| 
			
			
				
					R-410A   MODELS: PC090 Thru 240   PD180 Thru 240   7.5 - 20 Ton   60 Hertz   TABLE OF CONTENTS   Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   Crankcase Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17   Heating Sequence of Operation . . . . . . . . . . . . . . . . . . . . 20   LIST OF TABLES   1 5 PC090 - 240 and PD180 - 240 Physical Data. . . . . . . . . . 4   Electrical Data - Outdoor Unit - HP Without Powered   11 PD180 thru 240 Unit Control Board Flash Codes. . . . . . 22   6 Electrical Data - Outdoor Unit - HP With Powered   LIST OF FIGURES   3 9 Fan Orientation, Control Box End . . . . . . . . . . . . . . . . . 21   Typical Field Wiring Diagram - NC090 Air Handling Unit   Typical Field Wiring Diagram - NC120 thru 240 Evaporator   4 6 Typical Field Wiring Diagram - ND180 thru 240   PC/PD180 & PC/PD240 Unit Dimensions and Piping   8 430645-YIM-D-0610   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Safety Considerations   Reference   Installer should pay particular attention to the words: NOTE,   CAUTION, and WARNING. Notes are intended to clarify or   make the installation easier. Cautions are given to prevent   equipment damage. Warnings are given to alert installer that   personal injury and/or equipment damage may result if   installation procedure is not handled properly.   This instruction covers the installation and operation of the   basic condensing unit. For refrigerant piping installation   instructions refer to document 247077 “Application Data -   General Piping Recommendations for Split System Air   Conditioning and Heat Pumps”. For information on the   installation and operation of the evaporator blower units, refer   to Instruction Manual No. 508526.   All accessories come with a separate Installation Manual.   Renewal Parts   Improper installation may create a condition where the   operation of the product could cause personal injury or   property damage. Improper installation, adjustment,   alteration, service or maintenance can cause injury or   property damage. Refer to this manual for assistance or   for additional information, consult a qualified contractor,   installer or service agency.   Contact your local Source 1 Center for authorized replacement   parts.   Agency Approvals   Design certified by CSA as follows:   1. For use as a cooling/heating unit.   2. For outdoor installation only.   Before performing service or maintenance operations on   unit, turn off main power switch to unit. Electrical shock   could cause personal injury. Improper installation,   adjustment, alteration, service or maintenance can   cause injury or property damage. Refer to this manual.   For assistance or additional information consult a   qualified installer, service agency or the gas supplier.   Inspection   As soon as a unit is received, it should be inspected for possible   damage during transit. If damage is evident, the extent of the   damage should be noted on the carrier’s freight bill. A separate   request for inspection by the carrier’s agent should be made in   writing.   This product must be installed in strict compliance with   the enclosed installation instructions and any applicable   local, state and national codes including, but not limited   to, building, electrical, and mechanical codes.   This system uses R-410A Refrigerant which operates at   higher pressures than R-22. No other refrigerant may be   used in this system. Gage sets, hoses, refrigerant   containers and recovery systems must be designed to   handle R-410A. If you are unsure, consult the   equipment manufacturer. Failure to use R-410A   compatible servicing equipment may result in property   damage or injury.   Johnson Controls Unitary Products   3 Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Physical Data   Table 1: PC090 - 240 and PD180 - 240 Physical Data   Models   Component   PC090   PC120   10   PC180   15   PD180   15   PC240   20   PD240   20   Nominal Tonnage   REFRIGERANT   Refrigerant type   Holding charge (lb)   7.5   R-410A   1.0   R-410A   1.0   R-410A   1.0   R-410A   1.0   R-410A   1.0   R-410A   1.0   1 System #1   System #2   23.9   ---   27.5   ---   54.0   ---   27.0   60.0   ---   34.0   2 Operating Charge (lb)   27.0   34.0   DIMENSIONS (inches)   WEIGHTS (lb)   Length   Width   59.1   31.9   44.5   59.1   31.9   50.0   59.1   64.1   44.5   59.1   64.1   44.5   59.1   64.1   50.0   59.1   64.1   50.0   Height   Shipping   421   430   543   574   947   968   921   942   1116   1152   1090   1126   Operating   3 COMPRESSORS   Type   Single Scroll   1 Tandem Scroll Tandem Scroll   Single Scroll   2 Tandem Scroll   1 Single Scroll   2 Quantity   Cooling   1 1 System #1   System #2   System #1   System #2   7.5   ---   1 10   ---   2 15   ---   2 7.5   7.5   1 20   ---   2 10   10   1 Nominal Capacity (Tons)   Capacity Stages   ---   ---   ---   1 ---   1 Heating   Nominal Capacity (Tons)   Capacity Stages   System #1 & #2   System #1 & #2   7.5   1 10   1 15   1 15   1 20   1 20   1 SYSTEM DATA   No. Refrigeration Circuits   Suction Line OD (in.)   Liquid Line OD (in.)   1 1 1 2 1 2 1 1/8   5/8   1 3/8   7/8   1 5/8   7/8   1 3/8   5/8   1 5/8   7/8   1 3/8   7/8   OUTDOOR COIL DATA   Face area (Sq. Ft.)   23.8   2 29.0   2 47.5   2 47.5   2 58.1   2 58.1   2 Rows   Fins per inch   20   20   20   20   20   20   Tube diameter (in./MM)   Circuitry Type   Refrigerant Control   0.38 / 10   Interlaced   TXV   0.38 / 10   Interlaced   TXV   0.38 / 10   Interlaced   TXV   0.38 / 10   Interlaced   TXV   0.38 / 10   Interlaced   TXV   0.38 / 10   Interlaced   TXV   CONDENSER FAN DATA   No. Fans / Diameter (in.)   Type   2/24   Axial   Direct   1 2/24   Axial   Direct   1 4/24   Axial   Direct   1 4/24   Axial   Direct   1 4/24   Axial   Direct   1 4/24   Axial   Direct   1 Drive type   No. speeds   System #1   System #2   2 2 4 2 4 2 Number of motors   Motor HP (ea.)   ---   ---   ---   2 ---   2 1/3   3/4   1/3   1/3   3/4   3/4   4 Rotation   CW   850   7500   ---   CW   1100   9800   ---   CW   850   15000   ---   CW   850   7500   7500   CW   1100   19600   ---   CW   1100   9800   9800   RPM   System #1   System #2   Nominal CFM   1. Holding Charge is the amount in the unit as shipped from the factory.   2. Includes matched evaporator unit with 25 ft of piping.   3. All Compressors include crankcase heater.   4. When viewing the shaft end of the motor.   4 Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   3. The heat pump and the evaporator should be positioned to   minimize the number of bends in the refrigerant piping.   Table 2: Unit Application Data   208/230-3-60   187/252   432/504   540/630   4. The heat pump should be as close to the evaporator as   practical.   1 Voltage Variation   Min. / Max.   460-3-60   575-3-60   5. The heat pump should not be installed where normal   operating sounds may be objectionable.   Ambient Air on Condenser Coil   40°F/125°F   2 6. The evaporator should be located within the building, either   outside or inside the conditioned space.   Min. /Max.   Suction Pressure at Compressor and   Corresponding Temp. at Saturation   Min. / Max.   101.6 psig / 156.6 psig   32.0 ºF / 55.0 ºF   Rooftop Locations   Be careful not to damage the roof. Consult the building   contractor or architect if the roof is bonded. Choose a location   with adequate structural strength to support the unit.   1.Utilization range “A” in accordance with ARI Standard 110.   2.These units can operate in an ambient temperature of   125°F providing the wet bulb temperature of the air enter-   ing the evaporator coil does not exceed 67°F. Unit can   operate to 0°F if equipped with a low ambient kit.   The heat pump must be mounted on level supports. The   supports can be channel iron beams or wooden beams treated   to reduce deterioration.   Installation   Minimums of two (2) beams are required to support each unit.   The beams should: (1) be positioned perpendicular to the roof   joists. (2) Extend beyond the dimensions of the section to   distribute the load on the roof. (3) Be capable of adequately   supporting the concentrated loads at the corners. These beams   can usually be set directly on the roof. Flashing is not required.   Limitations   These units must be installed in accordance with all national   and local safety codes. If no local codes apply, installation must   conform to the appropriate national codes. Units are designed   to meet National Safety Code Standards. If components are to   be added to a unit to meet local codes, they are to be installed   at the dealer's and/or the customer's expense.   NOTE: On bonded roofs, check for special installation   requirements.   Ground Level Locations   Location   It is important that the units be installed on a substantial base   that will not settle, causing strain on the refrigerant lines and   possible leaks. A one-piece concrete slab with footers that   extend below the frost line is recommended. The slab should   not be tied to the building foundation, as noise will telegraph   through the slab.   Use the following guidelines to select a suitable location for   both the condensing unit and the evaporator.   1. The heat pump is designed for outdoor installation only.   2. The condenser fans are the propeller type and are not   suitable for use with ductwork in the condenser air stream.   