415571-UTG-C-0309
DESCRIPTION
TECHNICAL
GUIDE
The 13 SEER Series condensing unit is the outdoor part of a
versatile system of air conditioning. It is designed to be custom-
matched with one of UPG’s complete line of evaporator sec-
tions, with each serving a specific function. Matching Air Han-
dlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters are
available, if required. Add-on coils are available for use with
upflow, downflow, or horizontal furnaces and air handlers.
WARRANTY
TECHNICAL GUIDE
1-year limited parts warranty.
5-year limited compressor warranty.
SPLIT-SYSTEM
AIR CONDITIONERS
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed of
aluminum microchannel tubing and enhanced aluminum fins
for increased efficiency and corrosion protection.
13 SEER – R-410A – 3 PHASE
MODELS:
TCGD30 THRU 60
(2.5 THRU 5 NOMINAL TONS)
• PROTECTED COMPRESSOR - The compressor is inter-
nally protected against high pressure, temperature, and
externally by a factory installed high pressure switch. This is
accomplished by the simultaneous operation of high pres-
sure relief valve and a temperature sensor which protects the
compressor if undesirable operating conditions occur. A liq-
uid line filter-drier further protects the compressor.
• DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs are
reduced by easy power and control wiring connections.
Available in sweat connect models only. The unit contains
enough refrigerant for matching indoor coils and 15 feet of
interconnecting piping. The small base dimension means
less space is required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted fan
is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise away from the living area.
The rigid top panel effectively isolates any motor sound. Iso-
lator mounted compressor and the rippled fins of the con-
denser coil muffle the normal fan motor and compressor
operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
ISO 9001
Certified Quality
Management System
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant con-
nections, and a single panel covering the electrical controls
make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable service
valves are provided on both the liquid and vapor sweat con-
nections for ease of evacuating and charging.
LISTED
• U.L. and C.U.L. listed - approved for outdoor application.
Due to continuous product improvement, specifications
are subject to change without notice.
• Agency Listed - U.L. and C.U.L. listed - approved for out-
door application. The unit is certified in accordance with the
Unitary Small Equipment certification program, which is
based on ARI Standard 210/240.
Additional rating information can be found at
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
System Charge for Various Matched Systems
Outdoor Unit
Required Orifice or TXV 1,2
Factory Charge, lbs-oz
TCGD30S4(3,4)S1
TCGD36S4(3,4)S1
0.065/4G1
4 - 9
TCGD42S4(3,4)S1
0.075/4G1
4 - 5
TCGD48S4(3,4)S1
0.073/4H1
4 - 9
TCGD60S4(3,4)S1
0.087/4J1
0.061/4F1
3 - 14
5 - 6
Indoor Coil3,4
AHP30
Additional Charge, oz
0
2
–
–
0
2
–
–
–
–
–
0
–
–
0
0
–
–
–
0
0
2
2
–
–
–
0
2
–
–
–
–
0
0
–
–
0
8
–
–
–
–
–
8
–
–
–
8
–
–
–
–
0
0
8
–
–
–
0
–
8
–
–
–
–
–
0
–
–
–
0
–
–
–
–
4
0
–
–
–
0
–
–
–
–
–
4
0
–
–
–
–
4
0
–
–
–
0
–
–
–
–
4
–
–
–
–
0
–
–
–
–
4
–
–
–
–
–
0
4
–
–
0
–
0
AHP36
AHP42
AHP/SHP60
AHX30
AHX36
AHX42
AHX48
AHX60
F4FP024
F4FP036
F4FP040
F5FP048
F5FP060
F6FP030
F6FP036
F6FP042
F6FP048
F6FP060
FC/MC/PC32
FC/MC/PC35
FC/MC/PC37
FC/MC/PC43
FC/MC/PC48
FC/MC/PC60
FC/MC62
HC36
–
0
–
–
–
2
–
–
–
–
–
2
–
–
–
2
TXV + 2
–
–
–
–
0
2
–
–
–
0
–
2
–
HC42
HC60
UC48
UC60
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting
line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator +
adder for line set.
Johnson Controls Unitary Products
3
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING CAPACITY - With Air Handler Coils
AIR HANDLER
COOLING
NET MBH
UNIT
MODEL
COIL
RATED
CFM
MODEL1
MODEL
W
SEER
EER
TOTAL
SENS.
