		 Uni- Fit R   
					Thru-the-Wall Series   
					Service and Parts   
					Manual   
					Thru-the-Wall Series   
					115 Volts US08C10 US10C10 US12C10   
					230 Volts US10C30 US12C30 US14C30   
					Unifit Cool Svc Parts 2010 (05/10)   
					Unifit. Cool (03/07)   
					
				CONTENTS   
					2.4 REFRIGERATION CYCLE.................................14   
					1. PREFACE   
					2.4.1 CONDENSER ......................................14   
					2.4.2 EVAPORATOR ....................................14   
					2.4.3 CAPILLARY TUBE...............................14   
					1.1 SAFETY PRECAUTIONS ...............................2   
					1.2 INSULATION RESISTANCE TEST.................2   
					1.3 SPECIFICATIONS ..........................................3~8   
					1.4 FEATURES.....................................................9   
					1.5 CONTROL LOCATIONS.................................9   
					3. TROUBLESHOOTING GUIDE   
					3.1 OUTSIDE DIMENSIONS...............................17   
					3.2 PIPING SYSTEM ..........................................17   
					3.3 TROUBLESHOOTING GUIDE......................18   
					2. DISASSEMBLY INSTRUCTIONS   
					2.1 MECHANICAL PARTS....................................10   
					2.1.1 FRONT GRILLE.....................................10   
					2.1.2 CABINET................................................10   
					2.1.3 CONTROL BOX.....................................10   
					2.2 AIR HANDLING PARTS..................................11   
					2.2.1 ORIFICE, HEATER ASSY AND TURBO FAN .........11   
					2.2.2 FAN........................................................11   
					2.2.3 SHROUD................................................12   
					2.3 ELECTRICAL PARTS.....................................12   
					2.3.1 MOTOR..................................................12   
					2.3.2 COMPRESSOR .....................................12   
					2.3.3 CAPACITOR ..........................................12   
					2.3.4 POWER CORD......................................13   
					2.3.5 THERMISTOR .......................................13   
					4. SCHEMATIC DIAGRAM   
					4.1 CIRCUIT DIAGRAM......................................23   
					5. EXPLODED VIEW..................................24   
					6. REPLACEMENT PARTS LIST .......25~30   
					1. PREFACE   
					This SERVICE MANUAL provides various service information, including the mechanical and electrical   
					parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.   
					The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.   
					1.1 SAFETY PRECAUTIONS   
					1. When servicing the unit, turn off the air conditioner   
					and unplug the power cord.   
					1.2 INSULATION RESISTANCE TEST   
					1. Unplug the power cord and connect a jumper   
					between 2 pins (black and white).   
					2. Observe the original lead dress.   
					2. The grounding conductor (green or green & yellow)   
					is to be open.   
					3. Measure the resistance value with an ohm meter   
					between the jumpered lead and each exposed   
					metallic part on the equipment.   
					If a short circuit is found, replace all parts which   
					have been overheated or damaged by the short   
					circuit.   
					3. After servicing the unit, make an insulation   
					resistance test to protect the customer from being   
					exposed to shock hazards.   
					4. The value should be over 1MΩ.   
					—2—   
				1.3 SPECIFICATIONS   
					MODELS   
					REMARK   
					US08C10   
					ITEMS   
					POWER SUPPLY   
					1Ø, 115V, 60Hz   
					COOLING CAPACITY (Btu/h)   
					8,000   
					INPUT   
					(W)   
					830   
					RUNNING CURRENT (A)   
					7.5   
					9.6   
					E.E.R   
					(Btu/w.h)   
					REFRIGERANT (R410A) CHARGE   
					400g(14.1OZ)   
					OPERATING   
					INDOOR (°F)   
					80(DB) 67(WB)   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					95(DB) 75(WB)   
					2 ROW 12STACKS   
					5 2ROW 18STACKS, L-BENDING TYPE   
					TURBO FAN   
					Ø 
					LOUVERED-FIN TYPE   
					PROPELLER TYPE FAN WITH SLINGER-RING   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					3/3   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—3—   
				1.3 SPECIFICATIONS   
					MODELS   
					REMARK   
					US10C10   
					ITEMS   
					POWER SUPPLY   
					1Ø, 115V, 60Hz   
					COOLING CAPACITY (Btu/h)   
					9,800   
					INPUT   
					(W)   
					1,040   
					9.6   
					RUNNING CURRENT (A)   
					E.E.R   