Johnson Controls Unitary Products   5 Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Table 3: Corner Weights & Center of Gravity   Weight (lbs.)   Model   Center of Gravity (in.)   4 Point Load Location (lbs.)   Shipping   421   Operating   430   X Y A B C D 87   PC090   PC120   PC180   PD180   PC240   PD240   17.3   16.4   32.5   34   32.1   31.2   33   32.3   33   32.5   30.8   31.8   110   153   266   243   300   311   130   161   274   275   301   295   103   134   217   225   276   253   543   947   921   1116   1090   574   968   942   1152   1126   127   211   199   275   267   LEFT   A D LEFT   DIM X   A B D C CG   DIM X   CG   FRONT   FRONT   REAR   REAR   WIDTH   WIDTH   DIM Y   LENGTH   RIGHT   PC090, PC120   B C DIM Y   LENGTH   RIGHT   PC180, PD180,   PC240, PD240   Figure 1: Corner Weights & Center Of Gravity   NOTE: Front of unit is considered the side having the control   Holes are provided in the base rails for bolting the unit to its   foundation.   box.   Concrete piers can also support ground level units. These piers   should (1) extend below the frost line, (2) be located under each   of the section's four corners, and (3) be sized to carry the load   of the corner it supports.   For ground level installations, precautions should be taken to   protect the unit from tampering and unauthorized persons from   injury. Screws on access panels will prevent casual tampering.   Further safety precautions such as a fenced enclosure or   locking devices on the panels may be advisable. Check local   authorities for safety regulations.   On either rooftop or ground level installations, rubber padding   can be applied under the unit to lessen any transmission of   vibration.   6 Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.   Clearances   The unit must be installed with sufficient clearance for air to   enter the condenser coils, for air discharge and for servicing   Spreaders, longer than the largest dimension across the   unit must be used across the top of the unit.   NOTE: Additional clearance is required to remove the   compressors out the back of the unit.   Table 4: Minimum Clearances   Clearance Description   Distance in Inches   Overhead (Top)   Front   120   36   36   30   30   0 Before lifting a unit, make sure that its weight is   distributed equally on the cables so that it will lift evenly.   Rear   Left Side   Right Side   1 Bottom   1.In all installations where snow accumulates and winter oper-   ation is expected, additional height must be provided to   insure normal condenser airflow.   Do not permit overhanging structures or shrubs to   obstruct condenser air discharge.   Rigging   Exercise care when moving the unit. Do not remove any   packaging until the unit is near the place of installation. Rig the   unit by attaching chain or cable slings to the lifting holes   provided in the base rails. Spreader bars, whose length   exceeds the largest dimension across the unit, MUST be used   across the top of the unit.   Figure 2: Typical Rigging   The unit may be moved or lifted with a forklift. Slotted openings   in the base rails are provided for this purpose.   Johnson Controls Unitary Products   7 Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Power Wiring   Check the available power and the unit nameplate for correct   voltage. Run the necessary number of properly sized wires to   the unit. Provide a disconnect switch (if not included with the   unit) and fusing as required (Factory disconnect is a fused   disconnect /breaker). Route the conduit through the large   knockout located near the electrical box. See Table 5 for   Electrical Data.   Do not leave the system open to the atmosphere. Unit   damage could occur due to moisture being absorbed by   the POE oil in the system. This type of oil is highly   susceptible to moisture absorption   POE (polyolester) compressor lubricants are known to cause   long term damage to some synthetic roofing materials.   The disconnect switch may be bolted to the side of the unit but   not to any of the removable panels; which would interfere with   access to the unit. Make sure that no refrigerant lines will be   punctured when mounting the disconnect switch, and note that   it must be suitable for outdoor installation.   Exposure, even if immediately cleaned up, may cause   embrittlement (leading to cracking) to occur in one year   or more. When performing any service that may risk   exposure of compressor oil to the roof, take precautions   to protect roofing.   All power and control wiring must be in accordance   with National and Local electrical codes.   Procedures which risk oil leakage include, but are not limited to,   compressor replacement, repairing refrigerant leaks, replacing   refrigerant components such as filter drier, pressure switch,   metering device or coil.   Control Wiring   Route the necessary low voltage control wires from the   Simplicity™ control board to the thermostat and also between   the terminal blocks inside the heat pump and evaporator control   boxes. Refer to Figures 3 thru 6 for field wiring diagrams.   The unit is shipped with compressor mounting bolts which are   factory adjusted and ready for operation.   Compressors   The scroll compressors used in this product are specifically   designed to operate with R-410A Refrigerant and cannot be   interchanged.   Do not loosen compressor mounting bolts.   Phasing   Three-phase, scroll compressors operate in only one direction.   If the scroll is drawing low amperage, has similar suction and   discharge pressures, or is producing a high noise level, the   scroll is misphased. Change the incoming line connection   phasing to obtain the proper rotation.   This system uses R-410A Refrigerant which operates at   higher pressures than R-22. No other refrigerant may be   used in this system.   The compressor also uses a polyolester (POE oil), Mobil 3MA   POE. This oil is extremely hydroscopic, meaning it absorbs   water readily. POE oil can absorb 15 times as much water as   other oils designed for HCFC and CFC refrigerants. Take all   necessary precautions to avoid exposure of the oil to the   atmosphere.   Scroll compressors require proper rotation to operate   properly. Failure to check and correct rotation may result   in property damage.   8 Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Electrical Data   Table 5: Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet   Compressors   Outdoor Fan Motor   Pwr Conv Outlet   Minimum   Maximum   Fuse Size   (A)   Model   Circuit   Ampacity   Power   RLA   Qty   MCC   LRA   Power   FLA   (each)   1 2 HP Qty   FLA   Supply   (each) (each) (each)   Supply   208/230-1-60   460-1-60   208/230-3-60   460-3-60   1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 25.0   12.2   9.0   39   19   164   100   78   1/3   1/3   1/3   3/4   3/4   3/4   1/3   1/3   1/3   1/3   1/3   1/3   3/4   3/4   3/4   3/4   3/4   3/4   2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 4 2.1   1.2   0.9   3.0   1.6   1.4   2.1   1.2   0.9   2.1   1.2   0.9   3.0   1.6   1.4   3.0   1.6   1.4   - - - - - - - - - - - - - - - - - - 35.5   17.6   13.1   46.8   23.5   18.0   64.7   32.2   24.0   64.7   32.2   24.0   79.8   44.0   32.9   79.8   44.0   32.9   45   25   20   60   30   20   80   40   30   80   40   30   100   60   45   100   60   45   PC090   575-3-60   14   575-1-60   208/230-3-60   460-3-60   18.1   9.0   28.3   14.0   10.6   39   137   62   208/230-1-60   460-1-60   PC120   PC180   PD180   PC240   PD240   575-3-60   6.8   50   575-1-60   208/230-3-60   460-3-60   25.0   12.2   9.0   164   100   78   208/230-1-60   460-1-60   19   575-3-60   14   575-1-60   208/230-3-60   460-3-60   25.0   12.2   9.0   39   164   100   78   208/230-1-60   460-1-60   19   575-3-60   14   575-1-60   208/230-3-60   460-3-60   30.1   16.7   12.2   30.1   16.7   12.2   47   225   114   80   208/230-1-60   460-1-60   26   575-3-60   19   575-1-60   208/230-3-60   460-3-60   47   225   114   80   208/230-1-60   460-1-60   26   575-3-60   19   575-1-60   1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.   2. Maximum fuse or maximum circuit breaker (HACR type per NEC).   Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.   Table 6: Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet   Compressors   Outdoor Fan Motor   Pwr Conv Outlet   FLA   Minimum   Circuit   Ampacity   Maximum   Fuse Size   (A)   Model   Power   RLA   Qty   MCC   LRA   Power   FLA   (each)   1 2 HP Qty   Supply   (each) (each) (each)   Supply   208/230-1-60   460-1-60   208/230-3-60   460-3-60   1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 25.0   12.2   9.0   39   19   164   100   78   1/3   1/3   1/3   3/4   3/4   3/4   1/3   1/3   1/3   1/3   1/3   1/3   3/4   3/4   3/4   3/4   3/4   3/4   2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 4 2.1   1.2   0.9   3.0   1.6   1.4   2.1   1.2   0.9   2.1   1.2   0.9   3.0   1.6   1.4   3.0   1.6   1.4   10.0   5.0   45.5   22.6   17.1   56.8   28.5   22.0   74.7   37.2   28.0   74.7   37.2   28.0   89.8   49.0   36.9   89.8   49.0   36.9   60   30   25   70   35   25   90   45   35   90   45   35   110   60   45   110   60   45   PC090   575-3-60   14   575-1-60   4.0   208/230-3-60   460-3-60   18.1   9.0   28.3   14.0   10.6   39   137   62   208/230-1-60   460-1-60   10.0   5.0   PC120   PC180   PD180   PC240   PD240   575-3-60   6.8   50   575-1-60   4.0   208/230-3-60   460-3-60   25.0   12.2   9.0   164   100   78   208/230-1-60   460-1-60   10.0   5.0   19   575-3-60   14   575-1-60   4.0   208/230-3-60   460-3-60   25.0   12.2   9.0   39   164   100   78   208/230-1-60   460-1-60   10.0   5.0   19   575-3-60   14   575-1-60   4.0   208/230-3-60   460-3-60   30.1   16.7   12.2   30.1   16.7   12.2   47   225   114   80   208/230-1-60   460-1-60   10.0   5.0   26   575-3-60   19   575-1-60   4.0   208/230-3-60   460-3-60   47   225   114   80   208/230-1-60   460-1-60   10.0   5.0   26   575-3-60   19   575-1-60   4.0   1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.   