fired operation,  
but may be converted to operate on propane (LP) gas by using a fac-  
tory-supplied LP conversion kit. Follow the instructions supplied with  
the LP kit.  
An accessible manual shutoff valve must be installed upstream of  
the furnace gas controls and within 6 feet (1.8 m) of the furnace.  
The furnace must be isolated from the gas supply piping system by  
closing its individual external manual shutoff valve during any pressure  
testing of the gas supply piping system at pressures equal to or less  
than 1/2 psig (3.5 kPa).  
LoNOx furnaces requiring propane (LP) gas must have the LoNOx  
screens removed prior to installation and operation. See propane  
instructions.  
HIGH ALTITUDE GAS ORIFICE CONVERSION  
This furnace is constructed at the factory for natural gas-fired operation  
at 0 –5,000 feet (0-m – 1,524 m) above sea level.  
The gas valve body is a very thin casting that cannot take any  
external pressure. Never apply a pipe wrench to the body of the gas  
valve when installing piping. A wrench must be placed on the octa-  
gon hub located on the gas inlet side of the valve. Placing a wrench  
to the body of the gas valve will damage the valve causing improper  
operation and/or the valve to leak.  
The manifold pressure must be changed in order to maintain proper  
and safe operation when the furnace is installed in a location where the  
altitude is greater than 5,000 feet (1,524 m) above sea level. Refer to  
Table 5 for proper manifold pressure settings.  
Gas piping may be connected from either side of the furnace using any  
of the gas pipe entry on both sides of the furnace. Refer to Figure 12.  
HIGH ALTITUDE PRESSURE SWITCH CONVERSION  
For installation where the altitude is less than 5,000 feet (1,524m), it is  
not required that the pressure switch be changed unless you are in an  
area subject to low pressure inversions.  
Table 5: Nominal Manifold Pressure  
Manifold Pressures (in wc)  
Manifold Pressures (kpa)  
Altitude (feet)  
Altitude (m)  
0-7999  
3.5  
8000-8999  
3.5  
9000-9999  
3.5  
0-2437  
0.87  
0.87  
0.87  
0.87  
0.87  
0.87  
0.80  
2.44  
2438-2742  
0.87  
2743-3048  
0.87  
800  
850  
29.8  
31.7  
3.5  
3.5  
3.5  
0.87  
0.87  
900  
3.5  
3.5  
3.5  
33.5  
0.87  
0.87  
950  
3.5  
3.5  
3.3  
35.4  
0.87  
0.81  
1000  
1050  
1100  
3.5  
3.2  
2.9  
37.3  
0.80  
0.73  
3.5  
2.9  
2.7  
39.1  
0.73  
0.67  
3.2  
2.7  
2.4  
41.0  
0.66  
0.61  
2500 (LP)  
9.8  
8.2  
7.5  
93.2 (LP)  
2.03  
1.86  
DANGER  
PROPANE AND HIGH ALTITUDE CONVERSION KITS  
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed.  
Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-  
pane (LP) gas. Do not use this furnace with butane gas.  
Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat  
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death.  
High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application.  
An authorized distributor or dealer must make all gas conversions.  
In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.  
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed.  
Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames,  
causing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage  
and/or death.  
Johnson Controls Unitary Products  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
SECTION V: ELECTRICAL POWER  
ELECTRICAL POWER CONNECTIONS  
Use copper conductors only.  
Field wiring to the unit must be grounded. Electric wires that are field  
installed shall conform to the temperature limitation for 63°F (35°C) rise  
wire when installed in accordance with instructions. Refer to Table 6 in  
these instructions for specific furnace electrical data.  
Table 6: Ratings & Physical / Electrical Data  
Max.  
Outlet  
Air Temp  
Nominal  
Airflow  
Air Temp.  
Rise  
Input  
MB  
Output  
MB  
Blower  
Blower  
Max  
Over-Current  
Protect  
Total  
Unit  
Amps  
Min. wire Size  
(awg) @ 75 ft  
one way  
AFU  
E
Size  
m3/  
Amp  
s
kW  
kW CFM  
°F  
°C  
°F  
°C  
HP  
H
H
min  
22.7  
28.3  
34.0  
34.0  
45.3  
62.3  
34.0  
45.3  
56.6  
45.3  
56.6  
56.6  
40 11.7 32  
9.4 800  
80.0 25-55 14-31 155 68.3 1/5  
80.0 25-55 14-31 155 68.3 1/3  
80.0 30-60 17-33 170 76.7 1/3  
80.0 35-65 19-36 165 73.9 1/3  
80.0 25-55 14-31 155 68.3 1/2  
2.1  
3.8  
4.8  
4.8  
9 x 8  
9 x 8  
10  
10  
10  
10  
15  
20  
10  
15  
20  
15  
20  
20  
4.5  
6.0  
14  
14  
14  
14  
14  
12  
14  
14  
12  
14  
12  
12  
60 17.6 48 14.1 1000  
60 17.6 48 14.1 1200  
80 23.5 64 18.8 1200  
80 23.5 64 18.8 1600  
80 23.5 64 18.8 2200  
100 29.3 80 23.4 1200  
100 29.3 80 23.4 1600  
100 29.3 80 23.4 2000  
120 33.7 96 26.9 1600  
120 33.7 96 26.9 2000  
130 38.1 104 30.5 2000  
11 x 8  
11 x 8  
7.0  
7.5  
7.5 11 x 10  
14.5 11 x 11  
10.0  
16.0  
7.5  
80.0 25-55 14-31 155 68.3  
1
80.0 40-70 22-39 170 76.7 1/3  
80.0 35-65 19-36 165 73.9 1/2  
4.8  
9 x 8  
7.5 11 x 10  
14.5 11 x 11  
7.5 11 x 10  
14.5 11 x 11  
14.5 11 x 11  
10.0  
17.0  
10.0  
17.0  
17.0  
80.0 25-55 14-31 155 68.3  
1
80.0 40-70 22-39 170 76.7 1/2  
80.0 30-60 17-33 160 71.1  
80.0 35-65 19-36 165 73.9  
1
1
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.  
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.  
The furnace shall be installed so that the electrical components are protected from water.  
3. The furnace's control system requires correct polarity of the power  
supply and a proper ground connection. Refer to Figure 16  
SUPPLY VOLTAGE CONNECTIONS  
Junction  
Box  
The power connection leads and wiring box may be relocated to the  
left side of the furnace. Remove the screws and cut wire tie holding  
excess wiring. Reposition on the left side of the furnace and fasten  
using holes provided.  
Connect ground  
lead to screw  
Electrical Entry  
BLK  
LOW VOLTAGE CONTROL WIRING CONNECTIONS  
L1-Hot  
Neutral  
WHT  
Install the field-supplied thermostat by following the instructions that  
come with the thermostat. With the thermostat set in the OFF position  
and the main electrical source disconnected, connect the thermostat  
wiring from the wiring connections on the thermostat to the terminal  
board on the ignition module, as shown in Figures 17 or 18. Electronic  
thermostats may require the common wire to be connected. Apply  
strain relief to thermostat wires passing through cabinet. If air condition-  
ing equipment is installed, use thermostat wiring to connect the Y and C  
terminals on the furnace control board to the proper wires on the con-  
densing unit (unit outside).  
FIGURE 16: Electrical Wiring  
1. Provide a power supply separate from all other circuits. Install  
overcurrent protection and disconnect switch per local/national  
electrical codes. The switch should be close to the unit for conve-  
nience in servicing. With the disconnect or fused switch in the OFF  
position, check all wiring against the unit wiring label. Refer to the  
wiring diagram in this instruction.  
2. Remove the screws retaining the wiring box cover. Route the  
power wiring through the opening in the unit into the junction box  
with a conduit connector or other proper connection. In the junc-  
tion box there will be 3 wires, a Black Wire, a White Wire. Connect  
the power supply as shown on the unit-wiring label on the inside of  
the blower compartment door or the wiring schematic in this sec-  
tion. The black furnace lead must be connected to the L1 (hot)  
wire from the power supply. The white furnace screw must be con-  
nected to neutral. Connect the power supply ground to the green  
screw (equipment ground) An alternate wiring method is to use a  
field provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the out-  
side of the furnace. Route the furnace leads into the box using a  
protective bushing where the wires pass through the furnace  
panel. After making the wiring connections replace the wiring box  
cover and screws. Refer to Figure 16.  
Set the heat anticipator in the room thermostat to 0.4 amps. Setting  
it lower will cause short cycles. Setting it higher will cause the room  
temperature to exceed the set points.  
Some electronic thermostats do not have adjustable heat anticipa-  
tors. They should be set to six cycles per hour. Follow the thermo-  
stat manufacturer's instructions.  
The 24-volt, 40 VA transformer is sized for the furnace components  
only, and should not be connected to power auxiliary devices such as  
humidifiers, air cleaners, etc. The transformer may provide power for an  
air conditioning unit contactor.  
12  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Product Catalog Section.  