					(Btu/w.h)   
					9.4   
					REFRIGERANT (R-410A) CHARGE   
					445g(15.7OZ)   
					OPERATING   
					INDOOR (°F)   
					80 (DB) 67(WB)   
					95(DB) 75 (WB)   
					2 ROW 12STACKS   
					3ROW 18STACKS, L-BENDING TYPE   
					TURBO FAN   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					Ø5.0   
					LOUVERED-FIN TYPE   
					PROPELLER TYPE FAN WITH SLINGER-RING   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					3/3   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—4—   
				MODELS   
					REMARK   
					US10C30   
					ITEMS   
					1Ø, 230V/208V, 60Hz   
					POWER SUPPLY   
					10,000/9,800   
					1060/1040   
					4.7/5.2   
					COOLING CAPACITY (Btu/h)   
					INPUT (W)   
					RUNNING CURRENT (A)   
					E.E.R   
					(Btu/w.h)   
					9.4/9.4   
					REFRIGERANT (R410A) CHARGE   
					460g(16.2 OZ)   
					80(DB) 67(WB)   
					OPERATING   
					INDOOR (°F)   
					95(DB) 75(WB)   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					2 ROW 12STACKS   
					5.0 3ROW 18STACKS, L-BENDING TYPE   
					TURBO FAN   
					LOUVERED-FIN TYPE   
					Ø 
					PROPELLER TYPE FAN WITH SLINGER-RING   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					3/3   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—5—   
				MODELS   
					REMARK   
					US12C10   
					ITEMS   
					POWER SUPPLY   
					1Ø, 230V/208V, 60Hz   
					COOLING CAPACITY (Btu/h)   
					INPUT (W)   
					RUNNING CURRENT (A)   
					11500/11200   
					1220/1190   
					5.6/6.0   
					E.E.R   
					(Btu/w.h)   
					9.4/9.4   
					525g(18.0 OZ)   
					REFRIGERANT (R-410A) CHARGE   
					OPERATING   
					INDOOR (°F)   
					80(DB) 67(WB)   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					95(DB) 75(WB)   
					2 ROW 12STACKS   
					LOUVERED-FIN TYPE   
					3ROW 18STACKS, L-BENDING TYPE, 1 ROW   
					TURBO FAN   
					PROPELLER TYPE FAN WITH SLINGER-RING   
					3/3   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—6—   
				MODELS   
					REMARK   
					US12C30   
					ITEMS   
					POWER SUPPLY   
					1Ø, 230/208V, 60Hz   
					COOLING CAPACITY (Btu/h)   
					INPUT (W)   
					RUNNING CURRENT (A)   
					11,500/11,200   
					1,220/1,190   
					5.6/6.0   
					E.E.R   
					(Btu/w.h)   
					9.4/9.4   
					REFRIGERANT (R-410A) CHARGE   
					510g(18.0OZ)   
					OPERATING   
					INDOOR (°F)   
					80(DB) 67(WB)   
					95(DB) 75(WB)   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					2 ROW 12STACKS   
					3ROW 18STACKS, L-BENDING TYPE 1 ROW   
					TURBO FAN   
					LOUVERED-FIN TYPE   
					PROPELLER TYPE FAN WITH SLINGER-RING   
					3/3   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—7—   
				MODELS   
					REMARK   
					US14C30   
					ITEMS   
					POWER SUPPLY   
					1Ø, 230/208V, 60Hz   
					COOLING CAPACITY (Btu/h)   
					INPUT (W)   
					RUNNING CURRENT (A)   
					13,000/12,600   
					1,530/1,480   
					7.0/7.5   
					E.E.R   
					(Btu/w.h)   
					8.5/8.5   
					REFRIGERANT (R-410A) CHARGE   
					510g(18.0OZ)   
					OPERATING   
					INDOOR (°F)   
					80(DB) 67(WB)   
					TEMPERATURE   
					EVAPORATOR   
					CONDENSER   
					FAN, INDOOR   
					FAN, OUTDOOR   
					OUTDOOR (°F)   
					95(DB) 75(WB)   
					2 ROW 12STACKS   
					3ROW 18STACKS, L-BENDING TYPE,1ROW   
					LOUVERED-FIN TYPE   
					TURBO FAN   
					PROPELLER TYPE FAN WITH SLINGER-RING   
					FAN SPEEDS, FAN/COOLING   
					FAN MOTOR   
					3/3   
					6 POLES   
					OPERATION CONTROL   
					ROOM TEMP. CONTROL   
					AIR DIRECTION CONTROL   
					ELECTRIC   
					THERMISTOR   
					VERTICAL LOUVER(RIGHT & LEFT)   
					HORIZONTAL LOUVER(UP & DOWN)   
					TOP-DOWN   
					CONSTRUCTION   
					PROTECTOR   
					COMPRESSOR   
					FAN MOTOR   
					EXTERNAL OVERLOAD PROTECTOR   
					INTERNAL THERMAL PROTECTOR   
					3WIRES WITH GROUNDING   
					ATTACHMENT PLUG(CORD-CONNECTED TYPE, LCDI)   
					SPLASHED BY FAN SLINGER   
					73/33   
					POWER CORD   
					DRAIN SYSTEM   
					NET WEIGHT   
					(lbs/kg)   
					DIMENSION   
					(inch)   
					24 x 1413/32 x 20 3/32   
					(W x H x D)   
					(mm)   
					(inch)   
					(mm)   
					(inch)   
					(mm)   
					610 x 366 x 499   
					SLEEVE DIMESION   
					(W x H x D)   
					25 7/8 x 15 17/32 x 16 23/32   
					656 x 394 x 425   
					OPTIONAL   
					PART   
					SLEEVE DEPTH   
					WITH FRONT GRILLE   
					20 1/2   
					521   
					—8—   
				1.4 FEATURES   
					• Designed for cooling only.   