2. Maximum fuse or maximum circuit breaker (HACR type per NEC).   Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.   Johnson Controls Unitary Products   9 Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Take Adequate Precautions   Refrigerant Mains   Many service problems can be avoided by taking adequate   precautions to provide an internally clean and dry system and   by using procedures and materials that conform to established   standards.   This Split-System (Air Condensing / Heat Pump / Air   Handling) unit is one component of an entire system. As   such it requires specific application considerations with   regard to the rest of the system (air handling unit, duct   design, condensing unit, refrigerant piping and control   scheme).   Use hard drawn copper tubing where no appreciable amount of   bending around pipes or other obstructions is necessary. If soft   copper is used, care should be taken to avoid sharp bends that   may cause a restriction. Pack fiberglass insulation and a   sealing material such as permagum around refrigerant lines   where they penetrate a wall to reduce vibrations and to retain   some flexibility.   Failure to properly apply this equipment with the rest of   the system may result in premature failure and/or   reduced performance / increased costs. Warranty   coverage specifically excludes failures due to improper   application and Unitary Products specifically disclaims   any liability resulting from improper application.   Support all tubing at minimum intervals with suitable hangers,   brackets or clamps.   Braze all copper-to-copper joints with Silfos-5 or equivalent   brazing material. Do not use soft solder. Insulate all suction   lines with a minimum of 1/2" ARMAFLEX or equivalent that   meets local codes. Liquid lines exposed to direct sunlight and/   or high temperatures must also be insulated. Never solder   suction and liquid lines together. They can be taped together for   convenience and support purposes, but they must be   completely insulated from each other.   Please refer to the equipment Technical Guide,   Installation Manual and the piping applications bulletin   247077 or call the applications department for Unitary   Products @ 1-877-UPG-SERV for guidance.   Line Sizing   When sizing refrigerant pipe for a split-system air conditioner,   check the following:   The liquid and suction service ports on the condenser section   permit leak testing, evacuation, and partial charging of the field   piping and the evaporator without disturbing refrigerant stored   in the condenser during initial installation.   1. Suction line pressure drop due to friction.   2. Liquid line pressure drop due to friction.   3. Suction line velocity for oil return.   Before beginning installation of the main lines, be sure that the   evaporator section has not developed a leak in transit. Check   pressure at the Schrader valve located on the header of each   coil. If pressure still exists in the system, it can be assumed to   be leak free. If pressure DOES NOT exist the section will need   to be repaired before evacuation and charging is performed.   4. Liquid line pressure drop due to vertical rise. For certain   piping arrangements, different sizes of suction line pipe   may have to be used. The velocity of the refrigerant vapor   must always be great enough to carry the oil back to the   compressor.   A bi-flow solid core filter-drier MUST be field-installed in the   liquid line of every system to prevent dirt and moisture from   damaging the system. Properly sized filter-driers are shipped   with each condensing section.   5. Evaporator Located Below Condenser - On a split   system where the evaporator blower is located below the   condenser, the suction line must be sized for both pressure   drop and for oil return.   NOTE: Installing a filter-drier does not eliminate the need for   6. Condenser Located Below Evaporator - When the   condenser is located below the evaporator blower, the   liquid line must be designed for the pressure drop due to   both friction loss and vertical rise. If the pressure drop due   to vertical rise and friction exceeds 60 psi, some refrigerant   will flash before it reaches the thermal expansion valve.   the proper evacuation of a system before it is charged.   A field-installed moisture indicating sight-glass should be   installed in the liquid line(s) between the filter-drier and the   evaporator coil. The moisture indicating sight-glass can be used   to check for excess moisture in the system.   Flash gas:   Both condenser and evaporator sections have copper sealing   disks brazed over the end of liquid and suction connections.   The temperature required to make or break a brazed joint is   high enough to cause oxidation of the copper unless an inert   atmosphere is provided.   1. Increases the liquid line pressure loss due to friction that in   turn causes further flashing.   2. Reduces the capacity of the refrigerant control device   which starves the evaporator.   NOTE: Dry nitrogen should flow through the system at all times   when heat is being applied and until the joint has   cooled. The flow of nitrogen will prevent oxidation of the   copper lines during installation.   3. Erodes the seat of the refrigerant control device.   4. Causes erratic control of the refrigerant entering the   evaporator.   10   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Always punch a small hole in sealing disks before unbrazing to   prevent the pressure in the line from blowing them off. Do not   use a drill as copper shavings can enter system.   suction sealing disks and prepare the joints for connections of   the main lines.   Connect the main liquid line to the liquid line connection on the   evaporator section, while maintaining a flow of nitrogen.   NOTE: Solenoid and hot gas bypass valves (if used) should be   opened manually or electrically during brazing or   evacuating.   Make the suction line connection at the evaporator and run the   line to the heat pump. Connect the main suction line to the   suction line service valve connection, while maintaining a flow   of nitrogen. Cool the valve body and replace the Schrader valve   stem in the service port.   NOTE: Schrader valves located on unit service valves should   have their stems removed during brazing to prevent   damage to the valve and reduce system evacuation   time.   Once the brazing process is complete, leak testing should be   done on all interconnecting piping and the evaporator before   proper evacuation to below 500 microns is performed.   Start Installation   Start the installation of main lines at the heat pump. Verify   holding charge in unit by cracking open valve. If pressure is   present, close valve and proceed with installation. If no   pressure is present, check system for leaks.   Verify evacuation with micron guage or thermocouple. Once the   line set and evaporator section is properly evacuated, the   service valves can be opened and the heat pump is now ready   to charge with the appropriate weight of refrigerant. Calculate   the correct system charge for the outdoor unit, the indoor unit   and the field line set.   Verify all service valves are fully seated by screwing the stems   of both valves down into the valve bodies until they stop.   Remove the Schrader valve stem and connect a low-pressure   nitrogen source to the service port on the suction line valve   body. Punch a small hole in the sealing disk; the flow of   nitrogen will prevent any debris from entering the system. Wrap   the valve body with a wet rag to prevent overheating during the   brazing process. Overheating the valve will damage the valve   seals. Unbraze the sealing disk, cool the valve body and   prepare the joint for connections of the main lines. Repeat for   the liquid line valve body.   Charge the system by introducing liquid refrigerant into the   liquid line through the liquid port connection. Complete adding   the refrigerant in vapor form into the suction port when the   compressor is started.   The correct refrigerant pressures are indicated as shown in   This system uses R-410A Refrigerant which operates at   higher pressures than R-22. No other refrigerant may be   used in this system. Gage sets, hoses, refrigerant   containers and recovery systems must be designed to   handle R-410A. If you are unsure, consult the   equipment manufacturer. Failure to use R-410A   compatible servicing equipment may result in property   damage or injury.   Never remove a cap from an access port unless the   valve is fully back-seated with its valve stem in the   maximum counter-clockwise position because the   refrigerant charge will be lost. Always use a refrigeration   valve wrench to open and close these service valves.   