13 SEER AC WITH MA
MA12B
MA12B
MA12B
MA14D
MA16C
MA14D
MA16C
MA16C
MA20D
MA16C
MA20D
MA20D
MA20D
17
17
17
24
21
24
21
21
24
21
24
24
24
FC/MC35B
FC/MC43B
FC/MC43B
FC/MC48D
FC/MC43C
FC/MC48D
FC/MC48C
FC/MC48C
FC/MC48D
FC60C
1000
29.0
29.0
35.0
35.0
42.0
42.0
42.0
48.0
48.0
48.0
48.0
57.0
57.0
21.0
21.0
24.8
24.8
29.2
29.2
29.2
34.4
34.4
34.4
34.4
38.5
38.5
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
TCGD30S4(3,4)S1
TCGD36S4(3,4)S1
1000
1200
1200
1400
1400
1400
1600
1600
1600
1600
1800
1800
TCGD42S4(3,4)S1
TCGD48S4(3,4)S1
TCGD60S4(3,4)S1
FC/MC60D
FC/MC60D
FC/MC62D
13 SEER AC WITH AHP / SHP / AHX / F*FP
AHP30
AHP36
17
21
17
21
18
17
21
21
21
21
21
24
21
21
21
24
21
24
24
24
24
24
24
24
24
24
24
24
–
–
-
1015
1040
1025
1005
1050
1035
980
29.0
29.0
29.4
30.0
29.0
29.2
29.4
35.0
35.0
35.2
35.4
35.0
35.8
41.0
42.0
41.0
42.0
41.5
48.0
48.0
48.0
48.0
48.0
47.0
57.0
58.5
57.0
57.5
21.0
21.0
22.2
22.3
21.0
21.6
21.4
24.8
24.8
25.0
25.2
24.8
25.8
29.2
29.9
29.2
30.1
29.4
34.4
35.0
35.4
34.4
34.4
34.8
38.5
40.0
38.5
39.0
13.00
13.00
14.00
14.50
13.00
13.50
14.00
13.00
13.00
13.50
14.00
13.00
13.50
13.00
14.50
13.00
14.00
13.50
13.00
13.50
13.50
13.00
13.00
13.00
13.00
13.50
13.00
13.50
11.00
11.00
11.75
12.00
11.00
11.40
12.00
11.00
11.00
11.50
11.80
11.00
11.50
11.00
12.00
11.00
11.75
11.70
11.00
11.00
11.50
11.00
11.00
11.30
11.00
11.50
11.00
11.50
AHX30
TCGD30S4(3,4)S1
AHX36
-
F4FP040
F6FP030
F6FP036
AHP36
–
-
-
–
–
-
1235
1255
1225
1190
1235
1290
1485
1395
1455
1455
1380
1675
1600
1660
1600
1600
1625
1850
1905
1900
1710
AHP42
AHX36
TCGD36S4(3,4)S1
TCGD42S4(3,4)S1
AHX42
-
F5FP048
F6FP042
AHP42
–
-
–
-
AHX42
F5FP048
F6FP042
F6FP048
AHP/SHP48
AHP/SHP60
AHX48
–
-
-
–
–
-
TCGD48S4(3,4)S1
TCGD60S4(3,4)S1
F5FP048
F5FP060
F6FP048
AHP/SHP60
AHX60
–
–
-
–
-
F5FP060
F6FP060
–
-
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
4
Johnson Controls Unitary Products
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
FURNACE**
COOLING
NET MBH
COIL
MODEL
UNIT MODEL
CFM RANGE
(Min.-max.)
RATED
CFM
W
SEER1
EER
TOTAL
29.0
29.0
29.0
29.0
29.0
29.0
35.0
35.0
35.0
35.0
35.0
42.0
42.0
42.0
42.0
48.0
48.0
48.0
48.0
48.0
57.0
57.0
57.0
57.0
SENS.
21.0
21.0
21.0
21.0
21.0
21.0
24.8
24.8
24.8
24.8
24.8
29.2
29.2
29.2
29.2
34.4
34.4
34.4
34.4
34.4
38.5
38.5
38.5
38.5
800 - 1200
800 - 1200
800 - 1200
800 - 1200
800 - 1200
800 - 1200
1000 - 1400
1000 - 1400
1000 - 1400
1000 - 1400
1000 - 1400
1200 - 1600
1200 - 1600
1200 - 1600
1200 - 1600
1400 - 1800
1400 - 1800
1400 - 1800
1400 - 1800
1400 - 1800
1600 - 2000
1600 - 2000
1600 - 2000
1600 - 2000
14
17,21
14
FC/MC/PC32
FC/MC/PC35
FC/MC/PC37
FC/MC/PC43
HC36
1000
1000
1000
1000
1000
1000
1200
1200
1200
1200
1200
1400
1400
1400
1400
1600
1600
1600
1600
1600
1800
1800
1800
1800
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
TCGD30S4(3,4)S1
17,21
17
21
HC42
14
FC/MC/PC37
FC/MC/PC43
FC/MC/PC48
HC42
17,21
21,24
21
TCGD36S4(3,4)S1
TCGD42S4(3,4)S1
TCGD48S4(3,4)S1
TCGD60S4(3,4)S1
21,24
17,21
21,24
21
UC48
FC/MC/PC43
FC/MC/PC48
HC42
21,24
21,24
21,24
24
UC48
FC/MC/PC48
FC/MC/PC60
HC60
21,24
21,24
21,24
24
UC48
UC60
FC/MC/PC60
FC/MC62
HC60
24
21,24
UC60
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.