					• Built in adjustable THERMOSTAT.   
					• Washable one-touch filter.   
					• Compact size.   
					• Powerful and quiet.   
					• Slide out chassis for the simple installation and service.   
					1.5 CONTROL LOCATIONS   
					1.5.1 COOLING ONLY MODEL   
					• OPERATION   
					• VENTILATION   
					Push the lever to the "CLOSE" position to cool, heat or recirculate room air only.   
					Pull the lever to the "OPEN" position to exhaust smoke or stale air from the room.   
					This feature is best used in conjunction with the FAN ONLY position.   
					CAUTION   
					When the air conditioner has been operating in the   
					cooling and is turned off or set to the fan only position,   
					wait at least 3 minutes before resetting to the cooling   
					operation again.   
					PULL OPEN / PUSH CLOSE   
					—9—   
				2. DISASSEMBLY INSTRUCTIONS   
					— Prior to disassembling the unit, make sure that the POWER is off and the power cord is unplugged from the   
					wall receptacle.   
					2.1 MECHANICAL PARTS   
					2.1.1 FRONT GRILLE   
					1. Open the inlet grille downward.   
					2. Remove the screw which fastens the front grille.   
					3. Pull the front grille from the right side.   
					4. Remove the front grille. (See Fig. 1)   
					5. Re-install the component by referring to the   
					removal procedure.   
					Figure 1   
					2.1.2 CABINET   
					1. After disassembling the FRONT GRILLE, remove   
					the 6 screws which fasten the cabinet at the both   
					sides and the top. (See Fig. 2)   
					Keep these for later use.   
					Figure 2   
					2.1.3 CONTROL BOX   
					1. Remove the front grille. (Refer to section 2.1.1)   
					2. Remove the screw which fasten the control   
					box. (See Fig. 3)   
					3. Pull the control box from the barrier.(See Fig.3)   
					4. Discharge the capacitor by placing a 20,000 ohm   
					resistor across the capacitor terminals.   
					5. Disconnect two wire housings in the control box.   
					6. Pull the control box forward completely.   
					7. Re-install the components by referring to the   
					removal procedure. (See Fig. 3)   
					Figure 3   
					(Refer to the circuit diagram found on page 19 in   
					this manual and on the control box.)   
					—10—   
				2.2 AIR HANDLING PARTS   
					2.2.1 ORIFICE, AND TURBO FAN   
					1. Remove the front grille. (Refer to section 2.1.1)   
					2. Remove the cabinet. (Refer to section 2.1.2)   
					3. Remove the 2 screws which fasten the   
					evaporator at the left side and the right side.   
					(See Fig. 4)   
					4. Move the evaporator to the side carefully.   
					Figure 4   
					5. Remove the orifice. (See Fig. 5)   
					Figure 5   
					8. Using handheld pliers, remove the clamp which   
					secures the turbo fan. (See Fig. 6)   
					Figure 6   
					9. Remove the turbo fan with pliers or your hand,   
					without touching blades. (See Fig. 7)   
					10. Re-install the components by referring to the   
					removal procedures, above.   
					Figure 7   
					2.2.2 FAN   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. Remove the brace.   
					(Refer to section 2.2.1)   
					3. Remove the 7 screws which fasten the condenser.   
					4. Move the condenser to the side carefully.   
					5. Using handheld pliers, remove the clamp which   
					secures the fan.   
					6. Remove the fan. (See Fig. 8)   
					7. Re-install the components by referring to the   
					removal procedures, above.   