Connect the main liquid line to the liquid line service valve   connection, while maintaining a flow of nitrogen. Cool the valve   body and replace the Schrader valve stem in the service port.   Install the liquid line from the heat pump to the evaporator liquid   connection, maintaining a flow of nitrogen during all brazing   operations.   Wear safety glasses and gloves when handling   refrigerants. Failure to follow this warning can cause   serious personal injury.   The filter-drier and sight glass must be located in the liquid line,   leaving the O.D. unit.   NOTE: This instruction covers the installation and operation of   the basic heat pump. For refrigerant piping installation   instructions refer to document 247077 "Application   Data - General Piping Recommendations for Split   System Air Conditioning and Heat Pumps".   Connect a low-pressure nitrogen source to the Schrader valve   located on the evaporator section coil headers. Punch a small   hole in the sealing disks, the flow of nitrogen will prevent any   debris from entering the system. Unbraze both liquid and   Johnson Controls Unitary Products   11   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   NOTE: Do not use a heat pump thermostat.   Y1   G W1 W2   R C THERMOSTAT   SINGLE STAGE COOLING   TWO STAGE HEATING   NOTE: Liquid line solenoid is not included or required   on 7.5 Ton Single Stage Units.   Figure 3: Typical Field Wiring Diagram - NC090 Air Handling Unit With PC090 Heat Pump   12   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   NOTE: Do not use a heat pump thermostat.   Y1   Y2   W1 W2   R C G THERMOSTAT   TWO STAGE COOLING   TWO STAGE HEATING   NOTE: Liquid line solenoid is only activated during   second stage cooling operation.   Figure 4: Typical Field Wiring Diagram - NC120 thru 240 Evaporator Unit with PC120 thru 240 Heat Pump   VALVE SYS 2   218 / BR   219 / Y   BLK   1LLS   BLK   Figure 5: NC120 - 240 Liquid Line Solenoid Wiring   Johnson Controls Unitary Products   13   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   NOTE: Do not use a heat pump thermostat.   Y1   Y2   W1 W2   R C G THERMOSTAT   TWO STAGE COOLING   TWO STAGE HEATING   NOTE: Liquid line solenoid is not included or required   on any 4 pipe units.   Figure 6: Typical Field Wiring Diagram - ND180 thru 240 Evaporator Unit with PD180 thru 240 Heat Pump   14   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   RIGHT   REAR   FRONT   LEFT   CONVENIENCE   OUTLET   A 2X (Ø 1.375)   KNOCKOUT   30.994   2X (Ø 0.875)   KNOCKOUT   12.126   9.876   4.751   3.883   23.000   37.000   7.000   7.000   10.000   7.000   7.000   3.664   2.933   1.664   24.000   31.758   58.500   RIGHT   FRONT   SYSTEM 2   2X (Ø 0.875)   KNOCKOUT   2X (Ø 1.375)   KNOCKOUT   15.53   12.70   12.000   10.000   SYSTEM 1   4.875   6.26   7.52   8.98   10.60   4.132   2.382   1.882   REAR   LEFT   Figure 7: PC090, PC120 Unit Dimensions   NOTE: Use System 1 piping dimensions when applying a PC090/120 model system.   Table 7: PC090, PC120 Unit Height Dimensions   MODEL   PC090   PC120   A 44.5   50.0   Johnson Controls Unitary Products   15   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   REAR   RIGHT   LEFT   FRONT   A SYSTEM 2   SYSTEM 1   2X (Ø 1.375)   KNOCKOUT   30.994   2X (Ø 0.875)   KNOCKOUT   11.375   9.125   4.750   4.132   23.000   37.000   7.000   7.000   23.000   37.000   7.000   7.000   3.913   3.181   1.913   64.000   59.000   FRONT   RIGHT   SYSTEM 2   SYSTEM 1   16.133   13.133   17.367   18.867   20.617   22.617   FRONT   (PIPING DETAIL)   Figure 8: PC/PD180 & PC/PD240 Unit Dimensions and Piping & Electrical Dimensions   NOTE: Use System 1 piping dimensions when applying a PC180/240 model system.   Table 8: PC/PD180 & PC/PD240 Unit Height Dimensions   MODEL   PC180   PD180   PC240   PD240   A 44.5   44.5   50.0   50.0   16   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Table 9: Piping and Electrical Connection Sizes   MODEL   No. Refrigeration Circuits   Suction Line OD (in.)   Liquid Line OD (in.)   PC090   PC120   1 PC180   1 PD180   2 PC240   1 PD240   2 1 1 1/8   5/8   1 3/8   7/8   1 5/8   7/8   1 3/8   5/8   1 5/8   7/8   1 3/8   7/8   Power Wiring Knockout   Control Wiring Knockout   1 3/8   7/8   1 3/8   7/8   1 3/8   7/8   1 3/8   7/8   1 3/8   7/8   1 3/8   7/8   5. Does the available power supply agree with the nameplate   data on the unit?   Piping And Electrical Connections   Piping connections are made from the rear of 7.5 thru 12.5 Ton   units and from the front of 15 thru 20 Ton units. Stubouts are   provided on the suction and liquid line service valves. Piping   can be routed to the unit from the left or right side.   6. Is the control circuit transformer set for the proper voltage?   7. Have the fuses, disconnect switch and power wire been   sized properly?   8. Are all compressor mounting bolts properly secured?   Electrical connections for power and control wiring are made   from the right or left side of the electrical control box. See Table   9 and Figures 7 and 8 for piping sizes and electrical knockout   details.   9. Are any refrigerant lines touching each other or any sheet   metal surface? Rubbing due to vibration could cause a   refrigerant leak.   10. Are there any visible signs of a refrigerant leak, such as oil   residue?   Start-Up   11. Has the refrigeration system been leak checked,   evacuated and had the correctly calculated charge   weighted in?   Crankcase Heaters   12. Is any electrical wire laying against a hot refrigerant line?   The crankcase heaters must be energized at least 8 hours   before starting the compressors. To energize the crankcase   heaters, the main disconnect switch must be closed. During this   8 hour period, the system switch on the room thermostat must   be “OFF” to prevent the compressor from starting. Make sure   that the bottom of the compressor is warm to the touch to prove   crankcase heater operation.   Initial Start-Up   1. Supply power to the unit through the disconnect switch at   least 8 hours prior to starting the compressor.   2. Move the system switch on the thermostat to the AUTO or   COOL position.   3. Reduce the setting of the room thermostat to energize the   compressor.   4. Check the operation of the evaporator unit per the   manufacturer’s recommendations.   Do not attempt to start the compressor without at least 8   hours of crankcase heat or compressor damage can   occur.   5. With an ammeter, check the compressor amps against the   unit data plate.   Pre-Start Check   6. Check for refrigerant leaks.   7. Check for any abnormal noises and/or vibrations, and   make the necessary adjustments to correct fan blade(s)   touching shroud, refrigerant lines hitting on sheet metal,   etc.   Before starting the unit, complete the following check list:   1. Have sufficient clearances been provided?   2. Has all foreign matter been removed from the interior of the   unit (tools, construction or shipping materials, etc.)?   8. After the unit has been operating for several minutes, shut   off the main power supply at the disconnect switch and   inspect all factory wiring connections and bolted surfaces   for tightness.   3. Have the condenser fans been rotated manually to check   for free rotation?   4. Are all wiring connections tight?   Johnson Controls Unitary Products   17   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Compressor Protection   Operation   In addition to the external pressure switches, the compressors   also have inherent (internal) protection. If there is an abnormal   temperature rise in a compressor, the protector will open to shut   down the compressor. The UCB incorporates features to   minimize compressor wear and damage. An Anti-Short Cycle   Delay (ASCD) is utilized to prevent operation of a compressor   too soon after its previous run. Additionally, a minimum run time   is imposed any time a compressor is energized.   Unit Control Overview   This series of heat pumps come factory equipped with   Simplicity™ controls to monitor all unit functionality and safety   controls.   Safety Controls   The Simplicity™ control board incorporates features to monitor   safety circuits as well as minimize compressor wear and   damage. An anti-short cycle delay (ASCD) is utilized to prevent   operation of a compressor too soon after its previous run. The   ASCD is initiated on unit start-up and on any compressor reset   or lockout.   The ASCD is initiated on unit start-up and on any compressor   reset or lock-out.   Flash Codes   The UCB will initiate a flash code associated with errors within   the system. Refer to UNIT CONTROL BOARD FLASH CODES   The Simplicity™ control board monitors the following inputs for   each cooling system:   • A high-pressure switch is factory installed to protect   against excessive discharge pressure due to a blocked   condenser coil or a condenser fan motor failure. During   cooling operation, if a high-pressure limit switch opens,   the Simplicity™ control board will de-energize the   associated compressors and initiate the 5-minute ASCD.   