Ingersoll Rand Home Security System 7940 8770 User Manual

LCN  
®
7940-8770 Presence Sensor  
Installation Instructions  
LCN®  
Hardware Products  
121 West Railroad Avenue  
Princeton, IL 61356-0100  
1-800-526-2400  
FAX: 800-248-1460  
© 2006 Ingersoll-Rand Company Limited  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY  
PRECAUTIONS  
Shut off all power going to the header before attempting any wiring procedures.  
Maintain a clean & safe environment when working in public areas.  
Constantly be aware of pedestrian traffic around the door area.  
Always stop pedestrian traffic through the doorway when performing testing that may result in unexpected  
reactions by the door.  
Always check placement of all wiring and components before powering up to insure that moving door  
parts will not catch any wires and cause damage to equipment.  
MECHANICAL  
INSTALLATION -  
PREPARATION  
To prepare the Presence Sensor for mounting to the header, perform the following:  
a) Remove both end caps from the Presence Sensor (picture 1). Each is attached by one Phillips head screw.  
1
2
b) Remove both lenses from Presence Sensor by simply sliding them out at each end, as shown above in  
picture 2.  
c) Remove the center eye shield as shown in picture 3 (take care not to damage the light tube on the inner  
side of the shield). Simply pull out from the top end and rotate out as shown below.  
3
4
d) Slide the PCB out of the extrusion and set it aside as shown above in picture 4.  
Remember these guidelines when installing a Presence Sensor:  
MECHANICAL  
INSTALLATION –  
PLACEMENT OF  
THE SENSOR  
The Presence Sensor should be mounted at a height range of 6’ 6” to 8’. Maximum mounting height is 9’.  
The Presence Sensor should be mounted above the door on the swing side.  
The Presence Sensor shall be mounted flush with the bottom of the automatic door header. This is absolutely  
necessary to allow the detection pattern to reach back through the threshold area when the Presence Sensor  
is in the open door position.  
For single door applications, the Presence Sensor should be mounted at the center of the door opening.  
However, if this is not possible, the unit may be installed off-center. In such cases, pattern location will have to  
be altered for proper placement of the field of detection. Try to avoid mounting locations that may pose  
potential problems such as directly over a door arm.  
For double-egress applications, one Presence Sensor  
should be mounted over each swing-path. There should  
be at least 40” of separation between the 2 Presence  
Sensors when measured between the centerline of each  
sensor.  
Wall Switch  
An optional BodyMount  
3” Standoff may be used  
during sensor installation  
20” min  
20” min  
If the Presence Sensor is the only sensor being used for  
safety at the swing side of the door, to be in compliance  
with ANSI 156.10, a lockout safety beam or door  
mounted safety side (DMSS) is needed in addition to the  
Presence Sensor.  
Presence Sensor  
Presence Sensor  
For all applications, refer to the pattern charts for  
width and depth in the applicable section of this  
Guide. Patterns shall be adjusted to achieve  
maximum detection zones, and shall be in  
compliance with all applicable safety standards (i.e.  
ANSI A156.10).  
Wall Switch  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 2 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MECHANICAL  
INSTALLATION  
NOTE: LCN recommends the use of a BodyMount P/N 761222-79 for most Presence Sensor applications. The  
BodyMount is a 3” standoff that allows the Presence Sensor to be slightly distanced from the face of the  
closed door. This helps to prevent ghosting caused by slight door movement while closed, and also  
prevents ghosting when Door Mounted Safety Sensors are used (as the Door Mounted Safety Sensor  
extrusions at the top of the door are extremely close to the sensor while the door is closed).  
1. The extrusion has pre-drilled mounting holes at each end as shown below in pictures 5 & 6.  
5
6
Pre Drilled  
Mounting Holes  
Approx. 9 ¾” Apart  
2. Hold the Presence Sensor up to the pre-determined location, and attach using the 2 self-drilling screws  
that are included with the package, as shown in picture 7 below. It may be necessary to pre-drill a pilot  
hole (picture 8) in the header for ease of screw installation. Ensure that Presence Sensor is mounted  
securely at each end.  
7
8
3. If Presence Sensor is mounted directly to door header, and cabling is to pass directly into header, drill a ¼”  
hole next to the Presence Sensor’s left side end cap to allow wire passage into header as shown below.  
The wire passage hole should be in a location that aligns with the cut out in the end cap as shown below.  
9
ELECTRICAL  
INSTALLATION  
AND CABLING  
Once the Presence Sensor is securely attached to header, cabling & wiring may be completed.  
1. Install the 10-pin connector as shown below in picture 10. If wiring the Presence Sensor to a LCN module, refer to  
the schematic for the respective module.  