					Figure 8   
					—11—   
				2.2.3 SHROUD   
					1. Remove the fan. (Refer to section 2.2.2)   
					2. Remove the shroud. (See Fig. 9)   
					3. Re-install the components by referring to the   
					removal procedures, above.   
					2.3 ELECTRICAL PARTS   
					2.3.1 MOTOR   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. Remove the clamp cord and disconnect the wire   
					housing in control box. (Refer to section 2.1.3)   
					3. Remove the turbo fan. (Refer to section 2.2.2)   
					4. Remove the fan. (Refer to section 2.2.2)   
					5. Remove the 4 or 2 screws which fasten the motor.   
					(See Fig. 10)   
					Figure 9   
					6. Remove the motor.   
					7. Re-install the components by referring to the   
					removal procedures, above.   
					2.3.2 COMPRESSOR   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. Discharge the refrigerant system using a FreonTM   
					Recovery System.   
					Figure 10   
					Install a valve for recovery before venting the   
					Freon. Remove the valve when finished.   
					3. Disconnect the 3 leads from the compressor.   
					4. After purging the unit completely, unbraze the   
					suction and discharge tubes at the compressor   
					connections.   
					5. Remove the 3 nuts and the 3 washers which   
					fasten the compressor. (See Fig. 11)   
					6. Remove the compressor.   
					7. Re-install the components by referring to the   
					removal procedures, above.   
					2.3.3 CAPACITOR   
					1. Remove the control box. (Refer to section 2.1.3)   
					Figure 11   
					2. Remove the 1 screw   
					3. Open the control box   
					4. Disconnect all the leads on the capacitor terminals.   
					5. Re-install the components by referring to the   
					removal procedures, above.   
					Figure 12   
					—12—   
				2.3.4 POWER CORD   
					1. Remove the control box. (Refer to section 2.1.3)   
					2. Unfold the control box. (Refer to section 2.3.3)   
					3. Disconnect the grounding screw from the Base   
					pan.   
					4. Disconnect 2 receptacles.   
					5. Remove a screw which fastens the clip cord.   
					6. Pull the power cord. (See Fig. 13)   
					7. Re-install the components by referring to the   
					removal procedure, above.   
					(Use only one ground-marked hole, , for ground   
					connection.)   
					8. If the supply cord of this appliance is damaged, it   
					must be replaced with the factory-authorized and   
					specified cord.   
					Figure 13   
					2.3.5 ELECTRONIC CONTROL BOARD   
					1. Remove the control box. (Refer to section 2.1.3)   
					2. Unfold the control box. (Refer to section 2.3.3)   
					3. Disconnect all the leads of Electronic control board   
					terminals.   
					4. Remove the Electronic control board. (See Fig. 14)   
					5. Re-install the components by referring to the   
					removal procedures, above.   
					Figure 14   
					—13—   
				2.4 REFRIGERATION CYCLE   
					CAUTION   
					TM   
					Discharge the refrigerant system using a Freon   
					Recovery System.   
					Install a valve for the recovery, before venting   
					the Freon, remove the valve when finished.   
					2.4.1 CONDENSER   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. Remove the brace.   
					(Refer to section 2.2.1)   
					3. Remove the 7 screws which fasten the condenser.   
					4. After discharging the refrigerant completely into a   
					FreonTM Recovery System, unbraze the   
					interconnecting tube at the condenser   
					connections.   
					5. Remove the condenser.   
					6. Re-install the components by referring to the notes   
					– on pages 11-13. (See Fig. 15)   
					Figure 15   
					2.4.2 EVAPORATOR   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. Discharge the refrigerant completely – into a   
					FreonTM Recovery System.   
					3. Remove the 2 screws which fasten the evaporator   
					at the left side and the right side.   
					4. Move the evaporator to the side carefully and then   
					unbraze the interconnecting tube at the evaporator   
					connectors.   
					5. Remove the evaporator.   
					6. Re-install the components by referring to the notes   
					– on pages 11-13. (See Fig. 16)   
					Figure 16   
					2.4.3 CAPILLARY TUBE   
					1. Remove the cabinet. (Refer to section 2.1.2)   
					2. After discharging the refrigerant completely – into   
					a FreonTM Recovery System, unbraze the   
					interconnecting tube at the capillary tube.   
					3. Remove the capillary tube.   
					4. Re-install the components by referring to the notes   
					– on page 11-13.   
					—14—   
				NOTES   
					— Replacement of the refrigeration cycle.   
					1. When replacing refrigeration components, be sure   
					to discharge the refrigerant system using a FreonTM   
					recovery System.   