Johnson Controls Unitary Products
5
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING CAPACITY - With High Efficiency Motor Furnaces
COOLING
Net MBH
UNIT
MODEL
FURNACE
MODEL
COIL
W
RATED
CFM
MODEL1
SEER
EER
TOTAL
SENS.
13 SEER HP WITH VARIABLE SPEED FURNACES2
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC35C
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
UC48C
14
17
21
21
17
21
14
17
21
21
17
21
21
14
17
21
21
17
21
21
21
21
21
21
24
21
21
21
21
24
17
21
21
17
21
21
21
21
21
21
24
21
21
21
21
24
970
29.2
30.0
30.0
28.8
29.8
29.8
30.0
30.0
28.2
29.6
30.0
30.0
28.2
35.2
35.2
35.2
35.6
35.2
35.4
35.0
35.6
35.8
35.8
35.4
35.4
34.2
34.8
34.6
34.0
34.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
42.0
41.5
42.0
42.0
21.4
22.8
22.8
20.6
22.8
22.4
22.9
22.9
19.3
21.2
22.9
22.9
19.3
25.4
25.4
24.8
25.6
25.4
25.4
24.6
25.2
25.8
25.8
25.0
25.0
24.8
25.4
24.8
24.6
24.6
29.0
29.9
29.5
29.0
29.6
29.6
29.5
30.1
29.3
29.3
29.7
29.4
30.0
29.2
29.4
29.4
13.20
14.00
14.00
14.00
14.00
14.00
13.80
14.00
14.00
14.00
13.80
14.00
14.00
13.30
13.30
14.00
13.80
13.25
13.45
13.55
14.00
14.00
13.70
13.70
13.70
13.50
13.50
13.15
13.25
13.30
13.50
13.50
13.50
13.50
13.30
13.50
13.80
14.00
13.50
13.50
13.50
13.50
13.50
13.30
13.20
13.40
11.00
11.50
12.00
12.00
12.00
12.00
11.50
12.00
12.00
12.00
11.50
12.00
12.00
11.25
11.25
11.50
11.70
11.25
11.40
11.40
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.20
11.20
11.25
11.50
11.50
11.50
11.50
11.00
11.00
11.50
11.50
11.50
11.50
11.50
11.00
11.00
11.00
11.00
11.00
1120
1105
850
1085
1075
1105
1125
710
T*9X*C16
TCGD30S4(3,4)S1
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
870
1095
1055
720
T*9X*C16
T*9X*C20
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
1290
1300
1175
1250
1270
1260
1185
1185
1270
1280
1205
1240
1185
1300
1280
1205
1240
1300
1475
1415
1270
1410
1400
1360
1475
1425
1420
1435
1400
1515
1425
1420
1435
T*9X*C16
T*9X*C20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
TCGD36S4(3,4)S1
T*9X*C20
T*9X*D20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
UC48C
UC48C
T*9X*C20
UC48C
T*9X*D20
UC48D
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
UC48C
T*9X*C16
T*9X*C20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
TCGD42S4(3,4)S1
T*9X*C20
T*9X*D20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
UC48C
UC48C
T*9X*C20
UC48C
T*9X*D20
UC48D
For Notes See Page 7.
6
Johnson Controls Unitary Products
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued)
COOLING
Net MBH
UNIT
MODEL
FURNACE
MODEL
COIL
W
RATED
CFM
MODEL1
SEER
EER
TOTAL
SENS.
13 SEER HP WITH VARIABLE SPEED FURNACES2
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
FC/PC60C
FC/MC/PC60D
FC/PC60C
FC/PC60C
FC/MC/PC60D
FC/PC60C
FC/PC60C
FC/PC60C
FC/MC/PC60D
FC/PC60C
FC/PC60C
FC/MC/PC60D
FC/MC/PC60D
FC/MC62D
UC60C
21
21
21
21
24
21
21
21
21
24
21
21
21
21
21
21
24
21
21
21
21
21
21
24
21
21
1600
1660
1565
1615
1635
1605
1595
1575
1625
1490
1575
1625
1605
1690
1575
1560
1630
1645
1665
1640
1735
1575
1560
1630
1735
1645
48.0
48.0
48.0
48.0
48.0
48.0
48.0
48.0
47.0
47.5
47.0
47.0
56.5
57.0
56.0
56.0
56.5
56.5
57.0
56.0
56.5
56.0
56.0
56.0
56.5
56.0
34.4
34.4
34.8
34.4
34.8
34.6
34.8
34.6
34.6
33.8
33.8
33.8
37.8
37.8
37.8
37.8
37.8
37.8
37.8
37.2
38.5
37.2
37.2
37.2
38.5
37.2
13.30
13.20
13.10
13.20
13.20
13.30
13.30
13.30
13.40
13.20
13.10
13.10
13.50
13.50
13.30
13.30
13.30
13.30
13.50
13.00
13.00
13.00
13.00
13.00
13.00
13.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
T*9X*C20
T*9X*D20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
TCGD48S4(3,4)S1
T*9X*C20
T*9X*D20
T*9X*C16
T*9X*C20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
T*9X*C20
T*9X*D20
T*9X*C20
T*(8,L)X*C20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
TCGD60S4(3,4)S1
UC60D
FC/PC60C
FC/PC60C
UC60D
T*9X*C20
T*9X*D20
T*(8,L)X*C20
T*9X*C20
UC60D
UC60D
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
Johnson Controls Unitary Products
7
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
ACCESSORIES
SOUND POWER RATINGS*
Refer to Price Manual for specific model numbers.