AC 5D  
Single Stage Air Conditioner – Single Stage PSC Furnace  
ID MODELS  
G*(8/9)S  
G*9F  
GF(8/9)  
LF8  
L(Y/M)8S  
G8C  
(G,T)G(8/9)S  
(G/T)GLS  
THERMOSTAT  
SINGLE STAGE  
SINGLE STAGE  
AIR  
CONDITIONER  
*PP11C70224  
PSC  
FURNACE  
SINGLE STAGE PSC  
FURNACE  
SINGLE STAGE  
1
AIR CONDITIONER  
C
C
24 – Volt Common  
24 – Volt Common  
Y
Y/Y2  
Y
Full Stage Compressor  
Full Stage Compressor  
CompressorContactor  
RH  
R
24 – Volt Hot  
(Heat XFMR)  
24 – Volt Hot  
G
Fan  
G
Fan  
W
Full Stage Heat  
RC  
24 – Volt Hot  
(Cool XFMR)  
W
Full Stage Heat  
24VAC Humidifier  
(Optional)  
HM1  
Humidistat  
Clipping Jumper W914 for  
electric heat on thermostat  
is not necessary  
Other Part Numbers:  
1
SAP  
=
Legacy  
265901 = 031-09166  
FIGURE 17: Thermostat Chart - Single Stage AC with Single Stage PSC Furnaces  
Johnson Controls Unitary Products  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
HP 2C  
Single Stage Heat Pump – Single Stage PSC Furnace  
ID MODELS  
OD MODELS  
G*(8/9)S  
G*9F  
GF(8/9)  
LF8  
E*R*  
*RHS  
HP*  
E*ZD  
E*B*  
L(Y/M)8S  
G8C  
(G,T)G(8/9)S  
(G/T)GLS  
*HGD  
THERMOSTAT  
THERMOSTAT  
THERMOSTAT  
*BP21H50124  
*BN21H00124  
*DP21H40124  
*DN21H00124  
SINGLE STAGE  
SINGLE STAGE  
HEAT PUMP  
*DN22U00124  
*DP32H70124  
PSC  
FURNACE  
SINGLE STAGE PSC  
FURNACE  
2
DEMAND DEFROST  
CONTROL  
1
C
C
C
24 – Volt Common  
24 – Volt Common  
24 – Volt Common  
Y1  
Y/Y2  
Y
First Stage Compressor  
Full Stage Compressor  
Compressor  
R
R
R
24 – Volt Hot  
24 – Volt Hot  
24 – Volt Hot  
G
Fan  
G
Fan  
E
W
W1/66(out)  
Heat  
Emergency Heat  
Full Stage Heat  
W2  
N/A  
N/A  
Third Stage Heat  
O
O
Reversing Valve  
Energized in Cool  
Reversing Valve  
Energized in Cool  
L
X/L  
Malfunction Light  
Malfunction Light  
Y2  
Second Stage Compressor  
W1  
W
Second Stage Aux. Heat  
Auxiliary Heat  
3
External Humidistat  
(Optional)  
Open on Humidity Rise  
24VAC Humidifier  
(Optional)  
Step 1 of Thermostat  
Installer / Configuration  
Menu must be set to  
Heat Pump 1  
Step 9 of Thermostat  
Installer / Configuration  
Menu must be set to  
Pump OFF  
Other Part Numbers:  
Part Numbers:  
3
1
Part Number:  
S1-2HU16700124  
2
SAP  
=
Legacy  
SAP  
=
Legacy  
265901 = 031-09166  
67297 = 031-01975  
FIGURE 18: Thermostat Chart - Single Stage HP with Single Stage PSC Furnaces  
14  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
ACCESSORY CONNECTIONS  
Vent Pipe  
The furnace control will allow power-switching control of various acces-  
sories.  
ELECTRONIC AIR CLEANER CONNECTION  
Two 1/4” (0.64 cm) spade terminals (EAC and NEUTRAL) for electronic  
air cleaner connections are located on the control board. The terminals  
provide 115 VAC (1.0 amp maximum) during circulating blower opera-  
tion.  
Gas Supply  
(Both sides)  
Electrical  
Supply  
HUMIDIFIER CONNECTION  
Two 1/4” (0.64 cm) spade terminals (HUM and NEUTRAL) for humidi-  
fier connections are located on the control board. The terminals provide  
115 VAC (1.0 amp maximum) during heating system operation.  
1 Coil for  
Each Furnace  
Supply  
Air  
A mounting hole is provided on the control panel next to the furnace  
control board for mounting a humidifier transformer if required.  
FIGURE 19: Typical Twinned Furnace Application  
SECTION VI: TWINNING AND STAGING  
In applications where more heating capacity or more airflow capacity is  
needed than what one furnace can deliver, twinning can be used to  
make two furnaces operate in tandem. When two furnaces are installed  
using the same duct system, it is very important that the two furnace cir-  
culating air blowers operate in unison. If one blower starts before the  
second blower, the duct system will become pressurized and the blower  
on the second furnace will turn backwards causing the second furnace  
to overheat, resulting in damage to the furnace. Twinning is used to  
make two furnaces operate in tandem, using one duct system, one  
room thermostat and causing both furnaces to turn on and off simulta-  
neously.  
When two furnaces are twinned, typical system total airflow will be  
approximately 85% of additive individual furnaces, i.e., two 2000  
CFM units will yield a total 3400 CFM.  
If a return duct is connected to only one furnace (with a connection  
between the two furnaces) an imbalance in the airflow will occur  
and the furnace furthest from the return plenum will overheat.  
GAS PIPING  
Before installing the relay and wiring, disconnect electrical power to  
both furnaces. Failure to cut power could result in electrical shock  
or equipment damage.  
Furnace gas supplies must be provided as specified with these instruc-  
tions. Since the furnaces are side by side, with no space between, gas  
supplies must enter on the right and left respectively. All gas piping  
must be in accordance with the national fuel gas code, ANSI Z223.1,  
latest edition, and/or all local code or utility requirements.  
TWINNING  
In applications where more heating capacity or more airflow capacity is  
needed than what one furnace can deliver, twinning can be used to  
make two furnaces operate in tandem, using one duct system and one  
room thermostat. When one duct system is used for two furnaces, it is  
necessary that the two blowers operate in unison. The twinning function  
of the board in this furnace ensures that both blowers turn on and off  
simultaneously, and operate on the same blower speed.  
The relay must not be installed in any location where it could be  
exposed to water. If the relay has been exposed to water in any  
way, it must not be used.  
TWINNING DUCT SYSTEM  
Twinned furnaces must only be applied on a common duct system. A  
single air supply plenum must be used for both furnaces and coil(s).  
Separate plenums and supply ducts systems cannot be utilized. A sin-  
gle return air plenum, common to both furnaces must be used. It is sug-  
gested that a return platform be utilized, with bottom air entrance into  
each furnace. If a side entrance returns system is used, the common  
return duct must be divided equally so as to supply each furnace with  
an equal amount of return air.  
Single-Wire Twinning  
The control in the furnace has the single-wire twinning feature. With this  
feature, a single wire is connected between the TWIN terminal on one  
furnace board to the TWIN terminal on the second furnace board. The  
board then communicates the blower status from one furnace to the  
other along this wire. This communication makes the second furnace  
blower come on at the same time, and on the same speed, as the first  
furnace blower. To ensure stable communication, the common terminal  
of each control must be connected.  
Both furnaces must be identical models in both heating capacity and  
CFM capacity. Both furnaces must be operated on the same motor  
speed tap. See typical application, Figure 19.  
If furnace staging is desired with two single stage furnaces on a com-  
mon duct, where the gas burner on the first furnace operates on W1  
and the gas burner on the second furnace operates on W2, then the  
use of an air-mixing device in the plenum to mix the air from both fur-  
naces is strongly recommended. The mixing device must be installed  
before any ducts that supply air to occupied spaces. Twinning causes  
both indoor fans to operate simultaneously. If a mixing device is not  
used, any ducts that are connected down stream from the furnace that  
operates on W2, will be supplying cold air in the Heating mode to the  
occupied spaces unless W2 is energized.  
Single-Wire Twinning Instructions  
Connect the control wiring as shown in Figure 21.  
1. Connect the low voltage wiring from the wall thermostat to the ter-  
minal strip on the control board of Furnace #1.  
2. Connect a wire from the TWIN terminal of Furnace #1 to the TWIN  
terminal of Furnace #2.  
3. Install a separate 24V relay as shown in the diagram below. Use of  
this relay is required, as it ensures that the transformers of the two  
furnaces are isolated, thus preventing the possibility of any safety  
devices being bypassed.  
4. Connect the common wires of furnace #1 to the common terminal  
of furnace #2.  
Johnson Controls Unitary Products  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Single-Wire Twinning Operation  
Single-Wire Staging Operation  
Heating - On a call for heat (W signal) from the wall thermostat, both  
furnaces will start the ignition sequence and the burners on both fur-  
naces will light. About thirty seconds after the burners light, the blowers  
on both furnaces will come on in heating speed. When the thermostat is  
satisfied, the burners will all shut off and, after the selected blower off  
delay time, both blowers will shut off at the same time. The twinning  
control ensures that both blowers come on and shut off at the same  
time.  
Cooling - On a call for cooling (Y signal) from the wall thermostat, both  
furnace blowers will come on at the same time in cooling speed. When  
the thermostat is satisfied, both blowers will stay on for 60 seconds,  
then will shut off at the same time.  
Heating - On a call for first-stage heat (W1 signal) from the wall thermo-  
stat, Furnace #1 will start the ignition sequence and the burners will  
light. About thirty seconds after the burners light, the blowers on both  
furnaces will come on in heating speed. When the thermostat is satis-  
fied, the burners will shut off and, after the selected blower off delay  
time, both blowers will shut off at the same time. On a call for second  
stage of heat, the burners of Furnace #2 will also light and both blowers  
will run. The twinning control ensures that both blowers come on and  
shut off at the same time.  
Cooling - On a call for cooling (Y signal) from the wall thermostat, both  
furnace blowers will come on at the same time. When the thermostat is  
satisfied, both blowers will stay on for 60 seconds, then will shut off at  
the same time.  
Continuous Fan - On a thermostat call for continuous fan (G signal),  
both furnace blowers will come on at the same time in cooling speed  
and will stay on until the G signal is removed.  
Continuous Fan - On a thermostat call for continuous fan (G signal),  
both furnace blowers will come on at the same time in cooling speed  
and will stay on until the G signal is removed.  