					Install a valve for the recovery, before venting the   
					Freon, remove the valve when finished.   
					2. After discharging the unit completely, remove the   
					desired component, and unbraze the pinch-off   
					tubes.   
					3. Solder service valves into the pinch-off tube ports,   
					leaving the valves open.   
					4. Solder the pinch-off tubes with Service valves.   
					5. Evacuate as follows.   
					6. Recharge as follows :   
					1) Refrigeration cycle systems are charged from the   
					High-side. If the total charge cannot be put   
					in the High-side, the balance will be put in the   
					suction line through the access valve which you   
					installed as the system was opened.   
					2) Connect the charging cylinder as shown in Fig. 17B.   
					With valve C open, discharge the hose at the   
					manifold connection.   
					3) Open valve A and allow the proper charge to   
					enter the system. Valve B is still closed.   
					4) If more charge is required, and the high-side will   
					not   
					1) Connect the vacuum pump, as illustrated Fig.   
					17A.   
					take it. Close valve A.   
					2) Start the vacuum pump, slowly open manifold   
					valves A and B with two full turns   
					5) With the unit running, open valve B and add the   
					balance of the charge.   
					counterclockwise and leave the valves closed.   
					The vacuum pump is now pulling through valves   
					A and B up to valve C by means of the manifold   
					and entire system.   
					a. Do not add the liquid refrigerant to the Low-   
					side.   
					b. Watch the Low-side gauge; allow pressure to   
					rise to 39 lbs.   
					c. Turn off valve B and allow pressure to drop.   
					d. Repeat steps B and C until the balance of the   
					charge is in the system.   
					CAUTION   
					If high vacuum equipment is used, just crack   
					valves A and B for a few minutes, then open   
					slowly with the two full turns counterclockwise.   
					This will keep oil from foaming and being   
					drawn into the vacuum pump.   
					6) When satisfied the unit is operating correctly,   
					use the pinch-off tool with the unit still running   
					and clamp on to the pinch-off tube. Using a tube   
					cutter, cut the pinch-off tube about 2 inches from   
					the pinch-off tool. Use sil-fos solder and solder   
					pinch-off tube closed. Turn off the unit, allow it to   
					set for a while, and then test for leakage add the   
					pinch-off connection.   
					3) Operate the vacuum pump for 20 to 30 minutes,   
					until 600 microns of vacuum is obtained. Close   
					valves A and B, and observe vacuum gauge for   
					a few minutes. A rise in pressure would   
					indicate a possible leak or moisture remaining in   
					the system. With valves A and B closed, stop   
					the vacuum pump.   
					4) Remove the hose from the vacuum pump and   
					place it on the charging cylinder. See Fig. 17B.   
					Open valve C.   
					Discharge the line at the manifold connection.   
					5) The system is now ready for final charging.   
					—15—   
				Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool   
					capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service   
					valve.   
					COMPOUND GAUGE   
					CONDENSER   
					(HIGH PRESSURE SIDE)   
					MANIFOLD   
					GAUGE   
					A 
					B 
					CAPILLARY TUBE   
					SEE INSETS   
					BELOW   
					EVAPORATOR   
					(LOW PRESSURE SIDE)   
					COMPRESSOR   
					HI   
					LOW   
					A 
					B 
					A 
					B 
					EXTERNAL   
					VACUUM PUMP   
					CHARGING   
					CYLINDER   
					C 
					Figure 17A-Pulling Vacuum   
					Figure 17B-Charging   
					—16—   
				3. TROUBLESHOOTING GUIDE   
					3.1 OUTSIDE DIMENSIONS   
					20-3/32"   
					24"   
					(610mm)   
					(499mm)   
					3.2 PIPING SYSTEM   
					CONDENSER COILS   
					FAN   
					CAPILLARY TUBE   
					COMPRESSOR   
					MOTOR   
					TURBO FAN   
					EVAPORATOR COILS   
					: REFRIGERANT FLOW   
					Following is a brief description of the important components and their functions in the refrigeration system.   
					Refer to Fig. 18 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.   