(dBA)
UNIT
MODEL
230V
76
460V
76
OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to
prevent rapid recycling of the compressor.
30
36
76
76
ROOM THERMOSTATS - A wide selection of compatible ther-
mosets are available to provide optimum performance and fea-
tures for any installation.
42
77
76
48
77
77
60
78
78
1H/1C, manual changeover electronic non-programmable ther-
mostat.
* Rated in accordance with ARI 270-95 Standards.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the price
book or consult factory.
TYPICAL INSTALLATION
MINIMUM 18” SERVICE
ACCESS CLEARANCE
ON ONE SIDE
THERMOSTAT
60” OVERHEAD
CLEARANCE
WEATHERPROOF
DISCONNECT
SWITCH
NEC CLASS 1 WIRING
6” CLEARANCE
AROUND PERIMETER
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
NOTE:
ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
CONTROL
ACCESS
PANEL
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
POWER WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
Y R G W
C
*
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
CONTACTOR
TERMINALS
GND.
LUG
*
COIL
Y
R
G
W
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
8
Johnson Controls Unitary Products
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
TGCGD30S4(3,4)S1
FC/MC/PC35
800
IDCFM
1000
75
1200
CONDENSING
ENTERING AIR
TEMPERATURE
ID DB (°F)
80
80
62
75
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
ID WB (°F) 57
62
T.C.
S.C.
KW
28.4 31.4 30.8 33.1 34.4 29.8 31.8 31.4 33.4 34.5 31.2 32.3 32.1 33.7 34.7
28.8 25.8 21.7 21.2 16.0 30.4 28.2 23.6 22.6 17.1 31.9 30.7 25.4 24.0 18.1
65
75
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
T.C.
S.C.
KW
26.4 28.8 28.2 30.9 32.6 27.9 29.7 28.9 31.4 32.8 29.5 30.5 29.6 31.8 32.9
26.9 24.7 20.5 20.3 15.4 28.5 27.1 22.6 22.0 16.4 30.2 29.5 24.6 23.7 17.5
1.8
1.8
1.8
1.9
1.9
1.8
1.8
1.8
1.9
1.9
1.9
1.9
1.9
1.9
1.9
T.C.
S.C.
KW
24.4 26.3 25.6 28.8 30.9 26.0 27.5 26.4 29.3 31.0 27.7 28.7 27.1 29.8 31.2
24.9 23.6 19.4 19.4 14.7 26.6 26.0 21.6 21.4 15.8 28.4 28.4 23.9 23.4 16.8
85
2.0
2.0
2.0
2.0
2.1
2.0
2.0
2.0
2.0
2.1
2.0
2.0
2.0
2.1
2.1
T.C.
S.C.
KW
22.4 23.8 23.0 26.7 29.1 24.2 25.3 23.8 29.0 29.3 26.0 26.9 24.7 27.9 29.4
22.9 22.5 18.2 18.5 14.1 24.8 24.9 20.7 21.2 15.1 26.7 27.3 23.1 23.1 16.2
95
2.1
2.1
2.1
2.2
2.3
2.2
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.2
2.3
T.C.
S.C.
KW
20.5 21.8 20.4 23.7 26.3 22.0 23.1 21.3 24.3 26.4 23.6 24.5 22.1 24.8 26.4
21.0 20.7 17.1 17.4 13.2 22.6 22.7 19.1 19.7 14.3 24.3 24.7 21.0 22.0 15.4
105
115
125
2.3
2.3
2.3
2.4
2.4
2.4
2.4
2.3
2.4
2.5
2.4
2.4
2.3
2.4
2.5
T.C.
S.C.
KW
18.6 19.8 17.9 20.9 23.5 19.9 21.0 18.8 21.4 23.5 21.2 22.2 19.6 21.8 23.6
19.1 18.9 15.9 16.4 12.3 20.5 20.5 17.5 18.6 13.5 22.0 22.2 19.1 20.9 14.7
2.5
2.5
2.4
2.5
2.6
2.5
2.5
2.5
2.5
2.6
2.6
2.6
2.5
2.6
2.6
T.C.