FURNACE 1  
CONTROL BOARD  
FURNACE 2  
CONTROL BOARD  
FURNACE 1  
CONTROL BOARD  
FURNACE 2  
CONTROL BOARD  
W
G
C
W
G
C
W
G
C
W
G
C
R
Y
TWIN  
R TWIN  
Y
ISOLATION  
RELAY  
TWIN  
R
R
Y
TWIN  
Y
ISOLATION  
RELAY  
W
G
R
Y
TO A/C  
WALL THERMOSTAT  
FIGURE 20: Single Wire Twinning Wiring Diagram  
TO A/C  
W1  
G
R
Y
W2  
WALL THERMOSTAT  
STAGING  
FIGURE 21: Single Wire Staging Wiring Diagram  
This control can also be used along with a two-stage wall thermostat to  
stage two twinned furnaces, making them operate like a single two-  
stage furnace. This allows only one furnace to supply heat during times  
when the heat output from one furnace is sufficient to satisfy the  
demand. When one duct system is used for two furnaces, it is neces-  
sary that the two blowers operate in unison. The twinning function of  
this board ensures that both blowers turn on and off simultaneously,  
and operate on the same blower speed. Even when only one furnace is  
supplying heat, both furnace blowers must run.  
SECTION VII: VENT SYSTEM  
VENT CONNECTIONS  
All models are provided with a flue transition that is sized for 4” diame-  
ter vent connections. If a larger size vent connector is required, that  
connection must be installed external to the furnace. Figure 22 shows  
the furnace as it is shipped from the factory. To convert to a horizontal  
or downflow position, remove the four screws that secure the inducer  
assembly and rotate 90° being careful not to damage the gasket. Rein-  
stall screws. Remove cap from appropriate vent outlet location on the  
cabinet, cut insulation in cabinet to same size as the hole provided and  
reinstall cap in the hole in the top panel.  
Single-Wire Staging  
The single-wire twinning feature of this board can also be used for stag-  
ing of two furnaces. With this feature, a single wire is connected  
between the TWIN terminal on one furnace board to the TWIN terminal  
on the second furnace board. The board then communicates the blower  
status from one furnace to the other along this wire. This communica-  
tion makes the second furnace blower come on at the same time, and  
on the same speed, as the first furnace blower. To ensure stable com-  
munication, the common terminal of each control must be connected.  
In downflow applications, do not block the combustion air inlet. The  
furnace must be installed on a coil cabinet or subbase to allow com-  
bustion air to enter the burner compartment.  
Single-Wire Staging Instructions  
Connect the control wiring as shown in Figure 22.  
COMBUSTION AIR INDUCER  
90°  
90°  
1. Connect the low voltage wiring from the wall thermostat to the ter-  
minal strip on the control board of Furnace #1. For staging applica-  
tions, the wire from thermostat W1 is connected to the W  
connection on the board on Furnace #1. The wire from thermostat  
W2 is connected to Furnace #2 through a separate relay, as  
described below.  
Mounting Screw  
(Remove)  
Pressure Switch  
Tube Routing  
2. Connect a wire from the TWIN terminal of Furnace #1 to the TWIN  
terminal of Furnace #2.  
Flue Transition  
(Do Not Remove)  
3. Install a separate 24V relay as shown in the diagram below. Use of  
this relay is required, as it ensures that the transformers of the two  
furnaces are isolated, thus preventing the possibility of any safety  
devices being bypassed.  
Pressure  
Switch  
Mounting Screw  
(Remove)  
4. Connect the common between furnace #1 and furnace #2.  
FIGURE 22: Combustion Air Inducer  
16  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
CATEGORY 1 - 450 F. MAX. VENT TEMP.  
Combustion Air  
The venting system must be installed in accordance with Section 5.3,  
Air for Combustion and Ventilation, of the National Fuel Gas Code  
Z223.1/NFPA 54 (latest edition), or Sections 7.2, 7.3 or 7.4 of CSA  
B149.1, National Gas and Propane Codes (latest edition) or applicable  
provisions of the local building code and these instructions.  
The furnace shall be connected to any type of B, BW or L vent connec-  
tor, and shall be connected to a factory-built or masonry chimney. The  
furnace shall not be connected to a chimney flue serving a sepa-  
rate appliance designed to burn solid fuel.  
It is recommended that the appliance is installed in a location where the  
space temperature is 32 °F (0°C) or higher. If the appliance is installed  
in a location where the ambient temperature is below 32 °F (0°C), the  
combustion byproducts could condense causing damage to the appli-  
ance heat exchanger.  
FIGURE 23: Combustion Airflow Path Through The Furnace Casing to  
This appliance may be common vented with another gas appliance for  
residential installations as allowed by the codes and standards listed in  
these instructions.  
the Burner Compartment  
Non-HUD approved Modular Homes must be vented with an approved  
roof jack and may not be common vented with other appliances.  
This type of installation requires that the supply air to the appli-  
ance(s) be of a sufficient amount to support all of the appliance(s)  
in the area. Operation of a mechanical exhaust, such as an exhaust  
fan, kitchen ventilation system, clothes dryer or fireplace may cre-  
ate conditions requiring special attention to avoid unsatisfactory  
operation of gas appliances. A venting problem or a lack of supply  
air will result in a hazardous condition, which can cause the appli-  
ance to soot and generate dangerous levels of CARBON MONOX-  
IDE, which can lead to serious injury, property damage and / or  
death.  
VENTING  
Category I venting consists of vertically venting one or more appliances  
in B-vent or masonry chimney (as allowed), using single wall metal pipe  
or B-vent connectors. Type B-vent system extends in a general vertical  
direction and does not contain offsets exceeding 45°. A vent system  
having not more than one 60° offset is permitted.  
VENTING INTO AN EXISTING CHIMNEY  
For Category I installations, the furnace shall be connected to a factory  
built chimney or vent complying with a recognized standard, or a  
masonry or concrete chimney lined with a material acceptable to the  
authority having jurisdiction. Venting into an unlined masonry chimney  
or concrete chimney is prohibited.  
An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/  
hr (0.2928 kW) input rating for all of the appliances installed in that  
area.  
Rooms communicating directly with the space containing the appli-  
ances are considered part of the unconfined space, if doors are fur-  
nished with openings or louvers.  
Where use of an existing chimney is unavoidable, the following rules  
must be followed:  
1. The masonry chimney must be built and installed in accordance  
with nationally recognized building codes or standards and must  
be lined with approved fire clay tile flue liners or other approved  
liner material that will resist corrosion, softening, or cracking from  
flue gases. THIS FURNACE IS NOT TO BE VENTED INTO AN  
UNLINED MASONRY CHIMNEY.  
A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000  
Btu/hr (0.2928 kW) input rating for all of the appliances installed in that  
area. The following must be considered to obtain proper air for combus-  
tion and ventilation in confined spaces.  
Combustion Air Source From Outdoors  
2. This furnace must be vented into a fire clay tile lined masonry  
chimney only if a source of dilution air is provided, such as by com-  
mon venting with a draft hood equipped water heater. If no source  
of dilution air is available, Type B vent must be used, or masonry  
chimney vent kit 1CK0603 or 1CK0604 must be used. Refer to the  
instructions with the kit to properly apply these masonry chimney  
kits.  
The blocking effects of louvers, grilles and screens must be given con-  
sideration in calculating free area. If the free area of a specific louver or  
grille is not known, refer to Table 7, to estimate free area.  
Table 7: Estimated Free Area  
Wood or Metal  
Louvers or Grilles  
Wood 20-25%*  
Metal 60-70% *  
3. The chimney must extend at least 3 ft (0.91 m) above the highest  
point where it passes through a roof of a building and at least two  
feet higher than any portion of the building with a horizontal dis-  
tance of ten feet.  
1/4” (0.635 cm)  
mesh or larger 100%  
Screens+  
* Do not use less than 1/4”(0.635 cm) mesh  
+ Free area of louvers and grille varies widely; the installer should follow  
louver or grille manufacturer’s instructions.  
4. The chimney must extend at least 5 ft (1.5 m) above the highest  
equipment draft hood or flue collar.  
Dampers, Louvers and Grilles (Canada Only)  
FAN-ASSISTED COMBUSTION SYSTEM  
This appliance is equipped with an integral mechanical means to either  
draw products of combustion through the heat exchanger.  
1. The free area of a supply air opening shall be calculated by sub-  
tracting the blockage area of all fixed louvers grilles or screens  
from the gross area of the opening.  
2. Apertures in a fixed louver, a grille, or screen shall have no dimen-  
sion smaller than 0.25” (0.64 cm).  
Ambient Combustion Air Supply  
This type installation will draw the air required for combustion from  
within the space surrounding the appliance and from areas or rooms  
adjacent to the space surrounding the appliance. This may be from  
within the space in a non-confined location or it may be brought into the  
furnace area from outdoors through permanent openings or ducts. A  
single, properly sized pipe from the furnace vent connector to the out-  
doors must be provided. Combustion air is brought into the furnace  
through the unit top panel opening.  
3. A manually operated damper or manually adjustable louvers are  
not permitted for use.  
4. A automatically operated damper or automatically adjustable lou-  
vers shall be interlocked so that the main burner cannot operate  
unless either the damper or the louver is in the fully open position.  
Johnson Controls Unitary Products  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Table 9: Free Area  
Minimum Free Area Required for Each Opening  
Vertical Duct or  
BTUH Input  
Rating  
When a Category I furnace is removed or replaced, the original  
venting system may no longer be correctly sized to properly vent  
the attached appliances.  
Horizontal Duct  
Round Duct  
Opening to Outside  
(4,000 BTUH)  
(2,000 BTUH)  
(4,000 BTUH)  
20 in2 (129 cm2)  
30 in2 (193 cm2)  
40 in2 (258 cm2)  
50 in2 (322 cm2)  
60 in2 (387 cm2)  
65 in2 (419 cm2)  
10 in2 (64 cm2)  
15 in2 (97 cm2)  
20 in2 (129 cm2)  
25 in2 (161 cm2)  
30 in2 (193 cm2)  
33 in2 (213 cm2)  
An improperly sized vent system can cause CARBON MONOXIDE  
to spill into the living space causing personal injury, and or death.  