Position  
1
Connection 7-Pin  
12 to 24 V AC / DC Red  
+/- 10%  
24 to 24 V AC / DC Black  
+/- 10%  
Wire Color (10-pin cable)  
10  
1 PWR  
2 PWR  
3 COM  
4 NO  
2
5 NC  
3
4
5
6
7
Common  
White  
Green  
6 IN -  
7 IN +  
Normally Open  
Normally Closed  
Data -  
10 PIN  
Brown  
Blue  
10 PIN  
Data +  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 3 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Once all installation, wiring and cabling procedures have been completed, mechanical adjustments can be made.  
Please note that further adjustments may be required after powering and walk testing the detection field.  
MECHANICAL  
ADJUSTMENTS  
Aside from placement on the header, the only mechanical adjustment that may be made to the sensor is the angle  
adjustment. The Presence Sensor is factory pre-set to the +5º position, but may be reduced to a 0º position or  
increased to a 10º position. The greater the angle, the farther from the door the pattern will be. The 0º angle should  
only be used when the Presence Sensor is mounted to a BodyMount block or to a soffett above the door that  
extends out from the face of the safety side of the door – in this case, the 0º setting would improve the location of  
the detection field across the threshold area of the doorway. It is recommended that for most applications, the unit  
be powered and walk tested at the pre-set 5º angle. After walk testing, if the detection field needs to be changed,  
then proceed with changes to the angle setting as shown below.  
1. To change the angle setting the end caps, lenses, and center eye shield must be removed (as shown on page 2).  
The terminal block must also be removed if it has been wired. Once removed release the white clips, as shown  
below, and rotate outward to remove the PCB as shown in pictures 12 & 13.  
12  
13  
2. Once the PCB is completely removed from the housing, the angle position may be changed. There are two clips  
per Presence Sensor and the angle must match for each clip on the same PCB. The positions are shown below.  
10°  
5°  
0°  
Factory Default  
3. Slide the left and right lens back into place and proceed with power-up procedures. Leave the end caps off until all  
final adjustments have been made.  
14  
POWER-UP  
PROCEDURES  
1. Upon completion of mechanical and electrical installation, apply 12 to 24 V AC / DC +/- 10% to the Presence  
Sensor, with the door in the closed position. The Presence Sensor will flash a green LED at a rate of 2 Hz, then it  
will expire upon a successful set-up in the door-closed position.  
NOTE: If applying the Presence Sensor to a door control that requires a learn cycle upon powering, it is  
recommended to allow the doors to complete a learn cycle before applying power to the Presence Sensor.  
2. Activate the door to the full open position. The Presence Sensor will once again flash the green LED and will  
execute a door-open set-up. Upon completion of the set-up for the door-open position, the doors will begin closing.  
Normal operation should resume thereafter. Proceed with fine-tuning to insure compliance with all applicable  
safety standards (i.e. ANSI A156.10). If set-up is unsuccessful, refer to the Troubleshooting Guide at the end of  
this Users Guide, and also to the guide located at the end of the respective lockout User’s Guide.  
NOTE: Always be sure to refer to the applicable lockout User’s Guide for more detailed information.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 4 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOUBLE EGREES:  
REDUCING  
CROSS TALK  
Perform the following set up using LCN’s remote control to reduce cross talk between duel egress applications. Refer to  
the figure on page 2 to ensure the two Presence Sensors are installed with at least 40” of separation when measured  
between the centerline of each sensor.  
1. Place doors in the hold open position. Unlock sensor and set open door Pattern Depth to 5 (Medium Pattern).  
This sequence will turn off threshold IR while door is in open position. This function should be changed on both  
sensors:  
+ +  
then  
+
2. The infrared frequency function may need to be changed. Change frequency on one of the sensors:  
+ +  
then  
+
3. Change to a different mode in applications where high gloss floors or multiple doors are installed in vestibules.  
Change sensor one to:  
+ +  
Change sensor two to:  
then  
then  
+
+
+ +  
LCN’S UNIVERSAL  
REMOTE  
CONTROL  
The Presence Sensor is fully compatible with LCN’s Remote Control as shown below. Use of the remote control should  
be conducted within 10’ – 15’ of the sensor, and the remote should be pointed directly at the sensor when used. Refer to  
the “Programming Guide” in the following section for each parameter and its values.  