S.C.
KW
16.8 17.9 15.4 18.1 20.7 17.8 18.9 16.2 18.5 20.7 18.9 19.9 17.1 18.8 20.7
17.3 17.2 14.8 15.3 11.4 18.4 18.4 16.0 17.6 12.6 19.6 19.6 17.1 19.8 13.9
2.7
2.7
2.6
2.7
2.8
2.7
2.7
2.6
2.7
2.8
2.7
2.7
2.7
2.7
2.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handlers
–
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.03
1.00
1.00
1.00
1.01
1.01
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.06
1.06
1.00
1.00
1.00
1.03
1.02
KW
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.95
0.95
1.00
1.00
1.00
0.97
0.93
Furnaces
Coils
T.C.
1.01
1.03
1.03
0.99
1.03
1.03
1.03
1.03
0.97
1.02
1.03
1.03
0.97
S.C.
1.02
1.09
1.09
0.98
1.09
1.07
1.09
1.09
0.92
1.01
1.09
1.09
0.92
KW
1.01
0.99
0.95
0.91
0.94
0.94
0.99
0.95
0.89
0.94
0.99
0.95
0.89
FC/MC/PC35
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC35C
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
–
FC/MC/PC37
–
FC/MC/PC43
–
HC36
–
HC42
AHP30
AHP36
AHX30
AHX36
MA12B
MA12B
F4FP040
F6FP030
F6FP036
–
T*9X*C16
–
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
–
–
FC/MC35B
FC/MC43B
–
–
–
T*9X*C16
T*9X*C20
Johnson Controls Unitary Products
9
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
TCGD36S4(3,4)S1
FC/MC/PC43
1000
IDCFM
1200
75
1400
75
CONDENSING
ENTERING AIR
TEMPERATURE
ID DB (°F)
80
80
62
75
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
ID WB (°F) 57
62
62
T.C.
S.C.
KW
34.7 36.1 35.2 37.4 37.3 33.8 35.5 34.8 37.0 37.5 32.9 34.9 34.4 36.6 37.6
34.3 33.0 27.6 25.5 18.4 33.3 31.0 26.2 24.6 18.0 32.3 29.1 24.7 23.6 17.7
65
75
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
1.9
2.0
1.9
2.0
2.0
T.C.
S.C.
KW
33.6 34.7 33.6 35.9 36.6 32.6 33.9 33.2 35.5 36.6 31.5 33.2 32.7 35.1 36.6
33.3 32.5 27.5 25.6 18.6 32.1 30.6 25.8 24.5 18.0 31.0 28.7 24.2 23.3 17.5
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.2
2.2
2.2
2.2
T.C.
S.C.
KW
32.4 33.2 32.0 34.4 35.8 31.3 32.3 31.5 34.1 35.7 30.2 31.5 31.0 33.7 35.5
32.2 32.0 27.3 25.8 18.8 30.9 30.2 25.5 24.3 18.0 29.6 28.3 23.7 22.9 17.3
85
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.3
2.4
2.4
2.4
2.4
T.C.
S.C.
KW
31.3 31.7 30.4 33.0 35.0 30.1 30.7 29.9 35.0 34.8 28.9 29.8 29.4 32.2 34.5
31.1 31.5 27.2 26.0 19.0 29.7 29.7 25.2 24.9 18.0 28.3 27.9 23.2 22.5 17.1
95
2.6
2.6
2.6
2.6
2.7
2.6
2.6
2.6
2.6
2.7
2.5
2.6
2.6
2.6
2.6
T.C.
S.C.
KW
27.9 28.8 27.2 29.8 32.5 27.0 27.8 26.6 29.4 32.2 26.0 26.9 25.9 29.0 31.9
28.7 28.9 25.0 25.0 18.4 27.3 27.2 23.2 23.2 17.3 25.8 25.6 21.5 21.4 16.2
105
115
125
2.8
2.8
2.8
2.8
2.9
2.8
2.8
2.8
2.8
2.9
2.7
2.8
2.7
2.8
2.9
T.C.
S.C.
KW
24.6 26.0 24.2 26.8 30.1 23.9 25.1 23.4 26.3 29.8 23.3 24.1 22.6 25.9 29.5
26.3 26.3 22.8 24.1 17.8 24.9 24.8 21.3 22.2 16.6 23.5 23.3 19.8 20.3 15.4
3.0
3.0
3.0
3.0
3.1
3.0
3.0
2.9
3.0
3.1
2.9
2.9
2.9
3.0
3.1
T.C.
S.C.