If the call for cool is still present at the end of the ASCD,   the control board will re-energize the halted compressor. If   a high-pressure switch opens three times within two hours   of operation, the Simplicity™ control board will lockout the   associated system compressors and will flash an error   Reset   Remove the call for cooling, by raising thermostat setting higher   than the conditioned space temperature. This resets any   pressure or freezestat flash codes. Simplicity™ only has   minimum run time in cool. Heat pump mode shuts off   immediately.   Sequence of Operation   Continuous Blower   By setting the room thermostat to “ON,” the low voltage control   circuit from the “R” to “G” is completed and the supply air blower   will operate continuously.   • A low-pressure switch to protect the unit against   excessively low suction pressure is standard on all   condensing units. If the low-pressure switch opens during   normal operation, the Simplicity™ control board will de-   energize the compressor, initiate the ASCD, and shut   down the condenser fans. On startup, if the low-pressure   switch opens, the Simplicity™ control board will monitor   the low-pressure switch to make sure it closes within one   minute. If it fails to close, the unit will shut down the   associated compressor and begin an ASCD. If the call for   cool is still present at the end of the anti-short cycle time   delay, the control board will re-energize the halted   compressor. If a low-pressure switch opens three times   within one hour of operation, the Simplicity™ control   board will lock-out the associated compressor and flash   Intermittent Blower   With the room thermostat fan switch set to “AUTO” and the   system switch set to either the “AUTO” or “HEAT” settings, the   blower is energized whenever a cooling or heating operation is   requested. The blower is energized after any specified delay   associated with the operation.   When energized, the indoor blower has a minimum run time of   30 seconds. Additionally, the indoor blower has a delay of 10   seconds between operations.   Cooling Sequence Of Operation   Single-Stage Heat Pump (PC090)   • An ambient air switch will lock out mechanical cooling at   40F. If the product was equipped from the factory with   the low ambient option the unit will operate down to 0F. If   the unit was not ordered with the factory low ambient   option a field installed low ambient kit is available.   A single stage thermostat is required to operate the heat pump   in cooling mode.   The reversing valve is energized during cooling mode. A   continuous 24V signal is passed through the normally closed   contacts of relay RY2 to the "O" terminal of the Defrost Control   Board (DC). The normally closed relay DR-2 within DC   energizes the solenoid (SOL) of the reversing valve.   The refrigerant systems are independently monitored and   controlled. On any fault, only the associated system will be   affected by any safety/preventive action. The other refrigerant   system will continue to operate unless it is affected by the fault   as well.   When the thermostat calls for cooling (Y1), the Simplicity   control board (UCB) closes the coils of relay RY1 and contactor   18   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   M1 while sending a signal to one of the "CFAN" terminals on   DC.   • Relay RY2 has two functions. 1) control the crankcase   heater CCH2, 2) control the 24V output signal to S2 on   terminal block TB2.   • Relay RY1 controls the crankcase heater (CCH1). The   normally closed contacts allow CCH1 to operate during   unit shutdown.   • Contactor M2 controls compressor COMPR2.   If the initial call for cooling requires both stages (Y1 and Y2), the   UCB will delay the second stage by 30 seconds to avoid an   excessive power inrush.   • Contactor M1 controls compressor COMPR1.   The output signal from the remaining "CFAN" terminal on DC   closes the coil of contactor M3.   When the call for cooling (Y2) is satisfied, the UCB disables the   signal to RY2 and M2 as long as the specified minimum run   time (ASCD) has elapsed.   • Contactor M3 controls outdoor fans ODFAN1 & 2.   After completing the specified time for fan on-delay, UCB closes   the coil of relay BR1.   When the call for cooling (Y1) is satisfied, the UCB disables the   signal to RY1 and M1 as long as the specified minimum run   time (ASCD) has elapsed.   • Relay BR1 sends a 24V signal to G1 of terminal block   TB2. It may be used to control operation of an indoor   blower.   Dual Stage Heat Pump - 4 pipe (PD180-240)   A two stage thermostat is required to operate the heat pump in   cooling mode.   When the call for cooling (Y1) is satisfied, the UCB disables the   signal to RY1, M1 and DC as long as the specified minimum run   time (ASCD) has elapsed.   Both reversing valves are energized during cooling mode.   Continuous 24V signals are passed through the normally   closed contacts of relays RY2 and RY3 to the "O" terminals of   their respective Defrost Control Boards (DC1 and DC2). The   normally closed relays DR-2 within DC1 and DC2 energize the   solenoids (SOL1 and SOL2) of the reversing valves.   The UCB disables the signal to BR1 after completing the fan   off-delay period.   Dual Stage Heat Pump (PC120-240)   A two stage thermostat is required to operate the heat pump in   cooling mode.   When the thermostat calls for first-stage cooling (Y1), the   Simplicity control board (UCB) closes the coils of relay RY1 and   contactor M1 while sending a signal to one of the "CFAN"   terminals on DC1.   The reversing valve is energized during cooling mode. A   continuous 24V signal is passed through the normally closed   contacts of relay RY2 to the "O" terminal of the Defrost Control   Board (DC). The normally closed relay DR-2 within DC   energizes the solenoid (SOL) of the reversing valve.   • Relay RY1 has two functions. 1) control the crankcase   heater CCH1, 2) control the 24V output signal to S1 on   terminal block TB2.   When the thermostat calls for first-stage cooling (Y1), the   Simplicity control board (UCB) closes the coils of relay RY1 and   contactor M1 while sending a signal to one of the "CFAN"   terminals on DC.   • Contactor M1 controls compressor COMPR1.   The output signal from the remaining "CFAN" terminal on DC1   closes the coil of contactor M3.   • Contactor M3 controls outdoor fans ODFAN1 & 2.   • Relay RY1 has two functions. 1) control the crankcase   heater CCH1, 2) control the 24V output signal to S1 on   terminal block TB2.   After completing the specified time for fan on-delay, UCB closes   the coil of relay BR1.   • Contactor M1 controls compressor COMPR1.   • Relay BR1 sends a 24V signal to G1 of terminal block   TB2. It may be used to control operation of an indoor   blower.   The output signal from the remaining "CFAN" terminal on DC   closes the coil of contactor M3.   • Contactor M3 controls all outdoor fans.   When the thermostat calls for second-stage cooling (Y2), the   Simplicity control board (UCB) closes the coils of relay RY2 and   contactor M2 while sending a signal to one of the "CFAN"   terminals on DC2.   After completing the specified time for fan on-delay, UCB closes   the coil of relay BR1.   • Relay BR1 sends a 24V signal to G1 of terminal block   TB2. It may be used to control operation of an indoor   blower.   • Relay RY2 has two functions. 1) control the crankcase   heater CCH2, 2) control the 24V output signal to S2 on   terminal block TB2.   When the thermostat calls for second-stage cooling (Y2), the   Simplicity control board (UCB) closes the coil of relay RY2 and   contactor M2.   • Contactor M2 controls compressor COMPR2.   The output signal from the remaining "CFAN" terminal on DC2   closes the coil of contactor M4.   Johnson Controls Unitary Products   19   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   • Contactor M4 controls outdoor fans ODFAN3 & 4.   • Relay RY1 has two functions: 1) control the operation of   crankcase heater CCH1, and 2) control the 24V output   signal to S1 on terminal block TB2.   If the initial call for cooling requires both stages (Y1 and Y2), the   UCB will delay the second stage by 30 seconds to avoid an   excessive power inrush.   • Contactor M1 controls compressor COMPR1.   • Relay RY3 (RY2 for PC090 model) toggles the 24V signal   from the "O" terminal of DC to the "Y" terminal assuring   the reversing valve cannot be energized except during   defrost.   When the call for cooling (Y2) is satisfied, the UCB disables the   signal to RY2 and M2 as long as the specified minimum run   time (ASCD) has elapsed.   When the call for cooling (Y1) is satisfied, the UCB disables the   signal to RY1 and M1 as long as the specified minimum run   time (ASCD) has elapsed.   • Concurrently, a 24V signal is sent to one of the "CFAN"   terminals of DC. The output signal from the remaining   "CFAN" terminal closes the coil of contactor M3.   • Contactor M3 controls outdoor fans ODFAN1 & 2 (all   models) and ODFAN3 & 4 (PC180-240).   Low Ambient Cooling   These units are factory equipped with low ambient switches   that work through the Simplicity control board to operate the   compressors and condenser fans normally to 40ºF ambient   temperature. The Electronic Low Ambient Controller   2LA04703000 Accessory is designed to assure safe operation   through condenser head pressure regulation down to 0ºF   ambient temperature.   (PC120-240; PD180-240 models)   • After a two second delay, the UCB energizes the contacts   of relay RY2 and contactor M2.   • Relay RY2 has two functions: 1) control the operation of   crankcase heater CCH2, and 2) control the 24V output   signal to S2 on terminal block TB2.   Low Ambient Control Operation   • Contactor M2 controls compressor COMPR2.   • A call for cooling closes contactor M3 which energizes all   condenser fans. The Low Ambient Control starts all fans   at full speed then adjusts according to the liquid line   temperature.   (PD180-240 models only)   • Concurrently, a 24V signal is sent to one of the "CFAN"   terminals of defrost control board DC2. The output signal   from the remaining "CFAN" terminal closes the coil of   contactor M4.   Refer to the appropriate 2LA low ambient kit instructions for   additional detail on the factory or field installed low ambient kit   and its operation.   • Contactor M4 controls outdoor fans ODFAN3 & 4.   Heating Sequence of Operation   General   Second Stage Heating Operation   When the thermostat calls for second stage heating (W2):   Heat pump models are to be matched with air handlers of   equivalent tonnage ratings. Twinning of heat pumps and air   handlers is not recommended.   • A 24V signal passes through UCB sending an input signal   to the "W" terminal of DC. This signal passes through DC   as an output signal to the "66" terminal of TB2 to be used   as a control signal for first stage electric heat.   A two stage thermostat is required to operate the heat pump in   heating mode.   Emergency Heating Operation   All reversing valves are de-energized during normal heating   mode. They are energized only during cooling and defrost   modes.   When the thermostat calls for emergency heating (EMER):   • The UCB de-energizes all compressor relays and   contactors.   The heat pump operates all compressors during a first stage   call for heating unless locked out by the Unit Control Board   (UCB).   • A 24V signal passes through UCB sending an input signal   to the "W" terminal of DC. This signal passes through DC   as an output signal to the "66" terminal of TB2 to be used   as a control signal for first stage electric heat.   First Stage Heating Operation   • The normally closed contacts of M1-AUX and M2-AUX   (PC120-240; PD180-240 models only) send a 24V output   signal to the "60" terminal of TB2 to be used as a control   signal for second stage electric heat.   When the thermostat calls for first stage heating (W1):   • The Simplicity control board (UCB) goes into a five minute   ASCD timer delay.   • When the ASCD time delay is satisfied, the UCB closes its   internal compressor relay contact, thus energizing the   contacts of relay RY1 and contactor M1.   20   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Defrost Operation   NOTE: The DC has two flash codes that only initiate if the   jumper between the two pressure switch terminals is   removed or broken.   The defrost control board (DC) utilizes a time/temperature   defrost scheme. The DC repeats normal heating run cycles,   which must be completed, until one of the following conditions   is met and the DC enters defrost mode:   Blower Operation   After completing the specified time for fan on-delay, UCB closes   the coil of relay BR1.   1. The DC satisfies its accumulated minimum run time. This   is factory set at 60 minutes, but is field adjustable to 30, 60   or 90 minutes.   • Relay BR1 sends a 24V signal to G1 of terminal block   TB2. It may be used to control operation of an indoor   blower.   2. The defrost switch(es) is closed. This normally open   switch is set to close at 28° F (+/-3°).   The UCB disables the signal to BR1 after completing the fan   off-delay period.   When the DC enters defrost mode, its on-board defrost relays   are powered. This energizes the reversing valve solenoid, de-   energizes the condenser fan motors and energizes the unit's   optional electric heater. The DC remains in defrost mode until   either of the following two conditions are met:   Rear   Rear   1. Both of the liquid line thermostats are open. Each is set to   open at 55 degrees (+/- 3).   2 2 4 3 2. The maximum defrost run time of 10 minutes is met.   The DC also contains a set of test pins. Placing a jumper   across these pins will result in the following actions:   • If the ASCD timer is active, it is now bypassed, allowing   the compressor to run.   1 1 • If the DC is in a lockout condition, the lockout is reset.   • If the compressor is running, the DC is forced into defrost   mode. The control will remain in defrost mode as long as   the jumper is in place. When the jumper is removed, the   control will terminate defrost mode.   Front   Front   Figure 9: Fan Orientation, Control Box End   Table 10: PC090 thru 240 Unit Control Board Flash Codes   GREEN   LED   16   RED   LED   8 RED   LED   4 RED   LED   2 RED   LED   1 FLASH CODE   DESCRIPTION   On Steady   1 Flash   This is a Control Failure   Not Applicable   - - - - - - - - - - Control waiting ASCD1   2 Flashes   3 Flashes   4 Flashes   5 Flashes   6 Flashes   7 Flashes   8 Flashes   10 Flashes   12 Flashes   13 Flashes   14 Flashes   OFF   Flashing   Off   Off   - Off   Off   - On   On   - Off   On   - HPS1 Compressor Lockout   Not Applicable   Off   - LPS1 Compressor Lockout   Not Applicable   Off   Off   - On   - Off   - On   - - Off   FS1 Compressor Lockout2   Not Applicable   Off   - On   - On   - On   - - Compressors Locked Out on Low Outdoor Air Temperature1   Unit Locked Out due to Fan Overload Switch Failure   Flashing   Off   On   On   On   On   Off   Off   On   On   On   Off   On   Off   Off   On   Off   Off   Off   On   Off   Off   Compressor Held Off due to Low Voltage1   EEPROM Storage Failure   Flashing   Off   No Power or Control Failure   Off   1. Non-alarm condition.   2. Freeze - stat not applicable.   Johnson Controls Unitary Products   21   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Table 11: PD180 thru 240 Unit Control Board Flash Codes   GREEN   LED   16   RED   LED   8 RED   LED   4 RED   LED   2 RED   LED   1 FLASH CODE   DESCRIPTION   On Steady   1 Flash   This is a Control Failure   Not Applicable   - - - - - - - - - - Control waiting ASCD1   2 Flashes   3 Flashes   4 Flashes   5 Flashes   6 Flashes   7 Flashes   Flashing   Off   Off   Off   Off   Off   Off   Off   Off   Off   On   On   On   On   On   On   Off   Off   On   On   Off   On   Off   On   Off   On   HPS1 Compressor Lockout   HPS2 Compressor Lockout   LPS1 Compressor Lockout   LPS2 Compressor Lockout   Off   Off   Off   FS1 Compressor Lockout2   FS2 Compressor Lockout2   Off   8 Flashes   Off   On   Off   Off   Off   Compressors Locked Out on Low Outdoor Air Temperature1   Unit Locked Out due to Fan Overload Switch Failure   10 Flashes   12 Flashes   13 Flashes   14 Flashes   OFF   Flashing   Off   On   On   On   On   Off   Off   On   On   On   Off   On   Off   Off   On   Off   Off   Off   On   Off   Off   Compressor Held Off due to Low Voltage1   EEPROM Storage Failure   Flashing   Off   No Power or Control Failure   Off   1. Non-alarm condition.   2. Freeze - stat not applicable.   Check   Alarm   History   Reset All   ASCDs for   One Cycle   Non Alarm   Condition Green   LED Flashing   Current Alarm   Flashed   Red LED   Figure 10: Unit Control Board   22   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Flash Codes   Normal Maintenance   Various flash codes are utilized by the unit control board (UCB)   to aid in troubleshooting. Flash codes are distinguished by the   short on and off cycle used (approximately 200ms on and   200ms off). To show normal operation, the control board   flashes a 1 second on, 1 second off "heartbeat" during normal   operation. This is to verify that the UCB is functioning correctly.   Do not confuse this with an error flash code. To prevent   confusion, a 1-flash, flash code is not used.   Prior to any of the following maintenance procedures,   shut off all power to the unit, to avoid personal injury.   Periodic maintenance consists of changing or cleaning filters   and general cleaning of the outdoor coil.   Alarm condition codes are flashed on the UCB lower left Red   LED, See Figure Table 11. While the alarm code is being   flashed, it will also be shown by the other LEDs: lit continuously   while the alarm is being flashed. The total of the continuously lit   LEDs equates to the number of flashes, and is shown in the   table. Pressing and releasing the LAST ERROR button on the   UCB can check the alarm history. The UCB will cycle through   the last five (5) alarms, most recent to oldest, separating each   alarm flash code by approximately 2 seconds. In all cases, a   flashing Green LED will be used to indicate non-alarm   condition.   FILTERS - Inspect once a month. Replace Disposable or clean   Permanent Type as necessary. DO NOT replace Permanent   Type with Disposable.   MOTORS - Outdoor fan motors are permanently lubricated and   require no maintenance.   OUTDOOR COIL - Dirt should not be allowed to accumulate on   the outdoor coil surface or other parts in the air circuit. Cleaning   should be as often as necessary to keep the coil clean. Use a   brush, vacuum cleaner attachment, or other suitable means. Be   sure that the power to the unit is shut off prior to cleaning.   