					ROOM AIR CONDITIONER   
					CYCLE OF REFRIGERATION   
					EVAPORATOR COILS   
					CONDENSER COILS   
					VAPOR INLET   
					SUCTION LINE   
					COOL LOW PRESSURE VAPOR   
					HOT   
					DISCHARGED   
					AIR   
					COMPLETE LIQUID   
					BOIL OFF POINT   
					COOLED   
					AIR   
					ROOM AIR HEAT LOAD   
					OUTSIDE COOLING   
					AIR FOR REFRIGERANT   
					PASS THROUGH   
					MOTOR   
					COMPRESSOR   
					OIL   
					LIQUID   
					PRESSURE   
					DROP   
					LIQUID OUTLET   
					HIGH PRESSURE VAPOR   
					(LIQUID REFRIGERANT)   
					LIQUID REFRIGERANT   
					LOW PRESSURE VAPOR   
					CAPILLARY TUBE   
					Figure 18   
					—17—   
				3.3 TROUBLESHOOTING GUIDE   
					In general, possible trouble is classified in two causes.   
					One is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning   
					caused by a defect in the refrigeration circuit and/or improper application.   
					Unit is running but cooling is ineffective   
					Ineffective Cooling   
					Check cold air circulation   
					for smooth flow.   
					Check outdoor coil   
					(heat exchanger) & the fan   
					operation.   
					Check heat load increase.   
					Unexpected residue   
					Overloaded Circuit   
					Dirty indoor coil   
					(Heat exchanger)   
					Check gas leakage.   
					Repair gas leak.   
					Malfunction of fan   
					Clogged air filter   
					Check inside gas pressure.   
					Replacement of unit if the   
					unit is beyond repair.   
					Obstruction at air outlet   
					Adjusting of refrigerant   
					charge   
					Correct above troubles   
					Malfunction of compressor   
					Check for a clog in   
					refrigeration circuit.   
					Replacement of   
					compressor   
					Satisfactory operation with   
					temperature difference of   
					inlet & outlet air ; 18-26°F   
					Repair for a clog in   
					refrigeration circuit.   
					—18—   
				Fails to Start   
					Check power source.   
					Check circuit breaker   
					and fuse.   
					Check control switch   
					setting.   
					Check control board   
					Only compressor fails to   
					start.   
					Only fan fails to start.   
					Improper wiring.   
					Drop in power voltage.   
					Improper thermostat setting   
					Defect of fan motor   
					capacitor.   
					Defective compressor   
					capacitor.   
					Loose terminal connection.   
					Improper wiring   
					Irregular motor resistance   
					( 
					).   
					Irregular motor insulation   
					).   
					Check capacitor.   
					Replacement.   
					( 
					Replacement of fan motor   
					Regular but fails to start   
					Irregular motor resistance ( )   
					Irregular motor insulation ( )   
					Replacement of compressor   
					(locking of rotor, metal)   
					Replacement of compressor   
					(Motor damaged)   
					—19—   
				COMPLAINT   
					CAUSE   
					REMEDY   
					Fan motor will not run.   
					No power   
					Check voltage at outlet. Correct if none.   
					Wire disconnected or   
					connection loose   
					Connect wire. Refer to wiring diagram for terminal   
					identification. Repair or replace loose terminal.   
					Capacitor (Discharge   
					Test capacitor.   
					capacitor before testing.)   
					Replace if not within ±10% of manufacturer's   
					rating. Replace if shorted, open, or damaged.   
					Will not rotate   
					Fan blade hitting shroud or blower wheel hitting   
					scroll. Realign assembly.   
					Units using slinger ring condenser fans must   
					have 1/4 to 5/16 inch clearance to the base. If it is   
					hitting the base, shim up the bottom of the fan   
					motor with mounting screw(s).   
					Check fan motor bearings; if motor shaft will not   
					rotate, replace the motor.   
					Fan motor runs   
					intermittently   
					Cycles on overload.   
					Check voltage. See limits on page 17. If not within   
					limits, call an electrician.   
					Test capacitor.   
					Check bearings. Does the fan blade rotate freely?   
					If not, replace fan motor.   
					Pay attention to any change from high speed to   
					low speed. If the speed does not change, replace   
					the motor.   
					Fan motor noise.   
					Grommets   
					Fan   
					Check grommets; if worn or missing, replace them.   
					If cracked, out of balance, or partially missing,   
					replace it.   
					Turbo fan   
					If cracked, out of balance, or partially missing,   
					replace it.   
					Loose set screw   
					Worn bearings   
					Tighten it.   
					If knocking sounds continue when running or   
					loose, replace the motor. If the motor hums or   
					noise appears to be internal while running,   
					replace motor.   
					—20—   
				COMPLAINT   
					CAUSE   
					REMEDY   
					Compressor will not run,   
					but fan motor runs.   
					Voltage   
					Wiring   
					Check voltage. See the limits on the preceding.   
					page. If not within limits, call an electrician.   
					Check the wire connections, if loose, repair or   
					replace the terminal. If wires are off, refer to wiring   
					diagram for identification, and replace. Check wire   
					locations. If not per wiring diagram, correct.   