KW
21.3 23.2 21.1 23.7 27.6 20.9 22.3 20.2 23.2 27.3 20.5 21.3 19.3 22.7 27.0
23.9 23.8 20.6 23.2 17.2 22.5 22.4 19.4 21.2 15.9 21.1 21.0 18.2 19.2 14.6
3.2
3.2
3.2
3.2
3.4
3.2
3.2
3.1
3.2
3.3
3.1
3.1
3.1
3.2
3.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handlers
–
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.01
1.00
1.00
1.00
1.02
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.02
1.00
1.00
1.00
1.04
KW
1.00
1.00
1.00
1.00
1.00
1.00
0.96
0.94
1.00
1.00
1.00
0.98
Furnaces
Coils
T.C.
1.01
1.01
1.01
1.02
1.01
1.01
1.00
1.02
1.02
1.02
1.01
1.01
0.98
0.99
0.99
0.97
0.97
S.C.
1.02
1.02
1.00
1.03
1.02
1.02
0.99
1.02
1.04
1.04
1.01
1.01
1.00
1.02
1.00
0.99
0.99
KW
0.98
0.98
0.96
0.96
0.98
0.98
0.96
0.97
0.98
0.98
0.97
0.97
0.93
0.95
0.97
0.95
0.95
FC/MC/PC43
T*(8,L)X*A12
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
UC48C
–
FC/MC/PC48
–
HC42
–
UC48
AHP36
AHP42
AHX36
AHX42
MA12B
MA14D
F5FP048
F6FP042
–
–
T*9X*C16
–
T*9X*C20
–
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
FC/MC43B
FC/MC48D
–
–
T*9X*C20
T*9X*D20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
UC48C
UC48C
T*9X*C20
UC48C
T*9X*D20
UC48D
10
Johnson Controls Unitary Products
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
TCGD42S4(3,4)S1
FC/MC/PC43
1200
IDCFM
1400
75
1600
CONDENSING
ENTERING AIR
TEMPERATURE
ID DB (°F)
80
80
62
75
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
ID WB (°F) 57
62
T.C.
S.C.
KW
44.4 45.5 43.6 47.0 48.5 45.9 46.5 45.0 48.5 49.8 47.5 47.5 46.5 50.1 51.1
41.5 35.6 29.7 28.7 21.5 42.9 37.5 31.4 30.2 22.9 44.4 39.4 33.2 31.7 24.3
65
75
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.5
2.5
2.5
2.5
2.6
T.C.
S.C.
KW
42.3 42.9 41.2 45.1 46.6 44.2 44.3 42.7 46.6 47.9 46.0 45.7 44.2 48.1 49.1
39.4 35.2 29.2 28.5 21.3 41.1 37.4 31.1 30.1 22.4 42.9 39.7 33.0 31.8 23.6
2.7
2.7
2.7
2.8
2.8
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.9
T.C.
S.C.
KW
40.2 40.3 38.9 43.3 44.6 42.4 42.1 40.4 44.7 45.9 44.6 43.9 41.9 46.0 47.2
37.2 34.7 28.7 28.2 21.2 39.3 37.3 30.8 30.0 22.0 41.5 40.0 32.9 31.8 22.9
85
3.0
3.0
3.0
3.0
3.1
3.0
3.0
3.0
3.1
3.1
3.0
3.0
3.0
3.1
3.1
T.C.
S.C.
KW
38.2 37.7 36.5 41.5 42.7 40.7 39.9 38.0 42.0 44.0 43.2 42.1 39.6 43.9 45.3
35.0 34.3 28.1 28.0 21.0 37.5 37.3 30.5 29.4 21.6 40.0 40.3 32.8 31.9 22.2
95
3.2
3.2
3.2
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.4
T.C.
S.C.
KW
35.3 34.7 32.8 37.4 38.7 37.5 36.7 34.2 38.6 39.8 39.8 38.8 35.6 39.8 40.9
32.3 32.1 26.5 26.4 19.6 34.5 34.5 28.8 28.4 20.4 36.7 37.0 31.1 30.5 21.2
105
115
125
3.5
3.5
3.5
3.6
3.7
3.5
3.5
3.5
3.6
3.7
3.6
3.6
3.5
3.6
3.7
T.C.
S.C.
KW
32.4 31.7 29.2 33.4 34.8 34.5 33.6 30.5 34.6 35.7 36.5 35.5 31.8 35.7 36.7
29.7 30.0 25.0 24.9 18.2 31.6 31.9 27.2 27.0 19.3 33.5 33.8 29.4 29.1 20.3
3.7
3.7
3.7
3.8
4.0
3.8
3.8
3.7
3.8
4.0
3.8
3.8
3.7
3.9
4.0
T.C.
S.C.
KW
29.6 28.8 25.6 29.4 30.9 31.4 30.5 26.8 30.5 31.7 33.2 32.2 28.0 31.7 32.5
27.1 27.9 23.5 23.4 16.8 28.7 29.3 25.6 25.6 18.1 30.2 30.6 27.6 27.8 19.4
4.0
4.0
3.9
4.0
4.2
4.0
4.0
4.0
4.1
4.3
4.1
4.1
4.0
4.1
4.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handlers
–
Coils
T.C.