40,000  
60,000  
4” (10 cm)  
5” (13 cm)  
5” (13 cm)  
6” (15 cm)  
7” (18 cm)  
7” (18 cm)  
80,000  
Table 8: Unconfined Space Minimum Area  
100,000  
120,000  
130,000  
Minimum Free Area  
BTUH Input Rating  
Required for Each Opening  
40 in2 (258 cm2)  
40,000  
60 in2 (387 cm2)  
60,000  
EXAMPLE: Determining Free Area.  
Appliance 1 Appliance  
80 in2 (516 cm2)  
2 Total Input  
80,000  
100,000 + 30,000 = (130,000 4,000) = 32.5 Sq. In. Vertical  
Appliance 1 Appliance 2 Total Input  
100,000 + 30,000 = (130,000 2,000) = 65 Sq. In. Horizontal  
100 in2 (645 cm2)  
100,000  
120 in2 (742 cm2)  
120,000  
130 in2 (838 cm2)  
130,000  
Gas  
Vent  
Gas  
Vent  
Gas  
Vent  
Gable  
Vent  
Gable  
Vent  
Ventilated  
Attic  
Ventilated  
Attic  
Optional  
Inlet (a)  
Top Above  
Insulation  
Top Above  
Insulation  
Outlet  
Air (a)  
Soffit  
Vent  
Soffit  
Vent  
Outlet  
Air (b)  
Outlet  
Air (a)  
Gas  
Water  
Heater  
Gas  
Water  
Heater  
Gas  
Water  
Heater  
Inlet  
Air (b)  
Inlet  
Air (b)  
Inlet  
Air (a)  
Inlet  
Air (a)  
Ventilated  
Crawl Space  
FIGURE 24: Outside and Ambient Combustion Air  
2. One permanent openings, commencing within 12 in (30.5 mm) of  
the top of the enclosure shall be permitted where the equipment  
has clearances of at least 1 in (2.54 cm) from the sides and back  
and 6 in (15.24 cm) from the front of the appliance. The opening  
shall communicate directly with the outdoors and shall have a min-  
imum free area of:  
Air Supply Openings and Ducts  
1. An opening may be used in lieu of a duct to provide the outside air  
supply to an appliance unless otherwise permitted by the authority  
having jurisdiction. The opening shall be located within 12” (30.5  
cm) horizontally from, the burner level of the appliance. Refer to  
“COMBUSTION AIR SOURCE FROM OUTDOORS and VENT  
AND SUPPLY AIR SAFETY CHECK” in these instructions for  
additional information and safety check procedure.  
a. 1 square in per 3000 Btu per hour (6.45 cm3 per 0.879 kW) of  
the total input rating of all equipment located in the enclosure.  
b. Not less than the sum of all vent connectors in the confined  
space.  
2. The duct shall be either metal, or a material meeting the class 1  
requirements of CAN4-S110 Standard for Air Ducts.  
3. The duct shall be least the same cross-sectional area as the free  
area of the air supply inlet opening to which it connects.  
3. The duct shall be least the same cross-sectional area as the free  
area of the air supply inlet opening to which it connects.  
4. The duct shall terminate within 12 in (30.5 cm) above, and within  
24 in (61 cm) horizontally from, the burner level of the appliance  
having the largest input.  
4. The blocking effects of louvers, grilles and screens must be given  
consideration in calculating free area. If the free area of a specific  
louver or grille is not known. Refer to Table 7 to estimate free area.  
5. A square or rectangular shaped duct shall only be used when the  
Ventilated Combustion Air  
required free area of the supply opening is 9 in2 (58.06 cm2) or  
larger. When a square or rectangular duct is used, its small dimen-  
sion shall not be less than 3 in (7.6 cm).  
The ventilated attic space or a crawl space from which the combustion  
air is taken must comply with the requirements specified in “AIR  
SOURCE FROM OUTDOORS” in this instruction or in Section 5.3, Air  
for Combustion and Ventilation of the National Fuel Gas Code, ANSI  
Z223.1 (latest edition). This type installation requires two properly sized  
pipes. One brings combustion air from a properly ventilated attic space  
or crawl space and a second pipe that extends from the furnace vent  
connection (top right of unit) to the exterior of the building.  
6. An air inlet supply from outdoors shall be equipped with a means  
to prevent the direct entry of rain and wind. Such means shall not  
reduce the required free area of the air supply opening.  
7. An air supply inlet opening from the outdoors shall be located not  
less than 12” (30.5 cm) above the outside grade level.  
Combustion Air Source from Outdoors  
Vent and Supply (Outside) Air Safety Check Procedure  
1. Two permanent openings, one within 12 in (30.5 mm) of the top  
and one within 12 in (30.5 mm) of bottom of the confined space,  
Two permanent openings, shall communicate directly or by means  
of ducts with the outdoors, crawl spaces or attic spaces.  
For Category I furnaces, vent installations shall be in accordance with  
Parts 7 and 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,  
and or Section 7 and Appendix B of the CSA B149.1, Natural Gas and  
Propane Installation Codes, the local building codes, furnace and vent  
manufacture's instructions.  
18  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Multi-story or common venting systems are permitted and must be  
installed in accordance with the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54 and / or the CSA B149.1, Natural Gas and Propane Installa-  
tion Codes, local codes, and the manufacture's instructions.  
Horizontal portions of the venting system shall be supported to prevent  
sagging using hangers or perforated straps and must slope upwards  
not less than 1/4" per foot (0.635 cm/m) from the furnace to the vent ter-  
minal.  
Vent connectors serving Category I furnaces shall not be connected  
into any portion of mechanical draft systems operating under positive  
pressure.  
It is recommended that you follow the venting safety procedure below.  
This procedure is designed to detect an inadequate ventilation system  
that can cause the appliances in the area to operate improperly causing  
unsafe levels of Carbon Monoxide or an unsafe condition to occur.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon-  
monxide poisoning or death.  
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances  
connected to the venting system are not in operation:  
1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other  
deficiencies, which could cause an unsafe condition  
2. Close all building doors and windows.  
3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum  
speed. Open the fireplace dampers. Do not operate a summer exhaust fan.  
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate contin-  
uously.  
5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening  
after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the  
appliance as possible. Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a  
downdraft or inadequate draft condition.  
6. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fire-  
place dampers and any other gas burning appliance to their normal condition.  
7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not  
have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can  
function safely.  
NOTE: An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1 in. W.C. (-25 kPa) with  
all of the appliance(s) operating at the same time.  
8. Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code  
Z223.1 or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the  
appropriate tables in Appendix G of the above codes or for this appliance.  
NOx SCREEN REMOVAL (Lo-NOx Models Only)  
If the furnace is equipped with NOx screens and is to be used with LP  
(propane) gas, the screens must be removed prior to start-up.  
SECTION VIII: START-UP AND  
ADJUSTMENTS  
The initial start-up of the furnace requires the following additional  
procedures:  
1. Make sure that the electrical power to the unit is turned off and that  
the gas supply is turned off at the shut-off valve.  
2. Remove the blower compartment and burner compartment access  
doors.  
All electrical connections made in the field and in the factory should  
be checked for proper tightness.  
3. Disconnect the gas supply piping at the union to permit removal of  
the entire burner and gas control assembly from the vestibule  
panel. Use the wrench boss on the gas valve when removing or  
installing the piping.  
When the gas supply is initially connected to the furnace, the gas piping  
may be full of air. In order to purge this air, it is recommended that the  
ground union be loosened until the odor of gas is detected. When gas is  
detected, immediately retighten the union and check for leaks. Allow  
five minutes for any gas to dissipate before continuing with the start-up  
procedure. Be sure proper ventilation is available to dilute and carry  
away any vented gas.  
4. Unplug the igniter from the wire harness. Disconnect the flame  
sensor wires located on top of the air shield. Unplug the gas valve  
from the wiring harness.  
5. Remove the screws holding the burner assembly to the vestibule  
panel.  
6. Remove the burner assembly. It should be possible to swing the  
burner assembly out of the way without disconnecting the remain-  
ing wires.  
7. With the burner assembly out of the way, simply slide the NOx  
screens out of the heat exchanger tubes and discard the screens.  
8. Replace all components in reverse order. Reconnect all wiring.  
Johnson Controls Unitary Products  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
With furnace in operation, check all of the pipe joints, gas valve connec-  
tions and manual valve connections for leakage using an approved gas  
detector, a non-corrosive leak detection fluid, or other leak detection  
methods. Take appropriate steps to stop any leak. If a leak persists,  
replace the component.  
GAS PIPING LEAK CHECK  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could result in serious  
injury, death or property damage.  
Never test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection of leaks  
to check all connections. A fire or explosion may result causing  
property damage, personal injury or loss of life.  
CALCULATING THE FURNACE INPUT  
(NATURAL GAS)  
NOTICE  
Burner orifices are sized to provide proper input rate using natural  
gas with a heating value of 1030 BTU/Ft3 (38.4 MJ/m3). If the heat-  
ing value of your gas is significantly different, it may be necessary  
to replace the orifices.  
Burner ignition may not be satisfactory on first startup due to resid-  
ual air in the gas line or until gas manifold pressure is adjusted. The  
ignition control will make three attempts to light before locking out.  
NOTICE  
If orifice hole appears damaged or it is suspected to have been  
redrilled, check orifice hole with a numbered drill bit of correct size.  
Never redrill an orifice. A burr-free and sqaurely aligned orifice hole  
is essential for proper flame characteristics.  
It is recommended that when the gas supply is first connected to the  
furnace, the ground union be loosened until the odor of gas is detected.  
When gas is detected, immediately tighten the union and check for gas  
leaks. Allow five minutes for any gas to dissipate before continuing with  
the start-up procedure. Be sure that proper ventilation is available to  
dilute and carry away any vented gas.  
With furnace in operation, check all of the pipe joints, gas valve connec-  
tions and manual valve connections for leakage using an approved gas  
detector, a non-corrosive leak detection fluid or other leak detection  
methods. Take appropriate action to stop any leak. If a leak persists,  
replace the faulty component.  
DO NOT bottom out gas valve regulator adjusting screw. This can  
result in unregulated manifold pressure and result in excess over-  
fire and heat exchanger failures.  