					Capacitor (Discharge   
					capacitor before   
					servicing.)   
					Check the capacitor.   
					Replace if not within ±10% of manufacturers   
					rating. Replace if shorted, open, or damaged.   
					Check the compressor for open circuit or   
					ground. If open or grounded, replace the   
					compressor.   
					Compressor   
					Overload   
					Check the compressor overload, if externally   
					mounted. Replace if open. (If the compressor   
					temperature is high, remove the overload, cool it,   
					and retest.)   
					ROOM AIR CONDITIONER VOLTAGE LIMITS   
					NAME PLATE RATING   
					MINIMUM   
					MAXIMUM   
					126.5V   
					253V   
					115V   
					103.5V   
					187V   
					208/230V   
					—21—   
				REMEDY   
					COMPLAINT   
					CAUSE   
					Compressor cycles   
					on overload.   
					Voltage   
					Check the voltage. See the limits on the preced-   
					ing page. If not within limits, call an electrician.   
					Overload   
					Check overload, if externally mounted.   
					Replace if open. (If the compressor temperature   
					is high, remove the overload, cool, and retest.)   
					Fan motor   
					If not running, determine the cause. Replace if   
					required.   
					Condenser air flow   
					restriction   
					Remove the cabinet. Inspect the interior surface   
					of the condenser; if restricted, clean carefully   
					(do not damage fins). Clean the interior base before   
					reassembling.   
					Condenser fins   
					(damaged)   
					If condenser fins are closed over a large area   
					on the coil surface, head pressures will increase,   
					causing the compressor to cycle. Straighten the   
					fins or replace the coil.   
					Capacitor   
					Test capacitor.   
					Wiring   
					Refrigerating system   
					Air filter   
					Check the terminals. If loose, repair or replace.   
					Check the system for a restriction.   
					If restricted, clean or replace.   
					Insufficient cooling or   
					heating   
					Exhaust damper door   
					Unit undersized   
					Close if open.   
					Determine if the unit is properly sized for the area to   
					be cooled.   
					Excessive noise.   
					Blower or fan   
					Copper tubing   
					Check the set screw or clamp. If loose or missing,   
					correct. If the blower or fan is hitting air guide,   
					rearrange the air handling parts.   
					Remove the cabinet and carefully rearrange tubing   
					not to contact cabinet, compressor, shroud, and   
					barrier.   
					—22—   
				4. SCHEMATIC DIAGRAM   
					4.1 CIRCUIT DIAGRAM   
					WIRING DIAGRAM   
					(SMPS)   
					250V/T2A   
					(250V/T3.15A)   
					MEZ62420710   
					—23—   
				Exploded View   
					Exploded View   
					132100   
					C 
					152302   
					147581   
					147582-1   
					135303   
					147582-2   
					131400   
					149980   
					135312   
					346811   
					359012   
					W48602   
					559011   
					349480   
					435301   
					435300   
					352380   
					731273   
					130410   
					267110   
					A 
					264110   
					268711-2   
					567480   
					249950   
					B 
					567502   
					268711-1   
					C 
					o 
					o 
					l 
					E 
					S 
					n 
					a 
					e 
					r 
					e 
					g 
					r 
					y 
					v 
					F 
					a 
					n 
					F 
					2 
					1 
					L 
					F 
					O 
					W 
					D 
					H 
					M 
					F 
					E 
					IG   
					3 
					H 
					T 
					i 
					m 
					e 
					' 
					r 
					F 
					MO   
					D 
					E 
					T 
					E 
					M 
					P 
					W0CZZ   
					T 
					I 
					M 
					E 
					R 
					F 
					E 
					A 
					E 
					S 
					N 
					D 
					P 
					P 
					O 
					W 
					E 
					R 
					550140   
					238310 237200   
					—24—   
				LocNo   
					Description   
					US08C10   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300709   
					67302925   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303021   
					67306205   
					67306256   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					147582-2   
					149980   
					LOUVER,VERTICAL   
					SHROUD   
					67306257   
					67500112   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					567502   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					67305000   
					67500113   
					67302739   
					67302607   
					67303202   
					67307804   
					67300027   
					67302239   
					67301907   
					67307620   
					67307619   
					67304801   
					67305510   
					67306311   
					67305521   
					67304801   
					67303409   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					OverloadProtect   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—25—   
				LocNo   
					Description   
					US10C10   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					147582-2   
					349600   
					149980   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					567502   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300724   
					67305520   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303023   
					67306205   
					67306256   
					67306257   
					67303606   
					67500112   
					67305000   
					67500113   
					67302741   
					67302607   
					67303202   
					67307804   
					67300027   
					67302239   
					67301905   
					67307620   