1.00
1.00
1.00
0.97
1.00
1.00
1.00
1.00
1.00
1.00
0.99
S.C.
1.00
1.00
1.00
1.00
1.02
1.00
1.00
1.00
1.00
1.03
1.01
KW
1.00
1.00
1.00
0.97
0.92
1.00
1.00
1.00
1.00
0.94
0.93
Furnaces
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.99
1.00
1.00
S.C.
0.99
1.02
1.01
0.99
1.02
1.02
1.01
1.03
1.00
1.00
1.02
1.01
1.03
1.00
1.01
1.01
KW
0.96
0.96
0.96
0.96
1.00
1.00
0.96
0.96
0.96
0.96
0.96
1.00
1.00
0.99
1.00
1.00
FC/MC/PC48
T*(8,L)X*B12
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*B12
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
UC48C
–
HC42
–
UC48
AHP42
AHX42
MA16C
MA14D
MA16C
F5FP048
F6FP042
F6FP048
–
–
T*9X*C16
FC/MC43C
T*9X*C20
FC/MC48D
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
FC/MC48C
–
–
–
T*9X*C20
T*9X*D20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
UC48C
UC48C
T*9X*C20
UC48C
T*9X*D20
UC48D
Johnson Controls Unitary Products
11
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
TCGD48S4(3,4)S1
FC/MC/PC48
1400
IDCFM
1600
75
1800
75
CONDENSING
ENTERING AIR
TEMPERATURE
ID DB (°F)
80
80
62
75
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
ID WB (°F) 57
62
62
T.C.
S.C.
KW
49.7 51.4 50.6 55.8 54.6 52.0 53.1 51.9 56.4 55.4 54.4 54.7 53.2 56.9 56.3
47.2 43.1 35.9 36.0 26.1 49.2 45.9 38.2 37.4 27.6 51.2 48.7 40.4 38.8 29.0
65
75
2.7
2.8
2.8
2.8
2.8
2.7
2.8
2.8
2.8
2.8
2.7
2.8
2.8
2.8
2.9
T.C.
S.C.
KW
47.5 48.6 47.7 52.9 52.4 49.8 50.3 48.9 53.6 53.1 52.0 52.1 50.2 54.3 53.8
44.9 42.0 35.0 34.9 25.4 47.0 44.8 37.1 36.5 26.8 49.0 47.6 39.3 38.2 28.1
3.0
3.0
3.0
3.1
3.1
3.0
3.0
3.0
3.1
3.2
3.0
3.0
3.0
3.1
3.2
T.C.
S.C.
KW
45.4 45.8 44.8 49.9 50.2 47.5 47.6 46.0 50.8 50.8 49.7 49.4 47.1 51.7 51.4
42.7 41.0 34.0 33.8 24.8 44.7 43.7 36.1 35.7 26.0 46.8 46.5 38.2 37.6 27.2
85
3.2
3.3
3.3
3.4
3.4
3.3
3.3
3.3
3.4
3.5
3.3
3.3
3.3
3.4
3.5
T.C.
S.C.
KW
43.2 42.9 42.0 47.0 47.9 45.3 44.9 43.1 48.0 48.4 47.4 46.8 44.1 49.1 48.9
40.4 39.9 33.0 32.7 24.1 42.4 42.6 35.1 34.6 25.2 44.5 45.4 37.1 37.0 26.3
95
3.5
3.5
3.5
3.6
3.7
3.6
3.6
3.5
3.7
3.8
3.6
3.6
3.6
3.7
3.8
T.C.
S.C.
KW
39.8 39.4 37.3 42.4 43.6 41.6 41.1 38.4 43.4 44.0 43.5 42.9 39.5 44.4 44.5
37.1 37.0 30.9 30.9 22.9 38.9 39.3 32.9 33.0 23.9 40.8 41.5 34.9 35.1 25.0
105
115
125
3.8
3.8
3.8
3.9
4.0
3.9
3.9
3.8
3.9
4.1
3.9
3.9
3.8
4.0
4.1
T.C.
S.C.
KW
36.5 35.9 32.7 38.0 39.3 38.1 37.5 33.9 38.9 39.8 39.7 39.1 35.1 39.8 40.2
33.9 34.2 28.9 29.2 21.6 35.5 36.0 30.9 31.3 22.7 37.2 37.7 32.8 33.3 23.8
4.1
4.1
4.0
4.2
4.3
4.1
4.1
4.1
4.2
4.4
4.2
4.2
4.1
4.2
4.4
T.C.
S.C.