The furnace and its equipment shut-off valve must be disconnected  
from the gas supply during any pressure testing of that system at test  
pressures in excess of 1/2 PSI (3.45 kPa).  
NOTICE  
DO NOT set manifold pressure less than 3.2 in wc or more than 3.8  
in wc for natural gas at sea level. If manifold pressure is outside this  
range, change main burner orifices.  
The furnace must be isolated from the gas supply piping system by  
closing the equipment shut-off valve during any pressure testing of the  
gas supply system.  
Verify natural gas input rate by clocking meter.  
IGNITION SYSTEM SEQUENCE  
1. Turn off all other gas appliances and pilots.  
1. Turn the gas supply ON at external valve and main gas valve.  
2. Set the thermostat above room temperature to call for heat.  
3. System start-up will occur as follows:  
2. Run furnace for a minimum of 3 minutes in heating operation.  
3. Measure time (in sec) for gas meter to complete 1 revolution and  
note reading. The 2 cubic feet dial provides a more accurate mea-  
surement of gas flow.  
a. The induced draft blower motor will start and come up to  
speed. Shortly after inducer start-up, the hot surface igniter  
will glow for about 17 seconds.  
4. Refer to Table 10 for cubic feet of gas per hour.  
5. Multiply cubic feet per hour by heating valve (BTU/cu ft) to obtain  
input.  
b. After this warm up, the ignition module will energize (open)  
the main gas valve.  
If clocked rate does not match the input rate from the unit nameplate.  
follow steps in next section to adjust the manifold pressure. Repeat  
steps 2 - 5 until correct input is achieved.  
c. After flame is established, the supply air blower will start in  
about 30 seconds.  
Be sure to relight any gas appliances that were turned off at the  
start of this input check.  
Burner ignition may not be satisfactory on first startup due to resi-  
dential air in the gas line or until gas manifold pressure is adjusted.  
The ignition control will make 3 attempts to light before locking out.  
20  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Table 10: Gas Rate (CU FT/HR)  
Size of Test Dial  
2 Cu Ft  
720  
Size of Test Dial  
Seconds For  
1 Revolution  
Seconds For  
1 Revolution  
1 Cu Ft  
360  
327  
300  
277  
257  
240  
225  
212  
200  
189  
180  
171  
164  
157  
150  
144  
138  
133  
129  
124  
120  
116  
113  
109  
106  
103  
100  
97  
5 Cu Ft  
1800  
1636  
1500  
1385  
1286  
1200  
1125  
1059  
1000  
947  
900  
857  
818  
783  
750  
720  
692  
667  
643  
621  
600  
581  
563  
545  
529  
514  
500  
486  
474  
462  
450  
439  
429  
419  
409  
400  
391  
383  
375  
367  
1 Cu Ft  
72  
71  
69  
68  
67  
65  
64  
63  
62  
61  
60  
58  
56  
54  
53  
51  
50  
48  
47  
46  
45  
44  
43  
42  
41  
40  
39  
38  
38  
37  
36  
35  
35  
34  
33  
33  
32  
31  
30  
2 Cu Ft  
144  
141  
138  
136  
133  
131  
129  
126  
124  
122  
120  
116  
112  
109  
106  
103  
100  
97  
5 Cu Ft  
360  
355  
346  
340  
333  
327  
321  
316  
310  
305  
300  
290  
281  
273  
265  
257  
250  
243  
237  
231  
225  
220  
214  
209  
205  
200  
196  
192  
188  
184  
180  
178  
173  
170  
167  
164  
161  
155  
150  
10  
50  
51  
11  
655  
12  
600  
52  
13  
555  
53  
14  
514  
54  
15  
480  
55  
16  
450  
56  
17  
424  
57  
18  
400  
58  
19  
379  
59  
20  
360  
60  
21  
343  
62  
22  
327  
64  
23  
313  
66  
24  
300  
68  
25  
288  
70  
26  
277  
72  
27  
267  
74  
28  
257  
76  
95  
29  
248  
78  
92  
30  
240  
80  
90  
31  
232  
82  
88  
32  
225  
84  
86  
33  
218  
86  
84  
34  
212  
88  
82  
35  
206  
90  
80  
36  
200  
92  
78  
37  
195  
94  
76  
38  
95  
189  
96  
75  
39  
92  
185  
98  
74  
40  
90  
180  
100  
102  
104  
106  
108  
110  
112  
116  
120  
72  
41  
88  
176  
71  
42  
86  
172  
69  
43  
84  
167  
68  
44  
82  
164  
67  
45  
80  
160  
65  
46  
78  
157  
64  
47  
76  
153  
62  
48  
75  
150  
60  
49  
73  
147  
Johnson Controls Unitary Products  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
ADJUSTMENT OF MANIFOLD GAS PRESSURE &  
INPUT RATE  
Inlet and manifold gas pressure may be measured by connecting the  
“U” tube manometer to the gas valve with a piece of tubing. Follow the  
appropriate section in the instructions below. Refer to Figure 25 for a  
drawing of the locations of the pressure ports on the gas valve.  
The cap for the pressure regulator must be removed to gain access  
to the adjustment screw. Loosening or tightening the cap does not  
adjust the flow of gas.  
Turn gas off at the ball valve or gas cock on gas supply line  
before the gas valve. Find the pressure ports on the gas  
valve marked Out P and In P.  
NOTICE  
The regulated outlet pressures, both low and high, have been cali-  
brated at the factory. Additional pressure adjustment should not be  
necessary. If adjustment is necessary, set to the following specifica-  
tions. After adjustment, check for gas leakage.  
1. The manifold pressure must be taken at the port marked OUT P.  
2. The gas line pressure must be taken at the port marked IN P.  
3. Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turn-  
ing it 1 turn counter clockwise. DO NOT REMOVE THE SET  
SCREW FROM THE PRESSURE PORT.  
1. Refer to Figure 25 for location of pressure regulator adjustment  
cap and adjustment screws on main gas valve.  
2. Turn gas and electrical supplies on and follow the operating  
instructions to place the unit back in operation.  
Read the inlet gas pressure  
Connect the positive side of the manometer to the IN P Tap on the gas  
valve. Do not connect any tubing to the negative side of the manometer,  
as it will reference atmospheric pressure. Refer to Figure 26 for connec-  
tion details.  
3. Adjust manifold pressure by adjusting gas valve regulator screw  
for the appropriate gas per the following:  
Table 12: Nominal Manifold Pressure  
1. Turn gas and electrical supplies on and follow the operating  
instructions to place the unit back in operation.  
NOMINAL MANIFOLD PRESSURE  
Natural Gas  
3.5" w.c. (0.87 kPa)  
Table 11: Inlet Gas Pressure Range  
Propane (LP) Gas  
10.0" w.c. (2.488 kPa)  
INLET GAS PRESSURE RANGE  
Natural Gas  
Propane (LP)  
OUTLET  
PRESSURE  
PORT  
VENT PORT  
Minimum*  
Maximum  
4.5” W.C. (1.12 kPa)  
10.5” W.C. (2.61 kPa)  
8.0” W.C. (1.99 kPa)  
13.0” (3.24 kPa) W.C.  
INLET  
OUTLET  
WRENCH  
BOSS  
The inlet gas pressure operating range table specifies what the  
minimum and maximum gas line pressures must be for the furnace  
to operate safely. The gas line pressure MUST BE a minimum of:  
INLET  
PRESSURE  
PORT  
MAIN REGULATOR  
ADJUSTMENT  
ON/OFF SWITCH  
(Shown in ON position)  
7” w.c. (1.74 kPA) for Natural Gas  
11” w.c. (2.74 kPA) for Propane (LP) Gas  
FIGURE 25: Gas Valve  
in order to obtain the BTU input specified on the rating plate and/or  
the nominal manifold pressure specified in these instructions and  
on the rating plate.  
If gas valve regulator is turned in (clockwise), manifold pressure is  
increased. If screw is turned out (counter clockwise), manifold pres-  
sure will decrease.  
2. Once the correct gas inlet pressure has been established, see  
Table 11, turn the gas valve to OFF and turn the electrical supply  
switch to OFF; then remove the flexible tubing from the gas valve  
pressure tap and tighten the pressure tap plug using the 3/32” (2.4  
mm) allen wrench.  
4. After the manifold pressure has been adjusted, re-calculate the  
furnace input to make sure you have not exceeded the specified  
input on the rating plate. Refer to “CALCULATING THE FURNACE  
INPUT (NATURAL GAS)”.  
3. Turn the electrical and gas supplies back on, and with the burners  
in operation, check for gas leakage around the gas valve pressure  
port for leakage using an approved non-corrosive gas leak detec-  
tion fluid, or other non-flammable leak detection methods.  
5. Once the correct BTU (kW) input has been established, turn the  
gas valve to OFF and turn the electrical supply switch to OFF; then  
remove the flexible tubing from the gas valve pressure tap and  
tighten the pressure tap plug using the 3/32” (2.4 mm) Allen  
wrench.  
Read the manifold gas pressure  
Connect the positive side of the manometer to the adapter previously  
installed in the OUT P Tap on the gas valve. Do not connect any tubing  
to the negative side of the manometer, as it will reference atmospheric  
pressure. Refer to Figure 26 for connection details.  
6. Turn the electrical and gas supplies back on, and with the burners  
in operation, check for gas leakage around the gas valve pressure  
port for leakage using an approved non-corrosive gas leak detec-  
tion fluid, or other non-flammable leak detection methods.  
22  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
After about 5 minutes of operation, determine the furnace temperature  
rise. Take readings of both the return air and the heated air in the ducts,  
about six feet (1.83 m) from the furnace where they will not be affected  
by radiant heat. Increase the blower speed to decrease the temperature  
rise; decrease the blower speed to increase the rise.  