					67307619   
					67304801   
					67305510   
					67306311   
					67305522   
					67304801   
					67303409   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					LOUVER,VERTICAL   
					BRACKET,MOTOR   
					SHROUD   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					OverloadProtect   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—26—   
				LocNo   
					Description   
					US10C30   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					147582-2   
					149980   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300709   
					67302925   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303024   
					67306205   
					67306256   
					67306257   
					67500112   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					LOUVER,VERTICAL   
					SHROUD   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					567502   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					67305000   
					67500113   
					67302740   
					67302607   
					67303202   
					67307804   
					67300026   
					67302239   
					67301908   
					67307618   
					67307619   
					67304801   
					67305510   
					67306311   
					67305523   
					67304801   
					67303409   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					OverloadProtect   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—27—   
				LocNo   
					Description   
					US12C10   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					147582-2   
					349600   
					149980   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					567502   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300729   
					67305520   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303023   
					67306205   
					67306256   
					67306257   
					67303606   
					67500112   
					67305000   
					67500113   
					67302741   
					67302607   
					67303202   
					67307804   
					67300025   
					67302239   
					67301905   
					67307620   
					67307619   
					67304801   
					67305510   
					67306311   
					67305524   
					67304801   
					67303409   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					LOUVER,VERTICAL   
					BRACKET,MOTOR   
					SHROUD   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					OverloadProtect   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—28—   
				LocNo·   
					Description   
					US12C30   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					147582-2   
					349600   
					149980   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					567502   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300726   
					67305520   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303037   
					67306205   
					67306256   
					67306257   
					67303606   
					67500112   
					67305000   
					67500113   
					67302741   
					67302607   
					67303202   
					67307804   
					67300026   
					67302239   
					67301906   
					67307618   
					67307619   
					67304801   
					67305510   
					67306311   
					67305525   
					67304801   
					67303409   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					LOUVER,VERTICAL   
					BRACKET,MOTOR   
					SHROUD   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					OverloadProtect   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—29—   
				LocNo·   
					Description   
					US14C30   
					W0CZZ   
					130410   
					130900   
					132100   
					135303   
					135312   
					238310   
					W48602   
					346811   
					147581   
					147582-1   
					147582-2   
					349600   
					149980   
					550140   
					152302   
					352380   
					359012   
					559011   
					567480   
					264110   
					267110   
					268711-2   
					268711-1   
					435300   
					237200   
					731273   
					249950   
					435301   
					349480   
					CAPACITOR,FILM,BOX   
					BASE ASSEMBLY,SINGLE   
					CABINET   
					67300709   
					67302926   
					67303717   
					67308102   
					67306106   
					67306012   
					67500114   
					67302500   
					67303037   
					67306205   
					67306256   
					67306257   
					67303606   
					67500112   
					67305000   
					67500113   
					67302741   
					67302607   
					67303202   
					67307804   
					67300026   
					67302239   
					67307618   
					67307619   
					67304801   
					67305510   
					67306311   
					67305526   
					67304801   
					67303409   
					FRAME   
					GRILLE,INLET   
					GRILLE ASSEMBLY,FRONT(SINGLE)   
					ESCUTCHEON   
					CLAMP,SPRING   
					MOTOR ASSEMBLY,SINGLE   
					LOUVER,HORIZONTAL   
					LOUVER,VERTICAL   
					LOUVER,VERTICAL   
					BRACKET,MOTOR   
					SHROUD   
					DAMPER,COMPRESSOR   
					FILTER,AIR   
					AIR GUIDE   
					FAN,TURBO   
					FAN ASSEMBLY,AXIAL   
					THERMISTOR ASSEMBLY   
					POWER CORD ASSEMBLY   
					REMOTE CONTROLLER ASSEMBLY   
					PWB(PCB) ASSEMBLY,MAIN   
					PWB(PCB) ASSEMBLY,DISPLAY   
					GRILLE,REAR   
					PANEL,CONTROL   
					INSTALL PART ASSEMBLY,SINGLE   
					CASE ASSEMBLY,CONTROL   
					GRILLE,REAR   
					ORIFICE   
					—30—   
				FRIEDRICH AIR CONDITIONING CO.   
					
					Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540   
					• (210) 357-4400 • FAX (210) 357-4480   
					P/NO.:3828A20294U   
					Printed in the U.S.A   
					Unifit Cool Svc Parts 2010 (05/10)   
				 |