KW
33.1 32.4 28.1 33.5 35.1 34.5 33.8 29.4 34.4 35.5 35.9 35.3 30.6 35.2 36.0
30.7 31.4 26.9 27.5 20.4 32.1 32.7 28.8 29.6 21.5 33.5 34.0 30.7 31.6 22.5
4.4
4.4
4.3
4.4
4.6
4.4
4.4
4.3
4.5
4.7
4.5
4.5
4.4
4.5
4.7
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handlers
–
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.98
S.C.
1.00
1.00
1.00
1.00
1.00
1.01
1.03
1.00
1.00
1.00
1.00
1.00
1.00
1.01
KW
1.00
1.00
1.00
1.00
1.00
1.00
0.96
1.00
1.00
1.00
1.00
1.00
1.00
0.95
Furnaces
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.98
0.99
0.98
0.98
S.C.
1.00
1.00
1.01
1.00
1.01
1.01
1.01
1.01
1.01
0.98
0.98
0.98
KW
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.98
0.99
0.98
0.98
FC/MC/PC60
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
FC/PC60C
–
HC60
–
UC48
–
UC60
T*9X*C20
AHP/SHP48
AHP/SHP60
AHX48
MA16C
MA20D
MA16C
MA20D
F5FP048
F5FP060
F6FP048
–
T*9X*D20
–
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
–
FC/MC/PC60D
FC/PC60C
FC/MC48C
FC/MC48D
T*9X*C20
FC/PC60C
FC60C
T*9X*D20
FC/MC/PC60D
FC/PC60C
FC/MC60D
T*9X*C16
–
–
–
T*9X*C20
FC/PC60C
12
Johnson Controls Unitary Products
Download from Www.Somanuals.com. All Manuals Search And Download.
415571-UTG-C-0309
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
TCGD60S4(3,4)S1
FC/MC/PC60
1400
IDCFM
1600
75
1800
CONDENSING
ENTERING AIR
TEMPERATURE
ID DB (°F)
80
80
62
75
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
ID WB (°F) 57
62
T.C.
S.C.
KW
55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8
54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6
65
75
3.0
3.0
3.0
3.1
3.1
3.0
3.0
3.0
3.1
3.1
3.0
3.1
3.0
3.1
3.1
T.C.
S.C.
KW
56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0
53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5
3.4
3.5
3.5
3.5
3.6
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
T.C.
S.C.
KW
58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1
53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4
85
3.9
3.9
3.9
3.9
4.0
3.9
3.9
3.9
3.9
4.0
3.9
3.9
3.9
3.9
4.0
T.C.
S.C.
KW
59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2
52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4
95
4.3
4.3
4.3
4.4
4.5
4.3
4.3
4.3
4.4
4.4
4.3
4.3
4.3
4.4
4.4
T.C.
S.C.
KW
56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4
49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0
105
115
125
4.9
4.9
4.9
4.9
5.0
4.9
4.9
4.9
5.0
5.0
4.9
4.9
4.9
5.0
5.0
T.C.
S.C.
KW
53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6
47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6
5.5
5.4
5.4
5.5
5.6
5.5
5.5
5.4
5.5
5.6
5.4
5.5
5.4
5.5
5.6
T.C.
S.C.
KW
51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8
44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2
6.1
6.0
5.9
6.1
6.2
6.0
6.0
6.0
6.1
6.2
6.0
6.0
6.0
6.1
6.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handlers
–
Coils
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
KW
1.00
1.00
1.00
1.00
0.98
1.00
1.00
1.00
0.96
Furnaces
Coils
T.C.
0.99
1.00
0.98
0.98
0.99
0.99
1.00
0.98
0.99
0.98
0.98
0.98
0.99
0.98
S.C.
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.97
1.00
0.97
0.97
0.97
1.00
0.97
KW
0.99
1.00
0.98
0.98
0.99
0.99
1.00
0.98
0.99
0.98
0.98
0.98
0.99
0.98
FC/MC62
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
FC/PC60C
FC/MC/PC60D
FC/PC60C
FC/PC60C
FC/MC/PC60D
FC/MC/PC60D
FC/MC62D
UC60C
–
HC60
–
UC60
AHP/SHP60
AHX60
MA20D
MA20D
F5FP060
F6FP060
–
T*9X*C20
–
T*9X*D20
FC/MC60D
T*9X*C20
FC/MC62D
T*(8,L)X*C20
T*(8,L)X*C16
T*(8,L)X*C20
T*9X*C16
–
–
UC60D
FC/PC60C
FC/PC60C
UC60D
T*9X*C20
T*9X*D20
T*(8,L)X*C20
T*9X*C20
UC60D
UC60D
Johnson Controls Unitary Products
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Subject to change without notice. Printed in U.S.A.
Copyright © 2009 by Johnson Controls, Inc. All rights reserved.
415571-UTG-C-0309
Supersedes 415571-UTG-B-0708
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Download from Www.Somanuals.com. All Manuals Search And Download.
|