Additional program notes:  
1. The Presence Sensor is capable of having two patterns (door closed and door open) that are  
independently adjustable. Thus, when programming, it is necessary to adjust the pattern for door closed,  
and then to adjust the pattern again when the door is open. The following functions may be  
independently adjusted for each door position:  
ƒ
ƒ
ƒ
Sensitivity  
Pattern Width  
Pattern Depth  
2. The following functions apply to both door closed and door open positions:  
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
Automatic Learn Time  
Immunity  
Frequency  
Output Configuration  
Door Control Mode  
Hold Time  
Interface Type  
3. The immunity modes include Rain Mode and Snow Mode. During these modes, learn time of the sensor  
will not be affected. These modes affect the interpretation of the objects in the field of detection relative  
to the background.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 5 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAMMING  
GUIDE –  
GENERAL  
FUNCTIONS  
REMOTE P/N  
7940-461  
Number Keys  
Number keys (0 through 9) are  
used for assigning a value for a  
given function  
Infrared Frequency  
Mode  
Normal  
Normal  
Quiet  
Frequency  
1
2
3
4
Low  
High  
Low  
High  
Interface  
1: LO-Linx  
Quiet  
2: LO21 - Old Style (LO21, B, K, P, U)  
See Note: Quiet Mode  
Door Control  
Unlock  
Inquire  
Lock  
1: normal  
(LED in normal mode)  
2: door permanently open  
(red LED ON)  
3: door permanently closed  
(red LED OFF)  
To UNLOCK the sensor:  
Press the UNLOCK key once. Red  
LED flashes slowly. If flashing fast,  
see Note below.  
Output  
To LOCK the sensor:  
Configuration  
Press the LOCK key twice, OR  
press once then followed by a 4-  
digit lock code. If less than 4  
digits, press lock again after the  
last digit. LED goes out when  
complete.  
1 – Normally Open Relay  
2 – Normally Closed Relay  
Setup  
To INQUIRE the sensor:  
Unlock the sensor, press the  
desired function key, followed by  
the INQUIRY key – the number of  
green flashes corresponds to the  
value.  
launch a quick setup  
restore factory defaults  
Hold Tme  
Note: If sensor is locked, but code  
is unknown, power the sensor off  
and then back on. Press the  
UNLOCK key within 60 seconds.  
Re-lock with 0000. This is the  
default code. Sensor will unlock  
with one press of the unlock key,  
when set to 0000.  
launch a closed door setup  
0 (0.5s) 9 (9s)  
launch an open door setup  
See Note: Automatic Setup  
NOTE: AUTOMATIC SETUP: When performing an automatic setup (setup key pressed twice in a row), the sensor will begin to  
flash green during the door closed position, and will continue to do so until the door is activated to the open position.  
The LED will then go out and the door will close. The LED will flash green again at the closed position until a setup is  
complete. Upon the next activation, the sensor will launch another setup for the open door position, and will begin  
normal operation thereafter.  
NOTE: QUIET MODE: The QUIET mode uses a different pulsing pattern to avoid interference with other infrared systems. The  
NORMAL mode transmits more energy and detects slightly in a more crisp fashion. The NORMAL mode is  
recommended for installations with only one door.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 6 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PROGRAMMING  
GUIDE – PATTERN  
ADJUSTMENTS  
Sensitivity  
Door Open-Closed  
Automatic Learn  
Time  
0 (min) 9 (max) (default 7 for  
door open, default 6 for door  
closed)  
0: 30 seconds  
1: 1 minute  
2: 2 minutes  
3: 3 minutes  
4: 5 minutes  
Pattern Width  
Door Open or  
Closed  
5: 7 minutes  
6: 10 minutes  
7: 15 minutes  
8: 10 seconds  
9: Infinity – no learn  
1: Wide (closed door)  
2 : Middle (open door)  
3 : Asymmetric Left Narrow  
4 : Asymmetric Right Narrow  
5 : Narrow Left  
6 : Narrow Right  
Immunity  
7 : Asymmetric Left Wide  
8 : Asymmetric Right Wide  
9 : Center Narrow  
1: Normal  
2 : Rain Mode  
3 : Snow Mode  
See Note: Pattern Width or Depth  
Pattern Depth  
1: Deep – Threshold ON  
2 : Medium – Threshold ON (open)  
3 : Limited – Threshold ON  
4 : Deep – Threshold OFF  
5 : Medium – Threshold OFF (closed)  
6 : Limited – Threshold OFF  
See Note: Threshold  
See Note: Pattern Width or Depth  
NOTE: THRESHOLD: The Threshold is always OFF when the door is closed.  