In some cases, it may be necessary to "zero" the ASCD for the   compressors in order to perform troubleshooting. To reset all   ASCDs for one cycle, press and release the UCB TEST/   RESET button once.   Flash codes that do and do not represent alarms are listed in   Exercise care when cleaning the coil so that the coil fins   are not damaged.   Do not permit the hot condenser air discharge to be   obstructed by overhanging structures or shrubs.   Unit Control Board Option Setup   Option Byte Setup   Troubleshooting   • Enter The Option Setup Mode By Pushing The Option   Setup / Store Button, And Holding It For At Least 2   Seconds.   • The Green Status Led (Option Byte) Will Be Turned On   And The Red Status Led (Heat Delay) Is Turned Off.   Troubleshooting of components necessarily requires   opening the electrical control box with the power   connected to the unit. Use extreme care when working   with live circuit! Check the unit nameplate for the correct   range before making any connections with line   terminals.   • The 4 Led Will Then Show The Status Of The Labeled   Option Low Ambient Lockout.   • Press The Up Or Down Button To Change The Led Status   To Correspond To The Desired Option Setup.   • To Save The Current Displayed Value, Push The Option   Setup / Store Button And Hold It For At Least 2 Seconds.   When The Value Is Saved, The Green Led Will Flash A   Few Times And Then Normal Display Will Resume.   NOTE: While in either Setup mode, if no buttons are pushed for   60 seconds, the display will revert to its normal display,   exiting the Option Setup mode. When saving, the   control board only saves the parameters for the   currently displayed mode (Option Byte or Heat   Delay). (Heat Delay not applicable on these units.)   The wire number or color and terminal designations   referred to may vary. Check the wiring label inside the   control box access panel for the correct wiring.   Johnson Controls Unitary Products   23   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   Cooling Troubleshooting Guide   2. If M1 is pulled in and voltage is supplied at M1, lightly touch   the compressor housing. If it is hot, the compressor may be   off on inherent protection. Cancel any calls for cooling and   wait for the internal overload to reset. Test again when   cool.   On calls for cooling, if the compressors are operating but the   supply air blower motor does not energize after a short delay   (the room thermostat fan switch is in the “AUTO” position):   1. Turn the thermostat fan switch to the ON position. If the   supply air blower motor does not energize, go to Step 3.   3. If M1 is not pulled in, check for 24 volts at the M1 coil. If 24   volts are present and M1 is not pulled in, replace the   contactor.   2. If the blower motor runs with the fan switch in the ON   position but will not run after the first compressor has   energized when the fan switch is in the AUTO position,   check the room thermostat for contact between R and G in   the AUTO position during calls for cooling.   4. Failing the above, if voltage is supplied at M1, M1 is pulled   in, and the compressor still does not operate, replace the   compressor.   5. If 24 volts is not present at M1, check for 24 volts at the   UCB terminal, C1. If 24 volts is present, check for loose   wiring between C1 and the compressor contactor.   3. If the supply air blower motor does not energize when the   fan switch is set to ON, check that line voltage is being   supplied to the contacts of the M3, contactor, and that the   contactor is pulled in. Check for loose wiring between the   contactor and the supply air blower motor.   6. If 24 volts is not present at the C1 terminal, check for 24   volts from the room thermostat at the UCB Y1 terminal. If   24 volts is not present from the room thermostat, check for   the following:   4. If M3 is pulled in and voltage is supplied to M3, lightly touch   the supply air blower motor housing. If it is hot, the motor   may be off on internal protection. Cancel any thermostat   calls and set the fan switch to AUTO. Wait for the internal   overload to reset. Test again when cool.   a. 24 volts at the thermostat Y1 terminal   b. Proper wiring between the room thermostat and the   UCB, i.e. Y1 to Y1, Y2 to Y2, and   c. Loose wiring from the room thermostat to the UCB   5. If M3 is not pulled in, check for 24 volts at the M3 coil. If 24   volts are present at M3 but M3 is not pulled in, replace the   contactor.   7. If 24 volts is present at the UCB Y1 terminal, the   compressor may be out due to an open high-pressure   switch or low-pressure switch. Check for 24 volts at the   HPS1 and LPS1 terminals of the UCB. If a switch has   opened, there should be a voltage potential between the   UCB terminals, e.g. if LPS1 has opened, there will be a 24-   volt potential between the LPS1 terminals.   6. Failing the above, if there is line voltage supplied at M3, M3   is pulled in, and the supply air blower motor still does not   operate, replace the motor.   7. If 24 volts is not present at M3, check that 24 volts is   present at the UCB supply air blower motor terminal,   “FAN”. If 24 volts is present at the FAN, check for loose   wiring between the UCB and M3.   8. If 24 volts is present at the UCB Y1 terminal and none of   the protection switches have opened, the UCB may have   locked out the compressor for repeat trips. The UCB   should be flashing an alarm code. If not, press and release   the ALARMS button on the UCB. The UCB will flash the   last five alarms on the LED. If the compressor is locked   out, cancel any call for cooling. This will reset any   compressor lock outs.   8. If 24 volts is not present at the “FAN” terminal, check for 24   volts from the room thermostat. If 24 volts are not present   from the room thermostat, check for the following:   a. Proper operation of the room thermostat (contact   between R and G with the fan switch in the ON position   and in the AUTO position during operation calls).   NOTE: While the above step will reset any lockouts,   compressor #1 may be held off for the ASCD. See the   next step.   b. Proper wiring between the room thermostat and the   UCB, and   c. Loose wiring from the room thermostat to the UCB   9. If 24 volts is present at the UCB Y1 terminal and none of   the switches are open and the compressor is not locked   out, the UCB may have the compressor in an ASCD.   Check the LED for an indication of an ASCD cycle. The   ASCD should time out within 5 minutes. Press and release   the TEST button to reset all ASCDs.   9. If 24 volts is present at the room thermostat but not at the   UCB, check for proper wiring between the thermostat and   the UCB, i.e. that the thermostat G terminal is connected to   the G terminal of the UCB, and for loose wiring.   10. If the thermostat and UCB are properly wired, replace the   UCB.   10. If 24 volts is present at the UCB Y1 terminal and the   compressor is not out due to a protective switch trip, repeat   trip lock out, or ASCD, the economizer terminals of the   UCB may be improperly wired. Check for 24 volts at the Y1   “OUT” terminal of the UCB.   On calls for cooling, the supply air blower motor is operating but   compressor #1 is not (the room thermostat fan switch is in the   “AUTO” position):   1. If compressor #1 does not energize on a call for cooling,   check for line voltage at the compressor contactor, M1, and   that the contactor is pulled in. Check for loose wiring   between the contactor and the compressor.   11. If 24 volts is not present at the Y1 “OUT” terminal, the UCB   must be replaced. (If 24 volts is present at the Y1 OUT   terminal, check for 24 volts at the Y1 “ECON” terminal. If   24 volts is not present, check for loose wiring from the Y1   24   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   “OUT” terminal to the Mate-N-Lock plug, the jumper in the   Mate-N-Lock plug, and in the wiring from the Mate-N-Lock   plug to the Y1 “ECON” terminal.)   remove any call for cooling at the thermostat or by   disconnecting the thermostat wiring at the Y2 UCB   terminal. This will reset any compressor lock outs.   12. If none of the above corrected the error, test the integrity of   the UCB. Disconnect the C1 terminal wire and jumper it to   the Y1 terminal. DO NOT jump the Y1 to C1 terminals. If   the compressor engages, the UCB has faulted.   NOTE: While the above step will reset any lock outs,   compressor #1 will be held off for the ASCD, and   compressor #2 may be held off for a portion of the   ASCD. See the next step.   13. If none of the above correct the error, replace the UCB.   9. If 24 volts is present at the UCB Y2 terminal and none of   the switches are open and the compressor is not locked   out, the UCB may have the compressor in an ASCD.   Check the LED for an indication of an ASCD cycle. The   ASCD should time out within 5 minutes. Press and release   the TEST button to reset all ASCDs.   For units with two stages of cooling: On calls for the second   stage of cooling, the supply air blower motor and compressor   #1 are operating but compressor #2 is not (the room thermostat   fan switch is in the “AUTO” position):   1. Compressor #2 will not energize simultaneously with   compressor #1 if a call for both stages of cooling is   received. The UCB delays compressor #2 by 30 seconds   to prevent a power surge. If after the delay compressor #2   does not energize on a second stage call for cooling, check   for line voltage at the compressor contactor, M2, and that   the contactor is pulled in. Check for loose wiring between   the contactor and the compressor.   