MANIFOLD PRESSURE “U” TUBE CONNECTION  
OUTLET  
PRESSURE TAP  
GAS VALVE  
1/4” TUBING  
All direct-drive blowers have multi-speed motors. The blower motor  
speed taps are located on the furnace control board in the blower com-  
partment. Refer to Figure 27, and the unit-wiring label to change the  
blower speed. To use the same speed tap for heating and cooling, the  
heat terminal and cool terminal must be connected using a jumper wire  
and connected to the desired motor lead. Place all unused motor leads  
on park terminals. Two park terminals are provided.  
MAINIFOLD  
PIPE  
FLAME  
SENSOR  
3.5 IN  
WATER  
COLUMN  
GAS  
PRESSURE  
SHOWN  
GAS  
BURNERS  
U-TUBE  
MANOMETER  
Do not energize more than one motor speed at a time or damage to  
the motor will result.  
FIGURE 26: Reading Gas Pressure  
ADJUSTMENT OF FAN CONTROL SETTINGS  
ADJUSTMENT OF TEMPERATURE RISE  
This furnace is equipped with a time-on/time-off heating fan control. The  
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,  
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-  
onds. The fan-off setting must be long enough to adequately cool the  
furnace, but not so long that cold air is blown into the heated space. The  
fan-off timing may be adjusted by positioning the jumper on two of the  
four pins as shown in Figure 27.  
DANGER  
The temperature rise, or temperature difference between the return  
air and the supply (heated) air from the furnace, must be within the  
range shown on the furnace rating plate and within the application  
limitations shown in SECTION 6.  
The supply air temperature cannot exceed the “Maximum Supply  
Air Temperature” specified in these instructions and on the fur-  
nace rating plate. Under NO circumstances can the furnace be  
allowed to operate above the Maximum Supply Air Temperature.  
Operating the furnace above the Maximum Supply Air Temperature  
will cause premature heat exchanger failure, high levels of Carbon  
Monoxide, a fire hazard, personal injury, property damage, and/or  
death.  
TWIN  
Blower Off  
Delay Timer  
(In seconds)  
PARK PARK  
HI COOL  
HEAT  
EAC-H  
L1  
XFMR  
HUM  
FIGURE 27: Furnace Control Board  
Johnson Controls Unitary Products  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Table 13: Blower Performance CFM - Any Position (without filter) - Bottom Return  
Bottom Airflow Data (SCFM)  
Ext. Static Pressure (in. H2O)  
Models  
Speed  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
121  
0.9  
NA  
1.0  
NA  
High  
Medium High  
Medium Low  
Low  
966  
923  
874  
804  
717  
566  
386  
813  
782  
743  
687  
605  
464  
280  
118  
NA  
NA  
040A08  
745  
706  
667  
619  
545  
413  
205  
NA  
NA  
NA  
684  
655  
614  
565  
489  
342  
171  
NA  
NA  
NA  
High  
1292  
1203  
1043  
869  
1230  
1157  
1010  
845  
1160  
1105  
962  
1088  
1035  
905  
1004  
942  
891  
760  
476  
129  
129  
Medium High  
Medium Low  
Low  
846  
728  
485  
133  
129  
060A10  
060A12  
080B12  
080C16  
080C22  
100B12  
100C16  
100C20  
120C16  
120C20  
130D20  
823  
705  
491  
305  
124  
123  
811  
772  
708  
579  
438  
178  
145  
125  
High  
1358  
1097  
935  
1341  
1083  
928  
1319  
1075  
920  
1303  
1064  
899  
1275  
1042  
872  
1238  
1024  
840  
1190  
997  
1130  
962  
1062  
906  
943  
Medium High  
Medium Low  
Low  
821  
809  
771  
731  
659  
800  
779  
763  
736  
711  
687  
657  
622  
584  
529  
High  
1329  
994  
1307  
1004  
790  
1285  
1008  
782  
1247  
984  
1195  
970  
1143  
941  
1091  
893  
1027  
839  
927  
806  
Medium High  
Medium Low  
Low  
773  
669  
786  
781  
761  
743  
726  
685  
630  
540  
655  
654  
647  
629  
620  
594  
560  
524  
469  
399  
High  
1881  
1553  
1312  
1169  
2811  
2234  
1722  
1396  
1314  
1010  
812  
1822  
1535  
1286  
1166  
2725  
2233  
1716  
1375  
1318  
1004  
805  
1783  
1492  
1288  
1128  
2638  
2147  
1690  
1348  
1292  
1003  
796  
1696  
1456  
1260  
1098  
2540  
2092  
1681  
1325  
1265  
995  
1602  
1408  
1205  
1069  
2448  
2042  
1603  
1263  
1223  
992  
1539  
1343  
1143  
1032  
2339  
1974  
1553  
1200  
1177  
956  
1465  
1279  
1091  
987  
1394  
1226  
1029  
909  
1267  
1113  
966  
1130  
1014  
841  
Medium High  
Medium Low  
Low  
835  
747  
High  
2224  
1907  
1489  
1150  
1119  
914  
2111  
1820  
1426  
1120  
1051  
857  
1974  
1705  
1335  
1052  
971  
1831  
1575  
1241  
965  
Medium High  
Medium Low  
Low  
High  
890  
Medium High  
Medium Low  
Low  
798  
721  
786  
777  
754  
727  
685  
626  
560  
661  
659  
644  
623  
614  
605  
568  
532  
482  
399  
High  
2069  
1662  
1368  
1016  
2893  
2272  
1765  
1425  
1752  
1469  
1248  
1076  
2701  
2125  
1664  
1358  
2823  
2242  
1805  
1425  
2014  
1656  
1371  
1014  
2774  
2243  
1752  
1380  
1724  
1449  
1235  
1076  
2620  
2083  
1664  
1339  
2714  
2188  
1791  
1427  
1956  
1639  
1377  
1018  
2687  
2204  
1737  
1409  
1702  
1453  
1226  
1046  
2533  
2046  
1647  
1330  
2613  
2154  
1738  
1403  
1885  
1608  
1376  
1030  
2589  
2169  
1718  
1378  
1664  
1420  
1207  
1025  
2429  
1994  
1619  
1318  
2507  
2102  
1725  
1335  
1820  
1586  
1367  
1012  
2478  
2086  
1674  
1307  
1600  
1382  
1179  
1002  
2338  
1955  
1580  
1286  
2399  
2045  
1675  
1324  
1748  
1544  
1334  
996  
1668  
1491  
1295  
975  
1577  
1421  
1250  
944  
1468  
1338  
1188  
898  
1362  
1204  
1104  
852  
Medium High  
Medium  
Low  
High  
2376  
2018  
1619  
1274  
1542  
1344  
1133  
968  
2255  
1940  
1561  
1226  
1454  
1269  
1077  
927  
2120  
1842  
1493  
1180  
1372  
1197  
992  
1978  
1743  
1437  
1113  
1264  
1118  
922  
1824  
1602  
1312  
1025  
1119  
1022  
841  
Medium High  
Medium Low  
Low  
High  
Medium High  
Medium Low  
Low  
869  
784  
707  
High  
2227  
1901  
1555  
1235  
2282  
1970  
1623  
1280  
2112  
1857  
1468  
1185  
2170  
1887  
1567  
1236  
1993  
1737  
1392  
1141  
2042  
1792  
1487  
1176  
1861  
1621  
1332  
1060  
1908  
1673  
1394  
1103  
1706  
1497  
1226  
938  
Medium High  
Medium Low  
Low  
High  
1761  
1537  
1256  
996  
Medium High  
Medium Low  
Low  
NOTES:  