NOTE: PATTERN WIDTH OR DEPTH: When pattern width or depth is changed, a setup of the new  
pattern size will automatically be triggered once a value key has been pressed.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 7 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MANUAL  
(NON-REMOTE)  
SET-UP  
Without the LCN Remote Control, the Presence Sensor may be set up using the manual push buttons (see  
diagram below) located under the right end cap. Only the sensitivity, relay mode, auto-learn time, pattern width,  
and pattern depth may be adjusted with the manual push buttons. To adjust the Presence Sensor, complete the  
following:  
PB1  
PB2  
1. To start the set-up process, press PB1 (for less than 2 seconds)  
The set-up function will be launched according to the current door position. The green LED will flash at  
2+/- Hz for 10 seconds. This LED will stop flashing once a successful set-up is achieved.  
If there is an interruption to the field of detection during this procedure, the green LED will flash at a slower  
rate. Press PB1 to re-launch the set-up.  
2. To change the detector’s parameters, press PB1 (for more than 2 seconds), then release.  
3. Press either PB1 or PB2. The LED will immediately flash red, followed by a sequence of green flashes.  
4. The red flashes indicate the parameter and the green flashes indicate the setting of the particular parameter.  
NOTE: Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of  
adjustments for that particular setting. Once you achieve the highest adjustment, the value will roll over to the  
lowest setting, upon the next press of PB2. A zero value will result in no flash of the LED.  
To exit manual set-up, simply wait 20 seconds or press PB1 for more than 2 seconds. Replace the right end cap  
back on the Presence Sensor.  
Use the chart below as a reference for the manual set-up process.  
RED LED  
STATUS  
PARAMETER  
DESCRIPTION  
GREEN LED STATUS  
1 Red Flash  
1
Sensitivity (Door open)  
0 – 9 Green Flashes (default = 7)  
2 Red Flashes  
3 Red Flashes  
2
3
Sensitivity (Door closed)  
Output Configuration  
0 – 9 Green Flashes (default = 6)  
1 – 2 Green Flashes (default = 1)  
4 Red Flashes  
4
Auto Learn Time  
0 – 9 Green Flashes (default = 0)  
5 Red Flashes  
6 Red Flashes  
7 Red Flashes  
8 Red Flashes  
5
6
7
8
Pattern Width (Door Open)  
Pattern Width (Door Closed)  
Pattern Depth (Door Open)  
Pattern Depth (Door Closed)  
0 – 9 Green Flashes (default = 2)  
0 – 9 Green Flashes (default = 1)  
1 – 6 Green Flashes (default = 1)  
1 – 6 Green Flashes (default = 1)  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 8 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRESENCE  
SENSOR WIDTH  
PATTERNS  
1st Row of Infrared  
Threshold  
1
7
2
8
3
9
4
5
6
nd Row of Infrared  
3rd Row of Infrared  
th Row of Infrared  
10  
16  
22  
11  
17  
23  
12  
18  
24  
2
13  
19  
14  
20  
15  
21  
4
(1) Wide Pattern  
(2) Middle Pattern  
(3) Asymmetric Left Narrow  
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
10 11 12  
10 11 12  
10 11 12  
13 14 15 16 17 18  
19 20 21 22 23 24  
(4) Asymmetric Right Narrow  
13 14 15 16 17 18  
19 20 21 22 23 24  
(5) Left Narrow  
13 14 15 16 17 18  
19 20 21 22 23 24  
(6) Right Narrow  
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
10 11 12  
10 11 12  
10 11 12  
13 14 15 16 17 18  
19 20 21 22 23 24  
(8) Asymmetric Right Wide  
13 14 15 16 17 18  
19 20 21 22 23 24  
(9) Center Narrow  
13 14 15 16 17 18  
19 20 21 22 23 24  
(7) Asymmetric Left Wide  
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
10 11 12  
10 11 12  
10 11 12  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
PRESENCE  
SENSOR DEPTH  
Row 1 (spots 1 through 6), remain on, even during the closed door position  
PATTERNS  
(1) Deep  
(2) Middle  
(3) Limited  
1
7
2
8
3
9
4
5
6
1
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
10 11 12  
7
10 11 12  
10 11 12  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
NOTE: When the Presence Sensor is mounted at 7’, each block on the pattern charts shown above  
equates to a size of approximately 14” x 14”. Pattern sizes shown are only as an  
approximation. Always walk-test the pattern once complete, to insure compliance with all  
applicable safety and performance standards.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 9 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRESENCE  
SENSOR DEPTH  
PATTERNS -  
Cont.  
Row 1 (spots 1 through 6), are on during open door position and off during closed door position.  