10. If none of the above corrected the error, test the integrity of   the UCB. Disconnect the C2 terminal wire and jumper it to   the Y2 terminal. DO NOT jump the Y2 to C2 terminals. If   the compressor engages, the UCB has faulted.   11. If none of the above correct the error, replace the UCB.   On a call for cooling, the supply air blower motor and   compressor #2 are operating but compressor #1 is not (the   room thermostat fan switch is in the “AUTO” position):   2. If M2 is pulled in and voltage is supplied at M2, lightly touch   the compressor housing. If it is hot, the compressor may be   off on inherent protection. Cancel any calls for cooling and   wait for the internal overload to reset. Test again when cool.   1. Compressor #2 is energized in place of compressor #1   when compressor #1 is unavailable for cooling calls. Check   the UCB for alarms indicating that compressor #1 is locked   out. Press and release the ALARMS button if the LED is   not flashing an alarm.   3. If M2 is not pulled in, check for 24 volts at the M2 coil. If 24   volts is present and M2 is not pulled in, replace the   contactor.   2. Check for line voltage at the compressor contactor, M1,   and that the contactor is pulled in. Check for loose wiring   between the contactor and the compressor.   4. Failing the above, if voltage is supplied at M2, M2 is pulled   in, and the compressor still does not operate, replace the   compressor.   3. If M1 is pulled in and voltage is supplied at M1, lightly touch   the compressor housing. If it is hot, the compressor may be   off on inherent protection. Cancel any calls for cooling and   wait for the internal overload to reset. Test again when cool.   5. If 24 volts is not present at M2, check for 24 volts at the   UCB terminal, C2. If 24 volts are present, check for loose   wiring between C2 and the compressor contactor.   6. If 24 volts is not present at the C2 terminal, check for 24   volts from the room thermostat at the UCB Y2 terminal. If   24 volts is not present from the room thermostat, check for   the following:   4. If M1 is not pulled in, check for 24 volts at the M1 coil. If 24   volts is present and M1 is not pulled in, replace the   contactor.   5. Failing the above, if voltage is supplied at M1, M1 is pulled   in, and the compressor still does not operate, replace the   compressor.   a. 24 volts at the thermostat Y2 terminal   b. Proper wiring between the room thermostat and the   UCB, i.e. Y1 to Y1, Y2 to Y2, and   6. If 24 volts is not present at M1, check for 24 volts at the   UCB terminal, C1. If 24 volts is present, check for loose   wiring between C1 and the compressor contactor.   c. Loose wiring from the room thermostat to the UCB   7. If 24 volts is present at the UCB Y2 terminal, the   compressor may be out due to an open high-pressure   switch, low-pressure switch, or freezestat. Check for 24   volts at the HPS2, LPS2, and FS2 terminals of the UCB. If   a switch has opened, there should be a voltage potential   between the UCB terminals, e.g. if LPS2 has opened, there   will be 24 volts of potential between the LPS2 terminals.   7. If 24 volts is not present at the C1 terminal, check for 24   volts from the room thermostat at the UCB Y1 terminal. If   24 volts are not present at the UCB Y1 terminal, the UCB   may have faulted. Check for 24 volts at the Y1 ECON   terminal. If 24 volts is not present at Y1 “ECON”, the UCB   has faulted. The UCB should de-energize all compressors   on a loss of call for the first stage of cooling, i.e. a loss if 24   volts at the Y1 terminal.   8. If 24 volts is present at the UCB Y2 terminal and none of   the protection switches have opened, the UCB may have   locked out the compressor for repeat trips. The UCB   should be flashing a code. If not, press and release the   ALARMS button on the UCB. The UCB will flash the last   five alarms on the LED. If the compressor is locked out,   8. If 24 volts are present at the UCB Y1 terminal, the   compressor may be out due to an open high-pressure   switch or low-pressure switch. Check for 24 volts at the   Johnson Controls Unitary Products   25   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
				  
				
					430645-YIM-D-0610   HPS1 and LPS1 terminals of the UCB. If a switch has   opened, there should be a voltage potential between the   UCB terminals, e.g. if LPS1 has opened, there will be a 24-   volt potential between the LPS1 terminals.   ASCD should time out within 5 minutes. Press and release   the TEST button to reset all ASCDs.   11. If 24 volts is present at the UCB Y1 terminal and the   compressor is not out due to a protective switch trip, repeat   trip lock out, or ASCD, the economizer terminals of the UCB   may be improperly wired. Check for 24 volts at the Y1 “OUT”   terminal of the UCB. If 24 volts is not present at the Y1   “OUT” terminal, the UCB must be replaced.   9. If 24 volts is present at the UCB Y1 terminal and none of   the protection switches have opened, the UCB may have   locked out the compressor for repeat trips. The UCB   should be flashing a code. If not, press and release the   ALARMS button on the UCB. The UCB will flash the last   five alarms on the LED. If the compressor is locked out,   remove any call for cooling. This will reset any compressor   lock outs.   12. If 24 volts is present at the Y1 “OUT” terminal, check for 24   volts at the Y1 “ECON” terminal. If 24 volts is not present,   check for loose wiring from the Y1 “OUT” terminal to the   Mate-N-Lock plug, the jumper in the Mate-N-Lock plug,   and in the wiring from the Mate-N-Lock plug to the Y1   “ECON” terminal.   NOTE: While the above step will reset any lock outs,   compressor #2 will be held off for the ASCD, and   compressor #1 may be held off for a portion of the   ASCD. See the next step.   13. If none of the above corrected the error, test the integrity of   the UCB. Disconnect the C1 terminal wire and jumper it to   the Y1 terminal. DO NOT jump the Y1 to C1 terminals. If   the compressor engages, the UCB has faulted.   10. If 24 volts is present at the UCB Y1 terminal and none of   the switches are open and the compressor is not locked   out, the UCB may have the compressor in an ASCD.   Check the LED for an indication of an ASCD cycle. The   14. If none of the above correct the error, replace the UCB.   26   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Cooling Charging Curves   PC090   600   500   400   300   200   115°   105°   95°   85°   75°   65°   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that both condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 11: PC090 Charging Chart   Cooling Charging Curves   PC120   600   500   400   300   115°   105°   95°   85°   75°   65°   200   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that both condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 12: PC120 Charging Chart   Johnson Controls Unitary Products   27   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Cooling Charging Curves   PC180   600   500   400   300   200   115°   105°   95°   85°   75°   65°   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that all condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 13: PC180 Charging Chart   Cooling Charging Curves   PD180   600   500   400   300   115°   105°   95°   85°   75°   65°   200   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that all condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 14: PD180 Charging Chart   28   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Cooling Charging Curves   PC240   600   500   400   300   200   115°   105°   95°   85°   75°   65°   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that all condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 15: PC240 Charging Chart   Cooling Charging Curves   PD240   600   500   400   300   115°   105°   95°   85°   75°   65°   200   120   130   140   150   160   170   180   Suction Pressure (psi)   1. Make sure that all condenser fans are running when charging.   2. This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been   adjusted in the field, the charging chart may no longer apply.   Figure 16: PD240 Charging Chart   Johnson Controls Unitary Products   29   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Typical Wiring Diagrams   Figure 17: Typical PC090 Heat Pump Wiring Diagram   30   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Figure 18: Typical PC120 Heat Pump Wiring Diagram   Johnson Controls Unitary Products   31   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					430645-YIM-D-0610   Figure 19: Typical PC180 - 240 Heat Pump Wiring Diagram   32   Johnson Controls Unitary Products   Download from Www.Somanuals.com. All Manuals Search And Download.   
			
			
				
					Figure 20: Typical PD180 - 240 Heat Pump Wiring Diagram   Subject to change without notice. Printed in U.S.A.   430645-YIM-D-0610   Copyright © 2010 by Johnson Controls, Inc. All rights reserved.   Supersedes: 430645-YIM-C-0310   Johnson Controls Unitary Products   5005 York Drive   Norman, OK 73069   Download from Www.Somanuals.com. All Manuals Search And Download.   |