1. Airflow expressed in standard cubic feet per minute (CFM).  
2. Motor voltage at 115 V.  
24  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Table 14: Blower Performance CFM - Any Position (without filter) - Left Side Return  
Left Side Airflow Data (SCFM)  
Ext. Static Pressure (in. H2O)  
Models  
Speed  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
NA  
1.0  
NA  
High  
Medium High  
Medium Low  
Low  
994  
971  
942  
899  
829  
725  
419  
120  
824  
804  
777  
739  
675  
489  
350  
361  
NA  
NA  
040A08  
757  
733  
694  
659  
575  
444  
399  
NA  
NA  
NA  
707  
684  
641  
604  
495  
397  
282  
NA  
NA  
NA  
High  
1371  
1249  
1059  
854  
1323  
1207  
1026  
836  
1251  
1158  
997  
1169  
1098  
949  
1086  
1018  
889  
971  
843  
521  
NA  
NA  
Medium High  
Medium Low  
Low  
921  
669  
503  
NA  
NA  
060A10  
060A12  
080B12  
080C16  
080C22  
100B12  
100C16  
100C20  
120C16  
120C20  
130D20  
793  
582  
420  
NA  
NA  
809  
775  
717  
576  
464  
216  
NA  
NA  
High  
1406  
1129  
970  
1401  
1126  
947  
1394  
1107  
933  
1379  
1094  
916  
1338  
1076  
890  
1304  
1047  
863  
1261  
1010  
827  
1202  
966  
1135  
921  
1040  
843  
Medium High  
Medium Low  
Low  
789  
741  
668  
834  
809  
797  
768  
740  
710  
677  
634  
586  
534  
High  
1274  
975  
1285  
974  
1255  
968  
1239  
960  
1207  
948  
1158  
923  
1111  
879  
1049  
823  
979  
830  
Medium High  
Medium Low  
Low  
756  
672  
777  
771  
772  
762  
752  
734  
695  
651  
604  
529  
647  
634  
623  
610  
602  
588  
552  
506  
457  
381  
High  
1825  
1516  
1294  
1126  
2972  
2173  
1670  
1371  
1258  
986  
1781  
1493  
1297  
1115  
2863  
2146  
1667  
1339  
1278  
995  
1746  
1482  
1271  
1095  
2769  
2103  
1647  
1317  
1283  
1011  
786  
1695  
1464  
1238  
1049  
2671  
2082  
1618  
1284  
1259  
1003  
783  
1641  
1442  
1187  
1027  
2571  
2036  
1585  
1259  
1240  
962  
1587  
1411  
1120  
996  
1521  
1343  
1083  
957  
1429  
1275  
1028  
929  
1330  
1192  
979  
1184  
1035  
851  
Medium High  
Medium  
Low  
840  
742  
High  
2465  
1966  
1549  
1199  
1204  
935  
2352  
1904  
1492  
1147  
1149  
913  
2227  
1827  
1408  
1085  
1073  
861  
2095  
1738  
1350  
1024  
1015  
808  
1950  
1621  
1238  
928  
Medium High  
Medium Low  
Low  
High  
897  
Medium High  
Medium Low  
Low  
738  
793  
786  
780  
750  
733  
702  
627  
567  
667  
653  
640  
629  
604  
583  
558  
519  
469  
427  
High  
2009  
1523  
1230  
1126  
2964  
2192  
1699  
1361  
1789  
1451  
1202  
1063  
2828  
2085  
1620  
1322  
2958  
2191  
1737  
1404  
1994  
1506  
1249  
1115  
2886  
2178  
1695  
1356  
1774  
1445  
1210  
1050  
2768  
2073  
1631  
1311  
2862  
2182  
1738  
1394  
1933  
1521  
1245  
1095  
2794  
2150  
1706  
1337  
1738  
1431  
1266  
1033  
2699  
2042  
1636  
1302  
2758  
2157  
1713  
1380  
1893  
1490  
1230  
1049  
2707  
2109  
1632  
1304  
1702  
1413  
1252  
1010  
2612  
2029  
1593  
1271  
2662  
2092  
1691  
1355  
1836  
1466  
1218  
1027  
2623  
2098  
1612  
1267  
1665  
1394  
1226  
1007  
2524  
1967  
1567  
1241  
2553  
2085  
1675  
1327  
1763  
1435  
1195  
996  
1691  
1393  
1161  
957  
1606  
1326  
1120  
929  
1508  
1241  
1039  
840  
1389  
1119  
949  
Medium High  
Medium Low  
Low  
742  
High  
2522  
2007  
1568  
1243  
1608  
1362  
1191  
982  
2415  
1956  
1519  
1191  
1514  
1312  
1082  
941  
2281  
1888  
1460  
1149  
1431  
1235  
1028  
889  
2149  
1795  
1392  
1077  
1343  
1149  
950  
2012  
1671  
1293  
994  
Medium High  
Medium Low  
Low  
High  
1205  
1037  
852  
Medium High  
Medium  
Low  
845  
778  
High  
2423  
1896  
1557  
1201  
2447  
1997  
1590  
1276  
2308  
1893  
1520  
1162  
2328  
1932  
1531  
1220  
2219  
1816  
1476  
1101  
2203  
1844  
1467  
1163  
2118  
1717  
1407  
1042  
2056  
1741  
1389  
1095  
1982  
1635  
1263  
979  
Medium High  
Medium Low  
Low  
High  
1893  
1608  
1276  
1013  
Medium High  
Medium Low  
Low  
NOTES:  
1. Airflow expressed in standard cubic feet per minute (CFM).  
2. Return air is through side opposite motor (left side).  
3. Motor voltage at 115 V.  
4. Airflow through across motor side (right side) may be slightly less than the data shown above.  
Johnson Controls Unitary Products  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
Heating Cycle  
SECTION IX: SAFETY CONTROLS  
CONTROL CIRCUIT FUSE  
When the thermostat switch is set on HEAT and the fan is set on AUTO,  
and there is a call for heat, a circuit is completed between terminals R  
and W of the thermostat. When the proper amount of combustion air is  
being provided, the pressure switch will close, the ignition control pro-  
vides a 17-second ignitor warm-up period, the gas valve then opens,  
the gas starts to flow, ignition occurs and the flame sensor begins its  
sensing function. The blower motor will energize 30 seconds after the  
gas valve opens, if a flame is detected. Normal furnace operation will  
continue until the thermostat circuit between R and W is opened, which  
causes the ignition system and gas valve to de-energize and the burner  
flames to be extinguished. The vent motor will operate for 15 seconds  
and the blower motor will operate for the amount of time set by the fan-  
off delay jumper located on the control board. See Figure 27. The heat-  
ing cycle is now complete, and ready for the start of the next heating  
cycle.  
A 3-amp fuse is provided on the control circuit board to protect the 24-  
volt transformer from overload caused by control circuit wiring errors.  
This is an ATO 3, automotive type fuse and is located on the control  
board.  
BLOWER DOOR SAFETY SWITCH  
Main power to the unit must still be interrupted at the main power  
disconnect switch before any service or repair work is to be done to  
the unit. Do not rely upon the interlock switch as a main power dis-  
connect.  
Blower and burner must never be operated without the blower  
panel in place.  
If the flame is not detected within 7 seconds of the gas valve opening,  
the gas valve is shut off and a retry operation begins. Also, if the flame  
is lost for 2 seconds during the 10-second stabilization period, the gas  
valve is shut off and a retry operation begins. During a retry operation,  
the vent motor starts a 15 second inter-purge and the ignitor warm-up  
time is extended to 27 seconds. If the flame is established for more than  
10 seconds after ignition during a retry, the control will clear the ignition  
attempt (retry) counter. If three retries occur during a call for heat, the  
furnace will shut down for one hour. If at the end of the one hour shut  
down there is a call for heat, the furnace will initiate a normal start cycle.  
If the problem has not been corrected the furnace will again lockout  
after three retries.  
This unit is equipped with an electrical interlock switch mounted in the  
burner compartment. This switch interrupts all power at the unit when  
the panel covering the blower compartment is removed.  
Electrical supply to this unit is dependent upon the panel that covers the  
blower compartment being in place and properly positioned.  
ROLLOUT SWITCH CONTROLS  
These controls are mounted on the burner assembly. If the temperature  
in the area surrounding the burner exceeds its set point, the gas valve  
is de-energized. The operation of this control indicates a malfunction in  
the combustion air blower, heat exchanger or a blocked vent pipe con-  
nection. Corrective action is required. These are manual reset controls  
that must be reset before operation can continue.  
A momentary loss of gas supply, flame blowout, or a faulty flame probe  
circuit will result in a disruption in the flame and be sensed within 1.0  
seconds. The gas valve will de-energize and the control will begin a  
recycle operation. A normal ignition sequence will begin after a 15 sec-  
ond inter-purge. If during the five recycles the gas supply does not  
return, or the fault condition is not corrected the ignition control will lock-  
out for 60 minutes.  
PRESSURE SWITCHES  
This furnace is supplied with a pressure switch, which monitors the flow  
through the combustion air/vent piping system. This switch de-ener-  
gizes the gas valve if any of the following conditions are present.  
During burner operation, a momentary loss of power for 50 milliseconds  
or longer will de-energize the gas valve. When the power is restored,  
the gas valve will remain de-energized and the ignition sequence will  
immediately restart.  
1. Blockage of vent piping or terminal.  
2. Failure of combustion air blower motor.  
LIMIT CONTROLS  
There is a high temperature limit control located on the furnace vesti-  
bule panel near the gas valve. This is an automatic reset control that  
provides over temperature protection due to reduced airflow. This may  
be caused by:  
Hot Surface Ignition System  
1. A dirty filter.  
HOT SURFACE IGNITION SYSTEM  
Do not attempt to light this furnace by hand (with a match or any  
other means). There may be a potential shock hazard from the  
components of the hot surface ignition system. The furnace can  
only be lit automatically by its hot surface ignition system.  
2. If the indoor fan motor should fail.  
3. Too many supply or return registers closed or blocked off.  
The control module will lockout if the limit trips 5 consecutive times. If  
this occurs, control will reset & try ignition again after 1 hour.  
TROUBLESHOOTING  
The following visual checks should be made before troubleshooting:  
SEQUENCE OF OPERATION  
The following describes the sequence of operation of the furnace. Refer  
to Owners Manual for component location.  
1. Check to see that the power to the furnace and the ignition control  
module is ON.  
2. The manual shut-off valves in the gas line to the furnace must be  
open.  
3. Make sure all wiring connections are secure.  
4. Review the sequence of operation. Start the system by setting the  
thermostat above the room temperature. Observe the system’s  
response. Then use the troubleshooting section in this manual to  
check the system’s operation.  
Continuous Blower  
Cooling/heating thermostats have a fan switch that has an ON and  
AUTO position. In the ON position the thermostat circuit is completed  
between terminals R and G. The motor will operate continuously on the  
speed tap wire that is connected to the “HI COOL” cooling terminal on  
the control board. To obtain a constant air circulation at lower flow rate,  
change the high-speed wire to either the medium speed wire or the low  
speed wire.  
Intermittent Blower - Cooling  
Cooling/heating thermostats have a fan switch that has an ON and  
AUTO position. In the AUTO position the thermostat circuit is completed  
between terminals R and G when there is a call for cooling. The motor  
will operate on the speed tap wire that is connected to the “HI COOL”  
cooling terminal on the control board. The fan off setting is fixed at 60  
seconds to improve cooling efficiency.  
Never bypass any safety control to allow furnace operation. To do  
so will allow furnace to operate under potentially hazardous condi-  
tions.  
Do not try to repair controls. Replace defective controls with UPG  
Source 1 Parts.  
Never adjust pressure switch to allow furnace operation.  
26  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
5 RED FLASHES: This fault is indicated if the normally closed rollout  
switch opens. The rollout control is manually reset. Check for proper  
combustion air, proper inducer operation, and primary heat exchanger  
failure or burner problem. The control will enter a hard lockout and  
power will have to be cycled off and on to reset the control after the  
problem has been corrected.  
FURNACE CONTROL DIAGNOSTICS  
The furnace has built-in, self-diagnostic capability. A blinking LED light  
on the control board can flash red, green or amber to indicate various  
conditions. The control continuously monitors its own operation and the  
operation of the system. If a failure occurs, the LED light will indicate  
the failure code.  