(4) Deep Without Row 1  
(5) Middle Without Row 1  
(6) Limited Without Row 1  
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
1
7
2
8
3
9
4
5
6
10 11 12  
10 11 12  
10 11 12  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
13 14 15 16 17 18  
19 20 21 22 23 24  
TROUBLE-  
SHOOTING  
PROBLEM  
PROBABLE CAUSE  
1. Improper input voltage  
2. Presence Sensor is in detection  
3. Potential interferences from high  
intensity lighting  
CORRECTIVE ACTION  
Presence Sensor will not  
set-up upon initial powering  
1. Check terminals 1 & 2 for proper voltage  
24 V AC/DC + 10%.  
2. Make certain that the field of detection is all  
clear during the set-up and that all lenses  
are installed on the Presence Sensor. If  
detection is encountered upon initial set-up,  
the Presence Sensor will continuously flash  
Green at + 2 Hz. The Presence Sensor will  
also not set-up if permanent stationary  
objects are extremely close to the sensor.  
Ensure that, not only is the detection field all  
clear, but that the sensor is mounted  
properly (using the Presence Sensor  
mounting block if necessary).  
3. Ensure that no high intensity lighting is in  
the immediate area of the sensor.  
Door will not open once set-  
up has been completed.  
1. Presence Sensor is in detection.  
2. Improper wiring  
3. Lockout safety beams are in  
detection  
1. Ensure that there is no detection occurring  
at the Presence Sensor. If the Red LED is  
on steady, there is detection. Make sure  
there have been no changes in the field of  
detection since set-up. If permanent  
changes have occurred, launch a new set-  
up and re-test door.  
4. Improper relay output configuration  
2. Remove the output wires (common,  
normally open, normally closed) from the  
Presence Sensor. CAUTION – there may  
possibly be no safety on the door when  
this test is performed. Activate the door  
control, if the door opens, the fault exists  
with Presence Sensor or related wiring. If  
door does not open, the faults may exist  
with the door control or it’s related wiring.  
3. Ensure proper relay output setting. Refer to  
page 6. Typically, relay setting should be  
“Normally Open”. This means the relay  
would close upon detection.  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 10 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLE-  
SHOOTING –  
PROBLEM  
PROBABLE CAUSE  
CORRECTIVE ACTION  
Cont.  
Presence Sensor  
repeatedly re-learns the  
environment with each  
1. Improper data from the lockout  
device  
2. Data polarity at the Presence  
Sensor is incorrect  
1. Allow the door to open in the automatic  
mode. Unlock the Presence Sensor and  
launch a setup by pressing the Setup key,  
followed by the number 2. If the sensor  
does not begin flashing green, and instead  
goes back to a red indication, improper data  
exists. Refer to respective lockout User’s  
Guide for troubleshooting.  
2. Check for proper polarity at terminal 6 and  
7. The negative wire from the lockout  
(white) should be connected to terminal 6,  
and the red/white striped wire from the  
lockout should connect at terminal 7.  
HELPFUL HINT: If faulty data is suspected,  
simply power the door to the open position  
(by activation OR with the use of a hold  
open switch). While the door is open,  
unlock the Presence Sensor, and press the  
setup key, followed by the number 2. If the  
sensor goes back to a red LED (as opposed  
to flashing the green LED to indicate a  
setup), there is a strong probability that the  
data is incorrect. Refer then to the  
respective lockout User’s Guide for  
troubleshooting help.  
Presence Sensor not  
reacting to the remote  
control  
1. Batteries in the remote control are  
dead.  
2. Distance between sensor and  
remote is too far.  
1. Replace batteries in the remote control  
2. Move in closer to the sensor when  
programming.  
3. If remote control fails, manual programming  
procedures may have to be used. See page  
8.  
HELPFUL HINT: Use LCN’s Spotfinder to  
test the output of the remote control. Simply  
point the remote at the IR Spot on the  
Spotfinder, press the Unlock key on the  
remote, and red LED should illuminate.  
ACCESSORIES  
BodyMount  
P/N 761222-79  
Presence Sensor Quick Disconnect Harness  
P/N 20.5051.00  
Lockout Safety  
Beams / SBK-30  
75.5255.02 XXXXXXXX  
7940-8770 LCN  
Page 11 of 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Insignia MP3 Docking Station NS S4000 User Manual
Jotul Indoor Fireplace Wood Insert User Manual
JVC Camcorder M4S3 User Manual
JVC CD Player KD G430 User Manual
JVC Microcassette Recorder HR J695U User Manual
Kathrein Power Supply NCF 18 User Manual
Kenmore Sewing Machine 38519365 User Manual
Kenwood Car Stereo System KDC 2021S User Manual
Keurig Coffeemaker B70 User Manual
Keys Fitness Fitness Equipment KF LATM User Manual