6 RED FLASHES: This indicates that while the unit was operating, the  
pressure switch opened four times during the call for heat. Check for  
faulty inducer, blocked vent pipe or faulty pressure switch. The furnace  
will lock out for one hour and then restart.  
The SLOW flash speed is two seconds on and two seconds off.  
The other flash codes listed below have the following timing: LED light  
will turn on for 1/3 second and off for 1/3 second. This pattern will be  
repeated the number of times equal to the code. There will be a two-  
second pause between codes. For example, the six red flash code will  
flash the LED light on and off six times, then will be off for two seconds.  
This pattern will repeat as long as the fault condition remains. The con-  
tinuous flash codes listed below will flash the LED light on and off con-  
tinuously, with no breaks or longer pauses.  
7 RED FLASHES: This fault code indicates that the flame could not be  
established during three trials for ignition. Check that the gas valve  
switch is in the ON position. Check for low or no gas pressure, faulty  
gas valve, dirty or faulty flame sensor, faulty hot surface ignitor, loose  
wires or a burner problem. The furnace will lock out for one hour and  
then restart.  
SLOW GREEN FLASH: Normal operation, no thermostat calls.  
SLOW AMBER FLASH: Normal operation with call for heat.  
8 RED FLASHES: This fault is indicated if the flame is lost five times  
(four recycles) during the heating cycle. Check for low gas pressure,  
dirty or faulty flame sensor or faulty gas valve. The furnace will lock out  
for one hour and then restart.  
LED STEADY OFF – If the LED light does not flash at all, check for  
power to the board and check for a blown fuse on the board. If the  
board is properly powered and the fuse is not blown, the control board  
may need to be replaced.  
9 RED FLASHES: Indicates reversed line voltage polarity, grounding  
problem or reversed low voltage transformer wires. Both heating and  
cooling operations will be affected. Check polarity at furnace and  
branch. Check furnace grounding. Check that flame probe is not  
shorted to chassis. The furnace will not start the ignition sequence until  
this problem is corrected.  
STEADY ON ANY COLOR: Control failure. Turn power to the furnace  
off and back on. If the fault code returns, the control board must be  
replaced. The control board is not field-repairable.  
CONTINUOUS GREEN FLASH: Twinning error, incorrect 24V phasing  
or no power to twinned unit. Check twinning wiring. Confirm that both  
twinned units have power.  
10 RED FLASHES: Gas valve energized with no call for heat. The main  
blower and inducer blower will run and no ignition sequence will be  
started as long as this condition exists. Check gas valve and gas valve  
wiring.  
CONTINUOUS AMBER FLASH: Flame sense current is below 1.5  
microamps. Check and clean flame sensor. Check for proper gas flow.  
Verify that current is greater than 1.5 microamps at flame current test  
pad.  
11 RED FLASHES: This indicates that the main limit switch has opened  
its normally-closed contacts and has remained open for more than five  
minutes. This condition is usually caused by a failed blower motor or  
blower wheel. The control will enter a hard lockout and power will have  
to be cycled off and on to reset the control after the problem has been  
corrected.  
1 RED FLASH: This indicates that flame was sensed when there was  
not a call for heat. The control will turn on both the inducer motor and  
supply air blower. Check for a leaking or slow-closing gas valve.  
2 RED FLASHES: This indicates that the pressure switch is closed  
when it should be open. The control confirms that the pressure switch  
contacts are open at the beginning of each heat cycle and will not let  
the ignition sequence continue if the pressure switch contacts are  
closed when they should be open. Check for a faulty pressure switch or  
miswiring.  
4 AMBER FLASHES: The control is receiving a “Y” signal from the  
thermostat without a “G” signal. The furnace will operate normally in  
both heating and cooling, but this fault code will be displayed in order to  
alert the user that there is a wiring problem. Verify that the “G” wire from  
the thermostat is connected properly.  
3 RED FLASHES: This indicates the pressure switch contacts are open  
when they should be closed. Check for faulty inducer, blocked vent  
pipe, broken pressure switch hose, disconnected pressure switch or  
inducer wires or faulty pressure switch.  
SOFT LOCKOUT: This control includes a soft lockout that will reset  
automatically after one hour. This provides protection to an unoccupied  
structure if a temporary condition exists causing a furnace malfunction.  
An example of this is a temporary interruption in gas supply that would  
prevent the furnace from lighting. The control will keep trying to light  
each hour and will resume normal operation if the gas supply is  
restored.  
4 RED FLASHES: This indicates that the main limit switch has opened  
its normally closed contacts. The control will operate the supply air  
blower and inducer while the open limit condition exists. Check for a  
dirty filter, improperly sized duct system, incorrect blower speed setting,  
incorrect firing rate, loose limit switch wiring or faulty blower motor.  
HARD LOCKOUT: Some fault conditions result in a hard lockout, which  
requires power to the control to be turned off and then back on to reset  
the control. The control will not automatically restart.  
If the limit switch has not closed within five minutes, the control will  
assume that the blower is not functioning, will start a hard lockout and  
will begin to flash the 11 Red Flashes error code. Power will have to be  
cycled off and on to reset the control after the problem has been cor-  
rected. See “11Red Flashes” description below.  
IGNITION CONTROL FLAME SENSE LEVELS  
Normal flame sense current is approximately  
3.7 microamps DC (µa)  
Low flame signal warning starts at 1.5 microamps.  
Low flame signal control lockout point is  
0.1 microamps DC (µa)  
If the main limit switch opens five times within a single call for heat, the  
control will also indicate 4 Red Flashes and will enter a one-hour soft  
lockout.  
Johnson Controls Unitary Products  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
To retrieve the error codes, push the LAST ERROR button. The LED on  
the control will then flash the error codes that are in memory, starting  
with the most recent. There will be a two-second pause between each  
flash code. After the error codes have all been displayed, the LED will  
resume the normal slow green flash after a five second pause. To  
repeat the series of error codes, push the button again.  
DIAGNOSTIC FAULT CODE STORAGE AND  
RETRIEVAL  
The control in this furnace is equipped with memory that will store up to  
five error codes to allow a service technician to diagnose problems  
more easily. This memory will be retained even if power to the furnace  
is lost. This feature should only be used by a qualified service tech-  
nician.  
If there are no error codes in memory, the LED will flash two green  
flashes. To clear the memory, push the LAST ERROR button and hold it  
for more than five seconds. The LED will flash three green flashes when  
the memory has been cleared, then will resume the normal slow green  
flash after a five-second pause.  
If more than five error codes have occurred since the last reset, only the  
five most recent will be retained. The furnace control board has a but-  
ton, labeled "LAST ERROR" that is used to retrieve error codes. This  
function will only work if there are no active thermostat signals. So any  
call for heating, cooling or continuous fan must be terminated before  
attempting to retrieve error codes.  
SECTION X: REPLACEMENT PARTS LIST  
DESCRIPTION  
DESCRIPTION (Continued)  
FABRICATED PARTS  
MOTOR  
BRACKET, BLOWER TRACK (2 Req’d)  
HEAT EXCHANGER ASS’Y  
MANIFOLD, GAS  
MOTOR, DIRECT DRIVE BLOWER  
BLOWER, COMBUSTION  
ELECTRICAL  
PAN, BOTTOM  
CAPACITOR, RUN  
PANEL, TOP  
SWITCH, LIMIT  
PANEL, DOOR (2 Req’d)  
VENT PAN, COMBUSTION (w/Gasket)  
PANEL, BLOCKOFF  
CONTROL, FURNACE  
IGNITER  
SENSOR, FLAME  
LO-NOX SCREEN (L-Models Only)  
MISCELLANEOUS  
SWITCH, PRESSURE  
SWITCH, DOOR  
ORIFICE, BURNER (Natural #45)  
SIGHT GLASS, OVAL (2 Req’d)  
GASKET, FOAM (Door) (1.5 ft req’d)  
GASKET, INTAKE PAN  
PLUG, VENT HOLE  
TRANSFORMER  
VALVE, GAS  
CONTROL, TEMPERATURE  
AIR MOVING  
HOUSING, BLOWER  
HOUSING, BLOWER w/WHEEL  
WHEEL, BLOWER  
BRACKET, DOOR  
WIRING HARNESS  
FERRULE (3 Req’d)  
FABRICATED PARTS  
BAFFLE, FLUE  
GROMMET (3 Req’d)  
MOTOR MOUNT  
BURNER, MAIN GAS  
BRACKET, IGNITER  
SHELF, BLOWER  
TUBING, SILICON  
DIAGRAM, WIRING  
KNOB, QUARTER TURN (4 Req’d)  
RAIL, BLOWER (2 Req’d)  
REPLACEMENT PART CONTACT INFORMATION  
This is a generic parts list. To request a complete parts list, refer to the contact information below:  
1. Search for a part or browse the catalog.  
2. Find a dealer or distributor.  
3. Customer Service contact information.  
a. Click on the “Brand Links” button  
b. Click on the “Customer Service” button  
You can contact us by mail. Just send a written request to:  
Johnson Controls Unitary Products  
Consumer Relations  
5005 York Drive  
Norman, OK 73069  
28  
Johnson Controls Unitary Products  
Download from Www.Somanuals.com. All Manuals Search And Download.  
356485-UIM-G-1211  
SECTION XI: WIRING DIAGRAM  
FIGURE 28: Wiring Diagram  
Johnson Controls Unitary Products  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
Subject to change without notice. Published in U.S.A.  
356485-UIM-G-1211  
Copyright © 2011 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 356485-UIM-F-0910  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Infinity Speaker System BassLink User Manual
Jacuzzi Hot Tub EA90 User Manual
Jenn Air Refrigerator W10728796A User Manual
JVC Automobile Alarm UX A10DVD User Manual
JVC Car Video System KW AVX716 User Manual
JVC Projector Accessories DLA SH4KNL User Manual
Karcher Pressure Washer K 2050 User Manual
Kenmore Vacuum Cleaner 11625512 User Manual
Klipsch Speaker 2x RB 51 User Manual
Klipsch Speaker KL 6504 THX User Manual